Instep
Standby Diesel Generator Set
Objectives
1. State the purpose/main function of standby generator installation.
2. State, explain and identify the standby generator set assembly.
3. State, explain and identify the main component of AC Generator.
4. Describe the operation of Brushless Generator type.
5. Describe the metering, protection and control system.
6. State and explain the controlled parameters of Standby generator
installation.
7. Read and interpret layout drawing/diagram of Standby generator
installation.
8. Perform pre-start up inspection on Standby generator installation.
9. Perform Standby generator startup and shutdown according to
standard procedure.
Instep
Standby Diesel Generator Set
Coverage
Function
to deliver power automatically to essential and vital
switchboards in the event of power failure in order to powered
the critical equipment such as UPS systems, Plant shutdown
system, DCS, instrumentation,main motors, DC battery chargers
and emergency lighting.
Power Flow
Neutral Switch
/SYNCHRONIZING
Generator/
Synchronizing
Lightning
Arrestor
Lightning
Arrestor Switch Board
Main Switch
Board
AMF BOARD
AMF Board
Instep
- Overhead System
- Street Lighting
Sub Switch
Board Lightning
Arrestor
Essential Switch
Board Vital Switch
- Overhead System
Board VITAL SWITCH BOARD
- Street Lighting
Lightning
Arrestor - DCS
- Fire and Gas Detection System
Standby Diesel Generator Set
Assembly
AC Generator
Instep
Function
Principle
"Whenever a conductor or coil cuts a magnetic field or
vise-versa, an induced current will flow in a conductor or an
induced voltage will exist across the conductor"
Instep
AC Generator (Basic)
N
S Rotor
Rotation
N
S Frame of Yoke
Instep
Field Winding
AC Generator (Basic)
Requirements
1 Magnetic Fluxes
- produce by a copper conductors known as Field winding
when receives a DC supply from exciter.
2 Conductor or Coil
- a copper conductors known as Armature winding, carry
induced current when cutting process occurs.
3 Cutting Process
- is a process where a conductor cuts the magnetic field or a
magnetic field cuts the conductor which results and induce
current flow in the conductor.
Instep
AC Generator (Basic)
Performance
pN
f = in Hertz ( Hz )
120
f generator speed
Instep
AC Generator (Basic)
Performance
3. Generator Speed ( N )
120f
N = in Hertz ( Hz )
p
Output Wattage
h = x 100
Input Wattage
KVA h h
Mechanical Energy Input
(Engine Power)
KWinput
h h
KWout
Instep
AC Exciter
Rotating Rectifier
Main Generator
Brushless AC Generator
Inter-connector
Pole Shoe
Field Winding
Instep
Rotor Body
Permanent Magnet
Instep
AC Exciter Armature
Brushless AC Generator
Parts and Function
4 Automatic Voltage Regulator (AVR)
to control and regulate DC excitting current to the Exciter Field
consist of Rectifier circuit, Voltage regulator/adjuster/comparator
and Amplifier
Ac Exciter
Rotating rectifier
Armature
Ac Exciter Main
Field Generator
winding
Instep
AVR
Main Generator
Field
Brushless AC Generator
Parts and Function
5 Rotating Rectifier
a three-phase full-wave bridge, having six diode elements, mounted
on a rotating steel plate, located at the exciter end for easy
inspection, testing and replacement.
output of ac exciter is rectified and converted to DC excitation
voltage here for main generator field excitation.
Instep
Brushless AC Generator
Generator Excitation
Instep
Self excited,Brushless
Rotating coil stationary field
Three phase generator
Brushless AC Generator
Generator Excitation
Instep
Brushless AC Generator
Generator Excitation (with Pilot Exciter)
Instep
Self excited,Brushless
Rotating coil stationary field
Three phase generator
Brushless AC Generator
Generator Excitation (with Pilot Exciter)
Shaft Axis
Main Stator
Exciter
Stator Output
Permanent Magnet
Stator Terminals
AVR
Instep
Local Control Panel
Function
F F
G G
H I
K Q P P K Q L O
M N N M
A - Generator Metering Panel G - Circuit Breaker Control Panel M - Neutral Contactor Panel
D - Synchronizing Metering Panel J - Power Factor Correction Panel P - Battery Charger Panel
Protection System
Busbar
PM G
Metering System
Control System
Instep
Generator Board
1. Metering System
to monitor system performance
line voltage, line current,
power factor,reactive power , true power ,
frequency and
power consumption rate.
Electronic
Processor
Actuator
Input from manual and
Speed Trimmer
Amplifier Fuel Control Valve
Magnetic Pickup
Engine Generator
Instep
Engine Flywheel
Fuel line
Generator Board
2. Protection System
protects the generator against system problems/faults
overload, loss of load, unbalanced loading,
under/over frequency and under/over voltage,
Insulation failure,
mechanical failure,
excitation system failure
reverse power
Instep
Generator Board
2. Protection System Connection
Instep
Generator Board
2. Protection System (Alarm & Shutoff)
DC CONTROL SWITCH
occurring. FC-4
FSR-1 EFR-1
AFR-4
FC
shutdown
FST-1
FSR
EFR-2
EF-1
EFR
OC-1
OCR
RPR-1
Instep
RPTR
LOP-2 Alt-Relay No Contact
OPT-1
LOP ive
HWT-2
HWT
OSR-2
OSR
Charger and Battery Bank
Function
provide a DC supply to Starter Motor for engine cranking.
Static Charger
Instep
Battery Bank
Fuel Storage
Function (Bulk Storage)
intake line
Instep
Auto Main Failure Board (AMF)
Function
provide permissive to start signal to the generator set via
undervoltage relay
to do 'supply to the load' switching either from mains or from
generator.
connect/disconnect the generator to/from the essential/vital
switchboard. From Generator
From Board
MSB
Instep
Gen.1 Gen.2
AVR AVR
Mover Mover
Main Healthy
Rotary Battery Gen.1 Static Gen.1 Static Battery Rotary
Charger Bank Charger Charger Bank Charger
MUVR@AMF
AT
AT-1
AUTO SCR-1 AFR-2
SDT
FST
TEST AFR-4 AST-1
SR-3
ST
ST-1 SYNCHRONIZING
SR-4 MODE
SELECTOR SWITCH
START P/B S7
MASTER
MANUAL MASTER
START P/B
AUTO STOP P/B
MAN OFF
AFR-3 MSR
SR MSR-1
SR-4
AST MUVR-1
FSM-4 SDT-1 ASR
FSM
FC-4 AFR-4 GENSET
START_UP
OPT
SELECTOR
SWITCH
FSR-1 EFR-1 OCR-1 RPTR-1 LOP-1 HWT-1 OSR-1
S9
FC MSR
GEN.1OFF
GEN.2
ACR ASR
ACR-1
GR1a CON2
FC-2 ACR-2
AR GR2a CON1
FSR SNC1
EFR-2
SCR2
EF-1
GR1b
EFR
OCR-2 GR1a
OC-1 GR2a
OCR
GR2b
Instep
RPTR-2 GR1a
RPR-1
RPTR GR2a
OPT-1 OPT1
RR RY RY
ive
LOP
DBT1
HWT-2 OPT2
AR1
DBT2
HWT AR2
OSR-2
OSR
Standby Diesel Generator Set
Manual Start-up Procedure
C) Before operating the panel, ensure all breakers and switches are
in OFF position.
Instep
Standby Diesel Generator Set
Manual Start-up Procedure
D) Follow the procedure and refer to attach DC Control single line drawing.
Put DC Control switch to ON position and DC Selector Switch to manual
position .
Release the Emergency Stop button.
Press START button .................. Prime Mover will start.
Monitor generator metering panel.
- Adjust voltage and frequency using voltage trimmer and
speed trimmer to a required Value ( V= 415V, f= 50 Hz ).
Put a circuit breaker switch to manual mode.
Release circuit breaker Emergency Trip button.
ON Neutral Contactor or Close Neutral Knife Switch.
Press circuit breaker ON Push Button...........Circuit breaker will close.
Instep
Standby Diesel Generator Set
Manual Shutdown Procedure
E) Follow the procedure and refer to attach DC Control single line drawing.
Open generator circuit breaker by pressing 'OFF' push button
Press generator circuit breaker Emergency Trip Push Button to disable
closing of the circuit breaker electrically
Switch 'OFF' generator Neutral Contactor Switch of 'Open' Neutral Knife
switch
Turn the generator circuit breaker Mode Switch to 'OFF'
Press 'Emergency Stop' push button to disable starting the generator
prime mover electrically
Turn Duty Selector Switch to 'OFF'
Turn DC Control Switch to 'OFF'
Instep