Vous êtes sur la page 1sur 11

Downloaded from http://iranpaper.

ir
http://www.itrans24.com/landing1.html

1236 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 3, JUNE 2018

Setting Zero-Sequence Compensation Factor in


Distance Relays Protecting Distribution Systems
Aristotelis M. Tsimtsios , Student Member, IEEE and Vassilis C. Nikolaidis , Member, IEEE

Abstract—Reliable protection of modern distribution systems is [3], even as a solution for the coordination of protection means
challenging due to various technical difficulties, mainly related to in multi-recloser schemes [4].
the need for more efficient use of existing networks (e.g., shorter
Major issue for the proper application of distance protection
interruption durations and fewer affected customers, integration
of distributed generation, meshed network operation, etc.). Such in distribution systems with intermediate sources (DG) is the
challenges require, among others, the reconsideration of conven- infeed effect [2]. The latter is explicitly analysed in [5] and
tional protection techniques. A potential solution under examina- the performance of the distance relay is tested by using real-
tion concerns the adoption of distance protection for distribution world event report data. In [6], a multi-zone distance protection
feeders, due to its advantages compared to overcurrent protection. scheme for radial distribution systems with DG is presented,
However, as distance relays are mainly designed for transmission
networks, there are several issues to deal with in distribution ap- taking into account the infeed effect as well as the coordination
plications, such as the proper setting of the zero-sequence compen- of the distance relay with other protection means in the system.
sation factor (K0 ). The latter issue is critical in order to guarantee The application of distance protection to a distribution system
correct relay operation during single-line ground faults. This pa- with DG is examined in [7] but since, in this work, DG is always
per examines the effect of K0 on the operation accuracy of distance connected to the substation bus, coordination issues are not ac-
relays protecting inhomogeneous distribution feeders. Theoretical
analysis, as well as investigation of various influencing factors, re- tually dealt with. In [8], the authors investigate the replacement
sult in the determination of a pattern, which relates relay accuracy of overcurrent relays with distance relays in an actual distri-
to K0 . Based on this analysis, a simple methodology for setting K0 bution network with DG and study the infeed/outfeed effect
properly is proposed, which is implementable with commercially as well as the load variation effect on the performance of the
available relays. The methodology is applied on a test distribution
distance relays. Coordination between the line distance relays
feeder and meaningful conclusions are derived.
and distance relays used at the DG units (instead of common
Index Terms—Distance protection, distribution systems, relay undervoltage elements) to enhance fault-ride-through capabil-
accuracy, zero-sequence compensation factor. ity, is further checked. Distance protection is also considered in
microgrid applications [9], [10].
I. INTRODUCTION A significant issue that requires thorough investigation is the
proper setting of zero-sequence compensation factor (K0 ) so
ODERN distribution systems have to operate reliably
M into a challenging technical, economic, and regulatory
framework. Among other technical issues that need to be re-
that a distance relay installed in a distribution feeder can protect
against single-line-ground (SLG) faults efficiently. Although
this issue is important for transmission [11] and subtransmis-
solved in this context, protection philosophy should also be re- sion [12] systems as well, it is less challenging there, due to
considered in a way to obtain greater controllability and enhance the line homogeneity at high voltage levels, despite the fact
efficiency, reliability, and quality of service [1] in distribution that mutual coupling could make it quite demanding [13]. On
systems. Under such a demanding protection environment, the the contrary, in distribution systems, proper K0 setting could
application of non-conventional, highly-reliable protection con- be much more complicated due to the inhomogeneity of distri-
cepts in distribution systems is investigated. bution lines as for their impedance data. In [14], an optimized
A solution being considered concerns the application of dis- value of K0 is extracted for distance relays protecting distri-
tance relays to distribution systems. Inherent directionality and bution systems, through an optimization algorithm, achieving
independency from external system conditions [2] make dis- discrimination between different distance relays. However, dis-
tance protection an attractive option for distribution networks crimination between the zones of each individual distance relay
is not always achieved.
Manuscript received April 11, 2017; revised August 26, 2017; accepted Oc- As a further step by the authors in the examination of applying
tober 7, 2017. Date of publication October 12, 2017; date of current version distance protection to distribution systems, this paper analyses
April 6, 2018. Paper no. TPWRD-00530-2017. (Corresponding author: V. C.
Nikolaidis.) the effect of K0 on the operation of distance relays protect-
The authors are with the Department of Electrical and Computer Engineering, ing inhomogeneous radial feeders without DG and proposes a
Democritus University of Thrace, Xanthi 67100, Greece (e-mail: atsimtsi@ methodology for setting K0 properly in order to achieve effi-
ee.duth.gr; vnikolai@ee.duth.gr).
Color versions of one or more of the figures in this paper are available online cient protection against SLG faults. The proposed methodology
at http://ieeexplore.ieee.org. can also be used for setting K0 properly when DG is connected
Digital Object Identifier 10.1109/TPWRD.2017.2762465 to the feeder, as part of a preliminary attempt to deal with the

0885-8977 © 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

TSIMTSIOS AND NIKOLAIDIS: SETTING ZERO-SEQUENCE COMPENSATION FACTOR IN DISTANCE RELAYS 1237

infeed effect. This methodology is applicable using commer- TABLE I


K 0 VALUES CORRESPONDING TO SEVERAL ACSR NOMINAL CROSS-SECTIONS
cially available distance relays, without any need for interven-
tion in the relay logic.
The organization of this paper is as follows. Section II in- Nominal cross-section (mm2 ) Z 1 (Ω/km) Z 0 (Ω/km) K0
cludes a brief theoretical description of the basic K0 factor 95 0.215 + 0.334 j 0.363 + 1.556 j 1.030∠26o
aspects. In Section III, theoretical analysis of the effect that K0 50 0.404 + 0.386 j 0.552 + 1.584 j 0.720∠39o
has on the distance relay operation is performed, whereas the 35 0.576 + 0.397 j 0.724 + 1.595 j 0.580∠48o
16 1.268 + 0.422 j 1.416 + 1.620 j 0.300∠65o
findings are verified through simulations in a test distribution
feeder. In Section IV, a specific pattern, describing the effect
of K0 on the relay operation, is determined. Based on this, a
proper K0 setting methodology is presented and applied to a
test feeder without DG units. An extension of this methodology
to deal with the infeed effect if DG units are connected to the
feeder is also presented in this section. The conclusions of this
work are drawn in Section V.

II. ZERO-SEQUENCE COMPENSATION FACTOR (K0)


Distance relays are designed to determine the positive- se-
quence impedance up to the fault position, by measuring the
voltages and currents at the relay location [2]. Therefore, the
reach setting of each phase and ground zone of a distance relay
is set based solely on the positive-sequence impedance between
the relay and the endpoint of the line segment to protect. In
case of phase faults, the aforementioned setting is adequate for
the relay to locate the fault accurately, as the phase distance
element calculates the actual positive-sequence impedance up
to the fault position. However, in case of SLG faults, this reach Fig. 1. Distance relay protecting a line consisting of different segments.
setting cannot guarantee correct operation of the distance relay,
as the impedance calculated by the ground distance element is
not equal to the positive-sequence impedance up to the fault
III. EFFECT OF K0 ON THE RELAY ACCURACY
position due to the zero-sequence current effect. In order for the
ground element to operate correctly, the zero-sequence current A. Theoretical Analysis
is compensated by the zero-sequence compensation factor (K0 ), In case of a distance relay protecting a line or a line segment,
which stands for a complex value included in the relay settings. which is homogenous in terms of conductor type and cross-
K0 factor is mainly expressed as: section, setting K0 is simple, as only the Z1 and Z0 values of
K0 = (Z0 − Z1)/(KZ1) (1) the line to protect are needed. It is worth mentioning that, in this
case, the proper K0 factor is independent of the line length, as
where Z1 and Z0 stand for the actual positive- and zero-sequence according to the definitions of the previous section, only the p.u.
line impedance from the relay location up to the fault position values of Z1 and Z0 are needed for its calculation. If, however,
respectively, whereas K can be equal to 1 or 3, depending on the the protected line consists of segments with different Z1 and Z0
relay design [15]. values, the determination of K0 factor for efficient protection
Alternatively, for several relays, K0 is expressed as the com- against SLG faults is rather complicated. In other words, the
plex ratio of Z0 to Z1 [16]. K0 can also be expressed by being impedance calculated by a ground distance element in case of a
split into a real and an imaginary part giving a reactive and a SLG fault is inaccurate if K0 is incompatible with the protected
resistive zero-sequence compensation factor [16]. inhomogeneous line.
It is clear that each K0 value refers to a specific line type, The latter can be shown with the help of Fig. 1, which depicts
having specific characteristics, as each line type corresponds to a radial overhead line with laterals as well as its representa-
unique values for Z1 and Z0 . Table I presents all the ACSR tion on the complex impedance plane. The main trunk con-
conductor nominal cross-sections used in the Greek distribution sists of segments (LA1 , LA2 , . . . , LAn ) of the same length, con-
system, the corresponding per unit (p.u.) Z1 and Z0 values, as ductor type and nominal cross-section, which are represented
well as the corresponding K0 factor, calculated using (1) for on the R-X plane by the positive-sequence impedance vectors
K = 3. It is apparent that, as the conductor nominal cross- ZA1 , ZA2 , . . . , ZAn respectively. For all the line laterals, the
section decreases, K0 decreases in magnitude and increases in same conductor is considered which is of the same length but
angle. This behaviour of K0 , shown above for ACSR conduc- smaller nominal cross-section compared to the conductor of the
tors, is generic and holds for all common conductor types used main trunk segments. Laterals LB1 , LB2 , . . . , LBn are repre-
in overhead distribution systems. sented on the R-X plane by the positive-sequence impedance
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

1238 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 3, JUNE 2018

vectors ZB1 , ZB2 , . . . , ZBn respectively. Because of the smaller position SC1 (i.e., the non-compensated calculated impedance
cross-sections, ZB vectors have a greater magnitude and smaller for sub-segment LB1 ). We assume that, in (4), K0 has been set
angle compared to ZA vectors. The whole line is protected by according to the impedance data of segment LA1 , i.e., the re-
a distance relay (namely DR) installed at the head of segment lay can operate accurately only for SLG faults occurring in this
LA1 , i.e., at the departure of the feeder. Only one ground dis- segment (and the rest of the main trunk).
tance zone is shown in Fig. 1, which is set to reach up to the The right part of (4) is the sum of two terms. The first term
endpoint of lateral LB1 , covering also a part of lateral LB2 . It is ZA 1n c /(1 + K0 ), where the calculated impedance for seg-
is assumed that the time delay of this zone is set, so that the ment LA1 is “corrected” by being multiplied by 1/(1 + K0 ),
distance relay coordinates properly with the protection means with K0 being compatible with the impedance data of this seg-
(e.g., main fuses fB1 and fB2 ) of laterals LB1 and LB2 . ment. The second term is ZB 1 nc/(1 + K0 ), where the calcu-
Let us focus on the two segments LA1 and LB1 . If K0 is lated impedance for sub-segment LB1 is intended to be “cor-
set according to the positive- and zero-sequence impedance of rected” based on a K0 value, which is incompatible with the
segment LA1 , then, for a SLG fault anywhere in this segment, impedance data of LB1 . Hence, it would be reasonable to say
the ground distance element will calculate the positive-sequence that ZB 1 nc/(1 + K0 ) is the term that affects the impedance
impedance up to the fault position accurately. Nevertheless, in calculation accuracy of the ground distance element and, subse-
case of a SLG fault occurring anywhere in segment LB1 (e.g., at quently, the fault distance calculation accuracy. That means that
point SC1 ’ in Fig. 1), the aforementioned K0 setting will result the inaccuracy rate of the ground distance element is propor-
in an inaccurate ground distance calculation and consequently, tional to the magnitude of ZB 1 nc. Since the impedance mag-
in an inaccurate fault location. It should be noted that this prob- nitude of a line is proportional to its length, we could say that
lem cannot be solved if K0 is set based on the impedance data the inaccuracy rate of a ground distance element increases as
of segment LB1 , as segment LA1 interposes between the relay the length of the protected segment, whose impedance data are
location and segment LB1 . The latter K0 setting would be proper incompatible to the K0 setting, increases.
only if the relay was installed at the beginning of segment LB1 The above conclusions can be further clarified with a more
(i.e., protecting only this segment). In order to achieve accurate detailed analysis using Fig. 1. We examine now three fault cases,
impedance calculation for a SLG fault at point SC1 , K0 should in which SLG faults occur in the main trunk and in the first lateral
be set according to the impedance data of the fictitious segment LB1 , at the same distance from the relay location. In particular,
LC1 , whose positive-sequence impedance is represented by the the following fault cases are examined:
vector ZC1 on the R-X plane of Fig. 1. However, in this case, 1) Faults SC1 and SC1 , at distance d1 from the relay location.
the relay will locate the fault accurately only if the fault occurs 2) Faults SC2 and SC2 , at distance d2 from the relay location.
exactly at point SC1 , whereas the problem will remain unsolved 3) Faults SC3 and SC3 , at distance d3 from the relay location.
for the rest of the line. where d1 < d2 < d3 . Note that all SLG faults (six in total)
It can be derived that, when a distance relay protects a line shown in Fig. 1 with their actual fault position (symbol SC) are
consisting of segments with different impedance data, it is not independent of each other and do not occur at the same time.
possible to determine a single value for K0 which results in ac- Due to the differences in the conductor cross-sections, the
curate fault distance calculation for all the possible SLG fault sit- impedance vector (dashed lines) up to the fault position for a
uations in the protected line. This phenomenon can be analysed fault in the lateral is of greater magnitude and smaller angle com-
based on the general expression of the impedance calculated by pared to the corresponding vector for a fault in the main trunk,
the relay in case of a phase-a SLG fault [2]: at the same distance from the relay location. Furthermore, it is
apparent that as the distance from the relay location increases,
Za = V a/[Ia(1 + K0 )] (2)
the divergence of the impedance vector for a lateral fault, from
where Va and Ia are the phase-a voltage and current measured the corresponding vector for a fault in the main trunk, increases.
by the relay respectively. Assuming that K0 is set according to the impedance data of the
We could express (2) as: main trunk, then, as the lateral conductor length up to the fault
position increases, the compatibility of K0 decreases, so does
Za = Znc/(1 + K0 ) (3)
the relay accuracy. This can be related to the previous interpre-
where Zn c stands for the non-compensated impedance, namely tation of (4). In general, one could say that the inaccuracy rate
the calculated impedance up to the fault position without the of a ground distance element is proportional to the percentage
consideration of K0 , which would lead the relay to an inaccurate of the total conductor length up to the fault position that corre-
fault distance calculation. sponds to different impedance data compared to the impedance
Considering again the example of Fig. 1 and based on (3), data based on which K0 is set.
the impedance calculated by the relay for a phase-a SLG fault
at point SC1 of segment LB1 will be:
B. Simulation Results
Za = [ZA1nc/(1 + K0 )] + [ZB1 nc/(1 + K0 )] (4)
The previous analysis is performed for the radial 20 kV,
where ZA 1n c is the non-compensated impedance from the re- 50 Hz, overhead distribution line, shown in Fig. 2, which
lay location to the endpoint of LA1 and ZB 1 nc is the non- is based on typical data of the Greek distribution system,
compensated impedance from the endpoint of LA1 to the fault as received by the Hellenic Electricity Distribution Network
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

TSIMTSIOS AND NIKOLAIDIS: SETTING ZERO-SEQUENCE COMPENSATION FACTOR IN DISTANCE RELAYS 1239

Fig. 2. Test distribution feeder.

Fig. 4. Variation of the relay accuracy with regard to the K 0 value.

TABLE II
CALCULATED IMPEDANCE FOR EACH FAULT LOCATION POINT

Fault location point Impedance Z (Ω Reactance X (Ω Resistance R (Ω


primary) primary) primary)

C1 2.979∠57.12o 2.502 1.617


C2 2.220∠54.00o 1.796 1.305
Fig. 3. Variation of the relay accuracy with regard to the actual fault position. C3 4.487∠63.45o 4.014 2.006
C4 3.145∠47.11o 2.304 2.141
C5 2.915∠67.13o 2.686 1.133
Operator S.A. (HEDNO S.A.). All segments of the main trunk
consist of 5-km long, 95 − mm2 ACSR conductors, whereas the
laterals consist of 3-km long, 16 − mm2 ACSR conductors. The
total line load is 3.32 MVA (2.86 MW). The transmission grid because P1 belongs to the main trunk. However, as the actual
is represented by an equivalent source with a maximum short- fault position moves away from P1 and consequently, from the
circuit power of 2085.1 MVA at 150 kV. The feeder is supplied main trunk, the divergence of the calculated fault position from
from the external transmission grid through a 150/20 kV bulk the actual one increases, i.e., the accuracy of the relay decreases.
distribution transformer. The distribution system is modelled The above observations agree with the findings of the previous
using DIgSILENT PowerFactory 2016. theoretical analysis.
A particular distance relay model was chosen from the soft- At this point, it is interesting to examine how the relay accu-
ware database to replicate the relay that is considered being racy varies with the change of K0 , for a SLG fault at a given
installed at the head of the line. The relay model used pro- position. Fig. 4 shows the different positions where the relay
vides four independent quadrilateral phase elements and four locates a SLG fault occurring at the midpoint of segment L12 ,
independent quadrilateral ground elements. The quadrilateral depending on the K0 setting. In particular, five cases are illus-
characteristic is selected due to its advantages compared to oth- trated in Fig. 4, depending on how K0 is set:
ers (e.g., mho), especially regarding fault resistance coverage. 1) K0 is set according to the impedance data of the main
In addition, the relay model used provides four independent po- trunk, being equal to 1.03∠26o . The relay locates the fault
larizing elements, which allow the user to set a different K0 accurately, at the midpoint of segment L12 (point C1 ).
value for each ground element, whereas it applies expression 2) The magnitude of the accurate K0 is increased by 0.7, i.e.,
(1) with K = 3 for the calculation of K0 . the K0 setting is equal to 1.73∠26o . The relay locates the
At first, the variation of the relay accuracy (calculated fault fault inaccurately, at point C2 .
position) with regard to the actual fault position is examined. 3) The magnitude of the accurate K0 is decreased by 0.7,
For this purpose, four SLG faults are simulated at points P1 , i.e., the K0 setting is equal to 0.33∠26o . The relay locates
P2 , P3 and P4 across lateral L1 (shown in Fig. 3), correspond- the fault inaccurately, at point C3 .
ing to a distance equal to 0%, 20%, 50%, and 100% from the 4) The angle of the accurate K0 is increased by 20o , i.e.,
beginning of L1 respectively. F1 , F2 , F3 and F4 in Fig. 3 stand the K0 setting is equal to 1.03∠46o . The relay locates the
for the positions, at which the relay locates the faults occurring fault inaccurately, at point C4 .
at P1 , P2 , P3 and P4 respectively, if K0 is set according to 5) The angle of the accurate K0 is decreased by 20o , i.e.,
the impedance data of the main trunk. As can be seen, in the K0 setting is equal to 1.03∠6o . The relay locates the fault
first case, point F1 coincides with the actual fault position P1 , inaccurately, at point C5 .
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

1240 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 3, JUNE 2018

Fig. 5(a) shows the vector (1 + K0 ), as well as its compo-


nents 1∠0 and K0 . As can be derived from this vector diagram:
1) If only the magnitude |K0 | of K0 increases, then magni-
tude B and angle b increase both. This results in a decrease
in magnitude C and angle c (as A and a remain constant).
2) If only the magnitude |K0 | of K0 decreases, then mag-
nitude B and angle b decrease both. This results in an
increase in magnitude C and angle c.
3) If only the angle g of K0 increases, then angle b increases,
whereas magnitude B decreases. This results in a decrease
Fig. 5. (a) Vector diagram of (1 + K 0 ) and its components, (b) Variation of
the calculated reactance with regard to the change of vector C ∠c. in angle c and an increase in magnitude C.
4) If only the angle g of K0 decreases, then angle b decreases,
whereas magnitude B increases. This results in an increase
in angle c and a decrease in magnitude C.
Table II shows the positive-sequence impedance values, cor-
It can be seen that, in general, the K0 setting affects the relay
responding to points C1 − C5 of Fig. 4, as calculated by the
accuracy following a specific pattern.
ground distance element of the relay. As can be derived by
Let us refer to the example of Fig. 3 again. ZP2 , ZP3 and
Fig. 4 and Table II, by increasing the magnitude of K0 , the re-
ZP4 stand for the impedance vectors up to the fault positions
lay calculates an impedance of smaller magnitude and smaller
P2 , P3 and P4 respectively. ZP2 , ZP3 and ZP4 represent the
angle compared to the impedance of the actual fault position
impedance vectors up to the fault position for SLG faults at the
(C1 ), whereas, by decreasing the magnitude of K0 , exactly the
same distance from the relay location compared to the faults at
opposite is valid. In addition, by increasing the angle of K0 , the
P2 , P3 and P4 respectively, but in a fictitious 16 − mm2 con-
relay calculates an impedance of smaller angle and greater mag-
ductor starting from the relay location. It can be seen that as the
nitude compared to the impedance of the actual fault position,
fault position moves away from the main trunk across the lateral
whereas, by decreasing the angle of K0 , the opposite is valid.
L1 , the fault impedance vector differs considerably from that of
The above results show that the variation of the fault location
a SLG fault at the same distance in the main trunk (increases in
point with regard to the K0 value follows a specific pattern.
magnitude and decreases in angle). Actually, it tends to become
The generalization of this pattern assists in coming up with a
similar to the fault impedance vector corresponding to a SLG
solution for setting K0 factor properly.
fault at the same distance in the fictitious 16 − mm2 conduc-
tor. In fact, the (theoretical) ideal K0 value for accurate fault
IV. EXAMINATION OF THE K0 SETTING PROBLEM location approaches the K0 value of a 16 − mm2 conductor,
As mentioned in the previous section, in case of a distance i.e., decreases in magnitude and increases in angle. Since K0
relay protecting an inhomogeneous feeder, it is not possible to is set based on the impedance data of the main trunk (having a
achieve absolute fault distance calculation accuracy for every 95 − mm2 cross-section conductor), it is of greater magnitude
SLG fault by using a single K0 setting, at least with the cur- and smaller angle (see Table I) compared to the ideal K0 value
rent relay technologies. However, that might not be necessary. for a fault anywhere in lateral L1 .
Actually, what should be preserved is the relay never to locate In general, situations such as the above constitute a combi-
a fault outside the desirable distance zone due to under-reach nation of Cases 1 and 4 described previously. Based on that,
phenomena. That means that relay inaccuracy could be allowed, the ground distance element will calculate an impedance of
as long as the fault is located inside the desirable distance zone. smaller magnitude compared to the actual impedance up to the
Nevertheless, in order to achieve this goal, a specific pattern fault position. However, Cases 1 and 4 are contradictive regard-
for the K0 effect should be determined first. Otherwise, this ing the angle change of K0 , and by extension, the change of
procedure would be much more complicated and considerable angle c. Case 1 (resp. Case 4) indicates a decrease (resp. in-
computational effort would be needed. crease) in angle c of the calculated impedance compared to the
actual impedance. Nevertheless, no matter whether the variation
A. Determination of the K0 Effect Pattern of angle c is positive or negative, it always results in a lower
calculated reactance than that of the actual fault position. Bear-
The terms Zn c and (1 + K0 ), used in (3), can be expressed ing in mind that in order for this to be valid, the combination of
in their polar form as: Cases 1 and 4 should result in decrease of magnitude C (increase
of magnitude B) and/or decrease of angle c (increase of angle
Znc = A∠a
b), it is explained as follows:
(1 + K0) = B∠b (5) Table III shows the percentage variation of magnitude B and
angle b of term (1 + K0 ), when moving from a lower to a
Therefore, (3) can be alternatively expressed as: greater ACSR nominal cross-section (i.e., from CSi to CSi + 1 ,
Za = C∠c (6) i = 1, . . . , 4), which gives a combination of Cases 1 and 4 as for
the change of K0 . As can be seen, when the variation of angle b is
where C = A/B and c = a − b. negative (which tends to increase angle c and thus the calculated
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

TSIMTSIOS AND NIKOLAIDIS: SETTING ZERO-SEQUENCE COMPENSATION FACTOR IN DISTANCE RELAYS 1241

TABLE III
PERCENTAGE (%) VARIATION OF MAGNITUDE AND ANGLE OF TERM (1 + K 0 )

C Si Nominal 1 + K0 Moving from C S i to C S i +1


cross-section (B∠b)
(mm2 )

% variation of B % variation of b

C S1 16 1.16∠13.57o + 25.00 + 27.12 Fig. 6. Ground distance zones for the examined distribution feeder.
C S2 35 1.45∠17.25o
+ 11.72 −6.09
C S3 50 1.62∠16.20o + 22.22 −18.58
C S4 95 1.98∠13.19o - -
effect of K0 on the relay accuracy. The proposed methodol-
ogy mainly considers the calculated reactance variation and is
implementable using the current relay technologies and logics;
reactance) the variation of magnitude B (always positive) is however, it requires that the relay allows the determination of a
greater than that of angle b. Therefore, the tendency towards the different K0 setting for each ground distance element, a feature
reduction of the calculated reactance is always dominant. Note provided by several well-established relay manufacturers.
that in the case of moving from CS1 to CS2 , the percentage In principle, the proposed methodology is based on the setting
variation of angle b is greater than that of magnitude B; however, rules originally described in [6]. To briefly illustrate these set-
as this variation is positive, it further strengthens the tendency ting rules, let us consider again the radial overhead line depicted
towards the reduction of the calculated reactance. in Fig. 2. Fuses f1 - f4 protect the main laterals, whereas fuses
Based on the above explanation, the decrease of magnitude f1.r − f 4.r protect the remotest tapped distribution transformer
C is always more intense than the possible increase of angle c. connected to each lateral. Coordination between the main fuse
In fact, when the combination of Cases 1 and 4 results in an in- and the fuse at the primary of the tapped transformers is always
crease of angle c, this increase is not enough to compensate for assumed. According to the setting philosophy of [6], the zone
the decrease of magnitude C and lead to a greater calculated re- 1 phase and ground distance elements of the relay are set to
actance compared to that of the actual fault position. This can be cover 85% of the main line between the relay location and the
further clarified with the example of Fig. 5(b), which illustrates first lateral. The higher-step distance zones are set to protect up
the impedance vectors Cact ∠cact and Ca ∠ca corresponding to to the endpoint of one or more laterals, i.e., up to the remotest
the actual and the calculated fault position respectively, on the distribution transformer(s) fed by the lateral(s), without over-
R-X plane. In this example, it is assumed that Ca and ca both reaching it (them). Fig. 6 shows the feeder with ground distance
differ by 50% (decrease and increase respectively) compared to zones graphically illustrated on it.
Cact and cact respectively. As analysed before, the variation in Moreover, the fuse-blowing principle is adopted in [6], mean-
angle c is always less intense. However, even in this case, where ing that faults occurring in a lateral are let to be cleared by the
the vector magnitude and angle are equally varied, the calcu- lateral fuse before the distance relay trips. This way, the relay
lated reactance (+ Xa ) is considerably lower than the reactance serves as primary protection for the main line and as backup
of the actual fault position (+ Xact ). protection for the line laterals, which are primarily protected
To sum up, it is generally fair to say that when a SLG fault by the fuses. In order for this to be ensured, the time delay of
occurs at a point that corresponds to an impedance vector of each phase/ground distance zone is set greater (increased by the
greater magnitude and smaller angle compared to the impedance proper Coordination Time Interval - CTI) than the maximum
vector based on which K0 is set, the relay calculates a lower possible total clearing time of any main fuse(s) included in this
reactance value compared to the reactance of the actual fault zone. In addition, coordination between two successive zones
position. Similar analysis showed that exactly the opposite is is achieved, meaning that the time delay tk of zone k is always
also valid. Just to mention, in the example of Fig. 3, for the SLG lower than the time delay tk + 1 of zone k + 1.
faults at P2 , P3 and P4 , the ground distance element calculates, Assuming now that the reach and time delay settings of the
in each case, an impedance of smaller magnitude and greater ground elements of a distance relay, protecting a distribution
angle (resulting to a lower reactance), compared to the actual feeder, have already been set based on [6], K0 for each ground
impedance up to the fault position. element is set following the next steps:
1) The areas Ak −1,k , formed in the complex impedance plane
between + Xk −1 and + Xk , where + Xk is the forward
B. Proposed K0 Setting Methodology
reactance reach of ground distance zone k, are determined.
Major problem for setting a ground distance element pro- The first area A01 is the area between the R-X origin
tecting an inhomogeneous line part is that a single K0 cannot (relay location) and the forward reactance reach of the
be compatible with all the possible fault cases. This can result first ground distance zone.
in undetected ground faults, if the fault is located outside the 2) The positive-sequence impedance (Z1 ) and the zero-
desirable zone, or in undesired zone trips due to under-/over- sequence impedance (Z0 ) of the main trunk, from the
reach. This work proposes a simple methodοlogy to deal with relay location up to the beginning of the lateral in-
this problem, based on the previously derived pattern for the side each area Ak −1,k which is closest to the relay, are
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

1242 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 3, JUNE 2018

Fig. 8. Ground zone characteristics of the distance relay.

will always lie between line e and the UB of zone k. Similarly,


if a SLG fault occurs anywhere upstream to S, the Z1 vector
up to the fault position will always be of smaller magnitude
Fig. 7. Explanation of the proposed methodology. and greater angle compared to the corresponding vector up to
S. Thus, the fault point calculated by element k will always lie
under line e.
calculated. These calculations give a pair of Z1,k and Z0,k
The second condition that should be fulfilled is ground dis-
values defining a reference point for each ground distance
tance element k never to locate a SLG fault occurring in a lateral
element k.
Lk +j,m(j, m ≥ 1), that is assigned to a higher-step element
3) For each ground distance element k, K0 is calculated using
k + j, inside zone k. If this happens, selectivity problems be-
the Z1,k and Z0,k values calculated for this element. If the
tween the relay and the lateral’s fuse may occur (due to the lower
first ground distance zone is set to cover a part of the main
time delay of element k compared to that of element k + j). The
line between the relay location and the first lateral, K0 for
possibility of such undesired trips is lower, as closer the refer-
this zone element is calculated based on the p.u. Z1 and
ence point S is placed to lateral Lk + 1 ,m . This is because, then,
Z0 values of the protected segment.
the K0 setting value of element k will be as close as possible to
The rationale behind the proposed methodology is explained
the ideal K0 value for a SLG fault in lateral Lk + 1m . However,
through Fig. 7, which shows a part of a distribution line with
at the same time, the reference point S should be upstream to
four laterals on the R-X plane. A distance relay at the head of the
all the laterals assigned to element k, so that every SLG fault
feeder protects the whole line. Consider the area Ak −1,k between
in the segments S-U1, S-U2 or S-U3 is located under the UB
the + Xk −1 and + Xk settings of ground distance elements k-1
of zone k, according to the previous explanation. Therefore, the
and k respectively, shown with solid horizontal lines in Fig. 7.
consideration of the reference point S being the intersection
The + Xk setting of zone k is defined as the upper boundary
point of the main line and the lateral inside area Ak −1,k , which
(UB) of this zone. Lateral Lk −1 is assigned to zone k-1, laterals
is the closest to the relay, gives an optimized solution for set-
Lk 1 and Lk 2 are assigned to zone k and lateral Lk + 1 is assigned
ting K0 for ground distance element k. It has to be noted that
to zone k + 1 [6].
such undesired trips of a lower-step zone due to a SLG fault
The first condition that should be fulfilled by ground distance
occurring in a lateral assigned to a higher-step zone have never
element k is this element never to locate a SLG fault occurring
been observed whenever the proposed methodology has been
in the segments D − U1 , D − U2 or D − U3 outside of zone k,
applied, even after extensive simulations performed on different
i.e., above the UB ( + Xk ) of that zone. Let us consider the
distribution line configurations.
reference point S, which corresponds to the beginning of the
lateral inside the area Ak −1,k which is closest to the relay. Line
C. Application of the Proposed Methodology
e separates the feeder into the parts upstream and downstream
to S. If K0 factor for element k is calculated based on the Z1 The distribution feeder shown in Fig. 2 is considered again.
and Z0 values from the relay location up to S, it is guaranteed For the sake of generality, the main trunk is not assumed ho-
that any SLG fault inside area Ak −1,k will be located inside this mogenous in this example, but with different ACSR conductor
area (thus inside zone k). This is based on the derived pattern cross-sections along the line; 95 − mm2 for L01 , 50 − mm2 for
for the effect of K0 on the calculated reactance, in combination L12 , 35 − mm2 for L23 and L34 . The line is protected by the
with the fact that, in principle, the nominal cross-section of the previously described distance relay, which is installed at its de-
conductor that constitutes the segments of a distribution feeder parture and is set according to [6].
is descending as we move towards the end of the feeder. Fig. 8 depicts the zone characteristics of the ground distance
Specifically, if a SLG fault occurs anywhere downstream to elements of the relay. The first zone is set to protect the 85%
S, the Z1 vector up to the fault position will always be of greater of L01 instantaneously. The second and the third zone are set
magnitude and smaller angle compared to the corresponding to protect up to the endpoint of laterals L1 and L2 respectively,
vector up to S. Since K0 has been set based on the latter vector, whereas their time delays are set to be higher than the highest
the calculated reactance for a fault anywhere in the segments S- ground fault clearing time of the corresponding main lateral fuse.
U1, S-U2 or S-U3, will be lower than the reactance of the actual The fourth zone is set to protect up to the endpoint of lateral
fault position. Therefore, the fault point calculated by element k L4 (covering also lateral L3 ), with a time delay that is higher
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

TSIMTSIOS AND NIKOLAIDIS: SETTING ZERO-SEQUENCE COMPENSATION FACTOR IN DISTANCE RELAYS 1243

TABLE IV TABLE VI
CALCULATED K 0 VALUES FOR EACH GROUND DISTANCE ELEMENT CHECK FOR UNDESIRED TRIPS DUE TO SLG FAULTS IN LATERALS
ACCORDING TO THE PROPOSED METHODOLOGY
Calculated Calculated UB ( + X k )
Ground Z 1 up to the reference Z 0 up to the reference K0 reactance with reactance with the (Ω primary)
element (k) point (Ω primary) point (Ω primary) conventional K 0 proposed K 0
(Ω primary) (Ω primary)
2 1.075 + 1.670 j 1.815 + 7.780 j 1.030∠26o
3 3.095 + 3.600j 4.575 + 15.700j 0.860∠34o Ground B2 B3 B2 B3
4 5.975 + 5.585j 8.195 + 23.675j 0.740∠40o element (k)

2 3.33 4.88 3.33 4.88 2.97


3 3.33 4.88 3.56 5.18 4.90
TABLE V
CALCULATED REACTANCE FOR SLG FAULTS AT BOUNDARY POSITIONS

Calculated reactance D. Comparison With the Traditional K0 Setting Philosophy


(Ω primary)
To date, significant experience concerning K0 setting is re-
Ground element E1 E2 E3 E4 E5 UB ( + X k ) (Ω trieved from transmission line applications. However, as trans-
(k) primary) mission lines are in their vast majority homogeneous as to their
1 2.78 2.41 4.34 4.05 7.03 1.42 conductor type and cross-section, the traditional K0 setting phi-
2 2.78 2.41 4.34 4.05 7.03 2.97 losophy indicates that K0 is set simply based on the p.u. positive-
3 2.98 2.51 4.62 4.25 7.35 4.90
4 3.18 2.64 4.89 4.48 7.70 8.87
and zero-sequence impedance of the conductor where the dis-
tance relay is installed. That means that a uniform K0 setting
is determined for the whole line. Nevertheless, if this setting
than the highest ground fault clearing time of the main fuses at is applied to an inhomogeneous distribution line, protected by
laterals L3 and L4 . The positive resistive reach ( + Rk ) of each a multi-zone distance scheme as that of Fig. 8, there could be
zone k has been set equal to four times the positive reactance undesired zone trips due to the loss of discrimination between
reach ( + Xk ). This is a good assumption for considering fault the ground distance zones.
resistance in a medium voltage distribution network [3]. In the following, the possibility of an undesired zone trip
Based on the method-implementation steps described in the due to a SLG fault in a lateral assigned to a higher-step zone
previous section, the Z1 and Z0 values of the main line up to is checked, by applying the traditional and the proposed K0
buses B1 , B2 and B3 (reference points), are calculated. Then, setting methodology. For this purpose, SLG faults are simulated
by using (1), the K0 setting values for each ground distance at the beginning of every lateral that follows the UB of a ground
element are calculated. The results of the above calculations are distance zone. In the examined distribution system, SLG faults
given in Table IV. Note that the K0 setting for the first element are applied at buses B2 and B3 , from which laterals L2 and L3
is equal to the K0 value corresponding to the 95 − mm2 ACSR depart, so as to check whether those faults are located outside
conductor (K0 = 1.03∠26o ). zone 2 and zone 3 respectively (as desired), by zone 2 and zone
The above K0 settings are applied to each ground distance 3 elements respectively. This check is not performed for lateral
element and SLG faults are simulated at each point where the L1 , since zone 1 and zone 2 elements have the same K0 setting,
main trunk or the laterals cross the + Xk characteristic of each meaning that every fault in lateral L1 will be located by zone 1
ground zone k (i.e., the UB of each zone). The exact fault po- between bus B1 and the UB of zone 2. Moreover, simulations
sitions (points E) are given in Fig. 8. The reactance, calculated performed with the proposed K0 setting, are compared to those
by each ground distance element for those faults, is given in conducted with a uniform K0 setting for all ground distance
Table V. From all the calculated reactances, those correspond- elements. The latter is taken equal to the K0 setting of zone
ing to faults that are assigned to the corresponding ground dis- 1 element (i.e., that corresponding to the main line segment
tance element of the first column are highlighted with bold in where the relay is installed, according to the traditional K0
Table V. The non-bolded results refer to reactance values that are setting philosophy).
calculated by ground distance elements, which are not assigned The simulation results are given in Table VI. As can be seen,
to trip for the corresponding faults. for the conventional (uniform) K0 setting, zone 3 trips unde-
Table V gives also the reactance values of the UB ( + Xk ) sirably in case of a fault at B3 . Referring to Fig. 8, the fault
that should not be violated by zone k element in each case. As at B3 (inside zone 4) is located by zone 3 element inside zone
can be seen, in all cases, the bolded calculated reactances are 3. However, this is avoided if the proposed K0 setting is used.
below the corresponding UB value. Since this is valid for faults Note that due to the coincidence of the uniform K0 setting with
occurring at the zones’ UB and based on the previous analyses, the proposed K0 setting for zone 2, the corresponding element
any fault in the examined feeder will be located inside the desir- calculates the same reactance values in each case, whereas it
able zone. Note that in all fault cases, the fault is located inside never trips undesirably for a SLG fault at B2 or B3 .
the assigned zone, as well as inside all the higher-step zones, but It results that the traditional K0 setting philosophy is not suit-
never inside a lower-step zone. Therefore, the desirable ground able for distribution system applications, as it can lead to unde-
distance element always trips first. sired zone trips, affecting selectivity between the distance relay
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

1244 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 3, JUNE 2018

TABLE VII
TRIPPING TIME OF GROUND DISTANCE ELEMENTS COMPARED TO THAT OF A
TYPICAL RECLOSER

Ground Lateral(s) Examined tT C m a x (s) tk (s) tR E C (s)


element (k) where fuse (fk )
ground
faults are
simulated

1 - - 0.055
2 L1 f1 0.265 0.565 0.567
3 L2 f2 0.378 0.678 0.729
4 L3 , L4 f3 , f4 0.752 1.052 1.196

and the protection means of the line laterals. This is because K0


is uniform for the whole line and not suitably specialized for Fig. 9. Conventional recloser-fuses scheme.
each individual ground zone, so as to avoid undesired trips (see
Section IV.B). On the contrary, the proposed K0 can ensure the
detection of a fault inside the desirable zone and, at the same
time, eliminate the danger of undesired trips.

E. Advantages of the Proposed Distance Scheme Compared to


Overcurrent Protection
Distance protection provides inherent directionality and in-
Fig. 10. Connection of DG plants to the examined distribution line.
dependency from external system conditions compared to over-
current protection [2]. Apart from those advantages, the ability
of distance relays to coordinate efficiently with other protec-
tion means in the system (e.g., fuses), while, at the same time, relay location increases. Bear also in mind that the tripping
achieving the minimum possible fault clearing time, renders time of the recloser varies with respect to the fault location
the application of distance protection to distribution systems a due to the inverse-time characteristic, whereas the tripping time
promising solution. of each ground distance element remains always constant, in
Let us compare the distance-based protection scheme shown the lowest possible value. Moreover, the tripping time of the
in Fig. 8 with a typical overcurrent one, where a very common recloser varies with respect to the short-circuit capacity of the
recloser is installed at the head of the line. Since a fuse-blowing external grid, unlike the distance relay.
philosophy is adopted in the distance-based protection scheme,
the same philosophy is adopted in the recloser-fuses coordi-
nation. Remember that according to [6], the time delay tk of F. Setting the Distance Relay Considering DG
each ground distance zone k is set equal or greater to the largest It is a fact that (2)–(6) are not valid if intermediate sources are
possible total clearing time (tTCm ax ) of the main fuse at the present in a distribution line. Therefore, the proposed K0 set-
lateral(s) protected by this zone, plus the required CTI, which is ting alone cannot guarantee discrimination between the ground
here considered equal to 0.3 s. 30T fuse links are assumed at all distance zones due to the infeed effect [2], which usually results
the line laterals. in an increased reactance calculated by the DR [16]. However,
Table VII shows the largest total clearing times tTCm ax of the infeed effect can be compensated by increasing the forward
the main fuses, resulting from ground fault simulations at the reactance reach setting + Xk of each ground distance zone suit-
endpoint of each lateral. It also shows the time delay setting ably, even if the proposed K0 is taken into account, which is
tk of each ground distance element k. Zone 1 is set with an calculated without considering DG. In this way, in case of DG
almost instantaneous time delay. Zones 2 and 3 are coordinated being present in the line, the impedance that a ground distance
with the largest total clearing time of the main fuse f1 and f2 element will calculate, using the proposed K0 , for a SLG fault
respectively. Zone 4 is coordinated with the largest total clearing occurring anywhere in its assigned line part, will lie inside the
time out of those calculated for fuses f3 and f4 at laterals L3 and respective (desirable) zone area.
L4 respectively. Finally, Table VII includes the tripping time The latter conclusion will be verified by considering the dis-
tREC of the recloser, for the same simulated ground faults. It is tribution feeder of Fig. 2, having now two generating plants
shown that, for the same SLG faults, the recloser set with inverse connected through step-up transformers to buses B1 and B3 re-
time-overcurrent phase and ground characteristics (Fig. 9) acts spectively (Fig. 10). Three cases are considered as for the type
with an increased time delay compared to that of the distance of the DG units composing the plants:
relay. The difference in the tripping time between the recloser 1) A 1.0 MVA, 0.4 kV, 50 Hz round-rotor synchronous gen-
and the distance relay increases as the fault distance from the erator (SG), operating with a unity power factor.
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

TSIMTSIOS AND NIKOLAIDIS: SETTING ZERO-SEQUENCE COMPENSATION FACTOR IN DISTANCE RELAYS 1245

TABLE VIII for PV systems), the reactance seen by a ground element for a
+ X k SETTING DETERMINED IN EACH CASE TO ADDRESS THE INFEED EFFECT
SLG fault will be lower than the actual one, thus it will definitely
lie inside the assigned zone.
No DG 2 DG plants (at B 1 and B 3 ) Based on the results of the above analysis, the proposed K0
DG type Ground element Initial + X k for + X k for the setting facilitates the optimized adjustment of the relay settings
(k) + Xk ideal K 0 proposed K 0 to the infeed effect conditions. A more detailed study of setting
setting (Ω primary) (Ω primary) the ground distance elements rigorously, when DG is present, is
(Ω primary)
planned for future work.
SG 2 2.97 3.67 3.05
3 4.90 6.73 6.09
4 8.87 14.30 13.57 V. CONCLUSION
IG 2 2.97 3.72 3.08
3 4.90 6.84 6.18 This paper examines the effect of K0 on the operation accu-
4 8.87 14.63 13.88 racy of distance relays protecting distribution feeders. Accord-
PV 2 2.97 2.99 2.45
3 4.90 4.96 4.38 ing to the theoretical analysis performed and based on the results
4 8.87 9.02 8.25 extracted from the examined test cases, the K0 effect follows
a specific pattern, considering conductors commonly used in
distribution networks. In particular, if K0 has been set based
on a specific positive- and zero-sequence impedance (reference
2) A set of four 250 KVA, 0.4 kV, 50 Hz induction generators impedance corresponding to a reference position) and a fault oc-
(IGs). curs in a position (downstream to the reference position), which
3) A set of two 500 KVA, 0.4 kV, 50 Hz inverter-interfaced corresponds to a positive-sequence impedance of greater mag-
photovoltaic (PV) systems operating with a unity power nitude and smaller angle compared to the reference impedance,
factor. The maximum steady state short-circuit contribu- the ground distance element locates the fault in a position of
tion of each PV system is limited to its nominal current. lower reactance compared to that of the actual fault position,
SLG faults are simulated at the endpoints of laterals L1 , L2 i.e., over-reach appears. On the contrary, if a fault occurs up-
and L4 , which correspond to the UB of ground distance zones 2, stream to the reference position, under-reach may appear. If not
3, and 4 respectively, in order to calculate the increased + Xk considered properly, those phenomena may lead to incorrect
setting for those zones, which addresses the infeed effect. Zone relay operation.
1 remains unaffected. Each fault is simulated twice; at first for By exploiting this pattern, the authors develop a methodology
the (theoretical) ideal K0 corresponding exactly to the fault for determining a single K0 factor for each ground distance ele-
position, in order to extract the pure effect of the intermediate ment, which leads the element to locate any SLG fault occurring
infeed, and secondly for the K0 setting of Table IV. in its assigned line part, inside the corresponding (desirable) dis-
The results of this analysis are presented in Table VIII. Each tance zone. The proposed methodology can be applied offline,
value in the fourth column of Table VIII corresponds to the reac- does not require considerable computational effort, and is ef-
tance calculated by each ground distance element for the ideal ficient for distribution systems without DG, in contrast to the
and the proposed K0 setting, when DG production is present traditional K0 setting philosophy. If intermediate DG sources
in the line. These values can be compared to those of the third are considered, it is observed that the proposed K0 reduces the
column, corresponding to zero DG production, in order to cal- infeed effect, making its handling easier.
culate the required increase in the + Xk setting and achieve
discrimination between the ground distance zones. VI. FUTURE WORK
It is shown that when SG or IG type DG units are connected
to the line, the + Xk setting of all zones, except the first one, has Using the findings of this work, the authors intend to proceed
to be increased either if the ideal or the proposed K0 is assumed. with a deeper examination of additional parameters, such as the
However, when the proposed K0 setting is applied, the required effect of fault resistance and DG. In addition, several other set-
increase is reduced. Concerning the connection of PV type DG ting criteria considering the coverage and time delay of distance
units, the infeed effect is negligible due to their low short-circuit relay zones will be examined. The ultimate goal is to propose
contribution. Therefore, when the ideal K0 is considered, the complete guidelines for the optimized setting of distance relays
required increase of the + Xk setting for zones 2, 3 and 4, is protecting distribution feeders with DG.
very low in this case. On the contrary, when the proposed K0
is considered, not only there is no need to increase the + Xk REFERENCES
setting of the ground distance zones, but also the calculated
[1] J. A. Momoh, Electric Power Distribution, Automation, Protection, and
reactance becomes lower than the initial + Xk setting (i.e., the Control. Boca Raton, FL, USA: CRC, 2007.
reactance corresponding to the actual fault position). In the latter [2] J. M. Gers and E. J. Holmes, Protection of Electricity Distribution Net-
case, the proposed methodology seems to be fully efficient in works. London, U.K.: IET, 2004.
[3] J. Chang, L. Gara, P. Fong, and Y. Kyosev, “Application of a multifunc-
terms of addressing the infeed effect. tional distance protective IED in a 15KV distribution network,” in Proc.
DG intermittence is not a problem in the above-mentioned 66th Annu. Conf. Protect. Relay Eng., College Station, TX, USA, 2013,
approach, since when DG production is zero (e.g., during night pp. 150–171.
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html

1246 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 33, NO. 3, JUNE 2018

[4] A. Enayati and T. H. Ortmeyer, “A novel approach to provide relay coor- [14] C. Jecu et al., “Protection scheme based on non communicating relays
dination in distribution power systems with multiple reclosers,” in Proc. deployed on MV distribution grid,” in Proc. PowerTech, Grenoble, France,
North Amer. Power Symp., Charlotte, NC, 2015, pp. 1–6. 2013, pp. 1–4.
[5] A. Sinclair, D. Finney, D. Martin, and P. Sharma, “Distance protection in [15] J. G. Andrichak and G. E. Alexander, “Distance relays fundamentals,”
distribution systems: How it assists with integrating distributed resources,” General Electric Co., Malvern, PA, USA, Rep. GER-3966.
IEEE Trans. Ind. Appl., vol. 50, no. 3, pp. 2186–2196, May/Jun. 2014. [16] G. Ziegler, Numerical Distance Protection: Principles and Applications.
[6] V. C. Nikolaidis, C. Arsenopoulos, A. S. Safigianni, and C. D. Vournas, “A Erlangen, Germany: Publicis Publishing, 2011.
distance based protection scheme for distribution systems with distributed
generators,” in Proc. Power Syst. Comput. Conf., Genoa, Italy, 2016, pp.
1–7.
[7] I. Chilvers, N. Jenkins, and P. Crossley, “Distance relaying of 11kV circuits Aristotelis M. Tsimtsios (S’17) received the Diploma of Electrical and Com-
to increase the installed capacity of distributed generation,” Proc. Inst. puter Engineering and the M.Sc. degree in energy systems and renewable energy
Elect. Eng., Gen., Transm. Distrib., vol. 152, no. 1, pp. 40–46, Jan. 2005. sources from the Department of Electrical and Computer Engineering, Dem-
[8] K. Pandakov, H. K. Høidalen, and J. I. Marvik, “Implementation of dis- ocritus University of Thrace, Xanthi, Greece, in 2013 and 2015, respectively.
tance relaying in distribution network with distributed generation,” in Proc. He is currently working toward the Ph.D. degree at the same Department. His
13th Int. Conf. Develop. Power Syst. Protect., Edinburgh, U.K., 2016, pp. research interests include power system protection, distributed generation, and
1–7. power system reliability. Dr. Tsimtsios is a member of the Technical Chamber
[9] H. Lin, C. Liu, J. M. Guerrero, and J. C. Vásquez, “Distance protection for of Greece.
microgrids in distribution system,” in Proc. 41st Annu. Conf. IEEE Ind.
Electron. Soc. Yokohama, Japan, 2015, pp. 731–736.
[10] L. Jin, M. Jiang, and G. Yang, “Fault analysis of microgrid and adaptive
distance protection based on complex wavelet transform,” in Proc. Int. Vassilis C. Nikolaidis (M’11) received the five-year Diploma of Electrical
Power Electron. Appl. Conf. Expo., Shanghai, China, 2014, pp.1–5. and Computer Engineering from the Department of Electrical and Computer
[11] V. Sellwood, U. Klapper, M. Kruger, and S. Kaiser, “A new technique for Engineering, Democritus University of Thrace, Xanthi, Greece, in 2001, the
setting distance protection and fault location by measurement of transmis- M.Sc. degree in energy engineering and management from National Techni-
sion line system impedance characteristics,” in Proc. 8th IEE Int. Conf. cal University of Athens (NTUA), Athens, Greece, in 2002, and the Doctor of
AC DC Power Transm., London, U.K., 2006. Engineering degree from NTUA, in 2007. Since 2008, he has been working as a
[12] M. El-Hadidy, H. Farouk, and B. Soudy, “Zero sequence compensation power systems consulting engineer. He is currently an Assistant Professor with
factor effect on distance protection ground reach (practical study),” in the Department of Electrical and Computer Engineering, Democritus Univer-
Proc. CIGRE Paris Session, Paris, France, 2012, pp. 1–8. sity of Thrace. His research interests mainly include power system protection,
[13] Y. Hu, D. Novosel, M. M. Saha, and V. Leitloff, “An adaptive scheme for control, stability, and transients.
parallel-line distance protection,” IEEE Trans. Power Del., vol. 17, no. 1,
pp. 105–110, Jan. 2002.

Vous aimerez peut-être aussi