Académique Documents
Professionnel Documents
Culture Documents
Products & Services > SF6 Gas Analysis > 973-SF6 Gas Analyzer
Pure SF6 is the standard filling within GIS, but over time gas compartments become contaminated with water vapor (H2O) through permeation and by desorption from
internal materials. Whilst water vapor and SF6 do not normally react with each other, in the presence of a high-energy discharge, hydrogen and oxygen disassociated from
water vapor will react with the sulfur and fluorine from SF6 to form decomposition by-products. These include sulfur dioxide (SO2) and hydrofluoric acid (HF) that are
corrosive to the internal components of gas compartments.
SF6 with low water vapor content (low humidity) significantly reduces the potential for formation of these corrosive compounds, which is why accurate and repeatable
measurement data is an invaluable part of any GIS preventative maintenance program.
• 973-SF6 Instrument
• Transport Peli-Case 1620
• 6 m Stainless Steel armored PTFE tubing
• SF6 coupling DN8 with quick coupling (Rectus)
• SF6 coupling DN20 with quick coupling (Rectus)
• 90° Angle for Rectus-Coupling
• Serial cable DB9 3m 1:1 male/female
• RS-232 / USB Adapter
• USB stick with 973-SF6 Software and operation manuals
• Power cable (country specific)
• Hex key for SO2 module
• SO2 Dummy sensor
• Cotton swabs, sterile (10 pieces)
• Operation Manual (2 pieces)
• Calibration Certificate
All accessories can also be ordered separately to replace damaged or missing components.
• Features
• Key Specifications
• Typical Applications
• Accessories & Spare Parts
• Downloads
• Media
Features
• Simultaneous measurement of humidity, SF6 purity and SO2 concentration
• Integrated gas recovery system with automatic pump back
• Fully automated SF6 gas testing
• Fundamental drift-free measuring principle
• Measurement results at SF6 compartment or standard pressure
• Intuitive color touch screen user Interface
• User verifiable calibration
• Robust case for easy transportation
Key Specifications
• Frost/dew Point range: -50…+20 °C
• Volume SF6 range: 80…100%
• Inlet pressure range: 120…1’000 kPa abs.
• Frost/dew point accuracy: ± 0.5 °C
• ppmv /ppmw accuracy: ± 1 ppm +6% of reading
• Volume SF6 accuracy: ± 0.5%
• Pressure accuracy: ± 3 kPa
Typical Applications
• Electrical Power Utilities
• Gas insulated switchgear
• SF6 gas manufacturers and suppliers
Downloads
Datasheets
973-SF6 Datasheet
English Version
973-SF6 Datasheet
French Version
Manuals
973-SF6 Manual
English Version
973-SF6 Manual
German Version
973-SF6 Manual
French Version
Media
Contact Us
If you have further questions please don’t hesitate to contact us.
Links
• MBW Home
• Contact
• Terms & Conditions
• Impressum
Contact
+41 56 437 28 30
+41 56 437 28 40 (Fax)
About Us
At MBW Calibration, our humidity measuring and generating technology allows us to produce state-of-the-art products to fit our customers individual needs.