Infosys: Front-runner in energy efficiency- A Case Study


Focused efforts on smart buildings systems, retrofits, new building designs with an efficient
envelope, and renewable energy, have significantly reduced Infosys’s per capita energy
consumption in the last seven years. The high performance buildings built by Infosys have
demonstrated that with today’s technology we can design buildings which will consume one
third of the energy of normal buildings at no extra capital costs. Over the last seven years, the
company has been able to avoid consumption of over 880 million units of electricity, reducing
their per capita energy consumption by 46 percent as compared to the 2008 levels.

E
nergy is a precious resource, play- Building sector accounts for over 30% sign buildings which will consume one
ing a pivotal role in shaping our of the total energy consumed in India. We third of the energy of normal buildings at
country’s social and economic de- have estimated that, out of this, more than no extra capital costs. Over the last seven
velopment. Energy access, energy secu- 40% of energy use is taken up by heating years, the company has been able to avoid
rity, and climate change pose enormous and cooling systems. As corporates need consumption of over 880 million units of
challenge to India’s goal of achieving in- continuous power supply to run their busi- electricity, reducing their per capita energy
clusive economic growth. There is a huge ness operations, intervening in these areas consumption by 46 percent as compared
dependency on fossil fuels to meet the en- draws attractive reductions in energy use to the 2008 levels.
ergy needs. India is dependent on crude and costs. In the recent past, energy effi- All Infosys buildings are designed to
oil imports, about $125 billion annually, to ciency is gaining momentum among many achieve the new performance benchmarks
meet its energy demands, even as 300 mil- corporates. Push towards renewable ener- (see table 1). Infrastructure required for 1
lion of the population is without electricity. gy, energy efficient lighting, cooling, and million sq.ft is in table 2.
In the face of rising energy demands and heating system, etc. is being witnessed in Infosys has achieved significant energy
limited energy supply, the role of energy India. Infosys is leading from the front in savings by
efficiency in bridging the energy gap can- this area. It has made its buildings and op- 1. Developing super-efficient new
not be undermined. erations the most efficient ones and is still buildings,
Energy efficiency improvements have the continuing to do more with less. 2. Retrofitting existing buildings,
potential to accelerate economic growth Focused efforts on smart buildings sys- 3. Pushing boundaries and innovating,
and benefit the society at large. It yields tems, retrofits, new building designs with and
benefits across different levels of an econ- an efficient envelope, and renewable en- 4. Continuous monitoring to achieve
omy including, increased energy security, ergy, have significantly reduced Infosys’s highest levels of efficiency.
carbon emission mitigation, reduced ener- per capita energy consumption in the last
gy related expenditure, poverty alleviation, seven years. The high performance build- Super-efficient building designs
improved health and well-being, industrial ings built by Infosys have demonstrated Many buildings have over-designed sys-
productivity, and so on. that with today’s technology we can de- tems due to use of thumb-rule calculation
methodology, change of usage pattern,
etc. leading to inefficient operations. In-
TABLE 1 fosys has recognized that intervening in
Performance metric Infosys new design these areas can help fetch great results.
Energy Performance Index 75 kWh/m2/year Thus, Infosys focuses on bringing efficien-
Lighting design 0.48 W/sq.ft cy right from the design stage to elimi-
Air-conditioning design (Reduction in heat load) 750 sqft per TR
nate inefficiencies. Infosys buildings are
Total building electrical design 3.5 W/sq.ft
TABLE 2 designed with a super-efficient envelope
System Description Units Infosys new designs Conventional designs having appropriate north-south orienta-
Total electrical load MW 3.5 10.0 tion, insulated walls and roof, optimized
Transformer capacity MVA 4.0 12.0 window-wall ratio of less than 30%, nar-
DG set capacity MVA 5+2.5 15+3 row floor plate, and high performance
Annual energy consumption Million kWh 7.5 25 glazing with adequate shading. Window

4 energética india · JAN | FEB16


energy efficiency

Figure 1: Façade of Infosys SDB-1 building, Hyderabad.

design includes daylight pane, vision • Primary secondary systems in chiller These interventions have freed up almost
pane, light shelves, and other shading plants replaced with variable primary a third of the space that was previously oc-
devices which let in a good amount of inline pumps, resulting into about cupied in the plant room. Deep green ret-
natural light, removing the requirement 30% reduction in energy and about rofits in the air conditioning systems have
to switch on lights during the day. These 45% reduction in equipment helped achieve 15 MW connected load
interventions enable maximum daylight • In the air handling units, conventional reduction in the last four years. These ret-
penetration into the building with no fan system replaced with EC (Electroni- rofits have a short payback period of less
glare, providing a natural and healthy cally Commutated) fans leading to than three years with the life of equipment
work environment to the employees. nearly 50% reduction in energy being more than ten years, thus making
Today, the company has 14 buildings • Variable speed drives installed in each them financially viable for implementation.
with LEED Platinum and 4 buildings with and every equipment
GRIHA 5-star rating. This covers a total of • Chiller plants are designed with series UPS retrofit:
about 5.25 million sq.ft. of built up area counter flow arrangement for opti- In addition, conventional UPS systems
with highest level of green certification. mum energy use have been replaced with energy efficient
We have also achieved an Energy Perfor- • Reduction in the number of chiller modular UPS systems to reduce installed
mance Index (EPI) of 75 kWh/ sq.m. / Year, plants from 54 to 41. capacity and energy consumption. Modu-
among the lowest in the industry. • Older air-cooled Variable Refriger- lar UPS systems offer highest level of effi-
ant Volume (VRV) units replaced with ciency and flexibility through a unique sys-
Deep green retrofits chilled-water-based units which are tem design with cutting-edge architecture,
While making the new buildings super- free from harmful refrigerants and re- consisting of independent hot swappable
efficient, Infosys realized the great po- quire lower maintenance as compared modules- about 5 to 10 in number. These
tential in the existing buildings. Thus, to the previous system modules allow online interchangeability
to make old buildings as efficient as the
TABLE 3
new ones, they undertook massive HVAC,
Description Old System New System Impact
lighting, and UPS system retrofits. These
Elimination of 120 UPS
deep green retrofits have significantly re- Number of UPS systems 350 230
systems
duced the connected load in four years. UPS Capacity 30200 KVA 20000 KVA 34% reduction
The short payback period of these pro- Efficiency 79% 93% 18% improvement
jects clearly demonstrates the viability of Number of batteries 19500 10000 49% reduction
TABLE 4
retrofits in improving efficiency by huge
Particulars Conventional UPS Modular UPS
numbers.
Design Load–80 KVA 80 KVA x 2 20 KVA x 5
Total installed KVA 160 KVA 100 KVA
Chiller Plant Room retrofit: Operating daytime load -70 KVA 70 KVA 70 KVA
• Complete re-engineering of chiller Actual load on each UPS 44% 70%
plants minimized piping, eliminated Day time efficiency of UPS 84% 93%
use of balancing valves, thereby reduc- Operating night time load–35 KVA 35 KVA 35 KVA
ing pressure drop and right sizing the Actual load on each UPS 22% 35%

pumps Night time efficiency of UPS 73% 92%

energetica india · JAN | FEB16 5


energy efficiency

cost effective in India and be a major con-


straint for adoption.
Radiflux radiant cooling solution: To
overcome the limitations of these radiant
cooling systems, Infosys has developed
Radiflux radiant cooling solution in- house.
Radiflux is a high efficiency, high quality,
reliable, affordable and quick to install
cooling solution. It delivers about two
times more capacity for the same coverage
area, than other radiant panel solutions
available in the market today. Radiflux is
designed, developed and made in India so-
lution for the world, with patents pending
in US, Europe and India.

Continuous monitoring:
Infosys strongly believe that data talks.
Figure 2: Roof painted white to minimize heat ingress into the building.
Thus, the company is also monitoring and
measuring efficiency improvements in
of UPS systems. Each module within the a reduction of over 60% in the total light- real-time, through their central command
UPS system has a rectifier, inverter, static ing energy consumption. centre in Bangalore. The central command
bypass, and a processor, thereby ensuring center is managing the smart buildings,
continuous power supply even if one mod- Innovative technologies: energy management systems, solar PV
ule of the entire system fails. In addition to undertaking new energy ef- systems, data center power usage effec-
The table 3 shows the number, installed ficient buildings and deep retrofit projects tiveness, battery management systems,
capacity, and efficiency of the systems in existing buildings, Infosys has made its energy consumption for sewage treatment
both before and after retrofit, across Info- buildings live labs to test and adopt new plants, and weather stations for their per-
sys campuses in India. innovative technologies. formance across Infosys campuses from
In table 4 there is an example of UPS Radiant slab based cooling: Infosys SDB one single place. Operations data flow-
configuration comparison between con- 1 building in Hyderabad is the first radiant ing into the command center from various
ventional and modular UPS systems. cooled commercial building in India and systems across campuses is used to review
The average efficiency of the UPS system the biggest comparison of cooling systems and optimize operations, drive resource
has improved by 18 per cent, thereby re- in the world. The building is a live lab split conservation, perform fault detection and
ducing energy use and energy costs to a into two symmetric halves, one half with diagnostics, and ensure high level of com-
great extent. UPS retrofit has helped Info- conventional air conditioning and the oth- fort and indoor air quality to our building
sys achieve about 10 MW connected load er with radiant cooling. Data over the last occupants. The data helps in evaluating
reduction in the last four years. UPS retro- five years show that radiant cooling tech- and validating our current design, and also
fit has a short payback period of less than nology is 30% more efficient than conven- improving design for future buildings and
three years, making it financially viable for tional cooling. systems.
others to emulate. Radiant panel based cooling: Infosys Infosys is constantly pushing bounda-
is the first in India to implement the radi- ries and setting new benchmarks for the
White roofs: ant panel-based cooling system. Pipes are industry to achieve highest level of effi-
Additionally, Infosys roofs have been paint- embedded in panels of modular sizes like ciency. Infosys has made an unassailable
ed with High-albedo white paints (SRI val- ceiling tiles, and are then interconnected business case for large companies to im-
ue greater than 75 percent) to reduce heat to allow water flow. Cooling is achieved plement energy efficiency initiatives. The
gain and minimize air conditioning loads. when the occupants, computers, lighting company has demonstrated that these ini-
According to Infosys, this minimizes solar and equipment radiate directly to the cold tiatives have an attractive payback period
heat gain by reducing the roof’s surface ceiling. Fresh air is supplied through an for other corporates and wider communi-
temperature by up to 10degC. Infosys has air system that maintains pleasant indoor ties to emulate. All the data- backed ener-
also taken up lighting system retrofit to air quality. The company believes that this gy efficiency initiatives are easily replicable
optimize its lighting energy consumption. system is the solution for cases with spe- in large- scale across the globe in a cost
Conventional lighting fixtures have been cific ceiling designs and retrofits in existing effective manner. Infosys wants to lead a
replaced with efficient LED light fixtures buildings to achieve considerable energy systemic change and build a low carbon
and with essential controls such as occu- reduction. But, at the same time the avail- future for the benefit of the society and
pancy and daylight sensors. This has led to able radiant cooling solution may not be environment 

6 energetica india · JAN | FEB16