Académique Documents
Professionnel Documents
Culture Documents
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 32 50 00
Facsimile: +46 (0) 21 14 69 18
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC).
Table of contents
Section 1 Introduction.....................................................................29
Introduction to the technical reference manual.................................29
About the complete set of manuals for an IED............................29
About the technical reference manual.........................................30
This manual.................................................................................31
Introduction.............................................................................31
Principle of operation..............................................................31
Input and output signals.........................................................34
Function block........................................................................34
Setting parameters.................................................................34
Technical data........................................................................35
Intended audience.......................................................................35
Related documents......................................................................35
Revision notes.............................................................................36
1
Technical reference manual
Table of contents
2
Technical reference manual
Table of contents
3
Technical reference manual
Table of contents
Introduction................................................................................104
Principle of operation.................................................................104
Function block...........................................................................104
Output signals............................................................................104
Setting parameters....................................................................105
4
Technical reference manual
Table of contents
5
Technical reference manual
Table of contents
6
Technical reference manual
Table of contents
Technical data...........................................................................259
Power swing detection ZMRPSB ...................................................259
Introduction................................................................................259
Principle of operation.................................................................260
Resistive reach in forward direction.....................................261
Resistive reach in reverse direction.....................................262
Reactive reach in forward and reverse direction..................262
Basic detection logic.............................................................263
Operating and inhibit conditions...........................................265
Function block...........................................................................266
Input and output signals............................................................266
Setting parameters....................................................................267
Technical data...........................................................................268
Power swing logic ZMRPSL ..........................................................268
Introduction................................................................................268
Principle of operation.................................................................268
Communication and tripping logic........................................268
Blocking logic.......................................................................269
Function block...........................................................................271
Input and output signals............................................................271
Setting parameters....................................................................272
Pole slip protection PSPPPAM ......................................................272
Introduction................................................................................272
Principle of operation.................................................................272
Function block...........................................................................276
Input and output signals............................................................276
Setting parameters....................................................................277
Technical data...........................................................................277
Automatic switch onto fault logic, voltage and current based
ZCVPSOF ......................................................................................278
Introduction................................................................................278
Principle of operation.................................................................278
Function block...........................................................................280
Input and output signals............................................................280
Setting parameters....................................................................280
Technical data...........................................................................281
Phase preference logic PPLPHIZ...................................................281
Introduction................................................................................281
Principle of operation.................................................................281
Function block...........................................................................284
Input and output signals............................................................284
Setting parameters....................................................................285
8
Technical reference manual
Table of contents
9
Technical reference manual
Table of contents
Introduction................................................................................362
Principle of operation.................................................................363
Low pass filtering..................................................................365
Calibration of analog inputs..................................................365
Function block...........................................................................366
Input and output signals............................................................367
Setting parameters....................................................................367
Technical data...........................................................................369
Broken conductor check BRCPTOC .............................................369
Introduction................................................................................369
Principle of operation.................................................................369
Function block...........................................................................370
Input and output signals............................................................371
Setting parameters....................................................................371
Technical data...........................................................................371
10
Technical reference manual
Table of contents
Blocking................................................................................404
Design..................................................................................404
Function block...........................................................................405
Input and output signals............................................................406
Setting parameters....................................................................406
Technical data...........................................................................408
Overexcitation protection OEXPVPH ............................................408
Introduction................................................................................408
Principle of operation.................................................................409
Measured voltage.................................................................411
Operate time of the overexcitation protection.......................412
Cooling.................................................................................415
Overexcitation protection function measurands...................415
Overexcitation alarm............................................................416
Logic diagram.......................................................................417
Function block...........................................................................417
Input and output signals............................................................417
Setting parameters....................................................................418
Technical data...........................................................................419
Voltage differential protection VDCPTOV ......................................419
Introduction................................................................................419
Principle of operation.................................................................420
Function block...........................................................................421
Input and output signals............................................................422
Setting parameters....................................................................422
Technical data...........................................................................423
Loss of voltage check LOVPTUV ..................................................423
Introduction................................................................................423
Principle of operation.................................................................423
Function block...........................................................................425
Input and output signals............................................................426
Setting parameters....................................................................426
Technical data...........................................................................426
11
Technical reference manual
Table of contents
12
Technical reference manual
Table of contents
Introduction................................................................................467
Principle of operation.................................................................467
Function block...........................................................................469
Input and output signals............................................................469
Setting parameters....................................................................470
Technical data...........................................................................470
Fuse failure supervision SDDRFUF...............................................470
Introduction................................................................................470
Principle of operation.................................................................471
Zero and negative sequence detection................................471
Delta current and delta voltage detection.............................473
Dead line detection...............................................................476
Main logic.............................................................................476
Function block...........................................................................480
Input and output signals............................................................480
Setting parameters....................................................................480
Technical data...........................................................................481
Section 12 Control..........................................................................483
Synchrocheck, energizing check, and synchronizing
SESRSYN......................................................................................483
Introduction................................................................................483
Principle of operation.................................................................484
Basic functionality.................................................................484
Logic diagrams.....................................................................484
Function block...........................................................................493
Input and output signals............................................................493
Setting parameters....................................................................496
Technical data...........................................................................498
Autorecloser SMBRREC ...............................................................498
Introduction................................................................................499
Principle of operation.................................................................499
Logic Diagrams....................................................................499
Auto-reclosing operation Off and On....................................499
Auto-reclosing mode selection.............................................499
Start auto-reclosing and conditions for start of a
reclosing cycle......................................................................500
Control of the auto-reclosing open time for shot 1...............501
Long trip signal.....................................................................501
Time sequence diagrams.....................................................508
Function block...........................................................................511
Input and output signals............................................................511
Setting parameters....................................................................513
Technical data...........................................................................515
13
Technical reference manual
Table of contents
14
Technical reference manual
Table of contents
Function block......................................................................548
Input and output signals.......................................................549
Setting parameters...............................................................550
Interlocking ....................................................................................550
Introduction................................................................................550
Principle of operation.................................................................550
Logical node for interlocking SCILO .........................................553
Introduction...........................................................................553
Logic diagram.......................................................................553
Function block......................................................................554
Input and output signals.......................................................554
Interlocking for busbar earthing switch BB_ES .........................554
Introduction...........................................................................555
Function block......................................................................555
Logic diagram.......................................................................555
Input and output signals.......................................................555
Interlocking for bus-section breaker A1A2_BS..........................556
Introduction...........................................................................556
Function block......................................................................557
Logic diagram.......................................................................558
Input and output signals.......................................................559
Interlocking for bus-section disconnector A1A2_DC ................560
Introduction...........................................................................561
Function block......................................................................561
Logic diagram.......................................................................562
Input and output signals.......................................................562
Interlocking for bus-coupler bay ABC_BC ................................563
Introduction...........................................................................563
Function block......................................................................564
Logic diagram.......................................................................565
Input and output signals.......................................................567
Interlocking for 1 1/2 CB BH .....................................................570
Introduction...........................................................................570
Function blocks....................................................................571
Logic diagrams.....................................................................573
Input and output signals.......................................................578
Interlocking for double CB bay DB ...........................................582
Introduction...........................................................................582
Function block......................................................................583
Logic diagrams.....................................................................585
Input and output signals ......................................................588
Interlocking for line bay ABC_LINE ..........................................591
Introduction...........................................................................591
15
Technical reference manual
Table of contents
Function block......................................................................592
Logic diagram.......................................................................593
Input and output signals.......................................................598
Interlocking for transformer bay AB_TRAFO ............................600
Introduction...........................................................................601
Function block......................................................................602
Logic diagram.......................................................................603
Input and output signals.......................................................604
Position evaluation POS_EVAL.................................................606
Introduction...........................................................................606
Logic diagram.......................................................................606
Function block......................................................................607
Input and output signals.......................................................607
Logic rotating switch for function selection and LHMI
presentation SLGGIO.....................................................................607
Introduction................................................................................607
Principle of operation.................................................................607
Functionality and behaviour ................................................609
Graphical display..................................................................609
Function block...........................................................................611
Input and output signals............................................................611
Setting parameters....................................................................612
Selector mini switch VSGGIO.........................................................613
Introduction................................................................................613
Principle of operation.................................................................613
Function block...........................................................................614
Input and output signals............................................................614
Setting parameters....................................................................615
Generic double point function block DPGGIO................................615
Introduction................................................................................615
Principle of operation.................................................................615
Function block...........................................................................616
Input and output signals............................................................616
Settings......................................................................................616
Single point generic control 8 signals SPC8GGIO.........................616
Introduction................................................................................616
Principle of operation.................................................................617
Function block...........................................................................617
Input and output signals............................................................617
Setting parameters....................................................................618
AutomationBits, command function for DNP3.0 AUTOBITS..........618
Introduction................................................................................619
Principle of operation.................................................................619
16
Technical reference manual
Table of contents
Function block...........................................................................620
Input and output signals............................................................620
Setting parameters....................................................................621
Single command, 16 signals SINGLECMD....................................635
Introduction................................................................................635
Principle of operation.................................................................635
Function block...........................................................................636
Input and output signals............................................................636
Setting parameters....................................................................637
17
Technical reference manual
Table of contents
18
Technical reference manual
Table of contents
Technical data...........................................................................675
Section 14 Logic.............................................................................677
Tripping logic SMPPTRC ...............................................................677
Introduction................................................................................677
Principle of operation.................................................................677
Logic diagram.......................................................................679
Function block...........................................................................683
Input and output signals............................................................683
Setting parameters....................................................................684
Technical data...........................................................................685
Trip matrix logic TMAGGIO............................................................685
Introduction................................................................................685
Principle of operation.................................................................685
Function block...........................................................................687
Input and output signals............................................................687
Setting parameters....................................................................688
Configurable logic blocks................................................................689
Introduction................................................................................689
Inverter function block INV........................................................689
OR function block OR................................................................690
AND function block AND...........................................................691
Timer function block TIMER......................................................691
Pulse timer function block PULSETIMER..................................692
Exclusive OR function block XOR.............................................692
Loop delay function block LOOPDELAY...................................693
Set-reset with memory function block SRMEMORY.................693
Controllable gate function block GATE......................................694
Settable timer function block TIMERSET..................................695
Technical data...........................................................................696
Fixed signal function block FXDSIGN............................................696
Principle of operation.................................................................696
Function block...........................................................................697
Input and output signals............................................................697
Setting parameters....................................................................697
Boolean 16 to Integer conversion B16I..........................................697
Introduction................................................................................697
Principle of operation.................................................................698
Function block...........................................................................698
Input and output signals............................................................698
Setting parameters....................................................................699
Boolean 16 to Integer conversion with logic node
representation B16IGGIO...............................................................699
Introduction................................................................................699
19
Technical reference manual
Table of contents
Principle of operation.................................................................699
Function block...........................................................................700
Input and output signals............................................................700
Setting parameters....................................................................701
Integer to Boolean 16 conversion IB16..........................................701
Introduction................................................................................701
Principle of operation.................................................................701
Function block...........................................................................701
Input and output signals............................................................702
Setting parameters....................................................................702
Integer to Boolean 16 conversion with logic node
representation IB16GGIO...............................................................702
Introduction................................................................................703
Principle of operation.................................................................703
Function block...........................................................................703
Input and output signals............................................................703
Setting parameters....................................................................704
Section 15 Monitoring.....................................................................705
Measurements................................................................................705
Introduction................................................................................706
Principle of operation.................................................................707
Measurement supervision....................................................707
Measurements CVMMXU.....................................................711
Phase current measurement CMMXU.................................716
Phase-phase and phase-neutral voltage measurements
VMMXU, VNMMXU..............................................................717
Voltage and current sequence measurements VMSQI,
CMSQI..................................................................................717
Function block...........................................................................717
Input and output signals............................................................719
Setting parameters....................................................................722
Technical data...........................................................................735
Event counter CNTGGIO................................................................736
Introduction................................................................................736
Principle of operation.................................................................736
Reporting..............................................................................736
Design..................................................................................737
Function block...........................................................................737
Input signals..............................................................................737
Setting parameters....................................................................738
Technical data...........................................................................738
Event function EVENT....................................................................738
Introduction................................................................................738
20
Technical reference manual
Table of contents
Principle of operation.................................................................738
Function block...........................................................................740
Input and output signals............................................................740
Setting parameters....................................................................741
Logical signal status report BINSTATREP.....................................743
Introduction................................................................................743
Principle of operation.................................................................743
Function block...........................................................................744
Input and output signals............................................................744
Setting parameters....................................................................745
Fault locator LMBRFLO..................................................................745
Introduction................................................................................746
Principle of operation.................................................................746
Measuring Principle..............................................................747
Accurate algorithm for measurement of distance to fault.....747
The non-compensated impedance model............................751
IEC 60870-5-103..................................................................752
Function block...........................................................................752
Input and output signals............................................................752
Setting parameters....................................................................753
Technical data...........................................................................754
Measured value expander block RANGE_XP................................754
Introduction................................................................................754
Principle of operation.................................................................754
Function block...........................................................................755
Input and output signals............................................................755
Disturbance report DRPRDRE.......................................................755
Introduction................................................................................756
Principle of operation.................................................................756
Function block...........................................................................763
Input and output signals............................................................765
Setting parameters....................................................................766
Technical data...........................................................................776
Event list.........................................................................................776
Introduction................................................................................776
Principle of operation.................................................................776
Function block...........................................................................777
Input signals..............................................................................777
Technical data...........................................................................777
Indications......................................................................................777
Introduction................................................................................777
Principle of operation.................................................................778
Function block...........................................................................779
21
Technical reference manual
Table of contents
Input signals..............................................................................779
Technical data...........................................................................779
Event recorder ...............................................................................779
Introduction................................................................................779
Principle of operation.................................................................779
Function block...........................................................................780
Input signals..............................................................................780
Technical data...........................................................................780
Trip value recorder.........................................................................780
Introduction................................................................................780
Principle of operation.................................................................781
Function block...........................................................................781
Input signals..............................................................................781
Technical data...........................................................................782
Disturbance recorder......................................................................782
Introduction................................................................................782
Principle of operation.................................................................782
Memory and storage............................................................783
IEC 60870-5-103..................................................................784
Function block...........................................................................785
Input and output signals............................................................785
Setting parameters....................................................................785
Technical data...........................................................................785
Section 16 Metering.......................................................................787
Pulse-counter logic PCGGIO..........................................................787
Introduction................................................................................787
Principle of operation.................................................................787
Function block...........................................................................789
Input and output signals............................................................790
Setting parameters....................................................................790
Technical data...........................................................................791
Function for energy calculation and demand handling
ETPMMTR......................................................................................791
Introduction................................................................................791
Principle of operation.................................................................791
Function block...........................................................................792
Input and output signals............................................................792
Setting parameters....................................................................793
22
Technical reference manual
Table of contents
23
Technical reference manual
Table of contents
Function block...........................................................................851
Input and output signals............................................................851
Setting parameters....................................................................853
Goose binary receive GOOSEBINRCV..........................................854
Function block...........................................................................854
Input and output signals............................................................854
Setting parameters....................................................................855
Multiple command and transmit MULTICMDRCV,
MULTICMDSND.............................................................................855
Introduction................................................................................856
Principle of operation.................................................................856
Design.......................................................................................856
General.................................................................................856
Function block...........................................................................857
Input and output signals............................................................858
Setting parameters....................................................................859
Section 19 Hardware......................................................................869
Overview.........................................................................................869
Variants of case and local HMI display size..............................869
Case from the rear side.............................................................872
Hardware modules.........................................................................877
Overview....................................................................................877
Combined backplane module (CBM).........................................878
Introduction...........................................................................878
Functionality.........................................................................878
Design..................................................................................878
Universal backplane module (UBM)..........................................880
Introduction...........................................................................880
Functionality.........................................................................880
Design..................................................................................880
Numeric processing module (NUM)..........................................882
Introduction...........................................................................882
24
Technical reference manual
Table of contents
Functionality.........................................................................883
Block diagram.......................................................................884
Power supply module (PSM).....................................................884
Introduction...........................................................................884
Design..................................................................................884
Technical data......................................................................885
Local human-machine interface (Local HMI).............................885
Transformer input module (TRM)..............................................885
Introduction...........................................................................886
Design..................................................................................886
Technical data......................................................................886
Analog digital conversion module, with time
synchronization (ADM) .............................................................887
Introduction...........................................................................887
Design..................................................................................887
Binary input module (BIM).........................................................889
Introduction...........................................................................889
Design..................................................................................889
Technical data......................................................................893
Binary output modules (BOM)...................................................893
Introduction...........................................................................893
Design..................................................................................893
Technical data......................................................................895
Static binary output module (SOM)...........................................896
Introduction...........................................................................896
Design..................................................................................896
Technical data......................................................................898
Binary input/output module (IOM)..............................................899
Introduction...........................................................................899
Design..................................................................................900
Technical data......................................................................902
mA input module (MIM).............................................................903
Introduction...........................................................................903
Design..................................................................................903
Technical data......................................................................904
Serial and LON communication module (SLM) ........................905
Introduction...........................................................................905
Design..................................................................................905
Technical data......................................................................906
Galvanic RS485 communication module...................................907
Introduction...........................................................................907
Design..................................................................................907
Technical data......................................................................909
25
Technical reference manual
Table of contents
26
Technical reference manual
Table of contents
Section 20 Labels...........................................................................945
Different labels................................................................................945
Section 23 Glossary.......................................................................999
27
Technical reference manual
28
1MRK505183-UEN C Section 1
Introduction
Section 1 Introduction
Decommissioning
Commissioning
Maintenance
Engineering
Operation
Installing
Engineeringmanual
Installation and
Commissioning manual
Operator’s manual
Application manual
Technical reference
manual
IEC09000744-1-en.vsd
IEC09000744 V1 EN
29
Technical reference manual
Section 1 1MRK505183-UEN C
Introduction
The Engineering Manual (EM) contains instructions on how to engineer the IEDs
using the different tools in PCM600. The manual provides instructions on how to
set up a PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 61850 and DNP3.
• Local HMI describes the control panel on the IED and explains display
characteristics, control keys and various local HMI features.
• Basic IED functions presents functions for all protection types that are
included in all IEDs, for example, time synchronization, self supervision with
event list, test mode and other general functions.
• Differential protection describes differential functions and restricted earth fault
protection.
• Impedance protection describes functions for distance zones with their
quadrilateral characteristics, phase selection with load encroachment, power
swing detection and similar.
• Current protection describes functions, for example, over current protection,
breaker failure protection and pole discordance.
• Voltage protection describes functions for under voltage and over voltage
protection and residual over voltage protection.
• Frequency protection describes functions for over frequency, under frequency
and rate of change of frequency protection.
• Multipurpose protection describes the general protection function for current
and voltage.
• Secondary system supervision describes current based functions for current
circuit supervision and fuse failure supervision.
• Control describes control functions, for example, synchronization and
energizing check and other product specific functions.
• Scheme communication describes functions related to current reversal and
weak end infeed logic.
30
Technical reference manual
1MRK505183-UEN C Section 1
Introduction
1.1.3.1 Introduction
Logic diagrams
Logic diagrams describe the signal logic inside the function block and are bordered
by dashed lines.
Signal names
Input and output logic signals consist of two groups of letters separated by two
dashes. The first group consists of up to four letters and presents the abbreviated
name for the corresponding function. The second group presents the functionality
of the particular signal. According to this explanation, the meaning of the signal
BLKTR in figure 4 is as follows:
• BLKTR informs the user that the signal will BLOCK the TRIP command from
the under-voltage function, when its value is a logical one (1).
Input signals are always on the left hand side, and output signals on the right hand
side. Settings are not displayed.
31
Technical reference manual
Section 1 1MRK505183-UEN C
Introduction
Input and output signals can be configured using the ACT tool. They can be
connected to the inputs and outputs of other functions and to binary inputs and
outputs. Examples of input signals are BLKTR, BLOCK and VTSU. Examples
output signals are TRIP, START, STL1, STL2, STL3.
Setting parameters
Signals in frames with a shaded area on their right hand side represent setting
parameter signals. These parameters can only be set via the PST or LHMI. Their
values are high (1) only when the corresponding setting parameter is set to the
symbolic value specified within the frame. Example is the signal Block TUV=Yes.
Their logical values correspond automatically to the selected setting value.
Internal signals
Internal signals are illustrated graphically and end approximately 2 mm from the
frame edge. If an internal signal path cannot be drawn with a continuous line, the
suffix -int is added to the signal name to indicate where the signal starts and
continues, see figure 1.
BLKTR
TEST
TEST
&
Block TUV=Yes BLOCK-int.
>1
BLOCK
VTSU
BLOCK-int.
&
STUL1N
BLOCK-int.
& >1 & TRIP
t
STUL2N
BLOCK-int.
START
&
STUL3N
STL1
STL2
STL3
xx04000375.vsd
IEC04000375 V1 EN
32
Technical reference manual
1MRK505183-UEN C Section 1
Introduction
External signals
Signal paths that extend beyond the logic diagram and continue in another diagram
have the suffix “-cont.”, see figure 2 and figure 3.
STZMPP-cont.
>1
STCND
& STNDL1L2-cont.
1L1L2
STNDL2L3-cont.
&
1L2L3
& STNDL3L1-cont.
1L3L1
& STNDL1N-cont.
1L1N
& STNDL2N-cont.
1L2N
STNDL3N-cont.
&
1L3N
>1 STNDPE-cont.
>1
1--VTSZ 1--STND
>1 &
1--BLOCK
BLK-cont.
xx04000376.vsd
IEC04000376 V1 EN
STNDL1N-cont.
>1
STNDL2N-cont. 15 ms
& t STL1
STNDL3N-cont.
STNDL1L2-cont. >1 15 ms
& t STL2
STNDL2L3-cont.
15 ms
STNDL3L1-cont. & t STL3
>1
15 ms
& t START
>1
BLK-cont.
xx04000377.vsd
IEC04000377 V1 EN
33
Technical reference manual
Section 1 1MRK505183-UEN C
Introduction
Input and output signals are presented in two separate tables. Each table consists of
two columns. The first column contains the name of the signal and the second
column contains the description of the signal.
Input signals are always on the left hand side and output signals on the right hand
side. Settings are not displayed. Special kinds of settings are sometimes available.
These are supposed to be connected to constants in the configuration scheme and
are therefore depicted as inputs. Such signals will be found in the signal list but
described in the settings table.
• The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set a signal name of
their own in PCM600.
• The * character after an input or output signal name in the function block
symbol given for a function, indicates that the signal must be connected to
another function block in the application configuration to achieve a valid
application configuration.
IEC 61850 - 8 -1
Logical Node Mandatory
signal (*)
Inputs Outputs
PCGGIO
BLOCK INVALID
READ_VAL RESTART
BI_PULSE* BLOCKED
RS_CNT NEW_VAL
^SCAL_VAL
en05000511-1-en.vsd
User defined
name (^)
Diagram
Number
IEC05000511 V2 EN
These are presented in tables and include all parameters associated with the
function in question.
34
Technical reference manual
1MRK505183-UEN C Section 1
Introduction
The technical data section provides specific technical information about the
function or hardware described.
Requirements
The system engineer must have a thorough knowledge of protection systems,
protection equipment, protection functions and the configured functional logics in
the protective devices. The installation and commissioning personnel must have a
basic knowledge in the handling electronic equipment.
35
Technical reference manual
Section 1 1MRK505183-UEN C
Introduction
IEC 61850 Data objects list for IED 670, ver. 1.1 1MRK 500 084-WEN
Generic IEC 61850 IED Connectivity package 1KHA001027-UEN
Protection and Control IED Manager PCM 600 Installation sheet 1MRS755552
Engineering guide IED 670 products 1MRK 511 179-UEN
36
Technical reference manual
1MRK505183-UEN C Section 2
Analog inputs
2.1 Introduction
Analog input channels must be configured and set properly to get correct
measurement results and correct protection operations. For power measuring and
all directional and differential functions the directions of the input currents must be
defined properly. Measuring and protection algorithms in the IED use primary
system quantities. Set values are done in primary quantities as well and it is
important to set the data about the connected current and voltage transformers
properly.
The IED has the ability to receive analog values from primary
equipment, that are sampled by Merging units (MU) connected to a
process bus, via the IEC 61850-9-2 LE protocol.
The direction of a current to the IED depends on the connection of the CT. The
main CTs are typically star connected and can be connected with the star point to
the object or from the object. This information must be set to the IED.
• Positive value of current or power means quantity direction into the object.
• Negative value of current or power means quantity direction out from the object.
37
Technical reference manual
Section 2 1MRK505183-UEN C
Analog inputs
en05000456.vsd
IEC05000456 V1 EN
The ratios of the main CTs and VTs must be known to use primary system
quantities for settings and calculation in the IED, The user has to set the rated
secondary and primary currents and voltages of the CTs and VTs to provide the
IED with this information.
The CT and VT ratio and the name on respective channel is done under Main
menu/General settings/Analog module in the Parameter Settings tool.
38
Technical reference manual
1MRK505183-UEN C Section 2
Analog inputs
39
Technical reference manual
Section 2 1MRK505183-UEN C
Analog inputs
40
Technical reference manual
1MRK505183-UEN C Section 2
Analog inputs
41
Technical reference manual
Section 2 1MRK505183-UEN C
Analog inputs
42
Technical reference manual
1MRK505183-UEN C Section 2
Analog inputs
43
Technical reference manual
Section 2 1MRK505183-UEN C
Analog inputs
44
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI
The local human machine interface is available in a small and a medium sized
model. The difference between the two models is the size of the LCD. The small
size LCD can display seven lines of text and the medium size LCD can display the
single line diagram with up to 15 objects on each page. Up to 12 single line
diagram pages can be defined, depending on the product capability.
45
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI
IEC05000055-LITEN V1 EN
IEC05000056-LITEN V1 EN
46
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI
3.2.1 Small
The small sized HMI is available for 1/2, 3/4 and 1/1 x 19” case. The LCD on the
small HMI measures 32 x 90 mm and displays 7 lines with up to 40 characters per
line. The first line displays the product name and the last line displays date and
time. The remaining 5 lines are dynamic. This LCD has no graphic display potential.
3.2.2 Design
The local HMI is identical for both the 1/2, 3/4 and 1/1 cases. The different parts of
the small local HMI are shown in figure 8
47
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI
1 2 3
en05000055.eps
8 7
IEC05000055-CALLOUT V1 EN
48
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI
3.3.1 Medium
The following case sizes can be equipped with the medium size LCD:
• 1/2 x 19”
• 3/4 x 19”
• 1/1 x 19”
This is a fully graphical monochrome LCD which measures 120 x 90 mm. It has 28
lines with up to 40 characters per line. To display the single line diagram, this LCD
is required.
3.3.2 Design
The different parts of the medium size local HMI are shown in figure 9. The local
HMI exists in an IEC version and in an ANSI version. The difference is on the
keypad operation buttons and the yellow LED designation.
49
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI
1 2 3
en05000056.eps
8 7
IEC05000056-CALLOUT V1 EN
50
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI
3.4 Keypad
The keypad is used to monitor and operate the IED. The keypad has the same look
and feel in all IEDs. LCD screens and other details may differ but the way the keys
function is identical.
IEC05000153 V1 EN
Table 7 describes the HMI keys that are used to operate the IED.
Press to open two sub menus: Key operation and IED information.
IEC05000103 V1 EN
Press to open the main menu and to move to the default screen.
IEC05000105 V1 EN
Press to start the editing mode and confirm setting changes, when in editing mode.
IEC05000108 V1 EN
51
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI
Key Function
Press to navigate forward between screens and move right in editing mode.
IEC05000109 V1 EN
Press to navigate backwards between screens and move left in editing mode.
IEC05000110 V1 EN
Press to move up in the single line diagram and in the menu tree.
IEC05000111 V1 EN
Press to move down in the single line diagram and in the menu tree.
IEC05000112 V1 EN
3.5 LED
3.5.1 Introduction
The LED module is a unidirectional means of communicating. This means that
events may occur that activate a LED in order to draw the operators attention to
something that has occurred and needs some sort of action.
52
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI
Alarm indication LEDs and hardware associated LEDs are located on the right
hand side of the front panel. Alarm LEDs are located on the right of the LCD
screen and show steady or flashing light.
Alarm LEDs can be configured in PCM600 and depend on the binary logic.
Therefore they can not be configured on the local HMI.
The RJ45 port has a yellow LED indicating that communication has been
established between the IED and a computer.
The Local/Remote key on the front panel has two LEDs indicating whether local or
remote control of the IED is active.
3.6.1 Introduction
The local HMI can be adapted to the application configuration and to user preferences.
53
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI
3.6.3.1 Design
The function block LocalHMI controls and supplies information about the status of
the status indication LEDs. The input and output signals of local HMI are
configured with PCM600.
The function block can be used if any of the signals are required in a configuration
logic.
See section "Status indication LEDs" for information about the LEDs.
IEC05000773-2-en.vsd
IEC05000773 V2 EN
54
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI
3.6.4.1 Introduction
The function block LEDGEN controls and supplies information about the status of
the indication LEDs. The input and output signals of LEDGEN are configured with
PCM600. The input signal for each LED is selected individually with the Signal
Matrix Tool in PCM600.
Each indication LED on the local HMI can be set individually to operate in six
different sequences
The light from the LEDs can be steady (-S) or flashing (-F). See the technical
reference manual for more information.
3.6.4.2 Design
The information on the LEDs is stored at loss of the auxiliary power to the IED in
some of the modes of LEDGEN. The latest LED picture appears immediately after
the IED is successfully restarted.
Operating modes
• Collecting mode
55
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI
• Re-starting mode
• In the re-starting mode of operation each new start resets all previous
active LEDs and activates only those which appear during one
disturbance. Only LEDs defined for re-starting mode with the latched
sequence type 6 (LatchedReset-S) will initiate a reset and a restart at a
new disturbance. A disturbance is defined to end a settable time after the
reset of the activated input signals or when the maximum time limit has
elapsed.
Acknowledgment/reset
• From local HMI
• Active indications can be acknowledged or reset manually. Manual
acknowledgment and manual reset have the same meaning and is a
common signal for all the operating sequences and LEDs. The function
is positive edge triggered, not level triggered. The acknowledged or reset
is performed via the reset button and menus on the local HMI. See the
operator's manual for more information.
• Automatic reset
• Automatic reset can only be performed for indications defined for re-
starting mode with the latched sequence type 6 (LatchedReset-S). When
automatic reset of the LEDs has been performed, still persisting
indications will be indicated with a steady light.
Operating sequences
The operating sequences can be of type Follow or Latched.
• For the Follow type the LED follows the input signal completely.
• For the Latched type each LED latches to the corresponding input signal until
it is reset.
56
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI
Figure 12 show the function of available sequences that are selectable for each
LED separately.
The letters S and F in the sequence names have the meaning S = Steady and F =
Flashing.
At the activation of the input signal, the indication operates according to the
selected sequence diagrams.
In the sequence diagrams the LEDs have the characteristics as shown in figure 12.
en05000506.vsd
IEC05000506 V1 EN
Sequence 1 (Follow-S)
This sequence follows all the time, with a steady light, the corresponding input
signals. It does not react on acknowledgment or reset. Every LED is independent of
the other LEDs in its operation.
Activating
signal
LED
IEC01000228_2_en.vsd
IEC01000228 V2 EN
Sequence 2 (Follow-F)
This sequence is the same as sequence 1, Follow-S, but the LEDs are flashing
instead of showing steady light.
Sequence 3 (LatchedAck-F-S)
This sequence has a latched function and works in collecting mode. Every LED is
independent of the other LEDs in its operation. At the activation of the input signal,
the indication starts flashing. After acknowledgment the indication disappears if
57
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI
the signal is not present any more. If the signal is still present after
acknowledgment it gets a steady light.
Activating
signal
LED
Acknow.
en01000231.vsd
IEC01000231 V1 EN
Sequence 4 (LatchedAck-S-F)
This sequence has the same functionality as sequence 3, but steady and flashing
light have been alternated.
Sequence 5 (LatchedColl-S)
This sequence has a latched function and works in collecting mode. At the
activation of the input signal, the indication will light up with a steady light. The
difference to sequence 3 and 4 is that indications that are still activated will not be
affected by the reset that is, immediately after the positive edge of the reset has
been executed a new reading and storing of active signals is performed. Every LED
is independent of the other LEDs in its operation.
Activating
signal
LED
Reset
IEC01000235_2_en.vsd
IEC01000235 V2 EN
Sequence 6 (LatchedReset-S)
In this mode all activated LEDs, which are set to sequence 6 (LatchedReset-S), are
automatically reset at a new disturbance when activating any input signal for other
LEDs set to sequence 6 (LatchedReset-S). Also in this case indications that are still
activated will not be affected by manual reset, that is, immediately after the
positive edge of that the manual reset has been executed a new reading and storing
58
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI
of active signals is performed. LEDs set for sequence 6 are completely independent
in its operation of LEDs set for other sequences.
Definition of a disturbance
A disturbance is defined to last from the first LED set as LatchedReset-S is
activated until a settable time, tRestart, has elapsed after that all activating signals
for the LEDs set as LatchedReset-S have reset. However if all activating signals
have reset and some signal again becomes active before tRestart has elapsed, the
tRestart timer does not restart the timing sequence. A new disturbance start will be
issued first when all signals have reset after tRestart has elapsed. A diagram of this
functionality is shown in figure 16.
From
disturbance
length control ³1 New
per LED ³1 disturbance
set to
sequence 6
tRestart
& t
&
³1
³1
&
en01000237.vsd
IEC01000237 V1 EN
In order not to have a lock-up of the indications in the case of a persisting signal
each LED is provided with a timer, tMax, after which time the influence on the
definition of a disturbance of that specific LED is inhibited. This functionality is
shown i diagram in figure 17.
Activating signal
To LED
To disturbance
AND
tMax length control
t
en05000507.vsd
IEC05000507 V1 EN
59
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000239_2-en.vsd
IEC01000239 V2 EN
Figure 19 shows the timing diagram for a new indication after tRestart time has
elapsed.
Disturbance Disturbance
tRestart tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000240_2_en.vsd
IEC01000240 V2 EN
60
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI
Figure 20 shows the timing diagram when a new indication appears after the first
one has reset but before tRestart has elapsed.
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000241_2_en.vsd
IEC01000241 V2 EN
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000242_2_en.vsd
IEC01000242 V2 EN
61
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI
IEC05000508_2_en.vsd
IEC05000508 V2 EN
62
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI
63
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI
64
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
4.1 Authorization
To safeguard the interests of our customers, both the IED and the tools that are
accessing the IED are protected, subject of authorization handling. The concept of
authorization, as it is implemented in the IED and in PCM600 is based on the
following facts:
Be sure that the user logged on to the IED has the access required
when writing particular data to the IED from PCM600.
65
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
The IED users can be created, deleted and edited only with the User Management
Tool (UMT) within PCM600. The user can only LogOn or LogOff on the local
HMI on the IED, there are no users, groups or functions that can be defined on
local HMI.
66
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
At delivery the default user is the SuperUser. No Log on is required to operate the
IED until a user has been created with the User Management Tool.
Once a user is created and downloaded to the IED, that user can perform a Log on,
introducing the password assigned in the tool.
If there is no user created, an attempt to log on will display a message box: “No
user defined!”
If one user leaves the IED without logging off, then after the timeout (set in Main
menu/Settings/General Settings/HMI/Screen/Display Timeout) elapses, the IED
returns to Guest state, when only reading is possible. The display time out is set to
60 minutes at delivery.
If there are one or more users created with the User Management Tool and
downloaded into the IED, then, when a user intentionally attempts a Log on or
when the user attempts to perform an operation that is password protected, the Log
on window will appear.
The cursor is focused on the User identity field, so upon pressing the “E” key, the
user can change the user name, by browsing the list of users, with the “up” and
“down” arrows. After choosing the right user name, the user must press the “E”
key again. When it comes to password, upon pressing the “E” key, the following
character will show up: “$”. The user must scroll for every letter in the password.
After all the letters are introduced (passwords are case sensitive) choose OK and
press the “E” key again.
If everything is alright at a voluntary Log on, the local HMI returns to the
Authorization screen. If the Log on is OK, when required to change for example a
password protected setting, the local HMI returns to the actual setting folder. If the
Log on has failed, then the Log on window opens again, until either the user makes
it right or presses “Cancel”.
4.2.1 Introduction
Self supervision with internal event list function listens and reacts to internal
system events, generated by the different built-in self-supervision elements. The
internal events are saved in an internal event list.
67
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
The self-supervision function status can be monitored from the local HMI, from the
Event Viewer in PCM600 or from a SMS/SCS system.
Under the Diagnostics menu in the local HMI the present information from the self-
supervision function can be reviewed. The information can be found under Main
menu/Diagnostics/Internal events or Main menu/Diagnostics/IED status/
General. The information from the self-supervision function is also available in the
Event Viewer in PCM600.
IEC04000520 V1 EN
68
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
IO fail
OR Set e.g. BIM 1 Error
IO stopped
Reset
IO started
e.g. IOM2 Error OR
e.g. IO (n) Error Internal
OR FAIL
LON ERROR
TIMESYNCHERROR
OR TIMESYNCHERROR
Time reset Set
SYNCH OK Reset
SETCHGD
Settings changed
1 second pulse
en04000519-1.vsd
IEC04000519 V2 EN
Some signals are available from the INTERRSIG function block. The signals from
this function block are sent as events to the station level of the control system. The
signals from the INTERRSIG function block can also be connected to binary
outputs for signalization via output relays or they can be used as conditions for
other functions if required/desired.
Individual error signals from I/O modules can be obtained from respective module
in the Signal Matrix tool. Error signals from time synchronization can be obtained
from the time synchronization block TIME.
Self supervision provides several status signals, that tells about the condition of the
IED. As they provide information about the internal status of the IED, they are also
called internal signals. The internal signals can be divided into two groups.
• Standard signals are always presented in the IED, see table 15.
• Hardware dependent internal signals are collected depending on the hardware
configuration, see table 16.
69
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
70
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
The analog signals to the A/D converter is internally distributed into two different
converters, one with low amplification and one with high amplification, see figure
25.
ADx
Adx_Low
x1
u1
x2
Adx
Adx_High Controller
x1
u1
x2
en05000296-2-en.vsd
IEC05000296 V2 EN
71
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
The technique to split the analog input signal into two A/D converters with
different amplification makes it possible to supervise the incoming signals under
normal conditions where the signals from the two converters should be identical.
An alarm is given if the signals are out of the boundaries. Another benefit is that it
improves the dynamic performance of the A/D conversion.
When the signal is within measurable limits on both channels, a direct comparison
of the two channels can be performed. If the validation fails, the CPU will be
informed and an alarm will be given.
IEC09000787 V1 EN
72
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
4.3.1 Introduction
Use the time synchronization source selector to select a common source of absolute
time for the IED when it is a part of a protection system. This makes comparison of
events and disturbance data between all IEDs in a station automation system
possible. A common source shall be used for IED and merging unit when IEC
61850-9-2LE process bus communication is used.
Time definitions
The error of a clock is the difference between the actual time of the clock, and the
time the clock is intended to have. The rate accuracy of a clock is normally called
the clock accuracy and means how much the error increases, that is how much the
clock gains or loses time. A disciplined (trained) clock knows its own faults and
tries to compensate for them.
73
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
External
Synchronization
sources Time tagging and general synchronisation
Off
Comm- Protection
LON Events
Time- unication and control
SPA Regulator functions
Min. pulse
(Setting,
GPS see
SW-time
technical
SNTP
reference
DNP manual) Connected when GPS-time is
IRIG-B used for differential protection
PPS
*IEC 61850-9-2
IEC08000287-2-en.vsd
IEC08000287 V2 EN
All time tagging is performed by the software clock. When for example a status
signal is changed in the protection system with the function based on free running
hardware clock, the event is time tagged by the software clock when it reaches the
event recorder. Thus the hardware clock can run independently.
The echo mode for the differential protection is based on the hardware clock. Thus,
there is no need to synchronize the hardware clock and the software clock.
The synchronization of the hardware clock and the software clock is necessary only
when GPS or IRIG B 00X with optical fibre, IEEE 1344 is used for differential
protection. The two clock systems are synchronized by a special clock
synchronization unit with two modes, fast and slow. A special feature, an
automatic fast clock time regulator is used. The automatic fast mode makes the
synchronization time as short as possible during start-up or at interruptions/
disturbances in the GPS timing. The setting fast or slow is also available on the
local HMI.
If a GPS clock is used for other 670 series IEDs than line differential RED670, the
hardware and software clocks are not synchronized
74
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
When the time difference is >16us, the differential function is blocked and the time
regulator for the hardware clock is automatically using a fast mode to synchronize
the clock systems. The time adjustment is made with an exponential function, i.e.
big time adjustment steps in the beginning, then smaller steps until a time deviation
between the GPS time and the differential time system of >16us has been reached.
Then the differential function is enabled and the synchronization remains in fast
mode or switches to slow mode, depending on the setting.
Synchronization principle
From a general point of view synchronization can be seen as a hierarchical
structure. A function is synchronized from a higher level and provides
synchronization to lower levels.
Synchronization from
a higher level
Function
Optional synchronization of
modules at a lower level
IEC09000342-1-en.vsd
IEC09000342 V1 EN
75
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
The IED has a built-in real-time clock (RTC) with a resolution of one second. The
clock has a built-in calendar that handles leap years through 2038.
Synchronization messages configured as coarse are only used for initial setting of
the time. After this has been done, the messages are checked against the internal
time and only an offset of more than 10 seconds resets the time.
Rate accuracy
In the IED, the rate accuracy at cold start is 100 ppm but if the IED is synchronized
for a while, the rate accuracy is approximately 1 ppm if the surrounding
temperature is constant. Normally, it takes 20 minutes to reach full accuracy.
76
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
Three main alternatives of external time synchronization are available. Either the
synchronization message is applied via any of the communication ports of the IED
as a telegram message including date and time or as a minute pulse, connected to a
binary input, or via GPS. The minute pulse is used to fine tune already existing
time in the IEDs.
• Coarse message is sent every minute and comprises complete date and time,
that is, year, month, day, hours, minutes, seconds and milliseconds.
• Fine message is sent every second and comprises only seconds and milliseconds.
IEC60870-5-103 is not used to synchronize the IED, but instead the offset between
the local time in the IED and the time received from 103 is added to all times (in
events and so on) sent via 103. In this way the IED acts as it is synchronized from
various 103 sessions at the same time. Actually, there is a “local” time for each 103
session.
77
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
The minute pulse is connected to any channel on any Binary Input Module in the
IED. The electrical characteristic is thereby the same as for any other binary input.
The definition of a minute pulse is that it occurs one minute after the last pulse. As
only the flanks are detected, the flank of the minute pulse shall occur one minute
after the last flank.
Pulse data:
78
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
en05000251.vsd
IEC05000251 V1 EN
The default time-out-time for a minute pulse is two minutes, and if no valid minute
pulse is received within two minutes a SYNCERR will be given.
If contact bounces occurs, only the first pulse will be detected as a minute pulse.
The next minute pulse will be registered first 60 s - 50 ms after the last contact bounce.
If the minute pulses are perfect, for example, it is exactly 60 seconds between the
pulses, contact bounces might occur 49 ms after the actual minute pulse without
effecting the system. If contact bounces occurs more than 50 ms, for example, it is
less than 59950 ms between the two most adjacent positive (or negative) flanks, the
minute pulse will not be accepted.
79
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
IRIG-B is a protocol used only for time synchronization. A clock can provide local
time of the year in this format. The “B” in IRIG-B states that 100 bits per second
are transmitted, and the message is sent every second. After IRIG-B there numbers
stating if and how the signal is modulated and the information transmitted.
To receive IRIG-B there are two connectors in the IRIG-B module, one galvanic
BNC connector and one optical ST connector. IRIG-B 12x messages can be
supplied via the galvanic interface, and IRIG-B 00x messages can be supplied via
either the galvanic interface or the optical interface, where x (in 00x or 12x) means
a number in the range of 1-7.
“00” means that a base band is used, and the information can be fed into the IRIG-
B module via the BNC contact or an optical fiber. “12” means that a 1 kHz
modulation is used. In this case the information must go into the module via the
BNC connector.
The IRIG-B module also takes care of IEEE1344 messages that are sent by IRIG-B
clocks, as IRIG-B previously did not have any year information. IEEE1344 is
compatible with IRIG-B and contains year information and information of the time-
zone.
It is recommended to use IEEE 1344 for supplying time information to the IRIG-B
module. In this case, send also the local time in the messages, as this local time
plus the TZ Offset supplied in the message equals UTC at all times.
For the time synchronization of the process bus communication (IEC 61850-9-2LE
protocol) an optical PPS or IRIG-B signal can be used. This signal should emanate
from either an external GPS clock, or from the merging unit.
An optical PPS signal can be supplied to the optical interface of the IRIG-B module.
IEC05000425-2-en.vsd
IEC05000425 V2 EN
80
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
81
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
82
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
83
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
4.4.1 Introduction
Use the six sets of settings to optimize IED operation for different system
conditions. By creating and switching between fine tuned setting sets, either from
the local HMI or configurable binary inputs, results in a highly adaptable IED that
can cope with a variety of system scenarios.
A setting group is selected by using the local HMI, from a front connected personal
computer, remotely from the station control or station monitoring system or by
activating the corresponding input to the ActiveGroup function block.
Each input of the function block can be configured to connect to any of the binary
inputs in the IED. To do this PCM600 must be used.
The external control signals are used for activating a suitable setting group when
adaptive functionality is necessary. Input signals that should activate setting groups
must be either permanent or a pulse exceeding 400 ms.
More than one input may be activated at the same time. In such cases the lower
order setting group has priority. This means that if for example both group four and
group two are set to activate, group two will be the one activated.
Every time the active group is changed, the output signal SETCHGD is sending a
pulse.
The parameter MAXSETGR defines the maximum number of setting groups in use
to switch between.
84
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
ACTIVATE GROUP 6
ACTIVATE GROUP 5
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
+RL2 ACTIVATE GROUP 1
IOx-Bly1 ActiveGroup
Æ ACTGRP1 GRP1
IOx-Bly2
Æ ACTGRP2 GRP2
IOx-Bly3
Æ ACTGRP3 GRP3
IOx-Bly4
Æ ACTGRP4 GRP4
IOx-Bly5
Æ ACTGRP5 GRP5
IOx-Bly6 ACTGRP6
Æ GRP6
SETCHGD
en05000119.vsd
IEC05000119 V2 EN
The above example also includes seven output signals, for confirmation of which
group that is active.
SETGRPS function block has an input where the number of setting groups used is
defined. Switching can only be done within that number of groups. The number of
setting groups selected to be used will be filtered so only the setting groups used
will be shown on the Parameter Setting Tool.
IEC05000433_2_en.vsd
IEC05000433 V2 EN
SETGRPS
MAXSETGR
IEC05000716_2_en.vsd
IEC05000716 V2 EN
85
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
86
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
4.5.1 Introduction
Change lock function (CHNGLCK) is used to block further changes to the IED
configuration and settings once the commissioning is complete. The purpose is to
block inadvertent IED configuration changes beyond a certain point in time.
The function, when activated, will still allow the following changes of the IED
state that does not involve reconfiguring of the IED:
• Monitoring
• Reading events
• Resetting events
• Reading disturbance data
• Clear disturbances
• Reset LEDs
• Reset counters and other runtime component states
• Control operations
• Set system time
• Enter and exit from test mode
• Change of active setting group
The binary input signal LOCK controlling the function is defined in ACT or SMT:
Binary input Function
1 Activated
0 Deactivated
IEC09000946-1-en.vsd
IEC09000946 V1 EN
87
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
4.6.1 Introduction
When the Test mode functionality TESTMODE function is activated, protection
functions in the IED are automatically blocked. It is then possible to unblock the
protection functions individually from the local HMI or the Parameter Setting tool
to perform required tests.
When leaving TESTMODE, all blockings are removed and the IED resumes
normal operation. However, if during TESTMODE operation, power is removed
and later restored, the IED will remain in TESTMODE with the same protection
functions blocked or unblocked as before the power was removed. All testing will
be done with actually set and configured values within the IED. No settings will be
changed, thus mistakes are avoided.
While the IED is in test mode, the ACTIVE output of the function block
TESTMODE is activated. The other outputs of the function block TESTMODE
shows the generator of the “Test mode: On” state — input from configuration
(OUTPUT output is activated) or setting from local HMI (SETTING output is
activated).
While the IED is in test mode, the yellow START LED will flash and all functions
are blocked. Any function can be unblocked individually regarding functionality
and event signalling.
Most of the functions in the IED can individually be blocked by means of settings
from the local HMI. To enable these blockings the IED must be set in test mode
(output ACTIVE is activated), see example in figure 35. When leaving the test
88
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
mode, that is entering normal mode, these blockings are disabled and everything is
set to normal operation. All testing will be done with actually set and configured
values within the IED. No settings will be changed, thus no mistakes are possible.
The blocked functions will still be blocked next time entering the test mode, if the
blockings were not reset.
The blocking of a function concerns all output signals from the actual function, so
no outputs will be activated.
When a binary input is used to set the IED in test mode and a
parameter, that requires restart of the application, is changed, the
IED will re-enter test mode and all functions will be blocked, also
functions that were unblocked before the change. During the re-
entering to test mode, all functions will be temporarily unblocked
for a short time, which might lead to unwanted operations. This is
only valid if the IED is put in TEST mode by a binary input, not by
local HMI.
Each of the protection functions includes the blocking from the TESTMODE
function block. A typical example from the undervoltage function is shown in
figure 35.
The functions can also be blocked from sending events over IEC 61850 station bus
to prevent filling station and SCADA databases with test events, for example
during a maintenance test.
89
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
U Disconnection
Normal voltage
U1<
U2<
tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2
Time
Block step 1
Block step 2
en05000466.vsd
IEC05000466 V1 EN
IEC09000219-1.vsd
IEC09000219 V1 EN
90
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
4.7.1 Introduction
IED identifiers (TERMINALID) function allows the user to identify the individual
IED in the system, not only in the substation, but in a whole region or a country.
Use only characters A-Z, a-z and 0-9 in station, object and unit names.
91
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
4.8.1 Introduction
The Product identifiers function identifies the IED. The function has seven pre-set,
settings that are unchangeable but nevertheless very important:
• IEDProdType
• ProductDef
• FirmwareVer
• SerialNo
• OrderingNo
• ProductionDate
The settings are visible on the local HMI , under Main menu/Diagnostics/IED
status/Product identifiers
They are very helpful in case of support process (such as repair or maintenance).
4.8.3 Application
The factory defined settings are very useful for identifying a specific version and
very helpful in the case of maintenance, repair, interchanging IEDs between
different Substation Automation Systems and upgrading. The factory made settings
can not be changed by the customer. They can only be viewed. The settings are
found in the local HMI under Main menu/Diagnostics/IED status/Product
identifiers
• IEDProdType
• Describes the type of the IED (like REL, REC or RET). Example: REL670
• ProductDef
• Describes the release number, from the production. Example: 1.1.r01
• FirmwareVer
• Describes the firmware version. Example: 1.4.51
• Firmware versions numbers are “running” independently from the
release production numbers. For every release numbers (like 1.4.51)
92
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
4.9.1 Introduction
The Signal matrix for binary inputs (SMBI) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT),
see the application manual to get information about how binary inputs are brought
in for one IED configuration.
IEC05000434-2-en.vsd
IEC05000434 V2 EN
93
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
4.10.1 Introduction
The Signal matrix for binary outputs (SMBO) function is used within the
Application Configuration Tool (ACT) in direct relation with the Signal Matrix
Tool (SMT), see the application manual to get information about how binary inputs
are sent from one IED configuration.
94
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
IEC05000439-2-en.vsd
IEC05000439 V2 EN
95
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
4.11.1 Introduction
The Signal matrix for mA inputs (SMMI) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT),
see the application manual to get information about how milliamp (mA) inputs are
brought in for one IED configuration.
IEC05000440-2-en.vsd
IEC05000440 V2 EN
96
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
4.12.1 Introduction
Signal matrix for analog inputs function SMAI (or the pre-processing function) is
used within PCM600 in direct relation with the Signal Matrix tool or the
Application Configuration tool. Signal Matrix tool represents the way analog
inputs are brought in for one IED configuration.
The output signal AI1 to AI4 are direct output of the, in SMT, connected input to
GRPxL1, GRPxL2, GRPxL3 and GRPxN, x=1-12. AIN is always the neutral
current, calculated residual sum or the signal connected to GRPxN. Note that
function block will always calculate the residual sum of current/voltage if the input
is not connected in SMT. Applications with a few exceptions shall always be
connected to AI3P.
97
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
IEC10000060-1-en.vsd
IEC10000060 V1 EN
The outputs from the above configured SMAI block shall only be
used for Overfrequency protection (SAPTOF), Underfrequency
protection (SAPTUF) and Rate-of-change frequency protection
(SAPFRC) due to that all other information except frequency and
positive sequence voltage might be wrongly calculated.
IEC05000705-2-en.vsd
IEC05000705 V2 EN
98
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
SMAI2
BLOCK AI3P
^GRP2L1 AI1
^GRP2L2 AI2
^GRP2L3 AI3
^GRP2N AI4
TYPE AIN
IEC07000130-2-en.vsd
IEC07000130 V2 EN
99
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
100
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
101
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
4.13.1 Introduction
Summation block 3 phase function 3PHSUM is used to get the sum of two sets of
three-phase analog signals (of the same type) for those IED functions that might
need it.
102
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
IEC05000441-2-en.vsd
IEC05000441 V2 EN
103
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions
4.14.1 Introduction
Authority status (ATHSTAT) function is an indication function block for user log
on activity.
Whenever one of the two events occurs, the corresponding output (USRBLKED or
LOGGEDON) is activated. The output can for example, be connected on Event
(EVENT) function block for LON/SPA.The signals are also available on IEC
61850 station bus.
IEC06000503-2-en.vsd
IEC06000503 V2 EN
104
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions
105
Technical reference manual
106
1MRK505183-UEN C Section 5
Differential protection
SYMBOL-HH V1 EN
SYMBOL-HH V1 EN
SYMBOL-HH V1 EN
SYMBOL-HH V1 EN
5.1.1 Introduction
Line differential protection applies the Kirchhoff's law and compares the currents
entering and leaving the protected multi-terminal circuit, consisting of overhead
107
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
power lines, power transformers and cables. It offers phase-segregated true current
differential protection with high sensitivity and provides phase selection
information for single-pole tripping.
The three terminal version is used for conventional two-terminal lines with or
without 1 1/2 circuit breaker arrangement in one end, as well as three terminal lines
with single breaker arrangements at all terminals.
Protected zone
IEC05000039_2_en.vsd
IEC05000039 V2 EN
The six terminal versions are used for conventional two-terminal lines with 1 1/2
circuit breaker arrangements in both ends, as well as multi terminal lines with up to
five terminals.
Protected zone
IEC05000040_2_en.vsd
IEC05000040 V2 EN
The current differential algorithm provides high sensitivity for internal faults, at the
same time as it has excellent stability for external faults. Current samples from all
CTs are exchanged between the IEDs in the line ends (master-master mode) or sent
to one IED (master-slave mode) for evaluation.
A restrained dual biased slope evaluation is made where the bias current is the
highest phase current in any line end giving a secure through fault stability even
with heavily saturated CTs. In addition to the restrained evaluation, an unrestrained
high differential current setting can be used for fast tripping of internal faults with
very high currents.
A special feature with this function is that applications with small power
transformers (rated current less than 50 % of the differential current setting)
connected as line taps (that is, as "shunt" power transformers), without
measurements of currents in the tap, can be handled. The normal load current is
108
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
here considered to be negligible, and special measures need only to be taken in the
event of a short circuit on the LV side of the transformer. In this application, the
tripping of the differential protection can be time delayed for low differential
currents to achieve coordination with down stream over current IEDs.
Protected zone
IED
IEC05000042_2_en.vsd
IEC05000042 V2 EN
109
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
Protected zone
IED IED
Comm.
Channels
IEC0500043_2_en.vsd
IEC05000043 V2 EN
Protected zone
RED RED
670 670
Comm.
Channels
en05000044.vsd
IEC05000044 V1 EN
Current samples from IEDs located geographically apart from each other, must be
time coordinated so that the current differential algorithm can be executed
correctly. In IED, it is possible to make this coordination in two different ways.
The echo method of time synchronizing is normally used whereas for applications
where transmit and receive times can differ, the optional built in GPS receivers can
be used.
In Line differential protection function, measured current values from local and
remote line ends are evaluated in order to distinguish between internal or external
faults, or undisturbed conditions.
The local currents are fed to the IED via the Analog Input Modules and thereafter
they pass the Analog to Digital Converter, as shown in figure 50.
110
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
LDCM
Current
samples from
local end
Analog Input A/D
Module Converter Current
Pre-processing
samples from
Block
remote end
LDCM
Trip commands
CH1IL1IM Calculation of Differential ³1 TRIP
CH1IL2RE fundamental and bias currents
Start L1
CH1IL2IM frequency Magnitudes of applied to
differential differential operate / bias -, Start L2
currents Output logic: TRL1
currents (3x) and unrestrained Start L3 TRL2
Currents from
all ends as & bias current characteristics TRL3
Bias current St L1 low sens - 2nd harmonic block
phasors TRIPRES
- 5th harmonic block
St L2 low sens TRIPUNRE
CH1IL1SM St L3 low sens TRIPENHA
- Cross block logic
CH1IL2SM Calculation
CH1IL3SM of [samples] 2nd h. block
- Enhanced trip for START
CH2IL1SM instantaneous internal faults STL1
differential Harmonic STL2
Instantaneous analysis - Decreased STL3
currents
Curr. samples 5th h. block sensitivity for
differential
Information
from all ends (3x) ( 2nd and 5th)
currents external faults BLK2H
(samples) BLK2HL1
- BLK2HL2
CH1INSRE Conditional trip for BLK2HL3
CH1INSIM Calculation simultaneous external
of and internal faults BLK5H
CH1INSRE High sensitive Internal fault
negative-- BLK5HL1
CH1INSIM Two to six internal/external fault BLK5HL2
sequence contributions discriminator BLK5HL3
External fault -
differential to neg. seq. Conditional extra time
Neg. seq. current differential delay for trip signals
currents from current as INTFAULT
(1x)
all ends phasors EXTFAULT
as phasors
IEC05000294_2_en.vsd
IEC05000294 V2 EN
The remote currents are received to the IED as samples via a communication link.
When entering the IED, they are processed in the Line Differential Communication
Module (LDCM) where they are time coordinated with the local current samples,
and interpolated in order to be comparable with the local samples.
111
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
In the Pre-Processing Block, the real and imaginary parts of the fundamental
frequency phase currents and negative sequence currents are derived. Together
with the current samples, they are then forwarded to the differential function block
where three different analyses are carried out.
The first analysis is the classical differential and bias current evaluation with the
characteristic as seen in figure 51. Line differential protection is phase segregated
where the differential current is the vectorial sum of all measured currents taken
separately for each phase. The bias current, on the other hand, is considered as the
greatest phase current in any line end and it is common for all three phases. The
two slopes (SlopeSection1, SlopeSection2) and breakpoints (EndSection1,
EndSection2) can be set in PCM600 or via the local HMI.
Current values plotted above the characteristic formed by IdMin and the dual slope
will give a start in that phase. The level IdMinHigh is a setting value that is used to
temporarily decrease the sensitivity in situations when:
There is also an unrestrained high differential current setting that can be used for
fast tripping of internal faults with very high currents.
112
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
Operate current
[ in pu of IBase]
Operate
5
unconditionally
UnrestrainedLimit
4
Operate IdMinHigh
3 C
conditionally
A B
2
Section 1 Section 2 Section 3
SlopeSection3
1
IdMin
SlopeSection2 Restrain
0
0 1 2 3 4 5
en05000300.vsd
IEC05000300 V1 EN
where:
1. IdMin
2. EndSection1
3. EndSection2
SlopeSection2
4.
5. SlopeSection3
The second analysis is the 2nd and 5th harmonic analysis on the differential current.
Occurrence of these harmonics over a level that is set separately for each one will
block tripping action from the biased slope evaluation.
113
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
The third analysis is the negative sequence current analysis. Effectively this is a
fault discriminator that distinguishes between internal and external faults. It works
such that the phase angle of the negative sequence current from the local end is
compared with the phase angle of the sum of the negative sequence currents from
the remote ends. The characteristic for this fault discriminator is shown in
figure 52, where the directional characteristic is defined by the two setting
parameters IminNegSeq and NegSeqRoa.
90 deg
120 deg
If one or the Internal/external
other of fault boundary
currents is too
low, then no
measurement NegSeqROA
is done, and
(Relay
120 degrees
Operate
is mapped Angle)
IMinNegSeq
External Internal
fault fault
region region
270 deg
en05000188.vsd
IEC05000188 V1 EN
114
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
With reference to figure 50, the outputs from the three analysis blocks are fed to
the output logic. Figure 53 shows a simplified block diagram of this output logic
where only trip commands and no alarm signals are shown for simplicity.
Trip unrestrained L1
TRIP
Trip unrestrained L2 OR
Trip unrestrained L3
Start L1 TRL1
AND OR
Start L2 OR AND
OR
Start L3 TRL2
AND OR
OR AND
OR
OR TRL3
AND
St L1 IdMinHigh OR AND
OR
St L2 IdMinHigh
St L3 IdMinHigh
Internal fault
AND
NegSeqDiffEn
tIdMinHigh
AND t
External fault
OR
Line energizing
OR
AND
CrossBlockEn
IEC05000295-2-en.vsd
IEC05000295 V2 EN
Remembering that current values plotted above the characteristic formed by IdMin
and the dual slope in figure 52 are said to give a start, the output logic can be
summarized as follows:
• A start in one phase, gives a trip under the condition that the content of 2nd and
5th harmonic is below the set level for these harmonics. Otherwise it is blocked
115
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
as long as the harmonic is above the set level. However, when a line is
energized the current setting value IdMinHigh is used. Effectively this means
that the line A-B-C in figure 51 forms the characteristic.
• Current values above the unrestrained limit gives a trip irrespective of any
presence of harmonics.
• Classification of a fault as internal by the negative sequence fault
discriminator, will give a trip under the condition that a start has occurred in
that phase. This means that any harmonic blocking is then overridden.
However, occurrence of harmonics at the same time as the differential current
is below the level IdMinHigh, will block a trip even though the fault is
classified as internal. This latter condition is to prevent unwanted trips when
energizing a line tap transformer.
• Classification of a fault as external by the negative sequence fault
discriminator will cause IdMinHigh to be used as the lower limit for the
restrained characteristic according to figure 51. Cross blocking will also be
activated in this situation.
Values of the pre-fault differential currents are not updated under disturbance
conditions. The updating process is resumed 50 ms after normal conditions have
been restored. Normal conditions are only considered if there are no start signals,
neither internal nor external fault is declared, the power system is symmetrical and
so on.
It is thus obvious that the change in charging current that the fault causes by
decreasing the system voltage is not considered in the algorithm, a matter that is
further discussed in the application manual.
Note that all small pre-fault differential currents are subtracted, no matter what
their origin. Besides the true charging currents, the following currents are eliminated:
116
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
from the different line ends can be compared without introducing irrelevant errors.
Accuracy requirements on this time coordination are extremely high.
In Line differential protection, the time coordination is made with the so-called
echo method, which can be complemented with GPS synchronization as an option.
Each IED has an accurate local clock with a very small time drift. This clock
makes time tagging of telegrams, and the echo method is then used to find out the
time difference between the clocks in two ends of a power line.
Referring to figure 54, it works such that the transmission time to send a message
from station B to station A (T1 → T2) and receive a message from A to B (T3 →
T4) is measured. The time instances T2 and T3 are taken with the local clock
reference of station A, and the time instances T1 and T4 are taken with the local
clock reference of station B.
T2 T3
A
B
T1 T4
en05000293.vsd
IEC05000293 V1 EN
Calculation of the delay time one-way Td and the time difference Δt between the
clocks in A and B is then possible to do with equation 2 and equation 3, which are
only valid under the condition that the send and receive times are equal.
(T2 - T1 ) + (T4 - T3 )
Td =
2
EQUATION1358 V1 EN (Equation 2)
(T1 + T4 ) - (T2 + T3 )
Dt =
2
EQUATION1359 V1 EN (Equation 3)
Δt is calculated every time a telegram is received, and the time difference is then
used to adjust and interpolate the current measurements from the remote end before
the current differential algorithm is executed.
117
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
When the delay symmetry is lost, the expression for Δt given above is no longer
valid, and GPS synchronization of the local IED clocks must be used.
Including the optional GPS, means that there will be one GPS receiver module in
each IED, synchronizing its local IED clock. As GPS synchronization is very
accurate, in the order of 1 μs, all IEDs in the same line differential scheme will
have the same clock reference. It is then possible to detect asymmetric transmission
time delay and compensate for it.
When the IED is equipped with GPS, this hardware is integrated in the IED.
Besides the GPS receiver itself, it also consists of filters and regulators for post
processing of the GPS time synch pulse, which is necessary to achieve a reliable
GPS synchronization. Especially short interruptions and spurious out of synch GPS
signals are handled securely in this way.
Communication principle
For a two-terminal line, the current from the local CT needs to be communicated
over a 64 kbit/s channel to the remote line end, and the remote end current
communicated back on the same channel. If there is, for example, a three terminal
line another 64 kbit/s channel will be needed to exchange the same local current
with the third line end current.
In one-and-a-half breaker arrangements, there are two local currents meaning two
64 kbit/s channels to each remote substation. Alternatively, it is possible to add
together the two local currents before sending them and in that way reduce the
number of communication channels needed. This is achieved by selecting proper
setting for parameter TransmCurr (CT-SUM, CT-DIFF1 or CT-DIFF2). However,
information about bias currents is reduced if the alternative option is followed. For
further information and discussions on this matter, refer to the Application manual.
118
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
made in each IED. This means that a 64 kbit/s communication channel is needed
between every IED included in the same line differential protection zone.
Protected zone
IED IED
Comm. Channels
IEC05000292_2_en.vsd
IEC05000292 V2 EN
In the master-slave system, current samples are sent from all slave IEDs to one
master IED where the evaluation is made and trip signals are sent to the remote
ends when needed. In this system, a 64 kbit/s communication channel is only
needed between the master, and each one of the slave IEDs, as shown in figure 56.
Protected zone
IED IED
Comm. Channels
IEC05000291_2_en.vsd
IEC05000291 V2 EN
Test mode
Line differential protection function in one IED can be set in test mode. This can
block the trip outputs on that IED, and set the remote IEDs in a remote test mode,
so that injected currents can be echoed back phase shifted and with a settable
amplitude. The trip outputs in the remote IEDs can also be blocked automatically.
For further information, refer to the installation and commissioning manual.
119
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
Time
0 5 10 15 20 25 30 35 (ms)
en05000290.vsd
IEC05000290 V1 EN
where:
x is the current sampling moment
Telecom. Network
LD LD
CM CM
LD LD
CM CM
Telecom. Network
Primary
channel
Secondary redundant
channel en05000289.vsd
IEC05000289 V1 EN
Figure 58: Direct fibre optical connection between two IEDs with LDOM over
longer distances.
120
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
For more details about the remote communication see section "Remote
communication" and the application manual.
The open CT circuit condition creates unexpected operations for Line differential
protection under the normal load conditions. It is also possible to damage
secondary equipment due to high voltage produced from open CT circuit outputs.
Therefore, it is always a requirement from security and reliability points of view to
have open CT detection function to block Line differential protection function in
case of open CT conditions and at the same time, produce the alarm signal to the
operational personal to make quick remedy actions to correct the open CT condition.
If an open CT is detected and the output OPENCT set to 1, then all the differential
functions are blocked, except of the unrestrained (instantaneous) differential. An
121
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
The open CT feature works only during normal loading condition. Thus, the open
CT feature must be automatically disabled for all external faults, big overloads and
inrush conditions.
The open CT algorithm provides detailed information about the location of the
defective CT secondary circuit. The algorithm clearly indicates IED side, CT input
and phase in which open CT condition has been detected. These indications are
provided via the following outputs from Line differential protection function:
Once the open CT condition is declared, the algorithm stops to search for further
open CT circuits. It waits until the first open CT circuit has been corrected. Note
that once the open CT condition has been detected, it can be automatically reset
within the differential function. It is not possible to externally reset open CT
condition. To reset the open CT circuit alarm automatically, the following
conditions must be fulfilled:
After the reset, the open CT detection algorithm starts again to search for any other
open CT circuit within the protected zone.
There is space for eight binary signals integrated in the telegram of the line
differential analog communication. For further information, refer to section
"Binary signal transfer".
122
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
The function acts as the interface to and from Line differential protection.
IEC06000252-2-en.vsd
IEC06000252 V2 EN
123
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
L6CPDIF
I3P1* TRIP
I3P2* TRL1
I3P3* TRL2
I3P4* TRL3
I3P5* TRIPRES
I3P6* TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000253-2-en.vsd
IEC06000253 V2 EN
LT3CPDIF
I3P1* TRIP
I3P2* TRL1
I3P3* TRL2
TRL3
TRIPRES
TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000254_2_en.vsd
IEC06000254 V2 EN
124
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
LT6CPDIF
I3P1* TRIP
I3P2* TRL1
I3P3* TRL2
I3P4* TRL3
I3P5* TRIPRES
I3P6* TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000255_2_en.vsd
IEC06000255 V2 EN
LDLPDIF
CTFAIL TRIP
OUTSERV TRL1
BLOCK TRL2
TRL3
TRLOCAL
TRLOCL1
TRLOCL2
TRLOCL3
TRREMOTE
DIFLBLKD
IEC05000394-2-en.vsd
IEC05000394 V3 EN
125
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
126
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
127
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
128
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
129
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
130
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
131
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
132
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
133
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
134
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
135
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
136
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
137
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
138
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
139
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
140
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
SlopeSection2 (10.0-50.0)% -
SlopeSection3 (30.0-100.0)% -
EndSection 1 (20–150)% of IBase -
EndSection 2 (100–1000)% of IBase -
Unrestrained limit function (100–5000)% of IBase ± 2.0% of Ir at I ≤ Ir
± 2.0% of I at I > Ir
Inverse characteristics, see table 19 curve types See table 644 and
644, 645 and table 646 table 645
Operate time 25 ms typically at 0 to 10 x Id -
SYMBOL-CC V2 EN
141
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
5.2.1 Introduction
The 1Ph High impedance differential protection HZPDIF function can be used
when the involved CT cores have the same turn ratio and similar magnetizing
characteristic. It utilizes an external summation of the phases and neutral current
and a series resistor and a voltage dependent resistor externally to the IED.
See the application manual for operating voltage and sensitivity calculation.
The logic diagram shows the operation principles for the 1Ph High impedance
differential protection function HZPDIF, see figure 64. It is a simple one step IED
with an additional lower alarm level. By activating inputs, the HZPDIF function
can either be blocked completely, or only the trip output.
IEC05000301 V1 EN
Figure 64: Logic diagram for 1Ph High impedance differential protection
HZPDIF
142
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection
IEC05000363-2-en.vsd
IEC05000363 V2 EN
143
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection
144
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
S00346 V1 EN
S00346 V1 EN
Z<->
IEC09000167 V1 EN
6.1.1 Introduction
The line distance protection is a, up to four zone full scheme protection with three
fault loops for phase-to-phase faults and three fault loops for phase-to-earth fault
for each of the independent zones. Individual settings for each zone in resistive and
reactive reach gives flexibility for use as back-up protection for transformer
connected to overhead lines and cables of different types and lengths.
ZMQPDIS together with Phase selection with load encroachment FDPSPDIS has
functionality for load encroachment, which increases the possibility to detect high
resistive faults on heavily loaded lines, as shown in figure66.
145
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
Forward
operation
Reverse
operation
en05000034.vsd
IEC05000034 V1 EN
Figure 66: Typical quadrilateral distance protection zone with Phase selection
with load encroachment function FDPSPDIS activated
The independent measurement of impedance for each fault loop together with a
sensitive and reliable built-in phase selection makes the function suitable in
applications with single-phase autoreclosing.
The execution of the different fault loops within the IED are of full scheme type,
which means that each fault loop for phase-to-earth faults and phase-to-phase faults
for forward and reverse faults are executed in parallel.
146
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
en05000458.vsd
IEC05000458 V1 EN
Figure 67: The different measuring loops at phase-to-earth fault and phase-to-
phase fault.
The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a start element to select correct voltages and current
depending on fault type. Each distance protection zone performs like one
independent distance protection IED with six measuring elements.
The distance measuring zone includes six impedance measuring loops; three
intended for phase-to-earth faults, and three intended for phase-to-phase as well as,
three-phase faults.
The distance measuring zone will essentially operate according to the non-
directional impedance characteristics presented in figure 68 and figure 69. The phase-
to-earth characteristic is illustrated with the full loop reach while the phase-to-
phase characteristic presents the per phase reach.
147
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
X (Ohm/loop)
R1PE+Rn
RFPE RFPE
X0PE-X1PE
Xn =
3
X1PE+Xn R0PE-R1PE
Rn =
3
jN jN
R (Ohm/loop)
RFPE RFPE
X1PE+Xn
RFPE RFPE
en08000280-2-en.vsd
R1PE+Rn
IEC08000280 V1 EN
148
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
X (Ohm/phase)
j j
R (Ohm/phase)
RFPP RFPP
2 2
X1PP
The fault loop reach with respect to each fault type may also be presented as in
figure 70. Note in particular the difference in definition regarding the (fault)
resistive reach for phase-to-phase faults and three-phase faults.
149
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
IL1 R1 + j X1
Phase-to-earth
UL1
element
Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)
0
IN (R0-R1)/3 +
j (X0-X1)/3 )
IL1 R1 + j X1 Phase-to-phase
UL1 element L1-L2
Phase-to-phase
fault in phase RFPP
L1-L2 IL2
UL2 (Arc resistance)
R1 + j X1
The R1 and jX1 in figure 70 represents the positive sequence impedance from the
measuring point to the fault location. The settings RFPE and RFPP are the
eventual fault resistances in the faulty place.
Regarding the illustration of three-phase fault in figure 70, there is of course fault
current flowing also in the third phase during a three-phase fault. The illustration
merely reflects the loop measurement, which is made phase-to-phase.
150
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
X X X
R R R
en05000182.vsd
IEC05000182 V1 EN
For zone 1 with load compensation feature the additional criterion applies, that all
phase-to-earth loops will be blocked when IN < IMinOpIN, regardless of the phase
currents.
ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector
sum of the three-phase currents, that is, residual current 3I0.
ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.
Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits. The
151
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
UL1 – UL2
Zapp = -------------------------
I L1 – IL2
EQUATION1222 V1 EN (Equation 4)
Here U and I represent the corresponding voltage and current phasors in the
respective phase Ln (n = 1, 2, 3)
U L1
Z app = ------------------------------
I L1 + I N × KN
EQUATION1223 V1 EN (Equation 5)
Where:
UL1, IL1 and IN are the phase voltage, phase current and residual current present to the IED
KN is defined as:
Z0 - Z1
KN =
3 × Z1
EQUATION 2105 V1 EN
Z 0 = R0 + jX 0
EQUATION2106 V1 EN
Z1 = R1 + jX 1
EQUATION2107 V1 EN
Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach
Here IN is a phasor of the residual current in IED point. This results in the same
reach along the line for all types of faults.
152
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
The formula given in equation 5 is only valid for radial feeder application without
load. When load is considered in the case of single phase-to-earth fault,
conventional distance protection might overreach at exporting end and underreach
at importing end. The IED has an adaptive load compensation which increases the
security in such applications.
Measuring elements receive current and voltage information from the A/D
converter. The check sums are calculated and compared, and the information is
distributed into memory locations. For each of the six supervised fault loops,
sampled values of voltage (U), current (I), and changes in current between samples
(DI) are brought from the input memory and fed to a recursive Fourier filter.
The filter provides two orthogonal values for each input. These values are related
to the loop impedance according to equation 6,
X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN (Equation 6)
X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt
EQUATION354 V1 EN (Equation 7)
X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt
EQUATION355 V1 EN (Equation 8)
with
w0 = 2 × p × f 0
EQUATION356 V1 EN (Equation 9)
where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency
The algorithm calculates Rmmeasured resistance from the equation for the real
value of the voltage and substitutes it in the equation for the imaginary part. The
equation for the Xm measured reactance can then be solved. The final result is
equal to:
153
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN (Equation 10)
Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN (Equation 11)
The calculated Rm and Xm values are updated each sample and compared with the
set zone reach. The adaptive tripping counter counts the number of permissive
tripping results. This effectively removes any influence of errors introduced by the
capacitive voltage transformers or by other factors.
For the L1-L2 element, the equation in forward direction is according to.
where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default
set to 15 (= -15 degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default
set to 115 degrees, see figure 72.
U1L1 is positive sequence phase voltage in phase L1
U1L1L2M is memorized voltage difference between phase L1 and L2 (L2 lagging L1)
154
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115
degrees respectively (as shown in figure 72). It should not be changed unless
system studies have shown the necessity.
ZDRDIR gives binary coded directional information per measuring loop on the
output STDIRCND.
STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048
ArgNegRes
ArgDir
R
en05000722.vsd
IEC05000722 V1 EN
Figure 72: Setting angles for discrimination of forward and reverse fault in
Directional impedance quadrilateral function ZDRDIR
The polarizing voltage is available as long as the positive sequence voltage exceeds
5% of the set base voltage UBase. So the directional element can use it for all
unsymmetrical faults including close-in faults.
For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is
restored.
155
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
• If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set IED rated current IBase), the condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.
• If the current decreases below the minimum operating value, the memory
resets until the positive sequence voltage exceeds 10% of its rated value.
Phase-to-earth related signals are designated by L1N, L2N and L3N. The phase-to-
phase signals are designated by L1L2, L2L3, and L3L1.
Two types of function block, ZMQPDIS and ZMQAPDIS, are used in the IED.
ZMQPDIS is used for zone 1 and ZMQAPDIS for zone 2 - 5.
The STCND input signal represents a connection of six different integer values
from Phase selection with load encroachment, quadrilateral characteristic function
FDPSPDIS within the IED, which are converted within the zone measuring
function into corresponding boolean expressions for each condition separately.
Input signal STCND is connected to FDPSPDIS function output STCNDZ.
The input signal DIRCND is used to give condition for directionality for the
distance measuring zones. The signal contains binary coded information for both
forward and reverse direction. The zone measurement function filters out the
relevant signals depending on the setting of the parameter OperationDir. It must be
configured to the STDIR output on ZDRDIR function.
156
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
IEC99000557-TIFF V1 EN
Composition of the phase start signals for a case, when the zone operates in a non-
directional mode, is presented in figure 74.
STNDL1N
OR
STNDL2N
AND STL1
STNDL3N
STNDL1L2 OR STL2
AND
STNDL2L3
STNDL3L1 AND STL3
OR
AND START
OR
BLK
en00000488.vsd
IEC00000488 V1 EN
157
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
Results of the directional measurement enter the logic circuits, when the zone
operates in directional (forward or reverse) mode, as shown in figure 75.
STNDL1N
AND
DIRL1N STZMPE
OR
STNDL2N
DIRL2N AND
STNDL3N OR STL1
DIRL3N AND AND
STNDL1L2
DIRL1L2 AND OR STL2
AND
STNDL2L3
DIRL2L3 AND
OR STL3
STNDL3L1 AND
DIRL3L1 AND
STZMPP
OR
BLK
15 ms
OR START
AND t
en05000778.vsd
IEC05000778 V2 EN
Tripping conditions for the distance protection zone one are symbolically presented
in figure 76.
158
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
en00000490-3.vsd
IEC00000490 2 V1 EN
IEC06000256-2-en.vsd
IEC06000256 V2 EN
ZMQAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND
IEC09000884-1-en.vsd
IEC09000884 V1 EN
159
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
ZDRDIR
I3P* STDIR
U3P*
IEC05000681-2-en.vsd
IEC05000681 V2 EN
160
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
Signals and settings for ZMQPDIS are valid for zone 1 while
signals and settings for ZMQAPDIS are valid for zone 2 - 5
161
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
162
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
163
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
S00346 V1 EN
S00346 V1 EN
IEC09000167 V1 EN
164
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
6.2.1 Introduction
The line distance protection is a, up to four zone full scheme protection with three
fault loops for phase-to-phase faults and three fault loops for phase-to-earth fault
for each of the independent zones. Individual settings for each zone resistive and
reactive reach give flexibility for use on overhead lines and cables of different
types and lengths.
ZMCPDIS function has functionality for load encroachment which increases the
possibility to detect high resistive faults on heavily loaded lines.
Forward
operation
Reverse
operation
en05000034.vsd
IEC05000034 V1 EN
The independent measurement of impedance for each fault loop together with a
sensitive and reliable built in phase selection makes the function suitable in
applications with single phase auto-reclosing.
The distance protection zones can operate, independent of each other, in directional
(forward or reverse) or non-directional mode. This makes them suitable, together
with different communication schemes, for the protection of power lines and cables
in complex network configurations, such as parallel lines, multi-terminal lines.
165
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
The execution of the different fault loops within the IED are of full scheme type,
which means that earth fault loop for phase-to-earth faults and phase-to-phase
faults for forward and reverse faults are executed in parallel.
Figure 81 presents an outline of the different measuring loops for the basic five,
impedance-measuring zones.
en05000458.vsd
IEC05000458 V1 EN
Figure 81: The different measuring loops at phase-to-earth fault and phase-to-
phase fault
The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a start element to select correct voltages and current
depending on fault type. Each distance protection zone performs like one
independent distance protection IED with six measuring elements.
166
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
X (Ohm/loop)
R1PE+RNFw
X 0 PE - X 1FwPE
RFRvPE RFFwPE XNFw =
3
PG- -
XX00PE 1RVPG 1RvPE
1XRVPE
X
XNRV XNRv
XNRV == =XXNFw
3
×
3 X 1FwPE
XX0 PE - X-1X
0 PG FWPE
1FWPG
XNFW==
XNFW
X1FwPE+XNFw 3 3 R0 PE - R1PE
RNFw =
jN jN 3
R (Ohm/loop)
RFRvPE RFFwPE
X1RvPE+XNRv
jN
RFRvPE RFFwPE
IEC09000625-1-en.vsd
IEC09000625 V1 EN
167
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
X (Ohm/phase)
j j
jN R (Ohm/phase)
RFRvPP RFFwPP
2 2
X1RvPP
jN
RFRvPP RFFwPP
2 2
IEC09000632-1-en.vsd
IEC09000632 V1 EN
The fault loop reach with respect to each fault type may also be presented as in
figure 84. Note in particular the difference in definition regarding the (fault)
resistive reach for phase-to-phase faults and three-phase faults.
168
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
IL1 R1 + j X1
Phase-to-earth
UL1
element
Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)
0
IN (R0-R1)/3 +
j (X0-X1)/3 )
IL1 R1 + j X1 Phase-to-phase
UL1 element L1-L2
Phase-to-phase
fault in phase RFPP
L1-L2 IL2
UL2 (Arc resistance)
R1 + j X1
The R1 and jX1 in figure 84 represents the positive sequence impedance from the
measuring point to the fault location. The RFPE and RFPP is the eventual fault
resistance in the fault place.
Regarding the illustration of three-phase fault in figure 84, there is of course fault
current flowing also in the third phase during a three-phase fault. The illustration
merely reflects the loop measurement, which is made phase-to-phase.
169
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
X X X
R R R
en05000182.vsd
IEC05000182 V1 EN
For zone 1 with load compensation feature the additional criterion applies, that all
phase-to-earth loops will be blocked when IN < IMinOpIN, regardless of the phase
currents.
ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector
sum of the three phase currents, that is, residual current 3I0.
ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.
Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits. The
170
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
UL1 – UL2
Zapp = -------------------------
I L1 – IL2
EQUATION1222 V1 EN (Equation 14)
Here U and I represent the corresponding voltage and current phasors in the
respective phase.
U L1
Z app = ------------------------------
I L1 + I N × KN
EQUATION1223 V1 EN (Equation 15)
Where:
UL1, IL1 and IN are the phase voltage, phase current and residual current present to the IED
KN is defined as:
Z0 - Z1
KN =
3 × Z1
EQUATION 2105 V1 EN
Z 0 = R0 + jX 0
EQUATION2106 V1 EN
Z1 = R1 + jX 1
EQUATION2107 V1 EN
Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach
Here IN is a phasor of the residual current at the IED point. This results in the same
reach along the line for all types of faults.
171
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
The formula given in equation 15 is only valid for no loaded radial feeder
applications. When load is considered in the case of single phase-to-earth fault,
conventional distance protection might overreach at exporting end and underreach
at importing end. IED has an adaptive load compensation which increases the
security in such applications.
Measuring elements receive current and voltage information from the A/D
converter. The check sums are calculated and compared, and the information is
distributed into memory locations. For each of the six supervised fault loops,
sampled values of voltage (U), current (I), and changes in current between samples
(DI) are brought from the input memory and fed to a recursive Fourier filter.
The filter provides two orthogonal values for each input. These values are related
to the loop impedance according to equation 16,
X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN (Equation 16)
X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt
X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt
with
w0 = 2 × p × f 0
EQUATION356 V1 EN (Equation 19)
where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency
The algorithm calculates Rm measured resistance from the equation for the real
value of the voltage and substitute it in the equation for the imaginary part. The
equation for the Xm measured reactance can then be solved. The final result is
equal to:
172
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN (Equation 20)
Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN (Equation 21)
The calculated Rm and Xm values are updated each sample and compared with the
set zone reach. The adaptive tripping counter counts the number of permissive
tripping results. This effectively removes any influence of errors introduced by the
capacitive voltage transformers or by other factors.
In the basic distance protection function, the control of the memory for polarizing
voltage is performed by an under voltage control. In case of series compensated
line, a voltage reversal can occur with a relatively high voltage also when the
memory must be locked. Thus, a simple undervoltage type of voltage memory
control can not be used in case of voltage reversal. In the option for series
compensated network the polarizing quantity and memory are controlled by an
impedance measurement criterion.
At a three phase fault when no positive sequence voltage remains (all three phases
are disconnected) the memory is used for direction polarization during 100 ms.
The memory predicts the phase of the positive sequence voltage with the pre-fault
frequency. This extrapolation is made with a high accuracy and it is not the
accuracy of the memory that limits the time the memory can be used. The network
is at a three phase fault under way to a new equilibrium and the post-fault condition
can only be predicted accurately for a limited time from the pre-fault condition.
In case of a three phase fault after 100 ms the phase of the memorized voltage can
not be relied upon and the directional measurement has to be blocked. The
achieved direction criteria are sealed-in when the directional measurement is
blocked and kept until the impedance fault criteria is reset (the direction is stored
until the fault is cleared).
173
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
This memory control allows in the time domain unlimited correct directional
measurement for all unsymmetrical faults also at voltage reversal. Only at three
phase fault within the range of the set impedance reach of the criteria for control of
the polarization voltage the memory has to be used and the measurement is limited
to 100 ms and thereafter the direction is sealed-in. The special impedance
measurement to control the polarization voltage is set separately and has only to
cover (with some margin) the impedance to fault that can cause the voltage reversal.
U 1L1M
- ArgDir < arg < ArgNeg Re s
I L1
EQUATION2004 V2 EN (Equation 22)
For the L1-L2 element, the equation in forward direction is according to:
U 1L1L 2 M
- ArgDir < arg < ArgNeg Re s
I L1L 2
EQUATION2006 V2 EN (Equation 23)
where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default
set to 15 (= -15 degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default
set to 115 degrees, see figure 86.
U1L1M is positive sequence memorized phase voltage in phase L1
U1L1L2M is memorized voltage difference between phase L1 and L2 (L2 lagging L1)
The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115
degrees respectively, see figure 86, and it should not be changed unless system
studies have shown the necessity.
ZDSRDIR generates a binary coded signal on the output STDIR depending on the
evaluation where STFWL1N=1 adds 1, STRVL1N=1 adds 2, STFWL2N=1 adds 4.
174
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
ArgNegRes
ArgDir
R
en05000722.vsd
IEC05000722 V1 EN
Figure 86: Setting angles for discrimination of forward and reverse fault
Two types of function block, ZMCPDIS and ZMCAPDIS , are used in the IED.
ZMQPDIS is used for zone 1 and ZMQAPDIS for zone 2 - 5.
175
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
The STCND input signal represents a connection of six different integer values
from the phase selection function within the IED, which are converted within the
zone measuring function into corresponding boolean expressions for each
condition separately. It is connected to Phase selection with load enchroachment,
quadrilateral characteristic (FDPSPDIS) function output STCDZ.
IEC99000557-TIFF V1 EN
Composition of the phase starting signals for a case, when the zone operates in a non-
directional mode, is presented in figure 88.
176
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
IEC00000488-TIFF V1 EN
Results of the directional measurement enter the logic circuits, when the zone
operates in directional (forward or reverse) mode, as shown in figure 89.
STNDL1N
AND
DIRL1N STZMPE
OR
STNDL2N
DIRL2N AND
STNDL3N OR STL1
DIRL3N AND AND
STNDL1L2
DIRL1L2 AND OR STL2
AND
STNDL2L3
DIRL2L3 AND
OR STL3
STNDL3L1 AND
DIRL3L1 AND
STZMPP
OR
BLK
15 ms
OR START
AND t
en05000778.vsd
IEC05000778 V2 EN
Tripping conditions for the distance protection zone one are symbolically presented
in figure 90.
177
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
en00000490-3.vsd
IEC00000490 2 V1 EN
Figure 90: Tripping logic for the distance protection zone one
IEC07000036-2-en.vsd
IEC07000036 V2 EN
ZMCAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND
IEC09000890-1-en.vsd
IEC09000890 V1 EN
178
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
ZDSRDIR
I3P* STFW
U3P* STRV
STDIRCND
IEC07000035-2-en.vsd
IEC07000035 V2 EN
Input and output signals is shown for zone 1, zone 2 - 5 are equal.
179
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
180
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
Settings for ZMCPDIS are valid for zone 1, while settings for
ZMCAPDIS are valid for zone 2 - 5
181
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
182
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
183
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
SYMBOL-DD V1 EN
184
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
6.3.1 Introduction
The operation of transmission networks today is in many cases close to the stability
limit. Due to environmental considerations, the rate of expansion and
reinforcement of the power system is reduced, for example, difficulties to get
permission to build new power lines. The ability to accurately and reliably classify
the different types of fault, so that single pole tripping and autoreclosing can be
used plays an important role in this matter. Phase selection, quadrilateral
characteristic with fixed angle FDPSPDIS is designed to accurately select the
proper fault loop in the distance function dependent on the fault type.
The heavy load transfer that is common in many transmission networks may make
fault resistance coverage difficult to achieve. Therefore, FDPSPDIS has a built-in
algorithm for load encroachment, which gives the possibility to enlarge the
resistive setting of both the phase selection and the measuring zones without
interfering with the load.
The extensive output signals from the phase selection gives also important
information about faulty phase(s), which can be used for fault analysis.
1. Residual current criteria, that is, separation of faults with and without earth
connection
2. Regular quadrilateral impedance characteristic
3. Load encroachment characteristics is always active but can be switched off by
selecting a high setting.
185
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
These directional indications are based on the sector boundaries of the directional
function and the impedance setting of FDPSPDIS function. Their operating
characteristics are illustrated in figure 94.
X X X
R
R R
en08000286.vsd
IEC08000286 V1 EN
The setting of the load encroachment function may influence the total operating
characteristic, (for more information, refer to section "Load encroachment").
The input DIRCND contains binary coded information about the directional
coming from the directional function . It shall be connected to the STDIR output on
ZDRDIR, directional measuring block. This information is also transferred to the
input DIRCND on the distance measuring zones, that is, the ZMQPDIS, distance
measuring block.
186
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048
The code built up for release of the measuring fault loops is as follows:
ULn
ZPHSn =
ILn
EQUATION1255 V1 EN (Equation 24)
where:
n corresponds to the particular phase (n=1, 2 or 3)
The resistance RN and reactance XN are the impedance in the earth-return path
defined according to equation 25 and equation 26.
R0 - R1
RN =
3
EQUATION1256 V1 EN (Equation 25)
187
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
X 0 - X1
XN =
3
EQUATION1257 V1 EN (Equation 26)
X (ohm/loop)
Kr·(X1+XN)
RFRvPE RFFwPE
X1+XN
60 deg
RFFwPE
RFRvPE R (Ohm/loop)
60 deg
X1+XN
1
Kr =
tan(60deg)
RFRvPE RFFwPE
Kr·(X1+XN)
en06000396.vsd
IEC06000396 V2 EN
Besides this, the 3I0 residual current must fulfil the conditions according to
equation 27 and equation 28.
3 × I0 ³ 0.5 × IMinOpPE
EQUATION2108 V1 EN (Equation 27)
3 × I0 ³ INReleasePE
------------------------------------ × Iphmax
100
EQUATION766 V1 EN (Equation 28)
where:
IMinOpPE is the minimum operation current for forward zones
INReleasePE is the setting for the minimum residual current needed to enable operation in the phase-
to-earth fault loops (in %).
Iphmax is the maximum phase current in any of three phases.
188
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
ULm - ULn
ZPHS =
-2 × ILn
EQUATION1258 V1 EN (Equation 29)
ULm is the leading phase voltage, ULn the lagging phase voltage and ILn the
phase current in the lagging phase n.
X (W / phase)
0.5·RFRvPP 0.5·RFFwPP
Kr·X1
X1
0.5·RFFwPP
60 deg
R (W / phase)
60 deg
0.5·RFRvPP
X1
1
Kr =
tan(60 deg)
Kr·X1
0.5·RFRvPP 0.5·RFFwPP
IEC09000047-2-en.vsd
IEC09000047 V2 EN
In the same way as the condition for phase-to-earth fault, there are current
conditions that have to be fulfilled in order to release the phase-to-phase loop.
Those are according to equation 30 or equation 31.
3I 0 < IMinOpPE
EQUATION2109 V1 EN (Equation 30)
189
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
INBlockPP
3I 0 < × Iph max
100
EQUATION2110 V1 EN (Equation 31)
where:
IMinOpPE is the minimum operation current for earth measuring loops,
INBlockPP is 3I0 limit for blocking phase-to-phase measuring loop and
Iphmax is maximal magnitude of the phase currents.
The operation conditions for three-phase faults are the same as for phase-to-phase
fault, that is equation 29, equation 30 and equation 31 are used to release the
operation of the function.
X (O/phase)
4 × X1
3
90 deg
0.5·RFFwPP·K3
X1·K3 4 × RFFwPP
6
R (O/phase)
0.5·RFRvPP·K3
K3 = 2 / v(3)
30 deg
IEC05000671-3-en.vsd
IEC05000671 V3 EN
190
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
Each of the six measuring loops has its own load encroachment characteristic based
on the corresponding loop impedance. The load encroachment functionality is
always active, but can be switched off by selecting a high setting.
RLdFw
ArgLd ArgLd
R
ArgLd ArgLd
RLdRv
IEC09000042-1-en.vsd
IEC09000042 V1 EN
When output signal STCNDI is selected, the operation characteristic will be as the
right illustration in figure 99. The reach will in this case be limit by the minimum
operation current and the distance measuring zones.
191
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
X X
R R
STCNDZ STCNDI
en05000197.vsd
IEC05000197 V1 EN
When FDPSPDIS is set to operate together with a distance measuring zone the
resultant operate characteristic could look like in figure 100. The figure shows a
distance measuring zone operating in forward direction. Thus, the operating area is
highlighted in black.
"Phase selection"
"quadrilateral" zone
Load encroachment
characteristic
Directional line
en05000673.vsd
IEC05000673 V1 EN
192
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
Figure 100 is valid for phase-to-earth. During a three-phase fault, or load, when the
quadrilateral phase-to-phase characteristic is subject to enlargement and rotation
the operate area is transformed according to figure 101. Notice in particular what
happens with the resistive blinders of the "phase selection" "quadrilateral" zone.
Due to the 30-degree rotation, the angle of the blinder in quadrant one is now 90
degrees instead of the original 60 degrees. The blinder that is nominally located to
quadrant four will at the same time tilt outwards and increase the resistive reach
around the R-axis. Consequently, it will be more or less necessary to use the load
encroachment characteristic in order to secure a margin to the load impedance.
X (W / phase)
Phase selection
”Quadrilateral” zone
R (W / phase)
IEC09000049-1-en.vsd
IEC09000049 V1 EN
Figure 101: Operating characteristic for FDPSPDIS in forward direction for three-
phase fault, ohm/phase domain
The result from rotation of the load characteristic at a fault between two phases is
presented in fig 102. Since the load characteristic is based on the same
measurement as the quadrilateral characteristic, it will rotate with the quadrilateral
characteristic clockwise by 30 degrees when subject to a pure phase-to-phase fault.
At the same time the characteristic will "shrink" by 2/√3, from the full RLdFw and
RLdRv reach, which is valid at load or three-phase fault.
193
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
IEC08000437.vsd
IEC08000437 V1 EN
Figure 102: Rotation of load characteristic for a fault between two phases
The operation of the Phase selection with load encroachment function (FDPSPDIS)
is blocked if the magnitude of input currents falls below certain threshold values.
Figure 103 presents schematically the creation of the phase-to-phase and phase-to-
earth operating conditions. Consider only the corresponding part of measuring and
194
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
15 ms
3I 0 < IMinOpPE 10 ms 20 ms & t STPP
& t t
OR IRELPP
INBlockPP
3I 0 < × Iph max
100
IEC08000439_1_en.vsd
IEC08000439 1 EN V1 EN
195
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
INDL1N
INDL2N
INDL3N
15 ms
STNDPE
OR t
IRELPE
AND 15 ms
ZML1N STNDL1
OR t
AND
ZML2N
15 ms
STNDL2
OR t
AND
ZML3N
15 ms
ZML1L2 STNDL3
AND OR t
ZML2L3
AND INDL1L2
INDL2L3
ZML3L1
AND
INDL3L1
IRELPP
15 ms
STNDPP
OR t
IEC00000545_2_en.vsd
IEC00000545-TIFF V2 EN
196
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
INDL1N
AND
DRVL1N
INDL1L2 15 ms STRVL1
AND OR t
DRVL1L2
INDL3L1
AND
DRVL3L1 15 ms STRVPE
INDL2N OR t
AND
DRVL2N
INDL1L2 15 ms
STRVL2
AND OR t
INDL2L3 INDL1N
AND INDL2N
DRVL2L3
INDL3N Bool to STCNDZ
INDL3N INDL1L2 integer
AND INDL2L3
DRVL3N INDL3L1
INDL2L3 15 ms
STRVL3
AND OR t
INDL3L1
15 ms
AND STRVPP
OR t
IEC00000546_2_en.vsd
IEC00000546-TIFF V2 EN
197
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
AND
INDL1N
AND 15 ms 15 ms
DFWL1N STFW1PH
AND OR t t
INDL1L2
15 ms STFWL1
AND OR t
DFWL1L2
INDL3L1
AND
AND
DFWL3L1 15 ms
STFWPE
INDL2N OR t
AND
DFWL2N
AND 15 ms
INDL1L2 STFWL2
t
AND OR
15 ms 15 ms
INDL2L3 STFW2PH
AND OR t t
AND
DFWL2L3
INDL3N
AND AND
DFWL3N 15 ms
STFWL3
t
INDL2L3
AND OR
15 ms
INDL3L1 STFW3PH
AND t
AND
15 ms
STFWPP
OR t
IEC05000201_2_en.vsd
IEC05000201 V2 EN
Figure 107 presents the composition of output signals TRIP and START, where
internal signals STNDPP, STFWPP and STRVPP are the equivalent to internal
signals STNDPE, STFWPE and STRVPE, but for the phase-to-phase loops.
198
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
TimerPP=Off
tPP
AND AND
t
TRIP
OR OR
tPE
TimerPE=Off
t
AND AND
STNDPP
STFWPP OR
STRVPP
START
OR
STNDPE
STFWPE OR
STRVPE
IEC08000441_2_en.vsd
IEC08000441 1 V2 EN
IEC06000258-2-en.vsd
IEC06000258 V2 EN
199
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
200
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
201
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
S00346 V1 EN
6.4.1 Introduction
The numerical mho line distance protection is a, up to four zone full scheme
protection for back-up detection of short circuit and earth faults. The full scheme
technique provides back-up protection of power lines with high sensitivity and low
requirement on remote end communication. The four zones have fully independent
measuring and settings, which gives high flexibility for all types of lines.
The IED can be used up to the highest voltage levels. It is suitable for the
protection of heavily loaded lines and multi-terminal lines where the requirement
for tripping is one-, two- and/or three-pole.
202
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
The independent measurement of impedance for each fault loop together with a
sensitive and reliable built in phase selection makes the function suitable in
applications with single phase autoreclosing.
Operation area
en07000117.vsd
IEC07000117 V1 EN
The distance protection zones can operate, independent of each other, in directional
(forward or reverse) or non-directional mode (offset). This makes them suitable,
together with different communication schemes, for the protection of power lines
and cables in complex network configurations, such as parallel lines, multi-
terminal lines and so on.
The integrated control and monitoring functions offer effective solutions for
operating and monitoring all types of transmission and sub-transmission lines.
The execution of the different fault loops within the IED are of full scheme type,
which means that each fault loop for phase-to-earth faults and phase-to-phase faults
are executed in parallel.
The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a start element to select correct voltages and current
203
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
depending on fault type. So each distance protection zone performs like one
independent distance protection function with six measuring elements.
The distance function consists of five instances. Each instance can be selected to be
either forward or reverse with positive sequence polarized mho characteristic
alternatively self polarized offset mho characteristics with reverse offset. The
operating characteristic is in accordance to figure 110 where zone 5 is selected
offset mho.
jx
Mho, zone4
Mho, zone3
Zs=0
Mho, zone2
R
Mho, zone1
Zs=Z1
R Zs=2Z1
IEC09000143-1-en.vsd
IEC09000143 V1 EN
Figure 110: Mho, offset mho characteristic and the source impedance influence on the mho characteristic
The mho characteristic has a dynamic expansion due to the source impedance.
Instead of crossing the origin as for the mho to the left of figure 110, which is only
valid where the source impedance is zero, the crossing point is moved to the
coordinates of the negative source impedance given an expansion of the circle
shown to the right of figure 110.
The polarization quantities used for the mho circle are 100% memorized positive
sequence voltages. This will give a somewhat less dynamic expansion of the mho
circle during faults. However, if the source impedance is high, the dynamic
expansion of the mho circle might lower the security of the function too much with
high loading and mild power swing conditions.
The mho distance element has a load encroachment function which cuts off a
section of the characteristic when enabled. The function is enabled by setting the
setting parameter LoadEnchMode to On. Enabling of the load encroachment
204
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
function increases the possibility to detect high resistive faults without interfering
with the load impedance. The algorithm for the load encroachment is located in the
Faulty phase identification with load encroachment for mho function FMPSPDIS,
where also the relevant settings can be found. Information about the load
encroachment from FMPSPDIS to the zone measurement is given in binary format
to the input signal LDCND.
Each impedance zone can be switched On and Off by the setting parameter
Operation.
Each zone can also be set to Non-directional, Forward or Reverse by setting the
parameter DirMode.
For critical applications such as for lines with high SIRs as well as CVTs, it is
possible to improve the security by setting the parameter ReachMode to
Underreach. In this mode the reach for faults close to the zone reach is reduced by
20% and the filtering is also introduced to increase the accuracy in the measuring.
If the ReachMode is set to Overreach no reduction of the reach is introduced and
no extra filtering introduced. The latter setting is recommended for overreaching
pilot zone, zone 2 or zone 3 elements and reverse zone where overreaching on
transients is not a major issue either because of less likelihood of overreach with
higher settings or the fact that these elements do not initiate tripping unconditionally.
The zone reach for phase-to-earth fault and phase-to-phase fault is set individually
in polar coordinates.
The impedance is set by the parameters ZPE and ZPP and the corresponding
arguments by the parameters ZAngPE and ZAngPP.
Compensation for earth-return path for faults involving earth is done by setting the
parameter KNMag and KNAng where KNMag is the magnitude of the earth-return
path and KNAng is the difference of angles between KNMag and ZPE.
Z0-Z1
KNMag =
3 × Z1
EQUATION1579 V1 EN (Equation 32)
205
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
KNAng = arg
( Z 0 - Z1
3 × Z1
)
EQUATION1580 V1 EN (Equation 33)
where
Z0 is the complex zero sequence impedance of the line in Ω/phase
Z1 is the complex positive sequence impedance of the line in Ω/phase
The activation of input signal BLKZ can be made by external fuse failure function
or from the loss of voltage check in the Mho supervision logic (ZSMGAPC). In
both cases the output BLKZ in the Mho supervision logic shall be connected to the
input BLKZ in the Mho distance function block (ZMHPDIS)
The input signal BLKZMTD is activated during some ms after fault has been
detected by ZSMGAPC to avoid unwanted operations due to transients. It shall be
connected to the BLKZMTD output signal of ZSMGAPC function.
At SIR values >10, the use of electronic CVT might cause overreach due to the built-
in resonance circuit in the CVT, which reduce the secondary voltage for a while.
The input BLKHSIR shall be connected to the output signal HSIR on ZSMGAPC
for increasing of the filtering and high SIR values. This is valid only when
permissive underreach scheme is selected by setting ReachMode=Underreach.
206
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
Phase-to-phase fault
Mho
The plain mho circle has the characteristic as in figure 111. The condition for
deriving the angle β is according to equation 34.
where
207
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
IL1L2·X
Ucomp = UL1L2 - IL1L2 • ZPP
IL1L2 • ZPP
ß
Upol
UL1L2
IL1L2·R
en07000109.vsd
IEC07000109 V1 EN
Figure 111: Simplified mho characteristic and vector diagram for phase L1-to-
L2 fault
Offset Mho
The characteristic for offset mho is a circle where two points on the circle are the
setting parameters ZPP and ZRevPP. The vector ZPP in the impedance plane has
the settable angle AngZPP and the angle for ZRevPP is AngZPP+180°.
The condition for operation at phase-to-phase fault is that the angle β between the
two compensated voltages Ucomp1 and Ucomp2 is greater than or equal to 90°
(figure 112). The angle will be 90° for fault location on the boundary of the circle.
The angle β for L1-to-L2 fault can be defined according to equation 35.
æ U -IL1L2 × ZPP ö
b = arg ç ÷
è U-(-IL1L2 × ZRevPP) ø
EQUATION1792 V1 EN (Equation 35)
where
ZRevPP is the positive sequence impedance setting for phase-to-phase fault in reverse direction
208
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
IL1L2jX
U
Ucomp2 = U = IF•ZF=UL1L2
IL1L2R
- IL1L2 • Z RevPP
en07000110.vsd
IEC07000110 V1 EN
Figure 112: Simplified offset mho characteristic and voltage vectors for phase
L1-to-L2 fault.
where
ArgDir is the setting parameter for directional line in fourth quadrant in the directional element,
ZDMRDIR.
ArgNegRes is the setting parameter for directional line in second quadrant in the directional element,
ZDMRDIR.
β is calculated according to equation 35
The directional information is brought to the mho distance measurement from the
mho directional element as binary coded information to the input DIRCND. See
Directional impedance element for mho characteristic (ZDMRDIR) for information
about the mho directional element.
209
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
IL1L2jX
ZPP
UL1L2
ArgNegRes f
IL1L2
ArgDir
en07000111.vsd
IEC07000111 V1 EN
Figure 113: Simplified offset mho characteristic in forward direction for phase
L1-to-L2 fault
The β is derived according to equation 35 for the mho circle and φ is the angle
between the voltage and current.
210
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
ZPP
ArgNegRes
ϕ
IL1L2
ArgDir R
UL1L2
ZRevPP
en06000469.eps
IEC06000469 V1 EN
Phase-to-earth fault
Mho
The measuring of earth faults uses earth-return compensation applied in a
conventional way. The compensation voltage is derived by considering the
influence from the earth-return path.
For an earth fault in phase L1, the compensation voltage Ucomp can be derived, as
shown in figure 115.
where
Upol is the polarizing voltage (memorized UL1 for Phase L1-to- earth fault)
Z1+ZN = Z 1 × 1 + KN ( )
EQUATION1799 V1 EN (Equation 37)
Table continues on next page
211
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
where
Z1 is the positive sequence impedance of the line (Ohm/phase)
The angle β between the Ucomp and the polarize voltage Upol for a L1-to-earth
fault is
where
UL1 is the phase voltage in faulty phase L1
KN Z0-Z1
EQUATION1593 V1 EN
3 × Z1
EQUATION1594 V1 EN
the setting parameter for the zero sequence compensation consisting of the
magnitude KN and the angle KNAng.
Upol is the 100% of positive sequence memorized voltage UL1
IL1·X
IL1·ZN
Ucomp
IL1 • Zloop
IL1·ZPE
Upol
f
IL1 (Ref) IL1·R
en06000472_2.vsd
IEC06000472 V2 EN
Figure 115: Simplified offset mho characteristic and vector diagram for phase
L1-to-earth fault
212
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
Offset mho
The characteristic for offset mho at earth fault is a circle containing the two vectors
from the origin ZPE and ZRevPE where ZPE and ZrevPE are the setting reach for
the positive sequence impedance in forward respective reverse direction. The
vector ZPE in the impedance plane has the settable angle AngZPE and the angle for
ZRevPP is AngZPE+180°.
The condition for operation at phase-to-earth fault is that the angle β between the
two compensated voltages Ucomp1 and Ucomp2 is greater or equal to 90° see
figure 116. The angle will be 90° for fault location on the boundary of the circle.
where
is the phase L1 voltage
U L1
EQUATION1
805 V1 EN
IL1L 2 • jX
UL1
U comp2 = UL1 - (-IL1 • ZRevPE)
IL1L2 • R
- I L1 • Z Re vPe
en 06000465.vsd
IEC06000465 V1 EN
Figure 116: Simplified offset mho characteristic and voltage vector for phase L1-
to-L2 fault
213
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
where
ArgDir is the setting parameter for directional line in fourth quadrant in the directional element,
ZDMRDIR.
ArgNegRes is the setting parameter for directional line in second quadrant in the directional element,
ZDMRDIR.
β is calculated according to equation 41
IL1 jX
UL1
ArgNegRes f
IL1 IL1·R
ArgDir
en 06000466.vsd
IEC06000466 V1 EN
Figure 117: Simplified characteristic for offset mho in forward direction for L1-to-
earth fault
214
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
The conditions for operation of offset mho in reverse direction for L1-to-earth fault
is 90≤β≤270 and 180°-Argdir≤φ≤ArgNegRes+180°.
The β is derived according to equation 41 for the offset mho circle and φ is the
angle between the voltage and current.
ZPE
ArgNegRes
ϕ
IL1
ArgDir R
UL1
ZRevPE
en06000470.eps
IEC06000470 V1 EN
Figure 118: Simplified characteristic for offset mho in reverse direction for L1-to-
earth fault
215
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
IEC06000423_2_en.vsd
IEC06000423 V2 EN
216
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
217
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
218
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
S00346 V1 EN
S00346 V1 EN
6.5.1 Introduction
The line distance protection is a zone protection with three fault loops for phase-to-
earth fault for each of the independent zones. Individual settings for each zone
resistive and reactive reach give flexibility for use on overhead lines and cables of
different types and lengths.
219
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
Forward
operation
Reverse
operation
en05000034.vsd
IEC05000034 V1 EN
Figure 120: Typical quadrilateral distance protection zone with Phase selection,
quadrilateral characteristic with settable angle function FRPSPDIS
activated
The independent measurement of impedance for each fault loop together with a
sensitive and reliable built in phase selection makes the function suitable in
applications with single phase auto-reclosing.
The distance protection zones can operate, independent of each other, in directional
(forward or reverse) or non-directional mode. This makes them suitable, together
with different communication schemes, for the protection of power lines and cables
in complex network configurations, such as parallel lines, multi-terminal lines.
The different fault loops within the IED are operating in parallel in the same
principle as a full scheme measurement.
Figure 121 presents an outline of the different measuring loops for the basic five,
impedance-measuring zones l.
220
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
en07000080.vsd
IEC07000080 V1 EN
Figure 121: The different measuring loops at line-earth fault and phase-phase
fault.
The distance measuring zone include three impedance measuring loops; one fault
loop for each phase.
The distance measuring zone will essentially operate according to the non-
directional impedance characteristics presented in figure 122. The characteristic is
illustrated with the full loop reach.
221
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
X (Ohm/loop)
R1PE+Rn
RFPE RFPE
X0PE-X1PE
Xn =
3
X1PE+Xn R0PE-R1PE
Rn =
3
jN jN
R (Ohm/loop)
RFPE RFPE
X1PE+Xn
RFPE RFPE
en08000280-2-en.vsd
R1PE+Rn
IEC08000280 V1 EN
ILn R1 + j X1
Phase-to-earth
UL1
element
Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)
0
IN (R0-R1)/3 +
j (X0-X1)/3 ) en06000412.vsd
IEC06000412 V1 EN
222
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
The R1 and jX1 in figure 123 represents the positive sequence impedance from the
measuring point to the fault location. The RFPE is presented in order to “convey”
the fault resistance reach.
X X X
R R R
en05000182.vsd
IEC05000182 V1 EN
The operation of the distance measuring zone is blocked if the magnitude of input
currents fall below certain threshold values.
For zone 1 with load compensation feature the additional criterion applies, that all
phase-to-earth loops will be blocked when IN < IMinOpIN, regardless of the phase
currents.
ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector
sum of the three phase currents, that is, residual current 3I0.
223
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits.
Here U and I represent the corresponding voltage and current phasors in the
respective phase Ln (n = 1, 2, 3).
U L1
Z app = ------------------------------
I L1 + I N × KN
EQUATION1223 V1 EN (Equation 42)
Where:
UL1, IL1 and IN are the phase voltage, phase current and residual current present to the IED
KN is defined as:
Z0 - Z1
KN =
3 × Z1
EQUATION 2105 V1 EN
Z 0 = R0 + jX 0
EQUATION2106 V1 EN
Z1 = R1 + jX 1
EQUATION2107 V1 EN
Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach
Here IN is a phasor of the residual current in IED point. This results in the same
reach along the line for all types of faults.
The formula given in equation 42 is only valid for no loaded radial feeder
applications. When load is considered in the case of single line-to-earth fault,
224
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
Measuring elements receive current and voltage information from the A/D
converter. The check sums are calculated and compared, and the information is
distributed into memory locations. For each of the six supervised fault loops,
sampled values of voltage (U), current (I), and changes in current between samples
(DI) are brought from the input memory and fed to a recursive Fourier filter.
The filter provides two orthogonal values for each input. These values are related
to the loop impedance according to equation 43,
X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN (Equation 43)
X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt
X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt
with
w0 = 2 × p × f 0
EQUATION356 V1 EN (Equation 46)
where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency
The algorithm calculates Rm measured resistance from the equation for the real
value of the voltage and substitute it in the equation for the imaginary part. The
equation for the Xm measured reactance can then be solved. The final result is
equal to:
Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN (Equation 47)
225
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN (Equation 48)
The calculated Rm and Xm values are updated each sample and compared with the
set zone reach. The adaptive tripping counter counts the number of permissive
tripping results. This effectively removes any influence of errors introduced by the
capacitive voltage transformers or by other factors.
where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default
set to 15 (= -15 degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default
set to 115 degrees, see figure 125.
U1L1 is positive sequence phase voltage in phase L1
The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115
degrees respectively (see figure 125) and it should not be changed unless system
studies have shown the necessity.
226
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
ArgNegRes
ArgDir
R
en05000722.vsd
IEC05000722 V1 EN
Figure 125: Setting angles for discrimination of forward and reverse fault
For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is
restored.
• If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set IED rated current IBase), the condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.
• If the current decreases below the minimum operating value, the memory
resets until the positive sequence voltage exceeds 10% of its rated value.
227
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
The STCND input signal represents a connection of six different integer values
from the phase selection function within the IED, which are converted within the
zone measuring function into corresponding boolean expressions for each
condition separately. It is connected to the Phase selection with load
enchroachment, quadrilateral characteristic (FDPSPDIS) function output STCNDZ.
The input signal DIRCND is used to give condition for directionality for the
distance measuring zones. The signal contains binary coded information for both
forward and reverse direction. The zone measurement function filter out the
relevant signals on the DIRCND input depending on the setting of the parameter
OperationDir. It shall be configured to the DIRCND output on the Directional
impedance element for mho characteristic (ZDMRDIR) function.
228
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
STCND
AND STNDL1N
L1N
AND STNDL2N
L2N
STNDL3N
L3N AND
OR STNDPE
OR
VTSZ STND
OR AND
BLOCK
BLK
en06000408.vsd
IEC06000408 V1 EN
Composition of the phase starting signals for a case, when the zone operates in a non-
directional mode, is presented in figure 127.
STNDL1N 15 ms
AND t STL1
STNDL2N 15 ms
AND t STL2
STNDL3N 15 ms
AND t STL3
15 ms
AND t START
OR
BLK
en06000409.vsd
IEC06000409 V1 EN
Results of the directional measurement enter the logic circuits, when the zone
operates in directional (forward or reverse) mode, see figure 128.
229
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
STNDL1N
DIRL1N AND
OR STZMPE.
&
STNDL2N
DIRL2N AND
STNDL3N 15 ms
STL1
& t
DIRL3N AND
15 ms
STL2
& t
15 ms
STL3
& t
BLK
15 ms
OR START
& t
en07000081.vsd
IEC07000081 V1 EN
Tripping conditions for the distance protection zone one are symbolically presented
in figure 129.
en07000082.vsd
IEC07000082 V1 EN
Figure 129: Tripping logic for the distance protection zone one
230
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
IEC06000454-2-en.vsd
IEC06000454 V2 EN
ZMMAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
BLKZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND
IEC09000947-1-en.vsd
IEC09000947 V1 EN
231
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
232
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
233
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
S00346 V1 EN
S00346 V1 EN
234
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
6.6.1 Introduction
The phase-to-earth impedance elements can be optionally supervised by a phase
unselective directional function based on symmetrical components.
Where:
ArgDir Setting for the lower boundary of the forward directional characteristic, by default set to
15 (= -15 degrees)
ArgNegRes Setting for the upper boundary of the forward directional characteristic, by default set to
115 degrees, see figure 132 for mho characteristics.
U1L1 Positive sequence phase voltage in phase L1
U1L1L2M Memorized voltage difference between phase L1 and L2 (L2 lagging L1)
The default settings for ArgDir and ArgNegRes are 15 (= -15) and 115 degrees
respectively (see figure 132) and they should not be changed unless system studies
show the necessity.
235
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
X
Zset reach point
ArgNegRes
-ArgDir R
-Zs
en06000416.vsd
IEC06000416 V1 EN
For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100ms or until the positive sequence voltage is
restored. After 100ms, the following occurs:
236
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
• If the current is still above the set value of the minimum operating current the
condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.
• If the current decreases below the minimum operating value, no directional
indications will be given until the positive sequence voltage exceeds 10% of
its rated value.
The STDIRCND output provides an integer signal that depends on the evaluation
and is derived from a binary coded signal as follows:
Values for the following parameters are calculated, and may be viewed as service
values:
• resistance phase L1
• reactance phase L1
• resistance phase L2
• reactance phase L2
• resistance phase L3
• reactance phase L3
• direction phase L1
• direction phase L2
• direction phase L3
237
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
A Mho element needs a polarizing voltage for its operation. The positive-sequence
memory-polarized elements are generally preferred. The benefits include:
There are however some situations that can cause security problems like reverse
phase to phase faults and double phase-to-earth faults during high load periods. To
solve these, additional directional element is used.
For phase-to-earth faults, directional elements using sequence components are very
reliable for directional discrimination. The directional element can be based on one
of following types of polarization:
• Zero-sequence voltage
• Negative-sequence voltage
• Zero-sequence current
Zero-sequence voltage polarization is utilizing the phase relation between the zero-
sequence voltage and the zero-sequence current at the location of the protection.
The measurement principle is illustrated in figure 133.
238
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
- 3U 0
AngleOp
AngleRCA
3I 0
en06000417.vsd
IEC06000417 V1 EN
Zero-sequence current polarization is utilizing the phase relation between the zero-
sequence current at the location of the protection and some reference zero-
sequence current, for example, the current in the neutral of a power transformer.
Z0 SA I0 I0
Z0 Line Z0 SB
Charac te ris tic
ang le
U0 U0
K*I0
U0 + K*I0
IF
en06000418.vsd
IEC06000418 V1 EN
Note that the sequence based additional directional element cannot give per phase
information about direction to fault. This is why it is an AND-function with the
normal directional element that works on a per phase base. The release signals are
per phase and to have a release of a measuring element in a specific phase both the
additional directional element, and the normal directional element, for that phase
must indicate correct direction.
239
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
Normal
directional Release of distance
element measuring element
L1N, L2N, L3N L1N, L2N, L3N
AND
Additional
directional AND per
element phase
en06000419.vsd
IEC06000419 V1 EN
IEC06000422_2_en.vsd
IEC06000422 V2 EN
ZDARDIR
I3P* STFWPE
U3P* STRVPE
I3PPOL* DIREFCND
DIRCND
IEC06000425-2-en.vsd
IEC06000425 V2 EN
240
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
241
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
6.7.1 Introduction
The Mho impedance supervision logic (ZSMGAPC) includes features for fault
inception detection and high SIR detection. It also includes the functionality for
loss of potential logic as well as for the pilot channel blocking scheme.
242
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
The aim for the fault inception detector is to detect quickly that a fault has occurred
on the system.
The fault inception detection detects instantaneous changes in any phase currents
or zero sequence current in combination with a change in the corresponding phase
voltage or zero sequence voltage. If the change of any phase current and
corresponding phase voltage or 3U0 and 3I0 exceeds the settings DeltaI and
DeltaU respectively. Delta3U0 and Delta3I0 and the input signal BLOCK is not
activated, the output signal FLTDET is activated indicating that a system fault has
occurred.
If the setting PilotMode is set to On in blocking scheme and the fault inception
function has detected a system fault, a block signal BLKCHST will be issued and
send to remote end in order to block the overreaching zones. Different criteria has
to be fulfilled for sending the BLKCHST signal:
Or
If it is later detected that it was an internal fault that made the function issue the
BLKCHST signal, the function will issue a CHSTOP signal to unblock the remote
end. The criteria that have to be fulfilled for this are:
1. The function has to be in pilot mode, that is, the setting PilotMode has to be
set to On
2. The carrier send signal should be blocked, that is, input signal BLOCKCS is
On and,
3. A reverse fault should not have been detected while the carrier send signal was
not blocked, that is, input signals REVSTART and BLOCKCS is not activated.
ZSMGAPC function has a built in loss of voltage detection based on the evaluation
of the change in phase voltage or the change in zero sequence voltage (3U0). It
operates if the change in phase voltages exceeds the setting DeltaU or 3U0 exceeds
the setting Delta3U0.
If loss of voltage is detected, but not a fault inception, the distance protection
function will be blocked. This is also the case if a fuse failure is detected by the
243
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
external fuse failure function and activate the input FUSEFAIL. Those blocks are
generated by activating the output BLKZ, which shall be connected to the input
BLKZ on the distance Mho function block.
During fault inception a lot of transients will be developed which in turn might
cause the distance function to overreach. The Mho supervision logic (ZSMGAPC)
will increase the filtering during the most transient period of the fault. This is done
by activating the output BLKZMD, which shall be connected to the input
BLKZMTD on mho distance function block.
The SIR function calculates the SIR value as the source impedance divided by the
setting Zreach and activates the output signal HSIR if the calculated value for any
of the six basic shunt faults exceed the setting SIRLevel. The HSIR signal is
intended to block the delta based mho impedance function.
IEC06000426-2-en.vsd
IEC06000426 V2 EN
244
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
S00346 V1 EN
245
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
6.8.1 Introduction
The operation of transmission networks today is in many cases close to the stability
limit. Due to environmental considerations the rate of expansion and reinforcement
of the power system is reduced, for example difficulties to get permission to build
new power lines. The ability to accurate and reliable classifying the different types
of fault so that single phase tripping and autoreclosing can be used plays an
important roll in this matter.
The phase selection function is design to accurate select the proper fault loop in the
distance function dependent on the fault type.
The heavy load transfer that is common in many transmission networks may in
some cases interfere with the distance protection zone reach and cause unwanted
operation. Therefore the function has a built in algorithm for load encroachment,
which gives the possibility to enlarge the resistive setting of the measuring zones
without interfering with the load.
The output signals from the phase selection function produce important
information about faulty phase(s), which can be used for fault analysis as well.
Faulty phase identification with load encroachment for mho (FMPSPDIS) function
can be decomposed into six different parts:
The aim of the delta based phase selector is to provide very fast and reliable phase
selection for releasing of tripping from the high speed Mho measuring element and
is essential to Directional Comparison Blocking scheme (DCB), which uses Power
Line Carrier (PLC) communication system across the protected line.
The current and voltage samples for each phase passes through a notch filter that
filters out the fundamental components. Under steady state load conditions or when
no fault is present, the output of the filter is zero or close to zero. When a fault
246
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
occurs, currents and voltages change resulting in sudden changes in the currents
and voltages resulting in non-fundamental waveforms being introduced on the line.
At this point the notch filter produces significant non-zero output. The filter output
is processed by the delta function. The algorithm uses an adaptive relationship
between phases to determine if a fault has occurred, and determines the faulty phases.
The current and voltage delta based phase selector gives a real output signal if the
following criterion is fulfilled (only phase L1 shown):
Max(ΔUL1,ΔUL2,ΔUL3)>DeltaUMinOp
Max(ΔIL1,ΔIL2,ΔIL3)>DeltaIMinOp
where:
ΔUL1, ΔUL2 and ΔUL3 are the voltage change between sample t and sample t-1
DeltaUMinOp and DeltaIMinOp are the minimum harmonic level settings for the voltage and current
filters to decide that a fault has occurred. A slow evolving fault may not
produce sufficient harmonics to detect the fault; however, in such a
case speed is no longer the issue and the sequence components
phase selector will operate.
The delta voltages ΔULn and delta current ΔILn (n prefix for phase order) are the
voltage and current between sample t and sample t-1.
The delta phase selector employs adaptive techniques to determine the fault type.
The logic determines the fault type by summing up all phase values and dividing
by the largest value. Both voltages and currents are filtered out and evaluated. The
condition for fault type classification for the voltages and currents can be expressed
as:
247
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
The output signal is 1 for single phase-to-earth fault, 2 for phase-to-phase fault and
3 for three-phase fault. At this point the filter does not know if earth was involved
or not.
Typically there are induced harmonics in the non-faulted lines that will affect the
result. This method allows for a significant tolerance in the evaluation of FaultType
over its entire range.
When a single phase-to-earth fault has been detected, the logic determines the
largest quantity, and asserts that phase. If phase-to-phase fault is detected, the two
largest phase quantities will be detected and asserted as outputs.
The faults detected by the delta based phase selector are coordinated in a separate
block. Different phases of faults may be detected at slightly different times due to
differences in the angles of incidence of fault on the wave shape. Therefore the
output is forced to wait a certain time by means of a timer. If the timer expires, and
a fault is detected in one phase only, the fault is deemed as phase-to-earth. This
way a premature single phase-to-earth fault detection is not released for a phase-to-
phase fault. If, however, earth current is detected before the timer expires, the phase-
to-earth fault is released sooner.
If another phase picks up during the time delay, the wait time is reduced by a
certain amount. Each detection of either earth-to-phase or additional phases further
reduce the initial time delay and allow the delta phase selector output to be faster.
There is no time delay, if for example, all three phases are faulty.
The delta function is released if the input DELTAREL is activated at the same time
as input DELTABLK is not activated. Activating the DELTABLK input will block
the delta function. The release signal has an internal pulse timer of 100 ms. When
the DELTAREL signal has disappeared the delta logic is reset. In order not to get
too abrupt change, the reset is decayed in pre-defined steps.
248
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
The output from this detection is used to release the earth-fault loop.
|3I0|>maxIph: INRelPE
where:
|3I0| is the magnitude of the zero sequence current 3I0
The earth-fault loop is also released if the evaluation of the zero sequence current
by the main sequence function meets the following conditions:
|3I0|>IBase · 0.5
|3I0|>maxIph ·INRelPE
where:
maxIph is the maximal current magnitude found in any of the three phases
INRelPE is the setting of 3I0 limit for release of phase-to-earth measuring loop in % of IBase
IBase is the global setting of the base current (A)
In systems where the source impedance for zero sequence is high the change of
zero sequence current may not be significant and the above detection may fail. In
those cases the detection enters the second level, with evaluation of zero and
negative sequence voltage. The release of the earth-fault loops can then be
achieved if all of the following conditions are fulfilled:
|3U0|>|U2| · 0.5
|3U0|>|U1| · 0.2
and
249
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
or
3I0<maxIph · INRelPE
where:
3U0 is the magnitude of the zero sequence voltage
U2 is the magnitude of the negative sequence voltage at the relay measuring point of
phase L1
k5 is design parameter
ILmax is the maximal phase current
IMinOp is the setting of minimum operate phase current in % of IBase
60°
UL3
L3-L1 sector
UL2 0°
180° L2-L3 sector U1L1 (Ref)
L1-L2 sector
UL1
300°
en06000383.vsd
IEC06000383 V1 EN
The phase-to-phase loop for the faulty phases will be determined if the angle
between the sequence voltages U2 and U1 lies within the sector defined according
to figure 139 and the following conditions are fulfilled:
|U1|>U1MinOP
|U2|>U2MinOp
where:
U1MinOP and U2MinOp are the setting parameters for positive sequence and negative sequence
minimum operate voltages
250
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
If there is a three-phase fault, there will not be any release of the individual phase
signals, even if the general conditions for U2 and U1 are fulfilled.
80°
200°
L1-E sector
320°
IEC06000384-2-en.vsd
IEC06000384 V2 EN
The angle is calculated in a directional function block and gives the angle in
radians as input to the U2 and I0 function block. The input angle is released only if
the fault is in forward direction. This is done by the directional element. The fault
is classified as forward direction if the angle between U0 and I0 lies between 20 to
200 degrees, see figure 141.
251
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
Forward 20°
200° Reverse
en06000385.vsd
IEC06000385 V1 EN
Figure 141: Directional element used to release the measured angle between
Uo and I0
The input radians are summarized with an offset angle and the result evaluated. If
the angle is within the boundaries for a specific sector, the phase indication for that
sector will be active see figure 140. Only one sector signal is allowed to be
activated at the same time.
The sector function for condition 1 has an internal release signal which is active if
the main sequence function has classified the angle between U0 and I0 as valid. The
following conditions must be fulfilled for activating the release signals:
|U2|>U2MinOp
|3I0|>maxIph · INRelPE
where:
U2 and IN are the magnitude of the negative sequence voltage and zero-
sequence current (3I0)
The angle difference is phase shifted by 180 degrees if the fault is in reverse direction.
The condition 2 looks at the angle relationship between the negative sequence
voltage U2 and the positive sequence voltage U1. Since this is a phase-to-phase
voltage relationship, there is no need for shifting phases if the fault is in reverse
direction. A phase shift is introduced so that the fault sectors will have the same
angle boarders as for condition 1. If the calculated angle between U2 and U1 lies
252
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
within one sector, the corresponding phase for that sector will be activated. The
condition 2 is released if both the following conditions are fulfilled:
|U2|>U2MinOp
|U1|>U1MinOP
where:
|U1| and |U2| are the magnitude of the positive and negative sequence voltages.
U1MinOP and U2MinOp are the setting parameters for positive sequence and negative sequence
minimum operating voltages.
140°
L3-E sector
20°
U1L1
(Ref)
L1-E sector
L2-E sector
260° IEC06000413_2_en.vsd
IEC06000413 V2 EN
If both conditions are true and there is sector match, the fault is deemed as single
phase-to-earth. If the sectors, however, do not match the fault is determined to be
the complement of the second condition, that is, a phase-to-phase-to- earth fault.
The sequence phase selector is blocked when earth is not involved or if a three-
phase fault is detected.
|U1|<U1Level
253
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
and
|I1|>I1LowLevel
or
|I1|>IMaxLoad
where:
|U1| and |I1| are the positive sequence voltage and current magnitude
U1Level , are the setting of limits for positive sequence voltage and current
I1LowLevel
IMaxLoad is the setting of the maximum load current
The output signal for detection of three-phase fault is only released if not earth
fault and phase-to-phase fault in the main sequence function is detected.
The conditions for not detecting earth fault are the inverse of equation 5 to 10.
1:
earth fault is detected
or
|3I0IN|> 0.05 · IBase
and
|3I0IN|>maxIph ·INRelPE
2:
phase-to-earth and phase-to-phase faults are not fulfilled
and
maxIph<0.1 · IBase
and
|I2|<0.1 · maxIph
3:
|3I0IN|>maxIph · INBlockPP
or
|I2|<maxIph · I2maxIL
where:
maxIph is the maximum of the phase currents IL1, IL2 and IL3
INRelPE is the setting parameter for 3I0 limit for release of phase-to-earth fault loops
Table continues on next page
254
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
I2ILmax is the setting parameter for the relation between negative sequence current
to the maximum phase current in percent of IBase
INBlockPP is the setting parameter for 3I0 limit for blocking phase to phase measuring
loops
a a>b FaultPriority
DeltaIL1 then c=a c Adaptive release
b else c=a dependent on result
from Delta logic
DeltaUL1
Sequence based
function a<b
a
L1L2 fault
then c=b c
OR b else c=a OR
L1N fault
3 Phase fault
STL1
IL1Valid &
BLOCK
en06000386.vsd
IEC06000386 V1 EN
255
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
Blinder
Blinder provides a mean to discriminate high load from a fault. The operating
characteristic is illustrated in figure 144. There are six individual measuring loops
with the blinder functionality. Three phase-to-earth loops which estimate the
impedance according to
Zn = Uph / Iph
The start operations from respective loop are binary coded into one word and
provides an output signal STCNDPLE.
X jX
RLd
ArgLd ArgLd
R
ArgLd R
ArgLd
RLd
Operation area
en06000414.vsd
IEC06000414 V1 EN
Outputs
The output of the sequence components based phase selector and the delta logic
phase selector activates the output signals STL1, STL2 and STL3. If an earth fault
is detected the signal STPE gets activated.
The phase selector also gives binary coded signals that are connected to the zone
measuring element for opening the correct measuring loop(s). This is done by the
signal STCNDPHS. If only one phase is started (L1, L2 or L3), the corresponding
phase-to- element is enabled. STPE is expected to be made available for two-phase
and three-phase faults for the correct output to be selected. The fault loop is
indicated by one of the decimal numbers below.
The output STCNDPHS provides release information from the phase selection part
only. STCNDLE provides release information from the load encroachment part
only. STCNDPLE provides release information from the phase selection part and
256
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
the load encroachment part combined, that is, both parts have to issue a release at
the same time (this signal is normally not used in the zone measuring element). In
these signals, each fault type has an associated value, which represents the
corresponding zone measuring loop to be released. The values are presented in
table 132.
0= no faulted phases
1= L1E
2= L2E
3= L3E
4= -L1L2E
5= -L2L3E
6= -L3L1E
7= -L1L2L3E
8= -L1L2
9= -L2L3
10= -L3L1
11= L1L2L3
An additional logic is applied to handle the cases when phase-to-earth outputs are
to be asserted when the earth input G is not asserted.
The output signal STCNDPLE is activated when the load encroachment is operating.
IEC06000429-2-en.vsd
IEC06000429 V2 EN
257
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
258
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
Zpsb
SYMBOL-EE V1 EN
6.9.1 Introduction
Power swings may occur after disconnection of heavy loads or trip of big
generation plants.
259
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
Power swing detection function (ZMRPSB) is used to detect power swings and
initiate block of selected distance protection zones. Occurrence of earth-fault
currents during a power swing can block ZMRPSB function to allow fault clearance.
Its principle of operation is based on the measurement of the time it takes for a
power swing transient impedance to pass through the impedance area between the
outer and the inner characteristics. Power swings are identified by transition times
longer than a transition time set on corresponding timers. The impedance
measuring principle is the same as that used for the distance protection zones. The
impedance and the characteristic passing times are measured in all three phases
separately.
X1OutFw jX ZL R1LIn
X1InFw DFw
j
DRv
R1FInRv R1FInFw
DFw
ArgLd j
ArgLd
DRv
DFw
DFw
R
DFw
DRv
RLdInRv RLdInFw
DFw
DRv
RLdOutRv RLdOutFw
j DRv X1InRv
X1OutRv
IEC09000222_1_en.vsd
IEC09000222 V1 EN
260
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
æ ULn ö
Re çç ÷÷ £ Rset
è ILn ø
EQUATION1183 V2 EN (Equation 54)
æ ULn ö
Imçç ÷÷ £ Xset
è ILn ø
EQUATION1184 V2 EN (Equation 55)
RLdInFw = kLdRFw·RLdOutFw
EQUATION1185 V2 EN (Equation 56)
where:
kLdRFw is a settable multiplication factor less than 1
The slope of the load encroachment inner and outer boundary is defined by setting
the parameter ArgLd.
The load encroachment in the fourth quadrant uses the same settings as in the first
quadrant (same ArgLd and RLdOutFw and calculated value RLdInFw).
From the setting parameter RLdOutFw and the calculated value RLdInFw a
distance between the inner and outer boundary, DFw, is calculated. This value is
valid for R direction in first and fourth quadrant and for X direction in first and
second quadrant.
261
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
RLdInRv = kLdRRv·RLdOutRv
EQUATION1187 V2 EN (Equation 57)
where:
kLdRRv is a settable multiplication factor less than 1
From the setting parameter RLdOutRv and the calculated value RLdInRv, a
distance between the inner and outer boundary, DRv, is calculated. This value is
valid for R direction in second and third quadrant and for X direction in third and
fourth quadrant.
The inner resistive characteristic in the second quadrant outside the load
encroachment part corresponds to the setting parameter R1FInRv for the inner
boundary. The outer boundary is internally calculated as the sum of DRv+R1FInRv.
The inner resistive characteristic in the third quadrant outside the load
encroachment zone consist of the sum of the settings R1FInRv and the line
resistance R1LIn. The argument of the tilted lines outside the load encroachment is
the same as the tilted lines in the first quadrant. The distance between the inner and
outer boundary is the same as for the load encroachment in reverse direction, that is
DRv.
The inner characteristic for the reactive reach in forward direction correspond to
the setting parameter X1InFw and the outer boundary is defined as X1InFw + DFw,
where:
DFw = RLdOutFw - KLdRFw · RLdOutFw
The inner characteristic for the reactive reach in reverse direction correspond to the
setting parameter X1InRv for the inner boundary and the outer boundary is defined
as X1InRv + DRv.
where:
DRv = RLdOutRv - KLdRRv · RLdOutRv
262
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
The operation of the Power swing detection ZMRPSB is only released if the
magnitude of the current is above the setting of the min operating current,
IMinOpPE.
Signals ZOUTLn (outer boundary) and ZINLn (inner boundary) in figure 147 are
related to the operation of the impedance measuring elements in each phase
separately (n represents the corresponding L1, L2 and L3). They are internal
signals, calculated by ZMRPSB function.
The tP1 timer in figure 147 serve as detection of initial power swings, which are
usually not as fast as the later swings are. The tP2 timer become activated for the
detection of the consecutive swings, if the measured impedance exit the operate
area and returns within the time delay, set on the tW waiting timer. The upper part
of figure 147 (internal input signal ZOUTL1, ZINL1, AND-gates and tP-timers)
are duplicated for phase L2 and L3. All tP1 and tP2 timers in the figure have the
same settings.
ZOUTL1 AND
0-tP1
ZINL1 0 OR
-loop
0-tP2
-loop
AND
0
OR DET-L1
AND AND
ZOUTL2 OR
ZOUTL3
detected 0
0-tW
IEC05000113-2-en.vsd
IEC05000113 V2 EN
263
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
DET-L1
DET-L2 DET1of3 - int.
>1
DET-L3
&
DET2of3 - int.
& >1
&
IEC01000057-2-en.vsd
IEC01000057-TIFF V2 EN
Figure 148: Detection of power swing for 1-of-3 and 2-of-3 operating mode
ZOUTL1 ZOUT
OR
ZOUTL2 ZINL1
ZIN
ZOUTL3 AND ZINL2 OR
ZINL3
tEF
TRSP
t AND
I0CHECK
10 ms
AND t
BLKI02 OR
tR1
AND t INHIBIT
OR
-loop
tR2
BLKI01 AND t
BLOCK
-loop
DET1of3 - int.
REL1PH
AND
BLK1PH
tH
DET2of3 - int. OR t
REL2PH
AND
BLK2PH OR START
AND
EXTERNAL
en05000114.vsd
IEC05000114 V1 EN
264
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
Figure 149 presents a simplified logic diagram for the Power swing detection
function ZMRPSB. The internal signals DET1of3 and DET2of3 relate to the
detailed logic diagrams in figure 147 and figure 148 respectively.
The load encroachment characteristic can be switched off by setting the parameter
OperationLdCh = Off, but notice that the DFw and DRv will still be calculated from
RLdOutFw and RLdOutRv. The characteristic will in this case be only quadrilateral.
There are four different ways to form the internal INHIBIT signal:
265
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
IEC06000264-2-en.vsd
IEC06000264 V2 EN
266
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
267
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
6.10.1 Introduction
Power Swing Logic (ZMRPSL) is a complementary function to Power Swing
Detection (ZMRPSB) function. It provides possibility for selective tripping of
faults on power lines during system oscillations (power swings or pole slips), when
the distance protection function should normally be blocked. The complete logic
consists of two different parts:
Communication and tripping logic as used by the power swing distance protection
zones is schematically presented in figure 151.
268
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
STDEF
AR1P1 &
STPSD tCS
CS
BLOCK & t &
CSUR
BLKZMPS
tBlkTr &
tTrip t
t
CACC TRIP
>1
CR &
en06000236.vsd
IEC06000236 V1 EN
Figure 151: Simplified logic diagram – power swing communication and tripping
logic
The complete logic remains blocked as long as there is a logical one on the
BLOCK functional input signal. Presence of the logical one on the STDEF
functional input signal also blocks the logic as long as this block is not released by
the logical one on the AR1P1 functional input signal. The functional output signal
BLKZMPS remains logical one as long as the function is not blocked externally
(BLOCK is logical zero) and the earth-fault is detected on protected line (STDEF
is logical one), which is connected in three-phase mode (AR1P1 is logical zero).
Timer tBlkTr prolongs the duration of this blocking condition, if the measured
impedance remains within the operate area of the Power Swing Detection
(ZMRPSB) function (STPSD input active). The BLKZMPS can be used to block
the operation of the power-swing zones.
Logical one on functional input CSUR, which is normally connected to the TRIP
functional output of a power swing carrier sending zone, activates functional output
CS, if the function is not blocked by one of the above conditions. It also activates
the TRIP functional output.
Initiation of the CS functional output is possible only, if the STPSD input has been
active longer than the time delay set on the security timer tCS.
Figure 152 presents the logical circuits, which control the operation of the
underreaching zone (zone 1) at power swings, caused by the faults and their
clearance on the remote power lines.
269
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
&
BLKZMH
&
STZML tZL
STZMLL
BLOCK & t >1
&
STMZH tDZ
STZMPSD & t
>1
STPSD
&
-loop
en06000237.vsd
IEC06000237 V1 EN
The logic is disabled by a logical one on functional input BLOCK. It can start only
if the following conditions are simultaneously fulfilled:
• STPSD functional input signal must be a logical zero. This means, that Power
swing detection (ZMRPSB) function must not detect power swinging over the
protected power line.
• STZMPSD functional input must be a logical one. This means that the
impedance must be detected within the external boundary of ZMRPSB function.
• STZMOR functional input must be a logical one. This means that the fault
must be detected by the overreaching distance protection zone, for example
zone 2.
The STZMURPS functional output, which can be used in complete terminal logic
instead of a normal distance protection zone 1, becomes active under the following
conditions:
The BLKZMOR functional output signal can be used to block the operation of the
higher distance protection zone, if the fault has moved into the zone 1 operate area
after tDZ time delay.
270
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
IEC07000026-2-en.vsd
IEC07000026 V2 EN
271
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
<
SYMBOL-MM V1 EN
6.11.1 Introduction
Sudden events in an electrical power system such as large changes in load, fault
occurrence or fault clearance, can cause power oscillations referred to as power
swings. In a non-recoverable situation, the power swings become so severe that the
synchronism is lost, a condition referred to as pole slipping. The main purpose of
the pole slip protection (PSPPPAM) is to detect, evaluate, and take the required
action for pole slipping occurrences in the power system. The electrical system
parts swinging to each other can be separated with the line/s closest to the centre of
the power swing allowing the two systems to be stable as separated islands.
272
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
The movements in the impedance plain can be seen in figure 154. The transient
behaviour is described by the transient EMF's EA and EB, and by X'd, XT and the
transient system impedance ZS.
Zone 1 Zone 2
EB X’d XT XS EA
IED
B A
jX
XS
Pole slip
impedance XT
d Apparent generator
movement impedance R
X’d
IEC06000437_2_en.vsd
IEC06000437 V2 EN
where:
X'd = transient reactance of the generator
273
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
• the minimum current exceeds 0.10 IN (IN is IBase parameter set under general
setting).
• the maximum voltage falls below 0.92 UBase
• the voltage Ucosφ (the voltage in phase with the generator current) has an
angular velocity of 0.2...8 Hz and
• the corresponding direction is not blocked.
en07000004.vsd
IEC07000004 V1 EN
Figure 155: Different generator quantities as function of the angle between the
equivalent generators
An alarm is given when movement of the rotor is detected and the rotor angle
exceeds the angle set for 'WarnAngle'.
When the impedance crosses the slip line between ZB and ZC it counts as being in
zone 1 and between ZC and ZA in zone 2. The entire distance ZA-ZB becomes zone
1 when signal EXTZONE1 is high (external device detects the direction of the
centre of slipping).
After the first slip, the signals ZONE1 or ZONE2 and – depending on the direction
of slip - either GEN or MOTOR are issued.
274
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
Every time pole slipping is detected, the impedance of the point where the slip line
is crossed and the instantaneous slip frequency are displayed as measurements.
Further slips are only detected, if they are in the same direction and if the rate of
rotor movement has reduced in relation to the preceding slip or the slip line is
crossed in the opposite direction outside ZA-ZB. A further slip in the opposite
direction within ZA-ZB resets all the signals and is then signalled itself as a first slip.
The TRIP1 tripping command and signal are generated after N1 slips in zone 1,
providing the rotor angle is less than TripAngle. The TRIP2 signal is generated
after N2 slips in zone 2, providing the rotor angle is less than TripAngle.
START
AND
0.2 £ Slip.Freq. £ 8 Hz
d ³ startAngle
ZONE1
AND
Z cross line ZA - ZC
ZONE2
AND
Z cross line ZC - ZB
Counter
a
a³b
N1Limit b TRIP1
AND
d £ tripAngle TRIP
OR
Counter
a
N2Limit b a³b TRIP2
AND
en07000005.vsd
IEC07000005 V1 EN
Figure 156: Simplified logic diagram for pole slip protection PSPPPAM
275
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
IEC07000030-2-en.vsd
IEC07000030 V2 EN
276
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
277
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
6.12.1 Introduction
Automatic switch onto fault logic, voltage and current based (ZCVPSOF) is a
function that gives an instantaneous trip at closing of breaker onto a fault. A dead
line detection check is provided to activate the function when the line is dead.
Mho distance protections can not operate for switch onto fault condition when the
phase voltages are close to zero. An additional logic based on UI Level is used for
this purpose.
The activation from the Dead line detection function is released if the internal
signal deadLine from the UILevel function is activated at the same time as the
input ZACC is not activated during at least for a duration tDLD and the setting
parameter AutoInit is set to On.
When the setting AutoInit is Off, the function is activated by an external binary
input BC. To get a trip one of the following operation modes must also be selected
by the parameter Mode:
The internal signal deadLine from the UILevel detector is activated if all three
phase currents and voltages are below the setting IPh< and UPh<.
UI Level based measurement detects the switch onto fault condition even though
the voltage is very low. The logic is based on current and voltage levels. The
internal signal SOTF UILevel is activated if a phase voltage is below the setting
278
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
UPh< and corresponding phase current is above the setting IPh< longer than the
time tDuration.
ZCVPSOF can be activated externally from input BC and thus setting AutoInit is
bypassed.
BLOCK 15
t TRIP
AND
BC
AutiInit=On
200 1000
OR t
ZACC AND t
IL1
deadLine
IL2
IL3
UL1 UILevel detector
UL2
UL3
Iph<
SOTFU ILevel
Uph<
AND
Mode = Impedance
AND OR
Mode = UILevel
OR
AND
Mode = UILvl&Imp
en07000084.vsd
IEC07000084 V2 EN
Figure 158: Simplified logic diagram for Automatic switch onto fault logic,
voltage and current based.
279
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
IEC06000459-2-en.vsd
IEC06000459 V2 EN
280
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
6.13.1 Introduction
Phase preference logic function PPLPHIZ is intended to be used in isolated or high
impedance earthed networks where there is a requirement to trip only one of the
faulty lines at cross-country fault.
Phase preference logic inhibits tripping for single phase-to-earth faults in isolated
and high impedance earthed networks, where such faults are not to be cleared by
distance protection. For cross-country faults, the logic selects either the leading or
the lagging phase-earth loop for measurement and initiates tripping of the preferred
fault based on the selected phase preference. A number of different phase
preference combinations are available for selection.
281
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
table 156 below. The difference between cyclic and acyclic operation can be
explained by the following example. Assume a L1 fault on one line and a L3 fault
on another line. For OperMode = 1231c the line with L3 fault will be tripped (L3
before L1) while for OperMode = 123a the line with L1 1 fault will be tripped (L1
before L3).
The function can be divided into two parts; one labeled voltage and current
discrimination and the second one labeled phase preference evaluation, see
figure 160.
The aim with the voltage and current discrimination part is to discriminate faulty
phases and to determine if there is a cross-country fault. If cross-country fault is
detected, an internal signal “Detected cross-country fault” is created and sent to the
phase preference part to be used in the evaluation process for determining the
condition for trip.
The voltage and current discrimination part gives phase segregated start signals if
the respective measured phase voltage is below the setting parameter UPN< at the
same time as the zero sequence voltage is above the setting parameter 3U0>. If
there is a start in any phase the START out put signal will be activated.
282
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
1. The magnitude of 3I0 has been above the setting parameter IN> for a time
longer than the setting of pick-up timer tIN.
2. The magnitude of 3I0 has been above the setting parameter IN> at the same
time as the magnitude of 3U0 has been above the setting parameter 3U0>
during a time longer than the setting of pick-up timer tUN.
3. The magnitude of 3I0 has been above the setting parameter IN> at the same
time as one of the following conditions are fulfilled:
• the measured phase-to-phase voltage in at least one of the phase
combinations has been below the setting parameter UPP< for more than
20 ms.
• At least two of the phase voltages are below the setting parameter UPN<
for more than 20 ms.
The second part, phase preference evaluation, uses the internal signal
DetectCrossCountry from the voltage and current evaluation together with the
input signal STCND together with phase selection start condition (from phase
selection functions) connected to input STCND, and the information from the
setting parameter OperMode are used to determine the condition for trip. To
release the Phase preference logic, at least two out of three phases must be faulty.
The fault classification whether it is a single phase-to-earth, two-phase or cross-
country fault and which phase to be tripped at cross-country fault is converted into
a binary coded signal and sent to the distance protection measuring zone to release
the correct measuring zone according to the setting of OperMode. This is done by
activating the output ZREL and it shall be connected to the input STCND on the
distance zone measuring element.
The release signals from phase selection will only be gated with the cross-country
check from IN and UN but without time delay. If no phase selection start has
occurred, the release is based on current and voltage discriminating part only.
The input signal STCND consist of binary information of fault type and is
connected to the output STCND on phase selection function. The fault must be
activated in at least two phases to be classified as a cross-country fault in the phase
preference part of the logic.
The input signals RELxxx are additional fault release signals that can be connected
to external protection functions through binary input.
The output START and trip signals can be blocked by activating the input BLOCK
283
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
UL1
UL2
UL3
UL1UL2
UL2UL3
UL3UL1
IN Voltage and START
AND
UN Current
Discrimination
UPN<
UPP<
IN>
Detect Cross-
UN0> Country fault
OperMode
RELL1N ZREL
Phase Preference AND
RELL2N Evaluation
RELL3N
STCND
BLOCK
IEC09000220_1_en.vsd
IEC09000220 V2 EN
IEC07000029-2-en.vsd
IEC07000029 V2 EN
284
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection
285
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection
286
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
SYMBOL-Z V1 EN
7.1.1 Introduction
The instantaneous three phase overcurrent function has a low transient overreach
and short tripping time to allow use as a high set short-circuit protection function.
There is also a possibility to activate a preset change of the set operation current
(StValMult) via a binary input (ENMULT). In some applications the operation
value needs to be changed, for example due to transformer inrush currents.
287
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
IEC04000391-2-en.vsd
IEC04000391 V2 EN
288
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
7.2.1 Introduction
The four step phase overcurrent protection function OC4PTOC has an inverse or
definite time delay independent for each step separately.
All IEC and ANSI time delayed characteristics are available together with an
optional user defined time characteristic.
The directional function is voltage polarized with memory. The function can be set
to be directional or non-directional independently for each of the steps.
289
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
U3P
TRIP
Harmonic harmRestrBlock
I3P Restraint
Element
enableDir
Mode Selection
enableStep1-4
DirectionalMode1-4
en05000740.vsd
IEC05000740 V1 EN
A common setting for all steps, StartPhSel, is used to specify the number of phase
currents to be high to enable operation. The settings can be chosen: 1 out of 3, 2 out
of 3 or 3 out of 3.
290
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
If DFT option is selected then only the RMS value of the fundamental frequency
components of each phase current is derived. Influence of DC current component
and higher harmonic current components are almost completely suppressed. If
RMS option is selected then the true RMS values is used. The true RMS value in
addition to the fundamental frequency component includes the contribution from
the current DC component as well as from higher current harmonic. The selected
current values are fed to OC4PTOC.
In a comparator, for each phase current, the DFT or RMS values are compared to
the set operation current value of the function (I1>, I2>, I3> or I4>). If a phase
current is larger than the set operation current, outputs START, STx, STL1, STL2
and STL3 are, without delay, activated. Output signals STL1, STL2 and STL3 are
common for all steps. This means that the lowest set step will initiate the
activation. The START signal is common for all three phases and all steps. It shall
be noted that the selection of measured value (DFT or RMS) do not influence the
operation of directional part of OC4PTOC.
Service value for individually measured phase currents are also available on the
local HMI for OC4PTOC function, which simplifies testing, commissioning and in
service operational checking of the function.
A harmonic restrain of the function can be chosen. A set 2nd harmonic current in
relation to the fundamental current is used. The 2nd harmonic current is taken from
the pre-processing of the phase currents and the relation is compared to a set
restrain current level.
The function can be directional. The direction of the fault current is given as
current angle in relation to the voltage angle. The fault current and fault voltage for
the directional function is dependent of the fault type. To enable directional
measurement at close in faults, causing low measured voltage, the polarization
voltage is a combination of the apparent voltage (85%) and a memory voltage
(15%). The following combinations are used.
U refL1L 2 = U L1 - U L 2 I dirL1L 2 = I L1 - I L 2
EQUATION1449 V1 EN (Equation 58)
U refL 2 L 3 = U L 2 - U L 3 I dirL 2 L 3 = I L 2 - I L 3
EQUATION1450 V1 EN (Equation 59)
U refL 3 L1 = U L 3 - U L1 I dirL 3 L1 = I L 3 - I L1
EQUATION1451 V1 EN (Equation 60)
Table continues on next page
291
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
U refL1 = U L1 I dirL1 = I L1
EQUATION1452 V1 EN (Equation 61)
U refL 2 = U L 2 I dirL 2 = I L 2
EQUATION1453 V1 EN (Equation 62)
U refL 3 = U L 3 I dirL 3 = I L 3
EQUATION1454 V1 EN (Equation 63)
For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is
restored.
• If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set terminal rated current IBase), the condition
seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.
• If the current decreases below the minimum operating value, the memory
resets until the positive sequence voltage exceeds 10% of its rated value.
The directional setting is given as a characteristic angle AngleRCA for the function
and an angle window AngleROA.
292
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
Reverse
Uref
RCA
ROA
ROA Forward
Idir
en05000745.vsd
IEC05000745 V1 EN
The default value of AngleRCA is –65°. The parameters AngleROA gives the angle
sector from AngleRCA for directional borders.
A minimum current for directional phase start current signal can be set:
IminOpPhSel.
If no blockings are given the start signals will start the timers of the step. The time
characteristic for each step can be chosen as definite time delay or inverse time
characteristic. A wide range of standardized inverse time characteristics is
available. It is also possible to create a tailor made time characteristic. The
possibilities for inverse time characteristics are described in section "Inverse
characteristics".
All four steps in OC4PTOC can be blocked from the binary input BLOCK. The
binary input BLKSTx (x=1, 2, 3 or 4) blocks the operation of respective step.
293
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
IEC06000187-2-en.vsd
IEC06000187 V2 EN
294
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
295
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
296
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
297
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
298
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
299
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
300
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
301
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
IEF V1 EN
7.3.1 Introduction
The Instantaneous residual overcurrent protection EFPIOC has a low transient
overreach and short tripping times to allow the use for instantaneous earth-fault
protection, with the reach limited to less than typical eighty percent of the line at
minimum source impedance. EFPIOC can be configured to measure the residual
current from the three-phase current inputs or the current from a separate current
input. EFPIOC can be blocked by activating the input BLOCK.
There is also a possibility to activate a preset change of the set operation current
via a binary input (enable multiplier MULTEN). In some applications the operation
value needs to be changed, for example due to transformer inrush currents.
EFPIOC function can be blocked from the binary input BLOCK. The trip signals
from the function can be blocked from the binary input BLKAR, that can be
activated during single pole trip and autoreclosing sequences.
IEC06000269-2-en.vsd
IEC06000269 V2 EN
302
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
303
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
7.4.1 Introduction
The four step residual overcurrent protection EF4PTOC has an inverse or definite
time delay independent for each step separately.
All IEC and ANSI time delayed characteristics are available together with an
optional user defined characteristic.
EF4PTOC can also be used to provide a system back-up for example, in the case of
the primary protection being out of service due to communication or voltage
transformer circuit failure.
EF4PTOC can be configured to measure the residual current from the three-phase
current inputs or the current from a separate current input.
304
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
These inputs are connected from the corresponding pre-processing function blocks
in the Configuration Tool within PCM600.
The function always uses Residual Current (3I0) for its operating quantity. The
residual current can be:
where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.
The residual current is pre-processed by a discrete Fourier filter. Thus the phasor of
the fundamental frequency component of the residual current is derived. The
phasor magnitude is used within the EF4PTOC protection to compare it with the
305
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
set operation current value of the four steps (IN1>, IN2>, IN3> or IN4>). If the
residual current is larger than the set operation current and the step is used in non-
directional mode a signal from the comparator for this step is set to true. This
signal will, without delay, activate the output signal STINx (x=step 1-4) for this
step and a common START signal.
The function can be set to use voltage polarizing, current polarizing or dual polarizing.
Voltage polarizing
When voltage polarizing is selected the protection will use the residual voltage
-3U0 as polarizing quantity U3P. This voltage can be:
where:
UL1, UL2 and UL3 are fundamental frequency phasors of three individual phase voltages.
Note! In order to use this all three phase-to-earth voltages must be connected to three IED VT inputs.
The residual voltage is pre-processed by a discrete fourier filter. Thus, the phasor
of the fundamental frequency component of the residual voltage is derived. This
phasor is used together with the phasor of the operating current, in order to
determine the direction to the earth fault (Forward/Reverse). In order to enable
voltage polarizing the magnitude of polarizing voltage shall be bigger than a
minimum level defined by setting parameter UpolMin.
It shall be noted that –3U0 is used to determine the location of the earth fault. This
insures the required inversion of the polarizing voltage within the earth-fault function.
306
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
Current polarizing
When current polarizing is selected the function will use the residual current (3I0)
as polarizing quantity IPol. This current can be:
where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.
, which will be then used, together with the phasor of the operating current, in order
to determine the direction to the earth fault (Forward/Reverse). In order to enable
current polarizing the magnitude of polarizing current shall be bigger than a
minimum level defined by setting parameter IPolMin.
Dual polarizing
When dual polarizing is selected the function will use the vectorial sum of the
voltage based and current based polarizing in accordance with the following formula:
307
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
Then the phasor of the total polarizing voltage UTotPol will be used, together with
the phasor of the operating current, to determine the direction of the earth fault
(Forward/Reverse).
The individual steps within the protection can be set as non-directional. When this
setting is selected it is then possible via function binary input BLKSTx to provide
external directional control (that is, torque control) by for example using one of the
following functions if available in the IED:
The base quantities shall be entered as setting parameters for every earth-fault
function. Base current (IBase) shall be entered as rated phase current of the
protected object in primary amperes. Base voltage (UBase) shall be entered as
rated phase-to-phase voltage of the protected object in primary kV.
Each overcurrent step uses operating quantity Iop (residual current) as measuring
quantity. Each of the four residual overcurrent steps has the following built-in
facilities:
that the directional decision (Forward/Reverse) is not made within the residual
overcurrent step itself. The direction of the fault is determined in common
“directional supervision element”.
• Residual current pickup value.
• Type of operating characteristic (inverse or definite time). By this parameter
setting it is possible to select inverse or definite time delay for the earth-fault
protection. Most of the standard IEC and ANSI inverse characteristics are
available. For the complete list of available inverse curves please refer to
section "Inverse characteristics".
• Type of reset characteristic (Instantaneous / IEC Reset / ANSI Reset). By this
parameter setting it is possible to select the reset characteristic of the step. For
the complete list of available reset curves please refer to section "Inverse time
characteristics".
• Time delay related settings. By these parameter settings the properties like
definite time delay, minimum operating time for inverse curves, reset time
delay and parameters to define user programmable inverse curve are defined.
• Supervision by second harmonic blocking feature (On/Off). By this parameter
setting it is possible to prevent operation of the step if the second harmonic
content in the residual current exceeds the preset level.
• Multiplier for scaling of the set residual current pickup value by external
binary signal. By this parameter setting it is possible to increase residual
current pickup value when function binary input ENMULTx has logical value
1.
Simplified logic diagram for one residual overcurrent step is shown in figure 167.
BLKTR
Characteristx=DefTime tx TRINx
|IOP| AND
a OR
a>b
b
ENMULTx
STINx
INxMult AND
X T
INx> F
Inverse
BLKSTx
BLOCK Characteristx=Inverse
2ndH_BLOCK_Int
OR
HarmRestrain1=Disabled
DirModex=Off OR STAGEx_DIR_Int
DirModex=Non-directional
DirModex=Forward
AND OR
FORWARD_Int
DirModex=Reverse
AND
REVERSE_Int
en07000064.vsd
IEC07000064 V1 EN
Figure 167: Simplified logic diagram for residual overcurrent step x, where x =
step 1, 2, 3 or 4
The protection can be completely blocked from the binary input BLOCK. Output
signals for respective step, STINx and TRINx, can be blocked from the binary
309
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
input BLKSTx. The trip signals from the function can be blocked from the binary
input BLKTR.
The protection has integrated directional feature. As the operating quantity current
Iop is always used. The polarizing method is determined by the parameter setting
polMethod. The polarizing quantity will be selected by the function in one of the
following three ways:
The operating and polarizing quantity are then used inside the directional element,
as shown in figure 168, in order to determine the direction of the earth fault.
310
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
Reverse
Area
0.6·IN>Dir
AngleRCA Upol=-3Uo
IN>Dir
Forward
Area
Iop=3Io
IEC07000066-3-en.vsd
IEC07000066 V3 EN
311
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
|Iop|
a
a>b STRV
b AND
REVERSE_Int
0.6
X
a
a>b
AND STFW
IN>Dir b
FORWARD_Int
X
0.4
FWD
AND FORWARD_Int
AngleRCA
polMethod=Voltage
OR
UPolMin
Characteristic
Directional
polMethod=Dual UPol IPolMin
T
Iop
0.0 F
UTotPol
IPol AND REVERSE_Int
RVS
UIPol
RNPol Complex X T
XNPol Number 0.0 F STAGE1_DIR_Int
STAGE2_DIR_Int
STAGE3_DIR_Int OR
STAGE4_DIR_Int
BLOCK AND
IEC07000067-3-en.vsd
IEC07000067 V3 EN
Figure 169: Simplified logic diagram for directional supervision element with integrated directional
comparison step
In addition to the basic functionality explained above the 2nd harmonic blocking
can be set in such way to seal-in until residual current disappears. This feature
might be required to stabilize EF4PTOC during switching of parallel transformers
in the station. In case of parallel transformers there is a risk of sympathetic inrush
current. If one of the transformers is in operation, and the parallel transformer is
312
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
switched in, the asymmetric inrush current of the switched in transformer will
cause partial saturation of the transformer already in service. This is called
transferred saturation. The 2nd harmonic of the inrush currents of the two
transformers will be in phase opposition. The summation of the two currents will
thus give a small 2nd harmonic current. The residual fundamental current will
however be significant. The inrush current of the transformer in service before the
parallel transformer energizing, will be a little delayed compared to the first
transformer. Therefore we will have high 2nd harmonic current component initially.
After a short period this current will however be small and the normal 2nd
harmonic blocking will reset. If the BlkParTransf function is activated the 2nd
harmonic restrain signal will be latched as long as the residual current measured by
the relay is larger than a selected step current level.
This feature has been called Block for Parallel Transformers. This 2nd harmonic seal-
in feature will be activated when all of the following three conditions are
simultaneously fulfilled:
Once Block for Parallel Transformers is activated the basic 2nd harmonic blocking
signal will be sealed-in until the residual current magnitude falls below a value
defined by parameter setting UseStartValue (see condition 3 above).
Simplified logic diagram for 2nd harmonic blocking feature is shown in figure 170.
313
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
BLOCK
Extract second
IOP 2NDHARMD
harmonic current a
a>b
OR
component 2ndHarmStab b
X
Extract
fundamental
q-1
current component
t=70ms OR
t AN OR 2ndH_BLOCK_Int
D
BlkParTransf=On
|IOP|
a
a>b
b
UseStartValue
IN1>
IN2>
IN3>
IN4>
en07000068-2.vsd
IEC07000068 V2 EN
Figure 170: Simplified logic diagram for 2nd harmonic blocking feature and Block for Parallel Transformers
feature
Integrated in the four step residual overcurrent protection are Switch on to fault
logic (SOTF) and Under-Time logic. The setting parameter SOTF is set to activate
either SOTF or Under-Time logic or both. When the circuit breaker is closing there
is a risk to close it onto a permanent fault, for example during an autoreclosing
sequence. The SOTF logic will enable fast fault clearance during such situations.
The time during which SOTF and Under-Time logics will be active after activation
is defined by the setting parameter t4U.
The SOTF logic uses the start signal from step 2 or step 3 for its operation, selected
by setting parameter StepForSOTF. The SOTF logic can be activated either from
change in circuit breaker position or from circuit breaker close command pulse.
The setting parameter ActivationSOTF can be set for activation of CB position
open change, CB position closed change or CB close command. In case of a
residual current start from step 2 or 3 (dependent on setting) the function will give
a trip after a set delay tSOTF. This delay is normally set to a short time (default 200
ms).
The Under-Time logic always uses the start signal from the step 4. The Under-
Time logic will normally be set to operate for a lower current level than the SOTF
314
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
function. The Under-Time logic can also be blocked by the 2nd harmonic restraint
feature. This enables high sensitivity even if power transformer inrush currents can
occur at breaker closing. This logic is typically used to detect asymmetry of CB
poles immediately after switching of the circuit breaker. The Under-Time logic is
activated either from change in circuit breaker position or from circuit breaker
close and open command pulses. This selection is done by setting parameter
ActUnderTime. In case of a start from step 4 this logic will give a trip after a set
delay tUnderTime. This delay is normally set to a relatively short time (default 300
ms). Practically the Under-Time logic acts as circuit breaker pole-discordance
protection, but it is only active immediately after breaker switching. The Under-
Time logic can only be used in solidly or low impedance grounded systems.
SOTF
Open
tPulse
Closed
ActivationSOTF
Close command
tSOTF
AND
AND t
STIN2
StepForSOTF
STIN3
OperationMode
BLOCK
OFF
SOTF
UNDERTIME TRIP
UnderTime
tUnderTime
SOTF or
2nd Harmonic AND
HarmResSOFT t UnderTime
OR
Open
Close OR
tPulse
Close command
ActUnderTime
AND
STIN4
IEC06000643-2-en.vsd
IEC06000643 V2 EN
Figure 171: Simplified logic diagram for SOTF and Under-Time features
EF4PTOC Logic Diagram Simplified logic diagram for the complete EF4PTOC
function is shown in figure 172:
315
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
signal to
communication
scheme
Directional Check
Element
DirMode
enableDir
harmRestrBlock
3I0 Harmonic
Restraint ³1
Element
CB
DirMode pos
or cmd
enableDir
Mode
Selection enableStep1-4
DirectionalMode1-4
en06000376.vsd
IEC06000376 V1 EN
IEC06000424-2-en.vsd
IEC06000424 V2 EN
316
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
317
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
318
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
319
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
320
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
321
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
322
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
323
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
7.5.1 Introduction
In networks with high impedance earthing, the phase-to-earth fault current is
significantly smaller than the short circuit currents. Another difficulty for earth-
fault protection is that the magnitude of the phase-to-earth fault current is almost
independent of the fault location in the network.
Directional residual current can be used to detect and give selective trip of phase-to-
earth faults in high impedance earthed networks. The protection uses the residual
current component 3I0 · cos φ, where φ is the angle between the residual current
and the residual voltage (-3U0), compensated with a characteristic angle.
Alternatively, the function can be set to strict 3I0 level with an check of angle 3I0
and cos φ.
Directional residual power can also be used to detect and give selective trip of phase-
to-earth faults in high impedance earthed networks. The protection uses the
residual power component 3I0 · 3U0 · cos φ, where φ is the angle between the
residual current and the reference residual voltage, compensated with a
characteristic angle.
A normal non-directional residual current function can also be used with definite or
inverse time delay.
In an isolated network, that is, the network is only coupled to earth via the
capacitances between the phase conductors and earth, the residual current always
has -90º phase shift compared to the reference residual voltage. The characteristic
angle is chosen to -90º in such a network.
As the amplitude of the residual current is independent of the fault location the
selectivity of the earth-fault protection is achieved by time selectivity.
When should the sensitive directional residual overcurrent protection be used and
when should the sensitive directional residual power protection be used? Consider
the following facts:
324
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
The function is using phasors of the residual current and voltage. Group signals I3P
and U3P containing phasors of residual current and voltage is taken from pre-
processor blocks.
The sensitive directional earth fault protection has the following sub-functions
included:
325
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
Uref
RCADir = 0o, ROADir = 0o
3I0
j = ang(3I0 ) - ang(3Uref )
-3U0 = Uref
3I0 × cosj
IEC06000648_2_en.vsd
IEC06000648 V2 EN
Uref
RCADir = -90o, ROADir = 90o
3I0
3I0 × cos j
-3U0
IEC06000649_2_en.vsd
IEC06000649 V2 EN
For trip, both the residual current 3I0·cos φ and the release voltage 3U0, must be
larger than the set levels: INCosPhi> and UNRel>.
Trip from this function can be blocked from the binary input BLKTRDIR.
326
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef the binary output signals
TRIP and TRDIRIN are activated. The trip from this sub-function has definite time
delay.
There is a possibility to increase the operate level for currents where the angle φ is
larger than a set value as shown in the figure below. This is equivalent to blocking
of the function if φ > ROADir. This option is used to handle angle error for the
instrument transformers.
RCADir = 0o
3I0
Operate area
j
-3U0 = Uref
3I0 × cos j
ROADir
IEC06000650_2_en.vsd
IEC06000650 V2 EN
327
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
RCADir = 0º
Operate area
-3U0 =Uref
Instrument
transformer a
RCAcomp
angle error
Characteristic after
angle compensation
en06000651.vsd
IEC06000651 V2 EN
For trip, both the residual power 3I0 · 3U0 · cos φ, the residual current 3I0 and the
release voltage 3U0, shall be larger than the set levels (SN>, INRel> and UNRel>).
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef or after the inverse time
delay (setting kSN) the binary output signals TRIP and TRDIRIN are activated.
The function shall indicate forward/reverse direction to the fault. Reverse direction
is defined as 3I0 · 3U0·cos (φ + 180°) ³ the set value.
This variant has the possibility of choice between definite time delay and inverse
time delay.
328
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
RCADir = 0º
ROADir = 80º
Operate area
3I0
80 -3U0
en06000652.vsd
IEC06000652 V2 EN
For trip, both the residual current 3I0 and the release voltage 3U0, shall be larger
than the set levels INDir> and UNREL> and the angle φ shall be in the set sector
ROADir and RCADir.
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef the binary output signals
TRIP and TRDIRIN are activated.
329
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
Directional functions
For all the directional functions there are directional start signals STFW: fault in
the forward direction, and STRV: start in the reverse direction. Even if the
directional function is set to operate for faults in the forward direction a fault in the
reverse direction will give the start signal STRV. Also if the directional function is
set to operate for faults in the reverse direction a fault in the forward direction will
give the start signal STFW.
This variant shall have the possibility of choice between definite time delay and
inverse time delay. The inverse time delay shall be according to IEC 60255-3.
For trip, the residual current 3I0 shall be larger than the set levels (INNonDir>).
Trip from this function can be blocked from the binary input BLKNDN.
When the function is activated binary output signal STNDIN is activated. If the
activation is active after the set delay tINNonDir or after the inverse time delay the
binary output signals TRIP and TRNDIN are activated.
There shall also be a separate trip, with its own definite time delay, from this set
voltage level.
For trip, the residual voltage 3U0 shall be larger than the set levels (UN>).
Trip from this function can be blocked from the binary input BLKUN.
When the function is activated binary output signal STUN is activated. If the
activation is active after the set delay tUNNonDir TRIP and TRUN are activated. A
simplified logical diagram of the total function is shown in figure 179.
330
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
INNonDir> STNDIN
t TRNDIN
UN> STUN
t TRUN
OpMODE=3I0cosfi
IN>
&
INcosPhi>
OpMODE=3I03U0cosfi
INUNcosPhi> t
SN
& TRDIRIN
Phi in RCA +- ROA
TimeChar = InvTime
&
OpMODE=3I0 and fi
&
TimeChar = DefTime
DirMode = Reverse
&
Reverse STRV
en06000653.vsd
IEC06000653 V2 EN
Figure 179: Simplified logical diagram of the sensitive earth-fault current protection
IEC07000032-2-en.vsd
IEC07000032 V2 EN
331
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
332
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
333
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
334
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
335
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
SYMBOL-A V1 EN
7.6.1 Introduction
The increasing utilizing of the power system closer to the thermal limits has
generated a need of a thermal overload protection also for power lines.
A thermal overload will often not be detected by other protection functions and the
introduction of the thermal overload protection can allow the protected circuit to
operate closer to the thermal limits.
The three-phase current measuring protection has an I2t characteristic with settable
time constant and a thermal memory.
An alarm level gives early warning to allow operators to take action well before the
line is tripped.
2
æ I ö
Q final =ç ÷÷ × Tref
ç I ref
è ø
EQUATION1167 V1 EN (Equation 70)
where:
I is the largest phase current,
Iref is a given reference current and
336
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
æ Dt
ö
Qn = Qn -1 + ( Q final - Q n-1 ) × ç1 - e t ÷
-
è ø
EQUATION1168 V1 EN (Equation 71)
where:
Qn is the calculated present temperature,
When the component temperature reaches the set alarm level AlarmTemp the
output signal ALARM is set. When the component temperature reaches the set trip
level TripTemp the output signal TRIP is set.
There is also a calculation of the present time to operate with the present current.
This calculation is only performed if the final temperature is calculated to be above
the operation temperature:
æQ - Qoperate ö
toperate = -t × ln ç final
ç Q final - Q n ÷÷
è ø
EQUATION1169 V1 EN (Equation 72)
After a trip, caused by the thermal overload protection, there can be a lockout to
reconnect the tripped circuit. The output lockout signal LOCKOUT is activated
when the device temperature is above the set lockout release temperature setting
ReclTemp.
The time to lockout release is calculated that is, a calculation of the cooling time to
a set value. The thermal content of the function can be reset with input RESET.
337
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
æQ - Qlockout _ release ö
tlockout _ release = -t × ln ç final ÷÷
ç Q final - Q n
è ø
EQUATION1170 V1 EN (Equation 73)
Here the final temperature is equal to the set or measured ambient temperature. The
calculated time to reset of lockout is available as a real figure signal, TENRECL.
In some applications the measured current can involve a number of parallel lines.
This is often used for cable lines where one bay connects several parallel cables.
By setting the parameter IMult to the number of parallel lines (cables) the actual
current on one line is used in the protection algorithm. To activate this option the
input ENMULT must be activated.
The protection has a reset input: RESET. By activating this input the calculated
temperature is reset to its default initial value. This is useful during testing when
secondary injected current has given a calculated “false” temperature level.
actual temperature
Calculation
of actual
temperature
TRIP
Actual Temp
> TripTemp
Lock-
LOCKOUT
out
logic
Actual Temp
< Recl Temp
Calculation TTRIP
of time to
trip
Calculation
of time to TENRECL
reset of
lockout
IEC09000637_1_en.vsd
IEC09000637 V1 EN
338
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
IEC04000396-2-en.vsd
IEC04000396 V3 EN
339
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
340
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
3I>BF
SYMBOL-U V1 EN
7.7.1 Introduction
Breaker failure protection (CCRBRF) ensures fast back-up tripping of surrounding
breakers in case of own breaker failure to open. CCRBRF can be current based,
contact based, or adaptive combination between these two principles.
A current check with extremely short reset time is used as check criteria to achieve
a high security against unnecessary operation.
A contact check criteria can be used where the fault current through the breaker is
small.
CCRBRF can be single- or three-phase initiated to allow use with single phase
tripping applications. For the three-phase version of CCRBRF the current criteria
can be set to operate only if two out of four for example, two phases or one phase
plus the residual current start. This gives a higher security to the back-up trip
command.
The start signal can be phase selective or general (for all three phases). Phase
selective start signals enable single pole re-trip function. This means that a second
attempt to open the breaker is done. The re-trip attempt can be made after a set
time delay. For transmission lines single pole trip and autoreclosing is often used.
The re-trip function can be phase selective if it is initiated from phase selective line
protection. The re-trip function can be done with or without current check. With
the current check the re-trip is only performed if the current through the circuit
breaker is larger than the operate current level.
The start signal can be an internal or external protection trip signal. This signal will
start the back-up trip timer. If the opening of the breaker is successful this is
detected by the function, by detection of either low current through RMS
evaluation and a special adapted current algorithm or by open contact indication.
The special algorithm enables a very fast detection of successful breaker opening,
341
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
that is, fast resetting of the current measurement. If the current and/or contact
detection has not detected breaker opening before the back-up timer has run its
time a back-up trip is initiated.
• The minimum length of the re-trip pulse, the back-up trip pulse and the back-
up trip pulse 2 are settable. The re-trip pulse, the back-up trip pulse and the back-
up trip pulse 2 will however sustain as long as there is an indication of closed
breaker.
• In the current detection it is possible to use three different options: 1 out of 3
where it is sufficient to detect failure to open (high current) in one pole, 1 out
of 4 where it is sufficient to detect failure to open (high current) in one pole or
high residual current and 2 out of 4 where at least two current (phase current and/
or residual current) shall be high for breaker failure detection.
• The current detection level for the residual current can be set different from the
setting of phase current detection.
• It is possible to have different back-up time delays for single-phase faults and
for multi-phase faults.
• The back-up trip can be made without current check. It is possible to have this
option activated for small load currents only.
• It is possible to have instantaneous back-up trip function if a signal is high if
the circuit breaker is insufficient to clear faults, for example at low gas pressure.
START 30 ms
IEC09000976-1-en.vsd
IEC09000976 V1 EN
342
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
IP>
a
a>b
b
FunctionMode Current
OR AND Reset L1
OR
Contact
1 Time out L1
Current and Contact OR
AND
Current High L1
IL1 CB Closed L1
AND
OR
BFP Started L1
a AND AND
a>b OR AND
I>BlkCont b
IEC09000977-1-en.vsd
IEC09000977 V1 EN
t1 TRRETL3
BFP Started L1 From other
t Retrip Time Out L1
phases TRRETL2 OR
TRRET
tPulse
RetripMode No CBPos Check AND
OR TRRETL1
OR
1
OR AND
CB Pos Check
AND
CB Closed L1
CBFLT
IEC09000978-1-en.vsd
IEC09000978 V1 EN
343
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
IN
a
a>b AND
IN> b
CBFLT
AND
t2
BFP Started L1 Backup Trip L1
t AND
OR
t2MPh
AND t
AND
OR OR
tPulse
From other Backup Trip L2 OR TRBU
OR
phases Backup Trip L3
From other BFP Started L2 2 of 3
phases BFP Started L3 tPulse
t3
OR
TRBU2
S Q t
R SR
AND
IEC09000979-1-en.vsd
IEC09000979 V1 EN
Figure 186: Simplified logic scheme of the back-up trip logic function
Internal logical signals STIL1, STIL2, STIL3 have logical value 1 when current in
respective phase has magnitude larger than setting parameter IP>.
IEC06000188-2-en.vsd
IEC06000188 V2 EN
344
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
345
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
346
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
3I>STUB
SYMBOL-T V1 EN
7.8.1 Introduction
When a power line is taken out of service for maintenance and the line
disconnector is opened in multi-breaker arrangements the voltage transformers will
mostly be outside on the disconnected part. The primary line distance protection
will thus not be able to operate and must be blocked.
The stub protection STBPTOC covers the zone between the current transformers
and the open disconnector. The three-phase instantaneous overcurrent function is
released from a normally open, NO (b) auxiliary contact on the line disconnector.
If a phase current is larger than the set operating current the signal from the
comparator for this phase is activated. This signal will, in combination with the
release signal from line disconnection (RELEASE input), activate the timer for the
TRIP signal. If the fault current remains during the timer delay t, the TRIP output
signal is activated. The function can be blocked by activation of the BLOCK input.
347
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
BLOCK
TRIP
STIL1 AND
STIL2 OR
STIL3
RELEASE
en05000731.vsd
IEC05000731 V1 EN
IEC05000678-2-en.vsd
IEC05000678 V2 EN
348
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
PD
SYMBOL-S V1 EN
349
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
7.9.1 Introduction
Single pole operated circuit breakers can due to electrical or mechanical failures
end up with the different poles in different positions (close-open). This can cause
negative and zero sequence currents which gives thermal stress on rotating
machines and can cause unwanted operation of zero sequence or negative sequence
current functions.
Normally the own breaker is tripped to correct such a situation. If the situation
persists the surrounding breaker should be tripped to clear the unsymmetrical load
situation.
en05000287.vsd
IEC05000287 V2 EN
This binary signal is connected to a binary input of the IED. The appearance of this
signal will start a timer that will give a trip signal after the set time delay.
There is also a possibility to connect all phase selective auxiliary contacts (phase
contact open and phase contact closed) to binary inputs of the IED, see figure 191.
350
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
C.B.
+
poleOneOpened from C.B.
en05000288.vsd
IEC05000288 V1 EN
In this case the logic is realized within the function. If the inputs are indicating pole
discordance the trip timer is started. This timer will give a trip signal after the set
delay.
The function also has a binary input that can be configured from the autoreclosing
function, so that the pole discordance function can be blocked during sequences
with a single pole open if single pole autoreclosing is used.
The simplified block diagram of the current and contact based Pole discordance
protection function CCRPLD is shown in figure 192.
351
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
BLOCK
OR
BLKDBYAR
PolPosAuxCont
AND
POLE1OPN
POLE1CL
POLE2OPN
Discordance
POLE2CL
detection
POLE3OPN
POLE3CL t 150 ms
t TRIP
AND
OR
PD Signal from CB
AND
EXTPDIND
CLOSECMD t+200 ms
OR
OPENCMD
AND
Unsymmetry current
detection
en05000747.vsd
IEC05000747 V1 EN
• The IED is in TEST mode and CCRPLD has been blocked from the local HMI
• The input signal BLOCK is high
• The input signal BLKDBYAR is high
The BLOCK signal is a general purpose blocking signal of the pole discordance
protection. It can be connected to a binary input in the IED in order to receive a
block command from external devices or can be software connected to other
internal functions in the IED itself in order to receive a block command from
internal functions. Through OR gate it can be connected to both binary inputs and
internal function outputs.
The BLKDBYAR signal blocks the pole discordance operation when a single
phase autoreclosing cycle is in progress. It can be connected to the output signal
1PT1 on SMBRRECfunction block. If the autoreclosing function is an external
device, then BLKDBYAR has to be connected to a binary input in the IED and this
binary input is connected to a signalization “1phase autoreclosing in progress”
from the external autoreclosing device.
If the pole discordance protection is enabled, then two different criteria can
generate a trip signal TRIP:
352
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
If one or two poles of the circuit breaker have failed to open or to close the pole
discordance status, then the function input EXTPDIND is activated from the pole
discordance signal derived from the circuit breaker auxiliary contacts (one NO
contact for each phase connected in parallel, and in series with one NC contact for
each phase connected in parallel) and, after a settable time interval tTrip (0-60 s), a
150 ms trip pulse command TRIP is generated by the Polediscordance function.
• any phase current is lower than CurrUnsymLevel of the highest current in the
three phases.
• the highest phase current is greater than CurrRelLevel of IBase.
If these conditions are true, an unsymmetrical condition is detected and the internal
signal INPS is turned high. This detection is enabled to generate a trip after a set
time delay tTrip if the detection occurs in the next 200 ms after the circuit breaker
has received a command to open trip or close and if the unbalance persists. The 200
ms limitation is for avoiding unwanted operation during unsymmetrical load
conditions.
The pole discordance protection is informed that a trip or close command has been
given to the circuit breaker through the inputs CLOSECMD (for closing command
information) and OPENCMD (for opening command information). These inputs
can be connected to terminal binary inputs if the information are generated from
the field (that is from auxiliary contacts of the close and open push buttons) or may
be software connected to the outputs of other integrated functions (that is close
command from a control function or a general trip from integrated protections).
IEC06000275-2-en.vsd
IEC06000275 V2 EN
353
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
354
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
SYMBOL-LL V1 EN
7.10.1 Introduction
The task of a generator in a power plant is to convert mechanical energy available
as a torque on a rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that
it does not cover bearing losses and ventilation losses. Then, the synchronous
generator becomes a synchronous motor and starts to take electric power from the
rest of the power system. This operating state, where individual synchronous
machines operate as motors, implies no risk for the machine itself. If the generator
under consideration is very large and if it consumes lots of electric power, it may
be desirable to disconnect it to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous
state. The task of the reverse power protection is to protect the turbine and not to
protect the generator itself.
Figure 194 illustrates the reverse power protection with underpower IED and with
overpower IED. The underpower IED gives a higher margin and should provide
better dependability. On the other hand, the risk for unwanted operation
immediately after synchronization may be higher. One should set the underpower
IED to trip if the active power from the generator is less than about 2%. One
should set the overpower IED to trip if the power flow from the network to the
generator is higher than 1% depending on the type of turbine.
355
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
Operate
Q Q
Operate
Line Line
Margin Margin
P P
IEC06000315-2-en.vsd
IEC06000315 V2 EN
Chosen current
phasors P
P = POWRE
Q = POWIM
IEC09000018-2-en.vsd
IEC09000018 V2 EN
The function will use voltage and current phasors calculated in the pre-processing
blocks. The apparent complex power is calculated according to chosen formula as
shown in table 207.
356
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
The active and reactive power is available from the function and can be used for
monitoring and fault recording.
357
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
low, normally down to 0.02 p.u. of rated generator power. The hysteresis should
therefore be set to a smaller value. The drop-power value of stage1 can be
calculated with the Power1(2), Hysteresis1(2): drop-power1(2) = Power1(2) +
Hysteresis1(2)
For small power1 values the hysteresis1 may not be too big, because the drop-
power1(2) would be too small. In such cases, the hysteresis1 greater than (0.5 ·
Power1(2)) is corrected to the minimal value.
If the measured power drops under the drop-power1(2) value, the function will
reset after a set time DropDelay1(2). The reset means that the start signal will drop
out and that the timer of the stage will reset.
S = k × SOld + (1 - k ) × SCalculated
EQUATION1959 V1 EN (Equation 84)
Where
S is a new measured value to be used for the protection function
Sold is the measured value given from the function in previous execution cycle
Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. A typical value for
k=0.92 in case of slow operating functions.
Measured currents and voltages used in the Power function can be calibrated to get
class 0.5 measuring accuracy. This is achieved by amplitude and angle
compensation at 5, 30 and 100% of rated current and voltage. The compensation
below 5% and above 100% is constant and linear in between, see example in figure
196.
358
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
IEC05000652 V2 EN
The first current and voltage phase in the group signals will be used as reference
and the amplitude and angle compensation will be used for related input signals.
Analog outputs (Monitored data) from the function can be used for service values
or in the disturbance report. The active power is provided as MW value: P, or in
percent of base power: PPERCENT. The reactive power is provided as Mvar value:
Q, or in percent of base power: QPERCENT.
IEC07000027-2-en.vsd
IEC07000027 V2 EN
359
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
360
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
361
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
DOCUMENT172362-IMG158942
V1 EN
7.11.1 Introduction
The task of a generator in a power plant is to convert mechanical energy available
as a torque on a rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that
it does not cover bearing losses and ventilation losses. Then, the synchronous
generator becomes a synchronous motor and starts to take electric power from the
rest of the power system. This operating state, where individual synchronous
machines operate as motors, implies no risk for the machine itself. If the generator
under consideration is very large and if it consumes lots of electric power, it may
be desirable to disconnect it to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous
state. The task of the reverse power protection is to protect the turbine and not to
protect the generator itself.
Figure 198 illustrates the reverse power protection with underpower IED and with
overpower IED. The underpower IED gives a higher margin and should provide
better dependability. On the other hand, the risk for unwanted operation
immediately after synchronization may be higher. One should set the underpower
IED to trip if the active power from the generator is less than about 2%. One
should set the overpower IED to trip if the power flow from the network to the
generator is higher than 1%.
362
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
Operate
Q Q
Operate
Line Line
Margin Margin
P P
IEC06000315-2-en.vsd
IEC06000315 V2 EN
Figure 198: Reverse power protection with underpower IED and overpower IED
Chosen current
phasors P
P = POWRE
Q = POWIM
IEC06000567-2-en.vsd
IEC06000567 V2 EN
The function will use voltage and current phasors calculated in the pre-processing
blocks. The apparent complex power is calculated according to chosen formula as
shown in table 214.
363
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
The active and reactive power is available from the function and can be used for
monitoring and fault recording.
364
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
For small power1 values the hysteresis1 may not be too big, because the drop-
power1(2) would be too small. In such cases, the hysteresis1 greater than (0.5 ·
Power1(2)) is corrected to the minimal value.
If the measured power drops under the drop-power1(2) value the function will reset
after a set time DropDelay1(2). The reset means that the start signal will drop out
ant that the timer of the stage will reset.
S = k × SOld + (1 - k ) × SCalculated
EQUATION1959 V1 EN (Equation 94)
Where
S is a new measured value to be used for the protection function
Sold is the measured value given from the function in previous execution cycle
k is settable parameter by the end user which influence the filter properties
Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. A typical value for k =
0.14.
Measured currents and voltages used in the Power function can be calibrated to get
class 0.5 measuring accuracy. This is achieved by amplitude and angle
compensation at 5, 30 and 100% of rated current and voltage. The compensation
below 5% and above 100% is constant and linear in between, see example in figure
200.
365
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
IEC05000652 V2 EN
The first current and voltage phase in the group signals will be used as reference
and the amplitude and angle compensation will be used for related input signals.
Analog outputs from the function can be used for service values or in the
disturbance report. The active power is provided as MW value: P, or in percent of
base power: PPERCENT. The reactive power is provided as Mvar value: Q, or in
percent of base power: QPERCENT.
IEC07000028-2-en.vsd
IEC07000028 V2 EN
366
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
367
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
368
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
7.12.1 Introduction
Conventional protection functions can not detect the broken conductor condition.
Broken conductor check (BRCPTOC) function, consisting of continuous current
unsymmetrical check on the line where the IED is connected will give alarm or trip
at detecting broken conductors.
• The difference in currents between the phase with the lowest current and the
phase with the highest current is greater than set percentage Iub> of the
highest phase current
• The highest phase current is greater than the minimum setting value IP>.
• The lowest phase current is below 50% of the minimum setting value IP>
369
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection
The simplified logic diagram of the broken conductor check function is shown in
figure 202
• The IED is in TEST status and the function has been blocked from the local
HMI test menu (BlockBRC=Yes).
• The input signal BLOCK is high.
The BLOCK input can be connected to a binary input of the IED in order to receive
a block command from external devices, or can be software connected to other
internal functions of the IED itself to receive a block command from internal
functions.
The output trip signal TRIP is a three-phase trip. It can be used to command a trip
to the circuit breaker or for alarm purpose only.
TEST
TEST-ACTIVE
&
Block BRCPTOC=Yes
START
Function Enable
BLOCK =1
t
TRIP
& t
Unsymmetrical
Current Detection
STI
IL1<50%IP>
IL2<50%IP> =1
IL3<50%IP>
IEC09000158-1-en.vsd
IEC09000158 V1 EN
Figure 202: Simplified logic diagram for Broken conductor check BRCPTOC
IEC07000034-2-en.vsd
IEC07000034 V2 EN
370
Technical reference manual
1MRK505183-UEN C Section 7
Current protection
371
Technical reference manual
372
1MRK505183-UEN C Section 8
Voltage protection
3U<
SYMBOL-R V1 EN
8.1.1 Introduction
Undervoltages can occur in the power system during faults or abnormal conditions.
Two step undervoltage protection (UV2PTUV) function can be used to open circuit
breakers to prepare for system restoration at power outages or as long-time delayed
back-up to primary protection.
UV2PTUV has two voltage steps, each with inverse or definite time delay.
373
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
To avoid oscillations of the output START signal, a hysteresis has been included.
The time delay for the two steps can be either definite time delay (DT) or inverse
time delay (IDMT). For the inverse time delay three different modes are available:
• inverse curve A
• inverse curve B
• customer programmable inverse curve
k
t=
æ U < -U ö
ç ÷
è U< ø
EQUATION1431 V1 EN (Equation 97)
374
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
k × 480
t= 2.0
+ 0.055
æ U < -U ö
ç 32 × - 0.5 ÷
è U< ø
EQUATION1432 V1 EN (Equation 98)
é ù
ê ú
k×A
t=ê ú+D
êæ U < -U ö ú
p
êç B × -C÷ ú
ëè U< ø û
EQUATION1433 V1 EN (Equation 99)
When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore a tuning parameter
CrvSatn is set to compensate for this phenomenon. In the voltage interval U<
down to U< · (1.0 – CrvSatn/100) the used voltage will be: U< · (1.0 – CrvSatn/
100). If the programmable curve is used this parameter must be calculated so that:
CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN (Equation 100)
The lowest voltage is always used for the inverse time delay integration. The
details of the different inverse time characteristics are shown in section 22.3
"Inverse characteristics".
Trip signal issuing requires that the undervoltage condition continues for at least
the user set time delay. This time delay is set by the parameter t1 and t2 for definite
time mode (DT) and by some special voltage level dependent time curves for the
inverse time mode (IDMT). If the start condition, with respect to the measured
voltage ceases during the delay time, and is not fulfilled again within a user defined
reset time (tReset1 and tReset2 for the definite time and tIReset1 and
tIReset2pickup for the inverse time) the corresponding start output is reset. Here it
should be noted that after leaving the hysteresis area, the start condition must be
fulfilled again and it is not sufficient for the signal to only return back to the
hysteresis area. Note that for the undervoltage function the IDMT reset time is
constant and does not depend on the voltage fluctuations during the drop-off
period. However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time. See figure 204 and figure 205.
375
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
tReset1
Voltage tReset1
Measured
START Voltage
Hysteresis
TRIP
U1<
Time
START t1
TRIP
Time
Integrator Frozen Timer
t1
Time
Instantaneous
Linear Decrease
Reset IEC05000010-3-en.vsd
IEC05000010 V3 EN
Figure 204: Voltage profile not causing a reset of the start signal for step 1, and inverse time delay
376
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
tReset1
Voltage
tReset1
START
START
Hysteresis Measured Voltage
TRIP
U1<
Time
START t1
TRIP
Time Integrator
Frozen Timer
t1
Time
Instantaneous
Linear Decrease
Reset IEC05000011-en-2.vsd
IEC05000011 V2 EN
Figure 205: Voltage profile causing a reset of the start signal for step 1, and inverse time delay
When definite time delay is selected the function will operate as shown in figure
206. Detailed information about individual stage reset/operation behavior is shown
in figure 207 and figure 208 receptively. Note that by setting tResetn = 0.0s
instantaneous reset of the definite time delayed stage is ensured.
377
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
ST1
U tReset1 t1
a
b>a t t
TR1
U1<
b AND
OFF ON
Delay Delay
IEC09000785-1-en.vsd
IEC09000785 V1 EN
Un<
START
TRIP
tResetn
tn
IEC10000039-1-en.vsd
IEC10000039 V1 EN
378
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
Un<
START
TRIP
tResetn
tn
IEC10000040-1-en.vsd
IEC10000040 V1 EN
8.1.2.3 Blocking
If the measured voltage level decreases below the setting of IntBlkStVal1, either the
trip output of step 1, or both the trip and the START outputs of step 1, are blocked.
The characteristic of the blocking is set by the IntBlkSel1 parameter. This internal
blocking can also be set to Off resulting in no voltage based blocking.
Corresponding settings and functionality are valid also for step 2.
In case of disconnection of the high voltage component the measured voltage will
get very low. The event will START both the under voltage function and the
blocking function, as seen in figure 209. The delay of the blocking function must
be set less than the time delay of under voltage function.
379
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
U Disconnection
Normal voltage
U1<
U2<
tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2
Time
Block step 1
Block step 2
en05000466.vsd
IEC05000466 V1 EN
8.1.2.4 Design
380
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
Step 1
Time integrator TR1L2
MinVoltSelect t1 TRIP
or tReset1
ResetTypeCrv1 TR1L3
TR1
OR
Comparator ST2L1
UL1 < U2< Phase 1
Voltage Phase
Selector ST2L2
Comparator OpMode2 Phase 2
UL2 < U2< 1 out of 3
2 outof 3 ST2L3
Phase 3 Start
Comparator 3 out of 3
&
UL3 < U2< Trip ST2
Output OR
Step 2
Time integrator TR2L2
MinVoltSelect t2 TRIP
or tReset2
ResetTypeCrv2 TR2L3
TR2
OR
OR START
TRIP
OR
en05000012.vsd
IEC05000834 V1 EN
381
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
IEC06000276-2-en.vsd
IEC06000276 V2 EN
382
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
383
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
384
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
385
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
3U>
SYMBOL-C V1 EN
8.2.1 Introduction
Overvoltages may occur in the power system during abnormal conditions, such as,
sudden power loss, tap changer regulating failures, open line ends on long lines.
Two step overvoltage protection OV2PTOV can be used as open line end detector,
normally then combined with directional reactive over-power function or as system
voltage supervision, normally then giving alarm only or switching in reactors or
switch out capacitor banks to control the voltage.
OV2PTOV has two voltage steps, each of them with inverse or definite time delayed.
OV2PTOV has an extremely high reset ratio to allow setting close to system
service voltage.
The time delay characteristic is individually chosen for the two steps and can be
either, definite time delay or inverse time delay.
The voltage related settings are made in percent of the global set base voltage,
which is set in kV, phase-to-phase.
The setting of the analog inputs are given as primary phase-to-earth or phase-to-
phase voltage. OV2PTOV will operate if the voltage gets higher than the set
386
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
percentage of the set base voltage UBase. This means operation for phase-to-earth
voltage over:
All the three voltages are measured continuously, and compared with the set
values, U1> and U2>. The parameters OpMode1 and OpMode2 influence the
requirements to activate the START outputs. Either 1 out of 3, 2 out of 3 or 3 out of
3 measured voltages have to be higher than the corresponding set point to issue the
corresponding START signal.
To avoid oscillations of the output START signal, a hysteresis has been included.
The time delay for the two steps can be either definite time delay (DT) or inverse
time delay (IDMT). For the inverse time delay four different modes are available:
• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve
k
t=
æ U -U > ö
ç ÷
è U> ø
IEC09000051 V1 EN (Equation 103)
k × 480
t= 2.0
- 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2287 V1 EN (Equation 104)
387
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
k × 480
t= 3.0
+ 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2288 V1 EN (Equation 105)
k×A
t= p
+D
æ U -U > ö
çB× -C÷
è U> ø
EQUATION1439 V1 EN (Equation 106)
When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore, a tuning parameter
CrvSatn is set to compensate for this phenomenon. In the voltage interval U< down
to U< · (1.0 – CrvSatn/100) the used voltage will be: U< · (1.0 – CrvSatn/100). If
the programmable curve is used this parameter must be calculated so that:
CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN (Equation 107)
The highest phase (or phase-to-phase) voltage is always used for the inverse time
delay integration, see figure 212. The details of the different inverse time
characteristics are shown in section "Inverse characteristics"
388
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
Voltage
IDMT Voltage
UL1
UL2
UL3
Time
en05000016.vsd
IEC05000016 V1 EN
Figure 212: Voltage used for the inverse time characteristic integration
Trip signal issuing requires that the overvoltage condition continues for at least the
user set time delay. This time delay is set by the parameter t1 and t2 for definite
time mode (DT) and by selected voltage level dependent time curves for the
inverse time mode (IDMT). If the START condition, with respect to the measured
voltage ceases during the delay time, and is not fulfilled again within a user defined
reset time (tReset1 and tReset2 for the definite time and tIReset1 and tIReset2 for
the inverse time) the corresponding START output is reset, after that the defined
reset time has elapsed. Here it should be noted that after leaving the hysteresis area,
the START condition must be fulfilled again and it is not sufficient for the signal to
only return back to the hysteresis area. The hysteresis value for each step is settable
(HystAbs2) to allow an high and accurate reset of the function. It should be noted
that for Two step overvoltage protection OV2PTOV the IDMT reset time is
constant and does not depend on the voltage fluctuations during the drop-off
period. However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time..
389
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
tReset
1
tReset1
Voltage
START
TRIP
U1>
Hysteresis
Measured
Voltage
Time
START t1
TRIP
Time
Integrator Linear Decrease
Frozen Timer
t1
Instantaneous Time
Reset IEC09000055-en-1.vsd
IEC09000055 V1 EN
Figure 213: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay
390
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
tReset1
Voltage tReset1
START TRIP
START
Hysteresis
U1>
Measured Voltage
Time
START t1
TRIP
Time Integrator
Frozen Timer
t1
Time
Instantaneous IEC05000020-en-2.vsd
Linear Decrease
Reset
IEC05000020 V2 EN
Figure 214: Voltage profile causing a reset of the START signal for step 1, and inverse time delay
When definite time delay is selected the function will operate as shown in figure
215. Detailed information about individual stage reset/operation behavior is shown
in figure 207 and figure 208 receptively. Note that by setting tResetn = 0.0s
instantaneous reset of the definite time delayed stage is ensured
391
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
ST1
U tReset1 t1
a
b<a t t
TR1
U1>
b AND
OFF ON
Delay Delay
IEC10000100-1-en.vsd
IEC10000100 V1 EN
Un>
START
TRIP
tResetn
tn
IEC10000037-1-en.vsd
IEC10000037 V1 EN
392
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
Un>
START
TRIP
tResetn
tn
IEC10000038-1-en.vsd
IEC10000038 V1 EN
8.2.2.3 Blocking
8.2.2.4 Design
393
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
OR TR1
Comparator ST2L1
UL1 > U2> Phase 1
Voltage Phase
Selector ST2L2
Comparator OpMode2 Phase 2
UL2 > U2> 1 out of 3
2 outof 3 ST2L3
Phase 3 Start
3 out of 3
Comparator &
UL3 > U2> Trip ST2
OR
Output
START Logic TR2L1
Step 2
Time integrator TR2L2
MaxVoltSelect t2 TRIP
or tReset2
ResetTypeCrv2 TR2L3
TR2
OR
START
OR
TRIP
OR
en05000013.vsd
IEC05000013-WMF V1 EN
394
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
IEC06000277-2-en.vsd
IEC06000277 V2 EN
395
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
396
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
397
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
8.3.1 Introduction
Residual voltages may occur in the power system during earth faults.
398
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
ROV2PTOV has two voltage steps, each with inverse or definite time delayed.
The time delay characteristic is individually chosen for the two steps and can be
either, definite time delay or inverse time delay.
The voltage related settings are made in percent of the base voltage, which is set in
kV, phase-phase.
The residual voltage is measured continuously, and compared with the set values,
U1> and U2>.
To avoid oscillations of the output START signal, a hysteresis has been included.
The time delay for the two steps can be either definite time delay (DT) or inverse
time delay (IDMT). For the inverse time delay four different modes are available:
• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve
k
t=
æ U -U > ö
ç ÷
è U> ø
IEC09000051 V1 EN (Equation 108)
399
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
k × 480
t= 2.0
- 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2287 V1 EN (Equation 109)
k × 480
t= 3.0
+ 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2288 V1 EN (Equation 110)
k×A
t= p
+D
æ U -U > ö
çB× -C÷
è U> ø
EQUATION1439 V1 EN (Equation 111)
When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore a tuning parameter
CrvSatn is set to compensate for this phenomenon. In the voltage interval U> up to
U> · (1.0 + CrvSatn/100) the used voltage will be: U> · (1.0 + CrvSatn/100). If the
programmable curve is used this parameter must be calculated so that:
CrvSatn
B× -C > 0
100
EQUATION1440 V1 EN (Equation 112)
The details of the different inverse time characteristics are shown in section
"Inverse characteristics".
TRIP signal issuing requires that the residual overvoltage condition continues for at
least the user set time delay. This time delay is set by the parameter t1 and t2 for
definite time mode (DT) and by some special voltage level dependent time curves
for the inverse time mode (IDMT).
If the START condition, with respect to the measured voltage ceases during the
delay time, and is not fulfilled again within a user defined reset time (tReset1 and
tReset2 for the definite time and tIReset1 and tIReset2 for the inverse time) the
corresponding START output is reset, after that the defined reset time has elapsed.
Here it should be noted that after leaving the hysteresis area, the START condition
must be fulfilled again and it is not sufficient for the signal to only return back to
400
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
the hysteresis area. Also notice that for the overvoltage function IDMT reset time is
constant and does not depend on the voltage fluctuations during the drop-off
period. However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time. See figure 213 and figure 214.
tReset
1
tReset1
Voltage
START
TRIP
U1>
Hysteresis
Measured
Voltage
Time
START t1
TRIP
Time
Integrator Linear Decrease
Frozen Timer
t1
Instantaneous Time
Reset IEC09000055-en-1.vsd
IEC09000055 V1 EN
Figure 220: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay
401
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
tReset1
Voltage tReset1
START TRIP
START
Hysteresis
U1>
Measured Voltage
Time
START t1
TRIP
Time Integrator
Frozen Timer
t1
Time
Instantaneous IEC05000020-en-2.vsd
Linear Decrease
Reset
IEC05000020 V2 EN
Figure 221: Voltage profile causing a reset of the START signal for step 1, and inverse time delay
When definite time delay is selected the function will operate as shown in figure
222. Detailed information about individual stage reset/operation behavior is shown
in figure 207 and figure 208 receptively. Note that by setting tResetn = 0.0s
instantaneous reset of the definite time delayed stage is ensured
402
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
ST1
U tReset1 t1
a
b<a t t
TR1
U1>
b AND
OFF ON
Delay Delay
IEC10000100-1-en.vsd
IEC10000100 V1 EN
Un<
START
TRIP
tResetn
tn
IEC10000039-1-en.vsd
IEC10000039 V1 EN
403
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
Un<
START
TRIP
tResetn
tn
IEC10000040-1-en.vsd
IEC10000040 V1 EN
8.3.2.3 Blocking
8.3.2.4 Design
404
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
ST2
Comparator Phase 1
UN > U2> TR2
Start
START &
Trip START
Output OR
Time integrator
Logic
t2 TRIP
tReset2
Step 2
ResetTypeCrv2 TRIP
OR
en05000748.vsd
IEC05000748 V1 EN
IEC06000278-2-en.vsd
IEC06000278 V2 EN
405
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
406
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
407
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
U/f >
SYMBOL-Q V1 EN
8.4.1 Introduction
When the laminated core of a power transformer or generator is subjected to a
magnetic flux density beyond its design limits, stray flux will flow into non-
laminated components not designed to carry flux and cause eddy currents to flow.
408
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
The eddy currents can cause excessive heating and severe damage to insulation and
adjacent parts in a relatively short time. Overexcitation protection OEXPVPH has
settable inverse operating curve and independent alarm stage.
Modern design transformers are more sensitive to overexcitation than earlier types.
This is a result of the more efficient designs and designs which rely on the
improvement in the uniformity of the excitation level of modern systems. Thus, if
emergency that includes overexcitation does occur, transformers may be damaged
unless corrective action is promptly taken. Transformer manufacturers recommend
an overexcitation protection as a part of the transformer protection system.
E = 4.44 × f × n × Bmax× A
EQUATION898 V2 EN (Equation 113)
E f
M ( p.u.) =
( Ur ) ( fr )
IECEQUATION2296 V1 EN (Equation 114)
409
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
The IEC 60076 - 1 standard requires that transformers shall be capable of operating
continuously at 10% above rated voltage at no load, and rated frequency. At no
load, the ratio of the actual generator terminal voltage to the actual frequency
should not exceed 1.1 times the ratio of transformer rated voltage to the rated
frequency on a sustained basis, see equation 115.
---- £ 1.1 × Ur
E ------
f fr
EQUATION900 V1 EN (Equation 115)
E V Hz>
£
f fr
IECEQUATION2297 V1 EN (Equation 116)
where:
V/Hz> is the maximum continuously allowed voltage at no load, and rated frequency.
V/Hz> is a setting parameter. The setting range is 100% to 180%. If the user does
not know exactly what to set, then the standard IEC 60076 - 1, section 4.4, the
default value V/Hz> = 110% shall be used.
E f
M ( p.u. ) =
Ur fr
IECEQUATION2299 V1 EN (Equation 117)
It is clear from the above formula that, for an unloaded power transformer, M = 1
for any E and f, where the ratio E/f is equal to Ur/fr. A power transformer is not
overexcited as long as the relative excitation is M ≤ V/Hz>, V/Hz> expressed in %
of Ur/fr.
410
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
As an example, at a transformer with a 15% short circuit impedance Xsc, the full
load, 0.8 power factor, 105% voltage on the load side, the actual flux level in the
transformer core, will not be significantly different from that at the 110% voltage,
no load, rated frequency, provided that the short circuit impedance X can be
equally divided between the primary and the secondary winding: Xleak = Xleak1 =
Xleak2 = Xsc / 2 = 0.075 pu.
OEXPVPH calculates the internal induced voltage E if Xleak (meaning the leakage
reactance of the winding where OEXPVPH is connected) is known to the user. The
assumption taken for two-winding power transformers that Xleak = Xsc / 2 is
unfortunately most often not true. For a two-winding power transformer the
leakage reactances of the two windings depend on how the windings are located on
the core with respect to each other. In the case of three-winding power transformers
the situation is still more complex. If a user has the knowledge on the leakage
reactance, then it should applied. If a user has no idea about it, Xleak can be set to
Xc/2. OEXPVPH protection will then take the given measured voltage U, as the
induced voltage E.
If, for example, voltage UL1L2 is fed to OEXPVPH, then currents IL1, and IL2
must be applied. From these two input currents, current IL1L2 = IL1 - IL2 is
411
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
If three phase-to-earth voltages are available from the side where overexcitation is
connected, then OEXPVPH shall be set to measure positive sequence voltage and
current. In this case the positive sequence voltage and the positive sequence current
are used by OEXPVPH. A check is made if the positive sequence voltage is higher
than 70% of rated phase-to-earth voltage, when below this value, OEXPVPH exits
immediately, and no excitation is calculated. ERROR output is set to 1, and the
displayed value of relative excitation V/Hz shows 0.000.
The frequency value is received from the pre-processing block. The function is in
operation for frequencies within the range of 33-60 Hz and of 42-75 Hz for 50 and
60 Hz respectively.
Basically there are two different delay laws available to choose between:
The so called IEEE law approximates a square law and has been chosen based on
analysis of the various transformers’ overexcitation capability characteristics. They
can match well a transformer core capability.
0.18 × k
top = 2
æ M ö
ç V Hz> - 1 ÷
è ø
IECEQUATION2298 V1 EN (Equation 118)
where:
M the relative excitation
V/Hz> is maximum continuously allowed voltage at no load, and rated frequency, in pu and
k is time multiplier for inverse time functions, see figure 228.
Parameter k (“time multiplier setting”) selects one delay curve from the family of curves.
412
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
top
A digital, numerical relay will instead look for the lowest j (that is, j = n) where it
becomes true that:
n
2
Dt × å ( M(j) – V/Hz> ) ³ 0.18 × k
j=k
EQUATION906 V1 EN (Equation 120)
where:
Dt is the time interval between two successive executions of OEXPVPH and
M(j) - V/Hz> is the relative excitation at (time j) in excess of the normal (rated) excitation which is
given as Ur/fr.
As long as M > V/Hz> (that is, overexcitation condition), the above sum can only
be larger with time, and if the overexcitation persists, the protected transformer will
be tripped at j = n.
Inverse delays as per figure 228, can be modified (limited) by two special definite
delay settings, namely tMax and tMin, see figure 227.
delay in s
tMax
overexcitation
tMin
0 Mmax - V/Hz> Overexcitation M-V/Hz>
99001067.vsd
IEC99001067 V1 EN
413
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
A definite maximum time, tMax, can be used to limit the operate time at low
degrees of overexcitation. Inverse delays longer than tMax will not be allowed. In
case the inverse delay is longer than tMax, OEXPVPH trips after tMax seconds.
A definite minimum time, tMin, can be used to limit the operate time at high
degrees of overexcitation. In case the inverse delay is shorter than tMin,
OEXPVPH function trips after tMin seconds. Also, the inverse delay law is no
more valid beyond excitation Mmax. Beyond Mmax (for excitation M > V/Hz>),
the delay will always be tMin, irrespective of the overexcitation level.
1000
100
k = 60
k = 20
k = 10
10 k=9
k=8
k=7
k=6
k=5
k=4
k=3
k=2
k=1
1
1 2 3 4 5 10 20 30 40
OVEREXCITATION IN % (M-Emaxcont)*100)
en01000373.vsd
IEC01000373 V1 EN
414
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
(V Hz>> ) / f
M= = 1.40
Ur/fr
IECEQUATION2286 V1 EN (Equation 121)
delay in s
tMax
under- tMin
excitation Overexcitation M-Emaxcont
0 Mmax - Emaxcont Excitation M
Emaxcont Mmax
99001068.vsd
IEC99001068 V1 EN
Delays between two consecutive points, for example t3 and t4, are obtained by
linear interpolation.
Should it happen that tMax be lower than, for example, delays t1, and t2, the actual
delay would be tMax. Above Mmax, the delay can only be tMin.
8.4.2.3 Cooling
415
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
If the overexcitation is so low that the valid delay is tMax, then the estimation of
the remaining time to trip is done against tMax.
The relative excitation M, shown on the local HMI and in PCM600 as a monitored
data value VPERHZ, is calculated from the expression:
E f
M ( p.u. ) =
Ur fr
IECEQUATION2299 V1 EN (Equation 122)
If VPERHZ value is less than setting V/Hz> (in %), the power transformer is
underexcited. If VPERHZ is equal to V/Hz> (in %), the excitation is exactly equal
to the power transformer continuous capability. If VPERHZ is higher than V/Hz>,
the protected power transformer is overexcited. For example, if VPERHZ = 1.100,
while V/Hz> = 110 %, then the power transformer is exactly on its maximum
continuous excitation limit.
Monitored data value THERMSTA shows the thermal status of the protected
power transformer iron core. THERMSTA gives the thermal status in % of the trip
value which corresponds to 100%. THERMSTA should reach 100% at the same
time, as TMTOTRIP reaches 0 seconds. If the protected power transformer is then
for some reason not switched off, THERMSTA shall go over 100%.
If the delay as per IEEE law, or Tailor-made Law, is limited by tMax, and/or tMin,
then the Thermal status will generally not reach 100% at the same time, when
tTRIP reaches 0 seconds. For example, if, at low degrees of overexcitation, the
very long delay is limited by tMax, then the OEXPVPH TRIP output signal will be
set to 1 before the Thermal status reaches 100%.
416
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
BLOCK
AlarmLevel
ALARM
t>tAlarm &
t
tAlarm
M>V/Hz>
t>tMin TRIP
t &
V/Hz> tMin
U3P Calculation
Ei k
M
of internal M=
I3P induced (Ei / f) M IEEE law
voltage Ei (Ur / fr)
³1
M t
Tailor-made law
M>V/Hz>> tMax
Xleak
V/Hz>>
Simplification of the diagram is in the way the IEEE and Tailor-made delays are
calculated. The cooling process is not shown. It is not shown that voltage and
frequency are separately checked against their respective limit values.
IEC05000329-2-en.vsd
IEC05000329 V3 EN
417
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
418
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
(0.18 × k )
IEEE : t =
( M - 1) 2
where M = (E/f)/(Ur/fr)
Minimum time delay for inverse (0.000–60.000) s ± 0.5% ± 10 ms
function
Maximum time delay for inverse (0.00–9000.00) s ± 0.5% ± 10 ms
function
Alarm time delay (0.000–60.000) s ± 0.5% ± 10 ms
8.5.1 Introduction
A voltage differential monitoring function is available. It compares the voltages
from two three phase sets of voltage transformers and has one sensitive alarm step
and one trip step. It can be used to supervise the voltage from two fuse groups or
two different voltage transformers fuses as a fuse/MCB supervision function.
419
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
Loss of all U1or all U2 voltages will block the differential measurement. This
blocking can be switched off with setting BlkDiffAtULow = No.
VDCPTOV function can be blocked from an external condition with the binary
BLOCK input. It can for example, be activated from Fuse failure supervision
function SDDRFUF.
420
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
UDTripL1>
AND
UDTripL1>
AND
AND START
UDAlarmL1>
AND
UDAlarmL1> O tAlarm
AND
R t AND ALARM
UDAlarmL1>
AND
U1<L1
tAlarm
U1<L2 AND t U1LOW
AND
AND
U1<L3
OR
BlkDiffAtULow
U2<L1
t1
U2<L2 AND t U2LOW
AND
U2<L3
BLOCK
en06000382-1.vsd
IEC06000382 V2 EN
IEC06000528-2-en.vsd
IEC06000528 V2 EN
421
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
422
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
8.6.1 Introduction
Loss of voltage check (LOVPTUV) is suitable for use in networks with an
automatic system restoration function. LOVPTUV issues a three-pole trip
command to the circuit breaker, if all three phase voltages fall below the set value
for a time longer than the set time and the circuit breaker remains closed.
423
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
LOVPTUV operates again only if the line has been restored to full voltage for at
least tRestore. Operation of the function is also inhibited by fuse failure and open
circuit breaker information signals, by their connection to dedicated inputs of the
function block.
The BLOCK input can be connected to a binary input of the IED in order to receive
a block command from external devices or can be software connected to other
internal functions of the IED itself in order to receive a block command from
internal functions. LOVPTUV is also blocked when the IED is in TEST status and
the function has been blocked from the HMI test menu. (Blocked=Yes).
424
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection
TEST
TEST-ACTIVE
&
Blocked = Yes
START
BLOCK >1
Function Enable tTrip tPulse TRIP
STUL1N & t
STUL2N &
only 1 or 2 phases are low for
Latched at least 10 s (not three)
STUL3N Enable
&
tBlock
>1 t
IEC07000089_2_en.vsd
IEC07000089 V2 EN
IEC07000039-2-en.vsd
IEC07000039 V2 EN
425
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection
426
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection
f<
SYMBOL-P V1 EN
9.1.1 Introduction
Underfrequency occurs as a result of lack of generation in the network.
427
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection
voltage is lower than the set blocking voltage IntBlockLevel the function is blocked
and no START or TRIP signal is issued.
To avoid oscillations of the output START signal, a hysteresis has been included.
The time delay for underfrequency protection SAPTUF can be either a settable
definite time delay or a voltage magnitude dependent time delay, where the time
delay depends on the voltage level; a high voltage level gives a longer time delay
and a low voltage level causes a short time delay. For the definite time delay, the
setting TimeDlyOperate sets the time delay.
For the voltage dependent time delay the measured voltage level and the settings
UNom, UMin, Exponent, tMax and tMin set the time delay according to figure 236
and equation 124. The setting TimerOperation is used to decide what type of time
delay to apply.
Trip signal issuing requires that the underfrequency condition continues for at least
the user set time delay TimeDlyOperate. If the START condition, with respect to
the measured frequency ceases during this user set delay time, and is not fulfilled
again within a user defined reset time, TimeDlyReset, the START output is reset,
after that the defined reset time has elapsed. Here it should be noted that after
leaving the hysteresis area, the START condition must be fulfilled again and it is
not sufficient for the signal to only return back to the hysteresis area.
Since the fundamental frequency in a power system is the same all over the system,
except some deviations during power oscillations, another criterion is needed to
decide, where to take actions, based on low frequency. In many applications the
voltage level is very suitable, and in most cases is load shedding preferable in areas
with low voltage. Therefore, a voltage dependent time delay has been introduced,
to make sure that load shedding, or other actions, take place at the right location. At
constant voltage, U, the voltage dependent time delay is calculated according to
equation 124. At non-constant voltage, the actual time delay is integrated in a
428
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection
similar way as for the inverse time characteristic for the undervoltage and
overvoltage functions.
Exponent
é U - UMin ù
t=ê × ( tMax - tMin ) + tMin
ë UNom - UMin úû
EQUATION1182 V1 EN (Equation 124)
where:
t is the voltage dependent time delay (at constant voltage),
U is the measured voltage
Exponent is a setting,
UMin, UNom are voltage settings corresponding to
tMax, tMin are time settings.
UMin = 90%
UNom = 100%
tMax = 1.0 s
tMin = 0.0 s
Exponent = 0, 1, 2, 3 and 4
1
0
1
Exponenent
TimeDlyOperate [s]
2
3
0.5 4
0
90 95 100
U [% of UBase]
en05000075.vsd
IEC05000075 V1 EN
429
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection
9.1.2.4 Blocking
If the measured voltage level decreases below the setting of IntBlockLevel, both the
START and the TRIP outputs, are blocked.
9.1.2.5 Design
Block
BLOCK BLKDMAGN
OR
Comparator
U < IntBlockLevel
TimeDlyReset TRIP
100 ms
Comparator RESTORE
TimeDlyRestore
f > RestoreFreq
en05000726.vsd
IEC05000726 V1 EN
430
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection
IEC06000279_2_en.vsd
IEC06000279 V2 EN
431
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection
f>
SYMBOL-O V1 EN
432
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection
9.2.1 Introduction
Overfrequency protection function SAPTOF is applicable in all situations, where
reliable detection of high fundamental power system frequency is needed.
Overfrequency occurs at sudden load drops or shunt faults in the power network.
Close to the generating plant, generator governor problems can also cause over
frequency.
SAPTOF is used mainly for generation shedding and remedial action schemes. It is
also used as a frequency stage initiating load restoring.
The time delay for Overfrequency protection SAPTOF (81) is a settable definite
time delay, specified by the setting TimeDlyOperate.
TRIP signal issuing requires that the overfrequency condition continues for at least
the user set time delay, TimeDlyReset. If the START condition, with respect to the
measured frequency ceases during this user set delay time, and is not fulfilled again
within a user defined reset time, TimeDlyReset, the START output is reset, after
that the defined reset time has elapsed. It is to be noted that after leaving the
hysteresis area, the START condition must be fulfilled again and it is not sufficient
for the signal to only return back to the hysteresis area.
433
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection
9.2.2.3 Blocking
If the measured voltage level decreases below the setting of IntBlockLevel, both the
START and the TRIP outputs, are blocked.
9.2.2.4 Design
BLOCK
BLKTRIP BLOCK
OR BLKDMAGN
Comparator
U < IntBlockLevel
Start
&
Trip
Voltage Time integrator Output
Logic
Definite Time Delay START START
Frequency Comparator
f > StartFrequency TimeDlyOperate
TRIP
TimeDlyReset
TRIP
en05000735.vsd
IEC05000735 V1 EN
434
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection
IEC06000280_2_en.vsd
IEC06000280 V2 EN
435
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection
df/dt >
<
SYMBOL-N V1 EN
9.3.1 Introduction
Rate-of-change frequency protection function (SAPFRC) gives an early indication
of a main disturbance in the system. SAPFRC can be used for generation shedding,
load shedding, remedial action schemes. SAPFRC can discriminate between
positive or negative change of frequency.
436
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection
To avoid oscillations of the output START signal, a hysteresis has been included.
The RESTORE output of SAPFRC is set, after a time delay equal to the setting of
tRestore, when the measured frequency has returned to the level corresponding to
RestoreFreq, after an issue of the TRIP output signal. If tRestore is set to 0.000 s
the restore functionality is disabled, and no output will be given. The restore
functionality is only active for lowering frequency conditions and the restore
sequence is disabled if a new negative frequency gradient is detected during the
restore period, defined by the settings RestoreFreq and tRestore.
9.3.2.3 Blocking
437
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection
If the measured voltage level decreases below the setting of IntBlockLevel, both the
START and the TRIP outputs, are blocked.
9.3.2.4 Design
BLOCK
BLKTRIP
BLKRESET BLOCK
OR
Start
Rate-of-Change Time integrator &
Comparator
of Frequency Trip
If
Definite Time Delay Output
[StartFreqGrad<0 START START
Logic
AND
TimeDlyOperate
df/dt < StartFreqGrad]
OR
TimeDlyReset
[StartFreqGrad>0
AND
TRIP
df/dt > StartFreqGrad]
Then
START
100 ms
en05000835.vsd
IEC05000835 V1 EN
438
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection
IEC06000281-2-en.vsd
IEC06000281 V2 EN
439
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection
440
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection
10.1.1 Introduction
The General current and voltage protection (CVGAPC) can be utilized as a
negative sequence current protection detecting unsymmetrical conditions such as
open phase or unsymmetrical faults.
CVGAPC can also be used to improve phase selection for high resistive earth
faults, outside the distance protection reach, for the transmission line. Three
functions are used, which measures the neutral current and each of the three phase
voltages. This will give an independence from load currents and this phase
selection will be used in conjunction with the detection of the earth fault from the
directional earth fault protection function.
The user can select to measure one of the current quantities shown in table 271.
441
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection
11 Phase2-Phase3 CVGAPC function will measure the current phasor internally calculated
as the vector difference between the phase L2 current phasor and
phase L3 current phasor (IL2-IL3)
12 Phase3-Phase1 CVGAPC function will measure the current phasor internally calculated
as the vector difference between the phase L3 current phasor and
phase L1 current phasor ( IL3-IL1)
13 MaxPh-Ph CVGAPC function will measure ph-ph current phasor with the
maximum magnitude
14 MinPh-Ph CVGAPC function will measure ph-ph current phasor with the
minimum magnitude
15 UnbalancePh-Ph CVGAPC function will measure magnitude of unbalance current, which
is internally calculated as the algebraic magnitude difference between
the ph-ph current phasor with maximum magnitude and ph-ph current
phasor with minimum magnitude. Phase angle will be set to 0° all the
time
The user can select to measure one of the voltage quantities shown in table 272:
442
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection
13 MaxPh-Ph CVGAPC function will measure ph-ph voltage phasor with the
maximum magnitude
14 MinPh-Ph CVGAPC function will measure ph-ph voltage phasor with the
minimum magnitude
15 UnbalancePh-Ph CVGAPC function will measure magnitude of unbalance voltage,
which is internally calculated as the algebraic magnitude difference
between the ph-ph voltage phasor with maximum magnitude and ph-
ph voltage phasor with minimum magnitude. Phase angle will be set to
0° all the time
It is important to notice that the voltage selection from table 272 is always
applicable regardless the actual external VT connections. The three-phase VT
inputs can be connected to IED as either three phase-to-ground voltages UL1, UL2
& UL3 or three phase-to-phase voltages UL1L2, UL2L3 & UL3L1). This information
about actual VT connection is entered as a setting parameter for the pre-processing
block, which will then take automatic care about it.
The user can select one of the current quantities shown in table 273 for built-in
current restraint feature:
443
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection
The parameter settings for the base quantities, which represent the base (100%) for
pickup levels of all measuring stages, shall be entered as setting parameters for
every CVGAPC function.
1. rated phase current of the protected object in primary amperes, when the
measured Current Quantity is selected from 1 to 9, as shown in table 271.
2. rated phase current of the protected object in primary amperes multiplied by
√3 (1.732 · Iphase), when the measured Current Quantity is selected from 10
to 15, as shown in table 271.
1. rated phase-to-earth voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 1 to 9, as shown in table 272.
2. rated phase-to-phase voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 10 to 15, as shown in table 272.
Two overcurrent protection steps are available. They are absolutely identical and
therefore only one will be explained here.
Overcurrent step simply compares the magnitude of the measured current quantity
(see table 271) with the set pickup level. Non-directional overcurrent step will
pickup if the magnitude of the measured current quantity is bigger than this set
level. Reset ratio is settable, with default value of 0.96. However depending on
other enabled built-in features this overcurrent pickup might not cause the
overcurrent step start signal. Start signal will only come if all of the enabled built-
in features in the overcurrent step are fulfilled at the same time.
444
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection
This feature will simple prevent overcurrent step start if the second-to-first
harmonic ratio in the measured current exceeds the set level.
Directional feature
The overcurrent protection step operation can be can be made dependent on the
relevant phase angle between measured current phasor (see table 271) and
measured voltage phasor (see table 272). In protection terminology it means that
the General currrent and voltage protection (CVGAPC) function can be made
directional by enabling this built-in feature. In that case overcurrent protection step
will only operate if the current flow is in accordance with the set direction
(Forward, which means towards the protected object, or Reverse, which means
from the protected object). For this feature it is of the outmost importance to
understand that the measured voltage phasor (see table 272) and measured current
phasor (see table 271) will be used for directional decision. Therefore it is the sole
responsibility of the end user to select the appropriate current and voltage signals in
order to get a proper directional decision. CVGAPC function will NOT do this
automatically. It will just simply use the current and voltage phasors selected by
the end user to check for the directional criteria.
Table 274 gives an overview of the typical choices (but not the only possible ones)
for these two quantities for traditional directional relays.
Table 274: Typical current and voltage choices for directional feature
Set value for the Set value for the
parameter parameter Comment
CurrentInput VoltageInput
PosSeq PosSeq Directional positive sequence overcurrent function is
obtained. Typical setting for RCADir is from -45° to
-90° depending on the power
NegSeq -NegSeq Directional negative sequence overcurrent function is
obtained. Typical setting for RCADir is from -45° to
-90° depending on the power system voltage level (X/
R ratio)
3ZeroSeq -3ZeroSeq Directional zero sequence overcurrent function is
obtained. Typical setting for RCADir is from 0° to
-90° depending on the power system earthing (that
is, solidly earthed, earthed via resistor)
Table continues on next page
445
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection
Unbalance current or voltage measurement shall not be used when the directional
feature is enabled.
• the magnitude of the measured current is bigger than the set pick-up level
• the phasor of the measured current is within the operating region (defined by
the relay operate angle, ROADir parameter setting; see figure 243).
U=-3U0
RCADir
Operate region
mta line
en05000252.vsd
IEC05000252 V1 EN
where:
RCADir is -75°
ROADir is 50°
446
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection
• that the product I·cos(Φ) is bigger than the set pick-up level, where Φ is angle
between the current phasor and the mta line
• that the phasor of the measured current is within the operating region (defined
by the I·cos(Φ) straight line and the relay operate angle, ROADir parameter
setting; see figure 243).
U=-3U0
RCADir
Operate region
mta line
en05000253.vsd
IEC05000253 V1 EN
where:
RCADir is -75°
ROADir is 50°
Note that it is possible to decide by a parameter setting how the directional feature
shall behave when the magnitude of the measured voltage phasor falls below the pre-
set value. User can select one of the following three options:
It shall also be noted that the memory duration is limited in the algorithm to 100
ms. After that time the current direction will be locked to the one determined
during memory time and it will re-set only if the current fails below set pickup
level or voltage goes above set voltage memory limit.
447
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection
StartCurr_OC1
VDepFact_OC1 * StartCurr_OC1
ULowLimit_OC1 UHighLimit_OC1
Selected Voltage
Magnitude
en05000324.vsd
IEC05000324 V1 EN
Figure 245: Example for OC1 step current pickup level variation as function of
measured voltage magnitude in Slope mode of operation
StartCurr_OC1
VDepFact_OC1 * StartCurr_OC1
en05000323.vsd
IEC05000323 V1 EN
Figure 246: Example for OC1 step current pickup level variation as function of
measured voltage magnitude in Step mode of operation
This feature will simply change the set overcurrent pickup level in accordance with
magnitude variations of the measured voltage. It shall be noted that this feature will
as well affect the pickup current value for calculation of operate times for IDMT
448
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection
curves (overcurrent with IDMT curve will operate faster during low voltage
conditions).
IMeasured
ea ain
ar tr
te es
ra ff *Ir
pe e
O Co
es tr
I>R
IsetHigh
IsetLow
atan(RestrCoeff)
Restraint
en05000255.vsd
IEC05000255 V1 EN
This feature will simply prevent overcurrent step to start if the magnitude of the
measured current quantity is smaller than the set percentage of the restrain current
magnitude. However this feature will not affect the pickup current value for
calculation of operate times for IDMT curves. This means that the IDMT curve
operate time will not be influenced by the restrain current magnitude.
When set, the start signal will start definite time delay or inverse (IDMT) time
delay in accordance with the end user setting. If the start signal has value one for
longer time than the set time delay, the overcurrent step will set its trip signal to
one. Reset of the start and trip signal can be instantaneous or time delay in
accordance with the end user setting.
Two undercurrent protection steps are available. They are absolutely identical and
therefore only one will be explained here. Undercurrent step simply compares the
magnitude of the measured current quantity (see table 271) with the set pickup
level. The undercurrent step will pickup and set its start signal to one if the
magnitude of the measured current quantity is smaller than this set level. The start
signal will start definite time delay with set time delay. If the start signal has value
one for longer time than the set time delay the undercurrent step will set its trip
449
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection
signal to one. Reset of the start and trip signal can be instantaneous or time delay in
accordance with the setting.
Two overvoltage protection steps are available. They are absolutely identical and
therefore only one will be explained here.
Overvoltage step simply compares the magnitude of the measured voltage quantity
(see table 272) with the set pickup level. The overvoltage step will pickup if the
magnitude of the measured voltage quantity is bigger than this set level. Reset ratio
is settable, with default value of 0.99.
The start signal will start definite time delay or inverse (IDMT) time delay in
accordance with the end user setting. If the start signal has value one for longer
time than the set time delay, the overvoltage step will set its trip signal to one.
Reset of the start and trip signal can be instantaneous or time delay in accordance
with the end user setting.
Two undervoltage protection steps are available. They are absolutely identical and
therefore only one will be explained here.
The start signal will start definite time delay or inverse (IDMT) time delay in
accordance with the end user setting. If the start signal has value one for longer
time than the set time delay, the undervoltage step will set its trip signal to one.
Reset of the start and trip signal can be instantaneous or time delay in accordance
with the end user setting.
The simplified internal logics, for CVGAPC function are shown in the following
figures.
450
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection
IED
ADM CVGAPC function
Phasor calculation of
scaling with CT ratio
individual currents
A/D conversion
Selection of which current Selected current
and voltage shall be given to
Phasors &
samples
the built-in protection Selected voltage
elements
Phasors &
samples
IEC05000169_2_en.vsd
IEC05000169 V2 EN
Figure 248: Treatment of measured currents within IED for CVGAPC function
Figure 248 shows how internal treatment of measured currents is done for
multipurpose protection function
The following currents and voltages are inputs to the multipurpose protection
function. They must all be expressed in true power system (primary) Amperes and
kilovolts.
1. Selects one current from the three-phase input system (see table 271) for
internally measured current.
2. Selects one voltage from the three-phase input system (see table 272) for
internally measured voltage.
3. Selects one current from the three-phase input system (see table 273) for
internally measured restraint current.
451
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection
CURRENT
UC1
nd TRUC1
2 Harmonic
Selected current restraint
STUC2
UC2
TRUC2
2nd Harmonic
restraint
STOC1
OC1 TROC1
STOC2
OC2 TROC2
2nd Harmonic
restraint
Current restraint ³1
UDIRLOW
Directionality DIROC2
Voltage control /
restraint
STOV1
OV1 TROV1
STOV2
OV2 TROV2
STUV1
Selected voltage
UV1 TRUV1
STUV2
UV2 TRUV2
VOLTAGE
en05000170.vsd
IEC05000170 V1 EN
Figure 249: CVGAPC function main logic diagram for built-in protection elements
452
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection
1. The selected currents and voltage are given to built-in protection elements.
Each protection element and step makes independent decision about status of
its START and TRIP output signals.
2. More detailed internal logic for every protection element is given in the
following four figures
3. Common START and TRIP signals from all built-in protection elements &
steps (internal OR logic) are available from multipurpose function as well.
Enable
second
harmonic Second
harmonic check
1 DEF time BLKTROC
selected DEF 1 TROC1
AND
OR
Selected current a
a>b
b
OC1=On STOC1
AND
StartCurr_OC1 BLKOC1
X
Inverse
Selected voltage
Current
Restraint
Feature
Selected restrain current Imeasured > k Irestraint
en05000831.vsd
IEC05000831 V1 EN
Figure 250: Simplified internal logic diagram for built-in first overcurrent step that is, OC1 (step OC2 has the
same internal logic)
453
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection
Operation_UC1=On
STUC1
en05000750.vsd
IEC05000750 V1 EN
Figure 251: Simplified internal logic diagram for built-in first undercurrent step that is, UC1 (step UC2 has
the same internal logic)
Inverse
Operation_OV1=On
Inverse time
BLKOV1 selected
en05000751.vsd
IEC05000751 V1 EN
Figure 252: Simplified internal logic diagram for built-in first overvoltage step OV1 (step OV2 has the same
internal logic)
454
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection
Inverse
Operation_UV1=On
Inverse time
BLKUV1 selected
en05000752.vsd
IEC05000752 V1 EN
Figure 253: Simplified internal logic diagram for built-in first undervoltage step UV1 (step UV2 has the same
internal logic)
IEC05000372-2-en.vsd
IEC05000372 V2 EN
455
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection
456
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection
457
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection
458
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection
459
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection
460
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection
461
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection
462
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection
463
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection
464
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection
465
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection
466
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision
11.1.1 Introduction
Open or short circuited current transformer cores can cause unwanted operation of
many protection functions such as differential, earth-fault current and negative-
sequence current functions.
Current circuit supervision (CCSRDIF) compares the residual current from a three
phase set of current transformer cores with the neutral point current on a separate
input taken from another set of cores on the current transformer.
The FAIL output will be set to a logical one when the following criteria are fulfilled:
467
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision
• The numerical value of the difference |ΣIphase| – |Iref| is higher than 80% of
the numerical value of the sum |ΣIphase| + |Iref|.
• The numerical value of the current |ΣIphase| – |Iref| is equal to or higher than
the set operate value IMinOp.
• No phase current has exceeded Ip>Block during the last 10 ms.
• CCSRDIF is enabled by setting Operation = On.
The FAIL output remains activated 100 ms after the AND-gate resets when being
activated for more than 20 ms. If the FAIL lasts for more than 150 ms an ALARM
will be issued. In this case the FAIL and ALARM will remain activated 1 s after
the AND-gate resets. This prevents unwanted resetting of the blocking function
when phase current supervision element(s) operate, for example, during a fault.
IEC05000463 V1 EN
Figure 255: Simplified logic diagram for Current circuit supervision CCSRDIF
468
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision
| åI phase | - | I ref |
Slope = 1
Operation
Slope = 0.8
area
I MinOp
| åI phase | + | I ref |
99000068.vsd
IEC99000068 V1 EN
Due to the formulas for the axis compared, |SIphase | - |I ref | and |S
I phase | + | I ref | respectively, the slope can not be above 2.
IEC05000389-2-en.vsd
IEC05000389 V2 EN
469
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision
11.2.1 Introduction
The aim of the fuse failure supervision function (SDDRFUF) is to block voltage
measuring functions at failures in the secondary circuits between the voltage
470
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision
transformer and the IED in order to avoid unwanted operations that otherwise
might occur.
The fuse failure supervision function basically has two different algorithms,
negative sequence and zero sequence based algorithm and an additional delta
voltage and delta current algorithm.
The zero sequence detection algorithm is recommended for IEDs used in directly
or low impedance earthed networks. It is based on the zero sequence measuring
quantities, a high value of voltage 3U0 without the presence of the residual current
3I0.
A criterion based on delta current and delta voltage measurements can be added to
the fuse failure supervision function in order to detect a three phase fuse failure,
which in practice is more associated with voltage transformer switching during
station operations.
For better adaptation to system requirements, an operation mode setting has been
introduced which makes it possible to select the operating conditions for negative
sequence and zero sequence based function. The selection of different operation
modes makes it possible to choose different interaction possibilities between the
negative sequence and zero sequence based algorithm.
The zero and negative sequence function continuously measures the currents and
voltages in all three phases and calculates, see figure 258:
The measured signals are compared with their respective set values 3U0< and
3I0>, 3U2< and 3I2>.
The function enable the internal signal FuseFailDetZeroSeq if the measured zero-
sequence voltage is higher than the set value 3U0> and the measured zero-
sequence current is below the set value 3I0<.
471
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision
A drop off delay of 100 ms for the measured zero-sequence and negative sequence
current will prevent a false fuse failure detection at un-equal breaker opening at the
two line ends.
Sequence Detection
3I0< CurrZeroSeq
IL1
Zero 3I0
sequence
filter 100 ms CurrNegSeq
a
IL2 a>b t
b
Negative 3I2
sequence
IL3 filter FuseFailDetZeroSeq
AND
100 ms
a
a>b t
3I2< b
FuseFailDetNegSeq
AND
3U0>
VoltZeroSeq
UL1
Zero
sequence a 3U0
a>b
b
filter
UL2 VoltNegSeq
Negative
sequence a 3U2
a>b
UL3 filter b
3U2>
IEC10000036-1-en.vsd
IEC10000036 V1 EN
The calculated values 3U0, 3I0, 3I2 and 3U2 are available as service values on local
HMI and monitoring tool in PCM600.
The input BLOCK signal is a general purpose blocking signal of the fuse failure
supervision function. It can be connected to a binary input of the IED in order to
receive a block command from external devices or can be software connected to
other internal functions of the IED itself in order to receive a block command from
472
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision
internal functions. Through OR gate it can be connected to both binary inputs and
internal function outputs.
The input BLKSP is intended to be connected to the trip output at any of the
protection functions included in the IED. When activated for more than 20 ms, the
operation of the fuse failure is blocked during a fixed time of 100 ms. The aim is to
increase the security against unwanted operations during the opening of the
breaker, which might cause unbalance conditions for which the fuse failure might
operate.
The output signal BLKZ will also be blocked if the internal dead line detection is
activated. The block signal has a 200 ms drop-off time delay.
The input signal MCBOP is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the miniature circuit breaker protecting the VT
secondary circuit. The MCBOP signal sets the output signals BLKU and BLKZ in
order to block all the voltage related functions when the MCB is open independent
of the setting of OpMode selector. The additional drop-off timer of 150 ms
prolongs the presence of MCBOP signal to prevent the unwanted operation of
voltage dependent function due to non simultaneous closing of the main contacts of
the miniature circuit breaker.
The input signal DISCPOS is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the line disconnector. The DISCPOS signal sets the
output signal BLKU in order to block the voltage related functions when the line
disconnector is open. The impedance protection function is not affected by the
position of the line disconnector since there will be no line currents that can cause
maloperation of the distance protection. If DISCPOS=0 it signifies that the line is
connected to the system and when the DISCPOS=1 it signifies that the line is
disconnected from the system and the block signal BLKU is generated.
The output BLKU can be used for blocking the voltage related measuring functions
(undervoltage protection, synchro-check etc.) except for the impedance protection.
The function output BLKZ can be used for blocking the impedance protection
function.
The BLKZ will only be activated if not the internal dead line detection is activated
at the same time.
The fuse failure condition is unlatched when the normal voltage conditions are
restored.
When the output 3PH is activated, all three voltage are low.
A simplified diagram for the functionality is found in figure 259. The calculation of
the change is based on vector change which means that it detects both amplitude
and phase angle changes. The calculated delta quantities are compared with their
473
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision
respective set values DI< and DU> and the algorithm, detects a fuse failure if a
sufficient change in voltage without a sufficient change in current is detected in
each phase separately. The following quantities are calculated in all three phases:
• The magnitude of the phase-ground voltage has been above UPh> for more
than 1.5 cycle
• The magnitude of DU is higher than the corresponding setting DU>
• The magnitude of DI is below the setting DI>
• The magnitude of the phase current in the same phase is higher than the setting
IPh>
• The circuit breaker is closed (CBCLOSED = True)
The first criterion means that detection of failure in one phase together with high
current for the same phase will set the output. The measured phase current is used
to reduce the risk of false fuse failure detection. If the current on the protected line
is low, a voltage drop in the system (not caused by fuse failure) is not by certain
followed by current change and a false fuse failure might occur
The second criterion requires that the delta condition shall be fulfilled in any phase
at the same time as circuit breaker is closed. Opening circuit breaker at one end and
energizing the line from other end onto a fault could lead to wrong start of the fuse
failure function at the end with the open breaker. If this is considering to be an
important disadvantage, connect the CBCLOSED input to FALSE. In this way
only the first criterion can activate the delta function.
474
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision
DUDI Detection
DUDI detection Phase 1
IL1 One cycle
delay
|DI|
a
a>b
DI< b
20 ms 1.5 cycle
a
a>b t t
UPh> b
UL1
a
a<b
b
IL1
a
a>b
IPh> b AND
OR AND
CBCLOSED AND OR
UL2
a
a<b
b
IL2
a
a>b
b AND
OR AND
AND OR
UL3
a
a<b
b
IL3
a
a>b
b AND
OR AND FuseFailDetDUDI
AND OR
OR
IEC10000034-1-en.vsd
IEC10000034 V1 EN
475
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision
A simplified diagram for the functionality is found in figure 260. A dead phase
condition is indicated if both the voltage and the current in one phase is below their
respective setting values UDLD< and IDLD<. If at least one phase is considered to
be dead the output DLD1PH and the internal signal DeadLineDet1Ph is activated.
If all three phases are considered to be dead the output DLD3PH is activated
IL3
a
a<b
b
IDLD<
DeadLineDet1Ph
UL1
a AND
a<b
b OR DLD1PH
AND
UL2
a AND
a<b
b
AND DLD3PH
UL3 AND
a AND
a<b
b
UDLD<
intBlock
IEC10000035-1-en.vsd
IEC10000035 V1 EN
Figure 260: Simplified logic diagram for Dead Line detection part
A simplified diagram for the functionality is found in figure 261. The fuse failure
supervision function (SDDRFUF) can be switched on or off by the setting
parameter Operation to On or Off.
476
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision
The delta function can be activated by setting the parameter OpDUDI to On. When
selected it operates in parallel with the sequence based algorithms.
If the fuse failure situation is present for more than 5 seconds and the setting
parameter SealIn is set to On it will be sealed in over under-voltage as long as at
least one phase voltages is below the set value USealIn<. This will keep the BLKU
and BLKZ signals activated as long as any phase voltage is below the set value
USealIn<. If all three phase voltages drop below the set value USealIn< and the
setting parameter SealIn is set to On also the output signal 3PH will be activated.
The signals 3PH, BLKU and BLKZ signals will now be active as long as any phase
voltage is below the set value USealIn<.
If SealIn is set to On fuse failure condition is stored in the non volatile memory in
the IED. At start-up (due to auxiliary power interruption or re-start due to
configuration change) the IED checks the stored value in its non volatile memory
and re-establishes the conditions present before the shut down. All phase voltages
must became above USealIn< before fuse failure is de-activated and inhibits the
block of different protection functions.
The output signal BLKU will also be active if all phase voltages have been above
the setting USealIn< for more than 60 seconds, the zero or negative sequence
voltage has been above the set value 3U0> and 3U2> for more than 5 seconds, all
phase currents are below the setting IDLD< (operate level for dead line detection)
and the circuit breaker is closed (input CBCLOSED is activated).
The input signal MCBOP is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the miniature circuit breaker protecting the VT
secondary circuit. The MCBOP signal sets the output signals BLKU and BLKZ in
order to block all the voltage related functions when the MCB is open independent
of the setting of OpMode or OpDUDI. An additional drop-out timer of 150 ms
prolongs the presence of MCBOP signal to prevent the unwanted operation of
477
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision
voltage dependent function due to non simultaneous closing of the main contacts of
the miniature circuit breaker.
The input signal DISCPOS is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the line disconnector. The DISCPOS signal sets the
output signal BLKU in order to block the voltage related functions when the line
disconnector is open. The impedance protection function does not have to be
affected since there will be no line currents that can cause malfunction of the
distance protection.
The output signals 3PH, BLKU and BLKZ as well as the signals DLD1PH and
DLD3PH from dead line detections are blocked if any of the following conditions
occur:
The input BLOCK is a general purpose blocking signal of the fuse failure
supervision function. It can be connected to a binary input of the IED in order to
receive a block command from external devices or can be software connected to
other internal functions of the IED. Through OR gate it can be connected to both
binary inputs and internal function outputs.
The input BLKTRIP is intended to be connected to the trip output of any of the
protection functions included in the IED and/or trip from external equipments via
binary inputs. When activated for more than 20 ms without any fuse fail detected,
the operation of the fuse failure is blocked during a fixed time of 100 ms. The aim
is to increase the security against unwanted operations during the opening of the
breaker, which might cause unbalance conditions for which the fuse failure might
operate.
478
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision
TEST ACTIVE
AND
BlocFuse = Yes
BLOCK intBlock
OR
BLKTRIP 20 ms 100 ms
AND t t
AND
Any UL < UsealIn<
FuseFailDetDUDI
AND 5s
OpDUDI = On
OR t
FuseFailDetZeroSeq
AND
AND
FuseFailDetNegSeq
AND
UNsINs OR
UZsIZs OR
UZsIZs OR UNsINs
OpMode
UZsIZs AND UNsINs
OptimZsNs
OR
CurrZeroSeq
a AND
CurrNegSeq a>b
b
AND
200 ms
DeadLineDet1Ph AND BLKZ
t OR AND
150 ms
MCBOP t
AND BLKU
60 sec
t OR OR
All UL > UsealIn<
AND
VoltZeroSeq 5 sec
VoltNegSeq OR t
AllCurrLow
CBCLOSED
DISCPOS
IEC10000033-1-en.vsd
IEC10000033 V1 EN
Figure 261: Simplified logic diagram for fuse failure supervision function, Main
logic
479
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision
IEC05000700-2-en.vsd
IEC05000700 V3 EN
480
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision
481
Technical reference manual
482
1MRK505183-UEN C Section 12
Control
Section 12 Control
SYMBOL-M V1 EN
12.1.1 Introduction
The Synchronizing function allows closing of asynchronous networks at the correct
moment including the breaker closing time. The systems can thus be reconnected
after an autoreclose or manual closing, which improves the network stability.
SESRSYN function includes a built-in voltage selection scheme for double bus and
1½ breaker or ring busbar arrangements.
Manual closing as well as automatic reclosing can be checked by the function and
can have different settings.
483
Technical reference manual
Section 12 1MRK505183-UEN C
Control
The synchrocheck function measures the conditions across the circuit breaker and
compares them to set limits. The output is only given when all measured quantities
are simultaneously within their set limits.
The energizing check function measures the bus and line voltages and compares
them to both high and low threshold detectors. The output is given only when the
actual measured quantities match the set conditions.
The synchronizing function measures the conditions across the circuit breaker, and
also determines the angle change occurring during the closing delay of the circuit
breaker, from the measured slip frequency. The output is given only when all
measured conditions are simultaneously within their set limits. The issue of the
output is timed to give closure at the optimal time including the time for the circuit
breaker and the closing circuit.
For single circuit breaker and 1½ breaker circuit breaker arrangements, the
SESRSYN function blocks have the capability to make the necessary voltage
selection. For single circuit breaker arrangements, selection of the correct voltage
is made using auxiliary contacts of the bus disconnectors. For 1½ breaker circuit
breaker arrangements, correct voltage selection is made using auxiliary contacts of
the bus disconnectors as well as the circuit breakers.
The internal logic for each function block as well as, the input and outputs, and the
setting parameters with default setting and setting ranges is described in this
document. For application related information, please refer to the application manual.
Logic diagrams
The logic diagrams that follow illustrate the main principles of the synchronizing
function components such as Synchrocheck, Energizing check and Voltage
selection, and are intended to simplify the understanding of the function.
Synchrocheck
The voltage difference, frequency difference and phase angle difference values are
measured in the IED centrally and are available for the synchrocheck function for
evaluation. If the bus voltage is connected as phase-phase and the line voltage as
phase-neutral (or the opposite), this need to be compensated. This is done with a
setting, which scales up the line voltage to a level equal to the bus voltage.
When the function is set to OperationSC = On, the measuring will start.
The function will compare the bus and line voltage values with the set values for
UHighBusSC and UHighLineSC.
484
Technical reference manual
1MRK505183-UEN C Section 12
Control
If both sides are higher than the set values, the measured values are compared with
the set values for acceptable frequency, phase angle and voltage difference:
FreqDiff, PhaseDiff and UDiff. If a compensation factor is set due to the use of
different voltages on the bus and line, the factor is deducted from the line voltage
before the comparison of the phase angle values.
The frequency on both sides of the circuit breaker is also measured. The
frequencies must not deviate from the rated frequency more than +/-5Hz. The
frequency difference between the bus frequency and the line frequency is measured
and may not exceed the set value.
Two sets of settings for frequency difference and phase angle difference are
available and used for the manual closing and autoreclose functions respectively, as
required.
The inputs BLOCK and BLKSC are available for total block of the complete
Synchrocheck function and block of the Synchrocheck function respectively. Input
TSTSC will allow testing of the function where the fulfilled conditions are
connected to a separate test output.
The outputs MANSYOK and AUTOSYOK are activated when the actual measured
conditions match the set conditions for the respective output. The output signal can
be delayed independently for MANSYOK and AUTOSYOK conditions.
485
Technical reference manual
Section 12 1MRK505183-UEN C
Control
OperationSC = On
AND TSTAUTSY
AND
TSTSC
BLKSC AND
BLOCK OR
AUTOSYOK
AND
0-60 s
AND t
tSCA
UDiffSC 50 ms
AND t
UHighBusSC
UOKSC
AND
UHighLineSC
UDIFFSC
1
FRDIFFA
FreqDiffA 1
PHDIFFA
PhaseDiffA 1
UDIFFME
voltageDifferenceValue
FRDIFFME
frequencyDifferenceValue
PHDIFFME
phaseAngleDifferenceValue
IEC07000114-2-en.vsd
IEC07000114 V2 EN
Synchronizing
When the function is set to OperationSynch = On the measuring will be performed.
The function will compare the values for the bus and line voltage with the set
values for UHighBusSynch and UHighLineSynch, which is a supervision that the
voltages are both live. If both sides are higher than the set values the measured
values are compared with the set values for acceptable frequency, rate of change of
frequency, phase angle and voltage difference FreqDiffMax, FreqDiffMin and
UDiffSynch.
Measured frequencies between the settings for the maximum and minimum
frequency will initiate the measuring and the evaluation of the angle change to
allow operation to be sent in the right moment including the set tBreaker time.
There is a phase angle release internally to block any incorrect closing pulses. At
operation the SYNOK output will be activated with a pulse tClosePulse and the
function reset. The function will also reset if the synchronizing conditions are not
fulfilled within the set tMaxSynch time. This prevents that the functions are, by
mistake, maintained in operation for a long time, waiting for conditions to be fulfilled.
486
Technical reference manual
1MRK505183-UEN C Section 12
Control
The inputs BLOCK and BLKSYNCH are available for total block of the complete
function respective of the synchronizing part. TSTSYNCH will allow testing of the
function where the fulfilled conditions are connected to a separate output.
SYN1
OPERATION SYNCH
OFF
ON
TEST MODE
OFF
ON
STARTSYN SYNPROGR
AND
AND
S
BLKSYNCH
OR R
UDiffSynch
50 ms SYNOK
AND
UHighBusSynch AND t
UHighLineSynch OR
FreqDiffMax
AND
TSTSYNOK
FreqDiffMin OR
tClose
FreqRateChange Pulse
AND
fBus&fLine ± 5 Hz tMax
AND
Synch
PhaseDiff < 15 deg SYNFAIL
PhaseDiff=closing angle
IEC06000636-2-en.vsd
IEC06000636 V2 EN
Energizing check
Voltage values are measured in the IED centrally and are available for evaluation
by the Energizing check function. If the bus voltage is connected as phase-phase
and the line voltage as phase-neutral, (or the opposite) this needs to be
compensated. This is done with a setting, which scales the line voltage to a level
equal to the bus voltage.
The function measures voltages on the busbar and the line to verify whether they
are live or dead. This is done by comparing with the set values UHighBusEnerg
and ULowBusEnerg for bus energizing and UHighLineEnerg and ULowLineEnerg
for line energizing.
The frequency on both sides of the circuit breaker is also measured. The
frequencies must not deviate from the rated frequency more than +/-5Hz. The
frequency difference between the bus frequency and the line frequency is measured
and shall not exceed a set value.
487
Technical reference manual
Section 12 1MRK505183-UEN C
Control
The Energizing direction can be selected individually for the Manual and the
Automatic functions respectively. When the conditions are met the outputs
AUTOENOK and MANENOK respectively will be activated if the fuse
supervision conditions are fulfilled. The output signal can be delayed
independently for MANENOK and AUTOENOK conditions. The Energizing
direction can also be selected by an integer input AENMODE respective
MENMODE, which for example, can be connected to a Binary to Integer function
block (B16I). Integers supplied shall be 1=off, 2=DLLB, 3=DBLL and 4= Both.
Not connected input with connection of INTZERO output from Fixed Signals
(FIXDSIGN) function block will mean that the setting is done from Parameter
Setting tool. The active position can be read on outputs MODEAEN resp
MODEMEN. The modes are 0=OFF, 1=DLLB, 2=DBLL and 3=Both.
The inputs BLOCK and BLKENERG are available for total block of the complete
Synchronizing function respective block of the Energizing check function.
TSTENERG will allow testing of the function where the fulfilled conditions are
connected to a separate test output.
Voltage selection
The voltage selection module including supervision of included voltage
transformer fuses for the different arrangements is a basic part of the
Synchronizing function and determines the parameters fed to the Synchronizing,
Synchrocheck and Energizing check functions. This includes the selection of the
appropriate Line and Bus voltages and fuse supervision.
The voltage selection type to be used is set with the parameter CBConfig.
If No voltage sel. is set the default voltages used will be ULine1 and UBus1. This
is also the case when external voltage selection is provided. Fuse failure
supervision for the used inputs must also be connected.
The voltage selection function, selected voltages, and fuse conditions are the
Synchronizing, Synchrocheck and Energizing check inputs.
For the disconnector positions it is advisable to use (NO) a and (NC) b type
contacts to supply Disconnector Open and Closed positions but, it is also possible
to use an inverter for one of the positions.
The function checks the fuse-failure signals for bus 1, bus 2 and line voltage
transformers. Inputs UB1OK-UB1FF supervise the fuse for Bus 1 and UB2OK-
UB2FF supervises the fuse for Bus 2. ULN1OK-ULN1FF supervises the fuse for
the Line voltage transformer. The inputs fail (FF) or healthy (OK) can alternatively
488
Technical reference manual
1MRK505183-UEN C Section 12
Control
B1QOPEN
B1SEL
B1QCLD AND
B2QOPEN B2SEL
1
B2QCLD AND
AND invalidSelection
bus1Voltage
busVoltage
bus2Voltage
UB1OK AND
UB1FF OR
OR
AND selectedFuseOK
UB2OK AND
UB2FF OR USELFAIL
AND
ULN1OK
ULN1FF OR
BLOCK
en05000779.vsd
IEC05000779 V1 EN
Figure 265: Logic diagram for the voltage selection function of a single circuit breaker with double busbars
This voltage selection function uses the binary inputs from the disconnectors and
circuit breakers auxiliary contacts to select the right voltage for the Synchrocheck
(Synchronism and Energizing check) function. For the bus circuit breaker one side
of the circuit breaker is connected to the busbar and the other side is connected
either to line 1, line 2 or the other busbar depending on the arrangement.
489
Technical reference manual
Section 12 1MRK505183-UEN C
Control
respectively the Bus and Tie breakers. The Outputs LN1SEL, LN2SEL and B2SEL
will give indication of the selected Line voltage as a reference to the fixed Bus 1
voltage.
The tie circuit breaker is connected either to bus 1 or line 1 on one side and the
other side is connected either to bus 2 or line 2. Four different output combinations
are possible, bus to bus, bus to line, line to bus and line to line.
The function also checks the fuse-failure signals for bus 1, bus 2, line 1 and line 2.
If a fuse-failure is detected in the selected voltage an output signal USELFAIL is
set. This output signal is true if the selected bus or line voltages have a fuse failure.
This output as well as the function can be blocked with the input signal BLOCK.
The function block diagram for the voltage selection of a bus circuit breaker is
shown in figure 266 and for the tie circuit breaker in figure 267
490
Technical reference manual
1MRK505183-UEN C Section 12
Control
LN1QOPEN
AND
LN1SEL
LN1QCLD
B1QOPEN
LN2SEL
B1QCLD AND AND
OR
B2SEL
LN2QOPEN
LN2QCLD AND
AND invalidSelection
AND
B2QOPEN
B2QCLD AND
line1Voltage
lineVoltage
line2Voltage
bus2Voltage
UB1OK
UB1FF OR
OR
UB2OK AND
AND selectedFuseOK
UB2FF OR
USELFAIL
ULN1OK AND
AND
ULN1FF OR
ULN2OK
AND
ULN2FF OR
BLOCK
en05000780.vsd
IEC05000780 V1 EN
Figure 266: Simplified logic diagram for the voltage selection function for a bus circuit breaker in a 1 1/2
breaker arrangement
491
Technical reference manual
Section 12 1MRK505183-UEN C
Control
LN1QOPEN
LN1SEL
LN1QCLD AND
B1SEL
1
B1QOPEN AND
AND
B1QCLD AND
line1Voltage
busVoltage
bus1Voltage
LN2QOPEN
LN2SEL
LN2QCLD AND
B2SEL
1
OR invalidSelection
B2QOPEN AND
AND
B2QCLD AND
line2Voltage
lineVoltage
bus2Voltage
UB1OK AND
UB1FF OR
OR
UB2OK AND selectedFuseOK
AND
UB2FF OR
USELFAIL
ULN1OK AND
AND
ULN1FF OR
ULN2OK
AND
ULN2FF OR
BLOCK
en05000781.vsd
IEC05000781 V1 EN
Figure 267: Simplified logic diagram for the voltage selection function for the tie circuit breaker in 1 1/2
breaker arrangement.
492
Technical reference manual
1MRK505183-UEN C Section 12
Control
The UB1OK/UB2OK and UB1FF/UB2FF inputs are related to the busbar voltage
and the ULN1OK/ULN2OK and ULN1FF/ULN2FF inputs are related to the line
voltage. Configure them to the binary input or function outputs that indicate the
status of the external fuse failure of the busbar and line voltages. In the event of a
fuse failure, the energizing check functions are blocked. The synchronizing and the
synchrocheck function requires full voltage on both sides and will be blocked
automatically in the event of fuse failures.
IEC06000534-2-en.vsd
IEC06000534 V2 EN
493
Technical reference manual
Section 12 1MRK505183-UEN C
Control
494
Technical reference manual
1MRK505183-UEN C Section 12
Control
495
Technical reference manual
Section 12 1MRK505183-UEN C
Control
496
Technical reference manual
1MRK505183-UEN C Section 12
Control
497
Technical reference manual
Section 12 1MRK505183-UEN C
Control
O->I
SYMBOL-L V1 EN
498
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.2.1 Introduction
The autorecloser (SMBRREC) function provides high-speed and/or delayed auto-
reclosing for single or multi-breaker applications.
Up to five reclosing attempts can be programmed. The first attempt can be single-,
two and/or three phase for single phase or multi-phase faults respectively.
The logic diagrams below illustrate the principles applicable in the understanding
of the functionality.
Operation of the automatic reclosing can be set to Off or On via the setting
parameters and through external control. With the setting Operation = On, the
function is activated while with the setting Operation = Off the function is
deactivated. With the setting Operation = External ctrl, the activation/deactivation
is made by input signal pulses, for example, from a control system.
When the function is set On and is operative the output SETON is activated (high).
Other input conditions such as CBPOS and CBREADY must also be fulfilled. At
this point the automatic recloser is prepared to start the reclosing cycle and the
output signal READY on the SMBRREC function block is activated (high).
When INTZERO from Fixed signal function block is connected to the input
MODEINT the parameter setting selected will be valid.
499
Technical reference manual
Section 12 1MRK505183-UEN C
Control
The usual way in which to start a reclosing cycle, or sequence, is to start it when a
line protection tripping has occurred, by applying a signal to the START input. It
should be necessary to adjust three-phase auto-reclosing open time, (dead time) for
different power system configurations or during tripping at different protection
stages, the input STARTHS (start high-speed reclosing) can also be used.
• CBREADY: CB ready for a reclosing cycle, for example, charged operating gear
• CBPOS: to ensure that the CB was closed when the line fault occurred and
start was applied
• No blocking or inhibit signal shall be present.
After the start has been accepted, it is latched in and an internal signal “Started” is
set. It can be interrupted by certain events, like an inhibit signal.
The logic for switching the auto-recloser On/Off and the starting of the reclosing is
shown in figure 269. The following should be considered:
• Setting Operation can be set to Off, External ctrl or On. External ctrl offers
the possibility of switching by external switches to inputs ON and OFF,
communication commands to the same inputs, and so on.
• SMBRREC is normally started by tripping. It is either a Zone 1 and
Communication aided trip, or a general trip. If the general trip is used the
function must be blocked from all back-up tripping connected to INHIBIT. In
both alternatives the breaker failure function must be connected to inhibit the
function. START makes a first attempt with synchrocheck, STARTHS makes
its first attempt without synchrocheck. TRSOTF starts shots 2-5.
• Circuit breaker checks that the breaker was closed for a certain length of time
before the starting occurred and that the CB has sufficient stored energy to
perform an auto-reclosing sequence and is connected to inputs CBPOS and
CBREADY.
500
Technical reference manual
1MRK505183-UEN C Section 12
Control
Operation:On
Operation:Off
Operation:External Ctrl
OR
ON AND SETON
AND S
OR
OFF AND R
START
STARTHS OR
OR initiate
autoInitiate
Additional conditions
TRSOTF AND
start
120 ms
CBREADY AND
t AND
AND S
tCBClosedMin
CBPOS CB Closed
t R
AND
Blocking conditions READY
AND
OR
Inhibit condistions
count 0
en05000782.vsd
IEC05000782 V1 EN
It is possible to use up to four different time settings for the first shot, and one
extension time. There are separate settings for single- , two- and three-phase auto-
reclosing open times, t1 1Ph, t1 2Ph, t1 3Ph. If no particular input signal is applied,
and an auto-reclosing program with single-phase reclosing is selected, the auto-
reclosing open time t1 1Ph will be used. If one of the inputs TR2P or TR3P is
activated in connection with the input START, the auto-reclosing open time for two-
phase or three-phase reclosing is used. There is also a separate time setting facility
for three-phase high-speed auto-reclosing, t1 3PhHS available for use when
required. It is activated by input STARTHS.
An auto-reclosing open time extension delay, tExtended t1, can be added to the
normal shot 1 delay. It is intended to come into use if the communication channel
for permissive line protection is lost. In a case like this there can be a significant
time difference in fault clearance at the two line ends. A longer auto-reclosing open
time can then be useful. This extension time is controlled by setting parameter
Extended t1 = On and the input PLCLOST.
In normal circumstances the trip command resets quickly due to fault clearing. The
user can set a maximum trip pulse duration tTrip. When trip signals are longer, the
501
Technical reference manual
Section 12 1MRK505183-UEN C
Control
Extended t1
PLCLOST Extend t1
initiate AND OR AND
AND
tTrip
t
AND
start
long duration
AND
(block SMBRREC)
IEC05000783_2_en.vsd
IEC05000783 V2 EN
Figure 270: Control of extended auto-reclosing open time and long trip pulse detection
502
Technical reference manual
1MRK505183-UEN C Section 12
Control
The synchro-check or energizing check must be fulfilled within a set time interval,
tSync. If it is not, or if other conditions are not met, the reclosing is interrupted and
blocked.
The reclaim timer defines a time from the issue of the reclosing command, after
which the reclosing function resets. Should a new trip occur during this time, it is
treated as a continuation of the first fault. The reclaim timer is started when the CB
closing command is given.
A number of outputs for Autoreclosing state control keeps track of the actual state
in the reclosing sequence.
503
Technical reference manual
Section 12 1MRK505183-UEN C
Control
t1 1Ph
"SMBRREC Open time" timers
t
1P2PTO
From logic for t1 2Ph OR
reclosing t
programs
1P2PTO t1 3Ph HS
t
3PHSTO
3PHSTO
3PT1TO
t1 3Ph
3PT2TO t
3PT1TO
3PT3TO OR
AND
3PT4TO OR Pulse AR
3PT5TO AND
SYNC
initiate AND Blocking out
CBREADY AND OR
SMRREC State
tSync Control
AND t COUNTER
0 Shot 0
CL Shot 1
1
2 Shot 2
3 Shot 3
tReclaim
Pulse SMBRREC (above) AND t R 4 Shot 4
OR Shot 5
5
TR2P LOGIC Reclaim Timer On
TR3P reclosing
1PT1
programs
start 2PT1
initiate 3PHS INPROGR
Shot 0 3PT1 OR
Shot 1 3PT2
Shot 2
Shot 3 3PT3
Shot 4
Shot 5 3PT4
PERMIT1P
3PT5
PREP3P
1
Blocking out tInhibit
OR Inhibit (internal)
INHIBIT t
IEC05000784_2_en.vsd
IEC05000784 V2 EN
504
Technical reference manual
1MRK505183-UEN C Section 12
Control
CutPulse=On. In case of a new trip pulse, the closing command pulse is cut
(interrupted). The minimum duration of the pulse is always 50 ms. See figure 272
tPulse
pulse
**) AND CLOSECB
OR
initiate
50 ms
2PT1 AND
counter
COUNT2P
counter COUNTAR
RSTCOUNT
en05000785.vsd
IEC05000785 V1 EN
Figure 272: Pulsing of closing command and driving the operation counters
Transient fault
After the reclosing command the reclaim timer tReclaim starts running for the set
time. If no tripping occurs within this time, the auto-reclosing will reset.
505
Technical reference manual
Section 12 1MRK505183-UEN C
Control
will be ended. After the reclaim time has elapsed, the auto-reclosing function resets
but the CB remains open. The CB closed data at the CBPOS input will be missing.
Because of this, the reclosing function will not be ready for a new reclosing cycle.
Normally the signal UNSUCCL appears when a new trip and start is received after
the last reclosing shot has been made and the auto-reclosing function is blocked.
The signal resets once the reclaim time has elapsed. The “unsuccessful“ signal can
also be made to depend on CB position input. The parameter UnsucClByCBChk
should then be set to CBCheck, and a timer tUnsucCl should also be set. If the CB
does not respond to the closing command and does not close, but remains open, the
output UNSUCCL is set high after time tUnsucCl.
initiate
block start AND
OR UNSUCCL
AND S
shot 0
R
UnsucClByCBchk = CBcheck
eno5000786.vsd
IEC05000786 V1 EN
506
Technical reference manual
1MRK505183-UEN C Section 12
Control
tAutoContWait
t
AND
CLOSECB
AND
S Q
AND
CBPOS CBClosed
OR
initiate
START OR
en05000787.vsd
IEC05000787 V1 EN
507
Technical reference manual
Section 12 1MRK505183-UEN C
Control
StartByCBOpen = On
START AND
STARTHS AND
start
³1
100 ms
AND
100 ms
AND
en05000788.vsd
IEC05000788 V1 EN
Some examples of the timing of internal and external signals at typical transient
and permanent faults are shown below in figures 276 to 279.
Fault
CB POS
Closed Open Closed
CB READY
START (Trip)
SYNC
tReclaim
READY
INPROG
1PT1
ACTIVE
PREP3P
SUCCL
Time
en04000196-2-en.vsd
IEC04000196 V2 EN
508
Technical reference manual
1MRK505183-UEN C Section 12
Control
Fault
CB POS Open
Closed Open C C
CB READY
START (Trip)
TR3P
SYNC
READY
INPROGR
3PT1 t1 3Ph
3PT2 t2 3Ph
ACTIVE tReclaim
PREP3P
UNSUCCL
Time
en04000197.vsd
IEC04000197 V1 EN
509
Technical reference manual
Section 12 1MRK505183-UEN C
Control
Fault
AR01-CBCLOSED
AR01-CBREADY(CO)
AR01-START
AR01-TR3P
AR01-SYNC
AR01-READY
AR01-INPROGR
AR01-1PT1
AR01-T1
AR01-T2
AR01-CLOSECB t1s
AR01-P3P
AR01-UNSUC
tReclaim
en04000198.vsd
IEC04000198 V1 EN
Fault
AR01-CBCLOSED
AR01-CBREADY(CO)
AR01-START
AR01-TR3P
AR01-SYNC
AR01-READY
AR01-INPROGR
AR01-1PT1
AR01-T1
AR01-T2
t2
AR01-CLOSECB t1s
AR01-P3P
AR01-UNSUC
tReclaim
en04000199.vsd
IEC04000199 V1 EN
Figure 279: Permanent single-phase fault. Program 1ph + 3ph or 1/2ph + 3ph,
two-shot reclosing
510
Technical reference manual
1MRK505183-UEN C Section 12
Control
IEC06000189-2-en.vsd
IEC06000189 V2 EN
511
Technical reference manual
Section 12 1MRK505183-UEN C
Control
512
Technical reference manual
1MRK505183-UEN C Section 12
Control
513
Technical reference manual
Section 12 1MRK505183-UEN C
Control
514
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.3.1 Introduction
The apparatus control is a function for control and supervision of circuit breakers,
disconnectors and earthing switches within a bay. Permission to operate is given
after evaluation of conditions from other functions such as interlocking,
synchrocheck, operator place selection and external or internal blockings.
515
Technical reference manual
Section 12 1MRK505183-UEN C
Control
The software module is connected to the physical process in the switchyard via an
interface module by means of a number of digital inputs and outputs. One type of
interface module is intended for a circuit breaker (SXCBR) and another type is
intended for a disconnector or earthing switch (SXSWI). Four types of function
blocks are available to cover most of the control and supervision within the bay.
These function blocks are interconnected to form a control function reflecting the
switchyard configuration. The total number used depends on the switchyard
configuration. These four types are:
The three latter functions are logical nodes according to IEC 61850. The functions
Local Remote (LOCREM) and Local Remote Control (LOCREMCTRL), to handle
the local/remote switch, and the functions Bay reserve (QCRSV) and Reservation
input (RESIN), for the reservation function, also belong to the apparatus control
function. The principles of operation, function block, input and output signals and
setting parameters for all these functions are described below.
516
Technical reference manual
1MRK505183-UEN C Section 12
Control
517
Technical reference manual
Section 12 1MRK505183-UEN C
Control
12.3.4.1 Introduction
The bay control (QCBAY) function is used to handle the selection of the operator
place per bay. QCBAY also provides blocking functions that can be distributed to
different apparatuses within the bay.
The functionality of the Bay control (QCBAY) function is not defined in the IEC
61850–8–1 standard, which means that the function is a vendor specific logical node.
The function sends information about the Permitted Source To Operate (PSTO)
and blocking conditions to other functions within the bay for example, switch
control functions, voltage control functions and measurement functions.
518
Technical reference manual
1MRK505183-UEN C Section 12
Control
switch and its validity information are connected internally, and not via I/O boards.
When the switch is mounted separately on the IED the signals are connected to the
function via I/O boards.
When the local panel switch is in Off position all commands from remote and local
level will be ignored. If the position for the local/remote switch is not valid the
PSTO output will always be set to faulty state (3), which means no possibility to
operate.
To adapt the signals from the local HMI or from an external local/remote switch,
the function blocks LOCREM and LOCREMCTRL are needed and connected to
QCBAY.
Table 299: PSTO values for different Local panel switch positions
Local panel switch PSTO value AllPSTOValid Possible locations that shall be able to
positions (configuration operate
parameter)
0 = Off 0 -- Not possible to operate
1 = Local 1 FALSE Local Panel
1 = Local 5 TRUE Local or Remote level without any
priority
2 = Remote 2 FALSE Remote level
2 = Remote 5 TRUE Local or Remote level without any
priority
3 = Faulty 3 -- Not possible to operate
Blockings
The blocking states for position indications and commands are intended to provide
the possibility for the user to make common blockings for the functions configured
within a complete bay.
The blocking facilities provided by the bay control function are the following:
519
Technical reference manual
Section 12 1MRK505183-UEN C
Control
• Blocking of position indications, BL_UPD. This input will block all inputs
related to apparatus positions for all configured functions within the bay.
• Blocking of commands, BL_CMD. This input will block all commands for all
configured functions within the bay.
• Blocking of function, BLOCK, signal from DO (Data Object) Behavior (IEC
61850–8–1). If DO Behavior is set to "blocked" it means that the function is
active, but no outputs are generated, no reporting, control commands are
rejected and functional and configuration data is visible.
The switching of the Local/Remote switch requires at least system operator level.
The password will be requested at an attempt to operate if authority levels have
been defined in the IED. Otherwise the default authority level, SuperUser, can
handle the control without LogOn. The users and passwords are defined in PCM600.
520
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.3.5.1 Introduction
The signals from the local HMI or from an external local/remote switch are applied
via function blocks LOCREM and LOCREMCTRL to the Bay control (QCBAY)
function block. A parameter in function block LOCREM is set to choose if the
switch signals are coming from the local HMI or from an external hardware switch
connected via binary inputs.
The function block Local remote (LOCREM) handles the signals coming from the
local/remote switch. The connections are seen in figure 282, where the inputs on
function block LOCREM are connected to binary inputs if an external switch is
used. When a local HMI is used, the inputs are not used and are set to FALSE in
the configuration. The outputs from the LOCREM function block control the
output PSTO (Permitted Source To Operate) on Bay control (QCBAY).
521
Technical reference manual
Section 12 1MRK505183-UEN C
Control
LOCREM QCBAY
CTRLOFF OFF LR_OFF PSTO
LOCCTRL LOCAL LR_LOC UPD_BLKD
REMCTRL REMOTE LR_REM CMD_BLKD
LHMICTRL VALID LR_VALID
BL_UPD
BL_CMD
LOCREM QCBAY
CTRLOFF OFF LR_OFF PSTO
LOCCTRL LOCAL LR_LOC UPD_BLKD
REMCTRL REMOTE LR_REM CMD_BLKD
LHMICTRL VALID LR_VALID
BL_UPD
BL_CMD
LOCREMCTRL
PSTO1 HMICTR1
PSTO2 HMICTR2
PSTO3 HMICTR3
PSTO4 HMICTR4
PSTO5 HMICTR5
PSTO6 HMICTR6
PSTO7 HMICTR7
PSTO8 HMICTR8
PSTO9 HMICTR9
PSTO10 HMICTR10
PSTO11 HMICTR11
PSTO12 HMICTR12
IEC05000250_2_en.vsd
IEC05000250 V2 EN
Figure 282: Configuration for the local/remote handling for a local HMI with two
bays and two screen pages
If the IED contains control functions for several bays, the local/remote position can
be different for the included bays. When the local HMI is used the position of the
local/remote switch can be different depending on which single line diagram screen
page that is presented on the local HMI. The function block Local remote control
(LOCREMCTRL) controls the presentation of the LEDs for the local/remote
position to applicable bay and screen page.
The switching of the local/remote switch requires at least system operator level.
The password will be requested at an attempt to operate if authority levels have
been defined in the IED. Otherwise the default authority level, SuperUser, can
handle the control without LogOn. The users and passwords are defined in PCM600.
IEC05000360-2-en.vsd
IEC05000360 V2 EN
522
Technical reference manual
1MRK505183-UEN C Section 12
Control
LOCREMCTRL
PSTO1 HMICTR1
PSTO2 HMICTR2
PSTO3 HMICTR3
PSTO4 HMICTR4
PSTO5 HMICTR5
PSTO6 HMICTR6
PSTO7 HMICTR7
PSTO8 HMICTR8
PSTO9 HMICTR9
PSTO10 HMICTR10
PSTO11 HMICTR11
PSTO12 HMICTR12
IEC05000361-2-en.vsd
IEC05000361 V2 EN
523
Technical reference manual
Section 12 1MRK505183-UEN C
Control
12.3.6.1 Introduction
The Switch controller (SCSWI) initializes and supervises all functions to properly
select and operate switching primary apparatuses. The Switch controller may
handle and operate on one three-phase device.
The Switch controller (SCSWI) is provided with verification checks for the select -
execute sequence, that is, checks the conditions prior each step of the operation.
The involved functions for these condition verifications are interlocking,
reservation, blockings and synchrocheck.
524
Technical reference manual
1MRK505183-UEN C Section 12
Control
Control handling
.
Two types of control models can be used. The two control models are "direct with
normal security" and "SBO (Select-Before-Operate) with enhanced security". The
parameter CtlModel defines which one of the two control models is used. The
control model "direct with normal security" does not require a select whereas, the
"SBO with enhanced security" command model requires a select before execution.
Normal security means that only the command is evaluated and the resulting
position is not supervised. Enhanced security means that the command sequence is
supervised in three steps, the selection, command evaluation and the supervision of
position. Each step ends up with a pulsed signal to indicate that the respective step
in the command sequence is finished. If an error occurs in one of the steps in the
command sequence, the sequence is terminated and the error is mapped into the
enumerated variable "cause" attribute belonging to the pulsed response signal for
the IEC 61850 communication. The last cause L_CAUSE can be read from the
function block and used for example at commissioning.
Evaluation of position
In the case when there are three one-phase switches connected to the switch control
function, the switch control will "merge" the position of the three switches to the
resulting three-phase position. In the case when the position differ between the one-
phase switches, following principles will be applied:
525
Technical reference manual
Section 12 1MRK505183-UEN C
Control
The time stamp of the output three-phase position from switch control will have the
time stamp of the last changed phase when it goes to end position. When it goes to
intermediate position or bad state, it will get the time stamp of the first changed phase.
In addition, there is also the possibility that one of the one-phase switches will
change position at any time due to a trip. Such situation is here called pole
discordance and is supervised by this function. In case of a pole discordance
situation, that is, the position of the one-phase switches are not equal for a time
longer than the setting tPoleDiscord, an error signal POLEDISC will be set.
In the supervision phase, the switch controller function evaluates the "cause"
values from the switch modules Circuit breaker (SXCBR)/ Circuit switch
(SXSWI). At error the "cause" value with highest priority is shown.
Blocking principles
The blocking signals are normally coming from the bay control function (QCBAY)
and via the IEC 61850 communication from the operator place.
The different block conditions will only affect the operation of this
function, that is, no blocking signals will be "forwarded" to other
functions. The above blocking outputs are stored in a non-volatile
memory.
526
Technical reference manual
1MRK505183-UEN C Section 12
Control
SCSWI SXCBR
EXE_CL
OR CLOSE
SYNC_OK
START_SY
SY_INPRO
SESRSYN
CLOSECB
Synchro Synchronizing
check function
IEC09000209_1_en.vsd
IEC09000209 V1 EN
Time diagrams
The Switch controller (SCSWI) function has timers for evaluating different time
supervision conditions. These timers are explained here.
The timer tSelect is used for supervising the time between the select and the
execute command signal, that is, the time the operator has to perform the command
execution after the selection of the object to operate.
select
execute command
tSelect
timer t1 t1>tSelect, then long-
operation-time in 'cause'
is set
en05000092.vsd
IEC05000092 V1 EN
The parameter tResResponse is used to set the maximum allowed time to make the
reservation, that is, the time between reservation request and the feedback
reservation granted from all bays involved in the reservation function.
527
Technical reference manual
Section 12 1MRK505183-UEN C
Control
select
command termination
tResResponse t1>tResResponse, then
timer 1-of-n-control in 'cause'
t1 is set
en05000093.vsd
IEC05000093 V1 EN
The timer tExecutionFB supervises the time between the execute command and the
command termination, see figure 288.
execute command
position L1 open
close
position L2 open
close
position L3 open
close
cmd termination L1
cmd termination L2
cmd termination L3
cmd termination *
position open
close
The parameter tSynchrocheck is used to define the maximum allowed time between
the execute command and the input SYNC_OK to become true. If SYNC_OK=true
at the time the execute command signal is received, the timer "tSynchrocheck" will
not start. The start signal for the synchronizing is obtained if the synchrocheck
conditions are not fulfilled.
528
Technical reference manual
1MRK505183-UEN C Section 12
Control
execute command
SYNC_OK
tSynchrocheck
t1
START_SY
SY_INPRO
en05000095.vsd
IEC05000095 V1 EN
IEC05000337-2-en.vsd
IEC05000337 V2 EN
529
Technical reference manual
Section 12 1MRK505183-UEN C
Control
530
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.3.7.1 Introduction
The purpose of Circuit breaker (SXCBR) is to provide the actual status of positions
and to perform the control operations, that is, pass all the commands to primary
apparatuses in the form of circuit breakers via output boards and to supervise the
switching operation and position.
The users of the Circuit breaker function (SXCBR) is other functions such as for
example, switch controller, protection functions, autorecloser function or an IEC
61850 client residing in another IED or the operator place. This switch function
executes commands, evaluates block conditions and evaluates different time
supervision conditions. Only if all conditions indicate a switch operation to be
allowed, the function performs the execution command. In case of erroneous
conditions, the function indicates an appropriate "cause" value.
SXCBR has an operation counter for closing and opening commands. The counter
value can be read remotely from the operator place. The value is reset from a
binary input or remotely from the operator place by configuring a signal from the
Single Point Generic Control 8 signals (SPC8GGIO) for example.
531
Technical reference manual
Section 12 1MRK505183-UEN C
Control
Local/Remote switch
One binary input signal LR_SWI is included in SXCBR to indicate the local/
remote switch position from switchyard provided via the I/O board. If this signal is
set to TRUE it means that change of position is allowed only from switchyard
level. If the signal is set to FALSE it means that command from IED or higher
level is permitted. When the signal is set to TRUE all commands (for change of
position) from internal IED clients are rejected, even trip commands from
protection functions are rejected. The functionality of the local/remote switch is
described in figure 291.
Local= Operation at
RU
E switch yard level
T
en05000096.vsd
IEC05000096 V1 EN
Blocking principles
SXCBR includes several blocking principles. The basic principle for all blocking
signals is that they will affect commands from all other clients for example,
operators place, protection functions, autoreclosure and so on.
Substitution
The substitution part in SXCBR is used for manual set of the position for the
switch. The typical use of substitution is that an operator enters a manual value
because that the real process value is erroneous for some reason. SXCBR will then
532
Technical reference manual
1MRK505183-UEN C Section 12
Control
use the manually entered value instead of the value for positions determined by the
process.
Time diagrams
There are two timers for supervising of the execute phase, tStartMove and
tIntermediate. tStartMove supervises that the primary device starts moving after the
execute output pulse is sent. tIntermediate defines the maximum allowed time for
intermediate position. Figure 292 explains these two timers during the execute phase.
OPENPOS
CLOSEPOS
en05000097.vsd
IEC05000097 V1 EN
The timers tOpenPulse and tClosePulse are the length of the execute output pulses
to be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be
adaptive with the configuration parameter AdaptivePulse. Figure 293 shows the
principle of the execute output pulse. The AdaptivePulse parameter will have affect
on both execute output pulses.
533
Technical reference manual
Section 12 1MRK505183-UEN C
Control
OPENPOS
CLOSEPOS
AdaptivePulse=FALSE
EXE_CL
tClosePulse
AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN
If the pulse is set to be adaptive, it is not possible for the pulse to exceed
tOpenPulse or tClosePulse.
• the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.
There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in closed
position and a close command is executed. In these cases, with the additional
condition that the configuration parameter AdaptivePulse is true, the execute output
pulse is always activated and resets when tStartMove has elapsed. If the
configuration parameter AdaptivePulse is set to false the execution output remains
active until the pulse duration timer has elapsed.
534
Technical reference manual
1MRK505183-UEN C Section 12
Control
OPENPOS
CLOSEPOS
EXE_OP AdaptivePulse=FALSE
tOpenPulse
EXE_OP AdaptivePulse=TRUE
tOpenPulse
tStartMove timer
en05000099.vsd
IEC05000099 V1 EN
IEC05000338-2-en.vsd
IEC05000338 V2 EN
535
Technical reference manual
Section 12 1MRK505183-UEN C
Control
536
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.3.8.1 Introduction
The purpose of Circuit switch (SXSWI) function is to provide the actual status of
positions and to perform the control operations, that is, pass all the commands to
primary apparatuses in the form of disconnectors or earthing switches via output
boards and to supervise the switching operation and position.
The users of the Circuit switch (SXSWI) is other functions such as for example,
switch controller, protection functions, autorecloser function, or a 61850 client
residing in another IED or the operator place. SXSWI executes commands,
evaluates block conditions and evaluates different time supervision conditions.
Only if all conditions indicate a switch operation to be allowed, SXSWI performs
the execution command. In case of erroneous conditions, the function indicates an
appropriate "cause" value.
SXSWI has an operation counter for closing and opening commands. The counter
value can be read remotely from the operator place. The value is reset from a
binary input or remotely from the operator place by configuring a signal from the
Single Point Generic Control 8 signals (SPC8GGIO) for example.
Local/Remote switch
One binary input signal LR_SWI is included in SXSWI to indicate the local/remote
switch position from switchyard provided via the I/O board. If this signal is set to
TRUE it means that change of position is allowed only from switchyard level. If
the signal is set to FALSE it means that command from IED or higher level is
permitted. When the signal is set to TRUE all commands (for change of position)
from internal IED clients are rejected, even trip commands from protection
functions are rejected. The functionality of the local/remote switch is described in
figure 296.
Local= Operation at
RU
E switch yard level
T
en05000096.vsd
IEC05000096 V1 EN
Blocking principles
SXSWI includes several blocking principles. The basic principle for all blocking
signals is that they will affect commands from all other clients for example,
operators place, protection functions, autorecloser and so on.
537
Technical reference manual
Section 12 1MRK505183-UEN C
Control
Substitution
The substitution part in SXSWI is used for manual set of the position for the
switch. The typical use of substitution is that an operator enters a manual value
because the real process value is erroneous of some reason. SXSWI will then use
the manually entered value instead of the value for positions determined by the
process.
Time diagrams
There are two timers for supervising of the execute phase, tStartMove and
tIntermediate. tStartMove supervises that the primary device starts moving after the
execute output pulse is sent. tIntermediate defines the maximum allowed time for
intermediate position. Figure 297 explains these two timers during the execute phase.
538
Technical reference manual
1MRK505183-UEN C Section 12
Control
OPENPOS
CLOSEPOS
en05000097.vsd
IEC05000097 V1 EN
The timers tOpenPulse and tClosePulse are the length of the execute output pulses
to be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be
adaptive with the configuration parameter AdaptivePulse. Figure 298 shows the
principle of the execute output pulse. The AdaptivePulse parameter will have affect
on both execute output pulses.
OPENPOS
CLOSEPOS
AdaptivePulse=FALSE
EXE_CL
tClosePulse
AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN
If the pulse is set to be adaptive, it is not possible for the pulse to exceed
tOpenPulse or tClosePulse.
539
Technical reference manual
Section 12 1MRK505183-UEN C
Control
• the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.
There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in close
position and a close command is executed. In these cases, with the additional
condition that the configuration parameter AdaptivePulse is true, the execute output
pulse is always activated and resets when tStartMove has elapsed. If the
configuration parameter AdaptivePulse is set to false the execution output remains
active until the pulse duration timer has elapsed.
OPENPOS
CLOSEPOS
EXE_OP AdaptivePulse=FALSE
tOpenPulse
EXE_OP AdaptivePulse=TRUE
tOpenPulse
tStartMove timer
en05000099.vsd
IEC05000099 V1 EN
540
Technical reference manual
1MRK505183-UEN C Section 12
Control
IEC05000339-2-en.vsd
IEC05000339 V2 EN
541
Technical reference manual
Section 12 1MRK505183-UEN C
Control
12.3.9.1 Introduction
The Bay reserve (QCRSV) function handles the reservation. QCRSV function
starts to operate in two ways. It starts when there is a request for reservation of the
own bay or if there is a request for reservation from another bay. It is only possible
to reserve the function if it is not currently reserved. The signal that can reserve the
own bay is the input signal RES_RQx (x=1-8) coming from switch controller
(SCWI). The signals for request from another bay are the outputs RE_RQ_B and
V_RE_RQ from function block RESIN. These signals are included in signal
EXCH_OUT from RESIN and are connected to RES_DATA in QCRSV.
The parameters ParamRequestx (x=1-8) are chosen at reservation of the own bay
only (TRUE) or other bays (FALSE). To reserve the own bay only means that no
reservation request RES_BAYS is created.
542
Technical reference manual
1MRK505183-UEN C Section 12
Control
If the RESERVED output is not set, the selection is made with the output
RES_GRTx (where x=1-8 is the number of the requesting apparatus), which is
connected to switch controller SCSWI. If the bay already is reserved the command
sequence will be reset and the SCSWI will set the attribute "1-of-n-control" in the
"cause" signal.
When it receives acknowledge from the bays via the input RES_DATA, it sets the
output RES_GRTx (where x=1-8 is the number of the requesting apparatus). If not
acknowledgement from all bays is received within a certain time defined in SCSWI
(tResResponse), the SCSWI will reset the reservation and set the attribute "1-of-n-
control" in the "cause" signal.
The reservation function can also be overridden in the own bay with the
OVERRIDE input signal, that is, reserving the own bay without waiting for the
external acknowledge.
543
Technical reference manual
Section 12 1MRK505183-UEN C
Control
If there are more than eight apparatuses in the bay there has to be one additional
QCRSV. The two QCRSV functions have to communicate and this is done through
the input EXCH_IN and EXCH_OUT according to figure 301. If more then one
QCRSV are used, the execution order is very important. The execution order must
be in the way that the first QCRSV has a lower number than the next one.
QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_RQ2 RES_GRT3
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6
RES_RQ6 RES_GRT7
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLK_RES ACK_TO_B
OVERRIDE RESERVED
RES_DATA EXCH_OUT
QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_BAYS
RES_RQ2 RES_GRT3 ³1
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6 ACK_TO_B
RES_RQ6 RES_GRT7 ³1
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLK_RES ACK_TO_B RESERVED
³1
OVERRIDE RESERVED
RES_DATA EXCH_OUT
IEC05000088_2_en.vsd
IEC05000088 V2 EN
IEC05000340-2-en.vsd
IEC05000340 V2 EN
544
Technical reference manual
1MRK505183-UEN C Section 12
Control
545
Technical reference manual
Section 12 1MRK505183-UEN C
Control
12.3.10.1 Introduction
The Reservation input (RESIN) function receives the reservation information from
other bays. The number of instances is the same as the number of involved bays
(up to 60 instances are available).
546
Technical reference manual
1MRK505183-UEN C Section 12
Control
EXCH_IN INT
BIN
ACK_F_B
&
FutureUse
³1
ANY_ACK
BAY_ACK ³1
VALID_TX
&
BAY_VAL ³1
RE_RQ_B
³1
BAY_RES &
V _RE_RQ
³1
BIN
EXCH_OUT
INT
en05000089.vsd
IEC05000089 V1 EN
Figure 304 describes the principle of the data exchange between all RESIN
modules in the current bay. There is one RESIN function block per "other bay"
used in the reservation mechanism. The output signal EXCH_OUT in the last
RESIN functions are connected to the module bay reserve (QCRSV) that handles
the reservation function in the own bay. The value to the input EXCH_IN on the
first RESIN module in the chain has the integer value 5. This is provided by the use
of instance number one of the function block RESIN, where the input EXCH_IN is
set to #5, but is hidden for the user.
547
Technical reference manual
Section 12 1MRK505183-UEN C
Control
RESIN
BAY_ACK ACK_F_B
Bay 1 BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT
RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
Bay 2 BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT
RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
Bay n BAY_VAL VALID_TX
BAY_RES RE_RQ_B QCRSV
V_RE_RQ
EXCH_OUT RES_DATA
en05000090.vsd
IEC05000090 V2 EN
IEC05000341-2-en.vsd
IEC05000341 V2 EN
RESIN2
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC09000807_1_en.vsd
IEC09000807 V1 EN
548
Technical reference manual
1MRK505183-UEN C Section 12
Control
549
Technical reference manual
Section 12 1MRK505183-UEN C
Control
12.4 Interlocking
12.4.1 Introduction
The interlocking function blocks the possibility to operate high-voltage switching
devices, for instance when a disconnector is under load, in order to prevent
material damage and/or accidental human injury.
Each control IED has interlocking functions for different switchyard arrangements,
each handling the interlocking of one bay. The function is distributed to each
control IED and not dependent on any central function. For the station-wide
interlocking, the IEDs communicate via the station bus or by using hard wired
binary inputs/outputs.
The interlocking conditions depend on the circuit configuration and status of the
installation at any given time.
After the selection and reservation of an apparatus, the function has complete data
on the status of all apparatuses in the switchyard that are affected by the selection.
550
Technical reference manual
1MRK505183-UEN C Section 12
Control
Other operators cannot interfere with the reserved apparatus or the status of
switching devices that may affect it.
The open or closed positions of the HV apparatuses are inputs to software modules
distributed in the control IEDs. Each module contains the interlocking logic for a
bay. The interlocking logic in a module is different, depending on the bay function
and the switchyard arrangements, that is, double-breaker or 1 1/2 breaker bays have
different modules. Specific interlocking conditions and connections between
standard interlocking modules are performed with an engineering tool. Bay-level
interlocking signals can include the following kind of information:
Apparatus control
Interlocking
modules
modules in
SCILO SCSWI
other bays SXSWI
Apparatus control
modules
Interlocking SCILO SCSWI SXCBR
module
Apparatus control
modules
en04000526.vsd SCILO SCSWI SXSWI
IEC04000526 V1 EN
Bays communicate via the station bus and can convey information regarding the
following:
• Unearthed busbars
• Busbars connected together
• Other bays connected to a busbar
• Received data from other bays is valid
551
Technical reference manual
Section 12 1MRK505183-UEN C
Control
Station bus
Disc QB1 and QB2 closed Disc QB1 and QB2 closed WA1 unearthed
WA1 unearthed
WA1 and WA2 interconn
...
WA1 not earthed WA1 not earthed
WA2 not earthed WA2 not earthed WA1 and WA2 interconn
WA1 and WA2 interconn WA1 and WA2 interconn in other bay
..
WA1
WA2
QB1 QB2 QB1 QB2 QB1 QB2 QC1 QC2
QB9 QB9
en05000494.vsd
IEC05000494 V1 EN
When invalid data such as intermediate position, loss of a control IED, or input
board error are used as conditions for the interlocking condition in a bay, a release
for execution of the function will not be given.
On the local HMI an override function exists, which can be used to bypass the
interlocking function in cases where not all the data required for the condition is valid.
552
Technical reference manual
1MRK505183-UEN C Section 12
Control
The input signals EXDU_xx shall be set to true if there is no transmission error at
the transfer of information from other bays. Required signals with designations
ending in TR are intended for transfer to other bays.
12.4.3.1 Introduction
The Logical node for interlocking SCILO function is used to enable a switching
operation if the interlocking conditions permit. SCILO function itself does not
provide any interlocking functionality. The interlocking conditions are generated in
separate function blocks containing the interlocking logic.
The function contains logic to enable the open and close commands respectively if
the interlocking conditions are fulfilled. That means also, if the switch has a
defined end position for example, open, then the appropriate enable signal (in this
case EN_OPEN) is false. The enable signals EN_OPEN and EN_CLOSE can be
true at the same time only in the intermediate and bad position state and if they are
enabled by the interlocking function. The position inputs come from the logical
nodes Circuit breaker/Circuit switch (SXCBR/SXSWI) and the enable signals
553
Technical reference manual
Section 12 1MRK505183-UEN C
Control
come from the interlocking logic. The outputs are connected to the logical node
Switch controller (SCSWI). One instance per switching device is needed.
POSOPEN SCILO
POSCLOSE =1 1
EN_OPEN
&
>1
&
OPEN_EN
CLOSE_EN & EN_CLOSE
>1
&
en04000525.vsd
IEC04000525 V1 EN
IEC05000359-2-en.vsd
IEC05000359 V2 EN
554
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.4.4.1 Introduction
The interlocking for busbar earthing switch (BB_ES) function is used for one
busbar earthing switch on any busbar parts according to figure 311.
QC
en04000504.vsd
IEC04000504 V1 EN
IEC05000347-2-en.vsd
IEC05000347 V2 EN
QC_OP BBESOPTR
QC_CL BBESCLTR
en04000546.vsd
IEC04000546 V1 EN
555
Technical reference manual
Section 12 1MRK505183-UEN C
Control
12.4.5.1 Introduction
The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-
section circuit breaker between section 1 and 2 according to figure 313. The
function can be used for different busbars, which includes a bus-section circuit
breaker.
QA1
QC3 QC4
en04000516.vsd
A1A2_BS
IEC04000516 V1 EN
556
Technical reference manual
1MRK505183-UEN C Section 12
Control
IEC05000348-2-en.vsd
IEC05000348 V2 EN
557
Technical reference manual
Section 12 1MRK505183-UEN C
Control
VPQB1 QA1CLREL
VPQB2 & QA1CLITL
1
VPQA1
VPQC3 QB1REL
& >1
VPQC4 QB1ITL
1
VPS1QC1
QA1_OP
QC3_OP
QC4_OP
S1QC1_OP
EXDU_ES
QB1_EX1
VPQC3
VPS1QC1
&
QC3_CL
S1QC1_CL
EXDU_ES
QB1_EX2
en04000542.vsd
IEC04000542 V1 EN
558
Technical reference manual
1MRK505183-UEN C Section 12
Control
VPQA1
VPQC3 QB2REL
VPQC4 & >1
QB2ITL
VPS2QC2 1
QA1_OP
QC3_OP
QC4_OP
S2QC2_OP
EXDU_ES
QB2_EX1
VPQC4
VPS2QC2
&
QC4_CL
S2QC2_CL
EXDU_ES
QB2_EX2
VPQB1 QC3REL
VPQB2 QC3ITL
QB1_OP & 1
QC4REL
QB2_OP
QC4ITL
1
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB1_OP S1S2OPTR
QB2_OP >1 S1S2CLTR
QA1_OP 1
VPQB1
VPS1S2TR
VPQB2 &
VPQA1
en04000543.vsd
IEC04000543 V1 EN
559
Technical reference manual
Section 12 1MRK505183-UEN C
Control
560
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.4.6.1 Introduction
The interlocking for bus-section disconnector (A1A2_DC) function is used for one
bus-section disconnector between section 1 and 2 according to figure 315.
A1A2_DC function can be used for different busbars, which includes a bus-section
disconnector.
QB
WA1 (A1) WA2 (A2)
QC1 QC2
A1A2_DC en04000492.vsd
IEC04000492 V1 EN
IEC05000349-2-en.vsd
IEC05000349 V2 EN
561
Technical reference manual
Section 12 1MRK505183-UEN C
Control
EXDU_BB
QBOP_EX1
VPS1QC1
VPS2QC2
VPS2_DC &
S1QC1_OP
S2QC2_OP
S2DC_OP
EXDU_ES
EXDU_BB
QBOP_EX2
VPS1QC1
VPS2QC2
S1QC1_CL &
S2QC2_CL
EXDU_ES
QBOP_EX3
en04000544.vsd
IEC04000544 V1 EN
IEC04000545 V1 EN
562
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.4.7.1 Introduction
The interlocking for bus-coupler bay (ABC_BC) function is used for a bus-coupler
bay connected to a double busbar arrangement according to figure 317. The
function can also be used for a single busbar arrangement with transfer busbar or
double busbar arrangement without transfer busbar.
563
Technical reference manual
Section 12 1MRK505183-UEN C
Control
WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB20 QB7
QC1
QA1
QC2
en04000514.vsd
IEC04000514 V1 EN
IEC05000350-2-en.vsd
IEC05000350 V2 EN
564
Technical reference manual
1MRK505183-UEN C Section 12
Control
IEC04000533 V1 EN
VPQA1
VPQB2 QB1REL
& >1
VPQC1 QB1ITL
VPQC2 1
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VP_BC_12
&
QB2_CL
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX3
en04000534.vsd
IEC04000534 V1 EN
565
Technical reference manual
Section 12 1MRK505183-UEN C
Control
VPQA1
VPQB1 QB2REL
& >1
VPQC1 QB2ITL
VPQC2 1
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VP_BC_12
&
QB1_CL
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC21
&
QC1_CL
QC21_CL
EXDU_ES
QB2_EX3
en04000535.vsd
IEC04000535 V1 EN
VPQA1
VPQB20 QB7REL
& >1
VPQC1 QB7ITL
VPQC2 1
VPQC71
QA1_OP
QB20_OP
QC1_OP
QC2_OP
QC71_OP
EXDU_ES
QB7_EX1
VPQC2
VPQC71
&
QC2_CL
QC71_CL
EXDU_ES
QB7_EX2
VPQA1
VPQB7 QB20REL
& >1
VPQC1 QB20ITL
VPQC2 1
VPQC21
QA1_OP
QB7_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB20_EX1
VPQC2
VPQC21
&
QC2_CL
QC21_CL
EXDU_ES
QB20_EX2
en04000536.vsd
IEC04000536 V1 EN
566
Technical reference manual
1MRK505183-UEN C Section 12
Control
VPQB1 QC1REL
VPQB20 QC1ITL
& 1
VPQB7
QC2REL
VPQB2
QB1_OP QC2ITL
1
QB20_OP
QB7_OP
QB2_OP
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB20_OP QB220OTR
QB2_OP & QB220CTR
VPQB20 1
VQB220TR
VPQB2 &
QB7_OP QB7OPTR
QB7_CL QB7CLTR
VPQB7 VPQB7TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
QA1_OP BC12OPTR
QB1_OP >1 BC12CLTR
QB20_OP 1
VPQA1
VPBC12TR
VPQB1 &
VPQB20
QA1_OP BC17OPTR
QB1_OP >1 BC17CLTR
QB7_OP 1
VPQA1
VPBC17TR
VPQB1 &
VPQB7
QA1_OP BC27OPTR
QB2_OP >1 BC27CLTR
QB7_OP 1
VPQA1
VPBC27TR
VPQB2 &
VPQB7
en04000537.vsd
IEC04000537 V1 EN
567
Technical reference manual
Section 12 1MRK505183-UEN C
Control
568
Technical reference manual
1MRK505183-UEN C Section 12
Control
569
Technical reference manual
Section 12 1MRK505183-UEN C
Control
12.4.8.1 Introduction
Introduction
The interlocking for 1 1/2 breaker diameter (BH_CONN, BH_LINE_A,
BH_LINE_B) functions are used for lines connected to a 1 1/2 breaker diameter
according to figure 319.
WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC1
QA1 QA1
QC2 QC2
QB6 QB6
QC3 QC3
BH_LINE_A BH_LINE_B
QB9 QB9
QC1 QC2
QC9 QC9
BH_CONN
en04000513.vsd
IEC04000513 V1 EN
Three types of interlocking modules per diameter are defined. BH_LINE_A and
BH_LINE_B are the connections from a line to a busbar. BH_CONN is the
connection between the two lines of the diameter in the 1 1/2 breaker switchyard
layout.
570
Technical reference manual
1MRK505183-UEN C Section 12
Control
IEC05000352-2-en.vsd
IEC05000352 V2 EN
571
Technical reference manual
Section 12 1MRK505183-UEN C
Control
BH_LINE_B
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB6_OP QB6REL
QB6_CL QB6ITL
QB2_OP QB2REL
QB2_CL QB2ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC3_OP QC3REL
QC3_CL QC3ITL
QB9_OP QB9REL
QB9_CL QB9ITL
QC9_OP QC9REL
QC9_CL QC9ITL
CQA1_OP QB2OPTR
CQA1_CL QB2CLTR
CQB62_OP VPQB2TR
CQB62_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
QC21_OP
QC21_CL
VOLT_OFF
VOLT_ON
EXDU_ES
QB6_EX1
QB6_EX2
QB2_EX1
QB2_EX2
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
QB9_EX6
QB9_EX7
IEC05000353-2-en.vsd
IEC05000353 V2 EN
BH_CONN
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB61_OP QB61REL
QB61_CL QB61ITL
QB62_OP QB62REL
QB62_CL QB62ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
1QC3_OP
1QC3_CL
2QC3_OP
2QC3_CL
QB61_EX1
QB61_EX2
QB62_EX1
QB62_EX2
IEC05000351-2-en.vsd
IEC05000351 V2 EN
572
Technical reference manual
1MRK505183-UEN C Section 12
Control
IEC04000560 V1 EN
573
Technical reference manual
Section 12 1MRK505183-UEN C
Control
BH_LINE_A
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB6_OP
QB6_CL =1 VPQB6
QC9_OP
QC9_CL =1 VPQC9
QB9_OP
QB9_CL =1 VPQB9
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
CQA1_OP
CQA1_CL =1 VPCQA1
CQC1_OP
CQC1_CL =1 VPCQC1
CQC2_OP
CQC2_CL =1 VPCQC2
CQB61_OP
CQB61_CL =1 VPCQB61
QC11_OP
QC11_CL =1 VPQC11
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQB1 QA1CLREL
VPQB6 QA1CLITL
& 1
VPQB9
VPQA1
VPQC1 QB6REL
VPQC2 & >1
QB6ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB6_EX2
en04000554.vsd
IEC04000554 V1 EN
574
Technical reference manual
1MRK505183-UEN C Section 12
Control
VPQA1
VPQC1 QB1REL
VPQC2 & >1
QB1ITL
1
VPQC11
QA1_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2
VPQB1 QC1REL
VPQB6 QC1ITL
QB1_OP & 1
QC2REL
QB6_OP QC2ITL
VPQB6 1
VPQB9 QC3REL
VPCQB61 &
QC3ITL
1
QB6_OP
QB9_OP
CQB61_OP
VPQA1 QB9REL
VPQB6 QB9ITL
VPQC9 & >1 1
VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB61
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
>1
QA1_OP
QC1_OP
QC2_OP &
QB9_EX3
en04000555.vsd
IEC04000555 V1 EN
CQB61_OP
QB9_EX4
>1 & >1
CQA1_OP
CQC1_OP
CQC2_OP &
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
&
QC9_CL
QC3_CL
QB9_EX7
VPQB9 QC9REL
VPVOLT QC9ITL
QB9_OP & 1
VOLT_OFF
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
en04000556.vsd
IEC04000556 V1 EN
575
Technical reference manual
Section 12 1MRK505183-UEN C
Control
BH_LINE_B
QA1_OP
QA1_CL =1 VPQA1
QB2_OP
QB2_CL =1 VPQB2
QB6_OP
QB6_CL =1 VPQB6
QC9_OP
QC9_CL =1 VPQC9
QB9_OP
QB9_CL =1 VPQB9
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
CQA1_OP
CQA1_CL =1 VPCQA1
CQC1_OP
CQC1_CL =1 VPCQC1
CQC2_OP
CQC2_CL =1 VPCQC2
CQB62_OP
CQB62_CL =1 VPCQB62
QC21_OP
QC21_CL =1 VPQC21
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQB2 QA1CLREL
VPQB6 QA1CLITL
& 1
VPQB9
VPQA1
VPQC1 QB6REL
VPQC2 & >1
QB6ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB6_EX2
en04000557.vsd
IEC04000557 V1 EN
576
Technical reference manual
1MRK505183-UEN C Section 12
Control
VPQA1
VPQC1 QB2REL
VPQC2 & >1
QB2ITL
1
VPQC21
QA1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQC1
VPQC21
&
QC1_CL
QC21_CL
EXDU_ES
QB2_EX2
VPQB2 QC1REL
VPQB6 QC1ITL
QB2_OP & 1
QC2REL
QB6_OP QC2ITL
VPQB6 1
VPQB9 QC3REL
VPCQB62 &
QC3ITL
1
QB6_OP
QB9_OP
CQB62_OP
VPQA1 QB9REL
VPQB6 QB9ITL
VPQC9 & >1 1
VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB62
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
>1
QA1_OP
QC1_OP
QC2_OP &
QB9_EX3
en04000558.vsd
IEC04000558 V1 EN
CQB62_OP
QB9_EX4
>1 & >1
CQA1_OP
CQC1_OP
CQC2_OP &
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
&
QC9_CL
QC3_CL
QB9_EX7
VPQB9 QC9REL
VPVOLT QC9ITL
QB9_OP & 1
VOLT_OFF
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
en04000559.vsd
IEC04000559 V1 EN
577
Technical reference manual
Section 12 1MRK505183-UEN C
Control
578
Technical reference manual
1MRK505183-UEN C Section 12
Control
579
Technical reference manual
Section 12 1MRK505183-UEN C
Control
580
Technical reference manual
1MRK505183-UEN C Section 12
Control
581
Technical reference manual
Section 12 1MRK505183-UEN C
Control
12.4.9.1 Introduction
582
Technical reference manual
1MRK505183-UEN C Section 12
Control
WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC4
QA1 QA2
DB_BUS_A DB_BUS_B
QC2 QC5
QB61 QB62
QC3
QB9
DB_LINE
QC9
en04000518.vsd
IEC04000518 V1 EN
Three types of interlocking modules per double circuit breaker bay are defined.
DB_LINE is the connection from the line to the circuit breaker parts that are
connected to the busbars. DB_BUS_A and DB_BUS_B are the connections from
the line to the busbars.
en05000354.vsd
IEC05000354 V1 EN
583
Technical reference manual
Section 12 1MRK505183-UEN C
Control
DB_LINE
QA1_OP QB9REL
QA1_CL QB9ITL
QA2_OP QC3REL
QA2_CL QC3ITL
QB61_OP QC9REL
QB61_CL QC9ITL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QB62_OP
QB62_CL
QC4_OP
QC4_CL
QC5_OP
QC5_CL
QB9_OP
QB9_CL
QC3_OP
QC3_CL
QC9_OP
QC9_CL
VOLT_OFF
VOLT_ON
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
IEC05000356-2-en.vsd
IEC05000356 V2 EN
DB_BUS_B
QA2_OP QA2CLREL
QA2_CL QA2CLITL
QB2_OP QB62REL
QB2_CL QB62ITL
QB62_OP QB2REL
QB62_CL QB2ITL
QC4_OP QC4REL
QC4_CL QC4ITL
QC5_OP QC5REL
QC5_CL QC5ITL
QC3_OP QB2OPTR
QC3_CL QB2CLTR
QC21_OP VPQB2TR
QC21_CL
EXDU_ES
QB62_EX1
QB62_EX2
QB2_EX1
QB2_EX2
IEC05000355-2-en.vsd
IEC05000355 V2 EN
584
Technical reference manual
1MRK505183-UEN C Section 12
Control
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2
en04000547.vsd
IEC04000547 V1 EN
VPQB61 QC1REL
VPQB1 QC1ITL
& 1
QB61_OP QC2REL
QB1_OP QC2ITL
1
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
en04000548.vsd
IEC04000548 V1 EN
585
Technical reference manual
Section 12 1MRK505183-UEN C
Control
DB_BUS_B
QA2_OP
QA2_CL =1 VPQA2
QB62_OP
QB62_CL =1 VPQB62
QB2_OP
QB2_CL =1 VPQB2
QC4_OP
QC4_CL =1 VPQC4
QC5_OP
QC5_CL =1 VPQC5
QC3_OP
QC3_CL =1 VPQC3
QC21_OP
QC21_CL =1 VPQC21
VPQB62 QA2CLREL
VPQB2 & QA2CLITL
1
VPQA2
VPQC4 QB62REL
& >1
VPQC5 QB62ITL
1
VPQC3
QA2_OP
QC4_OP
QC5_OP
QC3_OP
QB62_EX1
VPQC5
VPQC3
&
QC5_CL
QC3_CL
QB62_EX2
VPQA2
VPQC4 QB2REL
& >1
VPQC5 QB2ITL
1
VPQC21
QA2_OP
QC4_OP
QC5_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQC4
VPQC21
&
QC4_CL
QC21_CL
EXDU_ES
QB2_EX2
en04000552.vsd
IEC04000552 V1 EN
VPQB62 QC4REL
VPQB2 QC4ITL
& 1
QB62_OP QC5REL
QB2_OP QC5ITL
1
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
en04000553.vsd
IEC04000553 V1 EN
586
Technical reference manual
1MRK505183-UEN C Section 12
Control
DB_LINE
QA1_OP
QA1_CL =1 VPQA1
QA2_OP
QA2_CL =1 VPQA2
QB61_OP
QB61_CL =1 VPQB61
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QB62_OP
QB62_CL =1 VPQB62
QC4_OP
QC4_CL =1 VPQC4
QC5_OP
QC5_CL =1 VPQC5
QB9_OP
QB9_CL =1 VPQB9
QC3_OP
QC3_CL =1 VPQC3
QC9_OP
QC9_CL =1 VPQC9
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQA1
VPQA2 QB9REL
VPQC1 & >1
QB9ITL
1
VPQC2
VPQC3
VPQC4
VPQC5
VPQC9
QA1_OP
QA2_OP
QC1_OP
QC2_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX1
& en04000549.vsd
IEC04000549 V1 EN
VPQA1
VPQC1
VPQC2 & >1
VPQC3
VPQC9
VPQB62
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QC9_OP
QB62_OP
QB9_EX2
VPQA2
VPQB61
&
VPQC3
VPQC4
VPQC5
VPQC9
QA2_OP
QB61_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX3
VPQC3
VPQC9
&
VPQB61
VPQB62
QC3_OP
QC9_OP
QB61_OP
QB62_OP
QB9_EX4
VPQC3
VPQC9
&
QC3_CL
QC9_CL
QB9_EX5
en04000550.vsd
IEC04000550 V1 EN
587
Technical reference manual
Section 12 1MRK505183-UEN C
Control
VPQB61
VPQB62 QC3REL
VPQB9 &
QC3ITL
1
QB61_OP
QB62_OP
QB9_OP
VPQB9
VPVOLT QC9REL
QB9_OP &
QC9ITL
1
VOLT_OFF
en04000551.vsd
IEC04000551 V1 EN
588
Technical reference manual
1MRK505183-UEN C Section 12
Control
589
Technical reference manual
Section 12 1MRK505183-UEN C
Control
590
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.4.10.1 Introduction
The interlocking for line bay (ABC_LINE) function is used for a line connected to
a double busbar arrangement with a transfer busbar according to figure 327. The
function can also be used for a double busbar arrangement without transfer busbar
or a single busbar arrangement with/without transfer busbar.
WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB7
QC1
QA1
QC2
QB9
QC9
en04000478.vsd
IEC04000478 V1 EN
591
Technical reference manual
Section 12 1MRK505183-UEN C
Control
IEC05000357-2-en.vsd
IEC05000357 V2 EN
592
Technical reference manual
1MRK505183-UEN C Section 12
Control
ABC_LINE
QA1_OP
QA1_CL =1 VPQA1
QB9_OP
QB9_CL =1 VPQB9
QA1CLREL
QB1_OP
QB1_CL =1 VPQB1 QA1CLITL
& 1
QB2_OP
QB2_CL =1 VPQB2
QB7_OP
QB7_CL =1 VPQB7
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC9_OP
QC9_CL =1 VPQC9
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
QC71_OP
QC71_CL =1 VPQC71
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQA1
VPQC1 QB9REL
VPQC2 & >1
QB9ITL
1
VPQC9
QA1_OP
QC1_OP
QC2_OP
QC9_OP
QB9_EX1
VPQC2
VPQC9
&
QC2_CL
QC9_CL
QB9_EX2
en04000527.vsd
IEC04000527 V1 EN
593
Technical reference manual
Section 12 1MRK505183-UEN C
Control
VPQA1 QB1REL
& ³1
VPQB2
VPQC1 1 QB1ITL
VPQC2
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2 &
VP_BC_12
QB2_CL
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1 &
VPQC11
QC1_CL
QC11_CL
EXDU_ES
QB1EX3
en04000528.vsd
IEC04000528 V1 EN
594
Technical reference manual
1MRK505183-UEN C Section 12
Control
VPQA1 QB2REL
& ³1
VPQB1
VPQC1 1 QB2ITL
VPQC2
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1 &
VP_BC_12
QB1_CL
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1 &
VPQC21
QC1_CL
QC21_CL
EXDU_ES
QB2_EX3
en04000529.vsd
IEC04000529 V1 EN
595
Technical reference manual
Section 12 1MRK505183-UEN C
Control
VPQC9 QB7REL
& >1
VPQC71
VP_BB7_D 1 QB7ITL
VP_BC_17
VP_BC_27
QC9_OP
QC71_OP
EXDU_ES
BB7_D_OP
EXDU_BPB
BC_17_OP
BC_27_OP
EXDU_BC
QB7_EX1
VPQA1
VPQB1
VPQC9
&
VPQB9
VPQC71
VP_BB7_D
VP_BC_17
QA1_CL
QB1_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES
BB7_D_OP
EXDU_BPB
BC_17_CL
EXDU_BC
QB7_EX2
IEC04000530 V1 EN
596
Technical reference manual
1MRK505183-UEN C Section 12
Control
VPQA1
VPQB2
& >1
VPQC9
VPQB9
VPQC71
VP_BB7_D
VP_BC_27
QA1_CL
QB2_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES
BB7_D_OP
EXDU_BPB
BC_27_CL
EXDU_BC
QB7_EX3
VPQC9
VPQC71
&
QC9_CL
QC71_CL
EXDU_ES
QB7_EX4
VPQB1 QC1REL
VPQB2 QC1ITL
VPQB9 & 1
QC2REL
QB1_OP
QB2_OP QC2ITL
1
QB9_OP
VPQB7
VPQB9 QC9REL
VPVOLT &
QC9ITL
QB7_OP 1
QB9_OP
VOLT_OFF
en04000531.vsd
IEC04000531 V1 EN
597
Technical reference manual
Section 12 1MRK505183-UEN C
Control
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB7_OP QB7OPTR
QB7_CL QB7CLTR
VPQB7 VPQB7TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000532.vsd
IEC04000532 V1 EN
598
Technical reference manual
1MRK505183-UEN C Section 12
Control
599
Technical reference manual
Section 12 1MRK505183-UEN C
Control
600
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.4.11.1 Introduction
WA1 (A)
WA2 (B)
QB1 QB2
QC1
QA1
AB_TRAFO
QC2
QC3
QA2
QA2 and QC4 are not
QC4 used in this interlocking
QB3 QB4
en04000515.vsd
IEC04000515 V1 EN
601
Technical reference manual
Section 12 1MRK505183-UEN C
Control
IEC05000358-2-en.vsd
IEC05000358 V2 EN
602
Technical reference manual
1MRK505183-UEN C Section 12
Control
VPQC2
VPQB3
VPQB4
VPQC3
QA1_EX2
QC3_OP
QA1_EX3
QC1_CL >1
QC2_CL
QC3_CL &
QA1_EX1
en04000538.vsd
IEC04000538 V1 EN
VPQA1
VPQB2 QB1REL
& >1
VPQC1 QB1ITL
VPQC2 1
VPQC3
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC3_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VPQC3
&
VP_BC_12
QB2_CL
QC3_OP
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC2
&
VPQC3
VPQC11
QC1_CL
QC2_CL
QC3_CL
QC11_CL
EXDU_ES
QB1_EX3
en04000539.vsd
IEC04000539 V1 EN
603
Technical reference manual
Section 12 1MRK505183-UEN C
Control
VPQA1
VPQB1 QB2REL
& >1
VPQC1 QB2ITL
VPQC2 1
VPQC3
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC3_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VPQC3
&
VP_BC_12
QB1_CL
QC3_OP
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC2
&
VPQC3
VPQC21
QC1_CL
QC2_CL
QC3_CL
QC21_CL
EXDU_ES
QB2_EX3
en04000540.vsd
IEC04000540 V1 EN
VPQB1 QC1REL
VPQB2 QC1ITL
& 1
VPQB3
QC2REL
VPQB4
QB1_OP QC2ITL
1
QB2_OP
QB3_OP
QB4_OP
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000541.vsd
IEC04000541 V1 EN
604
Technical reference manual
1MRK505183-UEN C Section 12
Control
605
Technical reference manual
Section 12 1MRK505183-UEN C
Control
12.4.12.1 Introduction
Position evaluation (POS_EVAL) function converts the input position data signal
POSITION, consisting of value, time and signal status, to binary signals
OPENPOS or CLOSEPOS.
The output signals are used by other functions in the interlocking scheme.
IEC08000469-1-en.vsd
IEC08000469-1-EN V1 EN
Only the value, open/close, and status is used in this function. Time information is
not used.
Input position (Value) Signal quality Output OPENPOS Output CLOSEPOS
0 (Breaker Good 0 0
intermediate)
1 (Breaker open) Good 1 0
2 (Breaker closed) Good 0 1
3 (Breaker faulty) Good 0 0
Any Invalid 0 0
Any Oscillatory 0 0
606
Technical reference manual
1MRK505183-UEN C Section 12
Control
IEC09000079_1_en.vsd
IEC09000079 V1 EN
12.5.1 Introduction
The logic rotating switch for function selection and LHMI presentation function
(SLGGIO) (or the selector switch function block) is used to get a selector switch
functionality similar with the one provided by a hardware selector switch.
Hardware selector switches are used extensively by utilities, in order to have
different functions operating on pre-set values. Hardware switches are however
sources for maintenance issues, lower system reliability and extended purchase
portfolio. The virtual selector switches eliminate all these problems.
607
Technical reference manual
Section 12 1MRK505183-UEN C
Control
in ascending order (if the present activated output is 3 – for example and one
operates the UP input, then the output 4 will be activated). When a signal is
received on the DOWN input, the block will activate the output next to the present
activated output, in descending order (if the present activated output is 3 – for
example and one operates the DOWN input, then the output 2 will be activated).
Depending on the output settings the output signals can be steady or pulsed. In case
of steady signals, in case of UP or DOWN operation, the previously active output
will be deactivated. Also, depending on the settings one can have a time delay
between the UP or DOWN activation signal positive front and the output activation.
608
Technical reference manual
1MRK505183-UEN C Section 12
Control
Control
Control Single Line Diagram Ctrl/Com
Measurements Commands Single Command
Events Selector Switch (GGIO)
Disturbance records
Settings
Diagnostics
Test
Reset
Authorization
Language
1 2 3
../Com/Sel Sw/ ../Com/Sel Sw/
../Ctrl/Com/Sel Sw SLGGIO3
SLGGIO1 SLGGIO3
Damage ctrl 4 Damage ctrl 4
SLGGIO2
..
..
SLGGIO15
OK Cancel
4
5
The dialog window that appears
../Com/Sel Sw/ shows the present position (P:)
DmgCtrl 7
and the new position (N:), both
Damage ctrl: in clear names, given by the
user (max. 13 characters).
E
Modify the position with arrows.
The pos will not be modified (outputs
will not be activated) until you press
the E-button for O.K. IEC06000420-2-en.vsd
IEC06000420 V2 EN
Figure 332: Example 1 on handling the switch from the local HMI.
From the local HMI:
609
Technical reference manual
Section 12 1MRK505183-UEN C
Control
• if it is used just for the monitoring, the switches will be listed with their actual
position names, as defined by the user (max. 13 characters).
• if it is used for control, the switches will be listed with their actual positions,
but only the first three letters of the name will be used.
In both cases, the switch full name will be shown, but the user has to redefine it
when building the Graphical Display Editor, under the "Caption". If used for the
control, the following sequence of commands will ensure:
Control
Control Single Line Diagram
Measurements Commands
Events
Disturbance records
Settings
Diagnostics
Test
Change to the "Switches" page Reset
of the SLD by left-right arrows. Authorization
Select switch by up-down Language
arrows
../Control/SLD/Switch
O I ../Control/SLD/Switch
SMBRREC control SMBRREC control
WFM Select switch. Press the
WFM
I or O key. A dialog box
Pilot setup appears.
Pilot setup
OFF OFF
Damage control E P: Disc N: Disc Fe
DAL
The pos will not be modified
(outputs will not be activated) until OK Cancel
you press the E-button for O.K.
../Control/SLD/Switch
SMBRREC control
WFM
Pilot setup
OFF
Damage control
DFW
IEC06000421-2-en.vsd
IEC06000421 V2 EN
Figure 333: Example 2 on handling the switch from the local HMI.
From the single line diagram on local HMI.
610
Technical reference manual
1MRK505183-UEN C Section 12
Control
IEC05000658-2-en.vsd
IEC05000658 V2 EN
611
Technical reference manual
Section 12 1MRK505183-UEN C
Control
612
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.6.1 Introduction
Selector mini switch (VSGGIO) function block is a multipurpose function used in
the configuration tool in PCM600 for a variety of applications, as a general purpose
switch.
VSGGIO can be controlled from the menu or from a symbol on the single line
diagram (SLD) on the local HMI.
• for indication on the single line diagram (SLD). Position is received through
the IPOS1 and IPOS2 inputs and distributed in the configuration through the
POS1 and POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
• for commands that are received via the local HMI or IEC 61850 and
distributed in the configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command
from the local HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command
from the local HMI when the SLD is displayed and the object is chosen.
The PSTO input is connected to the Local remote switch to have a selection of
operators place , operation from local HMI (Local) or through IEC 61850
613
Technical reference manual
Section 12 1MRK505183-UEN C
Control
The following table shows the relationship between IPOS1/IPOS2 inputs and the
name of the string that is shown on the SLD. The value of the strings are set in PST.
IPOS1 IPOS2 Name of displayed string Default string value
0 0 PosUndefined P00
1 0 Position1 P01
0 1 Position2 P10
1 1 PosBadState P11
IEC06000508-2-en.vsd
IEC06000508 V3 EN
614
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.7.1 Introduction
The IEC 61850 generic communication I/O functions (DPGGIO) function block is
used to send three logical signals to other systems or equipment in the substation. It
is especially used in the interlocking and reservation station-wide logics.
615
Technical reference manual
Section 12 1MRK505183-UEN C
Control
IEC07000200-2-en.vsd
IEC07000200 V2 EN
12.7.5 Settings
The function does not have any parameters available in the local HMI or PCM600.
12.8.1 Introduction
The Single point generic control 8 signals (SPC8GGIO) function block is a
collection of 8 single point commands, designed to bring in commands from
REMOTE (SCADA) to those parts of the logic configuration that do not need
complicated function blocks that have the capability to receive commands (for
example, SCSWI). In this way, simple commands can be sent directly to the IED
outputs, without confirmation. Confirmation (status) of the result of the commands
616
Technical reference manual
1MRK505183-UEN C Section 12
Control
IEC07000143-2-en.vsd
IEC07000143 V2 EN
617
Technical reference manual
Section 12 1MRK505183-UEN C
Control
618
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.9.1 Introduction
AutomationBits function for DNP3 (AUTOBITS) is used within PCM600 to get
into the configuration of the commands coming through the DNP3 protocol. The
AUTOBITS function plays the same role as functions GOOSEBINRCV (for IEC
61850) and MULTICMDRCV (for LON).
There is a BLOCK input signal, which will disable the operation of the function, in
the same way the setting Operation: On/Off does. That means that, upon activation
of the BLOCK input, all 32 CMDBITxx outputs will be set to 0. The BLOCK acts
like an overriding, the function still receives data from the DNP3 master. Upon
deactivation of BLOCK, all the 32 CMDBITxx outputs will be set by the DNP3
master again, momentarily. For AUTOBITS , the PSTO input determines the
operator place. The command can be written to the block while in “Remote”. If
PSTO is in “Local” then no change is applied to the outputs.
619
Technical reference manual
Section 12 1MRK505183-UEN C
Control
IEC09000925-1-en.vsd
IEC09000925 V1 EN
620
Technical reference manual
1MRK505183-UEN C Section 12
Control
621
Technical reference manual
Section 12 1MRK505183-UEN C
Control
622
Technical reference manual
1MRK505183-UEN C Section 12
Control
623
Technical reference manual
Section 12 1MRK505183-UEN C
Control
624
Technical reference manual
1MRK505183-UEN C Section 12
Control
625
Technical reference manual
Section 12 1MRK505183-UEN C
Control
626
Technical reference manual
1MRK505183-UEN C Section 12
Control
627
Technical reference manual
Section 12 1MRK505183-UEN C
Control
628
Technical reference manual
1MRK505183-UEN C Section 12
Control
629
Technical reference manual
Section 12 1MRK505183-UEN C
Control
630
Technical reference manual
1MRK505183-UEN C Section 12
Control
631
Technical reference manual
Section 12 1MRK505183-UEN C
Control
632
Technical reference manual
1MRK505183-UEN C Section 12
Control
633
Technical reference manual
Section 12 1MRK505183-UEN C
Control
634
Technical reference manual
1MRK505183-UEN C Section 12
Control
12.10.1 Introduction
The IEDs can receive commands either from a substation automation system or
from the local HMI. The command function block has outputs that can be used, for
example, to control high voltage apparatuses or for other user defined functionality.
The output signals can be of the types Off, Steady, or Pulse. This configuration
setting is done via the local HMI or PCM600 and is common for the whole
function block. The length of the output pulses are 100 ms. In steady mode,
SINGLECMD function has a memory to remember the output values at power
interruption of the IED. Also a BLOCK input is available used to block the
updating of the outputs.
The output signals, OUT1 to OUT16, are available for configuration to built-in
functions or via the configuration logic circuits to the binary outputs of the IED.
635
Technical reference manual
Section 12 1MRK505183-UEN C
Control
IEC05000698-2-en.vsd
IEC05000698 V3 EN
636
Technical reference manual
1MRK505183-UEN C Section 12
Control
637
Technical reference manual
638
1MRK505183-UEN C Section 13
Scheme communication
The chapter contains a short description of the design, simplified logical block
diagrams, figure of the function block, input and output signals and setting
parameters.
13.1.1 Introduction
To achieve instantaneous fault clearance for all line faults, a scheme
communication logic is provided. All types of communication schemes for
example, permissive underreaching, permissive overreaching, blocking,
unblocking, intertrip are available.
639
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
A permissive scheme is inherently faster and has better security against false
tripping than a blocking scheme. On the other hand, a permissive scheme depends
on a received signal for a fast trip, so its dependability is lower than that of a
blocking scheme.
The received signal, which shall be connected to CR, is used to not release the zone
to be accelerated to clear the fault instantaneously (after time tCoord). The
overreaching zone to be accelerated is connected to the input CACC, see figure 340.
In case of external faults, the blocking signal (CR) must be received before the
settable timer tCoord elapses, to prevent a false trip, see figure 340.
The function can be totally blocked by activating the input BLOCK, block of trip
by activating the input BLKTR, Block of signal send by activating the input BLKCS.
tCoord
CACC
t TRIP
CR AND
en05000512.vsd
IEC05000512 V1 EN
The logic for trip signal in permissive scheme is shown in figure 341.
640
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
tCoord
CACC
t TRIP
CR AND
en05000513.vsd
IEC05000513 V1 EN
The logic for trip signal is the same as for permissive underreaching, as in
figure 341.
The unblocking function uses a guard signal CRG, which must always be present,
even when no CR signal is received. The absence of the CRG signal for a time
longer than the setting tSecurity time is used as a CR signal, see figure 342. This
also enables a permissive scheme to operate when the line fault blocks the signal
transmission.
The received signal created by the unblocking function is reset 150 ms after the
security timer has elapsed. When that occurs an output signal LCG is activated for
signalling purpose. The unblocking function is reset 200 ms after that the guard
signal is present again.
641
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
CR
tSecurity CRL
t >1
1
CRG
200 ms 150 ms
t OR t AND
AND
LCG
en05000746.vsd
IEC05000746 V1 EN
The unblocking function can be set in three operation modes (setting Unblock):
In the direct intertrip scheme, the send signal CS is sent from an underreaching
zone that is tripping the line.
The received signal CR is directly transferred to a TRIP for tripping without local
criteria. The signal is further processed in the tripping logic.
The simplified logic diagram for the complete logic is shown in figure 343.
642
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
Unblock =Off
CR
Unblock =
OR CRL
NoRestart AND
CRL
Unblock =
tSecurit
Restart
y
CRG 1 t AND
SchemeType =
Intertrip
CSUR
tSendMi
n AND
OR
BLOCK AND
CSBLK OR
CRL
Schemetype =
Permissive UR AND CS
OR
tCoord
AND 25 ms
OR
t TRIP
CACC t
Schemetype =
Permissive OR
CSOR OR AND
AND
tSendMin
OR
AND
SchemeType =
Blocking
BLKCS
AND
IEC05000515-2-en.vsd
IEC05000515 V2 EN
643
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
IEC06000286-2-en.vsd
IEC06000286 V2 EN
644
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
645
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
13.2.1 Introduction
Communication between line ends is used to achieve fault clearance for all faults
on a power line. All possible types of communication schemes for example,
permissive underreach, permissive overreach and blocking schemes are available.
To manage problems with simultaneous faults on parallel power lines phase
segregated communication is needed. This will then replace the standard Scheme
communication logic for distance or Overcurrent protection (ZCPSCH) on
important lines where three communication channels (in each subsystem) are
available for the distance protection communication.
The main purpose of the Phase segregated scheme communication logic for
distance protection (ZC1PPSCH) function is to supplement the distance protection
function such that:
• fast clearance of faults is also achieved at the line end for which the faults are
on the part of the line not covered by its underreaching zone.
• correct phase selection can be maintained to support single-pole tripping for
faults occurring anywhere on the entire length of a double circuit line.
To accomplish this, three separate communication channels, that is, one per phase,
each capable of transmitting a signal in each direction is required.
ZC1PPSCH can be completed with the current reversal and WEI logic for phase
segregated communication, when found necessary in Blocking and Permissive
overreaching schemes.
A permissive scheme is inherently faster and has better security against false
tripping than a blocking scheme. On the other hand, a permissive scheme depends
on a received signal for a fast trip, so its dependability is lower than that of a
blocking scheme.
646
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
The ability to select which distance protection zone is assigned to which input of
ZC1PPSCH makes this logic able to support practically any scheme
communication requirements regardless of their basic operating principle. The
outputs to initiate tripping and sending of the teleprotection signal are given in
accordance with the type of communication-aided scheme selected and the zone(s)
and phase(s) of the distance protection which have operated.
When power line carrier communication channels are used for permissive schemes
communication, unblocking logic which uses the loss of guard signal as a receive
criteria is provided. This logic compensates for the lack of dependability due to the
transmission of the command signal over the faulted line.
ZC1PPSCH can be totally blocked by activating the input BLOCK, block of trip is
achieved by activating the input BLKTRLx, Block of carrier send is done by
activating the input BLKCSLx.
tCoord 25 ms
CACCLx
t t TRLx
CRLx AND
IEC06000310_2_en.vsd
IEC06000310 V2 EN
Figure 345: Basic logic for trip carrier in one phase of a blocking scheme
647
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
overreaching zone (connected to CACCLx) to trip after the tCoord timer has
elapsed. The tCoord is in permissive underreach schemes normally set to zero. The
logic for trip carrier in permissive scheme is shown in figure 346. Three channels
for communication in each direction must be available.
tCoord 25 ms
CACCLx t t TRLx
CRLx AND
IEC07000088_2_en.vsd
IEC07000088 V2 EN
Figure 346: Basic logic for trip carrier in one phase of a permissive underreach
scheme
The permissive overreach scheme has the same blocking possibilities as mentioned
for blocking scheme above. The blocking inputs are activated from the current
reversal logic when this function is included.
In the direct intertrip scheme, the carrier send signal CS is sent from an
underreaching zone that is tripping the line.
The received signal per phase is directly transferred to the trip function block for
tripping without local criteria. The signal is not further processed in the phase
segregated communication logic. In case of single-pole tripping the phase selection
and logic for tripping the three phases is performed in the trip function block.
648
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
The simplified logic diagram for one phase is shown in figure 347.
SchemeType =
Intertrip
CSURLx
tSendMin AND
OR
BLOCK
AND
CSBLKLx OR
CRLx
Scheme Type =
Permissive UR AND CSLx
OR
tCoord
25 ms
AND t TRLx
OR t
CACCLx
Scheme Type =
Permissive OR
CSORLx OR AND
AND
tSendMin
OR
AND
Scheme Type =
Blocking
BLKCSx
AND
CSL1
CSL2 AND
CSL2
OR CSMPH
CSL3 AND
CSL3
CSL1 AND
CSL1
CSL2 GENERAL
OR
CSL3
IEC06000311_2_en.vsd
IEC06000311 V2 EN
649
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
IEC06000427-2-en.vsd
IEC06000427 V2 EN
650
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
651
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
13.3.1 Introduction
The current reversal function is used to prevent unwanted operations due to current
reversal when using permissive overreach protection schemes in application with
parallel lines when the overreach from the two ends overlap on the parallel line.
652
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
The weak-end infeed logic is used in cases where the apparent power behind the
protection can be too low to activate the distance protection function. When
activated, received carrier signal together with local under voltage criteria and no
reverse zone operation gives an instantaneous trip. The received signal is also
echoed back to accelerate the sending end.
The current reversal logic uses a reverse zone connected to the input IRV to
recognize the fault on the parallel line in any of the phases. When the reverse zone
has been activated for a certain settable time tPickUpRev it prevents sending of a
communication signal and activation of trip signal for a predefined time tDelayRev.
This makes it possible for the receive signal to reset before the trip signal is
activated due to the current reversal by the forward directed zone, see figure 349.
tPickUpRev 10 ms tPickUpRev
IRV t t t
tDelayRev
IRVL
IRVBLK AND t
en05000122_2_en.vsd
IEC05000122 V2 EN
The preventing of sending the send signal CS and activating of the TRIP in the
scheme communication block ZCPSCH is carried out by connecting the IRVL
signal to input BLOCK in the ZCPSCH function.
The function has an internal 10 ms drop-off timer which secure that the current
reversal logic will be activated for short input signals even if the pick-up timer is
set to zero.
The weak-end infeed logic (WEI) function sends back (echoes) the received signal
under the condition that no fault has been detected on the weak-end by different
fault detection elements (distance protection in forward and reverse direction).
The WEI function returns the received signal, see figure 350, when:
653
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
IEC05000123 V1 EN
IEC00000551-TIFF V1 EN
654
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
IEC06000287-2-en.vsd
IEC06000287 V2 EN
655
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
656
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
13.4.1 Introduction
To achieve fast clearing of faults on the whole line, when no communication
channel is available, local acceleration logic (ZCLCPLAL) can be used. This logic
enables fast fault clearing during certain conditions, but naturally, it can not fully
replace a communication channel.
The logic can be controlled either by the autorecloser (zone extension) or by the loss-
of-load current (loss-of-load acceleration).
The overreaching zone is connected to the input EXACC. For this reason,
configure the ARREADY functional input to a READY functional output of a used
autoreclosing function or via the selected binary input to an external autoreclosing
device, see figure 353.
IEC05000157 V1 EN
After the autorecloser initiates the close command and remains in the reclaim state,
there will be no ARREADY signal, and the protection will trip normally with step
distance time functions.
In case of a fault on the adjacent line within the overreaching zone range, an
unwanted autoreclosing cycle will occur. The step distance function at the
reclosing attempt will prevent an unwanted retrip when the breaker is reclosed.
On the other hand, at a persistent line fault on line section not covered by
instantaneous zone (normally zone 1) only the first trip will be "instantaneous".
The function will be blocked if the input BLOCK is activated (common with loss-of-
load acceleration).
657
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
IEC05000158 V1 EN
Breaker closing signals can if decided be connected to block the function during
normal closing.
IEC05000333-2-en.vsd
IEC05000333 V2 EN
658
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
659
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
13.5.1 Introduction
13.5.1.1 Introduction
To achieve fast fault clearance of earth faults on the part of the line not covered by
the instantaneous step of the residual overcurrent protection, the directional
residual overcurrent protection can be supported with a logic that uses
communication channels.
660
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
In the blocking scheme a signal is sent to the other line end if the directional
element detects an earth fault in the reverse direction. When the forward directional
element operates, it trips after a short time delay if no blocking signal is received
from the opposite line end. The time delay, normally 30 – 40 ms, depends on the
communication transmission time and a chosen safety margin.
One advantage of the blocking scheme is that only one channel (carrier frequency)
is needed if the ratio of source impedances at both end is approximately equal for
zero and positive sequence source impedances, the channel can be shared with the
impedance measuring system, if that system also works in the blocking mode. The
communication signal is transmitted on a healthy line and no signal attenuation will
occur due to the fault.
If the fault is on the line, the forward direction measuring element operates. If no
blocking signal comes from the other line end via the CR binary input (received
signal) the TRIP output is activated after the tCoord set time delay.
661
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
IEC05000448 V1 EN
In the permissive scheme the forward directed earth-fault measuring element sends
a permissive signal to the other end, if an earth fault is detected in the forward
direction. The directional element at the other line end must wait for a permissive
signal before activating a trip signal. Independent channels must be available for
the communication in each direction.
An impedance measuring IED, which works in the same type of permissive mode,
with one channel in each direction, can share the channels with the communication
scheme for residual overcurrent protection. If the impedance measuring IED works
in the permissive overreaching mode, common channels can be used in single line
applications. In case of double lines connected to a common bus at both ends, use
common channels only if the ratio Z1S/Z0S (positive through zero-sequence source
impedance) is about equal at both ends. If the ratio is different, the impedance
measuring and the directional earth-fault current system of the healthy line may
detect a fault in different directions, which could result in unwanted tripping.
Common channels cannot be used when the weak-end infeed function is used in
the distance or earth-fault protection.
662
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
BLOCK
CRL
CR AND
25 ms
t TRIP
0 - 60 s
AND
BLKCS OR CS
AND
Overreach
CSOR AND
CSUR OR
en05000280_2_en.vsd
IEC05000280 V2 EN
The unblocking function uses a guard signal CRG, which must always be present,
even when no CR signal is received. The absence of the CRG signal for a time
longer than the setting tSecurity time is used as a CR signal, see figure 357. This
also enables a permissive scheme to operate when the line fault blocks the signal
transmission.
The received signal created by the unblocking function is reset 150 ms after the
security timer has elapsed. When that occurs an output signal LCG is activated for
signaling purpose. The unblocking function is reset 200 ms after that the guard
signal is present again.
663
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
CR
tSecurity CRL
t >1
1
CRG
200 ms 150 ms
t OR t AND
AND
LCG
en05000746.vsd
IEC05000746 V1 EN
The unblocking function can be set in three operation modes (setting Unblock):
IEC06000288-2-en.vsd
IEC06000288 V2 EN
664
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
665
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
13.6.1 Introduction
The Current reversal and weak-end infeed logic for residual overcurrent protection
ECRWPSCH is a supplement to Scheme communication logic for residual
overcurrent protection ECPSCH.
To achieve fast fault clearing for all earth faults on the line, the directional earth-
fault protection function can be supported with logic that uses communication
channels.
The 670 series IEDs have for this reason available additions to scheme
communication logic.
666
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
The directional comparison function contains logic for blocking overreaching and
permissive overreaching schemes.
The circuits for the permissive overreaching scheme contain logic for current
reversal and weak-end infeed functions. These functions are not required for the
blocking overreaching scheme.
Connect the necessary signal from the autorecloser for blocking of the directional
comparison scheme, during a single-phase autoreclosing cycle, to the BLOCK
input of the directional comparison module.
The fault current reversal logic uses a reverse directed element, connected to input
signal IRV, which recognizes that the fault is in reverse direction. When the
reverse direction element is activated during the tPickUpRev time, the output signal
IRVL is activated, see figure 359. The logic is now ready to handle a current
reversal without tripping. Output signal IRVL will be connected to the block input
on the permissive overreaching scheme.
When the fault current is reversed on the non faulty line, IRV is deactivated and
IRVBLK is activated. The reset of IRVL is delayed by the tDelayRev time, see
figure 359. This ensures the reset of the received CR signal.
667
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
BLOCK
0-60 s 10 ms 0-60 s 0-60 s
IRV AND IRVL
t t t t
IEC09000031-1-en.vsd
IEC09000031 V1 EN
The weak-end infeed function can be set to send only an echo signal (WEI=Echo)
or an echo signal and a trip signal (WEI=Echo & Trip). See figure 360 and figure
361.
The weak-end infeed logic uses normally a reverse and a forward direction
element, connected to WEIBLK1 via an OR-gate. See figure 360. If neither the
forward nor the reverse directional measuring element is activated during the last
200 ms, the weak-end infeed logic echoes back the received permissive signal. See
figure 360.
If the forward or the reverse directional measuring element is activated during the
last 200 ms, the fault current is sufficient for the IED to detect the fault with the
earth-fault function that is in operation.
BLOCK
200 ms
WEIBLK1 t
50 ms 200 ms
AND
ECHO
& t t
CRL
WEI = Echo
IEC09000032-1-en.vsd
IEC09000032 V1 EN
With the Echo & Trip setting, the logic sends an echo according to above. Further,
it activates the TRWEI signal to trip the breaker if the echo conditions are fulfilled
and the neutral point voltage is above the set operate value for 3U0>.
The voltage signal that is used to calculate the zero sequence voltage is set in the
earth-fault function that is in operation.
668
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
BLOCK
200 ms
WEIBLK1 50 ms 200 ms
AND
ECHO
t
AND t t
CRL
TRWEI
WEI = Echo&Trip AND
ST3U0
AND
CBOPEN
IEC09000020-1-en.vsd
IEC09000020 V1 EN
Figure 361: Simplified logic diagram, weak-end infeed - Echo & Trip
The weak-end infeed echo sent to the strong line end has a maximum duration of
200 ms. When this time period has elapsed, the conditions that enable the echo
signal to be sent are set to zero for a time period of 50 ms. This avoids ringing
action if the weak-end echo is selected for both line ends.
IEC06000289-2-en.vsd
IEC06000289 V2 EN
669
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
670
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
13.7.1 Introduction
Current reversal and weak-end infeed logic for phase segregated communication
(ZC1WPSCH) function is used to prevent unwanted operations due to current
reversal when using permissive overreach protection schemes in application with
parallel lines when the overreach from the two ends overlaps on the parallel line.
The weak-end infeed logic is used in cases where the apparent power behind the
protection can be too low to activate the distance protection function. When
activated, received carrier signal together with local under voltage criteria and no
reverse zone operation gives an instantaneous trip. The received signal is also
echoed back to accelerate the sending end.
The current reversal logic uses a reverse zone connected to the input IRVLx to
recognize the fault on the parallel line in phase Lx. When the reverse zone has been
activated for a certain settable time tPickUpRev it prevents sending of a
communication signal and activation of trip signal for a predefined time tDelayRev.
This makes it possible for the carrier receive signal to reset before the carrier aided
trip signal is activated due to the current reversal by the forward directed zone, see
figure 363.
tPickUpRev 10 ms tPickUpRev
IRVLn t t t
tDelayRev
IRVOPLn
IRVBLKLn & t
IEC06000474_2_en.vsd
IEC06000474 V2 EN
The preventing of sending carrier send signal CSLn and activating of the TRIPLn
in the Scheme communication logic for distance or Overcurrent protection
671
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
The Current reversal and weak-end infeed logic for phase segregated
communication (ZC1WPSCH) function has an internal 10 ms drop-off timer which
secure that the current reversal logic will be activated for short input signals even if
the pick-up timer is set to zero.
The WEI function sends back (echoes) the received carrier signal under the
condition that no fault has been detected at the weak end by different fault
detection elements (distance protection in forward and reverse direction).
VTSZ
BLOCK >1
200 ms
WEIBLKL2
t
IEC07000085_2_en.vsd
IEC07000085 V2 EN
The WEI function returns the received carrier signal, see figure 364, when:
• The input CRLx is active. This input is usually connected to the CRLx output
on the scheme communication logic for distance or Overcurrent protection
(ZCPSCH).
• The WEI function is not blocked by the active signal connected to the
WEIBLKLx input or to the VTSZ input. The later is usually configured to the
STGEN output of the fuse-failure function.
• No active signal has been present for at least 200 ms on the WEIBLK2 input.
An OR combination of all fault detection functions (not undervoltage) as
present within the IED is usually used for this purpose.
672
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
WEI = Echo&Trip
ECHOLn - cont.
CBOPEN
STUL1N
100 ms TRWEI
OR OR
STUL2N AND t
STUL3N 15 ms
TRWEIL1
AND t
15 ms
TRWEIL2
AND t
15 ms
TRWEIL3
AND t
en00000551.vsd
IEC00000551-WMF V1 EN
IEC06000477-2-en.vsd
IEC06000477 V2 EN
673
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication
674
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication
675
Technical reference manual
676
1MRK505183-UEN C Section 14
Logic
Section 14 Logic
I->O
SYMBOL-K V1 EN
14.1.1 Introduction
A function block for protection tripping is provided for each circuit breaker
involved in the tripping of the fault. It provides the pulse prolongation to ensure a
trip pulse of sufficient length, as well as all functionality necessary for correct co-
operation with autoreclosing functions.
The trip function block includes functionality for evolving faults and breaker lock-
out.
For three-phase tripping, SMPPTRC has a single input (TRIN) through which all
trip output signals from the protection functions within the IED, or from external
protection functions via one or more of the IEDs binary inputs, are routed. It has a
single trip output (TRIP) for connection to one or more of the IEDs binary outputs,
as well as to other functions within the IED requiring this signal.
677
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
BLOCK
tTripMin TRIP
TRIN OR
AND t
Operation Mode = On
Program = 3Ph
en05000789.vsd
IEC05000789 V1 EN
SMPPTRC function for single-phase and two-phase tripping has additional phase
segregated inputs for this, as well as inputs for faulted phase selection. The latter
inputs enable single- phase and two-phase tripping for those functions which do not
have their own phase selection capability, and therefore which have just a single
trip output and not phase segregated trip outputs for routing through the phase
segregated trip inputs of the expanded SMPPTRC function. Examples of such
protection functions are the residual overcurrent protections. The expanded
SMPPTRC function has two inputs for these functions, one for impedance tripping
(for example, carrier-aided tripping commands from the scheme communication
logic), and one for earth fault tripping (for example, tripping output from a residual
overcurrent protection).
The expanded SMPPTRC function has three trip outputs TRL1, TRL2, TRL3
(besides the trip output TRIP), one per phase, for connection to one or more of the
IEDs binary outputs, as well as to other functions within the IED requiring these
signals. There are also separate output signals indicating single-phase, two-phase or
three-phase trip. These signals are important for cooperation with the autorecloser
SMBRREC function.
The expanded SMPPTRC function is equipped with logic which secures correct
operation for evolving faults as well as for reclosing on to persistent faults. A
special input is also provided which disables single- phase and two-phase tripping,
forcing all tripping to be three-phase.
The breaker close lockout function can be activated from an external trip signal
from another protection function via input (SETLKOUT) or internally at a three-
phase trip, if desired.
The TRPx function for single- and two-pole tripping has additional phase
segregated inputs for this, as well as inputs for faulted phase selection. The latter
inputs enable single- and two-pole tripping for those functions which do not have
678
Technical reference manual
1MRK505183-UEN C Section 14
Logic
their own phase selection capability, and therefore which have just a single trip
output and not phase segregated trip outputs for routing through the phase
segregated trip inputs of the expanded TRPx function. Examples of such protection
functions are the residual overcurrent protections. The expanded TRPx function
has two inputs for these functions, one for impedance tripping (e.g. carrier-aided
tripping commands from the scheme communication logic), and one for earth fault
tripping (e.g. tripping output from a residual overcurrent protection). Additional
logic secures a three-pole final trip command for these protection functions in the
absence of the required phase selection signals.
The expanded TRPx function has three trip outputs TRL1, TRL2, TRL3 (besides
the trip output TRIP), one per phase, for connection to one or more of the IEDs
binary outputs, as well as to other functions within the IED requiring these signals.
There are also separate output signals indicating single pole, two pole or three pole
trip. These signals are important for cooperation with the auto-reclosing function.
The expanded TRPx function is equipped with logic which secures correct
operation for evolving faults as well as for reclosing on to persistent faults. A
special input is also provided which disables single- and two-pole tripping, forcing
all tripping to be three-pole.
In multi-breaker arrangements, one TRPx function block is used for each breaker.
This can be the case if single pole tripping and auto-reclosing is used.
The breaker close lockout function can be activated from an external trip signal
from another protection function via input (SETLKOUT) or internally at a three
pole trip, if desired.
TRINL1
TRINL2
OR
TRINL3
1PTRZ OR
1PTREF
OR
TRIN RSTTRIP - cont.
AND
Program = 3ph
en05000517.vsd
IEC05000517 V1 EN
679
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
TRIN
TRINL1
PSL1 L1TRIP
OR
AND
TRINL2
PSL2 L2TRIP
OR
AND
TRINL3
PSL3 L3TRIP
OR
AND
OR
OR OR
-loop
-loop
OR
AND AND
AND
1PTREF AND 50 ms
1PTRZ OR t
en05000518.vsd
IEC05000518-WMF V1 EN
680
Technical reference manual
1MRK505183-UEN C Section 14
Logic
150 ms
L1TRIP OR
t RTRIP
OR
2000 ms
t
OR
AND
150 ms
L2TRIP OR
t STRIP
OR
2000 ms
t
OR
AND
150 ms
L3TRIP OR
t TTRIP
OR
2000 ms
t
OR
AND
OR
OR AND
P3PTR
OR
-loop
en05000519.vsd
IEC05000519-WMF V1 EN
681
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
150 ms
L1TRIP - cont.
t OR RTRIP
OR
2000 ms
t
AND
150 ms
L2TRIP
t OR STRIP
OR
2000 ms
t AND
AND
150 ms
L3TRIP
t OR TTRIP
OR
2000 ms
t
AND
OR
AND
TRIP OR
OR
-loop
en05000520.vsd
IEC05000520-WMF V1 EN
682
Technical reference manual
1MRK505183-UEN C Section 14
Logic
BLOCK
RTRIP TRL1
AND
OR
STRIP TRL2
AND
OR
TTRIP TRL3
AND
OR
RSTTRIP
TRIP
OR
TR3P
AND AND
OR
-loop
AND 10 ms
TR1P
AND t
AND 5 ms
TR2P
AND t
OR
AND
-loop
en05000521.vsd
IEC05000521-WMF V1 EN
IEC05000707-2-en.vsd
IEC05000707 V2 EN
683
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
684
Technical reference manual
1MRK505183-UEN C Section 14
Logic
14.2.1 Introduction
Trip matrix logic (TMAGGIO) function is used to route trip signals and/or other
logical output signals to different output contacts on the IED.
TMAGGIO output signals and the physical outputs are available in PCM600 and
this allows the user to adapt the signals to the physical tripping outputs according
to the specific application needs.
Internal built-in OR logic is made in accordance with the following three rules:
1. when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical
value 1 (TRUE) the first output signal (OUTPUT1) will get logical value 1
(TRUE).
2. when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical
value 1 (TRUE) the second output signal (OUTPUT2) will get logical value 1
(TRUE).
3. when any one of all 32 input signals (INPUT1 to INPUT32) has logical value
1 (TRUE) the third output signal (OUTPUT3) will get logical value 1 (TRUE).
685
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
time. The ModeOutput for respective output decides wether the output shall be
steady with an drop-off delay as set by OffDelay or if it shall give a pulse with
duration set by PulseTime. Note that for pulsed operation since the inputs are
connected in an OR-function a new pulse will only be given on the output if all
related inputs are reset and then one is activated again. And for steady operation
the of delay will start when all related inputs have reset. Detailed logical diagram is
shown in figure 374
PulseTime
t
&
ModeOutput1
Input 1
Output 1
Ondelay Offdelay
&
³1
³1 t t
Input 16
PulseTime
t
&
ModeOutput2
Input 17
Output 2
Ondelay Offdelay
&
³1
³1 t t
Input 32
PulseTime
t
&
ModeOutput3
Output 3
Ondelay Offdelay
&
³1
³1 t t
IEC09000612_1_en.vsd
IEC09000612 V1 EN
Output signals from TMAGGIO are typically connected to other logic blocks or
directly to output contacts in the IED. When used for direct tripping of the circuit
breaker(s) the pulse time delay shall be set to approximately 0.150 seconds in order
to obtain satisfactory minimum duration of the trip pulse to the circuit breaker trip
coils.
686
Technical reference manual
1MRK505183-UEN C Section 14
Logic
IEC09000830-1-en.vsd
IEC09000830 V1 EN
687
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
688
Technical reference manual
1MRK505183-UEN C Section 14
Logic
14.3.1 Introduction
A number of logic blocks and timers are available for user to adapt the
configuration to the specific application needs.
• OR function block.
• PULSETIMER function block can be used, for example, for pulse extensions
or limiting of operation of outputs.
• GATE function block is used for controlling if a signal should be able to pass
from the input to the output or not depending on a setting.
• LOOPDELAY function block used to delay the output signal one execution
cycle.
• TIMERSET function has pick-up and drop-out delayed outputs related to the
input signal. The timer has a settable time delay.
• SRMEMORY function block is a flip-flop that can set or reset an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block after a power interruption should return to
the state before the interruption, or be reset. Set input has priority.
• RSMEMORY function block is a flip-flop that can reset or set an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block after a power interruption should return to
the state before the interruption, or be reset. Reset input has priority.
IEC04000404_2_en.vsd
IEC04000404 V2 EN
689
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
IEC04000405_2_en.vsd
IEC04000405 V2 EN
690
Technical reference manual
1MRK505183-UEN C Section 14
Logic
IEC04000406_2_en.vsd
IEC04000406 V2 EN
IEC04000378_2_en.vsd
IEC04000378 V2 EN
691
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
IEC04000407-2-en.vsd
IEC04000407 V2 EN
692
Technical reference manual
1MRK505183-UEN C Section 14
Logic
XOR
INPUT1 OUT
INPUT2 NOUT
IEC04000409-2-en.vsd
IEC04000409 V2 EN
LOOPDELAY
INPUT OUT
IEC09000296-1-en.vsd
IEC09000296 V1 EN
693
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
setting controls if the flip-flop after a power interruption will return the state it had
before or if it will be reset.
SRMEMORY
SET OUT
RESET NOUT
IEC04000408_2_en.vsd
IEC04000408 V2 EN
IEC04000410-2-en.vsd
IEC04000410 V2 EN
694
Technical reference manual
1MRK505183-UEN C Section 14
Logic
IEC04000411-2-en.vsd
IEC04000411 V2 EN
695
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
696
Technical reference manual
1MRK505183-UEN C Section 14
Logic
IEC05000445-2-en.vsd
IEC05000445 V2 EN
14.5.1 Introduction
Boolean 16 to integer conversion function (B16I) is used to transform a set of 16
binary (logical) signals into an integer.
697
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
IEC07000128-2-en.vsd
IEC07000128 V2 EN
698
Technical reference manual
1MRK505183-UEN C Section 14
Logic
14.6.1 Introduction
Boolean 16 to integer conversion with logic node representation function
(B16IGGIO) is used to transform a set of 16 binary (logical) signals into an integer.
B16IGGIO can receive remote values via IEC 61850 depending on the operator
position input (PSTO).
699
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
IEC07000129-2-en.vsd
IEC07000129 V2 EN
700
Technical reference manual
1MRK505183-UEN C Section 14
Logic
14.7.1 Introduction
Integer to boolean 16 conversion function (IB16) is used to transform an integer
into a set of 16 binary (logical) signals.
IEC06000501-2-en.vsd
IEC06000501 V2 EN
701
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
702
Technical reference manual
1MRK505183-UEN C Section 14
Logic
14.8.1 Introduction
Integer to boolean conversion with logic node representation function (IB16GGIO)
is used to transform an integer to 16 binary (logic) signals.
IB16GGIO function can receive remote values over IEC61850 depending on the
operator position input (PSTO).
The operator position input (PSTO) determines the operator place. The integer
number can be written to the block while in “Remote”. If PSTO is in ”Off”
or ”Local”, then no change is applied to the outputs.
IEC06000502-2-en.vsd
IEC06000502 V2 EN
703
Technical reference manual
Section 14 1MRK505183-UEN C
Logic
704
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
Section 15 Monitoring
15.1 Measurements
SYMBOL-RR V1 EN
SYMBOL-SS V1 EN
SYMBOL-UU V1 EN
SYMBOL-VV V1 EN
SYMBOL-TT V1 EN
SYMBOL-UU V1 EN
705
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
15.1.1 Introduction
Measurement functions is used for power system measurement, supervision and
reporting to the local HMI, monitoring tool within PCM600 or to station level for
example, via IEC 61850. The possibility to continuously monitor measured values
of active power, reactive power, currents, voltages, frequency, power factor etc. is
vital for efficient production, transmission and distribution of electrical energy. It
provides to the system operator fast and easy overview of the present status of the
power system. Additionally, it can be used during testing and commissioning of
protection and control IEDs in order to verify proper operation and connection of
instrument transformers (CTs and VTs). During normal service by periodic
comparison of the measured value from the IED with other independent meters the
proper operation of the IED analog measurement chain can be verified. Finally, it
can be used to verify proper direction orientation for distance or directional
overcurrent protection function.
All measured values can be supervised with four settable limits that is, low-low
limit, low limit, high limit and high-high limit. A zero clamping reduction is also
supported, that is, the measured value below a settable limit is forced to zero which
reduces the impact of noise in the inputs.
Dead-band supervision can be used to report measured signal value to station level
when change in measured value is above set threshold limit or time integral of all
changes since the last time value updating exceeds the threshold limit. Measure
value can also be based on periodic reporting.
It is possible to calibrate the measuring function above to get better then class 0.5
presentation. This is accomplished by angle and amplitude compensation at 5, 30
and 100% of rated current and at 100% of rated voltage.
706
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
The protection, control, and monitoring IEDs have functionality to measure and
further process information for currents and voltages obtained from the pre-
processing blocks. The number of processed alternate measuring quantities
depends on the type of IED and built-in options.
The information on measured quantities is available for the user at different locations:
707
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
• Overfunction, when the measured current exceeds the High limit (XHiLim) or
High-high limit (XHiHiLim) pre-set values
• Underfunction, when the measured current decreases under the Low limit
(XLowLim) or Low-low limit (XLowLowLim) pre-set values.
X_RANGE = 3
High-high limit
X_RANGE= 1 Hysteresis
High limit
X_RANGE=0
X_RANGE=0 t
Low limit
X_RANGE=2
Low-low limit
X_RANGE=4
en05000657.vsd
IEC05000657 V1 EN
The logical value of the functional output signals changes according to figure 391.
The user can set the hysteresis (XLimHyst), which determines the difference
between the operating and reset value at each operating point, in wide range for
each measuring channel separately. The hysteresis is common for all operating
values within one channel.
708
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting
(XRepTyp). The measuring channel reports the value independent of amplitude or
integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.
Y
Value Reported Value Reported
Value Reported Value Reported
(1st)
Y3 Value Reported
Y2 Y4
Y1 Y5
t
Value 1
Value 2
Value 3
Value 4
Value 5
en05000500.vsd
(*)Set value for t: XDbRepInt
IEC05000500 V1 EN
709
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
Value Reported
Y
99000529.vsd
IEC99000529 V1 EN
After the new value is reported, the ±ΔY limits for dead-band are automatically set
around it. The new value is reported only if the measured quantity changes more
than defined by the ±ΔY set limits. Even if amplitude dead-band reporting is
selected, there will be a 30 s "back-ground" cyclic reporting as well.
The last value reported, Y1 in figure 394 serves as a basic value for further
measurement. A difference is calculated between the last reported and the newly
measured value and is multiplied by the time increment (discrete integral). The
absolute values of these integral values are added until the pre-set value is
exceeded. This occurs with the value Y2 that is reported and set as a new base for
the following measurements (as well as for the values Y3, Y4 and Y5).
710
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
Y A1 >=
A >= pre-set value
A2 >=
pre-set value pre-set value
Y3 A3 + A4 + A5 + A6 + A7 >=
pre-set value
Y2 A1 A2
A4 A6
Value Reported Y4 A3 A5 A7
(1st) Value
Value Reported Y5
A Reported Value
Reported Value
Y1 Reported
t
99000530.vsd
IEC99000530 V1 EN
Mode of operation
The measurement function must be connected to three-phase current and three-
phase voltage input in the configuration tool (group signals), but it is capable to
measure and calculate above mentioned quantities in nine different ways depending
on the available VT inputs connected to the IED. The end user can freely select by
a parameter setting, which one of the nine available measuring modes shall be used
within the function. Available options are summarized in the following table:
Set value for Formula used for complex, three- Formula used for voltage and Comment
parameter phase power calculation current magnitude calculation
“Mode”
1 L1, L2, L3 Used when
* * *
S = U L1 × I L1 + U L 2 × I L 2 + U L 3 × I L 3 U = ( U L1 + U L 2 + U L 3 ) / 3
three phase-
EQUATION1385 V1 EN
to-earth
I = ( I L1 + I L 2 + I L 3 ) / 3
voltages are
EQUATION1386 V1 EN available
2 Arone Used when
S = U L1 L 2 × I L1 - U L 2 L 3 × I L 3
* *
U = ( U L1 L 2 + U L 2 L 3 ) / 2 three two
phase-to-
(Equation 126)
I = ( I L1 + I L 3 ) / 2 phase
EQUATION1387 V1 EN
voltages are
EQUATION1388 V1 EN (Equation 127) available
3 PosSeq Used when
S = 3 × U PosSeq × I PosSeq
*
U = 3 × U PosSeq only
symmetrical
(Equation 128) three phase
EQUATION1389 V1 EN
I = I PosSeq
power shall
EQUATION1390 V1 EN (Equation 129) be measured
711
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
Set value for Formula used for complex, three- Formula used for voltage and Comment
parameter phase power calculation current magnitude calculation
“Mode”
4 L1L2 Used when
S = U L1 L 2 × ( I L1 - I L 2 )
* *
U = U L1 L 2 only UL1L2
phase-to-
(Equation 130)
I = ( I L1 + I L 2 ) / 2
EQUATION1391 V1 EN
phase
voltage is
EQUATION1392 V1 EN (Equation 131) available
5 L2L3 Used when
S = U L 2 L3 × ( I L 2 - I L3 )
* *
U = U L2 L3 only UL2L3
phase-to-
(Equation 132)
I = ( I L2 + I L3 ) / 2
EQUATION1393 V1 EN
phase
voltage is
EQUATION1394 V1 EN (Equation 133) available
6 L3L1 Used when
S = U L 3 L1 × ( I L 3 - I L1 )
* *
U = U L 3 L1 only UL3L1
phase-to-
(Equation 134)
I = ( I L 3 + I L1 ) / 2
EQUATION1395 V1 EN
phase
voltage is
EQUATION1396 V1 EN (Equation 135) available
7 L1 Used when
S = 3 × U L1 × I L1
*
U = 3 × U L1 only UL1
phase-to-
(Equation 136) earth voltage
I = I L1
EQUATION1397 V1 EN
is available
EQUATION1398 V1 EN (Equation 137)
8 L2 Used when
S = 3 ×U L2 × I L2
*
U = 3 × U L2 only UL2
phase-to-
(Equation 138) earth voltage
I = IL2
EQUATION1399 V1 EN
is available
EQUATION1400 V1 EN (Equation 139)
9 L3 Used when
S = 3 ×U L3 × I L3
*
U = 3 × U L3 only UL3
phase-to-
(Equation 140)
I = I L3 earth voltage
EQUATION1401 V1 EN
is available
EQUATION1402 V1 EN (Equation 141)
* means complex conjugated value
It shall be noted that only in the first two operating modes that is, 1 & 2 the
measurement function calculates exact three-phase power. In other operating
modes that is, from 3 to 9 it calculates the three-phase power under assumption that
the power system is fully symmetrical. Once the complex apparent power is
calculated then the P, Q, S, & PF are calculated in accordance with the following
formulas:
P = Re( S )
EQUATION1403 V1 EN (Equation 142)
712
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
Q = Im( S )
EQUATION1404 V1 EN (Equation 143)
S = S = P +Q
2 2
PF = cosj = P
S
EQUATION1406 V1 EN (Equation 145)
Additionally to the power factor value the two binary output signals from the
function are provided which indicates the angular relationship between current and
voltage phasors. Binary output signal ILAG is set to one when current phasor is
lagging behind voltage phasor. Binary output signal ILEAD is set to one when
current phasor is leading the voltage phasor.
713
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
IEC05000652 V2 EN
The first current and voltage phase in the group signals will be used as reference
and the amplitude and angle compensation will be used for related input signals.
X = k × X Old + (1 - k ) × X Calculated
EQUATION1407 V1 EN (Equation 146)
where:
X is a new measured value (that is P, Q, S, U, I or PF) to be given out from the function
XOld is the measured value given from the measurement function in previous execution cycle
k is settable parameter by the end user which influence the filter properties
714
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. Appropriate value of k
shall be determined separately for every application. Some typical value for k =0.14.
Compensation facility
In order to compensate for small amplitude and angular errors in the complete
measurement chain (CT error, VT error, IED input transformer errors and so on.) it
is possible to perform on site calibration of the power measurement. This is
achieved by setting the complex constant which is then internally used within the
function to multiply the calculated complex apparent power S. This constant is set
as amplitude (setting parameter PowAmpFact, default value 1.000) and angle
(setting parameter PowAngComp, default value 0.0 degrees). Default values for
these two parameters are done in such way that they do not influence internally
calculated value (complex constant has default value 1). In this way calibration, for
specific operating range (for example, around rated power) can be done at site.
However, to perform this calibration it is necessary to have an external power
meter with high accuracy class available.
Directionality
If CT earthing parameter is set as described in section "Analog inputs", active and
reactive power will be measured always towards the protected object. This is
shown in the following figure 396.
715
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
Busbar
IED
P Q
Protected
Object
IEC09000038-1-en.vsd
IEC09000038-1-EN V1 EN
Practically, it means that active and reactive power will have positive values when
they flow from the busbar towards the protected object and they will have negative
values when they flow from the protected object towards the busbar.
In some application, for example, when power is measured on the secondary side
of the power transformer it might be desirable, from the end client point of view, to
have actually opposite directional convention for active and reactive power
measurements. This can be easily achieved by setting parameter PowAngComp to
value of 180.0 degrees. With such setting the active and reactive power will have
positive values when they flow from the protected object towards the busbar.
Frequency
Frequency is actually not calculated within measurement block. It is simply
obtained from the pre-processing block and then just given out from the
measurement block as an output.
716
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
Phase currents (amplitude and angle) are available on the outputs and each
amplitude output has a corresponding supervision level output (ILx_RANG). The
supervision output signal is an integer in the interval 0-4, see section
"Measurement supervision".
The voltages (phase or phase-phase voltage, amplitude and angle) are available on
the outputs and each amplitude output has a corresponding supervision level output
(ULxy_RANG). The supervision output signal is an integer in the interval 0-4, see
section "Measurement supervision".
Positive, negative and three times zero sequence quantities are available on the
outputs (voltage and current, amplitude and angle). Each amplitude output has a
corresponding supervision level output (X_RANGE). The output signal is an
integer in the interval 0-4, see section "Measurement supervision".
717
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
CVMMXU
I3P* S
U3P* S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
U
U_RANGE
I
I_RANGE
F
F_RANGE
IEC05000772-2-en.vsd
IEC05000772 V2 EN
CMMXU
I3P* IL1
IL1RANG
IL1ANGL
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL
IEC05000699-2-en.vsd
IEC05000699 V2 EN
VNMMXU
U3P* UL1
UL1RANG
UL1ANGL
UL2
UL2RANG
UL2ANGL
UL3
UL3RANG
UL3ANGL
IEC09000850-1-en.vsd
IEC09000850 V1 EN
VMMXU
U3P* UL12
UL12RANG
UL12ANGL
UL23
UL23RANG
UL23ANGL
UL31
UL31RANG
UL31ANGL
IEC05000701-2-en.vsd
IEC05000701 V2 EN
718
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
CMSQI
I3P* 3I0
3I0RANG
3I0ANGL
I1
I1RANG
I1ANGL
I2
I2RANG
I2ANGL
IEC05000703-2-en.vsd
IEC05000703 V2 EN
VMSQI
U3P* 3U0
3U0RANG
3U0ANGL
U1
U1RANG
U1ANGL
U2
U2RANG
U2ANGL
IEC05000704-2-en.vsd
IEC05000704 V2 EN
719
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
720
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
721
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
722
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
723
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
724
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
725
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
726
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
727
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
728
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
729
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
730
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
731
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
732
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
733
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
734
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
735
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
15.2.1 Introduction
Event counter (CNTGGIO) has six counters which are used for storing the number
of times each counter input has been activated.
To not risk that the flash memory is worn out due to too many writings, a
mechanism for limiting the number of writings per time period is included in the
product. This however gives as a result that it can take long time, up to several
minutes, before a new value is stored in the flash memory. And if a new
CNTGGIO value is not stored before auxiliary power interruption, it will be lost.
CNTGGIO stored values in flash memory will however not be lost at an auxiliary
power interruption.
The function block also has an input BLOCK. At activation of this input all six
counters are blocked. The input can for example, be used for blocking the counters
at testing.The function block has an input RESET. At activation of this input all six
counters are set to 0.
15.2.2.1 Reporting
Reset of counters can be performed in the local HMI and a binary input.
Reading of content can also be performed remotely, for example from a IEC 61850
client. The value can also be presented as a measuring value on the local HMI
graphical display.
736
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
15.2.2.2 Design
The function block has six inputs for increasing the counter values for each of the
six counters respectively. The content of the counters are stepped one step for each
positive edge of the input respectively.
The function block also has an input BLOCK. At activation of this input all six
counters are blocked and are not updated. Valid number is held.
The function block has an input RESET. At activation of this input all six counters
are set to 0.
IEC05000345-2-en.vsd
IEC05000345 V2 EN
737
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
15.3.1 Introduction
When using a Substation Automation system with LON or SPA communication,
time-tagged events can be sent at change or cyclically from the IED to the station
level. These events are created from any available signal in the IED that is
connected to the Event function (EVENT). The event function block is used for
LON and SPA communication.
Analog and double indication values are also transferred through EVENT function.
738
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
Each EVENT function has 16 inputs INPUT1 - INPUT16. Each input can be given
a name from the Application Configuration tool. The inputs are normally used to
create single events, but are also intended for double indication events.
EVENT function also has an input BLOCK to block the generation of events.
The events that are sent from the IED can originate from both internal logical
signals and binary input channels. The internal signals are time-tagged in the main
processing module, while the binary input channels are time-tagged directly on the
input module. The time-tagging of the events that are originated from internal
logical signals have a resolution corresponding to the execution cyclicity of
EVENT function. The time-tagging of the events that are originated from binary
input signals have a resolution of 1 ms.
The outputs from EVENT function are formed by the reading of status, events and
alarms by the station level on every single input. The user-defined name for each
input is intended to be used by the station level.
All events according to the event mask are stored in a buffer, which contains up to
1000 events. If new events appear before the oldest event in the buffer is read, the
oldest event is overwritten and an overflow alarm appears.
The events are produced according to the set-event masks. The event masks are
treated commonly for both the LON and SPA communication. The EventMask can
be set individually for each input channel. These settings are available:
• NoEvents
• OnSet
• OnReset
• OnChange
• AutoDetect
It is possible to define which part of EVENT function generates the events. This
can be performed individually for the SPAChannelMask and LONChannelMask
respectively. For each communication type these settings are available:
• Off
• Channel 1-8
• Channel 9-16
• Channel 1-16
For LON communication the events normally are sent to station level at change. It
is possibly also to set a time for cyclic sending of the events individually for each
input channel.
To protect the SA system from signals with a high change rate that can easily
saturate the event system or the communication subsystems behind it, a quota
limiter is implemented. If an input creates events at a rate that completely consume
the granted quota then further events from the channel will be blocked. This block
will be removed when the input calms down and the accumulated quota reach 66%
739
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
of the maximum burst quota. The maximum burst quota per input channel is 45
events per second.
IEC05000697-2-en.vsd
IEC05000697 V2 EN
740
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
741
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
742
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
15.4.1 Introduction
The Logical signal status report (BINSTATREP) function makes it possible for a
SPA master to poll signals from various other functions.
When an input is set, the respective output is set for a user defined time. If the
input signal remains set for a longer period, the output will remain set until the
input signal resets.
743
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
INPUTn
OUTPUTn
t t
IEC09000732-1-en.vsd
IEC09000732 V1 EN
IEC09000730-1-en.vsd
IEC09000730 V1 EN
744
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
745
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
15.5.1 Introduction
The accurate fault locator is an essential component to minimize the outages after a
persistent fault and/or to pin-point a weak spot on the line.
The fault locator is an impedance measuring function giving the distance to the
fault in percent, km or miles. The main advantage is the high accuracy achieved by
compensating for load current and for the mutual zero-sequence effect on double
circuit lines.
The compensation includes setting of the remote and local sources and calculation
of the distribution of fault currents from each side. This distribution of fault
current, together with recorded load (pre-fault) currents, is used to exactly calculate
the fault position. The fault can be recalculated with new source data at the actual
fault to further increase the accuracy.
Especially on heavily loaded long lines (where the fault locator is most important)
where the source voltage angles can be up to 35-40 degrees apart the accuracy can
be still maintained with the advanced compensation included in fault locator.
When calculating distance to fault, pre-fault and fault phasors of currents and
voltages are selected from the Trip value recorder data, thus the analog signals used
by the fault locator must be among those connected to the disturbance report
function. The analog configuration (channel selection) is performed using the
parameter setting tool within PCM600.
The calculation algorithm considers the effect of load currents, double-end infeed
and additional fault resistance.
R0L+jX0L
R1L+jX1L
R1A+jX1A R1B+jX1B
Z0m=Z0m+jX0m
R0L+jX0L
R1L+jX1L
DRPRDRE
LMBRFLO
IEC05000045_2_en.vsd
IEC05000045 V2 EN
Figure 407: Simplified network configuration with network data, required for
settings of the fault location-measuring function
746
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
If source impedance in the near and far end of the protected line have changed in a
significant manner relative to the set values at fault location calculation time (due
to exceptional switching state in the immediate network, power generation out of
order, and so on), new values can be entered via the local HMI and a recalculation
of the distance to the fault can be ordered using the algorithm described below. It’s
also possible to change fault loop. In this way, a more accurate location of the fault
can be achieved.
The function indicates the distance to the fault as a percentage of the line length, in
kilometers or miles as selected on the local HMI. The fault location is stored as a
part of the disturbance report information (ER, DR, IND, TVR and FL) and
managed via the local HMI or PCM600.
For transmission lines with voltage sources at both line ends, the effect of double-
end infeed and additional fault resistance must be considered when calculating the
distance to the fault from the currents and voltages at one line end. If this is not
done, the accuracy of the calculated figure will vary with the load flow and the
amount of additional fault resistance.
The calculation algorithm used in the fault locator in compensates for the effect of
double-end infeed, additional fault resistance and load current.
Figure 408 shows a single-line diagram of a single transmission line, that is fed
from both ends with source impedances ZA and ZB. Assume that the fault occurs at
a distance F from IED A on a line with the length L and impedance ZL. The fault
resistance is defined as RF. A single-line model is used for better clarification of
the algorithm.
747
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
A B
ZA IA pZL IB (1-p).ZL ZB
IF
UA RF
xx01000171.vsd
IEC01000171 V1 EN
U A = I A × p × Z L + IF × R F
EQUATION95 V1 EN (Equation 147)
Where:
IA is the line current after the fault, that is, pre-fault current plus current change due to the fault,
IF A
IF = --------
DA
EQUATION96 V1 EN (Equation 148)
Where:
IFA is the change in current at the point of measurement, IED A and
DA is a fault current-distribution factor, that is, the ratio between the fault current at line end A
and the total fault current.
( 1 – p ) × Z L + ZB
DA = -----------------------------------------
Z A + Z L + ZB
EQUATION97 V1 EN (Equation 149)
748
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
Thus, the general fault location equation for a single line is:
I FA
U A = I A × p × Z L + -------
- × RF
DA
EQUATION98 V1 EN (Equation 150)
Table 499: Expressions for UA, IA and IFA for different types of faults
The KN complex quantity for zero-sequence compensation for the single line is
equal to:
Z0L – Z 1L
K N = ------------------------
3 × Z1L
EQUATION99 V1 EN (Equation 151)
DI is the change in current, that is the current after the fault minus the current
before the fault.
In the following, the positive sequence impedance for ZA, ZB and ZL is inserted
into the equations, because this is the value used in the algorithm.
749
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
I FA
U A = I A × p × Z 1L + -------- × RF + I 0P × Z 0M
DA
EQUATION100 V1 EN (Equation 152)
Where:
I0P is a zero sequence current of the parallel line,
( 1 – p ) × ( ZA + ZA L + ZB ) + Z B
DA = ----------------------------------------------------------------------------
-
2 × ZA + Z L + 2 × Z B
EQUATION101 V1 EN
Z0L – Z 1L Z 0M I 0P
K N = ----------------------- - × -------
- + ----------------
3 × Z1L 3 × Z1L I 0A
EQUATION102 V1 EN (Equation 153)
From these equations it can be seen, that, if Z0m = 0, then the general fault location
equation for a single line is obtained. Only the distribution factor differs in these
two cases.
Where:
UA ZB
K 1 = ---------------
- + --------------------------
-+1
I A × ZL Z L + ZA DD
UA ZB
K2 = --------------- × æè --------------------------- + 1öø
IA × Z L Z L + Z A DD
IF A æ ZA + ZB
- × --------------------------- + 1ö
K 3 = ---------------
I A × Z L è Z 1 + ZA DD ø
EQUATION106 V1 EN (Equation 157)
and:
750
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
For a single line, Z0M = 0 and ZADD = 0. Thus, equation 154 applies to both single
and parallel lines.
– p × Im × ( K1 ) + Im × ( K 2 ) – R F × Im × ( K3 ) = 0
EQUATION108 V1 EN (Equation 159)
If the imaginary part of K3 is not zero, RF can be solved according to equation 159,
and then inserted to equation 158. According to equation 158, the relative distance
to the fault is solved as the root of a quadratic equation.
Equation 158 gives two different values for the relative distance to the fault as a
solution. A simplified load compensated algorithm, which gives an unequivocal
figure for the relative distance to the fault, is used to establish the value that should
be selected.
If the load compensated algorithms according to the above do not give a reliable
solution, a less accurate, non-compensated impedance model is used to calculate
the relative distance to the fault.
U A = p × Z 1 L × IA + R F × IA
EQUATION109 V1 EN (Equation 160)
Where:
IA is according to table 499.
751
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
The communication protocol IEC 60870-5-103 may be used to poll fault location
information from the IED to a master (that is station HSI). There are two outputs
that must be connected to appropriate inputs on the function block I103StatFltDis,
FLTDISTX gives distance to fault (reactance, according the standard) and
CALCMADE gives a pulse (100 ms) when a result is obtainable on FLTDISTX
output.
IEC05000679-2-en.vsd
IEC05000679 V3 EN
752
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
753
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
15.6.1 Introduction
The current and voltage measurements functions (CVMMXU, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI
and VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits that is low-low limit, low limit, high limit and
high-high limit. The measure value expander block (RANGE_XP) has been
introduced to be able to translate the integer output signal from the measuring
functions to 5 binary signals that is below low-low limit, below low limit, normal,
above high-high limit or above high limit. The output signals can be used as
conditions in the configurable logic.
754
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
IEC05000346-2-en.vsd
IEC05000346 V2 EN
755
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
15.7.1 Introduction
Complete and reliable information about disturbances in the primary and/or in the
secondary system together with continuous event-logging is accomplished by the
disturbance report functionality.
Disturbance report DRPRDRE, always included in the IED, acquires sampled data
of all selected analog input and binary signals connected to the function block that
is, maximum 40 analog and 96 binary signals.
• Event list
• Indications
• Event recorder
• Trip value recorder
• Disturbance recorder
• Fault locator
Every disturbance report recording is saved in the IED in the standard Comtrade
format. The same applies to all events, which are continuously saved in a ring-
buffer. The local HMI is used to get information about the recordings, but the
disturbance report files may be uploaded to PCM600 and further analysis using the
disturbance handling tool.
756
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
Figure 411 shows the relations between Disturbance Report, included functions
and function blocks. Event list (EL), Event recorder (ER) and Indications (IND)
uses information from the binary input function blocks (BxRBDR). Trip value
recorder (TVR) uses analog information from the analog input function blocks
(AxRADR). Disturbance recorder DRPRDRE acquires information from both
AxRADR and BxRBDR.
A4RADR DRPRDRE FL
Analog signals
Trip value rec Fault locator
B1-6RBDR Disturbance
recorder
Event recorder
Indications
IEC09000336-2-en.vsd
IEC09000336 V2 EN
The whole disturbance report can contain information for a number of recordings,
each with the data coming from all the parts mentioned above. The event list
function is working continuously, independent of disturbance triggering, recording
time, and so on. All information in the disturbance report is stored in non-volatile
flash memories. This implies that no information is lost in case of loss of auxiliary
power. Each report will get an identification number in the interval from 0-999.
757
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
Disturbance report
en05000125.vsd
IEC05000125 V1 EN
Number of recordings
100
3,4 s
80 3,4 s 20 analog
96 binary
40 analog
96 binary
60 6,3 s
6,3 s
6,3 s 50 Hz
40
60 Hz
Total recording time
en05000488.vsd
IEC05000488 V1 EN
Disturbance information
Date and time of the disturbance, the indications, events, fault location and the trip
values are available on the local HMI. To acquire a complete disturbance report the
758
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
user must use a PC and - either the PCM600 Disturbance handling tool - or a FTP
or MMS (over 61850) client. The PC can be connected to the IED front, rear or
remotely via the station bus (Ethernet ports).
Indications (IND)
Indications is a list of signals that were activated during the total recording time of
the disturbance (not time-tagged), see section "Indications" for more detailed
information.
Time tagging
The IED has a built-in real-time calendar and clock. This function is used for all
time tagging within the disturbance report
Recording times
Disturbance report DRPRDRE records information about a disturbance during a
settable time frame. The recording times are valid for the whole disturbance report.
Disturbance recorder (DR), event recorder (ER) and indication function register
disturbance data and events during tRecording, the total recording time.
759
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
Trig point
TimeLimit
PreFaultRecT PostFaultRecT
1 2 3
en05000487.vsd
IEC05000487 V1 EN
PreFaultRecT, 1 Pre-fault or pre-trigger recording time. The time before the fault including the
operate time of the trigger. Use the setting PreFaultRecT to set this time.
tFault, 2 Fault time of the recording. The fault time cannot be set. It continues as long as
any valid trigger condition, binary or analog, persists (unless limited by TimeLimit
the limit time).
PostFaultRecT, 3 Post fault recording time. The time the disturbance recording continues after all
activated triggers are reset. Use the setting PostFaultRecT to set this time.
TimeLimit Limit time. The maximum allowed recording time after the disturbance recording
was triggered. The limit time is used to eliminate the consequences of a trigger
that does not reset within a reasonable time interval. It limits the maximum
recording time of a recording and prevents subsequent overwriting of already
stored disturbances. Use the setting TimeLimit to set this time.
Analog signals
Up to 40 analog signals can be selected for recording by the Disturbance recorder
and triggering of the Disturbance report function. Out of these 40, 30 are reserved
for external analog signals from analog input modules (TRM) and line data
communication module (LDCM) via preprocessing function blocks (SMAI) and
summation block (3PHSUM). The last 10 channels may be connected to internally
calculated analog signals available as function block output signals (mA input
signals, phase differential currents, bias currents and so on).
760
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
SMAI A1RADR
Block AI3P A2RADR
^GRP2L1 AI1 INPUT1 A3RADR
External
analogue ^GRP2L2 AI2 INPUT2
signals ^GRP2L3 AI3 INPUT3
^GRP2N AI4 INPUT4
Type AIN INPUT5
INPUT6
...
A4RADR
INPUT31
INPUT32
INPUT33
Internal analogue signals INPUT34
INPUT35
INPUT36
...
INPUT40
IEC10000029-1-en.vsd
IEC10000029 V1 EN
The external input signals will be acquired, filtered and skewed and (after
configuration) available as an input signal on the AxRADR function block via the
SMAI function block. The information is saved at the Disturbance report base
sampling rate (1000 or 1200 Hz). Internally calculated signals are updated
according to the cycle time of the specific function. If a function is running at
lower speed than the base sampling rate, Disturbance recorder will use the latest
updated sample until a new updated sample is available.
If the IED is preconfigured the only tool needed for analog configuration of the
Disturbance report is the Signal Matrix Tool (SMT, external signal configuration).
In case of modification of a preconfigured IED or general internal configuration the
Application Configuration tool within PCM600 is used.
The preprocessor function block (SMAI) calculates the residual quantities in cases
where only the three phases are connected (AI4-input not used).SMAI makes the
information available as a group signal output, phase outputs and calculated
residual output (AIN-output). In situations where AI4-input is used as an input
signal the corresponding information is available on the non-calculated output
(AI4) on the SMAI function block. Connect the signals to the AxRADR accordingly.
For each of the analog signals, Operation = On means that it is recorded by the
disturbance recorder. The trigger is independent of the setting of Operation, and
triggers even if operation is set to Off. Both undervoltage and overvoltage can be
used as trigger conditions. The same applies for the current signals.
761
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
If Operation = On, waveform (samples) will also be recorded and reported in graph.
The analog signals are presented only in the disturbance recording, but they affect
the entire disturbance report when being used as triggers.
Binary signals
Up to 96 binary signals can be selected to be handled by disturbance report. The
signals can be selected from internal logical and binary input signals. A binary
signal is selected to be recorded when:
The selected signals are presented in the event recorder, event list and the
disturbance recording. But they affect the whole disturbance report when they are
used as triggers. The indications are also selected from these 96 signals with local
HMI IndicationMask=Show/Hide.
Trigger signals
The trigger conditions affect the entire disturbance report, except the event list,
which runs continuously. As soon as at least one trigger condition is fulfilled, a
complete disturbance report is recorded. On the other hand, if no trigger condition
is fulfilled, there is no disturbance report, no indications, and so on. This implies
the importance of choosing the right signals as trigger conditions.
• Manual trigger
• Binary-signal trigger
• Analog-signal trigger (over/under function)
Manual trigger
A disturbance report can be manually triggered from the local HMI, PCM600 or
via station bus (IEC 61850). When the trigger is activated, the manual trigger
signal is generated. This feature is especially useful for testing. Refer to the
operator's manual for procedure.
Binary-signal trigger
Any binary signal state (logic one or a logic zero) can be selected to generate a
trigger (Triglevel = Trig on 0/Trig on 1). When a binary signal is selected to
762
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
generate a trigger from a logic zero, the selected signal will not be listed in the
indications list of the disturbance report.
Analog-signal trigger
All analog signals are available for trigger purposes, no matter if they are recorded
in the disturbance recorder or not. The settings are OverTrigOp, UnderTrigOp,
OverTrigLe and UnderTrigLe.
The check of the trigger condition is based on peak-to-peak values. When this is
found, the absolute average value of these two peak values is calculated. If the
average value is above the threshold level for an overvoltage or overcurrent trigger,
this trigger is indicated with a greater than (>) sign with the user-defined name.
If the average value is below the set threshold level for an undervoltage or
undercurrent trigger, this trigger is indicated with a less than (<) sign with its name.
The procedure is separately performed for each channel.
This method of checking the analog start conditions gives a function which is
insensitive to DC offset in the signal. The operate time for this start is typically in
the range of one cycle, 20 ms for a 50 Hz network.
All under/over trig signal information is available on the local HMI and PCM600.
Post Retrigger
Disturbance report function does not respond to any new trig condition, during a
recording. Under certain circumstances the fault condition may reoccur during the
post-fault recording, for instance by automatic reclosing to a still faulty power line.
When the retrig parameter is disabled (PostRetrig = Off), a new recording will not
start until the post-fault (PostFaultrecT or TimeLimit) period is terminated. If a
new trig occurs during the post-fault period and lasts longer than the proceeding
recording a new complete recording will be fetched.
IEC05000406-3-en.vsd
IEC05000406 V3 EN
763
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
A1RADR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
IEC05000430-3-en.vsd
IEC05000430 V3 EN
A4RADR
^INPUT31
^INPUT32
^INPUT33
^INPUT34
^INPUT35
^INPUT36
^INPUT37
^INPUT38
^INPUT39
^INPUT40
IEC05000431-3-en.vsd
IEC05000431 V3 EN
B1RBDR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
IEC05000432-3-en.vsd
IEC05000432 V3 EN
Figure 419: B1RBDR function block, binary inputs, example for B1RBDR -
B6RBDR
764
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
765
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
766
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
767
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
768
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
769
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
770
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
771
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
772
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
773
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
774
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
775
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
15.8.1 Introduction
Continuous event-logging is useful for monitoring of the system from an overview
perspective and is a complement to specific disturbance recorder functions.
The event list logs all binary input signals connected to the Disturbance report
function. The list may contain of up to 1000 time-tagged events stored in a ring-buffer.
776
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
The list can be configured to show oldest or newest events first with a setting on
the local HMI.
The event list function runs continuously, in contrast to the event recorder function,
which is only active during a disturbance.
The name of the binary input signal that appears in the event recording is the user-
defined name assigned when the IED is configured. The same name is used in the
disturbance recorder function (DR), indications (IND)and the event recorder
function (ER).
The event list is stored and managed separate from the disturbance report
information (ER, DR, IND, TVR and FL).
15.9 Indications
15.9.1 Introduction
To get fast, condensed and reliable information about disturbances in the primary
and/or in the secondary system it is important to know, for example binary signals
that have changed status during a disturbance. This information is used in the short
perspective to get information via the local HMI in a straightforward way.
There are three LEDs on the local HMI (green, yellow and red), which will display
status information about the IED and the Disturbance report function (trigged).
777
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
The Indication list function shows all selected binary input signals connected to the
Disturbance report function that have changed status during a disturbance.
Green LED:
Yellow LED:
Red LED:
Indication list:
The possible indicated signals are the same as the ones chosen for the disturbance
report function and disturbance recorder.
The indication function tracks 0 to 1 changes of binary signals during the recording
period of the collection window. This means that constant logic zero, constant logic
one or state changes from logic one to logic zero will not be visible in the list of
indications. Signals are not time tagged. In order to be recorded in the list of
indications the:
The name of the binary input signal that appears in the Indication function is the user-
defined name assigned at configuration of the IED. The same name is used in
disturbance recorder function (DR), indications (IND) and event recorder function
(ER).
778
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
15.10.1 Introduction
Quick, complete and reliable information about disturbances in the primary and/or
in the secondary system is vital, for example, time tagged events logged during
disturbances. This information is used for different purposes in the short term (for
example corrective actions) and in the long term (for example Functional Analysis).
The event recorder logs all selected binary input signals connected to the
Disturbance report function. Each recording can contain up to 150 time-tagged events.
The event recorder information is available for the disturbances locally in the IED.
779
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
The name of the binary input signal that appears in the event recording is the user-
defined name assigned when configuring the IED. The same name is used in the
disturbance recorder function (DR), indications (IND) and event recorder function
(ER).
The event record is stored as a part of the disturbance report information (ER, DR,
IND, TVR and FL) and managed via the local HMI or PCM600.
15.11.1 Introduction
Information about the pre-fault and fault values for currents and voltages are vital
for the disturbance evaluation.
The Trip value recorder calculates the values of all selected analog input signals
connected to the Disturbance report function. The result is magnitude and phase
angle before and during the fault for each analog input signal.
The trip value recorder information is available for the disturbances locally in the
IED.
780
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
The trip value recorder information is an integrated part of the disturbance record
(Comtrade file).
When the disturbance report function is triggered the sample for the fault
interception is searched for, by checking the non-periodic changes in the analog
input signals. The channel search order is consecutive, starting with the analog
input with the lowest number.
When a starting point is found, the Fourier estimation of the pre-fault values of the
complex values of the analog signals starts 1.5 cycle before the fault sample. The
estimation uses samples during one period. The post-fault values are calculated
using the Recursive Least Squares (RLS) method. The calculation starts a few
samples after the fault sample and uses samples during 1/2 - 2 cycles depending on
the shape of the signals.
If no starting point is found in the recording, the disturbance report trig sample is
used as the start sample for the Fourier estimation. The estimation uses samples
during one cycle before the trig sample. In this case the calculated values are used
both as pre-fault and fault values.
The name of the analog input signal that appears in the Trip value recorder function
is the user-defined name assigned when the IED is configured. The same name is
used in the Disturbance recorder function (DR).
The trip value record is stored as a part of the disturbance report information (ER,
DR, IND, TVR and fault locator) and managed in via the local HMI or PCM600.
781
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
15.12.1 Introduction
The Disturbance recorder function supplies fast, complete and reliable information
about disturbances in the power system. It facilitates understanding system
behavior and related primary and secondary equipment during and after a
disturbance. Recorded information is used for different purposes in the short
perspective (for example corrective actions) and long perspective (for example
Functional Analysis).
The Disturbance recorder acquires sampled data from all selected analog input and
binary signals connected to the Disturbance report function (maximum 40 analog
and 96 binary signals). The binary signals are the same signals as available under
the event recorder function.
The disturbance recorder information for the last 100 disturbances are saved in the
IED and the local HMI is used to view the list of recordings.
782
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
Upon detection of a fault condition (triggering), the disturbance is time tagged and
the data storage continues in a post-fault buffer. The storage process continues as
long as the fault condition prevails - plus a certain additional time. This is called
the post-fault time and it can be set in the disturbance report.
The above mentioned two parts form a disturbance recording. The whole memory,
intended for disturbance recordings, acts as a cyclic buffer and when it is full, the
oldest recording is overwritten. The last 100 recordings are stored in the IED.
The time tagging refers to the activation of the trigger that starts the disturbance
recording. A recording can be trigged by, manual start, binary input and/or from
analog inputs (over-/underlevel trig).
A user-defined name for each of the signals can be set. These names are common
for all functions within the disturbance report functionality.
• Saving the data for analog channels with corresponding data for binary signals
• Add relevant data to be used by the Disturbance handling tool (part of PCM 600)
• Compression of the data, which is performed without losing any data accuracy
• Storing the compressed data in a non-volatile memory (flash memory)
The recording files comply with the Comtrade standard IEC 60255-24 and are
divided into three files; a header file (HDR), a configuration file (CFG) and a data
file (DAT).
The header file (optional in the standard) contains basic information about the
disturbance, that is, information from the Disturbance report sub-functions (ER,
TVR and FL). The Disturbance handling tool use this information and present the
recording in a user-friendly way.
General:
Analog:
783
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring
Binary:
• Signal names
• Status of binary input signals
The data file, which also is mandatory, containing values for each input channel for
each sample in the record (scaled value). The data file also contains a sequence
number and time stamp for each set of samples.
The last 8 recordings, out of maximum 100, are available for transfer to the master.
When the last one is transferred and acknowledged new recordings in the IED will
appear, in the master points of view (even if they already where stored in the IED).
To be able to report 40 analog channels from the IED using IEC 60870-5-103 the
first 8 channels are placed in the public range and the next 32 are placed in the
private range. To comply the standard the first 8 must be configured according to
table 521.
784
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring
The binary signals connected to BxRBDR are reported by polling. The function
blocks include function type and information number.
785
Technical reference manual
786
1MRK505183-UEN C Section 16
Metering
Section 16 Metering
S00947 V1 EN
16.1.1 Introduction
Pulse counter (PCGGIO) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module and then
read by the pulse counter function. A scaled service value is available over the
station bus. The special Binary input module with enhanced pulse counting
capabilities must be ordered to achieve this functionality.
The reporting time period can be set in the range from 1 second to 60 minutes and
is synchronized with absolute system time. Interrogation of additional pulse
counter values can be done with a command (intermediate reading) for a single
counter. All active counters can also be read by the LON General Interrogation
command (GI) or IEC 61850.
787
Technical reference manual
Section 16 1MRK505183-UEN C
Metering
The reported value to station HMI over the station bus contains Identity, Scaled
Value (pulse count x scale), Time, and Pulse Counter Quality. The Pulse Counter
Quality consists of:
The transmission of the counter value by SPA can be done as a service value, that
is, the value frozen in the last integration cycle is read by the station HMI from the
database. PCGGIO updates the value in the database when an integration cycle is
finished and activates the NEW_VAL signal in the function block. This signal can
be connected to an Event function block, be time tagged, and transmitted to the
station HMI. This time corresponds to the time when the value was frozen by the
function.
The pulse counter function requires a binary input card, BIMp, that
is specially adapted to the pulse counter function.
Figure 420 shows the pulse counter function block with connections of the inputs
and outputs.
788
Technical reference manual
1MRK505183-UEN C Section 16
Metering
The BI_PULSE input is connected to the used input of the function block for the
Binary Input Module (BIM).
Each pulse counter function block has four binary output signals that can be
connected to an Event function block for event recording: INVALID, RESTART,
BLOCKED and NEW_VAL. The SCAL_VAL signal can be connected to the IEC
Event function block.
The INVALID signal is a steady signal and is set if the Binary Input Module,
where the pulse counter input is located, fails or has wrong configuration.
The RESTART signal is a steady signal and is set when the reported value does not
comprise a complete integration cycle. That is, in the first message after IED start-
up, in the first message after deblocking, and after the counter has wrapped around
during last integration cycle.
The BLOCKED signal is a steady signal and is set when the counter is blocked.
There are two reasons why the counter is blocked:
The NEW_VAL signal is a pulse signal. The signal is set if the counter value was
updated since last report.
IEC05000709-2-en.vsd
IEC05000709 V3 EN
789
Technical reference manual
Section 16 1MRK505183-UEN C
Metering
790
Technical reference manual
1MRK505183-UEN C Section 16
Metering
16.2.1 Introduction
Outputs from Measurements (CVMMXU) function can be used to calculate
energy. Active as well as reactive values are calculated in import and export
direction. Values can be read or generated as pulses. Maximum demand power
values are also calculated by the function.
The maximum demand values for active and reactive power are calculated for the
set time tEnergy and the maximum value is stored in a register available over
communication and from outputs MAXPAFD, MAXPARD, MAXPRFD,
MAXPRRD for the active and reactive power forward and reverse direction until
reset with input signal RSTDMD or from the local HMI reset menu.
791
Technical reference manual
Section 16 1MRK505183-UEN C
Metering
CVMMXU ETPMMTR
PINST P
QINST Q
STACC
TRUE
RSTACC
FALSE
RSTDMD
FALSE
IEC07000121-2-en.vsd
IEC07000121 V2 EN
IEC07000120-2-en.vsd
IEC07000120 V2 EN
792
Technical reference manual
1MRK505183-UEN C Section 16
Metering
793
Technical reference manual
Section 16 1MRK505183-UEN C
Metering
794
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
17.1 Overview
17.2.1 Introduction
The IED is equipped with single or double optical Ethernet rear ports (order
dependent) for IEC 61850-8-1 station bus communication. IEC 61850-8-1
communication is also possible from the optical Ethernet front port. IEC 61850-8-1
protocol allows intelligent electrical devices (IEDs) from different vendors to
exchange information and simplifies system engineering. Peer-to-peer
communication according to GOOSE is part of the standard. Disturbance files
uploading is provided.
795
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
17.2.2.1 Introduction
IEC07000124-2-en.vsd
IEC07000124 V2 EN
SP16GGIO
BLOCK
^IN1
^IN2
^IN3
^IN4
^IN5
^IN6
^IN7
^IN8
^IN9
^IN10
^IN11
^IN12
^IN13
^IN14
^IN15
^IN16
IEC07000125-2-en.vsd
IEC07000125 V2 EN
796
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
The function does not have any parameters available in the local HMI or PCM600.
Upon receiving an analog signal at its input, IEC61850 generic communication I/O
functions (MVGGIO) will give the instantaneous value of the signal and the range,
as output values. In the same time, it will send over IEC 61850-8-1 the value, to
other IEC 61850 clients in the substation.
797
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
IEC05000408-2-en.vsd
IEC05000408 V2 EN
798
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
17.3.1 Introduction
The IEC 61850-9-2LE process bus communication protocol enables an IED to
communicate with devices providing measured values in digital format, commonly
known as Merging Units (MU). The physical interface in the IED that is used for
the communication is the OEM modules (the two port module version) "CD" port.
The IED communicates with the MUs over the process bus via the OEM module
port "CD". For the user, the MU appears in the IED as a normal analogue input
module and is engineered in the very same way.
799
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
IED
Application
Station Wide
Preprocessing blocks Preprocessing blocks GPS Clock
SMAI SMAI
MU1 MU2
Splitter
Electrical-to-
Optical Converter
1PPS
TRM module OEM Module
CD
110 V 1A 1A
IEC61850-9-2LE
Ethernet Switch
IEC61850-9-2LE
IEC61850-9-2LE
ABB ABB
1PPS 1PPS
Merging Merging
Unit Unit
Combi Combi
CT CT
Sensor Sensor
Conventional VT
en08000072-2.vsd
IEC08000072 V2 EN
Figure 427: Example of signal path for sampled analogue values from MU and
conventional CT/VT
800
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
Timeout
TSYNCERR Indicates that there is some timeout on any configured time source or
the time quality is worse than specified in SynchAccLevel. The timeout is
individually specified per time source (PPS, IRIG-B, SNTP etc.) See section
"Time synchronization"
Blocking condition
Application synch is not required for differential protection based on ECHO mode.
A missing PPS however will lead to a drift between MU and IED. Therefore
protection functions in this case will be blocked.
801
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
802
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
17.4.1 Introduction
An optical network can be used within the substation automation system. This
enables communication with the IED through the LON bus from the operator’s
workplace, from the control center and also from other terminals.
In this document the most common addresses for commands and events are
available. For other addresses, refer to section "Related documents".
It is assumed that the reader is familiar with LON communication protocol in general.
The LON bus links the different parts of the protection and control system. The
measured values, status information, and event information are spontaneously sent
to the higher-level devices. The higher-level devices can read and write memorized
values, setting values, and other parameter data when required. The LON bus also
enables the bay level devices to communicate with each other to deliver, for
example, interlocking information among the terminals without the need of a bus
master.
803
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
The LonTalk protocol supports two types of application layer objects: network
variables and explicit messages. Network variables are used to deliver short
messages, such as measuring values, status information, and interlocking/blocking
signals. Explicit messages are used to transfer longer pieces of information, such as
events and explicit read and write messages to access device data.
The benefits achieved from using the LON bus in protection and control systems
include direct communication among all terminals in the system and support for
multi-master implementations. The LON bus also has an open concept, so that the
terminals can communicate with external devices using the same standard of
network variables.
LON protocol
Configuration of LON
Lon Network Tool (LNT 505) is a multi-purpose tool for LonWorks network
configuration. All the functions required for setting up and configuring a
LonWorks network, is easily accessible on a single tool program. For more
information, refer to the operator's manual.
Vertical communication
Vertical communication describes communication between the monitoring devices
and protection and control IEDs. This communication includes sending of changed
process data to monitoring devices as events and transfer of commands, parameter
data and disturbance recorder files. This communication is implemented using
explicit messages.
804
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
signal is changed in the IED, one message with the value, quality and time is
transmitted from terminal.
Binary events
Binary events are generated in event function blocks EVENT:1 to EVENT:20 in
the 670 series IEDs. The event function blocks have predefined LON addresses.
table 542 shows the LON addresses to the first input on the event function blocks.
The addresses to the other inputs on the event function block are consecutive after
the first input. For example, input 15 on event block EVENT:17 has the address
1280 + 14 (15-1) = 1294.
For double indications only the first eight inputs 1–8 must be used. Inputs 9–16 can
be used for other type of events at the same event block.
As basic, three event function blocks EVENT:1 to EVENT:3 running with a fast
loop time (3 ms) is available in the 670 series IEDs. The remaining event function
blocks EVENT:4 to EVENT:9 runs with a loop time on 8 ms and EVENT:10 to
EVENT:20 runs with a loop time on 100 ms. The event blocks are used to send
binary signals, integers, real time values like analogue data from measuring
functions and mA input modules as well as pulse counter signals.
The first LON address in every event function block is found in table 542
805
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
Event masks
The event mask for each input can be set individually from Parameter Setting Tool
(PST) under: Settings/ General Settings/ Monitoring / EventFunction as follows:
• No events
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect, event system itself make the reporting decision, (reporting criteria
for integers has no semantic, prefer to be set by the user)
The following type of signals from application functions can be connected to the
event function block.
Single indication
Directly connected binary IO signal via binary input function block (SMBI) is
always reported on change, no changed detection is done in the event function
block. Other Boolean signals, for example a start or a trip signal from a protection
function is event masked in the event function block.
Double indications
Double indications can only be reported via switch-control (SCSWI) functions, the
event reporting is based on information from switch-control, no change detection is
done in the event function block.
Directly connected binary IO signal via binary input function block (SMBI) is not
possible to handle as double indication. Double indications can only be reported for
the first 8 inputs on an event function block.
Analog value
All analog values are reported cyclic, the reporting interval is taken from the
connected function if there is a limit supervised signal, otherwise it is taken from
the event function block.
Command handling
806
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
Both the SPA-bus command messages (R or W) and the reply messages (D, A or
N) are sent using the same message code. It is mandatory that one device sends out
only one SPA-bus message at a time to one node and waits for the reply before
sending the next message.
For commands from the operator workplace to the IED for apparatus control, That
is, the function blocks type SCSWI 1 to 32, SXCBR 1 to 18 and SXSWI 1 to 28;
the SPA addresses are according to table 543.
Horizontal communication
Network variables are used for communication between 500 series and 670 series
IEDs. The supported network variable type is SNVT_state (NV type 83).
SNVT_state is used to communicate the state of a set of 1 to 16 Boolean values.
This is an overview for configuring the network variables for 670 series IEDs.
807
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
LON
en05000718.vsd
IEC05000718 V2 EN
The network variable connections are done from the NV Connection window.
From LNT window select Connections/ NVConnections/ New.
en05000719.vsd
IEC05000719 V1 EN
There are two ways of downloading NV connections. Either the users can use the
drag-and-drop method where they can select all nodes in the device window, drag
them to the Download area in the bottom of the program window and drop them
808
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
there; or, they can perform it by selecting the traditional menu, Configuration/
Download.
en05000720.vsd
IEC05000720 V1 EN
Communication ports
The serial communication module (SLM) is used for SPA or IEC60870-5-103 and
LON communication. This module is a mezzanine module, and can be placed on
the Main Processing Module (NUM). The serial communication module can have
connectors for two plastic fibre cables (snap-in) or two glass fibre cables (ST,
bayonet) or a combination of plastic and glass fibre. Three different types are
available depending on type of fibre. The incoming optical fibre is connected to the
RX receiver input, and the outgoing optical fibre to the TX transmitter output.
When the fibre optic cables are laid out, pay special attention to the instructions
concerning the handling and connection of the optical fibres. The module is
identified with a number on the label on the module.
Table 543: SPA addresses for commands from the operator workplace to the IED for apparatus
control
Name Function SPA Description
block address
BL_CMD SCSWI01 1 I 5115 SPA parameters for block
command
BL_CMD SCSWI02 1 I 5139 SPA parameters for block
command
BL_CMD SCSWI02 1 I 5161 SPA parameters for block
command
BL_CMD SCSWI04 1 I 5186 SPA parameters for block
command
Table continues on next page
809
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
810
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
811
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
812
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
813
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
814
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
815
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
816
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
817
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
818
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
819
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
820
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
17.5.1 Introduction
In this section the most common addresses for commands and events are available.
For other addresses, refer to section "Related documents".
821
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
It is assumed that the reader is familiar with the SPA communication protocol in
general.
The master requests slave information using request messages and sends
information to the slave in write messages. Furthermore, the master can send all
slaves in common a broadcast message containing time or other data. The inactive
state of bus transmit and receive lines is a logical "1".
SPA protocol
The tables below specify the SPA addresses for reading data from and writing data
to an IED with the SPA communication protocol implemented.
The SPA addresses for the mA input service values (MIM3 to MIM16) are found
in table 547.
822
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
823
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
The SPA addresses for the pulse counter values PCGGIO:1 to PCGGIO:16 are
found in table 548.
824
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
I/O modules
To read binary inputs, the SPA-addresses for the outputs of the I/O-module
function block are used, that is, the addresses for BI1 – BI16. For SPA addresses,
refer to section "Related documents".
The signals can be individually controlled from the operator station, remote-control
gateway, or from the local HMI on the IED. For Single command, 16 signals
function block, SINGLECMD:1 to SINGLECMD:3, the address is for the first
output. The other outputs follow consecutively after the first one. For example,
output 7 on the SINGLECMD:2 function block has the 5O533 address.
825
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
Function block SPA address CMD Input SPA address CMD output
SINGLECMD1-Cmd5 4-S-4643 5-O-515
SINGLECMD1-Cmd6 4-S-4644 5-O-516
SINGLECMD1-Cmd7 4-S-4645 5-O-517
SINGLECMD1-Cmd8 4-S-4646 5-O-518
SINGLECMD1-Cmd9 4-S-4647 5-O-519
SINGLECMD1-Cmd10 4-S-4648 5-O-520
SINGLECMD1-Cmd11 4-S-4649 5-O-521
SINGLECMD1-Cmd12 4-S-4650 5-O-522
SINGLECMD1-Cmdt13 4-S-4651 5-O-523
SINGLECMD1-Cmd14 4-S-4652 5-O-524
SINGLECMD1-Cmd15 4-S-4653 5-O-525
SINGLECMD1-Cmd16 4-S-4654 5-O-526
SINGLECMD2-Cmd1 4-S-4672 5-O-527
SINGLECMD2-Cmd2 4-S-4673 5-O-528
SINGLECMD2-Cmdt3 4-S-4674 5-O-529
SINGLECMD2-Cmd4 4-S-4675 5-O-530
SINGLECMD2-Cmd5 4-S-4676 5-O-531
SINGLECMD2-Cmd6 4-S-4677 5-O-532
SINGLECMD2-Cmd7 4-S-4678 5-O-533
SINGLECMD2-Cmd8 4-S-4679 5-O-534
SINGLECMD2-Cmd9 4-S-4680 5-O-535
SINGLECMD2-Cmd10 4-S-4681 5-O-536
SINGLECMD2-Cmd11 4-S-4682 5-O-537
SINGLECMD2-Cmd12 4-S-4683 5-O-538
SINGLECMD2-Cmd13 4-S-4684 5-O-539
SINGLECMD2-Cmd14 4-S-4685 5-O-540
SINGLECMD2-Cmd15 4-S-4686 5-O-541
SINGLECMD2-Cmd16 4-S-4687 5-O-542
SINGLECMD3-Cmd1 4-S-4705 5-O-543
SINGLECMD3-Cmd2 4-S-4706 5-O-544
SINGLECMD3-Cmd3 4-S-4707 5-O-545
SINGLECMD3-Cmd4 4-S-4708 5-O-546
SINGLECMD3-Cmd5 4-S-4709 5-O-547
SINGLECMD3-Cmd6 4-S-4710 5-O-548
SINGLECMD3-Cmd7 4-S-4711 5-O-549
SINGLECMD3-Cmd8 4-S-4712 5-O-550
SINGLECMD3-Cmd9 4-S-4713 5-O-551
SINGLECMD3-Cmd10 4-S-4714 5-O-552
SINGLECMD3-Cmd11 4-S-4715 5-O-553
Table continues on next page
826
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
Function block SPA address CMD Input SPA address CMD output
SINGLECMD3-Cmd12 4-S-4716 5-O-554
SINGLECMD3-Cmd13 4-S-4717 5-O-555
SINGLECMD3-Cmd14 4-S-4718 5-O-556
SINGLECMD3-Cmd15 4-S-4719 5-O-557
SINGLECMD3-Cmd16 4-S-4720 5-O-558
Figure 431 shows an application example of how the user can, in a simplified way,
connect the command function via the configuration logic circuit in a protection
IED for control of a circuit breaker.
A pulse via the binary outputs of the IED normally performs this type of command
control. The SPA addresses to control the outputs OUT1 – OUT16 in SINGLECMD:
1 are shown in table 549.
SINGLECMD PULSETIMER
BLOCK ^OUT1 INPUT OUT To output board, CLOSE
^OUT2 #1.000 T
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7 AND PULSETIMER
^OUT8 INPUT1 OUT INPUT OUT To output board, OPEN
INPUT2 NOUT T
^OUT9 #1.000
INPUT3
^OUT10
INPUT4N
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16
SYNCH OK
IEC05000717-2-en.vsd
IEC05000717 V2 EN
Figure 431: Application example showing a simplified logic diagram for control
of a circuit breaker
The MODE input defines if the output signals from SINGLECMD:1 is off, steady
or pulsed signals. This is set in Parameter Setting Tool (PST) under: Setting /
General Settings / Control / Commands / Single Command.
Event function
Event function is intended to send time-tagged events to the station level (for
example, operator workplace) over the station bus. The events are there presented
in an event list. The events can be created from both internal logical signals and
binary input channels. All the internal signals are time tagged in the main
processing module, while the binary input channels are time tagged directly on
each I/O module. The events are produced according to the set event masks. The
event masks are treated commonly for both the LON and SPA channels. All events
according to the event mask are stored in a buffer, which contains up to 1000
events. If new events appear before the oldest event in the buffer is read, the oldest
event is overwritten and an overflow alarm appears.
827
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
Two special signals for event registration purposes are available in the IED,
Terminal Restarted (0E50) and Event buffer overflow (0E51).
The input parameters can be set individually from the Parameter Setting Tool
(PST) under: Setting / General Setting / Monitoring / Event Function as follows:
• No events
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect, event system itself make the reporting decision, (reporting criteria
for integers has no semantic, prefer to be set by the user)
The Status and event codes for the Event functions are found in table 550.
These values are only applicable if the Event mask is masked ≠ OFF.
828
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
EVENT
Block BLOCK
ILRANG ^INPUT1
PSTO ^INPUT2
UL12RANG ^INPUT3
UL23RANG ^INPUT4
UL31RANG ^INPUT5
3I0RANG ^INPUT6
3U0RANG ^INPUT7
FALSE ^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
IEC07000065-2-en.vsd
IEC07000065 V2 EN
The serial communication module (SLM) is used for SPA or IEC 60870-5-103 and
LON communication. This module is a mezzanine module, and can be placed on
the Analog/Digital conversion module (ADM). The serial communication module
can have connectors for two plastic fibre cables (snap-in) or two glass fibre cables
(ST, bayonet) or a combination of plastic and glass fibre. Three different types are
available depending on type of fibre.
The incoming optical fibre is connected to the RX receiver input, and the outgoing
optical fibre to the TX transmitter output. When the fibre optic cables are laid out,
pay special attention to the instructions concerning the handling and connection of
the optical fibres. The module is identified with a number on the label on the module.
The procedure to set the transfer rate and slave number can be found in the
Installation and commissioning manual for respective IEDs.
17.5.3 Design
When communicating locally with a computer (PC) in the station, using the rear
SPA port, the only hardware needed for a station monitoring system is:
• Optical fibres
• Opto/electrical converter for the PC
• PC
When communicating remotely with a PC using the rear SPA port, the same
hardware and telephone modems are needed.
When communicating between the local HMI and a PC, the only hardware required
is a front-connection cable.
829
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
17.6.1 Introduction
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must
have software that can interpret the IEC 60870-5-103 communication messages.
17.6.2.1 General
830
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
principle. The master must have software that can interpret IEC 60870-5-103
communication messages.
• Event handling
• Report of analog service values (measurements)
• Fault location
• Command handling
• Autorecloser ON/OFF
• Teleprotection ON/OFF
• Protection ON/OFF
• LED reset
• Characteristics 1 - 4 (Setting groups)
• File transfer (disturbance files)
• Time synchronization
For detailed information about IEC 60870-5-103, refer to the IEC 60870 standard
part 5: Transmission protocols, and to the section 103: Companion standard for the
informative interface of protection equipment.
IEC 60870-5-103
The tables in the following sections specify the information types supported by the
IEDs with the communication protocol IEC 60870-5-103 implemented.
Number of instances: 1
831
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
Number of instances: 1
Number of instances: 4
FUNCTION TYPE parameter for each block in private range. Default values are
defined in private range 1 - 4. One for each instance.
INFORMATION NUMBER is required for each output signal. Default values are 1
- 8.
Info. no. Message Supported
1 Output signal 01 Yes
2 Output signal 02 Yes
3 Output signal 03 Yes
4 Output signal 04 Yes
5 Output signal 05 Yes
6 Output signal 06 Yes
7 Output signal 07 Yes
8 Output signal 08 Yes
Status
Terminal status indications in monitor direction, I103IED
Indication block for status in monitor direction with defined IED functions.
Number of instances: 1
832
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
Number of instances: 20
FUNCTION TYPE parameter for each block in private range. Default values are
defined in private range 5 - 24. One for each instance.
INFORMATION NUMBER is required for each input signal. Default values are
defined in range 1 - 8.
Info. no. Message Supported
1 Input signal 01 Yes
2 Input signal 02 Yes
3 Input signal 03 Yes
4 Input signal 04 Yes
5 Input signal 05 Yes
6 Input signal 06 Yes
7 Input signal 07 Yes
8 Input signal 08 Yes
Number of instances: 1
833
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
Number of instances: 1
Number of instances: 1
Info. no. Message Supported
64 Start L1 Yes
65 Start L2 Yes
66 Start L3 Yes
67 Start IN Yes
84 General start Yes
69 Trip L1 Yes
70 Trip L2 Yes
71 Trip L3 Yes
68 General trip Yes
74 Fault forward/line Yes
75 Fault reverse/busbar Yes
78 Zone 1 Yes
79 Zone 2 Yes
80 Zone 3 Yes
81 Zone 4 Yes
82 Zone 5 Yes
76 Signal transmitted Yes
77 Signal received Yes
73 SCL, Fault location in ohm Yes
834
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
Number of instances: 1
Info. no. Message Supported
64 Start L1 Yes
65 Start L2 Yes
66 Start L3 Yes
67 Start IN Yes
84 General start Yes
69 Trip L1 Yes
70 Trip L2 Yes
71 Trip L3 Yes
68 General trip Yes
74 Fault forward/line Yes
75 Fault reverse/busbar Yes
85 Breaker failure Yes
86 Trip measuring system L1 Yes
87 Trip measuring system L2 Yes
88 Trip measuring system L3 Yes
89 Trip measuring system N Yes
90 Over current trip I> Yes
91 Over current trip I>> Yes
92 Earth fault trip IN> Yes
93 Earth fault trip IN>> Yes
Number of instances: 1
835
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
Measurands
Function blocks in monitor direction for input measurands. Typically connected to
monitoring function, for example to power measurement .
The IED reports all valid measuring types depending on connected signals.
Upper limit for measured currents, active/reactive-power is 2.4 times rated value.
Upper limit for measured voltages and frequency is 1.2 times rated value.
Info. no. Message Supported
148 IL1 Yes
144, 145, IL2 Yes
148
148 IL3 Yes
147 IN, Neutral current Yes
148 UL1 Yes
148 UL2 Yes
148 UL3 Yes
145, 146 UL1-UL2 Yes
147 UN, Neutral voltage Yes
146, 148 P, active power Yes
146, 148 Q, reactive power Yes
148 f, frequency Yes
FUNCTION TYPE parameter for each block in private range. Default values are
defined in private range 25 – 27. One for each instance.
836
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
Disturbance recordings
The following elements are used in the ASDUs (Application Service Data Units)
defined in the standard.
Analog signals, 40-channels: the channel number for each channel has to be
specified. Channels used in the public range are 1 to 8 and with:
Channel number used for the remaining 32 analog signals are numbers in the
private range 64 to 95.
Binary signals, 96-channels: for each channel the user can specify a FUNCTION
TYPE and an INFORMATION NUMBER.
Disturbance upload
All analog and binary signals that are recorded with disturbance recorder can be
reported to the master. The last eight disturbances that are recorded are available
for transfer to the master. A successfully transferred disturbance (acknowledged by
the master) will not be reported to the master again.
837
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
This section describes all data that is not exactly as specified in the standard.
ASDU23
• Bit TP: the protection equipment has tripped during the fault
• Bit TM: the disturbance data are currently being transmitted
• Bit TEST: the disturbance data have been recorded during normal operation or
test mode.
• Bit OTEV: the disturbance data recording has been initiated by another event
than start
The only information that is easily available is test-mode status. The other
information is always set (hard coded) to:
ASDU26
When a disturbance has been selected by the master; (by sending ASDU24), the
protection equipment answers by sending ASDU26, which contains an information
element named NOF (number of grid faults). This number must indicate fault
number in the power system,that is, a fault in the power system with several trip
and auto-reclosing has the same NOF (while the FAN must be incremented). NOF
is in 670 series, just as FAN, equal to disturbance number.
To get INF and FUN for the recorded binary signals there are parameters on the
disturbance recorder for each input. The user must set these parameters to whatever
he connects to the corresponding input.
838
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
839
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
Supported
ASDU Yes
6 Time synchronization Yes
7 General interrogation Yes
10 Generic data No
20 General command Yes
21 Generic command No
24 Order for disturbance data transmission Yes
25 Acknowledgement for distance data transmission Yes
Selection of basic application functions
Test mode No
Blocking of monitoring direction Yes
Disturbance data Yes
Private data Yes
Generic services No
The serial communication module (SLM) is used for SPA or IEC 60870-5-103 and
LON communication. This module is a mezzanine module, and can be placed on
the Analog/Digital conversion module (ADM). The serial communication module
can have connectors for two plastic fibre cables (snap-in) or two glass fibre cables
(ST, bayonet) or a combination of plastic and glass fibre. Three different types are
available depending on type of fibre.
The incoming optical fibre is connected to the RX receiver input, and the outgoing
optical fibre to the TX transmitter output. When the fibre optic cables are laid out,
pay special attention to the instructions concerning the handling and connection of
the optical fibres. The module is identified with a number on the label on the module.
IEC05000689-2-en.vsd
IEC05000689 V2 EN
I103CMD
BLOCK 16-AR
FUNTYPE 17-DIFF
18-PROT
IEC05000684-2-en.vsd
IEC05000684 V2 EN
840
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
I103USRCMD
BLOCK OUTPUT1
PULSEMOD OUTPUT2
T OUTPUT3
FUNTYPE OUTPUT4
INFNO_1 OUTPUT5
INFNO_2 OUTPUT6
INFNO_3 OUTPUT7
INFNO_4 OUTPUT8
INFNO_5
INFNO_6
INFNO_7
INFNO_8
IEC05000693-2-en.vsd
IEC05000693 V2 EN
I103IED
BLOCK
19_LEDRS
23_GRP1
24_GRP2
25_GRP3
26_GRP4
21_TESTM
FUNTYPE
IEC05000688-2-en.vsd
IEC05000688 V2 EN
I103USRDEF
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
FUNTYPE
INFNO_1
INFNO_2
INFNO_3
INFNO_4
INFNO_5
INFNO_6
INFNO_7
INFNO_8
IEC05000694-2-en.vsd
IEC05000694 V2 EN
I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
FUNTYPE
IEC05000692-2-en.vsd
IEC05000692 V2 EN
I103EF
BLOCK
51_EFFW
52_EFREV
FUNTYPE
IEC05000685-2-en.vsd
IEC05000685 V2 EN
841
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
I103FLTDIS
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
84_STGEN
69_TRL1
70_TRL2
71_TRL3
68_TRGEN
74_FW
75_REV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
76_TRANS
77_RECEV
73_SCL
FLTLOC
ARINPROG
FUNTYPE
IEC05000686-2-en.vsd
IEC05000686 V2 EN
I103FLTSTD
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
84_STGEN
69_TRL1
70_TRL2
71_TRL3
68_TRGEN
74_FW
75_REV
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FUNTYPE
IEC05000687-2-en.vsd
IEC05000687 V2 EN
I103AR
BLOCK
16_ARACT
128_CBON
130_UNSU
FUNTYPE
IEC05000683-2-en.vsd
IEC05000683 V2 EN
842
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
I103MEAS
BLOCK
IL1
IL2
IL3
IN
UL1
UL2
UL3
UL1L2
UN
P
Q
F
FUNTYPE
IEC05000690-2-en.vsd
IEC05000690 V2 EN
I103MEASUSR
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
FUNTYPE
INFNO
IEC05000691-2-en.vsd
IEC05000691 V2 EN
843
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
844
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
845
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
846
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
847
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
848
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
849
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
850
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
IEC07000048-2-en.vsd
IEC07000048 V2 EN
851
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
852
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
853
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
IEC07000047-2-en.vsd
IEC07000047 V2 EN
854
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
855
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
17.9.1 Introduction
The IED can be provided with a function to send and receive signals to and from
other IEDs via the interbay bus. The send and receive function blocks has 16 outputs/
inputs that can be used, together with the configuration logic circuits, for control
purposes within the IED or via binary outputs. When it is used to communicate
with other IEDs, these IEDs have a corresponding Multiple transmit function block
with 16 outputs to send the information received by the command block.
Sixteen signals can be connected and they will then be sent to the multiple
command block in the other IED. The connections are set with the LON Network
Tool (LNT).
The output signals, here OUTPUT1 to OUTPUT16, are then available for
configuration to built-in functions or via the configuration logic circuits to the
binary outputs of the IED.
MULTICMDRCV also has a supervision function, which sets the output VALID to
0 if the block does not receive data within set maximum time.
17.9.3 Design
17.9.3.1 General
The output signals can be of the types Off, Steady, or Pulse. The setting is done on
the MODE settings, common for the whole block, from PCM600.
856
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
• 0 = Off sets all outputs to 0, independent of the values sent from the station
level, that is, the operator station or remote-control gateway.
• 1 = Steady sets the outputs to a steady signal 0 or 1, depending on the values
sent from the station level.
• 2 = Pulse gives a pulse with one execution cycle duration, if a value sent from
the station level is changed from 0 to 1. That means that the configured logic
connected to the command function blocks may not have a cycle time longer
than the execution cycle time for the command function block.
IEC06000007-2-en.vsd
IEC06000007 V2 EN
MULTICMDSND
BLOCK ERROR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
IEC06000008-2-en.vsd
IEC06000008 V2 EN
857
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication
858
Technical reference manual
1MRK505183-UEN C Section 17
Station communication
859
Technical reference manual
860
1MRK505183-UEN C Section 18
Remote communication
18.1.1 Introduction
The remote end data communication is used either for the transmission of current
values together with maximum 8 binary signals in the line differential protection,
or for transmission of only binary signals, up to 192 signals, in the other 670 series
IEDs. The binary signals are freely configurable and can, thus, be used for any
purpose, for example, communication scheme related signals, transfer trip and/or
other binary signals between IEDs.
Communication between two IEDs requires that each IED is equipped with an
LDCM (Line Data Communication Module). The LDCMs are then interfaces to a
64 kbit/s communication channel for duplex communication between the IEDs.
The IED can be equipped with up to four short range, medium range or long range
LDCM.
861
Technical reference manual
Section 18 1MRK505183-UEN C
Remote communication
Start Stop
Information CRC
flag flag
IEC01000134 V1 EN
The start and stop flags are the 0111 1110 sequence (7E hexadecimal), defined in
the HDLC standard. The CRC is designed according to the standard CRC16
definition. The optional address field in the HDLC frame is not used instead a
separate addressing is included in the data field.
The address field is used for checking that the received message originates from
the correct equipment. There is always a risk that multiplexers occasionally mix the
messages up. Each terminal in the system is given a number. The terminal is then
programmed to accept messages from a specific terminal number. If the CRC
function detects a faulty message, the message is thrown away and not used in the
evaluation.
When the communication is used for line differential purpose, the transmitted data
consists of three currents, clock information, trip-, block- and alarm-signals and
eight binary signals which can be used for any purpose. The three currents are
represented as sampled values.
When the communication is used exclusively for binary signals, the full data
capacity of the communication channel is used for the binary signal purpose which
gives the capacity of 192 signals.
862
Technical reference manual
1MRK505183-UEN C Section 18
Remote communication
IEC07000043-2-en.vsd
IEC07000043 V2 EN
LDCMRecBinStat2
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
REMGPSER
SUBSTITU
LOWLEVEL
IEC07000044-2-en.vsd
IEC07000044 V2 EN
LDCMRecBinStat3
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
REMGPSER
SUBSTITU
LOWLEVEL
IEC05000451-2-en.vsd
IEC05000451 V2 EN
863
Technical reference manual
Section 18 1MRK505183-UEN C
Remote communication
864
Technical reference manual
1MRK505183-UEN C Section 18
Remote communication
865
Technical reference manual
Section 18 1MRK505183-UEN C
Remote communication
866
Technical reference manual
1MRK505183-UEN C Section 18
Remote communication
IEC10000017-1-en.vsd
IEC10000017 V1 EN
867
Technical reference manual
Section 18 1MRK505183-UEN C
Remote communication
868
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
Section 19 Hardware
19.1 Overview
xx04000458.eps
IEC04000458 V1 EN
Figure 441: 1/2 19” case with medium local HMI display.
869
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
xx04000459.eps
IEC04000459 V1 EN
Figure 442: 1/2 19” case with small local HMI display.
IEC05000762 V1 EN
Figure 443: 3/4 19” case with medium local HMI display.
xx05000763.eps
IEC05000763 V1 EN
Figure 444: 3/4 19” case with small local HMI display.
870
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
xx04000460.eps
IEC04000460 V1 EN
Figure 445: 1/1 19” case with medium local HMI display.
xx04000461.eps
IEC04000461 V1 EN
Figure 446: 1/1 19” case with small local HMI display.
871
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
872
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
Table 602: Designations for 3/4 x 19” casing with 1 TRM slot
873
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
Table 603: Designations for 3/4 x 19” casing with 2 TRM slot
874
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
Table 604: Designations for 1/1 x 19” casing with 1 TRM slot
IEC08000474 BG V1 EN
SLM X301:A, B, C, D
IRIG-B X302
OEM 2) X311:A, B, C, D
Note!
1) 2-4 LDCM can be included. First LDCM
always in position X313, second LDCM always in
position X303. LDCM can also be in position
X302 and X312 if IRIG-B respective RS485
modules are not included.
2) OEM X311:A, B (IEC 61850-8-1). OEM
X311:C, D (IEC 61850-8-1)(IEC 61850-9-2LE)
875
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
Table 605: Designations for 1/1 x 19” casing with 2 TRM slots
IEC08000475 BG V1 EN
SLM X301:A, B, C, D
IRIG-B or LDCM X302
1,2)
LDCM 2) X303
OEM 4) X311:A, B, C, D
RS485 or LDCM X312
2) 3)
LDCM 2) X313
LDCM 2) X322
LDCM 2) X323
TRM 1 X401
TRM 2 X411
876
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
19.2.1 Overview
Table 606: Basic modules
Module Description
Combined backplane module (CBM) A backplane PCB that carries all internal signals
between modules in an IED. Only the TRM (when
included) is not connected directly to this board.
Universal backplane module (UBM) A backplane PCB that forms part of the IED
backplane with connectors for TRM (when
included), ADM etc.
Power supply module (PSM) Including a regulated DC/DC converter that
supplies auxiliary voltage to all static circuits.
877
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
Module Description
GPS time synchronization module (GSM) Used to provide the IED with GPS time
synchronization.
Static output module (SOM) Module with 6 fast static outputs and 6 change
over output relays.
IRIG-B Time synchronization module (IRIG-B) Module with 2 inputs. One is used for handling
both pulse-width modulated signals and
amplitude modulated signals and one is used for
optical input type ST for PPS time synchronization.
19.2.2.1 Introduction
The combined backplane module (CBM) carries signals between modules in an IED.
19.2.2.2 Functionality
The Compact PCI makes 3.3V or 5V signaling in the backplane possible. The
CBM backplane and connected modules are 5V PCI-compatible.
Some pins on the Compact PCI connector are connected to the CAN bus, to be able
to communicate with CAN based modules.
If a modules self test discovers an error it informs other modules using the Internal
Fail signal IRF.
19.2.2.3 Design
Each PCI connector consists of 2 compact PCI receptacles. The euro connectors
are connected to the CAN bus and used for I/O modules and power supply.
878
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
1 2
en05000516.vsd
IEC05000516 V1 EN
Pos Description
1 CAN slots
2 CPCI slots
1 2
en05000755.vsd
IEC05000755 V1 EN
Pos Description
1 CAN slots
2 CPCI slots
879
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
en05000756.vsd
IEC05000756 V1 EN
Pos Description
1 CBM
19.2.3.1 Introduction
The Universal Backplane Module (UBM) is part of the IED backplane and is
mounted above the CBM. It connects the Transformer input module (TRM) to the
Analog digital conversion module (ADM) and the Numerical module (NUM).
19.2.3.2 Functionality
The Universal Backplane Module connects the CT and VT analog signals from the
transformer input module to the analog digital converter module. The Numerical
processing module (NUM) is also connected to the UBM. The ethernet contact on
the front panel as well as the internal ethernet contacts are connected to the UBM
which provides the signal path to the NUM board.
19.2.3.3 Design
It connects the Transformer input module (TRM) to the Analog digital conversion
module (ADM) and the Numerical module (NUM).
880
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
• for IEDs with two TRM and two ADM. It has four 48 pin euro connectors and
one 96 pin euro connector, see figure 451
• for IEDs with one TRM and one ADM. It has two 48 pin euro connectors and
one 96 pin euro connector, see figure 452.
The 96 pin euro connector is used to connect the NUM board to the backplane. The
48 pin connectors are used to connect the TRM and ADM.
TRM ADM
NUM
AD Data
X1 X2
X3 X4
RS485
X10 X10
Front Ethernet
LHMI connection
port
Ethernet X5
en05000489.vsd
IEC05000489 V1 EN
en05000757.vsd
IEC05000757 V1 EN
881
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
en05000758.vsd
IEC05000758 V1 EN
en05000759.vsd
IEC05000759 V1 EN
Pos Description
1 UBM
19.2.4.1 Introduction
882
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
For communication with high speed modules, e.g. analog input modules and high
speed serial interfaces, the NUM is equipped with a Compact PCI bus. The NUM
is the compact PCI system card i.e. it controls bus mastering, clock distribution and
receives interrupts.
19.2.4.2 Functionality
The NUM has one PMC slot (32-bit IEEE P1386.1 compliant) and two PC-MIP
slots onto which mezzanine cards such as SLM or LDCM can be mounted.
To reduce bus loading of the compact PCI bus in the backplane the NUM has one
internal PCI bus for internal resources and the PMC/PC-MIP slots and external PCI
accesses through the backplane are buffered in a PCI/PCI bridge.
The application code and configuration data are stored in flash memory using a
flash file system.
The NUM is equipped with a real time clock. It uses a capacitor for power backup
of the real time clock.
No forced cooling is used on this standard module because of the low power
dissipation.
883
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
Compact
Flash Logic
PMC
connector
PC-MIP
connector
UBM
Memory Ethernet
North
bridge
Backplane
PCI-PCI-
connector
bridge
CPU
en04000473.vsd
IEC04000473 V1 EN
19.2.5.1 Introduction
The power supply module is used to provide the correct internal voltages and full
isolation between the terminal and the battery system. An internal fail alarm output
is available.
19.2.5.2 Design
There are two types of the power supply module. They are designed for different
DC input voltage ranges see table 608. The power supply module contains a built-
884
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
in, self-regulated DC/DC converter that provides full isolation between the
terminal and the external battery system.
Block diagram
Input connector
Power
Filter supply
Backplane connector
Supervision
99000516.vsd
IEC99000516 V1 EN
885
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
19.2.7.1 Introduction
The transformer input module is used to galvanically separate and transform the
secondary currents and voltages generated by the measuring transformers. The
module has twelve inputs in different combinations of currents and voltage inputs.
19.2.7.2 Design
The transformer module has 12 input transformers. There are several versions of
the module, each with a different combination of voltage and current input
transformers.
Basic versions:
The TRM is connected to the ADM and NUM via the UBM.
For configuration of the input and output signals, refer to section "Signal matrix
for analog inputs SMAI".
886
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
19.2.8.1 Introduction
The Analog/Digital module has twelve analog inputs, 2 PC-MIP slots and 1 PMC
slot. The PC-MIP slot is used for PC-MIP cards and the PMC slot for PMC cards
according to table 610. The OEM card should always be mounted on the ADM
board. The UBM connects the ADM to the transformer input module (TRM).
19.2.8.2 Design
The Analog digital conversion module input signals are voltage and current from
the transformer module. Shunts are used to adapt the current signals to the
electronic voltage level. To gain dynamic range for the current inputs, two shunts
with separate A\D channels are used for each input current. In this way a 20 bit
dynamic range is obtained with a 16 bit A\D converter.
The A\D converted signals goes through a filter with a cut off frequency of 500 Hz
and are reported to the numerical module (NUM) with 1 kHz at 50 Hz system
frequency and 1,2 kHz at 60 Hz system frequency.
887
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
Channel 1
AD1 Channel 2
Channel 3
Channel 4
AD2
Channel 5
1.2v Channel 6
AD3 Channel 7
Channel 8
Channel 9
AD4 Channel 10
Channel 11
Channel 12
PMC
level shift
PC-MIP
2.5v
PCI to PCI
PC-MIP
en05000474.vsd
IEC05000474 V1 EN
888
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
19.2.9.1 Introduction
The binary input module has 16 optically isolated inputs and is available in two
versions, one standard and one with enhanced pulse counting capabilities on the
inputs to be used with the pulse counter function. The binary inputs are freely
programmable and can be used for the input of logical signals to any of the
functions. They can also be included in the disturbance recording and event-
recording functions. This enables extensive monitoring and evaluation of operation
of the IED and for all associated electrical circuits.
19.2.9.2 Design
The Binary input module contains 16 optical isolated binary inputs. The voltage
level of the binary input is selected at order.
For configuration of the input signals, refer to section "Signal matrix for binary
inputs SMBI".
Figure 457 shows the operating characteristics of the binary inputs of the four
voltage levels.
889
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
[V]
300
176
144
88
72
38
32
19
18
xx06000391.vsd
IEC06000391 V1 EN
Guaranteed operation
Operation uncertain
No operation
IEC99000517-ABC V1 EN
This binary input module communicates with the Numerical module (NUM) via
the CAN-bus on the backplane.
The design of all binary inputs enables the burn off of the oxide of the relay contact
connected to the input, despite the low, steady-state power consumption, which is
shown in figure 458 and 459.
890
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
[mA]
30 / 50
1
35 70 [ms]
en07000104-2.vsd
IEC07000104 V2 EN
Figure 458: Approximate binary input inrush current for the two standard
versions of BIM.
[mA]
30
1
3.5 7.0 [ms]
en07000105.vsd
IEC07000105 V1 EN
Figure 459: Approximate binary input inrush current for the BIM version with
enhanced pulse counting capabilities.
891
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
Backplane connector
Process connector
99000503.vsd
IEC99000503 V1 EN
892
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
Table 612: BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL 24/30 V RL ± 20%
48/60 V RL ± 20%
110/125 V RL ± 20%
220/250 V RL ± 20%
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
19.2.10.1 Introduction
The binary output module has 24 independent output relays and is used for trip
output or any signaling purpose.
19.2.10.2 Design
The binary output module (BOM) has 24 software supervised output relays. Each
pair of relays have a common power source input to the contacts, see figure 461.
893
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
This should be considered when connecting the wiring to the connection terminal
on the back of the IED.
The high closing and carrying current capability allows connection directly to
breaker trip and closing coils. If breaking capability is required to manage fail of
the breaker auxiliary contacts normally breaking the trip coil current, a parallel
reinforcement is required.
For configuration of the output signals, refer to section "Signal matrix for binary
outputs SMBO".
Output module
xx00000299.vsd
IEC00000299 V1 EN
894
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
Relay
Relay
Relay
Relay
Relay
Process connector
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Backplane connector
Process connector
Relay Micro-
controller
Relay
Relay
CAN
Relay
Relay Memory
Relay
Relay
99000505.vsd
IEC99000505 V1 EN
895
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
19.2.11.1 Introduction
The static binary output module has six fast static outputs and six change over
output relays for use in applications with high speed requirements.
19.2.11.2 Design
The Static output module (SOM) have 6 normally open (NO) static outputs and 6
electromechanical relay outputs with change over contacts.
• An MCU
• A CAN-driver
• 6 static relays outputs
• 6 electromechanical relay outputs
• A DC/DC converter
• Connectors interfacing
• CAN-bus to backplane CBM
• IO-connectors to binary outputs (2 pcs.)
896
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
Drive &
Read back
Drive &
Read back
Process connector
Drive &
Read back
Drive &
Read back
Drive &
Read back
MCU
CAN-
driver
Drive &
Read back
Drive &
Read back
Process connector
Backplane connector
DC/DC
Drive &
Read back
Internal_fail_n
Drive & AC_fail_n
Read back RCAN_ID
Sync
Drive &
Read back
Reset
Drive &
Read back
en07000115.vsd
IEC07000115 V1 EN
897
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
IEC09000974-1-en.vsd
IEC09000974 V1 EN
IEC09000975 V1 EN
898
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
Table 615: SOM - Static Output module data (reference standard: IEC 61810-2):
Electromechanical relay outputs
Function of quantity Trip and signal relays
Max system voltage 250V AC/DC
Number of outputs 6
Test voltage across open contact, 1 min 1000V rms
Current carrying capacity:
Continuous 8A
1.0s 10A
Making capacity at capacitive load with the
maximum capacitance of 0.2 μF:
0.2s 30A
1.0s 10A
Breaking capacity for DC with L/R ≤ 40ms 48V / 1A
110V / 0.4A
125V / 0,35A
220V / 0,2A
250V / 0.15A
19.2.12.1 Introduction
The binary input/output module is used when only a few input and output channels
are needed. The ten standard output channels are used for trip output or any
signaling purpose. The two high speed signal output channels are used for
applications where short operating time is essential. Eight optically isolated binary
inputs cater for required binary input information.
899
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
19.2.12.2 Design
The binary input/output module is available in two basic versions, one with
unprotected contacts and one with MOV (Metal Oxide Varistor) protected contacts.
Inputs are designed to allow oxide burn-off from connected contacts, and increase
the disturbance immunity during normal protection operate times. This is achieved
with a high peak inrush current while having a low steady-state current, see figure
458. Inputs are debounced by software.
Well defined input high and input low voltages ensures normal operation at battery
supply earth faults, see figure 457.
I/O events are time stamped locally on each module for minimum time deviance
and stored by the event recorder if present.
The binary I/O module, IOM, has eight optically isolated inputs and ten output
relays. One of the outputs has a change-over contact. The nine remaining output
contacts are connected in two groups. One group has five contacts with a common
and the other group has four contacts with a common, to be used as single-output
channels, see figure 466.
The binary I/O module also has two high speed output channels where a reed relay
is connected in parallel to the standard output relay.
For configuration of the input and output signals, refer to sections "Signal matrix
for binary inputs SMBI" and "Signal matrix for binary outputs SMBO".
900
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
IEC1MRK002801-AA11-UTAN-RAM V1 EN
Figure 466: Binary in/out module (IOM), input contacts named XA corresponds
to rear position X31, X41, and so on, and output contacts named
XB to rear position X32, X42, and so on
The binary input/output module version with MOV protected contacts can for
example be used in applications where breaking high inductive load would cause
excessive wear of the contacts.
The test voltage across open contact is lower for this version of the
binary input/output module.
901
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
xx04000069.vsd
IEC04000069 V1 EN
Table 617: IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel reed
relay)
Binary outputs 10 2
Max system voltage 250 V AC, DC 250 V AC, DC
Test voltage across open contact, 1000 V rms 800 V DC
1 min
Current carrying capacity
Continuous 8A 8A
1s 10 A 10 A
Making capacity at inductive load
with L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Breaking capacity for AC, cos φ > 250 V/8.0 A 250 V/8.0 A
0.4
Breaking capacity for DC with L/R 48 V/1 A 48 V/1 A
< 40 ms 110 V/0.4 A 110 V/0.4 A
125 V/0.35 A 125 V/0.35 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF
902
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
Table 618: IOM with MOV - contact data (reference standard: IEC 60255-23)
Function or quantity Trip and Signal relays Fast signal relays (parallel
reed relay)
Binary outputs IOM: 10 IOM: 2
Max system voltage 250 V AC, DC 250 V AC, DC
Test voltage across open 250 V rms 250 V DC
contact, 1 min
Current carrying capacity
Continuous 8A 8A
1s 10 A 10 A
Making capacity at inductive
loadwith L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Breaking capacity for AC, cos 250 V/8.0 A 250 V/8.0 A
j>0.4
Breaking capacity for DC with L/ 48 V/1 A 48 V/1 A
R < 40 ms 110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF
19.2.13.1 Introduction
The milli-ampere input module is used to interface transducer signals in the –20 to
+20 mA range from for example OLTC position, temperature or pressure
transducers. The module has six independent, galvanically separated channels.
19.2.13.2 Design
The Milliampere Input Module has six independent analog channels with separated
protection, filtering, reference, A/D-conversion and optical isolation for each input
making them galvanically isolated from each other and from the rest of the module.
For configuration of the input signals, refer to section "Signal matrix for mA
inputs SMMI".
The analog inputs measure DC current in the range of +/- 20 mA. The A/D
converter has a digital filter with selectable filter frequency. All inputs are
calibrated separately The filter parameters and the calibration factors are stored in a
non-volatile memory on the module.
The calibration circuitry monitors the module temperature and starts an automatical
calibration procedure if the temperature drift is outside the allowed range. The
module communicates, like the other I/O-modules on the serial CAN-bus.
903
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
Process connector
A/D Converter Opto-
Protection isolation
& filter
Volt-ref DC/DC
Backplane connector
A/D Converter Opto-
Protection isolation
& filter
Volt-ref DC/DC
CAN
Memory Micro-
controller
99000504.vsd
IEC99000504 V1 EN
904
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
19.2.14.1 Introduction
The serial and LON communication module (SLM) is used for SPA, IEC
60870-5-103 and LON communication. The module has two optical
communication ports for plastic/plastic, plastic/glass or glass/glass. One port is
used for serial communication (SPA and IEC 60870-5-103) and one port is
dedicated for LON communication.
19.2.14.2 Design
The SLM is a PMC card and it is factory mounted as a mezzanine card on the
NUM module. Three variants of the SLM is available with different combinations
of optical fiber connectors, see figure 469. The plastic fiber connectors are of snap-
in type and the glass fiber connectors are of ST type.
IEC05000760 V1 EN
905
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
IEC05000761 V1 EN
1 Receiver, LON
2 Transmitter, LON
3 Receiver, SPA/IEC 60870-5-103
4 Transmitter, SPA/IEC 60870-5-103
Observe that when the SLM is mounted on the NUM module, then
contact 4 above will be in the uppermost and contact 1 in the lowest
position.
906
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
19.2.15.1 Introduction
19.2.15.2 Design
The RS485 is a PMC card and it is factory mounted as a mezzanine card on the
NUM module. The internal structure of the RS485 can be seen in figure 471:
FPGA
32 MHz
Wishbone interconnect switch
Tx
PCI-con
Isolation
6-pole-connector
Internal UART RS485
bus tranceiver
PCI-bus Rx
Local bus Isolation
PCI-
to
Controller
wishbone
PCI-con
Isolation
Status
Register Termination
connector
Info
2-pole
Register
Control
ID-chip
Register Isolated Soft
DC/DC ground
IEC06000516 V1 EN
907
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
Angle
bracket
Screw
1
terminal
X3 2
1
2 RS485
3 PWB
Screw
4
terminal
5
X1
6
Backplane
IEC06000517 V1 EN
• Soft grounded: The IO is connected to the GND with an RC net parallel with a
MOV
908
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
19.2.16.1 Introduction
19.2.16.2 Functionality
19.2.16.3 Design
The Optical Ethernet module (OEM) is a PMC card and mounted as a mezzanine
card on the ADM. The OEM is a 100base Fx module and available as a single
channel or double channel unit.
PCI - bus Connector
100Base-FX
EEPROM
Transmitter ST fiber optic
Ethernet Controller connectors
100Base-FX
Receiver
100Base-FX
Transmitter
ID chip ST fiber optic
Ethernet Controller
connectors
100Base-FX
EEPROM
IO - bus Connector Receiver
en04000472.vsd
IEC04000472 V1 EN
909
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
ID chip
Receiver
IO bus
LED
Ethernet cont.
25MHz oscillator
Transmitter
Receiver
LED
PCI bus
Ethernet cont. PCI to PCI
bridge
25MHz oscillator
Transmitter
en05000472.vsd
IEC05000472 V1 EN
19.2.17.1 Introduction
The line data communication module (LDCM) is used for communication between
the IEDs situated at distances <110 km or from the IED to optical to electrical
converter with G.703 interface located on a distances <3 km away. The LDCM
module sends and rereceives data, to and from another LDCM module. The IEEE/
ANSI standard format is used.
The line data communication module is used for binary signal transfer. The module
has one optical port with ST connectors see figure 475.
910
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
Alternative cards for Long range (1550 nm single mode), Medium range (1310 nm
single mode) and Short range (850 nm multi mode) are available.
19.2.17.2 Design
The LDCM is a PCMIP type II single width format module. The LDCM can be
mounted on:
• the ADM
• the NUM
ID
ST
16.000
IO-connector
MHz
32,768
MHz
ST
en07000087.vsd
IEC07000087 V1 EN
Figure 475: The SR-LDCM layout. PCMIP type II single width format with two
PCI connectors and one I/O ST type connector
911
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
X1
C
ADN 2.5V
ID
2841
PCI9054
FPGA TQ176
DS DS
256 FBGA
3904 3904
3645
MAX
3
2
en06000393.vsd
IEC06000393 V1 EN
Figure 476: The MR-LDCM and LR-LDCM layout. PCMIP type II single width
format with two PCI connectors and one I/O FC/PC type connector
912
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
19.2.18.1 Introduction
The galvanic X.21 line data communication module is used for connection to
telecommunication equipment, for example leased telephone lines. The module
supports 64 kbit/s data communication between IEDs.
Examples of applications:
19.2.18.2 Design
The galvanic X.21 line data communication module uses a ABB specific PC*MIP
Type II format.
C
en07000196.vsd
IEC07000196 V1 EN
913
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
1 4
1 8
9 15
3 2
en07000239.wmf
IEC07000239 V1 EN
I/O
100kW 100nF
Soft ground
en07000242.vsd
IEC07000242 V1 EN
Grounding
At special problems with ground loops, the soft ground connection for the IO-
ground can be tested.
Three different kinds of grounding principles can be set (used for fault tracing):
1. Direct ground - The normal grounding is direct ground, connect terminal 2
direct to the chassi.
2. No ground - Leave the connector without any connection.
3. Soft ground - Connect soft ground pin (3), see figure 478
914
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
X.21 connector
19.2.18.3 Functionality
The data format is HDLC. The speed for the transmission of the messages used is
64 kbit/s.
A maximum of 100 meter of cable is allowed to ensure the quality of the data
(deviation from X.21 standard cable length).
Synchronization
The X.21 LDCM works like a DTE (Data Terminal Equipment) and is normally
expecting synchronization from the DCE (Data Circuit Equipment). The
transmission is normally synchronized to the Signal Element Timing signal when a
device is a DTE. When the signal is high it will read the data at the receiver and
when the signal is low it will write data to the transmitter. This behaviour can be
inverted in the control register.
Normally an external multiplexer is used and it should act like the master.
When two X.21 LDCM is directly communicating with each other one must be set
as a master generating the synchronization for the other (the slave). The DTE
Signal Element Timing is created from the internal 64 kHz clock.
915
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
19.2.19.1 Introduction
This module includes the GPS receiver used for time synchronization. The GPS
has one SMA contact for connection to an antenna.
19.2.19.2 Design
The GPS time synchronization module is 6U high and occupies one slot. The slot
closest to the NUM shall always be used.
The CCM is a carrier board for the GCM mezzanine PMC card and GPS unit, see
figure 481. There is a cable between the external antenna input on the back of the
GCM and the GPS-receiver. This is a galvanic connection vulnerable to electro-
magnetic interference. The connector is shielded and directly attached to a
grounded plate to reduce the risk. The second cable is a flat cable that connects the
GPS and the GCM. It is used for communication between the GCM and the GPS-
receiver. All communication between the GCM and the NUM is via the CAN-bus.
The CMPPS signal is sent from the GCM to the rest of the time system to provide
1µs accuracy at sampling level.
916
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
PMC
GPS GPS clock
GPS antenna
receiver module
CMPPS
Backplane CAN
CAN
connector
controller CAN
en05000675.vsd
IEC05000675 V1 EN
917
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
en07000086.vsd
IEC07000086 V1 EN
Figure 481: A CCM with the GCM and GPS mounted with cables
1 GPS receiver
2 GPS Clock module (GCM)
3 CAN carrier module (CCM)
4 Antenna connector
918
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
19.2.20.1 Introduction
In order to receive GPS signals from the satellites orbiting the earth a GPS antenna
with applicable cable must be used.
19.2.20.2 Design
The antenna with a console for mounting on a horizontal or vertical flat surface or
on an antenna mast. See figure 482
1 6
4 7
xx04000155.vsd
IEC04000155 V1 EN
where:
1 GPS antenna
2 TNC connector
3 Console, 78x150 mm
4 Mounting holes 5.5 mm
5 Tab for securing of antenna cable
6 Vertical mounting position
7 Horizontal mounting position
Always position the antenna and its console so that a continuous clear line-of-sight
visibility to all directions is obtained, preferably more than 75%. A minimum of
50% clear line-of-sight visibility is required for un-interrupted operation.
919
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
99001046.vsd
IEC99001046 V1 EN
Antenna cable
Use a 50 ohm coaxial cable with a male TNC connector in the antenna end and a
male SMA connector in the receiver end to connect the antenna to GSM. Choose
cable type and length so that the total attenuation is max. 26 dB at 1.6 GHz.
Make sure that the antenna cable is not charged when connected to
the antenna or to the receiver. Short-circuit the end of the antenna
cable with some metal device, when first connected to the antenna.
When the antenna is connected to the cable, connect the cable to the
receiver. REx670 must be switched off when the antenna cable is
connected.
920
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
19.2.21.1 Introduction
The IRIG-B time synchronizing module is used for accurate time synchronizing of
the IED from a station clock.
The Pulse Per Second (PPS) input shall be used for synchronizing when IEC
61850-9-2LE is used.
Electrical (BNC) and optical connection (ST) for 0XX and 12X IRIG-B support.
19.2.21.2 Design
The IRIG-B module have two inputs. One input is for the IRIG-B that can handle
both a pulse-width modulated signal (also called unmodulated) and an amplitude
modulated signal (also called sine wave modulated). The other is an optical input
type ST for PPS to synchronize the time between several protections.
32 MHz FPGA
connector
PCI-con
OPTO_INPUT
ST-
PCI-bus
Registers
PCI-Controller
PCI-con
4 mm barrier
IRIG- IRIG_INPUT
connector
Amplitude
ID-chip Decoder
BNC-
modulator
Capture1 Isolated
ZXING
receiver
Zero-cross
Capture2 detector
MPPS
IO-con
PPS
TSU Isolated
DC/DC
CMPPS 5 to +- 12V
en06000303.vsd
IEC06000303 V1 EN
921
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
A1
DC//DC
ST
C
Y2
C
C
A1
C
O
T
3
2
O
en06000304.vsd
IEC06000304 V1 EN
Figure 485: IRIG-B PC-MIP board with top left ST connector for PPS 820 nm
multimode fibre optic signal input and lower left BNC connector for
IRIG-B signal input
922
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
19.3 Dimensions
A
D
B C
xx08000164.vsd
IEC08000164 V1 EN
923
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
K
F
G
H J
xx08000166.vsd
IEC08000166 V1 EN
Figure 487: Case without rear cover with 19” rack mounting kit
924
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
A
D
B
C
xx08000163.vsd
IEC08000163 V1 EN
925
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
K
F
G
J
H
xx08000165.vsd
IEC08000165 V1 EN
Figure 489: Case with rear cover and 19” rack mounting kit
xx05000503.vsd
IEC05000503 V1 EN
926
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
A C
B
E
D
xx08000162.vsd
IEC08000162 V1 EN
927
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
xx06000182.vsd
IEC06000182 V1 EN
Figure 492: A 1/2 x 19” size 670 series IED side-by-side with RHGS6.
G
D
B
E
F
C
xx05000505.vsd
IEC05000505 V1 EN
928
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
B
E
C
D
en04000471.vsd
IEC04000471 V1 EN
929
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
[1.48]
[6.97]
[4.02]
Dimension
mm [inches] xx06000232.eps
IEC06000232 V1 EN
[7.50]
en06000234.eps
[inches]
IEC06000234 V1 EN
Figure 496: Dimension drawing of a three phase high impedance resistor unit
19.4.1.1 Overview
• 1/2 x 19”
• 3/4 x 19”
• 1/1 x 19”
• 1/4 x 19” (RHGS6 6U)
930
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
Only a single case can be mounted in each cut-out on the cubicle panel, for class
IP54 protection.
931
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
xx08000161.vsd
IEC08000161 V1 EN
932
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
19.4.2.1 Overview
All IED sizes can be mounted in a standard 19” cubicle rack by using the for each
size suited mounting kit which consists of two mounting angles and fastening
screws for the angles.
The mounting angles are reversible which enables mounting of IED size 1/2 x 19”
or 3/4 x 19” either to the left or right side of the cubicle.
Please note that the separately ordered rack mounting kit for side-by-
side mounted IEDs, or IEDs together with RHGS cases, is to be
selected so that the total size equals 19”.
933
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
1a
1b
xx08000160.vsd
IEC08000160 V1 EN
19.4.3.1 Overview
All case sizes, 1/2 x 19”, 3/4 x 19” and 1/1 x 19”, can be wall mounted. It is also
possible to mount the IED on a panel or in a cubicle.
934
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
When mounting the side plates, be sure to use screws that follows
the recommended dimensions. Using screws with other dimensions
than the original may damage the PCBs inside the IED.
If fiber cables are bent too much, the signal can be weakened. Wall
mounting is therefore not recommended for communication
modules with fiber connection; Serial SPA/IEC 60870-5-103 and
LON communication module (SLM), Optical Ethernet module
(OEM) and Line data communication module (LDCM).
3
4
2
6
xx04000453.vs d
DOCUMENT127716-IMG2265 V1 EN
935
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
4 Mounting bar 2 -
5 Screw 6 M5x8
6 Side plate 2 -
The IED can be equipped with a rear protection cover, which is recommended to
use with this type of mounting. See figure 500.
To reach the rear side of the IED, a free space of 80 mmis required on the unhinged
side.
3
1
80 mm 2
en06000135.vsd
IEC06000135 V1 EN
Figure 500: How to reach the connectors on the rear side of the IED.
19.4.4.1 Overview
IED case sizes, 1/2 x 19” or 3/4 x 19” and RHGS cases, can be mounted side-by-
side up to a maximum size of 19”. For side-by-side rack mounting, the side-by-side
mounting kit together with the 19” rack panel mounting kit must be used. The
mounting kit has to be ordered separately.
936
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
When mounting the plates and the angles on the IED, be sure to use
screws that follows the recommended dimensions. Using screws
with other dimensions than the original may damage the PCBs
inside the IED.
2
1
xx04000456.vsd
IEC04000456 V1 EN
An 1/2 x 19” or 3/4 x 19” size IED can be mounted with a RHGS (6 or 12
depending on IED size) case. The RHGS case can be used for mounting a test
switch of type RTXP 24. It also has enough space for a terminal base of RX 2 type
for mounting of, for example, a DC-switch or two trip IEDs.
937
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
1 2
1 2 1 2
1 1 1 1
2 2 2 2
3 3 3 3
4 4 4 4
5 5 5 5
6 6 6 6
7 7 7 7
8 8 8 8
xx06000180.vsd
IEC06000180 V1 EN
Figure 502: IED in the 670 series (1/2 x 19”) mounted with a RHGS6 case
containing a test switch module equipped with only a test switch
and a RX2 terminal base
19.4.5.1 Overview
When mounting the plates and the angles on the IED, be sure to use
screws that follows the recommended dimensions. Using screws
with other dimensions than the original may damage the PCBs
inside the IED.
938
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
1 2
xx06000181.vsd
IEC06000181 V1 EN
Figure 503: Side-by-side flush mounting details (RHGS6 side-by-side with 1/2 x
19” IED).
19.5.1 Enclosure
Table 631: Case
Material Steel sheet
Front plate Steel sheet profile with cut-out for HMI
Surface treatment Aluzink preplated steel
Finish Light grey (RAL 7035)
939
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
Table 632: Water and dust protection level according to IEC 60529
940
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
941
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware
942
Technical reference manual
1MRK505183-UEN C Section 19
Hardware
943
Technical reference manual
944
1MRK505183-UEN C Section 20
Labels
Section 20 Labels
2
3
6
6 5
7
xx06000574.eps
IEC06000574 V1 EN
945
Technical reference manual
Section 20 1MRK505183-UEN C
Labels
IEC06000577-CUSTOMER-SPECIFIC V1 EN
IEC06000576-POS-NO V1 EN
946
Technical reference manual
1MRK505183-UEN C Section 20
Labels
4
en06000573.eps
IEC06000573 V1 EN
1 Warning label
2 Caution label
3 Class 1 laser product label
IEC06000575 V1 EN
4 Warning label
947
Technical reference manual
948
1MRK505183-UEN C Section 21
Connection diagrams
This chapter includes diagrams of the IED with all slot, terminal block and optical
connector designations. It is a necessary guide when making electrical and optical
connections to the IED.
949
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams
IEC08000470 V1 EN
950
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams
IEC08000471 V1 EN
951
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams
IEC08000472 V1 EN
952
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams
IEC08000473 V1 EN
953
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams
IEC08000474 V1 EN
954
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams
IEC08000475 V1 EN
955
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams
IEC08000476 V1 EN
956
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams
IEC08000477 V1 EN
957
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams
IEC08000478 V1 EN
958
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams
IEC08000479 V1 EN
959
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams
IEC08000480 V1 EN
960
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams
IEC08000481 V1 EN
961
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams
IEC08000482 V1 EN
962
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams
IEC08000483 V1 EN
963
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams
IEC08000484 V1 EN
964
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
22.1 Application
Stage 3
Time
Stage 2 Stage 2
Fault point
position
en05000130.vsd
IEC05000130 V1 EN
965
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
Time
Fault point
position
en05000131.vsd
IEC05000131 V1 EN
The inverse time characteristic makes it possible to minimize the fault clearance
time and still assure the selectivity between protections.
To assure selectivity between protections there must be a time margin between the
operation time of the protections. This required time margin is dependent of
following factors, in a simple case with two protections in series:
966
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
A1 B1
Feeder
I> I>
Time axis
en05000132.vsd
IEC05000132 V1 EN
where:
t=0 is The fault occurs
t=t1 is Protection B1 trips
In most applications it is required that the times shall reset as fast as possible when
the current fed to the protection drops below the set current level, the reset time
shall be minimized. In some applications it is however beneficial to have some type
of delayed reset time of the overcurrent function. This can be the case in the
following applications:
967
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
• If there is a risk of intermittent faults. If the current IED, close to the faults,
starts and resets there is a risk of unselective trip from other protections in the
system.
• Delayed resetting could give accelerated fault clearance in case of automatic
reclosing to a permanent fault.
• Overcurrent protection functions are sometimes used as release criterion for
other protection functions. It can often be valuable to have a reset delay to
assure the release function.
If current in any phase exceeds the set start current value (here internal signal
startValue), a timer, according to the selected operating mode, is started. The
component always uses the maximum of the three phase current values as the
current level used in timing calculations.
In case of definite time-lag mode the timer will run constantly until the time is
reached or until the current drops below the reset value (start value minus the
hysteresis) and the reset time has elapsed.
For definite time delay curve ANSI/IEEE Definite time or IEC Definite time are
chosen.
The general expression for inverse time curves is according to equation 161.
æ ö
ç A
÷
t[ s ] = ç + B ÷×k
ç æ i öp ÷
çç ÷ -C ÷
è è in > ø ø
EQUATION1189 V1 EN (Equation 161)
where:
p, A, B, C are constants defined for each curve type,
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current.
968
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
For inverse time characteristics a time will be initiated when the current reaches the
set start level. From the general expression of the characteristic the following can
be seen:
ææ i öp ö
(top - B × k ) × ç ç ÷ - C ÷ = A×k
è è in > ø ø
EQUATION1190 V1 EN (Equation 162)
where:
top is the operating time of the protection
The time elapsed to the moment of trip is reached when the integral fulfils
according to equation 163, in addition to the constant time delay:
t
ææ i öp ö
ò ç çè in > ÷ø - C ÷ × dt ³ A × k
0 è ø
EQUATION1191 V1 EN (Equation 163)
For the numerical protection the sum below must fulfil the equation for trip.
n æ æ i( j ) ö p ö
Dt × å ç ç ÷ - C ÷ ³ A× k
j =1 è è in > ø ø
EQUATION1192 V1 EN (Equation 164)
where:
j=1 is the first protection execution cycle when a fault has been
detected, that is, when
i
>1
in >
EQUATION1193 V1 EN
For inverse time operation, the inverse time characteristic is selectable. Both the
IEC and ANSI/IEEE standardized inverse time characteristics are supported.
For the IEC curves there is also a setting of the minimum time-lag of operation, see
figure 508.
969
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
Operate
time
tMin
Current
IMin
IEC05000133-3-en.vsd
IEC05000133 V2 EN
In order to fully comply with IEC curves definition setting parameter tMin shall be
set to the value which is equal to the operating time of the selected IEC inverse
time curve for measured current of twenty times the set current pickup value. Note
that the operating time value is dependent on the selected setting value for time
multiplier k.
In addition to the ANSI and IEC standardized characteristics, there are also two
additional inverse curves available; the RI curve and the RD curve.
æ ö
ç k ÷
t[ s ] = ç
in > ÷
ç 0.339 - 0.235 × ÷
è i ø
EQUATION1194 V1 EN (Equation 166)
where:
in> is the set start current for step n
k is set time multiplier for step n
i is the measured current
970
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
æ i ö
t[ s ] = 5.8 - 1.35 × ln ç ÷
è k × in > ø
EQUATION1195 V1 EN (Equation 167)
where:
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current
If the curve type programmable is chosen, the user can make a tailor made inverse
time curve according to the general equation 168.
æ ö
ç A
÷
t[ s ] = ç + B÷×k
ç æ i öp ÷
çç ÷ -C ÷
è è in > ø ø
EQUATION1196 V1 EN (Equation 168)
Also the reset time of the delayed function can be controlled. There is the
possibility to choose between three different reset time-lags.
• Instantaneous Reset
• IEC Reset
• ANSI Reset.
If instantaneous reset is chosen the timer will be reset directly when the current
drops below the set start current level minus the hysteresis.
If IEC reset is chosen the timer will be reset after a set constant time when the
current drops below the set start current level minus the hysteresis.
If ANSI reset time is chosen the reset time will be dependent of the current after
fault clearance (when the current drops below the start current level minus the
hysteresis). The timer will reset according to equation 169.
971
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
æ ö
ç tr ÷
t [s] = ç ÷×k
çæ i ö ÷
2
çç ÷ -1 ÷
è è in > ø ø
EQUATION1197 V2 EN (Equation 169)
where:
The set value tr is the reset time in case of zero current after fault clearance.
For the definite time delay characteristics the possible reset time settings are
instantaneous and IEC constant time reset.
For ANSI inverse time delay characteristics all three types of reset time
characteristics are available; instantaneous, IEC constant time reset and ANSI
current dependent reset time.
For IEC inverse time delay characteristics the possible delay time settings are
instantaneous and IEC set constant time reset).
For the programmable inverse time delay characteristics all three types of reset
time characteristics are available; instantaneous, IEC constant time reset and ANSI
current dependent reset time. If the current dependent type is used settings pr, tr
and cr must be given, see equation 170:
æ ö
ç tr ÷
t [s] = ç ÷×k
çæ i ö ÷
pr
çç ÷ - cr ÷
è è in > ø ø
EQUATION1198 V2 EN (Equation 170)
For RI and RD inverse time delay characteristics the possible delay time settings
are instantaneous and IEC constant time reset.
972
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
Reset characteristic:
tr
t = ×k
(I 2
)
-1
EQUATION1250-SMALL V1 EN
I = Imeasured/Iset
973
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
æ A ö
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset
Time delay to reset, IEC inverse time (0.000-60.000) s ± 0.5% of set time ± 10
ms
IEC Normal Inverse A=0.14, P=0.02 IEC 60255-3, class 5 +
40 ms
IEC Very inverse A=13.5, P=1.0
IEC Inverse A=0.14, P=0.02
IEC Extremely inverse A=80.0, P=2.0
IEC Short time inverse A=0.05, P=0.04
IEC Long time inverse A=120, P=1.0
Programmable characteristic k = (0.05-999) in steps of 0.01 IEC 60255, class 5 + 40
Operate characteristic: A=(0.005-200.000) in steps ms
of 0.001
æ A ö B=(0.00-20.00) in steps of
t = ç P + B÷ × k 0.01
ç (I - C ) ÷ C=(0.1-10.0) in steps of 0.1
è ø
P=(0.005-3.000) in steps of
EQUATION1370-SMALL V1 EN
0.001
Reset characteristic: TR=(0.005-100.000) in steps
of 0.001
TR CR=(0.1-10.0) in steps of 0.1
t = ×k PR=(0.005-3.000) in steps of
(I PR
- CR ) 0.001
EQUATION1253-SMALL V1 EN
I = Imeasured/Iset
I = Imeasured/Iset
RD type logarithmic inverse characteristic k = (0.05-999) in steps of 0.01 IEC 60255-3, class 5 +
40 ms
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
974
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
U> = Uset
U = Umeasured
975
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
U< = Uset
U = UVmeasured
U< = Uset
U = Umeasured
976
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
U> = Uset
U = Umeasured
977
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
A070750 V2 EN
978
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
A070751 V2 EN
979
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
A070752 V2 EN
980
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
A070753 V2 EN
981
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
A070817 V2 EN
982
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
A070818 V2 EN
983
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
A070819 V2 EN
984
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
A070820 V2 EN
985
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
A070821 V2 EN
986
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
A070822 V2 EN
987
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
A070823 V2 EN
988
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
A070824 V2 EN
989
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
A070825 V2 EN
990
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
A070826 V2 EN
991
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
A070827 V2 EN
992
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
GUID-ACF4044C-052E-4CBD-8247-C6ABE3796FA6 V1 EN
993
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
GUID-F5E0E1C2-48C8-4DC7-A84B-174544C09142 V1 EN
994
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
GUID-A9898DB7-90A3-47F2-AEF9-45FF148CB679 V1 EN
995
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics
GUID-35F40C3B-B483-40E6-9767-69C1536E3CBC V1 EN
996
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics
GUID-B55D0F5F-9265-4D9A-A7C0-E274AA3A6BB1 V1 EN
997
Technical reference manual
998
1MRK505183-UEN C Section 23
Glossary
Section 23 Glossary
AC Alternating current
ACT Application configuration tool within PCM600
A/D converter Analog to digital converter
ADBS Amplitude dead-band supervision
ADM Analog digital conversion module, with time synchronization
ANSI American National Standards Institute
AR Autoreclosing
ArgNegRes Setting parameter/ZD/
ArgDir Setting parameter/ZD/
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
AWG American Wire Gauge standard
BBP Busbar protection
BFP Breaker failure protection
BIM Binary input module
BOM Binary output module
BR External bi-stable relay
BS British standard
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signals
between IEDs
CAN Controller Area Network. ISO standard (ISO 11898) for
serial communication
CB Circuit breaker
CBM Combined backplane module
999
Technical reference manual
Section 23 1MRK505183-UEN C
Glossary
1000
Technical reference manual
1MRK505183-UEN C Section 23
Glossary
1001
Technical reference manual
Section 23 1MRK505183-UEN C
Glossary
1002
Technical reference manual
1MRK505183-UEN C Section 23
Glossary
1003
Technical reference manual
Section 23 1MRK505183-UEN C
Glossary
1004
Technical reference manual
1MRK505183-UEN C Section 23
Glossary
1005
Technical reference manual
Section 23 1MRK505183-UEN C
Glossary
1006
Technical reference manual
1007
Contact us
www.abb.com/substationautomation