FOUNDATION CALCULATION
Estimate Pile Number of DM Water Treatment Foundation and Check Pile Cap Bearing Capacity
1 QUALITY OF MATERIAL
Deformed reinforcing
2 yield strength 4000 Kg/cm2
steel bar (fy)
Plain reinforcing
3 yield strength 2400 Kg/cm2
steel bar (fy)
C-50 ( compressive strength at 28 days ) 500 Kg/cm2
4 Pile dia 400 mm
Class A ( Axle Load Allowable 110 ton
2 PILE CAPACITY
Width B = 1800 mm
Length L = 1800 mm
Thickness Slab T = 600 mm
Depth D = 800 mm
F = 200 mm
Concrete Cover d' = 70 mm
Rebar Size f = 19 mm
Efective width, d = T-d'-0.5 f = 521 mm
Pedestal l = 500 mm
b = 800 mm
Square Pile 400 mm x 400 mm
Design Pile Bearing Capacity = 84 ton
1
PLTU BUNTOK 2X7MW NO T3125 - CA/C/T0502-01-RV.A
Fx = 4922 kg
Fy = 36548 kg
Fz = 11065 kg
Pv max = Pv
n
n = 1 ( pile number )
= 42.79
1
Pv max = 42.79 ton 5.3492
P comp. all / P = 84.18 / 42.79
= 1.967046 > 1.0 … (OK)
r min = 1.4 / fy
= 1.4 / 392
= 0.0036
2
PLTU BUNTOK 2X7MW NO T3125 - CA/C/T0502-01-RV.A
r max = 0.75 * rb
0.85*b1*f'c 600
= 0.75 x x{ }
fy 600 + fy
= 0.75 x 0.85 * 0.85 *29 x 600
392 600 +392
= 0.75 x 0.053 x 0.60
= 0.024
As min = r min * B * d r min = 0.0036
= 33.5 cm2
As req = 33.46 cm2 used D 16
(17 D16 - 100 )
As min = 1 % * Ag
= 25 cm2
As req = Max ( AS min, AS1 )
As req = 25.00 cm2 Use D 16
= 16 D16
Stirups
H lateral = Vu =Fx Vu = 4922.0 kg
= 4.92 ton
Nu = Fy Nu = 36548.0 kg
3
PLTU BUNTOK 2X7MW NO T3125 - CA/C/T0502-01-RV.A
Use f 10 - 150
S = 150 mm
Vc = (1+(Nu/14Ag)) 1
/6 fc'1/2 bw d Nu , Ag in (N/mm2)
= 22.30 ton
Vs = Av. Fy.d
s
Vs = 164200.58 N = 16.42 ton
Vn = Vc + Vs
= 38.72 ton