Vous êtes sur la page 1sur 4

Project : VN1752

POWER CONSUMER LIST FOR NON-PROCESS & CALCULATION (ESTIMATE)

Area Estimate Lux Power/unit Power (total) Power demand

Socket Simult. Power


BLD Load name Volt. Phase & Qty factor factor Remark
AC Ventil. Light.
(m²) Small Level (KW) (KVA) (KW) (KVA) (Ks) (cosj) (KW) (KVA)
W/m² W/m² W/m²
power
W/m²
1 Main production building (LP-Pro)
Ground floor
Warehouse 400/220 3&1 1,584.0 15 4 3 150-200 0.00 34.85 43.56 0.8 0.8 27.88 34.85
Production area 400/220 3&1 825.0 15 6 5 300 0.00 21.45 26.81 0.8 0.8 17.16 21.45
Battery charger 400/220 3&1 104.0 15 4 3 200 0.00 2.29 2.86 0.8 0.8 1.83 2.29
2 Office building (LP-Office)
Ground floor
Lab equipment 440/220 3&1 59.4 90 5 14 25 700 0.00 7.96 9.95 0.8 0.8 6.37 7.96
QC 400/220 3&1 28.8 70 5 10 15 500 0.00 2.88 3.60 0.8 0.8 2.30 2.88
Lab office 400/220 3&1 117.0 90 5 14 25 700 0.00 15.68 19.60 0.8 0.8 12.54 15.68
Reception waiting 400/220 3&1 32.4 70 5 6 15 300 0.00 3.11 3.89 0.8 0.8 2.49 3.11
Meeting 400/220 3&1 32.4 70 5 10 15 500 0.00 3.24 4.05 0.8 0.8 2.59 3.24
Toilet 400/220 3&1 64.8 15 4 15 200 0.00 2.20 2.75 0.8 0.8 1.76 2.20
3 Canteen and parking building (LP-Can)
Ground floor
Canteen 400/220 3&1 32.4 5 4 25 200 1 20.00 25.00 21.10 26.38 0.8 0.8 16.88 21.10
Parking building 400/220 3&1 423.0 15 4 3 150 0.00 9.31 11.63 0.8 0.8 7.44 9.31
4 Ultility building (LP-Ul)
Ground floor
Waste storage 400/220 3&1 90.0 15 4 3 200 1 2.0 2.50 3.98 4.98 0.8 0.8 3.18 3.98
Transformer room 400/220 3&1 22.5 15 2 100 0.00 0.38 0.48 0.8 0.8 0.31 0.38
MV room 400/220 3&1 24.8 15 4 2 200 0.00 0.52 0.65 0.8 0.8 0.42 0.52
LV room 400/220 3&1 47.3 15 4 2 200 0.00 0.99 1.24 0.8 0.8 0.79 0.99
Compressor room 400/220 3&1 112.5 15 6 5 300 1 2.0 2.50 4.93 6.16 0.8 0.8 3.94 4.93
5 Water tank and pump house (LP-WT)
Pump house 400/220 3&1 90.0 15 4 2 200 1 2.0 2.50 3.89 4.86 0.8 0.8 3.11 3.89
6 Gruard house (LP-GH)
Road light 400/220 3&1 10-20 32 0.2 0.25 6.40 8.00 0.8 0.8 5.12 6.40
Main door 400/220 3&1 300 1 5.0 6.25 5.00 6.25 0.8 0.8 4.00 5.00
Guard house 400/220 3&1 32.0 70 5 6 25 300 0.00 3.39 4.24 0.8 0.8 2.71 3.39
7 Production equipment (MCC)
ID (Ink Dispenser) 400/220 3&1 1 5.00 6.25 5.00 6.25 0.8 0.8 4.00 5.00
AC (Air compressor) 400/220 3&1 1 7.81 9.76 7.81 9.76 0.8 0.8 6.25 7.81
AC (Air compressor for LAB) 400/220 3&1 1 2.20 2.75 2.20 2.75 0.8 0.8 1.76 2.20
RM 01(Tri-roll mill) 400/220 3&1 1 3.00 3.75 3.00 3.75 0.8 0.8 2.40 3.00
RM 02 (Tri-roll mill) 400/220 3&1 1 2.20 2.75 2.20 2.75 0.8 0.8 1.76 2.20
Mixer 01 (Dough mixer) 400/220 3&1 1 0.18 0.23 0.18 0.23 0.8 0.8 0.14 0.18
Mixer 02 (Dough mixer) 400/220 3&1 1 1.10 1.38 1.10 1.38 0.8 0.8 0.88 1.10
Mixer 03 (Dough mixer) 400/220 3&1 1 1.80 2.25 1.80 2.25 0.8 0.8 1.44 1.80
Mixer 04 (Dough mixer) 400/220 3&1 1 0.75 0.94 0.75 0.94 0.8 0.8 0.60 0.75
Mixer 05 (High speed disperser) 400/220 3&1 1 30.00 37.50 30.00 37.50 0.8 0.8 24.00 30.00
Mixer 06 (High speed disperser) 400/220 3&1 1 22.00 27.50 22.00 27.50 0.8 0.8 17.60 22.00
Mixer 07 (High speed disperser) 400/220 3&1 1 3.75 4.69 3.75 4.69 0.8 0.8 3.00 3.75
Mixer 08 (High speed disperser) 400/220 3&1 1 45.00 56.25 45.00 56.25 0.8 0.8 36.00 45.00
Air-con 1HP 400/220 3&1 0 10.50 13.13 0.00 0.00 0.8 0.8 0.00 0.00
Air-con 2HP 400/220 3&1 0 21.00 26.25 0.00 0.00 0.8 0.8 0.00 0.00
Charger forklift PD 400/220 3&1 1 10.00 12.50 10.00 12.50 0.8 0.8 8.00 10.00
Charger stacker PD 400/220 3&1 1 1.20 1.50 1.20 1.50 0.8 0.8 0.96 1.20
Charger forklift WH 400/220 3&1 1 3.60 4.50 3.60 4.50 0.8 0.8 2.88 3.60

Page 1 of 4
Area Estimate Lux Power/unit Power (total) Power demand

Socket Simult. Power


BLD Load name Volt. Phase & Qty factor factor Remark
AC Ventil. Light.
(m²) Small Level (KW) (KVA) (KW) (KVA) (Ks) (cosj) (KW) (KVA)
W/m² W/m² W/m²
power
W/m²
Scale 2ton 400/220 3&1 1 0.20 0.25 0.20 0.25 0.8 0.8 0.16 0.20
Scale 3ton 400/220 3&1 1 0.30 0.38 0.30 0.38 0.8 0.8 0.24 0.30
Oven (QC) 400/220 3&1 1 0.50 0.63 0.50 0.63 0.8 0.8 0.40 0.50
3xLabel printer (QC) 400/220 3&1 1 1.20 1.50 1.20 1.50 0.8 0.8 0.96 1.20
4xIKA mixer (QC+LAB) 400/220 3&1 1 0.30 0.38 0.30 0.38 0.8 0.8 0.24 0.30
2xUV lamp (QC+LAB) 400/220 3&1 1 0.80 1.00 0.80 1.00 0.8 0.8 0.64 0.80
4xRK Proofer (QC) 400/220 3&1 1 1.20 1.50 1.20 1.50 0.8 0.8 0.96 1.20
2xOrange Proofer (LAB) 400/220 3&1 1 0.30 0.38 0.30 0.38 0.8 0.8 0.24 0.30
Harper proofer (LAB) 400/220 3&1 1 0.05 0.06 0.05 0.06 0.8 0.8 0.04 0.05
2xWater bath memert (LAB) 400/220 3&1 1 4.00 5.00 4.00 5.00 0.8 0.8 3.20 4.00
2xGravo Proofer (LAB) 400/220 3&1 1 0.80 1.00 0.80 1.00 0.8 0.8 0.64 0.80
4xDryer (QC + LAB) 400/220 3&1 1 4.80 6.00 4.80 6.00 0.8 0.8 3.84 4.80
7xScale (QC + LAB) 400/220 3&1 1 0.42 0.53 0.42 0.53 0.8 0.8 0.34 0.42
Light box (LAB) 400/220 3&1 1 0.50 0.63 0.50 0.63 0.8 0.8 0.40 0.50
Heat seal (LAB) 400/220 3&1 1 1.00 1.25 1.00 1.25 0.8 0.8 0.80 1.00
RUB Tester (LAB) 400/220 3&1 1 0.20 0.25 0.20 0.25 0.8 0.8 0.16 0.20
COF Tester (LAB) 400/220 3&1 1 0.60 0.75 0.60 0.75 0.8 0.8 0.48 0.60
Bond strength machine 400/220 3&1 1 0.60 0.75 0.60 0.75 0.8 0.8 0.48 0.60
GC machine 400/220 3&1 1 5.00 6.25 5.00 6.25 0.8 0.8 4.00 5.00
Volumn matric KF Titrator 400/220 3&1 1 0.20 0.25 0.20 0.25 0.8 0.8 0.16 0.20
21 x High voltage light (PD&WH) 400/220 3&1 0 5.25 6.56 0.00 0.00 0.8 0.8 0.00 0.00
6 x Gate Moter (Main+PD+WH) 400/220 3&1 1 1.38 1.73 1.38 1.73 0.8 0.8 1.10 1.38
TOTAL LOAD 253.99 317.48
SPARE 20% 50.80 63.50
TOTAL AMOUNT POWER CONSUMTION 304.78 380.98 419.075316

Page 2 of 4
Connect

Feeder

(kW)
46.87

28.06

24.33

8.64

3.11

11.83

131.15

Page 3 of 4
Connect

Feeder

(kW)

253.99
50.80
304.78

Page 4 of 4