MODERN POWER SYSTEM

Power Flow through a Transmission Line:


Power Flow through a Transmission Line – So far the transmission line performance equation was presented in the form of voltage and current
relationships between sending-and receiving-ends. Since loads are more often expressed in terms of real (watts/kW) and reactive (VARs/ kVAR) power, it
is convenient to deal with transmission line equations in the form of sending- and receiving-end complex power and voltages. While the problem of flow of
power in a general network will be treated in the next chapter, the principles involved are illustrated here through a single transmission line (2-node/2-bus
system) as shown in Fig. 5.17.

Let us take the receiving-end voltage as a reference phasor (VR=|VR|∠0°) and let the sending-end voltage lead it by an angle δ(Vs=|Vs|∠δ). The angle δ is
known as the torque angle whose significance has been explained in Chapter 4 and will further be taken up in Chapter 12 while dealing with the problem
of stability.

The complex power leaving the receiving-end and entering the sending-end of the transmission line can be expressed as (on per phase basis)

Receiving- and sending-end currents can, however, be expressed in terms of receiving- and sending-end voltages [see Eq. (5.1)1 as

http://www.eeeguide.com/power-flow-through-a-transmission-line/ 1/8
8/30/2017 Power Flow through a Transmission Line - EEEGUIDE

Let A, B, D, the transmission line constants, be written as

Therefore, we can write

In the above equations SR and Ss are per phase complex voltamperes, while VR and Vs are expressed in per phase volts. If VR and Vs are expressed in
kV line, then the three-phase receiving-end complex power is given by

http://www.eeeguide.com/power-flow-through-a-transmission-line/ 2/8
8/30/2017 Power Flow through a Transmission Line - EEEGUIDE

This indeed is the same as Eq. (5.58). The same result holds for Ss. Thus we see that Eqs. (5.58) and (5.59) give the three-phase MVA if Vs and VR are
expressed in kV line.

If Eq. (5.58) is expressed in real and imaginary parts, we can write the real and reactive powers at the receiving-end as

Similarly, the real and reactive powers at sending-end are

It is easy to see from Eq. (5.61) that the received power PR will be maximum at

http://www.eeeguide.com/power-flow-through-a-transmission-line/ 3/8
8/30/2017 Power Flow through a Transmission Line - EEEGUIDE

Thus the load must draw this much leading MVAR in order to receive the maximum real power.

Consider now the special case of a short line with a series impedance Z. Now

Substituting these in Eqs. (5.61) to (5.64), we get the simplified results for the short line as

for the receiving-end and for the sending-end

The above short line equation will also apply for a long line when the line is replaced by its equivalent- π (or nominal- π) and the shunt admittances are
lumped with the receiving-end load and sending-end generation. In fact, this technique is always used in the load flow problem to be treated in the next
chapter.

From Eq.(5.66), the maximum receiving-end power is received, when δ=θ

http://www.eeeguide.com/power-flow-through-a-transmission-line/ 4/8
8/30/2017 Power Flow through a Transmission Line - EEEGUIDE

Normally the resistance of a transmission line is small compared to its reactance (since it is necessary to maintain a high efficiency of transmission), so
that θ= tan-1 X/R 90′; where Z = R + jX. The receiving-end Eqs. (5.66) and (5.67) can then be approximated as

Equation (5.72) can be further simplified by assuming cos δ≈1, since δ is normally small*. Thus

Let |VS|-|VR|=|ΔV|, the magnitude of voltage drop across the transmission line.

Several important conclusions that easily follow from Eqs. (5.71) to (5.74) are enumerated below:

For R≈0 (which is a valid approximation for a transmission line) the real power transferred to the receiving-end is proportional to sin δ(≈δ for small
values of δ ), while the reactive power is proportional to the magnitude of the voltage drop across the line.

The real power received is maximum for δ = 90° and has a value |Vs||VR|/X. Of course, δ is restricted to values well below 90° from considerations of
stability to be discussed in Chapter 12.
Maximum real power transferred for. a given line (fixed X) can be increased by raising its voltage level. It is from this consideration that voltage levels
are being progressively pushed up to transmit larger chunks of power over longer distances warranted by large size generating

http://www.eeeguide.com/power-flow-through-a-transmission-line/ 5/8
8/30/2017 Power Flow through a Transmission Line - EEEGUIDE

For very long lines voltage level cannot be raised beyond the limits placed by present-day high voltage technology. To increase power transmitted in
such cases, the only choice is to reduce the line reactance. This is accomplished by adding series capacitors in the line. This idea will be pursued
further in Chapter 12. Series capacitors would of course increase the severity of line over voltages under switching conditions.

As said in 1 above, the VARs (lagging reactive power) delivered by a line is proportional to the line voltage drop and is independent of δ. Therefore, in
a transmission system if the VARs demand of the load is large, the voltage profile at that point tends to sag rather sharply. To maintain a desired
voltage profile, the VARs demand of the load must be met locally by employing positive VAR generators (condensers). This will be discussed at
length in Sec. 5.10.

A somewhat more accurate yet approximate result expressing line voltage drop in terms of active and reactive powers can be written directly from Eq.
(5.5), i.e.

This result reduces to that of Eq. (5.74) if R = 0.

MORE RELATED ARTICLE


Introduction to Optimal System Operation
Introduction to Power Transmission Lines
Capacitance of a Three Phase Line Unsymmetrical Sp...
Double Circuit Three Phase Lines
Recent Trends in Power System Stability

http://www.eeeguide.com/power-flow-through-a-transmission-line/ 6/8
8/30/2017 Power Flow through a Transmission Line - EEEGUIDE

Series Compensation
Network Model Formulation
Gauss Seidel Method
Introduction to State Estimation of Power Systems
Tuned Power Lines
Sequence Impedance of Transmission Lines
Medium Transmission Line
Simple System
Interpretation of the Long Line Equation
Potential Difference between Two Conductors
Decoupled Load Flow Methods
Decentralized Control
Introduction to Symmetrical Fault Analysis
Use of Computers and Microprocessors
Power System Voltage Stability
Introduction to Modern Power System
Steady State Stability
Line Compensation
Digital LF Controllers
Optimal Load Flow Solution
Capacitance of a Three Phase Line Equilateral Spac...

http://www.eeeguide.com/power-flow-through-a-transmission-line/ 7/8
8/30/2017 Power Flow through a Transmission Line - EEEGUIDE

Methods of Voltage Control


Short Circuit Current Computation through Thevenin...
Static State Estimation of Power Systems
Construction of Sequence Networks of a Power Syste...

http://www.eeeguide.com/power-flow-through-a-transmission-line/ 8/8

Vous aimerez peut-être aussi