Académique Documents
Professionnel Documents
Culture Documents
BARACK
CHK APR
DATE ISSUE ISSUE
REV PREPARE CHECKED APPROVED OWNER
ISSUED STAGE PURPOSE
APPROVED
Historical Sheet
ATTACHMENT
CALCULATION SHEET FOR MAINTENANCE BARACK
1. GENERAL
1.1 OUTLINE PROJECT AND SCOPE
Project : NPK - Chemical Project 500,000 MPTY
Client : PT. Pupuk Iskandar Muda
Location : Lhokseumawe, Aceh
Structure : Maintenance Barack
Type : Concrete structure with shallow foundation
> Factor of safety for foundation stability refers to Design specification for Civil & Structure 26th pages :
Overturning : SFop = 2
Sliding : SFsp = 2
Bouyancy : SFbp = 1.1
Settlement : δall = 25
2. OUTLINE OF STRUCTURE
2.1 GENERAL DESCRIPTION
This calculation covers the design of structure and foundation for Security Guard. This building is supported by shallow foundation.
Perspective
CALCULATION SHEET FOR MAINTENANCE BARACK
Structure Dimension
Dimension of Structure
Length of structure Ls = 15.00 m
Width of structure Bs = 8.00 m
Height of structure Hs = 4.50 m
L = 15.00 m
B = 8.00 m
he = 4.50 m
2. Roofing Load
Dead Load due to roofing
2
Screed = 100 kg/m
2
Gypsum Ceiling w/ PVC = 20 kg/m
2
Total Load = 120 kg/m
3. Wall
Height of Wall Hbw = 4.50 m
Thickness of wall Thk = 0.15 m
2
Unit weight of Brickwall γbr = 350 kg/m
Brickwall load Wbr = Hbw * γbr
= 4.5 x 350 = 1575 kg/m
2
4. Floor tiles (3 cm thk, with plaster) = 96 kg/m
Dead Loads
Windward Wall Column Line A&D 4.50 UNI GX 49.13 0.85 0.80 0.18 2.00 49.13
Leeward Wall Column Line A&D 4.50 UNI GX 49.13 0.85 0.30 0.18 2.00 7.37
Side Wall Column Line 1&4 4.50 UNI GZ 49.13 0.85 0.70 0.18 3.75 76.46
Leeward Roof Column Line 1&4 4.50 UNI GY 49.13 0.85 0.90 0.18 2.00 57.48
Windward Wall Column Line 1&4 4.50 UNI GZ 49.13 0.85 0.80 0.18 3.75 92.11
Leeward Wall Column Line 1&4 4.50 UNI GZ 49.13 0.85 0.30 0.18 3.75 13.82
Side Wall Column Line A&D 4.50 UNI GX 49.13 0.85 0.70 0.18 2.00 40.78
Leeward Roof Column Line 1&4 4.20 UNI GY 49.13 0.85 0.70 0.18 3.75 76.46
CALCULATION SHEET FOR MAINTENANCE BARACK
Wind - X
Wind - Z
Wind Loads: X-direction and Z-direction
CALCULATION SHEET FOR MAINTENANCE BARACK
Seismic parameters based on the "Design Specification for Civil and Structure" Document are as follows.
Soil Type : Medium Soil
Fa = 1.288 g Site Coefficient at short Period
Ss = 0.640 g MCE reponse spectra parameter at short period
Fv = 1.767 g Site Coefficient at 1 second
S1 = 0.316 g MCE reponse spectra parameter at 1 second
SMS = Fa x Ss = 0.824 MCE reponse spectra acceleration at short period
SM1 = Fv x S1 = 0.559 MCE reponse spectra acceleration at 1 second
Sa = SDS x (0.4 + 0.6 Tf/T0) Respon spectra acceleration for Tf < T0
Sa = SD1/Tf Respon spectra acceleration for Tf > Ts
T0 = 0.2 SD1/SDs = 0.136
Ts = SD1/SDs = 0.678
SDS = 0.550
SD1 = 0.373
SDS x I SDS . I
V = Cs x W Cs = V = x Wt
R R
Therefore, the CS value,
Dir. Value Base Shear = 4403.85 Kg
Csx x 0.110 = 4.404 Ton
Csz z 0.110
CALCULATION SHEET FOR MAINTENANCE BARACK
4. ANALYSIS RESULTS
4.1 HORIZONTAL DISPLACEMENT (COLUMN SWAY.)
Allowable horizontal displacement = H/200
Displacement ( STAAD PRO ) Elev. Allow Check
Displ. Node L/C Horiz Vertic. Horiz Result H Sway
result < Allow Sway
X mm Y mm Z mm mm mm H/200
Max X 50 106 2.680 -0.900 0.831 2.946 4500 22.5 OK
Min X 51 109 -2.680 0.794 -0.794 2.906 4500 22.5 OK
Max Z 90 122 0.778 0.009 2.784 2.891 4500 22.5 OK
Min Z 96 113 0.992 -0.775 -2.735 2.905 4500 22.5 OK
Allowable horizontal deflection due to service load combinations including seismic loads = 0.015 hsx
Deflection amplification factor (SNI 03-1726-2012, table-9):
Cdx = 4.5
Cdz = 4.5
Mub 239.20
Rn = = = 41528.472 kg/m2 = 0.415 Mpa
0.9xbxd^2 0.9 x 1 x 0.08^2
Required Reinforcement
Ascal = ρcal x b x d Asmin = ρmin x b x Hf Asreq = max (Ascal, Asmin)
= 0.00085 x 1000 x 80 = 0.0018 x 1000 x 120 = max (68.23, 72)
= 68.23438914 mm2 = 72 mm2 = 72 mm2
Required Reinforcement
Ascal = ρcal x b x d Asmin = ρmin x b x Hf Asreq = max (Ascal, Asmin)
= 0.00038 x 1000 x 100 = 0.0018 x 1000 x 150 = max (37.6, 180)
= 37.5950175 mm2 = 180 mm2 = 180 mm2
FOUNDATION DIMENSION
Footing length df = 1.50 m Column length dk = 0.4 m
Footing width bf = 1.50 m Column width bk = 0.4 m
Footing area Af = 2.25 m
2 Column area Ak = 0.16 m
2
bf
Buoyancy Status =
bk ha OK, hw > hu, No buoyancy effect
df
dk
hu hb
z
hf
x
Hw 1.73 GWL
2 2
Rn = Mmax = 1300.11 = 6715.42 kg/m = 0.066 N/mm
0.8xbxd^2 0.8x1x0.242^2
ρmax = 0.028
ρmin = 0.0018
ρshrinkage = ρmin / n = 0.0009
Required Reinforcement
0.85 fc 2 Rn
cal 1 1 ρcal = 0.000165
fy 0.85 fc
0.5
Vc1 = 0.17 x ( 1 + (2/b) ) x (fc') x bo x d = 1584.7128 kN
0.5
Vc2 = 0.083 x ( ((as x d)/bo)+2 ) x (fc') x bo x d = 1487.9709 kN
0.5
Vc3 = 0.33 x (fc') x bo x d = 1025.4024 kN
I1 = = 0.285
I2 = = 0.064
Is = 1.157
If = 0.780
Iw = Is . If
= 1.157 x 0.78
= 0.9024