Safety notes 1
Requirements 2
SINUMERIK
Method of delivery and
loading the EPLAN Add-in 3
SINUMERIK 840D sl / 828D
SINUMERIK Integrate Create Siemens DQ-Topo and
submenus 4
MyConfig - EPLAN Electric P8 Add-
In Configuring with EPLAN Add-
Operating Manual
In 5
EPLAN adaptations 6
DRIVE-CLiQ types 7
Messages 8
List of abbreviations A
Valid for:
CMC software version 4.8
12/2017
A5E43099659B-AA
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified
personnel are those who, based on their training and experience, are capable of identifying risks and avoiding
potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in
this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
SINUMERIK documentation
The SINUMERIK documentation is organized into the following categories:
● General documentation/catalogs
● User documentation
● Manufacturer/service documentation
Additional information
You can find information on the following topics at the following address (https://
support.industry.siemens.com/cs/de/en/view/108464614):
● Ordering documentation/overview of documentation
● Additional links to download documents
● Using documentation online (find and search in manuals/information)
If you have any questions regarding the technical documentation (e.g. suggestions,
corrections), please send an e-mail to the following address
(mailto:docu.motioncontrol@siemens.com).
mySupport/Documentation
At the following address (https://support.industry.siemens.com/My/ww/en/documentation),
you can find information on how to create your own individual documentation based on
Siemens' content, and adapt it for your own machine documentation.
Training
At the following address (http://www.siemens.com/sitrain), you can find information about
SITRAIN (Siemens training on products, systems and solutions for automation and drives).
FAQs
You can find Frequently Asked Questions in the Service&Support pages under Product
Support (https://support.industry.siemens.com/cs/de/en/ps/faq).
SINUMERIK
You can find information about SINUMERIK at the following address (http://www.siemens.com/
sinumerik).
Target group
This publication is intended for machine operators using EPLAN.
There is also basic information for administrators who, for example, install EPLAN Add-In.
Benefits
A SINAMICS topology configured in EPLAN can be used in Create MyConfig Topo.
The SINAMICS topology is exported to EPLAN electric P8 as a file via the "Siemens DQ-Topo"
Add-In. This output file is imported for further use in Create MyConfig Topo. The data already
configured for the production of a machine can therefore continue to be used with immediate
effect in CMC.
Standard scope
This documentation only describes the functionality of the standard scope. Additions or
revisions made by the machine manufacturer are documented by the machine manufacturer.
Other functions not described in this documentation might be executable in the control. This
does not, however, represent an obligation to supply such functions with a new control or when
servicing.
Furthermore, for the sake of clarity, this documentation does not contain all detailed information
about all product types and cannot cover every conceivable case of installation, operation or
maintenance.
Technical Support
Country-specific telephone numbers for technical support are provided in the Internet at the
following address (https://support.industry.siemens.com/sc/ww/en/sc/2090) in the "Contact"
area.
Preface.........................................................................................................................................................3
1 Safety notes..................................................................................................................................................7
1.1 Fundamental safety instructions..............................................................................................7
1.1.1 General safety instructions.......................................................................................................7
1.1.1.1 Danger to life if the safety instructions and residual risks are not observed............................7
1.1.1.2 Malfunctions of the machine as a result of incorrect or changed parameter settings..............7
1.1.2 Warranty and liability for application examples........................................................................7
1.1.3 Industrial security.....................................................................................................................8
2 Requirements...............................................................................................................................................9
3 Method of delivery and loading the EPLAN Add-in....................................................................................11
3.1 Method of delivery..................................................................................................................11
3.2 Loading the EPLAN Add-In....................................................................................................12
4 Siemens DQ-Topo and submenus.............................................................................................................15
5 Configuring with EPLAN Add-In.................................................................................................................17
5.1 Requirement...........................................................................................................................17
5.2 Settings..................................................................................................................................17
5.2.1 SINAMICS product catalog....................................................................................................17
5.2.2 Setting the path for the drive object list..................................................................................18
5.2.3 Defining unknown devices.....................................................................................................19
5.2.4 DRIVE-CLiQ configuration.....................................................................................................22
5.3 Define bus data......................................................................................................................22
5.3.1 Control master (NCU)............................................................................................................24
5.3.2 Expansion modules of the control..........................................................................................27
5.4 Assigning drive objects..........................................................................................................28
5.4.1 EPLAN devices......................................................................................................................28
5.4.2 Drive object list.......................................................................................................................29
5.4.3 Assignment of the DO component to the device component.................................................30
5.4.3.1 Assignment using drag-and-drop...........................................................................................30
5.4.3.2 Assignment via direct input....................................................................................................30
5.4.4 Filtering of EPLAN devices and drive objects........................................................................31
5.5 Exporting the DRIVE-CLiQ topology......................................................................................32
5.5.1 Requirement...........................................................................................................................32
5.5.2 Exporting the DRIVE-CLiQ topology......................................................................................33
5.6 Excluding devices from the export.........................................................................................34
5.7 Command line interface.........................................................................................................36
6 EPLAN adaptations....................................................................................................................................37
6.1 Settings via "Siemens DQ-Topo" add-in................................................................................37
1.1.1.1 Danger to life if the safety instructions and residual risks are not observed
WARNING
Danger to life if the safety instructions and residual risks are not observed
If the safety instructions and residual risks in the associated hardware documentation are not
observed, accidents involving severe injuries or death can occur.
● Observe the safety instructions given in the hardware documentation.
● Consider the residual risks for the risk evaluation.
WARNING
Malfunctions of the machine as a result of incorrect or changed parameter settings
As a result of incorrect or changed parameterization, machines can malfunction, which in turn
can lead to injuries or death.
● Protect the parameterization (parameter assignments) against unauthorized access.
● Handle possible malfunctions by taking suitable measures, e.g. emergency stop or
emergency off.
Note
Industrial security
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens products and solutions only represent one component of such a
concept.
The customer is responsible for preventing unauthorized access to its plants, systems,
machines and networks. Systems, machines and components should only be connected to
the enterprise network or the internet if and to the extent necessary and with appropriate
security measures (e.g. use of firewalls and network segmentation) in place.
Additionally, Siemens’ guidance on appropriate security measures should be taken into
account. For more information about industrial security, please visit:
Industrial security (http://www.siemens.com/industrialsecurity).
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends to apply product updates as soon as available and to always
use the latest product versions. Use of product versions that are no longer supported, and
failure to apply latest updates may increase customer’s exposure to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed at:
Industrial security (http://www.siemens.com/industrialsecurity).
WARNING
Unsafe operating states resulting from software manipulation
Software manipulations (e.g. viruses, trojans, malware or worms) can cause unsafe operating
states in your system that may lead to death, serious injury, and property damage.
● Keep the software up to date.
● Incorporate the automation and drive components into a holistic, state-of-the-art industrial
security concept for the installation or machine.
● Make sure that you include all installed products into the holistic industrial security concept.
● Protect files stored on exchangeable storage media from malicious software by with
suitable protection measures, e.g. virus scanners.
EPLAN versions
This documentation applies to the EPLAN Add-In version V1.9.
The EPLAN Add-In has been released for EPLAN electric P8 versions 2.3, 2.4 and 2.5.
The functionality of the Add-In is identical in all EPLAN versions. The only exception is the
definition of the PLC bus properties. The differences in the definition of the bus properties are
in the EPLAN software.
Requirement
You require two licenses to use the EPLAN Add-In:
● One license to load and use the EPLAN Add-In in the platform "EPLAN Electric P8" and
create the export file from EPLAN.
● A further license to import the export file from EPLAN with the DRIVE-CLiQ topology to
Create MyConfig Topo.
4. Select the file "Siemens.EplAddIn.DQTopo.dll" from the directory into which you unpacked
the EPLAN Add-In.
5.2 Settings
Note
A valid catalog path is indicated by a red border to the path.
The current catalog version is displayed via the "Display catalog version" button.
Note
Take the "*.uvdx" file extension into account
The DO list has the "*.uvdx" file extension.
If the path for the DO list has an incorrect file extension, this is indicated by a red border to the
path.
Please note that a data type will be saved even if it is incorrect.
2. Enter the path to the DO list manually starting from the project directory.
Procedure
Proceed as follows:
1. Click the "Define unknown devices" button.
The dialog with the same name opens.
The connections to be defined are read from the SINAMICS product catalog based on
similar device types from SIEMENS.
Possible port types are:
– Analog for encoder connection
– DRIVE-CLiQ
– Current
After "Save and close" of the dialogs, including the "Settings…" main dialog, the EPLAN
article database is updated with the device types.
Note
Updating changes in the project
In order that the changed "Settings…" can be used in the available projects, the changes must
be compared to the EPLAN article database and then taken into the project.
Note
Take the EPLAN version into account
The EPLAN Add-In supports the evaluation and the export of the bus data as of EPLAN version
2.4.
Requirement
Note
Bus data - Internal/external PROFIBUS connection
Note that the bus data for the internal PROFIBUS connection of the NXs on the NCU is not
configured because it has already been permanently defined.
Configure the external PROFINET connection and the PROFINET interface.
● Position / Node ID: The position of the master on the respective bus.
● Property name "MasterSystemID": Bus number
Procedure
You define the bus data in the "Properties (components): PLC connection points and bus ports"
dialog > "Bus data" tab.
1. Select an object in EPLAN, e.g. a port.
2. Double-click the object. The "Properties (components): PLC connection points and bus
ports" dialog opens.
3. Select the "Bus data" tab.
4. Define the bus data. Information on this is provided in the following examples for the NCU
connections.
5. Confirm the changes via the "OK" button.
Note
X150 connections
Only one of the two "X150" connections has to be configured because logically they represent
the same PROFINET interface.
If both connections are configured, the configurations must match.
Additional information
An additional component of the "CU link" type is displayed for each expandable master module .
Note
Assign a drive object component to all components of a device.
Messages that refer to the component distribution and set DRIVE-CLiQ type of a device are
displayed below the device:
Figure 5-13 Assigning warnings and messages to drive objects - excerpt from "Assign drive objects"
dialog, left-hand side
Figure 5-14 Structure of the DO list - excerpt from "Assign drive objects" dialog, right-hand side
All drive objects (DO) are listed on the first level. When a DO is selected, the associated
components are listed.
1. Select the required drive object (DO) in the "Assign drive objects" window on the right-hand
side.
2. Click "DO name".
The component list belonging to the DO opens.
3. Select the required DO component and drag it to the required component line below the
device on the left-hand side
The "Assigned drive object" and the "Assigned component" are displayed immediately.
4. After completing the assignment, you can confirm the changes via the "Apply" or "Save and
close" button or reject them with the "Cancel" button.
When the assignment has been accepted, the DO name and the component name are
displayed in the preconfigured EPLAN property field for the appropriated devices.
DO and component are displayed separated by a ">", e.g. "NCU710>NCU_01". If there are
a number of subcomponents, they are separated by a semicolon.
5. If you want to delete an assignment, select the appropriate line of the device component
and delete it via the "Del" key.
6. If you what to delete all assignments of a drive object, select the drive object and press the
"Del" key.
Character XML
< <
> >
& &
" "
' '
● If the DO name includes the ">" separator, enter it as previously defined in the table.
5.5.1 Requirement
The equipment parts list forms the basis for export with the following requirements:
● Select precisely one function as main function for each item designation.
● Store at least one article for each main function.
● Define a DRIVE-CLiQ type.
Examples
Note
Creating an export file
To create a complete export file, note that the following requirements must be satisfied:
● The drive objects have been assigned to the EPLAN devices
You will find information on this in Section Assigning drive objects (Page 28).
● The bus data has been configured
You will find information in Section Defining bus data (Page 22).
7. The "Open log file" button opens the log of the export operation.
8. You can correct any listed errors or warnings.
You will find further information on this in Section Messages (Page 43).
Note
"Without DO list" / "With DO list" options
With the "Without DO list" export, the DO assignment must be performed in Create MyConfig.
For this purpose, the DO list can also be read in separately in Create MyConfig Topo in addition
to the "*.sdx".
If the "With DO list" option is used for the export, the DO list must be under the set path and
must be valid. The DO list is then imported into Create MyConfig Topo.
Procedure
To exclude a device from the export, proceed as follows:
1. In the Add-In directory, open the file with the extension
"Siemens.EplAddin.DQTopo.dll.eplan.config".
This file is always automatically generated when a configuration is saved.
2. After opening the file, search for the appropriate key in the "ConfigurableFilterFunctions"
tag.
Introduction
You can also start the EPLAN Add-In via a non-graphical user interface. The required
command line parameters are transferred via a console. With successful execution of the
action, the return value is "0".
Command syntax
The EPLAN command line interface has the following syntax:
$Path $GeneralParameters $ActionName $ProjectName $OutputFile
$ExportDOList
Master modules
The DRIVE-CLiQ types (EPLAN database field) listed below are recognized as master
modules:
Note
Evaluation error in DRIVE-CLiQ topology
If an error is recognized in the DRIVE-CLiQ topology, e.g. ring closure or duplicate wiring, the
sub-topology is not output as of the corresponding control unit (NX or NCU).
HLA modules
Note the following during configuration of HLA modules:
● The analog connection of the HLA valve, which is connected to the HLA module, must have
the name "X2".
● Represent the connection between the valve and the cylinder with standard power
connections. The name of the connection is "X1".
HF modules
Note the following during configuration of HF modules:
● Configure the cross rail between the sine filter and damping module using a power
connection. "Rail" is used as the connection name.
● As the cross rail between HF motor module and damping module is connected by DRIVE-
CLiQ, no further configuration is required.
● S1
● T1
Note
Item designation that EPLAN does not recognize
There is no search for the following item designations:
● Item designation X24, +, M (Single Motor Module)
● X124, i.e. not a power supply connection for SINAMICS CPU in the export file "example.sdx"
Figure 6-1 "PLC structure data" tab, entry for "CPU: Name [1]"
When using an ancillary equipment unit for device representation, enter the tag "DeviceName"
in the field "Function text" under the "Ancillary equipment unit" tab.
Figure 6-2 "Ancillary equipment unit" tab, entry for "Function text"
* Further information on the maximum length of the EPLAN text fields can be found in the EPLAN help > "Find" tab:
"Article management: Field designations and field lengths of the article fields"
8.2 Errors
List of the possible errors for which feedback is available.
The errors are listed in alphabetical order according to error designation and are described.
Error
Description Remedy
DEVICE_TYPE_IS_EMPTY
The DRIVE-CLiQ type of a device in the DRIVE-CLiQ topol‐ Define a valid DRIVE-CLiQ type.
ogy is empty.
Note
If the device is not part of a topology, then this message is
not an error.
DEVICE_TYPE_IS_UNDEFINED
The DRIVE-CLiQ type of a device in the DRIVE-CLiQ topol‐ Define a valid DRIVE-CLiQ type.
ogy has not been defined.
Note
If the device is not part of a topology, then this message is
considered to be a warning.
DRIVECLIQ_MULTIPLE_WIRING
Two devices have been connected several times to each oth‐ Delete one of the connections.
er in the DRIVE-CLiQ topology.
DRIVECLIQ_NO_MASTER_FOUND
A master module is missing in the DRIVE-CLiQ topology. Connect a master module (NCU).
DRIVEOBJECT_FILE_IS_EMPTY
The file with the global drive objects is empty. Provide either a valid file or no file.
DRIVEOBJECT_FILE_IS_INVALID
The file with the global drive objects is damaged or corrupt Provide either a valid file or no file.
and therefore cannot be read.
ERR_MULTIPLE_ALLOCATION_AT_DriveCLiQ_PORT
A DRIVE-CLiQ port has either been assigned or connected Delete one of the connections.
several times.
ERR_MULTIPLE_DriveCLiQ_MASTER
A DRIVE-CLiQ topology contains a number of master mod‐ ● Remove a master module from the topology.
ules (NCUs).
● Or split the topology into two topologies.
ERR_RING_TOPOLOGY
A DRIVE-CLiQ topology contains a ring connection. Break up the ring connection in the tree.
EXCEPTION_READING_BOM_ENTRY
An unexpected exception has occurred while reading the Please contact the Support with the listed exception.
EPLAN data for a device. The problem may not be able to resolved by the user.
EXCEPTION_READING_SYSTEMCONFIGURATION
The "SystemConfiguration.xml" file cannot be read. ● Check whether the rights for this file are available.
● Install the EPLAN Add-In again.
Note that the unknown devices must then be defined
again.
8.3 Warnings
List of the possible warnings for which feedback is available.
The warnings are listed in alphabetical order and are described.
Warnings
Description Remedy
BUS_DATA_IS_NOT_NUMERIC
The bus data has not been defined numerically. In the "Properties (components): PLC connection points and
bus ports", enter a numeric value in the "Bus data" tab in the
"Position / Node ID" data filed for the single-pole PLC con‐
nector.
BUS_SYSTEMID_IS_DIFFERENT
Two different PROFINET networks are defined at two con‐ Unify the PROFINET data.
nections of the device.
CONFIGURATION_COULD_NOT_READING / CONFIGURATION_UNAUTHORIZED_READING
The configuration could not be read. 1. Correct the authorization error.
2. Delete the configuration files and save them again.
CONFIGURATION_COULD_NOT_WRITING / CONFIGURATION_UNAUTHORIZED_WRITING
The configuration could not be written. 1. Correct the authorization error.
2. Delete the configuration files and save them again.
CONNECTION_HAS_SAME_DEVICE_ON_BOTH_ENDS
The connection goes to the same device. Change the connection to the correct device.
CONNECTION_NOT_HOMOGEN
The connection is between different types, e.g. DRIVE-CLiQ Change the connection.
to Power.
CONNECTION_TO_UNKNOWN_DEVICE
The connection goes to an unknown device. The signaled device is unknown:
● Because not listed in the SINAMICS product catalog
● Not defined as unknown device
● Because no order number available
● No DRIVE-CLiQ type defined
CONNECTION_TO_UNKNOWN_PORT
The connection goes to an unknown port. Change the connection.
Or define the device as unknown device in order to specify
the port name and the type.
You can find further information in Section "Defining unknown
devices" (Page 19).
DEVICE_EXISTS_MULTIPLE_TIME
The device has more than one EPLAN main function? Select one EPLAN function as main function.
DEVICE_NOT_IN_DRIVECLIQ_TOPOLOGY
The DRIVE-CLiQ device is not contained in the DRIVE-CLiQ Integrate the device in the DRIVE-CLiQ topology.
topology.
DEVICE_ONLY_IN_POWERTOPOLOGY
The DRIVE-CLiQ device is only integrated in the power top‐ Also integrate the device in the DRIVE-CLiQ topology.
ology.
Warnings
Description Remedy
DRIVEOBJECT_COMPONENT_ALREADY_ASSIGNED
The drive object (DO) has already been assigned to another Make a unique assignment of the drive object (DO).
device.
DRIVEOBJECT_COMPONENT_NOT_IN_GLOBALDO_LIST
The assigned drive object is not contained in the global DO Update the global DO list and adapt the assignment.
list.
DRIVEOBJECT_ERROR_WHILE_READING
An error occurred while reading the drive object assignments. The export will be continued without the relevant assignmens.
Contact the Support.
DRIVEOBJECT_FILE_HAS_DUPLICATE_IDS
Duplicates of DO names have been found in the global DO Remove the duplicates from the global DO list.
list.
The IDs in the global DO list are the DO names.
UNKNOWN_ECAD_VERSION
Bus data has not been implemented for the used EPLAN ver‐ Use a different EPLAN version or contact the Support.
sion.
UNSUPPORTED_PROPERTY_TYPE
The EPLAN property for bus data has found an unsupported Check the bus data or contact the Support.
type.
This warning can occur with unsupported EPLAN versions or
when unsupported values have been entered.
Table A-1 File extensions for the file formats used in EPLAN
DRIVECLIQ_MULTIPLE_WIRING ERR_MULTIPLE_DriveCLiQ_MASTER
Error, 44 Error, 44
DRIVECLIQ_NO_MASTER_FOUND ERR_RING_TOPOLOGY
Error, 44 Error, 44
DRIVEOBJECT_COMPONENT_ALREADY_ASSIG Error
NED DEVICE_TYPE_IS_EMPTY, 44
Drive object, 43 DEVICE_TYPE_IS_UNDEFINED, 44
Warning, 46 DRIVECLIQ_MULTIPLE_WIRING, 44
DRIVEOBJECT_COMPONENT_NOT_IN_GLOBALD DRIVECLIQ_NO_MASTER_FOUND, 44
O_LIST DRIVEOBJECT_FILE_IS_EMPTY, 44
Drive object, 43 DRIVEOBJECT_FILE_IS_INVALID, 44
Warning, 46 ERR_MULTIPLE_ALLOCATION_AT_DriveCLiQ_
DRIVEOBJECT_ERROR_WHILE_READING PORT, 44
Warning, 46 ERR_MULTIPLE_DriveCLiQ_MASTER, 44
DRIVEOBJECT_FILE_HAS_DUPLICATE_IDS ERR_RING_TOPOLOGY, 44
Warning, 46 EXCEPTION_READING_BOM_ENTRY, 44
DRIVEOBJECT_FILE_IS_EMPTY EXCEPTION_READING_SYSTEMCONFIGURA
Error, 44 TION, 44
DRIVEOBJECT_FILE_IS_INVALID Examples
Error, 44 NCU connection, 25
DRIVEOBJECT_IS_UNASSIGNED EXCEPTION_READING_BOM_ENTRY
Drive object, 43 Error, 44
EXCEPTION_READING_SYSTEMCONFIGURATIO
N
E Error, 44
Expansion modules
EPLAN
Configuring, 27
Article database, 18, 21
Export, 33
Bus data, 22
Equipment parts list, 32
Command line interface, 36
Device connection name, 32
Display type, 35
Equipment parts list, 32
F
Exporting the configuration, 17 File type
Keys assignment, 35 *.sdx, 33
Minimum requirements on DRIVE-CLiQ *.uvdx, 18
topology, 37 filtering
Minimum requirements on power topology, 38 Drive objects, 32
Text fields, 42 EPLAN device, 31
EPLAN Add-In
Loading, 12, 36
Siemens DQ-Topo, 4 H
Version, 9
HF modules
EPLAN device, 28
Configuration, 38
filtering, 31
HLA modules
EPLAN Electric P8, 12
Configuration, 38
Version,
EPLAN property, 22
ERR_GLOBAL_DO_LIST_NOT_FOUND
Drive object, 43
I
ERR_MULTIPLE_ALLOCATION_AT_DriveCLiQ_PO import-catalog.log.xml, 18
RT Item designation, 28
Error, 44 Predefined, 38
topo.uvdx, 29
M
Main menu
U
Siemens DQ-Topo, 13, 15 UNKNOWN_ECAD_VERSION
Master modules Warning, 46
EPLAN database field, 37 UNSUPPORTED_PROPERTY_TYPE
MasterSystemID, 27 Warning, 46
Minimum requirements
Power topology, 38
V
Version
P EPLAN Add-In, 9
PLC unit EPLAN electric P8, 9
Device representation, 39
Predefined
DRIVE-CLiQ connection names, 37 W
Encoder connection names, 37
Warning
EPLAN property, 22
BUS_DATA_IS_NOT_NUMERIC, 45
Item designation, 38
BUS_SYSTEMID_IS_DIFFERENT, 45
Purpose of the document, 4
CONFIGURATION_COULD_NOT_READING, 45
CONFIGURATION_COULD_NOT_WRITING, 45
CONFIGURATION_UNAUTHORIZED_READING
R , 45
Requirement CONFIGURATION_UNAUTHORIZED_WRITING,
EPLAN versions, 9 45
SINAMICS product catalog, 9 CONNECTION_HAS_SAME_DEVICE_ON_BOT
H_ENDS, 45
CONNECTION_NOT_HOMOGEN, 45
S CONNECTION_TO_UNKNOWN_DEVICE, 45
CONNECTION_TO_UNKNOWN_PORT, 45
Settings
DEVICE_EXISTS_MULTIPLE_TIME, 45
Dialog, 15
DEVICE_NOT_IN_DRIVECLIQ_TOPOLOGY, 45
DO list, 18
DEVICE_ONLY_IN_POWERTOPOLOGY, 45
DRIVE-CLiQ type, 22
DRIVEOBJECT_COMPONENT_ALREADY_ASSI
Siemens DQ-Topo, 4, 13
GNED, 46
Submenus, 15
DRIVEOBJECT_ERROR_WHILE_READING, 46
Siemens.EplAddIn.DQTopo.dll, 18
DRIVEOBJECT_FILE_HAS_DUPLICATE_IDS,
Siemens.EplAddin.DQTopo.dll.eplan.config, 35
46
SINAMICS product catalog
RIVEOBJECT_COMPONENT_NOT_IN_GLOBAL
importing, 18
DO_LIST, 46
Path, 17
UNKNOWN_ECAD_VERSION, 46
Requirement, 9
UNSUPPORTED_PROPERTY_TYPE, 46
Version, 9
With DO list, 34
SINAMICS-DQ-Komponenten-Katalog.xml, 17
Without DO list, 34
Slave
Configuring, 27
T
Target group, 4