Introduction.................................................................................................................................................... 2
Transmissions ......................................................................................................................................... 18
References .................................................................................................................................................... 22
Evaporative cooling systems are the most popular type found in industry. This Application Note explains how
they work and the energy and water saving opportunities that they may present. For both evaporative and dry
air cooling systems, variations in ambient air conditions and process loads, means that they will spend much of
their time working at part load operation. On/off and variable speed control of the system fans and pumps can
give large energy savings, but the selection of methods depends on the detailed design of the cooling plant.
Care also must be taken to also ensure that the system will work satisfactorily at partial load.
Water treatment and selection, and maintenance of cooling tower fill are important for effective and reliable
operation, and have direct impact on energy use. Regular monitoring of the system will ensure that any
changes in performance can be identified and remedial measures taken.
This Application Note makes suggestions of well proven techniques to save energy, that vary from simple
maintenance tasks to operational and equipment changes that will require the input of a specialist.
This Application Note gives an overview of the design and operation of common types of industrial cooling
systems, showing how energy savings in excess of 10% can frequently be found without significant investment.
Improved operation and maintenance can also improve cooling plant performance and reliability, and lead to
1
reduced water consumption .
The cooling systems described in this Application Note are found in many high heat producing applications,
most commonly:
In addition, many of the considerations for the optimization of cooling towers used in industry are also very
relevant to the condenser cooling found on larger chiller systems, such as those of building air-conditioning
systems.
1
ISO16345:2014 “Water-cooling towers -- Testing and rating of thermal performance” gives in depth
information on how the performance of cooling towers can be assessed, and gives useful insights on the
factors that impact performance.
For the range of industrial processes considered in this Application Note, the choice is between different types
of evaporative or dry air water recirculation cooling systems. For very large plant, such as power generation
stations, a single pass system with discharge of warmed water back to source is common.
PSYCHROMETRY OF AIR
For dry air and evaporative cooling systems, the properties of the ambient air are critical for determining the
cooling ability of the system [1]. Three temperatures are of interest when considering cooling tower operation:
The temperature drop between the warm water entering the tower and the cold water exiting is known as the
temperature range. This is typically in the range 6 – 10°C. The difference between the cold water return
temperature and the temperature of the air is known as the approach temperature. This should ideally be as
small as possible.
The dry bulb temperature is the temperature of dry air, and is relevant where sensible heat transfer is the
underlying mechanism, such as for dry air coolers. An approach temperature of around 12°C is typically
achievable for these systems.
For evaporative cooling systems, the capacity of the air to hold additional evaporated water is an important
factor. The wet bulb temperature is a measure of the degree of saturation of the air, which takes into account
dry bulb temperature, relative humidity and air pressure. It is the lowest temperature to which water can
theoretically be cooled, taking into account the additional cooling from the latent heat used in the transition of
water from liquid to gas when it is evaporated. The lower the degree of saturation, the more moisture it is
capable of holding, and so the greater the cooling potential. An approach temperature of around 4°C is
achievable for these systems.
Table 1 shows the end (exit) temperatures achievable by dry and wet systems in a variety of temperature
conditions, showing clearly the lower temperatures achievable by evaporative systems.
Country, city Temperature (°C)* Temperature End temperature (°C) T (Wet – Dry)
Dry bulb Wet bulb difference Dry Wet systems (K)
(°C) system system
Greece, Athens 36 22 14 48 26 22
France, Paris 32 21 11 44 25 19
Portugal, Lisbon 32 27 5 44 31 13
Ireland, Dublin 23 18 5 35 22 13
Belgium, Brussels 28 21 7 40 25 15
Germany, Hamburg 27 20 7 39 24 15
* Statistically only 1% of the maximum temperatures are above this data.
Table 1 – Achievable cooling of dry air and evaporative cooling systems in different locations. Adapted from
IPPC BREF (Table 1) [2] .Illustrative only, based on a 4K (dry air) and 12K (evaporative) temperature approach.
Organic Rankine Cycle based power generation [3] could be considered, but the economics will be limited by
the temperature of the waste heat, and the variation in quantity of heat produced over the year. For more
information ORC, see the LE Application Note “Sustainable Heating and Cooling”.
On more complex energy intensive sites that have several different processes, a PINCH [4] approach can be
used to move waste heat energy between processes with different thermal heating/cooling requirements. For
example, a finished chemical product might require cooling from 120°C to 40°C, where some of this
temperature drop can be achieved by using heat exchangers to pre-heat an earlier stage of the process. This
use of waste energy will reduce the net cooling demand on the cooling towers.
Time-switches.
Load sensors.
Thermostats.
The use of a Variable Speed Drive to vary the pump speed will save energy by reducing flow as the total
demand varies.
To avoid subsequent damage to the pumps and other components, the spent water is captured in scale pits,
from where it is pumped by the scale pit pumps to a clarifier tank for further cleaning. It is then pumped
through a filter by the clarifier pumps, and then through the cooling tower. The mill supply pumps finally
supply the cooled water back to the mill processes.
Figure 2 – Simplified schematic of the water supply in a steel rolling mill, showing multiple pump stages used in
circulating the water around the supply and cooling loop [5].
There are two principal types of evaporative cooling towers; counterflow and crossflow. Both work on the
same thermodynamic principle. Towers are commonly made from galvanized steel and/or fibre re-inforced
plastic, with some older tower designs still using wooden walls. Large cooling towers may be constructed on
site out of concrete.
It is common to find several cooling towers installed in parallel to make up the required capacity. This gives
many options for part load control, and makes maintenance easier to schedule. The differing pressure:flow
characteristics of the crossflow and counterflow systems mean that in multiple tower systems, the two types
should not be mixed.
Cooling tower fill is essential for operation (figure 3), as it maximizes the air:water interface and transit time,
hence maximizing the amount of evaporation that can take place as the water falls through tower. Modern fill
usually consists of hexagonal tubes created from multiple pre-formed PVC sheets, with fine ridges (flutes) built
into the walls to direct the water on circuitous routes to the bottom. The fill will have an optimum air:water
flow ratio of around 3:1.
For dirtier water, coarser flutes are used, but at the expense of heat transfer capability. Where entrained dirt is
a big issue, some counterflow systems just use a direct spray of water into the cooling tower with no fill.
For extremely dirty water, descending fill bars are used, where the water falls and splashes from one bar to the
next. The reduced surface area of these droplets compared with film flow means that performance is not as
good.
2
Figure 3 – Cross section through PVC film fill for counterflow cooling towers .
2
Diagram taken from http://www.towercomponentsinc.com/operation-film-fill.php
As the water moves through the fill under gravity, a small proportion of the water is evaporated. The
remaining cooled water then falls into the cold water sump, from where it is then returned to the cooling loop.
For best operation, each flute should have equal air:water flows. However, the circular pattern of standard
nozzles means that this is difficult to achieve. This means that some flutes will have a poor air:water ratio, and
so will not work at their optimum. Bounceback of spray hitting the cooling tower walls can also cause a more
localized air:water imbalance around the cooling tower edge.
Figure 5 – Spray pattern of standard nozzles in a counterflow evaporative cooling tower, showing an uneven
water flow distribution.
Nozzles that produce a pattern that is closer to a square are also available, and should be considered for new
or retrofit installation.
Low water pressure operation could reduce the spray pattern diameter. This leads to wide water:air ratio
variations across the fill, limiting the pressure range over which the tower can work effectively. Some nozzles
have integral valves that close the nozzle if the supply pressure is too low (figures 6 and 7).
Figure 6 – Impact on the spray pattern of a counterflow evaporative cooling tower with insufficient pressure.
[6]
High pressure nozzles that have a wider spray pattern mean that the separation between nozzles and the top
of the fill can be minimized. If specified at design, this can decrease pumping energy and tower capital costs. If
retrofitted, the additional fill increases the effectiveness of heat transfer, since heat transfer within the flutes
is around ten times more effective than that in the freefall zone above.
An advantage of this system is that the nozzle head is fixed by the depth of water in the distribution pan, and
so a greater turndown flow ratio is possible than on counterflow systems with varying nozzle water pressure
On crossflow systems, the depth of water in the redistribution deck varies with the flow. The depth of water in
the distribution deck is typically 6” at rated flow. Very low water flows should be avoided, as it can lead to icing
Figure 9 – Use of nozzle cups and a dam to vary active zones with water flow on a crossflow redistribution deck.
Because there is no water loss, the operational water make-up and chemical dosing costs are negligible. This is
a major operational advantage over evaporative cooling towers. As water is only required to fill the system
once, they are ideal for sites where water is not always available. Because the water is not in contact with the
air, the risk of legionella bacteria is low, making these systems popular where people are at risk of inhaling
airborne water droplets.
A wider range of mediums can be used as a cooling fluid because the system is closed. There will also not be
the visible plume sometimes seen coming from evaporative cooling towers, which is a benefit in locations
where fog development is a risk.
However, because these systems rely on convection cooling only, they do not benefit from the latent heat
cooling of evaporation. As a result, they require more surface area. They are generally more expensive than
evaporative cooling systems.
The cooling matrix is built of an assembly of copper pipes inserted through aluminium fins to help heat
dissipation (figure 11). Air is then sucked through the fins to enhance heat transfer. It is usual for large arrays
to be built from multiple small fans. The fan power required is higher than for a comparable evaporative
system, and so this type of plant may also be noisier.
Dry air coolers are often sold as packaged units with multiple fans (figure 12). These can be controlled
sequentially or by speed reduction, with substantial energy savings possible through speed reduction at times
of low cooling duty. Brushless DC motors are popular, resulting in a high-energy efficiency both at full and at
reduced flow.
Figure 11 – A heat exchanger detail showing copper pipes with aluminium fins.
Periodic cleaning is required to ensure that the cooling fins do not get blocked, which is a particular risk in
dusty industrial environments.
Some dry air coolers include a water spray onto the fins for adiabatic cooling. In this way, almost free
additional cooling within 6°C of the wet bulb temperature can be gained when ambient conditions are
favourable.
Only a small amount of water will be used, but is designed to be completely evaporated. These systems are
therefore only applicable where there is water available. A drain point is required to drain of water in the
distribution pipes at the end of operation.
De-scaling of water might be required depending on water properties, and incoming water can be disinfected
using UV sterilization units.
At these lower duties, sufficient cooling can still be achieved with reduced airflow. This can be done by
installing a Variable Speed Drive (VSD) using temperature feedback to vary the speed of the fan. In this way,
the required set-point return water temperature can be maintained (figure 13).
Since the power consumption of a fan varies with the cube of the speed, even just a 20% reduction in fan
speed will theoretically almost halve the power consumed.[7].
3
Pnew = 0.8 x Poriginal => Pnew = 0.51 x Poriginal.
Where Poriginal is the original power consumption when it was running at full speed, and P new is the reduced
power consumption.
Figure 13 – Installation of a VSD to regulate the fan speed, using a temperature sensor to maintain return
water temperature. [8]
The VSD also gives a controlled increase of speed during start up, which reduces the mechanical stress, as well
as the peak currents when starting high inertia axial fans. The VSD will have internal losses, and will slightly
increase the losses in the motor, but these losses are small in comparison to the potential energy savings. The
typical increase in motor losses when driven by a VSD is approximately equivalent to the loss reduction
achieved through a downgrade of half of an IE motor efficiency class [9].
The airflow produced by the fan is proportional to the fan speed, with cooling capacity falling as the speed
falls. But because the fan power is proportional to the speed cubed, the specific fan power (kW/l/s) required
for the same total flow is now much less.
Figure 14 – Running three cooling tower fans at 2/3rds speed theoretically uses less than half the energy of two
fans running at full speed.
In the example shown in figure 14, 3 towers at 2/3 flow will give the same airflow as 2 towers at full flow,
(table 4). But the theoretical total energy consumption will now be just 45% (=100 x 89/200).
Fan Operation Flow (% of single fan rated Power (% of single fan rated
power) power)
2 Fans at full speed 200% 2 x 100% = 200%
3 Fans at 2/3rds speed 200% 3 x (2/3)3 x 100% = 89%
Table 4 – Energy savings from running multiple fans at reduced speed.
This is a very effective way to save energy, providing that the cooling tower can work satisfactorily at this
reduced airflow. Historically, variable pitch blades or two speed motors have been used to adjust the fan duty,
but their lower cost and other advantages have made VSDs popular in this application.
Instead, flow can be varied by switching on and off individual pumps in multiple pump systems. A common
energy saving opportunity is to review the control strategy of such pump banks in order to minimize the
number of pumps operating.
The system operating point with 1 and 2 pumps in use is shown in figure 15. When the second pump is
switched on, the total flow will increase by an amount that depends on the shape of the system curve. For a
system that has static head only and no friction, the flow would double. But for a real life system which does
have friction, the increased flow will give rise to an increase in friction head. This means that 1) despite having
two pumps, the flow has not doubled, 2) the pressure is higher than was originally needed, which represents
wasted energy, and 3) the pumps will be working at new operating points with different efficiencies (figure
16).
In this example, the pumps are selected for best performance when two are running. But it is also possible to
specify pumps that have optimum efficiency when just one pump is running. This enables the system to be
designed to have the lowest specific energy consumption when supplying the most common flow demand.
It is not unusual to find excess pumps running after they were used to overcome a short term peak in demand,
and were not switched off again afterwards. A PLC can be used for automatic sequencing of the pumps in
response to varying demand.
PUMP SELECTION
The circulation pumps should be chosen to be high efficiency designs, with a working range close to their Best
Efficiency Point (BEP). For larger pumps, it can be worth periodically checking their efficiency using an in situ
pump efficiency test method. The gradual decrease in efficiency can then be monitored and the pump
refurbished or replaced as necessary.
Figure 17 – Arrangement of multiple pumps and non-return valves on large cooling system [8].
It is usual, but not essential, for all the pumps in parallel systems to have identical characteristics.
High efficiency motors should be specified as standard. In many countries, motors of the high performance IE3
efficiency class are now the only ones available. Retrofit of working motors with new high efficiency motors is
unlikely to be economic, but when an older motor needs replacing anyway, the economics of upgrading to a
higher efficiency motor are usually attractive [10]
TRANSMISSIONS
The rotational speeds of standard induction motors are too high for cooling tower fans, and so a belt drive or
gearbox transmission are needed for the fan to operate correctly.
Wedged Drive belts are commonly used where the fan shaft and motor shaft are in the same orientation. As
they become slacker with use, internal energy losses will increase, and so they should be periodically re-
tensioned. As the belts wear, the sheaves (pulleys) will also wear and will require replacement. On drives
where there are several drive belts in parallel, it is important that they are equally tensioned. Where it is
practical, toothed belts are a good alternative that have much lower internal losses.
Gearboxes are used where the fan shaft is at 90° to the motor shaft. These have internal losses that vary by
type and also with the load. They also require periodic lubrication.
New direct drive motors are now available that are designed specifically for evaporative cooling tower fans,
which avoid the need for a separate transmission [11]. These give much higher efficiencies and will also
produce less noise. The maintenance requirement is less, and alignment is also simpler. However, care should
be taken that the fan supports can withstand the total weight of the motor in the centre of the tower.
Drift is spray or mist that is blown out of the cooling tower. Drift eliminators are boards that are
positioned to reduce airborne drift, but should be checked to ensure that they are functioning well. On
the best installations drift eliminators will keep drift to 0.001 – 0.005%. This airborne drift is distinct from
the plume of pure steam that is sometimes seen over cooling towers. Careful selection and maintenance
of drift eliminators is important to minimize the pressure drop, and the corresponding additional fan
energy required to overcome this.
Blowdown is necessary to maintain the right chemical balance of the water. Minimising the amount of
water lost through blowdown is described in the next section.
Leakage can occur anywhere in the system.
Any water that does not return to drain should not be included in the sewage charge. Fitting an approved
meter to the make-up water supply can be used to support a reduced waste water bill.
WATER TREATMENT
For evaporative systems that require ongoing filling with make-up water, regular dosing will be needed to
maintain effective and safe operation:
In addition, dirt, leaves, paper and other organic waste can be blown into evaporative systems. These larger
suspended solids can be removed by filtering.
Legionnella Pneumophilla bacteria is found in many systems and must be controlled in line with local legal
3
requirements and guidelines . It can become a hazard where the water temperature in all or some part of the
system may be between 20–50 °C; there are deposits that can support bacterial growth, such as rust, sludge,
scale and organic matter; and where it is possible for water droplets to be produced and dispersed.
Closed systems also require treatment, but because a regular input of fresh make-up water isn’t required, the
costs will be much lower.
3
The regulations published by the United Kingdom Health and Safety Executive give a good overview of the
approach that should be taken to managing legionella bacteria. [12]
On-line TDS monitoring reduces water use by only initiating blowdown when a defined TDS level has been
reached, greatly reducing the cost of replacing water and chemicals unnecessarily sent to drain. Systems that
can work satisfactorily with a higher TDS peak concentration will require less blowdown. Specialist advice and
training is recommended to specify and maintain a chemical dosing and blowdown regime appropriate to the
system. The equipment and processes are very similar to those used for blowdown of boiler water.
The heater controls should be checked to ensure that it switches the heater on and off at the required
temperatures. If the switch off temperature is too high, then excess energy will be used in heating the water to
this temperature.
OPERATOR TRAINING
It is important that the staff operating the cooling system are aware of the high electrical, water and chemical
costs of the plant that they control. Very often they have little idea of the costs of the regular decisions that
they make, and have not been given the knowledge to understand how they can make changes to operating
procedures in order to make useful energy savings. It is vital to involve the Production Department (and any
other customers of the cooling system) in any changes in operating procedures.
COOLING TOWER
Check the type and condition of the fill, and clean or replace as necessary.
Check that the water flow across the fill has acceptable variation.
Consider the use of alternative spray nozzles to give an improved spray pattern.
Check that the nozzles are not broken or blocked.
If fitted, valves should be adjusted to provide a more even flow across the nozzles.
Check the operation of drift eliminators. In particular, look for scaling or biological growth that might
be restricting air flow.
Check the operation of sump heater controls
For crossflow designs, check that the sump water level is above the bottom of the fill, otherwise it will
offer an alternative way to bypass where it is required.
Clean the cooling fins of dry air cooling systems to enhance air flow.
CIRCULATING PUMPS
Check proper operation of non-return valves.
Sequence the pump control to match the flow to instantaneous demand.
Assess performance of each pump to decide on priority pumps when sequencing.
Measure pump efficiency over time to decide the best time to replace or repair.
WATER MANAGEMENT
Use automatic Total Dissolved Solids (TDS) monitoring and blowdown control to minimise make-up
and to dose the use of chemicals.
Fit a water meter to the make-up water inlet to monitor usage.
ENERGY MANAGEMENT
Upgrade failed low efficiency motors to high efficiency types
Install electricity and water meters to enable ongoing review of system performance.
Train the operators to be aware of energy efficiency aspects during plant operation.
2 Integrated Pollution Prevention and Control (IPPC) – Reference Document on the application of Best
Available Techniques to Industrial Cooling Systems. European Commission December 2001.
5 Reducing Water Pumping Costs in the Steel Industry, GPG170, ETSU, 1996.
6 Variable flow over cooling towers TR-014, SPX Cooling Technologies, 2017.
http://spxcooling.com/library/detail/variable-flow-over-cooling-towers
7 Saving energy With Cooling Towers, Frank Morrison, Ashrae Journal, Feb 2014.
http://www.corecontrolsdfw.com/documentation/2014Feb_034-041_Morrison.pdf
8 Based on an example in “Industrial Cooling Water Systems”. Good Practice Guide 225, 1999.
11 ABB Industrial cooling direct drive motor and VSD packages, 2015.
http://search-
ext.abb.com/library/Download.aspx?DocumentID=3AUA0000179912&LanguageCode=en&DocumentPar
tId=&Action=Launch
12 Legionnaires’ disease: Technical guidance Part1: The control of legionella bacteria in evaporative cooling
systems, UK Health and Safety Executive, 2013. http://www.hse.gov.uk/pubns/priced/hsg274part1.pdf