Envicool)
User Manual
Issue 01
Date 2013-1-17
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Email: support@huawei.com
Overview
This use manual introduces PC500 air conditioner user introduction, summary, packaging and
transportation, unpacking and inspection, installation, power-on and checking, maintenance.
Target Reader
This Manual mainly applies to the following engineers:
Technical support engineer
Maintenance engineer
Market engineer
Service engineer
Modified Records
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.
Issue 01 (2013-01-17)
This is the first official release.
Content
7 Maintenance ................................................................................................................................. 25
7.1 Daily Maintenance ......................................................................................................................................... 25
7.1.1 Maintenance periodic table ................................................................................................................... 25
7.1.2 Tools ...................................................................................................................................................... 26
7.1.3 Spare Parts ............................................................................................................................................ 26
7.1.4 Electric control assembly maintance ..................................................................................................... 27
7.1.5 Internal cycle fan maintenance .............................................................................................................. 28
1 Use Instruction
This manual shall only be used as the guide for the installation and operation of the PC500
outdoor cabinet air conditioner. It introduces the functions and daily maintenances of the unit.
CAUTION
All wiring connections must comply with national and local electrical code; voltage,
frequency and power capacity must be consistent with the provisions of the use of this
product.
The product must be installed by trained professionals.
Don’t upside down, excessive tilt and collision.
Need circuit breaker for both DC and AC power supply.
Grounding connection must be reliable. Grounding wires can’t be connected to gas pipe,
water pipe, lightning rod, telephone wire. Otherwise, it causes the electric shock hazard.
Prohibited lead or extend the power line, the prohibition of weight, heating, pull the power
line.
Compressor use power input of 220 V AC (or 110 V AC dual live wire). Controller and
fans use power input of -48 V DC.
Power inputs of 220 V AC and -48 V DC are both on, the equipment works well. Only 220
V AC power input is on and -48 V DC is not on, the whole equipment doesn’t work. Only
-48 V DC is on and 220 V AC is not on, only fans and heat exchanger work, compressor
doesn’t work.
2 Product Overview
2.2 Features
This unit has perfect functions, such as with internal & external fan control function. And it
features high reliability and easy installation, so that it can work once the power supply is
available and no complex adjustment is needed.
Air conditioning works 24 hours a day, 365 days a year continuously running
Products with power-off memory calls function or self-starting function. Air conditioning
power down to memory before power off the set state, then after the caller according to
memory state parameter automatic operation; calls since the launch of the function that as
long as the air conditioner to on state, power conditioning can automatically put into
operation.
DC power supply input has a reverse connection preventing function. If power supply positive
and negative polarity reverse connection, equipment does not work, no damage. Positive and
negative pole is connected, machines can be normal operation
Air conditioner shell fixing screw all use the security design, Air conditioning is an integrated
structure, compressor, condenser, evaporator, expansion valve, control unit, the air unit and all
other components as a whole.
The air conditioner casing for outdoor metal structure, the anti-corrosion measures, improve
the ability of corrosion resistance, service life of 10 years.
Rated Voltage 220 V AC/50 HZ; -48 V DC Must connect both AC and
DC power supply. AC
powers compressor on. DC
power control and fans.
Rated Cooling Capacity 600 -
L35/L35 (W)
Rated Power L35/L35 (W) 265 -
AC circuit breaker capacity 6 -
(A)
DC circuit breaker capacity 3 -
(A)
Refrigerant /GWP R134a/150g -
Working Temperature Range -15~+55 -
(degC)
Relative Humidity Range 5~100% -
(%)
Storage Temperature Range -40~+70 -
(degC)
Altitude (m) 4000 -
Transport properties Adapt to train, car, airplane, -
shipping and other
transportation modes.
Max. noise Level dB(A) 65 -
Noise Level (25degC)dB(A) 55 -
Noise Level (40degC)dB(A) 62 -
IP Protection IPX5 -
Anti-flaming Meet UL94 requirements -
Reliability (Years) 10 -
External circulation Meet IEC 68-2-52, IEC -
corrosion 68-2-30
NOTE
Ti: Cabinet return air temperature; Ta: External ambient temperature;
Qk: Cooling capacity in the corresponding conditions;
Pk: Cooling power input in the corresponding conditions.
2.7 Components
This air conditioner main component contains: compressor, throttling element, internal &
external fan, evaporator, condenser and control assembly. Shown as follows:
Air blower
Control box
Evaporator
Throttling element
External fan
Compressor
Condenser
Internal cycle
hot air inlet Extemal cycle
hot air outlet
PC500
External cycle
Internal cycle air inlet
cold air outlet
The alarm display will be still on until the alarm has been resumed.
Through the “Figure 6-2 Unit menu structure” enter the “Alarm Menu” can view more alarm
information.
NOTE
When the package is removed, make sure that the air conditioner is placed vertically. It can’t be
placed horizontally or upside down.
When the external package is removed, please check carefully whether the appearance of the air
conditioner is damage or whether there is any oil. If any damage is found, please report this with the
barcode number on the package to the retailer or Huawei.
If there is no need to install the product immediately or it needs to be transported to other place,
please repack the air conditioner after the checking.
To protect the environment, it is recommended to recycle the packing cartons.
5 Installation
This chapter mainly introduces PC500 air conditioner mechanical & electrical installation.
Before installation, please pay attention to the following two points:
1), The placement of the equipment inside the cabinet should be proper. For example, any
obstruction to the internal cycle air inlet and outlet of the air conditioner should be avoided.
2), Check the accessories according to the attachment list and prepare tools.
Dimension
CAUTION
All the electrical connections should comply with the standards of the national and local
electrical codes. Please disconnect all the power supplies for the air conditioner before
the installation.
Select proper wire diameter and circuit protection device according to the air conditioner
nameplate and technical parameters
CAUTION
Unit used both AC 220 V AC and DC -48 V power supply input.
AC can be connected to dual live wire with 2 P circuit.
-48 V DC is for PCB control and fan assembly.
220 V AC is for compressor.
UNIT has no work and LCD has no power on while -48 V DC is broken or circuit breaker is
off.
Compressor has no work while AC power supply is broken or circuit breaker is off.
AC power cable is forbidden to DC power supply.
DC power cable is polarized and forbidden to AC power supply.
Alarm cable is forbidden to AC and DC power supply.
Communication port
Communication port adopts RJ45 communication coupler.
COM IN port is connected to monitor. COM OUT is connected to cascade unit.
1 Orange/white TX+
2 Orange TX-
4 Blue RX+
5 Blue/White RX-
Alarm Cable
Alarm cable is with “S+”, “S-” identifier.
This chapter mainly introduces PC500 air conditioner power-on and checking after
installation.
←: Left button, which is used to increase the setting value during the parameter setting or
select the previous bit of the data during the password setting.
→: Right button, which is used to decrease the setting value during the parameter setting or
select the next bit of the data during the password setting.
ENTER: the entry of main menu and submenus, confirm data input.
ESC: Quit button, which is used to return to the previous page menu.
Menu
NOTE
This diagram is unit menu structure, not the real setting.
Remarks:
In1: Internal return Temperature sensor1
In2: Internal return Temperature sensor2
Out: External ambient Temperature sensor
Tp: Evaporator coil Temperature sensor
Te: Compressor exhaust pipe Temperature sensor
Cond: Condenser coil Temperature sensor
Only “ENTER” and “ON/OFF” keys are available in main interface. Other key is not
available.
“ENTER” key is the entry of Menu.
“ON/OFF” key is to turn on/off unit.
ON/OFF function
Press and hold the button “ON/OFF” for at least 5 seconds, and then release hand, the air
conditioner will be turned from ON status to OFF.
Also, press and hold the button “ON/OFF” for at least 5 seconds, and then release hand, the
air conditioner will be turned from OFF to ON.
The following is the OFF interface.
NO. Item
NO. Item
5 Check the power supply voltage with current meter, Whether the power supply
voltage is normal, and comply with the nameplate parameter.
6.3 Running
Close the AC & DC power input circuit breaker. Air conditioner is powered on.
Normal running
At first, internal fan is running at low speed. 3 minutes later after power on, air conditioner
starts running.
When internal temperature reaches the cooling startup point, the cooling system starts with
compressor and external fan start running.
Many minutes later, the temperature of internal air supply port on bottom will lower than the
air return port on top. The temperature of external air exhaust outlet on top will higher than
ambient.
After self-test, the system enters the normal running status. Internal cycle fan keeps running,
if the cabinet internal Temperature reaches the cooling startup point, the cooling will start, and
then compressor and external fan run at the same time.
High temperature (Ambient temp 55degC): After cooling starts, visually check whether the
internal fan & compressor run normally DC (1.0±0.2 A), AC (1.3±0.2 A). In high temperature,
the AC current is higher than rated AC current.
Low temperature (Ambient temp 15degC): After cooling starts, visually check whether the
internal fan & compressor run normally DC (1.0±0.2 A),AC (0.7±0.2 A). In low Temperature,
the AC current is lower than rated AC current.
NOTE
The air conditioner cooling startup default valve is 25 degC, when the cabinet internal return
temperature is lower than 25 degC, the unit can’t start. Onsite checking, heating the
temperature sensor to the detected Temperature is higher than 25 degC, and then the unit can
start. During the checking, needn’t change the unit’s setting parameter. Cooling normal
judgment:
After cooling starts, if the internal & external fan and compressor run normally without
abnormal noise and the unit current is normal judged according to the above 3 points, and the
internal outlet Temperature is lower than the inlet Temperature; and the external outlet
Temperature is higher than the inlet Temp; it indicates that the unit is in normal cooling mode.
7 Maintenance
7.1.2 Tools
During the installation & maintenance, we need to use the following tools, but not limited to
them.
Wire Cutter Process cable and wipe off ribbon for strapping cable
onsite.
NOTE
Perform compressor capacitor and surge protection device maintenance according to the above 1 to 5
steps.
General dust treatment: Without removing the maintenance cover plate and shell, with a water
cannon directly external circulation air inlet and outlet rinse
CAUTION
When the summer is coming every year, need to perform the maintenance for condenser and
drainage outlet, get rid of impurities such as catkin, sand and dust.
Internal fan Terminal is loose Check whether the connecting terminal is loose.
doesn’t start
Power failure Check the DC input power voltage, whether the
voltage is in the range.
Fan blocking Check whether there is foreign matter blocking
the fan.
Internal return Check whether the internal return Temperature is
Temperature is too lower than the internal fan stop point. If so, the
low internal fan will.
External fan Terminal is loose Check whether the connecting terminal is loose.
doesn’t start
Power failure Check the DC input power voltage, whether the
voltage is in the range.
Fan blocking Check whether there is foreign matter blocking
the fan.
No cooling Check the detected internal Temperature and the
requirement external fan status through the display interface.
Fan has Bearing wear Replace fan.
abnormal noise
Fan impeller scrape Check whether there is interference between
other materials cables and fan impeller.
AC Input
Control board
Signals port
DC Input
DC SPD
Protection
Protection board
board
8 Barcode description
The date of manufacture and serial number on the barcode are showed as follows:
Air conditioner communicates with upstream equipment through ModBus protocol. The unit
supplies 2 RJ45. Port COM IN is used to communicate with upstream equipment. Port COM
OUT is used to cascading. (NOTE: Each RJ45 supplies one-way RS485 communication.) The
default communication rate is 9600 bps. The default address is 16H. The unreadable
parameter and invalid value default value are entire F (0xFF/0xFFFF).
The following air conditioner common parameter can be obtained through communication
protocol.
Unit electronic label length can be obtained through communication protocol, the register
address is 0x38E.
The following air conditioner information can be obtained through communication protocol.
NOTE
1) Unit Running Status:
0X01 Standby (Normally turn off the unit through communication or dry contact), or internal fan stops.
0X02 Running (Running without fault)
0X03 Fault (There is fault)
2) Definition of unit running status, internal fan status, external fan status, compressor status and
pump status:
0X01 Standby
0X02 Running (Running without fault)
0X03 Fault (There is fault)
3) Unit running time, compressor running time and internal fan running time are the accumulative
running time after delivery.
4) Upstream equipment can read all the above parameter through a multiple-address read command.
For unused address, the return value can be filled with 0xFFFF.
NOTE
1) Upstream equipment can set all the above parameter through a command writing multi-register, for
the unused address, the air conditioner skips without treatment.
2) Upstream equipment can read the setting value through parameter’s address.
NOTE
1) After remote OFF, the compressor, external fan and internal fan stop.
2) After remote ON, the air conditioner works according to the normal logic. For example, the
cooling startup point is 35degC, and the internal return Temperature exceeds 35 degC, the
compressor starts. Otherwise, the air conditioner is standby.
The following air conditioner alarm information can be obtained through protocol.
NOTE
Upstream equipment can read all the above alarm through a multiple-address read command.
For unused address, the return value can be filled with 0xFFFF