Académique Documents
Professionnel Documents
Culture Documents
Abstract –This paper proposes a set of performance factors for (boldface refers to vector quantities, while phase variables
load characterization and revenue metering. They are based on are indicated with subscript “m”). We define:
the Conservative Power Theory, and each of them relates to a
specific load non-ideality (unbalance, reactivity, distortion). The • Unbiased integral of phase voltages
performance factors are capable to characterize the load under û m (t ) = u m ³ (t ) − u m ³ (1)
different operating conditions, considering also the effect of non-
negligible line impedances and supply voltage deterioration. t T
1
where: u m ³ (t ) = u m (τ ) dτ , u m ³ =
³ u (t ) dt
³
I. INTRODUCTION 0
T 0 m³
The advent of smart microgrids, which are characterized • Instantaneous (active) power
by distributed energy sources and pervasive ICT, poses new
requirements for power metering and load characterization. M
r a
r v
I b2 Iu2 λ = λQ λ N λ D (16)
From (10), we may also decompose the apparent power Equation (16) allows a quantitative evaluation of the
in the form: influence of reactive, unbalance and distortion powers in the
A 2 = U 2 I 2 = P 2 + Q 2 + N a2 + N r2 + D 2 (11) power factor, decoupling their effects.
where: If the supply voltages are sinusoidal and symmetrical,
• A Apparent Power the load can be fully characterized by the above
• P = U I ab Active Power performance factors. However, if the supply voltages are
distorted and/or asymmetrical, or the line impedances are
• Q = U I rb Reactive Power; non-negligible, we need to discriminate the influence of the
• Na = U I au Active Unbalance Power source and load effects on the generation of the unwanted
• Nr = U I ru Reactive Unbalance Power power terms (accountability problem).
The following sections discuss load- and supply-side
• D = U Iv Distortion Power
modeling techniques which make possible a simple, even if
Apart from P, all power terms characterize a non-ideal approximated, approach to the accountability problem.
aspect the load performance. The global performance index These techniques are then analyzed by means of different
is the power factor: simulation cases in order to investigate the effectiveness of
P I P the accountability approach and to show the ability of the
λ= = a = (12)
A I P + Q + N 2 + N 2 + D2
2 2 above performance factors to characterize the load, also in
a r
view of a possible application to revenue metering.
which can be calculated for every circuit independently of
waveform distortion and asymmetry, and is affected not IV. LOAD MODELING
only by load unbalance and non-linearity, but also by supply The load modeling approach was fully analyzed in [12]
asymmetry and distortion. The separation of supply and and, for the sake of brevity, is reported here only for three-
load responsibility on the power factor reduction is the goal phase four-wire loads, whose single-phase equivalent circuit
of the following accountability approach. is shown in Fig.1.
di
e = u + RS i + LS (20)
dt
where, due to supply line symmetry, parameters RS and LS
are the same in all phases. Note that, due to the linearity of
(20), it can be applied separately to the fundamental
positive-sequence voltage and current terms ( e p , i p ) and
the remaining terms ( e n , i n ). Considering that e n represent
Fig. 1. Equivalent circuit for three-phase four-wire loads.
the unwanted terms of the source voltages, which ideally
should be purely fundamental positive-sequence quantities,
We assume that the measuring equipment at the load
RS and LS can be selected so as to minimize terms e n . In
terminals senses the line-to-neutral voltages u m and line
this way, the equivalent circuit of Fig. 2 gives a
currents im and is capable to discriminate their fundamental conservative representation of the voltage supply, in the
( u mf , imf ) and harmonic ( u mh , imh ) components. sense that it minimizes the impact of supply asymmetry and
distortion on the voltage measured at PCC. In order to
The parameters Rm and Lm of the equivalent circuit are ensure source impedance identification, we will assume that
computed to suit the circuit performance at the fundamental line voltage and current at PCC have non-negligible
frequency, thus: distortion or unbalanced components. According to this
uf uˆ f approach, RS and LS are chosen to minimize the function:
imf = m + m (17) M
R m Lm 2
ϕ = en = ¦ emn , emn (21.a)
Their values are easily derived by observing that: m =1
U f2 U f2 where e n is the vector of the unwanted components of the
Pmf = u mf , imf = m Rm = mf (18.a)
Rm Pm supply voltages, and includes all terms related to asymmetry
and distortion. Function ϕ can be expressed as:
Uˆ mf 2 Uˆ mf 2
Wmf = uˆ mf , imf = Lm = (18.b) 2
Rm Wmf 2 2 din
ϕ= u n
+ RS2 i n
+ L2S +
Finally, the current source j m is defined by difference: dt
(21.b)
u u din
j m = im − mf − mf (19.a) + 2 RS u , i n n
+ 2 LS n
u , LS
Rm Lm dt
From the above definitions, we see that j m only includes Minimization of ϕ gives:
harmonic terms. In fact, substituting (17) in (19.a), we get: ∂ϕ 2
= 0 RS = − u n , i n in (22.a)
uh u h ∂ RS
j m = imh − mf − mf (19.b)
Rm Lm 2
∂ϕ din din
For the validity of the model we should assume that the = 0 LS = − u n , (22.b)
∂ LS dt dt
equivalent circuit parameters remain the same within
reasonable variations of the voltage supply, both in terms of Obviously, only positive solutions are acceptable for RS
asymmetry and distortion. This is only approximately true and LS. In case of negative solution, the corresponding
in real networks, but it makes possible an accountability parameter is set to zero. Given RS and LS, we may compute:
approach based on measurement at the load terminals, di p
without requiring a precise knowledge of the load itself. e p = u p + R S i p + LS (23)
dt
V. SUPPLY MODELING which estimates the positive-sequence supply voltages to be
included in the equivalent circuit of Fig. 2.
Fig. 2 shows the single-phase equivalent circuit of the Note that ep, up, ip, are the fundamental positive sequence
voltage supply, which includes voltage source em , line components of the related voltages and currents, while, en,
resistance RS and line inductance LS. Considering three- un, in are calculated by difference to the original voltages
phase quantities we can write: and currents.
VI. ACCOUNTABILITY
From the above relations we may estimate the load and
supply contribution to the various power terms. Thus,
considering that the line impedance is much lower than the
load impedance and using the superposition principle, we
proceed as follows:
Fig. 2. Source equivalent circuit – per phase.
1) Based on the procedure of section IV, from the voltages
and currents measured at PCC we estimate the phase
parameters Rm and Lm and the current source jm of the
equivalent circuit of Fig.1.
2) Based on the procedure of section V, from the voltages
and currents measured at PCC we may estimate the Fig. 5. Equivalent circuit for the unwanted PCC voltage calculus.
supply line parameters RS and LS and the fundamental
positive-sequence supply voltages e p . VII. APPLICATION EXAMPLES
3) Applying now supply voltages e p at the input terminals In order to investigate the load characterization and
of the equivalent circuit of Fig. 2, and considering the revenue metering approach, two different load circuits were
equivalent circuit of Fig. 1, we may determine the simulated, as indicated in Fig. 6 and Fig. 7.
fundamental phase currents i Af absorbed by the load Table I shows the different supply conditions considered
under these supply conditions (Fig. 3) and the for the analysis. The line impedance (ZL) is the same for all
phases (R = 10.9m, L = 38.5H) and corresponds to a
corresponding fundamental phase voltages uAf
voltage drop about 4% at rated load power.
appearing at the PCC terminals (Fig. 4). Currents i Af
and voltages uAf may result asymmetrical due to load
unbalance. This non-ideality must obviously be
ascribed to the load, since the voltage supply and
distribution lines are symmetrical.
4) Finally, applying the harmonic current sources j acting
in the various load phases we determine the harmonic
voltages uAh and currents i Ah occurring at PCC, which
are also accountable to the load. Since the line Fig. 6. Unbalanced linear load.
impedances are much lower that load impedances, we
may express these quantities in the approximate form
(see Fig. 5):
i Ah ≅ j (24.a)
d j
uAh ≅ − RS j − LS (24.b)
dt
5) Let’s now compute the load voltages and currents at
PCC, which are accountable to the load:
uA = uAf + uAh (25.a)
Fig. 7. Unbalanced non-linear load.
i A = i Af + i Ah (25.b)
6) From the definitions of Sect II and III, we may easily TABLE I. Voltage Source Conditions for Cases 1 and 2.
compute all power terms accountable to the load and Case 1 Case 2
the corresponding performance factors. ݁ଵ ൌ ͳʹͲ Vrms ݁ଵ ൌ ݁ݏܽܥሺܫሻ σ ܪଵ Vrms
f
ilm ݁ଶ ൌ ͳʹ െ ͳʹͲ Vrms ݁ଶ ൌ ݁ݏܽܥሺܫሻ σ ܪଶ Vrms
݁ଷ ൌ ͳʹͳʹͲ Vrms ݁ଷ ൌ ݁ݏܽܥሺܫሻ σ ܪଷ Vrms
iRm iLm
+
emp Rm Lm In Case 2, the terms called ΣH represent the harmonic
_ contents of the phase voltages. Each phase voltage includes
2% of 3rd harmonic, 2% of 5th harmonic. The phase angle of
Fig. 3. Equivalent circuit for the fundamental load current calculus. each harmonic term is the phase angle of the fundamental
voltage (as in Case 1) multiplied by the harmonic order.
ia ib ic
B. Unbalanced Non Linear Load
400
ia ib ic -200
400
ia ib ic
200
500
0
-200 0
-400
-500
0.45 0.46 0.47 0.48 0.49 0.5
Tim e (s)
0.45 0.46 0.47 0.48 0.49 0.5
Tim e (s)
Fig. 9. PCC voltages and currents - Case A.2.
Fig. 10. PCC voltages and currents - Case B.1.
This simple comparison could justify the need of Under the assumption of unbalanced or distorted
additional information in terms of revenue metering in conditions, the proposed approach allows the separation of
modern power grids and the authors believe that the load and supply responsibility for the generation of active,
proposed performance factors would bring important reactive, unbalance and distortion power. Such approach is
information. essentially founded on a load and supply modeling by
means of the PCC voltage and current measurements.
2) Case B.2 – Non sinusoidal source voltages Moreover, a set of performance factors has also been
Figure 11 depicts the three-phase voltages and currents proposed to characterize the load in terms of imbalance,
in case of unbalanced non linear load fed by non sinusoidal reactivity and distortion .
voltages. In terms of revenue metering, the comparison among the
power terms measured at PCC and those accounted to the
In this case, it would be interesting to compare the load shows the effect of the line impedance and calls for
power terms and performance factors to Case B.1. Note that additional analyses to properly face the case of weak grids,
in such case, the active power is lower than in case of where the line impedance can affect dramatically the power
sinusoidal voltages. On the other hand, the power factor is measurement. In any case, the CPT definitions and the
increased. This would reflect the ability of the proposed proposed performance factors give a way to characterize the
methodology to estimate the interactions between source loads and to approach the accountability problem in the
voltage deterioration and voltage drop distortion caused by generality of distribution grids.
the non linear load behavior.
ua ub uc
REFERENCES
200
[1] A. Ferrero, L. Peretto and R. Sasdelli, "Revenue metering in the
100 presence of distortion and unbalance: myths and reality", in Proc.
0
1998 IEEE International Conference on Harmonics and Quality of
Power, pp. 42-47.
-100
[2] D.P. Manjure and E.B. Makram, “Effect of Nonlinearity and
-200 Unbalance on Power Factor,” in Proc. 2000 IEEE Power Engineering
Society Summer Meeting, pp. 956-962.
ia ib ic
[3] J. L. Willems, “Reflections on Power Theories for Poly-Phase
500
Nonsinusoidal Voltages and Currents”, Przegld Elektrotechniczny
no. 6, pp. 11-21, 2010.
0 [4] M. Depenbrock, “The FBD-Method, a Generally Applicable Tool for
Analyzing Power Relations”, IEEE Trans. on Power Systems, vol. 8,
-500
no 2, pp. 381-387, May 1993.
[5] L. Cristaldi, A. Ferrero, “Mathematical foundations of the
0.45 0.46 0.47 0.48 0.49 0.5 instantaneous power concept: an algebraic approach”, European
Tim e (s) Trans. on Electrical Power, vol. 6, no. 5, pp. 305-309, Sept./Oct.
Fig. 11. PCC voltages and currents - Case B.2. 1996.
[6] L. S. Czarnecki, “Currents’ Physical Components (CPC) Concept: a
Fundamental of Power Theory”, Przegld Elektrotechniczny no. 6,
TABLE III. Power terms measured at PCC and accountable to the load pp. 28-37, 2008.
(unbalanced non linear load).
[7] P. Tenti, P. Mattavelli, H. K. Morales P, “Conservative Power
Case B.1 Case B.2 Theory, Sequence Components and Accountability in Smart Grids”
PCC Load PCC Load Przeglad Elektrotechniczny, Vol. 6, pp. 30-37, 2010.
A [KVA] 93.267 94.007 89.494 91.207 [8] P. Tenti, H. K. Morales P, P. Mattavelli, “Conservative Power
P [KW] 63.909 63.334 62.738 62.763 Theory, a Framework to Approach Control and Accountability Issues
in Smart Microgrids”, IEEE Trans. on Power Electronics, vol. 26, no
Q [KVA] 33.274 35.376 33.599 36.159
3, pp. 664 - 673, March 2011.
N [KVA] 20.873 21.143 20.619 21.296
[9] A. Pavas, V. Staudt, H. Torres-Sánchez, “Discussion on existing
D [KVA] 55.421 55.916 50.190 51.171 methodologies for the resposabilities assigment problem”,
λ 0.6852 0.6737 0.7010 0.6881 International School on Nonsinusoidal Currents andCompensation.
λQ 0.8870 0.8730 0.8815 0.8665 Lagow, Poland, June 2008.
λN 0.9605 0.9601 0.9605 0.9594 [10] P. Tenti, H. K. M. Paredes, F. P. Marafao, P. Mattavelli,
“Accountability and Revenue Metering in Smart Micro-Grids”
λD 0.8043 0.8039 0.8279 0.8278 International Workshop of Applied Measurements for Power Systems
(AMPS), Sept 22-24, 2010, Achen.
[11] S. Fryze, “Wirk-, Blind-,Scheinleistung in Elektrische Stromkreisen
VIII. CONCLUSIONS mit nichtsinusformingen Verlauf von Strom und Spannung”, ETZ,
Bd. 53, pp. 596-599, 625-627, 700-702, 1932.
In this paper the Conservative Power Theory (CPT) is [12] P. Tenti, H. K. M. Paredes, F. P. Marafao, P. Mattavelli,
applied to the problem of load characterization and revenue “Accountability in Smart Microgrids Based on Conservative Power
metering. Theory”, IEEE Trans. on Instrumentation and Measurement, vol. 60,
no 9, pp. 3058 - 3069, September 2011.