_______:‫الفصل‬ ____________________________________________:‫االسم‬

Q1: Figure 1 show three core current transformer with 100/5 turns ratio on the same bar, cores 1&2 are
ideal , for the primary current of 1000 A.

Choose the correct answer:

A. If CT1 not saturated, the RMS value of secondary current Is1=…..A


( 50 A – less than 50 A – Zero –more than 50 A) CT1 CT2 CT3
B. If CT2 saturated, the RMS value of secondary current Is2=…..A
( 50 A – less than 50 A– Zero – more than 50 A)
C. If CT3 shorted, the RMS value of secondary current Is3=…..A
( 50 A – less than 50 A– Zero – more than 50 A)
Figure 1

Q2: Consider a current transformer with a turn’s ratio of 500: 5, and class designation is
10C400. For a resistive burden of 2.0 Ω and magnetizing impedance angle of 90°. If the primary
current is 1000 A. Calculate
a- The secondary current b- CT Ratio Error (Ɛ) c- Ratio Correction Factor (RCF)

Q3: Two ideal CTs with turn’s ratios of 300:5 and 600:5 are connected as shown in Figure 2 (a)
and (b). If the primary current is 3000 A and the burden is 1 Ω.

1-What are the value of burden voltage for two


cases?

2-Suggest a solution to obtain Zero burden


voltage?, and calculate the value of burden
seen by the each CT?

Solve Q3 on the other side of paper


side