Together with C60, C120, iDPN (DPN) circuit breakers, ID residual current
circuit breakers and I-NA switches of the Schneider Electric brand.
They allow remote tripping or indication.
They are fastened by clips (without tools) to the left side of the device.
d d
b The electrical auxiliaries are not compatible with ID b If the SD and OF+SD/OF auxiliary contacts are combined with tripping
residual current circuit breakers of type B. auxiliaries (MN, MX, etc.), they shall be mounted to the left of the latter.
DB122914
or
or
C60 C120
OF+ OF SD MX+OF, MN, MNs,
SD/OF MX or MSU MNx
OF.S ID
I-NA
OF.S
Connection
By screw clamp terminals for:
Flexible or rigid cable Flexible or rigid multi- Stripping length Tightening torque Posidriv
cables
DB112804
DB112805
DB112802
DB112806
DB112807
0.5 to 2.5 mm 2
2 x 1.5 mm 2
9 mm 1 N.m n°1 - Ø 4 mm
Tripping
MN MNs MNx MSU
Undervoltage release Release by OFF push button (PB) Voltage threshold release
Instantaneous Delayed
PB100202_SE-30
PB100203_SE-30
PB100205_SE-30
PB100206_SE-30
Use
b Emergency stop by OFF push button b Fail-safe emergency stop b Monitors the voltage between
b Ensures the safety of power supply circuits for several neutral and phase conductors
machines by preventing "uncontrolled" restarting
Function
b Controls tripping and opening of the device with which b Tripping auxiliary insensitive to power b Switches off the power supply by
it is combined when its supply voltage decreases supply circuit breaking opening the device with which it is
(between 70% and 35%). Prevents device reclosing until combined, in the event that the
its supply voltage is restored phase/neutral voltage is exceeded
(loss of neutral).
For a four-phase network, use
three MSU tripping auxiliaries
b Time delay of 0.2 b Tripping b Tripping
second on brownout voltage: voltage:
or voltage dip 275 V AC 255 V AC
Cat. no 26960 26961 26959 26963 26969 26977* 26971 26991* 26979 26479
Technical data
Control voltage V AC 220…240 48 115 220…240 230 400 230
V DC - 48 -
Operating Hz 50/60 400 50/60
frequency
Red mechanical indicator On front face
Test button -
Width in 9 mm modules 2
Auxiliary contact -
(breaking capacity)
Operating °C -25…+50
temperature
Storage °C -40…+85
temperature
Wiring diagrams
DB118804
DB118805
DB118806
* Tripping auxiliaries MNx ref. 26977 and 26991 are specific for C60 circuit breakers.
PB100198_SE-30
PB100628_SE-30
PB100626_SE-30
PB100627_SE-30
PB100625_SE-30
b Emergency stop by ON b Emergency stop by ON b Compulsory for b Remote indication of b Remote indication of b Remote indication of
push button push button the addition of the position of the tripping upon a fault of the position and/or tripping
b Remote indication of the tripping or indication associated device associated device upon a fault of the
position of the associated auxiliaries on a associated device
device residual current
circuit breaker
(except I-NA)
b Remote
indication of the
position of the
associated device
b Controls tripping and opening of the device with which b Changeover b Changeover contact: b Changeover contact: b Provision of an OF+SD
it is combined as soon as it is powered up contact: indicates indicates "open" or indicates "tripped upon or OF+OF contact by rotary
"open" or "closed" "closed" position of the fault" position of the device changeover switch
position of the device
device
-40…+85 -40…+85
DB118807
DB118808
DB118809
DB118810
DB118811
DB118812
14 12 11
OF position
DB118813
SD position