• On-load tap changers – the only moving part in a typical
power transformer • They represent a significant number of total transformer faults • The possibility pof „On-line“ testing • When the failure is present aditional tests are desirable to make good decision
• Analysis of vibrations measured on the external OLTC
tank using accelerometers • The result is a graph • The signal waveform is analyzed for characteristic points • The shape depends on the method of OLTC operation
the transformer tank where OLTC is placed • Screws, wax or magnet is used for sensor connection • Always connect to the same spot and in same way to get comparable results
„Online“ test • The vibration recording is possible when transformer is on-line • Safety is on the first place!!! • OLTC motor current roecording has aditional benefits
„Offline“ test • Complementary method with OLTC motor current measurement, DVtest / DRM testing, winding resistance measurement, DGA • Each test gives additional information about OLTC condition