Fig. 3-163b. Using the limited current test to find the open phase of a delta-
/
l connected motor. More current will flow when testing across the good phases than across
/
the open phase.
Test light t:\c;f't_- "
---~---- -------~'!.!~!.---_./
Fig. 3-162. Locating the open group with a test light.
Test panel
Phase B
PhaseC
c)
~ur~w
T3 Fig. 3-163c. Locating the open group in the A phase of a delta-connected motor us-
Phase C T2 ing the limited current method. The current in test 1 is high because it goes through only
a) . one group. The current in test 2 goes through most of the groups and is low.
Fig. 3-163a. Using the limited current method to find the open phase in a delta con-
nection. The open phase will have the lower amp reading. .