TENON TOP
LIGHTING POLE 4 4
CHS 219x5.0 / SHS 200x200x5.0
POWDER COATING MINM. 60 MICRONS 3
10000
10000
10000
IN RAL COLOUR ____________ . 3
10000
FLUTED ROUND SHAFT SHS 200x50x5.0 RHS 300x200x5.0
BASE PLATE WELDING
CROSS SECTION
DETAILS
16 FLAT FLUTE
280
RHS 300x200x5.0
350
280
33
26
NAME PLATE 350
M24
GUSSET PLATE
THREADED 100
500
800
1500
500
1500
GUSSET PLATE
500
GUSSET PLATE 0
PEDESTAL 4-M24 R2
ANCHOR BOLTS ANCHOR BOLT
BASE PLATE BASE PLATE C/W 2 NYLOCK NUTS 100
500
500
& 2 PLAIN WASHERS
219
ACCESS DOOR
FIRM BEARING STRATA
FOOTING BASE ANCHOR BOLT DETAILS
STRAIGHT ROUND SHAFT FLUTED ROUND SHAFT ALUMINIUM 3D VIEW OF SQUARE POLE RECTANGULAR POLE RECTANGULAR POLE
DECORATIVE BASE LIGHT POLE DECORATIVE BASE LIGHT POLE FLUTED POLES WITH CURVED ELEVATION
1. ALL DIMENSIONS ARE IN MILLIMETER UNLESS NOTED OTHERWISE. 5. COLUMNS ARE HOT DIP GALVANIZED TO 85 MICRONS AS PER BS EN ISO STANDARD 00 --
2. THE LIGHTING COLUMN ARE DESIGNED TO WITHSTAND 1461.
Project Name: Total Page: Scale: Revision Date: Drawn By: Reviewed By:
WIND SPEED OF 25M/SEC AS PER QCS 2014, CONSIDERING, 6. SERVICE DOOR/CABINET DIMENSIONS ARE GIVEN AS GUIDE ONLY. THE
TOPOGRAPHY, GROUND ROUGHNESS, TERRAIN. AND STATISTICAL ENGINEER MUST SATISFY HIMSELF THAT DIMENSIONS GIVEN ARE -- 01 OF 01 NTS 13/04/2019 ALI --
FACTOR OF 0.96. ADEQUATE FOR THE INSTALLATION OF THE CONTROL PANEL. Drawing Title: Project Number: Checked - Approved By:
3. COLUMNS & THEIR BASE ARE DESIGNED IN COMPLIANCE WITH 7. WELDING : ACC. TO AWS D1.1 DECORATIVE POLES
-- AYUB
BS 5950-1, BS 6399-2 & BS 8110-1. 8. ANCHOR BOLTS : GR. 4.6 TO DIN 267 Material: Finish - Treatment: Date:
4. MATERIALS USED FOR LIGHTING COLUMNS CONFIRM TO EN 10025-2 -- -- 13/04/2019
S355JO OR EQUIVALENT.
All linear dimensions in millimeter - All angular dimensions in decimal degree / this drawing is COASTAL's property. We mistrust anyone from divulgation and total or partial reproducing without our authorization.