Disclaimer: These battery calculations are designed exclusively for architects, engineers, consultants an
distributors to assist in the development of fire alarm equipment quotations. There are no implied warran
documents generated by this program other than the standard limited warranty offered by NOTIFIER. NOT
documents generated using this program meet all applicable codes and laws. The user of this program m
codes and laws as well as the requirements of the Authority Having Jurisdiction and must amend the gene
At some point in time, some of these devices may no longer be available from NOTIFIER.
This workbook contains battery calculation worksheets that allow you to:
Help
Version 2.7
AC Branch Current
Select devices using the "Qty" column.
Use yellow cells to enter quantities and current values.
To show only selected devices, select "Show Selected Devices".
To clear selected devices, select "Clear Selections".
Note: These selections only determine the AC branch current. If these devices will affect the battery requirements, you need to select
them on the System Current Draw sheet.
2
● 120 VAC ● 220/240 VAC
Device Qty Current Total
AMPS-24 1 x 5.00 A 5.00 A
AA-30 0 x 1.00 A
AA-120 0 x 1.85 A
ACPS-2406 0 x 2.70 A
APS-6R 0 x 2.50 A
AVPS-24 0 x 1.00 A
CHG-120 0 x 2.00 A
FCPS-24 0 x 2.00 A
FCPS-24S 0 x 3.20 A
MPS-24A 0 x 1.80 A
MPS-24B 0 x 2.40 A
XPIQ 0 x 3.50 A
XRM-24 0 x 1.00 A
DAA-5025/5070 0 x 4.50 A
ACPS-610 0 x 5.00 A
APS2-6R 0 x 2.90 A
DAA Series 0 x 4.50 A
HPFF8 0 x 3.60 A
HPFF12 0 x 5.00 A
DS-AMP (25V) 0 x 4.10 A
DS-AMP (70V) 0 x 3.55 A
NFC-50/100 0 x 3.50 A
NFC-50DA (25v) 0 x 1.10 A
NFC-50DA (70.7v) 0 x 1.20 A
NFC-125DA 0 x 2.20 A
DAA2-5025 0 x 1.17 A
DAA2-5070 0 x 1.22 A
DAA2-7525 0 x 1.66 A
DAX-5025 0 x 0.29 A
DAX-5070 0 x 0.32 A
DAX-3525 0 x 0.29 A
DAX-3570 0 x 0.32 A
[ ] 0 x 0.00 A
[ ] 0 x 0.00 A
mary Alarm - C2
18.985
r Used (Amps)
200 4.800 6.400 8.000
C3 - Secondary Non-Alarm
Draw Standby
0.12000 0.12000
0.13000 0.13000
0.22000
0.40000
0.20000
0.20000
0.11000
0.40000
0.13000 0.26000
0.10000 0.10000
0.20000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.06000
0.00600
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.04500
0.05000
0.30000
0.06000
0.17500
0.07500
0.06000
0.06000
0.06000
0.02000
0.00000
0.00000
0.00000
0.00000
0.01600
0.01600
0.00200
0.00200
0.00540
0.04000
0.01600
0.00200
0.01600
0.04000
0.02500
0.03000
0.02500
0.02900
0.05000
0.04500
0.30000 0.30000
0.04000
0.00200
0.00000
0.00000
0.00000
0.06200
0.03600
0.03300
0.00500
0.00000
0.00000
0.11000
0.04000
0.05200
0.03500
0.01700
0.04700
0.04900
0.02000
0.00030 0.04260
0.00030 0.03900
0.00030 0.02520
0.00049 0.00776
0.00026 0.00459
0.00035 0.01400
0.00040 0.00800
0.00000 0.00000
0.00000 0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000 0.00000
0.00000
0.00000
0.00640
0.01000
0.02600
0.00050
0.00050
0.00000
0.00000 0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
1.051
0.000
0.50000
0.00000
Total Standby
1.051
Load:
System Power Requirements
Notifier NFS2-3030 Fire Alarm Control Panel
Page 10 of 14
Battery Distribution Chart
Shows amp-hour distribution of your selections.
Comments
1. Battery size exceeds FACP capacity. BB-55 or other external battery box
required.
2. Selected battery size meets secondary load requirements.
3. The selected batteries (110AH) are outside the charger range of this power supply (7-26AH).
Spare Battery Capacity 66.74 Battery Selection (AH) - Secondary Load Requirements (AH)
Secondary Standby Load 30.27 Secondary Standby Load (AH) * Derating Factor
Secondary Alarm Load 0.47 Secondary Alarm Load (AH) * Derating Factor
Page 11 of 14
ements
28.03.2019
+88029137109
1207
Total (AH)
25.23
30
0.39
55.62
x 1.2
66.74 AH
Page 12 of 14
e Battery Capacity
ply (7-26AH).
Page 13 of 14
Device Current Draw
NFS2-3030 Fire Alarm Control Panel
Quantity x [device current draw] = total current draw per device (in amps)
Part Number Qty Primary Non-Alarm Primary Alarm Secondary Non-Alarm
CPU2-3030 1 x [0.12000] = 0.12000 x [0.12000] = 0.12000 x [0.12000] = 0.12000
AMPS-24 1 x [0.00000] = 0.00000 x [0.00000] = 0.00000 x [0.13000] = 0.13000
LCM-320 2 x [0.13000] = 0.26000 x [0.13000] = 0.26000 x [0.13000] = 0.26000
LEM-320 1 x [0.10000] = 0.10000 x [0.10000] = 0.10000 x [0.10000] = 0.10000
LCD-160 1 x [0.30000] = 0.30000 x [0.32500] = 0.32500 x [0.30000] = 0.30000
FAPT-851 142 x [0.00030] = 0.04260 x [0.00000] = 0.00000 x [0.00030] = 0.04260
FSP-851 130 x [0.00030] = 0.03900 x [0.00000] = 0.00000 x [0.00030] = 0.03900
FST-851 84 x [0.00030] = 0.02520 x [0.00000] = 0.00000 x [0.00030] = 0.02520
FCM-1 16 x [0.00049] = 0.00776 x [0.00000] = 0.00000 x [0.00049] = 0.00776
FRM-1 18 x [0.00026] = 0.00459 x [0.00000] = 0.00000 x [0.00026] = 0.00459
FMM-1 40 x [0.00035] = 0.01400 x [0.00000] = 0.00000 x [0.00035] = 0.01400
ISO-X 20 x [0.00040] = 0.00800 x [0.00000] = 0.00000 x [0.00040] = 0.00800
RA100Z 21 x [0.00000] = 0.00000 x [0.00000] = 0.00000 x [0.00000] = 0.00000
NBG-12 20 x [0.00000] = 0.00000 x [0.00000] = 0.00000 x [0.00000] = 0.00000
SLC Loop Device Activation Current 3 x [0.00000] = 0.00000 x [0.20000] = 0.60000 x [0.00000] = 0.00000
P2RH177 60 x [0.00000] = 0.00000 x [0.30300] = 18.18000 x [0.00000] = 0.00000