Académique Documents
Professionnel Documents
Culture Documents
Worksheet
TheSolarPlanner.com
This workbook was created With MS Excel. Select the "Save As"
command on the File Menu now and save the document in your
version. If you get a "read only" error message, save it under
another name. You may need to close the downloaded file in the
internet browser and reopen the new saved workbook in Excel.
Check to see that both the vertical scroll bar (to your right) and
the horizontal scroll bar below are visible. You should also see
tabs like "Worksheet" and "Resources" at the bottom of the
page. By clicking these tabs, you can navigate around the
workbook. If you don't see them, do the following: Select the
"Arrange" command from the Window Menu, then click on
"Tiled".
Max. High
Step 1: Size the source
Temperature Solar ABC's
circuit conductors.
(Celsius)
Step 5: Perform voltage drop calculations. Enter the number of modules in the array(s).
Module
Module Cable Length Module
Operating 48
in inches Count
Volts Vpm
Conductor
Length ft Ohms per kft
gauge
Calculations:
Note: Step 5 is
Inverter optional. It's accepted
Circuit: Source PV Output practice not to allow the
Out
voltage drop to go too
Voltage much higher than 3%,
Drop but the NEC doesn't
regulate this amount.
Circuit Volts 120 V
Percentage
0 0 0
Check box to
Scroll right for
use the next
Overcurrent
beefier wire New size New size New Size
Protection Ampacity
gauge for this
Check and EGC Sizing
circuit.
New Voltage
Drop/%
Do not remove these tables.
Ohms per
Voltage Drop Resistance Gauge kft
for Stranded Wire
1 0.154
2 0.194
3 0.245
4 0.308
6 0.491
8 0.778
10 1.24
12 1.98
Wire Sizing Worksheet After completing this page, click on the
Report tab below to view your results.
Step 6: Compare wire gauge ampacities to any overcurrent device
ratings.
Page 4
Note: Overcurrent protection in the PV Source and PV Output circuits may be optional
when you use less than 3 strings. Check the NEC or ask a qualified expert for
guidance.
Fill in each box if you plan to use O.C. protection for that
If the last column above
circuit. An O.C. device is rated in amps. Use the size
reads "check wire gauge",
nearest to, but not less than, the Overcurrent Ampacity
the circuit may require a
Calculation. Click the Resources tab below for links to
beefier conductor. However,
O.C. device sizes. NOTE: Per NEC 690.8(B)(1)(c), for
if the O.C. Rating is the next
any O.C. device subject to an ambient temperature more
available size for the Derated
than 40˚C, you must implement the fuse or breaker's
Wire Ampacity value, you
manufacturer temp correction factors when selecting a size.
can stick with the gauge
Once you've selected O.C. devices, enter values in all
that's listed.
three boxes below.
Conductor Enter final conductor gauges after reading the red instructions above.
Gauges PV Source PV Output Inverter Out
Transformerless See
Step 7: Choose a ground wire and gauge for each circui
inverter selected. Step 3
If a transformerless inverter is used, the EGC (ground wire) for each
NEC Table 250.122
circuit must be rated to carry twice the Overcurrent Ampacity Calc.
For a normal inverter: If an O.C. device is used, pick a gauge that
corresponds to the Max Amps in NEC Table 250.122 (e.g. a 30-amp AWG Max Amps
breaker requires Gauge 10 wire). If no O.C. device is used, pick the
same gauge as the conductors, or beefier. For bare copper, the 12 = 20
minimum gauge is usually 6.
Click Resources tab or NEC
Tables for help.
PV Source PV Output Inverter Out 10 E 30
Wire Type: 0 0 10 C 60
The most commonly used wire type in the Source circuit is Bare
Copper - AWG 6. PV and Inverter Output wire types were picked in 8 = 100
Steps 2-3.
Do not remove these tables.
0 0 0 0
Note: PV Output/Inverter Out calculations assume the same conductor type and gauge.
0 Transformerless = Ungrounded. 0 0 0
Wire Length Hot ft. Neu. ft. EGC ft.
Wire Totals Use the list below when preparing a purchase order.
Modules: 0 Inverter: 0
Project Name: 0
Wire Sizing Calculators
Online Resource Links
Raceway/Conduit Fill Calculator
Electrician2.com
Conduit Fill Calculator Vist the TheSolarPlanner.com Worksheets Page for instr
Southwire.com
14 25 10 or less 1.15
14 35
Also applies
12 40 to these
wire types:
10 55
TBS, SA,
8 80 SIS, FEP,
FEPB, MI,
6 105
RHH, RHW- Scroll down for more tables…
4 140 2, THHN,
3 165 THHW,
2 190 THW-2,
XHH,
1 220 XHHW,
1/0 260 XHHW-2,
2/0 300 ZW-2
3/0 350
NEC Tables and Charts cont…