Académique Documents
Professionnel Documents
Culture Documents
Abstract—Recent technological advances in the area of wide- However, the cost and associated complexities restrict the use
area measurement systems (WAMS) has enabled the use of a com- of such sophisticated signal transmission hardware in a large
bination of measured signals from remote locations for centralized commercial scale. As a more viable alternative, the existing
control purpose. The transmitted signals can be used for multiple
swing mode damping using a single controller. However, there is communication channels are often used to transmit signals from
an unavoidable delay involved before these signals are received at remote locations. The major problem is the delay involved be-
the controller site. To ensure satisfactory performance, this delay tween the instant of measurement and that of the signal being
needs to be taken into account in the control design stage. This available to the controller. This delay can typically be in the
paper focuses on damping control design taking into account a de- range of 0.5–1.0 s, depending on the distance, protocol of trans-
layed arrival of feedback signals. A predictor-based control
design strategy is discussed for such time-delayed systems. The mission and several other factors. As the delay is comparable
concept is utilized to design a WAMS-based damping controller to the time periods of some of the critical inter-area modes, it
for a prototype power system using a static var compensator. The should be accounted for in the design stage itself to ensure sat-
controller performance is evaluated for a range of operating con- isfactory control action. Our previous work [4] has illustrated
ditions. a -based centralized control design methodology without
Index Terms—H-infinity control, inter-area oscillations, LMI, considering the delay (0.02–0.05 s) involved in transmitting the
model reduction, remote signals, robustness, Smith predictor, remote signals. In that case, the delay was much less than the
swing mode.
lowest time period of the inter-area modes and therefore we
could ignore it in the design stage.
I. INTRODUCTION In this work, the power system is treated as a dead-time
system involving a delay in transmitting the measured signals
I N A PRACTICAL power system, the number of dominant
inter-area modes is often larger than the number of con-
trollable devices available to control them. Research attention,
from remote locations to the controller site. It is very difficult to
control such time-delayed systems [5]. Smith predictor (SP) [6],
therefore, has been focused on designing new control structures [7] approach, proposed in the early fifties, is the first effective
to improve the damping of multiple swing modes. The primary tool for handling such control problems. controllers are not
idea behind the control design is to employ a combination of likely to guarantee satisfactory control action for time-delayed
remote stabilizing signals with diverse modal contents [1]. systems. The difficulties associated with the design of
With rapid advancements in WAMS technology, the transmis- controllers for such systems and the potential solution using the
sion of measured signals to remote control center has become predictor-based approach is discussed in details in Section III.
relatively simpler. This has made the prospect of damping of One of the drawbacks of the classical Smith predictor (CSP)
inter-area oscillations through remote measurements a realistic approach is that it is very difficult to ensure a minimum damping
one. From an economic viewpoint, implementation of the cen- ratio of the closed loop poles when the open-loop plant has
tralized control using remote signals often turns out to be more lightly damped poles (as often encountered in power systems).
cost effective than installing new control devices [1]. The ob- A modified Smith predictor (MSP) approach, proposed by Wan-
vious question is how fast are these remote measurements avail- tanable et al. [8], can be used to overcome the drawbacks of the
able to the control site. Employing phasor measurement units CSP. However, the control design using MSP approach might
(PMU), it is possible to deliver the signals at a speed of as high run into numerical problems for systems with fast stable poles.
as 30 Hz sampling rate [2], [3]. It is possible to deploy the PMUs To overcome the drawbacks of CSP and MSP, an unified Smith
at strategic locations of the grid and obtain a coherent picture of predictor (USP) approach was proposed very recently by Zhong
the entire network in real time [3]. [9]. The USP approach effectively combines the advantageous
features of both the CSP and MSP.
Therefore, an USP approach is adopted in this work to for-
Manuscript received December 5, 2003. This work was supported by the ABB
(U.S.) and EPSRC (U.K.) under Grant GR/R/31676. Paper no. TPWRS-00592- mulate the damping control design problem for a power system
2003. having a signal transmission delay of 0.75 s. A controller
The authors are with the Department of Electrical and Electronic Engineering, is designed by solving the problem using linear matrix inequal-
Imperial College London, London SW7 2BT, U.K. (e-mail: b.chaudhuri@
imperial.ac.uk; r.majumder@imperial.ac.uk; b.pal@imperial.ac.uk). ities (LMIs) with additional pole-placement constraints. The
Digital Object Identifier 10.1109/TPWRS.2004.835669 methodology is demonstrated by designing a 2-input, 1-output
0885-8950/04$20.00 © 2004 IEEE
1972 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 4, NOVEMBER 2004
(1)
(2)
and
The computation of matrix exponential in (3) suffers
from numerical problems especially for systems having fast (6)
stable eigenvalues. In the worst case, it might well be noncom-
putable. This problem can even arise with reasonably small The predictor for the critical part is formulated using the MSP
amount of delays if some of the stable eigenvalues are very fast. approach by applying a completion operator [5]. On a rational
In , mixed-sensitivity formulation for power system transfer matrix , the completion
damping control design, the presence of fast stable eigenvalues operator is defined as follows:
in the augmented plant cannot be ruled out, the possible sources
being the fast sensing circuits , fast damper circuits (7)
, and even the weighting filters. These often lead
to numerical instability while solving the problem using LMIs. Using (7), the predictor for the critical part is given by (8)
These problems are overcome through the use of the USP [9] (see [5] for details)
formulation. This is achieved by decomposing the delay free
plant into a critical part and a noncritical part . The
critical part contains the poorly damped poles of the system
whereas, the noncritical part consists of poles with sufficiently
large negative real values. Section IVdescribes the generalized
(8)
problem formulation using this approach.
The predictor for the noncritical part is constructed following
IV. PROBLEM FORMULATION USING UNIFIED the CSP formulation and is given by
SMITH PREDICTOR
(9)
As indicated in Section III, the first step toward formulating
the control problem using the USP approach is to decompose The USP, denoted by , is simply the sum of and , as
the delay-free plant into critical and noncritical parts. This is shown in Fig. 8.
normally done by applying a suitable linear coordinate trans- It is given by
formation on the state-space representation of the plant. In this
(10)
work, a suitable transformation matrix was chosen such that
the transformed matrix is in the Jordan canon- where . Using (4), (6) and (8), the realiza-
ical form which is free from complex entries. The transforma- tion for can be expressed in the form
tion matrix was chosen using the “eig” function available in
Matlab [13]. The elements of the transformed matrix were (11)
converted from complex diagonal form to a real diagonal form
using the “cdf2rdf” function in Matlab [13]. The transformed where
augmented delay-free plant is given by
(12)
(4)
The augmented plant is obtained by connecting the
original dead-time plant and the USP in parallel—see Fig. 7,
where is critical and is the noncritical part of A. The where the new set of measured outputs are . The expression
augmented plant can be split as , where for is given by
(5) (13)
CHAUDHURI et al.: WIDE-AREA MEASUREMENT-BASED STABILIZING CONTROL 1975
(14)
Having formulated the generalized plant following the USP
approach, the objective is to design a controller to meet the
desired performance specifications. If ensures the desired
performance for , then controller predictor combination
is guaranteed to achieve the same for the orig-
inal dead-time plant [5].
V. CONTROL DESIGN
The control design problem was formulated using the stan-
dard mixed-sensitivity approach [4], [14] with modifications de- Fig. 11. Frequency response of the weighting filters.
scribed in the earlier sections. The overall control setup is shown
in Fig. 9, where is the power system model, is
2) Formulate the generalized plant using the reduced plant
the SVC model, , are the weighting filters, is
and the mixed-sensitivity weights.
the controller to be designed, is the SP, is the disturbance
3) Design the controller using the LMI Toolbox with addi-
at the plant output, is the weighted exogenous output, is
tional pole-placement constraints.
the measured output, and is the control input. In the context
4) Reduce the designed controller size.
of our problem, represents the remote measurements
4) Test the reduced controller on the full-order (real) plant
and and represents the supplementary control input to
with appropriate delays.
the SVC which corresponds to in Fig. 2. The design
The 134th-order open-loop plant was approximated to a
objective is the following: find a controller from the set of
tenth-order equivalent, as shown in Fig. 10.
internally stabilizing controllers such that
The weights were chosen as follows:
(15) (16)
where is the sensitivity. The solution to The frequency responses for the weighting filters are shown
the problem was sought numerically using LMI solver with ad- in Fig. 11. They are in accordance with the basic requirement
ditional pole-placement constraint. Once the generalized plant of mixed-sensitivity design, i.e., should be a low-pass
is formulated following the steps mentioned in Section IV, the filter for output disturbance rejection and should be a
basic steps for control design are similar to those outlined in high-pass filter in order to reduce the control effort and to ensure
[14] and are summarized below. robustness against additive uncertainties in the plant model in
1) Reduce the plant size. the high-frequency range.
1976 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 4, NOVEMBER 2004
TABLE II
DAMPING RATIOS AND FREQUENCIES OF THE INTER-AREA MODES
TABLE III
DAMPING RATIOS AND FREQUENCIES OF THE CRITICAL INTER-AREA MODES
AT DIFFERENT LEVELS OF POWER FLOW BETWEEN NETS AND NYPS
Fig. 14. Power flow in the tie-line 60–61; controller designed considering Fig. 17. Dynamic response of the system with a delay of 1.0 s.
delay.
Fig. 18. Dynamic response of the system; controller designed without Fig. 19. Power flow in the tie-line 60–61; controller designed without
considering delay. considering delay.
is therefore tested for a range of delays. It has been found that demonstrate a potential application of the USP approach for
below 0.5 and above 1.0 s delay, the performance deteriorates. power system damping control design involving a finite amount
Over the range of 0.5 to 1.0 s delay, the controller performs of signal transmission delay.
satisfactorily as shown in Figs. 16 and 17.
To demonstrate the drawback of the conventional design VIII. CONCLUSION
with a delay-free plant, a separate controller was designed for This paper presents a methodology for power system
the SVC without considering any delay at the design stage. The damping control design accounting for delayed arrival of
design was carried out following the LMI-based methodology feedback signals from remote locations. A predictor-based
described in [4], [14]. The controller performed satisfactorily control design strategy is discussed for such a time-delayed
both in time and frequency domain for delays up to 0.1 s. For system. The design procedure based on the USP approach has
larger time delays, the performance of the controller appeared been applied for centralized design of power system damping
to be poor and was even worse with increasing amount of delay. controller through an SVC. A combination of the USP and
Simulations were carried out with this controller considering a the designed controller is found to work satisfactorily under
time delay of 0.75 s. The simulation results following the same different operating scenarios even though the stabilizing signals
disturbance described above are shown in Figs. 18 and 19. could reach the controller site only after a finite time.
It is clear that the system performance deteriorates con- In this paper, a fixed time delay has been considered for all
siderably revealing the fact that if the delay is more than the the communication channels. In practice, this might not always
time-period corresponding to the dominant modes and it is not be the case as the distance of the measurement sites differs. De-
taken into account during the design stage the controller might pending on that, different amount of delays for each signal need
not perform as expected. Therefore, it is necessary to include to be considered during the design. We would like to continue
the delay in the control design formulation itself. The results our research in that direction.
CHAUDHURI et al.: WIDE-AREA MEASUREMENT-BASED STABILIZING CONTROL 1979
APPENDIX I [13] Matlab Users Guide, The Math Works, Inc., Natick, MA, 1998.
[14] B. Chaudhuri, B. Pal, A. C. Zolotas, I. M. Jaimoukha, and T. C. Green,
CONTROLLER STATE-SPACE REPRESENTATION
“Mixed-sensitivity approach to H control of power system oscilla-
The state-space representation of the 2-input, 1-output cen- tions employing multiple facts devices,” IEEE Trans. Power Syst., vol.
18, pp. 1149–1156, Aug. 2003.
tralized controller for the SVC is given in the equation at the [15] P. Kundur, Power System Stability and Control. New York: McGraw-
bottom of the previous page. Hill, 1994.
ACKNOWLEDGMENT
The authors gratefully acknowledge the ideas and sugges-
Balarko Chaudhuri (S’04) received the B.E.E.
tions received from Dr. Q. C. Zhong, Dr. I. M. Jaimoukha, and (Hons.) degree from Jadavpur University, Calcutta,
Dr. T. C. Green during this research. India, and the M.Tech from the Indian Institute
of Technology, Kanpur, India, in 2000 and 2002,
respectively. He is currently pursuing the Ph.D.
REFERENCES degree in the Control and Power Group at Imperial
[1] J. Chow, J. Sanchez-Gasca, H. Ren, and S. Wang, “Power system College London, London, U.K.
damping controller design using multiple input signals,” IEEE Control
Syst. Mag., vol. 20, pp. 82–90, Aug. 2000.
[2] I. Kamwa, R. Grondin, and V. Hebert, “Wide-area measurement based
stabilizing control of large power systems—A decentralizedlhierar-
chical approach,” IEEE Trans. Power Syst., vol. 16, pp. 136–153, Feb.
2001.
[3] G. Heydt, C. Lin, A. Phadke, and V. Vittal, “Solutions for the crisis in
electric power supply,” IEEE Comput. Appl. Power, vol. 14, pp. 22–30, Rajat Majumder (S’04) received the B.E.E. (Hons.)
July 2001. degree from Jadavpur University, Calcutta, India, and
[4] B. Chaudhuri and B. Pal, “Robust damping of multiple swing modes the M.Sc. (Engg.) degree from the Indian Institute
employing global stabilizing signals with a TCSC,” IEEE Trans. Power of Science, Bangalore, India, in 2000 and 2003, re-
Syst., vol. 19, pp. 499–506, Feb. 2004. spectively. He is currently pursuing the Ph.D. degree
[5] Q. C. Zhong, “ H control of dead time systems based on a transforma- in the Control and Power Group at Imperial College
tion,” Automatica, vol. 39, pp. 361–366, Feb. 2003. London, London, U.K.
[6] O. Smith, “Closer control of loops with dead time,” Chem. Eng. Prog.,
vol. 53, no. 5, pp. 217–219, 1957.
[7] , Feedback Control Systems. New York: McGraw-Hill, 1958.
[8] K. Wantanable and M. Ito, “A process-model control for linear systems
with delay,” IEEE Trans. Automat. Contr., vol. AC-26, pp. 1261–1269,
Dec. 1981.
[9] Q.-C. Zhong and G. Weiss. (2003) A onified Smith predictor based on
the spectral decomposition of the plant. Automatica [Online] Available
at http://www.ee.ic.ac.uk/CAP/Reporls/2003.html Bikash C. Pal (M’00–SM’ 03) received the B.E.E.
[10] B. Pal, A. Coonick, and B. Coty, “Robust damping of interarea oscilla- (Hons.) degree from Jadavpur University, Calcutta,
tions in power systems with superconducting magnetic energy storage India, and the M.E. degree from the Indian Institute
devices,” Proc. Inst. Elect. Eng. Generation Transmission and Distribu- of Science, Bangalore, India, in 1990 and 1992, re-
tion, vol. 146, no. 06, pp. 633–639, Nov. 1999. spectively. He received the Ph.D. degree from Impe-
[11] G. Rogers, Power System Oscillations. Norwell, MA: Kluwer, 2000. rial College London, London, U.K., in 1999.
[12] N. Martins and L. Lima, “Determination of suitable locations for He is presently a Lecturer in the Department of
power system stabilizers and static var compensators for damping Electrical and Electronic Engineering, Imperial Col-
electromechanical oscillations in large power systems,” IEEE Trans. lege London. His research interests are in the area of
Power Syst., vol. 5, pp. 1455–1469, Nov. 1990. power system dynamics and FACTS controllers.