TABLE OF CONTENTS REPUBLIC OF THE PHILIPPINES

Department of Public Works & Highways


SURVEY PLAN
OFFICE OF THE BUILDING OFFICIAL
ARCHITECTURAL
A-001 PERSPECTIVE, VICINITY MAP, RECOMMENDING APPROVAL
DRAWING INDEX, DIRECTORY
A-002 GEN. NOTES & SPECIFICATIONS
A-100 SITE DEVELOPMENT PLAN
A-101 LEVEL 2 FLOOR PLAN Engr. Samuel P. Salvador
A-102 LEVEL 3 FLOOR PLAN Chief, Processing & Enforcement Division
A-103 ROOF PLAN APPROVED
A-111 REFLECTED CEILING PLAN
A-201 EAST BUILDING ELEVATION
NORTH BUILDING ELEVATION
A-202 SOUTH BUILDING ELEVATION Engr. Nazita F. Bañez
Building Official
WEST BUILDING ELEVATION
A-301 BUILDING SECTION THRU 'BB'
A-302 BUILDING SECTION THRU 'AA'
A-401 WINDOW & DOOR SCHEDULE

STRUCTURAL
S-101 GENERAL NOTES, SPECIFICATIONS
MISCELLANEOUS DETAILS
S-102 FOUNDATION PLAN, 2L FRAMING LAND USE & ZONING

S-103 3F FRAMING PLAN, ROOF FRAMING


S-104 FOOTING DETAIL, COLUMN DETAIL
BEAM DETAILS
S-105 SLAB & RETAINING WALL DETAILS

PLUMBING
P-101 PLUMBING GENERAL NOTES,
SYMBOLS: ABBREVIATIONS: MATERIAL SPECIFICATIONS,
ENGR. GERALD SANNAD
LINE AND GRADE
A.F.F. ABOVE FINISHED FLOOR
BLDG BUILDING LEGENDS SYMBOLS &
C.B. CATCH BASIN ABBREVIATIONS, DETAILS
CLG CEILING
CHB CONCRETE HOLLOW BLOCK P-102 WATER SUPPLY LAYOUT,
# SECTION NUMBER C/W COMPLETE WITH ISOMETRIC VIEW
SITE A# PAGE NUMBER
CONC.
DIA.
CONCRETE
DIAMETER P-103 DRAINAGE LAYOUT,
D.O.W. DOOR OPENING WIDTH ISOMETRIC VIEW
ELECT. ELECTRICAL
ELEV. / EL. ELEVATION
F.D. FLOOR DRAIN ELECTRICAL ARCH. ODANEY T. BAGUIWEN
F.F.E. FINISHED FLOOR ELEVATION ARCHITECTURAL
E-101 GENERAL NOTES, POWER
# DETAIL NUMBER EQ
FIN.
EQUAL
FINISH SINGLE LINE DIAGRAM, LOAD
A# PAGE NUMBER F.R.R.
GA.
FIRE RESISTANCE RATING
GAUGE SCHEDULE, SPECIFICATIONS
G.C. GENERAL CONTRACTOR E-102 LIGHTING PLAN- LEVELS 1, 2 & 3
GEN. GENERAL
GWB GYPSUM WALL BOARD E-103 POWER PLAN - LEVELS 1, 2 & 3
H.C. HANDICAPPED
H.M. HOLLOW METAL
D101 DOOR NUMBER H.P. HIGH POINT
HT.
L.P.
HEIGHT
LOW POINT
PROJECT DIRECTORY ENGR. ISRAEL GALVEZ
MAX. MAXIMUM ARCHITECTURAL: STRUCTURAL
MDF MEDIUM DENSITY FIBERBOARD JUAN ALEXANDER S. BARREDO
MECHL. MECHANICAL
L14a, Blk2 Crystaldale Subdivision, Baguio City
W01 WINDOW NUMBER M.H.
MIN.
MANHOLE
MINIMUM CP (0947) 913-2412; email: bibjas@yahoo.com
MISC. MISCELLANEOUS
N/A NOT APPLICABLE STRUCTURAL:
N.I.C. NOT IN CONTRACT
SLOPE ARROW NTS NOT TO SCALE
ENGR. EDMAR SAMELO
O.C. ON CENTER Hillside, Baguio City
REQ'D REQUIRED CP (927) 510-0469; edmar0792@yahoo.com
R.D. ROOF DRAIN ENGR. ALBERT M. PAY-AN
RM ROOM
R.O. ROUGH OPENING
PLUMBING/ SANITARY: SANITARY/ PLUMBING
S.D. SCUPPER DRAIN ENGR. EDMAR SAMELO
S.G. SAFETY GLASS Hillside, Baguio City
SIM. SIMILAR CP (927) 510-0469; edmar0792@yahoo.com
SPEC. SPECIFICATIONS
S.S. STAINLESS STEEL
SM SQUARE METER ELECTRICAL:
STC SOUND TRANSMISSION CONTROL ENGR. PAULINO DELMAS
STO. STORAGE 86 M. Roxas St. Tabora Barangay, Baguio CIty
STRUCT. STRUCTURAL
S.F.L. STRUCTURAL FLOOR LEVEL
CP: (947) 987-5526; (908) 150-0923
TEL. TELEPHONE email: - ENGR. RENATO S. CIANO
TYP. TYPICAL ELECTRICAL
T/O TOP OF SOIL ANALYSIS:
T.O.C. TOP OF CURB / TOP OF CONCRETE
T.O.S. TOP OF SLAB
BIP STEADFAST GROUND INC.
U.N.O. UNLESS NOTED OTHERWISE No. 1 Purok 7, Bakakeng North, Baguio City
U/S UNDERSIDE (74) 442-4190 ; (74) 444-4830

1
VICINITY MAP VEST.
WC
W/
WD
VESTIBULE
WATER CLOSET
WITH
WOOD
SURVEYOR:
ENGR. CHARLIE BENAWE
NTS W.I.C.
W.T.C.
WALK-IN-CLOSET
WALK-THRU-CLOSET
3/F Lopez Building, Session Road, Baguio City
CP (0928) 756-4729
WT. WEIGHT FIRE DEPARTMENT

JA
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
PERSPECTIVE, VICINITY MAP, SYMBOLS, &
PROPOSED THREE LEVEL TRIPLEX ABBREVIATIONS, TABLE OF CONTENTS,
CARLOS & HELEN BARREDO A-001
SB
JUAN ALEXANDER S. BARREDO Architect, Leed AP Lot 7, Block 3 Crystaldale Subdivision, PROJECT DIRECTORY
PRC NO. 16394 VALIDITY: November 18, 2018 Bakakeng Central, Baguio City, Philippines 9715 Pililia St. Santiago Village, Makati City, Metro Manila
PTR NO. 3596747 DATE: March 16, 2018
PLACE: Baguio City TIN: 471-545-699
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
GENERAL NOTES DISPOSAL OF SURPLUS MATERIAL
Take possession of surplus material and remove it from the site. Remove
Provide a vapour barrier under slabs on ground including integral ground
beams and footings. Lay over the base, lap joints 200 mm and seal the laps CONTROL JOINTS
1. The General Contractor/ Builder shall check and verify all dimensions, cleared and grubbed ground material from the site. Dispose of this material and penetrations with waterproof adhesive tape. Seal punctures and tears Provide control joints 3 to 6 mm wide in the finish to coincide with control
surveyors metes and bounds, notes and any existing site conditions before legally. with waterproof tape before pouring concrete. joints in the substrate. Apply stopping beads and fill with a resilient sealant.
any construction work is started. All discrepancies shall be reported to the
architect. No work or ordering of material may be started until all EROSION CONTROL & PROTECTION WATERPROOFING VINYL FLOOR TILES
dimensioned items have been resolved. No extra charge of compensation Avoid erosion, contamination, and sedimentation of the site, its surrounding Integral waterproofing for concrete topping shall be 1 part portland cement, Installation of vinyl tiles shall not commence until interior painting has been
will be allowed on account of any difference between actual dimensions areas & drainage systems. Ensure that washout does not enter waterways 3 parts fine sand and 1 kilo 'sahara' admixture. completed. Floor surfaces that are to receive vinyl tiles shall be level, clean,
and the measurements which may be found as indicated on the drawings. or stormwater drains. Ensure that there are no cross connections between Membrane waterproofing shall be 'primero' elastomeric or approved equal. thoroughly dry, smooth, firm and sound, free from oil, paint, wax and any
The G.C. shall assume full and undivided responsibility for the accuracy, fit stormwater systems and sewerage systems. Mixture shall be applied by roller, paint brush or airless spray and shall other damaging materials. Use self-levelling concrete if necessary.
and stability of all parts of the work. Keep earthworks and the site of the works free of excess water. Provide remain tight under conditions of expansion, contraction and vibration of
and maintain slopes, crowns, drains, excavations and embankments to loads. Three-ply waterproofing is required for areas with foot traffic & each BATHROOM TILES
2. DO NOT SCALE THE DRAWINGS. REFER TO THE WRITTEN ensure free drainage. Place construction, including fill, masonry, concrete coat is allowed a minimum of 24 hours curing time between each coat or as Determine and mark layout of tiles as to joint location, position of trims and
DIMENSIONS PROVIDED. and services on ground from which free water has been removed. Prevent recommended in the product manufacturers instruction manual. fixtures so as to minimize cutting less than one half size of the tile.
water flow over freshly laid work. Before grouting of joints, tiles shall have been laid in place for at least 24
3. All labor, materials and installations must comply with the codes, rules 08 DOORS AND WINDOWS hours. Ensure max 1mm joint between tiles. Grouting mortar shall be white
and regulations of all authorities having jurisdiction. Any discrepancy which EXCAVATION WOOD DOORS cement with grout sealer. Clean tile surface thoroughly as possible upon
exists between the requirements by the plans, specifications, codes, rules SITE SURFACE: Proprietary doors manufactured for interior or exterior applications and for completion of grouting
and regulations shall be immediately brought to the attention of the Excavate to give the levels and profiles required for construction, site the finish required.
architect, in writing for resolution. services, paving, and landscaping. Allow for compaction or settlement or ALUMINUM WINDOW 10 SPECIALTIES
heaving. Windows shall be of sliding type U.N.O. Use 4mm thick clear glass on 11 EQUIPMENT
4. The contractor shall be responsible for adequately bracing and protecting powder coated aluminum frame which shall be true to the dimensions and 12 FURNISHINGS
all work during construction against damage, breakage, collapse, distortion FOOTINGS: placements as indicated in the plans. 13 SPECIAL CONSTRUCTION
and misalignment according to the applicable codes and standards. Excavate for footings to the required sizes and depths. Confirm that the 14 CONVEYING SYSTEMS
foundation conditions meet the design soil bearing capacity. 09 FINISHES 15 MECHANICAL (REFER TO SANITARY SPECIFICATIONS)
5. The contractor shall coordinate the work with mechanical, electrical and PAINTING 16 ELECTRICAL (REFER TO ELECTRICAL SPECIFICATIONS)
plumbing drawings for all necessary openings through walls, ceilings and FOUNDATIONS: Prime all areas subjected to paint removal during the course of fitting hinge
floors. After excavation, confirm that the soil bearing capacity is adequate. housings, locks and the like, prior to hanging. OWNER SUPPLIED ITEMS (exclude from contractors scope of work)
Within forty-eight hours of hanging and prior to the installation of door 1. Upvc WIndows - Supply and installation
6. All materials and construction to be incorporated in the work shall be in BEARING SURFACES: handles, weather excluders and the like (latches and locks excepted), 2. Doors & door hardware - Supply only
strict accordance with the latest edition of the astm specifications applicable Provide even plane bearing surfaces for load bearing elements including undercoat all surfaces, followed by a minimum 1 finishing coat to all 3. G.I. Roofing, flashings & gutters - Supply and installation
and shall conform to the standards and recommendations of the various footings. Step to accommodate level changes. Make the steps to the surfaces including top and bottom edges. the final coat may be applied at a 4. Kitchen countertop and overhead cabinet - Supply and installation
trade institutes (aci, aisc etc.) where applicable. appropriate courses if supporting masonry. later stage. 5. Bedroom Closets - Supply and Installation
All paints to be used shall be Boysen U.N.O: 6. Vinyl floor tiles - Supply only
ARCHITECTURALSPECIFICATIONS GRADING EXTERNAL AREAS:
Grade a minimum of 2% to slope away from buildings. Grade the ground
For exterior & interior plaster, use Boysen Titan Elastomeric paint w/ 1
primer coat & 2 final coats
7. Vertical blinds - Supply and installation
8. Bathroom accessories and fixtures - Supply only
01 GENERAL REQUIREMENTS surface under suspended floors and externally to drain ground or surface All colors shall be in accordance with samples to be approved by the owner 9. Electrical outlets & Lighting fixtures - Supply and Installation
The works under this project shall conform to all the technical drawings, water away from buildings to avoid ponding. of the building with the advice of the architect in charge of construction. 10. Stainless steel Watertank- Supply only
plans and all specifications here unto stated. All dimensions, lines, grades
All paints and other coatings shall be mixed and applied strictly in 11. Landscaping
shall be in accordance with the National Building Code of the PROTECTION, PUMPING & MAINTENANCE accordance with the manufacturers printed instructions. 12. Furnishings & Furnitures
Philippines. Other codes applicable therein shall also be complied with. The G.C. (general contractor) shall at all times protect the excavations and
The construction shall complete all phases of works as shown in the trenches from damages from rain water and all other sources of water. MOCK-UPS
drawings. The building lines shall be laid out accurately within the lot and all He shall provide and operate all pumps or other equipment necessary to Provide mock-up as required to demonstrate quality of workmanship BY
other measurements shall be correctly verified by the General Contractor. drain and keep excavations, pits trenches and the entire sub-grade area providing a 4 foot x 4 foot mock-up of each type of surface.
No part of this building with window opening shall be less than two meters free of water under any circumstances and contingencies that may arise.
from the boundary of the lot, unless the dimensions of the lot will not allow, The G.C. shall build all necessary enclosures, construct and maintain FIBERCEMENT
in which case a concrete firewall extending at least five hundred (500) temporary drainage for this purpose. He shall provide all shoring, bracing 4.5mm Thick hardiflex board - to be used for drop ceiling finishes such as
millimeters above the ridge of the roofing shall be erected on the side in and sheathing as required for safety, or necessary to support adjoining bathrooms.
which is less than two meters from the lot line. walls, walks, soils, streets, buildings, fences and the like for the prosecution
of the work. All of these shall be removed when work is completed and/ or PLAIN CEMENT PLASTER
02 SITE CONSTRUCTION required by owner. Joints and plastering mortar shall be composed of one part holcim wallright
SITE CLEARING OPERATIONS The contractor shall protect the excavation to be made below existing grade cement and four (4) parts sifted fine sand. clean water shall be added to
Protection of existing trees and site improvements not scheduled for line so that the soil of the adjoining property will not cave-in or settle and this mixture to form a workable paste.
clearing which might be damaged by construction activities. shall defray the cost of underpinning or extending the foundation of Surface shall be dampened before plastering, and the finished surface shall
Clearing and grubbing of stumps and vegetation, and removal and disposal buildings on adjoining properties. be kept wet for at least 72 hours.
of debris, rubbish, designated trees, and site improvements. Ready mix skim coat shall be applied to all interior surfaces u.n.o.
Topsoil stripping and stockpiling. FILL
Temporary erosion control, siltation control, and dust control. Place fill in near horizontal layers of uniform thickness no greater than 200 WORKMANSHIP:
Temporary protection of adjacent property, structures, benchmarks, and mm after compaction, deposited systematically across the fill area. Plaster work shall be finished level, plumb, square and true to line within a
monuments. Compact each layer to achieve the required density. Maximum depth of
Removal and legal disposal of cleared materials. tolerance of 3mm (81") in 3.00 meters without cracks, waves, blisters, pits,
sand fill is 400 mm. crazing, discolorations, projections and other imperfections.
CLEARING 1. Plaster work shall be formed carefully around angles, contours and
03 CONCRETE (REFER TO STRUCTURAL SPECIFICATIONS) well-up to screeds.
Prevent damage to existing improvements indicated to remain, including 04 MASONRY (REFER TO STRUCTURAL SPECIFICATIONS)
improvements on and off site. Protect existing trees and vegetation 2. Special care shall be taken to prevent sagging and consequent dropping
05 METALS of mortar during applications.
indicated to remain. Do not stockpile materials and restrict traffic within drip 06 WOOD & PLASTICS
line of existing trees to remain. Provide and maintain temporary guards to 3. There shall be no visible junction marks in the final coat where day work
Lumber shall be of the respective kinds for the various parts of the works, adjoins the other.
encircle trees or groups of trees to remain. well seasoned, free from large loose unsound knots, sap, cracks, shakes or
Prevent erosion and siltation of streets, catch basins and piping. Control other imperfections impairing its strength, durability and or appearance.
windblown dust. Remove waste materials and unsuitable soil from site and CEMENT PLASTER CURING:
Some wooden structural and framing lumber maybe rough in dimensions Do not allow rapid or uneven drying out. Keep continuously moist for 2 days
dispose of in a legal manner that are shown on the drawings. All exposed woodworks shall be smoothly and allow to dry for 5 days before applying further plaster coats.
planned and if necessary sand papered.
REMOVAL OF TOPSOIL Use approved good lumber for all rough wood works. All lumber in contact
Remove the topsoil layer of the natural ground which contains substantial V-JOINTS
with masonry shall be treated with approved wood preservatives or termite Provide v-joints cut straight through the plaster to the substrate at the
organic matter over the areas to be occupied by construction and paving. proofing compound.
Maximum depth: 300 mm. following locations: At junctions between different substrate materials ; At
abutments w/ other finishes ; At abutments with door frames.
07 THERMAL & MOISTURE PROTECTION

JA
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
GENERAL NOTES & SPECIFICATIONS
PROPOSED THREE LEVEL TRIPLEX
CARLOS & HELEN BARREDO A-002
SB
JUAN ALEXANDER S. BARREDO Architect, Leed AP Lot 7, Block 3 Crystaldale Subdivision,
PRC NO. 16394 VALIDITY: November 18, 2018 Bakakeng Central, Baguio City, Philippines 9715 Pililia St. Santiago Village, Makati City, Metro Manila
PTR NO. 3596747 DATE: March 16, 2018
PLACE: Baguio City TIN: 471-545-699
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
Lot 10, Block 3

JA
Tct # 2017001603

SB
6

PLACE:
PTR NO.
PRC NO.
N 81° 23' E 14.89m

CONSULTANT
overhead
watertank overhead

16394
2200L
1
watertank

3596747
GARDEN overhead
2200L

Baguio City
GARDEN GARDEN watertank
2200L

top of riprap retaining top of riprap retaining top of riprap retaining

600
wall 22 wall 22 22 wall

TIN:
JUAN ALEXANDER S. BARREDO
DATE:
2750
divide into 10 equal treads
GARDEN 12
GARDEN 12 12 GARDEN

471-545-699
1650

March 16, 2018


Architect, Leed AP
VALIDITY: November 18, 2018
top of riprap retaining top of riprap retaining top of riprap retaining

600
wall 11 wall 11 11 wall

CONCRETE CONCRETE CONCRETE


PATIO PATIO PATIO

2750
w/ 2% slope w/ 2% slope w/ 2% slope

PROJECT NAME
to drain to drain to drain

divide into 10 equal treads


1 1 1
UP UP UP
1000 1000 1000
G.I. gutter G.I. gutter G.I. gutter

1400
29.55m
32.43m

1
12% slope 12% slope 12% slope

Lot 5, Block 3 Lot 9, Block 3

Lot 7, Block 3 Crystaldale Subdivision,


Bakakeng Central, Baguio City, Philippines
Tct # 80092 Tct # 80386
S 12° 54' E

N 16° 33' W
LONG SPAN LONG SPAN LONG SPAN

PROPOSED THREE LEVEL TRIPLEX


PRE-PAINTED PRE-PAINTED PRE-PAINTED
G.I. ROOF G.I. ROOF G.I. ROOF

6000

OWNER
UNIT-A UNIT-B UNIT-C
roof ridge roof ridge roof ridge

LONG SPAN LONG SPAN LONG SPAN


PRE-PAINTED PRE-PAINTED PRE-PAINTED
G.I. ROOF G.I. ROOF G.I. ROOF
6000

12% slope 12% slope 12% slope


CARLOS & HELEN BARREDO

ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT.
9715 Pililia St. Santiago Village, Makati City, Metro Manila
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE

3
FD FD FD
waterproofed concrete
waterproofed concrete waterproofed concrete
1500

slab w/ 2% slope
slab w/ 2% slope slab w/ 2% slope

250
200

250
200

DRIVEWAY
SHEET CONTENTS
2000

BELOW
DRIVEWAY
5
BELOW
SITE PLAN/ ROOF PLAN

S 85° 15
50 'W 3.50m DRIVEWAY
4 BELOW

N8
FOR BIDDING PURPOSES

TRUE 2° 1
1' W
NORTH
7.57
PLAN m
BB N8
NORTH 3° 0
A-302 2.57 0' W
3 m
4300 4300
2
50
A B C D
SHEET NO.

1
SITE PLAN / ROOF PLAN
1:100 M
A-100
JA
SB
WALL TYPES:

PLACE:
PTR NO.
PRC NO.
(party wall between units)

CONSULTANT
2 layers 5" CHB wall w/ min. 1/2" thick plaster on each side.

16394
3596747
(rear fence)

Baguio City
6" CHB wall w/ min. 1/2" thick plaster on each side.

5" CHB wall w/ min. 1/2" thick plaster on each side.

TIN:
200mm thick concrete wall w/ waterproofing on one side.

JUAN ALEXANDER S. BARREDO


DATE:
Straight to finish

Note:
Use Holcim Wallright for cement plastering works.

471-545-699
March 16, 2018
Architect, Leed AP
VALIDITY: November 18, 2018
1400
250 250 250 250
1 500 500 500 500

PROJECT NAME
UNDISTURBED EARTH

apply

6000
2500 minimum 2500 2500
3 ply
waterproofing
on
CLO. this
CLO. CLO.

Lot 7, Block 3 Crystaldale Subdivision,


STORAGE STORAGE STORAGE

900
side

Bakakeng Central, Baguio City, Philippines


PROPOSED THREE LEVEL TRIPLEX
1950

MAIDS UP UP UP
D3a
D3a
D3a

900
ROOM
250 1 250 1 250 1 250
2 500 500 MAIDS 500 MAIDS 500
1100 1100 1100
ROOM D3a ROOM

OWNER
FFL D3a FFL D3a

1050
EL=2.80 m EL=2.20 m FFL
FOYER FOYER FOYER EL=1.60 m
1500 1300 1500 1300 1300 1500
D3
D3
D3

1500

T&B T&B
D1
D1
D1

T&B

W2 W1 W2 W1 W1 W2
900
900
900

6000

5 5 5
1200
1200
1200

1
1 1
UP UP
UP
1100 1100 1100
CARLOS & HELEN BARREDO
CARPORT
slab w/ 3% slope slab w/ 3% slope
CARPORT CARPORT
slab w/ 3% slope
250
to drain 250
to drain 250
to drain 250
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. 3 500 Epoxy Paint 500 Epoxy Paint 500 Epoxy Paint 500
9715 Pililia St. Santiago Village, Makati City, Metro Manila

FInish FInish FInish


COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
1500
same
slope w/
driveway

FLOOR PLANS
same
same

SHEET CONTENTS
2000
slope w/
slope w/

driveway
driveway

G01

650

400
650

50
G01

400
FOR BIDDING PURPOSES
650
G01

400
LEVEL 1 400
BB
A-302 50
FLOOR PLAN
650

1 4300 4300
1:75 M

A B C D
SHEET NO.

A-101
2750
GARDEN

JA
GARDEN

divide into 10 equal tr


GARDEN

SB
12 12 12

PLACE:
PTR NO.
PRC NO.
1650

CONSULTANT

16394
3596747
top of riprap retaining top of riprap retaining top of riprap retaining

600

Baguio City
wall 11 wall 11 11 wall

CONCRETE CONCRETE CONCRETE

2750
PATIO PATIO PATIO

TIN:
JUAN ALEXANDER S. BARREDO
DATE:
w/ 2% slope w/ 2% slope w/ 2% slope
to drain to drain to drain

divide into 10 equal treads


1 1 1
UP UP UP
1000 1000 1000

471-545-699
March 16, 2018
2400 1750 1750 1750

600
600

Architect, Leed AP
2250

VALIDITY: November 18, 2018


sink sink sink

D2
D2
D2

W4 W4 W4

600
600

1400
clerestory DN clerestory DN DN clerestory
250 250 250 250
1 500 500 500 500
1900

PROJECT NAME
MULTI-PURPOSE

2500
2500
2500

BDRM 3 BDRM 3
1350 1000 600 1000
400 700 400 D2 D2 D2

LINEN LIN LIN

6000
1425
1425

1550
T&B 3 D3
1m high
T&B 3 D3 600 1000 D3 T&B 3
wall
1150 1925 1100 1025 1925 1100 1100 1925 900
sto.

Lot 7, Block 3 Crystaldale Subdivision,


div. into 7 eq. treads DN div. into 7 eq. treads DN DN div. into 7 eq. treads

900

Bakakeng Central, Baguio City, Philippines


8 16

150

PROPOSED THREE LEVEL TRIPLEX


niche

seat
1450

1
D2
D2
D2

UP UP UP

900
900 150 900
900 150 900

sto.
250 250 250 250
2 500 500 500 500

OWNER
ref

600
600
600

ref
sink

sink stove
sink

ref
stove
stove

pantry

KITCHEN KITCHEN KITCHEN


FFL FFL FFL
EL=5.50 m EL=4.90 m EL=4.30 m

DINING DINING DINING


6000

LIVING LIVING LIVING


CARLOS & HELEN BARREDO
3000 3000 3000
250 250 250 250
500 500 500 500
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT.
3
9715 Pililia St. Santiago Village, Makati City, Metro Manila
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE

W3 W3 W3
BALCONY
1500

BALCONY BALCONY
w/ 2% slope to drain
1450

w/ 2% slope to drain
1650

w/ 2% slope to drain
400

tempered clear glass balluster


250 tempered clear glass balluster
FLOOR PLANS

250 tempered clear glass balluster


250 250
SHEET CONTENTS
2000

50
FOR BIDDING PURPOSES

BB
LEVEL 2 A-302 50

FLOOR PLAN 4300 4300


1
1:75 M
SHEET NO.

A B C D
A-102
JA
WALL TYPES:

SB
(party wall between units)

PLACE:
2 layers 5" CHB wall w/ min. 1/2" thick plaster on each side.

PTR NO.
PRC NO.
(rear fence)

CONSULTANT
6" CHB wall w/ min. 1/2" thick plaster on each side.

16394
3596747
Baguio City
5" CHB wall w/ min. 1/2" thick plaster on each side.

200mm thick concrete wall w/ waterproofing on one side.


Straight to finish

TIN:
Note:

JUAN ALEXANDER S. BARREDO


DATE:
Use Holcim Wallright for cement plastering works.

1400 1300 1400 1300 1400

471-545-699
W5 W5 W5

March 16, 2018


W6 W6 W6

Architect, Leed AP
300
300
300

VALIDITY: November 18, 2018


W/D

1400
W/D W/D

250 UTILITY 250 UTILITY 250 UTILITY 250


1 500 500 500 500

PROJECT NAME
1000
1000
1000

BDRM 2 BDRM 2 BDRM 2


D2a
D2a
D2a

800 1000 1000 800


1500
1500
1500

800 800 D2 D2 D2

STO.
300 1000 1000 300

6000
1400
1425
1425

T&B 2 1000 1000 T&B 2 T&B 2


D3 D3 D3

DN DN DN

Lot 7, Block 3 Crystaldale Subdivision,


1925 1925 1925
900
900

Bakakeng Central, Baguio City, Philippines


8 div into 7 eq. treads 16 8 div into 7 eq. treads 16 16 div into 7 eq. treads 8

PROPOSED THREE LEVEL TRIPLEX


1 1 1
900 150
900 150
900 150 900

250 250 250 250


2 500 500 500 500

OWNER
D2
D2
D2

1500
1500
1500

seat

T&B 1 T&B 2 T&B 2


D3 D3 D3

800 1700 800 800 1125 1200 1200 1100 800 800

BDRM 1
FFL
6000

BDRM 1 BDRM 1
EL=8.20 m

CARLOS & HELEN BARREDO


3000 3000 3000
250 250 250 250
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. 3 500 500 500 500
9715 Pililia St. Santiago Village, Makati City, Metro Manila
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE

BALCONY W3a W3a W3a


BALCONY BALCONY
1500

w/ 2% slope to drain
w/ 2% slope to drain w/ 2% slope to drain
200

250
200

250
FLOOR PLANS

250 250
SHEET CONTENTS
2000

50
FOR BIDDING PURPOSES

LEVEL 3 BB
A-302 50

1
FLOOR PLAN 4300 4300
1:75 M

A B C D
SHEET NO.

A-103
CF-4 CF-4 CF-4

EQ EQ
CF-1
CF-1 EQ EQ CF-1

EQ
EQ EQ

EQ
EQ EQ

EQ

EQ
EQ EQ EQ EQ CF-2 CF-2 CF-2
CF-2 CF-2 CF-2

EQ
EQ
CF-1 CF-1 CF-1

EQ
EQ EQ

EQ EQ
EF EF EF EF EF EF
CF-2 CF-2 CF-2

EQ
CF-2 CF-2 CF-2 CF-2 CF-2 CF-2 CF-2 CF-2 CF-2
S S S
S S S

EQ
CF-5 CF-5 CF-5
CF-3 CF-3 CF-3 EQ EQ

EQ
CF-2 CF-2 CF-2
EQ EQ

EQ
EF EF EF

1900
CF-2 CF-2 CF-2

EQ
EQ 2000 EQ EQ EQ

EQ
2150

CF-1 CF-1 CF-1


EQ EQ

CF-2 CF-2 CF-2

EQ
1900

EQ EQ 2
LEVEL 2 RCP
EQ

EQ
CF-1 1:100 M CF-1 CF-1 CF-1
CF-1 CF-1 EQ EQ
EQ

EQ
CF-3 CF-3 CF-3 1
LEVEL 1 RCP 3
LEVEL 3 RCP
CF-3 CF-3 CF-3 1:100 M 1:100 M
CF-2
EQ

S S S
CF-1 CF-1 CF-1
EQ EQ
CF-2 CF-2
EQ EQ

EQ

CF-1 CF-1 CF-1 LEGEND:


LED LIGHT FIXTURE, OWNER SUPPLIED CF-1 EXPOSED UNDERSIDE OF STRUCTURAL SLAB. TEXTURED PAINT
CF-2 4.5mm THK FIBERCEMENT 300mm DROP CEILING W/ 1X2 G.I. FRAME. 3 COATS
EQ

LED CHANDELIER SEMI-GLOSS WHITE.


CF-3 EXPOSED UNDERSIDE OF STAIR SLAB. PAINTED FINISH
EQ EQ CF-4 PERFORATED ALUMINUM SOFFIT BY COLORSTEEL
6W LED LIGHT W/ BUILT-IN SWITCH ATTACHED TO OVERHEAD CABINET / CF-5 SKYLIGHT PRISMATIC DIFFUSER
6W LED STRIP LIGHTING CONCEALED IN COVE
CF-1 CF-1 CF-1
SHEET NOTES:
EQ

WALL MOUNTED LED LIGHT FIXTURE (W/ OPTIONAL MOTION SENSOR)

S 2 IN 1 SMOKE & HEAT DETECTOR (BATTERY) 1. REFER TO ELECTRICAL PLANS FOR ADDITIONAL INFORMATION.
2. CEILING DROP SHALL NOT BE MORE THAN 300mm U.N.O.
EL EMERGENCY LIGHT (RECHARGABLE)
3. ALL POWER OUTLETS, LIGHTING FIXTURES SHALL BE OWNER SUPPLIED
CF-1
EQ

4. PROVIDE 1X1 'DRIP EDGING' AROUND SLAB PERIMETER EXPOSED TO


CF-1 EQ EQ CF-1 WEATHER
EQ

JA
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
REFLECTED CEILING PLAN
PROPOSED THREE LEVEL TRIPLEX
CARLOS & HELEN BARREDO A-111
SB
JUAN ALEXANDER S. BARREDO Architect, Leed AP Lot 7, Block 3 Crystaldale Subdivision,
PRC NO. 16394 VALIDITY: November 18, 2018 Bakakeng Central, Baguio City, Philippines 9715 Pililia St. Santiago Village, Makati City, Metro Manila
PTR NO. 3596747 DATE: March 16, 2018
PLACE: Baguio City TIN: 471-545-699
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BIDDING PURPOSES
6.2 6.1 B C D
ROOF APEX (Unit-A) MATERIAL LEGEND
EL=12.08 m
PL 1.1 PAINTED TITAN ELASTOMERIC; 3 COATS BANNISTER WHITE (ROUGH FIN)
1180

TOP OF ROOF BEAM (Unit-A) 1.2 PAINTED; TITAN ELASTOMERIC; 3 COATS DOVE GRAY (SMOOTH FIN)
FFL=10.90 m
1.3 PAINTED; FEATURE WALL (VERIFY WITH ARCHITECT)
1.3
2.1 FIREWALL. PAINTED TITAN ELASTOMERIC; 3 COATS BANNISTER WHITE
2700

3.1 OVER CEMENT PLASTER (W/ SAHARA WATERPROOFING)


9.1 3.1 uPVC WINDOW FRAME W/ 6mm THK CLEAR GLASS; COLOR WHITE
LEVEL 3 TOP OF SLAB (Unit-A) 4.1 STEEL GATE & FENCE; 3 COAT DAVIES AQUA GLOSS 'PITCH BLACK'
FFL=8.20 m
1.2 5.1 STEEL DOOR; GRAY
6.1 COLORSTEEL LONG SPAN G.I. ROOF. WHITE OR LIGHT COLORED
2700

2.1
6.2 G.I. CAPPING. TO MATCH ADJACENT COLOR
±12080

7.1 2X6 ALUMINUM TRIM (LAID HORIZONTALLY)


LEVEL 2 TOP OF SLAB (Unit-A)
FFL=5.50 m 8.1 CONCRETE RETAINING WALL; STRAIGHT TO FINISH (APPLY SEALER)
1.1
9.1 CLEAR GLASS BALLUSTER; TEMPERED
2700

1.2

4.1
LEVEL 1 TOP OF SLAB (Unit-A)
FFL=2.80 m
950

EXIST. UPPER SIDEWALK CORNER


FFL=1.85 m
1850

EXIST. LOWER SIDEWALK CORNER 1


SOUTH ELEVATION
FFL=0.00 m 1:100 M

1.1 4.1
1 2.1 6.2
2 3
ROOF APEX (Unit-A)
EL=12.08 m
1180

TOP OF ROOF BEAM (Unit-A)


FFL=10.90 m
2700

LEVEL 3 TOP OF SLAB (Unit-A)


FFL=8.20 m

1.2
2700
±12080

LEVEL 2 TOP OF SLAB (Unit-A)


FFL=5.50 m

WEST ELEVATION
2700

2
1:100 M
LEVEL 1 TOP OF SLAB (Unit-A)
FFL=2.80 m
950

JA
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
BUILDING ELEVATIONS
PROPOSED THREE LEVEL TRIPLEX
CARLOS & HELEN BARREDO A-201
SB
JUAN ALEXANDER S. BARREDO Architect, Leed AP Lot 7, Block 3 Crystaldale Subdivision,
PRC NO. 16394 VALIDITY: November 18, 2018 Bakakeng Central, Baguio City, Philippines 9715 Pililia St. Santiago Village, Makati City, Metro Manila
PTR NO. 3596747 DATE: March 16, 2018
PLACE: Baguio City TIN: 471-545-699
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
D C B MATERIAL LEGEND
1.1 PAINTED TITAN ELASTOMERIC; 3 COATS BANNISTER WHITE (ROUGH FIN)
ROOF APEX (Unit-A)
EL=12.08 m PL 1.2 PAINTED; TITAN ELASTOMERIC; 3 COATS DOVE GRAY (SMOOTH FIN)
1180

6.2 1.3 PAINTED; FEATURE WALL (VERIFY WITH ARCHITECT)


TOP OF ROOF BEAM (Unit-A)
FFL=10.90 m 2.1 FIREWALL. PAINTED TITAN ELASTOMERIC; 3 COATS BANNISTER WHITE
OVER CEMENT PLASTER (W/ SAHARA WATERPROOFING)
6.1
3.1 uPVC WINDOW FRAME W/ 6mm THK CLEAR GLASS; COLOR WHITE
2700

4.1 STEEL GATE & FENCE; 3 COAT DAVIES AQUA GLOSS 'PITCH BLACK'
3.1 5.1 STEEL DOOR; GRAY
LEVEL 3 TOP OF SLAB (Unit-A)
FFL=8.20 m 6.1 COLORSTEEL LONG SPAN G.I. ROOF. WHITE OR LIGHT COLORED
1.1 6.2 G.I. CAPPING. TO MATCH ADJACENT COLOR
2700

7.1 2X6 ALUMINUM TRIM (LAID HORIZONTALLY)


3.1 8.1 CONCRETE RETAINING WALL; STRAIGHT TO FINISH (APPLY SEALER)
LEVEL 2 TOP OF SLAB (Unit-A) 9.1 CLEAR GLASS BALLUSTER; TEMPERED
FFL=5.50 m 1.1
2700

1
NORTH ELEVATION
1:100 M

3 6.2 2 1 4.1
ROOF APEX (Unit-A)
EL=12.08 m
1180

TOP OF ROOF BEAM (Unit-A)


FFL=10.90 m
2700

2.1
LEVEL 3 TOP OF SLAB (Unit-A)
FFL=8.20 m
2700
±12080

1.2
LEVEL 2 TOP OF SLAB (Unit-A)
FFL=5.50 m
2700

LEVEL 1 TOP OF SLAB (Unit-A)


FFL=2.80 m
4.1
950

EXIST. UPPER SIDEWALK CORNER


FFL=1.85 m
1.1
EAST ELEVATION
1850

2
1:100 M
EXIST. LOWER SIDEWALK CORNER
FFL=0.00 m

JA
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
BUILDING ELEVATIONS
PROPOSED THREE LEVEL TRIPLEX
CARLOS & HELEN BARREDO A-202
SB
JUAN ALEXANDER S. BARREDO Architect, Leed AP Lot 7, Block 3 Crystaldale Subdivision,
PRC NO. 16394 VALIDITY: November 18, 2018 Bakakeng Central, Baguio City, Philippines 9715 Pililia St. Santiago Village, Makati City, Metro Manila
PTR NO. 3596747 DATE: March 16, 2018
PLACE: Baguio City TIN: 471-545-699
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
A B C -prepainted G.I. Roof (gauge 26)
-Foil faced insulation (w/ 50mm sag)
-2x6 steel purlins (2mm thick)
-50x50x6mm cont. angle bar w/ expansion bolt Note:
PL
Locate bottom of tank at
-50x50 tubular steel w/ strapping where required
least 1meter above highest
-CEILING PLENUM
shower head
-optional batt insulation
-4.5 mm thick fibercement on G.I. framing
ROOF APEX (Unit-A)
EL=12.08 m ELEVATED
% slope provide 12 WATER
provide 12 % slope
1180

TANK
ceiling plenum
TOP OF ROOF BEAM (Unit-A) 250100
FFL=10.90 m gutter

22
2700

2300

BALCONY MASTERS BEDROOM HALLWAY UTILITY


LEVEL 3 TOP OF SLAB (Unit-A)
250

FFL=8.20 m bulkhead beyond for kitchen exhaust duct 12


11
2700

2450
±12080

BALCONY LIVING DINING KIT HALLWAY PATIO


LEVEL 2 TOP OF SLAB (Unit-A) 1
250

FFL=5.50 m

PL open undisturbed earth


2700

LEVEL 1 TOP OF SLAB (Unit-A) FOYER STO


FFL=2.80 m
CARPORT
950

w/ 3% slope
EXIST. UPPER SIDEWALK CORNER
FFL=1.85 m
STREET
1850

EXIST. LOWER SIDEWALK CORNER


FFL=0.00 m

1
BUILDING SECTION THRU 'BB'
1:100 M

JA
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
BUILDING SECTION
PROPOSED THREE LEVEL TRIPLEX
CARLOS & HELEN BARREDO A-301
SB
JUAN ALEXANDER S. BARREDO Architect, Leed AP Lot 7, Block 3 Crystaldale Subdivision,
PRC NO. 16394 VALIDITY: November 18, 2018 Bakakeng Central, Baguio City, Philippines 9715 Pililia St. Santiago Village, Makati City, Metro Manila
PTR NO. 3596747 DATE: March 16, 2018
PLACE: Baguio City TIN: 471-545-699
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BIDDING PURPOSES
PL
ROOF APEX (Unit-A)
EL=12.08 m
1180
ceiling plenum
TOP OF ROOF BEAM (Unit-A)
FFL=10.90 m
ceiling plenum

ceiling plenum
2700

MBR TOILET
LEVEL 3 TOP OF SLAB (Unit-A)
FFL=8.20 m

600
MBR TOILET

1200
2700
±12080

KITCHEN
LEVEL 2 TOP OF SLAB (Unit-A)
FFL=5.50 m

600
KITCHEN

1200
KITCHEN
2700

LEVEL 1 TOP OF SLAB (Unit-A) MAIDS ROOM FOYER FOYER FOYER


FFL=2.80 m

600
950

1200
MAIDS ROOM
compacted soil/
EXIST. UPPER SIDEWALK CORNER undisturbed soil
FFL=1.85 m MAIDS ROOM
compacted soil/
undisturbed soil
1850

compacted soil/
undisturbed soil

EXIST. LOWER SIDEWALK CORNER


FFL=0.00 m

1
BUILDING SECTION THRU 'AA'
1:75 M

JA
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
BUILDING SECTION
PROPOSED THREE LEVEL TRIPLEX
CARLOS & HELEN BARREDO A-302
SB
JUAN ALEXANDER S. BARREDO Architect, Leed AP Lot 7, Block 3 Crystaldale Subdivision,
PRC NO. 16394 VALIDITY: November 18, 2018 Bakakeng Central, Baguio City, Philippines 9715 Pililia St. Santiago Village, Makati City, Metro Manila
PTR NO. 3596747 DATE: March 16, 2018
PLACE: Baguio City TIN: 471-545-699
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
TAG WIDTH X HEIGHT MATERIAL LOCATION DESCRIPTION

D1 900 X 2100 STEEL MAIN DOOR PEEP HOLE, DEAD BOLT, SS HEAVY DUTY HINGES, TRANSOM LIGHT
D2 800 X 2100 WOOD PATIO, BDRMS
D2a 800 X 2100 WOOD UTILITY WITH CLEAR GLASS
D3 700 X 2100 WOOD TOILETS WITH SMOKED GLASS
D3a 700 X 2100 WOOD MAIDS RM

G1 3700 X 1600 STEEL GARAGE GATE

NOTES:
1. ALL DIMENSIONS ARE APPROXIMATE AND SHOULD BE CHECK MEASURED ON-SITE BEFORE CONSTRUCTION.
2. ALL HARDWARE SHALL BE STAINLESS STEEL BRUSHED FINISH. OWNER SUPPLIED
3. ALL DOOR HANDLES TO BE LEVER TYPE. OWNER SUPPLIED

1
DOOR SCHEDULE
NTS

3000
EQ EQ EQ 3000
EQ EQ EQ
600 600 2000 1600 1300

500
600

F
1200

1200

1200
F F

2500

2300
F F F F
F F F

1600
1500

500 500
900

900

900
FFL
4 PCS 4 PCS 4 PCS 4 PCS 4 PCS 4 PCS 4 PCS
W1 L1 T&B W2 L1 Maids Room W3 L2 Living Rm W3a L3 Mbr W4 L2 Rear Bdrm W5 Bdrm 3 W6 Bdrm 3
(see arch'l elevs) (see arch'l elevation) (see arch'l elevation) (see arch'l elevation) (see arch'l elevation) (see arch'l elevation) (see arch'l elevation)

WINDOW NOTES:
1. ALL WINDOWS SHALL BE uPVC WHITE W/ 4.5mm THK CLEAR GLASS
2. WINDOW MANUFACTURER/ SUPPLIER SHALL VERIFY SITE MEASUREMENTS PRIOR TO FABRICATION
3. WINDOW MANUFACTURER/ SUPPLIER SHALL SUBMIT FRAME SAMPLE FOR ARCHITECT AND OWNER APPROVAL
4. WINDOW MANUFACTURER/ INSTALLER SHALL PROVIDE A 3 YEAR WARRANTY

2
WINDOW SCHEDULE
NTS

JA
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
DOOR SCHEDULE
PROPOSED THREE LEVEL TRIPLEX WINDOW SCHEDULE
CARLOS & HELEN BARREDO A-401
SB
JUAN ALEXANDER S. BARREDO Architect, Leed AP Lot 7, Block 3 Crystaldale Subdivision,
PRC NO. 16394 VALIDITY: November 18, 2018 Bakakeng Central, Baguio City, Philippines 9715 Pililia St. Santiago Village, Makati City, Metro Manila
PTR NO. 3596747 DATE: March 16, 2018
PLACE: Baguio City TIN: 471-545-699
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
JA
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
IMAGES
PROPOSED THREE LEVEL TRIPLEX
CARLOS & HELEN BARREDO A-601
SB
JUAN ALEXANDER S. BARREDO Architect, Leed AP Lot 7, Block 3 Crystaldale Subdivision,
PRC NO. 16394 VALIDITY: November 18, 2018 Bakakeng Central, Baguio City, Philippines 9715 Pililia St. Santiago Village, Makati City, Metro Manila
PTR NO. 3596747 DATE: March 16, 2018
PLACE: Baguio City TIN: 471-545-699
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
GENERAL NOTES : WALL RECEPTACLES AND PLATES ENTRANCE CAP
1.All electrical works herein shall comply with the latest edition Receptacle outlets, shall be 15A, 240 V, 2-pole, 3-wire parallel LOAD SCHEDULE (Typical for LPP1, LPP2 & LPP3)
of the Phililpine Electrical Code, the rules and regulations of the slot, grounding type. Fixing screws for wiring devices shall be 2-38 mm² THHN
local utility company and the laws and ordinances of the local concealed from sight. Other special purpose receptacle outlets in 32 mm RSC CKT VA PER PROTECTION
enforcing authorities concerned. LOAD DESCRIPTION L.O. C.O. VOLTS AMPS FEEDER WIRE CONDUIT SIZE
shall be as indicated in the drawings. Outlet devices shall be as NO. CIRCUIT AT KAIC
2. The electrical works shall be under the immediate manufactured by Panasonic wide sseries or approved equal.
supervision of competent duly licensed Electrical Engineer. Locking type and other special purpose receptacle outlets shall 220V, 1 Phase supply LPP 1 15W LED LIGHTING 10 150 230 0.65 15 4 2 - 2.0 mm² THHN 15 mm Ø PVC
3. All materials, devices, fixtures and equipment to be used be as indicated in the drawings. Appropriate weather proof UNIT-A 2 15W LED LIGHTING 13 196 230 0.85 15 4 2 - 2.0 mm² THHN 15 mm Ø PVC
such as ballast, led lighting, enclosures, wires & cables, shall fitting metal cast alloy boxes shall be provided for convenience 3 15W LED LIGHTING 12 180 230 0.78 15 4 2 - 3.5 mm² THHN 15 mm Ø PVC
have the ICC mark (imported commodity clearance) ; local outlet where indicated to be weather proof. M 4 180W CONV. OUTLETS 7 1260 230 5.48 20 4 2 - 3.5 mm² THHN 15 mm Ø PVC
products shall bear the PS mark. Provide weatherproof metal receptacle plate cover for each 2-30 mm² THHN 5 CONV. OUTLETS 9 1620 230 7.04 20 4 2 - 3.5 mm² THHN 15 mm Ø PVC
4. All electrical equipment shall be properly grounded in convenience receptacle outlet indicated as weatherproof. in 32 mm RSC 6 WATER HEATER 1 3500 230 15.22 30 4 2 - 5.5 mm² THHN 15 mm Ø PVC
accordance with the requirements of the latest edition of the Type and color of receptacle outlet and plates shall be as
Philippine Electrical Code. LPP 7 CONV.OUTLETS 3 540 230 2.35 20 4 2 - 3.5 mm² THHN 15 mm Ø PVC
5. All electrical materials and equipment to be used in this
selected by the Architect. Appropriate samples of outlets and
plates shall be submitted prior to purchase of devices.
M UNIT-B 8 1500W MICROWAVE 1 1500 230 6.52 20 4 2 - 3.5 mm² THHN 15 mm Ø PVC
project shall be brand-new and of approved quality and brand. 9 3000W RANGE (2 BURNER) 1 3000 230 13.04 20 4 2 - 3.5 mm² THHN 15 mm Ø PVC
All utility boxes intended for receptacle outlet devices shall be
10 WATER HEATER 1 3500 230 15.22 30 4 2 - 5.5 mm² THHN 15 mm Ø PVC
specially designed to receive the particular type of receptacle
11 WATER HEATER 1 3500 230 15.22 30 4 2 - 5.5 mm² THHN 15 mm Ø PVC
PROJECT SPECIFICATIONS: outlet device to be mounted and should be deep enough to
accept and fit the total number of conductors required as per M 12 WATER HEATER 1 3500 230 15.22 30 4 2 - 5.5 mm² THHN 15 mm Ø PVC
CONDUIT AND FITTINGS drawings. Receptacle with Ground Fault Circuit Interrupter LPP 13 2000W WASHING MACHINE 1 2000 230 8.70 20 4 2 - 3.5 mm² THHN 15 mm Ø PVC
Service entrance conduit shall be IMC (Intermediate Metallic (GFCI) shall be rated 15A, 2P, 3 wire grounding type, 240 V, 14 CONV. OUTLETS 5 900 230 3.91 20 4 2 - 3.5 mm² THHN 15 mm Ø PVC
UNIT-C
Conduit). parallel slot with 15 milliampere current sensitivity. 15 SPARE
Polyvinyl Chloride Conduit (PVC), schedule 40, heavy wall, Duplex conveninence outlets shall have a minimum separation 16 SPARE
high impact type with factory made bend, couplings and fittings of 20mm between outlet device.
and as manufactured by Neltex, Emerald, Atlanta or approved TOTAL 35 31 25346 230 110.20 100 100 2 - 30 mm² THHN 32 mm Ø RSC
equal. PVC conduits shall be embedded in concrete slabs or LIGHTING AND POWER PANELBOARD LPP (Lighting & Power Panelboard)
chb walls. CALCULATIONS: THEREFORE:
Panelboard for use as service disconnecting means shall (Typical for Units A, B & C ) As per table 2.20.4.5 (PEC) for Multi-Family Dwellings, use 45% D.F. (Demand Factor) Use: 2-30mm² THHN in 32mm Ø
conform to UL Standard. Design shall be such that any
OUTLETS, BOXES, AND FITTINGS I total = (25,346 / 230) X 0.45. RSC (Rigid Steel Conduit) Pipe
individual breaker can be removed without disturbing adjacent
Outlet boxes shall be fabricated from PVC boxes as follows: = 49.59 Amps
units or without loosening or removing supplemental insulation
A. Ceiling light outlets: 40mm deep, 100mm octagonal box supplied as a means of obtaining clearances. Panelboard shall
MAIN 100A,2P CB (WP)
for 1 or 2 raceway entries ; 55mm deep, 100mm be of weatherproof type. A removable circuit directory shall be
octagonal box for 3 or more raceway entries
B. Light control switch: 40mm deep, 50mm x 100mm utility
box for 1 or 2 raceway entries in one strap ; 55mm deep,
provided for each panel board for field markings of function and
number or each branch circuit. All directories shall be of
incorrodible material with matching clear plastic holder or 1
15A 15A
2 2
LOAD SCHEDULE
50mm x 100mm utility box for 3 switches in 1 strap. jacket. NTS
Mounting height shall be 1200mm above finish floor.
C. Convenience outlets: 55mm deep utility box. mounting MOLDED CASE CIRCUIT BREAKERS AND SWITCHES: 15A 20A
height shall be 450mm above finish floor. Provide individual circuit breakers, safety switches and
D. TV cable outlets: 55mm deep utility box ; mounting disconnect switches where indicated on plans. Voltage ratings
3 4
height shall be 450mm above f.f.l. shall be suitable in each case of service application.
E. Panel boards inside cabinets: mounting height shall be Enclosures shall be General Purpose, NEMA Type I, except 20A SPARE
1800mm above finish floor. where specifically noted on plans or assembled on panel
cabinets. 5 6
JUNCTION AND PULL BOXES All protective devices shall meet NEMA and Underwriter’s
Junction and pull boxes, of Code gauge steel, galvanized shall Laboratories, Inc. specifications. 20A 20A
be provided as indicated or as required for facilitating the Circuit breakers shall consist of a quick-make, quick-break type

t
pulling of wires and cables. Pull boxes in finished places shall 7 8

en
entirely trip-free operating mechanism with contacts,
be located and installed with the permission and to the arc-interrupter and thermal magnetic trip unit for each pole, all
satisfaction of the Architect and Engineers. magnetic trip unit for each pole, all enclosed in a
All junction and pull boxes on exposed conduit work shall be 20A 30A

m
molded-phenolic case. The thermal magnetic trip unit shall
provided with hubs for threaded pipe entry and covers provided provide time-delayed overload protection, and in case of 9 10
with neoprene gaskets. overload or short circuit current in any one pole. Circuit

ch
breaker shall be trip indicating, with the tripped position of
30 SQ. MM BCW

WIRES AND CABLES: breaker handle midway between “ON” and “OFF” positions. 30A 30A
All wires shall be copper, soft-drawn and annealed, shall be of Circuit breaker shall be as manufactured by G.E. or approved 11 12

ta
98% conductivity, shall be smooth and true of a cylindrical form equal.
and variation shall be within 1% of the actual size called for.

at
All wires and cables shall comply with the requirements of the 20A 20A
Underwriters Laboratories, the ASTM and ICEA as they apply
to the particular usage. 13 14

o
All wires and cables shall be as manufactured by Phelps
Dodge, American Wires and Cable Columbia, Philflex, Durex, SPARE SPARE

rt
or approved equal.
Wires and cables for power and lighting system shall be plastic 15 16

fe
insulated for 600 volts working pressure type “THHN” unless
otherwise noted on plans or specified.
GROUNDING WIRE

re
WALL SWITCHES AND PLATES CONNECT TO REBAR OR
Wall switches shall be rated 15A, 240V, 60 Hz. EMBED UNDERGROUND
Switches shall be for flush mounting type and of the quiet type,
spring operated. The type of switches shall be tumbler
operation and the color, plating and appearance of wall plates
shall be as selected by the Architect. Appropriate samples SINGLE LINE DIAGRAM 3
DESIGN ANALYSIS
shall be submitted prior to the purchase of wall switches and 1 NTS
face plates. Switches and plates shall be as manufactured by NTS
Panasonic Wide Series or approved equal.
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
GENERAL NOTES, SPECIFICATIONS
PROPOSED THREE LEVEL TRIPLEX SINGLE LINE DIAGRAM, LOAD SCHEDULE
ENGR. PAULINO D. DELMAS, PEE
PRC NO. 1823 VALIDITY: DECEMBER 18, 2020
Lot 7, Block 3 Crystaldale Subdivision,
Bakakeng Central, Baguio City, Philippines
CARLOS & HELEN BARREDO
9715 Pililia St. Santiago Village, Makati City, Metro Manila
& DESIGN ANALYSIS E-101
PTR NO. # DATE: JAN 2019
PLACE: BAGUIO CITY TIN: 184-156-076
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
v v v

k k k

S
k k k

w S
w S S
w
3 3 3

S
S

S
v,w v,w v,w
j j j

u u s s u
EF EF EF EF EF EF

S
S

S
b3W,j

b3W,j

b3W,j
t,u t,u t,u
t s t t

b3W,s

b3W,s

b3W,s
2 2 2
S

S
b3W b3W b3W
skylight skylight skylight

S
w/ diffuser w/ diffuser w/ diffuser
1 1 1
b3W b3W b3W
1 1 1
i3W i3W i3W
i3W i3W i3W S S S
SS

SS

SS
r p r p p r
EF EF EF

S
g,h g,h g,h q,r q,r q,r
q q q

g g g g g g

p p p

h h h

e,f e,f e,f


S

S
m,n m,n m,n

2
L2 LIGHTING LAYOUT
1:100 M
f e f f e f f e f m n m m n m m n m

S S S 1
L1 LIGHTING LAYOUT 3
L3 LIGHTING LAYOUT
1:100 M 1:100 M

c c c
c,d c,d c,d
1 S b3W 1 S b3W b3W S 1

d d d
a,b3W a,b3W a,b3W
S
S

3W

S
LED LIGHT FIXTURE, SURFACE MOUNTED THREE-WAY SWITCH

6W LED KITCHEN CABINET LIGHT w/ BUILT-IN SWITCH / # CIRCUIT HOME RUN (number identify circuit breaker)
a a a LED COVE LIGHT ABOVE BATHROOM MIRROR
EF EXHAUST FAN

WALL MOUNTED LED LIGHT FIXTURE (optional motion sensor)


SHEET NOTES:
WALL SWITCH (1200mm height measured from center of plate to ffl) 1. ALL LIGHTING SHALL BE LED
S

2. LIGHTING FIXTURES & RECPTACLES TO BE SUPPLIED BY OWNER


a a a

aa aa aa aa aa aa
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
LIGHTING LAYOUT
PROPOSED THREE LEVEL TRIPLEX
ENGR. PAULINO D. DELMAS, PEE
PRC NO. 1823 VALIDITY: DECEMBER 18, 2020
Lot 7, Block 3 Crystaldale Subdivision,
Bakakeng Central, Baguio City, Philippines
CARLOS & HELEN BARREDO
9715 Pililia St. Santiago Village, Makati City, Metro Manila
E-102
PTR NO. # DATE: JAN 2019
PLACE: BAGUIO CITY TIN: 184-156-076
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
WP WP WP
WD WD WD
GFCI GFCI GFCI
TV TV
TV TV TV TV 13 13 13

5 5 5

WH GFCI WH WH
WH GFCI WH GFCI GFCI WH GFCI GFCI
10 14 10 14 14 10 12 12 12

7 7 7
HOOD

HOOD

HOOD
RAN

RAN

RAN
MIC MIC MIC

LPP LPP LPP WH GFCI WH GFCI GFCI WH


GFCI

GFCI

GFCI
GFCI

GFCI

GFCI
REF

REF

REF
9 9 9 11 11 11
8 8 8

TV TV TV

4 4 4
2
L2 POWER LAYOUT WP WP WP
WP WP WP 1:100 M

1
L1 POWER LAYOUT 3
L3 POWER LAYOUT
1:100 M 1:100 M

4 4 4

6 6 6 LEGEND:
WH WH WH
DUPLEX CONVENIENCE OUTLET (450 mm from FFL unless noted otherwise) LPP LIGHTING & POWER PANELBOARD (locate inside kitchen overhead
cabinet)
WP WP WP DUPLEX CONVENIENCE OUTLET INSIDE CABINET M HOUSE METER (BENECO supplied)
GFCI DUPLEX CONVENIENCE OUTLET (w/ Ground Fault Circuit Interruptor)
RG-6 CABLE TV OUTLET (conceal behind tv)
WP WEATHER PROOF CONVENIENCE OUTLET WD WASHER / DRYER (gfci)

WH WATER HEATER OUTLET (ceiling mounted)

MIC MICROWAVE OUTLET (energy star rated)


SHEET NOTES:
REF REFRIGERATOR OUTLET (energy star rated) 1. USE GFCI POWER OUTLETS AT WET AREAS SUCH AS ABOVE KITCHEN
COUNTERTOP, TOILETS & GARAGE
RAN ELECTRIC STOVE OUTLET (for 2 burner induction)
2. ALL POWER OUTLETS SHALL HAVE GROUNDING WIRE
TV TELEVISION OUTLET (conceal behind tv)

CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.


POWER LAYOUT
PROPOSED THREE LEVEL TRIPLEX
ENGR. PAULINO D. DELMAS, PEE
PRC NO. 1823 VALIDITY: DECEMBER 18, 2020
Lot 7, Block 3 Crystaldale Subdivision,
Bakakeng Central, Baguio City, Philippines
CARLOS & HELEN BARREDO
9715 Pililia St. Santiago Village, Makati City, Metro Manila
E-103
PTR NO. # DATE: JAN 2019
PLACE: BAGUIO CITY TIN: 184-156-076
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
GENERAL NOTES: PROJECT SPECIFICATIONS WATER TEST ON SYSTEM
- Upon completion of the rough-in and before
1. All plumbing works included herein shall be NOTE:
connecting fixtures, the entire cold water piping 2250
executed according to the provisions of the COLD / HOT WATER LINES PROVIDE THREE MANHOLE (0.60X0.60)
Uniform Plumbing Code of the Philippines, the -shall be polypropylene pipes & fittings, PN-20 system shall be tested at a hydrostatic pressure 1 21 COVERS W/ LIFTING HANDLE
National Plumbing Code, rules and the minimum rating. Jointing shall be by socket fusion. times the expected working pressure in the system 150 1950 150
regulations of the concerned city. "Vespo", "Neltex", "Atlanta" or approved equal. during operation and shall remain tight and leak 12Ø BOTTOM BARS @ 200mm
2. Coordinate the drawing with other related proof. ON CENTER, BOTHWAYS
100Ø INLET
drawings and specifications. the engineer shall SEWER AND WASTE, STORM DRAIN,

150
DEFECTIVE WORK 500 500
be notified immediately of any discrepancy found DOWNSPOUTS & VENT PIPES
therein. -"Neltex" or "Emerald" PVC series 1000. Fittings shall - All defective work, materials replaced and tested C.O.
3. All pipes shall be installed as indicated on be pvc w/ solvent cement. will be repeated until satisfactory performance is AIR SPACE AIR SPACE

900
plans. any relocations required for proper attained. Caulking of screwed joints or holes will not DIGESTIVE CHAMBER water level
water level

execution of other trades shall be with prior WATER METER- "Nibco", "Kitz", "Amico" , "Arad" or be permitted.
approved equal

50
approval of the architect/ engineer.

50
150
DISINFECTION

2350
4. Proposed sanitary utilities shall conform to the
actual location, depth and inlet elevation of all GATE VALVES- "Kitz" or approved equal -The entire water distribution system shall be
20mm THK PLASTERING 20mm THK PLASTERING
existing pipes and structures as verified by the thoroughly flushed and treated with Chlorine before it WITH SAHARA WITH SAHARA
WATERPROOFING WATERPROOFING
is operated for human use. Disinfection shall be liquid TERTIARY SECONDARY

1000
builder. IDENTIFICATION & APPROVAL OF MATERIALS SECONDARY DIGESTIVE
5. All slopes for horizontal drainage shall -Each length of pipe, fittings, traps, fixtures and Chlorine or hypochlorite and shall be introduced in a CHAMBER CHAMBER CHAMBER CHAMBER
maintain 1% unless otherwise specified. device used in the Plumbing system shall have cast, manner approved as practiced for water distribution
6. Size of water supply pipes to fixtures shall be tamped or marked on it, the manufacturer's trade system.

150
in accordance with the manufacturer's mark or name, weight, type and classes of product After contact period of not less than 16 hours, the
instructions. when so required by the standard. heavily chlorinated water shall be flushed from the 100Ø OUTLET
7. The builder shall verify locations of all existing system with potable water.
150mm CHB WALL W/ 12Ø
utilities at site. He shall coordinate the sewer PITCH
line effluent disposal and water line service -All sewer and drainage pipes shall be pitched 6mm SHEET INDEX 150 900 150 900 150 REBARS SPACED @ 400mm
BOTHWAYS
connecting points. per 300mm. but in no case flatter than 3mm per P-101 GENERAL NOTES, DETAILS,
300mm. 12Ø BOTTOM BARS @ 200mm
8. All pipe sizes are in millimeters and all LEGENDS, SPECIFICATIONS,
1 ON CENTER, BOTHWAYS
dimensions are in meters unless otherwise SYMBOLS & ABBREVIATIONS
specified. ROUGHING IN P-102 WATER SUPPLY LAYOUT, P-101
9. All pipe diameter are inside dimension - Roughing-in for pipes and fixtures shall be carried ISOMETRIC VIEW PLAN SECTION
(nominal) unless otherwise specified. along with the building construction. Correctly P-103 DRAINAGE LAYOUT
10. Verify architectural plans for the exact
location or setting out of floor drains & floor clean
located openings of proper sizes shall be provided
where required in the walls and floors for the
ISOMETRIC VIEW
1
SEPTIC TANK DETAILS
outs. passage of pipes. All items to be embedded in LEGEND, SYMBOLS & 1:40m
11. All concealed valves or valves at ceiling level concrete shall be thoroughly clean and free from all
shall be provided with access manhole. rust, scale and paint. ABBREVIATIONS
12. Risers and stacks shall be provided with
sway braces every other floor starting at ground CLEANOUTS WATER DISTRIBUTION SYSTEM
floor. -shall be of the same size of the pipe, the location of CWL COLD WATER LINE
13. Upon completion of the water supply system which is extended to an easily accessible place. CWDF COLD WATER DOWN FEED
CWR COLD WATER RISER
or portions of the system and before piping is GV GATE VALVE
covered up, it shall be hydrostatically tested with TRAP M WM WATER METER
-every plumbing fixture of equipment requiring CV CHECK VALVE
potable water at one and a half (1 21) times the HB HOSE BIBB
expected working pressure in the system. connections to the drainage system shall be
14. Required fittings not shown on the plans equipped with a trap. Each trap shall be placed as
WASTE, SEWER AND VENT SYSTEM
shall be provided. near as possible to the fixture. No fixture shall be
15. All fixtures shall be vented unless otherwise double trapped. SP/ WP SOIL PIPE/ WASTE PIPE
VAC VENT AT CEILING
noted. FCO FLOOR CLEAN OUT
16. All vents passing thru roof shall be provided PIPE HANGER INSERTS and SUPPORTS VS VENT STACK
- Horizontal runs of pipe shall be hung with FD FLOOR DRAIN
with metal flashing and anchorage VSTR VENT STACK THRU ROOF
17. Plumbing drawings are essentially adjustable wrought iron or malleable pipe hangers AAV AIR ADMITTANCE VALVE
diagrammatic to the extent that many offset, spaced not over 3m apart. Wrought iron clamps shall SS SOIL STACK
SB SOIL BRANCH
bends, elbows, special fittings and exact be used to support vertical pipe runs or collars
locations of equipment, piping and related spaced not more than 9m apart.
STORM DRAINAGE SYSTEM
accessories are not indicated. the builder shall
carefully study the drawings and actual field DRAINAGE SYSTEM TEST DP DRAIN PIPE
-The entire drainage and venting system shall have DS DOWNSPOUT
conditions to determine the best method, exact
location, routing, obstructions, other trades etc all the necessary openings which can be plugged to ADCB AREA DRAIN / CATCH BASIN
permit the entire system to be filled with water to the
which affect the installation of his work.
18. Provide air chamber to all quick closing level of the highest stack vent above the roof. The
system shall hold the water for a full 30 min during 2
CATCH BASIN DETAILS
valves NTS
which time there shall be no drop greater than 10mm.
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
GENERAL NOTES, SPECIFICATIONS & DETAILS
PROPOSED THREE LEVEL TRIPLEX
e-mail: edmar0792@yahoo.com
Address: Hillside, Baguio City
EDMAR L. SAMELO, Sanitary Engineer
PRC NO. 3059 VALIDITY: September 7, 2019
Lot 7, Block 3 Crystaldale Subdivision,
Bakakeng Central, Baguio City, Philippines
CARLOS & HELEN BARREDO
9715 Pililia St. Santiago Village, Makati City, Metro Manila
P-101
PTR NO. 3448712 DATE: January 2019
PLACE: BAGUIO CITY TIN: 471-667-438-000
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
SINK SINK SINK
BESTANK BESTANK BESTANK
WATER TANK WATER TANK WATER TANK

1/2
L
L
2200L CAP. 2200L CAP. 2200L CAP.
CW

CW


BESTANK


WATER TANK

CW
1/2

1/2
2200L CAP.

L
3/4"Ø DF 3/4"Ø DF 3/4"Ø DF float valve
1/2"Ø CWL 1/2"Ø CWL 1/2"Ø CWL

3/4"Ø DF
LAV LAV LAV
WC WC WC
SHO SHO SHO 3/4"Ø to water tank 3/4"Ø to water tank 3/4"Ø to water tank
3/4"Ø CWL 3/4"Ø CWL 3/4"Ø CWL

3/4"Ø CWR 3/4"Ø CWR 3/4"Ø CWR L


CW WM
1/2"Ø CWL 1/2"Ø CWL 1/2"Ø CWL "Ø
3/4 SHO
SINK SINK SINK
DF 1/2 LAV
3/4"Ø DF 3/4"Ø DF 3/4"Ø DF "Ø "Ø WC
3/4 CW
L
SHO

2
L2 WATER SUPPLY 1/2"Ø CWL
WM
1/2"Ø CWL
WM WM
1/2"Ø CWL
1/2 WC
LAV
1:100 M "Ø

3/4"Ø CWL

3/4"Ø CWL

3/4"Ø CWL
CW SHO

3/4"Ø DF
L

1/2 LAV
WC

3/4"Ø CWR
3/4"Ø CWR 1/2"Ø CWL 1/2"Ø CWL 1/2"Ø CWL CW
3/4"Ø CWR KITCHEN L

3/4"Ø CWR
(TO WATER TANK)
(TO WATER TANK) (TO WATER TANK) SINK
SINK SINK SINK
WC WC WC 1/2
SHO SHO SHO " Ø
1/2"Ø DF 1/2"Ø DF 1/2"Ø DF CW

3/4"Ø CWL
L

3/4"Ø CWL

1/2"Ø DF
WC SHO WC SHO SHO WC
3/4"Ø CWL
3/4"Ø CWR 3/4"Ø CWR 3/4"Ø CWR
1/2"Ø CWL 1/2"Ø CWL 1/2"Ø CWL (supply to
1/2"Ø CWL 1/2"Ø CWL 1/2"Ø CWL
HB HB HB water tank)
SINK SINK SINK
WC WC WC
SHO SHO SHO

1/2 WC SHO

CW
3/4"Ø PPR (to water tank)

L
HB
3/4"Ø PPR (to water tank)

NOTE:
1. L2 & L3 TOILETS (SHOWER & LAVATORY) SHALL
EACH BE PROVIDED WITH A MULTIPOINT WATER
3/4"Ø PPR (to water tank)

HEATER.
FRO 1/2Ø
M ET M BAW FLE
E R B A DI
ANK
XIBL
E PI
PE TYPICAL
L1 1/2Ø 4
ISOMETRIC (UNIT-B)
FLE NTS
WATER SUPPLY
XIBLE P
I PE
3
L3 WATER SUPPLY
1 1:100 M
1:100 M
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
WATER SUPPLY LAYOUT
PROPOSED THREE LEVEL TRIPLEX
e-mail: edmar0792@yahoo.com
Address: Hillside, Baguio City
EDMAR L. SAMELO, Sanitary Engineer
PRC NO. 3059 VALIDITY: September 7, 2019
Lot 7, Block 3 Crystaldale Subdivision,
Bakakeng Central, Baguio City, Philippines
CARLOS & HELEN BARREDO
9715 Pililia St. Santiago Village, Makati City, Metro Manila
P-102
PTR NO. 3448712 DATE: January 2019
PLACE: BAGUIO CITY TIN: 471-667-438-000
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
DS DS DS
CO CO CO
FD FD FD

50Ø VTR
100Ø vent 100Ø vent 100Ø vent 50
Ø RD
FD sink FD sink sink FD
VP

100Ø SB

100Ø SB

100Ø SB
CO CO CO C. 50
WC 100Ø SB WC 100Ø SB 100Ø SB WC O. Ø
FD
LAV VP
100Ø SS 100Ø SS 100Ø SS 50 WC C.O
Ø .
50Ø WH 50Ø WH 50Ø WH 50Ø WH 50Ø WH 50Ø WH VP 75
. WD Ø
(WEEP HOLE) C.O C.O FD DP

100Ø SB

100Ø SB

100Ø SB
. LAV

100Ø DS
FD SP
WC 0Ø
ADCB ADCB ADCB 100Ø vent 100Ø vent 100Ø vent 10

100Ø SS
FD sink FD sink sink FD
C.O. ADCB
CO CO CO CO CO CO sink
WC 100Ø SB WC 100Ø SB 100Ø SB WC
15

15

15
D


C.O



DS DS DS RD C.

D
. 7
D

P
15
CB CB CB O.
P

P
LAV 5Ø
FD DP
sink sink sink WC 100
75Ø SB 75Ø SB 75Ø SB AAV Ø CB
co co co DP .
SINK C.O DP

C.O 75Ø 15
. DP
L3 DRAINAGE LAYOUT FD
Ø
SP
150Ø DP

150Ø DP

150Ø DP

0
C.O 10
3 .

100Ø DS
1:100 M

100Ø SS

150Ø DS
100Ø vent 100Ø vent 100Ø vent C.
100Ø DS 100Ø DS 100Ø DS O. WC
FD sink FD sink sink FD FD
100Ø SB

100Ø SB

100Ø SB

FD FD FD 10
CO CO CO FD 0Ø

trench
WC 100Ø SB WC 100Ø SB 100Ø SB WC SP

trench

trench
CB

100Ø SS
SS DS SS DS DS SS DP

15

150Ø DS
50Ø SB

50Ø SB

50Ø SB

SS CB SS CB CB SS

10 DP
0Ø 0Ø CB
CB DP 10
sink sink sink DP
TO E 0Ø

150Ø
DP

DP
15

100Ø SB
100Ø SB
100Ø SB
CO 50Ø SB CO CO 50Ø SB CO CO 50Ø SB CO E CT LIN
E

150Ø

150Ø
NN AG NK
CO AIN

DP
TA
TIC
DR
P
SE

TO E
E CT LIN
WC FD WC FD FD WC NN G E
CO CO CO CO AINA
DR
CB CB CB

TYPICAL
4
ISOMETRIC (UNIT-B)

150Ø DP
150Ø DP
NTS
150Ø DP
100Ø DP

100Ø DP

100Ø DP
100Ø DS 100Ø DS 100Ø DS
FD FD FD
trench

DS DS DS
trench

trench

100Ø DP 100Ø DP 100Ø DP


CB CB CB

L2 DRAINAGE LAYOUT septic septic septic


1
L1 DRAINAGE LAYOUT
2 tank tank tank 1:100 M
1:100 M
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
DRAINAGE LAYOUT
PROPOSED THREE LEVEL TRIPLEX
e-mail: edmar0792@yahoo.com
Address: Hillside, Baguio City
EDMAR L. SAMELO, Sanitary Engineer
PRC NO. 3059 VALIDITY: September 7, 2019
Lot 7, Block 3 Crystaldale Subdivision,
Bakakeng Central, Baguio City, Philippines
CARLOS & HELEN BARREDO
9715 Pililia St. Santiago Village, Makati City, Metro Manila
P-103
PTR NO. 3448712 DATE: January 2019
PLACE: BAGUIO CITY TIN: 471-667-438-000
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
STRUCTURAL NOTES AND SPECIFICATIONS:

CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.


STRUCTURAL GENERAL NOTES
PROPOSED THREE LEVEL TRIPLEX STRUCTURAL SPECIFICATIONS

e-mail: edmar0792@yahoo.com
Address: Hillside, Baguio City
EDMAR L. SAMELO, Civil Engineer
PRC NO. 138841 VALIDITY: September 7, 2021
Lot 7, Block 3 Crystaldale Subdivision,
Bakakeng Central, Baguio City, Philippines
CARLOS & HELEN BARREDO
9715 Pililia St. Santiago Village, Makati City, Metro Manila
S-101
PTR NO. 3448712 DATE: January 2019
PLACE: BAGUIO CITY TIN: 471-667-438-000
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
T.O.S. T.O.S. T.O.S.
SOG1 SOG1 SOG1
EL=5.40 m EL=4.80 m EL=4.20 m
2000 2300 2000 800 2500
2000

C1/ F1 C1/F2

1400

1400
C1/F1 C1/ F1

500

2000

2000

2500
2000
GB3 GB3 GB3
1 1 250
500
250
500
250
500
250
500

90
°
undisturbed earth

2800
6000

6000

B2

B3

B3

B2
3000 2500 2350 5000 SOG1 SOG1 SOG1
200mm thick concrete retaining wall. See detail 3 @ sheet S-105

400
stairwell stairwell stairwell

1950

1950

1950
w/ 2-16Ø @ w/ 2-16Ø @ w/ 2-16Ø @
1100 1100 1100
perimeter perimeter perimeter

2500

3000

3500
3000

2 250
500 GB1
250
500 GB1
250
500 GB1
250
500 2 250
500
B1
250
500
B1
250
500
B1
250
500

C1 C1 C1 C1
C1/F3 C1/F2 SOG1 T.O.S. T.O.S. T.O.S.
C1/F4 EL=5.50 m EL=4.90 m EL=4.30 m
SOG1 T.O.S. SOG1 T.O.S. T.O.S.

1500
EL=2.80 m EL=2.20 m EL=1.60 m
T.O.S.
GB1

GB1
GB2

GB2
6000

6000
T.O.S. T.O.S.

B2

B3

B3

B2
EL=1.95 m EL=1.35 m EL=0.75 m SS1 SS1 SS1

1250
SOG1 SOG1 SOG1

*depe
rssbeam
oa
tccomodaet *depe
rssbeam
oa
tccomodaet *depe
rssbeam
oa
tccomodaet
&soltm
ripie &soltm
ripie &soltm
ripie C1 C1 C1 C1

3000
B1 B1 B1
2500

*GB1 *GB1 *GB1


3 250
500
250
500
C1/
250
500
C1/
250
500 3 250
500
250
500
250
500
250
500

C1/
1500

1500

CB1

CB2

CB2
F1 F1 T.O.S. T.O.S. T.O.S.

CB1
C1/F2 F3 CS1 EL=5.425m CS1 EL=4.825m CS1 EL=4.225m
2000 2300 2000 300 3000

SLAB EDGE SLAB EDGE SLAB EDGE 250


EL=1.80 m EL=1.20 m EL=0.60 m 250
2000

2000

200

200
DGE
W A LK E
SIDE .83 m
EL=1 GE
K ED
I DE WAL
S .20 m
50 50
EL=1
exis EDG
E
ting W ALK
side E
SID .60 m
w al k EL=0

DG
ED
E
GE
AA KE
LLK
4300 4300 DEEWW 4300 4300
SIID
S .00 m
EL=0 50 50
A B C D A B C D

1
FOUNDATION PLAN 2
L2 FRAMING / FOUNDATION PLAN
1:100 M 1:100 M
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
STRUCTURAL FRAMING PLANS
PROPOSED THREE LEVEL TRIPLEX
e-mail: edmar0792@yahoo.com
Address: Hillside, Baguio City
EDMAR L. SAMELO, Civil Engineer
PRC NO. 138841 VALIDITY: SEPTEMBER 7, 2021
Lot 7, Block 3 Crystaldale Subdivision,
Bakakeng Central, Baguio City, Philippines
CARLOS & HELEN BARREDO
9715 Pililia St. Santiago Village, Makati City, Metro Manila
S-102
PTR NO. 3448712 DATE: January 2019
PLACE: BAGUIO CITY TIN: 471-667-438-000
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
2x6 G.I. PURLINS SPACED 2x2X41" ANGLE BAR W/ 21" DYNA
@ 600mm O.C. BOLT SPACED @ 600mm O.C.
REST OVER ANGLE BAR ATTACH TO PLASTERED WALL

RB2 RB2 RB2

CB1

RB1

RB1

RB1

RB1
CB2
CB1

CB2
1400

1400
CS1 CS1 CS1
B1 B1 B1
1 250
500
C2 C2
250
500
C2
250
500
C2
250
500 1

SS1 SS1 SS1

RB1

RB1

RB1

RB1
B2

B3

B3

B2
6000

6000
stairwell 1950
stairwell stairwell

1950

1950
1100 1100 1100

2 250
500 B1
250
500 B1
250
500 B1
250
500 2 RB1 RB1 RB1
C2 C2 C2 C2
T.O.S. T.O.S. T.O.S.
EL=8.20 m EL=7.60 m EL=7.00 m

RB1

RB1

RB1

RB1
6000

6000
B2

B3

B3

B2
SS1 SS1 SS1

C2 C2 C2 C2
B1 B1 B1 RB1 RB1 RB1
3 250
500
250
500
250
500
250
500 3

CB2
T.O.S.
1500

1500

CB1

CB2

CB1
CB1

CB2

T.O.S. T.O.S. T.O.S. SC-1 T.O.S. T.O.S.

CB1
CB2

CS1 CS1 CS1 EL=10.825m SC-1 SC-1


EL=8.125 m EL=7.525 m EL=6.925 m EL=10.225m EL=9.625m

250 250
250 250
2000

2000
200

200
200

200
50 50

4300 4300 4300 4300

50 50
A B C D A B C D

1
L3 FRAMING PLAN 2
ROOF FRAMING PLAN
1:100 M 1:100 M
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
STRUCTURAL FRAMING PLANS
PROPOSED THREE LEVEL TRIPLEX
e-mail: edmar0792@yahoo.com
Address: Hillside, Baguio City
EDMAR L. SAMELO, Civil Engineer
PRC NO. 138841 VALIDITY: SEPTEMBER 7, 2021
Lot 7, Block 3 Crystaldale Subdivision,
Bakakeng Central, Baguio City, Philippines
CARLOS & HELEN BARREDO
9715 Pililia St. Santiago Village, Makati City, Metro Manila
S-103
PTR NO. 3448712 DATE: January 2019
PLACE: BAGUIO CITY TIN: 471-667-438-000
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
WIDTH
RB1 (ROOF BEAM) RB2 (ROOF BEAM) C1 (FOUNDATION TO 2F) C2 (3F TO ROOF BEAM)
250 8-20Ø grade 40 MAIN BARS; 250 4-20Ø grade 40 MAIN BARS;
250 250 125

10Ø Ties: 10Ø Ties:


2 @ 50mm
350

350

350
2 @ 50mm

500

500
5@100mm 5@100mm

60
5@125mm,

0
5@125mm,

ty
Rest @ 200 mm

p
AT SUPPORTS AT MIDSPAN AT SUPPORTS & MIDSPAN Rest @ 200 mm
2-16Ø Cont. Top Bars 2-16Ø Cont. Top Bars 1-16Ø Cont. Top Bars

DEPTH
2-16Ø Extra Top Bars 2-16Ø Extra Bot Bars 1-16Ø Cont. Bot Bars NOTES:
2-16Ø Cont. Bot Bars 2-16Ø Cont. Bot Bars 1. MINIMUM 28-DAY CYLINDER COMPRESSIVE STRENGTH SHALL BE 21 MPA (3,000 PSI)
10 Ø STIRRUPS 10 Ø STIRRUPS 2. ALL MAIN BARS SHALL BE DEFOMED INTERMEDIATE GRADE, fy = 275 MPA (40,000 PSI)
2@50mm, 10@75mm, rest @ 150mm O.C. 2@50mm, 10@75mm, rest @ 150mm O.C. 3. LATERAL TIES SHALL BE DEFOMED GRADE, fy = 275 MPA (40,000 PSI)
4. PROVIDE 40mm CONCRETE COVER PROTECTION.
CB1 (CANTILEVERED BEAM) CB2 (CANTILEVERED BEAM) 5. SPLICES SHALL BE LAPPED AT A MINIMUM LENGTH OF 40 TIMES THE DIAMETER
6. ALL SPLICES SHALL BE LOCATED NEAR THE MID HEIGHT LEVEL
250
7. NO MORE THAN 50% OF THE TOTAL NUMBER OF MAIN BARS SHALL BE SPLICED AT
250 AT SUPPORT ANY SAME LEVEL LOCATION
3-16Ø cont. Top Bar
2-16Ø cont. Extra Top Bar

363
AT SUPPORT
3-16Ø Cont. Top Bars
2-16Ø cont. Bot Bar
COLUMN DETAILS PLAN
500

725
2-16Ø Cont. Bot Bars 3-16Ø cont. Top Bar 2
1:30 M

363
2-16Ø cont. Extra Top Bar NATURAL GRADE LEVEL
2-16Ø cont. Bot Bar

10 Ø STIRRUPS 10 Ø STIRRUPS

TYPICAL FOOTING DEPTH


2@50mm, 10@75mm, rest @ 150mm O.C. 2@50mm, 10@75mm, rest @ 150mm O.C.

B1 (BEAM) B2 (BEAM) B3 (BEAM)

2000
250 250
250 250
AT SUPPORTS AT MIDSPAN
3-16Ø Cont. Top Bars 3-16Ø Cont. Top Bars

363

363
2-16Ø Extra Top Bars 2-16Ø Extra Bot Bars 75 75
AT SUPPORTS & MIDSPAN AT SUPPORTS & MIDSPAN 3-16Ø Cont. Bot Bars 3-16Ø Cont. Bot Bars

725
3-16Ø Cont. Top Bars

725
500

500

5-16Ø Cont. Top Bars


3-16Ø Cont. Bot Bars

HEIGHT
3-16Ø Cont. Bot Bars 3-16Ø Cont. Top Bars 3-16Ø Cont. Top Bars 600

363

363
2-16Ø Extra Top Bars 2-16Ø Extra Bot Bars
3-16Ø Cont. Bot Bars 3-16Ø Cont. Bot Bars

75
10 Ø STIRRUPS 10 Ø STIRRUPS 10 Ø STIRRUPS SECTION UNDISTURBED SOIL
2@50mm, 10@75mm, rest @ 150mm O.C. 2@50mm, 10@75mm, rest @ 150mm O.C. 2@50mm, 10@75mm, rest @ 150mm O.C.
50mm THICK COMPACTED GRAVEL BASE
GB1 (GRADE BEAM) GB2 (GRADE BEAM) GB3 (GRADE BEAM)
TAG LENGTH X WIDTH HEIGHT REINFORCEMENTS
250 250 250 250
AT SUPPORTS
F1 2000x2000 300 mm 20Ø spaced @ 200mm O.C.B.W.
3-16Ø Cont. Top Bars
2-16Ø Extra Top Bars AT MIDSPAN
363

363

3-16Ø Cont. Top Bars AT SUPPORTS & MIDSPAN


AT SUPPORTS & MIDSPAN 2-16Ø Cont. Bot Bars
3-16Ø Cont. Bot Bars F2 2500x2500 350 mm 20Ø spaced @ 200mm O.C.B.W.
500

500
5-16Ø Cont. Top Bars
725

725

3-16Ø Cont. Top Bars


3-16Ø Cont. Bot Bars 3-16Ø Cont. Top Bars 3-16Ø Cont. Bot Bars
3-16Ø Cont. Top Bars
363

20Ø spaced @ 200mm O.C.B.W.


363

2-16Ø Extra Top Bars F3 3000x3000 400 mm


2-16Ø Cont. Bot Bars 3-16Ø Cont. Bot Bars

F4 3000x5000 450 mm 20Ø spaced @ 200mm O.C.B.W.


10 Ø STIRRUPS 10 Ø STIRRUPS 10 Ø STIRRUPS
2@50mm, 10@75mm, rest @ 150mm O.C. 2@50mm, 10@75mm, rest @ 150mm O.C. 2@50mm, 10@75mm, rest @ 150mm O.C.
FOOTING NOTES:
1. FOOTINGS ARE DESIGNED TO REST ON SOIL WITH A MINIMUM SOIL BEARING
CAPACITY OF 150 KPA.
LENGTH / 3 LENGTH / 3 2. NO FOOTING SHALL REST OF FILL.
3. PROVIDE MINIMUM FOOTING EMBEDMENT OF 2000mm FROM NGL.
4. FOOTING BARS SHALL BE DEFORMED INTERMEDIATE GRADE 40.
5. PROVIDE 50mm THICK COMPACTED GRAVEL BEDDING.
6. THE MINIMUM 28 DAY CYLINDER COMPRESSIVE TEST SHALL BE 3000 psi
H

7. PROVIDE 75mm CONCRETE COVER PROTECTION.

BEAM DETAILS
L/5 L/5
1
FOOTING DETAILS
3 LENGTH (CLEAR SPAN)
1:30 M
1:30 M
CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.
FOOTING DETAILS
PROPOSED THREE LEVEL TRIPLEX COLUMN DETAILS

e-mail: edmar0792@yahoo.com
Address: Hillside, Baguio City
EDMAR L. SAMELO, Civil Engineer
PRC NO. 138841 VALIDITY: SEPTEMBER 7, 2021
Lot 7, Block 3 Crystaldale Subdivision,
Bakakeng Central, Baguio City, Philippines
CARLOS & HELEN BARREDO
9715 Pililia St. Santiago Village, Makati City, Metro Manila
BEAM DETAILS S-104
PTR NO. 3448712 DATE: January 2019
PLACE: BAGUIO CITY TIN: 471-667-438-000
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BUILDING PERMIT APPLICATION
LENGTH
PART OF HALLWAY
200 600 600 LENGTH /4 LENGTH/ 2 LENGTH/ 4
GRASS BY

125
L2 TOP OF SLAB OWNER
FFL=varies
150

75
COMPACTED COMPACTED
BACKFILL BACKFILL

LENGTH/ 4
RIPRAP

2100
GATHERED
16Ø VERTICAL BARS FROM SITE

2575
SPACED @ 300 O.C. 2" DIA PVC
DRAIN PIPE
16Ø HOROZONTAL BARS
PART OF SPACED @ 600 O.C.
STORAGE

150
200
APPLY MORTAR

500
BED EVERY 1M
L1 TOP OF SLAB HEIGHT
FFL=varies

LENGTH/ 2
UNDISTURBED

LENGTH
600

SOIL

1400
200

600

CONC. RET. WALL RIPRAP

LENGTH/ 4
3
DETAILED SECTION 4
DETAILED SECTION
1:40 M 1:40 M

FLOOR SLAB TYPES


SLAB 135 °
TAG TOP BAR Reinforcement BOTTOM BAR Reinforcement REMARKS ° 135
THICKNESS
SS1

BEAM

BEAM
12Ø @ 300mm O.C.
125mm 12Ø @ 300mm O.C.B.W. refer to Diagramatic Detail
(suspended slab) (SHORTER SPAN)
L;ENGTH /4

LENGTH/ 4 LENGTH/ 2
LENGTH

SOG1
125mm - 12Ø @ 400mm O.C.B.W. -
(slab on grade)
12Ø TOP BARS @ 300mm O.C. AT SHORTER SPAN
12Ø BENT BARS @ 300mm O.C. BOTHWAYS
CS1 provide minimum 12Ø BOTTOM BARS @ 300mm O.C. BOTHWAYS
125mm 12Ø @ 150mm B.W. -
(cantilevered slab) 500mm Anchorage

2
SLAB SCHEDULE 1
DIAGRAMMATIC DETAIL FOR SS1
NTS NTS

CONSULTANT PROJECT NAME OWNER SHEET CONTENTS SHEET NO.


SLAB DETAILS
PROPOSED THREE LEVEL TRIPLEX RETAINING WALL DETAILS

e-mail: edmar0792@yahoo.com
Address: Hillside, Baguio City
EDMAR L. SAMELO, Civil Engineer
PRC NO. 138841 VALIDITY: SEPTEMBER 7, 2021
Lot 7, Block 3 Crystaldale Subdivision,
Bakakeng Central, Baguio City, Philippines
CARLOS & HELEN BARREDO
9715 Pililia St. Santiago Village, Makati City, Metro Manila
S-105
PTR NO. 3448712 DATE: January 2019
PLACE: BAGUIO CITY TIN: 471-667-438-000
COPYRIGHT RESERVED. THIS PLAN AND DESIGN ARE, AND AT ALL TIMES REMAIN THE EXCLUSIVE PROPERTY OF THE
ARCHITECT OF RECORD AND CANNOT BE USED OR REPRODUCED WITHOUT THE ARCHITECT'S WRITTEN CONSENT. FOR BIDDING PURPOSES

Vous aimerez peut-être aussi