Vous êtes sur la page 1sur 1014

Relion® 670 series

Line differential protection RED670


Technical reference manual
Document ID: 1MRK505183-UEN
Issued: June 2010
Revision: C
Product version: 1.1

© Copyright 2010 ABB. All rights reserved


Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.

The software or hardware described in this document is furnished under a license


and may be used or disclosed only in accordance with the terms of such license.

Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.

Warranty
Please inquire about the terms of warranty from your nearest ABB representative.

ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 32 50 00
Facsimile: +46 (0) 21 14 69 18
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC).

This conformity is proved by tests conducted by ABB AB in accordance with the


generic standard EN 50263 for the EMC directive, and with the standards EN
60255-5 and/or EN 50178 for the low voltage directive.

This product is designed and produced for industrial use.


Table of contents

Table of contents

Section 1 Introduction.....................................................................29
Introduction to the technical reference manual.................................29
About the complete set of manuals for an IED............................29
About the technical reference manual.........................................30
This manual.................................................................................31
Introduction.............................................................................31
Principle of operation..............................................................31
Input and output signals.........................................................34
Function block........................................................................34
Setting parameters.................................................................34
Technical data........................................................................35
Intended audience.......................................................................35
Related documents......................................................................35
Revision notes.............................................................................36

Section 2 Analog inputs..................................................................37


Introduction.......................................................................................37
Operation principle...........................................................................37
Function block..................................................................................38
Setting parameters...........................................................................39

Section 3 Local HMI.......................................................................45


Human machine interface ................................................................45
Small size HMI..................................................................................47
Small............................................................................................47
Design.........................................................................................47
Medium size graphic HMI.................................................................49
Medium........................................................................................49
Design.........................................................................................49
Keypad.............................................................................................51
LED...................................................................................................52
Introduction..................................................................................52
Status indication LEDs................................................................52
Indication LEDs...........................................................................52
Local HMI related functions..............................................................53
Introduction..................................................................................53
General setting parameters.........................................................54
Status indication LEDs................................................................54
Design....................................................................................54
Function block........................................................................54

1
Technical reference manual
Table of contents

Input and output signals.........................................................54


Indication LEDs...........................................................................55
Introduction.............................................................................55
Design....................................................................................55
Function block........................................................................62
Input and output signals.........................................................62
Setting parameters.................................................................62

Section 4 Basic IED functions........................................................65


Authorization.....................................................................................65
Principle of operation...................................................................65
Authorization handling in the IED...........................................67
Self supervision with internal event list.............................................67
Introduction..................................................................................67
Principle of operation...................................................................68
Internal signals.......................................................................69
Run-time model......................................................................71
Function block.............................................................................72
Output signals..............................................................................72
Setting parameters......................................................................72
Technical data.............................................................................73
Time synchronization........................................................................73
Introduction..................................................................................73
Principle of operation...................................................................73
General concepts...................................................................73
Real-time clock (RTC) operation............................................76
Synchronization alternatives..................................................77
Process bus IEC 61850-9-2LE synchronization.....................80
Function block.............................................................................80
Output signals..............................................................................81
Setting parameters......................................................................81
Technical data.............................................................................84
Parameter setting groups.................................................................84
Introduction..................................................................................84
Principle of operation...................................................................84
Function block.............................................................................85
Input and output signals..............................................................86
Setting parameters......................................................................86
ChangeLock function CHNGLCK.....................................................86
Introduction..................................................................................87
Principle of operation...................................................................87
Function block.............................................................................87
Input and output signals..............................................................87
Setting parameters......................................................................88

2
Technical reference manual
Table of contents

Test mode functionality TEST..........................................................88


Introduction..................................................................................88
Principle of operation...................................................................88
Function block.............................................................................90
Input and output signals..............................................................90
Setting parameters......................................................................91
IED identifiers...................................................................................91
Introduction..................................................................................91
Setting parameters......................................................................91
Product information..........................................................................92
Introduction..................................................................................92
Setting parameters......................................................................92
Application...................................................................................92
Factory defined settings.........................................................92
Signal matrix for binary inputs SMBI................................................93
Introduction..................................................................................93
Principle of operation...................................................................93
Function block.............................................................................93
Input and output signals..............................................................94
Signal matrix for binary outputs SMBO ...........................................94
Introduction..................................................................................94
Principle of operation...................................................................95
Function block.............................................................................95
Input and output signals..............................................................95
Signal matrix for mA inputs SMMI....................................................95
Introduction..................................................................................96
Principle of operation...................................................................96
Function block.............................................................................96
Input and output signals..............................................................96
Signal matrix for analog inputs SMAI...............................................97
Introduction..................................................................................97
Principle of operation...................................................................97
Frequency values........................................................................97
Function block.............................................................................98
Input and output signals..............................................................99
Setting parameters....................................................................100
Summation block 3 phase 3PHSUM..............................................102
Introduction................................................................................102
Principle of operation.................................................................102
Function block...........................................................................103
Input and output signals............................................................103
Setting parameters....................................................................103
Authority status ATHSTAT.............................................................104

3
Technical reference manual
Table of contents

Introduction................................................................................104
Principle of operation.................................................................104
Function block...........................................................................104
Output signals............................................................................104
Setting parameters....................................................................105

Section 5 Differential protection...................................................107


Line differential protection..............................................................107
Introduction................................................................................107
Line differential protection, 3 or 6 CT sets L3CPDIF,
L6CPDIF...............................................................................107
Line differential protection 3 or 6 CT sets, with in-zone
transformers LT3CPDIF, LT6CPDIF....................................109
Analog signal transfer for line differential protection............109
Principle of operation.................................................................110
Algorithm and logic...............................................................110
Time synchronization...........................................................116
Analog signal communication for line differential
protection..............................................................................118
Open CT detection feature...................................................121
Binary signal transfer............................................................122
Line differential coordination function LDLPDIF ..................123
Function block...........................................................................123
Input and output signals............................................................125
Setting parameters....................................................................131
Technical data...........................................................................141
1Ph High impedance differential protection HZPDIF .....................141
Introduction................................................................................142
Principle of operation.................................................................142
Logic diagram.......................................................................142
Function block...........................................................................143
Input and output signals............................................................143
Setting parameters....................................................................143
Technical data...........................................................................144

Section 6 Impedance protection ..................................................145


Distance measuring zones, quadrilateral characteristic
ZMQPDIS, ZMQAPDIS, ZDRDIR...................................................145
Introduction................................................................................145
Principle of operation.................................................................146
Full scheme measurement...................................................146
Impedance characteristic.....................................................147
Minimum operating current...................................................151
Measuring principles............................................................151

4
Technical reference manual
Table of contents

Directional impedance element for quadrilateral


characteristics......................................................................154
Simplified logic diagrams......................................................156
Function block...........................................................................159
Input and output signals............................................................160
Setting parameters....................................................................161
Technical data...........................................................................163
Distance measuring zone, quadrilateral characteristic for
series compensated lines ZMCPDIS, ZMCAPDIS, ZDSRDIR.......164
Introduction................................................................................165
Principle of operation.................................................................166
Full scheme measurement...................................................166
Impedance characteristic.....................................................166
Minimum operating current...................................................170
Measuring principles............................................................170
Directionality for series compensation..................................173
Simplified logic diagrams......................................................175
Function block...........................................................................178
Input and output signals............................................................179
Setting parameters....................................................................181
Technical data...........................................................................184
Phase selection, quadrilateral characteristic with fixed angle
FDPSPDIS......................................................................................184
Introduction................................................................................185
Principle of operation.................................................................185
Phase-to-earth fault..............................................................187
Phase-to-phase fault............................................................189
Three-phase faults...............................................................190
Load encroachment..............................................................191
Minimum operate currents....................................................194
Simplified logic diagrams......................................................194
Function block...........................................................................199
Input and output signals............................................................200
Setting parameters....................................................................201
Technical data...........................................................................202
Full-scheme distance measuring, Mho characteristic
ZMHPDIS ......................................................................................202
Introduction................................................................................202
Principle of operation.................................................................203
Full scheme measurement...................................................203
Impedance characteristic.....................................................204
Basic operation characteristics.............................................205
Theory of operation..............................................................206
Function block...........................................................................216

5
Technical reference manual
Table of contents

Input and output signals............................................................216


Setting parameters....................................................................217
Technical data...........................................................................218
Full-scheme distance protection, quadrilateral for earth faults
ZMMPDIS, ZMMAPDIS..................................................................219
Introduction................................................................................219
Principle of operation.................................................................220
Full scheme measurement...................................................220
Impedance characteristic.....................................................221
Minimum operating current...................................................223
Measuring principles............................................................224
Directional lines....................................................................226
Simplified logic diagrams......................................................228
Function block...........................................................................231
Input and output signals............................................................231
Setting parameters....................................................................232
Technical data...........................................................................234
Directional impedance element for mho characteristic and
additional distance protection directional function for earth
faults ZDMRDIR, ZDARDIR...........................................................234
Introduction................................................................................235
Principle of operation.................................................................235
Directional impedance element for mho characteristic
ZDMRDIR.............................................................................235
Additional distance protection directional function for
earth faults ZDARDIR ..........................................................238
Function block...........................................................................240
Input and output signals............................................................240
Setting parameters....................................................................241
Mho impedance supervision logic ZSMGAPC................................242
Introduction................................................................................242
Principle of operation.................................................................243
Fault inception detection......................................................243
Function block...........................................................................244
Input and output signals............................................................244
Setting parameters....................................................................245
Faulty phase identification with load encroachment
FMPSPDIS.....................................................................................245
Introduction................................................................................246
Principle of operation.................................................................246
The phase selection function................................................246
Function block...........................................................................257
Input and output signals............................................................258
Setting parameters....................................................................258

6
Technical reference manual
Table of contents

Technical data...........................................................................259
Power swing detection ZMRPSB ...................................................259
Introduction................................................................................259
Principle of operation.................................................................260
Resistive reach in forward direction.....................................261
Resistive reach in reverse direction.....................................262
Reactive reach in forward and reverse direction..................262
Basic detection logic.............................................................263
Operating and inhibit conditions...........................................265
Function block...........................................................................266
Input and output signals............................................................266
Setting parameters....................................................................267
Technical data...........................................................................268
Power swing logic ZMRPSL ..........................................................268
Introduction................................................................................268
Principle of operation.................................................................268
Communication and tripping logic........................................268
Blocking logic.......................................................................269
Function block...........................................................................271
Input and output signals............................................................271
Setting parameters....................................................................272
Pole slip protection PSPPPAM ......................................................272
Introduction................................................................................272
Principle of operation.................................................................272
Function block...........................................................................276
Input and output signals............................................................276
Setting parameters....................................................................277
Technical data...........................................................................277
Automatic switch onto fault logic, voltage and current based
ZCVPSOF ......................................................................................278
Introduction................................................................................278
Principle of operation.................................................................278
Function block...........................................................................280
Input and output signals............................................................280
Setting parameters....................................................................280
Technical data...........................................................................281
Phase preference logic PPLPHIZ...................................................281
Introduction................................................................................281
Principle of operation.................................................................281
Function block...........................................................................284
Input and output signals............................................................284
Setting parameters....................................................................285

Section 7 Current protection.........................................................287


7
Technical reference manual
Table of contents

Instantaneous phase overcurrent protection PHPIOC ..................287


Introduction................................................................................287
Principle of operation.................................................................287
Function block...........................................................................288
Input and output signals............................................................288
Setting parameters....................................................................288
Technical data...........................................................................289
Four step phase overcurrent protection OC4PTOC ......................289
Introduction................................................................................289
Principle of operation.................................................................289
Function block...........................................................................294
Input and output signals............................................................294
Setting parameters....................................................................296
Technical data...........................................................................301
Instantaneous residual overcurrent protection EFPIOC ................301
Introduction................................................................................302
Principle of operation.................................................................302
Function block...........................................................................302
Input and output signals............................................................303
Setting parameters....................................................................303
Technical data...........................................................................303
Four step residual overcurrent protection EF4PTOC ....................304
Introduction................................................................................304
Principle of operation.................................................................305
Operating quantity within the function..................................305
Internal polarizing.................................................................306
External polarizing for earth-fault function............................308
Base quantities within the protection....................................308
Internal earth-fault protection structure................................308
Four residual overcurrent steps............................................308
Directional supervision element with integrated
directional comparison function............................................310
Second harmonic blocking element.....................................312
Switch on to fault feature......................................................314
Function block...........................................................................316
Input and output signals............................................................317
Setting parameters....................................................................318
Technical data...........................................................................323
Sensitive directional residual overcurrent and power protection
SDEPSDE .....................................................................................323
Introduction................................................................................324
Principle of operation.................................................................325
Function inputs.....................................................................325
Function block...........................................................................331

8
Technical reference manual
Table of contents

Input and output signals............................................................332


Setting parameters....................................................................333
Technical data...........................................................................335
Thermal overload protection, one time constant LPTTR ...............336
Introduction................................................................................336
Principle of operation.................................................................336
Function block...........................................................................339
Input and output signals............................................................339
Setting parameters....................................................................339
Technical data...........................................................................340
Breaker failure protection CCRBRF ..............................................340
Introduction................................................................................341
Principle of operation.................................................................341
Function block...........................................................................344
Input and output signals............................................................345
Setting parameters....................................................................345
Technical data...........................................................................346
Stub protection STBPTOC ............................................................347
Introduction................................................................................347
Principle of operation.................................................................347
Function block...........................................................................348
Input and output signals............................................................348
Setting parameters....................................................................349
Technical data...........................................................................349
Pole discordance protection CCRPLD ..........................................349
Introduction................................................................................350
Principle of operation.................................................................350
Pole discordance signaling from circuit breaker...................353
Unsymmetrical current detection..........................................353
Function block...........................................................................353
Input and output signals............................................................354
Setting parameters....................................................................354
Technical data...........................................................................355
Directional underpower protection GUPPDUP...............................355
Introduction................................................................................355
Principle of operation.................................................................356
Low pass filtering..................................................................358
Calibration of analog inputs..................................................358
Function block...........................................................................359
Input and output signals............................................................360
Setting parameters....................................................................360
Technical data...........................................................................361
Directional overpower protection GOPPDOP ................................362

9
Technical reference manual
Table of contents

Introduction................................................................................362
Principle of operation.................................................................363
Low pass filtering..................................................................365
Calibration of analog inputs..................................................365
Function block...........................................................................366
Input and output signals............................................................367
Setting parameters....................................................................367
Technical data...........................................................................369
Broken conductor check BRCPTOC .............................................369
Introduction................................................................................369
Principle of operation.................................................................369
Function block...........................................................................370
Input and output signals............................................................371
Setting parameters....................................................................371
Technical data...........................................................................371

Section 8 Voltage protection........................................................373


Two step undervoltage protection UV2PTUV ................................373
Introduction................................................................................373
Principle of operation.................................................................373
Measurement principle.........................................................374
Time delay............................................................................374
Blocking................................................................................379
Design..................................................................................380
Function block...........................................................................382
Input and output signals............................................................382
Setting parameters....................................................................383
Technical data...........................................................................385
Two step overvoltage protection OV2PTOV ..................................386
Introduction................................................................................386
Principle of operation.................................................................386
Measurement principle.........................................................387
Time delay............................................................................387
Blocking................................................................................393
Design..................................................................................393
Function block...........................................................................395
Input and output signals............................................................395
Setting parameters....................................................................396
Technical data...........................................................................398
Two step residual overvoltage protection ROV2PTOV .................398
Introduction................................................................................398
Principle of operation.................................................................399
Measurement principle.........................................................399
Time delay............................................................................399

10
Technical reference manual
Table of contents

Blocking................................................................................404
Design..................................................................................404
Function block...........................................................................405
Input and output signals............................................................406
Setting parameters....................................................................406
Technical data...........................................................................408
Overexcitation protection OEXPVPH ............................................408
Introduction................................................................................408
Principle of operation.................................................................409
Measured voltage.................................................................411
Operate time of the overexcitation protection.......................412
Cooling.................................................................................415
Overexcitation protection function measurands...................415
Overexcitation alarm............................................................416
Logic diagram.......................................................................417
Function block...........................................................................417
Input and output signals............................................................417
Setting parameters....................................................................418
Technical data...........................................................................419
Voltage differential protection VDCPTOV ......................................419
Introduction................................................................................419
Principle of operation.................................................................420
Function block...........................................................................421
Input and output signals............................................................422
Setting parameters....................................................................422
Technical data...........................................................................423
Loss of voltage check LOVPTUV ..................................................423
Introduction................................................................................423
Principle of operation.................................................................423
Function block...........................................................................425
Input and output signals............................................................426
Setting parameters....................................................................426
Technical data...........................................................................426

Section 9 Frequency protection....................................................427


Underfrequency protection SAPTUF .............................................427
Introduction................................................................................427
Principle of operation.................................................................427
Measurement principle.........................................................428
Time delay............................................................................428
Voltage dependent time delay..............................................428
Blocking................................................................................430
Design..................................................................................430
Function block...........................................................................431

11
Technical reference manual
Table of contents

Input and output signals............................................................431


Setting parameters....................................................................431
Technical data...........................................................................432
Overfrequency protection SAPTOF ...............................................432
Introduction................................................................................433
Principle of operation.................................................................433
Measurement principle.........................................................433
Time delay............................................................................433
Blocking................................................................................434
Design..................................................................................434
Function block...........................................................................435
Input and output signals............................................................435
Setting parameters....................................................................435
Technical data...........................................................................436
Rate-of-change frequency protection SAPFRC .............................436
Introduction................................................................................436
Principle of operation.................................................................436
Measurement principle.........................................................437
Time delay............................................................................437
Blocking................................................................................437
Design..................................................................................438
Function block...........................................................................439
Input and output signals............................................................439
Setting parameters....................................................................439
Technical data...........................................................................440

Section 10 Multipurpose protection................................................441


General current and voltage protection CVGAPC..........................441
Introduction................................................................................441
Principle of operation.................................................................441
Measured quantities within CVGAPC...................................441
Base quantities for CVGAPC function..................................444
Built-in overcurrent protection steps.....................................444
Built-in undercurrent protection steps...................................449
Built-in overvoltage protection steps....................................450
Built-in undervoltage protection steps..................................450
Logic diagram.......................................................................450
Function block...........................................................................455
Input and output signals............................................................456
Setting parameters....................................................................457
Technical data...........................................................................464

Section 11 Secondary system supervision.....................................467


Current circuit supervision CCSRDIF ............................................467

12
Technical reference manual
Table of contents

Introduction................................................................................467
Principle of operation.................................................................467
Function block...........................................................................469
Input and output signals............................................................469
Setting parameters....................................................................470
Technical data...........................................................................470
Fuse failure supervision SDDRFUF...............................................470
Introduction................................................................................470
Principle of operation.................................................................471
Zero and negative sequence detection................................471
Delta current and delta voltage detection.............................473
Dead line detection...............................................................476
Main logic.............................................................................476
Function block...........................................................................480
Input and output signals............................................................480
Setting parameters....................................................................480
Technical data...........................................................................481

Section 12 Control..........................................................................483
Synchrocheck, energizing check, and synchronizing
SESRSYN......................................................................................483
Introduction................................................................................483
Principle of operation.................................................................484
Basic functionality.................................................................484
Logic diagrams.....................................................................484
Function block...........................................................................493
Input and output signals............................................................493
Setting parameters....................................................................496
Technical data...........................................................................498
Autorecloser SMBRREC ...............................................................498
Introduction................................................................................499
Principle of operation.................................................................499
Logic Diagrams....................................................................499
Auto-reclosing operation Off and On....................................499
Auto-reclosing mode selection.............................................499
Start auto-reclosing and conditions for start of a
reclosing cycle......................................................................500
Control of the auto-reclosing open time for shot 1...............501
Long trip signal.....................................................................501
Time sequence diagrams.....................................................508
Function block...........................................................................511
Input and output signals............................................................511
Setting parameters....................................................................513
Technical data...........................................................................515

13
Technical reference manual
Table of contents

Apparatus control APC...................................................................515


Introduction................................................................................515
Principle of operation.................................................................515
Error handling............................................................................516
Bay control QCBAY...................................................................518
Introduction...........................................................................518
Principle of operation............................................................518
Function block......................................................................520
Input and output signals.......................................................520
Setting parameters...............................................................521
Local/Remote switch.................................................................521
Introduction...........................................................................521
Principle of operation............................................................521
Function block......................................................................522
Input and output signals.......................................................523
Setting parameters...............................................................524
Switch controller SCSWI...........................................................524
Introduction...........................................................................524
Principle of operation............................................................524
Function block......................................................................529
Input and output signals.......................................................529
Setting parameters...............................................................531
Circuit breaker SXCBR..............................................................531
Introduction...........................................................................531
Principle of operation............................................................531
Function block......................................................................535
Input and output signals.......................................................535
Setting parameters...............................................................536
Circuit switch SXSWI.................................................................536
Introduction...........................................................................537
Principle of operation............................................................537
Function block......................................................................541
Input and output signals.......................................................541
Setting parameters...............................................................542
Bay reserve QCRSV..................................................................542
Introduction...........................................................................542
Principle of operation............................................................542
Function block......................................................................544
Input and output signals.......................................................545
Setting parameters...............................................................546
Reservation input RESIN...........................................................546
Introduction...........................................................................546
Principle of operation............................................................546

14
Technical reference manual
Table of contents

Function block......................................................................548
Input and output signals.......................................................549
Setting parameters...............................................................550
Interlocking ....................................................................................550
Introduction................................................................................550
Principle of operation.................................................................550
Logical node for interlocking SCILO .........................................553
Introduction...........................................................................553
Logic diagram.......................................................................553
Function block......................................................................554
Input and output signals.......................................................554
Interlocking for busbar earthing switch BB_ES .........................554
Introduction...........................................................................555
Function block......................................................................555
Logic diagram.......................................................................555
Input and output signals.......................................................555
Interlocking for bus-section breaker A1A2_BS..........................556
Introduction...........................................................................556
Function block......................................................................557
Logic diagram.......................................................................558
Input and output signals.......................................................559
Interlocking for bus-section disconnector A1A2_DC ................560
Introduction...........................................................................561
Function block......................................................................561
Logic diagram.......................................................................562
Input and output signals.......................................................562
Interlocking for bus-coupler bay ABC_BC ................................563
Introduction...........................................................................563
Function block......................................................................564
Logic diagram.......................................................................565
Input and output signals.......................................................567
Interlocking for 1 1/2 CB BH .....................................................570
Introduction...........................................................................570
Function blocks....................................................................571
Logic diagrams.....................................................................573
Input and output signals.......................................................578
Interlocking for double CB bay DB ...........................................582
Introduction...........................................................................582
Function block......................................................................583
Logic diagrams.....................................................................585
Input and output signals ......................................................588
Interlocking for line bay ABC_LINE ..........................................591
Introduction...........................................................................591

15
Technical reference manual
Table of contents

Function block......................................................................592
Logic diagram.......................................................................593
Input and output signals.......................................................598
Interlocking for transformer bay AB_TRAFO ............................600
Introduction...........................................................................601
Function block......................................................................602
Logic diagram.......................................................................603
Input and output signals.......................................................604
Position evaluation POS_EVAL.................................................606
Introduction...........................................................................606
Logic diagram.......................................................................606
Function block......................................................................607
Input and output signals.......................................................607
Logic rotating switch for function selection and LHMI
presentation SLGGIO.....................................................................607
Introduction................................................................................607
Principle of operation.................................................................607
Functionality and behaviour ................................................609
Graphical display..................................................................609
Function block...........................................................................611
Input and output signals............................................................611
Setting parameters....................................................................612
Selector mini switch VSGGIO.........................................................613
Introduction................................................................................613
Principle of operation.................................................................613
Function block...........................................................................614
Input and output signals............................................................614
Setting parameters....................................................................615
Generic double point function block DPGGIO................................615
Introduction................................................................................615
Principle of operation.................................................................615
Function block...........................................................................616
Input and output signals............................................................616
Settings......................................................................................616
Single point generic control 8 signals SPC8GGIO.........................616
Introduction................................................................................616
Principle of operation.................................................................617
Function block...........................................................................617
Input and output signals............................................................617
Setting parameters....................................................................618
AutomationBits, command function for DNP3.0 AUTOBITS..........618
Introduction................................................................................619
Principle of operation.................................................................619

16
Technical reference manual
Table of contents

Function block...........................................................................620
Input and output signals............................................................620
Setting parameters....................................................................621
Single command, 16 signals SINGLECMD....................................635
Introduction................................................................................635
Principle of operation.................................................................635
Function block...........................................................................636
Input and output signals............................................................636
Setting parameters....................................................................637

Section 13 Scheme communication...............................................639


Scheme communication logic for distance or overcurrent
protection ZCPSCH .......................................................................639
Introduction................................................................................639
Principle of operation.................................................................640
Blocking scheme..................................................................640
Permissive underreaching scheme......................................640
Permissive overreaching scheme........................................641
Unblocking scheme..............................................................641
Intertrip scheme....................................................................642
Simplified logic diagram.......................................................642
Function block...........................................................................644
Input and output signals............................................................644
Setting parameters....................................................................645
Technical data...........................................................................645
Phase segregated scheme communication logic for distance
protection ZC1PPSCH ...................................................................646
Introduction................................................................................646
Principle of operation.................................................................646
Blocking scheme..................................................................647
Permissive underreach scheme...........................................647
Permissive overreach scheme.............................................648
Unblocking scheme..............................................................648
Intertrip scheme....................................................................648
Simplified logic diagram.......................................................649
Function block...........................................................................650
Input and output signals............................................................650
Setting parameters....................................................................652
Technical data...........................................................................652
Current reversal and weak-end infeed logic for distance
protection ZCRWPSCH .................................................................652
Introduction................................................................................652
Principle of operation.................................................................653
Current reversal logic...........................................................653

17
Technical reference manual
Table of contents

Weak-end infeed logic..........................................................653


Function block...........................................................................655
Input and output signals............................................................655
Setting parameters....................................................................656
Technical data...........................................................................656
Local acceleration logic ZCLCPLAL...............................................656
Introduction................................................................................657
Principle of operation.................................................................657
Zone extension.....................................................................657
Loss-of-Load acceleration....................................................658
Function block...........................................................................658
Input and output signals............................................................659
Setting parameters....................................................................659
Scheme communication logic for residual overcurrent
protection ECPSCH .......................................................................660
Introduction................................................................................660
Introduction...........................................................................660
Principle of operation.................................................................660
Blocking scheme..................................................................661
Permissive under/overreaching scheme..............................662
Unblocking scheme..............................................................663
Function block...........................................................................664
Input and output signals............................................................665
Setting parameters....................................................................665
Technical data...........................................................................666
Current reversal and weak-end infeed logic for residual
overcurrent protection ECRWPSCH ..............................................666
Introduction................................................................................666
Principle of operation.................................................................667
Directional comparison logic function...................................667
Fault current reversal logic...................................................667
Weak-end infeed logic..........................................................668
Function block...........................................................................669
Input and output signals............................................................669
Setting parameters....................................................................670
Technical data...........................................................................670
Current reversal and weak-end infeed logic for phase
segregated communication ZC1WPSCH ......................................671
Introduction................................................................................671
Principle of operation.................................................................671
Current reversal logic ..........................................................671
Function block...........................................................................673
Input and output signals............................................................674
Setting parameters....................................................................675

18
Technical reference manual
Table of contents

Technical data...........................................................................675

Section 14 Logic.............................................................................677
Tripping logic SMPPTRC ...............................................................677
Introduction................................................................................677
Principle of operation.................................................................677
Logic diagram.......................................................................679
Function block...........................................................................683
Input and output signals............................................................683
Setting parameters....................................................................684
Technical data...........................................................................685
Trip matrix logic TMAGGIO............................................................685
Introduction................................................................................685
Principle of operation.................................................................685
Function block...........................................................................687
Input and output signals............................................................687
Setting parameters....................................................................688
Configurable logic blocks................................................................689
Introduction................................................................................689
Inverter function block INV........................................................689
OR function block OR................................................................690
AND function block AND...........................................................691
Timer function block TIMER......................................................691
Pulse timer function block PULSETIMER..................................692
Exclusive OR function block XOR.............................................692
Loop delay function block LOOPDELAY...................................693
Set-reset with memory function block SRMEMORY.................693
Controllable gate function block GATE......................................694
Settable timer function block TIMERSET..................................695
Technical data...........................................................................696
Fixed signal function block FXDSIGN............................................696
Principle of operation.................................................................696
Function block...........................................................................697
Input and output signals............................................................697
Setting parameters....................................................................697
Boolean 16 to Integer conversion B16I..........................................697
Introduction................................................................................697
Principle of operation.................................................................698
Function block...........................................................................698
Input and output signals............................................................698
Setting parameters....................................................................699
Boolean 16 to Integer conversion with logic node
representation B16IGGIO...............................................................699
Introduction................................................................................699

19
Technical reference manual
Table of contents

Principle of operation.................................................................699
Function block...........................................................................700
Input and output signals............................................................700
Setting parameters....................................................................701
Integer to Boolean 16 conversion IB16..........................................701
Introduction................................................................................701
Principle of operation.................................................................701
Function block...........................................................................701
Input and output signals............................................................702
Setting parameters....................................................................702
Integer to Boolean 16 conversion with logic node
representation IB16GGIO...............................................................702
Introduction................................................................................703
Principle of operation.................................................................703
Function block...........................................................................703
Input and output signals............................................................703
Setting parameters....................................................................704

Section 15 Monitoring.....................................................................705
Measurements................................................................................705
Introduction................................................................................706
Principle of operation.................................................................707
Measurement supervision....................................................707
Measurements CVMMXU.....................................................711
Phase current measurement CMMXU.................................716
Phase-phase and phase-neutral voltage measurements
VMMXU, VNMMXU..............................................................717
Voltage and current sequence measurements VMSQI,
CMSQI..................................................................................717
Function block...........................................................................717
Input and output signals............................................................719
Setting parameters....................................................................722
Technical data...........................................................................735
Event counter CNTGGIO................................................................736
Introduction................................................................................736
Principle of operation.................................................................736
Reporting..............................................................................736
Design..................................................................................737
Function block...........................................................................737
Input signals..............................................................................737
Setting parameters....................................................................738
Technical data...........................................................................738
Event function EVENT....................................................................738
Introduction................................................................................738

20
Technical reference manual
Table of contents

Principle of operation.................................................................738
Function block...........................................................................740
Input and output signals............................................................740
Setting parameters....................................................................741
Logical signal status report BINSTATREP.....................................743
Introduction................................................................................743
Principle of operation.................................................................743
Function block...........................................................................744
Input and output signals............................................................744
Setting parameters....................................................................745
Fault locator LMBRFLO..................................................................745
Introduction................................................................................746
Principle of operation.................................................................746
Measuring Principle..............................................................747
Accurate algorithm for measurement of distance to fault.....747
The non-compensated impedance model............................751
IEC 60870-5-103..................................................................752
Function block...........................................................................752
Input and output signals............................................................752
Setting parameters....................................................................753
Technical data...........................................................................754
Measured value expander block RANGE_XP................................754
Introduction................................................................................754
Principle of operation.................................................................754
Function block...........................................................................755
Input and output signals............................................................755
Disturbance report DRPRDRE.......................................................755
Introduction................................................................................756
Principle of operation.................................................................756
Function block...........................................................................763
Input and output signals............................................................765
Setting parameters....................................................................766
Technical data...........................................................................776
Event list.........................................................................................776
Introduction................................................................................776
Principle of operation.................................................................776
Function block...........................................................................777
Input signals..............................................................................777
Technical data...........................................................................777
Indications......................................................................................777
Introduction................................................................................777
Principle of operation.................................................................778
Function block...........................................................................779

21
Technical reference manual
Table of contents

Input signals..............................................................................779
Technical data...........................................................................779
Event recorder ...............................................................................779
Introduction................................................................................779
Principle of operation.................................................................779
Function block...........................................................................780
Input signals..............................................................................780
Technical data...........................................................................780
Trip value recorder.........................................................................780
Introduction................................................................................780
Principle of operation.................................................................781
Function block...........................................................................781
Input signals..............................................................................781
Technical data...........................................................................782
Disturbance recorder......................................................................782
Introduction................................................................................782
Principle of operation.................................................................782
Memory and storage............................................................783
IEC 60870-5-103..................................................................784
Function block...........................................................................785
Input and output signals............................................................785
Setting parameters....................................................................785
Technical data...........................................................................785

Section 16 Metering.......................................................................787
Pulse-counter logic PCGGIO..........................................................787
Introduction................................................................................787
Principle of operation.................................................................787
Function block...........................................................................789
Input and output signals............................................................790
Setting parameters....................................................................790
Technical data...........................................................................791
Function for energy calculation and demand handling
ETPMMTR......................................................................................791
Introduction................................................................................791
Principle of operation.................................................................791
Function block...........................................................................792
Input and output signals............................................................792
Setting parameters....................................................................793

Section 17 Station communication.................................................795


Overview.........................................................................................795
IEC 61850-8-1 communication protocol.........................................795
Introduction................................................................................795

22
Technical reference manual
Table of contents

IEC 61850 generic communication I/O functions SPGGIO,


SP16GGIO................................................................................795
Introduction...........................................................................796
Principle of operation............................................................796
Function block......................................................................796
Input and output signals.......................................................796
Setting parameters...............................................................797
IEC 61850 generic communication I/O functions MVGGIO.......797
Principle of operation............................................................797
Function block......................................................................798
Input and output signals.......................................................798
Setting parameters...............................................................798
Setting parameters....................................................................799
Technical data...........................................................................799
IEC 61850-9-2LE communication protocol.....................................799
Introduction................................................................................799
Principle of operation.................................................................799
Function block...........................................................................801
Output signals............................................................................802
Setting parameters....................................................................802
Technical data...........................................................................803
LON communication protocol.........................................................803
Introduction................................................................................803
Principle of operation.................................................................803
Setting parameters....................................................................821
Technical data...........................................................................821
SPA communication protocol.........................................................821
Introduction................................................................................821
Principle of operation.................................................................822
Communication ports...........................................................829
Design.......................................................................................829
Setting parameters....................................................................830
Technical data...........................................................................830
IEC 60870-5-103 communication protocol.....................................830
Introduction................................................................................830
Principle of operation.................................................................830
General.................................................................................830
Communication ports...........................................................840
Function block...........................................................................840
Input and output signals............................................................843
Setting parameters....................................................................848
Technical data...........................................................................850
Horizontal communication via GOOSE for interlocking
GOOSEINTLKRCV.........................................................................851

23
Technical reference manual
Table of contents

Function block...........................................................................851
Input and output signals............................................................851
Setting parameters....................................................................853
Goose binary receive GOOSEBINRCV..........................................854
Function block...........................................................................854
Input and output signals............................................................854
Setting parameters....................................................................855
Multiple command and transmit MULTICMDRCV,
MULTICMDSND.............................................................................855
Introduction................................................................................856
Principle of operation.................................................................856
Design.......................................................................................856
General.................................................................................856
Function block...........................................................................857
Input and output signals............................................................858
Setting parameters....................................................................859

Section 18 Remote communication................................................861


Binary signal transfer......................................................................861
Introduction................................................................................861
Principle of operation.................................................................861
Function block...........................................................................863
Input and output signals............................................................863
Setting parameters....................................................................865
Transmission of analog data from LDCM LDCMTransmit..............867
Function block...........................................................................867
Input and output signals............................................................868

Section 19 Hardware......................................................................869
Overview.........................................................................................869
Variants of case and local HMI display size..............................869
Case from the rear side.............................................................872
Hardware modules.........................................................................877
Overview....................................................................................877
Combined backplane module (CBM).........................................878
Introduction...........................................................................878
Functionality.........................................................................878
Design..................................................................................878
Universal backplane module (UBM)..........................................880
Introduction...........................................................................880
Functionality.........................................................................880
Design..................................................................................880
Numeric processing module (NUM)..........................................882
Introduction...........................................................................882

24
Technical reference manual
Table of contents

Functionality.........................................................................883
Block diagram.......................................................................884
Power supply module (PSM).....................................................884
Introduction...........................................................................884
Design..................................................................................884
Technical data......................................................................885
Local human-machine interface (Local HMI).............................885
Transformer input module (TRM)..............................................885
Introduction...........................................................................886
Design..................................................................................886
Technical data......................................................................886
Analog digital conversion module, with time
synchronization (ADM) .............................................................887
Introduction...........................................................................887
Design..................................................................................887
Binary input module (BIM).........................................................889
Introduction...........................................................................889
Design..................................................................................889
Technical data......................................................................893
Binary output modules (BOM)...................................................893
Introduction...........................................................................893
Design..................................................................................893
Technical data......................................................................895
Static binary output module (SOM)...........................................896
Introduction...........................................................................896
Design..................................................................................896
Technical data......................................................................898
Binary input/output module (IOM)..............................................899
Introduction...........................................................................899
Design..................................................................................900
Technical data......................................................................902
mA input module (MIM).............................................................903
Introduction...........................................................................903
Design..................................................................................903
Technical data......................................................................904
Serial and LON communication module (SLM) ........................905
Introduction...........................................................................905
Design..................................................................................905
Technical data......................................................................906
Galvanic RS485 communication module...................................907
Introduction...........................................................................907
Design..................................................................................907
Technical data......................................................................909

25
Technical reference manual
Table of contents

Optical ethernet module (OEM).................................................909


Introduction...........................................................................909
Functionality.........................................................................909
Design..................................................................................909
Technical data......................................................................910
Line data communication module (LDCM)................................910
Introduction...........................................................................910
Design..................................................................................911
Technical data......................................................................912
Galvanic X.21 line data communication (X.21-LDCM)..............913
Introduction...........................................................................913
Design..................................................................................913
Functionality.........................................................................915
Technical data......................................................................916
GPS time synchronization module (GSM).................................916
Introduction...........................................................................916
Design..................................................................................916
Technical data......................................................................918
GPS antenna.............................................................................919
Introduction...........................................................................919
Design..................................................................................919
Technical data......................................................................920
IRIG-B time synchronization module IRIG-B.............................921
Introduction...........................................................................921
Design..................................................................................921
Technical data......................................................................922
Dimensions.....................................................................................923
Case without rear cover.............................................................923
Case with rear cover..................................................................925
Flush mounting dimensions.......................................................927
Side-by-side flush mounting dimensions...................................928
Wall mounting dimensions.........................................................929
External resistor unit for high impedance differential
protection...................................................................................929
Mounting alternatives.....................................................................930
Flush mounting..........................................................................930
Overview..............................................................................930
Mounting procedure for flush mounting................................932
19” panel rack mounting............................................................933
Overview..............................................................................933
Mounting procedure for 19” panel rack mounting.................934
Wall mounting............................................................................934
Overview..............................................................................934

26
Technical reference manual
Table of contents

Mounting procedure for wall mounting.................................935


How to reach the rear side of the IED..................................936
Side-by-side 19” rack mounting.................................................936
Overview..............................................................................936
Mounting procedure for side-by-side rack mounting............937
IED in the 670 series mounted with a RHGS6 case.............937
Side-by-side flush mounting......................................................938
Overview..............................................................................938
Mounting procedure for side-by-side flush mounting...........939
Technical data................................................................................939
Enclosure...................................................................................939
Connection system....................................................................940
Influencing factors.....................................................................940
Type tests according to standard..............................................941

Section 20 Labels...........................................................................945
Different labels................................................................................945

Section 21 Connection diagrams...................................................949

Section 22 Inverse time characteristics..........................................965


Application......................................................................................965
Principle of operation......................................................................968
Mode of operation......................................................................968
Inverse characteristics....................................................................973

Section 23 Glossary.......................................................................999

27
Technical reference manual
28
1MRK505183-UEN C Section 1
Introduction

Section 1 Introduction

About this chapter


This chapter explains concepts and conventions used in this manual and provides
information necessary to understand the contents of the manual.

1.1 Introduction to the technical reference manual

1.1.1 About the complete set of manuals for an IED


The user’s manual (UM) is a complete set of five different manuals:

deinstalling & disposal


Planning & purchase

Decommissioning
Commissioning

Maintenance
Engineering

Operation
Installing

Engineeringmanual
Installation and
Commissioning manual

Operator’s manual

Application manual

Technical reference
manual
IEC09000744-1-en.vsd
IEC09000744 V1 EN

The Application Manual (AM) contains application descriptions, setting


guidelines and setting parameters sorted per function. The application manual
should be used to find out when and for what purpose a typical protection function
could be used. The manual should also be used when calculating settings.

The Technical Reference Manual (TRM) contains application and functionality


descriptions and it lists function blocks, logic diagrams, input and output signals,
setting parameters and technical data sorted per function. The technical reference

29
Technical reference manual
Section 1 1MRK505183-UEN C
Introduction

manual should be used as a technical reference during the engineering phase,


installation and commissioning phase, and during normal service.

The Installation and Commissioning Manual (ICM) contains instructions on


how to install and commission the protection IED. The manual can also be used as
a reference during periodic testing. The manual covers procedures for mechanical
and electrical installation, energizing and checking of external circuitry, setting and
configuration as well as verifying settings and performing directional tests. The
chapters are organized in the chronological order (indicated by chapter/section
numbers) in which the protection IED should be installed and commissioned.

The Operator’s Manual (OM) contains instructions on how to operate the


protection IED during normal service once it has been commissioned. The
operator’s manual can be used to find out how to handle disturbances or how to
view calculated and measured network data in order to determine the cause of a fault.

The Engineering Manual (EM) contains instructions on how to engineer the IEDs
using the different tools in PCM600. The manual provides instructions on how to
set up a PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 61850 and DNP3.

1.1.2 About the technical reference manual


The following chapters are included in the technical reference manual.

• Local HMI describes the control panel on the IED and explains display
characteristics, control keys and various local HMI features.
• Basic IED functions presents functions for all protection types that are
included in all IEDs, for example, time synchronization, self supervision with
event list, test mode and other general functions.
• Differential protection describes differential functions and restricted earth fault
protection.
• Impedance protection describes functions for distance zones with their
quadrilateral characteristics, phase selection with load encroachment, power
swing detection and similar.
• Current protection describes functions, for example, over current protection,
breaker failure protection and pole discordance.
• Voltage protection describes functions for under voltage and over voltage
protection and residual over voltage protection.
• Frequency protection describes functions for over frequency, under frequency
and rate of change of frequency protection.
• Multipurpose protection describes the general protection function for current
and voltage.
• Secondary system supervision describes current based functions for current
circuit supervision and fuse failure supervision.
• Control describes control functions, for example, synchronization and
energizing check and other product specific functions.
• Scheme communication describes functions related to current reversal and
weak end infeed logic.

30
Technical reference manual
1MRK505183-UEN C Section 1
Introduction

• Logic describes trip logic and related functions.


• Monitoring describes measurement related functions that are used to provide
data regarding relevant quantities, events and faults, for example.
• Metering describes pulse counter logic.
• Station communication describes Ethernet based communication in general,
including the use of IEC 61850 and horizontal communication via GOOSE.
• Remote communication describes binary and analog signal transfer, and the
associated hardware.
• Hardware describes the IED and its components.
• Connection diagrams provides terminal wiring diagrams and information
regarding connections to and from the IED.
• Inverse time characteristics describes and explains inverse time delay, inverse
time curves and their effects.
• Glossary is a list of terms, acronyms and abbreviations used in ABB technical
documentation.

1.1.3 This manual


The description of each IED related function follows the same structure (where
applicable). The different sections are outlined below.

1.1.3.1 Introduction

Outlines the implementation of a particular protection function.

1.1.3.2 Principle of operation

Describes how the function works, presents a general background to algorithms


and measurement techniques. Logic diagrams are used to illustrate functionality.

Logic diagrams
Logic diagrams describe the signal logic inside the function block and are bordered
by dashed lines.

Signal names
Input and output logic signals consist of two groups of letters separated by two
dashes. The first group consists of up to four letters and presents the abbreviated
name for the corresponding function. The second group presents the functionality
of the particular signal. According to this explanation, the meaning of the signal
BLKTR in figure 4 is as follows:

• BLKTR informs the user that the signal will BLOCK the TRIP command from
the under-voltage function, when its value is a logical one (1).

Input signals are always on the left hand side, and output signals on the right hand
side. Settings are not displayed.

31
Technical reference manual
Section 1 1MRK505183-UEN C
Introduction

Input and output signals


In a logic diagram, input and output signal paths are shown as a lines that touch the
outer border of the diagram.

Input and output signals can be configured using the ACT tool. They can be
connected to the inputs and outputs of other functions and to binary inputs and
outputs. Examples of input signals are BLKTR, BLOCK and VTSU. Examples
output signals are TRIP, START, STL1, STL2, STL3.

Setting parameters
Signals in frames with a shaded area on their right hand side represent setting
parameter signals. These parameters can only be set via the PST or LHMI. Their
values are high (1) only when the corresponding setting parameter is set to the
symbolic value specified within the frame. Example is the signal Block TUV=Yes.
Their logical values correspond automatically to the selected setting value.

Internal signals
Internal signals are illustrated graphically and end approximately 2 mm from the
frame edge. If an internal signal path cannot be drawn with a continuous line, the
suffix -int is added to the signal name to indicate where the signal starts and
continues, see figure 1.

BLKTR

TEST

TEST
&
Block TUV=Yes BLOCK-int.
>1

BLOCK

VTSU
BLOCK-int.
&
STUL1N
BLOCK-int.
& >1 & TRIP
t
STUL2N
BLOCK-int.
START
&
STUL3N
STL1

STL2

STL3

xx04000375.vsd
IEC04000375 V1 EN

Figure 1: Logic diagram example with -int signals

32
Technical reference manual
1MRK505183-UEN C Section 1
Introduction

External signals
Signal paths that extend beyond the logic diagram and continue in another diagram
have the suffix “-cont.”, see figure 2 and figure 3.

STZMPP-cont.
>1
STCND

& STNDL1L2-cont.
1L1L2
STNDL2L3-cont.
&
1L2L3

& STNDL3L1-cont.
1L3L1

& STNDL1N-cont.
1L1N

& STNDL2N-cont.
1L2N
STNDL3N-cont.
&
1L3N

>1 STNDPE-cont.

>1
1--VTSZ 1--STND
>1 &
1--BLOCK
BLK-cont.

xx04000376.vsd
IEC04000376 V1 EN

Figure 2: Logic diagram example with an outgoing -cont signal

STNDL1N-cont.
>1
STNDL2N-cont. 15 ms
& t STL1
STNDL3N-cont.
STNDL1L2-cont. >1 15 ms
& t STL2
STNDL2L3-cont.
15 ms
STNDL3L1-cont. & t STL3
>1
15 ms
& t START
>1

BLK-cont.

xx04000377.vsd
IEC04000377 V1 EN

Figure 3: Logic diagram example with an incoming -cont signal

33
Technical reference manual
Section 1 1MRK505183-UEN C
Introduction

1.1.3.3 Input and output signals

Input and output signals are presented in two separate tables. Each table consists of
two columns. The first column contains the name of the signal and the second
column contains the description of the signal.

1.1.3.4 Function block

Each function block is illustrated graphically.

Input signals are always on the left hand side and output signals on the right hand
side. Settings are not displayed. Special kinds of settings are sometimes available.
These are supposed to be connected to constants in the configuration scheme and
are therefore depicted as inputs. Such signals will be found in the signal list but
described in the settings table.

• The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set a signal name of
their own in PCM600.
• The * character after an input or output signal name in the function block
symbol given for a function, indicates that the signal must be connected to
another function block in the application configuration to achieve a valid
application configuration.

IEC 61850 - 8 -1
Logical Node Mandatory
signal (*)

Inputs Outputs
PCGGIO
BLOCK INVALID
READ_VAL RESTART
BI_PULSE* BLOCKED
RS_CNT NEW_VAL
^SCAL_VAL

en05000511-1-en.vsd
User defined
name (^)

Diagram
Number
IEC05000511 V2 EN

Figure 4: Example of a function block

1.1.3.5 Setting parameters

These are presented in tables and include all parameters associated with the
function in question.

34
Technical reference manual
1MRK505183-UEN C Section 1
Introduction

1.1.3.6 Technical data

The technical data section provides specific technical information about the
function or hardware described.

1.1.4 Intended audience


General
This manual addresses system engineers, installation and commissioning
personnel, who use technical data during engineering, installation and
commissioning, and in normal service.

Requirements
The system engineer must have a thorough knowledge of protection systems,
protection equipment, protection functions and the configured functional logics in
the protective devices. The installation and commissioning personnel must have a
basic knowledge in the handling electronic equipment.

1.1.5 Related documents


Documents related to RED670 Identity number
Operator’s manual 1MRK 505 184-UEN
Installation and commissioning manual 1MRK 505 185-UEN
Technical reference manual 1MRK 505 183-UEN
Application manual 1MRK 505 186-UEN
Buyer’s guide 1MRK 505 188-BEN
Sample specification SA2005-001281
Connection diagram, Single breaker arr. Three phase tripping arr. 1MRK 002 801-BA
Connection diagram, Single breaker arr. Single phase tripping arr. 1MRK 002 801-CA
Connection diagram, Multi breaker arr. Three phase tripping arr. 1MRK 002 801-DA
Connection diagram, Multi breaker arr. Single phase tripping arr. 1MRK 002 801-EA
Configuration diagram A, Single breaker with single or double busbars 1MRK 004 500-82
Configuration diagram B, Single breakers with single or double busbars 1MRK 004 500-83
Configuration diagram C, Multi breakers such as 1 1/2 or ring busbar arr. 1MRK 004 500-84
Configuration diagram D, Multi breakers such as 1 1/2 or ring busbar arr. 1MRK 004 500-85
Setting example 1, 230 kV Short cable line with 1 1/2CB arr. 1MRK 505 175-WEN

Connection and Installation components 1MRK 513 003-BEN


Test system, COMBITEST 1MRK 512 001-BEN
Accessories for IED 670 1MRK 514 012-BEN
Getting started guide IED 670 1MRK 500 080-UEN
SPA and LON signal list for IED 670, ver. 1.1 1MRK 500 083-WEN
Table continues on next page

35
Technical reference manual
Section 1 1MRK505183-UEN C
Introduction

IEC 61850 Data objects list for IED 670, ver. 1.1 1MRK 500 084-WEN
Generic IEC 61850 IED Connectivity package 1KHA001027-UEN
Protection and Control IED Manager PCM 600 Installation sheet 1MRS755552
Engineering guide IED 670 products 1MRK 511 179-UEN

More information can be found on www.abb.com/substationautomation.

1.1.6 Revision notes


Revision Description
C No functionality added. Changes made in content due to problem reports.

36
Technical reference manual
1MRK505183-UEN C Section 2
Analog inputs

Section 2 Analog inputs

2.1 Introduction

Analog input channels must be configured and set properly to get correct
measurement results and correct protection operations. For power measuring and
all directional and differential functions the directions of the input currents must be
defined properly. Measuring and protection algorithms in the IED use primary
system quantities. Set values are done in primary quantities as well and it is
important to set the data about the connected current and voltage transformers
properly.

A reference PhaseAngleRef can be defined to facilitate service values reading. This


analog channels phase angle will always be fixed to zero degree and all other angle
information will be shown in relation to this analog input. During testing and
commissioning of the IED the reference channel can be changed to facilitate testing
and service values reading.

The IED has the ability to receive analog values from primary
equipment, that are sampled by Merging units (MU) connected to a
process bus, via the IEC 61850-9-2 LE protocol.

The availability of VT inputs depends on the ordered transformer


input module (TRM) type.

2.2 Operation principle

The direction of a current to the IED depends on the connection of the CT. The
main CTs are typically star connected and can be connected with the star point to
the object or from the object. This information must be set to the IED.

Directional conventions for current or power, for example

• Positive value of current or power means quantity direction into the object.
• Negative value of current or power means quantity direction out from the object.

Directional conventions for directional functions (see figure 5)

37
Technical reference manual
Section 2 1MRK505183-UEN C
Analog inputs

• Forward means direction into the object.


• Reverse means direction out from the object.

Definition of direction Definition of direction


for directional functions for directional functions
Reverse Forward Forward Reverse
Protected Object
Line, transformer, etc
e.g. P, Q, I e.g. P, Q, I
Measured quantity is Measured quantity is
positive when flowing positive when flowing
towards the object towards the object

Set parameter Set parameter


CTStarPoint CTStarPoint
Correct Setting is Correct Setting is
"ToObject" "FromObject"

en05000456.vsd
IEC05000456 V1 EN

Figure 5: Internal convention of the directionality in the IED

The correct setting of the primary CT direction

• CTStarPoint is set to FromObject or ToObject.


• Positive quantities flow towards the object.
• Direction is defined as Forward and looks towards the object.

The ratios of the main CTs and VTs must be known to use primary system
quantities for settings and calculation in the IED, The user has to set the rated
secondary and primary currents and voltages of the CTs and VTs to provide the
IED with this information.

The CT and VT ratio and the name on respective channel is done under Main
menu/General settings/Analog module in the Parameter Settings tool.

2.3 Function block

The function blocks are not represented in the configuration tool.


The signals appear only in the SMT tool when a TRM is included in
the configuration with the function selector tool. In the SMT tool
they can be mapped to the desired virtual input (SMAI) of the IED
and used internally in the configuration.

38
Technical reference manual
1MRK505183-UEN C Section 2
Analog inputs

2.4 Setting parameters

Dependent on ordered IED type.

Table 1: AISVBAS Non group settings (basic)


Name Values (Range) Unit Step Default Description
PhaseAngleRef TRM40-Ch1 - - TRM40-Ch1 Reference channel for phase angle
TRM40-Ch2 presentation
TRM40-Ch3
TRM40-Ch4
TRM40-Ch5
TRM40-Ch6
TRM40-Ch7
TRM40-Ch8
TRM40-Ch9
TRM40-Ch10
TRM40-Ch11
TRM40-Ch12
TRM41-Ch1
TRM41-Ch2
TRM41-Ch3
TRM41-Ch4
TRM41-Ch5
TRM41-Ch6
TRM41-Ch7
TRM41-Ch8
TRM41-Ch9
TRM41-Ch10
TRM41-Ch11
TRM41-Ch12
MU1-L1I
MU1-L2I
MU1-L3I
MU1-L4I
MU1-L1U
MU1-L2U
MU1-L3U
MU1-L4U
MU2-L1I
MU2-L2I
MU2-L3I
MU2-L4I
MU2-L1U
MU2-L2U
MU2-L3U
MU2-L4U
MU3-L1I
MU3-L2I
MU3-L3I
MU3-L4I
MU3-L1U
MU3-L2U
MU3-L3U
MU3-L4U

39
Technical reference manual
Section 2 1MRK505183-UEN C
Analog inputs

Table 2: TRM_12I Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec8 1 - 10 A 1 1 Rated CT secondary current
CTprim8 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec9 1 - 10 A 1 1 Rated CT secondary current
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint10 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec10 1 - 10 A 1 1 Rated CT secondary current
CTprim10 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint11 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec11 1 - 10 A 1 1 Rated CT secondary current
Table continues on next page

40
Technical reference manual
1MRK505183-UEN C Section 2
Analog inputs

Name Values (Range) Unit Step Default Description


CTprim11 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint12 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec12 1 - 10 A 1 1 Rated CT secondary current
CTprim12 1 - 99999 A 1 3000 Rated CT primary current

Table 3: TRM_6I_6U Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
VTsec7 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim7 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec8 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim8 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec9 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim9 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
Table continues on next page

41
Technical reference manual
Section 2 1MRK505183-UEN C
Analog inputs

Name Values (Range) Unit Step Default Description


VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

Table 4: TRM_6I Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current

Table 5: TRM_7I_5U Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
Table continues on next page

42
Technical reference manual
1MRK505183-UEN C Section 2
Analog inputs

Name Values (Range) Unit Step Default Description


CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
VTsec8 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim8 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec9 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim9 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

Table 6: TRM_9I_3U Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
Table continues on next page

43
Technical reference manual
Section 2 1MRK505183-UEN C
Analog inputs

Name Values (Range) Unit Step Default Description


CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec8 1 - 10 A 1 1 Rated CT secondary current
CTprim8 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec9 1 - 10 A 1 1 Rated CT secondary current
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

44
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI

Section 3 Local HMI

About this chapter


This chapter describes the structure and use of local HMI, which is the control
panel at the IED.

3.1 Human machine interface

The local human machine interface is available in a small and a medium sized
model. The difference between the two models is the size of the LCD. The small
size LCD can display seven lines of text and the medium size LCD can display the
single line diagram with up to 15 objects on each page. Up to 12 single line
diagram pages can be defined, depending on the product capability.

The local HMI is divided into zones with different functionality.

• Status indication LEDs.


• Alarm indication LEDs, which consist of 15 LEDs (6 red and 9 yellow) with
user printable label. All LEDs are configurable from PCM600.
• Liquid crystal display (LCD).
• Keypad with push buttons for control and navigation purposes, switch for
selection between local and remote control and reset.
• Isolated RJ45 communication port.

45
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI

IEC05000055-LITEN V1 EN

Figure 6: Small, alpha numeric HMI

IEC05000056-LITEN V1 EN

Figure 7: Medium graphic HMI, 15 controllable objects

46
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI

3.2 Small size HMI

3.2.1 Small
The small sized HMI is available for 1/2, 3/4 and 1/1 x 19” case. The LCD on the
small HMI measures 32 x 90 mm and displays 7 lines with up to 40 characters per
line. The first line displays the product name and the last line displays date and
time. The remaining 5 lines are dynamic. This LCD has no graphic display potential.

3.2.2 Design
The local HMI is identical for both the 1/2, 3/4 and 1/1 cases. The different parts of
the small local HMI are shown in figure 8

47
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI

1 2 3

en05000055.eps
8 7
IEC05000055-CALLOUT V1 EN

Figure 8: Small graphic HMI

1 Status indication LEDs


2 LCD
3 Indication LEDs
4 Label
5 Local/Remote LEDs
6 RJ45 port
7 Communication indication LED
8 Keypad

48
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI

3.3 Medium size graphic HMI

3.3.1 Medium
The following case sizes can be equipped with the medium size LCD:

• 1/2 x 19”
• 3/4 x 19”
• 1/1 x 19”

This is a fully graphical monochrome LCD which measures 120 x 90 mm. It has 28
lines with up to 40 characters per line. To display the single line diagram, this LCD
is required.

3.3.2 Design
The different parts of the medium size local HMI are shown in figure 9. The local
HMI exists in an IEC version and in an ANSI version. The difference is on the
keypad operation buttons and the yellow LED designation.

49
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI

1 2 3

en05000056.eps
8 7
IEC05000056-CALLOUT V1 EN

Figure 9: Medium size graphic HMI

1 Status indication LEDs


2 LCD
3 Indication LEDs
4 Label
5 Local/Remote LEDs
6 RJ45 port
7 Communication indication LED
8 Keypad

50
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI

3.4 Keypad

The keypad is used to monitor and operate the IED. The keypad has the same look
and feel in all IEDs. LCD screens and other details may differ but the way the keys
function is identical.

IEC05000153 V1 EN

Figure 10: The HMI keypad.

Table 7 describes the HMI keys that are used to operate the IED.

Table 7: HMI keys on the front of the IED


Key Function

Press to close or energize a breaker or disconnector.


IEC05000101 V1 EN

Press to open a breaker or disconnector.


IEC05000102 V1 EN

Press to open two sub menus: Key operation and IED information.
IEC05000103 V1 EN

Press to clear entries, cancel commands or edit.


IEC05000104 V1 EN

Press to open the main menu and to move to the default screen.
IEC05000105 V1 EN

Press to set the IED in local or remote control mode.


IEC05000106 V1 EN

Press to open the reset screen.


IEC05000107 V1 EN

Press to start the editing mode and confirm setting changes, when in editing mode.
IEC05000108 V1 EN

Table continues on next page

51
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI

Key Function

Press to navigate forward between screens and move right in editing mode.
IEC05000109 V1 EN

Press to navigate backwards between screens and move left in editing mode.
IEC05000110 V1 EN

Press to move up in the single line diagram and in the menu tree.
IEC05000111 V1 EN

Press to move down in the single line diagram and in the menu tree.
IEC05000112 V1 EN

3.5 LED

3.5.1 Introduction
The LED module is a unidirectional means of communicating. This means that
events may occur that activate a LED in order to draw the operators attention to
something that has occurred and needs some sort of action.

3.5.2 Status indication LEDs


The three LEDs above the LCD provide information as shown in the table below.
LED Indication Information
Green:
Steady In service
Flashing Internal failure
Dark No power supply
Yellow:
Steady Dist. rep. triggered
Flashing Terminal in test mode
Red:
Steady Trip command issued

3.5.3 Indication LEDs


The LED indication module comprising 15 LEDs is standard in 670 series. Its main
purpose is to present an immediate visual information for protection indications or
alarm signals.

52
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI

Alarm indication LEDs and hardware associated LEDs are located on the right
hand side of the front panel. Alarm LEDs are located on the right of the LCD
screen and show steady or flashing light.

• Steady light indicates normal operation.


• Flashing light indicates alarm.

Alarm LEDs can be configured in PCM600 and depend on the binary logic.
Therefore they can not be configured on the local HMI.

Typical examples of alarm LEDs

• Bay controller failure


• CB close blocked
• Interlocking bypassed
• Differential protection trip
• SF6 Gas refill
• Position error
• CB spring charge alarm
• Oil temperature alarm
• Thermal overload trip

The RJ45 port has a yellow LED indicating that communication has been
established between the IED and a computer.

The Local/Remote key on the front panel has two LEDs indicating whether local or
remote control of the IED is active.

3.6 Local HMI related functions

3.6.1 Introduction
The local HMI can be adapted to the application configuration and to user preferences.

• Function block LocalHMI


• Function block LEDGEN
• Setting parameters

53
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI

3.6.2 General setting parameters


Table 8: SCREEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
Language English - - English Local HMI language
OptionalLanguage
DisplayTimeout 10 - 120 Min 10 60 Local HMI display timeout
AutoRepeat Off - - On Activation of auto-repeat (On) or not (Off)
On
ContrastLevel -10 - 20 % 1 0 Contrast level for display
DefaultScreen 0-0 - 1 0 Default screen
EvListSrtOrder Latest on top - - Latest on top Sort order of event list
Oldest on top
SymbolFont IEC - - IEC Symbol font for Single Line Diagram
ANSI

3.6.3 Status indication LEDs

3.6.3.1 Design

The function block LocalHMI controls and supplies information about the status of
the status indication LEDs. The input and output signals of local HMI are
configured with PCM600.

The function block can be used if any of the signals are required in a configuration
logic.

See section "Status indication LEDs" for information about the LEDs.

3.6.3.2 Function block


LocalHMI
CLRLEDS HMI-ON
RED-S
YELLOW-S
YELLOW-F
CLRPULSE
LEDSCLRD

IEC05000773-2-en.vsd
IEC05000773 V2 EN

Figure 11: LocalHMI function block

3.6.3.3 Input and output signals


Table 9: LocalHMI Input signals
Name Type Default Description
CLRLEDS BOOLEAN 0 Input to clear the LCD-HMI LEDs

54
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI

Table 10: LocalHMI Output signals


Name Type Description
HMI-ON BOOLEAN Backlight of the LCD display is active
RED-S BOOLEAN Red LED on the LCD-HMI is steady
YELLOW-S BOOLEAN Yellow LED on the LCD-HMI is steady
YELLOW-F BOOLEAN Yellow LED on the LCD-HMI is flashing
CLRPULSE BOOLEAN A pulse is provided when the LEDs on the LCD-
HMI are cleared
LEDSCLRD BOOLEAN Active when the LEDs on the LCD-HMI are not
active

3.6.4 Indication LEDs

3.6.4.1 Introduction

The function block LEDGEN controls and supplies information about the status of
the indication LEDs. The input and output signals of LEDGEN are configured with
PCM600. The input signal for each LED is selected individually with the Signal
Matrix Tool in PCM600.

• LEDs (number 1–6) for trip indications are red.


• LEDs (number 7–15) for start indications are yellow.

Each indication LED on the local HMI can be set individually to operate in six
different sequences

• Two sequences operate as follow type.


• Four sequences operate as latch type.
• Two of the latching sequence types are intended to be used as a
protection indication system, either in collecting or restarting mode, with
reset functionality.
• Two of the latching sequence types are intended to be used as signaling
system in collecting (coll) mode with an acknowledgment functionality.

The light from the LEDs can be steady (-S) or flashing (-F). See the technical
reference manual for more information.

3.6.4.2 Design

The information on the LEDs is stored at loss of the auxiliary power to the IED in
some of the modes of LEDGEN. The latest LED picture appears immediately after
the IED is successfully restarted.

Operating modes
• Collecting mode

55
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI

• LEDs which are used in collecting mode of operation are accumulated


continuously until the unit is acknowledged manually. This mode is
suitable when the LEDs are used as a simplified alarm system.

• Re-starting mode
• In the re-starting mode of operation each new start resets all previous
active LEDs and activates only those which appear during one
disturbance. Only LEDs defined for re-starting mode with the latched
sequence type 6 (LatchedReset-S) will initiate a reset and a restart at a
new disturbance. A disturbance is defined to end a settable time after the
reset of the activated input signals or when the maximum time limit has
elapsed.

Acknowledgment/reset
• From local HMI
• Active indications can be acknowledged or reset manually. Manual
acknowledgment and manual reset have the same meaning and is a
common signal for all the operating sequences and LEDs. The function
is positive edge triggered, not level triggered. The acknowledged or reset
is performed via the reset button and menus on the local HMI. See the
operator's manual for more information.

• From function input


• Active indications can also be acknowledged or reset from an input,
RESET, to the function. This input can, for example, be configured to a
binary input operated from an external push button. The function is
positive edge triggered, not level triggered. This means that even if the
button is continuously pressed, the acknowledgment or reset only affects
indications active at the moment when the button is first pressed.

• Automatic reset
• Automatic reset can only be performed for indications defined for re-
starting mode with the latched sequence type 6 (LatchedReset-S). When
automatic reset of the LEDs has been performed, still persisting
indications will be indicated with a steady light.

Operating sequences
The operating sequences can be of type Follow or Latched.

• For the Follow type the LED follows the input signal completely.
• For the Latched type each LED latches to the corresponding input signal until
it is reset.

56
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI

Figure 12 show the function of available sequences that are selectable for each
LED separately.

• The acknowledgment or reset function is not applicable for sequence 1 and 2


(Follow type).
• Sequence 3 and 4 (Latched type with acknowledgement) are only working in
collecting mode.
• Sequence 5 is working according to Latched type and collecting mode.
• Sequence 6 is working according to Latched type and re-starting mode.

The letters S and F in the sequence names have the meaning S = Steady and F =
Flashing.

At the activation of the input signal, the indication operates according to the
selected sequence diagrams.

In the sequence diagrams the LEDs have the characteristics as shown in figure 12.

= No indication = Steady light = Flash

en05000506.vsd
IEC05000506 V1 EN

Figure 12: Symbols used in the sequence diagrams

Sequence 1 (Follow-S)
This sequence follows all the time, with a steady light, the corresponding input
signals. It does not react on acknowledgment or reset. Every LED is independent of
the other LEDs in its operation.

Activating
signal

LED

IEC01000228_2_en.vsd
IEC01000228 V2 EN

Figure 13: Operating sequence 1 (Follow-S)

Sequence 2 (Follow-F)
This sequence is the same as sequence 1, Follow-S, but the LEDs are flashing
instead of showing steady light.

Sequence 3 (LatchedAck-F-S)
This sequence has a latched function and works in collecting mode. Every LED is
independent of the other LEDs in its operation. At the activation of the input signal,
the indication starts flashing. After acknowledgment the indication disappears if

57
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI

the signal is not present any more. If the signal is still present after
acknowledgment it gets a steady light.

Activating
signal

LED

Acknow.
en01000231.vsd
IEC01000231 V1 EN

Figure 14: Operating sequence 3 (LatchedAck-F-S)

Sequence 4 (LatchedAck-S-F)
This sequence has the same functionality as sequence 3, but steady and flashing
light have been alternated.

Sequence 5 (LatchedColl-S)
This sequence has a latched function and works in collecting mode. At the
activation of the input signal, the indication will light up with a steady light. The
difference to sequence 3 and 4 is that indications that are still activated will not be
affected by the reset that is, immediately after the positive edge of the reset has
been executed a new reading and storing of active signals is performed. Every LED
is independent of the other LEDs in its operation.

Activating
signal

LED

Reset

IEC01000235_2_en.vsd
IEC01000235 V2 EN

Figure 15: Operating sequence 5 (LatchedColl-S)

Sequence 6 (LatchedReset-S)
In this mode all activated LEDs, which are set to sequence 6 (LatchedReset-S), are
automatically reset at a new disturbance when activating any input signal for other
LEDs set to sequence 6 (LatchedReset-S). Also in this case indications that are still
activated will not be affected by manual reset, that is, immediately after the
positive edge of that the manual reset has been executed a new reading and storing

58
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI

of active signals is performed. LEDs set for sequence 6 are completely independent
in its operation of LEDs set for other sequences.

Definition of a disturbance
A disturbance is defined to last from the first LED set as LatchedReset-S is
activated until a settable time, tRestart, has elapsed after that all activating signals
for the LEDs set as LatchedReset-S have reset. However if all activating signals
have reset and some signal again becomes active before tRestart has elapsed, the
tRestart timer does not restart the timing sequence. A new disturbance start will be
issued first when all signals have reset after tRestart has elapsed. A diagram of this
functionality is shown in figure 16.

From
disturbance
length control ³1 New
per LED ³1 disturbance
set to
sequence 6
tRestart
& t

&
³1

³1
&

en01000237.vsd
IEC01000237 V1 EN

Figure 16: Activation of new disturbance

In order not to have a lock-up of the indications in the case of a persisting signal
each LED is provided with a timer, tMax, after which time the influence on the
definition of a disturbance of that specific LED is inhibited. This functionality is
shown i diagram in figure 17.

Activating signal
To LED

To disturbance
AND
tMax length control
t
en05000507.vsd
IEC05000507 V1 EN

Figure 17: Length control of activating signals

Timing diagram for sequence 6


Figure 18 shows the timing diagram for two indications within one disturbance.

59
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI

Disturbance
tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000239_2-en.vsd
IEC01000239 V2 EN

Figure 18: Operating sequence 6 (LatchedReset-S), two indications within


same disturbance

Figure 19 shows the timing diagram for a new indication after tRestart time has
elapsed.

Disturbance Disturbance

tRestart tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000240_2_en.vsd
IEC01000240 V2 EN

Figure 19: Operating sequence 6 (LatchedReset-S), two different disturbances

60
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI

Figure 20 shows the timing diagram when a new indication appears after the first
one has reset but before tRestart has elapsed.

Disturbance

tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000241_2_en.vsd
IEC01000241 V2 EN

Figure 20: Operating sequence 6 (LatchedReset-S), two indications within


same disturbance but with reset of activating signal between

Figure 21 shows the timing diagram for manual reset.

Disturbance

tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000242_2_en.vsd
IEC01000242 V2 EN

Figure 21: Operating sequence 6 (LatchedReset-S), manual reset

61
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI

3.6.4.3 Function block


LEDGEN
BLOCK NEWIND
RESET ACK
LEDTEST

IEC05000508_2_en.vsd
IEC05000508 V2 EN

Figure 22: LEDGEN function block

3.6.4.4 Input and output signals


Table 11: LEDGEN Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Input to block the operation of the LED-unit
RESET BOOLEAN 0 Input to acknowledge/reset the indications of the
LED-unit
LEDTEST BOOLEAN 0 Input for external LED test

Table 12: LEDGEN Output signals


Name Type Description
NEWIND BOOLEAN A new signal on any of the indication inputs occurs
ACK BOOLEAN A pulse is provided when the LEDs are
acknowledged

3.6.4.5 Setting parameters


Table 13: LEDGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation mode for the LED function
On
tRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance length
tMax 0.0 - 100.0 s 0.1 0.0 Maximum time for the definition of a
disturbance
SeqTypeLED1 Follow-S - - Follow-S Sequence type for LED 1
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
SeqTypeLED2 Follow-S - - Follow-S Sequence type for LED 2
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Table continues on next page

62
Technical reference manual
1MRK505183-UEN C Section 3
Local HMI

Name Values (Range) Unit Step Default Description


SeqTypeLED3 Follow-S - - Follow-S Sequence type for LED 3
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
SeqTypeLED4 Follow-S - - Follow-S Sequence type for LED 4
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
SeqTypeLED5 Follow-S - - Follow-S Sequence type for LED 5
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
SeqTypeLED6 Follow-S - - Follow-S Sequence type for LED 6
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
SeqTypeLED7 Follow-S - - Follow-S Sequence type for LED 7
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
SeqTypeLED8 Follow-S - - Follow-S sequence type for LED 8
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
SeqTypeLED9 Follow-S - - Follow-S Sequence type for LED 9
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
SeqTypeLED10 Follow-S - - Follow-S Sequence type for LED 10
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
SeqTypeLED11 Follow-S - - Follow-S Sequence type for LED 11
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Table continues on next page

63
Technical reference manual
Section 3 1MRK505183-UEN C
Local HMI

Name Values (Range) Unit Step Default Description


SeqTypeLED12 Follow-S - - Follow-S Sequence type for LED 12
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
SeqTypeLED13 Follow-S - - Follow-S Sequence type for LED 13
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
SeqTypeLED14 Follow-S - - Follow-S Sequence type for LED 14
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
SeqTypeLED15 Follow-S - - Follow-S Sequence type for LED 15
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

64
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

Section 4 Basic IED functions

About this chapter


This chapter presents functions that are basic to all 670 series IEDs. Typical
functions in this category are time synchronization, self supervision and test mode.

4.1 Authorization

To safeguard the interests of our customers, both the IED and the tools that are
accessing the IED are protected, subject of authorization handling. The concept of
authorization, as it is implemented in the IED and in PCM600 is based on the
following facts:

There are two types of access points to the IED:


• local, through the local HMI
• remote, through the communication ports

4.1.1 Principle of operation


There are different levels (or types) of users that can access or operate different
areas of the IED and tools functionality. The pre-defined user types are given in
table below.

Be sure that the user logged on to the IED has the access required
when writing particular data to the IED from PCM600.

The meaning of the legends used in the table:


• R= Read
• W= Write
• - = No access rights

65
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

Table 14: Pre-defined user types


Access rights System Protection Design User
Guest Super User SPA Guest
Operator Engineer Engineer Administrator
Basic setting possibilities (change R R/W R R/W R/W R/W R
setting group, control settings,
limit supervision)
Advanced setting possibilities (for R R/W R R R/W R/W R
example protection settings)
Basic control possibilities (process R R/W R/W R/W R/W R/W R
control, no bypass)
Advanced control possibilities R R/W R/W R/W R/W R/W R
(process control including interlock
trigg)
Basic command handling (for R R/W R R/W R/W R/W R
example clear LEDs, manual trigg)
Advanced command handling (for R R/W R R R/W R/W R/W
example clear disturbance record)
Basic configuration possibilities (I/ R R/W R R R R/W R/W
O-configuration in SMT)
Advanced configuration R R/W R R R R/W R/W
possibilities (application
configuration including SMT, GDE
and CMT)
File loading (database loading - R/W - - - R/W R/W
from XML-file)
File dumping (database dumping - R/W - - - R/W R/W
to XML-file)
File transfer (FTP file transfer) - R/W - R/W R/W R/W R/W
File transfer (limited) (FTP file R R/W R R/W R/W R/W R/W
transfer)
File Transfer (SPA File Transfer) - R/W - - - R/W -
Database access for normal user R R/W R R/W R/W R/W R/W
User administration (user R R/W R R R R R/W
management – FTP File Transfer)
User administration (user - R/W - - - - -
management – SPA File Transfer)

The IED users can be created, deleted and edited only with the User Management
Tool (UMT) within PCM600. The user can only LogOn or LogOff on the local
HMI on the IED, there are no users, groups or functions that can be defined on
local HMI.

Only characters A - Z, a - z and 0 - 9 should be used in user names


and passwords.

66
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

At least one user must be included in the UserAdministrator group


to be able to write users, created in PCM600, to IED.

4.1.1.1 Authorization handling in the IED

At delivery the default user is the SuperUser. No Log on is required to operate the
IED until a user has been created with the User Management Tool.

Once a user is created and downloaded to the IED, that user can perform a Log on,
introducing the password assigned in the tool.

If there is no user created, an attempt to log on will display a message box: “No
user defined!”

If one user leaves the IED without logging off, then after the timeout (set in Main
menu/Settings/General Settings/HMI/Screen/Display Timeout) elapses, the IED
returns to Guest state, when only reading is possible. The display time out is set to
60 minutes at delivery.

If there are one or more users created with the User Management Tool and
downloaded into the IED, then, when a user intentionally attempts a Log on or
when the user attempts to perform an operation that is password protected, the Log
on window will appear.

The cursor is focused on the User identity field, so upon pressing the “E” key, the
user can change the user name, by browsing the list of users, with the “up” and
“down” arrows. After choosing the right user name, the user must press the “E”
key again. When it comes to password, upon pressing the “E” key, the following
character will show up: “$”. The user must scroll for every letter in the password.
After all the letters are introduced (passwords are case sensitive) choose OK and
press the “E” key again.

If everything is alright at a voluntary Log on, the local HMI returns to the
Authorization screen. If the Log on is OK, when required to change for example a
password protected setting, the local HMI returns to the actual setting folder. If the
Log on has failed, then the Log on window opens again, until either the user makes
it right or presses “Cancel”.

4.2 Self supervision with internal event list

4.2.1 Introduction
Self supervision with internal event list function listens and reacts to internal
system events, generated by the different built-in self-supervision elements. The
internal events are saved in an internal event list.

67
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

4.2.2 Principle of operation


The self-supervision operates continuously and includes:

• Normal micro-processor watchdog function.


• Checking of digitized measuring signals.
• Other alarms, for example hardware and time synchronization.

The self-supervision function status can be monitored from the local HMI, from the
Event Viewer in PCM600 or from a SMS/SCS system.

Under the Diagnostics menu in the local HMI the present information from the self-
supervision function can be reviewed. The information can be found under Main
menu/Diagnostics/Internal events or Main menu/Diagnostics/IED status/
General. The information from the self-supervision function is also available in the
Event Viewer in PCM600.

A self-supervision summary can be obtained by means of the potential free alarm


contact (INTERNAL FAIL) located on the power supply module. The function of
this output relay is an OR-function between the INT-FAIL signal see figure 24 and
a couple of more severe faults that can occur in the IED, see figure 23

IEC04000520 V1 EN

Figure 23: Hardware self-supervision, potential-free alarm contact

68
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

IO fail
OR Set e.g. BIM 1 Error
IO stopped
Reset
IO started
e.g. IOM2 Error OR
e.g. IO (n) Error Internal
OR FAIL
LON ERROR

FTF fatal error


OR
Watchdog NUMFAIL
RTE fatal error
Internal
Set WARN
RTE Appl-fail
OR
RTE OK Reset

IEC61850 not ready NUMWARNING


OR
RTCERROR Set RTCERROR
RTC OK Reset

TIMESYNCHERROR
OR TIMESYNCHERROR
Time reset Set

SYNCH OK Reset
SETCHGD
Settings changed
1 second pulse

en04000519-1.vsd
IEC04000519 V2 EN

Figure 24: Software self-supervision, IES (IntErrorSign) function block

Some signals are available from the INTERRSIG function block. The signals from
this function block are sent as events to the station level of the control system. The
signals from the INTERRSIG function block can also be connected to binary
outputs for signalization via output relays or they can be used as conditions for
other functions if required/desired.

Individual error signals from I/O modules can be obtained from respective module
in the Signal Matrix tool. Error signals from time synchronization can be obtained
from the time synchronization block TIME.

4.2.2.1 Internal signals

Self supervision provides several status signals, that tells about the condition of the
IED. As they provide information about the internal status of the IED, they are also
called internal signals. The internal signals can be divided into two groups.

• Standard signals are always presented in the IED, see table 15.
• Hardware dependent internal signals are collected depending on the hardware
configuration, see table 16.

Explanations of internal signals are listed in table 17.

69
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

Table 15: Self-supervision's standard internal signals


Name of signal Description
FAIL Internal Fail status
WARNING Internal Warning status
NUMFAIL CPU module Fail status
NUMWARNING CPU module Warning status
RTCERROR Real Time Clock status
TIMESYNCHERROR Time Synchronization status
RTEERROR Runtime Execution Error status
IEC61850ERROR IEC 61850 Error status
WATCHDOG SW Watchdog Error status
LMDERROR LON/Mip Device Error status
APPERROR Runtime Application Error status
SETCHGD Settings changed
SETGRPCHGD Setting groups changed
FTFERROR Fault Tolerant Filesystem status

Table 16: Self-supervision's hardware dependent internal signals


Card Name of signal Description
PSM PSM-Error Power Supply Module Error status
ADOne ADOne-Error Analog In Module Error status
BIM BIM-Error Binary In Module Error status
BOM BOM-Error Binary Out Module Error status
IOM IOM-Error In/Out Module Error status
MIM MIM-Error Millampere Input Module Error status
LDCM LDCM-Error Line Differential Communication Error status

Table 17: Explanations of internal signals


Name of signal Reasons for activation
FAIL This signal will be active if one or more of the following internal
signals are active; NUMFAIL, LMDERROR, WATCHDOG,
APPERROR, RTEERROR, FTFERROR, or any of the HW
dependent signals
WARNING This signal will be active if one or more of the following internal
signals are active; RTCERROR, IEC61850ERROR,
TIMESYNCHERROR
NUMFAIL This signal will be active if one or more of the following internal
signals are active; WATCHDOG, APPERROR, RTEERROR,
FTFERROR
NUMWARNING This signal will be active if one or more of the following internal
signals are active; RTCERROR, IEC61850ERROR
RTCERROR This signal will be active when there is a hardware error with the
real time clock.
Table continues on next page

70
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

Name of signal Reasons for activation


TIMESYNCHERROR This signal will be active when the source of the time
synchronization is lost, or when the time system has to make a
time reset.
RTEERROR This signal will be active if the Runtime Engine failed to do some
actions with the application threads. The actions can be loading
of settings or parameters for components, changing of setting
groups, loading or unloading of application threads.
IEC61850ERROR This signal will be active if the IEC 61850 stack did not succeed
in some actions like reading IEC 61850 configuration, startup,
for example
WATCHDOG This signal will be activated when the terminal has been under
too heavy load for at least 5 minutes. The operating systems
background task is used for the measurements.
LMDERROR LON network interface, MIP/DPS, is in an unrecoverable error
state.
APPERROR This signal will be active if one or more of the application threads
are not in the state that Runtime Engine expects. The states can
be CREATED, INITIALIZED, RUNNING, for example
SETCHGD This signal will generate an Internal Event to the Internal Event
list if any settings are changed.
SETGRPCHGD This signal will generate an Internal Event to the Internal Event
list if any setting groups are changed.
FTFERROR This signal will be active if both the working file and the backup
file are corrupted and can not be recovered.

4.2.2.2 Run-time model

The analog signals to the A/D converter is internally distributed into two different
converters, one with low amplification and one with high amplification, see figure
25.

ADx
Adx_Low
x1

u1

x2

Adx
Adx_High Controller
x1

u1

x2

en05000296-2-en.vsd
IEC05000296 V2 EN

Figure 25: Simplified drawing of A/D converter for the IED.

71
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

The technique to split the analog input signal into two A/D converters with
different amplification makes it possible to supervise the incoming signals under
normal conditions where the signals from the two converters should be identical.
An alarm is given if the signals are out of the boundaries. Another benefit is that it
improves the dynamic performance of the A/D conversion.

The self-supervision of the A/D conversion is controlled by the ADx_Controller


function. One of the tasks for the controller is to perform a validation of the input
signals. This is done in a validation filter which has mainly two objects: First is the
validation part that checks that the A/D conversion seems to work as expected.
Secondly, the filter chooses which of the two signals that shall be sent to the CPU,
that is the signal that has the most suitable level, the ADx_LO or the 16 times
higherADx_HI.

When the signal is within measurable limits on both channels, a direct comparison
of the two channels can be performed. If the validation fails, the CPU will be
informed and an alarm will be given.

The ADx_Controller also supervise other parts of the A/D converter.

4.2.3 Function block

IEC09000787 V1 EN

Figure 26: INTERRSIG function block

4.2.4 Output signals


Table 18: INTERRSIG Output signals
Name Type Description
FAIL BOOLEAN Internal fail
WARNING BOOLEAN Internal warning
CPUFAIL BOOLEAN CPU fail
CPUWARN BOOLEAN CPU warning

4.2.5 Setting parameters


The function does not have any parameters available in the local HMI or PCM600.

72
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

4.2.6 Technical data


Table 19: Self supervision with internal event list
Data Value
Recording manner Continuous, event controlled
List size 1000 events, first in-first out

4.3 Time synchronization

4.3.1 Introduction
Use the time synchronization source selector to select a common source of absolute
time for the IED when it is a part of a protection system. This makes comparison of
events and disturbance data between all IEDs in a station automation system
possible. A common source shall be used for IED and merging unit when IEC
61850-9-2LE process bus communication is used.

Micro SCADA OPC server should not be used as a time


synchronization source.

4.3.2 Principle of operation

4.3.2.1 General concepts

Time definitions
The error of a clock is the difference between the actual time of the clock, and the
time the clock is intended to have. The rate accuracy of a clock is normally called
the clock accuracy and means how much the error increases, that is how much the
clock gains or loses time. A disciplined (trained) clock knows its own faults and
tries to compensate for them.

Design of the time system (clock synchronization)


The time system is based on a software clock, which can be adjusted from external
time sources and a hardware clock. The protection and control modules will be
timed from a hardware clock, which runs independently from the software clock.
See figure 27.

73
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

External
Synchronization
sources Time tagging and general synchronisation

Off
Comm- Protection
LON Events
Time- unication and control
SPA Regulator functions
Min. pulse
(Setting,
GPS see
SW-time
technical
SNTP
reference
DNP manual) Connected when GPS-time is
IRIG-B used for differential protection

PPS

Synchronization for differential protection


(ECHO-mode or GPS)
Off Time-
GPS Regulator HW-time
(fast or slow)
IRIG-B
PPS Diff.-
A/D Trans-
converter comm- ducers*
unication

*IEC 61850-9-2

IEC08000287-2-en.vsd
IEC08000287 V2 EN

Figure 27: Design of time system (clock synchronization)

All time tagging is performed by the software clock. When for example a status
signal is changed in the protection system with the function based on free running
hardware clock, the event is time tagged by the software clock when it reaches the
event recorder. Thus the hardware clock can run independently.

The echo mode for the differential protection is based on the hardware clock. Thus,
there is no need to synchronize the hardware clock and the software clock.

The synchronization of the hardware clock and the software clock is necessary only
when GPS or IRIG B 00X with optical fibre, IEEE 1344 is used for differential
protection. The two clock systems are synchronized by a special clock
synchronization unit with two modes, fast and slow. A special feature, an
automatic fast clock time regulator is used. The automatic fast mode makes the
synchronization time as short as possible during start-up or at interruptions/
disturbances in the GPS timing. The setting fast or slow is also available on the
local HMI.

If a GPS clock is used for other 670 series IEDs than line differential RED670, the
hardware and software clocks are not synchronized

74
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

Fast clock synchronization mode


At startup and after interruptions in the GPS or IRIG B time signal, the clock
deviation between the GPS time and the internal differential time system can be
substantial. A new startup is also required after for example maintenance of the
auxiliary voltage system.

When the time difference is >16us, the differential function is blocked and the time
regulator for the hardware clock is automatically using a fast mode to synchronize
the clock systems. The time adjustment is made with an exponential function, i.e.
big time adjustment steps in the beginning, then smaller steps until a time deviation
between the GPS time and the differential time system of >16us has been reached.
Then the differential function is enabled and the synchronization remains in fast
mode or switches to slow mode, depending on the setting.

Slow clock synchronization mode


During normal service, a setting with slow synchronization mode is normally used,
which prevents the hardware clock to make too big time steps, >16µs, emanating
from the differential protection requirement of correct timing.

Synchronization principle
From a general point of view synchronization can be seen as a hierarchical
structure. A function is synchronized from a higher level and provides
synchronization to lower levels.

Synchronization from
a higher level

Function

Optional synchronization of
modules at a lower level

IEC09000342-1-en.vsd
IEC09000342 V1 EN

Figure 28: Synchronization principle

A function is said to be synchronized when it periodically receives synchronization


messages from a higher level. As the level decreases, the accuracy of the
synchronization decreases as well. A function can have several potential sources of
synchronization, with different maximum errors, which give the function the
possibility to choose the source with the best quality, and to adjust its internal clock
after this source. The maximum error of a clock can be defined as:

75
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

• The maximum error of the last used synchronization message


• The time since the last used synchronization message
• The rate accuracy of the internal clock in the function.

4.3.2.2 Real-time clock (RTC) operation

The IED has a built-in real-time clock (RTC) with a resolution of one second. The
clock has a built-in calendar that handles leap years through 2038.

Real-time clock at power off


During power off, the system time in the IED is kept by a capacitor-backed real-
time clock that will provide 35 ppm accuracy for 5 days. This means that if the
power is off, the time in the IED may drift with 3 seconds per day, during 5 days,
and after this time the time will be lost completely.

Real-time clock at startup

Time synchronization startup procedure


The first message that contains the full time (as for instance LON, SNTP and GPS)
gives an accurate time to the IED. After the initial setting of the clock, one of three
things happens with each of the coming synchronization messages configured as
“fine”:

• If the synchronization message, which is similar to the other messages, has an


offset compared to the internal time in the IED, the message is used directly
for synchronization, that is, for adjusting the internal clock to obtain zero
offset at the next coming time message.
• If the synchronization message has an offset that is large compared to the other
messages, a spike-filter in the IED removes this time-message.
• If the synchronization message has an offset that is large, and the following
message also has a large offset, the spike filter does not act and the offset in
the synchronization message is compared to a threshold that defaults to 100
milliseconds. If the offset is more than the threshold, the IED is brought into a
safe state and the clock is set to the correct time. If the offset is lower than the
threshold, the clock is adjusted with 1000 ppm until the offset is removed.
With an adjustment of 1000 ppm, it takes 100 seconds or 1.7 minutes to
remove an offset of 100 milliseconds.

Synchronization messages configured as coarse are only used for initial setting of
the time. After this has been done, the messages are checked against the internal
time and only an offset of more than 10 seconds resets the time.

Rate accuracy
In the IED, the rate accuracy at cold start is 100 ppm but if the IED is synchronized
for a while, the rate accuracy is approximately 1 ppm if the surrounding
temperature is constant. Normally, it takes 20 minutes to reach full accuracy.

76
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

Time-out on synchronization sources


All synchronization interfaces has a time-out and a configured interface must
receive time-messages regularly in order not to give an error signal (TSYNCERR).
Normally, the time-out is set so that one message can be lost without getting a
TSYNCERR, but if more than one message is lost, a TSYNCERR is given.

4.3.2.3 Synchronization alternatives

Three main alternatives of external time synchronization are available. Either the
synchronization message is applied via any of the communication ports of the IED
as a telegram message including date and time or as a minute pulse, connected to a
binary input, or via GPS. The minute pulse is used to fine tune already existing
time in the IEDs.

Synchronization via SNTP


SNTP provides a ping-pong method of synchronization. A message is sent from an
IED to an SNTP server, and the SNTP server returns the message after filling in a
reception time and a transmission time. SNTP operates via the normal Ethernet
network that connects IEDs together in an IEC 61850 network. For SNTP to
operate properly, there must be an SNTP-server present, preferably in the same
station. The SNTP synchronization provides an accuracy that gives 1 ms accuracy
for binary inputs. The IED itself can be set as an SNTP-time server.

SNTP server requirements


The SNTP server to be used is connected to the local network, that is not more than
4-5 switches or routers away from the IED. The SNTP server is dedicated for its
task, or at least equipped with a real-time operating system, that is not a PC with
SNTP server software. The SNTP server should be stable, that is, either
synchronized from a stable source like GPS, or local without synchronization.
Using a local SNTP server without synchronization as primary or secondary server
in a redundant configuration is not recommended.

Synchronization via Serial Communication Module (SLM)


On the serial buses (both LON and SPA) two types of synchronization messages
are sent.

• Coarse message is sent every minute and comprises complete date and time,
that is, year, month, day, hours, minutes, seconds and milliseconds.
• Fine message is sent every second and comprises only seconds and milliseconds.

IEC60870-5-103 is not used to synchronize the IED, but instead the offset between
the local time in the IED and the time received from 103 is added to all times (in
events and so on) sent via 103. In this way the IED acts as it is synchronized from
various 103 sessions at the same time. Actually, there is a “local” time for each 103
session.

The SLM module is located on the AD conversion Module (ADM).

77
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

Synchronization via Built-in-GPS


The built in GPS clock modules receives and decodes time information from the
global positioning system. The modules are located on the GPS time
synchronization Module (GSM).

Synchronization via binary input


The IED accepts minute pulses to a binary input. These minute pulses can be
generated from, for example station master clock. If the station master clock is not
synchronized from a world wide source, time will be a relative time valid for the
substation. Both positive and negative edge on the signal can be accepted. This
signal is also considered as a fine time synchronization signal.

The minute pulse is connected to any channel on any Binary Input Module in the
IED. The electrical characteristic is thereby the same as for any other binary input.

If the objective of synchronization is to achieve a relative time within the


substation and if no station master clock with minute pulse output is available, a
simple minute pulse generator can be designed and used for synchronization of the
IEDs. The minute pulse generator can be created using the logical elements and
timers available in the IED.

The definition of a minute pulse is that it occurs one minute after the last pulse. As
only the flanks are detected, the flank of the minute pulse shall occur one minute
after the last flank.

Binary minute pulses are checked with reference to frequency.

Pulse data:

• Period time (a) should be 60 seconds.


• Pulse length (b):
• Minimum pulse length should be >50 ms.
• Maximum pulse length is optional.
• Amplitude (c) - please refer to section "Binary input module (BIM)".

Deviations in the period time larger than 50 ms will cause TSYNCERR.

78
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

en05000251.vsd
IEC05000251 V1 EN

Figure 29: Binary minute pulses

The default time-out-time for a minute pulse is two minutes, and if no valid minute
pulse is received within two minutes a SYNCERR will be given.

If contact bounces occurs, only the first pulse will be detected as a minute pulse.
The next minute pulse will be registered first 60 s - 50 ms after the last contact bounce.

If the minute pulses are perfect, for example, it is exactly 60 seconds between the
pulses, contact bounces might occur 49 ms after the actual minute pulse without
effecting the system. If contact bounces occurs more than 50 ms, for example, it is
less than 59950 ms between the two most adjacent positive (or negative) flanks, the
minute pulse will not be accepted.

Binary synchronization example


An IED is configured to use only binary input, and a valid binary input is applied
to a binary input card. The HMI is used to tell the IED the approximate time and
the minute pulse is used to synchronize the IED thereafter. The definition of a
minute pulse is that it occurs one minute after the previous minute pulse, so the
first minute pulse is not used at all. The second minute pulse will probably be
rejected due to the spike filter. The third pulse will give the IED a good time and
will reset the time so that the fourth minute pulse will occur on a minute border.
After the first three minutes, the time in the IED will be good if the coarse time is
set properly via the HMI or the RTC backup still keeps the time since last up-time.
If the minute pulse is removed for instance for an hour, the internal time will drift
by maximum the error rate in the internal clock. If the minute pulse is returned, the
first pulse automatically is rejected. The second pulse will possibly be rejected due
to the spike filter. The third pulse will either synchronize the time, if the time offset
is more than 100 ms, or adjust the time, if the time offset is small enough. If the
time is set, the application will be brought to a safe state before the time is set. If
the time is adjusted, the time will reach its destination within 1.7 minutes.

Synchronization via IRIG-B


The DNP3 communication can be the source for the course time synchronization,
while the fine time synchronization needs a source with higher accuracy.

79
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

IRIG-B is a protocol used only for time synchronization. A clock can provide local
time of the year in this format. The “B” in IRIG-B states that 100 bits per second
are transmitted, and the message is sent every second. After IRIG-B there numbers
stating if and how the signal is modulated and the information transmitted.

To receive IRIG-B there are two connectors in the IRIG-B module, one galvanic
BNC connector and one optical ST connector. IRIG-B 12x messages can be
supplied via the galvanic interface, and IRIG-B 00x messages can be supplied via
either the galvanic interface or the optical interface, where x (in 00x or 12x) means
a number in the range of 1-7.

“00” means that a base band is used, and the information can be fed into the IRIG-
B module via the BNC contact or an optical fiber. “12” means that a 1 kHz
modulation is used. In this case the information must go into the module via the
BNC connector.

If the x in 00x or 12x is 4, 5, 6 or 7, the time message from IRIG-B contains


information of the year. If x is 0, 1, 2 or 3, the information contains only the time
within the year, and year information has to come from PCM600 or local HMI.

The IRIG-B module also takes care of IEEE1344 messages that are sent by IRIG-B
clocks, as IRIG-B previously did not have any year information. IEEE1344 is
compatible with IRIG-B and contains year information and information of the time-
zone.

It is recommended to use IEEE 1344 for supplying time information to the IRIG-B
module. In this case, send also the local time in the messages, as this local time
plus the TZ Offset supplied in the message equals UTC at all times.

4.3.2.4 Process bus IEC 61850-9-2LE synchronization

For the time synchronization of the process bus communication (IEC 61850-9-2LE
protocol) an optical PPS or IRIG-B signal can be used. This signal should emanate
from either an external GPS clock, or from the merging unit.

An optical PPS signal can be supplied to the optical interface of the IRIG-B module.

4.3.3 Function block


TIMEERR
TSYNCERR
RTCERR

IEC05000425-2-en.vsd
IEC05000425 V2 EN

Figure 30: TIMEERR function block

80
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

4.3.4 Output signals


Table 20: TIMEERR Output signals
Name Type Description
TSYNCERR BOOLEAN Time synchronization error
RTCERR BOOLEAN Real time clock error

4.3.5 Setting parameters


Path in the local HMI is located under Main menu/Setting/Time

Path in PCM600 is located under Main menu/Settings/Time/Synchronization

Table 21: TIMESYNCHGEN Non group settings (basic)


Name Values (Range) Unit Step Default Description
CoarseSyncSrc Off - - Off Coarse time synchronization source
SPA
LON
SNTP
DNP
FineSyncSource Off - - Off Fine time synchronization source
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
SyncMaster Off - - Off Activate IEDas synchronization master
SNTP-Server
TimeAdjustRate Slow - - Slow Adjust rate for time synchronization
Fast

Table 22: SYNCHBIN Non group settings (basic)


Name Values (Range) Unit Step Default Description
ModulePosition 3 - 16 - 1 3 Hardware position of IO module for time
synchronization
BinaryInput 1 - 16 - 1 1 Binary input number for time
synchronization
BinDetection PositiveEdge - - PositiveEdge Positive or negative edge detection
NegativeEdge

81
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

Table 23: SYNCHSNTP Non group settings (basic)


Name Values (Range) Unit Step Default Description
ServerIP-Add 0 - 18 IP 1 0.0.0.0 Server IP-address
Address
RedServIP-Add 0 - 18 IP 1 0.0.0.0 Redundant server IP-address
Address

Table 24: DSTBEGIN Non group settings (basic)


Name Values (Range) Unit Step Default Description
MonthInYear January - - March Month in year when daylight time starts
February
March
April
May
June
July
August
September
October
November
December
DayInWeek Sunday - - Sunday Day in week when daylight time starts
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
WeekInMonth Last - - Last Week in month when daylight time starts
First
Second
Third
Fourth
UTCTimeOfDay 0 - 86400 s 1 3600 UTC Time of day in seconds when
daylight time starts

82
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

Table 25: DSTEND Non group settings (basic)


Name Values (Range) Unit Step Default Description
MonthInYear January - - October Month in year when daylight time ends
February
March
April
May
June
July
August
September
October
November
December
DayInWeek Sunday - - Sunday Day in week when daylight time ends
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
WeekInMonth Last - - Last Week in month when daylight time ends
First
Second
Third
Fourth
UTCTimeOfDay 0 - 86400 s 1 3600 UTC Time of day in seconds when
daylight time ends

Table 26: TIMEZONE Non group settings (basic)


Name Values (Range) Unit Step Default Description
NoHalfHourUTC -24 - 24 - 1 0 Number of half-hours from UTC

Table 27: SYNCHIRIG-B Non group settings (basic)


Name Values (Range) Unit Step Default Description
SynchType BNC - - Opto Type of synchronization
Opto
TimeDomain LocalTime - - LocalTime Time domain
UTC
Encoding IRIG-B - - IRIG-B Type of encoding
1344
1344TZ
TimeZoneAs1344 MinusTZ - - PlusTZ Time zone as in 1344 standard
PlusTZ

83
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

4.3.6 Technical data


Table 28: Time synchronization, time tagging
Function Value
Time tagging resolution, events and sampled measurement values 1 ms
Time tagging error with synchronization once/min (minute pulse ± 1.0 ms typically
synchronization), events and sampled measurement values
Time tagging error with SNTP synchronization, sampled ± 1.0 ms typically
measurement values

4.4 Parameter setting groups

4.4.1 Introduction
Use the six sets of settings to optimize IED operation for different system
conditions. By creating and switching between fine tuned setting sets, either from
the local HMI or configurable binary inputs, results in a highly adaptable IED that
can cope with a variety of system scenarios.

4.4.2 Principle of operation


Parameter setting groups ActiveGroup function has six functional inputs, each
corresponding to one of the setting groups stored in the IED. Activation of any of
these inputs changes the active setting group. Seven functional output signals are
available for configuration purposes, so that up to date information on the active
setting group is always available.

A setting group is selected by using the local HMI, from a front connected personal
computer, remotely from the station control or station monitoring system or by
activating the corresponding input to the ActiveGroup function block.

Each input of the function block can be configured to connect to any of the binary
inputs in the IED. To do this PCM600 must be used.

The external control signals are used for activating a suitable setting group when
adaptive functionality is necessary. Input signals that should activate setting groups
must be either permanent or a pulse exceeding 400 ms.

More than one input may be activated at the same time. In such cases the lower
order setting group has priority. This means that if for example both group four and
group two are set to activate, group two will be the one activated.

Every time the active group is changed, the output signal SETCHGD is sending a
pulse.

The parameter MAXSETGR defines the maximum number of setting groups in use
to switch between.

84
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

ACTIVATE GROUP 6
ACTIVATE GROUP 5
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
+RL2 ACTIVATE GROUP 1

IOx-Bly1 ActiveGroup
Æ ACTGRP1 GRP1
IOx-Bly2
Æ ACTGRP2 GRP2
IOx-Bly3
Æ ACTGRP3 GRP3
IOx-Bly4
Æ ACTGRP4 GRP4
IOx-Bly5
Æ ACTGRP5 GRP5
IOx-Bly6 ACTGRP6
Æ GRP6
SETCHGD

en05000119.vsd
IEC05000119 V2 EN

Figure 31: Connection of the function to external circuits

The above example also includes seven output signals, for confirmation of which
group that is active.

SETGRPS function block has an input where the number of setting groups used is
defined. Switching can only be done within that number of groups. The number of
setting groups selected to be used will be filtered so only the setting groups used
will be shown on the Parameter Setting Tool.

4.4.3 Function block


ActiveGroup
ACTGRP1 GRP1
ACTGRP2 GRP2
ACTGRP3 GRP3
ACTGRP4 GRP4
ACTGRP5 GRP5
ACTGRP6 GRP6
SETCHGD

IEC05000433_2_en.vsd
IEC05000433 V2 EN

Figure 32: ActiveGroup function block

SETGRPS
MAXSETGR

IEC05000716_2_en.vsd
IEC05000716 V2 EN

Figure 33: SETGRPS function block

85
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

4.4.4 Input and output signals


Table 29: ActiveGroup Input signals
Name Type Default Description
ACTGRP1 BOOLEAN 0 Selects setting group 1 as active
ACTGRP2 BOOLEAN 0 Selects setting group 2 as active
ACTGRP3 BOOLEAN 0 Selects setting group 3 as active
ACTGRP4 BOOLEAN 0 Selects setting group 4 as active
ACTGRP5 BOOLEAN 0 Selects setting group 5 as active
ACTGRP6 BOOLEAN 0 Selects setting group 6 as active

Table 30: ActiveGroup Output signals


Name Type Description
GRP1 BOOLEAN Setting group 1 is active
GRP2 BOOLEAN Setting group 2 is active
GRP3 BOOLEAN Setting group 3 is active
GRP4 BOOLEAN Setting group 4 is active
GRP5 BOOLEAN Setting group 5 is active
GRP6 BOOLEAN Setting group 6 is active
SETCHGD BOOLEAN Pulse when setting changed

4.4.5 Setting parameters


Table 31: ActiveGroup Non group settings (basic)
Name Values (Range) Unit Step Default Description
t 0.0 - 10.0 s 0.1 1.0 Pulse length of pulse when setting
changed

Table 32: SETGRPS Non group settings (basic)


Name Values (Range) Unit Step Default Description
ActiveSetGrp SettingGroup1 - - SettingGroup1 ActiveSettingGroup
SettingGroup2
SettingGroup3
SettingGroup4
SettingGroup5
SettingGroup6
MAXSETGR 1-6 No 1 1 Max number of setting groups 1-6

4.5 ChangeLock function CHNGLCK

86
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

4.5.1 Introduction
Change lock function (CHNGLCK) is used to block further changes to the IED
configuration and settings once the commissioning is complete. The purpose is to
block inadvertent IED configuration changes beyond a certain point in time.

4.5.2 Principle of operation


The Change lock function (CHNGLCK) is configured using ACT.

The function, when activated, will still allow the following changes of the IED
state that does not involve reconfiguring of the IED:
• Monitoring
• Reading events
• Resetting events
• Reading disturbance data
• Clear disturbances
• Reset LEDs
• Reset counters and other runtime component states
• Control operations
• Set system time
• Enter and exit from test mode
• Change of active setting group

The binary input signal LOCK controlling the function is defined in ACT or SMT:
Binary input Function
1 Activated
0 Deactivated

4.5.3 Function block


CHNGLCK
LOCK

IEC09000946-1-en.vsd
IEC09000946 V1 EN

Figure 34: CHNGLCK function block

4.5.4 Input and output signals


Table 33: CHNGLCK Input signals
Name Type Default Description
LOCK BOOLEAN 0 Parameter change lock

87
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

4.5.5 Setting parameters


Table 34: CHNGLCK Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation LockHMI and Com - - LockHMI and Com Operation mode of change lock
LockHMI,
EnableCom
EnableHMI,
LockCom

4.6 Test mode functionality TEST

4.6.1 Introduction
When the Test mode functionality TESTMODE function is activated, protection
functions in the IED are automatically blocked. It is then possible to unblock the
protection functions individually from the local HMI or the Parameter Setting tool
to perform required tests.

When leaving TESTMODE, all blockings are removed and the IED resumes
normal operation. However, if during TESTMODE operation, power is removed
and later restored, the IED will remain in TESTMODE with the same protection
functions blocked or unblocked as before the power was removed. All testing will
be done with actually set and configured values within the IED. No settings will be
changed, thus mistakes are avoided.

4.6.2 Principle of operation


Put the IED into test mode to test functions in the IED. Set the IED in test mode by

• configuration, activating the input signal of the function block TESTMODE.


• setting TestMode to On in the local HMI, under Main menu/TEST/IED test
mode.

While the IED is in test mode, the ACTIVE output of the function block
TESTMODE is activated. The other outputs of the function block TESTMODE
shows the generator of the “Test mode: On” state — input from configuration
(OUTPUT output is activated) or setting from local HMI (SETTING output is
activated).

While the IED is in test mode, the yellow START LED will flash and all functions
are blocked. Any function can be unblocked individually regarding functionality
and event signalling.

Most of the functions in the IED can individually be blocked by means of settings
from the local HMI. To enable these blockings the IED must be set in test mode
(output ACTIVE is activated), see example in figure 35. When leaving the test

88
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

mode, that is entering normal mode, these blockings are disabled and everything is
set to normal operation. All testing will be done with actually set and configured
values within the IED. No settings will be changed, thus no mistakes are possible.

The blocked functions will still be blocked next time entering the test mode, if the
blockings were not reset.

The blocking of a function concerns all output signals from the actual function, so
no outputs will be activated.

When a binary input is used to set the IED in test mode and a
parameter, that requires restart of the application, is changed, the
IED will re-enter test mode and all functions will be blocked, also
functions that were unblocked before the change. During the re-
entering to test mode, all functions will be temporarily unblocked
for a short time, which might lead to unwanted operations. This is
only valid if the IED is put in TEST mode by a binary input, not by
local HMI.

The TESTMODE function block might be used to automatically block functions


when a test handle is inserted in a test switch. A contact in the test switch (RTXP24
contact 29-30) can supply a binary input which in turn is configured to the
TESTMODE function block.

Each of the protection functions includes the blocking from the TESTMODE
function block. A typical example from the undervoltage function is shown in
figure 35.

The functions can also be blocked from sending events over IEC 61850 station bus
to prevent filling station and SCADA databases with test events, for example
during a maintenance test.

89
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

U Disconnection

Normal voltage

U1<

U2<

tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2

Time

Block step 1

Block step 2
en05000466.vsd
IEC05000466 V1 EN

Figure 35: Example of blocking the time delayed undervoltage protection


function.

4.6.3 Function block


TESTMODE
INPUT ACTIVE
OUTPUT
SETTING
NOEVENT

IEC09000219-1.vsd
IEC09000219 V1 EN

Figure 36: TESTMODE function block

4.6.4 Input and output signals


Table 35: TESTMODE Input signals
Name Type Default Description
INPUT BOOLEAN 0 Sets terminal in test mode when active

90
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

Table 36: TESTMODE Output signals


Name Type Description
ACTIVE BOOLEAN Terminal in test mode when active
OUTPUT BOOLEAN Test input is active
SETTING BOOLEAN Test mode setting is (On) or not (Off)
NOEVENT BOOLEAN Event disabled during testmode

4.6.5 Setting parameters


Table 37: TESTMODE Non group settings (basic)
Name Values (Range) Unit Step Default Description
TestMode Off - - Off Test mode in operation (On) or not (Off)
On
EventDisable Off - - Off Event disable during testmode
On
CmdTestBit Off - - Off Command bit for test required or not
On during testmode

4.7 IED identifiers

4.7.1 Introduction
IED identifiers (TERMINALID) function allows the user to identify the individual
IED in the system, not only in the substation, but in a whole region or a country.

Use only characters A-Z, a-z and 0-9 in station, object and unit names.

4.7.2 Setting parameters


Table 38: TERMINALID Non group settings (basic)
Name Values (Range) Unit Step Default Description
StationName 0 - 18 - 1 Station name Station name
StationNumber 0 - 99999 - 1 0 Station number
ObjectName 0 - 18 - 1 Object name Object name
ObjectNumber 0 - 99999 - 1 0 Object number
UnitName 0 - 18 - 1 Unit name Unit name
UnitNumber 0 - 99999 - 1 0 Unit number

91
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

4.8 Product information

4.8.1 Introduction
The Product identifiers function identifies the IED. The function has seven pre-set,
settings that are unchangeable but nevertheless very important:

• IEDProdType
• ProductDef
• FirmwareVer
• SerialNo
• OrderingNo
• ProductionDate

The settings are visible on the local HMI , under Main menu/Diagnostics/IED
status/Product identifiers

They are very helpful in case of support process (such as repair or maintenance).

4.8.2 Setting parameters


The function does not have any parameters available in the local HMI or PCM600.

4.8.3 Application

4.8.3.1 Factory defined settings

The factory defined settings are very useful for identifying a specific version and
very helpful in the case of maintenance, repair, interchanging IEDs between
different Substation Automation Systems and upgrading. The factory made settings
can not be changed by the customer. They can only be viewed. The settings are
found in the local HMI under Main menu/Diagnostics/IED status/Product
identifiers

The following identifiers are available:

• IEDProdType
• Describes the type of the IED (like REL, REC or RET). Example: REL670
• ProductDef
• Describes the release number, from the production. Example: 1.1.r01
• FirmwareVer
• Describes the firmware version. Example: 1.4.51
• Firmware versions numbers are “running” independently from the
release production numbers. For every release numbers (like 1.4.51)

92
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

there can be one or more firmware versions, depending on the small


issues corrected in between releases.
• IEDMainFunType
• Main function type code according to IEC 60870-5-103. Example: 128
(meaning line protection).
• SerialNo
• OrderingNo
• ProductionDate

4.9 Signal matrix for binary inputs SMBI

4.9.1 Introduction
The Signal matrix for binary inputs (SMBI) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT),
see the application manual to get information about how binary inputs are brought
in for one IED configuration.

4.9.2 Principle of operation


The Signal matrix for binary inputs (SMBI) function , see figure 37, receives its
inputs from the real (hardware) binary inputs via the Signal Matrix Tool (SMT),
and makes them available to the rest of the configuration via its outputs, BI1 to
BI10. The inputs and outputs, as well as the whole block, can be given a user
defined name. These names will be represented in SMT as information which
signals shall be connected between physical IO and SMBI function. The input/
output user defined name will also appear on the respective output/input signal.

4.9.3 Function block


SMBI
^VIN1 ^BI1
^VIN2 ^BI2
^VIN3 ^BI3
^VIN4 ^BI4
^VIN5 ^BI5
^VIN6 ^BI6
^VIN7 ^BI7
^VIN8 ^BI8
^VIN9 ^BI9
^VIN10 ^BI10

IEC05000434-2-en.vsd
IEC05000434 V2 EN

Figure 37: SMBI function block

93
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

4.9.4 Input and output signals


Table 39: SMBI Input signals
Name Type Default Description
VIn1 BOOLEAN 0 SMT Connect input
VIn2 BOOLEAN 0 SMT Connect input
VIn3 BOOLEAN 0 SMT Connect input
VIn4 BOOLEAN 0 SMT Connect input
VIn5 BOOLEAN 0 SMT Connect input
VIn6 BOOLEAN 0 SMT Connect input
VIn7 BOOLEAN 0 SMT Connect input
VIn8 BOOLEAN 0 SMT Connect input
VIn9 BOOLEAN 0 SMT Connect input
VIn10 BOOLEAN 0 SMT Connect input

Table 40: SMBI Output signals


Name Type Description
BI1 BOOLEAN Binary input 1
BI2 BOOLEAN Binary input 2
BI3 BOOLEAN Binary input 3
BI4 BOOLEAN Binary input 4
BI5 BOOLEAN Binary input 5
BI6 BOOLEAN Binary input 6
BI7 BOOLEAN Binary input 7
BI8 BOOLEAN Binary input 8
BI9 BOOLEAN Binary input 9
BI10 BOOLEAN Binary input 10

4.10 Signal matrix for binary outputs SMBO

4.10.1 Introduction
The Signal matrix for binary outputs (SMBO) function is used within the
Application Configuration Tool (ACT) in direct relation with the Signal Matrix
Tool (SMT), see the application manual to get information about how binary inputs
are sent from one IED configuration.

94
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

4.10.2 Principle of operation


The Signal matrix for binary outputs (SMBO) function , see figure 38, receives
logical signal from the IED configuration, which is transferring to the real
(hardware) outputs, via the Signal Matrix Tool (SMT). The inputs in SMBO are
BO1 to BO10 and they, as well as the whole function block, can be tag-named. The
name tags will appear in SMT as information which signals shall be connected
between physical IO and the SMBO.

4.10.3 Function block


SMBO
BO1 ^BO1
BO2 ^BO2
BO3 ^BO3
BO4 ^BO4
BO5 ^BO5
BO6 ^BO6
BO7 ^BO7
BO8 ^BO8
BO9 ^BO9
BO10 ^BO10

IEC05000439-2-en.vsd
IEC05000439 V2 EN

Figure 38: SMBO function block

4.10.4 Input and output signals


Table 41: SMBO Input signals
Name Type Default Description
BO1 BOOLEAN 1 Signal name for BO1 in Signal Matrix Tool
BO2 BOOLEAN 1 Signal name for BO2 in Signal Matrix Tool
BO3 BOOLEAN 1 Signal name for BO3 in Signal Matrix Tool
BO4 BOOLEAN 1 Signal name for BO4 in Signal Matrix Tool
BO5 BOOLEAN 1 Signal name for BO5 in Signal Matrix Tool
BO6 BOOLEAN 1 Signal name for BO6 in Signal Matrix Tool
BO7 BOOLEAN 1 Signal name for BO7 in Signal Matrix Tool
BO8 BOOLEAN 1 Signal name for BO8 in Signal Matrix Tool
BO9 BOOLEAN 1 Signal name for BO9 in Signal Matrix Tool
BO10 BOOLEAN 1 Signal name for BO10 in Signal Matrix Tool

4.11 Signal matrix for mA inputs SMMI

95
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

4.11.1 Introduction
The Signal matrix for mA inputs (SMMI) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT),
see the application manual to get information about how milliamp (mA) inputs are
brought in for one IED configuration.

4.11.2 Principle of operation


The Signal matrix for mA inputs (SMMI) function, see figure 39, receives its
inputs from the real (hardware) mA inputs via the Signal Matrix Tool (SMT), and
makes them available to the rest of the configuration via its analog outputs, named
AI1 to AI6. The inputs, as well as the whole block, can be tag-named. These tags
will be represented in SMT.

The outputs on SMMI are normally connected to the IEC61850 generic


communication I/O functions (MVGGIO) function for further use of the mA signals.

4.11.3 Function block


SMMI
^VIN1 AI1
^VIN2 AI2
^VIN3 AI3
^VIN4 AI4
^VIN5 AI5
^VIN6 AI6

IEC05000440-2-en.vsd
IEC05000440 V2 EN

Figure 39: SMMI function block

4.11.4 Input and output signals


Table 42: SMMI Input signals
Name Type Default Description
VIn1 REAL 0 SMT connected milliampere input
VIn2 REAL 0 SMT connected milliampere input
VIn3 REAL 0 SMT connected milliampere input
VIn4 REAL 0 SMT connected milliampere input
VIn5 REAL 0 SMT connected milliampere input
VIn6 REAL 0 SMT connected milliampere input

96
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

Table 43: SMMI Output signals


Name Type Description
AI1 REAL Analog milliampere input 1
AI2 REAL Analog milliampere input 2
AI3 REAL Analog milliampere input 3
AI4 REAL Analog milliampere input 4
AI5 REAL Analog milliampere input 5
AI6 REAL Analog milliampere input 6

4.12 Signal matrix for analog inputs SMAI

4.12.1 Introduction
Signal matrix for analog inputs function SMAI (or the pre-processing function) is
used within PCM600 in direct relation with the Signal Matrix tool or the
Application Configuration tool. Signal Matrix tool represents the way analog
inputs are brought in for one IED configuration.

4.12.2 Principle of operation


Every Signal matrix for analog inputs function (SMAI) can receive four analog
signals (three phases and one neutral value), either voltage or current, see figure 41
and figure 42. SMAI outputs give information about every aspect of the 3ph analog
signals acquired (phase angle, RMS value, frequency and frequency derivates etc. –
244 values in total). The BLOCK input will reset all outputs to 0.

The output signal AI1 to AI4 are direct output of the, in SMT, connected input to
GRPxL1, GRPxL2, GRPxL3 and GRPxN, x=1-12. AIN is always the neutral
current, calculated residual sum or the signal connected to GRPxN. Note that
function block will always calculate the residual sum of current/voltage if the input
is not connected in SMT. Applications with a few exceptions shall always be
connected to AI3P.

4.12.3 Frequency values


The frequency functions includes a functionality based on level of positive
sequence voltage, IntBlockLevel, to validate if the frequency measurement is valid
or not. If positive sequence voltage is lower than IntBlockLevel the function is
blocked. IntBlockLevel, is set in % of UBase/√3

If SMAI setting ConnectionType is Ph-Ph at least two of the inputs GRPxL1,


GRPxL2 and GRPxL3 must be connected in order to calculate positive sequence
voltage. If SMAI setting ConnectionType is Ph-N, all three inputs GRPxL1,

97
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

GRPxL2 and GRPxL3 must be connected in order to calculate positive sequence


voltage.

If only one phase-phase voltage is available and SMAI setting ConnectionType is


Ph-Ph the user is advised to connect two (not three) of the inputs GRPxL1,
GRPxL2 and GRPxL3 to the same voltage input as shown in figure 40 to make
SMAI calculating a positive sequence voltage (that is input voltage/√3).

IEC10000060-1-en.vsd
IEC10000060 V1 EN

Figure 40: Connection example

The above described scenario does not work if SMAI setting


ConnectionType is Ph-N. If only one phase-earth voltage is
available, the same type of connection can be used but the SMAI
ConnectionType setting must still be Ph-Ph and this has to be
accounted for when setting IntBlockLevel. If SMAI setting
ConnectionType is Ph-N and the same voltage is connected to all
three SMAI inputs, the positive sequence voltage will be zero and
the frequency functions will not work properly.

The outputs from the above configured SMAI block shall only be
used for Overfrequency protection (SAPTOF), Underfrequency
protection (SAPTUF) and Rate-of-change frequency protection
(SAPFRC) due to that all other information except frequency and
positive sequence voltage might be wrongly calculated.

4.12.4 Function block


SMAI1
BLOCK SPFCOUT
DFTSPFC AI3P
^GRP1L1 AI1
^GRP1L2 AI2
^GRP1L3 AI3
^GRP1N AI4
TYPE AIN

IEC05000705-2-en.vsd
IEC05000705 V2 EN

Figure 41: SMAI1 function block

98
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

SMAI2
BLOCK AI3P
^GRP2L1 AI1
^GRP2L2 AI2
^GRP2L3 AI3
^GRP2N AI4
TYPE AIN

IEC07000130-2-en.vsd
IEC07000130 V2 EN

Figure 42: SMAI2 function block

4.12.5 Input and output signals


Table 44: SMAI1 Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block group 1
DFTSPFC REAL 20.0 Number of samples per fundamental cycle used
for DFT calculation
GRP1L1 STRING - Sample input to be used for group 1 phase L1
calculations
GRP1L2 STRING - Sample input to be used for group 1 phase L2
calculations
GRP1L3 STRING - Sample input to be used for group 1 phase L3
calculations
GRP1N STRING - Sample input to be used for group 1 residual
calculations

Table 45: SMAI1 Output signals


Name Type Description
SPFCOUT REAL Number of samples per fundamental cycle from
internal DFT reference function
AI3P GROUP SIGNAL Group 1 analog input 3-phase group
AI1 GROUP SIGNAL Group 1 analog input 1
AI2 GROUP SIGNAL Group 1 analog input 2
AI3 GROUP SIGNAL Group 1 analog input 3
AI4 GROUP SIGNAL Group 1 analog input 4
AIN GROUP SIGNAL Group 1 analog input residual for disturbance
recorder

99
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

Table 46: SMAI2 Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block group 2
GRP2L1 STRING - Sample input to be used for group 2 phase L1
calculations
GRP2L2 STRING - Sample input to be used for group 2 phase L2
calculations
GRP2L3 STRING - Sample input to be used for group 2 phase L3
calculations
GRP2N STRING - Sample input to be used for group 2 residual
calculations

Table 47: SMAI2 Output signals


Name Type Description
AI3P GROUP SIGNAL Group 2 analog input 3-phase group
AI1 GROUP SIGNAL Group 2 analog input 1
AI2 GROUP SIGNAL Group 2 analog input 2
AI3 GROUP SIGNAL Group 2 analog input 3
AI4 GROUP SIGNAL Group 2 analog input 4
AIN GROUP SIGNAL Group 2 analog input residual for disturbance
recorder

4.12.6 Setting parameters

Settings DFTRefExtOut and DFTReference shall be set to default


value InternalDFTRef if no VT inputs are available. Internal
nominal frequency DFT reference is then the reference.

100
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

Table 48: SMAI1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
DFTRefExtOut InternalDFTRef - - InternalDFTRef DFT reference for external output
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref
DFTReference InternalDFTRef - - InternalDFTRef DFT reference
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref
ConnectionType Ph-N - - Ph-N Input connection type
Ph-Ph
TYPE 1-2 Ch 1 1 1=Voltage, 2=Current

Table 49: SMAI1 Non group settings (advanced)


Name Values (Range) Unit Step Default Description
Negation Off - - Off Negation
NegateN
Negate3Ph
Negate3Ph+N
MinValFreqMeas 5 - 200 % 1 10 Limit for frequency calculation in % of
UBase
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage

101
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

Table 50: SMAI2 Non group settings (basic)


Name Values (Range) Unit Step Default Description
DFTReference InternalDFTRef - - InternalDFTRef DFT reference
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref
ConnectionType Ph-N - - Ph-N Input connection type
Ph-Ph
TYPE 1-2 Ch 1 1 1=Voltage, 2=Current

Table 51: SMAI2 Non group settings (advanced)


Name Values (Range) Unit Step Default Description
Negation Off - - Off Negation
NegateN
Negate3Ph
Negate3Ph+N
MinValFreqMeas 5 - 200 % 1 10 Limit for frequency calculation in % of
UBase
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage

4.13 Summation block 3 phase 3PHSUM

4.13.1 Introduction
Summation block 3 phase function 3PHSUM is used to get the sum of two sets of
three-phase analog signals (of the same type) for those IED functions that might
need it.

4.13.2 Principle of operation


Summation block 3 phase 3PHSUM receives the three-phase signals from Signal
matrix for analog inputs function (SMAI). In the same way, the BLOCK input will
reset all the outputs of the function to 0.

102
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

4.13.3 Function block


3PHSUM
BLOCK AI3P
DFTSPFC AI1
G1AI3P* AI2
G2AI3P* AI3
AI4

IEC05000441-2-en.vsd
IEC05000441 V2 EN

Figure 43: 3PHSUM function block

4.13.4 Input and output signals


Table 52: 3PHSUM Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block
DFTSPFC REAL 0 Number of samples per fundamental cycle used
for DFT calculation
G1AI3P GROUP - Group 1 analog input 3-phase group
SIGNAL
G2AI3P GROUP - Group 2 analog input 3-phase group
SIGNAL

Table 53: 3PHSUM Output signals


Name Type Description
AI3P GROUP SIGNAL Group analog input 3-phase group
AI1 GROUP SIGNAL Group 1 analog input
AI2 GROUP SIGNAL Group 2 analog input
AI3 GROUP SIGNAL Group 3 analog input
AI4 GROUP SIGNAL Group 4 analog input

4.13.5 Setting parameters

Settings DFTRefExtOut and DFTReference shall be set to default


value InternalDFTRef if no VT inputs are available.

Table 54: 3PHSUM Non group settings (basic)


Name Values (Range) Unit Step Default Description
SummationType Group1+Group2 - - Group1+Group2 Summation type
Group1-Group2
Group2-Group1
-(Group1+Group2)
DFTReference InternalDFTRef - - InternalDFTRef DFT reference
AdDFTRefCh1
External DFT ref

103
Technical reference manual
Section 4 1MRK505183-UEN C
Basic IED functions

Table 55: 3PHSUM Non group settings (advanced)


Name Values (Range) Unit Step Default Description
FreqMeasMinVal 5 - 200 % 1 10 Amplitude limit for frequency calculation
in % of Ubase
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage

4.14 Authority status ATHSTAT

4.14.1 Introduction
Authority status (ATHSTAT) function is an indication function block for user log
on activity.

4.14.2 Principle of operation


Authority status (ATHSTAT) function informs about two events related to the IED
and the user authorization:
• the fact that at least one user has tried to log on wrongly into the IED and it
was blocked (the output USRBLKED)
• the fact that at least one user is logged on (the output LOGGEDON)

Whenever one of the two events occurs, the corresponding output (USRBLKED or
LOGGEDON) is activated. The output can for example, be connected on Event
(EVENT) function block for LON/SPA.The signals are also available on IEC
61850 station bus.

4.14.3 Function block


ATHSTAT
USRBLKED
LOGGEDON

IEC06000503-2-en.vsd
IEC06000503 V2 EN

Figure 44: ATHSTAT function block

4.14.4 Output signals


Table 56: ATHSTAT Output signals
Name Type Description
USRBLKED BOOLEAN At least one user is blocked by invalid password
LOGGEDON BOOLEAN At least one user is logged on

104
Technical reference manual
1MRK505183-UEN C Section 4
Basic IED functions

4.14.5 Setting parameters


The function does not have any parameters available in the local HMI or PCM600.

105
Technical reference manual
106
1MRK505183-UEN C Section 5
Differential protection

Section 5 Differential protection

About this chapter


This chapter describes the measuring principles, functions and parameters used in
differential protection.

5.1 Line differential protection

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number

Line differential protection, 3 CT sets, 3Id/I>


L3CPDIF 87L
2-3 line ends

SYMBOL-HH V1 EN

Line differential protection, 6 CT sets, 3Id/I>


L6CPDIF 87L
3-5 line ends

SYMBOL-HH V1 EN

Line differential protection 3 CT sets, 3Id/I>


LT3CPDIF 87LT
with in-zone transformers, 2-3 line ends

SYMBOL-HH V1 EN

Line differential protection 6 CT sets, 3Id/I>


LT6CPDIF 87LT
with in-zone transformers, 3-5 line ends

SYMBOL-HH V1 EN

Line differential logic LDLPDIF - 87L

5.1.1 Introduction

5.1.1.1 Line differential protection, 3 or 6 CT sets L3CPDIF, L6CPDIF

Line differential protection applies the Kirchhoff's law and compares the currents
entering and leaving the protected multi-terminal circuit, consisting of overhead

107
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

power lines, power transformers and cables. It offers phase-segregated true current
differential protection with high sensitivity and provides phase selection
information for single-pole tripping.

The three terminal version is used for conventional two-terminal lines with or
without 1 1/2 circuit breaker arrangement in one end, as well as three terminal lines
with single breaker arrangements at all terminals.

Protected zone

IED Comm. Channel IED

IEC05000039_2_en.vsd
IEC05000039 V2 EN

Figure 45: Example of application on a conventional two-terminal line

The six terminal versions are used for conventional two-terminal lines with 1 1/2
circuit breaker arrangements in both ends, as well as multi terminal lines with up to
five terminals.

Protected zone

IED Comm. Channel IED

Comm. Channel Comm. Channel


IED

IEC05000040_2_en.vsd
IEC05000040 V2 EN

Figure 46: Example of application on a three-terminal line with 1 1/2 breaker


arrangements

The current differential algorithm provides high sensitivity for internal faults, at the
same time as it has excellent stability for external faults. Current samples from all
CTs are exchanged between the IEDs in the line ends (master-master mode) or sent
to one IED (master-slave mode) for evaluation.

A restrained dual biased slope evaluation is made where the bias current is the
highest phase current in any line end giving a secure through fault stability even
with heavily saturated CTs. In addition to the restrained evaluation, an unrestrained
high differential current setting can be used for fast tripping of internal faults with
very high currents.

A special feature with this function is that applications with small power
transformers (rated current less than 50 % of the differential current setting)
connected as line taps (that is, as "shunt" power transformers), without
measurements of currents in the tap, can be handled. The normal load current is

108
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

here considered to be negligible, and special measures need only to be taken in the
event of a short circuit on the LV side of the transformer. In this application, the
tripping of the differential protection can be time delayed for low differential
currents to achieve coordination with down stream over current IEDs.

A line charging current compensation provides increased sensitivity of Line


differential protection.

5.1.1.2 Line differential protection 3 or 6 CT sets, with in-zone transformers


LT3CPDIF, LT6CPDIF

Two two-winding power transformers, or one three-winding power transformer,


can be included in the line differential protection zone. Both two- and three-
winding transformers are correctly represented with vector group compensations
made in the algorithm. The function includes 2nd and 5th harmonic restraint and zero-
sequence current elimination.

Protected zone

IED Comm. Channel IED

Comm. Channel Comm. Channel

IED

IEC05000042_2_en.vsd
IEC05000042 V2 EN

Figure 47: Example of application on a three-terminal line with a power


transformer in the protection zone

5.1.1.3 Analog signal transfer for line differential protection

The line differential communication can be arranged as a master-master system or


a master-slave system alternatively. In the former, current samples are exchanged
between all IEDs, and an evaluation is made in each IED. This means that a 64 kbit/
s communication channel is needed between every IED included in the same line
differential protection zone. In the latter, current samples are sent from all slave
IEDs to one master IED where the evaluation is made, and trip signals are sent to
the remote ends when needed. In this system, a 64 kbit/s communication channel is
only needed between the master, and each one of the slave IEDs.

109
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

Protected zone

IED IED

Comm.
Channels

IED IED IED

IEC0500043_2_en.vsd
IEC05000043 V2 EN

Figure 48: Five terminal lines with master-master system

Protected zone

RED RED
670 670

Comm.
Channels

RED RED RED


670 670 670

en05000044.vsd
IEC05000044 V1 EN

Figure 49: Five terminal line with master-slave system

Current samples from IEDs located geographically apart from each other, must be
time coordinated so that the current differential algorithm can be executed
correctly. In IED, it is possible to make this coordination in two different ways.
The echo method of time synchronizing is normally used whereas for applications
where transmit and receive times can differ, the optional built in GPS receivers can
be used.

The communication link is continuously monitored, and an automatic switchover


to a standby link is possible after a preset time.

5.1.2 Principle of operation

5.1.2.1 Algorithm and logic

In Line differential protection function, measured current values from local and
remote line ends are evaluated in order to distinguish between internal or external
faults, or undisturbed conditions.

The local currents are fed to the IED via the Analog Input Modules and thereafter
they pass the Analog to Digital Converter, as shown in figure 50.

110
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

Local end Remote end

Remote end IED

LDCM

Local end IED

Current
samples from
local end
Analog Input A/D
Module Converter Current
Pre-processing
samples from
Block
remote end
LDCM

Line Diffferential Function

CH1IL1RE [magnitude] Trip by unrestrained differential protection

Trip commands
CH1IL1IM Calculation of Differential ³1 TRIP
CH1IL2RE fundamental and bias currents
Start L1
CH1IL2IM frequency Magnitudes of applied to
differential differential operate / bias -, Start L2
currents Output logic: TRL1
currents (3x) and unrestrained Start L3 TRL2
Currents from
all ends as & bias current characteristics TRL3
Bias current St L1 low sens - 2nd harmonic block
phasors TRIPRES
- 5th harmonic block
St L2 low sens TRIPUNRE
CH1IL1SM St L3 low sens TRIPENHA
- Cross block logic
CH1IL2SM Calculation
CH1IL3SM of [samples] 2nd h. block
- Enhanced trip for START
CH2IL1SM instantaneous internal faults STL1
differential Harmonic STL2
Instantaneous analysis - Decreased STL3
currents
Curr. samples 5th h. block sensitivity for
differential

Information
from all ends (3x) ( 2nd and 5th)
currents external faults BLK2H
(samples) BLK2HL1
- BLK2HL2
CH1INSRE Conditional trip for BLK2HL3
CH1INSIM Calculation simultaneous external
of and internal faults BLK5H
CH1INSRE High sensitive Internal fault
negative-- BLK5HL1
CH1INSIM Two to six internal/external fault BLK5HL2
sequence contributions discriminator BLK5HL3
External fault -
differential to neg. seq. Conditional extra time
Neg. seq. current differential delay for trip signals
currents from current as INTFAULT
(1x)
all ends phasors EXTFAULT
as phasors

IEC05000294_2_en.vsd
IEC05000294 V2 EN

Figure 50: The principle for the line differential protection

The remote currents are received to the IED as samples via a communication link.
When entering the IED, they are processed in the Line Differential Communication
Module (LDCM) where they are time coordinated with the local current samples,
and interpolated in order to be comparable with the local samples.

111
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

In the Pre-Processing Block, the real and imaginary parts of the fundamental
frequency phase currents and negative sequence currents are derived. Together
with the current samples, they are then forwarded to the differential function block
where three different analyses are carried out.

The first analysis is the classical differential and bias current evaluation with the
characteristic as seen in figure 51. Line differential protection is phase segregated
where the differential current is the vectorial sum of all measured currents taken
separately for each phase. The bias current, on the other hand, is considered as the
greatest phase current in any line end and it is common for all three phases. The
two slopes (SlopeSection1, SlopeSection2) and breakpoints (EndSection1,
EndSection2) can be set in PCM600 or via the local HMI.

Current values plotted above the characteristic formed by IdMin and the dual slope
will give a start in that phase. The level IdMinHigh is a setting value that is used to
temporarily decrease the sensitivity in situations when:

• the line is energized


• when a fault is classified as external
• when a tap transformer is switched in

There is also an unrestrained high differential current setting that can be used for
fast tripping of internal faults with very high currents.

112
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

Operate current
[ in pu of IBase]
Operate
5
unconditionally

UnrestrainedLimit
4

Operate IdMinHigh
3 C
conditionally
A B

2
Section 1 Section 2 Section 3

SlopeSection3
1
IdMin
SlopeSection2 Restrain
0
0 1 2 3 4 5

EndSection1 Restrain current


EndSection2 [ in pu of IBase]

en05000300.vsd
IEC05000300 V1 EN

Figure 51: Description of the restrained-, and the unrestrained operate


characteristics

where:

slope = D Ioperate × 100%


D Irestrain
EQUATION1246 V1 EN

and where the restrained characteristic is defined


by the settings:

1. IdMin
2. EndSection1
3. EndSection2
SlopeSection2
4.
5. SlopeSection3

The second analysis is the 2nd and 5th harmonic analysis on the differential current.
Occurrence of these harmonics over a level that is set separately for each one will
block tripping action from the biased slope evaluation.

113
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

The third analysis is the negative sequence current analysis. Effectively this is a
fault discriminator that distinguishes between internal and external faults. It works
such that the phase angle of the negative sequence current from the local end is
compared with the phase angle of the sum of the negative sequence currents from
the remote ends. The characteristic for this fault discriminator is shown in
figure 52, where the directional characteristic is defined by the two setting
parameters IminNegSeq and NegSeqRoa.

90 deg
120 deg
If one or the Internal/external
other of fault boundary
currents is too
low, then no
measurement NegSeqROA
is done, and
(Relay
120 degrees
Operate
is mapped Angle)

180 deg 0 deg

IMinNegSeq

External Internal
fault fault
region region

270 deg
en05000188.vsd
IEC05000188 V1 EN

Figure 52: Operating characteristic of the internal/external fault discriminator

Reference direction of currents is considered to be towards the line. Thus, when


both currents to be compared have this direction, the phase difference between
them will ideally be zero. In the opposite case, when one current is entering and the
other is leaving the protected object, the phase difference will ideally be 180
degree. In case either the local or the sum of the remote negative sequence currents
or both is below the set level, the fault discriminator will not make any fault
classification and the value 120 degree is set. This value is then an indication that
negative sequence directional comparison has not been possible to make, and it
does not mean classification as external fault.

When a fault is classified as internal by the negative sequence fault discriminator, a


trip is issued under the condition that the dual slope restrained function has started ,
while a classification as external fault results in an increase of the restrained
characteristic trip values IdMinHigh.

114
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

With reference to figure 50, the outputs from the three analysis blocks are fed to
the output logic. Figure 53 shows a simplified block diagram of this output logic
where only trip commands and no alarm signals are shown for simplicity.

Trip unrestrained L1
TRIP
Trip unrestrained L2 OR
Trip unrestrained L3

Start L1 TRL1
AND OR
Start L2 OR AND
OR
Start L3 TRL2
AND OR
OR AND
OR
OR TRL3
AND
St L1 IdMinHigh OR AND
OR
St L2 IdMinHigh
St L3 IdMinHigh

Internal fault
AND
NegSeqDiffEn

tIdMinHigh
AND t
External fault
OR
Line energizing

Diff curr L1 2nd harm AND


OR OR
Diff curr L2 2nd harm
Diff curr L3 2nd harm AND
OR OR
Diff curr L1 5th harm
th
Diff curr L2 5 harm AND
OR OR
Diff curr L3 5th harm

OR
AND

CrossBlockEn

IEC05000295-2-en.vsd
IEC05000295 V2 EN

Figure 53: Simplified block diagram

Remembering that current values plotted above the characteristic formed by IdMin
and the dual slope in figure 52 are said to give a start, the output logic can be
summarized as follows:

• A start in one phase, gives a trip under the condition that the content of 2nd and
5th harmonic is below the set level for these harmonics. Otherwise it is blocked
115
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

as long as the harmonic is above the set level. However, when a line is
energized the current setting value IdMinHigh is used. Effectively this means
that the line A-B-C in figure 51 forms the characteristic.
• Current values above the unrestrained limit gives a trip irrespective of any
presence of harmonics.
• Classification of a fault as internal by the negative sequence fault
discriminator, will give a trip under the condition that a start has occurred in
that phase. This means that any harmonic blocking is then overridden.
However, occurrence of harmonics at the same time as the differential current
is below the level IdMinHigh, will block a trip even though the fault is
classified as internal. This latter condition is to prevent unwanted trips when
energizing a line tap transformer.
• Classification of a fault as external by the negative sequence fault
discriminator will cause IdMinHigh to be used as the lower limit for the
restrained characteristic according to figure 51. Cross blocking will also be
activated in this situation.

Compensation for charging currents can be selected active or not by setting


ChargCurEnableYes or No. The compensation works such that the fundamental
frequency differential current that is measured under steady state undisturbed
conditions, is identified and then subtracted making the resulting differential
current zero (or close to zero). This action is made separately for each phase. The
magnitude of the subtracted pre-fault currents in Amperes can be read at any time
as the service value ICHARGE.

Values of the pre-fault differential currents are not updated under disturbance
conditions. The updating process is resumed 50 ms after normal conditions have
been restored. Normal conditions are only considered if there are no start signals,
neither internal nor external fault is declared, the power system is symmetrical and
so on.

It is thus obvious that the change in charging current that the fault causes by
decreasing the system voltage is not considered in the algorithm, a matter that is
further discussed in the application manual.

Note that all small pre-fault differential currents are subtracted, no matter what
their origin. Besides the true charging currents, the following currents are eliminated:

• Small differential currents due to small errors (inequalities) of current


transformers.
• Small differential currents because of off-nominal load tap changer positions
when a power transformer is included in the protected zone.
• Load currents of tap loads included in the protected zone.

5.1.2.2 Time synchronization

In a numerical line differential protection, current samples from protections located


geographically apart from each other, must be time coordinated so that the currents

116
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

from the different line ends can be compared without introducing irrelevant errors.
Accuracy requirements on this time coordination are extremely high.

As an example, an inaccuracy of 0.1 ms in a 50 Hz system gives a maximum


amplitude error approximately around 3% whilst an inaccuracy of 1 ms gives a
maximum amplitude error of approximately 31%. The corresponding figures for a
60 Hz system are 4% and 38% respectively.

In Line differential protection, the time coordination is made with the so-called
echo method, which can be complemented with GPS synchronization as an option.

Each IED has an accurate local clock with a very small time drift. This clock
makes time tagging of telegrams, and the echo method is then used to find out the
time difference between the clocks in two ends of a power line.

Referring to figure 54, it works such that the transmission time to send a message
from station B to station A (T1 → T2) and receive a message from A to B (T3 →
T4) is measured. The time instances T2 and T3 are taken with the local clock
reference of station A, and the time instances T1 and T4 are taken with the local
clock reference of station B.

T2 T3
A

B
T1 T4
en05000293.vsd
IEC05000293 V1 EN

Figure 54: Measuring time differences

Calculation of the delay time one-way Td and the time difference Δt between the
clocks in A and B is then possible to do with equation 2 and equation 3, which are
only valid under the condition that the send and receive times are equal.

(T2 - T1 ) + (T4 - T3 )
Td =
2
EQUATION1358 V1 EN (Equation 2)

(T1 + T4 ) - (T2 + T3 )
Dt =
2
EQUATION1359 V1 EN (Equation 3)

Δt is calculated every time a telegram is received, and the time difference is then
used to adjust and interpolate the current measurements from the remote end before
the current differential algorithm is executed.

117
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

The echo method without GPS, can be used in telecommunications transmission


networks with varying signal propagation delay as long as there is delay symmetry,
that is, the send and receive delays are equal. The delay variation can depend on
the signal going different routes in the network from time to other.

When the delay symmetry is lost, the expression for Δt given above is no longer
valid, and GPS synchronization of the local IED clocks must be used.

Including the optional GPS, means that there will be one GPS receiver module in
each IED, synchronizing its local IED clock. As GPS synchronization is very
accurate, in the order of 1 μs, all IEDs in the same line differential scheme will
have the same clock reference. It is then possible to detect asymmetric transmission
time delay and compensate for it.

When the IED is equipped with GPS, this hardware is integrated in the IED.
Besides the GPS receiver itself, it also consists of filters and regulators for post
processing of the GPS time synch pulse, which is necessary to achieve a reliable
GPS synchronization. Especially short interruptions and spurious out of synch GPS
signals are handled securely in this way.

When GPS synchronization is used, an interruption in the GPS signal leads to


freewheeling during 8 seconds that is, during this time the synchronization benefits
from the stability in the local clocks. If the interruption persists more than 8
seconds, either fall back to the echo synchronization method or blocking of Line
differential protection function is made, as selected through setting parameter
GPSSyncErr.

For a description of the time synchronization function, refer to section "Time


synchronization".

5.1.2.3 Analog signal communication for line differential protection

Communication principle
For a two-terminal line, the current from the local CT needs to be communicated
over a 64 kbit/s channel to the remote line end, and the remote end current
communicated back on the same channel. If there is, for example, a three terminal
line another 64 kbit/s channel will be needed to exchange the same local current
with the third line end current.

In one-and-a-half breaker arrangements, there are two local currents meaning two
64 kbit/s channels to each remote substation. Alternatively, it is possible to add
together the two local currents before sending them and in that way reduce the
number of communication channels needed. This is achieved by selecting proper
setting for parameter TransmCurr (CT-SUM, CT-DIFF1 or CT-DIFF2). However,
information about bias currents is reduced if the alternative option is followed. For
further information and discussions on this matter, refer to the Application manual.

The communication can be arranged as a master-master system or a master-slave


system alternatively. Figure 55 shows a master-master system for a five-terminal
line. Here current samples are exchanged between all IEDs, and an evaluation is

118
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

made in each IED. This means that a 64 kbit/s communication channel is needed
between every IED included in the same line differential protection zone.

Protected zone

IED IED

Comm. Channels

IED IED IED

IEC05000292_2_en.vsd
IEC05000292 V2 EN

Figure 55: 5–terminal line with master-master system

In the master-slave system, current samples are sent from all slave IEDs to one
master IED where the evaluation is made and trip signals are sent to the remote
ends when needed. In this system, a 64 kbit/s communication channel is only
needed between the master, and each one of the slave IEDs, as shown in figure 56.

Protected zone

IED IED

Comm. Channels

IED IED IED

IEC05000291_2_en.vsd
IEC05000291 V2 EN

Figure 56: 5–terminal line with master-slave system

The master-slave configuration is achieved by setting parameter Operation in the


slaves to Off for Line differential protection function, and setting parameter
ChannelMode to On for the LDCMs in the slaves.

Test mode
Line differential protection function in one IED can be set in test mode. This can
block the trip outputs on that IED, and set the remote IEDs in a remote test mode,
so that injected currents can be echoed back phase shifted and with a settable
amplitude. The trip outputs in the remote IEDs can also be blocked automatically.
For further information, refer to the installation and commissioning manual.

Communication of current sampled values


The currents are sampled twenty times per power system cycle in the protection
terminals, but the communication exchange is made only once every 5 ms. This

119
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

means that at in each telegram sent, 5 consecutive current samples in a 50 Hz


system and 6 consecutive current samples in a 60 Hz system (three phases each
sampling instant) are included. Figure 57 shows the principle.

Current Current Current Current Current Current Current Current


sample sample sample sample sample sample sample sample
telegram telegram telegram telegram telegram telegram telegram telegram
sent sent sent sent sent sent sent sent

Time
0 5 10 15 20 25 30 35 (ms)

en05000290.vsd
IEC05000290 V1 EN

Figure 57: Communication of current sampled values.

where:
x is the current sampling moment

Redundant communication channels


With redundant communication channels, as shown in figure 58, both channels are
in operation continuously but with one of them favoured as a primary channel.

Telecom. Network
LD LD
CM CM
LD LD
CM CM
Telecom. Network

Primary
channel
Secondary redundant
channel en05000289.vsd
IEC05000289 V1 EN

Figure 58: Direct fibre optical connection between two IEDs with LDOM over
longer distances.

If communication is lost on the primary channel, switchover to the secondary


channel is made after a settable time delay RedChSwTime. Return of the primary
channel will cause a switchback after another settable time delay RedChRturnTime.

For a three-, four- or five-terminals line in a master-master configuration, a loss of


one communication channel will not cause the line differential protection to be

120
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

unserviceable. Instead it will automatically revert to a partial master-slave mode


with the two IEDs that have an unserviceable communication link between them,
will serve as slaves.

For more details about the remote communication see section "Remote
communication" and the application manual.

5.1.2.4 Open CT detection feature

Line differential protection has a built-in, advanced open CT detection feature.

The open CT circuit condition creates unexpected operations for Line differential
protection under the normal load conditions. It is also possible to damage
secondary equipment due to high voltage produced from open CT circuit outputs.
Therefore, it is always a requirement from security and reliability points of view to
have open CT detection function to block Line differential protection function in
case of open CT conditions and at the same time, produce the alarm signal to the
operational personal to make quick remedy actions to correct the open CT condition.

The built-in open CT feature can be enabled or disabled by a setting parameter


OpenCTEnable (Off/On). When enabled, this feature prevents mal-operation when
a loaded main CT connected to Line differential protection is by mistake open
circuited on the secondary side. Note that this feature can only detect interruption
of one CT phase current at the time. If two or even all three-phase currents of one
set of CT are accidentally interrupted at the same time this feature cannot operate
and Line differential protection generates trip signal, if the false differential current
is sufficiently high. To ensure blocking of the differential protection for open CT
condition this algorithm must operate within 10 ms in order to be able to prevent
unwanted operation of Line differential protection under all loading conditions.

The principle applied to detect an open CT is a simple pattern recognition method,


similar to the waveform check which has been with advantage used by the Power
Transformer Differential Protection in order to detect the magnetizing inrush
condition. The open CT detection principle is based on the fact, that for an open
CT, the current in the phase with the open CT suddenly drops (at least
theoretically) to zero (that is, as seen by the protection), while the currents of the
other two phases continue as before.

The open CT function is supposed to detect an open CT under normal conditions,


that is, with the protected multi-terminal circuit under normal load. If the load
currents are very low or zero, the open CT condition cannot be detected. The open
CT algorithm only detects an open CT if the load on the power transformer is from
10% to 110% of the rated load. Outside this range an open CT condition is not
even looked for. The search for an open CT starts after 60 seconds (50 seconds in
60 Hz systems) since the bias current enters the 10–110% range. The Open CT
detection feature can also be explicitly deactivated by setting: OpenCTEnable = 0
(Off).

If an open CT is detected and the output OPENCT set to 1, then all the differential
functions are blocked, except of the unrestrained (instantaneous) differential. An

121
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

alarm signal is also produced after a settable delay (tOCTAlarmDelay) to report to


operational personal for quick remedy actions once the open CT is detected. When
the open CT condition is removed (that is, the previously open CT reconnected),
the functions remain blocked for a specified interval of time, which is also a setting
(tOCTResetDelay). The task of this measure is to prevent an eventual mal-
operation after the reconnection of the previously open CT secondary circuit.

The open CT feature works only during normal loading condition. Thus, the open
CT feature must be automatically disabled for all external faults, big overloads and
inrush conditions.

The open CT algorithm provides detailed information about the location of the
defective CT secondary circuit. The algorithm clearly indicates IED side, CT input
and phase in which open CT condition has been detected. These indications are
provided via the following outputs from Line differential protection function:

1. Output OPENCT provides instant information to indicate that open CT circuit


has been detected
2. Output OPENCTAL provides time delayed alarm that the open CT circuit has
been detected. Time delay is defined by setting parameter tOCTAlarmDelay.
3. Integer output OPENCTIN provides information on the local HMI regarding
which open CT circuit has been detected (1=CT input No 1; 2=CT input No 2)
4. Integer output OPENCTPH provides information on the local HMI regarding
in which phase open CT circuit has been detected (1=Phase L1; 2= Phase L2;
3= Phase L3)

Once the open CT condition is declared, the algorithm stops to search for further
open CT circuits. It waits until the first open CT circuit has been corrected. Note
that once the open CT condition has been detected, it can be automatically reset
within the differential function. It is not possible to externally reset open CT
condition. To reset the open CT circuit alarm automatically, the following
conditions must be fulfilled:

• Bias current is for at least one minute smaller than 110%


• Open CT condition in defective CT circuit has been rectified (for example,
current asymmetry disappears)
• Above two conditions are fulfilled for longer time than defined by the setting
parameter tOCTResetDelay

After the reset, the open CT detection algorithm starts again to search for any other
open CT circuit within the protected zone.

5.1.2.5 Binary signal transfer

There is space for eight binary signals integrated in the telegram of the line
differential analog communication. For further information, refer to section
"Binary signal transfer".

122
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

5.1.2.6 Line differential coordination function LDLPDIF

Line differential coordination function (LDLPDIF) is a support function to Line


differential protection functions L3CPDIF, L6CPDIF , LT3CPDIF and LT6CPDIF.
The function gathers and coordinates local IED signals and the signals from remote
IEDs between the Line differential protection functions and the LDCM
communication module.

The function acts as the interface to and from Line differential protection.

5.1.3 Function block


L3CPDIF
I3P1* TRIP
I3P2* TRL1
I3P3* TRL2
TRL3
TRIPRES
TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG

IEC06000252-2-en.vsd
IEC06000252 V2 EN

Figure 59: L3CPDIF function block

123
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

L6CPDIF
I3P1* TRIP
I3P2* TRL1
I3P3* TRL2
I3P4* TRL3
I3P5* TRIPRES
I3P6* TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG

IEC06000253-2-en.vsd
IEC06000253 V2 EN

Figure 60: L6CPDIF function block

LT3CPDIF
I3P1* TRIP
I3P2* TRL1
I3P3* TRL2
TRL3
TRIPRES
TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG

IEC06000254_2_en.vsd
IEC06000254 V2 EN

Figure 61: LT3CPDIF function block

124
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

LT6CPDIF
I3P1* TRIP
I3P2* TRL1
I3P3* TRL2
I3P4* TRL3
I3P5* TRIPRES
I3P6* TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG

IEC06000255_2_en.vsd
IEC06000255 V2 EN

Figure 62: LT6CPDIF function block

LDLPDIF
CTFAIL TRIP
OUTSERV TRL1
BLOCK TRL2
TRL3
TRLOCAL
TRLOCL1
TRLOCL2
TRLOCL3
TRREMOTE
DIFLBLKD

IEC05000394-2-en.vsd
IEC05000394 V3 EN

Figure 63: LDLPDIF function block

5.1.4 Input and output signals


Table 57: L3CPDIF Input signals
Name Type Default Description
I3P1 GROUP - Three phase current grp1 samples and DFT values
SIGNAL
I3P2 GROUP - Three phase current grp1 samples and DFT values
SIGNAL
I3P3 GROUP - Three phase current grp1 samples and DFT values
SIGNAL

125
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

Table 58: L3CPDIF Output signals


Name Type Description
TRIP BOOLEAN Common, main, trip output signal
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
TRIPRES BOOLEAN Trip by restrained differential protection
TRIPUNRE BOOLEAN Trip by unrestrained differential protection
TRIPENHA BOOLEAN Trip by enhanced restrained differential protection
START BOOLEAN Common, main, start output signal
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
BLK2H BOOLEAN Common block signal, due to 2nd harmonic
BLK2HL1 BOOLEAN Block signal due to 2nd harmonic, phase L1
BLK2HL2 BOOLEAN Block signal due to 2nd harmonic, phase L2
BLK2HL3 BOOLEAN Block signal due to 2nd harmonic, phase L3
BLK5H BOOLEAN Common block signal, due to 5-th harmonic
BLK5HL1 BOOLEAN Block signal due to 5th harmonic, phase L1
BLK5HL2 BOOLEAN Block signal due to 5th harmonic, phase L2
BLK5HL3 BOOLEAN Block signal due to 5th harmonic, phase L3
OPENCT BOOLEAN An open CT was detected
ALARM BOOLEAN Alarm for sustained differential current
OPENCTAL BOOLEAN Open CT Alarm output signal. Issued after a
delay ...
IDL1 REAL Instantaneous differential current, phase L1
IDL2 REAL Instantaneous differential current, phase L2
IDL3 REAL Instantaneous differential current, phase L3
IDL1MAG REAL Magnitude of fund. freq. differential current,
phase L1
IDL2MAG REAL Magnitude of fund. freq. differential current,
phase L2
IDL3MAG REAL Magnitude of fund. freq. differential current,
phase L3
IBIAS REAL Magnitude of the bias current, common for L1,
L2, L3
IDNSMAG REAL Magnitude of the negative sequence differential
current

126
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

Table 59: L6CPDIF Input signals


Name Type Default Description
I3P1 GROUP - Three phase current grp1 samples and DFT values
SIGNAL
I3P2 GROUP - Three phase current grp1 samples and DFT values
SIGNAL
I3P3 GROUP - Three phase current grp1 samples and DFT values
SIGNAL
I3P4 GROUP - Three phase current grp1 samples and DFT values
SIGNAL
I3P5 GROUP - Three phase current grp1 samples and DFT values
SIGNAL
I3P6 GROUP - Three phase current grp1 samples and DFT values
SIGNAL

Table 60: L6CPDIF Output signals


Name Type Description
TRIP BOOLEAN Common, main, trip output signal
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
TRIPRES BOOLEAN Trip by restrained differential protection
TRIPUNRE BOOLEAN Trip by unrestrained differential protection
TRIPENHA BOOLEAN Trip by enhanced restrained differential protection
START BOOLEAN Common, main, start output signal
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
BLK2H BOOLEAN Common block signal, due to 2nd harmonic
BLK2HL1 BOOLEAN Block signal due to 2nd harmonic, phase L1
BLK2HL2 BOOLEAN Block signal due to 2nd harmonic, phase L2
BLK2HL3 BOOLEAN Block signal due to 2nd harmonic, phase L3
BLK5H BOOLEAN Common block signal, due to 5-th harmonic
BLK5HL1 BOOLEAN Block signal due to 5th harmonic, phase L1
BLK5HL2 BOOLEAN Block signal due to 5th harmonic, phase L2
BLK5HL3 BOOLEAN Block signal due to 5th harmonic, phase L3
OPENCT BOOLEAN An open CT was detected
ALARM BOOLEAN Alarm for sustained differential current
OPENCTAL BOOLEAN Open CT Alarm output signal. Issued after a
delay ...
IDL1 REAL Instantaneous differential current, phase L1
IDL2 REAL Instantaneous differential current, phase L2
Table continues on next page

127
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

Name Type Description


IDL3 REAL Instantaneous differential current, phase L3
IDL1MAG REAL Magnitude of fund. freq. differential current,
phase L1
IDL2MAG REAL Magnitude of fund. freq. differential current,
phase L2
IDL3MAG REAL Magnitude of fund. freq. differential current,
phase L3
IBIAS REAL Magnitude of the bias current, common for L1,
L2, L3
IDNSMAG REAL Magnitude of the negative sequence differential
current

Table 61: LT3CPDIF Input signals


Name Type Default Description
I3P1 GROUP - Three phase current grp1 samples and DFT values
SIGNAL
I3P2 GROUP - Three phase current grp1 samples and DFT values
SIGNAL
I3P3 GROUP - Three phase current grp1 samples and DFT values
SIGNAL

Table 62: LT3CPDIF Output signals


Name Type Description
TRIP BOOLEAN Common, main, trip output signal
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
TRIPRES BOOLEAN Trip by restrained differential protection
TRIPUNRE BOOLEAN Trip by unrestrained differential protection
TRIPENHA BOOLEAN Trip by enhanced restrained differential protection
START BOOLEAN Common, main, start output signal
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
BLK2H BOOLEAN Common block signal, due to 2nd harmonic
BLK2HL1 BOOLEAN Block signal due to 2nd harmonic, phase L1
BLK2HL2 BOOLEAN Block signal due to 2nd harmonic, phase L2
BLK2HL3 BOOLEAN Block signal due to 2nd harmonic, phase L3
BLK5H BOOLEAN Common block signal, due to 5-th harmonic
BLK5HL1 BOOLEAN Block signal due to 5th harmonic, phase L1
BLK5HL2 BOOLEAN Block signal due to 5th harmonic, phase L2
Table continues on next page

128
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

Name Type Description


BLK5HL3 BOOLEAN Block signal due to 5th harmonic, phase L3
OPENCT BOOLEAN An open CT was detected
ALARM BOOLEAN Alarm for sustained differential current
OPENCTAL BOOLEAN Open CT Alarm output signal. Issued after a
delay ...
IDL1 REAL Instantaneous differential current, phase L1
IDL2 REAL Instantaneous differential current, phase L2
IDL3 REAL Instantaneous differential current, phase L3
IDL1MAG REAL Magnitude of fund. freq. differential current,
phase L1
IDL2MAG REAL Magnitude of fund. freq. differential current,
phase L2
IDL3MAG REAL Magnitude of fund. freq. differential current,
phase L3
IBIAS REAL Magnitude of the bias current, common for L1,
L2, L3
IDNSMAG REAL Magnitude of the negative sequence differential
current

Table 63: LT6CPDIF Input signals


Name Type Default Description
I3P1 GROUP - Three phase current grp1 samples and DFT values
SIGNAL
I3P2 GROUP - Three phase current grp2 samples and DFT values
SIGNAL
I3P3 GROUP - Three phase current grp3 samples and DFT values
SIGNAL
I3P4 GROUP - Three phase current grp4 samples and DFT values
SIGNAL
I3P5 GROUP - Three phase current grp5 samples and DFT values
SIGNAL
I3P6 GROUP - Three phase current grp6 samples and DFT values
SIGNAL

Table 64: LT6CPDIF Output signals


Name Type Description
TRIP BOOLEAN Common, main, trip output signal
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
TRIPRES BOOLEAN Trip by restrained differential protection
TRIPUNRE BOOLEAN Trip by unrestrained differential protection
TRIPENHA BOOLEAN Trip by enhanced restrained differential protection
Table continues on next page

129
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

Name Type Description


START BOOLEAN Common, main, start output signal
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
BLK2H BOOLEAN Common block signal, due to 2nd harmonic
BLK2HL1 BOOLEAN Block signal due to 2nd harmonic, phase L1
BLK2HL2 BOOLEAN Block signal due to 2nd harmonic, phase L2
BLK2HL3 BOOLEAN Block signal due to 2nd harmonic, phase L3
BLK5H BOOLEAN Common block signal, due to 5-th harmonic
BLK5HL1 BOOLEAN Block signal due to 5th harmonic, phase L1
BLK5HL2 BOOLEAN Block signal due to 5th harmonic, phase L2
BLK5HL3 BOOLEAN Block signal due to 5th harmonic, phase L3
OPENCT BOOLEAN An open CT was detected
ALARM BOOLEAN Alarm for sustained differential current
OPENCTAL BOOLEAN Open CT Alarm output signal. Issued after a
delay ...
IDL1 REAL Instantaneous differential current, phase L1
IDL2 REAL Instantaneous differential current, phase L2
IDL3 REAL Instantaneous differential current, phase L3
IDL1MAG REAL Magnitude of fund. freq. differential current,
phase L1
IDL2MAG REAL Magnitude of fund. freq. differential current,
phase L2
IDL3MAG REAL Magnitude of fund. freq. differential current,
phase L3
IBIAS REAL Magnitude of the bias current, common for L1,
L2, L3
IDNSMAG REAL Magnitude of the negative sequence differential
current

Table 65: LDLPDIF Input signals


Name Type Default Description
CTFAIL BOOLEAN 0 CT failure indication from local CT supervision
OUTSERV BOOLEAN 0 Input for indicating that the terminal is out of service
BLOCK BOOLEAN 0 Block of function

Table 66: LDLPDIF Output signals


Name Type Description
TRIP BOOLEAN General trip from differential protection system
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
Table continues on next page

130
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

Name Type Description


TRL3 BOOLEAN Trip signal from phase L3
TRLOCAL BOOLEAN Trip from local differential function
TRLOCL1 BOOLEAN Trip from local differential function in phase L1
TRLOCL2 BOOLEAN Trip from local differential function in phase L2
TRLOCL3 BOOLEAN Trip from local differential function in phase L3
TRREMOTE BOOLEAN Trip from remote differential function
DIFLBLKD BOOLEAN Local line differential function blocked

5.1.5 Setting parameters


Table 67: L3CPDIF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IdMin 0.20 - 2.00 IB 0.01 0.30 Oper - restr charact., section 1
sensitivity, multiple IBase
IdMinHigh 0.20 - 10.00 IB 0.01 0.80 Initial lower sensitivity, as multiple of
IBase
tIdMinHigh 0.000 - 60.000 s 0.001 1.000 Time interval of initial lower sensitivity, in
sec
IdUnre 1.00 - 50.00 IB 0.01 10.00 Unrestrained differential current limit,
multiple of IBase
NegSeqDiffEn Off - - On Off/On selection for internal / external
On fault discriminator
NegSeqROA 30.0 - 120.0 Deg 1.0 60.0 Internal/external fault discriminator
Operate Angle, degrees
IMinNegSeq 0.01 - 0.20 IB 0.01 0.04 Min. value of neg. seq. curr. as multiple
of IBase
CrossBlockEn No - - No Off/On selection of the cross -block logic
Yes
ChargCurEnable Off - - Off Off/On selection for compensation of
On charging currents
AddDelay Off - - Off Off/On selection for delayed diff. trip
On command
IMaxAddDelay 0.20 - 5.00 IB 0.01 1.00 Below limit, extra delay can be applied,
multiple of IBase
tDefTime 0.000 - 6.000 s 0.001 0.000 Definite time additional delay in seconds
tMinInv 0.001 - 6.000 s 0.001 0.010 Inverse Delay Minimum Time. In seconds
Table continues on next page

131
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

Name Values (Range) Unit Step Default Description


CurveType ANSI Ext. inv. - - IEC Def. Time 19 curve types. Example: 15 for definite
ANSI Very inv. time delay.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
k 0.05 - 1.10 - 0.01 1.00 Time Multiplier Setting (TMS) for inverse
delays
IdiffAlarm 0.05 - 1.00 IB 0.01 0.15 Sustained differential current alarm,
factor of IBase
tAlarmdelay 0.000 - 60.000 s 0.001 10.000 Delay for alarm due to sustained
differential current, in s

Table 68: L3CPDIF Group settings (advanced)


Name Values (Range) Unit Step Default Description
EndSection1 0.20 - 1.50 IB 0.01 1.25 End of section 1, as multiple of reference
current IBase
EndSection2 1.00 - 10.00 IB 0.01 3.00 End of section 2, as multiple of reference
current IBase
SlopeSection2 10.0 - 50.0 % 0.1 40.0 Slope in section 2 of operate-restrain
characteristic, in %
SlopeSection3 30.0 - 100.0 % 0.1 80.0 Slope in section 3 of operate- restrain
characteristic, in %
I2/I1Ratio 5.0 - 100.0 % 1.0 10.0 Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio 5.0 - 100.0 % 1.0 25.0 Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
p 0.01 - 1000.00 - 0.01 0.02 Settable curve parameter, user-
programmable curve type.
a 0.01 - 1000.00 - 0.01 0.14 Settable curve parameter, user-
programmable curve type.
b 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
c 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
OpenCTEnable Off - - On Open CTEnable Off/On
On
tOCTAlarmDelay 0.100 - 10.000 s 0.001 1.000 Open CT: time in s to alarm after an
open CT is detected
tOCTResetDelay 0.100 - 10.000 s 0.001 0.250 Reset delay in s. After delay, diff.
function is activated

132
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

Table 69: L3CPDIF Non group settings (basic)


Name Values (Range) Unit Step Default Description
NoOfTerminals 2 - - 2 Number of current terminals of the
3 protected circuit
Chan2IsLocal No - - No 2-nd local current connected to input
Yes channel 2, Yes/ No
IBase 50.0 - 9999.9 A 0.1 3000.0 Base (reference) current of the
differential protection

Table 70: L6CPDIF Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IdMin 0.20 - 2.00 IB 0.01 0.30 Oper - restr charact., section 1
sensitivity, multiple IBase
IdMinHigh 0.20 - 10.00 IB 0.01 0.80 Initial lower sensitivity, as multiple of
IBase
tIdMinHigh 0.000 - 60.000 s 0.001 1.000 Time interval of initial lower sensitivity, in
sec
IdUnre 1.00 - 50.00 IB 0.01 10.00 Unrestrained differential current limit,
multiple of IBase
NegSeqDiffEn Off - - On Off/On selection for internal / external
On fault discriminator
NegSeqROA 30.0 - 120.0 Deg 1.0 60.0 Internal/external fault discriminator
Operate Angle, degrees
IMinNegSeq 0.01 - 0.20 IB 0.01 0.04 Min. value of neg. seq. curr. as multiple
of IBase
CrossBlockEn No - - No Off/On selection of the cross -block logic
Yes
I2/I1Ratio 5.0 - 100.0 % 1.0 10.0 Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio 5.0 - 100.0 % 1.0 25.0 Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
ChargCurEnable Off - - Off Off/On selection for compensation of
On charging currents
AddDelay Off - - Off Off/On selection for delayed diff. trip
On command
IMaxAddDelay 0.20 - 5.00 IB 0.01 1.00 Below limit, extra delay can be applied,
multiple of IBase
tDefTime 0.000 - 6.000 s 0.001 0.000 Definite time additional delay in seconds
tMinInv 0.001 - 6.000 s 0.001 0.010 Inverse Delay Minimum Time. In seconds
Table continues on next page

133
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

Name Values (Range) Unit Step Default Description


CurveType ANSI Ext. inv. - - IEC Def. Time 19 curve types. Example: 15 for definite
ANSI Very inv. time delay.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
k 0.05 - 1.10 - 0.01 1.00 Time Multiplier Setting (TMS) for inverse
delays
IdiffAlarm 0.05 - 1.00 IB 0.01 0.15 Sustained differential current alarm,
factor of IBase
tAlarmdelay 0.000 - 60.000 s 0.001 10.000 Delay for alarm due to sustained
differential current, in s

Table 71: L6CPDIF Group settings (advanced)


Name Values (Range) Unit Step Default Description
EndSection1 0.20 - 1.50 IB 0.01 1.25 End of section 1, as multiple of reference
current IBase
EndSection2 1.00 - 10.00 IB 0.01 3.00 End of section 2, as multiple of reference
current IBase
SlopeSection2 10.0 - 50.0 % 0.1 40.0 Slope in section 2 of operate-restrain
characteristic, in %
SlopeSection3 30.0 - 100.0 % 0.1 80.0 Slope in section 3 of operate- restrain
characteristic, in %
p 0.01 - 1000.00 - 0.01 0.02 Settable curve parameter, user-
programmable curve type.
a 0.01 - 1000.00 - 0.01 0.14 Settable curve parameter, user-
programmable curve type.
b 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
c 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
OpenCTEnable Off - - On Open CT detection feature. Open
On CTEnable Off/On
tOCTAlarmDelay 0.100 - 10.000 s 0.001 1.000 Open CT: time in s to alarm after an
open CT is detected
tOCTResetDelay 0.100 - 10.000 s 0.001 0.250 Reset delay in s. After delay, diff.
function is activated

134
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

Table 72: L6CPDIF Non group settings (basic)


Name Values (Range) Unit Step Default Description
NoOfTerminals 2 - - 2 Number of current terminals of the
3 protected circuit
4
5
6
Chan2IsLocal No - - No 2-nd local current connected to input
Yes channel 2, Yes/ No
IBase 50.0 - 9999.9 A 0.1 3000.0 Base (reference) current of the
differential protection

Table 73: LT3CPDIF Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IdMin 0.20 - 2.00 IB 0.01 0.30 Oper - restr charact., section 1
sensitivity, multiple IBase
IdMinHigh 0.20 - 10.00 IB 0.01 0.80 Initial lower sensitivity, as multiple of
IBase
tIdMinHigh 0.000 - 60.000 s 0.001 1.000 Time interval of initial lower sensitivity, in
sec
IdUnre 1.00 - 50.00 IB 0.01 10.00 Unrestrained differential current limit,
multiple of IBase
NegSeqDiffEn Off - - On Off/On selection for internal / external
On fault discriminator
NegSeqROA 30.0 - 120.0 Deg 1.0 60.0 Internal/external fault discriminator
Operate Angle, degrees
IMinNegSeq 0.01 - 0.20 IB 0.01 0.04 Min. value of neg. seq. curr. as multiple
of IBase
CrossBlockEn No - - No Off/On selection of the cross -block logic
Yes
ChargCurEnable Off - - Off Off/On selection for compensation of
On charging currents
AddDelay Off - - Off Off/On selection for delayed diff. trip
On command
IMaxAddDelay 0.20 - 5.00 IB 0.01 1.00 Below limit, extra delay can be applied,
multiple of IBase
tDefTime 0.000 - 6.000 s 0.001 0.000 Definite time additional delay in seconds
tMinInv 0.001 - 6.000 s 0.001 0.010 Inverse Delay Minimum Time. In seconds
Table continues on next page

135
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

Name Values (Range) Unit Step Default Description


CurveType ANSI Ext. inv. - - IEC Def. Time 19 curve types. Example: 15 for definite
ANSI Very inv. time delay.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
k 0.05 - 1.10 - 0.01 1.00 Time Multiplier Setting (TMS) for inverse
delays
IdiffAlarm 0.05 - 1.00 IB 0.01 0.15 Sustained differential current alarm,
factor of IBase
tAlarmdelay 0.000 - 60.000 s 0.001 10.000 Delay for alarm due to sustained
differential current, in s

Table 74: LT3CPDIF Group settings (advanced)


Name Values (Range) Unit Step Default Description
EndSection1 0.20 - 1.50 IB 0.01 1.25 End of section 1, as multiple of reference
current IBase
EndSection2 1.00 - 10.00 IB 0.01 3.00 End of section 2, as multiple of reference
current IBase
SlopeSection2 10.0 - 50.0 % 0.1 40.0 Slope in section 2 of operate-restrain
characteristic, in %
SlopeSection3 30.0 - 100.0 % 0.1 80.0 Slope in section 3 of operate- restrain
characteristic, in %
I2/I1Ratio 5.0 - 100.0 % 1.0 10.0 Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio 5.0 - 100.0 % 1.0 25.0 Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
p 0.01 - 1000.00 - 0.01 0.02 Settable curve parameter, user-
programmable curve type.
a 0.01 - 1000.00 - 0.01 0.14 Settable curve parameter, user-
programmable curve type.
b 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
c 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
OpenCTEnable Off - - On Open CT detection feature. Open
On CTEnable Off/On
tOCTAlarmDelay 0.100 - 10.000 s 0.001 1.000 Open CT: time in s to alarm after an
open CT is detected
tOCTResetDelay 0.100 - 10.000 s 0.001 0.250 Reset delay in s. After delay, diff.
function is activated

136
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

Table 75: LT3CPDIF Non group settings (basic)


Name Values (Range) Unit Step Default Description
NoOfTerminals 2 - - 2 Number of current terminals of the
3 protected circuit
Chan2IsLocal No - - No 2-nd local current connected to input
Yes channel 2, Yes/ No
IBase 50.0 - 9999.9 A 0.1 3000.0 Base (reference) current of the
differential protection
ZerSeqCurSubtr Off - - Off Off/On for elimination of zero seq. from
On diff. and bias curr
TraAOnInpCh No Transf A - - No Transf A Power transformer A applied on input
1 channel X
2
3
RatVoltW1TraA 1.0 - 9999.9 kV 0.1 130.0 Transformer A rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraA 1.0 - 9999.9 kV 0.1 130.0 Transformer A rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransA 0 [0 deg] - - 0 [0 deg] Transf. A phase shift in multiples of 30
1 [30 deg lag] deg, 5 for 150 deg
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
ZerSeqPassTraA No - - No Yes/No for capability of transf A to
Yes transform zero seq curr
TraBOnInpCh No Transf B - - No Transf B Power transformer B applied on input
1 channel X
2
3
RatVoltW1TraB 1.0 - 9999.9 kV 0.1 130.0 Transformer B rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraB 1.0 - 9999.9 kV 0.1 130.0 Transformer B rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransB 0 [0 deg] - - 0 [0 deg] Transf. B phase shift in multiples of 30
1 [30 deg lag] deg, 2 for 60 deg
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
ZerSeqPassTraB No - - No Yes/No for capability of transf B to
Yes transform zero seq curr

137
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

Table 76: LT6CPDIF Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IdMin 0.20 - 2.00 IB 0.01 0.30 Oper - restr charact., section 1
sensitivity, multiple IBase
IdMinHigh 0.20 - 10.00 IB 0.01 0.80 Initial lower sensitivity, as multiple of
IBase
tIdMinHigh 0.000 - 60.000 s 0.001 1.000 Time interval of initial lower sensitivity, in
sec
IdUnre 1.00 - 50.00 IB 0.01 10.00 Unrestrained differential current limit,
multiple of IBase
NegSeqDiffEn Off - - On Off/On selection for internal / external
On fault discriminator
NegSeqROA 30.0 - 120.0 Deg 1.0 60.0 Internal/external fault discriminator
Operate Angle, degrees
IMinNegSeq 0.01 - 0.20 IB 0.01 0.04 Min. value of neg. seq. curr. as multiple
of IBase
CrossBlockEn No - - No Off/On selection of the cross -block logic
Yes
I2/I1Ratio 5.0 - 100.0 % 1.0 10.0 Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio 5.0 - 100.0 % 1.0 25.0 Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
ChargCurEnable Off - - Off Off/On selection for compensation of
On charging currents
AddDelay Off - - Off On/Off selection for delayed diff. trip
On command
IMaxAddDelay 0.20 - 5.00 IB 0.01 1.00 Below limit, extra delay can be applied,
multiple of IBase
tDefTime 0.000 - 6.000 s 0.001 0.000 Definite time additional delay in seconds
tMinInv 0.001 - 6.000 s 0.001 0.010 Inverse Delay Minimum Time. In seconds
CurveType ANSI Ext. inv. - - IEC Def. Time 19 curve types. Example: 15 for definite
ANSI Very inv. time delay.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
Table continues on next page

138
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

Name Values (Range) Unit Step Default Description


k 0.05 - 1.10 - 0.01 1.00 Time Multiplier Setting (TMS) for inverse
delays
IdiffAlarm 0.05 - 1.00 IB 0.01 0.15 Sustained differential current alarm,
factor of IBase
tAlarmdelay 0.000 - 60.000 s 0.001 10.000 Delay for alarm due to sustained
differential current, in s

Table 77: LT6CPDIF Group settings (advanced)


Name Values (Range) Unit Step Default Description
EndSection1 0.20 - 1.50 IB 0.01 1.25 End of section 1, as multiple of reference
current IBase
EndSection2 1.00 - 10.00 IB 0.01 3.00 End of section 2, as multiple of reference
current IBase
SlopeSection2 10.0 - 50.0 % 0.1 40.0 Slope in section 2 of operate-restrain
characteristic, in %
SlopeSection3 30.0 - 100.0 % 0.1 80.0 Slope in section 3 of operate- restrain
characteristic, in %
p 0.01 - 1000.00 - 0.01 0.02 Settable curve parameter, user-
programmable curve type.
a 0.01 - 1000.00 - 0.01 0.14 Settable curve parameter, user-
programmable curve type.
b 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
c 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
OpenCTEnable Off - - On Open CTEnable Off/On
On
tOCTAlarmDelay 0.100 - 10.000 s 0.001 1.000 Open CT: time in s to alarm after an
open CT is detected
tOCTResetDelay 0.100 - 10.000 s 0.001 0.250 Reset delay in s. After delay, diff.
function is activated

Table 78: LT6CPDIF Non group settings (basic)


Name Values (Range) Unit Step Default Description
NoOfTerminals 2 - - 2 Number of current terminals of the
3 protected circuit
4
5
6
Chan2IsLocal No - - No 2-nd local current connected to input
Yes channel 2, Yes/ No
IBase 50.0 - 9999.9 A 0.1 3000.0 Base (reference) current of the
differential protection
ZerSeqCurSubtr Off - - Off Off/On for elimination of zero seq. from
On diff. and bias curr
Table continues on next page

139
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

Name Values (Range) Unit Step Default Description


TraAOnInpCh No Transf A - - No Transf A Power transformer A applied on input
1 channel X
2
3
4
5
6
RatVoltW1TraA 1.0 - 9999.9 kV 0.1 130.0 Transformer A rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraA 1.0 - 9999.9 kV 0.1 130.0 Transformer A rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransA 0 [0 deg] - - 0 [0 deg] Transf. A phase shift in multiples of 30
1 [30 deg lag] deg, 5 for 150 deg
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
ZerSeqPassTraA No - - No Yes/No for capability of transf A to
Yes transform zero seq curr
TraBOnInpCh No Transf B - - No Transf B Power transformer B applied on input
1 channel X
2
3
4
5
6
RatVoltW1TraB 1.0 - 9999.9 kV 0.1 130.0 Transformer B rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraB 1.0 - 9999.9 kV 0.1 130.0 Transformer B rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransB 0 [0 deg] - - 0 [0 deg] Transf. B phase shift in multiples of 30
1 [30 deg lag] deg, 2 for 60 deg
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
ZerSeqPassTraB No - - No Yes/No for capability of transf B to
Yes transform zero seq curr

140
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

Table 79: LDLPDIF Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
testModeSet Off - - Off Test mode On/Off
On
ReleaseLocal Block all - - Block all Release of local terminal for trip under
Release local test mode

5.1.6 Technical data


Table 80: L3CPDIF, L6CPDIF, LT3CPDIF, LT6CPDIF technical data
Function Range or value Accuracy
Minimum operate current (20-200)% of IBase ± 2.0% of Ir at I £ Ir
± 2.0% of I at I >I r

SlopeSection2 (10.0-50.0)% -
SlopeSection3 (30.0-100.0)% -
EndSection 1 (20–150)% of IBase -
EndSection 2 (100–1000)% of IBase -
Unrestrained limit function (100–5000)% of IBase ± 2.0% of Ir at I ≤ Ir
± 2.0% of I at I > Ir

Second harmonic blocking (5.0–100.0)% of fundamental ± 2.0% of Ir

Fifth harmonic blocking (5.0–100.0)% of fundamental ± 6.0% of Ir

Inverse characteristics, see table 19 curve types See table 644 and
644, 645 and table 646 table 645
Operate time 25 ms typically at 0 to 10 x Id -

Reset time 15 ms typically at 10 to 0 x Id -

Critical impulse time 2 ms typically at 0 to 10 x Id -

Charging current compensation On/Off -

5.2 1Ph High impedance differential protection HZPDIF

IEC 61850 IEC 60617 ANSI/IEEE C37.2


Function description
identification identification device number

1Ph High impedance differential Id


HZPDIF 87
protection

SYMBOL-CC V2 EN

141
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

5.2.1 Introduction
The 1Ph High impedance differential protection HZPDIF function can be used
when the involved CT cores have the same turn ratio and similar magnetizing
characteristic. It utilizes an external summation of the phases and neutral current
and a series resistor and a voltage dependent resistor externally to the IED.

5.2.2 Principle of operation


The 1Ph High impedance differential protection (HZPDIF) function is based on
one current input with external stabilizing resistors and voltage dependent resistors.
Three functions can be used to provide a three phase differential protection
function. The stabilizing resistor value is calculated from the IED operating value
UR calculated to achieve through fault stability. The supplied stabilizing resistor
has a link to allow setting of the correct resistance value.

See the application manual for operating voltage and sensitivity calculation.

5.2.2.1 Logic diagram

The logic diagram shows the operation principles for the 1Ph High impedance
differential protection function HZPDIF, see figure 64. It is a simple one step IED
with an additional lower alarm level. By activating inputs, the HZPDIF function
can either be blocked completely, or only the trip output.

IEC05000301 V1 EN

Figure 64: Logic diagram for 1Ph High impedance differential protection
HZPDIF

142
Technical reference manual
1MRK505183-UEN C Section 5
Differential protection

5.2.3 Function block


HZPDIF
ISI* TRIP
BLOCK ALARM
BLKTR MEASVOLT

IEC05000363-2-en.vsd
IEC05000363 V2 EN

Figure 65: HZPDIF function block

5.2.4 Input and output signals


Table 81: HZPDIF Input signals
Name Type Default Description
ISI GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip

Table 82: HZPDIF Output signals


Name Type Description
TRIP BOOLEAN Trip signal
ALARM BOOLEAN Alarm signal
MEASVOLT REAL Measured RMS voltage on CT secondary side

5.2.5 Setting parameters


Table 83: HZPDIF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
U>Alarm 2 - 500 V 1 10 Alarm voltage level in volts on CT
secondary side
tAlarm 0.000 - 60.000 s 0.001 5.000 Time delay to activate alarm
U>Trip 5 - 900 V 1 100 Operate voltage level in volts on CT
secondary side
SeriesResistor 10 - 20000 ohm 1 250 Value of series resistor in Ohms

143
Technical reference manual
Section 5 1MRK505183-UEN C
Differential protection

5.2.6 Technical data


Table 84: HZPDIFtechnical data
Function Range or value Accuracy
Operate voltage (20-400) V ± 1.0% of Ur for U < Ur
± 1.0% of U for U > Ur

Reset ratio >95% -


Maximum U>Trip2/series resistor ≤200 W -
continuous voltage
Operate time 10 ms typically at 0 to 10 x Ud -

Reset time 90 ms typically at 10 to 0 x Ud -

Critical impulse time 2 ms typically at 0 to 10 x Ud -

144
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Section 6 Impedance protection

About this chapter


This chapter describes distance protection and associated functions. It includes
function blocks, logic diagrams and data tables with information about distance
protection, automatic switch onto fault, weak end in-feed and other associated
functions. Quadrilateral characteristics are also covered.

6.1 Distance measuring zones, quadrilateral


characteristic ZMQPDIS, ZMQAPDIS, ZDRDIR

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Distance protection zone, quadrilateral ZMQPDIS 21
characteristic (zone 1)

S00346 V1 EN

Distance protection zone, quadrilateral ZMQAPDIS 21


characteristic (zone 2-5)

S00346 V1 EN

Directional impedance quadrilateral ZDRDIR 21D

Z<->

IEC09000167 V1 EN

6.1.1 Introduction
The line distance protection is a, up to four zone full scheme protection with three
fault loops for phase-to-phase faults and three fault loops for phase-to-earth fault
for each of the independent zones. Individual settings for each zone in resistive and
reactive reach gives flexibility for use as back-up protection for transformer
connected to overhead lines and cables of different types and lengths.

ZMQPDIS together with Phase selection with load encroachment FDPSPDIS has
functionality for load encroachment, which increases the possibility to detect high
resistive faults on heavily loaded lines, as shown in figure66.

145
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Forward
operation

Reverse
operation

en05000034.vsd
IEC05000034 V1 EN

Figure 66: Typical quadrilateral distance protection zone with Phase selection
with load encroachment function FDPSPDIS activated

The independent measurement of impedance for each fault loop together with a
sensitive and reliable built-in phase selection makes the function suitable in
applications with single-phase autoreclosing.

Built-in adaptive load compensation algorithm prevents overreaching of zone 1 at


load exporting end at phase-to-earth faults on heavily loaded power lines.

The distance protection zones can operate independently of each other in


directional (forward or reverse) or non-directional mode. This makes them suitable,
together with different communication schemes, for the protection of power lines
and cables in complex network configurations, such as parallel lines, multi-
terminal lines, and so on.

6.1.2 Principle of operation

6.1.2.1 Full scheme measurement

The execution of the different fault loops within the IED are of full scheme type,
which means that each fault loop for phase-to-earth faults and phase-to-phase faults
for forward and reverse faults are executed in parallel.

Figure 67 presents an outline of the different measuring loops for up to five,


impedance-measuring zones. There are 3 to 5 zones depending on product type and
variant.

146
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 1

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 2

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 3

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 4

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 5

en05000458.vsd
IEC05000458 V1 EN

Figure 67: The different measuring loops at phase-to-earth fault and phase-to-
phase fault.

The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a start element to select correct voltages and current
depending on fault type. Each distance protection zone performs like one
independent distance protection IED with six measuring elements.

6.1.2.2 Impedance characteristic

The distance measuring zone includes six impedance measuring loops; three
intended for phase-to-earth faults, and three intended for phase-to-phase as well as,
three-phase faults.

The distance measuring zone will essentially operate according to the non-
directional impedance characteristics presented in figure 68 and figure 69. The phase-
to-earth characteristic is illustrated with the full loop reach while the phase-to-
phase characteristic presents the per phase reach.

147
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

X (Ohm/loop)

R1PE+Rn

RFPE RFPE

X0PE-X1PE
Xn =
3
X1PE+Xn R0PE-R1PE
Rn =
3
jN jN
R (Ohm/loop)

RFPE RFPE

X1PE+Xn

RFPE RFPE
en08000280-2-en.vsd

R1PE+Rn
IEC08000280 V1 EN

Figure 68: Characteristic for phase-to-earth measuring, ohm/loop domain

148
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

X (Ohm/phase)

RFPP R1PP RFPP


2 2
X 0 PE - X 1RVPE
XNRV =XX00PEPG- -X31XRVPE
1RVPG
XNRV =
XNRV =
33
XX00 PE-
X 0 PG X
PE --1X 11FWPE
XFWPE
FWPG
XNFW===
XNFW
XNFW
X1PP 3 33

j j
R (Ohm/phase)

RFPP RFPP
2 2

X1PP

RFPP R1PP RFPP


2 2
en07000062.vsd
IEC07000062 V2 EN

Figure 69: Characteristic for phase-to-phase measuring

The fault loop reach with respect to each fault type may also be presented as in
figure 70. Note in particular the difference in definition regarding the (fault)
resistive reach for phase-to-phase faults and three-phase faults.

149
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

IL1 R1 + j X1
Phase-to-earth
UL1
element

Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)

0
IN (R0-R1)/3 +
j (X0-X1)/3 )

IL1 R1 + j X1 Phase-to-phase
UL1 element L1-L2
Phase-to-phase
fault in phase RFPP
L1-L2 IL2
UL2 (Arc resistance)
R1 + j X1

IL1 R1 + j X1 0.5·RFPP Phase-to-phase


UL1 element L1-L3
Three-phase
fault
IL3
UL3
R1 + j X1 0.5·RFPP
IEC08000282-2-en.vsd
IEC08000282 V2 EN

Figure 70: Fault loop model

The R1 and jX1 in figure 70 represents the positive sequence impedance from the
measuring point to the fault location. The settings RFPE and RFPP are the
eventual fault resistances in the faulty place.

Regarding the illustration of three-phase fault in figure 70, there is of course fault
current flowing also in the third phase during a three-phase fault. The illustration
merely reflects the loop measurement, which is made phase-to-phase.

The zone can be set to operate in Non-directional, Forward or Reverse direction


through the setting OperationDir. The result from respective set value is illustrated
in figure 71. The impedance reach is symmetric, in the sense that it conforms for
forward and reverse direction. Therefore, all reach settings apply to both directions.

150
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

X X X

R R R

Non-directional Forward Reverse

en05000182.vsd
IEC05000182 V1 EN

Figure 71: Directional operating modes of the distance measuring zones

6.1.2.3 Minimum operating current

The operation of Distance measuring zones, quadrilateral characteristic


(ZMQPDIS) is blocked if the magnitude of input currents fall below certain
threshold values.

The phase-to-earth loop Ln is blocked if ILn < IMinOpPE.

For zone 1 with load compensation feature the additional criterion applies, that all
phase-to-earth loops will be blocked when IN < IMinOpIN, regardless of the phase
currents.

ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector
sum of the three-phase currents, that is, residual current 3I0.

The phase-to-phase loop LmLn is blocked if ILmLn < IMinOpPP.

ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.

All three current limits IMinOpPE, IMinOpIN and IMinOpPP are


automatically reduced to 75% of regular set values if the zone is set
to operate in reverse direction, that is, OperationDir = Reverse.

6.1.2.4 Measuring principles

Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits. The

151
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

apparent impedances at phase-to-phase faults follow equation 4 (example for a


phase L1 to phase L2 fault).

UL1 – UL2
Zapp = -------------------------
I L1 – IL2
EQUATION1222 V1 EN (Equation 4)

Here U and I represent the corresponding voltage and current phasors in the
respective phase Ln (n = 1, 2, 3)

The earth return compensation applies in a conventional manner to phase-to-earth


faults (example for a phase L1 to earth fault) according to equation 5.

U L1
Z app = ------------------------------
I L1 + I N × KN
EQUATION1223 V1 EN (Equation 5)

Where:
UL1, IL1 and IN are the phase voltage, phase current and residual current present to the IED

KN is defined as:

Z0 - Z1
KN =
3 × Z1
EQUATION 2105 V1 EN

Z 0 = R0 + jX 0
EQUATION2106 V1 EN

Z1 = R1 + jX 1
EQUATION2107 V1 EN

Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach

Here IN is a phasor of the residual current in IED point. This results in the same
reach along the line for all types of faults.

The apparent impedance is considered as an impedance loop with resistance R and


reactance X.

152
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

The formula given in equation 5 is only valid for radial feeder application without
load. When load is considered in the case of single phase-to-earth fault,
conventional distance protection might overreach at exporting end and underreach
at importing end. The IED has an adaptive load compensation which increases the
security in such applications.

Measuring elements receive current and voltage information from the A/D
converter. The check sums are calculated and compared, and the information is
distributed into memory locations. For each of the six supervised fault loops,
sampled values of voltage (U), current (I), and changes in current between samples
(DI) are brought from the input memory and fed to a recursive Fourier filter.

The filter provides two orthogonal values for each input. These values are related
to the loop impedance according to equation 6,

X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN (Equation 6)

in complex notation, or:

X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt

EQUATION354 V1 EN (Equation 7)

X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt

EQUATION355 V1 EN (Equation 8)

with

w0 = 2 × p × f 0
EQUATION356 V1 EN (Equation 9)

where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency

The algorithm calculates Rmmeasured resistance from the equation for the real
value of the voltage and substitutes it in the equation for the imaginary part. The
equation for the Xm measured reactance can then be solved. The final result is
equal to:

153
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN (Equation 10)

Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN (Equation 11)

The calculated Rm and Xm values are updated each sample and compared with the
set zone reach. The adaptive tripping counter counts the number of permissive
tripping results. This effectively removes any influence of errors introduced by the
capacitive voltage transformers or by other factors.

The directional evaluations are performed simultaneously in both forward and


reverse directions, and in all six fault loops. Positive sequence voltage and a phase
locked positive sequence memory voltage are used as a reference. This ensures
unlimited directional sensitivity for faults close to the IED point.

6.1.2.5 Directional impedance element for quadrilateral characteristics

The evaluation of the directionality takes place in Directional impedance


quadrilateral function ZDRDIR. Equation 12 and equation 13 are used to classify
that the fault is in forward direction for phase-to-earth fault and phase-to-phase fault.

0.8 × U 1L1 + 0.2 × U 1L1 M


- ArgDir < arg < ArgNeg Re s
I L1
EQUATION725 V2 EN (Equation 12)

For the L1-L2 element, the equation in forward direction is according to.

0.8 × U 1L1 L 2 + 0.2 × U 1L1 L 2 M


- ArgDir < arg < ArgNeg Re s
I L1 L 2
EQUATION726 V2 EN (Equation 13)

where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default
set to 15 (= -15 degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default
set to 115 degrees, see figure 72.
U1L1 is positive sequence phase voltage in phase L1

U1L1M is positive sequence memorized phase voltage in phase L1

IL1 is phase current in phase L1

U1L1L2 is voltage difference between phase L1 and L2 (L2 lagging L1)

U1L1L2M is memorized voltage difference between phase L1 and L2 (L2 lagging L1)

IL1L2 is current difference between phase L1 and L2 (L2 lagging L1)

154
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115
degrees respectively (as shown in figure 72). It should not be changed unless
system studies have shown the necessity.

ZDRDIR gives binary coded directional information per measuring loop on the
output STDIRCND.

STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048

ArgNegRes

ArgDir
R

en05000722.vsd
IEC05000722 V1 EN

Figure 72: Setting angles for discrimination of forward and reverse fault in
Directional impedance quadrilateral function ZDRDIR

The reverse directional characteristic is equal to the forward characteristic rotated


by 180 degrees.

The polarizing voltage is available as long as the positive sequence voltage exceeds
5% of the set base voltage UBase. So the directional element can use it for all
unsymmetrical faults including close-in faults.

For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.

The memory voltage is used for 100 ms or until the positive sequence voltage is
restored.

After 100ms the following occurs:

155
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

• If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set IED rated current IBase), the condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.
• If the current decreases below the minimum operating value, the memory
resets until the positive sequence voltage exceeds 10% of its rated value.

6.1.2.6 Simplified logic diagrams

Distance protection zones


The design of the distance protection zones are presented for all measuring loops:
phase-to-earth as well as phase-to-phase.

Phase-to-earth related signals are designated by L1N, L2N and L3N. The phase-to-
phase signals are designated by L1L2, L2L3, and L3L1.

Fulfillment of two different measuring conditions is necessary to obtain the one


logical signal for each separate measuring loop:

• Zone measuring condition, which follows the operating equations described


above.
• Group functional input signal (STCND), as presented in figure 73.

Two types of function block, ZMQPDIS and ZMQAPDIS, are used in the IED.
ZMQPDIS is used for zone 1 and ZMQAPDIS for zone 2 - 5.

The STCND input signal represents a connection of six different integer values
from Phase selection with load encroachment, quadrilateral characteristic function
FDPSPDIS within the IED, which are converted within the zone measuring
function into corresponding boolean expressions for each condition separately.
Input signal STCND is connected to FDPSPDIS function output STCNDZ.

The input signal DIRCND is used to give condition for directionality for the
distance measuring zones. The signal contains binary coded information for both
forward and reverse direction. The zone measurement function filters out the
relevant signals depending on the setting of the parameter OperationDir. It must be
configured to the STDIR output on ZDRDIR function.

156
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

IEC99000557-TIFF V1 EN

Figure 73: Conditioning by a group functional input signal STCND, external


start condition

Composition of the phase start signals for a case, when the zone operates in a non-
directional mode, is presented in figure 74.

STNDL1N
OR
STNDL2N
AND STL1
STNDL3N
STNDL1L2 OR STL2
AND
STNDL2L3
STNDL3L1 AND STL3
OR

AND START
OR

BLK

en00000488.vsd
IEC00000488 V1 EN

Figure 74: Composition of starting signals in non-directional operating mode

157
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Results of the directional measurement enter the logic circuits, when the zone
operates in directional (forward or reverse) mode, as shown in figure 75.

STNDL1N
AND
DIRL1N STZMPE
OR
STNDL2N
DIRL2N AND

STNDL3N OR STL1
DIRL3N AND AND

STNDL1L2
DIRL1L2 AND OR STL2
AND
STNDL2L3
DIRL2L3 AND
OR STL3
STNDL3L1 AND
DIRL3L1 AND

STZMPP
OR

BLK

15 ms
OR START
AND t

en05000778.vsd
IEC05000778 V2 EN

Figure 75: Composition of start signals in directional operating mode

Tripping conditions for the distance protection zone one are symbolically presented
in figure 76.

158
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Timer tPP=On tPP


AND t
STZMPP
OR
Timer tPE=On tPE
AND t
STZMPE
15ms
BLKTR AND t
TRIP
BLK OR

STL1 AND TRL1

STL2 AND TRL2

STL3 AND TRL3

en00000490-3.vsd
IEC00000490 2 V1 EN

Figure 76: Tripping logic for the distance protection zone

6.1.3 Function block


ZMQPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC06000256-2-en.vsd
IEC06000256 V2 EN

Figure 77: ZMQPDIS function block

ZMQAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC09000884-1-en.vsd
IEC09000884 V1 EN

Figure 78: ZMQAPDIS function block (zone 2 - 5)

159
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

ZDRDIR
I3P* STDIR
U3P*

IEC05000681-2-en.vsd
IEC05000681 V2 EN

Figure 79: ZDRDIR function block

6.1.4 Input and output signals


Table 85: ZMQPDIS Input signals
Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
VTSZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

Table 86: ZMQPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or
loop

Table 87: ZMQAPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
VTSZ BOOLEAN 0 Blocks all output by fuse failure signal
Table continues on next page

160
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Name Type Default Description


BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

Table 88: ZMQAPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or
loop

Table 89: ZDRDIR Input signals


Name Type Default Description
I3P GROUP - Group connection
SIGNAL
U3P GROUP - Group connection
SIGNAL

Table 90: ZDRDIR Output signals


Name Type Description
STDIR INTEGER All start signals binary coded

6.1.5 Setting parameters

Signals and settings for ZMQPDIS are valid for zone 1 while
signals and settings for ZMQAPDIS are valid for zone 2 - 5

161
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Table 91: ZMQPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Off - - Forward Operation mode of directionality NonDir /
Non-directional Forw / Rev
Forward
Reverse
X1 0.10 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach
R1 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.10 - 9000.00 ohm/p 0.01 100.00 Zero sequence reactance reach
R0 0.50 - 3000.00 ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
RFPP 1.00 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach in ohm/loop, Ph-Ph
RFPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-E
OperationPP Off - - On Operation mode Off / On of Phase-
On Phase loops
Timer tPP Off - - On Operation mode Off / On of Zone timer,
On Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off - - On Operation mode Off / On of Phase-Earth
On loops
Timer tPE Off - - On Operation mode Off / On of Zone timer,
On Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 - 30 %IB 1 20 Minimum operate delta current for Phase-
Phase loops
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops
IMinOpIN 5 - 30 %IB 1 5 Minimum operate residual current for
Phase-Earth loops

Table 92: ZMQAPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Off - - Forward Operation mode of directionality NonDir /
Non-directional Forw / Rev
Forward
Reverse
X1 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach
Table continues on next page

162
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Name Values (Range) Unit Step Default Description


R1 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.50 - 9000.00 ohm/p 0.01 120.00 Zero sequence reactance reach
R0 0.50 - 3000.00 ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
RFPP 1.00 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach in ohm/loop, Ph-Ph
RFPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-E
OperationPP Off - - On Operation mode Off / On of Phase-
On Phase loops
Timer tPP Off - - On Operation mode Off / On of Zone timer,
On Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off - - On Operation mode Off / On of Phase-Earth
On loops
Timer tPE Off - - On Operation mode Off / On of Zone timer,
On Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 - 30 %IB 1 20 Minimum operate delta current for Phase-
Phase loops
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops

Table 93: ZDRDIR Group settings (basic)


Name Values (Range) Unit Step Default Description
ArgNegRes 90 - 175 Deg 1 115 Angle to blinder in second quadrant for
forward direction
ArgDir 5 - 45 Deg 1 15 Angle to blinder in fourth quadrant for
forward direction
IMinOp 1 - 99999 %IB 1 10 Minimum operate current in % of IBase
IBase 1 - 99999 A 1 3000 Base Current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base Voltage

6.1.6 Technical data


Table 94: ZMQPDIS technical data
Function Range or value Accuracy
Number of zones 34 with selectable -
direction
Minimum operate residual (5-30)% of IBase -
current, zone 1
Minimum operate current, phase- (10-30)% of IBase -
to-phase and phase-to-earth
Table continues on next page

163
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Function Range or value Accuracy


Positive sequence reactance, (0.10-3000.00) Ω/ ± 2.0% static accuracy
zone 1 phase ± 2.0 degrees static angular accuracy
Conditions:
Positive sequence reactance, (0.50-3000.00) Ω/ Voltage range: (0.1-1.1) x Ur
zone 2- phase
Current range: (0.5-30) x Ir
34
Angle: at 0 degrees and 85 degrees
Positive sequence resistance (0.10-1000.00) Ω/
phase
Zero sequence reactance, zone 1 (0.10-9000.00) Ω/
phase
Zero sequence reactance, (0.50-9000.00) Ω/
zone 2- phase
34
Zero sequence resistance (0.50-3000.00) Ω/
phase
Fault resistance, phase-to-earth (1.00-9000.00) Ω/loop
Fault resistance, phase-to-phase (1.00-3000.00) Ω/loop
Dynamic overreach <5% at 85 degrees -
measured with CVT’s
and 0.5<SIR<30
Impedance zone timers (0.000-60.000) s ± 0.5% ± 10 ms
Operate time 24 ms typically -
Reset ratio 105% typically -
Reset time 30 ms typically -

6.2 Distance measuring zone, quadrilateral


characteristic for series compensated lines
ZMCPDIS, ZMCAPDIS, ZDSRDIR

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Distance measuring zone, quadrilateral ZMCPDIS 21
characteristic for series compensated
lines (zone 1)

S00346 V1 EN

Distance measuring zone, quadrilateral ZMCAPDIS 21


characteristic for series compensated
lines (zone 2-5)

S00346 V1 EN

Directional impedance quadrilateral, ZDSRDIR 21D


including series compensation
Z<->

IEC09000167 V1 EN

164
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.2.1 Introduction
The line distance protection is a, up to four zone full scheme protection with three
fault loops for phase-to-phase faults and three fault loops for phase-to-earth fault
for each of the independent zones. Individual settings for each zone resistive and
reactive reach give flexibility for use on overhead lines and cables of different
types and lengths.

Quadrilateral characteristic is available.

ZMCPDIS function has functionality for load encroachment which increases the
possibility to detect high resistive faults on heavily loaded lines.

Forward
operation

Reverse
operation

en05000034.vsd
IEC05000034 V1 EN

Figure 80: Typical quadrilateral distance protection zone with load


encroachment function activated

The independent measurement of impedance for each fault loop together with a
sensitive and reliable built in phase selection makes the function suitable in
applications with single phase auto-reclosing.

Built-in adaptive load compensation algorithm for the quadrilateral function


prevents overreaching of zone1 at load exporting end at phase to earth-faults on
heavily loaded power lines.

The distance protection zones can operate, independent of each other, in directional
(forward or reverse) or non-directional mode. This makes them suitable, together
with different communication schemes, for the protection of power lines and cables
in complex network configurations, such as parallel lines, multi-terminal lines.

165
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.2.2 Principle of operation

6.2.2.1 Full scheme measurement

The execution of the different fault loops within the IED are of full scheme type,
which means that earth fault loop for phase-to-earth faults and phase-to-phase
faults for forward and reverse faults are executed in parallel.

Figure 81 presents an outline of the different measuring loops for the basic five,
impedance-measuring zones.

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 1

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 2

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 3

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 4

L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 Zone 5

en05000458.vsd
IEC05000458 V1 EN

Figure 81: The different measuring loops at phase-to-earth fault and phase-to-
phase fault

The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a start element to select correct voltages and current
depending on fault type. Each distance protection zone performs like one
independent distance protection IED with six measuring elements.

6.2.2.2 Impedance characteristic

Distance measuring zone, quadrilateral characteristic for series compensated lines


(ZMCPDIS) include six impedance measuring loops; three intended for phase-to-
earth faults, and three intended for phase-to-phase as well as, three-phase faults.

The distance measuring zone operates according to the non-directional impedance


characteristics presented in figure 82 and figure 83. The phase-to-earth
characteristic is illustrated with the full loop reach while the phase-to-phase
characteristic presents the per-phase reach.

166
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

X (Ohm/loop)

R1PE+RNFw
X 0 PE - X 1FwPE
RFRvPE RFFwPE XNFw =
3
PG- -
XX00PE 1RVPG 1RvPE
1XRVPE
X
XNRV XNRv
XNRV == =XXNFw
3
×
3 X 1FwPE
XX0 PE - X-1X
0 PG FWPE
1FWPG
XNFW==
XNFW
X1FwPE+XNFw 3 3 R0 PE - R1PE
RNFw =
jN jN 3
R (Ohm/loop)

RFRvPE RFFwPE

X1RvPE+XNRv

jN

RFRvPE RFFwPE
IEC09000625-1-en.vsd
IEC09000625 V1 EN

Figure 82: Characteristic for the phase-to-earth measuring loops, ohm/loop


domain

167
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

X (Ohm/phase)

RFRvPP R1PP RFFwPP


2 2
X 0 PE - X 1RVPE
XNRV =XX00PEPG- -X31XRVPE
1RVPG
XNRV =
XNRV =
33
XX00 PE-
X 0 PG X
PE --1X 11FWPE
XFWPE
FWPG
XNFW===
XNFW
XNFW
X1FwPP 3 33

j j
jN R (Ohm/phase)

RFRvPP RFFwPP
2 2

X1RvPP

jN

RFRvPP RFFwPP
2 2
IEC09000632-1-en.vsd
IEC09000632 V1 EN

Figure 83: Characteristic for the phase-to-phase measuring loops

The fault loop reach with respect to each fault type may also be presented as in
figure 84. Note in particular the difference in definition regarding the (fault)
resistive reach for phase-to-phase faults and three-phase faults.

168
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

IL1 R1 + j X1
Phase-to-earth
UL1
element

Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)

0
IN (R0-R1)/3 +
j (X0-X1)/3 )

IL1 R1 + j X1 Phase-to-phase
UL1 element L1-L2
Phase-to-phase
fault in phase RFPP
L1-L2 IL2
UL2 (Arc resistance)
R1 + j X1

IL1 R1 + j X1 0.5·RFPP Phase-to-phase


UL1 element L1-L3
Three-phase
fault
IL3
UL3
R1 + j X1 0.5·RFPP
IEC08000282-2-en.vsd
IEC08000282 V2 EN

Figure 84: Fault loop model

The R1 and jX1 in figure 84 represents the positive sequence impedance from the
measuring point to the fault location. The RFPE and RFPP is the eventual fault
resistance in the fault place.

Regarding the illustration of three-phase fault in figure 84, there is of course fault
current flowing also in the third phase during a three-phase fault. The illustration
merely reflects the loop measurement, which is made phase-to-phase.

The zone may be set to operate in Non-directional, Forward or Reverse direction


through the setting OperationDir. The result from respective set value is illustrated
in figure 85. It may be convenient to once again mention that the impedance reach
is symmetric, forward and reverse direction. Therefore, all reach settings apply to
both directions.

169
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

X X X

R R R

Non-directional Forward Reverse

en05000182.vsd
IEC05000182 V1 EN

Figure 85: Directional operating modes of the distance measuring zone

6.2.2.3 Minimum operating current

The operation of Distance measuring zone, quadrilateral characteristic for series


compensated lines (ZMCPDIS,ZMCAPDIS) is blocked if the magnitude of input
currents fall below certain threshold values.

The phase-to-earth loop Ln is blocked if ILn < IMinOpPE.

For zone 1 with load compensation feature the additional criterion applies, that all
phase-to-earth loops will be blocked when IN < IMinOpIN, regardless of the phase
currents.

ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector
sum of the three phase currents, that is, residual current 3I0.

The phase-to-phase loop LmLn is blocked if ILmLnAB (BC or CA)< IMinOpPP.

ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.

All three current limits IMinOpPE, IMinOpIN and IMinOpPP are


automatically reduced to 75% of regular set values if the zone is set
to operate in reverse direction, that is, OperationDir=Reverse.

6.2.2.4 Measuring principles

Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits. The

170
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

calculation of the apparent impedances at ph-ph faults follows equation 14


(example for a phase L1 to phase L2 fault).

UL1 – UL2
Zapp = -------------------------
I L1 – IL2
EQUATION1222 V1 EN (Equation 14)

Here U and I represent the corresponding voltage and current phasors in the
respective phase.

The earth return compensation applies in a conventional manner to ph-E faults


(example for a phase L1 to earth fault) according to equation 15.

U L1
Z app = ------------------------------
I L1 + I N × KN
EQUATION1223 V1 EN (Equation 15)

Where:
UL1, IL1 and IN are the phase voltage, phase current and residual current present to the IED
KN is defined as:

Z0 - Z1
KN =
3 × Z1
EQUATION 2105 V1 EN

Z 0 = R0 + jX 0
EQUATION2106 V1 EN

Z1 = R1 + jX 1
EQUATION2107 V1 EN

Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach

Here IN is a phasor of the residual current at the IED point. This results in the same
reach along the line for all types of faults.

The apparent impedance is considered as an impedance loop with resistance R and


reactance X.

171
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

The formula given in equation 15 is only valid for no loaded radial feeder
applications. When load is considered in the case of single phase-to-earth fault,
conventional distance protection might overreach at exporting end and underreach
at importing end. IED has an adaptive load compensation which increases the
security in such applications.

Measuring elements receive current and voltage information from the A/D
converter. The check sums are calculated and compared, and the information is
distributed into memory locations. For each of the six supervised fault loops,
sampled values of voltage (U), current (I), and changes in current between samples
(DI) are brought from the input memory and fed to a recursive Fourier filter.

The filter provides two orthogonal values for each input. These values are related
to the loop impedance according to equation 16,

X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN (Equation 16)

in complex notation, or:

X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt

EQUATION354 V1 EN (Equation 17)

X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt

EQUATION355 V1 EN (Equation 18)

with

w0 = 2 × p × f 0
EQUATION356 V1 EN (Equation 19)

where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency

The algorithm calculates Rm measured resistance from the equation for the real
value of the voltage and substitute it in the equation for the imaginary part. The
equation for the Xm measured reactance can then be solved. The final result is
equal to:

172
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN (Equation 20)

Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN (Equation 21)

The calculated Rm and Xm values are updated each sample and compared with the
set zone reach. The adaptive tripping counter counts the number of permissive
tripping results. This effectively removes any influence of errors introduced by the
capacitive voltage transformers or by other factors.

The directional evaluations are performed simultaneously in both forward and


reverse directions, and in all six fault loops. Positive sequence voltage and a phase
locked positive sequence memory voltage are used as a reference. This ensures
unlimited directional sensitivity for faults close to the IED point.

6.2.2.5 Directionality for series compensation

In the basic distance protection function, the control of the memory for polarizing
voltage is performed by an under voltage control. In case of series compensated
line, a voltage reversal can occur with a relatively high voltage also when the
memory must be locked. Thus, a simple undervoltage type of voltage memory
control can not be used in case of voltage reversal. In the option for series
compensated network the polarizing quantity and memory are controlled by an
impedance measurement criterion.

The polarizing voltage is a memorized positive sequence voltage. The memory is


continuously synchronized via a positive sequence filter. The memory is starting to
run freely instantaneously when a voltage change is detected in any phase. A non-
directional impedance measurement is used to detect a fault and identify the faulty
phase or phases.

At a three phase fault when no positive sequence voltage remains (all three phases
are disconnected) the memory is used for direction polarization during 100 ms.

The memory predicts the phase of the positive sequence voltage with the pre-fault
frequency. This extrapolation is made with a high accuracy and it is not the
accuracy of the memory that limits the time the memory can be used. The network
is at a three phase fault under way to a new equilibrium and the post-fault condition
can only be predicted accurately for a limited time from the pre-fault condition.

In case of a three phase fault after 100 ms the phase of the memorized voltage can
not be relied upon and the directional measurement has to be blocked. The
achieved direction criteria are sealed-in when the directional measurement is
blocked and kept until the impedance fault criteria is reset (the direction is stored
until the fault is cleared).

173
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

This memory control allows in the time domain unlimited correct directional
measurement for all unsymmetrical faults also at voltage reversal. Only at three
phase fault within the range of the set impedance reach of the criteria for control of
the polarization voltage the memory has to be used and the measurement is limited
to 100 ms and thereafter the direction is sealed-in. The special impedance
measurement to control the polarization voltage is set separately and has only to
cover (with some margin) the impedance to fault that can cause the voltage reversal.

The evaluation of the directionality takes place in Directional impedance


quadrilateral, including series compensation (ZDSRDIR) function. Equation 22 and
equation 23 are used to classify that the fault is in forward direction for phase-to-
earth fault and phase-to-phase fault.

U 1L1M
- ArgDir < arg < ArgNeg Re s
I L1
EQUATION2004 V2 EN (Equation 22)

For the L1-L2 element, the equation in forward direction is according to:

U 1L1L 2 M
- ArgDir < arg < ArgNeg Re s
I L1L 2
EQUATION2006 V2 EN (Equation 23)

where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default
set to 15 (= -15 degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default
set to 115 degrees, see figure 86.
U1L1M is positive sequence memorized phase voltage in phase L1

IL1 is phase current in phase L1

U1L1L2M is memorized voltage difference between phase L1 and L2 (L2 lagging L1)

IL1L2 is current difference between phase L1 and L2 (L2 lagging L1)

The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115
degrees respectively, see figure 86, and it should not be changed unless system
studies have shown the necessity.

ZDSRDIR generates a binary coded signal on the output STDIR depending on the
evaluation where STFWL1N=1 adds 1, STRVL1N=1 adds 2, STFWL2N=1 adds 4.

174
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

ArgNegRes

ArgDir
R

en05000722.vsd
IEC05000722 V1 EN

Figure 86: Setting angles for discrimination of forward and reverse fault

The reverse directional characteristic is equal to the forward characteristic rotated


by 180 degrees.

6.2.2.6 Simplified logic diagrams

Distance protection zones


The design of distance protection zones are presented for all measuring loops: phase-
to-earth as well as phase-to-phase.

Phase-to-earth related signals are designated by Ln, where n represents the


corresponding phase number (L1, L2, and L3). The phase-to-phase signals are
designated by LnLm, where n and m represent the corresponding phase numbers
(L1L2, L2L3, and L3L1).

Fulfillment of two different measuring conditions is necessary to obtain the one


logical signal for each separate measuring loop:

• Zone measuring condition, which follows the operating equations described


above.
• Group functional input signal (STCND), as presented in figure 87.

Two types of function block, ZMCPDIS and ZMCAPDIS , are used in the IED.
ZMQPDIS is used for zone 1 and ZMQAPDIS for zone 2 - 5.

175
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

The STCND input signal represents a connection of six different integer values
from the phase selection function within the IED, which are converted within the
zone measuring function into corresponding boolean expressions for each
condition separately. It is connected to Phase selection with load enchroachment,
quadrilateral characteristic (FDPSPDIS) function output STCDZ.

IEC99000557-TIFF V1 EN

Figure 87: Conditioning by a group functional input signal STCND

Composition of the phase starting signals for a case, when the zone operates in a non-
directional mode, is presented in figure 88.

176
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

IEC00000488-TIFF V1 EN

Figure 88: Composition of starting signals in non-directional operating mode

Results of the directional measurement enter the logic circuits, when the zone
operates in directional (forward or reverse) mode, as shown in figure 89.

STNDL1N
AND
DIRL1N STZMPE
OR
STNDL2N
DIRL2N AND

STNDL3N OR STL1
DIRL3N AND AND

STNDL1L2
DIRL1L2 AND OR STL2
AND
STNDL2L3
DIRL2L3 AND
OR STL3
STNDL3L1 AND
DIRL3L1 AND

STZMPP
OR

BLK

15 ms
OR START
AND t

en05000778.vsd
IEC05000778 V2 EN

Figure 89: Composition of starting signals in directional operating mode

Tripping conditions for the distance protection zone one are symbolically presented
in figure 90.

177
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Timer tPP=On tPP


AND t
STZMPP
OR
Timer tPE=On tPE
AND t
STZMPE
15ms
BLKTR AND t
TRIP
BLK OR

STL1 AND TRL1

STL2 AND TRL2

STL3 AND TRL3

en00000490-3.vsd
IEC00000490 2 V1 EN

Figure 90: Tripping logic for the distance protection zone one

6.2.3 Function block


ZMCPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC07000036-2-en.vsd
IEC07000036 V2 EN

Figure 91: ZMCPDIS function block

ZMCAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC09000890-1-en.vsd
IEC09000890 V1 EN

Figure 92: ZMCAPDIS function block

178
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

ZDSRDIR
I3P* STFW
U3P* STRV
STDIRCND

IEC07000035-2-en.vsd
IEC07000035 V2 EN

Figure 93: ZDSRDIR function block

6.2.4 Input and output signals

Input and output signals is shown for zone 1, zone 2 - 5 are equal.

Table 95: ZMCPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
VTSZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

Table 96: ZMCPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or
loop

179
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Table 97: ZMCAPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
VTSZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

Table 98: ZMCAPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or
loop

Table 99: ZDSRDIR Input signals


Name Type Default Description
I3P GROUP - Group connection for current
SIGNAL
U3P GROUP - Group connection for voltage
SIGNAL

Table 100: ZDSRDIR Output signals


Name Type Description
STFW BOOLEAN Start in forward direction
STRV BOOLEAN Start in reverse direction
STDIRCND INTEGER Binary coded directional information per
measuring loop

180
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.2.5 Setting parameters

Settings for ZMCPDIS are valid for zone 1, while settings for
ZMCAPDIS are valid for zone 2 - 5

Table 101: ZMCPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Off - - Forward Operation mode of directionality NonDir /
Non-directional Forw / Rev
Forward
Reverse
OperationPP Off - - On Operation mode Off / On of Phase-
On Phase loops
X1FwPP 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
Ph, forward
R1PP 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for characteristic
angle, Ph-Ph
RFFwPP 1.00 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
X1RvPP 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
Ph, reverse
RFRvPP 1.00 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
Timer tPP Off - - On Operation mode Off / On of Zone timer,
On Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off - - On Operation mode Off / On of Phase-Earth
On loops
X1FwPE 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
E, forward
R1PE 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for characteristic
angle, Ph-E
X0PE 0.50 - 9000.00 ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-E
R0PE 0.50 - 3000.00 ohm/p 0.01 47.00 Zero seq. resistance for zone
characteristic angle, Ph-E
RFFwPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
X1RvPE 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
E, reverse
RFRvPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
Timer tPE Off - - On Operation mode Off / On of Zone timer,
On Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
Table continues on next page

181
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Name Values (Range) Unit Step Default Description


IMinOpPP 10 - 30 %IB 1 20 Minimum operate delta current for Phase-
Phase loops
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops
IMinOpIN 5 - 30 %IB 1 5 Minimum operate residual current for
Phase-Earth loops

Table 102: ZMCAPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Off - - Forward Operation mode of directionality NonDir /
Non-directional Forw / Rev
Forward
Reverse
OperationPP Off - - On Operation mode Off / On of Phase-
On Phase loops
X1FwPP 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
Ph, forward
R1PP 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for characteristic
angle, Ph-Ph
RFFwPP 1.00 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
X1RvPP 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
Ph, reverse
RFRvPP 1.00 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
Timer tPP Off - - On Operation mode Off / On of Zone timer,
On Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off - - On Operation mode Off / On of Phase-Earth
On loops
X1FwPE 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
E, forward
R1PE 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for characteristic
angle, Ph-E
X0PE 0.50 - 9000.00 ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-E
R0PE 0.50 - 3000.00 ohm/p 0.01 47.00 Zero seq. resistance for zone
characteristic angle, Ph-E
RFFwPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
X1RvPE 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
E, reverse
RFRvPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
Timer tPE Off - - On Operation mode Off / On of Zone timer,
On Ph-E
Table continues on next page

182
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Name Values (Range) Unit Step Default Description


tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 - 30 %IB 1 20 Minimum operate delta current for Phase-
Phase loops
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops

Table 103: ZDSRDIR Group settings (basic)


Name Values (Range) Unit Step Default Description
OperationSC NoSeriesComp - - SeriesComp Special directional criteria for voltage
SeriesComp reversal
IBase 1 - 99999 A 1 3000 Base setting for current level
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level
IMinOpPE 5 - 30 %IB 1 5 Minimum operate phase current for
Phase-Earth loops
IMinOpPP 5 - 30 %IB 1 10 Minimum operate delta current for Phase-
Phase loops
ArgNegRes 90 - 175 Deg 1 130 Angle of blinder in second quadrant for
forward direction
ArgDir 5 - 45 Deg 1 15 Angle of blinder in fourth quadrant for
forward direction
INReleasePE 10 - 100 %IPh 1 20 3I0 limit for releasing phase-to-earth
measuring loops
INBlockPP 10 - 100 %IPh 1 40 3I0 limit for blocking phase-to-phase
measuring loops
OperationLdCh Off - - On Operation of load discrimination
On characteristic
RLdFw 1.00 - 3000.00 ohm/p 0.01 80.00 Forward resistive reach within the load
impedance area
RLdRv 1.00 - 3000.00 ohm/p 0.01 80.00 Reverse resistive reach within the load
impedance area
ArgLd 5 - 70 Deg 1 30 Load angle determining the load
impedance area
X1FwPP 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach, Ph-
Ph, forward
R1PP 0.10 - 1000.00 ohm/p 0.01 7.00 Positive seq. resistance for characteristic
angle, Ph-Ph
RFFwPP 0.50 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
X1RvPP 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach, Ph-
Ph, reverse
RFRvPP 0.50 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
X1FwPE 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach, Ph-
E, forward
R1PE 0.10 - 1000.00 ohm/p 0.01 7.00 Positive seq. resistance for characteristic
angle, Ph-E
X0FwPE 0.50 - 9000.00 ohm/p 0.01 120.00 Zero sequence reactance reach, Ph-E,
forward
Table continues on next page

183
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Name Values (Range) Unit Step Default Description


R0PE 0.50 - 3000.00 ohm/p 0.01 20.00 Zero seq. resistance for zone
characteristic angle, Ph-E
RFFwPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
X1RvPE 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach, Ph-
E, reverse
X0RvPE 0.50 - 9000.00 ohm/p 0.01 120.00 Zero sequence reactance reach, Ph-E,
reverse
RFRvPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse

6.2.6 Technical data


Table 104: ZMCPDIS, ZMCAPDIS technical data
Function Range or value Accuracy
Number of zones 34 with selectable direction -
Minimum operate residual (5-30)% of IBase -
current, zone 1
Minimum operate current, Ph-Ph (10-30)% of IBase -
and Ph-E
Positive sequence reactance (0.50-3000.00) Ω/phase ± 2.0% static accuracy
± 2.0 degrees static angular
Positive sequence resistance (0.10-1000.00) Ω/phase accuracy
Zero sequence reactance (0.50-9000.00) Ω/phase Conditions:
Voltage range: (0.1-1.1) x Ur
Zero sequence resistance (0.50-3000.00) Ω/phase Current range: (0.5-30) x Ir
Fault resistance, Ph-E (1.00-9000.00) Ω/loop Angle: at 0 degrees and 85
degrees
Fault resistance, Ph-Ph (1.00-3000.00) Ω/loop
Dynamic overreach <5% at 85 degrees measured -
with CCVT’s and 0.5<SIR<30
Impedance zone timers (0.000-60.000) s ± 0.5% ± 10 ms
Operate time 24 ms typically -
Reset ratio 105% typically -
Reset time 30 ms typically -

6.3 Phase selection, quadrilateral characteristic with


fixed angle FDPSPDIS

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Phase selection with load FDPSPDIS 21
encroachment, quadrilateral
characteristic Z<phs

SYMBOL-DD V1 EN

184
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.3.1 Introduction
The operation of transmission networks today is in many cases close to the stability
limit. Due to environmental considerations, the rate of expansion and
reinforcement of the power system is reduced, for example, difficulties to get
permission to build new power lines. The ability to accurately and reliably classify
the different types of fault, so that single pole tripping and autoreclosing can be
used plays an important role in this matter. Phase selection, quadrilateral
characteristic with fixed angle FDPSPDIS is designed to accurately select the
proper fault loop in the distance function dependent on the fault type.

The heavy load transfer that is common in many transmission networks may make
fault resistance coverage difficult to achieve. Therefore, FDPSPDIS has a built-in
algorithm for load encroachment, which gives the possibility to enlarge the
resistive setting of both the phase selection and the measuring zones without
interfering with the load.

The extensive output signals from the phase selection gives also important
information about faulty phase(s), which can be used for fault analysis.

6.3.2 Principle of operation


The basic impedance algorithm for the operation of the phase selection measuring
elements is the same as for the distance zone measuring function. Phase selection
with load encroachment, quadrilateral characteristic FDPSPDIS includes six
impedance measuring loops; three intended for phase-to-earth faults, and three
intended for phase-to-phase faults as well as for three-phase faults.

The difference, compared to the distance zone measuring function, is in the


combination of the measuring quantities (currents and voltages) for different types
of faults.

A current-based phase selection is also included. The measuring elements


continuously measure three phase currents and the residual current, and compare
them with the set values. The current signals are filtered by Fourier's recursive
filter, and separate trip counter prevents too high overreaching of the measuring
elements.

The characteristic is basically non-directional, but FDPSPDIS uses information


from the directional function to discriminate whether the fault is in forward or
reverse direction.

The start condition STCNDZ is essentially based on the following criteria:

1. Residual current criteria, that is, separation of faults with and without earth
connection
2. Regular quadrilateral impedance characteristic
3. Load encroachment characteristics is always active but can be switched off by
selecting a high setting.

185
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

The current start condition STCNDI is based on the following criteria:

1. Residual current criteria


2. No quadrilateral impedance characteristic. The impedance reach outside the
load area is theoretically infinite. The practical reach, however, will be
determined by the minimum operating current limits.
3. Load encroachment characteristic is always active, but can be switched off by
selecting a high setting.

The STCNDI output is non-directional. The directionality is determined by the


distance zones directional function. There are outputs from FDPSPDIS that
indicate whether a start is in forward or reverse direction or non-directional, for
example STFWL1, STRVL1 and STNDL1.

These directional indications are based on the sector boundaries of the directional
function and the impedance setting of FDPSPDIS function. Their operating
characteristics are illustrated in figure 94.

X X X

R
R R

Non-directional (ND) Forward (FW) Reverse (RV)

en08000286.vsd
IEC08000286 V1 EN

Figure 94: Characteristics for non-directional, forward and reverse operation


of Phase selection with load encroachment, quadrilateral
characteristic FDPSPDIS

The setting of the load encroachment function may influence the total operating
characteristic, (for more information, refer to section "Load encroachment").

The input DIRCND contains binary coded information about the directional
coming from the directional function . It shall be connected to the STDIR output on
ZDRDIR, directional measuring block. This information is also transferred to the
input DIRCND on the distance measuring zones, that is, the ZMQPDIS, distance
measuring block.

The code built up for the directionality is as follows:

186
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048

If the binary information is 1 then it will be considered that we have start in


forward direction in phase L1. If the binary code is 3 then we have start in forward
direction in phase L1 and L2, binary code 192 means start in reverse direction in
phase L1 and L2A and B etc.

The STCNDZ or STCNDI output contains, in a similar way as DIRCND, binary


coded information, in this case information about the condition for opening correct
fault loop in the distance measuring element. It shall be connected to the STCND
input on the ZMQPDIS, distance measuring block.

The code built up for release of the measuring fault loops is as follows:

STCND = L1N*1 + L2N*2 + L3N*4 + L1L2*8 + L2L3*16 + L3L1*32

6.3.2.1 Phase-to-earth fault

For a phase-to-earth fault, the measured impedance by FDPSPDIS will be


according to equation 24.

Index PHS in images and equations reference settings for Phase


selection with load encroachment function FDPSPDIS.

ULn
ZPHSn =
ILn
EQUATION1255 V1 EN (Equation 24)

where:
n corresponds to the particular phase (n=1, 2 or 3)

The characteristic for FDPSPDIS function at phase-to-earth fault is according to


figure 95. The characteristic has a fixed angle for the resistive boundary in the first
quadrant of 60°.

The resistance RN and reactance XN are the impedance in the earth-return path
defined according to equation 25 and equation 26.

R0 - R1
RN =
3
EQUATION1256 V1 EN (Equation 25)

187
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

X 0 - X1
XN =
3
EQUATION1257 V1 EN (Equation 26)

X (ohm/loop)
Kr·(X1+XN)

RFRvPE RFFwPE

X1+XN

60 deg
RFFwPE

RFRvPE R (Ohm/loop)
60 deg
X1+XN

1
Kr =
tan(60deg)

RFRvPE RFFwPE

Kr·(X1+XN)
en06000396.vsd
IEC06000396 V2 EN

Figure 95: Characteristic of FDPSPDIS for phase-to-earth fault (setting


parameters in italic), ohm/loop domain (directional lines are drawn
as "line-dot-dot-line")

Besides this, the 3I0 residual current must fulfil the conditions according to
equation 27 and equation 28.

3 × I0 ³ 0.5 × IMinOpPE
EQUATION2108 V1 EN (Equation 27)

3 × I0 ³ INReleasePE
------------------------------------ × Iphmax
100
EQUATION766 V1 EN (Equation 28)

where:
IMinOpPE is the minimum operation current for forward zones
INReleasePE is the setting for the minimum residual current needed to enable operation in the phase-
to-earth fault loops (in %).
Iphmax is the maximum phase current in any of three phases.

188
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.3.2.2 Phase-to-phase fault

For a phase-to-phase fault, the measured impedance by FDPSPDIS will be


according to equation 29.

ULm - ULn
ZPHS =
-2 × ILn
EQUATION1258 V1 EN (Equation 29)

ULm is the leading phase voltage, ULn the lagging phase voltage and ILn the
phase current in the lagging phase n.

The operation characteristic is shown in figure 96.

X (W / phase)
0.5·RFRvPP 0.5·RFFwPP

Kr·X1

X1
0.5·RFFwPP
60 deg

R (W / phase)
60 deg
0.5·RFRvPP
X1
1
Kr =
tan(60 deg)

Kr·X1

0.5·RFRvPP 0.5·RFFwPP
IEC09000047-2-en.vsd
IEC09000047 V2 EN

Figure 96: The operation characteristics for FDPSPDIS at phase-to-phase


fault (setting parameters in italic, directional lines drawn as "line-dot-
dot-line"), ohm/phase domain

In the same way as the condition for phase-to-earth fault, there are current
conditions that have to be fulfilled in order to release the phase-to-phase loop.
Those are according to equation 30 or equation 31.

3I 0 < IMinOpPE
EQUATION2109 V1 EN (Equation 30)

189
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

INBlockPP
3I 0 < × Iph max
100
EQUATION2110 V1 EN (Equation 31)

where:
IMinOpPE is the minimum operation current for earth measuring loops,
INBlockPP is 3I0 limit for blocking phase-to-phase measuring loop and
Iphmax is maximal magnitude of the phase currents.

6.3.2.3 Three-phase faults

The operation conditions for three-phase faults are the same as for phase-to-phase
fault, that is equation 29, equation 30 and equation 31 are used to release the
operation of the function.

However, the reach is expanded by a factor 2/√3 (approximately 1.1547) in all


directions. At the same time the characteristic is rotated 30 degrees, counter-
clockwise. The characteristic is shown in figure 97.

X (O/phase)

4 × X1
3

90 deg

0.5·RFFwPP·K3

X1·K3 4 × RFFwPP
6

R (O/phase)

0.5·RFRvPP·K3

K3 = 2 / v(3)
30 deg

IEC05000671-3-en.vsd
IEC05000671 V3 EN

Figure 97: The characteristic of FDPSPDIS for three-phase fault (setting


parameters in italic)

190
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.3.2.4 Load encroachment

Each of the six measuring loops has its own load encroachment characteristic based
on the corresponding loop impedance. The load encroachment functionality is
always active, but can be switched off by selecting a high setting.

The outline of the characteristic is presented in figure 98. As illustrated, the


resistive blinders are set individually in forward and reverse direction while the
angle of the sector is the same in all four quadrants.

RLdFw
ArgLd ArgLd
R

ArgLd ArgLd
RLdRv

IEC09000042-1-en.vsd
IEC09000042 V1 EN

Figure 98: Characteristic of load encroachment function

The influence of load encroachment function on the operation characteristic is


dependent on the chosen operation mode of FDPSPDIS function. When output
signal STCNDZ is selected, the characteristic for FDPSPDIS (and also zone
measurement depending on settings) will be reduced by the load encroachment
characteristic (see figure 99, left illustration).

When output signal STCNDI is selected, the operation characteristic will be as the
right illustration in figure 99. The reach will in this case be limit by the minimum
operation current and the distance measuring zones.

191
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

X X

R R

STCNDZ STCNDI

en05000197.vsd
IEC05000197 V1 EN

Figure 99: Difference in operating characteristic depending on operation


mode when load encroachment is activated

When FDPSPDIS is set to operate together with a distance measuring zone the
resultant operate characteristic could look like in figure 100. The figure shows a
distance measuring zone operating in forward direction. Thus, the operating area is
highlighted in black.

"Phase selection"
"quadrilateral" zone

Distance measuring zone

Load encroachment
characteristic

Directional line

en05000673.vsd
IEC05000673 V1 EN

Figure 100: Operating characteristic in forward direction when load


encroachment is activated

192
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Figure 100 is valid for phase-to-earth. During a three-phase fault, or load, when the
quadrilateral phase-to-phase characteristic is subject to enlargement and rotation
the operate area is transformed according to figure 101. Notice in particular what
happens with the resistive blinders of the "phase selection" "quadrilateral" zone.
Due to the 30-degree rotation, the angle of the blinder in quadrant one is now 90
degrees instead of the original 60 degrees. The blinder that is nominally located to
quadrant four will at the same time tilt outwards and increase the resistive reach
around the R-axis. Consequently, it will be more or less necessary to use the load
encroachment characteristic in order to secure a margin to the load impedance.

X (W / phase)
Phase selection
”Quadrilateral” zone

Distance measuring zone

R (W / phase)

IEC09000049-1-en.vsd
IEC09000049 V1 EN

Figure 101: Operating characteristic for FDPSPDIS in forward direction for three-
phase fault, ohm/phase domain

The result from rotation of the load characteristic at a fault between two phases is
presented in fig 102. Since the load characteristic is based on the same
measurement as the quadrilateral characteristic, it will rotate with the quadrilateral
characteristic clockwise by 30 degrees when subject to a pure phase-to-phase fault.
At the same time the characteristic will "shrink" by 2/√3, from the full RLdFw and
RLdRv reach, which is valid at load or three-phase fault.

193
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

IEC08000437.vsd

IEC08000437 V1 EN

Figure 102: Rotation of load characteristic for a fault between two phases

There is a gain in selectivity by using the same measurement as for the


quadrilateral characteristic since not all phase-to-phase loops will be fully affected
by a fault between two phases. It should also provide better fault resistive coverage
in quadrant one. The relative loss of fault resistive coverage in quadrant four
should not be a problem even for applications on series compensated lines.

6.3.2.5 Minimum operate currents

The operation of the Phase selection with load encroachment function (FDPSPDIS)
is blocked if the magnitude of input currents falls below certain threshold values.

The phase-to-earth loop Ln is blocked if ILn<IMinOpPE, where ILn is the RMS


value of the current in phase Ln.

The phase-to-phase loop LmLn is blocked if (2·ILn<IMinOpPP).

6.3.2.6 Simplified logic diagrams

Figure 103 presents schematically the creation of the phase-to-phase and phase-to-
earth operating conditions. Consider only the corresponding part of measuring and

194
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

logic circuits, when only a phase-to-earth or phase-to-phase measurement is


available within the IED.

Load encroachment block

3I 0 ³ 0.5 × IMinOpPE IRELPE


15 ms
& & t STPE
INReleasePE
3I 0 ³ × Iphmax
100 Bool to &
STCNDI
BLOCK integer

15 ms
3I 0 < IMinOpPE 10 ms 20 ms & t STPP
& t t
OR IRELPP
INBlockPP
3I 0 < × Iph max
100
IEC08000439_1_en.vsd

IEC08000439 1 EN V1 EN

Figure 103: Phase-to-phase and phase-to-earth operating conditions (residual


current criteria)

A special attention is paid to correct phase selection at evolving faults. A STCNDI


output signal is created as a combination of the load encroachment characteristic
and current criteria, refer to figure 103. This signal can be configured to STCND
functional input signals of the distance protection zone and this way influence the
operation of the phase-to-phase and phase-to-earth zone measuring elements and
their phase related starting and tripping signals.

Figure 104 presents schematically the composition of non-directional phase


selective signals STNDLn. Internal signals ZMLnN and ZMLmLn (m and n
change between one and three according to the phase number) represent the
fulfilled operating criteria for each separate loop measuring element, that is, within
the characteristic.

195
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

INDL1N
INDL2N
INDL3N

15 ms
STNDPE
OR t

IRELPE
AND 15 ms
ZML1N STNDL1
OR t
AND
ZML2N
15 ms
STNDL2
OR t
AND
ZML3N
15 ms
ZML1L2 STNDL3
AND OR t

ZML2L3
AND INDL1L2
INDL2L3
ZML3L1
AND
INDL3L1
IRELPP
15 ms
STNDPP
OR t

IEC00000545_2_en.vsd
IEC00000545-TIFF V2 EN

Figure 104: Composition on non-directional phase selection signals

Composition of the directional (forward and reverse) phase selective signals is


presented schematically in figure 106 and figure 105. The directional criteria
appears as a condition for the correct phase selection in order to secure a high
phase selectivity for simultaneous and evolving faults on lines within the complex
network configurations. Internal signals DFWLn and DFWLnLm present the
corresponding directional signals for measuring loops with phases Ln and Lm.
Designation FW (figure 106) represents the forward direction as well as the
designation RV (figure 105) represents the reverse direction. All directional signals
are derived within the corresponding digital signal processor.

Figure 105 presents additionally a composition of a STCNDZ output signal, which


is created on the basis of impedance measuring conditions. This signal can be
configured to STCND functional input signals of the distance protection zone and
this way influence the operation of the phase-to-phase and phase-to-earth zone
measuring elements and their phase related starting and tripping signals.

196
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

INDL1N
AND
DRVL1N
INDL1L2 15 ms STRVL1
AND OR t
DRVL1L2
INDL3L1
AND
DRVL3L1 15 ms STRVPE
INDL2N OR t
AND
DRVL2N
INDL1L2 15 ms
STRVL2
AND OR t

INDL2L3 INDL1N
AND INDL2N
DRVL2L3
INDL3N Bool to STCNDZ
INDL3N INDL1L2 integer
AND INDL2L3
DRVL3N INDL3L1
INDL2L3 15 ms
STRVL3
AND OR t

INDL3L1
15 ms
AND STRVPP
OR t

IEC00000546_2_en.vsd
IEC00000546-TIFF V2 EN

Figure 105: Composition of phase selection signals for reverse direction

197
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

AND

INDL1N
AND 15 ms 15 ms
DFWL1N STFW1PH
AND OR t t
INDL1L2
15 ms STFWL1
AND OR t
DFWL1L2
INDL3L1
AND
AND
DFWL3L1 15 ms
STFWPE
INDL2N OR t
AND
DFWL2N
AND 15 ms
INDL1L2 STFWL2
t
AND OR
15 ms 15 ms
INDL2L3 STFW2PH
AND OR t t
AND
DFWL2L3
INDL3N
AND AND
DFWL3N 15 ms
STFWL3
t
INDL2L3
AND OR
15 ms
INDL3L1 STFW3PH
AND t
AND

15 ms
STFWPP
OR t

IEC05000201_2_en.vsd

IEC05000201 V2 EN

Figure 106: Composition of phase selection signals for forward direction

Figure 107 presents the composition of output signals TRIP and START, where
internal signals STNDPP, STFWPP and STRVPP are the equivalent to internal
signals STNDPE, STFWPE and STRVPE, but for the phase-to-phase loops.

198
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

TimerPP=Off
tPP
AND AND
t
TRIP
OR OR
tPE
TimerPE=Off
t
AND AND

STNDPP
STFWPP OR
STRVPP
START
OR
STNDPE
STFWPE OR
STRVPE

IEC08000441_2_en.vsd
IEC08000441 1 V2 EN

Figure 107: TRIP and START signal logic

6.3.3 Function block


FDPSPDIS
I3P* TRIP
U3P* START
BLOCK STFWL1
DIRCND STFWL2
STFWL3
STFWPE
STRVL1
STRVL2
STRVL3
STRVPE
STNDL1
STNDL2
STNDL3
STNDPE
STFW1PH
STFW2PH
STFW3PH
STPE
STPP
STCNDZ
STCNDI

IEC06000258-2-en.vsd
IEC06000258 V2 EN

Figure 108: FDPSPDIS function block

199
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.3.4 Input and output signals


Table 105: FDPSPDIS Input signals
Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
DIRCND INTEGER 0 External directional condition

Table 106: FDPSPDIS Output signals


Name Type Description
TRIP BOOLEAN Trip output
START BOOLEAN Start in any phase or loop
STFWL1 BOOLEAN Fault detected in phase L1 - forward direction
STFWL2 BOOLEAN Fault detected in phase L2 - forward direction
STFWL3 BOOLEAN Fault detected in phase L3 - forward direction
STFWPE BOOLEAN Earth fault detected in forward direction
STRVL1 BOOLEAN Fault detected in phase L1 - reverse direction
STRVL2 BOOLEAN Fault detected in phase L2 - reverse direction
STRVL3 BOOLEAN Fault detected in phase L3 - reverse direction
STRVPE BOOLEAN Earth fault detected in reverse direction
STNDL1 BOOLEAN Non directional start in L1
STNDL2 BOOLEAN Non directional start in L2
STNDL3 BOOLEAN Non directional start in L3
STNDPE BOOLEAN Non directional start, phase-earth
STFW1PH BOOLEAN Start in forward direction for single-phase fault
STFW2PH BOOLEAN Start in forward direction for two- phase fault
STFW3PH BOOLEAN Start in forward direction for thre-phase fault
STPE BOOLEAN Current conditions release of phase-earth
measuring elements
STPP BOOLEAN Current conditions release of phase-phase
measuring elements
STCNDZ INTEGER Start condition (PHS,LE and I based)
STCNDI INTEGER Start condition (LE and I based)

200
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.3.5 Setting parameters


Table 107: FDPSPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.01 400.00 Base voltage, i.e. rated voltage
INBlockPP 10 - 100 %IPh 1 40 3I0 limit for blocking phase-to-phase
measuring loops
INReleasePE 10 - 100 %IPh 1 20 3I0 limit for releasing phase-to-earth
measuring loops
RLdFw 1.00 - 3000.00 ohm/p 0.01 80.00 Forward resistive reach within the load
impedance area
RLdRv 1.00 - 3000.00 ohm/p 0.01 80.00 Reverse resistive reach within the load
impedance area
ArgLd 5 - 70 Deg 1 30 Load angle determining the load
impedance area
X1 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach
X0 0.50 - 9000.00 ohm/p 0.01 120.00 Zero sequence reactance reach
RFFwPP 0.50 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
RFRvPP 0.50 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
RFFwPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
RFRvPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
IMinOpPP 5 - 30 %IB 1 10 Minimum operate delta current for Phase-
Phase loops
IMinOpPE 5 - 30 %IB 1 5 Minimum operate phase current for
Phase-Earth loops

Table 108: FDPSPDIS Group settings (advanced)


Name Values (Range) Unit Step Default Description
TimerPP Off - - Off Operation mode Off / On of Zone timer,
On Ph-Ph
tPP 0.000 - 60.000 s 0.001 3.000 Time delay to trip, Ph-Ph
TimerPE Off - - Off Operation mode Off / On of Zone timer,
On Ph-E
tPE 0.000 - 60.000 s 0.001 3.000 Time delay to trip, Ph-E

201
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.3.6 Technical data


Table 109: FDPSPDIS technical data
Function Range or value Accuracy
Minimum operate current (5-30)% of IBase -
Reactive reach, positive (0.50–3000.00) Ω/phase ± 2.0% static accuracy
sequence, forward and reverse ± 2.0 degrees static angular
accuracy
Resistive reach, positive (0.10–1000.00) Ω/phase Conditions:
sequence Voltage range: (0.1-1.1) x Ur
Reactive reach, zero sequence, (0.50–9000.00) Ω/phase Current range: (0.5-30) x Ir
forward and reverse Angle: at 0 degrees and 85
degrees
Resistive reach, zero sequence (0.50–3000.00) Ω/phase
Fault resistance, phase-to-earth (1.00–9000.00) Ω/loop
faults, forward and reverse
Fault resistance, phase-to- (0.50–3000.00) Ω/loop
phase faults, forward and reverse
Load encroachment criteria:
Load resistance, forward and (1.00–3000.00) Ω/phase
reverse (5-70) degrees
Safety load impedance angle
Reset ratio 105% typically -

6.4 Full-scheme distance measuring, Mho


characteristic ZMHPDIS

Function description IEC 61850 IEC 60617 identification ANSI/IEEE


identification C37.2 device
number
Full-scheme distance protection, mho ZMHPDIS 21
characteristic

S00346 V1 EN

6.4.1 Introduction
The numerical mho line distance protection is a, up to four zone full scheme
protection for back-up detection of short circuit and earth faults. The full scheme
technique provides back-up protection of power lines with high sensitivity and low
requirement on remote end communication. The four zones have fully independent
measuring and settings, which gives high flexibility for all types of lines.

The IED can be used up to the highest voltage levels. It is suitable for the
protection of heavily loaded lines and multi-terminal lines where the requirement
for tripping is one-, two- and/or three-pole.

202
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

The independent measurement of impedance for each fault loop together with a
sensitive and reliable built in phase selection makes the function suitable in
applications with single phase autoreclosing.

Built-in adaptive load compensation algorithm prevents overreaching at phase-to-


earth faults on heavily loaded power lines, see figure 109.
jX

Operation area Operation area

Operation area

No operation area No operation area

en07000117.vsd
IEC07000117 V1 EN

Figure 109: Load encroachment influence on the offset mho characteristic

The distance protection zones can operate, independent of each other, in directional
(forward or reverse) or non-directional mode (offset). This makes them suitable,
together with different communication schemes, for the protection of power lines
and cables in complex network configurations, such as parallel lines, multi-
terminal lines and so on.

The possibility to use the phase-to-earth quadrilateral impedance characteristic


together with the mho characteristic increases the possibility to overcome eventual
lack of sensitivity of the mho element due to the shaping of the curve at remote end
faults.

The integrated control and monitoring functions offer effective solutions for
operating and monitoring all types of transmission and sub-transmission lines.

6.4.2 Principle of operation

6.4.2.1 Full scheme measurement

The execution of the different fault loops within the IED are of full scheme type,
which means that each fault loop for phase-to-earth faults and phase-to-phase faults
are executed in parallel.

The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a start element to select correct voltages and current

203
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

depending on fault type. So each distance protection zone performs like one
independent distance protection function with six measuring elements.

6.4.2.2 Impedance characteristic

The distance function consists of five instances. Each instance can be selected to be
either forward or reverse with positive sequence polarized mho characteristic
alternatively self polarized offset mho characteristics with reverse offset. The
operating characteristic is in accordance to figure 110 where zone 5 is selected
offset mho.

jx

Mho, zone4

Mho, zone3
Zs=0
Mho, zone2

R
Mho, zone1

Zs=Z1

R Zs=2Z1

Offset mho, zone5

IEC09000143-1-en.vsd

IEC09000143 V1 EN

Figure 110: Mho, offset mho characteristic and the source impedance influence on the mho characteristic

The mho characteristic has a dynamic expansion due to the source impedance.
Instead of crossing the origin as for the mho to the left of figure 110, which is only
valid where the source impedance is zero, the crossing point is moved to the
coordinates of the negative source impedance given an expansion of the circle
shown to the right of figure 110.

The polarization quantities used for the mho circle are 100% memorized positive
sequence voltages. This will give a somewhat less dynamic expansion of the mho
circle during faults. However, if the source impedance is high, the dynamic
expansion of the mho circle might lower the security of the function too much with
high loading and mild power swing conditions.

The mho distance element has a load encroachment function which cuts off a
section of the characteristic when enabled. The function is enabled by setting the
setting parameter LoadEnchMode to On. Enabling of the load encroachment

204
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

function increases the possibility to detect high resistive faults without interfering
with the load impedance. The algorithm for the load encroachment is located in the
Faulty phase identification with load encroachment for mho function FMPSPDIS,
where also the relevant settings can be found. Information about the load
encroachment from FMPSPDIS to the zone measurement is given in binary format
to the input signal LDCND.

6.4.2.3 Basic operation characteristics

Each impedance zone can be switched On and Off by the setting parameter
Operation.

Each zone can also be set to Non-directional, Forward or Reverse by setting the
parameter DirMode.

The operation for phase-to-earth and phase-to-phase fault can be individually


switched On and Off by the setting parameter OpModePE and OpModePP.

For critical applications such as for lines with high SIRs as well as CVTs, it is
possible to improve the security by setting the parameter ReachMode to
Underreach. In this mode the reach for faults close to the zone reach is reduced by
20% and the filtering is also introduced to increase the accuracy in the measuring.
If the ReachMode is set to Overreach no reduction of the reach is introduced and
no extra filtering introduced. The latter setting is recommended for overreaching
pilot zone, zone 2 or zone 3 elements and reverse zone where overreaching on
transients is not a major issue either because of less likelihood of overreach with
higher settings or the fact that these elements do not initiate tripping unconditionally.

The offset mho characteristic can be set in Non-directional, Forward or Reverse by


the setting parameter OffsetMhoDir. When Forward or Reverse is selected a
directional line is introduced. Information about the directional line is given from
the directional element and given to the measuring element as binary coded signal
to the input DIRCND.

The zone reach for phase-to-earth fault and phase-to-phase fault is set individually
in polar coordinates.

The impedance is set by the parameters ZPE and ZPP and the corresponding
arguments by the parameters ZAngPE and ZAngPP.

Compensation for earth-return path for faults involving earth is done by setting the
parameter KNMag and KNAng where KNMag is the magnitude of the earth-return
path and KNAng is the difference of angles between KNMag and ZPE.

Z0-Z1
KNMag =
3 × Z1
EQUATION1579 V1 EN (Equation 32)

205
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

KNAng = arg
( Z 0 - Z1

3 × Z1
)
EQUATION1580 V1 EN (Equation 33)

where
Z0 is the complex zero sequence impedance of the line in Ω/phase
Z1 is the complex positive sequence impedance of the line in Ω/phase

The phase-to-earth and phase-to-phase measuring loops can be time delayed


individually by setting the parameter tPE and tPP respectively. To release the time
delay, the operation mode for the timers, OpModetPE and OpModetPP, has to be
set to On. This is also the case for instantaneous operation.

The function can be blocked in the following ways:

• activating of input BLOCK blocks the whole function


• activating of the input BLKZ (fuse failure) blocks all output signals
• activating of the input BLKZMTD blocks the delta based algorithm
• activating of the input BLKHSIR blocks the instantaneous part of the
algorithm for high SIR values
• activating of the input BLKTRIP blocks all output signals
• activating the input BLKPE blocks the phase-to-earth fault loop outputs
• activating the input BLKPP blocks the phase-to-phase fault loop outputs

The activation of input signal BLKZ can be made by external fuse failure function
or from the loss of voltage check in the Mho supervision logic (ZSMGAPC). In
both cases the output BLKZ in the Mho supervision logic shall be connected to the
input BLKZ in the Mho distance function block (ZMHPDIS)

The input signal BLKZMTD is activated during some ms after fault has been
detected by ZSMGAPC to avoid unwanted operations due to transients. It shall be
connected to the BLKZMTD output signal of ZSMGAPC function.

At SIR values >10, the use of electronic CVT might cause overreach due to the built-
in resonance circuit in the CVT, which reduce the secondary voltage for a while.
The input BLKHSIR shall be connected to the output signal HSIR on ZSMGAPC
for increasing of the filtering and high SIR values. This is valid only when
permissive underreach scheme is selected by setting ReachMode=Underreach.

6.4.2.4 Theory of operation

The mho algorithm is based on phase comparison of a operating phasor and a


polarizing phasor. When the operating phasor leads the reference phasor by more
than 90 degrees, the function will operate and give a trip output.

206
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Phase-to-phase fault

Mho
The plain mho circle has the characteristic as in figure 111. The condition for
deriving the angle β is according to equation 34.

b = arg(U L1 L 2 - I L1 L 2 × ZPP ) - arg(U pol )


EQUATION1789 V1 EN (Equation 34)

where

U L1L2 is the voltage vector difference between phases L1 and L2


EQUATION1790 V2
EN

I L1L2 is the current vector difference between phases L1 and L2


EQUATION1791 V2
EN

ZPP is the positive sequence impedance setting for phase-to-phase fault


Upol is the polarizing voltage

The polarized voltage consists of 100% memorized positive sequence voltage


(UL1L2 for phase L1 to L2 fault). The memorized voltage will prevent collapse of
the mho circle for close in faults.

Operation occurs if 90≤β≤270

207
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

IL1L2·X
Ucomp = UL1L2 - IL1L2 • ZPP

IL1L2 • ZPP
ß
Upol
UL1L2

IL1L2·R

en07000109.vsd
IEC07000109 V1 EN

Figure 111: Simplified mho characteristic and vector diagram for phase L1-to-
L2 fault

Offset Mho
The characteristic for offset mho is a circle where two points on the circle are the
setting parameters ZPP and ZRevPP. The vector ZPP in the impedance plane has
the settable angle AngZPP and the angle for ZRevPP is AngZPP+180°.

The condition for operation at phase-to-phase fault is that the angle β between the
two compensated voltages Ucomp1 and Ucomp2 is greater than or equal to 90°
(figure 112). The angle will be 90° for fault location on the boundary of the circle.

The angle β for L1-to-L2 fault can be defined according to equation 35.

æ U -IL1L2 × ZPP ö
b = arg ç ÷
è U-(-IL1L2 × ZRevPP) ø
EQUATION1792 V1 EN (Equation 35)

where

U is the UL1L2 voltage


EQUATION1800 V1 EN

ZRevPP is the positive sequence impedance setting for phase-to-phase fault in reverse direction

208
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

IL1L2jX

Ucomp1 = UL1L2 - IL1L2 • ZPP


IL1L2 • ZPP

U
Ucomp2 = U = IF•ZF=UL1L2
IL1L2R

- IL1L2 • Z RevPP
en07000110.vsd
IEC07000110 V1 EN

Figure 112: Simplified offset mho characteristic and voltage vectors for phase
L1-to-L2 fault.

Operation occurs if 90≤β≤270.

Offset mho, forward direction


When forward direction has been selected for the offset mho, an extra criteria
beside the one for offset mho (90<β<270) is introduced, that is the angle φ between
the voltage and the current must lie between the blinders in second quadrant and
fourth quadrant. See figure 113. Operation occurs if 90≤β≤270 and
ArgDir≤φ≤ArgNegRes.

where
ArgDir is the setting parameter for directional line in fourth quadrant in the directional element,
ZDMRDIR.
ArgNegRes is the setting parameter for directional line in second quadrant in the directional element,
ZDMRDIR.
β is calculated according to equation 35

The directional information is brought to the mho distance measurement from the
mho directional element as binary coded information to the input DIRCND. See
Directional impedance element for mho characteristic (ZDMRDIR) for information
about the mho directional element.

209
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

IL1L2jX

ZPP

UL1L2

ArgNegRes f

IL1L2
ArgDir

en07000111.vsd
IEC07000111 V1 EN

Figure 113: Simplified offset mho characteristic in forward direction for phase
L1-to-L2 fault

Offset mho, reverse direction


The operation area for offset mho in reverse direction is according to figure 114.
The operation area in second quadrant is ArgNegRes+180°.

Operation occurs if 90≤β≤270 and 180° - ArgDir ≤φ ≤ ArgNegRes + 180°

The β is derived according to equation 35 for the mho circle and φ is the angle
between the voltage and current.

210
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

ZPP

ArgNegRes
ϕ

IL1L2

ArgDir R

UL1L2

ZRevPP

en06000469.eps
IEC06000469 V1 EN

Figure 114: Operation characteristic for reverse phase L1-to-L2 fault

Phase-to-earth fault

Mho
The measuring of earth faults uses earth-return compensation applied in a
conventional way. The compensation voltage is derived by considering the
influence from the earth-return path.

For an earth fault in phase L1, the compensation voltage Ucomp can be derived, as
shown in figure 115.

Ucomp = U pol - I L1 × Z loop


EQUATION1793 V1 EN (Equation 36)

where
Upol is the polarizing voltage (memorized UL1 for Phase L1-to- earth fault)

Zloop is the loop impedance, which in general terms can be expressed as

Z1+ZN = Z 1 × 1 + KN ( )
EQUATION1799 V1 EN (Equation 37)
Table continues on next page

211
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

where
Z1 is the positive sequence impedance of the line (Ohm/phase)

KN is the zero-sequence compensator factor

The angle β between the Ucomp and the polarize voltage Upol for a L1-to-earth
fault is

b = arg [UL1 -(IL1 +3I0 · KN ) · ZPE ] - arg( Upol)


GUID-A9492CDF-D3B7-4DC5-8E06-6638BEE2540B V1 EN (Equation 38)

where
UL1 is the phase voltage in faulty phase L1

IL1 is the phase current in faulty phase L1

IA is the phase current in faulty phase A

3I0 is the zero-sequence current in faulty phase L1

KN Z0-Z1
EQUATION1593 V1 EN
3 × Z1
EQUATION1594 V1 EN

the setting parameter for the zero sequence compensation consisting of the
magnitude KN and the angle KNAng.
Upol is the 100% of positive sequence memorized voltage UL1

Vpol is the 100% of positive sequence memorized voltage VA

IL1·X

IL1·ZN
Ucomp

IL1 • Zloop
IL1·ZPE
Upol

f
IL1 (Ref) IL1·R

en06000472_2.vsd
IEC06000472 V2 EN

Figure 115: Simplified offset mho characteristic and vector diagram for phase
L1-to-earth fault

212
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Operation occurs if 90≤β≤270.

Offset mho
The characteristic for offset mho at earth fault is a circle containing the two vectors
from the origin ZPE and ZRevPE where ZPE and ZrevPE are the setting reach for
the positive sequence impedance in forward respective reverse direction. The
vector ZPE in the impedance plane has the settable angle AngZPE and the angle for
ZRevPP is AngZPE+180°.

The condition for operation at phase-to-earth fault is that the angle β between the
two compensated voltages Ucomp1 and Ucomp2 is greater or equal to 90° see
figure 116. The angle will be 90° for fault location on the boundary of the circle.

The angle β for L1-to-earth fault can be defined as

æ UL1- IL1L × ZPE ö


b = arg ç ÷
è UL1-(- IL1 × Z Re vPE ) ø
EQUATION1802 V1 EN (Equation 41)

where
is the phase L1 voltage
U L1
EQUATION1
805 V1 EN

IL1L 2 • jX

U comp1 = UL1 - I L1• ZPE


IL1 • ZPE

UL1
U comp2 = UL1 - (-IL1 • ZRevPE)
IL1L2 • R

- I L1 • Z Re vPe

en 06000465.vsd
IEC06000465 V1 EN

Figure 116: Simplified offset mho characteristic and voltage vector for phase L1-
to-L2 fault

213
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Operation occurs if 90≤β≤270.

Offset mho, forward direction


In the same way as for phase-to-phase fault, selection of forward direction of offset
mho will introduce an extra criterion for operation. Beside the basic criteria for
offset mho according to equation 41 and 90≤β≤270, also the criteria that the angle
φ between the voltage and the current must lie between the blinders in second and
fourth quadrant. See figure 117. Operation occurs if 90≤β≤270 and
ArgDir≤φ≤ArgNegRes.

where
ArgDir is the setting parameter for directional line in fourth quadrant in the directional element,
ZDMRDIR.
ArgNegRes is the setting parameter for directional line in second quadrant in the directional element,
ZDMRDIR.
β is calculated according to equation 41

IL1 jX

UL1

ArgNegRes f

IL1 IL1·R

ArgDir

en 06000466.vsd
IEC06000466 V1 EN

Figure 117: Simplified characteristic for offset mho in forward direction for L1-to-
earth fault

Offset mho, reverse direction


In the same way as for offset in forward direction, the selection of offset mho in
reverse direction will introduce an extra criterion for operation compare to the
normal offset mho. The extra is that the angle between the fault voltage and the
fault current shall lie between the blinders in second and fourth quadrant. The
operation area in second quadrant is limited by the blinder defined as 180° -ArgDir
and in fourth quadrant ArgNegRes+180°, see figure 118.

214
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

The conditions for operation of offset mho in reverse direction for L1-to-earth fault
is 90≤β≤270 and 180°-Argdir≤φ≤ArgNegRes+180°.

The β is derived according to equation 41 for the offset mho circle and φ is the
angle between the voltage and current.

ZPE

ArgNegRes
ϕ

IL1
ArgDir R

UL1
ZRevPE

en06000470.eps
IEC06000470 V1 EN

Figure 118: Simplified characteristic for offset mho in reverse direction for L1-to-
earth fault

215
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.4.3 Function block


ZMHPDIS
I3P* TRIP
U3P* TRL1
CURR_INP* TRL2
VOLT_INP* TRL3
POL_VOLT* TRPE
BLOCK TRPP
BLKZ START
BLKZMTD STL1
BLKHSIR STL2
BLKTRIP STL3
BLKPE STPE
BLKPP STPP
DIRCND
STCND
LDCND

IEC06000423_2_en.vsd
IEC06000423 V2 EN

Figure 119: ZMHPDIS function block

6.4.4 Input and output signals


Table 110: ZMHPDIS Input signals
Name Type Default Description
I3P GROUP - Connection for current sample signals
SIGNAL
U3P GROUP - Connection for voltage sample signals
SIGNAL
CURR_INP GROUP - Connection for current signals
SIGNAL
VOLT_INP GROUP - Connection for voltage signals
SIGNAL
POL_VOLT GROUP - Connection for polarizing voltage
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Block due to fuse failure
BLKZMTD BOOLEAN 0 Block signal for blocking of time domaine function
BLKHSIR BOOLEAN 0 Blocks time domain function at high SIR
BLKTRIP BOOLEAN 0 Blocks all operate output signals
BLKPE BOOLEAN 0 Blocks phase-to-earth operation
BLKPP BOOLEAN 0 Blocks phase-to-phase operation
DIRCND INTEGER 0 External directional condition
STCND INTEGER 0 External start condition (loop enabler)
LDCND INTEGER 0 External load condition (loop enabler)

216
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Table 111: ZMHPDIS Output signals


Name Type Description
TRIP BOOLEAN Trip General
TRL1 BOOLEAN Trip phase L1
TRL2 BOOLEAN Trip phase L2
TRL3 BOOLEAN Trip phase L3
TRPE BOOLEAN Trip phase-to-earth
TRPP BOOLEAN Trip phase-to-phase
START BOOLEAN Start General
STL1 BOOLEAN Start phase L1
STL2 BOOLEAN Start phase L2
STL3 BOOLEAN Start phase L3
STPE BOOLEAN Start phase-to-earth
STPP BOOLEAN Start phase-to-phase

6.4.5 Setting parameters


Table 112: ZMHPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off/On
On
IBase 1 - 99999 A 1 3000 Base current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
DirMode Off - - Forward Direction mode
Offset
Forward
Reverse
LoadEnchMode Off - - Off Load enchroachment mode Off/On
On
ReachMode Overreach - - Overreach Reach mode Over/Underreach
Underreach
OpModePE Off - - On Operation mode Off / On of Phase-Earth
On loops
ZPE 0.005 - 3000.000 ohm/p 0.001 30.000 Positive sequence impedance setting for
Phase-Earth loop
ZAngPE 10 - 90 Deg 1 80 Angle for positive sequence line
impedance for Phase-Earth loop
KN 0.00 - 3.00 - 0.01 0.80 Magnitud of earth return compensation
factor KN
KNAng -180 - 180 Deg 1 -15 Angle for earth return compensation
factor KN
ZRevPE 0.005 - 3000.000 ohm/p 0.001 30.000 Reverse reach of the phase to earth
loop(magnitude)
tPE 0.000 - 60.000 s 0.001 0.000 Delay time for operation of phase to
earth elements
Table continues on next page

217
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Name Values (Range) Unit Step Default Description


IMinOpPE 10 - 30 %IB 1 20 Minimum operation phase to earth current
OpModePP Off - - On Operation mode Off / On of Phase-
On Phase loops
ZPP 0.005 - 3000.000 ohm/p 0.001 30.000 Impedance setting reach for phase to
phase elements
ZAngPP 10 - 90 Deg 1 85 Angle for positive sequence line
impedance for Phase-Phase elements
ZRevPP 0.005 - 3000.000 ohm/p 0.001 30.000 Reverse reach of the phase to phase
loop(magnitude)
tPP 0.000 - 60.000 s 0.001 0.000 Delay time for operation of phase to phase
IMinOpPP 10 - 30 %IB 1 20 Minimum operation phase to phase
current

Table 113: ZMHPDIS Group settings (advanced)


Name Values (Range) Unit Step Default Description
OffsetMhoDir Non-directional - - Non-directional Direction mode for offset mho
Forward
Reverse
OpModetPE Off - - On Operation mode Off / On of Zone timer,
On Ph-E
OpModetPP Off - - On Operation mode Off / On of Zone timer,
On Ph-ph

6.4.6 Technical data


Table 114: ZMHPDIS technical data
Function Range or value Accuracy
Number of zones with selectable Max 4 with selectable direction -
directions
Minimum operate current (10–30)% of IBase -

Positive sequence impedance, (0.005–3000.000) W/phase ± 2.0% static accuracy


phase-to-earth loop Conditions:
Voltage range: (0.1-1.1) x Ur
Positive sequence impedance (10–90) degrees
Current range: (0.5-30) x Ir
angle, phase-to-earth loop
Angle: at 0 degrees and 85
Reverse reach, phase-to-earth (0.005–3000.000) Ω/phase degrees
loop (Magnitude)
Magnitude of earth return (0.00–3.00)
compensation factor KN
Angle for earth compensation (-180–180) degrees
factor KN
Dynamic overreach <5% at 85 degrees measured -
with CVT’s and 0.5<SIR<30
Timers (0.000-60.000) s ± 0.5% ± 10 ms
Table continues on next page

218
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Function Range or value Accuracy


Operate time 20 ms typically (with static -
outputs)
Reset ratio 105% typically -
Reset time 30 ms typically -

6.5 Full-scheme distance protection, quadrilateral for


earth faults ZMMPDIS, ZMMAPDIS

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Fullscheme distance protection, ZMMPDIS 21
quadrilateral for earth faults (zone 1)

S00346 V1 EN

Fullscheme distance protection, ZMMAPDIS 21


quadrilateral for earth faults (zone 2-5)

S00346 V1 EN

6.5.1 Introduction
The line distance protection is a zone protection with three fault loops for phase-to-
earth fault for each of the independent zones. Individual settings for each zone
resistive and reactive reach give flexibility for use on overhead lines and cables of
different types and lengths.

The Full-scheme distance protection, quadrilateral for earth faults functions


ZMMDPIS and ZMMAPDIS have functionality for load encroachment, which
increases the possibility to detect high resistive faults on heavily loaded lines , see
figure 66.

219
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Forward
operation

Reverse
operation

en05000034.vsd
IEC05000034 V1 EN

Figure 120: Typical quadrilateral distance protection zone with Phase selection,
quadrilateral characteristic with settable angle function FRPSPDIS
activated

The independent measurement of impedance for each fault loop together with a
sensitive and reliable built in phase selection makes the function suitable in
applications with single phase auto-reclosing.

Built-in adaptive load compensation algorithm prevents overreaching of zone1 at


load exporting end at phase to earth faults on heavily loaded power lines.

The distance protection zones can operate, independent of each other, in directional
(forward or reverse) or non-directional mode. This makes them suitable, together
with different communication schemes, for the protection of power lines and cables
in complex network configurations, such as parallel lines, multi-terminal lines.

6.5.2 Principle of operation

6.5.2.1 Full scheme measurement

The different fault loops within the IED are operating in parallel in the same
principle as a full scheme measurement.

Figure 121 presents an outline of the different measuring loops for the basic five,
impedance-measuring zones l.

220
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

L1-N L2-N L3-N Zone 1

L1-N L2-N L3-N Zone 2

L1-N L2-N L3-N Zone 3

L1-N L2-N L3-N Zone 4

L1-N L2-N L3-N Zone 5

en07000080.vsd
IEC07000080 V1 EN

Figure 121: The different measuring loops at line-earth fault and phase-phase
fault.

6.5.2.2 Impedance characteristic

The distance measuring zone include three impedance measuring loops; one fault
loop for each phase.

The distance measuring zone will essentially operate according to the non-
directional impedance characteristics presented in figure 122. The characteristic is
illustrated with the full loop reach.

221
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

X (Ohm/loop)

R1PE+Rn

RFPE RFPE

X0PE-X1PE
Xn =
3
X1PE+Xn R0PE-R1PE
Rn =
3
jN jN
R (Ohm/loop)

RFPE RFPE

X1PE+Xn

RFPE RFPE
en08000280-2-en.vsd

R1PE+Rn
IEC08000280 V1 EN

Figure 122: Characteristic for the phase-to-earth measuring loops, ohm/loop


domain.

The fault loop reach may also be presented as in figure 123.

ILn R1 + j X1
Phase-to-earth
UL1
element

Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)

0
IN (R0-R1)/3 +
j (X0-X1)/3 ) en06000412.vsd
IEC06000412 V1 EN

Figure 123: Fault loop model

222
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

The R1 and jX1 in figure 123 represents the positive sequence impedance from the
measuring point to the fault location. The RFPE is presented in order to “convey”
the fault resistance reach.

The zone may be set to operate in Non-directional, Forward, Off or Reverse


direction through the setting OperationDir. The result from respective set value is
illustrated in figure 124. It may be convenient to once again mention that the
impedance reach is symmetric, in the sense that it is conform for forward and
reverse direction. Therefore, all reach settings apply to both directions.

X X X

R R R

Non-directional Forward Reverse

en05000182.vsd
IEC05000182 V1 EN

Figure 124: Directional operating modes of the distance measuring zone

6.5.2.3 Minimum operating current

The operation of the distance measuring zone is blocked if the magnitude of input
currents fall below certain threshold values.

The phase-to-earth loop Ln is blocked if ILn < IMinOpPE.

For zone 1 with load compensation feature the additional criterion applies, that all
phase-to-earth loops will be blocked when IN < IMinOpIN, regardless of the phase
currents.

ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector
sum of the three phase currents, that is, residual current 3I0.

Both current limits IMinOpPE and IMinOpIN are automatically


reduced to 75% of regular set values if the zone is set to operate in
reverse direction, that is, OperationDir=Reverse.

223
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.5.2.4 Measuring principles

Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits.

Here U and I represent the corresponding voltage and current phasors in the
respective phase Ln (n = 1, 2, 3).

The calculation of the apparant impedances at phase-to-earth fault follow equation


42

The earth return compensation applies in a conventional manner.

U L1
Z app = ------------------------------
I L1 + I N × KN
EQUATION1223 V1 EN (Equation 42)

Where:
UL1, IL1 and IN are the phase voltage, phase current and residual current present to the IED
KN is defined as:

Z0 - Z1
KN =
3 × Z1
EQUATION 2105 V1 EN

Z 0 = R0 + jX 0
EQUATION2106 V1 EN

Z1 = R1 + jX 1
EQUATION2107 V1 EN

Where
R0 is setting of the resistive zero sequence reach
X0 is setting of the reactive zero sequence reach
R1 is setting of the resistive positive sequence reach
X1 is setting of the reactive positive sequence reach

Here IN is a phasor of the residual current in IED point. This results in the same
reach along the line for all types of faults.

The apparent impedance is considered as an impedance loop with resistance R and


reactance X.

The formula given in equation 42 is only valid for no loaded radial feeder
applications. When load is considered in the case of single line-to-earth fault,

224
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

conventional distance protection might overreach at exporting end and underreach


at importing end. IED has an adaptive load compensation which increases the
security in such applications.

Measuring elements receive current and voltage information from the A/D
converter. The check sums are calculated and compared, and the information is
distributed into memory locations. For each of the six supervised fault loops,
sampled values of voltage (U), current (I), and changes in current between samples
(DI) are brought from the input memory and fed to a recursive Fourier filter.

The filter provides two orthogonal values for each input. These values are related
to the loop impedance according to equation 43,

X Di
U = R × i + ------ × -----
w 0 Dt
EQUATION1224 V1 EN (Equation 43)

in complex notation, or:

X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt

EQUATION354 V1 EN (Equation 44)

X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt

EQUATION355 V1 EN (Equation 45)

with

w0 = 2 × p × f 0
EQUATION356 V1 EN (Equation 46)

where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency

The algorithm calculates Rm measured resistance from the equation for the real
value of the voltage and substitute it in the equation for the imaginary part. The
equation for the Xm measured reactance can then be solved. The final result is
equal to:

Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
EQUATION357 V1 EN (Equation 47)

225
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
EQUATION358 V1 EN (Equation 48)

The calculated Rm and Xm values are updated each sample and compared with the
set zone reach. The adaptive tripping counter counts the number of permissive
tripping results. This effectively removes any influence of errors introduced by the
capacitive voltage transformers or by other factors.

The directional evaluations are performed simultaneously in both forward and


reverse directions, and in all six fault loops. Positive sequence voltage and a phase
locked positive sequence memory voltage are used as a reference. This ensures
unlimited directional sensitivity for faults close to the IED point.

6.5.2.5 Directional lines

The evaluation of the directionality takes place in the Directional impedance


element for mho characteristic ZDMRDIR function. Equation 49 is used to classify
that the fault is in forward direction for line-to-earth fault.

0.85 × U1L1 + 0.15 × U1L1M


- ArgDir < arg < ArgNeg Re s
I L1
EQUATION1617 V1 EN (Equation 49)

where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default
set to 15 (= -15 degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default
set to 115 degrees, see figure 125.
U1L1 is positive sequence phase voltage in phase L1

U1L1M is positive sequence memorized phase voltage in phase L1

IL1 is phase current in phase L1

The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115
degrees respectively (see figure 125) and it should not be changed unless system
studies have shown the necessity.

ZDMRDIR gives a binary coded signal on the output STDIRCND depending on


the evaluation where STFWL1N=1 adds 1, STRVL1N=1 adds 2, STFWL2N=1
adds 4 etc.

226
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

ArgNegRes

ArgDir
R

en05000722.vsd
IEC05000722 V1 EN

Figure 125: Setting angles for discrimination of forward and reverse fault

The reverse directional characteristic is equal to the forward characteristic rotated


by 180 degrees.

The polarizing voltage is available as long as the positive-sequence voltage


exceeds 5% of the set base voltage UBase. So the directional element can use it for
all unsymmetrical faults including close-in faults.

For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.

The memory voltage is used for 100 ms or until the positive sequence voltage is
restored.

After 100 ms, the following occurs:

• If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set IED rated current IBase), the condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.
• If the current decreases below the minimum operating value, the memory
resets until the positive sequence voltage exceeds 10% of its rated value.

227
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.5.2.6 Simplified logic diagrams

Distance protection zones


The design of distance protection zone 1 is presented for all measuring: phase-to-
earth loops.

Phase-to-earth related signals are designated by LnE, where n represents the


corresponding phase number (L1E, L2E, and L3E).

Fulfillment of two different measuring conditions is necessary to obtain the one


logical signal for each separate measuring loop:

• Zone measuring condition, which follows the operating equations described


above.
• Group functional input signal (STCND), as presented in figure 126.

The STCND input signal represents a connection of six different integer values
from the phase selection function within the IED, which are converted within the
zone measuring function into corresponding boolean expressions for each
condition separately. It is connected to the Phase selection with load
enchroachment, quadrilateral characteristic (FDPSPDIS) function output STCNDZ.

The input signal DIRCND is used to give condition for directionality for the
distance measuring zones. The signal contains binary coded information for both
forward and reverse direction. The zone measurement function filter out the
relevant signals on the DIRCND input depending on the setting of the parameter
OperationDir. It shall be configured to the DIRCND output on the Directional
impedance element for mho characteristic (ZDMRDIR) function.

228
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

STCND

AND STNDL1N
L1N

AND STNDL2N
L2N

STNDL3N
L3N AND

OR STNDPE

OR
VTSZ STND
OR AND
BLOCK
BLK

en06000408.vsd
IEC06000408 V1 EN

Figure 126: Conditioning by a group functional input signal STCND

Composition of the phase starting signals for a case, when the zone operates in a non-
directional mode, is presented in figure 127.

STNDL1N 15 ms
AND t STL1

STNDL2N 15 ms
AND t STL2

STNDL3N 15 ms
AND t STL3

15 ms
AND t START
OR

BLK

en06000409.vsd
IEC06000409 V1 EN

Figure 127: Composition of starting signals in non-directional operating mode

Results of the directional measurement enter the logic circuits, when the zone
operates in directional (forward or reverse) mode, see figure 128.

229
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

STNDL1N
DIRL1N AND
OR STZMPE.
&
STNDL2N
DIRL2N AND

STNDL3N 15 ms
STL1
& t
DIRL3N AND

15 ms
STL2
& t

15 ms
STL3
& t

BLK

15 ms
OR START
& t

en07000081.vsd
IEC07000081 V1 EN

Figure 128: Composition of starting signals in directional operating mode

Tripping conditions for the distance protection zone one are symbolically presented
in figure 129.

Timer tPE=On tPE


AND t
STZMPE
15ms
BLKTR AND t
TRIP

STL1 AND TRL1

STL2 AND TRL2

STL3 AND TRL3

en07000082.vsd
IEC07000082 V1 EN

Figure 129: Tripping logic for the distance protection zone one

230
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.5.3 Function block


ZMMPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
BLKZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC06000454-2-en.vsd
IEC06000454 V2 EN

Figure 130: ZMMPDIS function block

ZMMAPDIS
I3P* TRIP
U3P* TRL1
BLOCK TRL2
BLKZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND

IEC09000947-1-en.vsd
IEC09000947 V1 EN

Figure 131: ZMMAPDIS function block

6.5.4 Input and output signals


Table 115: ZMMPDIS Input signals
Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

Table 116: ZMMPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
Table continues on next page

231
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Name Type Description


START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or
loop

Table 117: ZMMAPDIS Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Blocks all output by fuse failure signal
BLKTR BOOLEAN 0 Blocks all trip outputs
STCND INTEGER 0 External start condition (loop enabler)
DIRCND INTEGER 0 External directional condition

Table 118: ZMMAPDIS Output signals


Name Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
START BOOLEAN General Start, issued from any phase or loop
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STND BOOLEAN Non-directional start, issued from any phase or
loop

6.5.5 Setting parameters


Table 119: ZMMPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
Table continues on next page

232
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Name Values (Range) Unit Step Default Description


OperationDir Off - - Forward Operation mode of directionality NonDir /
Non-directional Forw / Rev
Forward
Reverse
X1 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach
R1 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.50 - 9000.00 ohm/p 0.01 100.00 Zero sequence reactance reach
R0 0.50 - 3000.00 ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
RFPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-E
Timer tPE Off - - On Operation mode Off / On of Zone timer,
On Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops
IMinOpIN 5 - 30 %IB 1 5 Minimum operate residual current for
Phase-Earth loops

Table 120: ZMMAPDIS Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Off - - Forward Operation mode of directionality NonDir /
Non-directional Forw / Rev
Forward
Reverse
X1 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach
R1 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.50 - 9000.00 ohm/p 0.01 120.00 Zero sequence reactance reach
R0 0.50 - 3000.00 ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
RFPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-E
Timer tPE Off - - On Operation mode Off / On of Zone timer,
On Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops

233
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.5.6 Technical data


Table 121: ZMMPDIS technical data
Function Range or value Accuracy
Number of zones with selectable direction -
Minimum operate current (10-30)% of IBase -
Positive sequence reactance (0.50-3000.00) W/phase ± 2.0% static accuracy
± 2.0 degrees static angular
Positive sequence resistance (0.10-1000.00) Ω/phase accuracy
Zero sequence reactance (0.50-9000.00) Ω/phase Conditions:
Voltage range: (0.1-1.1) x Ur
Zero sequence resistance (0.50-3000.00) Ω/phase Current range: (0.5-30) x Ir
Fault resistance, Ph-E (1.00-9000.00) W/loop Angle: at 0 degrees and 85
degrees
Dynamic overreach <5% at 85 degrees measured -
with CCVT’s and 0.5<SIR<30
Impedance zone timers (0.000-60.000) s ± 0.5% ± 10 ms
Operate time 24 ms typically -
Reset ratio 105% typically -
Reset time 30 ms typically -

6.6 Directional impedance element for mho


characteristic and additional distance protection
directional function for earth faults ZDMRDIR,
ZDARDIR

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional impedance element for mho ZDMRDIR 21D
characteristic

S00346 V1 EN

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Additional distance protection ZDARDIR -
directional function for earth faults

S00346 V1 EN

234
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.6.1 Introduction
The phase-to-earth impedance elements can be optionally supervised by a phase
unselective directional function based on symmetrical components.

6.6.2 Principle of operation

6.6.2.1 Directional impedance element for mho characteristic ZDMRDIR

The evaluation of the directionality takes place in Directional impedance element


for mho characteristic (ZDMRDIR). Equation 50 and equation 51 are used to
classify that the fault is in the forward direction for phase-to-earth fault and phase-
to-phase fault respectively.

0.85 × U1L1 + 0.15 × U1L1M


- ArgDir < arg < ArgNeg Re s
I L1
EQUATION1617 V1 EN (Equation 50)

0.85 × U1L1L 2 + 0.15 × U1L1L 2M


- ArgDir < arg < ArgNeg Re s
I L1L 2
EQUATION1619 V1 EN (Equation 51)

Where:
ArgDir Setting for the lower boundary of the forward directional characteristic, by default set to
15 (= -15 degrees)
ArgNegRes Setting for the upper boundary of the forward directional characteristic, by default set to
115 degrees, see figure 132 for mho characteristics.
U1L1 Positive sequence phase voltage in phase L1

U1L1M Positive sequence memorized phase voltage in phase L1

IL1 Phase current in phase L1

U1L1L2 Voltage difference between phase L1 and L2 (L2 lagging L1)

U1L1L2M Memorized voltage difference between phase L1 and L2 (L2 lagging L1)

IL1L2 Current difference between phase L1 and L2 (L2 lagging L1)

The default settings for ArgDir and ArgNegRes are 15 (= -15) and 115 degrees
respectively (see figure 132) and they should not be changed unless system studies
show the necessity.

If one sets DirEvalType to Comparator (which is recommended when using the


mho characteristic) then the directional lines are computed by means of a comparator-
type calculation, meaning that the directional lines are based on mho-circles (of
infinite radius). The default setting value Impedance otherwise means that the

235
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

directional lines are implemented based on an impedance calculation equivalent to


the one used for the quadrilateral impedance characteristics.

When Directional impedance element for mho characteristic


(ZDMRDIR) is used together with Fullscheme distance protection,
mho characteristic (ZMHPDIS) the following settings for
parameter DirEvalType is vital:
• alternative Comparator is strongly recommended
• alternative Imp/Comp should generally not be used
• alternative Impedance should not be used. This altenative is
intended for use together with Distance protection zone,
quadrilateral characteristic (ZMQPDIS)

X
Zset reach point

ArgNegRes

-ArgDir R

-Zs
en06000416.vsd

IEC06000416 V1 EN

Figure 132: Setting angles for discrimination of forward fault

The reverse directional characteristic is equal to the forward characteristic rotated


by 180 degrees.

The polarizing voltage is available as long as the positive-sequence voltage


exceeds 5% of the set base voltage UBase. So the directional element can use it for
all unsymmetrical faults including close-in faults.

For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.

The memory voltage is used for 100ms or until the positive sequence voltage is
restored. After 100ms, the following occurs:

236
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

• If the current is still above the set value of the minimum operating current the
condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.
• If the current decreases below the minimum operating value, no directional
indications will be given until the positive sequence voltage exceeds 10% of
its rated value.

The Directional impedance element for mho characteristic (ZDMRDIR) function


has the following output signals:

The STDIRCND output provides an integer signal that depends on the evaluation
and is derived from a binary coded signal as follows:

bit 11 bit 10 bit 9 bit 8 bit 7 bit 6


(2048) (1024) (512) (256) (128) (64)
STRVL3L1= STRVL2L3= STRVL1L2= STRVL3N=1 STRVL2N=1 STRVL1N=1
1 1 1
bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
(32) (16) (8) (4) (2) (1)
STFWL3L1= STFWL2L3= STFWL1L2= STFWL3N=1 STFWL2N=1 STFWL1N=1
1 1 1

The STFW output is a logical signal with value 1 or 0. It is made up as an OR-


function of all the forward starting conditions, that is, STFWL1N, STFWL2N,
STFWL3N, STFWL1L2, STFWL2L3 and STFWL3L1. The STRV output is
similar to the STFW output, the only difference being that it is made up as an OR-
function of all the reverse starting conditions, that is, STRVL1N, STRVL2N,
STRVL3N, STRVL1L2, STRVL2L3 and STRVL3L1.

Values for the following parameters are calculated, and may be viewed as service
values:

• resistance phase L1
• reactance phase L1
• resistance phase L2
• reactance phase L2
• resistance phase L3
• reactance phase L3
• direction phase L1
• direction phase L2
• direction phase L3

237
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.6.2.2 Additional distance protection directional function for earth faults


ZDARDIR

A Mho element needs a polarizing voltage for its operation. The positive-sequence
memory-polarized elements are generally preferred. The benefits include:

• The greatest amount of expansion for improved resistive coverage. These


elements always expand back to the source.
• Memory action for all fault types. This is very important for close-in three-
phase faults.
• A common polarizing reference for all six distance-measuring loops. This is
important for single-pole tripping, during a pole-open period.

There are however some situations that can cause security problems like reverse
phase to phase faults and double phase-to-earth faults during high load periods. To
solve these, additional directional element is used.

For phase-to-earth faults, directional elements using sequence components are very
reliable for directional discrimination. The directional element can be based on one
of following types of polarization:

• Zero-sequence voltage
• Negative-sequence voltage
• Zero-sequence current

These additional directional criteria are evaluated in the Additional distance


protection directional function for earth faults (ZDARDIR).

Zero-sequence voltage polarization is utilizing the phase relation between the zero-
sequence voltage and the zero-sequence current at the location of the protection.
The measurement principle is illustrated in figure 133.

238
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

- 3U 0

AngleOp
AngleRCA

3I 0

en06000417.vsd
IEC06000417 V1 EN

Figure 133: Principle for zero-sequence voltage polarized additional directional


element

Negative-sequence voltage polarization is utilizing the phase relation between the


negative-sequence voltage and the negative-sequence current at the location of the
protection.

Zero-sequence current polarization is utilizing the phase relation between the zero-
sequence current at the location of the protection and some reference zero-
sequence current, for example, the current in the neutral of a power transformer.

The principle of zero-sequence voltage polarization with zero-sequence current


compensation is described in figure 134. The same also applies for the negative-
sequence function.

Z0 SA I0 I0
Z0 Line Z0 SB
Charac te ris tic
ang le
U0 U0
K*I0

U0 + K*I0
IF
en06000418.vsd
IEC06000418 V1 EN

Figure 134: Principle for zero sequence compensation

Note that the sequence based additional directional element cannot give per phase
information about direction to fault. This is why it is an AND-function with the
normal directional element that works on a per phase base. The release signals are
per phase and to have a release of a measuring element in a specific phase both the
additional directional element, and the normal directional element, for that phase
must indicate correct direction.

239
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Normal
directional Release of distance
element measuring element
L1N, L2N, L3N L1N, L2N, L3N
AND

Additional
directional AND per
element phase

en06000419.vsd
IEC06000419 V1 EN

Figure 135: Earth distance element directional supervision

6.6.3 Function block


ZDMRDIR
I3P* DIR_CURR
U3P* DIR_VOLT
DIR_POL
STFW
STRV
STDIRCND

IEC06000422_2_en.vsd
IEC06000422 V2 EN

Figure 136: ZDMRDIR function block

ZDARDIR
I3P* STFWPE
U3P* STRVPE
I3PPOL* DIREFCND
DIRCND

IEC06000425-2-en.vsd
IEC06000425 V2 EN

Figure 137: ZDARDIR function block

6.6.4 Input and output signals


Table 122: ZDMRDIR Input signals
Name Type Default Description
I3P GROUP - group connection for current abs 1
SIGNAL
U3P GROUP - group connection for voltage abs 1
SIGNAL

240
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Table 123: ZDMRDIR Output signals


Name Type Description
DIR_CURR GROUP SIGNAL Group connection
DIR_VOLT GROUP SIGNAL Group connection
DIR_POL GROUP SIGNAL Group connection
STFW BOOLEAN Start in forward direction
STRV BOOLEAN Start in reverse direction
STDIRCND INTEGER Binary coded directional information per
measuring loop

Table 124: ZDARDIR Input signals


Name Type Default Description
I3P GROUP - Current signals
SIGNAL
U3P GROUP - Voltage signals
SIGNAL
I3PPOL GROUP - Polarisation current signals
SIGNAL
DIRCND INTEGER 0 Binary coded directional signal

Table 125: ZDARDIR Output signals


Name Type Description
STFWPE BOOLEAN Forward start signal from phase-to-ground
directional element
STRVPE BOOLEAN Reverse start signal from phase-to-ground
directional element
DIREFCND INTEGER Start direction Binary coded

6.6.5 Setting parameters


Table 126: ZDMRDIR Group settings (basic)
Name Values (Range) Unit Step Default Description
IBase 1 - 99999 - 1 3000 Base setting for current level
UBase 0.05 - 2000.00 - 0.05 400.00 Base setting for voltage level
DirEvalType Impedance - - Comparator Directional evaluation mode Impedance /
Comparator Comparator
Imp/Comp
ArgNegRes 90 - 175 Deg 1 115 Angle of blinder in second quadrant for
forward direction
ArgDir 5 - 45 Deg 1 15 Angle of blinder in fourth quadrant for
forward direction
IMinOpPE 5 - 30 %IB 1 5 Minimum operate phase current for
Phase-Earth loops
IMinOpPP 5 - 30 %IB 1 10 Minimum operate delta current for Phase-
Phase loops

241
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Table 127: ZDARDIR Group settings (basic)


Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Base setting for current values
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level in kV
PolMode -3U0 - - -3U0 Polarization quantity for opt dir function
-U2 for P-E faults
IPol
Dual
-3U0Comp
-U2comp
AngleRCA -90 - 90 Deg 1 75 Characteristic relay angle (= MTA or
base angle)
I> 1 - 200 %IB 1 5 Minimum operation current in % of IBase
UPol> 1 - 100 %UB 1 1 Minimum polarizing voltage in % of UBase
IPol> 5 - 100 %IB 1 10 Minimum polarizing current in % of IBase

Table 128: ZDARDIR Group settings (advanced)


Name Values (Range) Unit Step Default Description
AngleOp 90 - 180 Deg 1 160 Operation sector angle
Kmag 0.50 - 3000.00 ohm 0.01 40.00 Boost-factor in -U0comp and -U2comp
polarization

6.7 Mho impedance supervision logic ZSMGAPC

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Mho Impedance supervision logic ZSMGAPC - -

6.7.1 Introduction
The Mho impedance supervision logic (ZSMGAPC) includes features for fault
inception detection and high SIR detection. It also includes the functionality for
loss of potential logic as well as for the pilot channel blocking scheme.

ZSMGAPC can mainly be decomposed in two different parts:

1. A fault inception detection logic


2. High SIR detection logic

242
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.7.2 Principle of operation

6.7.2.1 Fault inception detection

The aim for the fault inception detector is to detect quickly that a fault has occurred
on the system.

The fault inception detection detects instantaneous changes in any phase currents
or zero sequence current in combination with a change in the corresponding phase
voltage or zero sequence voltage. If the change of any phase current and
corresponding phase voltage or 3U0 and 3I0 exceeds the settings DeltaI and
DeltaU respectively. Delta3U0 and Delta3I0 and the input signal BLOCK is not
activated, the output signal FLTDET is activated indicating that a system fault has
occurred.

If the setting PilotMode is set to On in blocking scheme and the fault inception
function has detected a system fault, a block signal BLKCHST will be issued and
send to remote end in order to block the overreaching zones. Different criteria has
to be fulfilled for sending the BLKCHST signal:

1. The setting PilotMode has to be set to On


2. The breaker has to be closed, that is, the input signal CBOPEN has to be
deactivated
3. A reverse fault should have been detected while the carrier send signal is not
blocked, that is, input signal REVSTART is activated and input signal
BLOCKCS is not activated

Or

A fault inception is detected

If it is later detected that it was an internal fault that made the function issue the
BLKCHST signal, the function will issue a CHSTOP signal to unblock the remote
end. The criteria that have to be fulfilled for this are:

1. The function has to be in pilot mode, that is, the setting PilotMode has to be
set to On
2. The carrier send signal should be blocked, that is, input signal BLOCKCS is
On and,
3. A reverse fault should not have been detected while the carrier send signal was
not blocked, that is, input signals REVSTART and BLOCKCS is not activated.

ZSMGAPC function has a built in loss of voltage detection based on the evaluation
of the change in phase voltage or the change in zero sequence voltage (3U0). It
operates if the change in phase voltages exceeds the setting DeltaU or 3U0 exceeds
the setting Delta3U0.

If loss of voltage is detected, but not a fault inception, the distance protection
function will be blocked. This is also the case if a fuse failure is detected by the

243
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

external fuse failure function and activate the input FUSEFAIL. Those blocks are
generated by activating the output BLKZ, which shall be connected to the input
BLKZ on the distance Mho function block.

During fault inception a lot of transients will be developed which in turn might
cause the distance function to overreach. The Mho supervision logic (ZSMGAPC)
will increase the filtering during the most transient period of the fault. This is done
by activating the output BLKZMD, which shall be connected to the input
BLKZMTD on mho distance function block.

High SIR detection


High SIR values increases the likelihood that CVT will introduce a prolonged and
distorted transient, increasing the risk for overreach of the distance function.

The SIR function calculates the SIR value as the source impedance divided by the
setting Zreach and activates the output signal HSIR if the calculated value for any
of the six basic shunt faults exceed the setting SIRLevel. The HSIR signal is
intended to block the delta based mho impedance function.

6.7.3 Function block


ZSMGAPC
I3P* BLKZMTD
U3P* BLKCHST
BLOCK CHSTOP
REVSTART HSIR
BLOCKCS
CBOPEN

IEC06000426-2-en.vsd
IEC06000426 V2 EN

Figure 138: ZSMGAPC function block

6.7.4 Input and output signals


Table 129: ZSMGAPC Input signals
Name Type Default Description
I3P GROUP - Three phase current samples and DFT magnitude
SIGNAL
U3P GROUP - Three phase phase-neutral voltage samples and
SIGNAL DFT magnitude
BLOCK BOOLEAN 0 Block of the function
REVSTART BOOLEAN 0 Indication of reverse start
BLOCKCS BOOLEAN 0 Blocks the blocking carrier signal to remote end
CBOPEN BOOLEAN 0 Indicates that the breaker is open

244
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Table 130: ZSMGAPC Output signals


Name Type Description
BLKZMTD BOOLEAN Block signal for blocking of time domained mho
BLKCHST BOOLEAN Blocking signal to remote end to block
overreaching zone
CHSTOP BOOLEAN Stops the blocking signal to remote end
HSIR BOOLEAN Indication of source impedance ratio above set limit

6.7.5 Setting parameters


Table 131: ZSMGAPC Group settings (basic)
Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Base value for current measurement
UBase 0.05 - 2000.00 kV 0.05 400.00 Base value for voltage measurement
PilotMode Off - - Off Pilot mode Off/On
On
Zreach 0.1 - 3000.0 ohm 0.1 38.0 Line impedance
IMinOp 10 - 30 %IB 1 20 Minimum operating current for SIR
measurement

Table 132: ZSMGAPC Group settings (advanced)


Name Values (Range) Unit Step Default Description
DeltaI 0 - 200 %IB 1 10 Current change level in %IB for fault
inception detection
Delta3I0 0 - 200 %IB 1 10 Zero seq current change level in % of IB
DeltaU 0 - 100 %UB 1 5 Voltage change level in %UB for fault
inception detection
Delta3U0 0 - 100 %UB 1 5 Zero seq voltage change level in % of UB
SIRLevel 5 - 15 - 1 10 Settable level for source impedance ratio

6.8 Faulty phase identification with load encroachment


FMPSPDIS

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Faulty phase identification with load FMPSPDIS 21
encroachment for mho

S00346 V1 EN

245
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.8.1 Introduction
The operation of transmission networks today is in many cases close to the stability
limit. Due to environmental considerations the rate of expansion and reinforcement
of the power system is reduced, for example difficulties to get permission to build
new power lines. The ability to accurate and reliable classifying the different types
of fault so that single phase tripping and autoreclosing can be used plays an
important roll in this matter.

The phase selection function is design to accurate select the proper fault loop in the
distance function dependent on the fault type.

The heavy load transfer that is common in many transmission networks may in
some cases interfere with the distance protection zone reach and cause unwanted
operation. Therefore the function has a built in algorithm for load encroachment,
which gives the possibility to enlarge the resistive setting of the measuring zones
without interfering with the load.

The output signals from the phase selection function produce important
information about faulty phase(s), which can be used for fault analysis as well.

6.8.2 Principle of operation

6.8.2.1 The phase selection function

Faulty phase identification with load encroachment for mho (FMPSPDIS) function
can be decomposed into six different parts:

1. A high speed delta based current phase selector


2. A high speed delta based voltage phase selector
3. A symmetrical components based phase selector
4. Fault evaluation and selection logic
5. A load encroachment logic
6. A blinder logic

The total function can be blocked by activating the input BLOCK.

Delta based current and voltages


The delta based fault detection function uses adaptive technique and is based on
patent US4409636.

The aim of the delta based phase selector is to provide very fast and reliable phase
selection for releasing of tripping from the high speed Mho measuring element and
is essential to Directional Comparison Blocking scheme (DCB), which uses Power
Line Carrier (PLC) communication system across the protected line.

The current and voltage samples for each phase passes through a notch filter that
filters out the fundamental components. Under steady state load conditions or when
no fault is present, the output of the filter is zero or close to zero. When a fault

246
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

occurs, currents and voltages change resulting in sudden changes in the currents
and voltages resulting in non-fundamental waveforms being introduced on the line.
At this point the notch filter produces significant non-zero output. The filter output
is processed by the delta function. The algorithm uses an adaptive relationship
between phases to determine if a fault has occurred, and determines the faulty phases.

The current and voltage delta based phase selector gives a real output signal if the
following criterion is fulfilled (only phase L1 shown):

Max(ΔUL1,ΔUL2,ΔUL3)>DeltaUMinOp

Max(ΔIL1,ΔIL2,ΔIL3)>DeltaIMinOp

where:
ΔUL1, ΔUL2 and ΔUL3 are the voltage change between sample t and sample t-1
DeltaUMinOp and DeltaIMinOp are the minimum harmonic level settings for the voltage and current
filters to decide that a fault has occurred. A slow evolving fault may not
produce sufficient harmonics to detect the fault; however, in such a
case speed is no longer the issue and the sequence components
phase selector will operate.

The delta voltages ΔULn and delta current ΔILn (n prefix for phase order) are the
voltage and current between sample t and sample t-1.

The delta phase selector employs adaptive techniques to determine the fault type.
The logic determines the fault type by summing up all phase values and dividing
by the largest value. Both voltages and currents are filtered out and evaluated. The
condition for fault type classification for the voltages and currents can be expressed
as:

S( DUL1, DUL2, DUL3)


Fa ulType =
Ma x( DIL1, DIL2, DUL3)
EQUATION1621 V1 EN (Equation 52)

S( DIL1, DIL2, DIL3)


Fa ultType =
Ma x( DIL1, DIL2, DIL3)
EQUATION1622 V1 EN (Equation 53)

The value of FaultType for different shunt faults are as follows:

Under ideal conditions: (Patent pending)


Single phase-to-earth; FaultType=1
Phase-to-phase fault FaultType=2
Three-phase fault; FaultType=3

247
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

The output signal is 1 for single phase-to-earth fault, 2 for phase-to-phase fault and
3 for three-phase fault. At this point the filter does not know if earth was involved
or not.

Typically there are induced harmonics in the non-faulted lines that will affect the
result. This method allows for a significant tolerance in the evaluation of FaultType
over its entire range.

When a single phase-to-earth fault has been detected, the logic determines the
largest quantity, and asserts that phase. If phase-to-phase fault is detected, the two
largest phase quantities will be detected and asserted as outputs.

The faults detected by the delta based phase selector are coordinated in a separate
block. Different phases of faults may be detected at slightly different times due to
differences in the angles of incidence of fault on the wave shape. Therefore the
output is forced to wait a certain time by means of a timer. If the timer expires, and
a fault is detected in one phase only, the fault is deemed as phase-to-earth. This
way a premature single phase-to-earth fault detection is not released for a phase-to-
phase fault. If, however, earth current is detected before the timer expires, the phase-
to-earth fault is released sooner.

If another phase picks up during the time delay, the wait time is reduced by a
certain amount. Each detection of either earth-to-phase or additional phases further
reduce the initial time delay and allow the delta phase selector output to be faster.
There is no time delay, if for example, all three phases are faulty.

The delta function is released if the input DELTAREL is activated at the same time
as input DELTABLK is not activated. Activating the DELTABLK input will block
the delta function. The release signal has an internal pulse timer of 100 ms. When
the DELTAREL signal has disappeared the delta logic is reset. In order not to get
too abrupt change, the reset is decayed in pre-defined steps.

Symmetrical component based phase selector


The symmetrical component phase selector uses preprocessed calculated sequence
voltages and currents as inputs. It also uses sampled values of the phase currents.
All the symmetrical quantities mentioned further in this section are with reference
to phase L1.

The function is made up of four main parts:

A Detection of the presence of earth fault


B A phase-to-phase logic block based on U1/U2 angle relationship

C A phase-to-earth component based on patent US5390067 where the angle relationships


between U2/I0 and U2/U1 is evaluated to determine earth fault or phase- to-phase to earth fault

D Logic for detection of three-phase fault

248
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Presence of earth-fault detection


This detection of earth fault is performed in two levels, first by evaluation of the
magnitude of zero sequence current, and secondly by the evaluation of the zero and
negative sequence voltage. It is a complement to the earth-fault signal built-in in
the Symmetrical component based phase selector.

The complementary based zero-sequence current function evaluates the presence of


earth fault by calculating the 3I0 and comparing the result with the setting
parameter INRelPE. The output signal is used to release the earth-fault loop. It is a
complement to the earth-fault signal built-in in the sequence based phase selector.
The condition for releasing the phase-to-earth loop is as follows:

The output from this detection is used to release the earth-fault loop.

|3I0|>maxIph: INRelPE

where:
|3I0| is the magnitude of the zero sequence current 3I0

maxIph is the maximum magnitude of the phase currents


INRelPE is a setting parameter for the relation between the magnitude of 3I0 and the
maximum phase current

The earth-fault loop is also released if the evaluation of the zero sequence current
by the main sequence function meets the following conditions:

|3I0|>IBase · 0.5

|3I0|>maxIph ·INRelPE

where:
maxIph is the maximal current magnitude found in any of the three phases
INRelPE is the setting of 3I0 limit for release of phase-to-earth measuring loop in % of IBase
IBase is the global setting of the base current (A)

In systems where the source impedance for zero sequence is high the change of
zero sequence current may not be significant and the above detection may fail. In
those cases the detection enters the second level, with evaluation of zero and
negative sequence voltage. The release of the earth-fault loops can then be
achieved if all of the following conditions are fulfilled:

|3U0|>|U2| · 0.5

|3U0|>|U1| · 0.2

|U1|> UBase · 0.2/√(3)

and

249
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

3I0> 0.1 · IBase

or

3I0<maxIph · INRelPE

where:
3U0 is the magnitude of the zero sequence voltage

U2 is the magnitude of the negative sequence voltage at the relay measuring point of
phase L1
k5 is design parameter
ILmax is the maximal phase current
IMinOp is the setting of minimum operate phase current in % of IBase

Phase-to-phase fault detection


The detection of phase-to-phase fault is performed by evaluation of the angle
difference between the sequence voltages U2 and U1.

60°
UL3

L3-L1 sector

UL2 0°
180° L2-L3 sector U1L1 (Ref)

L1-L2 sector
UL1

300°
en06000383.vsd
IEC06000383 V1 EN

Figure 139: Definition of fault sectors for phase-to-phase fault

The phase-to-phase loop for the faulty phases will be determined if the angle
between the sequence voltages U2 and U1 lies within the sector defined according
to figure 139 and the following conditions are fulfilled:

|U1|>U1MinOP

|U2|>U2MinOp

where:
U1MinOP and U2MinOp are the setting parameters for positive sequence and negative sequence
minimum operate voltages

250
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

The positive sequence voltage U1L1 in figure 139 above is reference.

If there is a three-phase fault, there will not be any release of the individual phase
signals, even if the general conditions for U2 and U1 are fulfilled.

Phase-to-earth and phase-to-phase-to-earth-fault detection


The detection of phase-to-earth and phase-to-phase-to-earth fault (US patent
5390067) is based on two conditions:

1. Angle relationship between U2 and I0

2. Angle relationship between U2 and U1

The condition 1 determines faulty phase at single phase-to-earth fault by determine


the argument between U2 and I0.

80°

L2-E sector L3-E sector

200°
L1-E sector
320°

IEC06000384-2-en.vsd
IEC06000384 V2 EN

Figure 140: Condition 1: Definition of faulty phase sector as angle between U2


and I0

The angle is calculated in a directional function block and gives the angle in
radians as input to the U2 and I0 function block. The input angle is released only if
the fault is in forward direction. This is done by the directional element. The fault
is classified as forward direction if the angle between U0 and I0 lies between 20 to
200 degrees, see figure 141.

251
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Forward 20°

200° Reverse

en06000385.vsd

IEC06000385 V1 EN

Figure 141: Directional element used to release the measured angle between
Uo and I0

The input radians are summarized with an offset angle and the result evaluated. If
the angle is within the boundaries for a specific sector, the phase indication for that
sector will be active see figure 140. Only one sector signal is allowed to be
activated at the same time.

The sector function for condition 1 has an internal release signal which is active if
the main sequence function has classified the angle between U0 and I0 as valid. The
following conditions must be fulfilled for activating the release signals:

|U2|>U2MinOp

|3I0|> 0.05 · IBase

|3I0|>maxIph · INRelPE

where:
U2 and IN are the magnitude of the negative sequence voltage and zero-
sequence current (3I0)

U2MinOp is the setting parameter for minimum operating negative sequence


voltage
maxIph is the maximum phase current
INRelPE is the setting parameter for 3I0 limit for releasing phase-to-earth loop

The angle difference is phase shifted by 180 degrees if the fault is in reverse direction.

The condition 2 looks at the angle relationship between the negative sequence
voltage U2 and the positive sequence voltage U1. Since this is a phase-to-phase
voltage relationship, there is no need for shifting phases if the fault is in reverse
direction. A phase shift is introduced so that the fault sectors will have the same
angle boarders as for condition 1. If the calculated angle between U2 and U1 lies

252
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

within one sector, the corresponding phase for that sector will be activated. The
condition 2 is released if both the following conditions are fulfilled:

|U2|>U2MinOp

|U1|>U1MinOP

where:
|U1| and |U2| are the magnitude of the positive and negative sequence voltages.

U1MinOP and U2MinOp are the setting parameters for positive sequence and negative sequence
minimum operating voltages.

140°
L3-E sector
20°

U1L1
(Ref)
L1-E sector
L2-E sector

260° IEC06000413_2_en.vsd
IEC06000413 V2 EN

Figure 142: Condition 2: U2 and U1 angle relationship

If both conditions are true and there is sector match, the fault is deemed as single
phase-to-earth. If the sectors, however, do not match the fault is determined to be
the complement of the second condition, that is, a phase-to-phase-to- earth fault.

Condition 1 and Condition 2 ⇒ Fault type


L3-E L3-E L3-E
L2-E L1-E L2-L3-E

The sequence phase selector is blocked when earth is not involved or if a three-
phase fault is detected.

Three-phase fault detection


Unless it has been categorized as a single or two-phase fault, the function classifies
it as a three-phase fault if the following conditions are fulfilled:

|U1|<U1Level

253
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

and

|I1|>I1LowLevel

or

|I1|>IMaxLoad

where:
|U1| and |I1| are the positive sequence voltage and current magnitude

U1Level , are the setting of limits for positive sequence voltage and current
I1LowLevel
IMaxLoad is the setting of the maximum load current

The output signal for detection of three-phase fault is only released if not earth
fault and phase-to-phase fault in the main sequence function is detected.

The conditions for not detecting earth fault are the inverse of equation 5 to 10.

The condition for not detecting phase-to-phase faults is determined by three


conditions. Each of them gives condition for not detecting phase-to-phase fault.
Those are:

1:
earth fault is detected
or
|3I0IN|> 0.05 · IBase

and
|3I0IN|>maxIph ·INRelPE

2:
phase-to-earth and phase-to-phase faults are not fulfilled
and
maxIph<0.1 · IBase
and
|I2|<0.1 · maxIph

3:
|3I0IN|>maxIph · INBlockPP

or
|I2|<maxIph · I2maxIL

where:
maxIph is the maximum of the phase currents IL1, IL2 and IL3
INRelPE is the setting parameter for 3I0 limit for release of phase-to-earth fault loops
Table continues on next page

254
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

|I2| is the magnitude of the negative sequence current

I2ILmax is the setting parameter for the relation between negative sequence current
to the maximum phase current in percent of IBase
INBlockPP is the setting parameter for 3I0 limit for blocking phase to phase measuring
loops

Fault evaluation and selection logic


The phase selection logic has an evaluation procedure that can be simplified
according to figure 143. Only phase L1 is shown in the figure. If the internal signal
3 Phase fault is activated, all four outputs START, STL1, STL2 and STL3 gets
activated.

a a>b FaultPriority
DeltaIL1 then c=a c Adaptive release
b else c=a dependent on result
from Delta logic
DeltaUL1

Sequence based
function a<b
a
L1L2 fault
then c=b c
OR b else c=a OR
L1N fault

3 Phase fault

STL1
IL1Valid &

BLOCK

en06000386.vsd
IEC06000386 V1 EN

Figure 143: Simplified diagram for fault evaluation, phase L1

Load encroachment logic


Each of the six measuring loops has its own load (encroachment) characteristic
based on the corresponding loop impedance. The load encroachment functionality
is always activated in faulty phase identification with load encroachment for mho
(FMPSPDIS) function but the influence on the zone measurement can be switched
On/Offin the respective impedance measuring function.

The outline of the characteristic is presented in figure 144. As illustrated, the


resistive reach in forward and reverse direction and the angle of the sector is the
same in all four quadrants. The reach for the phase selector will be reduced by the
load encroachment function, as shown in figure 144.

255
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Blinder
Blinder provides a mean to discriminate high load from a fault. The operating
characteristic is illustrated in figure 144. There are six individual measuring loops
with the blinder functionality. Three phase-to-earth loops which estimate the
impedance according to

Zn = Uph / Iph

and three phase-to-phase loops according to

Zph-ph = Uph-ph / Iph-ph

The start operations from respective loop are binary coded into one word and
provides an output signal STCNDPLE.
X jX

Operation area Operation area

RLd
ArgLd ArgLd
R

ArgLd R
ArgLd
RLd

Operation area

No operation area No operation area

en06000414.vsd
IEC06000414 V1 EN

Figure 144: Influence on the characteristic by load encroachment logic

Outputs
The output of the sequence components based phase selector and the delta logic
phase selector activates the output signals STL1, STL2 and STL3. If an earth fault
is detected the signal STPE gets activated.

The phase selector also gives binary coded signals that are connected to the zone
measuring element for opening the correct measuring loop(s). This is done by the
signal STCNDPHS. If only one phase is started (L1, L2 or L3), the corresponding
phase-to- element is enabled. STPE is expected to be made available for two-phase
and three-phase faults for the correct output to be selected. The fault loop is
indicated by one of the decimal numbers below.

The output STCNDPHS provides release information from the phase selection part
only. STCNDLE provides release information from the load encroachment part
only. STCNDPLE provides release information from the phase selection part and

256
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

the load encroachment part combined, that is, both parts have to issue a release at
the same time (this signal is normally not used in the zone measuring element). In
these signals, each fault type has an associated value, which represents the
corresponding zone measuring loop to be released. The values are presented in
table 132.

0= no faulted phases
1= L1E
2= L2E
3= L3E
4= -L1L2E
5= -L2L3E
6= -L3L1E
7= -L1L2L3E
8= -L1L2
9= -L2L3
10= -L3L1
11= L1L2L3

An additional logic is applied to handle the cases when phase-to-earth outputs are
to be asserted when the earth input G is not asserted.

The output signal STCNDPLE is activated when the load encroachment is operating.

STCNDPLE is connected to the input STCND for selected quadrilateral impedance


measuring zones to be blocked. The signal must be connected to the input LDCND
for selected mho impedance measuring zones .

The load encroachment at the measuring zone must be activated to


release the blocking from the load encroachment function.

6.8.3 Function block


FMPSPDIS
I3P* STL1
U3P* STL2
BLOCK STL3
ZSTART STPE
TR3PH STCNDPHS
1POLEAR STCNDPLE
STCNDLE
START

IEC06000429-2-en.vsd
IEC06000429 V2 EN

Figure 145: FMPSPDIS function block

257
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.8.4 Input and output signals


Table 133: FMPSPDIS Input signals
Name Type Default Description
I3P GROUP - Group signal for current
SIGNAL
U3P GROUP - Group signal for voltage
SIGNAL
BLOCK BOOLEAN 0 Block of function
ZSTART BOOLEAN 0 Start from underimpdeance function
TR3PH BOOLEAN 0 Three phase tripping initiated
1POLEAR BOOLEAN 0 Single pole autoreclosing in progress

Table 134: FMPSPDIS Output signals


Name Type Description
STL1 BOOLEAN Fault detected in phase L1
STL2 BOOLEAN Fault detected in phase L2
STL3 BOOLEAN Fault detected in phase L3
STPE BOOLEAN Earth fault detected
STCNDPHS INTEGER Binary coded starts from phase selection
STCNDPLE INTEGER Binary coded starts from ph sel with load
encroachment
STCNDLE INTEGER Binary coded starts from load encroachment only
START BOOLEAN Indicates that something has started

6.8.5 Setting parameters


Table 135: FMPSPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Base current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
IMaxLoad 10 - 5000 %IB 1 200 Maximum load for identification of three
phase fault in % of IBase
RLd 1.00 - 3000.00 ohm/p 0.01 80.00 Load encroachment resistive reach in
ohm/phase
ArgLd 5 - 70 Deg 1 20 Load encroachment inclination of load
angular sector

258
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Table 136: FMPSPDIS Group settings (advanced)


Name Values (Range) Unit Step Default Description
DeltaIMinOp 5 - 100 %IB 1 10 Delta current level in % of IBase
DeltaUMinOp 5 - 100 %UB 1 20 Delta voltage level in % of UBase
U1Level 5 - 100 %UB 1 80 Pos seq voltage limit for identification of 3-
ph fault
I1LowLevel 5 - 200 %IB 1 10 Pos seq current level for identification of
3-ph fault in % of IBase
U1MinOp 5 - 100 %UB 1 20 Minimum operate positive sequence
voltage for ph sel
U2MinOp 1 - 100 %UB 1 5 Minimum operate negative sequence
voltage for ph sel
INRelPE 10 - 100 %IB 1 20 3I0 limit for release ph-e measuring
loops in % of max phase current
INBlockPP 10 - 100 %IB 1 40 3I0 limit for blocking phase-to-phase
measuring loops in % of max phase
current

6.8.6 Technical data


Table 137: FMPSPDIS technical data
Function Range or value Accuracy
Minimum operate current (5-30)% of IBase ± 1.0% of Ir

Load encroachment criteria: (0.5–3000) W/phase ± 2.0% static accuracy


Load resistance, forward and (5–70) degrees Conditions:
reverse Voltage range: (0.1–1.1) x Un
Current range: (0.5–30) x In
Angle: at 0 degrees and 85 degrees

6.9 Power swing detection ZMRPSB

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Power swing detection ZMRPSB 68

Zpsb

SYMBOL-EE V1 EN

6.9.1 Introduction
Power swings may occur after disconnection of heavy loads or trip of big
generation plants.

259
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Power swing detection function (ZMRPSB) is used to detect power swings and
initiate block of selected distance protection zones. Occurrence of earth-fault
currents during a power swing can block ZMRPSB function to allow fault clearance.

6.9.2 Principle of operation


Power swing detection (ZMRPSB ) function comprises an inner and an outer
quadrilateral measurement characteristic with load encroachment, as shown in
figure 146.

Its principle of operation is based on the measurement of the time it takes for a
power swing transient impedance to pass through the impedance area between the
outer and the inner characteristics. Power swings are identified by transition times
longer than a transition time set on corresponding timers. The impedance
measuring principle is the same as that used for the distance protection zones. The
impedance and the characteristic passing times are measured in all three phases
separately.

One-out-of-three or two-out-of-three operating modes can be selected according to


the specific system operating conditions.

X1OutFw jX ZL R1LIn
X1InFw DFw

j
DRv
R1FInRv R1FInFw
DFw
ArgLd j

ArgLd
DRv
DFw

DFw

R
DFw
DRv

RLdInRv RLdInFw
DFw

DRv
RLdOutRv RLdOutFw

j DRv X1InRv
X1OutRv

IEC09000222_1_en.vsd
IEC09000222 V1 EN

Figure 146: Operating characteristic for ZMRPSB function (setting parameters


in italic)

260
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

The impedance measurement within ZMRPSB function is performed by solving


equation 54 and equation 55 (n = 1, 2, 3 for each corresponding phase L1, L2 and
L3).

æ ULn ö
Re çç ÷÷ £ Rset
è ILn ø
EQUATION1183 V2 EN (Equation 54)

æ ULn ö
Imçç ÷÷ £ Xset
è ILn ø
EQUATION1184 V2 EN (Equation 55)

The Rset and Xset are R and X boundaries.

6.9.2.1 Resistive reach in forward direction

To avoid load encroachment, the resistive reach is limited in forward direction by


setting the parameter RLdOutFw which is the outer resistive load boundary value
while the inner resistive boundary is calculated according to equation 56.

RLdInFw = kLdRFw·RLdOutFw
EQUATION1185 V2 EN (Equation 56)

where:
kLdRFw is a settable multiplication factor less than 1

The slope of the load encroachment inner and outer boundary is defined by setting
the parameter ArgLd.

The load encroachment in the fourth quadrant uses the same settings as in the first
quadrant (same ArgLd and RLdOutFw and calculated value RLdInFw).

The quadrilateral characteristic in the first quadrant is tilted to get a better


adaptation to the distance measuring zones. The angle is the same as the line angle
and derived from the setting of the reactive reach inner boundary X1InFw and the
line resistance for the inner boundary R1LIn. The fault resistance coverage for the
inner boundary is set by the parameter R1FInFw.

From the setting parameter RLdOutFw and the calculated value RLdInFw a
distance between the inner and outer boundary, DFw, is calculated. This value is
valid for R direction in first and fourth quadrant and for X direction in first and
second quadrant.

261
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.9.2.2 Resistive reach in reverse direction

To avoid load encroachment in reverse direction, the resistive reach is limited by


setting the parameter RLdOutRv for the outer boundary of the load encroachment
zone. The distance to the inner resistive load boundary RLdInRv is determined by
using the setting parameter kLdRRv in equation 57.

RLdInRv = kLdRRv·RLdOutRv
EQUATION1187 V2 EN (Equation 57)

where:
kLdRRv is a settable multiplication factor less than 1

From the setting parameter RLdOutRv and the calculated value RLdInRv, a
distance between the inner and outer boundary, DRv, is calculated. This value is
valid for R direction in second and third quadrant and for X direction in third and
fourth quadrant.

The inner resistive characteristic in the second quadrant outside the load
encroachment part corresponds to the setting parameter R1FInRv for the inner
boundary. The outer boundary is internally calculated as the sum of DRv+R1FInRv.

The inner resistive characteristic in the third quadrant outside the load
encroachment zone consist of the sum of the settings R1FInRv and the line
resistance R1LIn. The argument of the tilted lines outside the load encroachment is
the same as the tilted lines in the first quadrant. The distance between the inner and
outer boundary is the same as for the load encroachment in reverse direction, that is
DRv.

6.9.2.3 Reactive reach in forward and reverse direction

The inner characteristic for the reactive reach in forward direction correspond to
the setting parameter X1InFw and the outer boundary is defined as X1InFw + DFw,

where:
DFw = RLdOutFw - KLdRFw · RLdOutFw

The inner characteristic for the reactive reach in reverse direction correspond to the
setting parameter X1InRv for the inner boundary and the outer boundary is defined
as X1InRv + DRv.

where:
DRv = RLdOutRv - KLdRRv · RLdOutRv

262
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.9.2.4 Basic detection logic

The operation of the Power swing detection ZMRPSB is only released if the
magnitude of the current is above the setting of the min operating current,
IMinOpPE.

ZMRPSB function can operate in two operating modes:

• The 1 out of 3 operating mode is based on detection of power swing in any of


the three phases. Figure 147 presents a composition of an internal detection
signal DET-L1 in this particular phase.
• The 2 out of 3 operating mode is based on detection of power swing in at least
two out of three phases. Figure 148 presents a composition of the detection
signals DET1of3 and DET2of3.

Signals ZOUTLn (outer boundary) and ZINLn (inner boundary) in figure 147 are
related to the operation of the impedance measuring elements in each phase
separately (n represents the corresponding L1, L2 and L3). They are internal
signals, calculated by ZMRPSB function.

The tP1 timer in figure 147 serve as detection of initial power swings, which are
usually not as fast as the later swings are. The tP2 timer become activated for the
detection of the consecutive swings, if the measured impedance exit the operate
area and returns within the time delay, set on the tW waiting timer. The upper part
of figure 147 (internal input signal ZOUTL1, ZINL1, AND-gates and tP-timers)
are duplicated for phase L2 and L3. All tP1 and tP2 timers in the figure have the
same settings.

ZOUTL1 AND
0-tP1
ZINL1 0 OR
-loop
0-tP2
-loop
AND
0
OR DET-L1
AND AND

ZOUTL2 OR
ZOUTL3

detected 0
0-tW

IEC05000113-2-en.vsd
IEC05000113 V2 EN

Figure 147: Detection of power swing in phase L1

263
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

DET-L1
DET-L2 DET1of3 - int.
>1
DET-L3

&

DET2of3 - int.
& >1

&

IEC01000057-2-en.vsd
IEC01000057-TIFF V2 EN

Figure 148: Detection of power swing for 1-of-3 and 2-of-3 operating mode

ZOUTL1 ZOUT
OR
ZOUTL2 ZINL1
ZIN
ZOUTL3 AND ZINL2 OR

ZINL3
tEF
TRSP
t AND

I0CHECK

10 ms
AND t
BLKI02 OR

tR1
AND t INHIBIT
OR
-loop
tR2
BLKI01 AND t
BLOCK
-loop
DET1of3 - int.
REL1PH
AND
BLK1PH
tH
DET2of3 - int. OR t
REL2PH
AND
BLK2PH OR START
AND
EXTERNAL

en05000114.vsd
IEC05000114 V1 EN

Figure 149: Simplified block diagram for ZMRPSB function

264
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.9.2.5 Operating and inhibit conditions

Figure 149 presents a simplified logic diagram for the Power swing detection
function ZMRPSB. The internal signals DET1of3 and DET2of3 relate to the
detailed logic diagrams in figure 147 and figure 148 respectively.

Selection of the operating mode is possible by the proper configuration of the


functional input signals REL1PH, BLK1PH, REL2PH, and BLK2PH.

The load encroachment characteristic can be switched off by setting the parameter
OperationLdCh = Off, but notice that the DFw and DRv will still be calculated from
RLdOutFw and RLdOutRv. The characteristic will in this case be only quadrilateral.

There are four different ways to form the internal INHIBIT signal:

• Logical 1 on functional input BLOCK inhibits the output START signal


instantaneously.
• The INHIBIT internal signal is activated, if the power swing has been detected
and the measured impedance remains within its operate characteristic for the
time, which is longer than the time delay set on tR2 timer. It is possible to
disable this condition by connecting the logical 1 signal to the BLKI01
functional input.
• The INHIBIT internal signal is activated after the time delay, set on tR1 timer,
if an earth-fault appears during the power swing (input IOCHECK is high) and
the power swing has been detected before the earth-fault (activation of the
signal I0CHECK). It is possible to disable this condition by connecting the
logical 1 signal to the BLKI02 functional input.
• The INHIBIT logical signals becomes logical 1, if the functional input
I0CHECK appears within the time delay, set on tEF timer and the impedance
has been seen within the outer characteristic of ZMRPSB operate
characteristic in all three phases. This function prevents the operation of
ZMRPSB function in cases, when the circuit breaker closes onto persistent
single-phase fault after single-phase autoreclosing dead time, if the initial single-
phase fault and single-phase opening of the circuit breaker causes the power
swing in the remaining two phases.

265
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.9.3 Function block


ZMRPSB
I3P* START
U3P* ZOUT
BLOCK ZIN
BLKI01
BLKI02
BLK1PH
REL1PH
BLK2PH
REL2PH
I0CHECK
TRSP
EXTERNAL

IEC06000264-2-en.vsd
IEC06000264 V2 EN

Figure 150: ZMRPSB function block

6.9.4 Input and output signals


Table 138: ZMRPSB Input signals
Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKI01 BOOLEAN 0 Block inhibit of start output for slow swing condition
BLKI02 BOOLEAN 0 Block inhibit of start output for subsequent
residual current detection
BLK1PH BOOLEAN 0 Block one-out-of-three-phase operating mode
REL1PH BOOLEAN 0 Release one-out-of-three-phase operating mode
BLK2PH BOOLEAN 0 Block two-out-of-three-phase operating mode
REL2PH BOOLEAN 0 Release two-out-of-three-phase operating mode
I0CHECK BOOLEAN 0 Residual current (3I0) detection used to inhibit
start output
TRSP BOOLEAN 0 Single-pole tripping command issued by tripping
function
EXTERNAL BOOLEAN 0 Input for external detection of power swing

Table 139: ZMRPSB Output signals


Name Type Description
START BOOLEAN Power swing detected
ZOUT BOOLEAN Measured impedance within outer impedance
boundary
ZIN BOOLEAN Measured impedance within inner impedance
boundary

266
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.9.5 Setting parameters


Table 140: ZMRPSB Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Mode On / Off
On
X1InFw 0.10 - 3000.00 ohm 0.01 30.00 Inner reactive boundary, forward
R1LIn 0.10 - 1000.00 ohm 0.01 30.00 Line resistance for inner characteristic
angle
R1FInFw 0.10 - 1000.00 ohm 0.01 30.00 Fault resistance coverage to inner
resistive line, forward
X1InRv 0.10 - 3000.00 ohm 0.01 30.00 Inner reactive boundary, reverse
R1FInRv 0.10 - 1000.00 ohm 0.01 30.00 Fault resistance line to inner resistive
boundary, reverse
OperationLdCh Off - - On Operation of load discrimination
On characteristic
RLdOutFw 0.10 - 3000.00 ohm 0.01 30.00 Outer resistive load boundary, forward
ArgLd 5 - 70 Deg 1 25 Load angle determining load impedance
area
RLdOutRv 0.10 - 3000.00 ohm 0.01 30.00 Outer resistive load boundary, reverse
kLdRFw 0.50 - 0.90 Mult 0.01 0.75 Multiplication factor for inner resistive
load boundary, forward
kLdRRv 0.50 - 0.90 Mult 0.01 0.75 Multiplication factor for inner resistive
load boundary, reverse
tEF 0.000 - 60.000 s 0.001 3.000 Timer for overcoming single-pole
reclosing dead time
IMinOpPE 5 - 30 %IB 1 10 Minimum operate current in % of IBase
IBase 1 - 99999 A 1 3000 Base setting for current level settings

Table 141: ZMRPSB Group settings (advanced)


Name Values (Range) Unit Step Default Description
tP1 0.000 - 60.000 s 0.001 0.045 Timer for detection of initial power swing
tP2 0.000 - 60.000 s 0.001 0.015 Timer for detection of subsequent power
swings
tW 0.000 - 60.000 s 0.001 0.250 Waiting timer for activation of tP2 timer
tH 0.000 - 60.000 s 0.001 0.500 Timer for holding power swing START
output
tR1 0.000 - 60.000 s 0.001 0.300 Timer giving delay to inhibit by the
residual current
tR2 0.000 - 60.000 s 0.001 2.000 Timer giving delay to inhibit at very slow
swing

267
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.9.6 Technical data


Table 142: ZMRPSB technical data
Function Range or value Accuracy
Reactive reach (0.10-3000.00) W/phase ± 2.0% static accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Resistive reach (0.10–1000.00)W/loop Angle: at 0 degrees and 85
degrees
Timers (0.000-60.000) s ± 0.5% ± 10 ms

6.10 Power swing logic ZMRPSL

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Power swing logic ZMRPSL - -

6.10.1 Introduction
Power Swing Logic (ZMRPSL) is a complementary function to Power Swing
Detection (ZMRPSB) function. It provides possibility for selective tripping of
faults on power lines during system oscillations (power swings or pole slips), when
the distance protection function should normally be blocked. The complete logic
consists of two different parts:

• Communication and tripping part: provides selective tripping on the basis of


special distance protection zones and a scheme communication logic, which
are not blocked during the system oscillations.
• Blocking part: blocks unwanted operation of instantaneous distance protection
zone 1 for oscillations, which are initiated by faults and their clearing on the
adjacent power lines and other primary elements.

6.10.2 Principle of operation

6.10.2.1 Communication and tripping logic

Communication and tripping logic as used by the power swing distance protection
zones is schematically presented in figure 151.

268
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

STDEF
AR1P1 &

STPSD tCS
CS
BLOCK & t &

CSUR
BLKZMPS
tBlkTr &
tTrip t
t

CACC TRIP
>1
CR &

en06000236.vsd
IEC06000236 V1 EN

Figure 151: Simplified logic diagram – power swing communication and tripping
logic

The complete logic remains blocked as long as there is a logical one on the
BLOCK functional input signal. Presence of the logical one on the STDEF
functional input signal also blocks the logic as long as this block is not released by
the logical one on the AR1P1 functional input signal. The functional output signal
BLKZMPS remains logical one as long as the function is not blocked externally
(BLOCK is logical zero) and the earth-fault is detected on protected line (STDEF
is logical one), which is connected in three-phase mode (AR1P1 is logical zero).
Timer tBlkTr prolongs the duration of this blocking condition, if the measured
impedance remains within the operate area of the Power Swing Detection
(ZMRPSB) function (STPSD input active). The BLKZMPS can be used to block
the operation of the power-swing zones.

Logical one on functional input CSUR, which is normally connected to the TRIP
functional output of a power swing carrier sending zone, activates functional output
CS, if the function is not blocked by one of the above conditions. It also activates
the TRIP functional output.

Initiation of the CS functional output is possible only, if the STPSD input has been
active longer than the time delay set on the security timer tCS.

Simultaneous presence of the functional input signals PLTR_CRD and CR (local


trip condition) also activates the TRIP functional output, if the function is not
blocked by one of the above conditions and the STPSD signal has been present
longer then the time delay set on the trip timer tTrip.

6.10.2.2 Blocking logic

Figure 152 presents the logical circuits, which control the operation of the
underreaching zone (zone 1) at power swings, caused by the faults and their
clearance on the remote power lines.

269
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

&

BLKZMH
&
STZML tZL
STZMLL
BLOCK & t >1
&
STMZH tDZ
STZMPSD & t
>1
STPSD

&
-loop

en06000237.vsd
IEC06000237 V1 EN

Figure 152: Control of underreaching distance protection (Zone 1) at power


swings caused by the faults and their clearance on adjacent lines
and other system elements

The logic is disabled by a logical one on functional input BLOCK. It can start only
if the following conditions are simultaneously fulfilled:

• STPSD functional input signal must be a logical zero. This means, that Power
swing detection (ZMRPSB) function must not detect power swinging over the
protected power line.
• STZMPSD functional input must be a logical one. This means that the
impedance must be detected within the external boundary of ZMRPSB function.
• STZMOR functional input must be a logical one. This means that the fault
must be detected by the overreaching distance protection zone, for example
zone 2.

The STZMURPS functional output, which can be used in complete terminal logic
instead of a normal distance protection zone 1, becomes active under the following
conditions:

• If the STZMUR signal appears at the same time as the STZMOR or if it


appears with a time delay, which is shorter than the time delay set on timer
tDZ.
• If the STZMUR signal appears after the STZMOR signal with a time delay
longer than the delay set on the tDZ timer, and remains active longer than the
time delay set on the tZL timer.

The BLKZMOR functional output signal can be used to block the operation of the
higher distance protection zone, if the fault has moved into the zone 1 operate area
after tDZ time delay.

270
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.10.3 Function block


ZMRPSL
BLOCK TRIP
STZMUR STZMURPS
STZMOR BLKZMUR
STPSD BLKZMOR
STDEF CS
STZMPSD
CACC
AR1P1
CSUR
CR

IEC07000026-2-en.vsd
IEC07000026 V2 EN

Figure 153: ZMRPSL function block

6.10.4 Input and output signals


Table 143: ZMRPSL Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
STZMUR BOOLEAN 0 Start of the underreaching zone
STZMOR BOOLEAN 0 Start of the overreaching zone
STPSD BOOLEAN 0 Power swing detected
STDEF BOOLEAN 0 Start from Earth Fault Protection in forward or
reverse direction
STZMPSD BOOLEAN 0 Operation of Power Swing Detection external
characteristic
CACC BOOLEAN 0 Overreaching ZM zone to be accelerated
AR1P1 BOOLEAN 0 Single pole auto-reclosing in progress
CSUR BOOLEAN 0 Carrier send by the underreaching power-swing
zone
CR BOOLEAN 0 Carrier receive signal during power swing
detection operation

Table 144: ZMRPSL Output signals


Name Type Description
TRIP BOOLEAN Trip through Power Swing Logic
STZMURPS BOOLEAN Start of Underreaching zone controlled by PSL to
be used in configuration
BLKZMUR BOOLEAN Block trip of underreaching impedance zone
BLKZMOR BOOLEAN Block trip of overreaching distance protection
zones
CS BOOLEAN Carrier send signal controlled by the power swing

271
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.10.5 Setting parameters


Table 145: ZMRPSL Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
tDZ 0.000 - 60.000 s 0.001 0.050 Permitted max oper time diff between
higher and lower zone
tDZMUR 0.000 - 60.000 s 0.001 0.200 Delay for oper of underreach zone with
detected diff in oper time
tCS 0.000 - 60.000 s 0.001 0.100 Conditional timer for sending the CS at
power swings
tTrip 0.000 - 60.000 s 0.001 0.100 Conditional timer for tripping at power
swings
tBlkTr 0.000 - 60.000 s 0.001 0.300 Timer for blocking the overreaching
zones trip

6.11 Pole slip protection PSPPPAM

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Pole slip protection PSPPPAM 78

<
SYMBOL-MM V1 EN

6.11.1 Introduction
Sudden events in an electrical power system such as large changes in load, fault
occurrence or fault clearance, can cause power oscillations referred to as power
swings. In a non-recoverable situation, the power swings become so severe that the
synchronism is lost, a condition referred to as pole slipping. The main purpose of
the pole slip protection (PSPPPAM) is to detect, evaluate, and take the required
action for pole slipping occurrences in the power system. The electrical system
parts swinging to each other can be separated with the line/s closest to the centre of
the power swing allowing the two systems to be stable as separated islands.

6.11.2 Principle of operation


If the generator is faster than the power system, the rotor movement in the
impedance and voltage diagram is from right to left and generating is signalled. If
the generator is slower than the power system, the rotor movement is from left to
right and motoring is signalled (the power system drives the generator as if it were
a motor).

272
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

The movements in the impedance plain can be seen in figure 154. The transient
behaviour is described by the transient EMF's EA and EB, and by X'd, XT and the
transient system impedance ZS.

Zone 1 Zone 2

EB X’d XT XS EA

IED
B A

jX

XS

Pole slip
impedance XT
d Apparent generator
movement impedance R

X’d

IEC06000437_2_en.vsd
IEC06000437 V2 EN

Figure 154: Movements in the impedance plain

where:
X'd = transient reactance of the generator

XT = short-circuit reactance of the step-up transformer

ZS = impedance of the power system A

The detection of rotor angle is enabled when:

273
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

• the minimum current exceeds 0.10 IN (IN is IBase parameter set under general
setting).
• the maximum voltage falls below 0.92 UBase
• the voltage Ucosφ (the voltage in phase with the generator current) has an
angular velocity of 0.2...8 Hz and
• the corresponding direction is not blocked.

en07000004.vsd
IEC07000004 V1 EN

Figure 155: Different generator quantities as function of the angle between the
equivalent generators

An alarm is given when movement of the rotor is detected and the rotor angle
exceeds the angle set for 'WarnAngle'.

Slipping is detected when:

• a change of rotor angle of min. 50 ms is recognized


• the slip line is crossed between ZA and ZB.

When the impedance crosses the slip line between ZB and ZC it counts as being in
zone 1 and between ZC and ZA in zone 2. The entire distance ZA-ZB becomes zone
1 when signal EXTZONE1 is high (external device detects the direction of the
centre of slipping).

After the first slip, the signals ZONE1 or ZONE2 and – depending on the direction
of slip - either GEN or MOTOR are issued.

274
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Every time pole slipping is detected, the impedance of the point where the slip line
is crossed and the instantaneous slip frequency are displayed as measurements.

Further slips are only detected, if they are in the same direction and if the rate of
rotor movement has reduced in relation to the preceding slip or the slip line is
crossed in the opposite direction outside ZA-ZB. A further slip in the opposite
direction within ZA-ZB resets all the signals and is then signalled itself as a first slip.

The TRIP1 tripping command and signal are generated after N1 slips in zone 1,
providing the rotor angle is less than TripAngle. The TRIP2 signal is generated
after N2 slips in zone 2, providing the rotor angle is less than TripAngle.

All signals are reset if:

• the direction of movement reverses


• the rotor angle detector resets without a slip being counted or
• no rotor relative movement was detected during the time ResetTime.

Imin > 0.10 IBase

Ucosj < 0.92 UBase AND

START
AND
0.2 £ Slip.Freq. £ 8 Hz

d ³ startAngle

ZONE1
AND
Z cross line ZA - ZC

ZONE2
AND
Z cross line ZC - ZB

Counter
a
a³b
N1Limit b TRIP1
AND

d £ tripAngle TRIP
OR

Counter
a
N2Limit b a³b TRIP2
AND

en07000005.vsd

IEC07000005 V1 EN

Figure 156: Simplified logic diagram for pole slip protection PSPPPAM

275
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.11.3 Function block


PSPPPAM
I3P* TRIP
U3P* TRIP1
BLOCK TRIP2
BLKGEN START
BLKMOTOR ZONE1
EXTZONE1 ZONE2
GEN
MOTOR
SFREQ
SLIPZOHM
SLIPZPER
UCOSKV
UCOSPER

IEC07000030-2-en.vsd
IEC07000030 V2 EN

Figure 157: PSPPPAM function block

6.11.4 Input and output signals


Table 146: PSPPPAM Input signals
Name Type Default Description
I3P GROUP - Current group connection
SIGNAL
U3P GROUP - Voltage group connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKGEN BOOLEAN 0 Block operation in generating direction
BLKMOTOR BOOLEAN 0 Block operation in motor direction
EXTZONE1 BOOLEAN 0 Extension of zone1 with zone2 region

Table 147: PSPPPAM Output signals


Name Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip1 after the N1Limit slip in zone1
TRIP2 BOOLEAN Trip2 after the N2Limit slip in zone2
START BOOLEAN Common start signal
ZONE1 BOOLEAN First slip in zone1 region
ZONE2 BOOLEAN First slip in zone2 region
GEN BOOLEAN Generator is faster then the system
MOTOR BOOLEAN Generator is slower then the system
SFREQ REAL Slip frequency
SLIPZOHM REAL Slip impedance in ohms
SLIPZPER REAL Slip impedance in percent of ZBase
UCOSKV REAL UCosPhi voltage in kV
UCOSPER REAL UCosPhi voltage in percent of UBase

276
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

6.11.5 Setting parameters


Table 148: PSPPPAM Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation On / Off
On
OperationZ1 Off - - On Operation Zone1 On / Off
On
OperationZ2 Off - - On Operation Zone2 On / Off
On
ImpedanceZA 0.00 - 1000.00 % 0.01 10.00 Forward impedance in % of Zbase
ImpedanceZB 0.00 - 1000.00 % 0.01 10.00 Reverse impedance in % of Zbase
ImpedanceZC 0.00 - 1000.00 % 0.01 10.00 Impedance of zone1 limit in % of Zbase
AnglePhi 72.00 - 90.00 Deg 0.01 85.00 Angle of the slip impedance line
StartAngle 0.0 - 180.0 Deg 0.1 110.0 Rotor angle for the start signal
TripAngle 0.0 - 180.0 Deg 0.1 90.0 Rotor angle for the trip1 and trip2 signals
N1Limit 1 - 20 - 1 1 Count limit for the trip1 signal
N2Limit 1 - 20 - 1 3 Count limit for the trip2 signal

Table 149: PSPPPAM Group settings (advanced)


Name Values (Range) Unit Step Default Description
ResetTime 0.000 - 60.000 s 0.001 5.000 Time without slip to reset all signals

Table 150: PSPPPAM Non group settings (basic)


Name Values (Range) Unit Step Default Description
IBase 0.1 - 99999.9 A 0.1 3000.0 Base Current (primary phase current in
Amperes)
UBase 0.1 - 9999.9 kV 0.1 20.0 Base Voltage (primary phase-to-phase
voltage in kV)
MeasureMode PosSeq - - PosSeq Measuring mode (PosSeq, L1L2, L2L3,
L1L2 L3L1)
L2L3
L3L1
InvertCTcurr No - - No Invert current direction
Yes

6.11.6 Technical data


Table 151: PSPPPAM technical data
Function Range or value Accuracy
Impedance reach (0.00–1000.00)% of Zbase ± 2.0% of Ur/Ir
Characteristic angle (72.00–90.00) degrees ± 5.0 degrees
Start and trip angles (0.0–180.0) degrees ± 5.0 degrees
Zone 1 and Zone 2 trip counters (1-20) -

277
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.12 Automatic switch onto fault logic, voltage and


current based ZCVPSOF

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Automatic switch onto fault logic, ZCVPSOF - -
voltage and current based

6.12.1 Introduction
Automatic switch onto fault logic, voltage and current based (ZCVPSOF) is a
function that gives an instantaneous trip at closing of breaker onto a fault. A dead
line detection check is provided to activate the function when the line is dead.

Mho distance protections can not operate for switch onto fault condition when the
phase voltages are close to zero. An additional logic based on UI Level is used for
this purpose.

6.12.2 Principle of operation


Automatic switch onto fault logic, voltage and current based function (ZCVPSOF)
can be activated externally by Breaker Closed Input or internally (automatically)
by using UI Level Based Logic see figure 158.

The activation from the Dead line detection function is released if the internal
signal deadLine from the UILevel function is activated at the same time as the
input ZACC is not activated during at least for a duration tDLD and the setting
parameter AutoInit is set to On.

When the setting AutoInit is Off, the function is activated by an external binary
input BC. To get a trip one of the following operation modes must also be selected
by the parameter Mode:

Mode = Impedance; trip is released if the input ZACC is activated (normal


connected to non directional distance protection zone).

Mode = UILevel; trip is released if UILevel detector is activated.

Mode = UILvl&Imp; trip is initiated based on impedance measured criteria or


UILevel detection.

The internal signal deadLine from the UILevel detector is activated if all three
phase currents and voltages are below the setting IPh< and UPh<.

UI Level based measurement detects the switch onto fault condition even though
the voltage is very low. The logic is based on current and voltage levels. The
internal signal SOTF UILevel is activated if a phase voltage is below the setting

278
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

UPh< and corresponding phase current is above the setting IPh< longer than the
time tDuration.

ZCVPSOF can be activated externally from input BC and thus setting AutoInit is
bypassed.

The function is released during a settable time tSOTF.

The function can be blocked by activating the input BLOCK.

BLOCK 15
t TRIP
AND

BC

AutiInit=On

200 1000
OR t
ZACC AND t

IL1
deadLine
IL2
IL3
UL1 UILevel detector
UL2
UL3

Iph<
SOTFU ILevel
Uph<

AND
Mode = Impedance

AND OR
Mode = UILevel

OR
AND
Mode = UILvl&Imp

en07000084.vsd

IEC07000084 V2 EN

Figure 158: Simplified logic diagram for Automatic switch onto fault logic,
voltage and current based.

279
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

6.12.3 Function block


ZCVPSOF
I3P* TRIP
U3P*
BLOCK
BC
ZACC

IEC06000459-2-en.vsd
IEC06000459 V2 EN

Figure 159: ZCVPSOF function block

6.12.4 Input and output signals


Table 152: ZCVPSOF Input signals
Name Type Default Description
I3P GROUP - Current DFT
SIGNAL
U3P GROUP - Voltage DFT
SIGNAL
BLOCK BOOLEAN 0 Block of function
BC BOOLEAN 0 External enabling of SOTF
ZACC BOOLEAN 0 Distance zone to be accelerated by SOTF

Table 153: ZCVPSOF Output signals


Name Type Description
TRIP BOOLEAN Trip output

6.12.5 Setting parameters


Table 154: ZCVPSOF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current (A)
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage L-L (kV)
Mode Impedance - - UILevel Mode of operation of SOTF Function
UILevel
UILvl&Imp
AutoInit Off - - Off Automatic switchonto fault initialization
On
IPh< 1 - 100 %IB 1 20 Current level for detection of dead line in
% of IBase
UPh< 1 - 100 %UB 1 70 Voltage level for detection of dead line in
% of UBase
Table continues on next page

280
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Name Values (Range) Unit Step Default Description


tDuration 0.000 - 60.000 s 0.001 0.020 Time delay for UI detection (s)
tSOTF 0.000 - 60.000 s 0.001 1.000 Drop off delay time of switch onto fault
function
tDLD 0.000 - 60.000 s 0.001 0.200 Delay time for activation of dead line
detection

6.12.6 Technical data


Table 155: ZCVPSOF technical data
Parameter Range or value Accuracy
Operate voltage, detection of dead line (1–100)% of ± 1.0% of Ur
UBase
Operate current, detection of dead line (1–100)% of ± 1.0% of Ir
IBase
Delay following dead line detection input before (0.000–60.000) s ± 0.5% ± 10 ms
Automatic switch into fault logic function is
automatically turned On
Time period after circuit breaker closure in which (0.000–60.000) s ± 0.5% ± 10 ms
Automatic switch into fault logic function is active

6.13 Phase preference logic PPLPHIZ

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Phase preference logic PPLPHIZ - -

6.13.1 Introduction
Phase preference logic function PPLPHIZ is intended to be used in isolated or high
impedance earthed networks where there is a requirement to trip only one of the
faulty lines at cross-country fault.

Phase preference logic inhibits tripping for single phase-to-earth faults in isolated
and high impedance earthed networks, where such faults are not to be cleared by
distance protection. For cross-country faults, the logic selects either the leading or
the lagging phase-earth loop for measurement and initiates tripping of the preferred
fault based on the selected phase preference. A number of different phase
preference combinations are available for selection.

6.13.2 Principle of operation


Phase preference logic PPLPHIZ has 10 operation modes, which can be set by the
parameter OperMode. The different modes and their explanation are shown in

281
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

table 156 below. The difference between cyclic and acyclic operation can be
explained by the following example. Assume a L1 fault on one line and a L3 fault
on another line. For OperMode = 1231c the line with L3 fault will be tripped (L3
before L1) while for OperMode = 123a the line with L1 1 fault will be tripped (L1
before L3).

Table 156: Operation modes for Phase preference logic


OperMode Description
No filter No filter, phase-to-phase measuring loops are not blocked during single phase-to-
earth faults. Tripping is allowed without any particular phase preference at cross-
country faults
No pref No preference, trip is blocked during single phase-to-earth faults, trip is allowed
without any particular phase preference at cross-country fault
1231 c Cyclic 1231c; L1 before L2 before L3 before L1
1321 c Cyclic 1321c; L1 before L3 before L2 before L1
123 a Acyclic 123a; L1 before L2before L3
132 a Acyclic 132a; L1 before L3 before L2
213 a Acyclic 213a; L2 before L1 before L3
231 a Acyclic 231a; L2 before L3 before L1
312 a Acyclic 312a; L3 before L1 before L2
321 a Acyclic 321a; L3 before L2 before L1

The function can be divided into two parts; one labeled voltage and current
discrimination and the second one labeled phase preference evaluation, see
figure 160.

The aim with the voltage and current discrimination part is to discriminate faulty
phases and to determine if there is a cross-country fault. If cross-country fault is
detected, an internal signal “Detected cross-country fault” is created and sent to the
phase preference part to be used in the evaluation process for determining the
condition for trip.

The voltage and current discrimination part gives phase segregated start signals if
the respective measured phase voltage is below the setting parameter UPN< at the
same time as the zero sequence voltage is above the setting parameter 3U0>. If
there is a start in any phase the START out put signal will be activated.

The internal signal for detection of cross-country fault, DetectCrossCountry, that


come from the voltage and current discrimination part of the function can be
achieved in three different ways:

282
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

1. The magnitude of 3I0 has been above the setting parameter IN> for a time
longer than the setting of pick-up timer tIN.
2. The magnitude of 3I0 has been above the setting parameter IN> at the same
time as the magnitude of 3U0 has been above the setting parameter 3U0>
during a time longer than the setting of pick-up timer tUN.
3. The magnitude of 3I0 has been above the setting parameter IN> at the same
time as one of the following conditions are fulfilled:
• the measured phase-to-phase voltage in at least one of the phase
combinations has been below the setting parameter UPP< for more than
20 ms.
• At least two of the phase voltages are below the setting parameter UPN<
for more than 20 ms.

The second part, phase preference evaluation, uses the internal signal
DetectCrossCountry from the voltage and current evaluation together with the
input signal STCND together with phase selection start condition (from phase
selection functions) connected to input STCND, and the information from the
setting parameter OperMode are used to determine the condition for trip. To
release the Phase preference logic, at least two out of three phases must be faulty.
The fault classification whether it is a single phase-to-earth, two-phase or cross-
country fault and which phase to be tripped at cross-country fault is converted into
a binary coded signal and sent to the distance protection measuring zone to release
the correct measuring zone according to the setting of OperMode. This is done by
activating the output ZREL and it shall be connected to the input STCND on the
distance zone measuring element.

The release signals from phase selection will only be gated with the cross-country
check from IN and UN but without time delay. If no phase selection start has
occurred, the release is based on current and voltage discriminating part only.

The input signal STCND consist of binary information of fault type and is
connected to the output STCND on phase selection function. The fault must be
activated in at least two phases to be classified as a cross-country fault in the phase
preference part of the logic.

The input signals RELxxx are additional fault release signals that can be connected
to external protection functions through binary input.

The output START and trip signals can be blocked by activating the input BLOCK

283
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

UL1
UL2
UL3
UL1UL2
UL2UL3
UL3UL1
IN Voltage and START
AND
UN Current
Discrimination
UPN<

UPP<

IN>
Detect Cross-
UN0> Country fault

OperMode
RELL1N ZREL
Phase Preference AND
RELL2N Evaluation
RELL3N
STCND

BLOCK

IEC09000220_1_en.vsd
IEC09000220 V2 EN

Figure 160: Simplified block diagram for Phase preference logic

6.13.3 Function block


PPLPHIZ
I3P* START
U3P* ZREL
BLOCK
RELL1N
RELL2N
RELL3N
STCND

IEC07000029-2-en.vsd
IEC07000029 V2 EN

Figure 161: PPLPHIZ function block

6.13.4 Input and output signals


Table 157: PPLPHIZ Input signals
Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
Table continues on next page

284
Technical reference manual
1MRK505183-UEN C Section 6
Impedance protection

Name Type Default Description


RELL1N BOOLEAN 0 Release condition for the L1 to earth loop
RELL2N BOOLEAN 0 Release condition for the L2 to earth loop
RELL3N BOOLEAN 0 Release condition for the L3 to earth loop
STCND INTEGER 0 Integer coded external release signals

Table 158: PPLPHIZ Output signals


Name Type Description
START BOOLEAN Indicates start for earth fault(s), regardless of
direction
ZREL INTEGER Integer coded output release signal

6.13.5 Setting parameters


Table 159: PPLPHIZ Group settings (basic)
Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Base current
UBase 0.05 - 2000.00 kV 0.01 400.00 Base voltage
OperMode No Filter - - No Filter Operating mode (c=cyclic,a=acyclic)
NoPref
1231c
1321c
123a
132a
213a
231a
312a
321a
UPN< 10.0 - 100.0 %UB 1.0 70.0 Operate value of phase undervoltage (%
of UBase)
UPP< 10.0 - 100.0 %UB 1.0 50.0 Operate value of line to line
undervoltage (% of UBase)
3U0> 5.0 - 70.0 %UB 1.0 20.0 Operate value of residual voltage (% of
UBase)
IN> 10 - 200 %IB 1 20 Operate value of residual current (% of
IBase)
tUN 0.000 - 60.000 s 0.001 0.100 Pickup-delay for residual voltage
tOffUN 0.000 - 60.000 s 0.001 0.100 Dropoff-delay for residual voltage
tIN 0.000 - 60.000 s 0.001 0.150 Pickup-delay for residual current

285
Technical reference manual
Section 6 1MRK505183-UEN C
Impedance protection

Table 160: PPLPHIZ technical data


Function Range or value Accuracy
Operate value, phase-to-phase (10.0 - 100.0)% of UBase ± 0,5% of Ur
and phase-to-neutral
undervoltage
Reset ratio, undervoltage < 105% -
Operate value, residual voltage (5.0 - 70.0)% of UBase ± 0,5% of Ur

Reset ratio, residual voltage > 95% -


Operate value, residual current (10 - 200)% of IBase ± 1,0% of Ir for I < Ir
± 1,0% of I for I > Ir

Reset ratio, residual current > 95% -


Timers (0.000 - 60.000) s ± 0,5% ± 10ms
Operating mode No Filter, NoPref
Cyclic: 1231c, 1321c
Acyclic: 123a, 132a, 213a, 231a,
312a, 321a

286
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Section 7 Current protection

About this chapter


This chapter describes current protection functions. These include functions like
Instantaneous phase overcurrent protection, Four step phase overcurrent protection,
Pole discordance protection and Residual overcurrent protection.

7.1 Instantaneous phase overcurrent protection PHPIOC

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Instantaneous phase overcurrent PHPIOC 50
protection
3I>>

SYMBOL-Z V1 EN

7.1.1 Introduction
The instantaneous three phase overcurrent function has a low transient overreach
and short tripping time to allow use as a high set short-circuit protection function.

7.1.2 Principle of operation


The sampled analogue phase currents are pre-processed in a discrete Fourier filter
(DFT) block. The RMS value of each phase current is derived from the
fundamental frequency components, as well as sampled values of each phase
current. These phase current values are fed to the instantaneous phase overcurrent
protection function PHPIOC. In a comparator the RMS values are compared to the
set operation current value of the function (IP>>). If a phase current is larger than
the set operation current a signal from the comparator for this phase is set to true.
This signal will, without delay, activate the output signal TRLn (n=1,2,3) for this
phase and the TRIP signal that is common for all three phases.

There is an operation mode (OpMode) setting: 1 out of 3 or 2 out of 3. If the


parameter is set to 1 out of 3 any phase trip signal will be activated. If the
parameter is set to 2 out of 3 at least two phase signals must be activated for trip.

There is also a possibility to activate a preset change of the set operation current
(StValMult) via a binary input (ENMULT). In some applications the operation
value needs to be changed, for example due to transformer inrush currents.

287
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

PHPIOC can be blocked from the binary input BLOCK.

7.1.3 Function block


PHPIOC
I3P* TRIP
BLOCK TRL1
ENMULT TRL2
TRL3

IEC04000391-2-en.vsd
IEC04000391 V2 EN

Figure 162: PHPIOC function block

7.1.4 Input and output signals


Table 161: PHPIOC Input signals
Name Type Default Description
I3P GROUP - Three phase current
SIGNAL
BLOCK BOOLEAN 0 Block of function
ENMULT BOOLEAN 0 Enable current start value multiplier

Table 162: PHPIOC Output signals


Name Type Description
TRIP BOOLEAN Trip signal from any phase
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3

7.1.5 Setting parameters


Table 163: PHPIOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current
OpMode 2 out of 3 - - 1 out of 3 Select operation mode 2-out of 3 / 1-out
1 out of 3 of 3
IP>> 1 - 2500 %IB 1 200 Operate phase current level in % of IBase

Table 164: PHPIOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
StValMult 0.5 - 5.0 - 0.1 1.0 Multiplier for operate current level

288
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.1.6 Technical data


Table 165: PHPIOC technical data
Function Range or value Accuracy
Operate current (1-2500)% of lBase ± 1.0% of Ir at I £ Ir
± 1.0% of I at I > Ir

Reset ratio > 95% -


Operate time 25 ms typically at 0 to 2 x Iset -

Reset time 25 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time 10 ms typically at 0 to 10 x Iset -

Reset time 35 ms typically at 10 to 0 x Iset -

Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

7.2 Four step phase overcurrent protection OC4PTOC

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Four step phase overcurrent protection OC4PTOC 51/67
3I>
4
alt
4
TOC-REVA V1 EN

7.2.1 Introduction
The four step phase overcurrent protection function OC4PTOC has an inverse or
definite time delay independent for each step separately.

All IEC and ANSI time delayed characteristics are available together with an
optional user defined time characteristic.

The directional function is voltage polarized with memory. The function can be set
to be directional or non-directional independently for each of the steps.

A 2nd harmonic blocking can be set individually for each step.

7.2.2 Principle of operation


The Four step overcurrent protection function OC4PTOC is divided into four
different sub-functions, one for each step. For each step x , where x is step 1, 2, 3

289
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

and 4, an operation mode is set by DirModex: Off/Non-directional/Forward/


Reverse.

The protection design can be decomposed in four parts:

• The direction element


• The harmonic Restraint Blocking function
• The four step over current function
• The mode selection

If VT inputs are not available or not connected, setting parameter


DirModex shall be left to default value, Non-directional.

4 step over current


Direction dirPh1Flt element faultState
faultState
Element One element for each
dirPh2Flt step
I3P dirPh3Flt START

U3P

TRIP

Harmonic harmRestrBlock
I3P Restraint
Element

enableDir
Mode Selection
enableStep1-4
DirectionalMode1-4

en05000740.vsd

IEC05000740 V1 EN

Figure 163: Functional overview of OC4PTOC

A common setting for all steps, StartPhSel, is used to specify the number of phase
currents to be high to enable operation. The settings can be chosen: 1 out of 3, 2 out
of 3 or 3 out of 3.

290
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

The sampled analogue phase currents are processed in a pre-processing function


block. Using a parameter setting MeasType within the general settings for the four
step phase overcurrent protection function OC4PTOC, it is possible to select the
type of the measurement used for all overcurrent stages. It is possible to select
either discrete Fourier filter (DFT) or true RMS filter (RMS).

If DFT option is selected then only the RMS value of the fundamental frequency
components of each phase current is derived. Influence of DC current component
and higher harmonic current components are almost completely suppressed. If
RMS option is selected then the true RMS values is used. The true RMS value in
addition to the fundamental frequency component includes the contribution from
the current DC component as well as from higher current harmonic. The selected
current values are fed to OC4PTOC.

In a comparator, for each phase current, the DFT or RMS values are compared to
the set operation current value of the function (I1>, I2>, I3> or I4>). If a phase
current is larger than the set operation current, outputs START, STx, STL1, STL2
and STL3 are, without delay, activated. Output signals STL1, STL2 and STL3 are
common for all steps. This means that the lowest set step will initiate the
activation. The START signal is common for all three phases and all steps. It shall
be noted that the selection of measured value (DFT or RMS) do not influence the
operation of directional part of OC4PTOC.

Service value for individually measured phase currents are also available on the
local HMI for OC4PTOC function, which simplifies testing, commissioning and in
service operational checking of the function.

A harmonic restrain of the function can be chosen. A set 2nd harmonic current in
relation to the fundamental current is used. The 2nd harmonic current is taken from
the pre-processing of the phase currents and the relation is compared to a set
restrain current level.

The function can be directional. The direction of the fault current is given as
current angle in relation to the voltage angle. The fault current and fault voltage for
the directional function is dependent of the fault type. To enable directional
measurement at close in faults, causing low measured voltage, the polarization
voltage is a combination of the apparent voltage (85%) and a memory voltage
(15%). The following combinations are used.

Phase-phase short circuit:

U refL1L 2 = U L1 - U L 2 I dirL1L 2 = I L1 - I L 2
EQUATION1449 V1 EN (Equation 58)

U refL 2 L 3 = U L 2 - U L 3 I dirL 2 L 3 = I L 2 - I L 3
EQUATION1450 V1 EN (Equation 59)

U refL 3 L1 = U L 3 - U L1 I dirL 3 L1 = I L 3 - I L1
EQUATION1451 V1 EN (Equation 60)
Table continues on next page

291
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Phase-earth short circuit:

U refL1 = U L1 I dirL1 = I L1
EQUATION1452 V1 EN (Equation 61)

U refL 2 = U L 2 I dirL 2 = I L 2
EQUATION1453 V1 EN (Equation 62)

U refL 3 = U L 3 I dirL 3 = I L 3
EQUATION1454 V1 EN (Equation 63)

The polarizing voltage is available as long as the positive-sequence voltage


exceeds 4% of the set base voltage UBase. So the directional element can use it for
all unsymmetrical faults including close-in faults.

For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.

The memory voltage is used for 100 ms or until the positive sequence voltage is
restored.

After 100 ms, the following occurs:

• If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set terminal rated current IBase), the condition
seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.
• If the current decreases below the minimum operating value, the memory
resets until the positive sequence voltage exceeds 10% of its rated value.

The directional setting is given as a characteristic angle AngleRCA for the function
and an angle window AngleROA.

292
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Reverse

Uref

RCA
ROA

ROA Forward

Idir

en05000745.vsd
IEC05000745 V1 EN

Figure 164: Directional characteristic of the phase overcurrent protection

The default value of AngleRCA is –65°. The parameters AngleROA gives the angle
sector from AngleRCA for directional borders.

A minimum current for directional phase start current signal can be set:
IminOpPhSel.

If no blockings are given the start signals will start the timers of the step. The time
characteristic for each step can be chosen as definite time delay or inverse time
characteristic. A wide range of standardized inverse time characteristics is
available. It is also possible to create a tailor made time characteristic. The
possibilities for inverse time characteristics are described in section "Inverse
characteristics".

All four steps in OC4PTOC can be blocked from the binary input BLOCK. The
binary input BLKSTx (x=1, 2, 3 or 4) blocks the operation of respective step.

Different types of reset time can be selected as described in section "Inverse


characteristics".

There is also a possibility to activate a preset change (IxMult x= 1, 2, 3 or 4) of the


set operation current via a binary input (enable multiplier). In some applications the
operation value needs to be changed, for example due to changed network
switching state. The function can be blocked from the binary input BLOCK. The
start signals from the function can be blocked from the binary input BLKST. The
trip signals from the function can be blocked from the binary input BLKTR.

293
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

7.2.3 Function block


OC4PTOC
I3P* TRIP
U3P* TR1
BLOCK TR2
BLKTR TR3
BLKST1 TR4
BLKST2 TRL1
BLKST3 TRL2
BLKST4 TRL3
ENMULT1 TR1L1
ENMULT2 TR1L2
ENMULT3 TR1L3
ENMULT4 TR2L1
TR2L2
TR2L3
TR3L1
TR3L2
TR3L3
TR4L1
TR4L2
TR4L3
START
ST1
ST2
ST3
ST4
STL1
STL2
STL3
ST1L1
ST1L2
ST1L3
ST2L1
ST2L2
ST2L3
ST3L1
ST3L2
ST3L3
ST4L1
ST4L2
ST4L3
2NDHARM
DIRL1
DIRL2
DIRL3

IEC06000187-2-en.vsd
IEC06000187 V2 EN

Figure 165: OC4PTOC function block

7.2.4 Input and output signals


Table 166: OC4PTOC Input signals
Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
BLKST1 BOOLEAN 0 Block of Step1
BLKST2 BOOLEAN 0 Block of Step2
Table continues on next page

294
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Name Type Default Description


BLKST3 BOOLEAN 0 Block of Step3
BLKST4 BOOLEAN 0 Block of Step4
ENMULT1 BOOLEAN 0 When activated, the current multiplier is in use for
step1
ENMULT2 BOOLEAN 0 When activated, the current multiplier is in use for
step2
ENMULT3 BOOLEAN 0 When activated, the current multiplier is in use for
step3
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for
step4

Table 167: OC4PTOC Output signals


Name Type Description
TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR2 BOOLEAN Common trip signal from step2
TR3 BOOLEAN Common trip signal from step3
TR4 BOOLEAN Common trip signal from step4
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
TR1L1 BOOLEAN Trip signal from step1 phase L1
TR1L2 BOOLEAN Trip signal from step1 phase L2
TR1L3 BOOLEAN Trip signal from step1 phase L3
TR2L1 BOOLEAN Trip signal from step2 phase L1
TR2L2 BOOLEAN Trip signal from step2 phase L2
TR2L3 BOOLEAN Trip signal from step2 phase L3
TR3L1 BOOLEAN Trip signal from step3 phase L1
TR3L2 BOOLEAN Trip signal from step3 phase L2
TR3L3 BOOLEAN Trip signal from step3 phase L3
TR4L1 BOOLEAN Trip signal from step4 phase L1
TR4L2 BOOLEAN Trip signal from step4 phase L2
TR4L3 BOOLEAN Trip signal from step4 phase L3
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST2 BOOLEAN Common start signal from step2
ST3 BOOLEAN Common start signal from step3
ST4 BOOLEAN Common start signal from step4
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
Table continues on next page

295
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Name Type Description


STL3 BOOLEAN Start signal from phase L3
ST1L1 BOOLEAN Start signal from step1 phase L1
ST1L2 BOOLEAN Start signal from step1 phase L2
ST1L3 BOOLEAN Start signal from step1 phase L3
ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2
ST2L3 BOOLEAN Start signal from step2 phase L3
ST3L1 BOOLEAN Start signal from step3 phase L1
ST3L2 BOOLEAN Start signal from step3 phase L2
ST3L3 BOOLEAN Start signal from step3 phase L3
ST4L1 BOOLEAN Start signal from step4 phase L1
ST4L2 BOOLEAN Start signal from step4 phase L2
ST4L3 BOOLEAN Start signal from step4 phase L3
2NDHARM BOOLEAN Block from second harmonic detection
DIRL1 INTEGER Direction for phase1
DIRL2 INTEGER Direction for phase2
DIRL3 INTEGER Direction for phase3

7.2.5 Setting parameters


Table 168: OC4PTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
AngleRCA 40 - 65 Deg 1 55 Relay characteristic angle (RCA)
AngleROA 40 - 89 Deg 1 80 Relay operation angle (ROA)
StartPhSel Not Used - - 1 out of 3 Number of phases required for op (1 of
1 out of 3 3, 2 of 3, 3 of 3)
2 out of 3
3 out of 3
DirMode1 Off - - Non-directional Directional mode of step 1 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Table continues on next page

296
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Name Values (Range) Unit Step Default Description


Characterist1 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. step 1
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I1> 1 - 2500 %IB 1 1000 Phase current operate level for step1 in
% of IBase
t1 0.000 - 60.000 s 0.001 0.000 Definitive time delay of step 1
k1 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delay
for step 1
t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves
for step 1
I1Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for
step 1
DirMode2 Off - - Non-directional Directional mode of step 2 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist2 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. step 2
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2> 1 - 2500 %IB 1 500 Phase current operate level for step2 in
% of IBase
t2 0.000 - 60.000 s 0.001 0.400 Definitive time delay of step 2
k2 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delay
for step 2
Table continues on next page

297
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Name Values (Range) Unit Step Default Description


I2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for
step 2
t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves
for step 2
DirMode3 Off - - Non-directional Directional mode of step 3 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist3 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. step 3
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I3> 1 - 2500 %IB 1 250 Phase current operate level for step3 in
% of IBase
t3 0.000 - 60.000 s 0.001 0.800 Definitive time delay of step 3
k3 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delay
for step 3
t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves
for step 3
I3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for
step 3
DirMode4 Off - - Non-directional Directional mode of step 4 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist4 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. step 4
ANSI Norm. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
Table continues on next page

298
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Name Values (Range) Unit Step Default Description


I4> 1 - 2500 %IB 1 175 Phase current operate level for step4 in
% of IBase
t4 0.000 - 60.000 s 0.001 2.000 Definitive time delay of step 4
k4 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delay
for step 4
t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves
for step 4
I4Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for
step 4

Table 169: OC4PTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
IMinOpPhSel 1 - 100 %IB 1 7 Minimum current for phase selection in
% of IBase
2ndHarmStab 5 - 100 %IB 1 20 Operate level of 2nd harm restrain op in
% of Fundamental
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of reset curve type for step 1
IEC Reset
ANSI reset
tReset1 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC Definite
Time curve step 1
tPCrv1 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
tACrv1 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 1
tBCrv1 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 1
tCCrv1 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 1
tPRCrv1 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 1
tTRCrv1 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 1
tCRCrv1 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 1
HarmRestrain1 Off - - Off Enable block of step 1 from harmonic
On restrain
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of reset curve type for step 2
IEC Reset
ANSI reset
tReset2 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC Definite
Time curve step 2
tPCrv2 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 2
tACrv2 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 2
tBCrv2 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 2
Table continues on next page

299
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Name Values (Range) Unit Step Default Description


tCCrv2 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 2
tPRCrv2 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 2
tTRCrv2 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 2
tCRCrv2 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 2
HarmRestrain2 Off - - Off Enable block of step 2 from harmonic
On restrain
ResetTypeCrv3 Instantaneous - - Instantaneous Selection of reset curve type for step 3
IEC Reset
ANSI reset
tReset3 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC Definite
Time curve step 3
tPCrv3 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 3
tACrv3 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 3
tBCrv3 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 3
tCCrv3 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 3
tPRCrv3 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 3
tTRCrv3 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 3
tCRCrv3 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 3
HarmRestrain3 Off - - Off Enable block of step3 from harmonic
On restrain
ResetTypeCrv4 Instantaneous - - Instantaneous Selection of reset curve type for step 4
IEC Reset
ANSI reset
tReset4 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC Definite
Time curve step 4
tPCrv4 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 4
tACrv4 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 4
tBCrv4 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 4
tCCrv4 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 4
tPRCrv4 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 4
Table continues on next page

300
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Name Values (Range) Unit Step Default Description


tTRCrv4 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 4
HarmRestrain4 Off - - Off Enable block of step 4 from harmonic
On restrain

Table 170: OC4PTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
MeasType DFT - - DFT Selection between DFT and RMS
RMS measurement

7.2.6 Technical data


Table 171: OC4PTOC technical data
Function Setting range Accuracy
Operate current (1-2500)% of lBase ± 1.0% of Ir at I £ Ir
± 1.0% of I at I > Ir

Reset ratio > 95% -


Min. operating current (1-100)% of lBase ± 1.0% of Ir

Relay characteristic angle (RCA) (-70.0– -50.0) degrees ± 2.0 degrees


Maximum forward angle (40.0–70.0) degrees ± 2.0 degrees
Minimum forward angle (75.0–90.0) degrees ± 2.0 degrees
2nd harmonic blocking (5–100)% of fundamental ± 2.0% of Ir

Independent time delay (0.000-60.000) s ± 0.5% ± 10 ms


Minimum operate time (0.000-60.000) s ± 0.5% ± 10 ms
Inverse characteristics, see 19 curve types See table 644, table 645 and
table 644, table 645 and table table 646
646
Operate time, start function 25 ms typically at 0 to 2 x Iset -

Reset time, start function 25 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

7.3 Instantaneous residual overcurrent protection


EFPIOC

301
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Instantaneous residual overcurrent EFPIOC 50N
protection
IN>>

IEF V1 EN

7.3.1 Introduction
The Instantaneous residual overcurrent protection EFPIOC has a low transient
overreach and short tripping times to allow the use for instantaneous earth-fault
protection, with the reach limited to less than typical eighty percent of the line at
minimum source impedance. EFPIOC can be configured to measure the residual
current from the three-phase current inputs or the current from a separate current
input. EFPIOC can be blocked by activating the input BLOCK.

7.3.2 Principle of operation


The sampled analog residual currents are pre-processed in a discrete Fourier filter
(DFT) block. From the fundamental frequency components of the residual current,
as well as from the sample values the equivalent RMS value is derived. This
current value is fed to the Instantaneous residual overcurrent protection (EFPIOC).
In a comparator the RMS value is compared to the set operation current value of
the function (IN>>). If the residual current is larger than the set operation current a
signal from the comparator is set to true. This signal will, without delay, activate
the output signal TRIP.

There is also a possibility to activate a preset change of the set operation current
via a binary input (enable multiplier MULTEN). In some applications the operation
value needs to be changed, for example due to transformer inrush currents.

EFPIOC function can be blocked from the binary input BLOCK. The trip signals
from the function can be blocked from the binary input BLKAR, that can be
activated during single pole trip and autoreclosing sequences.

7.3.3 Function block


EFPIOC
I3P* TRIP
BLOCK
BLKAR
MULTEN

IEC06000269-2-en.vsd
IEC06000269 V2 EN

Figure 166: EFPIOC function block

302
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.3.4 Input and output signals


Table 172: EFPIOC Input signals
Name Type Default Description
I3P GROUP - Three phase currents
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKAR BOOLEAN 0 Block input for auto reclose
MULTEN BOOLEAN 0 Enable current multiplier

Table 173: EFPIOC Output signals


Name Type Description
TRIP BOOLEAN Trip signal

7.3.5 Setting parameters


Table 174: EFPIOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current
IN>> 1 - 2500 %IB 1 200 Operate residual current level in % of
IBase

Table 175: EFPIOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
StValMult 0.5 - 5.0 - 0.1 1.0 Multiplier for operate current level

7.3.6 Technical data


Table 176: EFPIOC technical data
Function Range or value Accuracy
Operate current (1-2500)% of lBase ± 1.0% of Ir at I £ Ir
± 1.0% of I at I > Ir

Reset ratio > 95% -


Operate time 25 ms typically at 0 to 2 x Iset -

Reset time 25 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time 10 ms typically at 0 to 10 x Iset -

Table continues on next page

303
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Function Range or value Accuracy


Reset time 35 ms typically at 10 to 0 x Iset -

Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

7.4 Four step residual overcurrent protection EF4PTOC

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Four step residual overcurrent EF4PTOC IN 51N/67N
protection
4
alt
4
TEF-REVA V1 EN

7.4.1 Introduction
The four step residual overcurrent protection EF4PTOC has an inverse or definite
time delay independent for each step separately.

All IEC and ANSI time delayed characteristics are available together with an
optional user defined characteristic.

The directional function is voltage polarized, current polarized or dual polarized.

EF4PTOC can be set directional or non-directional independently for each of the


steps.

A second harmonic blocking can be set individually for each step.

EF4PTOC can be used as main protection for phase-to-earth faults.

EF4PTOC can also be used to provide a system back-up for example, in the case of
the primary protection being out of service due to communication or voltage
transformer circuit failure.

Directional operation can be combined together with corresponding


communication logic in permissive or blocking teleprotection scheme. Current
reversal and weak-end infeed functionality are available as well.

EF4PTOC can be configured to measure the residual current from the three-phase
current inputs or the current from a separate current input.

304
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.4.2 Principle of operation


This function has the following three “Analog Inputs” on its function block in the
configuration tool:

1. I3P, input used for “Operating Quantity”.


2. U3P, input used for “Voltage Polarizing Quantity”.
3. I3PPOL, input used for “Current Polarizing Quantity”.

These inputs are connected from the corresponding pre-processing function blocks
in the Configuration Tool within PCM600.

7.4.2.1 Operating quantity within the function

The function always uses Residual Current (3I0) for its operating quantity. The
residual current can be:

1. directly measured (when a dedicated CT input of the IED is connected in


PCM600 to the fourth analog input of the pre-processing block connected to
EF4PTOC function input I3P). This dedicated IED CT input can be for
example, connected to:
• parallel connection of current instrument transformers in all three phases
(Holm-Green connection).
• one single core balance, current instrument transformer (cable CT).
• one single current instrument transformer located between power system
star point and earth (that is, current transformer located in the star point
of a star connected transformer winding).
• one single current instrument transformer located between two parts of a
protected object (that is, current transformer located between two star
points of double star shunt capacitor bank).
2. calculated from three-phase current input within the IED (when the fourth
analog input into the pre-processing block connected to EF4PTOC function
Analog Input I3P is not connected to a dedicated CT input of the IED in
PCM600). In such case the pre-processing block will calculate 3I0 from the
first three inputs into the pre-processing block by using the following formula:

Iop = 3I0 = IL1 + IL2 + IL3


EQUATION1874 V2 EN (Equation 64)

where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.

The residual current is pre-processed by a discrete Fourier filter. Thus the phasor of
the fundamental frequency component of the residual current is derived. The
phasor magnitude is used within the EF4PTOC protection to compare it with the

305
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

set operation current value of the four steps (IN1>, IN2>, IN3> or IN4>). If the
residual current is larger than the set operation current and the step is used in non-
directional mode a signal from the comparator for this step is set to true. This
signal will, without delay, activate the output signal STINx (x=step 1-4) for this
step and a common START signal.

7.4.2.2 Internal polarizing

A polarizing quantity is used within the protection in order to determine the


direction to the earth fault (Forward/Reverse).

The function can be set to use voltage polarizing, current polarizing or dual polarizing.

Voltage polarizing
When voltage polarizing is selected the protection will use the residual voltage
-3U0 as polarizing quantity U3P. This voltage can be:

1. directly measured (when a dedicated VT input of the IED is connected in


PCM600 to the fourth analog input of the pre-processing block connected to
EF4PTOC function input U3P). This dedicated IED VT input shall be then
connected to open delta winding of a three phase main VT.
2. calculated from three phase voltage input within the IED (when the fourth
analog input into the pre-processing block connected to EF4PTOC analog
function input U3P is NOT connected to a dedicated VT input of the IED in
PCM600). In such case the pre-processing block will calculate -3U0 from the
first three inputs into the pre-processing block by using the following formula:

UPol = -3U 0 = -(UL1 + UL2 + UL3)


EQUATION1875 V2 EN (Equation 65)

where:
UL1, UL2 and UL3 are fundamental frequency phasors of three individual phase voltages.
Note! In order to use this all three phase-to-earth voltages must be connected to three IED VT inputs.

The residual voltage is pre-processed by a discrete fourier filter. Thus, the phasor
of the fundamental frequency component of the residual voltage is derived. This
phasor is used together with the phasor of the operating current, in order to
determine the direction to the earth fault (Forward/Reverse). In order to enable
voltage polarizing the magnitude of polarizing voltage shall be bigger than a
minimum level defined by setting parameter UpolMin.

It shall be noted that –3U0 is used to determine the location of the earth fault. This
insures the required inversion of the polarizing voltage within the earth-fault function.

306
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Current polarizing
When current polarizing is selected the function will use the residual current (3I0)
as polarizing quantity IPol. This current can be:

1. directly measured (when a dedicated CT input of the IED is connected in


PCM600 to the fourth analog input of the pre-processing block connected to
EF4PTOC function input I3PPOL). This dedicated IED CT input is then
typically connected to one single current transformer located between power
system star point and earth (current transformer located in the star point of a
star connected transformer winding).
• For some special line protection applications this dedicated IED CT
input can be connected to parallel connection of current transformers in
all three phases (Holm-Green connection)
2. calculated from three phase current input within the IED (when the fourth
analog input into the pre-processing block connected to EF4PTOC function
analog input I3PPOL is NOT connected to a dedicated CT input of the IED in
PCM600). In such case the pre-processing block will calculate 3I0 from the
first three inputs into the pre-processing block by using the following formula:

IPol = 3I0 = IL1 + IL2 + IL3


EQUATION2018 V2 EN (Equation 66)

where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.

The residual polarizing current is pre-processed by a discrete fourier filter. Thus


the phasor of the fundamental frequency component of the residual current is
derived. This phasor is then multiplied with pre-set equivalent zero-sequence
source Impedance in order to calculate equivalent polarizing voltage UIPol in
accordance with the following formula:

UIPol = Z 0s × IPol = (RNPol + j × XNPol) × IPol


EQUATION1877 V2 EN (Equation 67)

, which will be then used, together with the phasor of the operating current, in order
to determine the direction to the earth fault (Forward/Reverse). In order to enable
current polarizing the magnitude of polarizing current shall be bigger than a
minimum level defined by setting parameter IPolMin.

Dual polarizing
When dual polarizing is selected the function will use the vectorial sum of the
voltage based and current based polarizing in accordance with the following formula:

307
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

UTotPol = UUPol + UIPol = -3U 0 + Z 0 s × IPol = -3U 0 + ( RNPol + jXNPol ) × IPol


EQUATION1878 V3 EN (Equation 68)

Then the phasor of the total polarizing voltage UTotPol will be used, together with
the phasor of the operating current, to determine the direction of the earth fault
(Forward/Reverse).

7.4.2.3 External polarizing for earth-fault function

The individual steps within the protection can be set as non-directional. When this
setting is selected it is then possible via function binary input BLKSTx to provide
external directional control (that is, torque control) by for example using one of the
following functions if available in the IED:

1. Distance protection directional function.


2. Negative sequence polarized General current and voltage multi purpose
protection function.

7.4.2.4 Base quantities within the protection

The base quantities shall be entered as setting parameters for every earth-fault
function. Base current (IBase) shall be entered as rated phase current of the
protected object in primary amperes. Base voltage (UBase) shall be entered as
rated phase-to-phase voltage of the protected object in primary kV.

7.4.2.5 Internal earth-fault protection structure

The protection is internally divided into the following parts:

1. Four residual overcurrent steps.


2. Directional supervision element for residual overcurrent steps with integrated
directional comparison step for communication based earth-fault protection
schemes (permissive or blocking).
3. Second harmonic blocking element with additional feature for sealed-in
blocking during switching of parallel transformers.
4. Switch on to fault feature with integrated Under-Time logic for detection of
breaker problems during breaker opening or closing sequence.

Each part is described separately in the following sections.

7.4.2.6 Four residual overcurrent steps

Each overcurrent step uses operating quantity Iop (residual current) as measuring
quantity. Each of the four residual overcurrent steps has the following built-in
facilities:

• Directional mode can be set to Off/Non-directional/Forward/Reverse. By this


parameter setting the directional mode of the step is selected. It shall be noted
308
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

that the directional decision (Forward/Reverse) is not made within the residual
overcurrent step itself. The direction of the fault is determined in common
“directional supervision element”.
• Residual current pickup value.
• Type of operating characteristic (inverse or definite time). By this parameter
setting it is possible to select inverse or definite time delay for the earth-fault
protection. Most of the standard IEC and ANSI inverse characteristics are
available. For the complete list of available inverse curves please refer to
section "Inverse characteristics".
• Type of reset characteristic (Instantaneous / IEC Reset / ANSI Reset). By this
parameter setting it is possible to select the reset characteristic of the step. For
the complete list of available reset curves please refer to section "Inverse time
characteristics".
• Time delay related settings. By these parameter settings the properties like
definite time delay, minimum operating time for inverse curves, reset time
delay and parameters to define user programmable inverse curve are defined.
• Supervision by second harmonic blocking feature (On/Off). By this parameter
setting it is possible to prevent operation of the step if the second harmonic
content in the residual current exceeds the preset level.
• Multiplier for scaling of the set residual current pickup value by external
binary signal. By this parameter setting it is possible to increase residual
current pickup value when function binary input ENMULTx has logical value
1.

Simplified logic diagram for one residual overcurrent step is shown in figure 167.

BLKTR

Characteristx=DefTime tx TRINx
|IOP| AND
a OR
a>b
b
ENMULTx
STINx
INxMult AND
X T
INx> F
Inverse
BLKSTx

BLOCK Characteristx=Inverse

2ndH_BLOCK_Int
OR
HarmRestrain1=Disabled

DirModex=Off OR STAGEx_DIR_Int

DirModex=Non-directional
DirModex=Forward
AND OR
FORWARD_Int
DirModex=Reverse

AND
REVERSE_Int

en07000064.vsd

IEC07000064 V1 EN

Figure 167: Simplified logic diagram for residual overcurrent step x, where x =
step 1, 2, 3 or 4

The protection can be completely blocked from the binary input BLOCK. Output
signals for respective step, STINx and TRINx, can be blocked from the binary

309
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

input BLKSTx. The trip signals from the function can be blocked from the binary
input BLKTR.

7.4.2.7 Directional supervision element with integrated directional


comparison function

It shall be noted that at least one of the four residual overcurrent


steps shall be set as directional in order to enable execution of the
directional supervision element and the integrated directional
comparison function.

The protection has integrated directional feature. As the operating quantity current
Iop is always used. The polarizing method is determined by the parameter setting
polMethod. The polarizing quantity will be selected by the function in one of the
following three ways:

1. When polMethod = Voltage, UVPol will be used as polarizing quantity.


2. When polMethod = Current, UIpol will be used as polarizing quantity.
3. WhenpolMethod = Dual, UTotPol will be used as polarizing quantity.

The operating and polarizing quantity are then used inside the directional element,
as shown in figure 168, in order to determine the direction of the earth fault.

310
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Reverse
Area

0.6·IN>Dir

AngleRCA Upol=-3Uo

IN>Dir

Forward
Area
Iop=3Io

IEC07000066-3-en.vsd
IEC07000066 V3 EN

Figure 168: Operating characteristic for earth-fault directional element

Two relevant setting parameters for directional supervision element are:

• Directional element will be internally enabled to operate as soon as Iop is


bigger than 40% of IN>Dir and directional condition is fulfilled in set direction.
• Relay characteristic angle AngleRCA, which defines the position of forward
and reverse areas in the operating characteristic.

Directional comparison step, built-in within directional supervision element, will


set EF4PTOC function output binary signals:

1. STFW=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is


bigger than setting parameterIN>Dir and directional supervision element
detects fault in forward direction.
2. STRV=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is
bigger than 60% of setting parameter IN>Dir and directional supervision
element detects fault in reverse direction.

These signals shall be used for communication based earth-fault teleprotection


communication schemes (permissive or blocking).

Simplified logic diagram for directional supervision element with integrated


directional comparison step is shown in figure 169:

311
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

|Iop|
a
a>b STRV
b AND
REVERSE_Int
0.6
X
a
a>b
AND STFW
IN>Dir b
FORWARD_Int

X
0.4

FWD
AND FORWARD_Int
AngleRCA
polMethod=Voltage
OR
UPolMin

Characteristic
Directional
polMethod=Dual UPol IPolMin
T
Iop
0.0 F
UTotPol
IPol AND REVERSE_Int
RVS
UIPol
RNPol Complex X T
XNPol Number 0.0 F STAGE1_DIR_Int
STAGE2_DIR_Int
STAGE3_DIR_Int OR
STAGE4_DIR_Int
BLOCK AND

IEC07000067-3-en.vsd

IEC07000067 V3 EN

Figure 169: Simplified logic diagram for directional supervision element with integrated directional
comparison step

7.4.2.8 Second harmonic blocking element

A harmonic restrain of the Four step residual overcurrent protection function


EF4PTOC can be chosen. If the ratio of the 2nd harmonic component in relation to
the fundamental frequency component in the residual current exceeds the pre-set
level (defined by parameter setting 2ndHarmStab) any of the four residual
overcurrent stages can be selectively blocked by a parameter setting
HarmRestrainx. When 2nd harmonic restraint feature is active the EF4PTOC
function output signal 2NDHARMD will be set to logical value one.

In addition to the basic functionality explained above the 2nd harmonic blocking
can be set in such way to seal-in until residual current disappears. This feature
might be required to stabilize EF4PTOC during switching of parallel transformers
in the station. In case of parallel transformers there is a risk of sympathetic inrush
current. If one of the transformers is in operation, and the parallel transformer is

312
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

switched in, the asymmetric inrush current of the switched in transformer will
cause partial saturation of the transformer already in service. This is called
transferred saturation. The 2nd harmonic of the inrush currents of the two
transformers will be in phase opposition. The summation of the two currents will
thus give a small 2nd harmonic current. The residual fundamental current will
however be significant. The inrush current of the transformer in service before the
parallel transformer energizing, will be a little delayed compared to the first
transformer. Therefore we will have high 2nd harmonic current component initially.
After a short period this current will however be small and the normal 2nd
harmonic blocking will reset. If the BlkParTransf function is activated the 2nd
harmonic restrain signal will be latched as long as the residual current measured by
the relay is larger than a selected step current level.

This feature has been called Block for Parallel Transformers. This 2nd harmonic seal-
in feature will be activated when all of the following three conditions are
simultaneously fulfilled:

1. Feature is enabled by entering setting parameter BlkParTransf = On.


2. Basic 2nd harmonic restraint feature has been active for at least 70ms.
3. Residual current magnitude is higher than the set start value for one of the four
residual overcurrent stages. By a parameter setting UseStartValue it is possible
to select which one of the four start values that will be used (IN1> or IN2> or
IN3> or IN4>).

Once Block for Parallel Transformers is activated the basic 2nd harmonic blocking
signal will be sealed-in until the residual current magnitude falls below a value
defined by parameter setting UseStartValue (see condition 3 above).

Simplified logic diagram for 2nd harmonic blocking feature is shown in figure 170.

313
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

BLOCK

Extract second
IOP 2NDHARMD
harmonic current a
a>b
OR
component 2ndHarmStab b
X
Extract
fundamental
q-1
current component

t=70ms OR
t AN OR 2ndH_BLOCK_Int
D

BlkParTransf=On
|IOP|
a
a>b
b
UseStartValue
IN1>
IN2>
IN3>
IN4>

en07000068-2.vsd

IEC07000068 V2 EN

Figure 170: Simplified logic diagram for 2nd harmonic blocking feature and Block for Parallel Transformers
feature

7.4.2.9 Switch on to fault feature

Integrated in the four step residual overcurrent protection are Switch on to fault
logic (SOTF) and Under-Time logic. The setting parameter SOTF is set to activate
either SOTF or Under-Time logic or both. When the circuit breaker is closing there
is a risk to close it onto a permanent fault, for example during an autoreclosing
sequence. The SOTF logic will enable fast fault clearance during such situations.
The time during which SOTF and Under-Time logics will be active after activation
is defined by the setting parameter t4U.

The SOTF logic uses the start signal from step 2 or step 3 for its operation, selected
by setting parameter StepForSOTF. The SOTF logic can be activated either from
change in circuit breaker position or from circuit breaker close command pulse.
The setting parameter ActivationSOTF can be set for activation of CB position
open change, CB position closed change or CB close command. In case of a
residual current start from step 2 or 3 (dependent on setting) the function will give
a trip after a set delay tSOTF. This delay is normally set to a short time (default 200
ms).

The Under-Time logic always uses the start signal from the step 4. The Under-
Time logic will normally be set to operate for a lower current level than the SOTF

314
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

function. The Under-Time logic can also be blocked by the 2nd harmonic restraint
feature. This enables high sensitivity even if power transformer inrush currents can
occur at breaker closing. This logic is typically used to detect asymmetry of CB
poles immediately after switching of the circuit breaker. The Under-Time logic is
activated either from change in circuit breaker position or from circuit breaker
close and open command pulses. This selection is done by setting parameter
ActUnderTime. In case of a start from step 4 this logic will give a trip after a set
delay tUnderTime. This delay is normally set to a relatively short time (default 300
ms). Practically the Under-Time logic acts as circuit breaker pole-discordance
protection, but it is only active immediately after breaker switching. The Under-
Time logic can only be used in solidly or low impedance grounded systems.

SOTF

Open
tPulse
Closed
ActivationSOTF
Close command
tSOTF
AND
AND t
STIN2

StepForSOTF
STIN3

OperationMode
BLOCK
OFF
SOTF
UNDERTIME TRIP
UnderTime

tUnderTime
SOTF or
2nd Harmonic AND
HarmResSOFT t UnderTime

OR

Open
Close OR

tPulse

Close command
ActUnderTime
AND

STIN4

IEC06000643-2-en.vsd

IEC06000643 V2 EN

Figure 171: Simplified logic diagram for SOTF and Under-Time features

EF4PTOC Logic Diagram Simplified logic diagram for the complete EF4PTOC
function is shown in figure 172:

315
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

signal to
communication
scheme
Directional Check
Element

4 step over current


INPol Direction
operatingCurrent element TRIP
Element
3U0 One element for each
earthFaultDirection step
3I0 angleValid

DirMode
enableDir

harmRestrBlock
3I0 Harmonic
Restraint ³1
Element

start step 2, 3 and


4
Blocking at parallel
transformers
SwitchOnToFault
TRIP

CB
DirMode pos
or cmd
enableDir
Mode
Selection enableStep1-4

DirectionalMode1-4

en06000376.vsd
IEC06000376 V1 EN

Figure 172: Functional overview of EF4PTOC

7.4.3 Function block


EF4PTOC
I3P* TRIP
U3P* TRIN1
I3PPOL* TRIN2
BLOCK TRIN3
BLKTR TRIN4
BLKST1 TRSOTF
BLKST2 START
BLKST3 STIN1
BLKST4 STIN2
ENMULT1 STIN3
ENMULT2 STIN4
ENMULT3 STSOTF
ENMULT4 STFW
CBPOS STRV
CLOSECB 2NDHARMD
OPENCB

IEC06000424-2-en.vsd
IEC06000424 V2 EN

Figure 173: EF4PTOC function block

316
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.4.4 Input and output signals


Table 177: EF4PTOC Input signals
Name Type Default Description
I3P GROUP - Current connection
SIGNAL
U3P GROUP - Polarizing voltage connection
SIGNAL
I3PPOL GROUP - Polarizing current connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
BLKST1 BOOLEAN 0 Block of step 1 (Start and trip)
BLKST2 BOOLEAN 0 Block of step 2 (Start and trip)
BLKST3 BOOLEAN 0 Block of step 3 (Start and trip)
BLKST4 BOOLEAN 0 Block of step 4 (Start and trip)
ENMULT1 BOOLEAN 0 When activated, the current multiplier is in use for
step1
ENMULT2 BOOLEAN 0 When activated, the current multiplier is in use for
step2
ENMULT3 BOOLEAN 0 When activated, the current multiplier is in use for
step3
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for
step4
CBPOS BOOLEAN 0 Breaker position
CLOSECB BOOLEAN 0 Breaker close command
OPENCB BOOLEAN 0 Breaker open command

Table 178: EF4PTOC Output signals


Name Type Description
TRIP BOOLEAN Trip
TRIN1 BOOLEAN Trip signal from step 1
TRIN2 BOOLEAN Trip signal from step 2
TRIN3 BOOLEAN Trip signal from step 3
TRIN4 BOOLEAN Trip signal from step 4
TRSOTF BOOLEAN Trip signal from earth fault switch onto fault function
START BOOLEAN General start signal
STIN1 BOOLEAN Start signal step 1
STIN2 BOOLEAN Start signal step 2
STIN3 BOOLEAN Start signal step 3
STIN4 BOOLEAN Start signal step 4
STSOTF BOOLEAN Start signal from earth fault switch onto fault
function
Table continues on next page

317
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Name Type Description


STFW BOOLEAN Forward directional start signal
STRV BOOLEAN Reverse directional start signal
2NDHARMD BOOLEAN 2nd harmonic block signal

7.4.5 Setting parameters


Table 179: EF4PTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base value for current settings
UBase 0.05 - 2000.00 kV 0.05 400.00 Base value for voltage settings
AngleRCA -180 - 180 Deg 1 65 Relay characteristic angle (RCA)
polMethod Voltage - - Voltage Type of polarization
Current
Dual
UPolMin 1 - 100 %UB 1 1 Minimum voltage level for polarization in
% of UBase
IPolMin 2 - 100 %IB 1 5 Minimum current level for polarization in
% of IBase
RNPol 0.50 - 1000.00 ohm 0.01 5.00 Real part of source Z to be used for
current polarisation
XNPol 0.50 - 3000.00 ohm 0.01 40.00 Imaginary part of source Z to be used for
current polarisation
IN>Dir 1 - 100 %IB 1 10 Residual current level for Direction
release in % of IBase
2ndHarmStab 5 - 100 % 1 20 Second harmonic restrain operation in %
of IN amplitude
BlkParTransf Off - - Off Enable blocking at parallel transformers
On
UseStartValue IN1> - - IN4> Current level blk at parallel transf (step1,
IN2> 2, 3 or 4)
IN3>
IN4>
SOTF Off - - Off SOTF operation mode (Off/SOTF/
SOTF Undertime/SOTF+undertime)
UnderTime
SOTF+UnderTime
ActivationSOTF Open - - Open Select signal that shall activate SOTF
Closed
CloseCommand
StepForSOTF Step 2 - - Step 2 Selection of step used for SOTF
Step 3
HarmResSOTF Off - - Off Enable harmonic restrain function in
On SOTF
tSOTF 0.000 - 60.000 s 0.001 0.200 Time delay for SOTF
t4U 0.000 - 60.000 s 0.001 1.000 Switch-onto-fault active time
Table continues on next page

318
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Name Values (Range) Unit Step Default Description


DirMode1 Off - - Non-directional Directional mode of step 1 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist1 ANSI Ext. inv. - - ANSI Def. Time Time delay curve type for step 1
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN1> 1 - 2500 %IB 1 100 Operate residual current level for step 1
in % of IBase
t1 0.000 - 60.000 s 0.001 0.000 Independent (defenite) time delay of step
1
k1 0.05 - 999.00 - 0.01 0.05 Time multiplier for the dependent time
delay for step 1
IN1Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting
value for step 1
t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves
for step 1
HarmRestrain1 Off - - On Enable block of step 1 from harmonic
On restrain
DirMode2 Off - - Non-directional Directional mode of step 2 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist2 ANSI Ext. inv. - - ANSI Def. Time Time delay curve type for step 2
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
Table continues on next page

319
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Name Values (Range) Unit Step Default Description


IN2> 1 - 2500 %IB 1 50 Operate residual current level for step 2
in % of IBase
t2 0.000 - 60.000 s 0.001 0.400 Independent (definitive) time delay of
step 2
k2 0.05 - 999.00 - 0.01 0.05 Time multiplier for the dependent time
delay for step 2
IN2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting
value for step 2
t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves
step 2
HarmRestrain2 Off - - On Enable block of step 2 from harmonic
On restrain
DirMode3 Off - - Non-directional Directional mode of step 3 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist3 ANSI Ext. inv. - - ANSI Def. Time Time delay curve type for step 3
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN3> 1 - 2500 %IB 1 33 Operate residual current level for step 3
in % of IBase
t3 0.000 - 60.000 s 0.001 0.800 Independent time delay of step 3
k3 0.05 - 999.00 - 0.01 0.05 Time multiplier for the dependent time
delay for step 3
IN3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting
value for step 3
t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves
for step 3
HarmRestrain3 Off - - On Enable block of step 3 from harmonic
On restrain
DirMode4 Off - - Non-directional Directional mode of step 4 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Table continues on next page

320
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Name Values (Range) Unit Step Default Description


Characterist4 ANSI Ext. inv. - - ANSI Def. Time Time delay curve type for step 4
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN4> 1 - 2500 %IB 1 17 Operate residual current level for step 4
in % of IBase
t4 0.000 - 60.000 s 0.001 1.200 Independent (definitive) time delay of
step 4
k4 0.05 - 999.00 - 0.01 0.05 Time multiplier for the dependent time
delay for step 4
IN4Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting
value for step 4
t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time in inverse curves
step 4
HarmRestrain4 Off - - On Enable block of step 4 from harmonic
On restrain

Table 180: EF4PTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
ActUnderTime CB position - - CB position Select signal to activate under time (CB
CB command Pos/CBCommand)
tUnderTime 0.000 - 60.000 s 0.001 0.300 Time delay for under time
ResetTypeCrv1 Instantaneous - - Instantaneous Reset curve type for step 1
IEC Reset
ANSI reset
tReset1 0.000 - 60.000 s 0.001 0.020 Reset curve type for step 1
tPCrv1 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
tACrv1 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 1
tBCrv1 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 1
tCCrv1 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 1
tPRCrv1 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 1
Table continues on next page

321
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Name Values (Range) Unit Step Default Description


tTRCrv1 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 1
tCRCrv1 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 1
ResetTypeCrv2 Instantaneous - - Instantaneous Reset curve type for step 2
IEC Reset
ANSI reset
tReset2 0.000 - 60.000 s 0.001 0.020 Reset curve type for step 2
tPCrv2 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 2
tACrv2 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 2
tBCrv2 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 2
tCCrv2 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 2
tPRCrv2 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 2
tTRCrv2 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 2
tCRCrv2 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 2
ResetTypeCrv3 Instantaneous - - Instantaneous Reset curve type for step 3
IEC Reset
ANSI reset
tReset3 0.000 - 60.000 s 0.001 0.020 Reset curve type for step 3
tPCrv3 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 3
tACrv3 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 3
tBCrv3 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 3
tCCrv3 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve step 3
tPRCrv3 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve step 3
tTRCrv3 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve step 3
tCRCrv3 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 3
ResetTypeCrv4 Instantaneous - - Instantaneous Reset curve type for step 4
IEC Reset
ANSI reset
tReset4 0.000 - 60.000 s 0.001 0.020 Reset curve type for step 4
tPCrv4 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 4
tACrv4 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve step 4
Table continues on next page

322
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Name Values (Range) Unit Step Default Description


tBCrv4 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 4
tCCrv4 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve step 4
tPRCrv4 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve step 4
tTRCrv4 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve step 4

7.4.6 Technical data


Table 181: EF4PTOC technical data
Function Range or value Accuracy
Operate current (1-2500)% of lBase ± 1.0% of Ir at I £ Ir
± 1.0% of I at I > Ir

Reset ratio > 95% -


Operate current for directional (1–100)% of lBase ± 1.0% of Ir
comparison
Timers (0.000-60.000) s ± 0.5% ± 10 ms
Inverse characteristics, see 18 curve types See table 644, table 645 and
table 644, table 645 and table 646 table 646
Second harmonic restrain (5–100)% of fundamental ± 2.0% of Ir
operation
Relay characteristic angle (-180 to 180) degrees ± 2.0 degrees
Minimum polarizing voltage (1–100)% of UBase ± 0.5% of Ur

Minimum polarizing current (1-30)% of IBase ±0.25% of Ir

Real part of source Z used for (0.50-1000.00) W/phase -


current polarization
Imaginary part of source Z used (0.50–3000.00) W/phase -
for current polarization
Operate time, start function 25 ms typically at 0 to 2 x Iset -

Reset time, start function 25 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

7.5 Sensitive directional residual overcurrent and power


protection SDEPSDE

323
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Sensitive directional residual over SDEPSDE - 67N
current and power protection

7.5.1 Introduction
In networks with high impedance earthing, the phase-to-earth fault current is
significantly smaller than the short circuit currents. Another difficulty for earth-
fault protection is that the magnitude of the phase-to-earth fault current is almost
independent of the fault location in the network.

Directional residual current can be used to detect and give selective trip of phase-to-
earth faults in high impedance earthed networks. The protection uses the residual
current component 3I0 · cos φ, where φ is the angle between the residual current
and the residual voltage (-3U0), compensated with a characteristic angle.
Alternatively, the function can be set to strict 3I0 level with an check of angle 3I0
and cos φ.

Directional residual power can also be used to detect and give selective trip of phase-
to-earth faults in high impedance earthed networks. The protection uses the
residual power component 3I0 · 3U0 · cos φ, where φ is the angle between the
residual current and the reference residual voltage, compensated with a
characteristic angle.

A normal non-directional residual current function can also be used with definite or
inverse time delay.

A back-up neutral point voltage function is also available for non-directional


sensitive back-up protection.

In an isolated network, that is, the network is only coupled to earth via the
capacitances between the phase conductors and earth, the residual current always
has -90º phase shift compared to the reference residual voltage. The characteristic
angle is chosen to -90º in such a network.

In resistance earthed networks or in Petersen coil earthed, with a parallel resistor,


the active residual current component (in phase with the residual voltage) should be
used for the earth-fault detection. In such networks the characteristic angle is
chosen to 0º.

As the amplitude of the residual current is independent of the fault location the
selectivity of the earth-fault protection is achieved by time selectivity.

When should the sensitive directional residual overcurrent protection be used and
when should the sensitive directional residual power protection be used? Consider
the following facts:

324
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

• Sensitive directional residual overcurrent protection gives possibility for better


sensitivity
• Sensitive directional residual power protection gives possibility to use inverse
time characteristics. This is applicable in large high impedance earthed
networks, with large capacitive earth-fault current
• In some power systems a medium size neutral point resistor is used, for
example, in low impedance earthed system. Such a resistor will give a resistive
earth-fault current component of about 200 - 400 A at a zero resistive phase-to-
earth fault. In such a system the directional residual power protection gives
better possibilities for selectivity enabled by inverse time power characteristics.

7.5.2 Principle of operation

7.5.2.1 Function inputs

The function is using phasors of the residual current and voltage. Group signals I3P
and U3P containing phasors of residual current and voltage is taken from pre-
processor blocks.

The sensitive directional earth fault protection has the following sub-functions
included:

Directional residual current protection measuring 3I0·cos φ


φ is defined as the angle between the residual current 3I0 and the reference voltage
compensated with the set characteristic angle RCADir (φ=ang(3I0)-ang(Uref) ).
Uref = -3U0 ejRCADIr. RCADir is normally set equal to 0 in a high impedance
earthed network with a neutral point resistor as the active current component is
appearing out on the faulted feeder only. RCADir is set equal to -90° in an isolated
network as all currents are mainly capacitive. The function operates when 3I0·cos φ
gets larger than the set value.

325
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Uref
RCADir = 0o, ROADir = 0o

3I0

j = ang(3I0 ) - ang(3Uref )
-3U0 = Uref
3I0 × cosj

IEC06000648_2_en.vsd
IEC06000648 V2 EN

Figure 174: RCADir set to 0°

Uref
RCADir = -90o, ROADir = 90o

3I0
3I0 × cos j

j = ang (3I0 ) - ang (Uref )

-3U0

IEC06000649_2_en.vsd
IEC06000649 V2 EN

Figure 175: RCADir set to -90°

For trip, both the residual current 3I0·cos φ and the release voltage 3U0, must be
larger than the set levels: INCosPhi> and UNRel>.

Trip from this function can be blocked from the binary input BLKTRDIR.

326
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef the binary output signals
TRIP and TRDIRIN are activated. The trip from this sub-function has definite time
delay.

There is a possibility to increase the operate level for currents where the angle φ is
larger than a set value as shown in the figure below. This is equivalent to blocking
of the function if φ > ROADir. This option is used to handle angle error for the
instrument transformers.

RCADir = 0o

3I0
Operate area

j
-3U0 = Uref
3I0 × cos j

ROADir

IEC06000650_2_en.vsd
IEC06000650 V2 EN

Figure 176: Characteristic with ROADir restriction

The function indicates forward/reverse direction to the fault. Reverse direction is


defined as 3I0·cos (φ + 180°) ≥ the set value.

It is also possible to tilt the characteristic to compensate for current transformer


angle error with a setting RCAComp as shown in the figure 177:

327
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

RCADir = 0º

Operate area

-3U0 =Uref

Instrument
transformer a
RCAcomp
angle error
Characteristic after
angle compensation

3I0 (to prot)


3I0 (prim)

en06000651.vsd
IEC06000651 V2 EN

Figure 177: Explanation of RCAComp

Directional residual power protection measuring 3I0 · 3U0 · cos φ


φ is defined as the angle between the residual current 3I0 and the reference voltage
compensated with the set characteristic angle RCADir (φ=ang(3I0)—ang(Uref) ).
Uref = -3U0 e-jRCA. The function operates when 3I0 · 3U0 · cos φ gets larger than
the set value.

For trip, both the residual power 3I0 · 3U0 · cos φ, the residual current 3I0 and the
release voltage 3U0, shall be larger than the set levels (SN>, INRel> and UNRel>).

Trip from this function can be blocked from the binary input BLKTRDIR.

When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef or after the inverse time
delay (setting kSN) the binary output signals TRIP and TRDIRIN are activated.

The function shall indicate forward/reverse direction to the fault. Reverse direction
is defined as 3I0 · 3U0·cos (φ + 180°) ³ the set value.

This variant has the possibility of choice between definite time delay and inverse
time delay.

328
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

The inverse time delay is defined as:

kSN × (3I0 × 3U 0 × cos j(reference))


t inv =
3I0 × 3U 0 × cos j(measured)
EQUATION1942 V2 EN (Equation 69)

Directional residual current protection measuring 3I0 and φ


The function will operate if the residual current is larger that the set value and the
angle φ = ang(3I0)-ang(Uref) is within the sector RCADir ± ROADir

RCADir = 0º

ROADir = 80º

Operate area

3I0

80 -3U0

en06000652.vsd
IEC06000652 V2 EN

Figure 178: Example of characteristic

For trip, both the residual current 3I0 and the release voltage 3U0, shall be larger
than the set levels INDir> and UNREL> and the angle φ shall be in the set sector
ROADir and RCADir.

Trip from this function can be blocked from the binary input BLKTRDIR.

When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef the binary output signals
TRIP and TRDIRIN are activated.

The function indicate forward/reverse direction to the fault. Reverse direction is


defined as φ is within the angle sector: RCADir + 180° ± ROADir

This variant shall have definite time delay.

329
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Directional functions
For all the directional functions there are directional start signals STFW: fault in
the forward direction, and STRV: start in the reverse direction. Even if the
directional function is set to operate for faults in the forward direction a fault in the
reverse direction will give the start signal STRV. Also if the directional function is
set to operate for faults in the reverse direction a fault in the forward direction will
give the start signal STFW.

Non-directional earth fault current protection


This function will measure the residual current without checking the phase angle.
The function will be used to detect cross-country faults. This function can serve as
alternative or back-up to distance protection with phase preference logic. To assure
selectivity the distance protection can block the non-directional earth fault current
function via the input BLKNDN.

If available the non-directional function is using the calculated residual current,


derived as sum of the phase currents. This will give a better ability to detect cross-
country faults with high residual current, also when dedicated core balance CT for
the sensitive earth fault protection will saturate.

This variant shall have the possibility of choice between definite time delay and
inverse time delay. The inverse time delay shall be according to IEC 60255-3.

For trip, the residual current 3I0 shall be larger than the set levels (INNonDir>).

Trip from this function can be blocked from the binary input BLKNDN.

When the function is activated binary output signal STNDIN is activated. If the
activation is active after the set delay tINNonDir or after the inverse time delay the
binary output signals TRIP and TRNDIN are activated.

Residual overvoltage release and protection


The directional function shall be released when the residual voltage gets higher
than a set level.

There shall also be a separate trip, with its own definite time delay, from this set
voltage level.

For trip, the residual voltage 3U0 shall be larger than the set levels (UN>).

Trip from this function can be blocked from the binary input BLKUN.

When the function is activated binary output signal STUN is activated. If the
activation is active after the set delay tUNNonDir TRIP and TRUN are activated. A
simplified logical diagram of the total function is shown in figure 179.

330
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

INNonDir> STNDIN
t TRNDIN

UN> STUN
t TRUN

OpMODE=3I0cosfi

IN>
&

INcosPhi>

OpMODE=3I03U0cosfi

& ³1 & STARTDIRIN

INUNcosPhi> t

SN
& TRDIRIN
Phi in RCA +- ROA
TimeChar = InvTime
&
OpMODE=3I0 and fi

&
TimeChar = DefTime

DirMode = Forward & ³1


Forward STFW

DirMode = Reverse
&
Reverse STRV

en06000653.vsd

IEC06000653 V2 EN

Figure 179: Simplified logical diagram of the sensitive earth-fault current protection

7.5.3 Function block


SDEPSDE
I3P* TRIP
U3P* TRDIRIN
BLOCK TRNDIN
BLKTR TRUN
BLKTRDIR START
BLKNDN STDIRIN
BLKUN STNDIN
STUN
STFW
STRV
STDIR
UNREL

IEC07000032-2-en.vsd
IEC07000032 V2 EN

Figure 180: SDEPSDE function block

331
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

7.5.4 Input and output signals


Table 182: SDEPSDE Input signals
Name Type Default Description
I3P GROUP - Group signal for current
SIGNAL
U3P GROUP - Group signal for voltage
SIGNAL
BLOCK BOOLEAN 0 Blocks all the outputs of the function
BLKTR BOOLEAN 0 Blocks the operate outputs of the function
BLKTRDIR BOOLEAN 0 Blocks the directional operate outputs of the
function
BLKNDN BOOLEAN 0 Blocks the Non directional current residual outputs
BLKUN BOOLEAN 0 Blocks the Non directional voltage residual outputs

Table 183: SDEPSDE Output signals


Name Type Description
TRIP BOOLEAN General trip of the function
TRDIRIN BOOLEAN Trip of the directional residual over current function
TRNDIN BOOLEAN Trip of non directional residual over current
TRUN BOOLEAN Trip of non directional residual over voltage
START BOOLEAN General start of the function
STDIRIN BOOLEAN Start of the directional residual over current
function
STNDIN BOOLEAN Start of non directional residual over current
STUN BOOLEAN Start of non directional residual over voltage
STFW BOOLEAN Start of directional function for a fault in forward
direction
STRV BOOLEAN Start of directional function for a fault in reverse
direction
STDIR INTEGER Direction of fault. A general signal common to all
three mode of residual over current protection
UNREL BOOLEAN Residual voltage release of operation of all
directional modes

332
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.5.5 Setting parameters


Table 184: SDEPSDE Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OpMode 3I0Cosfi - - 3I0Cosfi Selection of operation mode for protection
3I03U0Cosfi
3I0 and fi
DirMode Forward - - Forward Direction of operation forward or reverse
Reverse
RCADir -179 - 180 Deg 1 -90 Relay characteristic angle RCA, in deg
RCAComp -10.0 - 10.0 Deg 0.1 0.0 Relay characteristic angle compensation
ROADir 0 - 90 Deg 1 90 Relay open angle ROA used as release
in phase mode, in deg
INCosPhi> 0.25 - 200.00 %IB 0.01 1.00 Set level for 3I0cosFi, directional res
over current, in %Ib
SN> 0.25 - 200.00 %SB 0.01 10.00 Set level for 3I03U0cosFi, starting inv
time count, in %Sb
INDir> 0.25 - 200.00 %IB 0.01 5.00 Set level for directional residual over
current prot, in %Ib
tDef 0.000 - 60.000 s 0.001 0.100 Definite time delay directional residual
overcurrent, in sec
SRef 0.03 - 200.00 %SB 0.01 10.00 Reference value of res power for inverse
time count, in %Sb
kSN 0.00 - 2.00 - 0.01 0.10 Time multiplier setting for directional
residual power mode
OpINNonDir> Off - - Off Operation of non-directional residual
On overcurrent protection
INNonDir> 1.00 - 400.00 %IB 0.01 10.00 Set level for non directional residual over
current, in %Ib
tINNonDir 0.000 - 60.000 s 0.001 1.000 Time delay for non-directional residual
over current, in sec
TimeChar ANSI Ext. inv. - - IEC Norm. inv. Operation curve selection for IDMT
ANSI Very inv. operation
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
Table continues on next page

333
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Name Values (Range) Unit Step Default Description


tMin 0.000 - 60.000 s 0.001 0.040 Minimum operate time for IEC IDMT
curves, in sec
kIN 0.00 - 2.00 - 0.01 1.00 IDMT time mult for non-dir res over
current protection
OpUN> Off - - Off Operation of non-directional residual
On overvoltage protection
UN> 1.00 - 200.00 %UB 0.01 20.00 Set level for non-directional residual over
voltage, in %Ub
tUN 0.000 - 60.000 s 0.001 0.100 Time delay for non-directional residual
over voltage, in sec
INRel> 0.25 - 200.00 %IB 0.01 1.00 Residual release current for all
directional modes, in %Ib
UNRel> 0.01 - 200.00 %UB 0.01 3.00 Residual release voltage for all direction
modes, in %Ub

Table 185: SDEPSDE Group settings (advanced)


Name Values (Range) Unit Step Default Description
tReset 0.000 - 60.000 s 0.001 0.040 Time delay used for reset of definite
timers, in sec
tPCrv 0.005 - 3.000 - 0.001 1.000 Setting P for customer programmable
curve
tACrv 0.005 - 200.000 - 0.001 13.500 Setting A for customer programmable
curve
tBCrv 0.00 - 20.00 - 0.01 0.00 Setting B for customer programmable
curve
tCCrv 0.1 - 10.0 - 0.1 1.0 Setting C for customer programmable
curve
ResetTypeCrv Immediate - - IEC Reset Reset mode when current drops off.
IEC Reset
ANSI reset
tPRCrv 0.005 - 3.000 - 0.001 0.500 Setting PR for customer programmable
curve
tTRCrv 0.005 - 100.000 - 0.001 13.500 Setting TR for customer programmable
curve
tCRCrv 0.1 - 10.0 - 0.1 1.0 Setting CR for customer programmable
curve

Table 186: SDEPSDE Non group settings (basic)


Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 100 Base Current, in A
UBase 0.05 - 2000.00 kV 0.05 63.50 Base Voltage, in kV Phase to Neutral
SBase 0.05 - kVA 0.05 6350.00 Base Power, in kVA. IBase*Ubase
200000000.00

334
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Table 187: SDEPSDE Non group settings (advanced)


Name Values (Range) Unit Step Default Description
RotResU 0 deg - - 180 deg Setting for rotating polarizing quantity if
180 deg necessary

7.5.6 Technical data


Table 188: SDEPSDE technical data
Function Range or value Accuracy
Operate level for 3I0·cosj (0.25-200.00)% of lBase ± 1.0% of Ir at I £ Ir
directional residual overcurrent ± 1.0% of I at I > Ir
At low setting:
(2.5-10) mA ±1.0 mA
(10-50) mA ±0.5 mA
Operate level for 3I0·3U0 · cosj (0.25-200.00)% of SBase ± 1.0% of Sr at S £ Sr
directional residual power ± 1.0% of S at S > Sr
At low setting:
(0.25-5.00)% of SBase ± 10% of set value
Operate level for 3I0 and j (0.25-200.00)% of lBase ± 1.0% of Ir at £ Ir
residual overcurrent ± 1.0% of I at I > Ir
At low setting:
(2.5-10) mA ±1.0 mA
(10-50) mA ±0.5 mA
Operate level for non directional (1.00-400.00)% of lBase ± 1.0% of Ir at I £ Ir
overcurrent ± 1.0% of I at I > Ir
At low setting:
(10-50) mA ± 1.0 mA
Operate level for non directional (1.00-200.00)% of UBase ± 0.5% of Ur at U£Ur
residual overvoltage ± 0.5% of U at U > Ur

Residual release current for all (0.25-200.00)% of lBase ± 1.0% of Ir at I £ Ir


directional modes ± 1.0% of I at I > Ir
At low setting:
(2.5-10) mA ±1.0 mA
(10-50) mA ± 0.5 mA
Residual release voltage for all (0.01-200.00)% of UBase ± 0.5% of Ur at U£Ur
directional modes ± 0.5% of U at U > Ur

Reset ratio > 95% -


Timers (0.000-60.000) s ± 0.5% ± 10 ms
Inverse characteristics, see 19 curve types See table 644, table 645 and
table 644, table 645 and table table 646
646
Relay characteristic angle RCA (-179 to 180) degrees ± 2.0 degrees
Relay open angle ROA (0-90) degrees ± 2.0 degrees
Operate time, non directional 60 ms typically at 0 to 2 x Iset -
residual over current
Reset time, non directional 60 ms typically at 2 to 0 x Iset -
residual over current
Operate time, start function 150 ms typically at 0 to 2 x Iset -

Reset time, start function 50 ms typically at 2 to 0 x Iset -

335
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

7.6 Thermal overload protection, one time constant


LPTTR

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Thermal overload protection, one time LPTTR 26
constant

SYMBOL-A V1 EN

7.6.1 Introduction
The increasing utilizing of the power system closer to the thermal limits has
generated a need of a thermal overload protection also for power lines.

A thermal overload will often not be detected by other protection functions and the
introduction of the thermal overload protection can allow the protected circuit to
operate closer to the thermal limits.

The three-phase current measuring protection has an I2t characteristic with settable
time constant and a thermal memory.

An alarm level gives early warning to allow operators to take action well before the
line is tripped.

7.6.2 Principle of operation


The sampled analog phase currents are pre-processed and for each phase current
the RMS value is derived. These phase current values are fed to the thermal
overload protection, one time constant function LPTTR.

From the largest of the three-phase currents a final temperature is calculated


according to the expression:

2
æ I ö
Q final =ç ÷÷ × Tref
ç I ref
è ø
EQUATION1167 V1 EN (Equation 70)

where:
I is the largest phase current,
Iref is a given reference current and

Tref is steady state temperature corresponding to Iref

336
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

The ambient temperature is added to the calculated final temperature. If this


temperature is larger than the set operate temperature level, TripTemp, a START
output signal is activated.

The actual temperature at the actual execution cycle is calculated as:

æ Dt
ö
Qn = Qn -1 + ( Q final - Q n-1 ) × ç1 - e t ÷
-

è ø
EQUATION1168 V1 EN (Equation 71)

where:
Qn is the calculated present temperature,

Qn-1 is the calculated temperature at the previous time step,

Qfinal is the calculated final temperature with the actual current,

Dt is the time step between calculation of the actual temperature and


t is the set thermal time constant for the protected device (line or cable)

The actual temperature of the protected component (line or cable) is calculated by


adding the ambient temperature to the calculated temperature, as shown above. The
ambient temperature can be taken from a separate sensor or can be given a constant
value. The calculated component temperature is available as a real figure signal,
TEMP.

When the component temperature reaches the set alarm level AlarmTemp the
output signal ALARM is set. When the component temperature reaches the set trip
level TripTemp the output signal TRIP is set.

There is also a calculation of the present time to operate with the present current.
This calculation is only performed if the final temperature is calculated to be above
the operation temperature:

æQ - Qoperate ö
toperate = -t × ln ç final
ç Q final - Q n ÷÷
è ø
EQUATION1169 V1 EN (Equation 72)

The calculated time to trip is available as a real figure signal, TTRIP.

After a trip, caused by the thermal overload protection, there can be a lockout to
reconnect the tripped circuit. The output lockout signal LOCKOUT is activated
when the device temperature is above the set lockout release temperature setting
ReclTemp.

The time to lockout release is calculated that is, a calculation of the cooling time to
a set value. The thermal content of the function can be reset with input RESET.

337
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

æQ - Qlockout _ release ö
tlockout _ release = -t × ln ç final ÷÷
ç Q final - Q n
è ø
EQUATION1170 V1 EN (Equation 73)

Here the final temperature is equal to the set or measured ambient temperature. The
calculated time to reset of lockout is available as a real figure signal, TENRECL.

In some applications the measured current can involve a number of parallel lines.
This is often used for cable lines where one bay connects several parallel cables.
By setting the parameter IMult to the number of parallel lines (cables) the actual
current on one line is used in the protection algorithm. To activate this option the
input ENMULT must be activated.

The protection has a reset input: RESET. By activating this input the calculated
temperature is reset to its default initial value. This is useful during testing when
secondary injected current has given a calculated “false” temperature level.

Final Temp START


> TripTemp

actual temperature
Calculation
of actual
temperature

IL1, IL2, IL3 Calculation


of final
temperature

Actual Temp >


ALARM
AlarmTemp

TRIP
Actual Temp
> TripTemp
Lock-
LOCKOUT
out
logic
Actual Temp
< Recl Temp

Calculation TTRIP
of time to
trip

Calculation
of time to TENRECL
reset of
lockout

IEC09000637_1_en.vsd
IEC09000637 V1 EN

Figure 181: Functional overview of LPTTR

338
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.6.3 Function block


LPTTR
I3P* TRIP
BLOCK START
BLKTR ALARM
ENMULT LOCKOUT
AMBTEMP
SENSFLT
RESET

IEC04000396-2-en.vsd
IEC04000396 V3 EN

Figure 182: LPTTR function block

7.6.4 Input and output signals


Table 189: LPTTR Input signals
Name Type Default Description
I3P GROUP - Group connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
ENMULT BOOLEAN 0 Current multiplyer used when THOL is for two or
more lines
AMBTEMP REAL 0 Ambient temperature from external temperature
sensor
SENSFLT BOOLEAN 0 Validity status of ambient temperature sensor
RESET BOOLEAN 0 Reset of internal thermal load counter

Table 190: LPTTR Output signals


Name Type Description
TRIP BOOLEAN Trip
START BOOLEAN Start Signal
ALARM BOOLEAN Alarm signal
LOCKOUT BOOLEAN Lockout signal

7.6.5 Setting parameters


Table 191: LPTTR Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IBase 0 - 99999 A 1 3000 Base current in A
TRef 0 - 600 Deg 1 90 End temperature rise above ambient of
the line when loaded with IRef
Table continues on next page

339
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Name Values (Range) Unit Step Default Description


IRef 0 - 400 %IB 1 100 The load current (in %of IBase) leading
to TRef temperature
IMult 1-5 - 1 1 Current multiplier when function is used
for two or more lines
Tau 0 - 1000 Min 1 45 Time constant of the line in minutes.
AlarmTemp 0 - 200 Deg 1 80 Temperature level for start (alarm)
TripTemp 0 - 600 Deg 1 90 Temperature level for trip
ReclTemp 0 - 600 Deg 1 75 Temperature for reset of lockout after trip
tPulse 0.05 - 0.30 s 0.01 0.1 Operate pulse length. Minimum one
execution cycle
AmbiSens Off - - Off External temperature sensor availiable
On
DefaultAmbTemp -50 - 250 Deg 1 20 Ambient temperature used when
AmbiSens is set to Off.
DefaultTemp -50 - 600 Deg 1 50 Temperature raise above ambient
temperature at startup

7.6.6 Technical data


Table 192: LPTTR technical data
Function Range or value Accuracy
Reference current (0-400)% of IBase ± 1.0% of Ir

Start temperature reference (0-400)°C ± 1.0°C


Operate time: Time constant t = (0–1000) IEC 60255-8, class 5 + 200 ms
minutes
æ I 2 - I p2 ö
t = t × ln ç 2 ÷
ç I - Ib 2 ÷
è ø
EQUATION1356 V1 EN (Equation 74)
I = actual measured current
Ip = load current before overload
occurs
Ib = base current, IBase

Alarm temperature (0-200)°C ± 2.0% of heat content trip


Trip temperature (0-400)°C ± 2.0% of heat content trip
Reset level temperature (0-400)°C ± 2.0% of heat content trip

7.7 Breaker failure protection CCRBRF

340
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Breaker failure protection CCRBRF 50BF

3I>BF

SYMBOL-U V1 EN

7.7.1 Introduction
Breaker failure protection (CCRBRF) ensures fast back-up tripping of surrounding
breakers in case of own breaker failure to open. CCRBRF can be current based,
contact based, or adaptive combination between these two principles.

A current check with extremely short reset time is used as check criteria to achieve
a high security against unnecessary operation.

A contact check criteria can be used where the fault current through the breaker is
small.

CCRBRF can be single- or three-phase initiated to allow use with single phase
tripping applications. For the three-phase version of CCRBRF the current criteria
can be set to operate only if two out of four for example, two phases or one phase
plus the residual current start. This gives a higher security to the back-up trip
command.

CCRBRF function can be programmed to give a single- or three-phase re-trip of


the own breaker to avoid unnecessary tripping of surrounding breakers at an
incorrect initiation due to mistakes during testing.

7.7.2 Principle of operation


Breaker failure protection CCRBRF is initiated from protection trip command,
either from protection functions within the IED or from external protection devices.

The start signal can be phase selective or general (for all three phases). Phase
selective start signals enable single pole re-trip function. This means that a second
attempt to open the breaker is done. The re-trip attempt can be made after a set
time delay. For transmission lines single pole trip and autoreclosing is often used.
The re-trip function can be phase selective if it is initiated from phase selective line
protection. The re-trip function can be done with or without current check. With
the current check the re-trip is only performed if the current through the circuit
breaker is larger than the operate current level.

The start signal can be an internal or external protection trip signal. This signal will
start the back-up trip timer. If the opening of the breaker is successful this is
detected by the function, by detection of either low current through RMS
evaluation and a special adapted current algorithm or by open contact indication.
The special algorithm enables a very fast detection of successful breaker opening,

341
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

that is, fast resetting of the current measurement. If the current and/or contact
detection has not detected breaker opening before the back-up timer has run its
time a back-up trip is initiated.

Further the following possibilities are available:

• The minimum length of the re-trip pulse, the back-up trip pulse and the back-
up trip pulse 2 are settable. The re-trip pulse, the back-up trip pulse and the back-
up trip pulse 2 will however sustain as long as there is an indication of closed
breaker.
• In the current detection it is possible to use three different options: 1 out of 3
where it is sufficient to detect failure to open (high current) in one pole, 1 out
of 4 where it is sufficient to detect failure to open (high current) in one pole or
high residual current and 2 out of 4 where at least two current (phase current and/
or residual current) shall be high for breaker failure detection.
• The current detection level for the residual current can be set different from the
setting of phase current detection.
• It is possible to have different back-up time delays for single-phase faults and
for multi-phase faults.
• The back-up trip can be made without current check. It is possible to have this
option activated for small load currents only.
• It is possible to have instantaneous back-up trip function if a signal is high if
the circuit breaker is insufficient to clear faults, for example at low gas pressure.

START 30 ms

STL1 OR BFP Started L1


150 ms
AND S
SR Q t
Time out L1
R AND
BLOCK
OR
Reset L1
Retrip Time Out L1
BackupTrip L1 OR

IEC09000976-1-en.vsd
IEC09000976 V1 EN

Figure 183: Simplified logic scheme of the CCRBRF starting logic

342
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

IP>
a
a>b
b
FunctionMode Current
OR AND Reset L1
OR
Contact
1 Time out L1
Current and Contact OR
AND
Current High L1

IL1 CB Closed L1
AND
OR
BFP Started L1

a AND AND
a>b OR AND
I>BlkCont b

CBCLDL1 Contact Closed L1


AND

IEC09000977-1-en.vsd

IEC09000977 V1 EN

Figure 184: Simplified logic scheme of the CCRBRF, CB position evaluation

t1 TRRETL3
BFP Started L1 From other
t Retrip Time Out L1
phases TRRETL2 OR
TRRET

tPulse
RetripMode No CBPos Check AND
OR TRRETL1
OR

1
OR AND

CB Pos Check
AND
CB Closed L1
CBFLT

IEC09000978-1-en.vsd

IEC09000978 V1 EN

Figure 185: Simplified logic scheme of the retrip logic function

343
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

IN
a
a>b AND
IN> b

BUTripMode Contact Closed L1


2 out of 4
1 out of 4 OR
1
1 out of 3 OR
Current High L2
From other
Current High L3
phases
Current High L1 AND

CBFLT
AND

t2
BFP Started L1 Backup Trip L1
t AND
OR
t2MPh

AND t

AND
OR OR
tPulse
From other Backup Trip L2 OR TRBU
OR
phases Backup Trip L3
From other BFP Started L2 2 of 3
phases BFP Started L3 tPulse
t3
OR
TRBU2
S Q t
R SR
AND

IEC09000979-1-en.vsd

IEC09000979 V1 EN

Figure 186: Simplified logic scheme of the back-up trip logic function

Internal logical signals STIL1, STIL2, STIL3 have logical value 1 when current in
respective phase has magnitude larger than setting parameter IP>.

7.7.3 Function block


CCRBRF
I3P* TRBU
BLOCK TRBU2
START TRRET
STL1 TRRETL1
STL2 TRRETL2
STL3 TRRETL3
CBCLDL1 CBALARM
CBCLDL2
CBCLDL3
CBFLT

IEC06000188-2-en.vsd
IEC06000188 V2 EN

Figure 187: CCRBRF function block

344
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.7.4 Input and output signals


Table 193: CCRBRF Input signals
Name Type Default Description
I3P GROUP - Current connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
START BOOLEAN 0 Three phase start of breaker failure protection
function
STL1 BOOLEAN 0 Start signal of phase L1
STL2 BOOLEAN 0 Start signal of phase L2
STL3 BOOLEAN 0 Start signal of phase L3
CBCLDL1 BOOLEAN 1 Circuit breaker closed in phase L1
CBCLDL2 BOOLEAN 1 Circuit breaker closed in phase L2
CBCLDL3 BOOLEAN 1 Circuit breaker closed in phase L3
CBFLT BOOLEAN 0 CB faulty, unable to trip. Back-up trip
instantanously.

Table 194: CCRBRF Output signals


Name Type Description
TRBU BOOLEAN Back-up trip by breaker failure protection function
TRBU2 BOOLEAN Second back-up trip by breaker failure protection
function
TRRET BOOLEAN Retrip by breaker failure protection function
TRRETL1 BOOLEAN Retrip by breaker failure protection function
phase L1
TRRETL2 BOOLEAN Retrip by breaker failure protection function
phase L2
TRRETL3 BOOLEAN Retrip by breaker failure protection function
phase L3
CBALARM BOOLEAN Alarm for faulty circuit breaker

7.7.5 Setting parameters


Table 195: CCRBRF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current
FunctionMode Current - - Current Detection principle for back-up trip
Contact
Current&Contact
Table continues on next page

345
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Name Values (Range) Unit Step Default Description


BuTripMode 2 out of 4 - - 1 out of 3 Back-up trip mode
1 out of 3
1 out of 4
RetripMode Retrip Off - - Retrip Off Operation mode of re-trip logic
CB Pos Check
No CBPos Check
IP> 5 - 200 %IB 1 10 Operate phase current level in % of IBase
IN> 2 - 200 %IB 1 10 Operate residual current level in % of
IBase
t1 0.000 - 60.000 s 0.001 0.000 Time delay of re-trip
t2 0.000 - 60.000 s 0.001 0.150 Time delay of back-up trip
t2MPh 0.000 - 60.000 s 0.001 0.150 Time delay of back-up trip at multi-phase
start
tPulse 0.000 - 60.000 s 0.001 0.200 Trip pulse duration

Table 196: CCRBRF Group settings (advanced)


Name Values (Range) Unit Step Default Description
I>BlkCont 5 - 200 %IB 1 20 Current for blocking of CB contact
operation in % of IBase
t3 0.000 - 60.000 s 0.001 0.030 Additional time delay to t2 for a second
back-up trip
tCBAlarm 0.000 - 60.000 s 0.001 5.000 Time delay for CB faulty signal

7.7.6 Technical data


Table 197: CCRBRF technical data
Function Range or value Accuracy
Operate phase (5-200)% of lBase ± 1.0% of Ir at I £ Ir
current ± 1.0% of I at I > Ir

Reset ratio, phase > 95% -


current
Operate residual (2-200)% of lBase ± 1.0% of Ir at I £ Ir
current ± 1.0% of I at I > Ir

Reset ratio, residual > 95% -


current
Phase current level (5-200)% of lBase ± 1.0% of Ir at I £ Ir
for blocking of ± 1.0% of I at I > Ir
contact function
Reset ratio > 95% -
Timers (0.000-60.000) s ± 0.5% ± 10 ms
Operate time for 10 ms typically -
current detection
Reset time for 15 ms maximum -
current detection

346
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.8 Stub protection STBPTOC

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Stub protection STBPTOC 50STB

3I>STUB

SYMBOL-T V1 EN

7.8.1 Introduction
When a power line is taken out of service for maintenance and the line
disconnector is opened in multi-breaker arrangements the voltage transformers will
mostly be outside on the disconnected part. The primary line distance protection
will thus not be able to operate and must be blocked.

The stub protection STBPTOC covers the zone between the current transformers
and the open disconnector. The three-phase instantaneous overcurrent function is
released from a normally open, NO (b) auxiliary contact on the line disconnector.

7.8.2 Principle of operation


The sampled analog phase currents are pre-processed in a discrete Fourier filter
(DFT) block. From the fundamental frequency components of each phase current
the RMS value of each phase current is derived. These phase current values are fed
to a comparator in the stub protection function STBPTOC. In a comparator the
RMS values are compared to the set operating current value of the function I>.

If a phase current is larger than the set operating current the signal from the
comparator for this phase is activated. This signal will, in combination with the
release signal from line disconnection (RELEASE input), activate the timer for the
TRIP signal. If the fault current remains during the timer delay t, the TRIP output
signal is activated. The function can be blocked by activation of the BLOCK input.

347
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

STUB PROTECTION FUNCTION

BLOCK

TRIP
STIL1 AND

STIL2 OR

STIL3

RELEASE

en05000731.vsd
IEC05000731 V1 EN

Figure 188: Simplified logic diagram for Stub protection

7.8.3 Function block


STBPTOC
I3P* TRIP
BLOCK START
BLKTR
RELEASE

IEC05000678-2-en.vsd
IEC05000678 V2 EN

Figure 189: STBPTOC function block

7.8.4 Input and output signals


Table 198: STBPTOC Input signals
Name Type Default Description
I3P GROUP - Three phase currents
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
RELEASE BOOLEAN 0 Release of stub protection

Table 199: STBPTOC Output signals


Name Type Description
TRIP BOOLEAN Trip
START BOOLEAN General start

348
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.8.5 Setting parameters


Table 200: STBPTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current
ReleaseMode Release - - Release Release of stub protection
Continuous
I> 1 - 2500 %IB 1 200 Operate current level in % of IBase

Table 201: STBPTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
t 0.000 - 60.000 s 0.001 0.000 Time delay

7.8.6 Technical data


Table 202: STBPTOC technical data
Function Range or value Accuracy
Operating current (1-2500)% of IBase ± 1.0% of Ir at I £ Ir
± 1.0% of I at I > Ir

Reset ratio > 95% -


Definite time (0.000-60.000) s ± 0.5% ± 10 ms
Operating time, start 25 ms typically at 0 to 2 x Iset -
function
Resetting time, 25 ms typically at 2 to 0 x Iset -
startfunction
Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

7.9 Pole discordance protection CCRPLD

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Pole discordance protection CCRPLD 52PD

PD

SYMBOL-S V1 EN

349
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

7.9.1 Introduction
Single pole operated circuit breakers can due to electrical or mechanical failures
end up with the different poles in different positions (close-open). This can cause
negative and zero sequence currents which gives thermal stress on rotating
machines and can cause unwanted operation of zero sequence or negative sequence
current functions.

Normally the own breaker is tripped to correct such a situation. If the situation
persists the surrounding breaker should be tripped to clear the unsymmetrical load
situation.

The Polediscordance protection function CCRPLD operates based on information


from auxiliary contacts of the circuit breaker for the three phases with additional
criteria from unsymmetrical phase current when required.

7.9.2 Principle of operation


The detection of pole discordance can be made in two different ways. If the contact
based function is used an external logic can be made by connecting the auxiliary
contacts of the circuit breaker so that a pole discordance is indicated, see figure 190.
circuit breaker

Pole discordance signal from circuit breaker

en05000287.vsd

IEC05000287 V2 EN

Figure 190: Pole discordance external detection logic

This binary signal is connected to a binary input of the IED. The appearance of this
signal will start a timer that will give a trip signal after the set time delay.

There is also a possibility to connect all phase selective auxiliary contacts (phase
contact open and phase contact closed) to binary inputs of the IED, see figure 191.

350
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

C.B.

poleOneClosed from C.B.

poleTwoClosed from C.B.

poleThreeClosed from C.B.

+
poleOneOpened from C.B.

poleTwoOpened from C.B.

poleThreeOpened from C.B.

en05000288.vsd
IEC05000288 V1 EN

Figure 191: Pole discordance signals for internal logic

In this case the logic is realized within the function. If the inputs are indicating pole
discordance the trip timer is started. This timer will give a trip signal after the set
delay.

Pole discordance can also be detected by means of phase selective current


measurement. The sampled analog phase currents are pre-processed in a discrete
Fourier filter (DFT) block. From the fundamental frequency components of each
phase current the RMS value of each phase current is derived. The smallest and the
largest phase current are derived. If the smallest phase current is lower than the
setting CurrUnsymLevel times the largest phase current the settable trip timer
(tTrip) is started. The tTrip timer gives a trip signal after the set delay. The TRIP
signal is a pulse 150 ms long. The current based pole discordance function can be
set to be active either continuously or only directly in connection to breaker open
or close command.

The function also has a binary input that can be configured from the autoreclosing
function, so that the pole discordance function can be blocked during sequences
with a single pole open if single pole autoreclosing is used.

The simplified block diagram of the current and contact based Pole discordance
protection function CCRPLD is shown in figure 192.

351
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

BLOCK
OR
BLKDBYAR

PolPosAuxCont

AND
POLE1OPN
POLE1CL
POLE2OPN
Discordance
POLE2CL
detection
POLE3OPN
POLE3CL t 150 ms
t TRIP
AND
OR

PD Signal from CB
AND
EXTPDIND

CLOSECMD t+200 ms
OR
OPENCMD

AND

Unsymmetry current
detection

en05000747.vsd
IEC05000747 V1 EN

Figure 192: Simplified block diagram of pole discordance function CCRPLD -


contact and current based

CCRPLDis blocked if:

• The IED is in TEST mode and CCRPLD has been blocked from the local HMI
• The input signal BLOCK is high
• The input signal BLKDBYAR is high

The BLOCK signal is a general purpose blocking signal of the pole discordance
protection. It can be connected to a binary input in the IED in order to receive a
block command from external devices or can be software connected to other
internal functions in the IED itself in order to receive a block command from
internal functions. Through OR gate it can be connected to both binary inputs and
internal function outputs.

The BLKDBYAR signal blocks the pole discordance operation when a single
phase autoreclosing cycle is in progress. It can be connected to the output signal
1PT1 on SMBRRECfunction block. If the autoreclosing function is an external
device, then BLKDBYAR has to be connected to a binary input in the IED and this
binary input is connected to a signalization “1phase autoreclosing in progress”
from the external autoreclosing device.

If the pole discordance protection is enabled, then two different criteria can
generate a trip signal TRIP:

• Pole discordance signaling from the circuit breaker.


• Unsymmetrical current detection.

352
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.9.2.1 Pole discordance signaling from circuit breaker

If one or two poles of the circuit breaker have failed to open or to close the pole
discordance status, then the function input EXTPDIND is activated from the pole
discordance signal derived from the circuit breaker auxiliary contacts (one NO
contact for each phase connected in parallel, and in series with one NC contact for
each phase connected in parallel) and, after a settable time interval tTrip (0-60 s), a
150 ms trip pulse command TRIP is generated by the Polediscordance function.

7.9.2.2 Unsymmetrical current detection

Unsymmetrical current indicated if:

• any phase current is lower than CurrUnsymLevel of the highest current in the
three phases.
• the highest phase current is greater than CurrRelLevel of IBase.

If these conditions are true, an unsymmetrical condition is detected and the internal
signal INPS is turned high. This detection is enabled to generate a trip after a set
time delay tTrip if the detection occurs in the next 200 ms after the circuit breaker
has received a command to open trip or close and if the unbalance persists. The 200
ms limitation is for avoiding unwanted operation during unsymmetrical load
conditions.

The pole discordance protection is informed that a trip or close command has been
given to the circuit breaker through the inputs CLOSECMD (for closing command
information) and OPENCMD (for opening command information). These inputs
can be connected to terminal binary inputs if the information are generated from
the field (that is from auxiliary contacts of the close and open push buttons) or may
be software connected to the outputs of other integrated functions (that is close
command from a control function or a general trip from integrated protections).

7.9.3 Function block


CCRPLD
I3P* TRIP
BLOCK START
BLKDBYAR
CLOSECMD
OPENCMD
EXTPDIND
POLE1OPN
POLE1CL
POLE2OPN
POLE2CL
POLE3OPN
POLE3CL

IEC06000275-2-en.vsd
IEC06000275 V2 EN

Figure 193: CCRPLD function block

353
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

7.9.4 Input and output signals


Table 203: CCRPLD Input signals
Name Type Default Description
I3P GROUP - Three phase currents
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKDBYAR BOOLEAN 0 Block of function at CB single phase auto re-
closing cycle
CLOSECMD BOOLEAN 0 Close order to CB
OPENCMD BOOLEAN 0 Open order to CB
EXTPDIND BOOLEAN 0 Pole discordance signal from CB logic
POLE1OPN BOOLEAN 1 Pole one opened indication from CB
POLE1CL BOOLEAN 0 Pole one closed indication from CB
POLE2OPN BOOLEAN 1 Pole two opened indication from CB
POLE2CL BOOLEAN 0 Pole two closed indication from CB
POLE3OPN BOOLEAN 1 Pole three opened indication from CB
POLE3CL BOOLEAN 0 Pole three closed indication from CB

Table 204: CCRPLD Output signals


Name Type Description
TRIP BOOLEAN Trip signal to CB
START BOOLEAN Trip condition TRUE, waiting for time delay

7.9.5 Setting parameters


Table 205: CCRPLD Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IBase 1 - 99999 - 1 3000 Base current
tTrip 0.000 - 60.000 s 0.001 0.300 Time delay between trip condition and
trip signal
ContSel Off - - Off Contact function selection
PD signal from CB
Pole pos aux cont.
CurrSel Off - - Off Current function selection
CB oper monitor
Continuous monitor
CurrUnsymLevel 0 - 100 % 1 80 Unsym magn of lowest phase current
compared to the highest.
CurrRelLevel 0 - 100 %IB 1 10 Current magnitude for release of the
function in % of IBase

354
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.9.6 Technical data


Table 206: CCRPLD technical data
Function Range or value Accuracy
Operate current (0–100)% of IBase ± 1.0% of Ir

Time delay (0.000-60.000) s ± 0.5% ± 10 ms

7.10 Directional underpower protection GUPPDUP

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional underpower protection GUPPDUP 37
P<

SYMBOL-LL V1 EN

7.10.1 Introduction
The task of a generator in a power plant is to convert mechanical energy available
as a torque on a rotating shaft to electric energy.

Sometimes, the mechanical power from a prime mover may decrease so much that
it does not cover bearing losses and ventilation losses. Then, the synchronous
generator becomes a synchronous motor and starts to take electric power from the
rest of the power system. This operating state, where individual synchronous
machines operate as motors, implies no risk for the machine itself. If the generator
under consideration is very large and if it consumes lots of electric power, it may
be desirable to disconnect it to ease the task for the rest of the power system.

Often, the motoring condition may imply that the turbine is in a very dangerous
state. The task of the reverse power protection is to protect the turbine and not to
protect the generator itself.

Figure 194 illustrates the reverse power protection with underpower IED and with
overpower IED. The underpower IED gives a higher margin and should provide
better dependability. On the other hand, the risk for unwanted operation
immediately after synchronization may be higher. One should set the underpower
IED to trip if the active power from the generator is less than about 2%. One
should set the overpower IED to trip if the power flow from the network to the
generator is higher than 1% depending on the type of turbine.

355
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Underpower IED Overpower IED

Operate
Q Q
Operate
Line Line

Margin Margin
P P

Operating point Operating point


without without
turbine torque turbine torque

IEC06000315-2-en.vsd
IEC06000315 V2 EN

Figure 194: Protection with underpower IED and overpower IED

7.10.2 Principle of operation


A simplified scheme showing the principle of the power protection function is
shown in figure 195. The function has two stages with individual settings.

Chosen current
phasors P

Complex Derivation of S(angle)


S(angle) < t TRIP1
power S(composant)
Chosen voltage Power1
calculation in Char angle
phasors Q
START1

S(angle) < t TRIP2


Power2
START2

P = POWRE

Q = POWIM

IEC09000018-2-en.vsd
IEC09000018 V2 EN

Figure 195: Simplified logic diagram of the power protection function

The function will use voltage and current phasors calculated in the pre-processing
blocks. The apparent complex power is calculated according to chosen formula as
shown in table 207.

356
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Table 207: Complex power calculation


Set value: Mode Formula used for complex power calculation
L1, L2, L3
S = U L1 × I L1* + U L 2 × I L 2* + U L 3 × I L 3*
EQUATION1697 V1 EN (Equation 75)
Arone
S = U L1L 2 × I L1* - U L 2 L 3 × I L 3*
EQUATION1698 V1 EN (Equation 76)
PosSeq
S = 3 × U PosSeq × I PosSeq *
EQUATION1699 V1 EN (Equation 77)
L1L2
S = U L1L 2 × ( I L1* - I L 2* )
EQUATION1700 V1 EN (Equation 78)
L2L3
S = U L 2 L 3 × ( I L 2* - I L 3* )
EQUATION1701 V1 EN (Equation 79)
L3L1
S = U L 3 L1 × ( I L 3* - I L1* )
EQUATION1702 V1 EN (Equation 80)
L1
S = 3 × U L1 × I L1*
EQUATION1703 V1 EN (Equation 81)
L2
S = 3 × U L 2 × I L 2*
EQUATION1704 V1 EN (Equation 82)
L3
S = 3 × U L 3 × I L 3*
EQUATION1705 V1 EN (Equation 83)

The active and reactive power is available from the function and can be used for
monitoring and fault recording.

The component of the complex power S = P + jQ in the direction Angle1(2) is


calculated. If this angle is 0° the active power component P is calculated. If this
angle is 90° the reactive power component Q is calculated.

The calculated power component is compared to the power pick up setting


Power1(2). For directional underpower protection, a start signal START1(2) is
activated if the calculated power component is smaller than the pick up value. For
directional overpower protection, a start signal START1(2) is activated if the
calculated power component is larger than the pick up value. After a set time delay
TripDelay1(2) a trip TRIP1(2) signal is activated if the start signal is still active. At
activation of any of the two stages a common signal START will be activated. At
trip from any of the two stages also a common signal TRIP will be activated.

To avoid instability there is a settable hysteresis in the power function. The


absolute hysteresis of the stage1(2) is Hysteresis1(2) = abs (Power1(2) + drop-
power1(2)). For generator low forward power protection the power setting is very

357
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

low, normally down to 0.02 p.u. of rated generator power. The hysteresis should
therefore be set to a smaller value. The drop-power value of stage1 can be
calculated with the Power1(2), Hysteresis1(2): drop-power1(2) = Power1(2) +
Hysteresis1(2)

For small power1 values the hysteresis1 may not be too big, because the drop-
power1(2) would be too small. In such cases, the hysteresis1 greater than (0.5 ·
Power1(2)) is corrected to the minimal value.

If the measured power drops under the drop-power1(2) value, the function will
reset after a set time DropDelay1(2). The reset means that the start signal will drop
out and that the timer of the stage will reset.

7.10.2.1 Low pass filtering

In order to minimize the influence of the noise signal on the measurement it is


possible to introduce the recursive, low pass filtering of the measured values for S
(P, Q). This will make slower measurement response to the step changes in the
measured quantity. Filtering is performed in accordance with the following
recursive formula:

S = k × SOld + (1 - k ) × SCalculated
EQUATION1959 V1 EN (Equation 84)

Where
S is a new measured value to be used for the protection function
Sold is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle


k is settable parameter by the end user which influence the filter properties

Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. A typical value for
k=0.92 in case of slow operating functions.

7.10.2.2 Calibration of analog inputs

Measured currents and voltages used in the Power function can be calibrated to get
class 0.5 measuring accuracy. This is achieved by amplitude and angle
compensation at 5, 30 and 100% of rated current and voltage. The compensation
below 5% and above 100% is constant and linear in between, see example in figure
196.

358
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

IEC05000652 V2 EN

Figure 196: Calibration curves

The first current and voltage phase in the group signals will be used as reference
and the amplitude and angle compensation will be used for related input signals.

Analog outputs (Monitored data) from the function can be used for service values
or in the disturbance report. The active power is provided as MW value: P, or in
percent of base power: PPERCENT. The reactive power is provided as Mvar value:
Q, or in percent of base power: QPERCENT.

7.10.3 Function block


GUPPDUP
I3P* TRIP
U3P* TRIP1
BLOCK TRIP2
BLOCK1 START
BLOCK2 START1
START2
P
PPERCENT
Q
QPERCENT

IEC07000027-2-en.vsd
IEC07000027 V2 EN

Figure 197: GUPPDUP function block

359
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

7.10.4 Input and output signals


Table 208: GUPPDUP Input signals
Name Type Default Description
I3P GROUP - Current group connection
SIGNAL
U3P GROUP - Voltage group connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLOCK1 BOOLEAN 0 Block of stage 1
BLOCK2 BOOLEAN 0 Block of stage 2

Table 209: GUPPDUP Output signals


Name Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip of stage 1
TRIP2 BOOLEAN Trip of stage 2
START BOOLEAN Common start
START1 BOOLEAN Start of stage 1
START2 BOOLEAN Start of stage 2
P REAL Active Power in MW
PPERCENT REAL Active power in % of SBASE
Q REAL Reactive power in Mvar
QPERCENT REAL Reactive power in % of SBASE

7.10.5 Setting parameters


Table 210: GUPPDUP Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OpMode1 Off - - UnderPower Operation mode 1
UnderPower
Power1 0.0 - 500.0 %SB 0.1 1.0 Power setting for stage 1 in % of Sbase
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Angle for stage 1
TripDelay1 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 1
DropDelay1 0.010 - 6000.000 s 0.001 0.060 Drop delay for stage 1
OpMode2 Off - - UnderPower Operation mode 2
UnderPower
Power2 0.0 - 500.0 %SB 0.1 1.0 Power setting for stage 2 in % of Sbase
Angle2 -180.0 - 180.0 Deg 0.1 0.0 Angle for stage 2
TripDelay2 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 2
DropDelay2 0.010 - 6000.000 s 0.001 0.060 Drop delay for stage 2

360
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Table 211: GUPPDUP Group settings (advanced)


Name Values (Range) Unit Step Default Description
k 0.00 - 0.99 - 0.01 0.00 Low pass filter coefficient for power
measurement, P and Q
Hysteresis1 0.2 - 5.0 pu 0.1 0.5 Absolute hysteresis of stage 1
Hysteresis2 0.2 - 5.0 pu 0.1 0.5 Absolute hysteresis of stage 2
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
30% of Ir
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
100% of Ir
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir

Table 212: GUPPDUP Non group settings (basic)


Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Current-Reference (primary current A)
UBase 0.05 - 2000.00 kV 0.05 400.00 Voltage-Reference (primary voltage kV)
Mode L1, L2, L3 - - Pos Seq Selection of measured current and
Arone voltage
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3

7.10.6 Technical data


Table 213: GUPPDUP technical data
Function Range or value Accuracy
Power level (0.0–500.0)% of SBase ± 1.0% of Sr at S < Sr
± 1.0% of S at S > Sr
At low setting:
(0.5-2.0)% of SBase < ± 50% of set value
(2.0-10)% of SBase < ± 20% of set value
Characteristic angle (-180.0–180.0) degrees 2 degrees
Timers (0.00-6000.00) s ± 0.5% ± 10 ms

361
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

7.11 Directional overpower protection GOPPDOP

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional overpower protection GOPPDOP 32
P>

DOCUMENT172362-IMG158942
V1 EN

7.11.1 Introduction
The task of a generator in a power plant is to convert mechanical energy available
as a torque on a rotating shaft to electric energy.

Sometimes, the mechanical power from a prime mover may decrease so much that
it does not cover bearing losses and ventilation losses. Then, the synchronous
generator becomes a synchronous motor and starts to take electric power from the
rest of the power system. This operating state, where individual synchronous
machines operate as motors, implies no risk for the machine itself. If the generator
under consideration is very large and if it consumes lots of electric power, it may
be desirable to disconnect it to ease the task for the rest of the power system.

Often, the motoring condition may imply that the turbine is in a very dangerous
state. The task of the reverse power protection is to protect the turbine and not to
protect the generator itself.

Figure 198 illustrates the reverse power protection with underpower IED and with
overpower IED. The underpower IED gives a higher margin and should provide
better dependability. On the other hand, the risk for unwanted operation
immediately after synchronization may be higher. One should set the underpower
IED to trip if the active power from the generator is less than about 2%. One
should set the overpower IED to trip if the power flow from the network to the
generator is higher than 1%.

362
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

Underpower IED Overpower IED

Operate
Q Q
Operate
Line Line

Margin Margin
P P

Operating point Operating point


without without
turbine torque turbine torque

IEC06000315-2-en.vsd
IEC06000315 V2 EN

Figure 198: Reverse power protection with underpower IED and overpower IED

7.11.2 Principle of operation


A simplified scheme showing the principle of the power protection function is
shown in figure 199. The function has two stages with individual settings.

Chosen current
phasors P

Complex Derivation of S(angle)


S(angle) > t TRIP1
power S(composant)
Chosen voltage Power1
calculation in Char angle
phasors Q
START1

S(angle) > t TRIP2


Power2
START2

P = POWRE

Q = POWIM

IEC06000567-2-en.vsd
IEC06000567 V2 EN

Figure 199: Simplified logic diagram of the power protection function

The function will use voltage and current phasors calculated in the pre-processing
blocks. The apparent complex power is calculated according to chosen formula as
shown in table 214.

363
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Table 214: Complex power calculation


Set value: Mode Formula used for complex power calculation
L1, L2, L3
S = U L1 × I L1* + U L 2 × I L 2* + U L 3 × I L 3*
EQUATION1697 V1 EN (Equation 85)
Arone
S = U L1L 2 × I L1* - U L 2 L 3 × I L 3*
EQUATION1698 V1 EN (Equation 86)
PosSeq
S = 3 × U PosSeq × I PosSeq *
EQUATION1699 V1 EN (Equation 87)
L1L2
S = U L1L 2 × ( I L1* - I L 2* )
EQUATION1700 V1 EN (Equation 88)
L2L3
S = U L 2 L 3 × ( I L 2* - I L 3* )
EQUATION1701 V1 EN (Equation 89)
L3L1
S = U L 3 L1 × ( I L 3* - I L1* )
EQUATION1702 V1 EN (Equation 90)
L1
S = 3 × U L1 × I L1*
EQUATION1703 V1 EN (Equation 91)
L2
S = 3 × U L 2 × I L 2*
EQUATION1704 V1 EN (Equation 92)
L3
S = 3 × U L 3 × I L 3*
EQUATION1705 V1 EN (Equation 93)

The active and reactive power is available from the function and can be used for
monitoring and fault recording.

The component of the complex power S = P + jQ in the direction Angle1(2) is


calculated. If this angle is 0° the active power component P is calculated. If this
angle is 90° the reactive power component Q is calculated.

The calculated power component is compared to the power pick up setting


Power1(2). A start signal START1(2) is activated if the calculated power
component is larger than the pick up value. After a set time delay TripDelay1(2) a
trip TRIP1(2) signal is activated if the start signal is still active. At activation of
any of the two stages a common signal START will be activated. At trip from any
of the two stages also a common signal TRIP will be activated.

To avoid instability there is a settable hysteresis in the power function. The


absolute hysteresis of the stage1(2) is Hysteresis1(2) = abs (Power1(2) – drop-
power1(2)). For generator reverse power protection the power setting is very low,
normally down to 0.02 p.u. of rated generator power. The hysteresis should
therefore be set to a smaller value. The drop-power value of stage1 can be

364
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

calculated with the Power1(2), Hysteresis1(2): drop-power1(2) = Power1(2) –


Hysteresis1(2)

For small power1 values the hysteresis1 may not be too big, because the drop-
power1(2) would be too small. In such cases, the hysteresis1 greater than (0.5 ·
Power1(2)) is corrected to the minimal value.

If the measured power drops under the drop-power1(2) value the function will reset
after a set time DropDelay1(2). The reset means that the start signal will drop out
ant that the timer of the stage will reset.

7.11.2.1 Low pass filtering

In order to minimize the influence of the noise signal on the measurement it is


possible to introduce the recursive, low pass filtering of the measured values for S
(P, Q). This will make slower measurement response to the step changes in the
measured quantity. Filtering is performed in accordance with the following
recursive formula:

S = k × SOld + (1 - k ) × SCalculated
EQUATION1959 V1 EN (Equation 94)

Where
S is a new measured value to be used for the protection function
Sold is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle

k is settable parameter by the end user which influence the filter properties

Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. A typical value for k =
0.14.

7.11.2.2 Calibration of analog inputs

Measured currents and voltages used in the Power function can be calibrated to get
class 0.5 measuring accuracy. This is achieved by amplitude and angle
compensation at 5, 30 and 100% of rated current and voltage. The compensation
below 5% and above 100% is constant and linear in between, see example in figure
200.

365
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

IEC05000652 V2 EN

Figure 200: Calibration curves

The first current and voltage phase in the group signals will be used as reference
and the amplitude and angle compensation will be used for related input signals.

Analog outputs from the function can be used for service values or in the
disturbance report. The active power is provided as MW value: P, or in percent of
base power: PPERCENT. The reactive power is provided as Mvar value: Q, or in
percent of base power: QPERCENT.

7.11.3 Function block


GOPPDOP
I3P* TRIP
U3P* TRIP1
BLOCK TRIP2
BLOCK1 START
BLOCK2 START1
START2
P
PPERCENT
Q
QPERCENT

IEC07000028-2-en.vsd
IEC07000028 V2 EN

Figure 201: GOPPDOP function block

366
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.11.4 Input and output signals


Table 215: GOPPDOP Input signals
Name Type Default Description
I3P GROUP - Current group connection
SIGNAL
U3P GROUP - Voltage group connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLOCK1 BOOLEAN 0 Block of stage 1
BLOCK2 BOOLEAN 0 Block of stage 2

Table 216: GOPPDOP Output signals


Name Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip of stage 1
TRIP2 BOOLEAN Trip of stage 2
START BOOLEAN Common start
START1 BOOLEAN Start of stage 1
START2 BOOLEAN Start of stage 2
P REAL Active Power in MW
PPERCENT REAL Active power in % of SBASE
Q REAL Reactive power in Mvar
QPERCENT REAL Reactive power in % of SBASE

7.11.5 Setting parameters


Table 217: GOPPDOP Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OpMode1 Off - - OverPower Operation mode 1
OverPower
Power1 0.0 - 500.0 %SB 0.1 120.0 Power setting for stage 1 in % of Sbase
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Angle for stage 1
TripDelay1 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 1
DropDelay1 0.010 - 6000.000 s 0.001 0.060 Drop delay for stage 1
OpMode2 Off - - OverPower Operation mode 2
OverPower
Power2 0.0 - 500.0 %SB 0.1 120.0 Power setting for stage 2 in % of Sbase
Angle2 -180.0 - 180.0 Deg 0.1 0.0 Angle for stage 2
TripDelay2 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 2
DropDelay2 0.010 - 6000.000 s 0.001 0.060 Drop delay for stage 2

367
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

Table 218: GOPPDOP Group settings (advanced)


Name Values (Range) Unit Step Default Description
k 0.00 - 0.99 - 0.01 0.00 Low pass filter coefficient for power
measurement, P and Q
Hysteresis1 0.2 - 5.0 pu 0.1 0.5 Absolute hysteresis of stage 1 in % of
Sbase
Hysteresis2 0.2 - 5.0 pu 0.1 0.5 Absolute hysteresis of stage 2 in % of
Sbase
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
30% of Ir
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
100% of Ir
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir

Table 219: GOPPDOP Non group settings (basic)


Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Current-Reference (primary current A)
UBase 0.05 - 2000.00 kV 0.05 400.00 Voltage-Reference (primary voltage kV)
Mode L1, L2, L3 - - Pos Seq Selection of measured current and
Arone voltage
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3

368
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.11.6 Technical data


Table 220: GOPPDOP technical data
Function Range or value Accuracy
Power level (0.0–500.0)% of Sbase ± 1.0% of Sr at S < Sr
± 1.0% of S at S > Sr
At low setting:
(0.5-2.0)% of Sbase < ± 50% of set value
(2.0-10)% of Sbase < ± 20% of set value

Characteristic angle (-180.0–180.0) degrees 2 degrees


Timers (0.00-6000.00) s ± 0.5% ± 10 ms

7.12 Broken conductor check BRCPTOC

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Broken conductor check BRCPTOC - 46

7.12.1 Introduction
Conventional protection functions can not detect the broken conductor condition.
Broken conductor check (BRCPTOC) function, consisting of continuous current
unsymmetrical check on the line where the IED is connected will give alarm or trip
at detecting broken conductors.

7.12.2 Principle of operation


Broken conductor check (BRCPTOC) detects a broken conductor condition by
detecting the asymmetry between currents in the three phases. The current-
measuring elements continuously measure the three-phase currents.

The current asymmetry signal output START is set on if:

• The difference in currents between the phase with the lowest current and the
phase with the highest current is greater than set percentage Iub> of the
highest phase current
• The highest phase current is greater than the minimum setting value IP>.
• The lowest phase current is below 50% of the minimum setting value IP>

The third condition is included to avoid problems in systems involving parallel


lines. If a conductor breaks in one phase on one line, the parallel line will
experience an increase in current in the same phase. This might result in the first
two conditions being satisfied. If the unsymmetrical detection lasts for a period
longer than the set time tOper the TRIP output is activated.

369
Technical reference manual
Section 7 1MRK505183-UEN C
Current protection

The simplified logic diagram of the broken conductor check function is shown in
figure 202

BRCPTOC is disabled (blocked) if:

• The IED is in TEST status and the function has been blocked from the local
HMI test menu (BlockBRC=Yes).
• The input signal BLOCK is high.

The BLOCK input can be connected to a binary input of the IED in order to receive
a block command from external devices, or can be software connected to other
internal functions of the IED itself to receive a block command from internal
functions.

The output trip signal TRIP is a three-phase trip. It can be used to command a trip
to the circuit breaker or for alarm purpose only.

TEST

TEST-ACTIVE
&
Block BRCPTOC=Yes
START

Function Enable
BLOCK =1
t
TRIP
& t
Unsymmetrical
Current Detection
STI

IL1<50%IP>

IL2<50%IP> =1

IL3<50%IP>

IEC09000158-1-en.vsd
IEC09000158 V1 EN

Figure 202: Simplified logic diagram for Broken conductor check BRCPTOC

7.12.3 Function block


BRCPTOC
I3P* TRIP
BLOCK START
BLKTR

IEC07000034-2-en.vsd
IEC07000034 V2 EN

Figure 203: BRCPTOC function block

370
Technical reference manual
1MRK505183-UEN C Section 7
Current protection

7.12.4 Input and output signals


Table 221: BRCPTOC Input signals
Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Blocks the operate output

Table 222: BRCPTOC Output signals


Name Type Description
TRIP BOOLEAN Operate signal of the protection logic
START BOOLEAN Start signal of the protection logic

7.12.5 Setting parameters


Table 223: BRCPTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IBase 0 - 99999 A 1 3000 IBase
Iub> 50 - 90 %IM 1 50 Unbalance current operation value in
percent of max current
IP> 5 - 100 %IB 1 20 Minimum phase current for operation of
Iub> in % of Ibase
tOper 0.000 - 60.000 s 0.001 5.000 Operate time delay

Table 224: BRCPTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
tReset 0.010 - 60.000 s 0.001 0.100 Time delay in reset

7.12.6 Technical data


Table 225: BRCPTOC technical data
Function Range or value Accuracy
Minimum phase current for (5–100)% of IBase ± 0.1% of Ir
operation
Unbalance current operation (0–100)% of maximum current ± 0.1% of Ir

Timer (0.00-6000.00) s ± 0.5% ± 10 ms

371
Technical reference manual
372
1MRK505183-UEN C Section 8
Voltage protection

Section 8 Voltage protection

About this chapter


This chapter describes voltage related protection functions. The way the functions
work, their setting parameters, function blocks, input and output signals and
technical data are included for each function.

8.1 Two step undervoltage protection UV2PTUV

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Two step undervoltage protection UV2PTUV 27

3U<

SYMBOL-R V1 EN

8.1.1 Introduction
Undervoltages can occur in the power system during faults or abnormal conditions.
Two step undervoltage protection (UV2PTUV) function can be used to open circuit
breakers to prepare for system restoration at power outages or as long-time delayed
back-up to primary protection.

UV2PTUV has two voltage steps, each with inverse or definite time delay.

8.1.2 Principle of operation


Two-step undervoltage protection (UV2PTUV) is used to detect low power system
voltage. UV2PTUV has two voltage measuring steps with separate time delays. If
one, two or three phase voltages decrease below the set value, a corresponding
START signal is generated. UV2PTUV can be set to START/TRIP based on 1 out
of 3, 2 out of 3 or 3 out of 3 of the measured voltages, being below the set point. If
the voltage remains below the set value for a time period corresponding to the
chosen time delay, the corresponding trip signal is issued. To avoid an unwanted
trip due to disconnection of the related high voltage equipment, a voltage
controlled blocking of the function is available, that is, if the voltage is lower than
the set blocking level the function is blocked and no START or TRIP signal is
generated. The time delay characteristic is individually chosen for each step and
can be either definite time delay or inverse time delay.

373
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

UV2PTUV can be set to measure phase-to-earth fundamental value, phase-to-phase


fundamental value, phase-to-earth true RMS value or phase-to-phase true RMS
value. The choice of the measuring is done by the parameter ConnType. The
voltage related settings are made in percent of base voltage which is set in kV phase-
to-phase voltage. This means operation for phase-to-earth voltage under:

U < (%) × UBase( kV )


3
EQUATION1429 V1 EN (Equation 95)

and operation for phase-to-phase voltage under:

U < (%) × UBase(kV)


EQUATION1990 V1 EN (Equation 96)

8.1.2.1 Measurement principle

Depending on the set ConnType value, UV2PTUV measures phase-to-earth or phase-


to-phase voltages and compare against set values, U1< and U2<. The parameters
OpMode1 and OpMode2 influence the requirements to activate the START
outputs. Either 1 out of 3, 2 out of 3, or 3 out of 3 measured voltages have to be
lower than the corresponding set point to issue the corresponding START signal.

To avoid oscillations of the output START signal, a hysteresis has been included.

8.1.2.2 Time delay

The time delay for the two steps can be either definite time delay (DT) or inverse
time delay (IDMT). For the inverse time delay three different modes are available:
• inverse curve A
• inverse curve B
• customer programmable inverse curve

The type A curve is described as:

k
t=
æ U < -U ö
ç ÷
è U< ø
EQUATION1431 V1 EN (Equation 97)

The type B curve is described as:

374
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

k × 480
t= 2.0
+ 0.055
æ U < -U ö
ç 32 × - 0.5 ÷
è U< ø
EQUATION1432 V1 EN (Equation 98)

The customer programmable curve can be created as:

é ù
ê ú
k×A
t=ê ú+D
êæ U < -U ö ú
p

êç B × -C÷ ú
ëè U< ø û
EQUATION1433 V1 EN (Equation 99)

When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore a tuning parameter
CrvSatn is set to compensate for this phenomenon. In the voltage interval U<
down to U< · (1.0 – CrvSatn/100) the used voltage will be: U< · (1.0 – CrvSatn/
100). If the programmable curve is used this parameter must be calculated so that:

CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN (Equation 100)

The lowest voltage is always used for the inverse time delay integration. The
details of the different inverse time characteristics are shown in section 22.3
"Inverse characteristics".

Trip signal issuing requires that the undervoltage condition continues for at least
the user set time delay. This time delay is set by the parameter t1 and t2 for definite
time mode (DT) and by some special voltage level dependent time curves for the
inverse time mode (IDMT). If the start condition, with respect to the measured
voltage ceases during the delay time, and is not fulfilled again within a user defined
reset time (tReset1 and tReset2 for the definite time and tIReset1 and
tIReset2pickup for the inverse time) the corresponding start output is reset. Here it
should be noted that after leaving the hysteresis area, the start condition must be
fulfilled again and it is not sufficient for the signal to only return back to the
hysteresis area. Note that for the undervoltage function the IDMT reset time is
constant and does not depend on the voltage fluctuations during the drop-off
period. However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time. See figure 204 and figure 205.

375
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

tReset1
Voltage tReset1
Measured
START Voltage
Hysteresis
TRIP

U1<

Time

START t1

TRIP

Time
Integrator Frozen Timer

t1

Time
Instantaneous
Linear Decrease
Reset IEC05000010-3-en.vsd

IEC05000010 V3 EN

Figure 204: Voltage profile not causing a reset of the start signal for step 1, and inverse time delay

376
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

tReset1
Voltage
tReset1
START
START
Hysteresis Measured Voltage
TRIP

U1<

Time

START t1

TRIP

Time Integrator
Frozen Timer

t1

Time
Instantaneous
Linear Decrease
Reset IEC05000011-en-2.vsd

IEC05000011 V2 EN

Figure 205: Voltage profile causing a reset of the start signal for step 1, and inverse time delay

Definite timer delay

When definite time delay is selected the function will operate as shown in figure
206. Detailed information about individual stage reset/operation behavior is shown
in figure 207 and figure 208 receptively. Note that by setting tResetn = 0.0s
instantaneous reset of the definite time delayed stage is ensured.

377
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

ST1

U tReset1 t1
a
b>a t t
TR1
U1<
b AND
OFF ON
Delay Delay

IEC09000785-1-en.vsd
IEC09000785 V1 EN

Figure 206: Detailed logic diagram for step 1, DT operation

Un<

START

TRIP

tResetn

tn

IEC10000039-1-en.vsd
IEC10000039 V1 EN

Figure 207: Example for Definite Time Delay stage rest

378
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

Un<

START

TRIP

tResetn

tn

IEC10000040-1-en.vsd
IEC10000040 V1 EN

Figure 208: Example for Definite Time Delay stage operation

8.1.2.3 Blocking

It is possible to block Two step undervoltage protection UV2PTUV partially or


completely, by binary input signals or by parameter settings, where:

BLOCK: blocks all outputs


BLKTR1: blocks all trip outputs of step 1
BLKST1: blocks all start and trip outputs related to step 1
BLKTR2: blocks all trip outputs of step 2
BLKST2: blocks all start and trip outputs related to step 2

If the measured voltage level decreases below the setting of IntBlkStVal1, either the
trip output of step 1, or both the trip and the START outputs of step 1, are blocked.
The characteristic of the blocking is set by the IntBlkSel1 parameter. This internal
blocking can also be set to Off resulting in no voltage based blocking.
Corresponding settings and functionality are valid also for step 2.

In case of disconnection of the high voltage component the measured voltage will
get very low. The event will START both the under voltage function and the
blocking function, as seen in figure 209. The delay of the blocking function must
be set less than the time delay of under voltage function.

379
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

U Disconnection

Normal voltage

U1<

U2<

tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2

Time

Block step 1

Block step 2
en05000466.vsd

IEC05000466 V1 EN

Figure 209: Blocking function

8.1.2.4 Design

The voltage measuring elements continuously measure the three phase-to-neutral


voltages or the three phase-to-phase voltages. Recursive fourier filters, true RMS
filters or input voltage signals are used. The voltages are individually compared to
the set value, and the lowest voltage is used for the inverse time characteristic
integration. A special logic is included to achieve the 1 out of 3, 2 out of 3 and 3
out of 3 criteria to fulfill the START condition. The design of Two step
undervoltage protection UV2PTUV is schematically shown in figure 210.

380
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

UL1 Comparator ST1L1


UL1 < U1< Phase 1
Voltage Phase
Selector ST1L2
UL2 Comparator OpMode1 Phase 2
UL2 < U1< 1 out of 3
2 out of 3 ST1L3
Phase 3 Start
UL3 Comparator 3 out of 3
&
UL3 < U1< Trip ST1
OR
Output
START Logic TR1L1

Step 1
Time integrator TR1L2
MinVoltSelect t1 TRIP
or tReset1
ResetTypeCrv1 TR1L3

TR1
OR

Comparator ST2L1
UL1 < U2< Phase 1
Voltage Phase
Selector ST2L2
Comparator OpMode2 Phase 2
UL2 < U2< 1 out of 3
2 outof 3 ST2L3
Phase 3 Start
Comparator 3 out of 3
&
UL3 < U2< Trip ST2
Output OR

START Logic TR2L1

Step 2
Time integrator TR2L2
MinVoltSelect t2 TRIP
or tReset2
ResetTypeCrv2 TR2L3

TR2
OR

OR START

TRIP
OR

en05000012.vsd
IEC05000834 V1 EN

Figure 210: Schematic design of Two step undervoltage protection UV2PTUV

381
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

8.1.3 Function block


UV2PTUV
U3P* TRIP
BLOCK TR1
BLKTR1 TR1L1
BLKST1 TR1L2
BLKTR2 TR1L3
BLKST2 TR2
TR2L1
TR2L2
TR2L3
START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3

IEC06000276-2-en.vsd
IEC06000276 V2 EN

Figure 211: UV2PTUV function block

8.1.4 Input and output signals


Table 226: UV2PTUV Input signals
Name Type Default Description
U3P GROUP - Three phase voltages
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of operate signal, step 1
BLKST1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of operate signal, step 2
BLKST2 BOOLEAN 0 Block of step 2

Table 227: UV2PTUV Output signals


Name Type Description
TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR1L1 BOOLEAN Trip signal from step1 phase L1
TR1L2 BOOLEAN Trip signal from step1 phase L2
TR1L3 BOOLEAN Trip signal from step1 phase L3
TR2 BOOLEAN Common trip signal from step2
TR2L1 BOOLEAN Trip signal from step2 phase L1
TR2L2 BOOLEAN Trip signal from step2 phase L2
TR2L3 BOOLEAN Trip signal from step2 phase L3
START BOOLEAN General start signal
Table continues on next page

382
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

Name Type Description


ST1 BOOLEAN Common start signal from step1
ST1L1 BOOLEAN Start signal from step1 phase L1
ST1L2 BOOLEAN Start signal from step1 phase L2
ST1L3 BOOLEAN Start signal from step1 phase L3
ST2 BOOLEAN Common start signal from step2
ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2
ST2L3 BOOLEAN Start signal from step2 phase L3

8.1.5 Setting parameters


Table 228: UV2PTUV Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 1
Inverse curve B
Prog. inv. curve
OpMode1 1 out of 3 - - 1 out of 3 Number of phases required for op (1 of
2 out of 3 3, 2 of 3, 3 of 3) from step 1
3 out of 3
U1< 1 - 100 %UB 1 70 Voltage setting/start val (DT & IDMT) in
% of UBase, step 1
t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 1
k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 1
IntBlkSel1 Off - - Off Internal (low level) blocking mode, step 1
Block of trip
Block all
IntBlkStVal1 1 - 100 %UB 1 20 Voltage setting for internal blocking in %
of UBase, step 1
tBlkUV1 0.000 - 60.000 s 0.001 0.000 Time delay of internal (low level)
blocking for step 1
HystAbs1 0.0 - 100.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 1
OperationStep2 Off - - On Enable execution of step 2
On
Characterist2 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 2
Inverse curve B
Prog. inv. curve
Table continues on next page

383
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

Name Values (Range) Unit Step Default Description


OpMode2 1 out of 3 - - 1 out of 3 Number of phases required for op (1 of
2 out of 3 3, 2 of 3, 3 of 3) from step 2
3 out of 3
U2< 1 - 100 %UB 1 50 Voltage setting/start val (DT & IDMT) in
% of UBase, step 2
t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 2
k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 2
IntBlkSel2 Off - - Off Internal (low level) blocking mode, step 2
Block of trip
Block all
IntBlkStVal2 1 - 100 %UB 1 20 Voltage setting for internal blocking in %
of UBase, step 2
tBlkUV2 0.000 - 60.000 s 0.001 0.000 Time delay of internal (low level)
blocking for step 2
HystAbs2 0.0 - 100.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 2

Table 229: UV2PTUV Group settings (advanced)


Name Values (Range) Unit Step Default Description
tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 1
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of reset curve type for step 1
Frozen timer
Linearly decreased
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for prog. under voltage
IDMT curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 2
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of reset curve type for step 2
Frozen timer
Linearly decreased
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 2
Table continues on next page

384
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

Name Values (Range) Unit Step Default Description


BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 2
DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for prog. under voltage
IDMT curve, step 2

Table 230: UV2PTUV Non group settings (basic)


Name Values (Range) Unit Step Default Description
ConnType PhN DFT - - PhN DFT Group selector for connection type
PhPh RMS
PhN RMS
PhPh DFT

8.1.6 Technical data


Table 231: UV2PTUV technical data
Function Range or value Accuracy
Operate voltage, low (1–100)% of UBase ± 1.0% of Ur
and high step
Absolute hysteresis (0–100)% of UBase ± 1.0% of Ur

Internal blocking (1–100)% of UBase ± 1.0% of Ur


level, low and high
step
Inverse time - See table 648
characteristics for
low and high step,
see table 648
Definite time delays (0.000-60.000) s ± 0.5% ±10 ms
Minimum operate (0.000–60.000) s ± 0.5% ± 10 ms
time, inverse
characteristics
Operate time, start 25 ms typically at 2 to 0.5 x Uset -
function
Reset time, start 25 ms typically at 0 to 2 x Uset -
function
Critical impulse time 10 ms typically at 2 to 0 x Uset -

Impulse margin time 15 ms typically -

385
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

8.2 Two step overvoltage protection OV2PTOV

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Two step overvoltage protection OV2PTOV 59

3U>

SYMBOL-C V1 EN

8.2.1 Introduction
Overvoltages may occur in the power system during abnormal conditions, such as,
sudden power loss, tap changer regulating failures, open line ends on long lines.

Two step overvoltage protection OV2PTOV can be used as open line end detector,
normally then combined with directional reactive over-power function or as system
voltage supervision, normally then giving alarm only or switching in reactors or
switch out capacitor banks to control the voltage.

OV2PTOV has two voltage steps, each of them with inverse or definite time delayed.

OV2PTOV has an extremely high reset ratio to allow setting close to system
service voltage.

8.2.2 Principle of operation


Two step overvoltage protection OV2PTOV is used to detect high power system
voltage. OV2PTOV has two steps with separate time delays. If one-, two- or three-
phase voltages increase above the set value, a corresponding START signal is
issued. OV2PTOV can be set to START/TRIP, based on 1 out of 3, 2 out of 3 or 3
out of 3 of the measured voltages, being above the set point. If the voltage remains
above the set value for a time period corresponding to the chosen time delay, the
corresponding trip signal is issued.

The time delay characteristic is individually chosen for the two steps and can be
either, definite time delay or inverse time delay.

The voltage related settings are made in percent of the global set base voltage,
which is set in kV, phase-to-phase.

OV2PTOV can be set to measure phase-to-earth fundamental value, phase-to-phase


fundamental value, phase-to-earth RMS value or phase-to-phase RMS value. The
choice of measuring is done by the parameter ConnType.

The setting of the analog inputs are given as primary phase-to-earth or phase-to-
phase voltage. OV2PTOV will operate if the voltage gets higher than the set

386
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

percentage of the set base voltage UBase. This means operation for phase-to-earth
voltage over:

U > (%) × UBase( kV )


3
EQUATION1434 V1 EN (Equation 101)

and operation for phase for phase voltage over:

U > (%) × UBase(kV)


EQUATION1993 V1 EN (Equation 102)

8.2.2.1 Measurement principle

All the three voltages are measured continuously, and compared with the set
values, U1> and U2>. The parameters OpMode1 and OpMode2 influence the
requirements to activate the START outputs. Either 1 out of 3, 2 out of 3 or 3 out of
3 measured voltages have to be higher than the corresponding set point to issue the
corresponding START signal.

To avoid oscillations of the output START signal, a hysteresis has been included.

8.2.2.2 Time delay

The time delay for the two steps can be either definite time delay (DT) or inverse
time delay (IDMT). For the inverse time delay four different modes are available:
• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve

The type A curve is described as:

k
t=
æ U -U > ö
ç ÷
è U> ø
IEC09000051 V1 EN (Equation 103)

The type B curve is described as:

k × 480
t= 2.0
- 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2287 V1 EN (Equation 104)

387
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

The type C curve is described as:

k × 480
t= 3.0
+ 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2288 V1 EN (Equation 105)

The customer programmable curve can be created as:

k×A
t= p
+D
æ U -U > ö
çB× -C÷
è U> ø
EQUATION1439 V1 EN (Equation 106)

When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore, a tuning parameter
CrvSatn is set to compensate for this phenomenon. In the voltage interval U< down
to U< · (1.0 – CrvSatn/100) the used voltage will be: U< · (1.0 – CrvSatn/100). If
the programmable curve is used this parameter must be calculated so that:

CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN (Equation 107)

The highest phase (or phase-to-phase) voltage is always used for the inverse time
delay integration, see figure 212. The details of the different inverse time
characteristics are shown in section "Inverse characteristics"

388
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

Voltage
IDMT Voltage

UL1
UL2
UL3

Time

en05000016.vsd

IEC05000016 V1 EN

Figure 212: Voltage used for the inverse time characteristic integration

Trip signal issuing requires that the overvoltage condition continues for at least the
user set time delay. This time delay is set by the parameter t1 and t2 for definite
time mode (DT) and by selected voltage level dependent time curves for the
inverse time mode (IDMT). If the START condition, with respect to the measured
voltage ceases during the delay time, and is not fulfilled again within a user defined
reset time (tReset1 and tReset2 for the definite time and tIReset1 and tIReset2 for
the inverse time) the corresponding START output is reset, after that the defined
reset time has elapsed. Here it should be noted that after leaving the hysteresis area,
the START condition must be fulfilled again and it is not sufficient for the signal to
only return back to the hysteresis area. The hysteresis value for each step is settable
(HystAbs2) to allow an high and accurate reset of the function. It should be noted
that for Two step overvoltage protection OV2PTOV the IDMT reset time is
constant and does not depend on the voltage fluctuations during the drop-off
period. However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time..

389
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

tReset
1
tReset1
Voltage
START
TRIP

U1>

Hysteresis
Measured
Voltage

Time

START t1

TRIP

Time
Integrator Linear Decrease
Frozen Timer
t1

Instantaneous Time
Reset IEC09000055-en-1.vsd
IEC09000055 V1 EN

Figure 213: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay

390
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

tReset1
Voltage tReset1
START TRIP
START
Hysteresis

U1>

Measured Voltage

Time

START t1

TRIP

Time Integrator
Frozen Timer

t1

Time
Instantaneous IEC05000020-en-2.vsd
Linear Decrease
Reset

IEC05000020 V2 EN

Figure 214: Voltage profile causing a reset of the START signal for step 1, and inverse time delay

Definite time delay

When definite time delay is selected the function will operate as shown in figure
215. Detailed information about individual stage reset/operation behavior is shown
in figure 207 and figure 208 receptively. Note that by setting tResetn = 0.0s
instantaneous reset of the definite time delayed stage is ensured

391
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

ST1

U tReset1 t1
a
b<a t t
TR1
U1>
b AND
OFF ON
Delay Delay

IEC10000100-1-en.vsd
IEC10000100 V1 EN

Figure 215: Detailed logic diagram for step 1, DT operation

Un>

START

TRIP

tResetn

tn

IEC10000037-1-en.vsd
IEC10000037 V1 EN

Figure 216: Example for Definite Time Delay stage rest

392
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

Un>

START

TRIP

tResetn

tn

IEC10000038-1-en.vsd
IEC10000038 V1 EN

Figure 217: Example for Definite Time Delay stage operation

8.2.2.3 Blocking

It is possible to block Two step overvoltage protection OV2PTOV partially or


completely, by binary input signals where:

BLOCK: blocks all outputs


BLKTR1: blocks all trip outputs of step 1
BLKST1: blocks all start and trip outputs related to step 1
BLKTR2: blocks all trip outputs of step 2
BLKST2: blocks all start and trip outputs related to step 2

8.2.2.4 Design

The voltage measuring elements continuously measure the three phase-to-earth


voltages or the three phase-to-phase voltages. Recursive Fourier filters filter the
input voltage signals. The phase voltages are individually compared to the set
value, and the highest voltage is used for the inverse time characteristic integration.
A special logic is included to achieve the 1 out of 3, 2 out of 3 or 3 out of 3 criteria
to fulfill the START condition. The design of Two step overvoltage protection
(OV2PTOV) is schematically described in figure 218.

393
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

UL1 Comparator ST1L1


UL1 > U1> Phase 1
Voltage Phase
Selector ST1L2
UL2 Comparator OpMode1 Phase 2
UL2 > U1> 1 out of 3
2 outof 3 ST1L3
3 out of 3 Phase 3 Start
UL3 Comparator &
UL3 > U1> Trip ST1
OR
Output
START Logic TR1L1
Step 1
Time integrator TR1L2
MaxVoltSelect t1 TRIP
or tReset1
ResetTypeCrv1 TR1L3

OR TR1

Comparator ST2L1
UL1 > U2> Phase 1
Voltage Phase
Selector ST2L2
Comparator OpMode2 Phase 2
UL2 > U2> 1 out of 3
2 outof 3 ST2L3
Phase 3 Start
3 out of 3
Comparator &
UL3 > U2> Trip ST2
OR
Output
START Logic TR2L1
Step 2
Time integrator TR2L2
MaxVoltSelect t2 TRIP
or tReset2
ResetTypeCrv2 TR2L3

TR2
OR

START
OR

TRIP
OR

en05000013.vsd
IEC05000013-WMF V1 EN

Figure 218: Schematic design of Two step overvoltage protection OV2PTOV

394
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

8.2.3 Function block


OV2PTOV
U3P* TRIP
BLOCK TR1
BLKTR1 TR1L1
BLKST1 TR1L2
BLKTR2 TR1L3
BLKST2 TR2
TR2L1
TR2L2
TR2L3
START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3

IEC06000277-2-en.vsd
IEC06000277 V2 EN

Figure 219: OV2PTOV function block

8.2.4 Input and output signals


Table 232: OV2PTOV Input signals
Name Type Default Description
U3P GROUP - Group signal for three phase voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of operate signal, step 1
BLKST1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of operate signal, step 2
BLKST2 BOOLEAN 0 Block of step 2

Table 233: OV2PTOV Output signals


Name Type Description
TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR1L1 BOOLEAN Trip signal from step1 phase L1
TR1L2 BOOLEAN Trip signal from step1 phase L2
TR1L3 BOOLEAN Trip signal from step1 phase L3
TR2 BOOLEAN Common trip signal from step2
TR2L1 BOOLEAN Trip signal from step2 phase L1
TR2L2 BOOLEAN Trip signal from step2 phase L2
TR2L3 BOOLEAN Trip signal from step2 phase L3
START BOOLEAN General start signal
Table continues on next page

395
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

Name Type Description


ST1 BOOLEAN Common start signal from step1
ST1L1 BOOLEAN Start signal from step1 phase L1
ST1L2 BOOLEAN Start signal from step1 phase L2
ST1L3 BOOLEAN Start signal from step1 phase L3
ST2 BOOLEAN Common start signal from step2
ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2
ST2L3 BOOLEAN Start signal from step2 phase L3

8.2.5 Setting parameters


Table 234: OV2PTOV Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 1
Inverse curve B
Inverse curve C
Prog. inv. curve
OpMode1 1 out of 3 - - 1 out of 3 Number of phases required for op (1 of
2 out of 3 3, 2 of 3, 3 of 3) from step 1
3 out of 3
U1> 1 - 200 %UB 1 120 Voltage setting/start val (DT & IDMT) in
% of UBase, step 1
t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 1
k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 1
HystAbs1 0.0 - 100.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 1
OperationStep2 Off - - On Enable execution of step 2
On
Characterist2 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 2
Inverse curve B
Inverse curve C
Prog. inv. curve
OpMode2 1 out of 3 - - 1 out of 3 Number of phases required for op (1 of
2 out of 3 3, 2 of 3, 3 of 3) from step 2
3 out of 3
U2> 1 - 200 %UB 1 150 Voltage setting/start val (DT & IDMT) in
% of UBase, step 2
Table continues on next page

396
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

Name Values (Range) Unit Step Default Description


t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 2
k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 2
HystAbs2 0.0 - 100.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 2

Table 235: OV2PTOV Group settings (advanced)


Name Values (Range) Unit Step Default Description
tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 1
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of reset curve type for step 1
Frozen timer
Linearly decreased
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for prog. over voltage
IDMT curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 2
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of reset curve type for step 2
Frozen timer
Linearly decreased
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 2
DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for prog. over voltage
IDMT curve, step 2

397
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

Table 236: OV2PTOV Non group settings (basic)


Name Values (Range) Unit Step Default Description
ConnType PhN DFT - - PhN DFT TBD
PhPh DFT
PhN RMS
PhPh RMS

8.2.6 Technical data


Table 237: OV2PTOV technical data
Function Range or value Accuracy
Operate voltage, low (1-200)% of UBase ± 1.0% of Ur at U < Ur
and high step ± 1.0% of U at U > Ur

Absolute hysteresis (0–100)% of UBase ± 1.0% of Ur at U < Ur


± 1.0% of U at U > Ur

Inverse time - See table 647


characteristics for
low and high step,
see table 647
Definite time delays (0.000-60.000) s ± 0.5% ± 10 ms
Minimum operate (0.000-60.000) s ± 0.5% ± 10 ms
time, Inverse
characteristics
Operate time, start 25 ms typically at 0 to 2 x Uset -
function
Reset time, start 25 ms typically at 2 to 0 x Uset -
function
Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -

8.3 Two step residual overvoltage protection


ROV2PTOV

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Two step residual overvoltage ROV2PTOV 59N
protection
3U0
TRV V1 EN

8.3.1 Introduction
Residual voltages may occur in the power system during earth faults.

398
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

Two step residual overvoltage protection ROV2PTOV calculates the residual


voltage from the three-phase voltage input transformers or from a single-phase
voltage input transformer fed from an open delta or neutral point voltage transformer.

ROV2PTOV has two voltage steps, each with inverse or definite time delayed.

8.3.2 Principle of operation


Two step residual overvoltage protection ROV2PTOV is used to detect high single-
phase voltage, such as high residual voltage, also called 3U0. The residual voltage
can be measured directly from a voltage transformer in the neutral of a power
transformer or from a three-phase voltage transformer, where the secondary
windings are connected in an open delta. Another possibility is to measure the three-
phase voltages and internally in the IED calculate the corresponding residual
voltage and connect this calculated residual voltage to ROV2PTOV. ROV2PTOV
has two steps with separate time delays. If the single-phase (residual) voltage
remains above the set value for a time period corresponding to the chosen time
delay, the corresponding TRIP signal is issued.

The time delay characteristic is individually chosen for the two steps and can be
either, definite time delay or inverse time delay.

The voltage related settings are made in percent of the base voltage, which is set in
kV, phase-phase.

8.3.2.1 Measurement principle

The residual voltage is measured continuously, and compared with the set values,
U1> and U2>.

To avoid oscillations of the output START signal, a hysteresis has been included.

8.3.2.2 Time delay

The time delay for the two steps can be either definite time delay (DT) or inverse
time delay (IDMT). For the inverse time delay four different modes are available:
• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve

The type A curve is described as:

k
t=
æ U -U > ö
ç ÷
è U> ø
IEC09000051 V1 EN (Equation 108)

399
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

The type B curve is described as:

k × 480
t= 2.0
- 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2287 V1 EN (Equation 109)

The type C curve is described as:

k × 480
t= 3.0
+ 0.035
æ 32 × U - U > - 0.5 ö
ç ÷
è U > ø
IECEQUATION2288 V1 EN (Equation 110)

The customer programmable curve can be created as:

k×A
t= p
+D
æ U -U > ö
çB× -C÷
è U> ø
EQUATION1439 V1 EN (Equation 111)

When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore a tuning parameter
CrvSatn is set to compensate for this phenomenon. In the voltage interval U> up to
U> · (1.0 + CrvSatn/100) the used voltage will be: U> · (1.0 + CrvSatn/100). If the
programmable curve is used this parameter must be calculated so that:

CrvSatn
B× -C > 0
100
EQUATION1440 V1 EN (Equation 112)

The details of the different inverse time characteristics are shown in section
"Inverse characteristics".

TRIP signal issuing requires that the residual overvoltage condition continues for at
least the user set time delay. This time delay is set by the parameter t1 and t2 for
definite time mode (DT) and by some special voltage level dependent time curves
for the inverse time mode (IDMT).

If the START condition, with respect to the measured voltage ceases during the
delay time, and is not fulfilled again within a user defined reset time (tReset1 and
tReset2 for the definite time and tIReset1 and tIReset2 for the inverse time) the
corresponding START output is reset, after that the defined reset time has elapsed.

Here it should be noted that after leaving the hysteresis area, the START condition
must be fulfilled again and it is not sufficient for the signal to only return back to

400
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

the hysteresis area. Also notice that for the overvoltage function IDMT reset time is
constant and does not depend on the voltage fluctuations during the drop-off
period. However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time. See figure 213 and figure 214.

tReset
1
tReset1
Voltage
START
TRIP

U1>

Hysteresis
Measured
Voltage

Time

START t1

TRIP

Time
Integrator Linear Decrease
Frozen Timer
t1

Instantaneous Time
Reset IEC09000055-en-1.vsd
IEC09000055 V1 EN

Figure 220: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay

401
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

tReset1
Voltage tReset1
START TRIP
START
Hysteresis

U1>

Measured Voltage

Time

START t1

TRIP

Time Integrator
Frozen Timer

t1

Time
Instantaneous IEC05000020-en-2.vsd
Linear Decrease
Reset

IEC05000020 V2 EN

Figure 221: Voltage profile causing a reset of the START signal for step 1, and inverse time delay

Definite timer delay

When definite time delay is selected the function will operate as shown in figure
222. Detailed information about individual stage reset/operation behavior is shown
in figure 207 and figure 208 receptively. Note that by setting tResetn = 0.0s
instantaneous reset of the definite time delayed stage is ensured

402
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

ST1

U tReset1 t1
a
b<a t t
TR1
U1>
b AND
OFF ON
Delay Delay

IEC10000100-1-en.vsd
IEC10000100 V1 EN

Figure 222: Detailed logic diagram for step 1, DT operation

Un<

START

TRIP

tResetn

tn

IEC10000039-1-en.vsd
IEC10000039 V1 EN

Figure 223: Example for Definite Time Delay stage rest

403
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

Un<

START

TRIP

tResetn

tn

IEC10000040-1-en.vsd
IEC10000040 V1 EN

Figure 224: Example for Definite Time Delay stage operation

8.3.2.3 Blocking

It is possible to block Two step residual overvoltage protection ROV2PTOV


partially or completely, by binary input signals where:

BLOCK: blocks all outputs


BLKTR1: blocks all trip outputs of step 1
BLKST1: blocks all start and trip outputs related to step 1
BLKTR2: blocks all trip outputs of step 2
BLKST2: blocks all START and trip inputs related to step 2

8.3.2.4 Design

The voltage measuring elements continuously measure the residual voltage.


Recursive Fourier filters filter the input voltage signal. The single input voltage is
compared to the set value, and is also used for the inverse time characteristic
integration. The design of Two step residual overvoltage protection (ROV2PTOV)
is schematically described in figure 225.

404
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

UN Comparator Phase 1 ST1


UN > U1>
TR1
START Start
&
Trip
Time integrator Output
t1 Logic
TRIP
tReset1
ResetTypeCrv1 Step 1

ST2
Comparator Phase 1
UN > U2> TR2

Start
START &
Trip START
Output OR
Time integrator
Logic
t2 TRIP
tReset2
Step 2
ResetTypeCrv2 TRIP
OR

en05000748.vsd
IEC05000748 V1 EN

Figure 225: Schematic design of Two step residual overvoltage protection


ROV2PTOV

8.3.3 Function block


ROV2PTOV
U3P* TRIP
BLOCK TR1
BLKTR1 TR2
BLKST1 START
BLKTR2 ST1
BLKST2 ST2

IEC06000278-2-en.vsd
IEC06000278 V2 EN

Figure 226: ROV2PTOV function block

405
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

8.3.4 Input and output signals


Table 238: ROV2PTOV Input signals
Name Type Default Description
U3P GROUP - Three phase voltages
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of operate signal, step 1
BLKST1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of operate signal, step 2
BLKST2 BOOLEAN 0 Block of step 2

Table 239: ROV2PTOV Output signals


Name Type Description
TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR2 BOOLEAN Common trip signal from step2
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST2 BOOLEAN Common start signal from step2

8.3.5 Setting parameters


Table 240: ROV2PTOV Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 1
Inverse curve B
Inverse curve C
Prog. inv. curve
U1> 1 - 200 %UB 1 30 Voltage setting/start val (DT & IDMT),
step 1 in % of UBase
t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 1
k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 1
HystAbs1 0.0 - 100.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 1
Table continues on next page

406
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

Name Values (Range) Unit Step Default Description


OperationStep2 Off - - On Enable execution of step 2
On
Characterist2 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 2
Inverse curve B
Inverse curve C
Prog. inv. curve
U2> 1 - 100 %UB 1 45 Voltage setting/start val (DT & IDMT),
step 2 in % of UBase
t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 2
k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 2
HystAbs2 0.0 - 100.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 2

Table 241: ROV2PTOV Group settings (advanced)


Name Values (Range) Unit Step Default Description
tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 1
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of reset curve type for step 1
Frozen timer
Linearly decreased
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for prog. over voltage
IDMT curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Time delay in DT reset (s), step 2
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of reset curve type for step 2
Frozen timer
Linearly decreased
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 2
Table continues on next page

407
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

Name Values (Range) Unit Step Default Description


DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for prog. over voltage
IDMT curve, step 2

8.3.6 Technical data


Table 242: ROV2PTOV technical data
Function Range or value Accuracy
Operate voltage, low (1-200)% of UBase ± 1.0% of Ur at U < Ur
and high step ± 1.0% of U at U > Ur

Absolute hysteresis (0–100)% of UBase ± 1.0% of Ur at U < Ur


± 1.0% of U at U > Ur

Inverse time - See table 649


characteristics for
low and high step,
see table 649
Definite time setting (0.000–60.000) s ± 0.5% ± 10 ms
Minimum operate (0.000-60.000) s ± 0.5% ± 10 ms
time
Operate time, start 25 ms typically at 0 to 2 x Uset -
function
Reset time, start 25 ms typically at 2 to 0 x Uset -
function
Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -

8.4 Overexcitation protection OEXPVPH

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Overexcitation protection OEXPVPH 24

U/f >

SYMBOL-Q V1 EN

8.4.1 Introduction
When the laminated core of a power transformer or generator is subjected to a
magnetic flux density beyond its design limits, stray flux will flow into non-
laminated components not designed to carry flux and cause eddy currents to flow.

408
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

The eddy currents can cause excessive heating and severe damage to insulation and
adjacent parts in a relatively short time. Overexcitation protection OEXPVPH has
settable inverse operating curve and independent alarm stage.

8.4.2 Principle of operation


The importance of Overexcitation protection OEXPVPH is growing as the power
transformers as well as other power system elements today operate most of the
time near their designated limits.

Modern design transformers are more sensitive to overexcitation than earlier types.
This is a result of the more efficient designs and designs which rely on the
improvement in the uniformity of the excitation level of modern systems. Thus, if
emergency that includes overexcitation does occur, transformers may be damaged
unless corrective action is promptly taken. Transformer manufacturers recommend
an overexcitation protection as a part of the transformer protection system.

Overexcitation results from excessive applied voltage, possibly in combination


with below-normal frequency. Such condition may occur when a transformer unit
is on load, but are more likely to arise when it is on open circuit, or at a loss of load
occurrence. Transformers directly connected to generators are in particular danger
to experience overexcitation condition. It follows from the fundamental
transformer equation, see equation 113, that peak flux density Bmax is directly
proportional to induced voltage E, and inversely proportional to frequency f, and
turns n.

E = 4.44 × f × n × Bmax× A
EQUATION898 V2 EN (Equation 113)

The relative excitation M is therefore according to equation 114.

E f
M ( p.u.) =
( Ur ) ( fr )
IECEQUATION2296 V1 EN (Equation 114)

Disproportional variations in quantities E and f may give rise to core overfluxing.


If the core flux density Bmax increases to a point above saturation level (typically
1.9 Tesla), the flux will no longer be contained within the core only but will extend
into other (non-laminated) parts of the power transformer and give rise to eddy
current circulations.

Overexcitation will result in:

• overheating of the non-laminated metal parts


• a large increase in magnetizing currents
• an increase in core and winding temperature
• an increase in transformer vibration and noise

409
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

Protection against overexcitation is based on calculation of the relative volt per


hertz (V/Hz) ratio. The action of the protection is usually to initiate a reduction of
excitation and, if this should fail, or is not possible, to trip the transformer after a
delay which can be from seconds to minutes, typically 5 - 10 seconds.

Overexcitation protection may be of particular concern on directly connected


generator unit transformers. Directly connected generator-transformers are
subjected to a wide range of frequencies during the acceleration and deceleration of
the turbine. In such cases, the overexcitation protection may trip the field breaker
during a start-up of a machine, by means of the overexcitation ALARM signal. If
this is not possible, the power transformer can be disconnected from the source,
after a delay, by the TRIP signal.

The IEC 60076 - 1 standard requires that transformers shall be capable of operating
continuously at 10% above rated voltage at no load, and rated frequency. At no
load, the ratio of the actual generator terminal voltage to the actual frequency
should not exceed 1.1 times the ratio of transformer rated voltage to the rated
frequency on a sustained basis, see equation 115.

---- £ 1.1 × Ur
E ------
f fr
EQUATION900 V1 EN (Equation 115)

or equivalently, with 1.1 · Ur = V/Hz> according to equation 116.

E V Hz>
£
f fr
IECEQUATION2297 V1 EN (Equation 116)

where:
V/Hz> is the maximum continuously allowed voltage at no load, and rated frequency.

V/Hz> is a setting parameter. The setting range is 100% to 180%. If the user does
not know exactly what to set, then the standard IEC 60076 - 1, section 4.4, the
default value V/Hz> = 110% shall be used.

In OEXPVPH, the relative excitation M is expressed according to equation 117.

E f
M ( p.u. ) =
Ur fr
IECEQUATION2299 V1 EN (Equation 117)

It is clear from the above formula that, for an unloaded power transformer, M = 1
for any E and f, where the ratio E/f is equal to Ur/fr. A power transformer is not
overexcited as long as the relative excitation is M ≤ V/Hz>, V/Hz> expressed in %
of Ur/fr.

410
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

The overexcitation protection algorithm is fed with an input voltage U which is in


general not the induced voltage E from the fundamental transformer equation. For
no load condition, these two voltages are the same, but for a loaded power
transformer the internally induced voltage E may be lower or higher than the
voltage U which is measured and fed to OEXPVPH , depending on the direction of
the power flow through the power transformer, the power transformer side where
OEXPVPH is applied, and the power transformer leakage reactance of the winding.
It is important to specify in the application configuration on which side of the
power transformer OEXPVPH is placed.

As an example, at a transformer with a 15% short circuit impedance Xsc, the full
load, 0.8 power factor, 105% voltage on the load side, the actual flux level in the
transformer core, will not be significantly different from that at the 110% voltage,
no load, rated frequency, provided that the short circuit impedance X can be
equally divided between the primary and the secondary winding: Xleak = Xleak1 =
Xleak2 = Xsc / 2 = 0.075 pu.

OEXPVPH calculates the internal induced voltage E if Xleak (meaning the leakage
reactance of the winding where OEXPVPH is connected) is known to the user. The
assumption taken for two-winding power transformers that Xleak = Xsc / 2 is
unfortunately most often not true. For a two-winding power transformer the
leakage reactances of the two windings depend on how the windings are located on
the core with respect to each other. In the case of three-winding power transformers
the situation is still more complex. If a user has the knowledge on the leakage
reactance, then it should applied. If a user has no idea about it, Xleak can be set to
Xc/2. OEXPVPH protection will then take the given measured voltage U, as the
induced voltage E.

It is assumed that overexcitation is a symmetrical phenomenon, caused by events


such as loss-of-load, and so on. It will be observed that a high phase-to-earth
voltage does not mean overexcitation. For example, in an unearthed power system,
a single phase-to-earth fault means high voltages of the “healthy” two phases-to-
earth, but no overexcitation on any winding. The phase-to-phase voltages will
remain essentially unchanged. The important voltage is the voltage between the
two ends of each winding.

8.4.2.1 Measured voltage

If one phase-to-phase voltage is available from the side where overexcitation


protection is applied, then Overexcitation protection OEXPVPH shall be set to
measure this voltage, MeasuredU. The particular voltage which is used determines
the two currents that must be used. This must be chosen with the setting MeasuredI.

It is extremely important that MeasuredU and MeasuredI are set to


same value.

If, for example, voltage UL1L2 is fed to OEXPVPH, then currents IL1, and IL2
must be applied. From these two input currents, current IL1L2 = IL1 - IL2 is

411
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

calculated internally by the OEXPVPH algorithm. The phase-to-phase voltage


must be higher than 70% of the rated value, otherwise the protection algorithm
exits without calculating the excitation. ERROR output is set to 1, and the
displayed value of relative excitation V/Hz shows 0.000.

If three phase-to-earth voltages are available from the side where overexcitation is
connected, then OEXPVPH shall be set to measure positive sequence voltage and
current. In this case the positive sequence voltage and the positive sequence current
are used by OEXPVPH. A check is made if the positive sequence voltage is higher
than 70% of rated phase-to-earth voltage, when below this value, OEXPVPH exits
immediately, and no excitation is calculated. ERROR output is set to 1, and the
displayed value of relative excitation V/Hz shows 0.000.

The frequency value is received from the pre-processing block. The function is in
operation for frequencies within the range of 33-60 Hz and of 42-75 Hz for 50 and
60 Hz respectively.

• OEXPVPH can be connected to any power transformer side, independent from


the power flow.
• The side with a possible load tap changer must not be used.

8.4.2.2 Operate time of the overexcitation protection

The operate time of the overexcitation protection OEXPVPH is a function of the


relative overexcitation.

Basically there are two different delay laws available to choose between:

• the so called IEEE law, and


• a tailor-made law.

The so called IEEE law approximates a square law and has been chosen based on
analysis of the various transformers’ overexcitation capability characteristics. They
can match well a transformer core capability.

The square law is according to equation 118.

0.18 × k
top = 2
æ M ö
ç V Hz> - 1 ÷
è ø
IECEQUATION2298 V1 EN (Equation 118)

where:
M the relative excitation
V/Hz> is maximum continuously allowed voltage at no load, and rated frequency, in pu and
k is time multiplier for inverse time functions, see figure 228.
Parameter k (“time multiplier setting”) selects one delay curve from the family of curves.

412
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

An analog overexcitation relay would have to evaluate the following integral


expression, which means to look for the instant of time t = top according to
equation 119.

top

ò (M (t) - V Hz > ) dt ³ 0.18 × k


2

IECEQUATION2300 V1 EN (Equation 119)

A digital, numerical relay will instead look for the lowest j (that is, j = n) where it
becomes true that:

n
2
Dt × å ( M(j) – V/Hz> ) ³ 0.18 × k
j=k
EQUATION906 V1 EN (Equation 120)

where:
Dt is the time interval between two successive executions of OEXPVPH and
M(j) - V/Hz> is the relative excitation at (time j) in excess of the normal (rated) excitation which is
given as Ur/fr.

As long as M > V/Hz> (that is, overexcitation condition), the above sum can only
be larger with time, and if the overexcitation persists, the protected transformer will
be tripped at j = n.

Inverse delays as per figure 228, can be modified (limited) by two special definite
delay settings, namely tMax and tMin, see figure 227.
delay in s

tMax

under - inverse delay law


excitation

overexcitation
tMin
0 Mmax - V/Hz> Overexcitation M-V/Hz>

M=V/Hz> Mmax Excitation M

V/Hz> Emax E (only if f = fr = const)

99001067.vsd
IEC99001067 V1 EN

Figure 227: Restrictions imposed on inverse delays by tMax and tMin

413
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

A definite maximum time, tMax, can be used to limit the operate time at low
degrees of overexcitation. Inverse delays longer than tMax will not be allowed. In
case the inverse delay is longer than tMax, OEXPVPH trips after tMax seconds.

A definite minimum time, tMin, can be used to limit the operate time at high
degrees of overexcitation. In case the inverse delay is shorter than tMin,
OEXPVPH function trips after tMin seconds. Also, the inverse delay law is no
more valid beyond excitation Mmax. Beyond Mmax (for excitation M > V/Hz>),
the delay will always be tMin, irrespective of the overexcitation level.

Time (s) IEEE OVEREXCITATION CURVES

1000

100

k = 60

k = 20

k = 10
10 k=9
k=8
k=7
k=6
k=5
k=4
k=3

k=2

k=1
1
1 2 3 4 5 10 20 30 40

OVEREXCITATION IN % (M-Emaxcont)*100)

en01000373.vsd

IEC01000373 V1 EN

Figure 228: Delays inversely proportional to the square of the overexcitation

The critical value of excitation M is determined indirectly via OEXPVPH setting V/


Hz>>. V/Hz>> can be thought of as a no-load-rated-frequency voltage, where the
inverse law should be replaced by a short definite delay, tMin. If, for example, V/
Hz>> = 140 %, then M is according to equation 121.

414
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

(V Hz>> ) / f
M= = 1.40
Ur/fr
IECEQUATION2286 V1 EN (Equation 121)

The Tailor-Made law allows a user to design an arbitrary delay characteristic. In


this case the interval between M = V/Hz>, and M = Mmax is automatically divided
into five equal subintervals, with six delays. (settings t1, t2, t3, t4, t5 and t6) as
shown in figure 229. These times should be set so that t1 => t2 => t3 => t4 => t5
=> t6.

delay in s

tMax

under- tMin
excitation Overexcitation M-Emaxcont
0 Mmax - Emaxcont Excitation M

Emaxcont Mmax
99001068.vsd
IEC99001068 V1 EN

Figure 229: An example of a Tailor-Made delay characteristic

Delays between two consecutive points, for example t3 and t4, are obtained by
linear interpolation.

Should it happen that tMax be lower than, for example, delays t1, and t2, the actual
delay would be tMax. Above Mmax, the delay can only be tMin.

8.4.2.3 Cooling

Overexcitation protection OEXPVPH is basically a thermal protection; therefore a


cooling process has been introduced. Exponential cooling process is applied.
Parameter Setting tool is an OEXPVPH setting, with a default time constant
tCooling of 20 minutes. This means that if the voltage and frequency return to their
previous normal values (no more overexcitation), the normal temperature is
assumed to be reached not before approximately 5 times tCooling minutes. If an
overexcitation condition would return before that, the time to trip will be shorter
than it would be otherwise.

8.4.2.4 Overexcitation protection function measurands

A monitored data value, TMTOTRIP, is available on the local HMI and in


PCM600. This value is an estimation of the remaining time to trip (in seconds), if
the overexcitation remained on the level it had when the estimation was done. This
information can be useful with small or moderate overexcitations.

415
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

If the overexcitation is so low that the valid delay is tMax, then the estimation of
the remaining time to trip is done against tMax.

The relative excitation M, shown on the local HMI and in PCM600 as a monitored
data value VPERHZ, is calculated from the expression:

E f
M ( p.u. ) =
Ur fr
IECEQUATION2299 V1 EN (Equation 122)

If VPERHZ value is less than setting V/Hz> (in %), the power transformer is
underexcited. If VPERHZ is equal to V/Hz> (in %), the excitation is exactly equal
to the power transformer continuous capability. If VPERHZ is higher than V/Hz>,
the protected power transformer is overexcited. For example, if VPERHZ = 1.100,
while V/Hz> = 110 %, then the power transformer is exactly on its maximum
continuous excitation limit.

Monitored data value THERMSTA shows the thermal status of the protected
power transformer iron core. THERMSTA gives the thermal status in % of the trip
value which corresponds to 100%. THERMSTA should reach 100% at the same
time, as TMTOTRIP reaches 0 seconds. If the protected power transformer is then
for some reason not switched off, THERMSTA shall go over 100%.

If the delay as per IEEE law, or Tailor-made Law, is limited by tMax, and/or tMin,
then the Thermal status will generally not reach 100% at the same time, when
tTRIP reaches 0 seconds. For example, if, at low degrees of overexcitation, the
very long delay is limited by tMax, then the OEXPVPH TRIP output signal will be
set to 1 before the Thermal status reaches 100%.

8.4.2.5 Overexcitation alarm

A separate step, AlarmLevel, is provided for alarming purpose. It is normally set


2% lower than (V/Hz>) and has a definite time delay, tAlarm. This will give the
operator an early abnormal voltages warning.

416
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

8.4.2.6 Logic diagram

BLOCK
AlarmLevel
ALARM
t>tAlarm &
t
tAlarm
M>V/Hz>
t>tMin TRIP
t &
V/Hz> tMin
U3P Calculation
Ei k
M
of internal M=
I3P induced (Ei / f) M IEEE law
voltage Ei (Ur / fr)
³1
M t
Tailor-made law
M>V/Hz>> tMax
Xleak

V/Hz>>

M = relative V/Hz as service value


IEC05000162-2-en.vsd
IEC05000162 V2 EN

Figure 230: A simplified logic diagram of the Overexcitation protection


OEXPVPH

Simplification of the diagram is in the way the IEEE and Tailor-made delays are
calculated. The cooling process is not shown. It is not shown that voltage and
frequency are separately checked against their respective limit values.

8.4.3 Function block


OEXPVPH
I3P* TRIP
U3P* START
BLOCK ALARM
RESET

IEC05000329-2-en.vsd
IEC05000329 V3 EN

Figure 231: OEXPVPH function block

8.4.4 Input and output signals


Table 243: OEXPVPH Input signals
Name Type Default Description
I3P GROUP - Current connection
SIGNAL
U3P GROUP - Voltage connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
RESET BOOLEAN 0 Reset operation

417
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

Table 244: OEXPVPH Output signals


Name Type Description
TRIP BOOLEAN Trip from overexcitation function
START BOOLEAN Overexcitation above set operate level
(instantaneous)
ALARM BOOLEAN Overexcitation above set alarm level (delayed)

8.4.5 Setting parameters


Table 245: OEXPVPH Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current (rated phase current) in A
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage (main voltage) in kV
V/Hz> 100.0 - 180.0 %UB/f 0.1 110.0 Operate level of V/Hz at no load and
rated freq in % of (Ubase/frated)
V/Hz>> 100.0 - 200.0 %UB/f 0.1 140.0 High level of V/Hz above which tMin is
used, in % of (Ubase/frated)
XLeak 0.000 - 200.000 ohm 0.001 0.000 Winding leakage reactance in primary
ohms
TrPulse 0.000 - 60.000 s 0.001 0.100 Length of the pulse for trip signal (in sec)
tMin 0.000 - 60.000 s 0.001 7.000 Minimum trip delay for V/Hz inverse
curve, in sec
tMax 0.00 - 9000.00 s 0.01 1800.00 Maximum trip delay for V/Hz inverse
curve, in sec
tCooling 0.10 - 9000.00 s 0.01 1200.00 Transformer magnetic core cooling time
constant, in sec
CurveType IEEE - - IEEE Inverse time curve selection, IEEE/Tailor
Tailor made made
kForIEEE 1 - 60 - 1 1 Time multiplier for IEEE inverse type
curve
AlarmLevel 50.0 - 120.0 % 0.1 100.0 Alarm operate level as % of operate level
tAlarm 0.00 - 9000.00 s 0.01 5.00 Alarm time delay, in sec

Table 246: OEXPVPH Group settings (advanced)


Name Values (Range) Unit Step Default Description
t1Tailor 0.00 - 9000.00 s 0.01 7200.00 Time delay t1 (longest) for tailor made
curve, in sec
t2Tailor 0.00 - 9000.00 s 0.01 3600.00 Time delay t2 for tailor made curve, in sec
t3Tailor 0.00 - 9000.00 s 0.01 1800.00 Time delay t3 for tailor made curve, in sec
t4Tailor 0.00 - 9000.00 s 0.01 900.00 Time delay t4 for tailor made curve, in sec
t5Tailor 0.00 - 9000.00 s 0.01 450.00 Time delay t5 for tailor made curve, in sec
t6Tailor 0.00 - 9000.00 s 0.01 225.00 Time delay t6 (shortest) for tailor made
curve, in sec

418
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

Table 247: OEXPVPH Non group settings (basic)


Name Values (Range) Unit Step Default Description
MeasuredU PosSeq - - L1L2 Selection of measured voltage
L1L2
L2L3
L3L1
MeasuredI L1L2 - - L1L2 Selection of measured current
L2L3
L3L1
PosSeq

8.4.6 Technical data


Table 248: OEXPVPH technical data
Function Range or value Accuracy
Operate value, start (100–180)% of (UBase/frated) ± 1.0% of U

Operate value, alarm (50–120)% of start level ± 1.0% of Ur at U ≤ Ur


± 1.0% of U at U > Ur

Operate value, high level (100–200)% of (UBase/frated) ± 1.0% of U

Curve type IEEE or customer defined Class 5 + 40 ms

(0.18 × k )
IEEE : t =
( M - 1) 2

EQUATION1319 V1 EN (Equation 123)

where M = (E/f)/(Ur/fr)
Minimum time delay for inverse (0.000–60.000) s ± 0.5% ± 10 ms
function
Maximum time delay for inverse (0.00–9000.00) s ± 0.5% ± 10 ms
function
Alarm time delay (0.000–60.000) s ± 0.5% ± 10 ms

8.5 Voltage differential protection VDCPTOV

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Voltage differential protection VDCPTOV - 60

8.5.1 Introduction
A voltage differential monitoring function is available. It compares the voltages
from two three phase sets of voltage transformers and has one sensitive alarm step
and one trip step. It can be used to supervise the voltage from two fuse groups or
two different voltage transformers fuses as a fuse/MCB supervision function.

419
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

8.5.2 Principle of operation


The Voltage differential protection function VDCPTOV (60) is based on
comparison of the amplitudes of the two voltages connected in each phase.
Possible differences between the ratios of the two Voltage/Capacitive voltage
transformers can be compensated for with a ratio correction factors RFLx. The
voltage difference is evaluated and if it exceeds the alarm level UDAlarm or trip
level UDATrip signals for alarm (ALARM output) or trip (TRIP output) is given
after definite time delay tAlarm respectively tTrip. The two three phase voltage
supplies are also supervised with undervoltage settings U1Low and U2Low. The
outputs for loss of voltage U1LOW resp U2LOW will be activated. The U1 voltage
is supervised for loss of individual phases whereas the U2 voltage is supervised for
loss of all three phases.

Loss of all U1or all U2 voltages will block the differential measurement. This
blocking can be switched off with setting BlkDiffAtULow = No.

VDCPTOV function can be blocked from an external condition with the binary
BLOCK input. It can for example, be activated from Fuse failure supervision
function SDDRFUF.

To allow easy commissioning the measured differential voltage is available as


service value. This allows simple setting of the ratio correction factor to achieve
full balance in normal service.

The principle logic diagram is shown in figure 232.

420
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

UDTripL1>
AND

UDTripL1> O tReset tTrip


AND
R t t
AND TRIP

UDTripL1>
AND
AND START

UDAlarmL1>
AND

UDAlarmL1> O tAlarm
AND
R t AND ALARM

UDAlarmL1>
AND

U1<L1
tAlarm
U1<L2 AND t U1LOW
AND
AND
U1<L3

OR
BlkDiffAtULow

U2<L1
t1
U2<L2 AND t U2LOW
AND

U2<L3

BLOCK

en06000382-1.vsd

IEC06000382 V2 EN

Figure 232: Principle logic for Voltage differential function VDCPTOV

8.5.3 Function block


VDCPTOV
U3P1* TRIP
U3P2* START
BLOCK ALARM
U1LOW
U2LOW
UL1DIFF
UL2DIFF
UL3DIFF

IEC06000528-2-en.vsd
IEC06000528 V2 EN

Figure 233: VDCPTOV function block

421
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

8.5.4 Input and output signals


Table 249: VDCPTOV Input signals
Name Type Default Description
U3P1 GROUP - Bus voltage
SIGNAL
U3P2 GROUP - Capacitor voltage
SIGNAL
BLOCK BOOLEAN 0 Block of function

Table 250: VDCPTOV Output signals


Name Type Description
TRIP BOOLEAN Voltage differential protection operated
START BOOLEAN Start of voltage differential protection
ALARM BOOLEAN Voltage differential protection alarm
U1LOW BOOLEAN Loss of U1 voltage
U2LOW BOOLEAN Loss of U2 voltage
UL1DIFF REAL Differential Voltage phase L1
UL2DIFF REAL Differential Voltage phase L2
UL3DIFF REAL Differential Voltage phase L3

8.5.5 Setting parameters


Table 251: VDCPTOV Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
UBase 0.50 - 2000.00 kV 0.01 400.00 Base Voltage
BlkDiffAtULow No - - Yes Block operation at low voltage
Yes
UDTrip 0.0 - 100.0 %UB 0.1 5.0 Operate level, in % of UBase
tTrip 0.000 - 60.000 s 0.001 1.000 Time delay for voltage differential
operate, in milliseconds
tReset 0.000 - 60.000 s 0.001 0.000 Time delay for voltage differential reset,
in seconds
U1Low 0.0 - 100.0 %UB 0.1 70.0 Input 1 undervoltage level, in % of UBase
U2Low 0.0 - 100.0 %UB 0.1 70.0 Input 2 undervoltage level, in % of UBase
tBlock 0.000 - 60.000 s 0.001 0.000 Reset time for undervoltage block
UDAlarm 0.0 - 100.0 %UB 0.1 2.0 Alarm level, in % of UBase
tAlarm 0.000 - 60.000 s 0.001 2.000 Time delay for voltage differential alarm,
in seconds

422
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

Table 252: VDCPTOV Group settings (advanced)


Name Values (Range) Unit Step Default Description
RFL1 0.000 - 3.000 - 0.001 1.000 Ratio compensation factor phase L1
U2L1*RFL1=U1L1
RFL2 0.000 - 3.000 - 0.001 1.000 Ratio compensation factor phase L2
U2L2*RFL2=U1L2
RFL3 0.000 - 3.000 - 0.001 1.000 Ratio compensation factor phase L3
U2L3*RFL3=U1L3

8.5.6 Technical data


Table 253: VDCPTOV technical data
Function Range or value Accuracy
Voltage difference for alarm and (0.0–100.0) % of UBase ± 0.5 % of Ur
trip
Under voltage level (0.0–100.0) % of UBase ± 0.5% of Ur

Timers (0.000–60.000)s ± 0.5% ± 10 ms

8.6 Loss of voltage check LOVPTUV

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Loss of voltage check LOVPTUV - 27

8.6.1 Introduction
Loss of voltage check (LOVPTUV) is suitable for use in networks with an
automatic system restoration function. LOVPTUV issues a three-pole trip
command to the circuit breaker, if all three phase voltages fall below the set value
for a time longer than the set time and the circuit breaker remains closed.

8.6.2 Principle of operation


The operation of Loss of voltage check LOVPTUV is based on line voltage
measurement. LOVPTUV is provided with a logic, which automatically recognises
if the line was restored for at least tRestore before starting the tTrip timer. All three
phases are required to be low before the output TRIP is activated. The START
output signal indicates start.

Additionally, LOVPTUV is automatically blocked if only one or two phase


voltages have been detected low for more than tBlock.

423
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

LOVPTUV operates again only if the line has been restored to full voltage for at
least tRestore. Operation of the function is also inhibited by fuse failure and open
circuit breaker information signals, by their connection to dedicated inputs of the
function block.

Due to undervoltage conditions being continuous the trip pulse is limited to a


length set by setting tPulse.

The operation of LOVPTUV is supervised by the fuse-failure function (VTSU


input) and the information about the open position (CBOPEN) of the associated
circuit breaker.

The BLOCK input can be connected to a binary input of the IED in order to receive
a block command from external devices or can be software connected to other
internal functions of the IED itself in order to receive a block command from
internal functions. LOVPTUV is also blocked when the IED is in TEST status and
the function has been blocked from the HMI test menu. (Blocked=Yes).

424
Technical reference manual
1MRK505183-UEN C Section 8
Voltage protection

TEST

TEST-ACTIVE
&
Blocked = Yes

START
BLOCK >1
Function Enable tTrip tPulse TRIP
STUL1N & t

STUL2N &
only 1 or 2 phases are low for
Latched at least 10 s (not three)
STUL3N Enable
&

tBlock
>1 t

CBOPEN Reset Enable


>1
&
VTSU
tRestore
>1 Set Enable
t
>1
Line restored for
at least 3 s

IEC07000089_2_en.vsd

IEC07000089 V2 EN

Figure 234: Simplified diagram of Loss of voltage check LOVPTUV

8.6.3 Function block


LOVPTUV
U3P* TRIP
BLOCK START
CBOPEN
VTSU

IEC07000039-2-en.vsd
IEC07000039 V2 EN

Figure 235: LOVPTUV function block

425
Technical reference manual
Section 8 1MRK505183-UEN C
Voltage protection

8.6.4 Input and output signals


Table 254: LOVPTUV Input signals
Name Type Default Description
U3P GROUP - Voltage connection
SIGNAL
BLOCK BOOLEAN 0 Block the all outputs
CBOPEN BOOLEAN 0 Circuit breaker open
VTSU BOOLEAN 0 Block from voltage circuit supervision

Table 255: LOVPTUV Output signals


Name Type Description
TRIP BOOLEAN Trip signal
START BOOLEAN Start signal

8.6.5 Setting parameters


Table 256: LOVPTUV Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
UBase 0.1 - 9999.9 kV 0.1 400.0 Base voltage
UPE 1 - 100 %UB 1 70 Operate voltagein% of base voltage
Ubase
tTrip 0.000 - 60.000 s 0.001 7.000 Operate time delay

Table 257: LOVPTUV Group settings (advanced)


Name Values (Range) Unit Step Default Description
tPulse 0.050 - 60.000 s 0.001 0.150 Duration of TRIP pulse
tBlock 0.000 - 60.000 s 0.001 5.000 Time delay to block when all 3ph
voltages are not low
tRestore 0.000 - 60.000 s 0.001 3.000 Time delay for enable the function after
restoration

8.6.6 Technical data


Table 258: LOVPTUV technical data
Function Range or value Accuracy
Operate voltage (0–100)% of UBase ± 0.5% of Ur

Pulse timer (0.050–60.000) s ± 0.5% ± 10 ms


Timers (0.000–60.000) s ± 0.5% ± 10 ms

426
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection

Section 9 Frequency protection

About this chapter


This chapter describes the frequency protection functions. The way the functions
work, their setting parameters, function blocks, input and output signals and
technical data are included for each function.

9.1 Underfrequency protection SAPTUF

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Underfrequency protection SAPTUF 81

f<

SYMBOL-P V1 EN

9.1.1 Introduction
Underfrequency occurs as a result of lack of generation in the network.

Underfrequency protection SAPTUF is used for load shedding systems, remedial


action schemes, gas turbine startup and so on.

SAPTUF is provided with an under voltage blocking.

The operation may be based on single-phase, phase-to-phase or positive-sequence


voltage measurement.

9.1.2 Principle of operation


Underfrequency protection SAPTUF is used to detect low power system frequency.
SAPTUF can either have a definite time delay or a voltage magnitude dependent
time delay. If the voltage magnitude dependent time delay is applied, the time
delay will be longer if the voltage is higher, and the delay will be shorter if the
voltage is lower. If the frequency remains below the set value for a time period
corresponding to the chosen time delay, the corresponding trip signal is issued. To
avoid an unwanted trip due to uncertain frequency measurement at low voltage
magnitude, a voltage controlled blocking of the function is available, that is, if the

427
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection

voltage is lower than the set blocking voltage IntBlockLevel the function is blocked
and no START or TRIP signal is issued.

9.1.2.1 Measurement principle

The fundamental frequency of the measured input voltage is measured


continuously, and compared with the set value, StartFrequency. The frequency
function is dependent on the voltage magnitude. If the voltage magnitude decreases
the setting IntBlockLevel, SAPTUF gets blocked, and the output BLKDMAGN is
issued. All voltage settings are made in percent of the setting UBase, which should
be set as a phase-phase voltage in kV.

To avoid oscillations of the output START signal, a hysteresis has been included.

9.1.2.2 Time delay

The time delay for underfrequency protection SAPTUF can be either a settable
definite time delay or a voltage magnitude dependent time delay, where the time
delay depends on the voltage level; a high voltage level gives a longer time delay
and a low voltage level causes a short time delay. For the definite time delay, the
setting TimeDlyOperate sets the time delay.

For the voltage dependent time delay the measured voltage level and the settings
UNom, UMin, Exponent, tMax and tMin set the time delay according to figure 236
and equation 124. The setting TimerOperation is used to decide what type of time
delay to apply.

Trip signal issuing requires that the underfrequency condition continues for at least
the user set time delay TimeDlyOperate. If the START condition, with respect to
the measured frequency ceases during this user set delay time, and is not fulfilled
again within a user defined reset time, TimeDlyReset, the START output is reset,
after that the defined reset time has elapsed. Here it should be noted that after
leaving the hysteresis area, the START condition must be fulfilled again and it is
not sufficient for the signal to only return back to the hysteresis area.

On the output of SAPTUF a 100ms pulse is issued, after a time delay


corresponding to the setting of TimeDlyRestore, when the measured frequency
returns to the level corresponding to the setting RestoreFreq.

9.1.2.3 Voltage dependent time delay

Since the fundamental frequency in a power system is the same all over the system,
except some deviations during power oscillations, another criterion is needed to
decide, where to take actions, based on low frequency. In many applications the
voltage level is very suitable, and in most cases is load shedding preferable in areas
with low voltage. Therefore, a voltage dependent time delay has been introduced,
to make sure that load shedding, or other actions, take place at the right location. At
constant voltage, U, the voltage dependent time delay is calculated according to
equation 124. At non-constant voltage, the actual time delay is integrated in a

428
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection

similar way as for the inverse time characteristic for the undervoltage and
overvoltage functions.
Exponent
é U - UMin ù
t=ê × ( tMax - tMin ) + tMin
ë UNom - UMin úû
EQUATION1182 V1 EN (Equation 124)

where:
t is the voltage dependent time delay (at constant voltage),
U is the measured voltage
Exponent is a setting,
UMin, UNom are voltage settings corresponding to
tMax, tMin are time settings.

The inverse time characteristics are shown in figure 236, for:

UMin = 90%
UNom = 100%
tMax = 1.0 s
tMin = 0.0 s
Exponent = 0, 1, 2, 3 and 4

1
0
1
Exponenent
TimeDlyOperate [s]

2
3
0.5 4

0
90 95 100

U [% of UBase]
en05000075.vsd
IEC05000075 V1 EN

Figure 236: Voltage dependent inverse time characteristics for underfrequency


protection SAPTUF. The time delay to operate is plotted as a
function of the measured voltage, for the Exponent = 0, 1, 2, 3, 4
respectively.

429
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection

9.1.2.4 Blocking

It is possible to block underfrequency protection SAPTUF partially or completely,


by binary input signals or by parameter settings, where:

BLOCK: blocks all outputs


BLKTRIP: blocks the TRIP output
BLKREST: blocks the RESTORE output

If the measured voltage level decreases below the setting of IntBlockLevel, both the
START and the TRIP outputs, are blocked.

9.1.2.5 Design

The frequency measuring element continuously measures the frequency of the


positive sequence voltage and compares it to the setting StartFrequency. The
frequency signal is filtered to avoid transients due to switchings and faults. The
time integrator can operate either due to a definite delay time or to the special
voltage dependent delay time. When the frequency has returned back to the setting
of RestoreFreq, the RESTORE output is issued after the time delay
TimeDlyRestore. The design of underfrequency protection SAPTUF is
schematically described in figure 237.

Block

BLOCK BLKDMAGN
OR
Comparator
U < IntBlockLevel

Voltage Time integrator


Start
TimerOperation Mode & START
Selector START
Frequency Comparator Trip
f < StartFrequency Output
TimeDlyOperate TRIP Logic

TimeDlyReset TRIP

100 ms

Comparator RESTORE
TimeDlyRestore
f > RestoreFreq

en05000726.vsd

IEC05000726 V1 EN

Figure 237: Simplified logic diagram for SAPTUF

430
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection

9.1.3 Function block


SAPTUF
U3P* TRIP
BLOCK START
BLKTRIP RESTORE
BLKREST BLKDMAGN
FREQ

IEC06000279_2_en.vsd
IEC06000279 V2 EN

Figure 238: SAPTUF function block

9.1.4 Input and output signals


Table 259: SAPTUF Input signals
Name Type Default Description
U3P GROUP - Voltage connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTRIP BOOLEAN 0 Blocking operate output.
BLKREST BOOLEAN 0 Blocking restore output.

Table 260: SAPTUF Output signals


Name Type Description
TRIP BOOLEAN Operate/trip signal for frequency.
START BOOLEAN Start/pick-up signal for frequency.
RESTORE BOOLEAN Restore signal for load restoring purposes.
BLKDMAGN BOOLEAN Blocking indication due to low amplitude.
FREQ REAL Measured frequency

9.1.5 Setting parameters


Table 261: SAPTUF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
StartFrequency 35.00 - 75.00 Hz 0.01 48.80 Frequency setting/start value.
IntBlockLevel 0 - 100 %UB 1 50 Internal blocking level in % of UBase.
TimeDlyOperate 0.000 - 60.000 s 0.001 0.200 Operate time delay in over/under-
frequency mode.
TimeDlyReset 0.000 - 60.000 s 0.001 0.000 Time delay for reset.
TimeDlyRestore 0.000 - 60.000 s 0.001 0.000 Restore time delay.
Table continues on next page

431
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection

Name Values (Range) Unit Step Default Description


RestoreFreq 45.00 - 65.00 Hz 0.01 50.10 Restore frequency if frequency is above
frequency value.
TimerOperation Definite timer - - Definite timer Setting for choosing timer mode.
Volt based timer
UNom 50 - 150 %UB 1 100 Nominal voltage in % of UBase for
voltage based timer.
UMin 50 - 150 %UB 1 90 Lower operation limit in % of UBase for
voltage based timer.
Exponent 0.0 - 5.0 - 0.1 1.0 For calculation of the curve form for
voltage based timer.
tMax 0.010 - 60.000 s 0.001 1.000 Maximum time operation limit for voltage
based timer.
tMin 0.010 - 60.000 s 0.001 1.000 Minimum time operation limit for voltage
based timer.

9.1.6 Technical data


Table 262: SAPTUF technical data
Function Range or value Accuracy
Operate value, start function (35.00-75.00) Hz ± 2.0 mHz
Operate time, start function 100 ms typically -
Reset time, start function 100 ms typically -
Operate time, definite time function (0.000-60.000)s ± 0.5% ±
10 ms
Reset time, definite time function (0.000-60.000)s ± 0.5% ±
10 ms
Voltage dependent time delay Settings: Class 5 +
UNom=(50-150)% of Ubase 200 ms
é U - UMin ù
Exponent
UMin=(50-150)% of Ubase
t=ê × ( tMax - tMin ) + tMin
ë UNom - UMin ú û Exponent=0.0-5.0
tMax=(0.000-60.000)s
EQUATION1182 V1 EN (Equation 125)
tMin=(0.000-60.000)s
U=Umeasured

9.2 Overfrequency protection SAPTOF

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Overfrequency protection SAPTOF 81

f>

SYMBOL-O V1 EN

432
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection

9.2.1 Introduction
Overfrequency protection function SAPTOF is applicable in all situations, where
reliable detection of high fundamental power system frequency is needed.

Overfrequency occurs at sudden load drops or shunt faults in the power network.
Close to the generating plant, generator governor problems can also cause over
frequency.

SAPTOF is used mainly for generation shedding and remedial action schemes. It is
also used as a frequency stage initiating load restoring.

SAPTOF is provided with an undervoltage blocking. The operation is based on single-


phase, phase-to-phase or positive-sequence voltage measurement.

9.2.2 Principle of operation


Overfrequency protection SAPTOF is used to detect high power system frequency.
SAPTOF has a settable definite time delay. If the frequency remains above the set
value for a time period corresponding to the chosen time delay, the corresponding
TRIP signal is issued. To avoid an unwanted TRIP due to uncertain frequency
measurement at low voltage magnitude, a voltage controlled blocking of the
function is available from the preprocessing function, that is, if the voltage is lower
than the set blocking voltage in the preprocessing function, the function is blocked
and no START or TRIP signal is issued.

9.2.2.1 Measurement principle

The fundamental frequency of the positive sequence voltage is measured


continuously, and compared with the set value, StartFrequency. Overfrequency
protection SAPTOF is dependent on the voltage magnitude. If the voltage
magnitude decreases below the setting IntBlockLevel, SAPTOF is blocked, and the
output BLKDMAGN is issued. All voltage settings are made in percent of the
UBase, which should be set as a phase-phase voltage in kV. To avoid oscillations
of the output START signal, a hysteresis has been included.

9.2.2.2 Time delay

The time delay for Overfrequency protection SAPTOF (81) is a settable definite
time delay, specified by the setting TimeDlyOperate.

TRIP signal issuing requires that the overfrequency condition continues for at least
the user set time delay, TimeDlyReset. If the START condition, with respect to the
measured frequency ceases during this user set delay time, and is not fulfilled again
within a user defined reset time, TimeDlyReset, the START output is reset, after
that the defined reset time has elapsed. It is to be noted that after leaving the
hysteresis area, the START condition must be fulfilled again and it is not sufficient
for the signal to only return back to the hysteresis area.

433
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection

9.2.2.3 Blocking

It is possible to block overfrequency protection SAPTOF partially or completely,


by binary input signals or by parameter settings, where:

BLOCK: blocks all outputs


BLKTRIP: blocks the TRIP output

If the measured voltage level decreases below the setting of IntBlockLevel, both the
START and the TRIP outputs, are blocked.

9.2.2.4 Design

The frequency measuring element continuously measures the frequency of the


positive sequence voltage and compares it to the setting StartFrequency. The
frequency signal is filtered to avoid transients due to switchings and faults in the
power system. The time integrator operates due to a definite delay time. The design
of overfrequency protection SAPTOF is schematically described in figure 239.

BLOCK
BLKTRIP BLOCK
OR BLKDMAGN
Comparator
U < IntBlockLevel

Start
&
Trip
Voltage Time integrator Output
Logic
Definite Time Delay START START
Frequency Comparator
f > StartFrequency TimeDlyOperate
TRIP
TimeDlyReset
TRIP

en05000735.vsd

IEC05000735 V1 EN

Figure 239: Schematic design of overfrequency protection SAPTOF

434
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection

9.2.3 Function block


SAPTOF
U3P* TRIP
BLOCK START
BLKTRIP BLKDMAGN
FREQ

IEC06000280_2_en.vsd
IEC06000280 V2 EN

Figure 240: SAPTOF function block

9.2.4 Input and output signals


Table 263: SAPTOF Input signals
Name Type Default Description
U3P GROUP - Voltage connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTRIP BOOLEAN 0 Blocking operate output.

Table 264: SAPTOF Output signals


Name Type Description
TRIP BOOLEAN Operate/trip signal for frequency.
START BOOLEAN Start/pick-up signal for frequency.
BLKDMAGN BOOLEAN Blocking indication due to low amplitude.
FREQ REAL Measured frequency

9.2.5 Setting parameters


Table 265: SAPTOF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
StartFrequency 35.00 - 75.00 Hz 0.01 51.20 Frequency setting/start value.
IntBlockLevel 0 - 100 %UB 1 50 Internal blocking level in % of UBase.
TimeDlyOperate 0.000 - 60.000 s 0.001 0.000 Operate time delay in over/under-
frequency mode.
TimeDlyReset 0.000 - 60.000 s 0.001 0.000 Time delay for reset.

435
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection

9.2.6 Technical data


Table 266: SAPTOF technical data
Function Range or value Accuracy
Operate value, start function (35.00-75.00) Hz ± 2.0 mHz at symmetrical three-
phase voltage
Operate time, start function 100 ms typically -
Reset time, start function 100 ms typically -
Operate time, definite time (0.000-60.000)s ± 0.5% ± 10 ms
function
Reset time, definite time (0.000-60.000)s ± 0.5% ± 10 ms
function

9.3 Rate-of-change frequency protection SAPFRC

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Rate-of-change frequency protection SAPFRC 81

df/dt >
<

SYMBOL-N V1 EN

9.3.1 Introduction
Rate-of-change frequency protection function (SAPFRC) gives an early indication
of a main disturbance in the system. SAPFRC can be used for generation shedding,
load shedding, remedial action schemes. SAPFRC can discriminate between
positive or negative change of frequency.

SAPFRC is provided with an undervoltage blocking. The operation may be based


on single-phase, phase-to-phase or positive-sequence voltage measurement.

9.3.2 Principle of operation


Rate-of-change frequency protection SAPFRC is used to detect fast power system
frequency changes, increase as well as, decrease at an early stage. SAPFRC has a
settable definite time delay. If the rate-of-change of frequency remains below the
set value, for negative rate-of-change, for a time period equal to the chosen time
delay, the TRIP signal is issued. If the rate-of-change of frequency remains above
the set value, for positive rate-of-change, for a time period equal to the chosen time
delay, the TRIP signal is issued. To avoid an unwanted TRIP due to uncertain
frequency measurement at low voltage magnitude, a voltage controlled blocking of
the function is available, that is if the voltage is lower than the set blocking voltage

436
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection

IntBlockLevel, the function is blocked and no START or TRIP signal is issued. If


the frequency recovers, after a frequency decrease, a restore signal is issued.

9.3.2.1 Measurement principle

The rate-of-change of the fundamental frequency of the selected voltage is


measured continuously, and compared with the set value, StartFreqGrad. Rate-of-
change frequency protection SAPFRC is also dependent on the voltage magnitude.
If the voltage magnitude decreases below the setting IntBlockLevel, SAPFRC is
blocked, and the output BLKDMAGN is issued. The sign of the setting
StartFreqGrad, controls if SAPFRC reacts on a positive or on a negative change in
frequency. If SAPFRC is used for decreasing frequency that is, the setting
StartFreqGrad has been given a negative value, and a trip signal has been issued,
then a 100 ms pulse is issued on the RESTORE output, when the frequency
recovers to a value higher than the setting RestoreFreq. A positive setting of
StartFreqGrad, sets SAPFRC to START and TRIP for frequency increases.

To avoid oscillations of the output START signal, a hysteresis has been included.

9.3.2.2 Time delay

Rate-of-change frequency protection SAPFRC has a settable definite time delay,


tTrip. .

Trip signal issuing requires that the rate-of-change of frequency condition


continues for at least the user set time delay, tTrip. If the START condition, with
respect to the measured frequency ceases during the delay time, and is not fulfilled
again within a user defined reset time, tReset, the START output is reset, after that
the defined reset time has elapsed. Here it should be noted that after leaving the
hysteresis area, the START condition must be fulfilled again and it is not sufficient
for the signal to only return back into the hysteresis area.

The RESTORE output of SAPFRC is set, after a time delay equal to the setting of
tRestore, when the measured frequency has returned to the level corresponding to
RestoreFreq, after an issue of the TRIP output signal. If tRestore is set to 0.000 s
the restore functionality is disabled, and no output will be given. The restore
functionality is only active for lowering frequency conditions and the restore
sequence is disabled if a new negative frequency gradient is detected during the
restore period, defined by the settings RestoreFreq and tRestore.

9.3.2.3 Blocking

Rate-of-change frequency protection (SAPFRC) can be partially or totally blocked,


by binary input signals or by parameter settings, where:

BLOCK: blocks all outputs


BLKTRIP: blocks the TRIP output
BLKREST: blocks the RESTORE output

437
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection

If the measured voltage level decreases below the setting of IntBlockLevel, both the
START and the TRIP outputs, are blocked.

9.3.2.4 Design

Rate-of-change frequency protection (SAPFRC) measuring element continuously


measures the frequency of the selected voltage and compares it to the setting
StartFreqGrad. The frequency signal is filtered to avoid transients due to power
system switchings and faults. The time integrator operates with a definite delay
time. When the frequency has returned back to the setting of RestoreFreq, the
RESTORE output is issued after the time delay tRestore, if the TRIP signal has
earlier been issued. The sign of the setting StartFreqGrad is essential, and controls
if the function is used for raising or lowering frequency conditions. The design of
SAPFRC is schematically described in figure 241.

BLOCK
BLKTRIP

BLKRESET BLOCK
OR

Voltage Comparator BLKDMAGN


U < IntBlockLevel

Start
Rate-of-Change Time integrator &
Comparator
of Frequency Trip
If
Definite Time Delay Output
[StartFreqGrad<0 START START
Logic
AND
TimeDlyOperate
df/dt < StartFreqGrad]
OR
TimeDlyReset
[StartFreqGrad>0
AND
TRIP
df/dt > StartFreqGrad]
Then
START
100 ms

Frequency Comparator RESTORE


TimeDlyRestore
f > RestoreFreq

en05000835.vsd

IEC05000835 V1 EN

Figure 241: Schematic design of Rate-of-change frequency protection SAPFRC

438
Technical reference manual
1MRK505183-UEN C Section 9
Frequency protection

9.3.3 Function block


SAPFRC
U3P* TRIP
BLOCK START
BLKTRIP RESTORE
BLKREST BLKDMAGN

IEC06000281-2-en.vsd
IEC06000281 V2 EN

Figure 242: SAPFRC function block

9.3.4 Input and output signals


Table 267: SAPFRC Input signals
Name Type Default Description
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTRIP BOOLEAN 0 Blocking operate output.
BLKREST BOOLEAN 0 Blocking restore output.

Table 268: SAPFRC Output signals


Name Type Description
TRIP BOOLEAN Operate/trip signal for frequencyGradient
START BOOLEAN Start/pick-up signal for frequencyGradient
RESTORE BOOLEAN Restore signal for load restoring purposes.
BLKDMAGN BOOLEAN Blocking indication due to low amplitude.

9.3.5 Setting parameters


Table 269: SAPFRC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for the phase-phase voltage
in kV
StartFreqGrad -10.00 - 10.00 Hz/s 0.01 0.50 Frequency gradient start value. Sign
defines direction.
IntBlockLevel 0 - 100 %UB 1 50 Internal blocking level in % of UBase.
tTrip 0.000 - 60.000 s 0.001 0.200 Operate time delay in pos./neg.
frequency gradient mode.
RestoreFreq 45.00 - 65.00 Hz 0.01 49.90 Restore frequency if frequency is above
frequency value (Hz)
tRestore 0.000 - 60.000 s 0.001 0.000 Restore time delay.
tReset 0.000 - 60.000 s 0.001 0.000 Time delay for reset.

439
Technical reference manual
Section 9 1MRK505183-UEN C
Frequency protection

9.3.6 Technical data


Table 270: SAPFRC Technical data
Function Range or value Accuracy
Operate value, start function (-10.00-10.00) Hz/s ± 10.0 mHz/s
Operate value, internal (0-100)% of UBase ± 1.0% of Ur
blocking level
Operate time, start function 100 ms typically -

440
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection

Section 10 Multipurpose protection

About this chapter


This chapter describes Multipurpose protection and includes the General current
and voltage function. The way the functions work, their setting parameters,
function blocks, input and output signals and technical data are included for each
function.

10.1 General current and voltage protection CVGAPC

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
General current and voltage protection CVGAPC - -

10.1.1 Introduction
The General current and voltage protection (CVGAPC) can be utilized as a
negative sequence current protection detecting unsymmetrical conditions such as
open phase or unsymmetrical faults.

CVGAPC can also be used to improve phase selection for high resistive earth
faults, outside the distance protection reach, for the transmission line. Three
functions are used, which measures the neutral current and each of the three phase
voltages. This will give an independence from load currents and this phase
selection will be used in conjunction with the detection of the earth fault from the
directional earth fault protection function.

10.1.2 Principle of operation

10.1.2.1 Measured quantities within CVGAPC

General current and voltage protection (CVGAPC) function is always connected to


three-phase current and three-phase voltage input in the configuration tool, but it
will always measure only one current and one voltage quantity selected by the end
user in the setting tool.

The user can select to measure one of the current quantities shown in table 271.

441
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection

Table 271: Current selection for CVGAPC function


Set value for the
parameter Comment
CurrentInput
1 Phase1 CVGAPC function will measure the phase L1 current phasor
2 Phase2 CVGAPC function will measure the phase L2 current phasor
3 Phase3 CVGAPC function will measure the phase L3 current phasor
4 PosSeq CVGAPC function will measure internally calculated positive sequence
current phasor
5 NegSeq CVGAPC function will measure internally calculated negative
sequence current phasor
6 3ZeroSeq CVGAPC function will measure internally calculated zero sequence
current phasor multiplied by factor 3
7 MaxPh CVGAPC function will measure current phasor of the phase with
maximum magnitude
8 MinPh CVGAPC function will measure current phasor of the phase with
minimum magnitude
9 UnbalancePh CVGAPC function will measure magnitude of unbalance current, which
is internally calculated as the algebraic magnitude difference between
the current phasor of the phase with maximum magnitude and current
phasor of the phase with minimum magnitude. Phase angle will be set
to 0° all the time
10 Phase1-Phase2 CVGAPC function will measure the current phasor internally calculated
as the vector difference between the phase L1 current phasor and
phase L2 current phasor (IL1-IL2)

11 Phase2-Phase3 CVGAPC function will measure the current phasor internally calculated
as the vector difference between the phase L2 current phasor and
phase L3 current phasor (IL2-IL3)

12 Phase3-Phase1 CVGAPC function will measure the current phasor internally calculated
as the vector difference between the phase L3 current phasor and
phase L1 current phasor ( IL3-IL1)

13 MaxPh-Ph CVGAPC function will measure ph-ph current phasor with the
maximum magnitude
14 MinPh-Ph CVGAPC function will measure ph-ph current phasor with the
minimum magnitude
15 UnbalancePh-Ph CVGAPC function will measure magnitude of unbalance current, which
is internally calculated as the algebraic magnitude difference between
the ph-ph current phasor with maximum magnitude and ph-ph current
phasor with minimum magnitude. Phase angle will be set to 0° all the
time

The user can select to measure one of the voltage quantities shown in table 272:

Table 272: Voltage selection for CVGAPC function


Set value for the
parameter Comment
VoltageInput
1 Phase1 CVGAPC function will measure the phase L1 voltage phasor
2 Phase2 CVGAPC function will measure the phase L2 voltage phasor
3 Phase3 CVGAPC function will measure the phase L3 voltage phasor
Table continues on next page

442
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection

Set value for the


parameter Comment
VoltageInput
4 PosSeq CVGAPC function will measure internally calculated positive sequence
voltage phasor
5 -NegSeq CVGAPC function will measure internally calculated negative
sequence voltage phasor. This voltage phasor will be intentionally
rotated for 180° in order to enable easier settings for the directional
feature when used.
6 -3ZeroSeq CVGAPC function will measure internally calculated zero sequence
voltage phasor multiplied by factor 3. This voltage phasor will be
intentionally rotated for 180° in order to enable easier settings for the
directional feature when used.
7 MaxPh CVGAPC function will measure voltage phasor of the phase with
maximum magnitude
8 MinPh CVGAPC function will measure voltage phasor of the phase with
minimum magnitude
9 UnbalancePh CVGAPC function will measure magnitude of unbalance voltage,
which is internally calculated as the algebraic magnitude difference
between the voltage phasor of the phase with maximum magnitude
and voltage phasor of the phase with minimum magnitude. Phase
angle will be set to 0° all the time
10 Phase1-Phase2 CVGAPC function will measure the voltage phasor internally
calculated as the vector difference between the phase L1 voltage
phasor and phase L2 voltage phasor (UL1-UL2)

11 Phase2-Phase3 CVGAPC function will measure the voltage phasor internally


calculated as the vector difference between the phase L2 voltage
phasor and phase L3 voltage phasor (UL2-UL3)

12 Phase3-Phase1 CVGAPC function will measure the voltage phasor internally


calculated as the vector difference between the phase L3 voltage
phasor and phase L1 voltage phasor ( UL3-UL1)

13 MaxPh-Ph CVGAPC function will measure ph-ph voltage phasor with the
maximum magnitude
14 MinPh-Ph CVGAPC function will measure ph-ph voltage phasor with the
minimum magnitude
15 UnbalancePh-Ph CVGAPC function will measure magnitude of unbalance voltage,
which is internally calculated as the algebraic magnitude difference
between the ph-ph voltage phasor with maximum magnitude and ph-
ph voltage phasor with minimum magnitude. Phase angle will be set to
0° all the time

It is important to notice that the voltage selection from table 272 is always
applicable regardless the actual external VT connections. The three-phase VT
inputs can be connected to IED as either three phase-to-ground voltages UL1, UL2
& UL3 or three phase-to-phase voltages UL1L2, UL2L3 & UL3L1). This information
about actual VT connection is entered as a setting parameter for the pre-processing
block, which will then take automatic care about it.

The user can select one of the current quantities shown in table 273 for built-in
current restraint feature:

443
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection

Table 273: Restraint current selection for CVGAPC function


Set value for the
parameter RestrCurr Comment
1 PosSeq CVGAPC function will measure internally calculated positive sequence
current phasor
2 NegSeq CVGAPC function will measure internally calculated negative
sequence current phasor
3 3ZeroSeq CVGAPC function will measure internally calculated zero sequence
current phasor multiplied by factor 3
4 MaxPh CVGAPC function will measure current phasor of the phase with
maximum magnitude

10.1.2.2 Base quantities for CVGAPC function

The parameter settings for the base quantities, which represent the base (100%) for
pickup levels of all measuring stages, shall be entered as setting parameters for
every CVGAPC function.

Base current shall be entered as:

1. rated phase current of the protected object in primary amperes, when the
measured Current Quantity is selected from 1 to 9, as shown in table 271.
2. rated phase current of the protected object in primary amperes multiplied by
√3 (1.732 · Iphase), when the measured Current Quantity is selected from 10
to 15, as shown in table 271.

Base voltage shall be entered as:

1. rated phase-to-earth voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 1 to 9, as shown in table 272.
2. rated phase-to-phase voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 10 to 15, as shown in table 272.

10.1.2.3 Built-in overcurrent protection steps

Two overcurrent protection steps are available. They are absolutely identical and
therefore only one will be explained here.

Overcurrent step simply compares the magnitude of the measured current quantity
(see table 271) with the set pickup level. Non-directional overcurrent step will
pickup if the magnitude of the measured current quantity is bigger than this set
level. Reset ratio is settable, with default value of 0.96. However depending on
other enabled built-in features this overcurrent pickup might not cause the
overcurrent step start signal. Start signal will only come if all of the enabled built-
in features in the overcurrent step are fulfilled at the same time.

444
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection

Second harmonic feature


The overcurrent protection step can be restrained by a second harmonic component
in the measured current quantity (see table 271). However it shall be noted that this
feature is not applicable when one of the following measured currents is selected:

• PosSeq (positive sequence current)


• NegSeq (negative sequence current)
• UnbalancePh (unbalance phase current)
• UnbalancePh-Ph (unbalance ph-ph current)

This feature will simple prevent overcurrent step start if the second-to-first
harmonic ratio in the measured current exceeds the set level.

Directional feature
The overcurrent protection step operation can be can be made dependent on the
relevant phase angle between measured current phasor (see table 271) and
measured voltage phasor (see table 272). In protection terminology it means that
the General currrent and voltage protection (CVGAPC) function can be made
directional by enabling this built-in feature. In that case overcurrent protection step
will only operate if the current flow is in accordance with the set direction
(Forward, which means towards the protected object, or Reverse, which means
from the protected object). For this feature it is of the outmost importance to
understand that the measured voltage phasor (see table 272) and measured current
phasor (see table 271) will be used for directional decision. Therefore it is the sole
responsibility of the end user to select the appropriate current and voltage signals in
order to get a proper directional decision. CVGAPC function will NOT do this
automatically. It will just simply use the current and voltage phasors selected by
the end user to check for the directional criteria.

Table 274 gives an overview of the typical choices (but not the only possible ones)
for these two quantities for traditional directional relays.

Table 274: Typical current and voltage choices for directional feature
Set value for the Set value for the
parameter parameter Comment
CurrentInput VoltageInput
PosSeq PosSeq Directional positive sequence overcurrent function is
obtained. Typical setting for RCADir is from -45° to
-90° depending on the power
NegSeq -NegSeq Directional negative sequence overcurrent function is
obtained. Typical setting for RCADir is from -45° to
-90° depending on the power system voltage level (X/
R ratio)
3ZeroSeq -3ZeroSeq Directional zero sequence overcurrent function is
obtained. Typical setting for RCADir is from 0° to
-90° depending on the power system earthing (that
is, solidly earthed, earthed via resistor)
Table continues on next page

445
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection

Set value for the Set value for the


parameter parameter Comment
CurrentInput VoltageInput
Phase1 Phase2-Phase3 Directional overcurrent function for the first phase is
obtained. Typical setting for RCADir is +30° or +45°
Phase2 Phase3-Phase1 Directional overcurrent function for the second phase
is obtained. Typical setting for RCADir is +30° or +45°
Phase3 Phase1-Phase2 Directional overcurrent function for the third phase is
obtained. Typical setting for RCADir is +30° or +45°

Unbalance current or voltage measurement shall not be used when the directional
feature is enabled.

Two types of directional measurement principles are available, I & U and


IcosPhi&U. The first principle, referred to as "I & U" in the parameter setting tool,
checks that:

• the magnitude of the measured current is bigger than the set pick-up level
• the phasor of the measured current is within the operating region (defined by
the relay operate angle, ROADir parameter setting; see figure 243).

U=-3U0
RCADir

Ipickup ROADir I=3Io

Operate region
mta line

en05000252.vsd
IEC05000252 V1 EN

Figure 243: I & U directional operating principle for CVGAPC function

where:
RCADir is -75°
ROADir is 50°

The second principle, referred to as "IcosPhi&U" in the parameter setting tool,


checks that:

446
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection

• that the product I·cos(Φ) is bigger than the set pick-up level, where Φ is angle
between the current phasor and the mta line
• that the phasor of the measured current is within the operating region (defined
by the I·cos(Φ) straight line and the relay operate angle, ROADir parameter
setting; see figure 243).

U=-3U0
RCADir

Ipickup ROADir F I=3Io

Operate region
mta line

en05000253.vsd
IEC05000253 V1 EN

Figure 244: CVGAPC, IcosPhi&U directional operating principle

where:
RCADir is -75°
ROADir is 50°

Note that it is possible to decide by a parameter setting how the directional feature
shall behave when the magnitude of the measured voltage phasor falls below the pre-
set value. User can select one of the following three options:

• Non-directional (operation allowed for low magnitude of the reference voltage)


• Block (operation prevented for low magnitude of the reference voltage)
• Memory (memory voltage shall be used to determine direction of the current)

It shall also be noted that the memory duration is limited in the algorithm to 100
ms. After that time the current direction will be locked to the one determined
during memory time and it will re-set only if the current fails below set pickup
level or voltage goes above set voltage memory limit.

Voltage restraint/control feature


The overcurrent protection step operation can be can be made dependent of a
measured voltage quantity (see table 272). Practically then the pickup level of the
overcurrent step is not constant but instead decreases with the decrease in the
magnitude of the measured voltage quantity. Two different types of dependencies
are available:

• Voltage restraint overcurrent (when setting parameter VDepMode_OC1=Slope)

447
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection

OC1 Stage Pickup Level

StartCurr_OC1

VDepFact_OC1 * StartCurr_OC1

ULowLimit_OC1 UHighLimit_OC1
Selected Voltage
Magnitude
en05000324.vsd
IEC05000324 V1 EN

Figure 245: Example for OC1 step current pickup level variation as function of
measured voltage magnitude in Slope mode of operation

• Voltage controlled overcurrent (when setting parameter


VDepMode_OC1=Step)

OC1 Stage Pickup Level

StartCurr_OC1

VDepFact_OC1 * StartCurr_OC1

UHighLimit_OC1 Selected Voltage Magnitude

en05000323.vsd
IEC05000323 V1 EN

Figure 246: Example for OC1 step current pickup level variation as function of
measured voltage magnitude in Step mode of operation

This feature will simply change the set overcurrent pickup level in accordance with
magnitude variations of the measured voltage. It shall be noted that this feature will
as well affect the pickup current value for calculation of operate times for IDMT

448
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection

curves (overcurrent with IDMT curve will operate faster during low voltage
conditions).

Current restraint feature


The overcurrent protection step operation can be made dependent of a restraining
current quantity (see table 273). Practically then the pickup level of the overcurrent
step is not constant but instead increases with the increase in the magnitude of the
restraining current.

IMeasured
ea ain
ar tr
te es
ra ff *Ir
pe e
O Co
es tr
I>R
IsetHigh

IsetLow

atan(RestrCoeff)

Restraint
en05000255.vsd
IEC05000255 V1 EN

Figure 247: Current pickup variation with restraint current magnitude

This feature will simply prevent overcurrent step to start if the magnitude of the
measured current quantity is smaller than the set percentage of the restrain current
magnitude. However this feature will not affect the pickup current value for
calculation of operate times for IDMT curves. This means that the IDMT curve
operate time will not be influenced by the restrain current magnitude.

When set, the start signal will start definite time delay or inverse (IDMT) time
delay in accordance with the end user setting. If the start signal has value one for
longer time than the set time delay, the overcurrent step will set its trip signal to
one. Reset of the start and trip signal can be instantaneous or time delay in
accordance with the end user setting.

10.1.2.4 Built-in undercurrent protection steps

Two undercurrent protection steps are available. They are absolutely identical and
therefore only one will be explained here. Undercurrent step simply compares the
magnitude of the measured current quantity (see table 271) with the set pickup
level. The undercurrent step will pickup and set its start signal to one if the
magnitude of the measured current quantity is smaller than this set level. The start
signal will start definite time delay with set time delay. If the start signal has value
one for longer time than the set time delay the undercurrent step will set its trip

449
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection

signal to one. Reset of the start and trip signal can be instantaneous or time delay in
accordance with the setting.

10.1.2.5 Built-in overvoltage protection steps

Two overvoltage protection steps are available. They are absolutely identical and
therefore only one will be explained here.

Overvoltage step simply compares the magnitude of the measured voltage quantity
(see table 272) with the set pickup level. The overvoltage step will pickup if the
magnitude of the measured voltage quantity is bigger than this set level. Reset ratio
is settable, with default value of 0.99.

The start signal will start definite time delay or inverse (IDMT) time delay in
accordance with the end user setting. If the start signal has value one for longer
time than the set time delay, the overvoltage step will set its trip signal to one.
Reset of the start and trip signal can be instantaneous or time delay in accordance
with the end user setting.

10.1.2.6 Built-in undervoltage protection steps

Two undervoltage protection steps are available. They are absolutely identical and
therefore only one will be explained here.

Undervoltage step simply compares the magnitude of the measured voltage


quantity (see table 272) with the set pickup level. The undervoltage step will
pickup if the magnitude of the measured voltage quantity is smaller than this set
level. Reset ratio is settable, with default value of 1.01.

The start signal will start definite time delay or inverse (IDMT) time delay in
accordance with the end user setting. If the start signal has value one for longer
time than the set time delay, the undervoltage step will set its trip signal to one.
Reset of the start and trip signal can be instantaneous or time delay in accordance
with the end user setting.

10.1.2.7 Logic diagram

The simplified internal logics, for CVGAPC function are shown in the following
figures.

450
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection

IED
ADM CVGAPC function

Current and voltage selection


settings

Phasor calculation of
scaling with CT ratio

individual currents
A/D conversion
Selection of which current Selected current
and voltage shall be given to

Phasors &
samples
the built-in protection Selected voltage
elements

Restraint current selection

Selected restraint current


A/D conversion scaling

Selection of restraint current


Phasor calculation of
individual voltages
with CT ratio

Phasors &
samples

IEC05000169_2_en.vsd

IEC05000169 V2 EN

Figure 248: Treatment of measured currents within IED for CVGAPC function

Figure 248 shows how internal treatment of measured currents is done for
multipurpose protection function

The following currents and voltages are inputs to the multipurpose protection
function. They must all be expressed in true power system (primary) Amperes and
kilovolts.

1. Instantaneous values (samples) of currents & voltages from one three-phase


current and one three-phase voltage input.
2. Fundamental frequency phasors from one three-phase current and one three-
phase voltage input calculated by the pre-processing modules.
3. Sequence currents & voltages from one three-phase current and one three-
phase voltage input calculated by the pre-processing modules.

The multipurpose protection function:

1. Selects one current from the three-phase input system (see table 271) for
internally measured current.
2. Selects one voltage from the three-phase input system (see table 272) for
internally measured voltage.
3. Selects one current from the three-phase input system (see table 273) for
internally measured restraint current.

451
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection

CURRENT

UC1
nd TRUC1
2 Harmonic
Selected current restraint
STUC2
UC2
TRUC2
2nd Harmonic
restraint

STOC1
OC1 TROC1

2nd Harmonic BLK2ND


restraint ³1
Selected restraint current
Current restraint
DIROC1
Directionality
Voltage control /
restraint

STOC2
OC2 TROC2

2nd Harmonic
restraint
Current restraint ³1
UDIRLOW

Directionality DIROC2

Voltage control /
restraint

STOV1
OV1 TROV1

STOV2
OV2 TROV2

STUV1
Selected voltage
UV1 TRUV1

STUV2
UV2 TRUV2

VOLTAGE

en05000170.vsd
IEC05000170 V1 EN

Figure 249: CVGAPC function main logic diagram for built-in protection elements

452
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection

Logic in figure 249 can be summarized as follows:

1. The selected currents and voltage are given to built-in protection elements.
Each protection element and step makes independent decision about status of
its START and TRIP output signals.
2. More detailed internal logic for every protection element is given in the
following four figures
3. Common START and TRIP signals from all built-in protection elements &
steps (internal OR logic) are available from multipurpose function as well.

Enable
second
harmonic Second
harmonic check
1 DEF time BLKTROC
selected DEF 1 TROC1
AND
OR
Selected current a
a>b
b
OC1=On STOC1
AND
StartCurr_OC1 BLKOC1
X
Inverse

Voltage Directionality DIR_OK Inverse


control or time
check selected
restraint
feature

Selected voltage
Current
Restraint
Feature
Selected restrain current Imeasured > k Irestraint

en05000831.vsd

IEC05000831 V1 EN

Figure 250: Simplified internal logic diagram for built-in first overcurrent step that is, OC1 (step OC2 has the
same internal logic)

453
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection

Bin input: BLKUC1TR

Selected current a TRUC1


b>a
DEF AND
b
StartCurr_UC1
AND

Operation_UC1=On
STUC1

Bin input: BLKUC1

en05000750.vsd

IEC05000750 V1 EN

Figure 251: Simplified internal logic diagram for built-in first undercurrent step that is, UC1 (step UC2 has
the same internal logic)

DEF time BLKTROV1


selected DEF TROV1
AND
OR
Selected voltage a
a>b
b STOV1
StartVolt_OV1
AND

Inverse
Operation_OV1=On
Inverse time
BLKOV1 selected

en05000751.vsd

IEC05000751 V1 EN

Figure 252: Simplified internal logic diagram for built-in first overvoltage step OV1 (step OV2 has the same
internal logic)

454
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection

DEF time BLKTRUV


selected DEF 1 TRUV1
AND
OR
Selected voltage a
b>a
b STUV1
AND
StartVolt_UV1

Inverse
Operation_UV1=On
Inverse time
BLKUV1 selected

en05000752.vsd

IEC05000752 V1 EN

Figure 253: Simplified internal logic diagram for built-in first undervoltage step UV1 (step UV2 has the same
internal logic)

10.1.3 Function block


CVGAPC
I3P* TRIP
U3P* TROC1
BLOCK TROC2
BLKOC1 TRUC1
BLKOC1TR TRUC2
ENMLTOC1 TROV1
BLKOC2 TROV2
BLKOC2TR TRUV1
ENMLTOC2 TRUV2
BLKUC1 START
BLKUC1TR STOC1
BLKUC2 STOC2
BLKUC2TR STUC1
BLKOV1 STUC2
BLKOV1TR STOV1
BLKOV2 STOV2
BLKOV2TR STUV1
BLKUV1 STUV2
BLKUV1TR BLK2ND
BLKUV2 DIROC1
BLKUV2TR DIROC2
UDIRLOW
CURRENT
ICOSFI
VOLTAGE
UIANGLE

IEC05000372-2-en.vsd
IEC05000372 V2 EN

Figure 254: CVGAPC function block

455
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection

10.1.4 Input and output signals


Table 275: CVGAPC Input signals
Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKOC1 BOOLEAN 0 Block of over current function OC1
BLKOC1TR BOOLEAN 0 Block of trip for over current function OC1
ENMLTOC1 BOOLEAN 0 When activated, the current multiplier is in use for
OC1
BLKOC2 BOOLEAN 0 Block of over current function OC2
BLKOC2TR BOOLEAN 0 Block of trip for over current function OC2
ENMLTOC2 BOOLEAN 0 When activated, the current multiplier is in use for
OC2
BLKUC1 BOOLEAN 0 Block of under current function UC1
BLKUC1TR BOOLEAN 0 Block of trip for under current function UC1
BLKUC2 BOOLEAN 0 Block of under current function UC2
BLKUC2TR BOOLEAN 0 Block of trip for under current function UC2
BLKOV1 BOOLEAN 0 Block of over voltage function OV1
BLKOV1TR BOOLEAN 0 Block of trip for over voltage function OV1
BLKOV2 BOOLEAN 0 Block of over voltage function OV2
BLKOV2TR BOOLEAN 0 Block of trip for over voltage function OV2
BLKUV1 BOOLEAN 0 Block of under voltage function UV1
BLKUV1TR BOOLEAN 0 Block of trip for under voltage function UV1
BLKUV2 BOOLEAN 0 Block of under voltage function UV2
BLKUV2TR BOOLEAN 0 Block of trip for under voltage function UV2

Table 276: CVGAPC Output signals


Name Type Description
TRIP BOOLEAN General trip signal
TROC1 BOOLEAN Trip signal from overcurrent function OC1
TROC2 BOOLEAN Trip signal from overcurrent function OC2
TRUC1 BOOLEAN Trip signal from undercurrent function UC1
TRUC2 BOOLEAN Trip signal from undercurrent function UC2
TROV1 BOOLEAN Trip signal from overvoltage function OV1
TROV2 BOOLEAN Trip signal from overvoltage function OV2
TRUV1 BOOLEAN Trip signal from undervoltage function UV1
TRUV2 BOOLEAN Trip signal from undervoltage function UV2
Table continues on next page

456
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection

Name Type Description


START BOOLEAN General start signal
STOC1 BOOLEAN Start signal from overcurrent function OC1
STOC2 BOOLEAN Start signal from overcurrent function OC2
STUC1 BOOLEAN Start signal from undercurrent function UC1
STUC2 BOOLEAN Start signal from undercurrent function UC2
STOV1 BOOLEAN Start signal from overvoltage function OV1
STOV2 BOOLEAN Start signal from overvoltage function OV2
STUV1 BOOLEAN Start signal from undervoltage function UV1
STUV2 BOOLEAN Start signal from undervoltage function UV2
BLK2ND BOOLEAN Block from second harmonic detection
DIROC1 INTEGER Directional mode of OC1 (nondir, forward,reverse)
DIROC2 INTEGER Directional mode of OC2 (nondir, forward,reverse)
UDIRLOW BOOLEAN Low voltage for directional polarization
CURRENT REAL Measured current value
ICOSFI REAL Measured current multiplied with cos (Phi)
VOLTAGE REAL Measured voltage value
UIANGLE REAL Angle between voltage and current

10.1.5 Setting parameters


Table 277: CVGAPC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
CurrentInput phase1 - - MaxPh Select current signal which will be
phase2 measured inside function
phase3
PosSeq
NegSeq
3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
IBase 1 - 99999 A 1 3000 Base Current
Table continues on next page

457
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection

Name Values (Range) Unit Step Default Description


VoltageInput phase1 - - MaxPh Select voltage signal which will be
phase2 measured inside function
phase3
PosSeq
-NegSeq
-3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
UBase 0.05 - 2000.00 kV 0.05 400.00 Base Voltage
OperHarmRestr Off - - Off Operation of 2nd harmonic restrain Off /
On On
l_2nd/l_fund 10.0 - 50.0 % 1.0 20.0 Ratio of second to fundamental current
harmonic in %
BlkLevel2nd 10 - 5000 %IB 1 5000 Harm analyse disabled above this
current level in % of Ibase
EnRestrainCurr Off - - Off Enable current restrain function On / Off
On
RestrCurrInput PosSeq - - PosSeq Select current signal which will be used
NegSeq for curr restrain
3*ZeroSeq
Max
RestrCurrCoeff 0.00 - 5.00 - 0.01 0.00 Restraining current coefficient
RCADir -180 - 180 Deg 1 -75 Relay Characteristic Angle
ROADir 1 - 90 Deg 1 75 Relay Operate Angle
LowVolt_VM 0.0 - 5.0 %UB 0.1 0.5 Below this level in % of Ubase setting
ActLowVolt takes over
Operation_OC1 Off - - Off Operation OC1 Off / On
On
StartCurr_OC1 2.0 - 5000.0 %IB 1.0 120.0 Operate current level for OC1 in % of
Ibase
CurveType_OC1 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for OC1
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
Table continues on next page

458
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection

Name Values (Range) Unit Step Default Description


tDef_OC1 0.00 - 6000.00 s 0.01 0.50 Independent (definitive) time delay of
OC1
k_OC1 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent time
delay for OC1
tMin_OC1 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IEC IDMT
curves for OC1
VCntrlMode_OC1 Voltage control - - Off Control mode for voltage controlled OC1
Input control function
Volt/Input control
Off
VDepMode_OC1 Step - - Step Voltage dependent mode OC1 (step,
Slope slope)
VDepFact_OC1 0.02 - 5.00 - 0.01 1.00 Multiplying factor for I pickup when OC1
is U dependent
ULowLimit_OC1 1.0 - 200.0 %UB 0.1 50.0 Voltage low limit setting OC1 in % of
Ubase
UHighLimit_OC1 1.0 - 200.0 %UB 0.1 100.0 Voltage high limit setting OC1 in % of
Ubase
HarmRestr_OC1 Off - - Off Enable block of OC1 by 2nd harmonic
On restrain
DirMode_OC1 Non-directional - - Non-directional Directional mode of OC1 (nondir,
Forward forward,reverse)
Reverse
DirPrinc_OC1 I&U - - I&U Measuring on IandU or IcosPhiandU for
IcosPhi&U OC1
ActLowVolt1_VM Non-directional - - Non-directional Low voltage level action for Dir_OC1
Block (Nodir, Blk, Mem)
Memory
Operation_OC2 Off - - Off Operation OC2 Off / On
On
StartCurr_OC2 2.0 - 5000.0 %IB 1.0 120.0 Operate current level for OC2 in % of
Ibase
CurveType_OC2 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for OC2
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
tDef_OC2 0.00 - 6000.00 s 0.01 0.50 Independent (definitive) time delay of
OC2
k_OC2 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent time
delay for OC2
Table continues on next page

459
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection

Name Values (Range) Unit Step Default Description


tMin_OC2 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IEC IDMT
curves for OC2
VCntrlMode_OC2 Voltage control - - Off Control mode for voltage controlled OC2
Input control function
Volt/Input control
Off
VDepMode_OC2 Step - - Step Voltage dependent mode OC2 (step,
Slope slope)
VDepFact_OC2 0.02 - 5.00 - 0.01 1.00 Multiplying factor for I pickup when OC2
is U dependent
ULowLimit_OC2 1.0 - 200.0 %UB 0.1 50.0 Voltage low limit setting OC2 in % of
Ubase
UHighLimit_OC2 1.0 - 200.0 %UB 0.1 100.0 Voltage high limit setting OC2 in % of
Ubase
HarmRestr_OC2 Off - - Off Enable block of OC2 by 2nd harmonic
On restrain
DirMode_OC2 Non-directional - - Non-directional Directional mode of OC2 (nondir,
Forward forward,reverse)
Reverse
DirPrinc_OC2 I&U - - I&U Measuring on IandU or IcosPhiandU for
IcosPhi&U OC2
ActLowVolt2_VM Non-directional - - Non-directional Low voltage level action for Dir_OC2
Block (Nodir, Blk, Mem)
Memory
Operation_UC1 Off - - Off Operation UC1 Off / On
On
EnBlkLowI_UC1 Off - - Off Enable internal low current level blocking
On for UC1
BlkLowCurr_UC1 0 - 150 %IB 1 20 Internal low current blocking level for
UC1 in % of Ibase
StartCurr_UC1 2.0 - 150.0 %IB 1.0 70.0 Operate undercurrent level for UC1 in %
of Ibase
tDef_UC1 0.00 - 6000.00 s 0.01 0.50 Independent (definitive) time delay of UC1
tResetDef_UC1 0.00 - 6000.00 s 0.01 0.00 Reset time delay used in IEC Definite
Time curve UC1
HarmRestr_UC1 Off - - Off Enable block of UC1 by 2nd harmonic
On restrain
Operation_UC2 Off - - Off Operation UC2 Off / On
On
EnBlkLowI_UC2 Off - - Off Enable internal low current level blocking
On for UC2
BlkLowCurr_UC2 0 - 150 %IB 1 20 Internal low current blocking level for
UC2 in % of Ibase
StartCurr_UC2 2.0 - 150.0 %IB 1.0 70.0 Operate undercurrent level for UC2 in %
of Ibase
tDef_UC2 0.00 - 6000.00 s 0.01 0.50 Independent (definitive) time delay of UC2
HarmRestr_UC2 Off - - Off Enable block of UC2 by 2nd harmonic
On restrain
Operation_OV1 Off - - Off Operation OV1 Off / On
On
Table continues on next page

460
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection

Name Values (Range) Unit Step Default Description


StartVolt_OV1 2.0 - 200.0 %UB 0.1 150.0 Operate voltage level for OV1 in % of
Ubase
CurveType_OV1 Definite time - - Definite time Selection of time delay curve type for OV1
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
tDef_OV1 0.00 - 6000.00 s 0.01 1.00 Operate time delay in sec for definite
time use of OV1
tMin_OV1 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IDMT curves
for OV1
k_OV1 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent time
delay for OV1
Operation_OV2 Off - - Off Operation OV2 Off / On
On
StartVolt_OV2 2.0 - 200.0 %UB 0.1 150.0 Operate voltage level for OV2 in % of
Ubase
CurveType_OV2 Definite time - - Definite time Selection of time delay curve type for OV2
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
tDef_OV2 0.00 - 6000.00 s 0.01 1.00 Operate time delay in sec for definite
time use of OV2
tMin_OV2 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IDMT curves
for OV2
k_OV2 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent time
delay for OV2
Operation_UV1 Off - - Off Operation UV1 Off / On
On
StartVolt_UV1 2.0 - 150.0 %UB 0.1 50.0 Operate undervoltage level for UV1 in %
of Ubase
CurveType_UV1 Definite time - - Definite time Selection of time delay curve type for UV1
Inverse curve A
Inverse curve B
Prog. inv. curve
tDef_UV1 0.00 - 6000.00 s 0.01 1.00 Operate time delay in sec for definite
time use of UV1
tMin_UV1 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IDMT curves
for UV1
k_UV1 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent time
delay for UV1
EnBlkLowV_UV1 Off - - On Enable internal low voltage level
On blocking for UV1
BlkLowVolt_UV1 0.0 - 5.0 %UB 0.1 0.5 Internal low voltage blocking level for
UV1 in % of Ubase
Operation_UV2 Off - - Off Operation UV2 Off / On
On
StartVolt_UV2 2.0 - 150.0 %UB 0.1 50.0 Operate undervoltage level for UV2 in %
of Ubase
Table continues on next page

461
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection

Name Values (Range) Unit Step Default Description


CurveType_UV2 Definite time - - Definite time Selection of time delay curve type for UV2
Inverse curve A
Inverse curve B
Prog. inv. curve
tDef_UV2 0.00 - 6000.00 s 0.01 1.00 Operate time delay in sec for definite
time use of UV2
tMin_UV2 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IDMT curves
for UV2
k_UV2 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent time
delay for UV2
EnBlkLowV_UV2 Off - - On Enable internal low voltage level
On blocking for UV2
BlkLowVolt_UV2 0.0 - 5.0 %UB 0.1 0.5 Internal low voltage blocking level for
UV2 in % of Ubase

Table 278: CVGAPC Group settings (advanced)


Name Values (Range) Unit Step Default Description
CurrMult_OC1 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting
value for OC1
ResCrvType_OC1 Instantaneous - - Instantaneous Selection of reset curve type for OC1
IEC Reset
ANSI reset
tResetDef_OC1 0.00 - 6000.00 s 0.01 0.00 Reset time delay used in IEC Definite
Time curve OC1
P_OC1 0.001 - 10.000 - 0.001 0.020 Parameter P for customer programmable
curve for OC1
A_OC1 0.000 - 999.000 - 0.001 0.140 Parameter A for customer programmable
curve for OC1
B_OC1 0.000 - 99.000 - 0.001 0.000 Parameter B for customer programmable
curve for OC1
C_OC1 0.000 - 1.000 - 0.001 1.000 Parameter C for customer
programmable curve for OC1
PR_OC1 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for OC1
TR_OC1 0.005 - 600.000 - 0.001 13.500 Parameter TR for customer
programmable curve for OC1
CR_OC1 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for OC1
CurrMult_OC2 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting
value for OC2
ResCrvType_OC2 Instantaneous - - Instantaneous Selection of reset curve type for OC2
IEC Reset
ANSI reset
tResetDef_OC2 0.00 - 6000.00 s 0.01 0.00 Reset time delay used in IEC Definite
Time curve OC2
P_OC2 0.001 - 10.000 - 0.001 0.020 Parameter P for customer programmable
curve for OC2
A_OC2 0.000 - 999.000 - 0.001 0.140 Parameter A for customer programmable
curve for OC2
Table continues on next page

462
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection

Name Values (Range) Unit Step Default Description


B_OC2 0.000 - 99.000 - 0.001 0.000 Parameter B for customer programmable
curve for OC2
C_OC2 0.000 - 1.000 - 0.001 1.000 Parameter C for customer
programmable curve for OC2
PR_OC2 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for OC2
TR_OC2 0.005 - 600.000 - 0.001 13.500 Parameter TR for customer
programmable curve for OC2
CR_OC2 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for OC2
tResetDef_UC2 0.00 - 6000.00 s 0.01 0.00 Reset time delay used in IEC Definite
Time curve UC2
ResCrvType_OV1 Instantaneous - - Instantaneous Selection of reset curve type for OV1
Frozen timer
Linearly decreased
tResetDef_OV1 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for definite time
use of OV1
tResetIDMT_OV1 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for IDMT curves
for OV1
A_OV1 0.005 - 999.000 - 0.001 0.140 Parameter A for customer programmable
curve for OV1
B_OV1 0.500 - 99.000 - 0.001 1.000 Parameter B for customer programmable
curve for OV1
C_OV1 0.000 - 1.000 - 0.001 1.000 Parameter C for customer
programmable curve for OV1
D_OV1 0.000 - 10.000 - 0.001 0.000 Parameter D for customer
programmable curve for OV1
P_OV1 0.001 - 10.000 - 0.001 0.020 Parameter P for customer programmable
curve for OV1
ResCrvType_OV2 Instantaneous - - Instantaneous Selection of reset curve type for OV2
Frozen timer
Linearly decreased
tResetDef_OV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for definite time
use of OV2
tResetIDMT_OV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for IDMT curves
for OV2
A_OV2 0.005 - 999.000 - 0.001 0.140 Parameter A for customer programmable
curve for OV2
B_OV2 0.500 - 99.000 - 0.001 1.000 Parameter B for customer programmable
curve for OV2
C_OV2 0.000 - 1.000 - 0.001 1.000 Parameter C for customer
programmable curve for OV2
D_OV2 0.000 - 10.000 - 0.001 0.000 Parameter D for customer
programmable curve for OV2
P_OV2 0.001 - 10.000 - 0.001 0.020 Parameter P for customer programmable
curve for OV2
ResCrvType_UV1 Instantaneous - - Instantaneous Selection of reset curve type for UV1
Frozen timer
Linearly decreased
Table continues on next page

463
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection

Name Values (Range) Unit Step Default Description


tResetDef_UV1 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for definite time
use of UV1
tResetIDMT_UV1 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for IDMT curves
for UV1
A_UV1 0.005 - 999.000 - 0.001 0.140 Parameter A for customer programmable
curve for UV1
B_UV1 0.500 - 99.000 - 0.001 1.000 Parameter B for customer programmable
curve for UV1
C_UV1 0.000 - 1.000 - 0.001 1.000 Parameter C for customer
programmable curve for UV1
D_UV1 0.000 - 10.000 - 0.001 0.000 Parameter D for customer
programmable curve for UV1
P_UV1 0.001 - 10.000 - 0.001 0.020 Parameter P for customer programmable
curve for UV1
ResCrvType_UV2 Instantaneous - - Instantaneous Selection of reset curve type for UV2
Frozen timer
Linearly decreased
tResetDef_UV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for definite time
use of UV2
tResetIDMT_UV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for IDMT curves
for UV2
A_UV2 0.005 - 999.000 - 0.001 0.140 Parameter A for customer programmable
curve for UV2
B_UV2 0.500 - 99.000 - 0.001 1.000 Parameter B for customer programmable
curve for UV2
C_UV2 0.000 - 1.000 - 0.001 1.000 Parameter C for customer
programmable curve for UV2
D_UV2 0.000 - 10.000 - 0.001 0.000 Parameter D for customer
programmable curve for UV2
P_UV2 0.001 - 10.000 - 0.001 0.020 Parameter P for customer programmable
curve for UV2

10.1.6 Technical data


Table 279: CVGAPC technical data
Function Range or value Accuracy
Measuring current phase1, phase2, phase3, PosSeq, -
input NegSeq, 3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2, phase2-
phase3, phase3-phase1, MaxPh-Ph,
MinPh-Ph, UnbalancePh-Ph
Base current (1 - 99999) A -
Measuring voltage phase1, phase2, phase3, PosSeq, - -
input NegSeq, -3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2, phase2-
phase3, phase3-phase1, MaxPh-Ph,
MinPh-Ph, UnbalancePh-Ph
Base voltage (0.05 - 2000.00) kV -
Table continues on next page

464
Technical reference manual
1MRK505183-UEN C Section 10
Multipurpose protection

Function Range or value Accuracy


Start overcurrent, (2 - 5000)% of IBase ± 1.0% of Ir for I<Ir
step 1 and 2 ± 1.0% of I for I>Ir

Start undercurrent, (2 - 150)% of IBase ± 1.0% of Ir for I<Ir


step 1 and 2 ± 1.0% of I for I>Ir

Definite time delay (0.00 - 6000.00) s ± 0.5% ± 10 ms


Operate time start 25 ms typically at 0 to 2 x Iset -
overcurrent
Reset time start 25 ms typically at 2 to 0 x Iset -
overcurrent
Operate time start 25 ms typically at 2 to 0 x Iset -
undercurrent
Reset time start 25 ms typically at 0 to 2 x Iset -
undercurrent
See table 644 and Parameter ranges for customer defined See table 644 and table 645
table 645 characteristic no 17:
k: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0
Voltage level where (0.0 - 5.0)% of UBase ± 1.0% of Ur
voltage memory
takes over
Start overvoltage, (2.0 - 200.0)% of UBase ± 1.0% of Ur for U<Ur
step 1 and 2 ± 1.0% of U for U>Ur

Start undervoltage, (2.0 - 150.0)% of UBase ± 1.0% of Ur for U<Ur


step 1 and 2 ± 1.0% of U for U>Ur

Operate time, start 25 ms typically at 0 to 2 x Uset -


overvoltage
Reset time, start 25 ms typically at 2 to 0 x Uset -
overvoltage
Operate time start 25 ms typically 2 to 0 x Uset -
undervoltage
Reset time start 25 ms typically at 0 to 2 x Uset -
undervoltage
High and low voltage (1.0 - 200.0)% of UBase ± 1.0% of Ur for U<Ur
limit, voltage ± 1.0% of U for U>Ur
dependent operation
Directional function Settable: NonDir, forward and reverse -
Relay characteristic (-180 to +180) degrees ± 2.0 degrees
angle
Relay operate angle (1 to 90) degrees ± 2.0 degrees
Reset ratio, > 95% -
overcurrent
Reset ratio, < 105% -
undercurrent
Table continues on next page

465
Technical reference manual
Section 10 1MRK505183-UEN C
Multipurpose protection

Function Range or value Accuracy


Reset ratio, > 95% -
overvoltage
Reset ratio, < 105% -
undervoltage
Overcurrent:
Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -


Undercurrent:
Critical impulse time 10 ms typically at 2 to 0 x Iset -

Impulse margin time 15 ms typically -


Overvoltage:
Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -


Undervoltage:
Critical impulse time 10 ms typically at 2 to 0 x Uset -

Impulse margin time 15 ms typically -

466
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision

Section 11 Secondary system supervision

About this chapter


This chapter describes functions like Current circuit supervision and Fuse failure
supervision. The way the functions work, their setting parameters, function blocks,
input and output signals and technical data are included for each function.

11.1 Current circuit supervision CCSRDIF

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Current circuit supervision CCSRDIF - 87

11.1.1 Introduction
Open or short circuited current transformer cores can cause unwanted operation of
many protection functions such as differential, earth-fault current and negative-
sequence current functions.

It must be remembered that a blocking of protection functions at an occurrence of


open CT circuit will mean that the situation will remain and extremely high
voltages will stress the secondary circuit.

Current circuit supervision (CCSRDIF) compares the residual current from a three
phase set of current transformer cores with the neutral point current on a separate
input taken from another set of cores on the current transformer.

A detection of a difference indicates a fault in the circuit and is used as alarm or to


block protection functions expected to give unwanted tripping.

11.1.2 Principle of operation


Current circuit supervision CCSRDIF compares the absolute value of the vectorial
sum of the three phase currents |ΣIphase| and the numerical value of the residual
current |Iref| from another current transformer set, see figure 255.

The FAIL output will be set to a logical one when the following criteria are fulfilled:

467
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision

• The numerical value of the difference |ΣIphase| – |Iref| is higher than 80% of
the numerical value of the sum |ΣIphase| + |Iref|.
• The numerical value of the current |ΣIphase| – |Iref| is equal to or higher than
the set operate value IMinOp.
• No phase current has exceeded Ip>Block during the last 10 ms.
• CCSRDIF is enabled by setting Operation = On.

The FAIL output remains activated 100 ms after the AND-gate resets when being
activated for more than 20 ms. If the FAIL lasts for more than 150 ms an ALARM
will be issued. In this case the FAIL and ALARM will remain activated 1 s after
the AND-gate resets. This prevents unwanted resetting of the blocking function
when phase current supervision element(s) operate, for example, during a fault.

IEC05000463 V1 EN

Figure 255: Simplified logic diagram for Current circuit supervision CCSRDIF

The operate characteristic is percentage restrained, see figure 256.

468
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision

| åI phase | - | I ref |

Slope = 1

Operation
Slope = 0.8
area
I MinOp

| åI phase | + | I ref |
99000068.vsd

IEC99000068 V1 EN

Figure 256: Operate characteristics

Due to the formulas for the axis compared, |SIphase | - |I ref | and |S
I phase | + | I ref | respectively, the slope can not be above 2.

11.1.3 Function block


CCSRDIF
I3P* FAIL
IREF* ALARM
BLOCK

IEC05000389-2-en.vsd
IEC05000389 V2 EN

Figure 257: CCSRDIF function block

11.1.4 Input and output signals


Table 280: CCSRDIF Input signals
Name Type Default Description
I3P GROUP - Group signal for three phase current input
SIGNAL
IREF GROUP - TBD
SIGNAL
BLOCK BOOLEAN 0 Block of function

469
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision

Table 281: CCSRDIF Output signals


Name Type Description
FAIL BOOLEAN Detection of current circuit failure
ALARM BOOLEAN Alarm for current circuit failure

11.1.5 Setting parameters


Table 282: CCSRDIF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IBase 1 - 99999 A 1 3000 IBase value for current level detectors
IMinOp 5 - 200 %IB 1 20 Minimum operate current differential
level in % of IBase

Table 283: CCSRDIF Group settings (advanced)


Name Values (Range) Unit Step Default Description
Ip>Block 5 - 500 %IB 1 150 Block of the function at high phase
current, in % of IBase

11.1.6 Technical data


Table 284: CCSRDIF technical data
Function Range or value Accuracy
Operate current (5-200)% of Ir ± 10.0% of Ir at I £ Ir
± 10.0% of I at I > Ir

Block current (5-500)% of Ir ± 5.0% of Ir at I £ Ir


± 5.0% of I at I > Ir

11.2 Fuse failure supervision SDDRFUF

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Fuse failure supervision SDDRFUF - -

11.2.1 Introduction
The aim of the fuse failure supervision function (SDDRFUF) is to block voltage
measuring functions at failures in the secondary circuits between the voltage

470
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision

transformer and the IED in order to avoid unwanted operations that otherwise
might occur.

The fuse failure supervision function basically has two different algorithms,
negative sequence and zero sequence based algorithm and an additional delta
voltage and delta current algorithm.

The negative sequence detection algorithm is recommended for IEDs used in


isolated or high-impedance earthed networks. It is based on the negative-sequence
measuring quantities, a high value of voltage 3U2 without the presence of the
negative-sequence current 3I2.

The zero sequence detection algorithm is recommended for IEDs used in directly
or low impedance earthed networks. It is based on the zero sequence measuring
quantities, a high value of voltage 3U0 without the presence of the residual current
3I0.

A criterion based on delta current and delta voltage measurements can be added to
the fuse failure supervision function in order to detect a three phase fuse failure,
which in practice is more associated with voltage transformer switching during
station operations.

For better adaptation to system requirements, an operation mode setting has been
introduced which makes it possible to select the operating conditions for negative
sequence and zero sequence based function. The selection of different operation
modes makes it possible to choose different interaction possibilities between the
negative sequence and zero sequence based algorithm.

11.2.2 Principle of operation

11.2.2.1 Zero and negative sequence detection

The zero and negative sequence function continuously measures the currents and
voltages in all three phases and calculates, see figure 258:

• the zero-sequence voltage 3U0


• the zero-sequence current 3I0
• the negative sequence current 3I2
• the negative sequence voltage 3U2

The measured signals are compared with their respective set values 3U0< and
3I0>, 3U2< and 3I2>.

The function enable the internal signal FuseFailDetZeroSeq if the measured zero-
sequence voltage is higher than the set value 3U0> and the measured zero-
sequence current is below the set value 3I0<.

471
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision

The function enable the internal signal FuseFailDetNegSeq if the measured


negative sequence voltage is higher than the set value 3U2> and the measured
negative sequence current is below the set value 3I2<.

A drop off delay of 100 ms for the measured zero-sequence and negative sequence
current will prevent a false fuse failure detection at un-equal breaker opening at the
two line ends.

Sequence Detection
3I0< CurrZeroSeq
IL1
Zero 3I0
sequence
filter 100 ms CurrNegSeq
a
IL2 a>b t
b
Negative 3I2
sequence
IL3 filter FuseFailDetZeroSeq
AND
100 ms
a
a>b t
3I2< b
FuseFailDetNegSeq
AND
3U0>
VoltZeroSeq
UL1
Zero
sequence a 3U0
a>b
b
filter
UL2 VoltNegSeq

Negative
sequence a 3U2
a>b
UL3 filter b

3U2>

IEC10000036-1-en.vsd
IEC10000036 V1 EN

Figure 258: Simplified logic diagram for sequence detection part

The calculated values 3U0, 3I0, 3I2 and 3U2 are available as service values on local
HMI and monitoring tool in PCM600.

Input and output signals


The output signals 3PH, BLKU and BLKZ can be blocked in the following conditions:

• The input BLOCK is activated


• The input BLKTRIP is activated at the same time as the internal signal
fufailStarted is not present
• The operation mode selector OpMode is set to Off.
• The IED is in TEST status (TEST-ACTIVE is high) and the function has been
blocked from the HMI (BlockFUSE=Yes)

The input BLOCK signal is a general purpose blocking signal of the fuse failure
supervision function. It can be connected to a binary input of the IED in order to
receive a block command from external devices or can be software connected to
other internal functions of the IED itself in order to receive a block command from

472
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision

internal functions. Through OR gate it can be connected to both binary inputs and
internal function outputs.

The input BLKSP is intended to be connected to the trip output at any of the
protection functions included in the IED. When activated for more than 20 ms, the
operation of the fuse failure is blocked during a fixed time of 100 ms. The aim is to
increase the security against unwanted operations during the opening of the
breaker, which might cause unbalance conditions for which the fuse failure might
operate.

The output signal BLKZ will also be blocked if the internal dead line detection is
activated. The block signal has a 200 ms drop-off time delay.

The input signal MCBOP is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the miniature circuit breaker protecting the VT
secondary circuit. The MCBOP signal sets the output signals BLKU and BLKZ in
order to block all the voltage related functions when the MCB is open independent
of the setting of OpMode selector. The additional drop-off timer of 150 ms
prolongs the presence of MCBOP signal to prevent the unwanted operation of
voltage dependent function due to non simultaneous closing of the main contacts of
the miniature circuit breaker.

The input signal DISCPOS is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the line disconnector. The DISCPOS signal sets the
output signal BLKU in order to block the voltage related functions when the line
disconnector is open. The impedance protection function is not affected by the
position of the line disconnector since there will be no line currents that can cause
maloperation of the distance protection. If DISCPOS=0 it signifies that the line is
connected to the system and when the DISCPOS=1 it signifies that the line is
disconnected from the system and the block signal BLKU is generated.

The output BLKU can be used for blocking the voltage related measuring functions
(undervoltage protection, synchro-check etc.) except for the impedance protection.

The function output BLKZ can be used for blocking the impedance protection
function.

The BLKZ will only be activated if not the internal dead line detection is activated
at the same time.

The fuse failure condition is unlatched when the normal voltage conditions are
restored.

When the output 3PH is activated, all three voltage are low.

11.2.2.2 Delta current and delta voltage detection

A simplified diagram for the functionality is found in figure 259. The calculation of
the change is based on vector change which means that it detects both amplitude
and phase angle changes. The calculated delta quantities are compared with their

473
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision

respective set values DI< and DU> and the algorithm, detects a fuse failure if a
sufficient change in voltage without a sufficient change in current is detected in
each phase separately. The following quantities are calculated in all three phases:

• The change in voltage DU


• The change in current DI

The internal FuseFailDetDUDI signal is activated if the following conditions are


fulfilled for a phase:

• The magnitude of the phase-ground voltage has been above UPh> for more
than 1.5 cycle
• The magnitude of DU is higher than the corresponding setting DU>
• The magnitude of DI is below the setting DI>

and at least one of the following conditions are fulfilled:

• The magnitude of the phase current in the same phase is higher than the setting
IPh>
• The circuit breaker is closed (CBCLOSED = True)

The first criterion means that detection of failure in one phase together with high
current for the same phase will set the output. The measured phase current is used
to reduce the risk of false fuse failure detection. If the current on the protected line
is low, a voltage drop in the system (not caused by fuse failure) is not by certain
followed by current change and a false fuse failure might occur

The second criterion requires that the delta condition shall be fulfilled in any phase
at the same time as circuit breaker is closed. Opening circuit breaker at one end and
energizing the line from other end onto a fault could lead to wrong start of the fuse
failure function at the end with the open breaker. If this is considering to be an
important disadvantage, connect the CBCLOSED input to FALSE. In this way
only the first criterion can activate the delta function.

474
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision

DUDI Detection
DUDI detection Phase 1
IL1 One cycle
delay
|DI|
a
a>b
DI< b

UL1 One cycle


delay
|DU|
a
a>b AND
DU> b

20 ms 1.5 cycle
a
a>b t t
UPh> b

IL2 DUDI detection Phase 2


UL2

Same logic as for phase 1

IL3 DUDI detection Phase 3


UL3

Same logic as for phase 1

UL1
a
a<b
b

IL1
a
a>b
IPh> b AND

OR AND
CBCLOSED AND OR

UL2
a
a<b
b

IL2
a
a>b
b AND

OR AND
AND OR

UL3
a
a<b
b

IL3
a
a>b
b AND

OR AND FuseFailDetDUDI
AND OR
OR

IEC10000034-1-en.vsd
IEC10000034 V1 EN

Figure 259: Simplified logic diagram for DU/DI detection part

475
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision

11.2.2.3 Dead line detection

A simplified diagram for the functionality is found in figure 260. A dead phase
condition is indicated if both the voltage and the current in one phase is below their
respective setting values UDLD< and IDLD<. If at least one phase is considered to
be dead the output DLD1PH and the internal signal DeadLineDet1Ph is activated.
If all three phases are considered to be dead the output DLD3PH is activated

Dead Line Detection


IL1
a
a<b AllCurrLow
b
AND
IL2
a
a<b
b

IL3
a
a<b
b

IDLD<
DeadLineDet1Ph
UL1
a AND
a<b
b OR DLD1PH
AND
UL2
a AND
a<b
b
AND DLD3PH
UL3 AND
a AND
a<b
b

UDLD<

intBlock

IEC10000035-1-en.vsd
IEC10000035 V1 EN

Figure 260: Simplified logic diagram for Dead Line detection part

11.2.2.4 Main logic

A simplified diagram for the functionality is found in figure 261. The fuse failure
supervision function (SDDRFUF) can be switched on or off by the setting
parameter Operation to On or Off.

For increased flexibility and adaptation to system requirements an operation mode


selector, OpMode, has been introduced to make it possible to select different
operating modes for the negative and zero sequence based algorithms. The
different operation modes are:

• Off; The negative and zero sequence function is switched off


• UNsINs; Negative sequence is selected
• UZsIZs; Zero sequence is selected

476
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision

• UZsIZsORUNsINs; Both negative and zero sequence is activated and working


in parallel in an OR-condition
• UZsIZs AND UNsINs; Both negative and zero sequence is activated and
working in series (AND-condition for operation)
• OptimZsNs; Optimum of negative and zero sequence (the function that has the
highest magnitude of measured negative and zero sequence current will be
activated)

The delta function can be activated by setting the parameter OpDUDI to On. When
selected it operates in parallel with the sequence based algorithms.

As soon as any fuse failure situation is detected, signals FuseFailDetZeroSeq,


FuseFailDetNegSeq or FuseFailDetDUDI, and the specific functionality is
released, the function will activate the output signal BLKU. The output signal
BLKZ will be activated as well if not the internal dead phase detection,
DeadLineDet1Ph, is activated at the same time. The output BLKU can be used for
blocking voltage related measuring functions (under voltage protection, synchro-
check, and so on). For blocking of impedance protection functions output BLKZ
shall be used.

If the fuse failure situation is present for more than 5 seconds and the setting
parameter SealIn is set to On it will be sealed in over under-voltage as long as at
least one phase voltages is below the set value USealIn<. This will keep the BLKU
and BLKZ signals activated as long as any phase voltage is below the set value
USealIn<. If all three phase voltages drop below the set value USealIn< and the
setting parameter SealIn is set to On also the output signal 3PH will be activated.
The signals 3PH, BLKU and BLKZ signals will now be active as long as any phase
voltage is below the set value USealIn<.

If SealIn is set to On fuse failure condition is stored in the non volatile memory in
the IED. At start-up (due to auxiliary power interruption or re-start due to
configuration change) the IED checks the stored value in its non volatile memory
and re-establishes the conditions present before the shut down. All phase voltages
must became above USealIn< before fuse failure is de-activated and inhibits the
block of different protection functions.

The output signal BLKU will also be active if all phase voltages have been above
the setting USealIn< for more than 60 seconds, the zero or negative sequence
voltage has been above the set value 3U0> and 3U2> for more than 5 seconds, all
phase currents are below the setting IDLD< (operate level for dead line detection)
and the circuit breaker is closed (input CBCLOSED is activated).

The input signal MCBOP is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the miniature circuit breaker protecting the VT
secondary circuit. The MCBOP signal sets the output signals BLKU and BLKZ in
order to block all the voltage related functions when the MCB is open independent
of the setting of OpMode or OpDUDI. An additional drop-out timer of 150 ms
prolongs the presence of MCBOP signal to prevent the unwanted operation of

477
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision

voltage dependent function due to non simultaneous closing of the main contacts of
the miniature circuit breaker.

The input signal DISCPOS is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the line disconnector. The DISCPOS signal sets the
output signal BLKU in order to block the voltage related functions when the line
disconnector is open. The impedance protection function does not have to be
affected since there will be no line currents that can cause malfunction of the
distance protection.

The output signals 3PH, BLKU and BLKZ as well as the signals DLD1PH and
DLD3PH from dead line detections are blocked if any of the following conditions
occur:

• The operation mode selector OpMode is set to Off


• The input BLOCK is activated
• The IED is in TEST status (TEST-ACTIVE is high) and the function has been
blocked from the HMI (BlockFUSE=Yes)

The input BLOCK is a general purpose blocking signal of the fuse failure
supervision function. It can be connected to a binary input of the IED in order to
receive a block command from external devices or can be software connected to
other internal functions of the IED. Through OR gate it can be connected to both
binary inputs and internal function outputs.

The input BLKTRIP is intended to be connected to the trip output of any of the
protection functions included in the IED and/or trip from external equipments via
binary inputs. When activated for more than 20 ms without any fuse fail detected,
the operation of the fuse failure is blocked during a fixed time of 100 ms. The aim
is to increase the security against unwanted operations during the opening of the
breaker, which might cause unbalance conditions for which the fuse failure might
operate.

478
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision

Fuse failure detection


Main logic
TEST

TEST ACTIVE
AND
BlocFuse = Yes

BLOCK intBlock
OR
BLKTRIP 20 ms 100 ms
AND t t

All UL < USealIn<


OR
AND
3PH
AND
SealIn = On AND

AND
Any UL < UsealIn<

FuseFailDetDUDI
AND 5s
OpDUDI = On
OR t
FuseFailDetZeroSeq
AND

AND

FuseFailDetNegSeq
AND

UNsINs OR
UZsIZs OR
UZsIZs OR UNsINs
OpMode
UZsIZs AND UNsINs
OptimZsNs
OR
CurrZeroSeq
a AND
CurrNegSeq a>b
b

AND

200 ms
DeadLineDet1Ph AND BLKZ
t OR AND
150 ms
MCBOP t

AND BLKU
60 sec
t OR OR
All UL > UsealIn<
AND

VoltZeroSeq 5 sec
VoltNegSeq OR t

AllCurrLow
CBCLOSED

DISCPOS

IEC10000033-1-en.vsd
IEC10000033 V1 EN

Figure 261: Simplified logic diagram for fuse failure supervision function, Main
logic

479
Technical reference manual
Section 11 1MRK505183-UEN C
Secondary system supervision

11.2.3 Function block


SDDRFUF
I3P* BLKZ
U3P* BLKU
BLOCK 3PH
CBCLOSED DLD1PH
MCBOP DLD3PH
DISCPOS
BLKTRIP

IEC05000700-2-en.vsd
IEC05000700 V3 EN

Figure 262: SDDRFUF function block

11.2.4 Input and output signals


Table 285: SDDRFUF Input signals
Name Type Default Description
I3P GROUP - Current connection
SIGNAL
U3P GROUP - Voltage connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
CBCLOSED BOOLEAN 0 Active when circuit breaker is closed
MCBOP BOOLEAN 0 Active when external MCB opens protected
voltage circuit
DISCPOS BOOLEAN 0 Active when line disconnector is open
BLKTRIP BOOLEAN 0 Blocks operation of function when active

Table 286: SDDRFUF Output signals


Name Type Description
BLKZ BOOLEAN Start of current and voltage controlled function
BLKU BOOLEAN General start of function
3PH BOOLEAN Three-phase start of function
DLD1PH BOOLEAN Dead line condition in at least one phase
DLD3PH BOOLEAN Dead line condition in all three phases

11.2.5 Setting parameters


Table 287: SDDRFUF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
Table continues on next page

480
Technical reference manual
1MRK505183-UEN C Section 11
Secondary system supervision

Name Values (Range) Unit Step Default Description


OpMode Off - - UZsIZs Operating mode selection
UNsINs
UZsIZs
UZsIZs OR UNsINs
UZsIZs AND
UNsINs
OptimZsNs
3U0> 1 - 100 %UB 1 30 Operate level of residual overvoltage
element in % of UBase
3I0< 1 - 100 %IB 1 10 Operate level of residual undercurrent
element in % of IBase
3U2> 1 - 100 %UB 1 30 Operate level of neg seq overvoltage
element in % of UBase
3I2< 1 - 100 %IB 1 10 Operate level of neg seq undercurrent
element in % of IBase
OpDUDI Off - - Off Operation of change based function Off/
On On
DU> 1 - 100 %UB 1 60 Operate level of change in phase voltage
in % of UBase
DI< 1 - 100 %IB 1 15 Operate level of change in phase current
in % of IBase
UPh> 1 - 100 %UB 1 70 Operate level of phase voltage in % of
UBase
IPh> 1 - 100 %IB 1 10 Operate level of phase current in % of
IBase
SealIn Off - - On Seal in functionality Off/On
On
USealln< 1 - 100 %UB 1 70 Operate level of seal-in phase voltage in
% of UBase
IDLD< 1 - 100 %IB 1 5 Operate level for open phase current
detection in % of IBase
UDLD< 1 - 100 %UB 1 60 Operate level for open phase voltage
detection in % of UBase

11.2.6 Technical data


Table 288: SDDRFUF technical data
Function Range or value Accuracy
Operate voltage, zero sequence (1-100)% of UBase ± 1.0% of Ur

Operate current, zero sequence (1–100)% of IBase ± 1.0% of Ir

Operate voltage, negative sequence (1–100)% of UBase ± 1.0% of Ur

Operate current, negative sequence (1–100)% of IBase ± 1.0% of Ir

Operate voltage change level (1–100)% of UBase ± 5.0% of Ur

Operate current change level (1–100)% of IBase ± 5.0% of Ir

481
Technical reference manual
482
1MRK505183-UEN C Section 12
Control

Section 12 Control

About this chapter


This chapter describes the control functions. The way the functions work, their
setting parameters, function blocks, input and output signals and technical data are
included for each function.

12.1 Synchrocheck, energizing check, and synchronizing


SESRSYN

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Synchrocheck, energizing check, and SESRSYN 25
synchronizing
sc/vc

SYMBOL-M V1 EN

12.1.1 Introduction
The Synchronizing function allows closing of asynchronous networks at the correct
moment including the breaker closing time. The systems can thus be reconnected
after an autoreclose or manual closing, which improves the network stability.

Synchrocheck, energizing check (SESRSYN) function checks that the voltages on


both sides of the circuit breaker are in synchronism, or with at least one side dead
to ensure that closing can be done safely.

SESRSYN function includes a built-in voltage selection scheme for double bus and
1½ breaker or ring busbar arrangements.

Manual closing as well as automatic reclosing can be checked by the function and
can have different settings.

For systems which are running asynchronous a synchronizing function is provided.


The main purpose of the synchronizing function is to provide controlled closing of
circuit breakers when two asynchronous systems are going to be connected. It is
used for slip frequencies that are larger than those for synchrocheck and lower than
a set maximum level for the synchronizing function.

483
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.1.2 Principle of operation

12.1.2.1 Basic functionality

The synchrocheck function measures the conditions across the circuit breaker and
compares them to set limits. The output is only given when all measured quantities
are simultaneously within their set limits.

The energizing check function measures the bus and line voltages and compares
them to both high and low threshold detectors. The output is given only when the
actual measured quantities match the set conditions.

The synchronizing function measures the conditions across the circuit breaker, and
also determines the angle change occurring during the closing delay of the circuit
breaker, from the measured slip frequency. The output is given only when all
measured conditions are simultaneously within their set limits. The issue of the
output is timed to give closure at the optimal time including the time for the circuit
breaker and the closing circuit.

For single circuit breaker and 1½ breaker circuit breaker arrangements, the
SESRSYN function blocks have the capability to make the necessary voltage
selection. For single circuit breaker arrangements, selection of the correct voltage
is made using auxiliary contacts of the bus disconnectors. For 1½ breaker circuit
breaker arrangements, correct voltage selection is made using auxiliary contacts of
the bus disconnectors as well as the circuit breakers.

The internal logic for each function block as well as, the input and outputs, and the
setting parameters with default setting and setting ranges is described in this
document. For application related information, please refer to the application manual.

12.1.2.2 Logic diagrams

Logic diagrams
The logic diagrams that follow illustrate the main principles of the synchronizing
function components such as Synchrocheck, Energizing check and Voltage
selection, and are intended to simplify the understanding of the function.

Synchrocheck
The voltage difference, frequency difference and phase angle difference values are
measured in the IED centrally and are available for the synchrocheck function for
evaluation. If the bus voltage is connected as phase-phase and the line voltage as
phase-neutral (or the opposite), this need to be compensated. This is done with a
setting, which scales up the line voltage to a level equal to the bus voltage.

When the function is set to OperationSC = On, the measuring will start.

The function will compare the bus and line voltage values with the set values for
UHighBusSC and UHighLineSC.

484
Technical reference manual
1MRK505183-UEN C Section 12
Control

If both sides are higher than the set values, the measured values are compared with
the set values for acceptable frequency, phase angle and voltage difference:
FreqDiff, PhaseDiff and UDiff. If a compensation factor is set due to the use of
different voltages on the bus and line, the factor is deducted from the line voltage
before the comparison of the phase angle values.

The frequency on both sides of the circuit breaker is also measured. The
frequencies must not deviate from the rated frequency more than +/-5Hz. The
frequency difference between the bus frequency and the line frequency is measured
and may not exceed the set value.

Two sets of settings for frequency difference and phase angle difference are
available and used for the manual closing and autoreclose functions respectively, as
required.

The inputs BLOCK and BLKSC are available for total block of the complete
Synchrocheck function and block of the Synchrocheck function respectively. Input
TSTSC will allow testing of the function where the fulfilled conditions are
connected to a separate test output.

The outputs MANSYOK and AUTOSYOK are activated when the actual measured
conditions match the set conditions for the respective output. The output signal can
be delayed independently for MANSYOK and AUTOSYOK conditions.

A number of outputs are available as information about fulfilled checking


conditions. UOKSC shows that the voltages are high, UDIFFSC, FRDIFFA,
FRDIFFM, PHDIFFA, PHDIFFM shows when the voltage difference, frequency
difference and phase angle difference conditions are met.

485
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Note! Similar logic for Manual Synchrocheck.

OperationSC = On
AND TSTAUTSY
AND

TSTSC

BLKSC AND
BLOCK OR
AUTOSYOK
AND
0-60 s
AND t
tSCA

UDiffSC 50 ms
AND t
UHighBusSC
UOKSC
AND
UHighLineSC
UDIFFSC
1
FRDIFFA
FreqDiffA 1

PHDIFFA
PhaseDiffA 1

UDIFFME
voltageDifferenceValue
FRDIFFME
frequencyDifferenceValue
PHDIFFME
phaseAngleDifferenceValue

IEC07000114-2-en.vsd
IEC07000114 V2 EN

Figure 263: Simplified logic diagram for the Synchrocheck function

Synchronizing
When the function is set to OperationSynch = On the measuring will be performed.

The function will compare the values for the bus and line voltage with the set
values for UHighBusSynch and UHighLineSynch, which is a supervision that the
voltages are both live. If both sides are higher than the set values the measured
values are compared with the set values for acceptable frequency, rate of change of
frequency, phase angle and voltage difference FreqDiffMax, FreqDiffMin and
UDiffSynch.

Measured frequencies between the settings for the maximum and minimum
frequency will initiate the measuring and the evaluation of the angle change to
allow operation to be sent in the right moment including the set tBreaker time.
There is a phase angle release internally to block any incorrect closing pulses. At
operation the SYNOK output will be activated with a pulse tClosePulse and the
function reset. The function will also reset if the synchronizing conditions are not
fulfilled within the set tMaxSynch time. This prevents that the functions are, by
mistake, maintained in operation for a long time, waiting for conditions to be fulfilled.

486
Technical reference manual
1MRK505183-UEN C Section 12
Control

The inputs BLOCK and BLKSYNCH are available for total block of the complete
function respective of the synchronizing part. TSTSYNCH will allow testing of the
function where the fulfilled conditions are connected to a separate output.

SYN1
OPERATION SYNCH
OFF
ON
TEST MODE
OFF
ON
STARTSYN SYNPROGR
AND
AND
S
BLKSYNCH
OR R

UDiffSynch
50 ms SYNOK
AND
UHighBusSynch AND t

UHighLineSynch OR

FreqDiffMax
AND
TSTSYNOK
FreqDiffMin OR

tClose
FreqRateChange Pulse
AND

fBus&fLine ± 5 Hz tMax
AND
Synch
PhaseDiff < 15 deg SYNFAIL

PhaseDiff=closing angle

IEC06000636-2-en.vsd
IEC06000636 V2 EN

Figure 264: Simplified logic diagram for the synchronizing function

Energizing check
Voltage values are measured in the IED centrally and are available for evaluation
by the Energizing check function. If the bus voltage is connected as phase-phase
and the line voltage as phase-neutral, (or the opposite) this needs to be
compensated. This is done with a setting, which scales the line voltage to a level
equal to the bus voltage.

The function measures voltages on the busbar and the line to verify whether they
are live or dead. This is done by comparing with the set values UHighBusEnerg
and ULowBusEnerg for bus energizing and UHighLineEnerg and ULowLineEnerg
for line energizing.

The frequency on both sides of the circuit breaker is also measured. The
frequencies must not deviate from the rated frequency more than +/-5Hz. The
frequency difference between the bus frequency and the line frequency is measured
and shall not exceed a set value.

487
Technical reference manual
Section 12 1MRK505183-UEN C
Control

The Energizing direction can be selected individually for the Manual and the
Automatic functions respectively. When the conditions are met the outputs
AUTOENOK and MANENOK respectively will be activated if the fuse
supervision conditions are fulfilled. The output signal can be delayed
independently for MANENOK and AUTOENOK conditions. The Energizing
direction can also be selected by an integer input AENMODE respective
MENMODE, which for example, can be connected to a Binary to Integer function
block (B16I). Integers supplied shall be 1=off, 2=DLLB, 3=DBLL and 4= Both.
Not connected input with connection of INTZERO output from Fixed Signals
(FIXDSIGN) function block will mean that the setting is done from Parameter
Setting tool. The active position can be read on outputs MODEAEN resp
MODEMEN. The modes are 0=OFF, 1=DLLB, 2=DBLL and 3=Both.

The inputs BLOCK and BLKENERG are available for total block of the complete
Synchronizing function respective block of the Energizing check function.
TSTENERG will allow testing of the function where the fulfilled conditions are
connected to a separate test output.

Voltage selection
The voltage selection module including supervision of included voltage
transformer fuses for the different arrangements is a basic part of the
Synchronizing function and determines the parameters fed to the Synchronizing,
Synchrocheck and Energizing check functions. This includes the selection of the
appropriate Line and Bus voltages and fuse supervision.

The voltage selection type to be used is set with the parameter CBConfig.

If No voltage sel. is set the default voltages used will be ULine1 and UBus1. This
is also the case when external voltage selection is provided. Fuse failure
supervision for the used inputs must also be connected.

The voltage selection function, selected voltages, and fuse conditions are the
Synchronizing, Synchrocheck and Energizing check inputs.

For the disconnector positions it is advisable to use (NO) a and (NC) b type
contacts to supply Disconnector Open and Closed positions but, it is also possible
to use an inverter for one of the positions.

Voltage selection for a single circuit breaker with double busbars


This function uses the binary input from the disconnectors auxiliary contacts
B1QOPEN-B1QCLD for Bus 1, and B2QOPEN-B2QCLD for Bus 2 to select
between bus 1 and bus 2 voltages. If the disconnector connected to bus 2 is closed
and the disconnector connected to bus 1 is opened the bus 2 voltage is used. All
other combinations use the bus 1 voltage. The Outputs B1SEL and B2SEL
respectively indicate the selected Bus voltage.

The function checks the fuse-failure signals for bus 1, bus 2 and line voltage
transformers. Inputs UB1OK-UB1FF supervise the fuse for Bus 1 and UB2OK-
UB2FF supervises the fuse for Bus 2. ULN1OK-ULN1FF supervises the fuse for
the Line voltage transformer. The inputs fail (FF) or healthy (OK) can alternatively

488
Technical reference manual
1MRK505183-UEN C Section 12
Control

be used dependent on the available signal. If a fuse-failure is detected in the


selected voltage source an output signal USELFAIL is set. This output signal is
true if the selected bus or line voltages have a fuse failure. This output as well as
the function can be blocked with the input signal BLOCK. The function logic
diagram is shown in figure 265.

B1QOPEN
B1SEL
B1QCLD AND

B2QOPEN B2SEL
1
B2QCLD AND

AND invalidSelection

bus1Voltage
busVoltage
bus2Voltage

UB1OK AND
UB1FF OR
OR
AND selectedFuseOK
UB2OK AND
UB2FF OR USELFAIL
AND

ULN1OK
ULN1FF OR

BLOCK

en05000779.vsd
IEC05000779 V1 EN

Figure 265: Logic diagram for the voltage selection function of a single circuit breaker with double busbars

Voltage selection for a 1 1/2 circuit breaker arrangement


Note that with 1½ breaker schemes two Synchrocheck functions must be used in
the IED (three for two IEDs in a complete bay). Below, the scheme for one Bus
breaker and the Tie breakers is described.

This voltage selection function uses the binary inputs from the disconnectors and
circuit breakers auxiliary contacts to select the right voltage for the Synchrocheck
(Synchronism and Energizing check) function. For the bus circuit breaker one side
of the circuit breaker is connected to the busbar and the other side is connected
either to line 1, line 2 or the other busbar depending on the arrangement.

Inputs LN1QOPEN-LN1QCLD, B1QOPEN-B1QCLD, B2QOPEN-B2QCLD,


LN2QOPEN-LN2QCLD are inputs for the position of the Line disconnectors

489
Technical reference manual
Section 12 1MRK505183-UEN C
Control

respectively the Bus and Tie breakers. The Outputs LN1SEL, LN2SEL and B2SEL
will give indication of the selected Line voltage as a reference to the fixed Bus 1
voltage.

The fuse supervision is connected to ULNOK-ULNFF, and with alternative


Healthy or Failing fuse signals depending on what is available for each of fuse (MCB).

The tie circuit breaker is connected either to bus 1 or line 1 on one side and the
other side is connected either to bus 2 or line 2. Four different output combinations
are possible, bus to bus, bus to line, line to bus and line to line.

• The line 1 voltage is selected if the line 1 disconnector is closed.


• The bus 1 voltage is selected if the line 1 disconnector is open and the bus 1
circuit breaker is closed.
• The line 2 voltage is selected if the line 2 disconnector is closed.
• The bus 2 voltage is selected if the line 2 disconnector is open and the bus 2
Circuit breaker is closed.

The function also checks the fuse-failure signals for bus 1, bus 2, line 1 and line 2.
If a fuse-failure is detected in the selected voltage an output signal USELFAIL is
set. This output signal is true if the selected bus or line voltages have a fuse failure.
This output as well as the function can be blocked with the input signal BLOCK.
The function block diagram for the voltage selection of a bus circuit breaker is
shown in figure 266 and for the tie circuit breaker in figure 267

490
Technical reference manual
1MRK505183-UEN C Section 12
Control

LN1QOPEN
AND
LN1SEL
LN1QCLD

B1QOPEN
LN2SEL
B1QCLD AND AND

OR
B2SEL
LN2QOPEN
LN2QCLD AND
AND invalidSelection
AND
B2QOPEN
B2QCLD AND

line1Voltage
lineVoltage
line2Voltage

bus2Voltage

UB1OK
UB1FF OR

OR
UB2OK AND
AND selectedFuseOK
UB2FF OR

USELFAIL
ULN1OK AND
AND
ULN1FF OR

ULN2OK
AND
ULN2FF OR

BLOCK

en05000780.vsd

IEC05000780 V1 EN

Figure 266: Simplified logic diagram for the voltage selection function for a bus circuit breaker in a 1 1/2
breaker arrangement

491
Technical reference manual
Section 12 1MRK505183-UEN C
Control

LN1QOPEN
LN1SEL
LN1QCLD AND
B1SEL
1

B1QOPEN AND
AND
B1QCLD AND

line1Voltage
busVoltage
bus1Voltage
LN2QOPEN
LN2SEL
LN2QCLD AND
B2SEL
1
OR invalidSelection
B2QOPEN AND
AND
B2QCLD AND

line2Voltage
lineVoltage
bus2Voltage

UB1OK AND
UB1FF OR

OR
UB2OK AND selectedFuseOK
AND
UB2FF OR

USELFAIL
ULN1OK AND
AND
ULN1FF OR

ULN2OK
AND
ULN2FF OR

BLOCK

en05000781.vsd

IEC05000781 V1 EN

Figure 267: Simplified logic diagram for the voltage selection function for the tie circuit breaker in 1 1/2
breaker arrangement.

Fuse failure supervision


External fuse failure signals or signals from a tripped fuse switch/MCB are
connected to binary inputs that are configured to the inputs of the synchronizing
functions in the IED. Alternatively, the internal signals from fuse failure
supervision can be used when available. There are two alternative connection
possibilities. Inputs labelled OK must be connected if the available contact
indicates that the voltage circuit is healthy. Inputs labelled FF must be connected if
the available contact indicates that the voltage circuit is faulty.

492
Technical reference manual
1MRK505183-UEN C Section 12
Control

The UB1OK/UB2OK and UB1FF/UB2FF inputs are related to the busbar voltage
and the ULN1OK/ULN2OK and ULN1FF/ULN2FF inputs are related to the line
voltage. Configure them to the binary input or function outputs that indicate the
status of the external fuse failure of the busbar and line voltages. In the event of a
fuse failure, the energizing check functions are blocked. The synchronizing and the
synchrocheck function requires full voltage on both sides and will be blocked
automatically in the event of fuse failures.

12.1.3 Function block


SESRSYN
U3PBB1* SYNOK
U3PBB2* AUTOSYOK
U3PLN1* AUTOENOK
U3PLN2* MANSYOK
BLOCK MANENOK
BLKSYNCH TSTSYNOK
BLKSC TSTAUTSY
BLKENERG TSTMANSY
B1QOPEN TSTENOK
B1QCLD USELFAIL
B2QOPEN B1SEL
B2QCLD B2SEL
LN1QOPEN LN1SEL
LN1QCLD LN2SEL
LN2QOPEN SYNPROGR
LN2QCLD SYNFAIL
UB1OK UOKSYN
UB1FF UDIFFSYN
UB2OK FRDIFSYN
UB2FF FRDIFFOK
ULN1OK FRDERIVA
ULN1FF UOKSC
ULN2OK UDIFFSC
ULN2FF FRDIFFA
STARTSYN PHDIFFA
TSTSYNCH FRDIFFM
TSTSC PHDIFFM
TSTENERG UDIFFME
AENMODE FRDIFFME
MENMODE PHDIFFME
MODEAEN
MODEMEN

IEC06000534-2-en.vsd
IEC06000534 V2 EN

Figure 268: SESRSYN function block

12.1.4 Input and output signals


Table 289: SESRSYN Input signals
Name Type Default Description
U3PBB1 GROUP - Group signal for voltage input busbar 1
SIGNAL
U3PBB2 GROUP - Group signal for voltage input busbar 2
SIGNAL
U3PLN1 GROUP - Group signal for voltage input line 1
SIGNAL
U3PLN2 GROUP - Group signal for voltage input line 2
SIGNAL
Table continues on next page

493
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Default Description


BLOCK BOOLEAN 0 General block
BLKSYNCH BOOLEAN 0 Block synchronizing
BLKSC BOOLEAN 0 Block synchro check
BLKENERG BOOLEAN 0 Block energizing check
B1QOPEN BOOLEAN 0 Open status for CB or disconnector connected to
bus1
B1QCLD BOOLEAN 0 Close status for CB or disconnector connected to
bus1
B2QOPEN BOOLEAN 0 Open status for CB or disconnector connected to
bus2
B2QCLD BOOLEAN 0 Close status for CB or disconnector connected to
bus2
LN1QOPEN BOOLEAN 0 Open status for CB or disconnector connected to
line1
LN1QCLD BOOLEAN 0 Close status for CB or disconnector connected to
line1
LN2QOPEN BOOLEAN 0 Open status for CB or disconnector connected to
line2
LN2QCLD BOOLEAN 0 Close status for CB or disconnector connected to
line2
UB1OK BOOLEAN 0 Bus1 voltage transformer OK
UB1FF BOOLEAN 0 Bus1 voltage transformer fuse failure
UB2OK BOOLEAN 0 Bus2 voltage transformer OK
UB2FF BOOLEAN 0 Bus2 voltage transformer fuse failure
ULN1OK BOOLEAN 0 Line1 voltage transformer OK
ULN1FF BOOLEAN 0 Line1 voltage transformer fuse failure
ULN2OK BOOLEAN 0 Line2 voltage transformer OK
ULN2FF BOOLEAN 0 Line2 voltage transformer fuse failure
STARTSYN BOOLEAN 0 Start synchronizing
TSTSYNCH BOOLEAN 0 Set synchronizing in test mode
TSTSC BOOLEAN 0 Set synchro check in test mode
TSTENERG BOOLEAN 0 Set energizing check in test mode
AENMODE INTEGER 0 Input for setting of automatic energizing mode
MENMODE INTEGER 0 Input for setting of manual energizing mode

Table 290: SESRSYN Output signals


Name Type Description
SYNOK BOOLEAN Synchronizing OK output
AUTOSYOK BOOLEAN Auto synchro check OK
AUTOENOK BOOLEAN Automatic energizing check OK
MANSYOK BOOLEAN Manual synchro check OK
MANENOK BOOLEAN Manual energizing check OK
Table continues on next page

494
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Type Description


TSTSYNOK BOOLEAN Synchronizing OK test output
TSTAUTSY BOOLEAN Auto synchro check OK test output
TSTMANSY BOOLEAN Manual synchro check OK test output
TSTENOK BOOLEAN Energizing check OK test output
USELFAIL BOOLEAN Selected voltage transformer fuse failed
B1SEL BOOLEAN Bus1 selected
B2SEL BOOLEAN Bus2 selected
LN1SEL BOOLEAN Line1 selected
LN2SEL BOOLEAN Line2 selected
SYNPROGR BOOLEAN Synchronizing in progress
SYNFAIL BOOLEAN Synchronizing failed
UOKSYN BOOLEAN Voltage amplitudes for synchronizing above set
limits
UDIFFSYN BOOLEAN Voltage difference out of limit for synchronizing
FRDIFSYN BOOLEAN Frequency difference out of limit for synchronizing
FRDIFFOK BOOLEAN Frequency difference in band for synchronizing
FRDERIVA BOOLEAN Frequency derivative out of limit for synchronizing
UOKSC BOOLEAN Voltage amplitudes above set limits
UDIFFSC BOOLEAN Voltage difference out of limit
FRDIFFA BOOLEAN Frequency difference out of limit for Auto operation
PHDIFFA BOOLEAN Phase angle difference out of limit for Auto
operation
FRDIFFM BOOLEAN Frequency difference out of limit for Manual
operation
PHDIFFM BOOLEAN Phase angle difference out of limit for Manual
Operation
UDIFFME REAL Calculated difference in voltage
FRDIFFME REAL Calculated difference in frequency
PHDIFFME REAL Calculated difference of phase angle
MODEAEN INTEGER Selected mode for automatic energizing
MODEMEN INTEGER Selected mode for manual energizing

495
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.1.5 Setting parameters


Table 291: SESRSYN Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
SelPhaseBus1 phase1 - - phase2 Select phase for bus1
phase2
phase3
phase1-phase2
phase2-phase3
phase3-phase1
SelPhaseBus2 phase1 - - phase2 Select phase for bus2
phase2
phase3
phase1-phase2
phase2-phase3
phase3-phase1
SelPhaseLine1 phase1 - - phase2 Select phase for line1
phase2
phase3
phase1-phase2
phase2-phase3
phase3-phase1
SelPhaseLine2 phase1 - - phase2 Select phase for line2
phase2
phase3
phase1-phase2
phase2-phase3
phase3-phase1
CBConfig No voltage sel. - - No voltage sel. Select CB configuration
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB
UBase 0.001 - 9999.999 kV 0.001 400.000 Base voltage in kV
PhaseShift -180 - 180 Deg 5 0 Phase shift
URatio 0.040 - 25.000 - 0.001 1.000 Voltage ratio
OperationSynch Off - - Off Operation for synchronizing function Off/
On On
UHighBusSynch 50.0 - 120.0 %UB 1.0 80.0 Voltage high limit bus for synchronizing
in % of UBase
UHighLineSynch 50.0 - 120.0 %UB 1.0 80.0 Voltage high limit line for synchronizing
in % of UBase
UDiffSynch 2.0 - 50.0 %UB 1.0 10.0 Voltage difference limit for synchronizing
in % of UBase
FreqDiffMin 0.003 - 0.250 Hz 0.001 0.010 Minimum frequency difference limit for
synchronizing
FreqDiffMax 0.050 - 0.250 Hz 0.001 0.200 Maximum frequency difference limit for
synchronizing
FreqRateChange 0.000 - 0.500 Hz/s 0.001 0.300 Maximum allowed frequency rate of
change
tBreaker 0.000 - 60.000 s 0.001 0.080 Closing time of the breaker
Table continues on next page

496
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Values (Range) Unit Step Default Description


tClosePulse 0.050 - 60.000 s 0.001 0.200 Breaker closing pulse duration
tMaxSynch 0.00 - 6000.00 s 0.01 600.00 Resets synch if no close has been made
before set time
tMinSynch 0.000 - 60.000 s 0.001 2.000 Minimum time to accept synchronizing
conditions
OperationSC Off - - On Operation for synchronism check
On function Off/On
UHighBusSC 50.0 - 120.0 %UB 1.0 80.0 Voltage high limit bus for synchrocheck
in % of UBase
UHighLineSC 50.0 - 120.0 %UB 1.0 80.0 Voltage high limit line for synchrocheck
in % of UBase
UDiffSC 2.0 - 50.0 %UB 1.0 15.0 Voltage difference limit in % of UBase
FreqDiffA 0.003 - 1.000 Hz 0.001 0.010 Frequency difference limit between bus
and line Auto
FreqDiffM 0.003 - 1.000 Hz 0.001 0.010 Frequency difference limit between bus
and line Manual
PhaseDiffA 5.0 - 90.0 Deg 1.0 25.0 Phase angle difference limit between
bus and line Auto
PhaseDiffM 5.0 - 90.0 Deg 1.0 25.0 Phase angle difference limit between
bus and line Manual
tSCA 0.000 - 60.000 s 0.001 0.100 Time delay output for synchrocheck Auto
tSCM 0.000 - 60.000 s 0.001 0.100 Time delay output for synchrocheck
Manual
AutoEnerg Off - - DBLL Automatic energizing check mode
DLLB
DBLL
Both
ManEnerg Off - - Both Manual energizing check mode
DLLB
DBLL
Both
ManEnergDBDL Off - - Off Manual dead bus, dead line energizing
On
UHighBusEnerg 50.0 - 120.0 %UB 1.0 80.0 Voltage high limit bus for energizing
check in % of UBase
UHighLineEnerg 50.0 - 120.0 %UB 1.0 80.0 Voltage high limit line for energizing
check in % of UBase
ULowBusEnerg 10.0 - 80.0 %UB 1.0 40.0 Voltage low limit bus for energizing
check in % of UBase
ULowLineEnerg 10.0 - 80.0 %UB 1.0 40.0 Voltage low limit line for energizing
check in % of UBase
UMaxEnerg 50.0 - 180.0 %UB 1.0 115.0 Maximum voltage for energizing in % of
UBase
tAutoEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for automatic energizing
check
tManEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for manual energizing check

497
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.1.6 Technical data


Table 292: SESRSYN technical data
Function Range or value Accuracy
Phase shift, jline - jbus (-180 to 180) degrees -

Voltage ratio, Ubus/Uline (0.40-25.000) % of UBase -

Voltage high limit for (50.0-120.0)% of UBase ± 1.0% of Ur at U ≤ Ur


synchronizing and ± 1.0% of U at U >Ur
synchrocheck
Reset ratio, synchrocheck > 95% -
Frequency difference limit (0.003-1.000) Hz ± 2.0 mHz
between bus and line
Phase angle difference limit (5.0-90.0) degrees ± 2.0 degrees
between bus and line
Voltage difference limit (2.0-50.0)% of UBase ± 1.0% of Ur
between bus and line
Time delay output for (0.000-60.000) s ± 0.5% ± 10 ms
synchrocheck
Voltage high limit for (50.0-120.0)% of UBase ± 1.0% of Ur at U ≤ Ur
energizing check ± 1.0% of U at U >Ur

Reset ratio, voltage high limit > 95% -


Voltage low limit for (10.0-80.0)% of UBase ± 1.0% of Ur
energizing check
Reset ratio, voltage low limit < 105% -
Maximum voltage for (50.0-180.0)% of UBase ± 1.0% of Ur at U ≤ Ur
energizing ± 1.0% of U at U >Ur

Time delay for energizing (0.000-60.000) s ± 0.5% ± 10 ms


check
Operate time for 160 ms typically -
synchrocheck function
Operate time for energizing 80 ms typically -
function

12.2 Autorecloser SMBRREC

Function Description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Autorecloser SMBRREC 79

O->I

SYMBOL-L V1 EN

498
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.2.1 Introduction
The autorecloser (SMBRREC) function provides high-speed and/or delayed auto-
reclosing for single or multi-breaker applications.

Up to five reclosing attempts can be programmed. The first attempt can be single-,
two and/or three phase for single phase or multi-phase faults respectively.

Multiple autoreclosing functions are provided for multi-breaker arrangements. A


priority circuit allows one circuit breaker to close first and the second will only
close if the fault proved to be transient.

Each autoreclosing function can be configured to co-operate with a synchrocheck


function.

12.2.2 Principle of operation

12.2.2.1 Logic Diagrams

The logic diagrams below illustrate the principles applicable in the understanding
of the functionality.

12.2.2.2 Auto-reclosing operation Off and On

Operation of the automatic reclosing can be set to Off or On via the setting
parameters and through external control. With the setting Operation = On, the
function is activated while with the setting Operation = Off the function is
deactivated. With the setting Operation = External ctrl, the activation/deactivation
is made by input signal pulses, for example, from a control system.

When the function is set On and is operative the output SETON is activated (high).
Other input conditions such as CBPOS and CBREADY must also be fulfilled. At
this point the automatic recloser is prepared to start the reclosing cycle and the
output signal READY on the SMBRREC function block is activated (high).

12.2.2.3 Auto-reclosing mode selection

The Auto-reclosing mode is selected with setting ARMode = 3phase(0), 1/2/3ph(1),


1/2ph(2), 1ph+1*2ph(3), 1/2ph+1*3ph(4), 1ph+1*2/3ph(5). The selected mode
can be read as integer as per above list on output MODE.

As an alternative to setting the mode can be selected by connecting an integer, for


example from function block B16I to input MODEINT.

Following integers shall be used: 1=3phase, 2=1/2/3ph, 3=1/2ph, 4=1ph+1*2ph,


5=1/2ph+1*3ph or 6=1ph+1*2/3ph.

When INTZERO from Fixed signal function block is connected to the input
MODEINT the parameter setting selected will be valid.

499
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.2.2.4 Start auto-reclosing and conditions for start of a reclosing cycle

The usual way in which to start a reclosing cycle, or sequence, is to start it when a
line protection tripping has occurred, by applying a signal to the START input. It
should be necessary to adjust three-phase auto-reclosing open time, (dead time) for
different power system configurations or during tripping at different protection
stages, the input STARTHS (start high-speed reclosing) can also be used.

For a new auto-reclosing cycle to be started, a number of conditions need to be


met. They are linked to dedicated inputs. The inputs are:

• CBREADY: CB ready for a reclosing cycle, for example, charged operating gear
• CBPOS: to ensure that the CB was closed when the line fault occurred and
start was applied
• No blocking or inhibit signal shall be present.

After the start has been accepted, it is latched in and an internal signal “Started” is
set. It can be interrupted by certain events, like an inhibit signal.

To start auto-reclosing by CB position Open instead of from protection trip signals,


one has to configure the CB Open position signal to inputs CBPOS and START
and set a parameter StartByCBOpen = On and CBAuxContType = NormClosed
(normally closed). One also has to configure and connect signals from manual trip
commands to input INHIBIT.

The logic for switching the auto-recloser On/Off and the starting of the reclosing is
shown in figure 269. The following should be considered:

• Setting Operation can be set to Off, External ctrl or On. External ctrl offers
the possibility of switching by external switches to inputs ON and OFF,
communication commands to the same inputs, and so on.
• SMBRREC is normally started by tripping. It is either a Zone 1 and
Communication aided trip, or a general trip. If the general trip is used the
function must be blocked from all back-up tripping connected to INHIBIT. In
both alternatives the breaker failure function must be connected to inhibit the
function. START makes a first attempt with synchrocheck, STARTHS makes
its first attempt without synchrocheck. TRSOTF starts shots 2-5.
• Circuit breaker checks that the breaker was closed for a certain length of time
before the starting occurred and that the CB has sufficient stored energy to
perform an auto-reclosing sequence and is connected to inputs CBPOS and
CBREADY.

500
Technical reference manual
1MRK505183-UEN C Section 12
Control

Operation:On

Operation:Off

Operation:External Ctrl
OR
ON AND SETON
AND S
OR
OFF AND R

START
STARTHS OR
OR initiate
autoInitiate

Additional conditions
TRSOTF AND

start
120 ms
CBREADY AND
t AND
AND S
tCBClosedMin
CBPOS CB Closed
t R

AND
Blocking conditions READY
AND
OR
Inhibit condistions

count 0

en05000782.vsd

IEC05000782 V1 EN

Figure 269: Auto-reclosing Off/On and start

12.2.2.5 Control of the auto-reclosing open time for shot 1

It is possible to use up to four different time settings for the first shot, and one
extension time. There are separate settings for single- , two- and three-phase auto-
reclosing open times, t1 1Ph, t1 2Ph, t1 3Ph. If no particular input signal is applied,
and an auto-reclosing program with single-phase reclosing is selected, the auto-
reclosing open time t1 1Ph will be used. If one of the inputs TR2P or TR3P is
activated in connection with the input START, the auto-reclosing open time for two-
phase or three-phase reclosing is used. There is also a separate time setting facility
for three-phase high-speed auto-reclosing, t1 3PhHS available for use when
required. It is activated by input STARTHS.

An auto-reclosing open time extension delay, tExtended t1, can be added to the
normal shot 1 delay. It is intended to come into use if the communication channel
for permissive line protection is lost. In a case like this there can be a significant
time difference in fault clearance at the two line ends. A longer auto-reclosing open
time can then be useful. This extension time is controlled by setting parameter
Extended t1 = On and the input PLCLOST.

12.2.2.6 Long trip signal

In normal circumstances the trip command resets quickly due to fault clearing. The
user can set a maximum trip pulse duration tTrip. When trip signals are longer, the

501
Technical reference manual
Section 12 1MRK505183-UEN C
Control

auto-reclosing open time is extended by tExtended t1. If Extended t1 = Off, a long


trip signal interrupts the reclosing sequence in the same way as a signal to input
INHIBIT.

Extended t1

PLCLOST Extend t1
initiate AND OR AND
AND
tTrip
t
AND
start

long duration
AND
(block SMBRREC)

IEC05000783_2_en.vsd

IEC05000783 V2 EN

Figure 270: Control of extended auto-reclosing open time and long trip pulse detection

Reclosing checks and the reclaim timer


When dead time has elapsed during the auto-reclosing procedure certain conditions
must be fulfilled before the CB closing command is issued. To achieve this, signals
are exchanged between program modules to check that these conditions are met. In
three-phase reclosing a synchronizing and/or energizing check can be used. It is
possible to use a synchrocheck function in the same physical device or an external
one. The release signal is configured by connecting to the auto-reclosing function
input SYNC. If reclosing without checking is preferred the SYNC input can be set
to TRUE (set high). Another possibility is to set the output of the synchro-check
function to a permanently activated state. At confirmation from the synchro-check,
or if the reclosing is of single-phase or two-phase type, the signal passes on. At single-
phase, two-phase reclosing and at three-phase high-speed reclosing started by
STARTHS, synchronization is not checked, and the state of the SYNC input is
disregarded.

By choosing CBReadyType = CO (CB ready for a Close-Open sequence) the


readiness of the circuit breaker is also checked before issuing the CB closing
command. If the CB has a readiness contact of type CBReadyType = OCO (CB
ready for an Open-Close-Open sequence) this condition may not be complied with
after the tripping and at the moment of reclosure. The Open-Close-Open condition
was however checked at the start of the reclosing cycle and it is then likely that the
CB is prepared for a Close-Open sequence.

502
Technical reference manual
1MRK505183-UEN C Section 12
Control

The synchro-check or energizing check must be fulfilled within a set time interval,
tSync. If it is not, or if other conditions are not met, the reclosing is interrupted and
blocked.

The reclaim timer defines a time from the issue of the reclosing command, after
which the reclosing function resets. Should a new trip occur during this time, it is
treated as a continuation of the first fault. The reclaim timer is started when the CB
closing command is given.

A number of outputs for Autoreclosing state control keeps track of the actual state
in the reclosing sequence.

503
Technical reference manual
Section 12 1MRK505183-UEN C
Control

t1 1Ph
"SMBRREC Open time" timers
t
1P2PTO
From logic for t1 2Ph OR
reclosing t
programs
1P2PTO t1 3Ph HS
t
3PHSTO
3PHSTO
3PT1TO
t1 3Ph
3PT2TO t
3PT1TO
3PT3TO OR
AND
3PT4TO OR Pulse AR
3PT5TO AND

SYNC
initiate AND Blocking out
CBREADY AND OR

SMRREC State
tSync Control
AND t COUNTER
0 Shot 0
CL Shot 1
1
2 Shot 2
3 Shot 3
tReclaim
Pulse SMBRREC (above) AND t R 4 Shot 4
OR Shot 5
5
TR2P LOGIC Reclaim Timer On
TR3P reclosing
1PT1
programs
start 2PT1
initiate 3PHS INPROGR
Shot 0 3PT1 OR
Shot 1 3PT2
Shot 2
Shot 3 3PT3
Shot 4
Shot 5 3PT4
PERMIT1P
3PT5
PREP3P
1
Blocking out tInhibit
OR Inhibit (internal)
INHIBIT t

IEC05000784_2_en.vsd

IEC05000784 V2 EN

Figure 271: Reclosing Reclaim and Inhibit timers

Pulsing of the CB closing command


The CB closing command, CLOSECB is a pulse with a duration set by parameter
tPulse. For circuit-breakers without anti-pumping function, the close pulse cutting
described below can be used. This is done by selecting the parameter

504
Technical reference manual
1MRK505183-UEN C Section 12
Control

CutPulse=On. In case of a new trip pulse, the closing command pulse is cut
(interrupted). The minimum duration of the pulse is always 50 ms. See figure 272

When a reclosing command is issued, the appropriate reclosing operation counter is


incremented. There is a counter for each type of reclosing and one for the total
number of reclosing commands issued.

tPulse
pulse
**) AND CLOSECB
OR
initiate
50 ms

1PT1 AND COUNT1P


counter

2PT1 AND
counter
COUNT2P

3PT1 AND COUNT3P1


counter

3PT2 AND COUNT3P2


counter

3PT3 AND COUNT3P3


counter

3PT4 AND COUNT3P4


counter

3PT5 AND COUNT3P5


counter

counter COUNTAR
RSTCOUNT

**) Only if "CutPulse" = On

en05000785.vsd

IEC05000785 V1 EN

Figure 272: Pulsing of closing command and driving the operation counters

Transient fault
After the reclosing command the reclaim timer tReclaim starts running for the set
time. If no tripping occurs within this time, the auto-reclosing will reset.

Permanent fault and reclosing unsuccessful signal


If a new trip occurs after the CB closing command, and a new input signal START
or TRSOTF appears, the output UNSUCCL (unsuccessful closing) is set high. The
timers for the first shot can no longer be started. Depending on the setting for the
number of reclosing shots, further shots may be made or the reclosing sequence

505
Technical reference manual
Section 12 1MRK505183-UEN C
Control

will be ended. After the reclaim time has elapsed, the auto-reclosing function resets
but the CB remains open. The CB closed data at the CBPOS input will be missing.
Because of this, the reclosing function will not be ready for a new reclosing cycle.

Normally the signal UNSUCCL appears when a new trip and start is received after
the last reclosing shot has been made and the auto-reclosing function is blocked.
The signal resets once the reclaim time has elapsed. The “unsuccessful“ signal can
also be made to depend on CB position input. The parameter UnsucClByCBChk
should then be set to CBCheck, and a timer tUnsucCl should also be set. If the CB
does not respond to the closing command and does not close, but remains open, the
output UNSUCCL is set high after time tUnsucCl.

initiate
block start AND
OR UNSUCCL
AND S

shot 0
R

UnsucClByCBchk = CBcheck

Pulse AR (Closing) OR tUnsucCl


AND
AND t
CBPOS CBclosed

eno5000786.vsd

IEC05000786 V1 EN

Figure 273: Issue of signal UNSUCCL, unsuccessful reclosing

Automatic continuation of the reclosing sequence


The auto-reclosing function can be programmed to proceed to the following
reclosing shots (if selected) even if the start signals are not received from the
protection functions, but the breaker is still not closed. This is done by setting
parameter AutoCont = On and tAutoContWait to the required delay for the function
to proceed without a new start.

506
Technical reference manual
1MRK505183-UEN C Section 12
Control

tAutoContWait
t

AND

CLOSECB
AND
S Q

AND

CBPOS CBClosed
OR

initiate
START OR

en05000787.vsd
IEC05000787 V1 EN

Figure 274: Automatic proceeding of shot 2 to 5

Start of reclosing from CB open information


If a user wants to apply starting of auto-reclosing from CB open position instead of
from protection trip signals, the function offers such a possibility. This starting
mode is selected by a setting parameter StartByCBOpen = On. One needs then to
block reclosing at all manual trip operations. Typically, one also set
CBAuxContType = NormClosed and connect a CB auxiliary contact of type NC
(normally closed) to inputs CBPOS and START. When the signal changes from
CB closed to CB open an auto-reclosing start pulse of limited length is generated
and latched in the function, subject to the usual checks. Then the reclosing
sequence continues as usual. One needs to connect signals from manual tripping
and other functions, which shall prevent reclosing, to the input INHIBIT.

507
Technical reference manual
Section 12 1MRK505183-UEN C
Control

StartByCBOpen = On

START AND

STARTHS AND
start
³1
100 ms
AND

100 ms
AND

en05000788.vsd
IEC05000788 V1 EN

Figure 275: Pulsing of the start inputs

12.2.2.7 Time sequence diagrams

Some examples of the timing of internal and external signals at typical transient
and permanent faults are shown below in figures 276 to 279.

Fault
CB POS
Closed Open Closed
CB READY

START (Trip)
SYNC
tReclaim
READY

INPROG

1PT1

ACTIVE

CLOSE CB t1 1Ph tPulse

PREP3P

SUCCL

Time

en04000196-2-en.vsd
IEC04000196 V2 EN

Figure 276: Transient single-phase fault. Single -phase reclosing

508
Technical reference manual
1MRK505183-UEN C Section 12
Control

Fault
CB POS Open
Closed Open C C
CB READY

START (Trip)

TR3P
SYNC

READY

INPROGR

3PT1 t1 3Ph

3PT2 t2 3Ph

ACTIVE tReclaim

CLOSE CB tPulse tPulse

PREP3P

UNSUCCL
Time

en04000197.vsd
IEC04000197 V1 EN

Figure 277: Permanent fault. Three-phase trip. Two-shot reclosing

509
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Fault
AR01-CBCLOSED
AR01-CBREADY(CO)

AR01-START

AR01-TR3P

AR01-SYNC

AR01-READY

AR01-INPROGR

AR01-1PT1

AR01-T1

AR01-T2

AR01-CLOSECB t1s

AR01-P3P

AR01-UNSUC
tReclaim

en04000198.vsd
IEC04000198 V1 EN

Figure 278: Permanent single-phase fault. Program 1/2/3ph, single-phase


single-shot reclosing

Fault
AR01-CBCLOSED
AR01-CBREADY(CO)

AR01-START

AR01-TR3P

AR01-SYNC

AR01-READY

AR01-INPROGR

AR01-1PT1

AR01-T1

AR01-T2
t2
AR01-CLOSECB t1s

AR01-P3P

AR01-UNSUC
tReclaim

en04000199.vsd
IEC04000199 V1 EN

Figure 279: Permanent single-phase fault. Program 1ph + 3ph or 1/2ph + 3ph,
two-shot reclosing

510
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.2.3 Function block


SMBRREC
ON BLOCKED
OFF SETON
BLKON READY
BLKOFF ACTIVE
RESET SUCCL
INHIBIT UNSUCCL
START INPROGR
STARTHS 1PT1
TRSOTF 2PT1
SKIPHS 3PT1
ZONESTEP 3PT2
TR2P 3PT3
TR3P 3PT4
THOLHOLD 3PT5
CBREADY PERMIT1P
CBPOS PREP3P
PLCLOST CLOSECB
SYNC WFMASTER
WAIT COUNT1P
RSTCOUNT COUNT2P
MODEINT COUNT3P1
COUNT3P2
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
MODE

IEC06000189-2-en.vsd
IEC06000189 V2 EN

Figure 280: SMBRREC function block

12.2.4 Input and output signals


Table 293: SMBRREC Input signals
Name Type Default Description
ON BOOLEAN 0 Switches the AR On (at Operation = ExternalCtrl)
OFF BOOLEAN 0 Switches the AR Off (at Operation = ExternalCtrl)
BLKON BOOLEAN 0 Sets the AR in blocked state
BLKOFF BOOLEAN 0 Releases the AR from the blocked state
RESET BOOLEAN 0 Resets the AR to initial conditions
INHIBIT BOOLEAN 0 Interrupts and inhibits reclosing sequence
START BOOLEAN 0 Reclosing sequence starts by a protection trip
signal
STARTHS BOOLEAN 0 Start HS reclosing without SC: t13PhHS
TRSOTF BOOLEAN 0 Makes AR to continue to shots 2-5 at a trip from
SOTF
SKIPHS BOOLEAN 0 Will skip the high speed shot and continue on
delayed shots
ZONESTEP BOOLEAN 0 Coordination between local AR and down stream
devices
TR2P BOOLEAN 0 Signal to the AR that a two-phase tripping occurred
TR3P BOOLEAN 0 Signal to the AR that a three-phase tripping
occurred
Table continues on next page

511
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Default Description


THOLHOLD BOOLEAN 0 Hold the AR in wait state
CBREADY BOOLEAN 0 CB must be ready for CO/OCO operation to allow
start / close
CBPOS BOOLEAN 0 Status of the circuit breaker Closed/Open
PLCLOST BOOLEAN 0 Power line carrier or other form of permissive sig‐
nal lost
SYNC BOOLEAN 0 Synchronizing check fulfilled (for 3Ph attempts)
WAIT BOOLEAN 0 Wait for master (in Multi-breaker arrangements)
RSTCOUNT BOOLEAN 0 Resets all counters
MODEINT INTEGER 0 Integer input used to set the reclosingMode,
alternative to setting

Table 294: SMBRREC Output signals


Name Type Description
BLOCKED BOOLEAN The AR is in blocked state
SETON BOOLEAN The AR operation is switched on, operative
READY BOOLEAN Indicates that the AR function is ready for a new
sequence
ACTIVE BOOLEAN Reclosing sequence in progress
SUCCL BOOLEAN Activated if CB closes during the time tUnsucCl
UNSUCCL BOOLEAN Reclosing unsuccessful, signal resets after the
reclaim time
INPROGR BOOLEAN Reclosing shot in progress, activated during open
time
1PT1 BOOLEAN Single-phase reclosing is in progress, shot 1
2PT1 BOOLEAN Two-phase reclosing is in progress, shot 1
3PT1 BOOLEAN Three-phase reclosing in progress, shot 1
3PT2 BOOLEAN Three-phase reclosing in progress, shot 2
3PT3 BOOLEAN Three-phase reclosing in progress, shot 3
3PT4 BOOLEAN Three-phase reclosing in progress, shot 4
3PT5 BOOLEAN Three-phase reclosing in progress, shot 5
PERMIT1P BOOLEAN Permit single-phase trip, inverse signal to PREP3P
PREP3P BOOLEAN Prepare three-phase trip, control of the next trip
operation
CLOSECB BOOLEAN Closing command for CB
WFMASTER BOOLEAN Signal to Slave issued by Master for sequential
reclosing
COUNT1P INTEGER Counting the number of single-phase reclosing
shots
COUNT2P INTEGER Counting the number of two-phase reclosing shots
COUNT3P1 INTEGER Counting the number of three-phase reclosing
shot 1
Table continues on next page

512
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Type Description


COUNT3P2 INTEGER Counting the number of three-phase reclosing
shot 2
COUNT3P3 INTEGER Counting the number of three-phase reclosing
shot 3
COUNT3P4 INTEGER Counting the number of three-phase reclosing
shot 4
COUNT3P5 INTEGER Counting the number of three-phase reclosing
shot 5
COUNTAR INTEGER Counting total number of reclosing shots
MODE INTEGER Integer output for reclosing mode

12.2.5 Setting parameters


Table 295: SMBRREC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - External ctrl Off, ExternalCtrl, On
External ctrl
On
ARMode 3 phase - - 1/2/3ph The AR mode selection e.g. 3ph, 1/3ph
1/2/3ph
1/2ph
1ph+1*2ph
1/2ph+1*3ph
1ph+1*2/3ph
t1 1Ph 0.000 - 60.000 s 0.001 1.000 Open time for shot 1, single-phase
t1 3Ph 0.000 - 60.000 s 0.001 6.000 Open time for shot 1, delayed reclosing
3ph
t1 3PhHS 0.000 - 60.000 s 0.001 0.400 Open time for shot 1, high speed
reclosing 3ph
tReclaim 0.00 - 6000.00 s 0.01 60.00 Duration of the reclaim time
tSync 0.00 - 6000.00 s 0.01 30.00 Maximum wait time for synchrocheck OK
tTrip 0.000 - 60.000 s 0.001 0.200 Maximum trip pulse duration
tPulse 0.000 - 60.000 s 0.001 0.200 Duration of the circuit breaker closing
pulse
tCBClosedMin 0.00 - 6000.00 s 0.01 5.00 Min time that CB must be closed before
new sequence allows
tUnsucCl 0.00 - 6000.00 s 0.01 30.00 Wait time for CB before indicating
Unsuccessful/Successful
Priority None - - None Priority selection between adjacent
Low terminals None/Low/High
High
tWaitForMaster 0.00 - 6000.00 s 0.01 60.00 Maximum wait time for release from
Master

513
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Table 296: SMBRREC Group settings (advanced)


Name Values (Range) Unit Step Default Description
NoOfShots 1 - - 1 Max number of reclosing shots 1-5
2
3
4
5
StartByCBOpen Off - - Off To be set ON if AR is to be started by
On CB open position
CBAuxContType NormClosed - - NormOpen Select the CB aux contact type NC/NO
NormOpen for CBPOS input
CBReadyType CO - - CO Select type of circuit breaker ready
OCO signal CO/OCO
t1 2Ph 0.000 - 60.000 s 0.001 1.000 Open time for shot 1, two-phase
t2 3Ph 0.00 - 6000.00 s 0.01 30.00 Open time for shot 2, three-phase
t3 3Ph 0.00 - 6000.00 s 0.01 30.00 Open time for shot 3, three-phase
t4 3Ph 0.00 - 6000.00 s 0.01 30.00 Open time for shot 4, three-phase
t5 3Ph 0.00 - 6000.00 s 0.01 30.00 Open time for shot 5, three-phase
Extended t1 Off - - Off Extended open time at loss of
On permissive channel Off/On
tExtended t1 0.000 - 60.000 s 0.001 0.500 3Ph Dead time is extended with this
value at loss of perm ch
tInhibit 0.000 - 60.000 s 0.001 5.000 Inhibit reclosing reset time
CutPulse Off - - Off Shorten closing pulse at a new trip Off/On
On
Follow CB Off - - Off Advance to next shot if CB has been
On closed during dead time
AutoCont Off - - Off Continue with next reclosing-shot if
On breaker did not close
tAutoContWait 0.000 - 60.000 s 0.001 2.000 Wait time after close command before
proceeding to next shot
UnsucClByCBChk NoCBCheck - - NoCBCheck Unsuccessful closing signal obtained by
CB check checking CB position
BlockByUnsucCl Off - - Off Block AR at unsuccessful reclosing
On
ZoneSeqCoord Off - - Off Coordination of down stream devices to
On local prot unit’s AR

514
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.2.6 Technical data


Table 297: SMBRREC technical data
Function Range or value Accuracy
Number of autoreclosing shots 1-5 -
Autoreclosing open time:
shot 1 - t1 1Ph (0.000-60.000) s ± 0.5% ± 10 ms
shot 1 - t1 2Ph
shot 1 - t1 3PhHS
shot 1 - t1 3PhDld
shot 2 - t2 (0.00-6000.00) s
shot 3 - t3
shot 4 - t4
shot 5 - t5
Extended autorecloser open time (0.000-60.000) s
Autorecloser maximum wait time for sync (0.00-6000.00) s
Maximum trip pulse duration (0.000-60.000) s
Inhibit reset time (0.000-60.000) s
Reclaim time (0.00-6000.00) s
Minimum time CB must be closed before AR (0.00-6000.00) s
becomes ready for autoreclosing cycle
Circuit breaker closing pulse length (0.000-60.000) s
CB check time before unsuccessful (0.00-6000.00) s
Wait for master release (0.00-6000.00) s
Wait time after close command before (0.000-60.000) s
proceeding to next shot

12.3 Apparatus control APC

12.3.1 Introduction
The apparatus control is a function for control and supervision of circuit breakers,
disconnectors and earthing switches within a bay. Permission to operate is given
after evaluation of conditions from other functions such as interlocking,
synchrocheck, operator place selection and external or internal blockings.

12.3.2 Principle of operation


A bay can handle, for example a power line, a transformer, a reactor, or a capacitor
bank. The different primary apparatuses within the bay can be controlled via the
apparatus control function directly by the operator or indirectly by automatic
sequences.

515
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Because a primary apparatus can be allocated to many functions within a


Substation Automation system, the object-oriented approach with a function
module that handles the interaction and status of each process object ensures
consistency in the process information used by higher-level control functions.

Primary apparatuses such as breakers and disconnectors are controlled and


supervised by one software module (SCSWI) each. Because the number and type
of signals connected to a breaker and a disconnector are almost the same, the same
software is used to handle these two types of apparatuses.

The software module is connected to the physical process in the switchyard via an
interface module by means of a number of digital inputs and outputs. One type of
interface module is intended for a circuit breaker (SXCBR) and another type is
intended for a disconnector or earthing switch (SXSWI). Four types of function
blocks are available to cover most of the control and supervision within the bay.
These function blocks are interconnected to form a control function reflecting the
switchyard configuration. The total number used depends on the switchyard
configuration. These four types are:

• Bay control QCBAY


• Switch controller SCSWI
• Circuit breaker SXCBR
• Circuit switch SXSWI

The three latter functions are logical nodes according to IEC 61850. The functions
Local Remote (LOCREM) and Local Remote Control (LOCREMCTRL), to handle
the local/remote switch, and the functions Bay reserve (QCRSV) and Reservation
input (RESIN), for the reservation function, also belong to the apparatus control
function. The principles of operation, function block, input and output signals and
setting parameters for all these functions are described below.

12.3.3 Error handling


Depending on the error that occurs during the command sequence the error signal
will be set with a value. Table 298 describes vendor specific cause values in
addition to these specified in IEC 61850-8-1 standard. The list of values of the
“cause” are in order of priority. The values are available over the IEC 61850. An
output L_CAUSE on the function block for Switch controller (SCSWI), Circuit
breaker (SXCBR) and Circuit switch (SXSWI) indicates the latest value of the
error during the command.

516
Technical reference manual
1MRK505183-UEN C Section 12
Control

Table 298: Values for "cause" signal in priority order


Attribute value Description Supported
Defined in IEC 61850 0 no error X
1 serviceError-type
2 blocked-by-switching- X
hierarchy
3 select-failed X
4 invalid-position X
5 position-reached X
6 parameter-change-in- X
execution
7 step-limit X
8 blocked-by-mode X
9 blocked-by-process X
10 blocked-by-interlocking X
11 blocked-by- X
synchrocheck
12 command-already-in- X
execution
13 blocked-by-health X
14 1-of-n-control X
15 abortion-by-cancel X
16 time-limit-over X
17 abortion-by-trip X
18 object-not-selected X
19 Not in use

Table continues on next page

517
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Attribute value Description Supported


Vendor specific -20 Not in use
-21 Not in use
-23 blocked-for-command X
-24 blocked-for-open- X
command
-25 blocked-for-close- X
command
-26 Not in use
-27 Not in use
-28 Not in use
-29 Not in use
-30 long-operation-time X
-31 switch-not-start-moving X
-32 persisting-intermediate- X
state
-33 switch-returned-to-initial- X
position
-34 switch-in-bad-state X
-35 not-expected-final- X
position

12.3.4 Bay control QCBAY

12.3.4.1 Introduction

The bay control (QCBAY) function is used to handle the selection of the operator
place per bay. QCBAY also provides blocking functions that can be distributed to
different apparatuses within the bay.

12.3.4.2 Principle of operation

The functionality of the Bay control (QCBAY) function is not defined in the IEC
61850–8–1 standard, which means that the function is a vendor specific logical node.

The function sends information about the Permitted Source To Operate (PSTO)
and blocking conditions to other functions within the bay for example, switch
control functions, voltage control functions and measurement functions.

Local panel switch


The local panel switch is a switch that defines the operator place selection. The
switch connected to this function can have three positions remote/local/off. The
positions are here defined so that remote means that operation is allowed from station/
remote level and local from the IED level. The local/remote switch is normally
situated on the control/protection IED itself, which means that the position of the

518
Technical reference manual
1MRK505183-UEN C Section 12
Control

switch and its validity information are connected internally, and not via I/O boards.
When the switch is mounted separately on the IED the signals are connected to the
function via I/O boards.

When the local panel switch is in Off position all commands from remote and local
level will be ignored. If the position for the local/remote switch is not valid the
PSTO output will always be set to faulty state (3), which means no possibility to
operate.

To adapt the signals from the local HMI or from an external local/remote switch,
the function blocks LOCREM and LOCREMCTRL are needed and connected to
QCBAY.

Permitted Source To Operate (PSTO)


The actual state of the operator place is presented by the value of the Permitted
Source To Operate, PSTO signal. The PSTO value is evaluated from the local/
remote switch position according to table 299. In addition, there is one
configuration parameter that affects the value of the PSTO signal. If the parameter
AllPSTOValid is set and LR-switch position is in Local or Remote state, the PSTO
value is set to 5 (all), that is, it is permitted to operate from both local and remote
level without any priority. When the external panel switch is in Off position the
PSTO value shows the actual state of switch that is, 0. In this case it is not possible
to control anything.

Table 299: PSTO values for different Local panel switch positions
Local panel switch PSTO value AllPSTOValid Possible locations that shall be able to
positions (configuration operate
parameter)
0 = Off 0 -- Not possible to operate
1 = Local 1 FALSE Local Panel
1 = Local 5 TRUE Local or Remote level without any
priority
2 = Remote 2 FALSE Remote level
2 = Remote 5 TRUE Local or Remote level without any
priority
3 = Faulty 3 -- Not possible to operate

Blockings
The blocking states for position indications and commands are intended to provide
the possibility for the user to make common blockings for the functions configured
within a complete bay.

The blocking facilities provided by the bay control function are the following:

519
Technical reference manual
Section 12 1MRK505183-UEN C
Control

• Blocking of position indications, BL_UPD. This input will block all inputs
related to apparatus positions for all configured functions within the bay.
• Blocking of commands, BL_CMD. This input will block all commands for all
configured functions within the bay.
• Blocking of function, BLOCK, signal from DO (Data Object) Behavior (IEC
61850–8–1). If DO Behavior is set to "blocked" it means that the function is
active, but no outputs are generated, no reporting, control commands are
rejected and functional and configuration data is visible.

The switching of the Local/Remote switch requires at least system operator level.
The password will be requested at an attempt to operate if authority levels have
been defined in the IED. Otherwise the default authority level, SuperUser, can
handle the control without LogOn. The users and passwords are defined in PCM600.

12.3.4.3 Function block


QCBAY
LR_OFF PSTO
LR_LOC UPD_BLKD
LR_REM CMD_BLKD
LR_VALID
BL_UPD
BL_CMD
IEC05000796-2-en.vsd
IEC05000796 V2 EN

Figure 281: QCBAY function block

12.3.4.4 Input and output signals


Table 300: QCBAY Input signals
Name Type Default Description
LR_OFF BOOLEAN 0 External Local/Remote switch is in Off position
LR_LOC BOOLEAN 0 External Local/Remote switch is in Local position
LR_REM BOOLEAN 0 External Local/Remote switch is in Remote
position
LR_VALID BOOLEAN 0 Data representing the L/R switch position is valid
BL_UPD BOOLEAN 0 Steady signal to block the position updates
BL_CMD BOOLEAN 0 Steady signal to block the command

Table 301: QCBAY Output signals


Name Type Description
PSTO INTEGER The value for the operator place allocation
UPD_BLKD BOOLEAN The update of position is blocked
CMD_BLKD BOOLEAN The function is blocked for commands

520
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.3.4.5 Setting parameters


Table 302: QCBAY Non group settings (basic)
Name Values (Range) Unit Step Default Description
AllPSTOValid Priority - - Priority The priority of originators
No priority

12.3.5 Local/Remote switch

12.3.5.1 Introduction

The signals from the local HMI or from an external local/remote switch are applied
via function blocks LOCREM and LOCREMCTRL to the Bay control (QCBAY)
function block. A parameter in function block LOCREM is set to choose if the
switch signals are coming from the local HMI or from an external hardware switch
connected via binary inputs.

12.3.5.2 Principle of operation

The function block Local remote (LOCREM) handles the signals coming from the
local/remote switch. The connections are seen in figure 282, where the inputs on
function block LOCREM are connected to binary inputs if an external switch is
used. When a local HMI is used, the inputs are not used and are set to FALSE in
the configuration. The outputs from the LOCREM function block control the
output PSTO (Permitted Source To Operate) on Bay control (QCBAY).

521
Technical reference manual
Section 12 1MRK505183-UEN C
Control

LOCREM QCBAY
CTRLOFF OFF LR_OFF PSTO
LOCCTRL LOCAL LR_LOC UPD_BLKD
REMCTRL REMOTE LR_REM CMD_BLKD
LHMICTRL VALID LR_VALID
BL_UPD
BL_CMD

LOCREM QCBAY
CTRLOFF OFF LR_OFF PSTO
LOCCTRL LOCAL LR_LOC UPD_BLKD
REMCTRL REMOTE LR_REM CMD_BLKD
LHMICTRL VALID LR_VALID
BL_UPD
BL_CMD

LOCREMCTRL
PSTO1 HMICTR1
PSTO2 HMICTR2
PSTO3 HMICTR3
PSTO4 HMICTR4
PSTO5 HMICTR5
PSTO6 HMICTR6
PSTO7 HMICTR7
PSTO8 HMICTR8
PSTO9 HMICTR9
PSTO10 HMICTR10
PSTO11 HMICTR11
PSTO12 HMICTR12

IEC05000250_2_en.vsd
IEC05000250 V2 EN

Figure 282: Configuration for the local/remote handling for a local HMI with two
bays and two screen pages

If the IED contains control functions for several bays, the local/remote position can
be different for the included bays. When the local HMI is used the position of the
local/remote switch can be different depending on which single line diagram screen
page that is presented on the local HMI. The function block Local remote control
(LOCREMCTRL) controls the presentation of the LEDs for the local/remote
position to applicable bay and screen page.

The switching of the local/remote switch requires at least system operator level.
The password will be requested at an attempt to operate if authority levels have
been defined in the IED. Otherwise the default authority level, SuperUser, can
handle the control without LogOn. The users and passwords are defined in PCM600.

12.3.5.3 Function block


LOCREM
CTRLOFF OFF
LOCCTRL LOCAL
REMCTRL REMOTE
LHMICTRL VALID

IEC05000360-2-en.vsd
IEC05000360 V2 EN

Figure 283: LOCREM function block

522
Technical reference manual
1MRK505183-UEN C Section 12
Control

LOCREMCTRL
PSTO1 HMICTR1
PSTO2 HMICTR2
PSTO3 HMICTR3
PSTO4 HMICTR4
PSTO5 HMICTR5
PSTO6 HMICTR6
PSTO7 HMICTR7
PSTO8 HMICTR8
PSTO9 HMICTR9
PSTO10 HMICTR10
PSTO11 HMICTR11
PSTO12 HMICTR12

IEC05000361-2-en.vsd
IEC05000361 V2 EN

Figure 284: LOCREMCTRL function block

12.3.5.4 Input and output signals


Table 303: LOCREM Input signals
Name Type Default Description
CTRLOFF BOOLEAN 0 Disable control
LOCCTRL BOOLEAN 0 Local in control
REMCTRL BOOLEAN 0 Remote in control
LHMICTRL INTEGER 0 LHMI control

Table 304: LOCREM Output signals


Name Type Description
OFF BOOLEAN Control is disabled
LOCAL BOOLEAN Local control is activated
REMOTE BOOLEAN Remote control is activated
VALID BOOLEAN Outputs are valid

Table 305: LOCREMCTRL Input signals


Name Type Default Description
PSTO1 INTEGER 0 PSTO input channel 1
PSTO2 INTEGER 0 PSTO input channel 2
PSTO3 INTEGER 0 PSTO input channel 3
PSTO4 INTEGER 0 PSTO input channel 4
PSTO5 INTEGER 0 PSTO input channel 5
PSTO6 INTEGER 0 PSTO input channel 6
PSTO7 INTEGER 0 PSTO input channel 7
PSTO8 INTEGER 0 PSTO input channel 8
PSTO9 INTEGER 0 PSTO input channel 9
Table continues on next page

523
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Default Description


PSTO10 INTEGER 0 PSTO input channel 10
PSTO11 INTEGER 0 PSTO input channel 11
PSTO12 INTEGER 0 PSTO input channel 12

Table 306: LOCREMCTRL Output signals


Name Type Description
HMICTR1 INTEGER Bitmask output 1 to local remote LHMI input
HMICTR2 INTEGER Bitmask output 2 to local remote LHMI input
HMICTR3 INTEGER Bitmask output 3 to local remote LHMI input
HMICTR4 INTEGER Bitmask output 4 to local remote LHMI input
HMICTR5 INTEGER Bitmask output 5 to local remote LHMI input
HMICTR6 INTEGER Bitmask output 6 to local remote LHMI input
HMICTR7 INTEGER Bitmask output 7 to local remote LHMI input
HMICTR8 INTEGER Bitmask output 8 to local remote LHMI input
HMICTR9 INTEGER Bitmask output 9 to local remote LHMI input
HMICTR10 INTEGER Bitmask output 10 to local remote LHMI input
HMICTR11 INTEGER Bitmask output 11 to local remote LHMI input
HMICTR12 INTEGER Bitmask output 12 to local remote LHMI input

12.3.5.5 Setting parameters


Table 307: LOCREM Non group settings (basic)
Name Values (Range) Unit Step Default Description
ControlMode Internal LR-switch - - Internal LR-switch Control mode for internal/external LR-
External LR-switch switch

12.3.6 Switch controller SCSWI

12.3.6.1 Introduction

The Switch controller (SCSWI) initializes and supervises all functions to properly
select and operate switching primary apparatuses. The Switch controller may
handle and operate on one three-phase device.

12.3.6.2 Principle of operation

The Switch controller (SCSWI) is provided with verification checks for the select -
execute sequence, that is, checks the conditions prior each step of the operation.
The involved functions for these condition verifications are interlocking,
reservation, blockings and synchrocheck.

524
Technical reference manual
1MRK505183-UEN C Section 12
Control

Control handling
.
Two types of control models can be used. The two control models are "direct with
normal security" and "SBO (Select-Before-Operate) with enhanced security". The
parameter CtlModel defines which one of the two control models is used. The
control model "direct with normal security" does not require a select whereas, the
"SBO with enhanced security" command model requires a select before execution.

The parameter CtlModel's alternative settings Dir Norm and Dir


Norm (ABB) have identical functionality and so have SBO Enh
(ABB) and SBO Enh.

Normal security means that only the command is evaluated and the resulting
position is not supervised. Enhanced security means that the command sequence is
supervised in three steps, the selection, command evaluation and the supervision of
position. Each step ends up with a pulsed signal to indicate that the respective step
in the command sequence is finished. If an error occurs in one of the steps in the
command sequence, the sequence is terminated and the error is mapped into the
enumerated variable "cause" attribute belonging to the pulsed response signal for
the IEC 61850 communication. The last cause L_CAUSE can be read from the
function block and used for example at commissioning.

There is no relation between the command direction and the actual


position. For example, if the switch is in close position it is possible
to execute a close command.

Before an execution command, an evaluation of the position is done. If the


parameter PosDependent is true and the position is in intermediate state or in bad
state no execution command is sent. If the parameter is false the execution
command is sent independent of the position value.

Evaluation of position
In the case when there are three one-phase switches connected to the switch control
function, the switch control will "merge" the position of the three switches to the
resulting three-phase position. In the case when the position differ between the one-
phase switches, following principles will be applied:

The position output from switch (SXCBR or SXSWI) is connected to SCSWI.


With the group signal connection the SCSWI obtains the position, time stamps and
quality attributes of the position which is used for further evaluation.

All switches in open position: switch control position = open


All switches in close position: switch control position = close
One switch =open, two switches= close (or switch control position = intermediate
inversely):
Any switch in intermediate position: switch control position = intermediate
Any switch in bad state: switch control position = bad state

525
Technical reference manual
Section 12 1MRK505183-UEN C
Control

The time stamp of the output three-phase position from switch control will have the
time stamp of the last changed phase when it goes to end position. When it goes to
intermediate position or bad state, it will get the time stamp of the first changed phase.

In addition, there is also the possibility that one of the one-phase switches will
change position at any time due to a trip. Such situation is here called pole
discordance and is supervised by this function. In case of a pole discordance
situation, that is, the position of the one-phase switches are not equal for a time
longer than the setting tPoleDiscord, an error signal POLEDISC will be set.

In the supervision phase, the switch controller function evaluates the "cause"
values from the switch modules Circuit breaker (SXCBR)/ Circuit switch
(SXSWI). At error the "cause" value with highest priority is shown.

Blocking principles
The blocking signals are normally coming from the bay control function (QCBAY)
and via the IEC 61850 communication from the operator place.

The different blocking possibilities are:

• Block/deblock of command. It is used to block command for operation of


position.
• Blocking of function, BLOCK, signal from DO (Data Object) Behavior (IEC
61850). If DO Behavior is set to "blocked" it means that the function is active,
but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.

The different block conditions will only affect the operation of this
function, that is, no blocking signals will be "forwarded" to other
functions. The above blocking outputs are stored in a non-volatile
memory.

Interaction with synchrocheck and synchronizing functions


The Switch controller (SCSWI) works in conjunction with the synchrocheck and
the synchronizing function (SESRSYN). It is assumed that the synchrocheck
function is continuously in operation and gives the result to SCSWI. The result
from the synchrocheck function is evaluated during the close execution. If the
operator performs an override of the synchrocheck, the evaluation of the
synchrocheck state is omitted. When there is a positive confirmation from the
synchrocheck function, SCSWI will send the close signal EXE_CL to the switch
function Circuit breaker (SXCBR).

When there is no positive confirmation from the synchrocheck function, SCSWI


will send a start signal START_SY to the synchronizing function, which will send
the closing command to SXCBR when the synchronizing conditions are fulfilled,
see figure 285. If no synchronizing function is included, the timer for supervision
of the "synchronizing in progress signal" is set to 0, which means no start of the

526
Technical reference manual
1MRK505183-UEN C Section 12
Control

synchronizing function. SCSWI will then set the attribute "blocked-by-


synchrocheck" in the "cause" signal. See also the time diagram in figure 289.

SCSWI SXCBR
EXE_CL
OR CLOSE

SYNC_OK

START_SY

SY_INPRO
SESRSYN

CLOSECB
Synchro Synchronizing
check function

IEC09000209_1_en.vsd
IEC09000209 V1 EN

Figure 285: Example of interaction between SCSWI, SESRSYN (synchrocheck


and synchronizing function) and SXCBR function

Time diagrams
The Switch controller (SCSWI) function has timers for evaluating different time
supervision conditions. These timers are explained here.

The timer tSelect is used for supervising the time between the select and the
execute command signal, that is, the time the operator has to perform the command
execution after the selection of the object to operate.

select
execute command
tSelect
timer t1 t1>tSelect, then long-
operation-time in 'cause'
is set

en05000092.vsd
IEC05000092 V1 EN

Figure 286: tSelect

The parameter tResResponse is used to set the maximum allowed time to make the
reservation, that is, the time between reservation request and the feedback
reservation granted from all bays involved in the reservation function.

527
Technical reference manual
Section 12 1MRK505183-UEN C
Control

select

reservation request RES_RQ

reservation granted RES_GRT

command termination
tResResponse t1>tResResponse, then
timer 1-of-n-control in 'cause'
t1 is set
en05000093.vsd

IEC05000093 V1 EN

Figure 287: tResResponse

The timer tExecutionFB supervises the time between the execute command and the
command termination, see figure 288.

execute command

position L1 open

close

position L2 open

close

position L3 open

close

cmd termination L1

cmd termination L2

cmd termination L3

cmd termination *

position open

close

tExecutionFB t1>tExecutionFB, then


timer long-operation-time in
t1 'cause' is set

* The cmd termination will be delayed one execution sample.


en05000094.vsd
IEC05000094 V1 EN

Figure 288: tExecutionFB

The parameter tSynchrocheck is used to define the maximum allowed time between
the execute command and the input SYNC_OK to become true. If SYNC_OK=true
at the time the execute command signal is received, the timer "tSynchrocheck" will
not start. The start signal for the synchronizing is obtained if the synchrocheck
conditions are not fulfilled.

528
Technical reference manual
1MRK505183-UEN C Section 12
Control

execute command

SYNC_OK

tSynchrocheck
t1
START_SY

SY_INPRO

tSynchronizing t2>tSynchronizing, then


t2 blocked-by-synchrocheck in
'cause' is set

en05000095.vsd

IEC05000095 V1 EN

Figure 289: tSynchroCheck and tSynchronizing

12.3.6.3 Function block


SCSWI
BLOCK EXE_OP
PSTO EXE_CL
L_SEL SELECTED
L_OPEN RES_RQ
L_CLOSE START_SY
AU_OPEN POSITION
AU_CLOSE OPENPOS
BL_CMD CLOSEPOS
RES_GRT POLEDISC
RES_EXT CMD_BLK
SY_INPRO L_CAUSE
SYNC_OK XOUT
EN_OPEN POS_INTR
EN_CLOSE
XPOS1
XPOS2
XPOS3

IEC05000337-2-en.vsd
IEC05000337 V2 EN

Figure 290: SCSWI function block

12.3.6.4 Input and output signals


Table 308: SCSWI Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 2 Operator place selection
L_SEL BOOLEAN 0 Select signal from local panel
L_OPEN BOOLEAN 0 Open signal from local panel
L_CLOSE BOOLEAN 0 Close signal from local panel
AU_OPEN BOOLEAN 0 Used for local automation function
AU_CLOSE BOOLEAN 0 Used for local automation function
BL_CMD BOOLEAN 0 Steady signal for block of the command
Table continues on next page

529
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Default Description


RES_GRT BOOLEAN 0 Positive acknowledge that all reservations are
made
RES_EXT BOOLEAN 0 Reservation is made externally
SY_INPRO BOOLEAN 0 Synchronizing function in progress
SYNC_OK BOOLEAN 0 Closing is permitted at set to true by the
synchrocheck
EN_OPEN BOOLEAN 0 Enables open operation
EN_CLOSE BOOLEAN 0 Enables close operation
XPOS1 GROUP - Pos 1
SIGNAL
XPOS2 GROUP - Pos 2
SIGNAL
XPOS3 GROUP - Pos 3
SIGNAL

Table 309: SCSWI Output signals


Name Type Description
EXE_OP BOOLEAN Execute command for open direction
EXE_CL BOOLEAN Execute command for close direction
SELECTED BOOLEAN The select conditions are fulfilled
RES_RQ BOOLEAN Request signal to the reservation function
START_SY BOOLEAN Starts the synchronizing function
POSITION INTEGER Position indication
OPENPOS BOOLEAN Open position indication
CLOSEPOS BOOLEAN Closed position indication
POLEDISC BOOLEAN The positions for poles L1-L3 are not equal after
a set time
CMD_BLK BOOLEAN Commands are blocked
L_CAUSE INTEGER Latest value of the error indication during command
XOUT BOOLEAN Execution information to XCBR/XSWI
POS_INTR BOOLEAN Stopped in intermediate position

530
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.3.6.5 Setting parameters


Table 310: SCSWI Non group settings (basic)
Name Values (Range) Unit Step Default Description
CtlModel Dir Norm - - SBO Enh Specifies the type for control model
SBO Enh (ABB) according to IEC 61850
Dir Norm (ABB)
SBO Enh
PosDependent Always permitted - - Always permitted Permission to operate depending on the
Not perm at 00/11 position
tSelect 0.000 - 60.000 s 0.001 30.000 Max time between select and execute
signals
tResResponse 0.000 - 60.000 s 0.001 5.000 Allowed time from reservation request to
reservation granted
tSynchrocheck 0.00 - 600.00 s 0.01 10.00 Allowed time for synchrocheck to fulfil
close conditions
tSynchronizing 0.00 - 600.00 s 0.01 0.00 Supervision time to get the signal
synchronizing in progress
tExecutionFB 0.00 - 600.00 s 0.01 30.00 Max time from command execution to
termination
tPoleDiscord 0.000 - 60.000 s 0.001 2.000 Allowed time to have discrepancy
between the poles

12.3.7 Circuit breaker SXCBR

12.3.7.1 Introduction

The purpose of Circuit breaker (SXCBR) is to provide the actual status of positions
and to perform the control operations, that is, pass all the commands to primary
apparatuses in the form of circuit breakers via output boards and to supervise the
switching operation and position.

12.3.7.2 Principle of operation

The users of the Circuit breaker function (SXCBR) is other functions such as for
example, switch controller, protection functions, autorecloser function or an IEC
61850 client residing in another IED or the operator place. This switch function
executes commands, evaluates block conditions and evaluates different time
supervision conditions. Only if all conditions indicate a switch operation to be
allowed, the function performs the execution command. In case of erroneous
conditions, the function indicates an appropriate "cause" value.

SXCBR has an operation counter for closing and opening commands. The counter
value can be read remotely from the operator place. The value is reset from a
binary input or remotely from the operator place by configuring a signal from the
Single Point Generic Control 8 signals (SPC8GGIO) for example.

531
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Local/Remote switch
One binary input signal LR_SWI is included in SXCBR to indicate the local/
remote switch position from switchyard provided via the I/O board. If this signal is
set to TRUE it means that change of position is allowed only from switchyard
level. If the signal is set to FALSE it means that command from IED or higher
level is permitted. When the signal is set to TRUE all commands (for change of
position) from internal IED clients are rejected, even trip commands from
protection functions are rejected. The functionality of the local/remote switch is
described in figure 291.

Local= Operation at
RU
E switch yard level
T

From I/O switchLR


FAL
SE
Remote= Operation at
IED or higher level

en05000096.vsd
IEC05000096 V1 EN

Figure 291: Local/Remote switch

Blocking principles
SXCBR includes several blocking principles. The basic principle for all blocking
signals is that they will affect commands from all other clients for example,
operators place, protection functions, autoreclosure and so on.

The blocking possibilities are:

• Block/deblock for open command. It is used to block operation for open


command. Note that this block signal also affects the input OPEN for
immediate command.
• Block/deblock for close command. It is used to block operation for close
command. Note that this block signal also affects the input CLOSE for
immediate command.
• Update block/deblock of positions. It is used to block the updating of position
values. Other signals related to the position will be reset.
• Blocking of function, BLOCK, signal from DO (Data Object) Behavior (IEC
61850). If DO Behavior is set to "blocked" it means that the function is active,
but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.

The above blocking outputs are stored in a non-volatile memory.

Substitution
The substitution part in SXCBR is used for manual set of the position for the
switch. The typical use of substitution is that an operator enters a manual value
because that the real process value is erroneous for some reason. SXCBR will then

532
Technical reference manual
1MRK505183-UEN C Section 12
Control

use the manually entered value instead of the value for positions determined by the
process.

It is always possible to make a substitution, independently of the


position indication and the status information of the I/O board.
When substitution is enabled, the position values are blocked for
updating and other signals related to the position are reset. The
substituted values are stored in a non-volatile memory.

Time diagrams
There are two timers for supervising of the execute phase, tStartMove and
tIntermediate. tStartMove supervises that the primary device starts moving after the
execute output pulse is sent. tIntermediate defines the maximum allowed time for
intermediate position. Figure 292 explains these two timers during the execute phase.

EXE_CL AdaptivePulse = TRUE


Close pulse duration

OPENPOS

CLOSEPOS

if t1 > tStartMove then


tStartMove timer "switch-not-start-moving"
t1 attribute in 'cause' is set
tStartMove

if t2 > tIntermediate then


tIntermediate timer "persisting-intermediate-state"
t2 attribute in 'cause' is set
tIntermediate

en05000097.vsd

IEC05000097 V1 EN

Figure 292: The timers tStartMove and tIntermediate

The timers tOpenPulse and tClosePulse are the length of the execute output pulses
to be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be
adaptive with the configuration parameter AdaptivePulse. Figure 293 shows the
principle of the execute output pulse. The AdaptivePulse parameter will have affect
on both execute output pulses.

533
Technical reference manual
Section 12 1MRK505183-UEN C
Control

OPENPOS

CLOSEPOS

AdaptivePulse=FALSE
EXE_CL
tClosePulse

AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN

Figure 293: Execute output pulse

If the pulse is set to be adaptive, it is not possible for the pulse to exceed
tOpenPulse or tClosePulse.

The execute output pulses are reset when:

• the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.

There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in closed
position and a close command is executed. In these cases, with the additional
condition that the configuration parameter AdaptivePulse is true, the execute output
pulse is always activated and resets when tStartMove has elapsed. If the
configuration parameter AdaptivePulse is set to false the execution output remains
active until the pulse duration timer has elapsed.

If the start position indicates bad state (OPENPOS=1 and


CLOSEPOS =1) when a command is executed the execute output
pulse resets only when timer tOpenPulse or tClosePulse has elapsed.

An example of when a primary device is open and an open command is executed is


shown in figure 294 .

534
Technical reference manual
1MRK505183-UEN C Section 12
Control

OPENPOS

CLOSEPOS

EXE_OP AdaptivePulse=FALSE

tOpenPulse

EXE_OP AdaptivePulse=TRUE

tOpenPulse

tStartMove timer

en05000099.vsd
IEC05000099 V1 EN

Figure 294: Open command with open position indication

12.3.7.3 Function block


SXCBR
BLOCK XPOS
LR_SWI EXE_OP
OPEN EXE_CL
CLOSE SUBSTED
BL_OPEN OP_BLKD
BL_CLOSE CL_BLKD
BL_UPD UPD_BLKD
POSOPEN POSITION
POSCLOSE OPENPOS
TR_OPEN CLOSEPOS
TR_CLOSE TR_POS
RS_CNT CNT_VAL
XIN L_CAUSE

IEC05000338-2-en.vsd
IEC05000338 V2 EN

Figure 295: SXCBR function block

12.3.7.4 Input and output signals


Table 311: SXCBR Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
LR_SWI BOOLEAN 0 Local/Remote switch indication from switchyard
OPEN BOOLEAN 0 Pulsed signal used to immediately open the switch
CLOSE BOOLEAN 0 Pulsed signal used to immediately close the switch
BL_OPEN BOOLEAN 0 Signal to block the open command
BL_CLOSE BOOLEAN 0 Signal to block the close command
BL_UPD BOOLEAN 0 Steady signal for block of the position updating
Table continues on next page

535
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Default Description


POSOPEN BOOLEAN 0 Signal for open position of apparatus from I/O
POSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/O
TR_OPEN BOOLEAN 0 Signal for open position of truck from I/O
TR_CLOSE BOOLEAN 0 Signal for close position of truck from I/O
RS_CNT BOOLEAN 0 Resets the operation counter
XIN BOOLEAN 0 Execution information from CSWI

Table 312: SXCBR Output signals


Name Type Description
XPOS GROUP SIGNAL Group signal for XCBR output
EXE_OP BOOLEAN Executes the command for open direction
EXE_CL BOOLEAN Executes the command for close direction
SUBSTED BOOLEAN Indication that the position is substituted
OP_BLKD BOOLEAN Indication that the function is blocked for open
commands
CL_BLKD BOOLEAN Indication that the function is blocked for close
commands
UPD_BLKD BOOLEAN The update of position indication is blocked
POSITION INTEGER Apparatus position indication
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
TR_POS INTEGER Truck position indication
CNT_VAL INTEGER The value of the operation counter
L_CAUSE INTEGER Latest value of the error indication during command

12.3.7.5 Setting parameters


Table 313: SXCBR Non group settings (basic)
Name Values (Range) Unit Step Default Description
tStartMove 0.000 - 60.000 s 0.001 0.100 Supervision time for the apparatus to
move after a command
tIntermediate 0.000 - 60.000 s 0.001 0.150 Allowed time for intermediate position
AdaptivePulse Not adaptive - - Not adaptive The output resets when a new correct
Adaptive end position is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close command

12.3.8 Circuit switch SXSWI

536
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.3.8.1 Introduction

The purpose of Circuit switch (SXSWI) function is to provide the actual status of
positions and to perform the control operations, that is, pass all the commands to
primary apparatuses in the form of disconnectors or earthing switches via output
boards and to supervise the switching operation and position.

12.3.8.2 Principle of operation

The users of the Circuit switch (SXSWI) is other functions such as for example,
switch controller, protection functions, autorecloser function, or a 61850 client
residing in another IED or the operator place. SXSWI executes commands,
evaluates block conditions and evaluates different time supervision conditions.
Only if all conditions indicate a switch operation to be allowed, SXSWI performs
the execution command. In case of erroneous conditions, the function indicates an
appropriate "cause" value.

SXSWI has an operation counter for closing and opening commands. The counter
value can be read remotely from the operator place. The value is reset from a
binary input or remotely from the operator place by configuring a signal from the
Single Point Generic Control 8 signals (SPC8GGIO) for example.

Local/Remote switch
One binary input signal LR_SWI is included in SXSWI to indicate the local/remote
switch position from switchyard provided via the I/O board. If this signal is set to
TRUE it means that change of position is allowed only from switchyard level. If
the signal is set to FALSE it means that command from IED or higher level is
permitted. When the signal is set to TRUE all commands (for change of position)
from internal IED clients are rejected, even trip commands from protection
functions are rejected. The functionality of the local/remote switch is described in
figure 296.

Local= Operation at
RU
E switch yard level
T

From I/O switchLR


FAL
SE
Remote= Operation at
IED or higher level

en05000096.vsd
IEC05000096 V1 EN

Figure 296: Local/Remote switch

Blocking principles
SXSWI includes several blocking principles. The basic principle for all blocking
signals is that they will affect commands from all other clients for example,
operators place, protection functions, autorecloser and so on.

537
Technical reference manual
Section 12 1MRK505183-UEN C
Control

The blocking possibilities are:

• Block/deblock for open command. It is used to block operation for open


command. Note that this block signal also affects the input OPEN for
immediate command.
• Block/deblock for close command. It is used to block operation for close
command. Note that this block signal also affects the input CLOSE for
immediate command.
• Update block/deblock of positions. It is used to block the updating of position
values. Other signals related to the position will be reset.
• Blocking of function, BLOCK, signal from DO (Data Object) Behavior (IEC
61850). If DO Behavior is set to "blocked" it means that the function is active,
but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.

The above blocking outputs are stored in a non-volatile memory.

Substitution
The substitution part in SXSWI is used for manual set of the position for the
switch. The typical use of substitution is that an operator enters a manual value
because the real process value is erroneous of some reason. SXSWI will then use
the manually entered value instead of the value for positions determined by the
process.

It is always possible to make a substitution, independently of the


position indication and the status information of the I/O board.
When substitution is enabled, the position values are blocked for
updating and other signals related to the position are reset. The
substituted values are stored in a non-volatile memory.

Time diagrams
There are two timers for supervising of the execute phase, tStartMove and
tIntermediate. tStartMove supervises that the primary device starts moving after the
execute output pulse is sent. tIntermediate defines the maximum allowed time for
intermediate position. Figure 297 explains these two timers during the execute phase.

538
Technical reference manual
1MRK505183-UEN C Section 12
Control

EXE_CL AdaptivePulse = TRUE


Close pulse duration

OPENPOS

CLOSEPOS

if t1 > tStartMove then


tStartMove timer "switch-not-start-moving"
t1 attribute in 'cause' is set
tStartMove

if t2 > tIntermediate then


tIntermediate timer "persisting-intermediate-state"
t2 attribute in 'cause' is set
tIntermediate

en05000097.vsd

IEC05000097 V1 EN

Figure 297: The timers tStartMove and tIntermediate

The timers tOpenPulse and tClosePulse are the length of the execute output pulses
to be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be
adaptive with the configuration parameter AdaptivePulse. Figure 298 shows the
principle of the execute output pulse. The AdaptivePulse parameter will have affect
on both execute output pulses.

OPENPOS

CLOSEPOS

AdaptivePulse=FALSE
EXE_CL
tClosePulse

AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN

Figure 298: Execute output pulse

If the pulse is set to be adaptive, it is not possible for the pulse to exceed
tOpenPulse or tClosePulse.

The execute output pulses are reset when:

539
Technical reference manual
Section 12 1MRK505183-UEN C
Control

If the start position indicates bad state (OPENPOS=1 and


CLOSEPOS =1) when a command is executed the execute output
pulse resets only when timer tOpenPulse or tClosePulse has elapsed.

• the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.

There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in close
position and a close command is executed. In these cases, with the additional
condition that the configuration parameter AdaptivePulse is true, the execute output
pulse is always activated and resets when tStartMove has elapsed. If the
configuration parameter AdaptivePulse is set to false the execution output remains
active until the pulse duration timer has elapsed.

An example when a primary device is open and an open command is executed is


shown in figure 299.

OPENPOS

CLOSEPOS

EXE_OP AdaptivePulse=FALSE

tOpenPulse

EXE_OP AdaptivePulse=TRUE

tOpenPulse

tStartMove timer

en05000099.vsd
IEC05000099 V1 EN

Figure 299: Open command with open position indication

540
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.3.8.3 Function block


SXSWI
BLOCK XPOS
LR_SWI EXE_OP
OPEN EXE_CL
CLOSE SUBSTED
BL_OPEN OP_BLKD
BL_CLOSE CL_BLKD
BL_UPD UPD_BLKD
POSOPEN POSITION
POSCLOSE OPENPOS
RS_CNT CLOSEPOS
XIN CNT_VAL
L_CAUSE

IEC05000339-2-en.vsd
IEC05000339 V2 EN

Figure 300: SXSWI function block

12.3.8.4 Input and output signals


Table 314: SXSWI Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
LR_SWI BOOLEAN 0 Local/Remote switch indication from switchyard
OPEN BOOLEAN 0 Pulsed signal used to immediately open the switch
CLOSE BOOLEAN 0 Pulsed signal used to immediately close the switch
BL_OPEN BOOLEAN 0 Signal to block the open command
BL_CLOSE BOOLEAN 0 Signal to block the close command
BL_UPD BOOLEAN 0 Steady signal for block of the position updating
POSOPEN BOOLEAN 0 Signal for open position of apparatus from I/O
POSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/O
RS_CNT BOOLEAN 0 Resets the operation counter
XIN BOOLEAN 0 Execution information from CSWI

Table 315: SXSWI Output signals


Name Type Description
XPOS GROUP SIGNAL Group signal for XSWI output
EXE_OP BOOLEAN Executes the command for open direction
EXE_CL BOOLEAN Executes the command for close direction
SUBSTED BOOLEAN Indication that the position is substituted
OP_BLKD BOOLEAN Indication that the function is blocked for open
commands
CL_BLKD BOOLEAN Indication that the function is blocked for close
commands
UPD_BLKD BOOLEAN The update of position indication is blocked
POSITION INTEGER Apparatus position indication
Table continues on next page

541
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Description


OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
CNT_VAL INTEGER The value of the operation counter
L_CAUSE INTEGER Latest value of the error indication during command

12.3.8.5 Setting parameters


Table 316: SXSWI Non group settings (basic)
Name Values (Range) Unit Step Default Description
tStartMove 0.000 - 60.000 s 0.001 3.000 Supervision time for the apparatus to
move after a command
tIntermediate 0.000 - 60.000 s 0.001 15.000 Allowed time for intermediate position
AdaptivePulse Not adaptive - - Not adaptive The output resets when a new correct
Adaptive end position is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close command
SwitchType Load Break - - Disconnector Switch Type
Disconnector
Earthing Switch
HS Earthing Switch

12.3.9 Bay reserve QCRSV

12.3.9.1 Introduction

The purpose of the reservation function is primarily to transfer interlocking


information between IEDs in a safe way and to prevent double operation in a bay,
switchyard part, or complete substation.

12.3.9.2 Principle of operation

The Bay reserve (QCRSV) function handles the reservation. QCRSV function
starts to operate in two ways. It starts when there is a request for reservation of the
own bay or if there is a request for reservation from another bay. It is only possible
to reserve the function if it is not currently reserved. The signal that can reserve the
own bay is the input signal RES_RQx (x=1-8) coming from switch controller
(SCWI). The signals for request from another bay are the outputs RE_RQ_B and
V_RE_RQ from function block RESIN. These signals are included in signal
EXCH_OUT from RESIN and are connected to RES_DATA in QCRSV.

The parameters ParamRequestx (x=1-8) are chosen at reservation of the own bay
only (TRUE) or other bays (FALSE). To reserve the own bay only means that no
reservation request RES_BAYS is created.

542
Technical reference manual
1MRK505183-UEN C Section 12
Control

Reservation request of own bay


If the reservation request comes from the own bay, the function QCRSV has to
know which apparatus the request comes from. This information is available with
the input signal RES_RQx and parameter ParamRequestx (where x=1-8 is the
number of the requesting apparatus). In order to decide if a reservation request of
the current bay can be permitted QCRSV has to know whether the own bay already
is reserved by itself or another bay. This information is available in the output
signal RESERVED.

If the RESERVED output is not set, the selection is made with the output
RES_GRTx (where x=1-8 is the number of the requesting apparatus), which is
connected to switch controller SCSWI. If the bay already is reserved the command
sequence will be reset and the SCSWI will set the attribute "1-of-n-control" in the
"cause" signal.

Reservation of other bays


When the function QCRSV receives a request from an apparatus in the own bay
that requires other bays to be reserved as well, it checks if it already is reserved. If
not, it will send a request to the other bays that are predefined (to be reserved) and
wait for their response (acknowledge). The request of reserving other bays is done
by activating the output RES_BAYS.

When it receives acknowledge from the bays via the input RES_DATA, it sets the
output RES_GRTx (where x=1-8 is the number of the requesting apparatus). If not
acknowledgement from all bays is received within a certain time defined in SCSWI
(tResResponse), the SCSWI will reset the reservation and set the attribute "1-of-n-
control" in the "cause" signal.

Reservation request from another bay


When another bay requests for reservation, the input BAY_RES in corresponding
function block RESIN is activated. The signal for reservation request is grouped
into the output signal EXCH_OUT in RESIN, which is connected to input
RES_DATA in QCRSV. If the bay is not reserved, the bay will be reserved and the
acknowledgment from output ACK_T_B is sent back to the requested bay. If the
bay already is reserved the reservation is kept and no acknowledgment is sent.

Blocking and overriding of reservation


If QCRSV function is blocked (input BLK_RES is set to true) the reservation is
blocked. That is, no reservation can be made from the own bay or any other bay.
This can be set, for example, via a binary input from an external device to prevent
operations from another operator place at the same time.

The reservation function can also be overridden in the own bay with the
OVERRIDE input signal, that is, reserving the own bay without waiting for the
external acknowledge.

Bay with more than eight apparatuses


If only one instance of QCRSV is used for a bay that is, use of up to eight
apparatuses, the input EXCH_IN must be set to FALSE.

543
Technical reference manual
Section 12 1MRK505183-UEN C
Control

If there are more than eight apparatuses in the bay there has to be one additional
QCRSV. The two QCRSV functions have to communicate and this is done through
the input EXCH_IN and EXCH_OUT according to figure 301. If more then one
QCRSV are used, the execution order is very important. The execution order must
be in the way that the first QCRSV has a lower number than the next one.

QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_RQ2 RES_GRT3
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6
RES_RQ6 RES_GRT7
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLK_RES ACK_TO_B
OVERRIDE RESERVED
RES_DATA EXCH_OUT

QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_BAYS
RES_RQ2 RES_GRT3 ³1
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6 ACK_TO_B
RES_RQ6 RES_GRT7 ³1
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLK_RES ACK_TO_B RESERVED
³1
OVERRIDE RESERVED
RES_DATA EXCH_OUT

IEC05000088_2_en.vsd
IEC05000088 V2 EN

Figure 301: Connection of two QCRSV function blocks

12.3.9.3 Function block


QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_RQ2 RES_GRT3
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6
RES_RQ6 RES_GRT7
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLK_RES ACK_TO_B
OVERRIDE RESERVED
RES_DATA EXCH_OUT

IEC05000340-2-en.vsd
IEC05000340 V2 EN

Figure 302: QCRSV function block

544
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.3.9.4 Input and output signals


Table 317: QCRSV Input signals
Name Type Default Description
EXCH_IN INTEGER 0 Used for exchange signals between different
BayRes blocks
RES_RQ1 BOOLEAN 0 Signal for app. 1 that requests to do a reservation
RES_RQ2 BOOLEAN 0 Signal for app. 2 that requests to do a reservation
RES_RQ3 BOOLEAN 0 Signal for app. 3 that requests to do a reservation
RES_RQ4 BOOLEAN 0 Signal for app. 4 that requests to do a reservation
RES_RQ5 BOOLEAN 0 Signal for app. 5 that requests to do a reservation
RES_RQ6 BOOLEAN 0 Signal for app. 6 that requests to do a reservation
RES_RQ7 BOOLEAN 0 Signal for app. 7 that requests to do a reservation
RES_RQ8 BOOLEAN 0 Signal for app. 8 that requests to do a reservation
BLK_RES BOOLEAN 0 Reservation is not possible and the output signals
are reset
OVERRIDE BOOLEAN 0 Signal to override the reservation
RES_DATA INTEGER 0 Reservation data coming from function block ResIn

Table 318: QCRSV Output signals


Name Type Description
RES_GRT1 BOOLEAN Reservation is made and the app. 1 is allowed to
operate
RES_GRT2 BOOLEAN Reservation is made and the app. 2 is allowed to
operate
RES_GRT3 BOOLEAN Reservation is made and the app. 3 is allowed to
operate
RES_GRT4 BOOLEAN Reservation is made and the app. 4 is allowed to
operate
RES_GRT5 BOOLEAN Reservation is made and the app. 5 is allowed to
operate
RES_GRT6 BOOLEAN Reservation is made and the app. 6 is allowed to
operate
RES_GRT7 BOOLEAN Reservation is made and the app. 7 is allowed to
operate
RES_GRT8 BOOLEAN Reservation is made and the app. 8 is allowed to
operate
RES_BAYS BOOLEAN Request for reservation of other bays
ACK_TO_B BOOLEAN Acknowledge to other bays that this bay is reserved
RESERVED BOOLEAN Indicates that the bay is reserved
EXCH_OUT INTEGER Used for exchange signals between different
BayRes blocks

545
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.3.9.5 Setting parameters


Table 319: QCRSV Non group settings (basic)
Name Values (Range) Unit Step Default Description
tCancelRes 0.000 - 60.000 s 0.001 10.000 Supervision time for canceling the
reservation
ParamRequest1 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 1
ParamRequest2 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 2
ParamRequest3 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 3
ParamRequest4 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 4
ParamRequest5 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 5
ParamRequest6 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 6
ParamRequest7 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 7
ParamRequest8 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 8

12.3.10 Reservation input RESIN

12.3.10.1 Introduction

The Reservation input (RESIN) function receives the reservation information from
other bays. The number of instances is the same as the number of involved bays
(up to 60 instances are available).

12.3.10.2 Principle of operation

The reservation input (RESIN) function is based purely on Boolean logic


conditions. The logic diagram in figure 303 shows how the output signals are
created. The inputs of the function block are connected to a receive function block
representing signals transferred over the station bus from another bay.

546
Technical reference manual
1MRK505183-UEN C Section 12
Control

EXCH_IN INT

BIN

ACK_F_B
&
FutureUse
³1

ANY_ACK
BAY_ACK ³1

VALID_TX
&

BAY_VAL ³1

RE_RQ_B
³1

BAY_RES &
V _RE_RQ
³1

BIN
EXCH_OUT
INT

en05000089.vsd
IEC05000089 V1 EN

Figure 303: Logic diagram for RESIN

Figure 304 describes the principle of the data exchange between all RESIN
modules in the current bay. There is one RESIN function block per "other bay"
used in the reservation mechanism. The output signal EXCH_OUT in the last
RESIN functions are connected to the module bay reserve (QCRSV) that handles
the reservation function in the own bay. The value to the input EXCH_IN on the
first RESIN module in the chain has the integer value 5. This is provided by the use
of instance number one of the function block RESIN, where the input EXCH_IN is
set to #5, but is hidden for the user.

547
Technical reference manual
Section 12 1MRK505183-UEN C
Control

RESIN
BAY_ACK ACK_F_B
Bay 1 BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT

RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
Bay 2 BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT

RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
Bay n BAY_VAL VALID_TX
BAY_RES RE_RQ_B QCRSV
V_RE_RQ
EXCH_OUT RES_DATA

en05000090.vsd
IEC05000090 V2 EN

Figure 304: Diagram of the chaining principle for RESIN

12.3.10.3 Function block


RESIN1
BAY_ACK ACK_F_B
BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT

IEC05000341-2-en.vsd
IEC05000341 V2 EN

Figure 305: RESIN1 function block

RESIN2
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC09000807_1_en.vsd
IEC09000807 V1 EN

Figure 306: RESIN2 function block

548
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.3.10.4 Input and output signals


Table 320: RESIN1 Input signals
Name Type Default Description
BAY_ACK BOOLEAN 0 Another bay has acknow. the reservation req.
from this bay
BAY_VAL BOOLEAN 0 The reserv. and acknow. signals from another
bay are valid
BAY_RES BOOLEAN 0 Request from other bay to reserve this bay

Table 321: RESIN1 Output signals


Name Type Description
ACK_F_B BOOLEAN All other bays have acknow. the reserv. req. from
this bay
ANY_ACK BOOLEAN Any other bay has acknow. the reserv. req. from
this bay
VALID_TX BOOLEAN The reserv. and acknow. signals from other bays
are valid
RE_RQ_B BOOLEAN Request from other bay to reserve this bay
V_RE_RQ BOOLEAN Check if the request of reserving this bay is valid
EXCH_OUT INTEGER Used for exchange signals between different
ResIn blocks

Table 322: RESIN2 Input signals


Name Type Default Description
EXCH_IN INTEGER 5 Used for exchange signals between different
ResIn blocks
BAY_ACK BOOLEAN 0 Another bay has acknow. the reservation req.
from this bay
BAY_VAL BOOLEAN 0 The reserv. and acknow. signals from another
bay are valid
BAY_RES BOOLEAN 0 Request from other bay to reserve this bay

Table 323: RESIN2 Output signals


Name Type Description
ACK_F_B BOOLEAN All other bays have acknow. the reserv. req. from
this bay
ANY_ACK BOOLEAN Any other bay has acknow. the reserv. req. from
this bay
VALID_TX BOOLEAN The reserv. and acknow. signals from other bays
are valid
RE_RQ_B BOOLEAN Request from other bay to reserve this bay
V_RE_RQ BOOLEAN Check if the request of reserving this bay is valid
EXCH_OUT INTEGER Used for exchange signals between different
ResIn blocks

549
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.3.10.5 Setting parameters


Table 324: RESIN1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
FutureUse Bay in use - - Bay in use The bay for this ResIn block is for future
Bay future use use

Table 325: RESIN2 Non group settings (basic)


Name Values (Range) Unit Step Default Description
FutureUse Bay in use - - Bay in use The bay for this ResIn block is for future
Bay future use use

12.4 Interlocking

12.4.1 Introduction
The interlocking function blocks the possibility to operate high-voltage switching
devices, for instance when a disconnector is under load, in order to prevent
material damage and/or accidental human injury.

Each control IED has interlocking functions for different switchyard arrangements,
each handling the interlocking of one bay. The function is distributed to each
control IED and not dependent on any central function. For the station-wide
interlocking, the IEDs communicate via the station bus or by using hard wired
binary inputs/outputs.

The interlocking conditions depend on the circuit configuration and status of the
installation at any given time.

12.4.2 Principle of operation


The interlocking function consists of software modules located in each control
IED. The function is distributed and not dependent on any central function.
Communication between modules in different bays is performed via the station bus.

The reservation function (see section "Introduction") is used to ensure that HV


apparatuses that might affect the interlock are blocked during the time gap, which
arises between position updates. This can be done by means of the communication
system, reserving all HV apparatuses that might influence the interlocking
condition of the intended operation. The reservation is maintained until the
operation is performed.

After the selection and reservation of an apparatus, the function has complete data
on the status of all apparatuses in the switchyard that are affected by the selection.

550
Technical reference manual
1MRK505183-UEN C Section 12
Control

Other operators cannot interfere with the reserved apparatus or the status of
switching devices that may affect it.

The open or closed positions of the HV apparatuses are inputs to software modules
distributed in the control IEDs. Each module contains the interlocking logic for a
bay. The interlocking logic in a module is different, depending on the bay function
and the switchyard arrangements, that is, double-breaker or 1 1/2 breaker bays have
different modules. Specific interlocking conditions and connections between
standard interlocking modules are performed with an engineering tool. Bay-level
interlocking signals can include the following kind of information:

• Positions of HV apparatuses (sometimes per phase)


• Valid positions (if evaluated in the control module)
• External release (to add special conditions for release)
• Line voltage (to block operation of line earthing switch)
• Output signals to release the HV apparatus

The interlocking module is connected to the surrounding functions within a bay as


shown in figure 307.

Apparatus control
Interlocking
modules
modules in
SCILO SCSWI
other bays SXSWI

Apparatus control
modules
Interlocking SCILO SCSWI SXCBR
module

Apparatus control
modules
en04000526.vsd SCILO SCSWI SXSWI

IEC04000526 V1 EN

Figure 307: Interlocking module on bay level

Bays communicate via the station bus and can convey information regarding the
following:

• Unearthed busbars
• Busbars connected together
• Other bays connected to a busbar
• Received data from other bays is valid

Figure 308 illustrates the data exchange principle.

551
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Station bus

Bay 1 Bay n Bus coupler

Disc QB1 and QB2 closed Disc QB1 and QB2 closed WA1 unearthed
WA1 unearthed
WA1 and WA2 interconn

...
WA1 not earthed WA1 not earthed
WA2 not earthed WA2 not earthed WA1 and WA2 interconn
WA1 and WA2 interconn WA1 and WA2 interconn in other bay

..
WA1

WA2
QB1 QB2 QB1 QB2 QB1 QB2 QC1 QC2

QA1 QA1 QA1

QB9 QB9

en05000494.vsd
IEC05000494 V1 EN

Figure 308: Data exchange between interlocking modules

When invalid data such as intermediate position, loss of a control IED, or input
board error are used as conditions for the interlocking condition in a bay, a release
for execution of the function will not be given.

On the local HMI an override function exists, which can be used to bypass the
interlocking function in cases where not all the data required for the condition is valid.

For all interlocking modules these general rules apply:

• The interlocking conditions for opening or closing of disconnectors and


earthing switches are always identical.
• Earthing switches on the line feeder end, for example, rapid earthing switches,
are normally interlocked only with reference to the conditions in the bay where
they are located, not with reference to switches on the other side of the line. So
a line voltage indication may be included into line interlocking modules. If
there is no line voltage supervision within the bay, then the appropriate inputs
must be set to no voltage, and the operator must consider this when operating.
• Earthing switches can only be operated on isolated sections for example,
without load/voltage. Circuit breaker contacts cannot be used to isolate a
section, that is, the status of the circuit breaker is irrelevant as far as the
earthing switch operation is concerned.
• Disconnectors cannot break power current or connect different voltage
systems. Disconnectors in series with a circuit breaker can only be operated if
the circuit breaker is open, or if the disconnectors operate in parallel with other
closed connections. Other disconnectors can be operated if one side is
completely isolated, or if the disconnectors operate in parallel to other closed
connections, or if they are earthed on both sides.
• Circuit breaker closing is only interlocked against running disconnectors in its
bay or additionally in a transformer bay against the disconnectors and earthing

552
Technical reference manual
1MRK505183-UEN C Section 12
Control

switch on the other side of the transformer, if there is no disconnector between


CB and transformer.
• Circuit breaker opening is only interlocked in a bus-coupler bay, if a bus bar
transfer is in progress.

To make the implementation of the interlocking function easier, a number of


standardized and tested software interlocking modules containing logic for the
interlocking conditions are available:

• Line for double and transfer busbars, ABC_LINE


• Bus for double and transfer busbars, ABC_BC
• Transformer bay for double busbars, AB_TRAFO
• Bus-section breaker for double busbars, A1A2_BS
• Bus-section disconnector for double busbars, A1A2_DC
• Busbar earthing switch, BB_ES
• Double CB Bay, DB_BUS_A, DB_LINE, DB_BUS_B
• 1 1/2-CB diameter, BH_LINE_A, BH_CONN, BH_LINE_B

The interlocking conditions can be altered, to meet the customer specific


requirements, by adding configurable logic by means of the graphical configuration
tool PCM600. The inputs Qx_EXy on the interlocking modules are used to add
these specific conditions.

The input signals EXDU_xx shall be set to true if there is no transmission error at
the transfer of information from other bays. Required signals with designations
ending in TR are intended for transfer to other bays.

12.4.3 Logical node for interlocking SCILO

12.4.3.1 Introduction

The Logical node for interlocking SCILO function is used to enable a switching
operation if the interlocking conditions permit. SCILO function itself does not
provide any interlocking functionality. The interlocking conditions are generated in
separate function blocks containing the interlocking logic.

12.4.3.2 Logic diagram

The function contains logic to enable the open and close commands respectively if
the interlocking conditions are fulfilled. That means also, if the switch has a
defined end position for example, open, then the appropriate enable signal (in this
case EN_OPEN) is false. The enable signals EN_OPEN and EN_CLOSE can be
true at the same time only in the intermediate and bad position state and if they are
enabled by the interlocking function. The position inputs come from the logical
nodes Circuit breaker/Circuit switch (SXCBR/SXSWI) and the enable signals

553
Technical reference manual
Section 12 1MRK505183-UEN C
Control

come from the interlocking logic. The outputs are connected to the logical node
Switch controller (SCSWI). One instance per switching device is needed.

POSOPEN SCILO
POSCLOSE =1 1
EN_OPEN
&
>1
&

OPEN_EN
CLOSE_EN & EN_CLOSE
>1
&
en04000525.vsd

IEC04000525 V1 EN

Figure 309: SCILO function logic diagram

12.4.3.3 Function block


SCILO
POSOPEN EN_OPEN
POSCLOSE EN_CLOSE
OPEN_EN
CLOSE_EN

IEC05000359-2-en.vsd
IEC05000359 V2 EN

Figure 310: SCILO function block

12.4.3.4 Input and output signals


Table 326: SCILO Input signals
Name Type Default Description
POSOPEN BOOLEAN 0 Open position of switch device
POSCLOSE BOOLEAN 0 Closed position of switch device
OPEN_EN BOOLEAN 0 Open operation from interlocking logic is enabled
CLOSE_EN BOOLEAN 0 Close operation from interlocking logic is enabled

Table 327: SCILO Output signals


Name Type Description
EN_OPEN BOOLEAN Open operation at closed or interm. or bad pos. is
enabled
EN_CLOSE BOOLEAN Close operation at open or interm. or bad pos. is
enabled

12.4.4 Interlocking for busbar earthing switch BB_ES

554
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.4.4.1 Introduction

The interlocking for busbar earthing switch (BB_ES) function is used for one
busbar earthing switch on any busbar parts according to figure 311.

QC

en04000504.vsd
IEC04000504 V1 EN

Figure 311: Switchyard layout BB_ES

12.4.4.2 Function block


BB_ES
QC_OP QCREL
QC_CL QCITL
BB_DC_OP BBESOPTR
VP_BB_DC BBESCLTR
EXDU_BB

IEC05000347-2-en.vsd
IEC05000347 V2 EN

Figure 312: BB_ES function block

12.4.4.3 Logic diagram


BB_ES
VP_BB_DC QCREL
BB_DC_OP QCITL
EXDU_BB & 1

QC_OP BBESOPTR
QC_CL BBESCLTR
en04000546.vsd

IEC04000546 V1 EN

12.4.4.4 Input and output signals


Table 328: BB_ES Input signals
Name Type Default Description
QC_OP BOOLEAN 0 Busbar earthing switch QC is in open position
QC_CL BOOLEAN 0 Busbar earthing switch QC is in closed position
BB_DC_OP BOOLEAN 0 All disconnectors on this busbar part are open
VP_BB_DC BOOLEAN 0 Status for all disconnectors on this busbar part
are valid
EXDU_BB BOOLEAN 0 No transm error from bays with disc on this
busbar part

555
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Table 329: BB_ES Output signals


Name Type Description
QCREL BOOLEAN Switching of QC is allowed
QCITL BOOLEAN Switching of QC is forbidden
BBESOPTR BOOLEAN QC on this busbar part is in open position
BBESCLTR BOOLEAN QC on this busbar part is in closed position

12.4.5 Interlocking for bus-section breaker A1A2_BS

12.4.5.1 Introduction

The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-
section circuit breaker between section 1 and 2 according to figure 313. The
function can be used for different busbars, which includes a bus-section circuit
breaker.

WA1 (A1) WA2 (A2)

QC1 QB1 QB2 QC2

QA1

QC3 QC4

en04000516.vsd
A1A2_BS
IEC04000516 V1 EN

Figure 313: Switchyard layout A1A2_BS

556
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.4.5.2 Function block


A1A2_BS
QA1_OP QA1OPREL
QA1_CL QA1OPITL
QB1_OP QA1CLREL
QB1_CL QA1CLITL
QB2_OP QB1REL
QB2_CL QB1ITL
QC3_OP QB2REL
QC3_CL QB2ITL
QC4_OP QC3REL
QC4_CL QC3ITL
S1QC1_OP QC4REL
S1QC1_CL QC4ITL
S2QC2_OP S1S2OPTR
S2QC2_CL S1S2CLTR
BBTR_OP QB1OPTR
VP_BBTR QB1CLTR
EXDU_12 QB2OPTR
EXDU_ES QB2CLTR
QA1O_EX1 VPS1S2TR
QA1O_EX2 VPQB1TR
QA1O_EX3 VPQB2TR
QB1_EX1
QB1_EX2
QB2_EX1
QB2_EX2

IEC05000348-2-en.vsd
IEC05000348 V2 EN

Figure 314: A1A2_BS function block

557
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.4.5.3 Logic diagram


A1A2_BS
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB2_OP
QB2_CL =1 VPQB2
QC3_OP
QC3_CL =1 VPQC3
QC4_OP
QC4_CL =1 VPQC4
S1QC1_OP
S1QC1_CL =1 VPS1QC1
S2QC2_OP
S2QC2_CL =1 VPS2QC2
VPQB1
QB1_OP QA1OPREL
& >1
QA1O_EX1 QA1OPITL
1
VPQB2
QB2_OP
&
QA1O_EX2
VP_BBTR
BBTR_OP
&
EXDU_12
QA1O_EX3

VPQB1 QA1CLREL
VPQB2 & QA1CLITL
1
VPQA1
VPQC3 QB1REL
& >1
VPQC4 QB1ITL
1
VPS1QC1
QA1_OP
QC3_OP
QC4_OP
S1QC1_OP
EXDU_ES
QB1_EX1

VPQC3
VPS1QC1
&
QC3_CL
S1QC1_CL
EXDU_ES
QB1_EX2

en04000542.vsd

IEC04000542 V1 EN

558
Technical reference manual
1MRK505183-UEN C Section 12
Control

VPQA1
VPQC3 QB2REL
VPQC4 & >1
QB2ITL
VPS2QC2 1
QA1_OP
QC3_OP
QC4_OP
S2QC2_OP
EXDU_ES
QB2_EX1
VPQC4
VPS2QC2
&
QC4_CL
S2QC2_CL
EXDU_ES
QB2_EX2

VPQB1 QC3REL
VPQB2 QC3ITL
QB1_OP & 1
QC4REL
QB2_OP
QC4ITL
1

QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR

QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB1_OP S1S2OPTR
QB2_OP >1 S1S2CLTR
QA1_OP 1
VPQB1
VPS1S2TR
VPQB2 &
VPQA1
en04000543.vsd

IEC04000543 V1 EN

12.4.5.4 Input and output signals


Table 330: A1A2_BS Input signals
Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QC4_OP BOOLEAN 0 QC4 is in open position
QC4_CL BOOLEAN 0 QC4 is in closed position
S1QC1_OP BOOLEAN 0 QC1 on bus section 1 is in open position
S1QC1_CL BOOLEAN 0 QC1 on bus section 1 is in closed position
S2QC2_OP BOOLEAN 0 QC2 on bus section 2 is in open position
S2QC2_CL BOOLEAN 0 QC2 on bus section 2 is in closed position
BBTR_OP BOOLEAN 0 No busbar transfer is in progress
VP_BBTR BOOLEAN 0 Status are valid for app. involved in the busbar
transfer
Table continues on next page

559
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Default Description


EXDU_12 BOOLEAN 0 No transm error from any bay connected to
busbar 1 and 2
EXDU_ES BOOLEAN 0 No transm error from bays containing earth. sw.
QC1 or QC2
QA1O_EX1 BOOLEAN 0 External open condition for apparatus QA1
QA1O_EX2 BOOLEAN 0 External open condition for apparatus QA1
QA1O_EX3 BOOLEAN 0 External open condition for apparatus QA1
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2

Table 331: A1A2_BS Output signals


Name Type Description
QA1OPREL BOOLEAN Opening of QA1 is allowed
QA1OPITL BOOLEAN Opening of QA1 is forbidden
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QC3REL BOOLEAN Switching of QC3 is allowed
QC3ITL BOOLEAN Switching of QC3 is forbidden
QC4REL BOOLEAN Switching of QC4 is allowed
QC4ITL BOOLEAN Switching of QC4 is forbidden
S1S2OPTR BOOLEAN No bus section connection between bus section 1
and 2
S1S2CLTR BOOLEAN Bus coupler connection between bus section 1
and 2 exists
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
VPS1S2TR BOOLEAN Status of the app. between bus section 1 and 2
are valid
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)

12.4.6 Interlocking for bus-section disconnector A1A2_DC

560
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.4.6.1 Introduction

The interlocking for bus-section disconnector (A1A2_DC) function is used for one
bus-section disconnector between section 1 and 2 according to figure 315.
A1A2_DC function can be used for different busbars, which includes a bus-section
disconnector.

QB
WA1 (A1) WA2 (A2)

QC1 QC2

A1A2_DC en04000492.vsd

IEC04000492 V1 EN

Figure 315: Switchyard layout A1A2_DC

12.4.6.2 Function block


A1A2_DC
QB_OP QBOPREL
QB_CL QBOPITL
S1QC1_OP QBCLREL
S1QC1_CL QBCLITL
S2QC2_OP DCOPTR
S2QC2_CL DCCLTR
S1DC_OP VPDCTR
S2DC_OP
VPS1_DC
VPS2_DC
EXDU_ES
EXDU_BB
QBCL_EX1
QBCL_EX2
QBOP_EX1
QBOP_EX2
QBOP_EX3

IEC05000349-2-en.vsd
IEC05000349 V2 EN

Figure 316: A1A2_DC function block

561
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.4.6.3 Logic diagram


A1A2_DC
QB_OP
VPQB VPDCTR
QB_CL =1
DCOPTR
DCCLTR
S1QC1_OP
VPS1QC1
S1QC1_CL =1
S2QC2_OP
VPS2QC2
S2QC2_CL =1
VPS1QC1
VPS2QC2
VPS1_DC & >1 QBOPREL
S1QC1_OP QBOPITL
1
S2QC2_OP
S1DC_OP
EXDU_ES

EXDU_BB
QBOP_EX1

VPS1QC1
VPS2QC2
VPS2_DC &
S1QC1_OP
S2QC2_OP
S2DC_OP
EXDU_ES

EXDU_BB
QBOP_EX2

VPS1QC1
VPS2QC2
S1QC1_CL &
S2QC2_CL
EXDU_ES
QBOP_EX3

en04000544.vsd

IEC04000544 V1 EN

IEC04000545 V1 EN

12.4.6.4 Input and output signals


Table 332: A1A2_DC Input signals
Name Type Default Description
QB_OP BOOLEAN 0 QB is in open position
QB_CL BOOLEAN 0 QB is in closed position
S1QC1_OP BOOLEAN 0 QC1 on bus section 1 is in open position
S1QC1_CL BOOLEAN 0 QC1 on bus section 1 is in closed position
Table continues on next page

562
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Type Default Description


S2QC2_OP BOOLEAN 0 QC2 on bus section 2 is in open position
S2QC2_CL BOOLEAN 0 QC2 on bus section 2 is in closed position
S1DC_OP BOOLEAN 0 All disconnectors on bus section 1 are in open
position
S2DC_OP BOOLEAN 0 All disconnectors on bus section 2 are in open
position
VPS1_DC BOOLEAN 0 Switch status of disconnectors on bus section 1
are valid
VPS2_DC BOOLEAN 0 Switch status of disconnectors on bus section 2
are valid
EXDU_ES BOOLEAN 0 No transm error from bays containing earth. sw.
QC1 or QC2
EXDU_BB BOOLEAN 0 No transm error from bays with disc conn to
section 1 and 2
QBCL_EX1 BOOLEAN 0 External close condition for section disconnector
QB
QBCL_EX2 BOOLEAN 0 External close condition for section disconnector
QB
QBOP_EX1 BOOLEAN 0 External open condition for section disconnector
QB
QBOP_EX2 BOOLEAN 0 External open condition for section disconnector
QB
QBOP_EX3 BOOLEAN 0 External open condition for section disconnector
QB

Table 333: A1A2_DC Output signals


Name Type Description
QBOPREL BOOLEAN Opening of QB is allowed
QBOPITL BOOLEAN Opening of QB is forbidden
QBCLREL BOOLEAN Closing of QB is allowed
QBCLITL BOOLEAN Closing of QB is forbidden
DCOPTR BOOLEAN The bus section disconnector is in open position
DCCLTR BOOLEAN The bus section disconnector is in closed position
VPDCTR BOOLEAN Switch status of QB is valid (open or closed)

12.4.7 Interlocking for bus-coupler bay ABC_BC

12.4.7.1 Introduction

The interlocking for bus-coupler bay (ABC_BC) function is used for a bus-coupler
bay connected to a double busbar arrangement according to figure 317. The
function can also be used for a single busbar arrangement with transfer busbar or
double busbar arrangement without transfer busbar.

563
Technical reference manual
Section 12 1MRK505183-UEN C
Control

WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB20 QB7
QC1

QA1

QC2

en04000514.vsd
IEC04000514 V1 EN

Figure 317: Switchyard layout ABC_BC

12.4.7.2 Function block


ABC_BC
QA1_OP QA1OPREL
QA1_CL QA1OPITL
QB1_OP QA1CLREL
QB1_CL QA1CLITL
QB2_OP QB1REL
QB2_CL QB1ITL
QB7_OP QB2REL
QB7_CL QB2ITL
QB20_OP QB7REL
QB20_CL QB7ITL
QC1_OP QB20REL
QC1_CL QB20ITL
QC2_OP QC1REL
QC2_CL QC1ITL
QC11_OP QC2REL
QC11_CL QC2ITL
QC21_OP QB1OPTR
QC21_CL QB1CLTR
QC71_OP QB220OTR
QC71_CL QB220CTR
BBTR_OP QB7OPTR
BC_12_CL QB7CLTR
VP_BBTR QB12OPTR
VP_BC_12 QB12CLTR
EXDU_ES BC12OPTR
EXDU_12 BC12CLTR
EXDU_BC BC17OPTR
QA1O_EX1 BC17CLTR
QA1O_EX2 BC27OPTR
QA1O_EX3 BC27CLTR
QB1_EX1 VPQB1TR
QB1_EX2 VQB220TR
QB1_EX3 VPQB7TR
QB2_EX1 VPQB12TR
QB2_EX2 VPBC12TR
QB2_EX3 VPBC17TR
QB20_EX1 VPBC27TR
QB20_EX2
QB7_EX1
QB7_EX2

IEC05000350-2-en.vsd
IEC05000350 V2 EN

Figure 318: ABC_BC function block

564
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.4.7.3 Logic diagram


ABC_BC
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB20_OP
QB20_CL =1 VPQB20
QB7_OP
QB7_CL =1 VPQB7
QB2_OP
QB2_CL =1 VPQB2
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
QC71_OP
QC71_CL =1 VPQC71
VPQB1
QB1_OP QA1OPREL
& >1 QA1OPITL
QA1O_EX1 1
VPQB20
QB20_OP &
QA1O_EX2
VP_BBTR
BBTR_OP &
EXDU_12
QA1O_EX3
VPQB1 QA1CLREL
VPQB2 QA1CLITL
VPQB7 & 1
VPQB20
en04000533.vsd

IEC04000533 V1 EN

VPQA1
VPQB2 QB1REL
& >1
VPQC1 QB1ITL
VPQC2 1
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VP_BC_12
&
QB2_CL
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX3

en04000534.vsd

IEC04000534 V1 EN

565
Technical reference manual
Section 12 1MRK505183-UEN C
Control

VPQA1
VPQB1 QB2REL
& >1
VPQC1 QB2ITL
VPQC2 1
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VP_BC_12
&
QB1_CL
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC21
&
QC1_CL
QC21_CL
EXDU_ES
QB2_EX3

en04000535.vsd

IEC04000535 V1 EN

VPQA1
VPQB20 QB7REL
& >1
VPQC1 QB7ITL
VPQC2 1
VPQC71
QA1_OP
QB20_OP
QC1_OP
QC2_OP
QC71_OP
EXDU_ES
QB7_EX1
VPQC2
VPQC71
&
QC2_CL
QC71_CL
EXDU_ES
QB7_EX2
VPQA1
VPQB7 QB20REL
& >1
VPQC1 QB20ITL
VPQC2 1
VPQC21
QA1_OP
QB7_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB20_EX1
VPQC2
VPQC21
&
QC2_CL
QC21_CL
EXDU_ES
QB20_EX2

en04000536.vsd

IEC04000536 V1 EN

566
Technical reference manual
1MRK505183-UEN C Section 12
Control

VPQB1 QC1REL
VPQB20 QC1ITL
& 1
VPQB7
QC2REL
VPQB2
QB1_OP QC2ITL
1
QB20_OP
QB7_OP
QB2_OP
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB20_OP QB220OTR
QB2_OP & QB220CTR
VPQB20 1
VQB220TR
VPQB2 &
QB7_OP QB7OPTR
QB7_CL QB7CLTR
VPQB7 VPQB7TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
QA1_OP BC12OPTR
QB1_OP >1 BC12CLTR
QB20_OP 1
VPQA1
VPBC12TR
VPQB1 &
VPQB20
QA1_OP BC17OPTR
QB1_OP >1 BC17CLTR
QB7_OP 1
VPQA1
VPBC17TR
VPQB1 &
VPQB7
QA1_OP BC27OPTR
QB2_OP >1 BC27CLTR
QB7_OP 1
VPQA1
VPBC27TR
VPQB2 &
VPQB7
en04000537.vsd

IEC04000537 V1 EN

12.4.7.4 Input and output signals


Table 334: ABC_BC Input signals
Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QB7_OP BOOLEAN 0 QB7 is in open position
QB7_CL BOOLEAN 0 QB7 is in closed position
QB20_OP BOOLEAN 0 QB20 is in open position
QB20_CL BOOLEAN 0 QB20 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC11_OP BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in open
position
Table continues on next page

567
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Default Description


QC11_CL BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in closed
position
QC21_OP BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in open
position
QC21_CL BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in closed
position
QC71_OP BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in open
position
QC71_CL BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in closed
position
BBTR_OP BOOLEAN 0 No busbar transfer is in progress
BC_12_CL BOOLEAN 0 A bus coupler connection exists between busbar
WA1 and WA2
VP_BBTR BOOLEAN 0 Status are valid for app. involved in the busbar
transfer
VP_BC_12 BOOLEAN 0 Status of the bus coupler app. between WA1 and
WA2 are valid
EXDU_ES BOOLEAN 0 No transm error from any bay containing earthing
switches
EXDU_12 BOOLEAN 0 No transm error from any bay connected to WA1/
WA2 busbars
EXDU_BC BOOLEAN 0 No transmission error from any other bus coupler
bay
QA1O_EX1 BOOLEAN 0 External open condition for apparatus QA1
QA1O_EX2 BOOLEAN 0 External open condition for apparatus QA1
QA1O_EX3 BOOLEAN 0 External open condition for apparatus QA1
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB1_EX3 BOOLEAN 0 External condition for apparatus QB1
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2
QB2_EX3 BOOLEAN 0 External condition for apparatus QB2
QB20_EX1 BOOLEAN 0 External condition for apparatus QB20
QB20_EX2 BOOLEAN 0 External condition for apparatus QB20
QB7_EX1 BOOLEAN 0 External condition for apparatus QB7
QB7_EX2 BOOLEAN 0 External condition for apparatus QB7

Table 335: ABC_BC Output signals


Name Type Description
QA1OPREL BOOLEAN Opening of QA1 is allowed
QA1OPITL BOOLEAN Opening of QA1 is forbidden
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
Table continues on next page

568
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Type Description


QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QB7REL BOOLEAN Switching of QB7 is allowed
QB7ITL BOOLEAN Switching of QB7 is forbidden
QB20REL BOOLEAN Switching of QB20 is allowed
QB20ITL BOOLEAN Switching of QB20 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
QB220OTR BOOLEAN QB2 and QB20 are in open position
QB220CTR BOOLEAN QB2 or QB20 or both are not in open position
QB7OPTR BOOLEAN QB7 is in open position
QB7CLTR BOOLEAN QB7 is in closed position
QB12OPTR BOOLEAN QB1 or QB2 or both are in open position
QB12CLTR BOOLEAN QB1 and QB2 are not in open position
BC12OPTR BOOLEAN No connection via the own bus coupler between
WA1 and WA2
BC12CLTR BOOLEAN Conn. exists via the own bus coupler between
WA1 and WA2
BC17OPTR BOOLEAN No connection via the own bus coupler between
WA1 and WA7
BC17CLTR BOOLEAN Conn. exists via the own bus coupler between
WA1 and WA7
BC27OPTR BOOLEAN No connection via the own bus coupler between
WA2 and WA7
BC27CLTR BOOLEAN Conn. exists via the own bus coupler between
WA2 and WA7
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)
VQB220TR BOOLEAN Switch status of QB2 and QB20 are valid (open
or closed)
VPQB7TR BOOLEAN Switch status of QB7 is valid (open or closed)
VPQB12TR BOOLEAN Switch status of QB1 and QB2 are valid (open or
closed)
VPBC12TR BOOLEAN Status of the bus coupler app. between WA1 and
WA2 are valid
VPBC17TR BOOLEAN Status of the bus coupler app. between WA1 and
WA7 are valid
VPBC27TR BOOLEAN Status of the bus coupler app. between WA2 and
WA7 are valid

569
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.4.8 Interlocking for 1 1/2 CB BH

12.4.8.1 Introduction

Introduction
The interlocking for 1 1/2 breaker diameter (BH_CONN, BH_LINE_A,
BH_LINE_B) functions are used for lines connected to a 1 1/2 breaker diameter
according to figure 319.

WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC1

QA1 QA1

QC2 QC2

QB6 QB6

QC3 QC3
BH_LINE_A BH_LINE_B

QB61 QA1 QB62

QB9 QB9
QC1 QC2
QC9 QC9

BH_CONN
en04000513.vsd

IEC04000513 V1 EN

Figure 319: Switchyard layout 1 1/2 breaker

Three types of interlocking modules per diameter are defined. BH_LINE_A and
BH_LINE_B are the connections from a line to a busbar. BH_CONN is the
connection between the two lines of the diameter in the 1 1/2 breaker switchyard
layout.

570
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.4.8.2 Function blocks


BH_LINE_A
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB6_OP QB6REL
QB6_CL QB6ITL
QB1_OP QB1REL
QB1_CL QB1ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC3_OP QC3REL
QC3_CL QC3ITL
QB9_OP QB9REL
QB9_CL QB9ITL
QC9_OP QC9REL
QC9_CL QC9ITL
CQA1_OP QB1OPTR
CQA1_CL QB1CLTR
CQB61_OP VPQB1TR
CQB61_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
QC11_OP
QC11_CL
VOLT_OFF
VOLT_ON
EXDU_ES
QB6_EX1
QB6_EX2
QB1_EX1
QB1_EX2
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
QB9_EX6
QB9_EX7

IEC05000352-2-en.vsd
IEC05000352 V2 EN

Figure 320: BH_LINE_A function block

571
Technical reference manual
Section 12 1MRK505183-UEN C
Control

BH_LINE_B
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB6_OP QB6REL
QB6_CL QB6ITL
QB2_OP QB2REL
QB2_CL QB2ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC3_OP QC3REL
QC3_CL QC3ITL
QB9_OP QB9REL
QB9_CL QB9ITL
QC9_OP QC9REL
QC9_CL QC9ITL
CQA1_OP QB2OPTR
CQA1_CL QB2CLTR
CQB62_OP VPQB2TR
CQB62_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
QC21_OP
QC21_CL
VOLT_OFF
VOLT_ON
EXDU_ES
QB6_EX1
QB6_EX2
QB2_EX1
QB2_EX2
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
QB9_EX6
QB9_EX7

IEC05000353-2-en.vsd
IEC05000353 V2 EN

Figure 321: BH_LINE_B function block

BH_CONN
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB61_OP QB61REL
QB61_CL QB61ITL
QB62_OP QB62REL
QB62_CL QB62ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
1QC3_OP
1QC3_CL
2QC3_OP
2QC3_CL
QB61_EX1
QB61_EX2
QB62_EX1
QB62_EX2

IEC05000351-2-en.vsd
IEC05000351 V2 EN

Figure 322: BH_CONN function block

572
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.4.8.3 Logic diagrams


BH_CONN
QA1_OP
QA1_CL =1 VPQA1
QB61_OP
QB61_CL =1 VPQB61
QB62_OP
QB62_CL =1 VPQB62
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
1QC3_OP
1QC3_CL =1 VP1QC3
2QC3_OP
2QC3_CL =1 VP2QC3
VPQB61 QA1CLREL
VPQB62 & QA1CLITL
1
VPQA1
VPQC1 QB61REL
& >1
VPQC2 QB61ITL
1
VP1QC3
QA1_OP
QC1_OP
QC2_OP
1QC3_OP
QB61_EX1
VPQC1
VP1QC3
&
QC1_CL
1QC3_CL
QB61_EX2
VPQA1
VPQC1 QB62REL
& >1
VPQC2 QB62ITL
1
VP2QC3
QA1_OP
QC1_OP
QC2_OP
2QC3_OP
QB62_EX1
VPQC2
VP2QC3
&
QC2_CL
2QC3_CL
QB62_EX2
VPQB61 QC1REL
VPQB62 QC1ITL
& 1
QB61_OP QC2REL
QB62_OP QC2ITL
1
en04000560.vsd

IEC04000560 V1 EN

573
Technical reference manual
Section 12 1MRK505183-UEN C
Control

BH_LINE_A
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB6_OP
QB6_CL =1 VPQB6
QC9_OP
QC9_CL =1 VPQC9
QB9_OP
QB9_CL =1 VPQB9
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
CQA1_OP
CQA1_CL =1 VPCQA1
CQC1_OP
CQC1_CL =1 VPCQC1
CQC2_OP
CQC2_CL =1 VPCQC2
CQB61_OP
CQB61_CL =1 VPCQB61
QC11_OP
QC11_CL =1 VPQC11
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQB1 QA1CLREL
VPQB6 QA1CLITL
& 1
VPQB9
VPQA1
VPQC1 QB6REL
VPQC2 & >1
QB6ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB6_EX2
en04000554.vsd

IEC04000554 V1 EN

574
Technical reference manual
1MRK505183-UEN C Section 12
Control

VPQA1
VPQC1 QB1REL
VPQC2 & >1
QB1ITL
1
VPQC11
QA1_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1

VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2

VPQB1 QC1REL
VPQB6 QC1ITL
QB1_OP & 1
QC2REL
QB6_OP QC2ITL
VPQB6 1
VPQB9 QC3REL
VPCQB61 &
QC3ITL
1
QB6_OP
QB9_OP
CQB61_OP
VPQA1 QB9REL
VPQB6 QB9ITL
VPQC9 & >1 1

VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB61
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
>1
QA1_OP
QC1_OP
QC2_OP &
QB9_EX3

en04000555.vsd

IEC04000555 V1 EN

CQB61_OP
QB9_EX4
>1 & >1
CQA1_OP
CQC1_OP
CQC2_OP &
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
&
QC9_CL
QC3_CL
QB9_EX7
VPQB9 QC9REL
VPVOLT QC9ITL
QB9_OP & 1

VOLT_OFF
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
en04000556.vsd

IEC04000556 V1 EN

575
Technical reference manual
Section 12 1MRK505183-UEN C
Control

BH_LINE_B
QA1_OP
QA1_CL =1 VPQA1
QB2_OP
QB2_CL =1 VPQB2
QB6_OP
QB6_CL =1 VPQB6
QC9_OP
QC9_CL =1 VPQC9
QB9_OP
QB9_CL =1 VPQB9
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
CQA1_OP
CQA1_CL =1 VPCQA1
CQC1_OP
CQC1_CL =1 VPCQC1
CQC2_OP
CQC2_CL =1 VPCQC2
CQB62_OP
CQB62_CL =1 VPCQB62
QC21_OP
QC21_CL =1 VPQC21
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQB2 QA1CLREL
VPQB6 QA1CLITL
& 1
VPQB9
VPQA1
VPQC1 QB6REL
VPQC2 & >1
QB6ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB6_EX2
en04000557.vsd

IEC04000557 V1 EN

576
Technical reference manual
1MRK505183-UEN C Section 12
Control

VPQA1
VPQC1 QB2REL
VPQC2 & >1
QB2ITL
1
VPQC21
QA1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1

VPQC1
VPQC21
&
QC1_CL
QC21_CL
EXDU_ES
QB2_EX2

VPQB2 QC1REL
VPQB6 QC1ITL
QB2_OP & 1
QC2REL
QB6_OP QC2ITL
VPQB6 1
VPQB9 QC3REL
VPCQB62 &
QC3ITL
1
QB6_OP
QB9_OP
CQB62_OP
VPQA1 QB9REL
VPQB6 QB9ITL
VPQC9 & >1 1

VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB62
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
>1
QA1_OP
QC1_OP
QC2_OP &
QB9_EX3

en04000558.vsd

IEC04000558 V1 EN

CQB62_OP
QB9_EX4
>1 & >1
CQA1_OP
CQC1_OP
CQC2_OP &
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
&
QC9_CL
QC3_CL
QB9_EX7
VPQB9 QC9REL
VPVOLT QC9ITL
QB9_OP & 1

VOLT_OFF
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
en04000559.vsd

IEC04000559 V1 EN

577
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.4.8.4 Input and output signals


Table 336: BH_LINE_A Input signals
Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB6_OP BOOLEAN 0 QB6 is in open position
QB6_CL BOOLEAN 0 QB6 is in close position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QB9_OP BOOLEAN 0 QB9 is in open position
QB9_CL BOOLEAN 0 QB9 is in closed position
QC9_OP BOOLEAN 0 QC9 is in open position
QC9_CL BOOLEAN 0 QC9 is in closed position
CQA1_OP BOOLEAN 0 QA1 in module BH_CONN is in open position
CQA1_CL BOOLEAN 0 QA1 in module BH_CONN is in closed position
CQB61_OP BOOLEAN 0 QB61 in module BH_CONN is in open position
CQB61_CL BOOLEAN 0 QB61 in module BH_CONN is in closed position
CQC1_OP BOOLEAN 0 QC1 in module BH_CONN is in open position
CQC1_CL BOOLEAN 0 QC1 in module BH_CONN is in closed position
CQC2_OP BOOLEAN 0 QC2 in module BH_CONN is in open position
CQC2_CL BOOLEAN 0 QC2 in module BH_CONN is in closed position
QC11_OP BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in open
position
QC11_CL BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in closed
position
VOLT_OFF BOOLEAN 0 There is no voltage on line and not VT (fuse) failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse)
failure
EXDU_ES BOOLEAN 0 No transm error from bay containing earthing
switch QC11
QB6_EX1 BOOLEAN 0 External condition for apparatus QB6
QB6_EX2 BOOLEAN 0 External condition for apparatus QB6
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB9_EX1 BOOLEAN 0 External condition for apparatus QB9
Table continues on next page

578
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Type Default Description


QB9_EX2 BOOLEAN 0 External condition for apparatus QB9
QB9_EX3 BOOLEAN 0 External condition for apparatus QB9
QB9_EX4 BOOLEAN 0 External condition for apparatus QB9
QB9_EX5 BOOLEAN 0 External condition for apparatus QB9
QB9_EX6 BOOLEAN 0 External condition for apparatus QB9
QB9_EX7 BOOLEAN 0 External condition for apparatus QB9

Table 337: BH_LINE_A Output signals


Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB6REL BOOLEAN Switching of QB6 is allowed
QB6ITL BOOLEAN Switching of QB6 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QC3REL BOOLEAN Switching of QC3 is allowed
QC3ITL BOOLEAN Switching of QC3 is forbidden
QB9REL BOOLEAN Switching of QB9 is allowed
QB9ITL BOOLEAN Switching of QB9 is forbidden
QC9REL BOOLEAN Switching of QC9 is allowed
QC9ITL BOOLEAN Switching of QC9 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)

Table 338: BH_LINE_B Input signals


Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB6_OP BOOLEAN 0 QB6 is in open position
QB6_CL BOOLEAN 0 QB6 is in close position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
Table continues on next page

579
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Default Description


QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QB9_OP BOOLEAN 0 QB9 is in open position
QB9_CL BOOLEAN 0 QB9 is in closed position
QC9_OP BOOLEAN 0 QC9 is in open position
QC9_CL BOOLEAN 0 QC9 is in closed position
CQA1_OP BOOLEAN 0 QA1 in module BH_CONN is in open position
CQA1_CL BOOLEAN 0 QA1 in module BH_CONN is in closed position
CQB62_OP BOOLEAN 0 QB62 in module BH_CONN is in open position
CQB62_CL BOOLEAN 0 QB62 in module BH_CONN is in closed position
CQC1_OP BOOLEAN 0 QC1 in module BH_CONN is in open position
CQC1_CL BOOLEAN 0 QC1 in module BH_CONN is in closed position
CQC2_OP BOOLEAN 0 QC2 in module BH_CONN is in open position
CQC2_CL BOOLEAN 0 QC2 in module BH_CONN is in closed position
QC21_OP BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in open
position
QC21_CL BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in closed
position
VOLT_OFF BOOLEAN 0 There is no voltage on line and not VT (fuse) failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse)
failure
EXDU_ES BOOLEAN 0 No transm error from bay containing earthing
switch QC21
QB6_EX1 BOOLEAN 0 External condition for apparatus QB6
QB6_EX2 BOOLEAN 0 External condition for apparatus QB6
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2
QB9_EX1 BOOLEAN 0 External condition for apparatus QB9
QB9_EX2 BOOLEAN 0 External condition for apparatus QB9
QB9_EX3 BOOLEAN 0 External condition for apparatus QB9
QB9_EX4 BOOLEAN 0 External condition for apparatus QB9
QB9_EX5 BOOLEAN 0 External condition for apparatus QB9
QB9_EX6 BOOLEAN 0 External condition for apparatus QB9
QB9_EX7 BOOLEAN 0 External condition for apparatus QB9

580
Technical reference manual
1MRK505183-UEN C Section 12
Control

Table 339: BH_LINE_B Output signals


Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB6REL BOOLEAN Switching of QB6 is allowed
QB6ITL BOOLEAN Switching of QB6 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QC3REL BOOLEAN Switching of QC3 is allowed
QC3ITL BOOLEAN Switching of QC3 is forbidden
QB9REL BOOLEAN Switching of QB9 is allowed
QB9ITL BOOLEAN Switching of QB9 is forbidden
QC9REL BOOLEAN Switching of QC9 is allowed
QC9ITL BOOLEAN Switching of QC9 is forbidden
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)

Table 340: BH_CONN Input signals


Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB61_OP BOOLEAN 0 QB61 is in open position
QB61_CL BOOLEAN 0 QB61 is in closed position
QB62_OP BOOLEAN 0 QB62 is in open position
QB62_CL BOOLEAN 0 QB62 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
1QC3_OP BOOLEAN 0 QC3 on line 1 is in open position
1QC3_CL BOOLEAN 0 QC3 on line 1 is in closed position
2QC3_OP BOOLEAN 0 QC3 on line 2 is in open position
2QC3_CL BOOLEAN 0 QC3 on line 2 is in closed position
QB61_EX1 BOOLEAN 0 External condition for apparatus QB61
Table continues on next page

581
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Default Description


QB61_EX2 BOOLEAN 0 External condition for apparatus QB61
QB62_EX1 BOOLEAN 0 External condition for apparatus QB62
QB62_EX2 BOOLEAN 0 External condition for apparatus QB62

Table 341: BH_CONN Output signals


Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB61REL BOOLEAN Switching of QB61 is allowed
QB61ITL BOOLEAN Switching of QB61 is forbidden
QB62REL BOOLEAN Switching of QB62 is allowed
QB62ITL BOOLEAN Switching of QB62 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden

12.4.9 Interlocking for double CB bay DB

12.4.9.1 Introduction

The interlocking for 1 1/2 breaker diameter including DB_BUS_A, DB_BUS_B,


DB_LINEfunctions are used for a line connected to a double circuit breaker
arrangement according to figure 323.

582
Technical reference manual
1MRK505183-UEN C Section 12
Control

WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC4

QA1 QA2

DB_BUS_A DB_BUS_B
QC2 QC5

QB61 QB62

QC3

QB9
DB_LINE

QC9

en04000518.vsd
IEC04000518 V1 EN

Figure 323: Switchyard layout double circuit breaker

Three types of interlocking modules per double circuit breaker bay are defined.
DB_LINE is the connection from the line to the circuit breaker parts that are
connected to the busbars. DB_BUS_A and DB_BUS_B are the connections from
the line to the busbars.

12.4.9.2 Function block


IB01-
DB_BUS_A
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB1_OP QB61REL
QB1_CL QB61ITL
QB61_OP QB1REL
QB61_CL QB1ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC3_OP QB1OPTR
QC3_CL QB1CLTR
QC11_OP VPQB1TR
QC11_CL
EXDU_ES
QB61_EX1
QB61_EX2
QB1_EX1
QB1_EX2

en05000354.vsd
IEC05000354 V1 EN

Figure 324: IB function block

583
Technical reference manual
Section 12 1MRK505183-UEN C
Control

DB_LINE
QA1_OP QB9REL
QA1_CL QB9ITL
QA2_OP QC3REL
QA2_CL QC3ITL
QB61_OP QC9REL
QB61_CL QC9ITL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QB62_OP
QB62_CL
QC4_OP
QC4_CL
QC5_OP
QC5_CL
QB9_OP
QB9_CL
QC3_OP
QC3_CL
QC9_OP
QC9_CL
VOLT_OFF
VOLT_ON
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5

IEC05000356-2-en.vsd
IEC05000356 V2 EN

Figure 325: DB_LINE function block

DB_BUS_B
QA2_OP QA2CLREL
QA2_CL QA2CLITL
QB2_OP QB62REL
QB2_CL QB62ITL
QB62_OP QB2REL
QB62_CL QB2ITL
QC4_OP QC4REL
QC4_CL QC4ITL
QC5_OP QC5REL
QC5_CL QC5ITL
QC3_OP QB2OPTR
QC3_CL QB2CLTR
QC21_OP VPQB2TR
QC21_CL
EXDU_ES
QB62_EX1
QB62_EX2
QB2_EX1
QB2_EX2

IEC05000355-2-en.vsd
IEC05000355 V2 EN

Figure 326: DB_BUS_B function block

584
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.4.9.3 Logic diagrams


DB_BUS_A
QA1_OP
QA1_CL =1 VPQA1
QB61_OP
QB61_CL =1 VPQB61
QB1_OP
QB1_CL =1 VPQB1
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
QC11_OP
QC11_CL =1 VPQC11
VPQB61 QA1CLREL
VPQB1 & QA1CLITL
1
VPQA1
VPQC1 QB61REL
& >1
VPQC2 QB61ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB61_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB61_EX2
VPQA1
VPQC1 QB1REL
& >1
VPQC2 QB1ITL
1
VPQC11
QA1_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1

VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2

en04000547.vsd

IEC04000547 V1 EN

VPQB61 QC1REL
VPQB1 QC1ITL
& 1
QB61_OP QC2REL
QB1_OP QC2ITL
1
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
en04000548.vsd

IEC04000548 V1 EN

585
Technical reference manual
Section 12 1MRK505183-UEN C
Control

DB_BUS_B
QA2_OP
QA2_CL =1 VPQA2
QB62_OP
QB62_CL =1 VPQB62
QB2_OP
QB2_CL =1 VPQB2
QC4_OP
QC4_CL =1 VPQC4
QC5_OP
QC5_CL =1 VPQC5
QC3_OP
QC3_CL =1 VPQC3
QC21_OP
QC21_CL =1 VPQC21
VPQB62 QA2CLREL
VPQB2 & QA2CLITL
1
VPQA2
VPQC4 QB62REL
& >1
VPQC5 QB62ITL
1
VPQC3
QA2_OP
QC4_OP
QC5_OP
QC3_OP
QB62_EX1
VPQC5
VPQC3
&
QC5_CL
QC3_CL
QB62_EX2
VPQA2
VPQC4 QB2REL
& >1
VPQC5 QB2ITL
1
VPQC21
QA2_OP
QC4_OP
QC5_OP
QC21_OP
EXDU_ES
QB2_EX1

VPQC4
VPQC21
&
QC4_CL
QC21_CL
EXDU_ES
QB2_EX2

en04000552.vsd

IEC04000552 V1 EN

VPQB62 QC4REL
VPQB2 QC4ITL
& 1
QB62_OP QC5REL
QB2_OP QC5ITL
1
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
en04000553.vsd

IEC04000553 V1 EN

586
Technical reference manual
1MRK505183-UEN C Section 12
Control

DB_LINE
QA1_OP
QA1_CL =1 VPQA1
QA2_OP
QA2_CL =1 VPQA2
QB61_OP
QB61_CL =1 VPQB61
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QB62_OP
QB62_CL =1 VPQB62
QC4_OP
QC4_CL =1 VPQC4
QC5_OP
QC5_CL =1 VPQC5
QB9_OP
QB9_CL =1 VPQB9
QC3_OP
QC3_CL =1 VPQC3
QC9_OP
QC9_CL =1 VPQC9
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQA1
VPQA2 QB9REL
VPQC1 & >1
QB9ITL
1
VPQC2
VPQC3
VPQC4
VPQC5
VPQC9
QA1_OP
QA2_OP
QC1_OP
QC2_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX1

& en04000549.vsd

IEC04000549 V1 EN

VPQA1
VPQC1
VPQC2 & >1
VPQC3
VPQC9
VPQB62
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QC9_OP
QB62_OP
QB9_EX2
VPQA2
VPQB61
&
VPQC3
VPQC4
VPQC5
VPQC9
QA2_OP
QB61_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX3
VPQC3
VPQC9
&
VPQB61
VPQB62
QC3_OP
QC9_OP
QB61_OP
QB62_OP
QB9_EX4
VPQC3
VPQC9
&
QC3_CL
QC9_CL
QB9_EX5
en04000550.vsd

IEC04000550 V1 EN

587
Technical reference manual
Section 12 1MRK505183-UEN C
Control

VPQB61
VPQB62 QC3REL
VPQB9 &
QC3ITL
1
QB61_OP
QB62_OP
QB9_OP
VPQB9
VPVOLT QC9REL
QB9_OP &
QC9ITL
1
VOLT_OFF
en04000551.vsd

IEC04000551 V1 EN

12.4.9.4 Input and output signals


Table 342: DB_BUS_A Input signals
Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB61_OP BOOLEAN 0 QB61 is in open position
QB61_CL BOOLEAN 0 QB61 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QC11_OP BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in open
position
QC11_CL BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in closed
position
EXDU_ES BOOLEAN 0 No transm error from bay containing earthing
switch QC11
QB61_EX1 BOOLEAN 0 External condition for apparatus QB61
QB61_EX2 BOOLEAN 0 External condition for apparatus QB61
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1

Table 343: DB_BUS_A Output signals


Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB61REL BOOLEAN Switching of QB61 is allowed
QB61ITL BOOLEAN Switching of QB61 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
Table continues on next page

588
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Type Description


QB1ITL BOOLEAN Switching of QB1 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)

Table 344: DB_LINE Input signals


Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QA2_OP BOOLEAN 0 QA2 is in open position
QA2_CL BOOLEAN 0 QA2 is in closed position
QB61_OP BOOLEAN 0 QB61 is in open position
QB61_CL BOOLEAN 0 QB61 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QB62_OP BOOLEAN 0 QB62 is in open position
QB62_CL BOOLEAN 0 QB62 is in closed position
QC4_OP BOOLEAN 0 QC4 is in open position
QC4_CL BOOLEAN 0 QC4 is in closed position
QC5_OP BOOLEAN 0 QC5 is in open position
QC5_CL BOOLEAN 0 QC5 is in closed position
QB9_OP BOOLEAN 0 QB9 is in open position
QB9_CL BOOLEAN 0 QB9 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QC9_OP BOOLEAN 0 QC9 is in open position
QC9_CL BOOLEAN 0 QC9 is in closed position
VOLT_OFF BOOLEAN 0 There is no voltage on the line and not VT (fuse)
failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse)
failure
QB9_EX1 BOOLEAN 0 External condition for apparatus QB9
QB9_EX2 BOOLEAN 0 External condition for apparatus QB9
Table continues on next page

589
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Default Description


QB9_EX3 BOOLEAN 0 External condition for apparatus QB9
QB9_EX4 BOOLEAN 0 External condition for apparatus QB9
QB9_EX5 BOOLEAN 0 External condition for apparatus QB9

Table 345: DB_LINE Output signals


Name Type Description
QB9REL BOOLEAN Switching of QB9 is allowed
QB9ITL BOOLEAN Switching of QB9 is forbidden
QC3REL BOOLEAN Switching of QC3 is allowed
QC3ITL BOOLEAN Switching of QC3 is forbidden
QC9REL BOOLEAN Switching of QC9 is allowed
QC9ITL BOOLEAN Switching of QC9 is forbidden

Table 346: DB_BUS_B Input signals


Name Type Default Description
QA2_OP BOOLEAN 0 QA2 is in open position
QA2_CL BOOLEAN 0 QA2 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QB62_OP BOOLEAN 0 QB62 is in open position
QB62_CL BOOLEAN 0 QB62 is in closed position
QC4_OP BOOLEAN 0 QC4 is in open position
QC4_CL BOOLEAN 0 QC4 is in closed position
QC5_OP BOOLEAN 0 QC5 is in open position
QC5_CL BOOLEAN 0 QC5 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QC21_OP BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in open
position
QC21_CL BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in closed
position
EXDU_ES BOOLEAN 0 No transm error from bay containing earthing
switch QC21
QB62_EX1 BOOLEAN 0 External condition for apparatus QB62
QB62_EX2 BOOLEAN 0 External condition for apparatus QB62
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2

590
Technical reference manual
1MRK505183-UEN C Section 12
Control

Table 347: DB_BUS_B Output signals


Name Type Description
QA2CLREL BOOLEAN Closing of QA2 is allowed
QA2CLITL BOOLEAN Closing of QA2 is forbidden
QB62REL BOOLEAN Switching of QB62 is allowed
QB62ITL BOOLEAN Switching of QB62 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QC4REL BOOLEAN Switching of QC4 is allowed
QC4ITL BOOLEAN Switching of QC4 is forbidden
QC5REL BOOLEAN Switching of QC5 is allowed
QC5ITL BOOLEAN Switching of QC5 is forbidden
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)

12.4.10 Interlocking for line bay ABC_LINE

12.4.10.1 Introduction

The interlocking for line bay (ABC_LINE) function is used for a line connected to
a double busbar arrangement with a transfer busbar according to figure 327. The
function can also be used for a double busbar arrangement without transfer busbar
or a single busbar arrangement with/without transfer busbar.

WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB7
QC1

QA1

QC2

QB9
QC9

en04000478.vsd
IEC04000478 V1 EN

Figure 327: Switchyard layout ABC_LINE

591
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.4.10.2 Function block


ABC_LINE
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB9_OP QB9REL
QB9_CL QB9ITL
QB1_OP QB1REL
QB1_CL QB1ITL
QB2_OP QB2REL
QB2_CL QB2ITL
QB7_OP QB7REL
QB7_CL QB7ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC9_OP QC9REL
QC9_CL QC9ITL
QC11_OP QB1OPTR
QC11_CL QB1CLTR
QC21_OP QB2OPTR
QC21_CL QB2CLTR
QC71_OP QB7OPTR
QC71_CL QB7CLTR
BB7_D_OP QB12OPTR
BC_12_CL QB12CLTR
BC_17_OP VPQB1TR
BC_17_CL VPQB2TR
BC_27_OP VPQB7TR
BC_27_CL VPQB12TR
VOLT_OFF
VOLT_ON
VP_BB7_D
VP_BC_12
VP_BC_17
VP_BC_27
EXDU_ES
EXDU_BPB
EXDU_BC
QB9_EX1
QB9_EX2
QB1_EX1
QB1_EX2
QB1_EX3
QB2_EX1
QB2_EX2
QB2_EX3
QB7_EX1
QB7_EX2
QB7_EX3
QB7_EX4

IEC05000357-2-en.vsd
IEC05000357 V2 EN

Figure 328: ABC_LINE function block

592
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.4.10.3 Logic diagram

ABC_LINE
QA1_OP
QA1_CL =1 VPQA1
QB9_OP
QB9_CL =1 VPQB9
QA1CLREL
QB1_OP
QB1_CL =1 VPQB1 QA1CLITL
& 1
QB2_OP
QB2_CL =1 VPQB2
QB7_OP
QB7_CL =1 VPQB7
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC9_OP
QC9_CL =1 VPQC9
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
QC71_OP
QC71_CL =1 VPQC71
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQA1
VPQC1 QB9REL
VPQC2 & >1
QB9ITL
1
VPQC9
QA1_OP
QC1_OP
QC2_OP
QC9_OP
QB9_EX1
VPQC2
VPQC9
&
QC2_CL
QC9_CL
QB9_EX2

en04000527.vsd

IEC04000527 V1 EN

593
Technical reference manual
Section 12 1MRK505183-UEN C
Control

VPQA1 QB1REL
& ³1
VPQB2
VPQC1 1 QB1ITL
VPQC2
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES

QB1_EX1

VPQB2 &
VP_BC_12
QB2_CL
BC_12_CL
EXDU_BC

QB1_EX2

VPQC1 &
VPQC11
QC1_CL
QC11_CL
EXDU_ES

QB1EX3

en04000528.vsd

IEC04000528 V1 EN

594
Technical reference manual
1MRK505183-UEN C Section 12
Control

VPQA1 QB2REL
& ³1
VPQB1
VPQC1 1 QB2ITL
VPQC2
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES

QB2_EX1

VPQB1 &
VP_BC_12
QB1_CL
BC_12_CL
EXDU_BC

QB2_EX2

VPQC1 &
VPQC21
QC1_CL
QC21_CL
EXDU_ES

QB2_EX3

en04000529.vsd

IEC04000529 V1 EN

595
Technical reference manual
Section 12 1MRK505183-UEN C
Control

VPQC9 QB7REL
& >1
VPQC71
VP_BB7_D 1 QB7ITL
VP_BC_17
VP_BC_27
QC9_OP
QC71_OP
EXDU_ES

BB7_D_OP
EXDU_BPB

BC_17_OP
BC_27_OP
EXDU_BC
QB7_EX1

VPQA1
VPQB1
VPQC9
&
VPQB9
VPQC71
VP_BB7_D
VP_BC_17
QA1_CL
QB1_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES

BB7_D_OP
EXDU_BPB
BC_17_CL

EXDU_BC

QB7_EX2

IEC04000530 V1 EN

596
Technical reference manual
1MRK505183-UEN C Section 12
Control

VPQA1
VPQB2
& >1
VPQC9
VPQB9
VPQC71
VP_BB7_D
VP_BC_27
QA1_CL
QB2_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES

BB7_D_OP
EXDU_BPB
BC_27_CL
EXDU_BC
QB7_EX3
VPQC9
VPQC71
&
QC9_CL
QC71_CL
EXDU_ES
QB7_EX4
VPQB1 QC1REL
VPQB2 QC1ITL
VPQB9 & 1
QC2REL
QB1_OP
QB2_OP QC2ITL
1
QB9_OP
VPQB7
VPQB9 QC9REL
VPVOLT &
QC9ITL
QB7_OP 1
QB9_OP
VOLT_OFF
en04000531.vsd

IEC04000531 V1 EN

597
Technical reference manual
Section 12 1MRK505183-UEN C
Control

QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB7_OP QB7OPTR
QB7_CL QB7CLTR
VPQB7 VPQB7TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000532.vsd

IEC04000532 V1 EN

12.4.10.4 Input and output signals


Table 348: ABC_LINE Input signals
Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB9_OP BOOLEAN 0 QB9 is in open position
QB9_CL BOOLEAN 0 QB9 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QB7_OP BOOLEAN 0 QB7 is in open position
QB7_CL BOOLEAN 0 QB7 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC9_OP BOOLEAN 0 QC9 is in open position
QC9_CL BOOLEAN 0 QC9 is in closed position
QC11_OP BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in open
position
QC11_CL BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in closed
position
QC21_OP BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in open
position
Table continues on next page

598
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Type Default Description


QC21_CL BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in closed
position
QC71_OP BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in open
position
QC71_CL BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in closed
position
BB7_D_OP BOOLEAN 0 Disconnectors on busbar WA7 except in the own
bay are open
BC_12_CL BOOLEAN 0 A bus coupler connection exists between busbar
WA1 and WA2
BC_17_OP BOOLEAN 0 No bus coupler connection exists between busbar
WA1 and WA7
BC_17_CL BOOLEAN 0 A bus coupler connection exists between busbar
WA1 and WA7
BC_27_OP BOOLEAN 0 No bus coupler connection exists between busbar
WA2 and WA7
BC_27_CL BOOLEAN 0 A bus coupler connection exists between busbar
WA2 and WA7
VOLT_OFF BOOLEAN 0 There is no voltage on the line and not VT (fuse)
failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse)
failure
VP_BB7_D BOOLEAN 0 Switch status of the disconnectors on busbar
WA7 are valid
VP_BC_12 BOOLEAN 0 Status of the bus coupler app. between WA1 and
WA2 are valid
VP_BC_17 BOOLEAN 0 Status of the bus coupler app. between WA1 and
WA7 are valid
VP_BC_27 BOOLEAN 0 Status of the bus coupler app. between WA2 and
WA7 are valid
EXDU_ES BOOLEAN 0 No transm error from any bay containing earthing
switches
EXDU_BPB BOOLEAN 0 No transm error from any bay with disconnectors
on WA7
EXDU_BC BOOLEAN 0 No transmission error from any bus coupler bay
QB9_EX1 BOOLEAN 0 External condition for apparatus QB9
QB9_EX2 BOOLEAN 0 External condition for apparatus QB9
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB1_EX3 BOOLEAN 0 External condition for apparatus QB1
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2
QB2_EX3 BOOLEAN 0 External condition for apparatus QB2
QB7_EX1 BOOLEAN 0 External condition for apparatus QB7
Table continues on next page

599
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Default Description


QB7_EX2 BOOLEAN 0 External condition for apparatus QB7
QB7_EX3 BOOLEAN 0 External condition for apparatus QB7
QB7_EX4 BOOLEAN 0 External condition for apparatus QB7

Table 349: ABC_LINE Output signals


Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB9REL BOOLEAN Switching of QB9 is allowed
QB9ITL BOOLEAN Switching of QB9 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QB7REL BOOLEAN Switching of QB7 is allowed
QB7ITL BOOLEAN Switching of QB7 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QC9REL BOOLEAN Switching of QC9 is allowed
QC9ITL BOOLEAN Switching of QC9 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
QB7OPTR BOOLEAN QB7 is in open position
QB7CLTR BOOLEAN QB7 is in closed position
QB12OPTR BOOLEAN QB1 or QB2 or both are in open position
QB12CLTR BOOLEAN QB1 and QB2 are not in open position
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)
VPQB7TR BOOLEAN Switch status of QB7 is valid (open or closed)
VPQB12TR BOOLEAN Switch status of QB1 and QB2 are valid (open or
closed)

12.4.11 Interlocking for transformer bay AB_TRAFO

600
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.4.11.1 Introduction

The interlocking for transformer bay (AB_TRAFO) function is used for a


transformer bay connected to a double busbar arrangement according to figure 329.
The function is used when there is no disconnector between circuit breaker and
transformer. Otherwise, the interlocking for line bay (ABC_LINE) function can be
used. This function can also be used in single busbar arrangements.

WA1 (A)
WA2 (B)
QB1 QB2
QC1

QA1
AB_TRAFO
QC2

QC3

QA2
QA2 and QC4 are not
QC4 used in this interlocking

QB3 QB4

en04000515.vsd
IEC04000515 V1 EN

Figure 329: Switchyard layout AB_TRAFO

601
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.4.11.2 Function block


AB_TRAFO
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB1_OP QB1REL
QB1_CL QB1ITL
QB2_OP QB2REL
QB2_CL QB2ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QB3_OP QB1OPTR
QB3_CL QB1CLTR
QB4_OP QB2OPTR
QB4_CL QB2CLTR
QC3_OP QB12OPTR
QC3_CL QB12CLTR
QC11_OP VPQB1TR
QC11_CL VPQB2TR
QC21_OP VPQB12TR
QC21_CL
BC_12_CL
VP_BC_12
EXDU_ES
EXDU_BC
QA1_EX1
QA1_EX2
QA1_EX3
QB1_EX1
QB1_EX2
QB1_EX3
QB2_EX1
QB2_EX2
QB2_EX3

IEC05000358-2-en.vsd
IEC05000358 V2 EN

Figure 330: AB_TRAFO function block

602
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.4.11.3 Logic diagram


AB_TRAFO
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB2_OP
QB2_CL =1 VPQB2
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QB3_OP
QB3_CL =1 VPQB3
QB4_OP
QB4_CL =1 VPQB4
QC3_OP
QC3_CL =1 VPQC3
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
VPQB1 QA1CLREL
VPQB2 QA1CLITL
VPQC1 & 1

VPQC2
VPQB3
VPQB4
VPQC3
QA1_EX2
QC3_OP
QA1_EX3
QC1_CL >1
QC2_CL
QC3_CL &
QA1_EX1

en04000538.vsd

IEC04000538 V1 EN

VPQA1
VPQB2 QB1REL
& >1
VPQC1 QB1ITL
VPQC2 1
VPQC3
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC3_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VPQC3
&
VP_BC_12
QB2_CL
QC3_OP
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC2
&
VPQC3
VPQC11
QC1_CL
QC2_CL
QC3_CL
QC11_CL
EXDU_ES
QB1_EX3

en04000539.vsd

IEC04000539 V1 EN

603
Technical reference manual
Section 12 1MRK505183-UEN C
Control

VPQA1
VPQB1 QB2REL
& >1
VPQC1 QB2ITL
VPQC2 1
VPQC3
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC3_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VPQC3
&
VP_BC_12
QB1_CL
QC3_OP
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC2
&
VPQC3
VPQC21
QC1_CL
QC2_CL
QC3_CL
QC21_CL
EXDU_ES
QB2_EX3

en04000540.vsd

IEC04000540 V1 EN

VPQB1 QC1REL
VPQB2 QC1ITL
& 1
VPQB3
QC2REL
VPQB4
QB1_OP QC2ITL
1
QB2_OP
QB3_OP
QB4_OP
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000541.vsd

IEC04000541 V1 EN

12.4.11.4 Input and output signals


Table 350: AB_TRAFO Input signals
Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
Table continues on next page

604
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Type Default Description


QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QB3_OP BOOLEAN 0 QB3 is in open position
QB3_CL BOOLEAN 0 QB3 is in closed position
QB4_OP BOOLEAN 0 QB4 is in open position
QB4_CL BOOLEAN 0 QB4 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QC11_OP BOOLEAN 0 QC11 on busbar WA1 is in open position
QC11_CL BOOLEAN 0 QC11 on busbar WA1 is in closed position
QC21_OP BOOLEAN 0 QC21 on busbar WA2 is in open position
QC21_CL BOOLEAN 0 QC21 on busbar WA2 is in closed position
BC_12_CL BOOLEAN 0 A bus coupler connection exists between busbar
WA1 and WA2
VP_BC_12 BOOLEAN 0 Status of the bus coupler app. between WA1 and
WA2 are valid
EXDU_ES BOOLEAN 0 No transm error from any bay containing earthing
switches
EXDU_BC BOOLEAN 0 No transmission error from any bus coupler bay
QA1_EX1 BOOLEAN 0 External condition for apparatus QA1
QA1_EX2 BOOLEAN 0 External condition for apparatus QA1
QA1_EX3 BOOLEAN 0 External condition for apparatus QA1
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB1_EX3 BOOLEAN 0 External condition for apparatus QB1
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2
QB2_EX3 BOOLEAN 0 External condition for apparatus QB2

Table 351: AB_TRAFO Output signals


Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
Table continues on next page

605
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Description


QC2ITL BOOLEAN Switching of QC2 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
QB12OPTR BOOLEAN QB1 or QB2 or both are in open position
QB12CLTR BOOLEAN QB1 and QB2 are not in open position
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)
VPQB12TR BOOLEAN Switch status of QB1 and QB2 are valid (open or
closed)

12.4.12 Position evaluation POS_EVAL

12.4.12.1 Introduction

Position evaluation (POS_EVAL) function converts the input position data signal
POSITION, consisting of value, time and signal status, to binary signals
OPENPOS or CLOSEPOS.

The output signals are used by other functions in the interlocking scheme.

12.4.12.2 Logic diagram


POS_EVAL
Position including quality POSITION OPENPOS
Open/close position of
CLOSEPOS switch device

IEC08000469-1-en.vsd
IEC08000469-1-EN V1 EN

Only the value, open/close, and status is used in this function. Time information is
not used.
Input position (Value) Signal quality Output OPENPOS Output CLOSEPOS
0 (Breaker Good 0 0
intermediate)
1 (Breaker open) Good 1 0
2 (Breaker closed) Good 0 1
3 (Breaker faulty) Good 0 0
Any Invalid 0 0
Any Oscillatory 0 0

606
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.4.12.3 Function block


POS_EVAL
POSITION OPENPOS
CLOSEPOS

IEC09000079_1_en.vsd
IEC09000079 V1 EN

Figure 331: POS_EVAL function block

12.4.12.4 Input and output signals


Table 352: POS_EVAL Input signals
Name Type Default Description
POSITION INTEGER 0 Position status including quality

Table 353: POS_EVAL Output signals


Name Type Description
OPENPOS BOOLEAN Open position
CLOSEPOS BOOLEAN Close position

12.5 Logic rotating switch for function selection and


LHMI presentation SLGGIO

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logic rotating switch for function SLGGIO - -
selection and LHMI presentation

12.5.1 Introduction
The logic rotating switch for function selection and LHMI presentation function
(SLGGIO) (or the selector switch function block) is used to get a selector switch
functionality similar with the one provided by a hardware selector switch.
Hardware selector switches are used extensively by utilities, in order to have
different functions operating on pre-set values. Hardware switches are however
sources for maintenance issues, lower system reliability and extended purchase
portfolio. The virtual selector switches eliminate all these problems.

12.5.2 Principle of operation


The logic rotating switch for function selection and LHMI presentation (SLGGIO)
function has two operating inputs – UP and DOWN. When a signal is received on
the UP input, the block will activate the output next to the present activated output,

607
Technical reference manual
Section 12 1MRK505183-UEN C
Control

in ascending order (if the present activated output is 3 – for example and one
operates the UP input, then the output 4 will be activated). When a signal is
received on the DOWN input, the block will activate the output next to the present
activated output, in descending order (if the present activated output is 3 – for
example and one operates the DOWN input, then the output 2 will be activated).
Depending on the output settings the output signals can be steady or pulsed. In case
of steady signals, in case of UP or DOWN operation, the previously active output
will be deactivated. Also, depending on the settings one can have a time delay
between the UP or DOWN activation signal positive front and the output activation.

Besides the inputs visible in the application configuration in the Application


Configuration tool, there are other possibilities that will allow an user to set the
desired position directly (without activating the intermediate positions), either
locally or remotely, using a “select before execute” dialog. One can block the
function operation, by activating the BLOCK input. In this case, the present
position will be kept and further operation will be blocked. The operator place
(local or remote) is specified through the PSTO input. If any operation is allowed
the signal INTONE from the Fixed signal function block can be connected.
SLGGIO function block has also an integer value output, that generates the actual
position number. The positions and the block names are fully settable by the user.
These names will appear in the menu, so the user can see the position names
instead of a number.

608
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.5.2.1 Functionality and behaviour

Control
Control Single Line Diagram Ctrl/Com
Measurements Commands Single Command
Events Selector Switch (GGIO)
Disturbance records
Settings
Diagnostics
Test
Reset
Authorization
Language

1 2 3
../Com/Sel Sw/ ../Com/Sel Sw/
../Ctrl/Com/Sel Sw SLGGIO3
SLGGIO1 SLGGIO3
Damage ctrl 4 Damage ctrl 4
SLGGIO2
..
..
SLGGIO15

P:Disc All N: Disc Fe

OK Cancel
4

5
The dialog window that appears
../Com/Sel Sw/ shows the present position (P:)
DmgCtrl 7
and the new position (N:), both
Damage ctrl: in clear names, given by the
user (max. 13 characters).

E
Modify the position with arrows.
The pos will not be modified (outputs
will not be activated) until you press
the E-button for O.K. IEC06000420-2-en.vsd
IEC06000420 V2 EN

Figure 332: Example 1 on handling the switch from the local HMI.
From the local HMI:

1 SLGGIO instances in the ACT application configuration


2 Switch name given by the user (max 13 characters)
3 Position number, up to 32 positions
4 Change position
5 New position

12.5.2.2 Graphical display

There are two possibilities for SLGGIO

609
Technical reference manual
Section 12 1MRK505183-UEN C
Control

• if it is used just for the monitoring, the switches will be listed with their actual
position names, as defined by the user (max. 13 characters).
• if it is used for control, the switches will be listed with their actual positions,
but only the first three letters of the name will be used.

In both cases, the switch full name will be shown, but the user has to redefine it
when building the Graphical Display Editor, under the "Caption". If used for the
control, the following sequence of commands will ensure:

From the graphical display:

Control
Control Single Line Diagram
Measurements Commands
Events
Disturbance records
Settings
Diagnostics
Test
Change to the "Switches" page Reset
of the SLD by left-right arrows. Authorization
Select switch by up-down Language
arrows

../Control/SLD/Switch
O I ../Control/SLD/Switch
SMBRREC control SMBRREC control
WFM Select switch. Press the
WFM
I or O key. A dialog box
Pilot setup appears.
Pilot setup
OFF OFF
Damage control E P: Disc N: Disc Fe
DAL
The pos will not be modified
(outputs will not be activated) until OK Cancel
you press the E-button for O.K.

../Control/SLD/Switch

SMBRREC control
WFM

Pilot setup
OFF

Damage control
DFW

IEC06000421-2-en.vsd
IEC06000421 V2 EN

Figure 333: Example 2 on handling the switch from the local HMI.
From the single line diagram on local HMI.

610
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.5.3 Function block


SLGGIO
BLOCK ^SWPOS01
PSTO ^SWPOS02
UP ^SWPOS03
DOWN ^SWPOS04
^SWPOS05
^SWPOS06
^SWPOS07
^SWPOS08
^SWPOS09
^SWPOS10
^SWPOS11
^SWPOS12
^SWPOS13
^SWPOS14
^SWPOS15
^SWPOS16
^SWPOS17
^SWPOS18
^SWPOS19
^SWPOS20
^SWPOS21
^SWPOS22
^SWPOS23
^SWPOS24
^SWPOS25
^SWPOS26
^SWPOS27
^SWPOS28
^SWPOS29
^SWPOS30
^SWPOS31
^SWPOS32
SWPOSN

IEC05000658-2-en.vsd
IEC05000658 V2 EN

Figure 334: SLGGIO function block

12.5.4 Input and output signals


Table 354: SLGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection
UP BOOLEAN 0 Binary "UP" command
DOWN BOOLEAN 0 Binary "DOWN" command

Table 355: SLGGIO Output signals


Name Type Description
SWPOS01 BOOLEAN Selector switch position 1
SWPOS02 BOOLEAN Selector switch position 2
SWPOS03 BOOLEAN Selector switch position 3
SWPOS04 BOOLEAN Selector switch position 4
SWPOS05 BOOLEAN Selector switch position 5
Table continues on next page

611
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Description


SWPOS06 BOOLEAN Selector switch position 6
SWPOS07 BOOLEAN Selector switch position 7
SWPOS08 BOOLEAN Selector switch position 8
SWPOS09 BOOLEAN Selector switch position 9
SWPOS10 BOOLEAN Selector switch position 10
SWPOS11 BOOLEAN Selector switch position 11
SWPOS12 BOOLEAN Selector switch position 12
SWPOS13 BOOLEAN Selector switch position 13
SWPOS14 BOOLEAN Selector switch position 14
SWPOS15 BOOLEAN Selector switch position 15
SWPOS16 BOOLEAN Selector switch position 16
SWPOS17 BOOLEAN Selector switch position 17
SWPOS18 BOOLEAN Selector switch position 18
SWPOS19 BOOLEAN Selector switch position 19
SWPOS20 BOOLEAN Selector switch position 20
SWPOS21 BOOLEAN Selector switch position 21
SWPOS22 BOOLEAN Selector switch position 22
SWPOS23 BOOLEAN Selector switch position 23
SWPOS24 BOOLEAN Selector switch position 24
SWPOS25 BOOLEAN Selector switch position 25
SWPOS26 BOOLEAN Selector switch position 26
SWPOS27 BOOLEAN Selector switch position 27
SWPOS28 BOOLEAN Selector switch position 28
SWPOS29 BOOLEAN Selector switch position 29
SWPOS30 BOOLEAN Selector switch position 30
SWPOS31 BOOLEAN Selector switch position 31
SWPOS32 BOOLEAN Selector switch position 32
SWPOSN INTEGER Switch position (integer)

12.5.5 Setting parameters


Table 356: SLGGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
NrPos 2 - 32 - 1 32 Number of positions in the switch
OutType Pulsed - - Steady Output type, steady or pulse
Steady
Table continues on next page

612
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Values (Range) Unit Step Default Description


tPulse 0.000 - 60.000 s 0.001 0.200 Operate pulse duration, in [s]
tDelay 0.000 - 60000.000 s 0.010 0.000 Time delay on the output, in [s]
StopAtExtremes Disabled - - Disabled Stop when min or max position is reached
Enabled

12.6 Selector mini switch VSGGIO

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Selector mini switch VSGGIO - -

12.6.1 Introduction
Selector mini switch (VSGGIO) function block is a multipurpose function used in
the configuration tool in PCM600 for a variety of applications, as a general purpose
switch.

VSGGIO can be controlled from the menu or from a symbol on the single line
diagram (SLD) on the local HMI.

12.6.2 Principle of operation


Selector mini switch (VSGGIO) function can be used for double purpose, in the
same way as switch controller (SCSWI) functions are used:

• for indication on the single line diagram (SLD). Position is received through
the IPOS1 and IPOS2 inputs and distributed in the configuration through the
POS1 and POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
• for commands that are received via the local HMI or IEC 61850 and
distributed in the configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command
from the local HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command
from the local HMI when the SLD is displayed and the object is chosen.

It is important for indication in the SLD that the a symbol is


associated with a controllable object, otherwise the symbol won't be
displayed on the screen. A symbol is created and configured in
GDE tool in PCM600.

The PSTO input is connected to the Local remote switch to have a selection of
operators place , operation from local HMI (Local) or through IEC 61850

613
Technical reference manual
Section 12 1MRK505183-UEN C
Control

(Remote). An INTONE connection from Fixed signal function block (FXDSIGN)


will allow operation from local HMI.

As it can be seen, both indications and commands are done in double-bit


representation, where a combination of signals on both inputs/outputs generate the
desired result.

The following table shows the relationship between IPOS1/IPOS2 inputs and the
name of the string that is shown on the SLD. The value of the strings are set in PST.
IPOS1 IPOS2 Name of displayed string Default string value
0 0 PosUndefined P00
1 0 Position1 P01
0 1 Position2 P10
1 1 PosBadState P11

12.6.3 Function block


VSGGIO
BLOCK BLOCKED
PSTO POSITION
IPOS1 POS1
IPOS2 POS2
CMDPOS12
CMDPOS21

IEC06000508-2-en.vsd
IEC06000508 V3 EN

Figure 335: VSGGIO function block

12.6.4 Input and output signals


Table 357: VSGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection
IPOS1 BOOLEAN 0 Position 1 indicating input
IPOS2 BOOLEAN 0 Position 2 indicating input

Table 358: VSGGIO Output signals


Name Type Description
BLOCKED BOOLEAN The function is active but the functionality is
blocked
POSITION INTEGER Position indication, integer
POS1 BOOLEAN Position 1 indication, logical signal
Table continues on next page

614
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Type Description


POS2 BOOLEAN Position 2 indication, logical signal
CMDPOS12 BOOLEAN Execute command from position 1 to position 2
CMDPOS21 BOOLEAN Execute command from position 2 to position 1

12.6.5 Setting parameters


Table 359: VSGGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
CtlModel Dir Norm - - Dir Norm Specifies the type for control model
SBO Enh according to IEC 61850
Mode Steady - - Pulsed Operation mode
Pulsed
tSelect 0.000 - 60.000 s 0.001 30.000 Max time between select and execute
signals
tPulse 0.000 - 60.000 s 0.001 0.200 Command pulse lenght

12.7 Generic double point function block DPGGIO

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
IEC 61850 generic communication I/O DPGGIO - -
functions

12.7.1 Introduction
The IEC 61850 generic communication I/O functions (DPGGIO) function block is
used to send three logical signals to other systems or equipment in the substation. It
is especially used in the interlocking and reservation station-wide logics.

12.7.2 Principle of operation


Upon receiving the input signals, the IEC 61850 generic communication I/O
functions (DPGGIO) function block will send the signals over IEC 61850-8-1 to
the equipment or system that requests these signals. To be able to get the signals,
other tools must be used, as described in the application manual, to PCM600 must
be used to define which function block in which equipment or system should
receive this information.

615
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.7.3 Function block


DPGGIO
OPEN POSITION
CLOSE
VALID

IEC07000200-2-en.vsd
IEC07000200 V2 EN

Figure 336: DPGGIO function block

12.7.4 Input and output signals


Table 360: DPGGIO Input signals
Name Type Default Description
OPEN BOOLEAN 0 Open indication
CLOSE BOOLEAN 0 Close indication
VALID BOOLEAN 0 Valid indication

Table 361: DPGGIO Output signals


Name Type Description
POSITION INTEGER Double point indication

12.7.5 Settings
The function does not have any parameters available in the local HMI or PCM600.

12.8 Single point generic control 8 signals SPC8GGIO

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Single point generic control 8 signals SPC8GGIO - -

12.8.1 Introduction
The Single point generic control 8 signals (SPC8GGIO) function block is a
collection of 8 single point commands, designed to bring in commands from
REMOTE (SCADA) to those parts of the logic configuration that do not need
complicated function blocks that have the capability to receive commands (for
example, SCSWI). In this way, simple commands can be sent directly to the IED
outputs, without confirmation. Confirmation (status) of the result of the commands

616
Technical reference manual
1MRK505183-UEN C Section 12
Control

is supposed to be achieved by other means, such as binary inputs and SPGGIO


function blocks.

12.8.2 Principle of operation


The PSTO input will determine which the allowed position for the operator
(LOCAL, REMOTE, ALL) is. Upon sending a command from an allowed operator
position, one of the 8 outputs will be activated. The settings Latchedx and tPulsex
(where x is the respective output) will determine if the signal will be pulsed (and
how long the pulse is) or latched (steady). BLOCK will block the operation of the
function – in case a command is sent, no output will be activated.

PSTO is the universal operator place selector for all control


functions. Even if PSTO can be configured to allow LOCAL or
ALL operator positions, the only functional position usable with the
SPC8GGIO function block is REMOTE.

12.8.3 Function block


SPC8GGIO
BLOCK ^OUT1
PSTO ^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8

IEC07000143-2-en.vsd
IEC07000143 V2 EN

Figure 337: SPC8GGIO function block

12.8.4 Input and output signals


Table 362: SPC8GGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Blocks the function operation
PSTO INTEGER 2 Operator place selection

Table 363: SPC8GGIO Output signals


Name Type Description
OUT1 BOOLEAN Output 1
OUT2 BOOLEAN Output2
OUT3 BOOLEAN Output3
OUT4 BOOLEAN Output4
Table continues on next page

617
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Type Description


OUT5 BOOLEAN Output5
OUT6 BOOLEAN Output6
OUT7 BOOLEAN Output7
OUT8 BOOLEAN Output8

12.8.5 Setting parameters


Table 364: SPC8GGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
Latched1 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 1
tPulse1 0.01 - 6000.00 s 0.01 0.10 Output1 Pulse Time
Latched2 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 2
tPulse2 0.01 - 6000.00 s 0.01 0.10 Output2 Pulse Time
Latched3 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 3
tPulse3 0.01 - 6000.00 s 0.01 0.10 Output3 Pulse Time
Latched4 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 4
tPulse4 0.01 - 6000.00 s 0.01 0.10 Output4 Pulse Time
Latched5 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 5
tPulse5 0.01 - 6000.00 s 0.01 0.10 Output5 Pulse Time
Latched6 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 6
tPulse6 0.01 - 6000.00 s 0.01 0.10 Output6 Pulse Time
Latched7 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 7
tPulse7 0.01 - 6000.00 s 0.01 0.10 Output7 Pulse Time
Latched8 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 8
tPulse8 0.01 - 6000.00 s 0.01 0.10 Output8 pulse time

12.9 AutomationBits, command function for DNP3.0


AUTOBITS

618
Technical reference manual
1MRK505183-UEN C Section 12
Control

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
AutomationBits, command function for
AUTOBITS - -
DNP3.0

12.9.1 Introduction
AutomationBits function for DNP3 (AUTOBITS) is used within PCM600 to get
into the configuration of the commands coming through the DNP3 protocol. The
AUTOBITS function plays the same role as functions GOOSEBINRCV (for IEC
61850) and MULTICMDRCV (for LON).

12.9.2 Principle of operation


AutomationBits function (AUTOBITS) has 32 individual outputs which each can
be mapped as a Binary Output point in DNP3. The output is operated by a "Object
12" in DNP3. This object contains parameters for control-code, count, on-time and
off-time. To operate an AUTOBITS output point, send a control-code of latch-On,
latch-Off, pulse-On, pulse-Off, Trip or Close. The remaining parameters will be
regarded were appropriate. ex: pulse-On, on-time=100, off-time=300, count=5
would give 5 positive 100 ms pulses, 300 ms apart.

There is a BLOCK input signal, which will disable the operation of the function, in
the same way the setting Operation: On/Off does. That means that, upon activation
of the BLOCK input, all 32 CMDBITxx outputs will be set to 0. The BLOCK acts
like an overriding, the function still receives data from the DNP3 master. Upon
deactivation of BLOCK, all the 32 CMDBITxx outputs will be set by the DNP3
master again, momentarily. For AUTOBITS , the PSTO input determines the
operator place. The command can be written to the block while in “Remote”. If
PSTO is in “Local” then no change is applied to the outputs.

619
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.9.3 Function block


AUTOBITS
BLOCK ^CMDBIT1
PSTO ^CMDBIT2
^CMDBIT3
^CMDBIT4
^CMDBIT5
^CMDBIT6
^CMDBIT7
^CMDBIT8
^CMDBIT9
^CMDBIT10
^CMDBIT11
^CMDBIT12
^CMDBIT13
^CMDBIT14
^CMDBIT15
^CMDBIT16
^CMDBIT17
^CMDBIT18
^CMDBIT19
^CMDBIT20
^CMDBIT21
^CMDBIT22
^CMDBIT23
^CMDBIT24
^CMDBIT25
^CMDBIT26
^CMDBIT27
^CMDBIT28
^CMDBIT29
^CMDBIT30
^CMDBIT31
^CMDBIT32

IEC09000925-1-en.vsd
IEC09000925 V1 EN

Figure 338: AUTOBITS function block

12.9.4 Input and output signals


Table 365: AUTOBITS Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection

Table 366: AUTOBITS Output signals


Name Type Description
CMDBIT1 BOOLEAN Command out bit 1
CMDBIT2 BOOLEAN Command out bit 2
CMDBIT3 BOOLEAN Command out bit 3
CMDBIT4 BOOLEAN Command out bit 4
CMDBIT5 BOOLEAN Command out bit 5
CMDBIT6 BOOLEAN Command out bit 6
CMDBIT7 BOOLEAN Command out bit 7
CMDBIT8 BOOLEAN Command out bit 8
Table continues on next page

620
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Type Description


CMDBIT9 BOOLEAN Command out bit 9
CMDBIT10 BOOLEAN Command out bit 10
CMDBIT11 BOOLEAN Command out bit 11
CMDBIT12 BOOLEAN Command out bit 12
CMDBIT13 BOOLEAN Command out bit 13
CMDBIT14 BOOLEAN Command out bit 14
CMDBIT15 BOOLEAN Command out bit 15
CMDBIT16 BOOLEAN Command out bit 16
CMDBIT17 BOOLEAN Command out bit 17
CMDBIT18 BOOLEAN Command out bit 18
CMDBIT19 BOOLEAN Command out bit 19
CMDBIT20 BOOLEAN Command out bit 20
CMDBIT21 BOOLEAN Command out bit 21
CMDBIT22 BOOLEAN Command out bit 22
CMDBIT23 BOOLEAN Command out bit 23
CMDBIT24 BOOLEAN Command out bit 24
CMDBIT25 BOOLEAN Command out bit 25
CMDBIT26 BOOLEAN Command out bit 26
CMDBIT27 BOOLEAN Command out bit 27
CMDBIT28 BOOLEAN Command out bit 28
CMDBIT29 BOOLEAN Command out bit 29
CMDBIT30 BOOLEAN Command out bit 30
CMDBIT31 BOOLEAN Command out bit 31
CMDBIT32 BOOLEAN Command out bit 32

12.9.5 Setting parameters


Table 367: AUTOBITS Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On

Table 368: DNPGEN Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation mode Off / On
On

621
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Table 369: CHSERRS485 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation mode
Serial-Mode
BaudRate 300 Bd - - 9600 Bd Baud-rate for serial port
600 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
WireMode Four-wire - - Two-wire RS485 wire mode
Two-wire

Table 370: CHSERRS485 Non group settings (advanced)


Name Values (Range) Unit Step Default Description
DLinkConfirm Never - - Never Data-link confirm
Sometimes
Always
tDLinkTimeout 0.000 - 60.000 s 0.001 2.000 Data-link confirm timeout in s
DLinkRetries 0 - 255 - 1 3 Data-link maximum retries
tRxToTxMinDel 0.000 - 60.000 s 0.001 0.000 Rx to Tx minimum delay in s
ApLayMaxRxSize 20 - 2048 - 1 2048 Application layer maximum Rx fragment
size
ApLayMaxTxSize 20 - 2048 - 1 2048 Application layer maximum Tx fragment
size
StopBits 1-2 - 1 1 Stop bits
Parity No - - Even Parity
Even
Odd
tRTSWarmUp 0.000 - 60.000 s 0.001 0.000 RTS warm-up in s
tRTSWarmDown 0.000 - 60.000 s 0.001 0.000 RTS warm-down in s
tBackOffDelay 0.000 - 60.000 s 0.001 0.050 RS485 back-off delay in s
tMaxRndDelBkOf 0.000 - 60.000 s 0.001 0.100 RS485 maximum back-off random delay
in s

Table 371: CH2TCP Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation mode
TCP/IP
UDP-Only
TCPIPLisPort 1 - 65535 - 1 20000 TCP/IP listen port
UDPPortAccData 1 - 65535 - 1 20000 UDP port to accept UDP datagrams from
master
UDPPortInitNUL 1 - 65535 - 1 20000 UDP portfor initial NULL response
UDPPortCliMast 0 - 65535 - 1 0 UDP port to remote client/master

622
Technical reference manual
1MRK505183-UEN C Section 12
Control

Table 372: CH2TCP Non group settings (advanced)


Name Values (Range) Unit Step Default Description
ApLayMaxRxSize 20 - 2048 - 1 2048 Application layer maximum Rx fragment
size
ApLayMaxTxSize 20 - 2048 - 1 2048 Application layer maximum Tx fragment
size

Table 373: CH3TCP Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation mode
TCP/IP
UDP-Only
TCPIPLisPort 1 - 65535 - 1 20000 TCP/IP listen port
UDPPortAccData 1 - 65535 - 1 20000 UDP port to accept UDP datagrams from
master
UDPPortInitNUL 1 - 65535 - 1 20000 UDP port for initial NULL response
UDPPortCliMast 0 - 65535 - 1 0 UDP port to remote client/master

Table 374: CH3TCP Non group settings (advanced)


Name Values (Range) Unit Step Default Description
ApLayMaxRxSize 20 - 2048 - 1 2048 Application layer maximum Rx fragment
size
ApLayMaxTxSize 20 - 2048 - 1 2048 Application layer maximum Tx fragment
size

Table 375: CH4TCP Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation mode
TCP/IP
UDP-Only
TCPIPLisPort 1 - 65535 - 1 20000 TCP/IP listen port
UDPPortAccData 1 - 65535 - 1 20000 UDP port to accept UDP datagrams from
master
UDPPortInitNUL 1 - 65535 - 1 20000 UDP port for initial NULL response
UDPPortCliMast 0 - 65535 - 1 0 UDP port to remote client/master

Table 376: CH4TCP Non group settings (advanced)


Name Values (Range) Unit Step Default Description
ApLayMaxRxSize 20 - 2048 - 1 2048 Application layer maximum Rx fragment
size
ApLayMaxTxSize 20 - 2048 - 1 2048 Application layer maximum Tx fragment
size

623
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Table 377: CH5TCP Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation mode
TCP/IP
UDP-Only
TCPIPLisPort 1 - 65535 - 1 20000 TCP/IP listen port
UDPPortAccData 1 - 65535 - 1 20000 UDP port to accept UDP datagrams from
master
UDPPortInitNUL 1 - 65535 - 1 20000 UDP port for initial NULL response
UDPPortCliMast 0 - 65535 - 1 0 UDP port to remote client/master

Table 378: CH5TCP Non group settings (advanced)


Name Values (Range) Unit Step Default Description
ApLayMaxRxSize 20 - 2048 - 1 2048 Application layer maximum Rx fragment
size
ApLayMaxTxSize 20 - 2048 - 1 2048 Application layer maximum Tx fragment
size

Table 379: MSTRS485 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
SlaveAddress 0 - 65519 - 1 1 Slave address
MasterAddres 0 - 65519 - 1 1 Master address
Obj1DefVar 1:BISingleBit - - 1:BISingleBit Object 1, default variation
2:BIWithStatus
Obj2DefVar 1:BIChWithoutTim - - 3:BIChWithRelTim Object 2, default variation
e e
2:BIChWithTime
3:BIChWithRelTim
e
Obj4DefVar 1:DIChWithoutTim - - 3:DIChWithRelTim Object 4, default variation
e e
2:DIChWithTime
3:DIChWithRelTim
e
Obj10DefVar 1:BO - - 2:BOStatus Object 10, default variation
2:BOStatus
Obj20DefVar 1:BinCnt32 - - 5:BinCnt32WoutF Object 20, default variation
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
Table continues on next page

624
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Values (Range) Unit Step Default Description


Obj22DefVar 1:BinCnt32EvWout - - 1:BinCnt32EvWou Object 22, default variation
T tT
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
Obj30DefVar 1:AI32Int - - 3:AI32IntWithoutF Object 30, default variation
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
Obj32DefVar 1:AI32IntEvWoutF - - 1:AI32IntEvWoutF Object 32, default variation
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

Table 380: MSTRS485 Non group settings (advanced)


Name Values (Range) Unit Step Default Description
ValMasterAddr No - - Yes Validate source (master) address
Yes
AddrQueryEnbl No - - Yes Address query enable
Yes
tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout
ApplMultFrgRes No - - Yes Enable application for multiple fragment
Yes response
ConfMultFrag No - - Yes Confirm each multiple fragment
Yes
UREnable No - - Yes Unsolicited response enabled
Yes
URSendOnline No - - No Unsolicited response sends when on-line
Yes
UREvClassMask Off - - Off Unsolicited response, event class mask
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
UROfflineRetry 0 - 10 - 1 5 Unsolicited response retries before off-
line retry mode
tURRetryDelay 0.00 - 60.00 s 0.01 5.00 Unsolicited response retry delay in s
tUROfflRtryDel 0.00 - 60.00 s 0.01 30.00 Unsolicited response off-line retry delay
in s
UREvCntThold1 1 - 100 - 1 5 Unsolicited response class 1 event count
report treshold
Table continues on next page

625
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Values (Range) Unit Step Default Description


tUREvBufTout1 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 1 event
buffer timeout
UREvCntThold2 1 - 100 - 1 5 Unsolicited response class 2 event count
report treshold
tUREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 event
buffer timeout
UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event count
report treshold
tUREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 event
buffer timeout
DelOldBufFull No - - No Delete oldest event when buffer is full
Yes
tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status is
generated
TSyncReqAfTout No - - No Time synchronization request after
Yes timeout
DNPToSetTime No - - Yes Allow DNP to set time in IED
Yes
Averag3TimeReq No - - No Use average of 3 time requests
Yes
PairedPoint No - - Yes Enable paired point
Yes
tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout

Table 381: MST1TCP Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
SlaveAddress 0 - 65519 - 1 1 Slave address
MasterAddres 0 - 65519 - 1 1 Master address
ValMasterAddr No - - Yes Validate source (master) address
Yes
MasterIP-Addr 0 - 18 - 1 0.0.0.0 Master IP-address
MasterIPNetMsk 0 - 18 - 1 255.255.255.255 Master IP net mask
Obj1DefVar 1:BISingleBit - - 1:BISingleBit Object 1, default variation
2:BIWithStatus
Obj2DefVar 1:BIChWithoutTim - - 3:BIChWithRelTim Object 2, default variation
e e
2:BIChWithTime
3:BIChWithRelTim
e
Obj4DefVar 1:DIChWithoutTim - - 3:DIChWithRelTim Object 4, default variation
e e
2:DIChWithTime
3:DIChWithRelTim
e
Obj10DefVar 1:BO - - 2:BOStatus Object 10, default variation
2:BOStatus
Table continues on next page

626
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Values (Range) Unit Step Default Description


Obj20DefVar 1:BinCnt32 - - 5:BinCnt32WoutF Object 20, default variation
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
Obj22DefVar 1:BinCnt32EvWout - - 1:BinCnt32EvWou Object 22, default variation
T tT
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
Obj30DefVar 1:AI32Int - - 3:AI32IntWithoutF Object 30, default variation
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
Obj32DefVar 1:AI32IntEvWoutF - - 1:AI32IntEvWoutF Object 32, default variation
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

Table 382: MST1TCP Non group settings (advanced)


Name Values (Range) Unit Step Default Description
AddrQueryEnbl No - - Yes Address query enable
Yes
tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout
ApplMultFrgRes No - - Yes Enable application for multiple fragment
Yes response
ConfMultFrag No - - Yes Confirm each multiple fragment
Yes
UREnable No - - Yes Unsolicited response enabled
Yes
URSendOnline No - - No Unsolicited response sends when on-line
Yes
UREvClassMask Off - - Off Unsolicited response, event class mask
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
UROfflineRetry 0 - 10 - 1 5 Unsolicited response retries before off-
line retry mode
tURRetryDelay 0.00 - 60.00 s 0.01 5.00 Unsolicited response retry delay in s
tUROfflRtryDel 0.00 - 60.00 s 0.01 30.00 Unsolicited response off-line retry delay
in s
Table continues on next page

627
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Values (Range) Unit Step Default Description


UREvCntThold1 1 - 100 - 1 5 Unsolicited response class 1 event count
report treshold
tUREvBufTout1 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 1 event
buffer timeout
UREvCntThold2 1 - 100 - 1 5 Unsolicited response class 2 event count
report treshold
tUREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 event
buffer timeout
UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event count
report treshold
tUREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 event
buffer timeout
DelOldBufFull No - - No Delete oldest event when buffer is full
Yes
tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status is
generated
TSyncReqAfTout No - - No Time synchronization request after
Yes timeout
DNPToSetTime No - - No Allow DNP to set time in IED
Yes
Averag3TimeReq No - - No Use average of 3 time requests
Yes
PairedPoint No - - Yes Enable paired point
Yes
tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout
tBrokenConTout 0 - 3600 s 1 0 Broken connection timeout
tKeepAliveT 0 - 3600 s 1 10 Keep-Alive timer

Table 383: MST2TCP Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
SlaveAddress 0 - 65519 - 1 1 Slave address
MasterAddres 0 - 65519 - 1 1 Master address
ValMasterAddr No - - Yes Validate source (master) address
Yes
MasterIP-Addr 0 - 18 - 1 0.0.0.0 Master IP-address
MasterIPNetMsk 0 - 18 - 1 255.255.255.255 Master IP net mask
Obj1DefVar 1:BISingleBit - - 1:BISingleBit Object 1, default variation
2:BIWithStatus
Obj2DefVar 1:BIChWithoutTim - - 3:BIChWithRelTim Object 2, default variation
e e
2:BIChWithTime
3:BIChWithRelTim
e
Table continues on next page

628
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Values (Range) Unit Step Default Description


Obj4DefVar 1:DIChWithoutTim - - 3:DIChWithRelTim Object 4, default variation
e e
2:DIChWithTime
3:DIChWithRelTim
e
Obj10DefVar 1:BO - - 2:BOStatus Object 10, default variation
2:BOStatus
Obj20DefVar 1:BinCnt32 - - 5:BinCnt32WoutF Object 20, default variation
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
Obj22DefVar 1:BinCnt32EvWout - - 1:BinCnt32EvWou Object 22, default variation
T tT
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
Obj30DefVar 1:AI32Int - - 3:AI32IntWithoutF Object 30, default variation
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
Obj32DefVar 1:AI32IntEvWoutF - - 1:AI32IntEvWoutF Object 32, default variation
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

Table 384: MST2TCP Non group settings (advanced)


Name Values (Range) Unit Step Default Description
AddrQueryEnbl No - - Yes Address query enable
Yes
tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout
ApplMultFrgRes No - - Yes Enable application for multiple fragment
Yes response
ConfMultFrag No - - Yes Confirm each multiple fragment
Yes
UREnable No - - Yes Unsolicited response enabled
Yes
URSendOnline No - - No Unsolicited response sends when on-line
Yes
Table continues on next page

629
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Values (Range) Unit Step Default Description


UREvClassMask Off - - Off Unsolicited response, event class mask
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
UROfflineRetry 0 - 10 - 1 5 Unsolicited response retries before off-
line retry mode
tURRetryDelay 0.00 - 60.00 s 0.01 5.00 Unsolicited response retry delay in s
tUROfflRtryDel 0.00 - 60.00 s 0.01 30.00 Unsolicited response off-line retry delay
in s
UREvCntThold1 1 - 100 - 1 5 Unsolicited response class 1 event count
report treshold
tUREvBufTout1 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 1 event
buffer timeout
UREvCntThold2 1 - 100 - 1 5 Unsolicited response class 2 event count
report treshold
tUREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 event
buffer timeout
UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event count
report treshold
tUREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 event
buffer timeout
DelOldBufFull No - - No Delete oldest event when buffer is full
Yes
tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status is
generated
TSyncReqAfTout No - - No Time synchronization request after
Yes timeout
DNPToSetTime No - - No Allow DNP to set time in IED
Yes
Averag3TimeReq No - - No Use average of 3 time requests
Yes
PairedPoint No - - Yes Enable paired point
Yes
tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout
tBrokenConTout 0 - 3600 s 1 0 Broken connection timeout
tKeepAliveT 0 - 3600 s 1 10 Keep-Alive timer

Table 385: MST3TCP Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
SlaveAddress 0 - 65519 - 1 1 Slave address
MasterAddres 0 - 65519 - 1 1 Master address
Table continues on next page

630
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Values (Range) Unit Step Default Description


ValMasterAddr No - - Yes Validate source (master) address
Yes
MasterIP-Addr 0 - 18 - 1 0.0.0.0 Master IP-address
MasterIPNetMsk 0 - 18 - 1 255.255.255.255 Master IP net mask
Obj1DefVar 1:BISingleBit - - 1:BISingleBit Object 1, default variation
2:BIWithStatus
Obj2DefVar 1:BIChWithoutTim - - 3:BIChWithRelTim Object 2, default variation
e e
2:BIChWithTime
3:BIChWithRelTim
e
Obj4DefVar 1:DIChWithoutTim - - 3:DIChWithRelTim Object 4, default variation
e e
2:DIChWithTime
3:DIChWithRelTim
e
Obj10DefVar 1:BO - - 2:BOStatus Object 10, default variation
2:BOStatus
Obj20DefVar 1:BinCnt32 - - 5:BinCnt32WoutF Object 20, default variation
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
Obj22DefVar 1:BinCnt32EvWout - - 1:BinCnt32EvWou Object 22, default variation
T tT
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
Obj30DefVar 1:AI32Int - - 3:AI32IntWithoutF Object 30, default variation
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
Obj32DefVar 1:AI32IntEvWoutF - - 1:AI32IntEvWoutF Object 32, default variation
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

Table 386: MST3TCP Non group settings (advanced)


Name Values (Range) Unit Step Default Description
AddrQueryEnbl No - - Yes Address query enable
Yes
tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout
ApplMultFrgRes No - - Yes Enable application for multiple fragment
Yes response
Table continues on next page

631
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Name Values (Range) Unit Step Default Description


ConfMultFrag No - - Yes Confirm each multiple fragment
Yes
UREnable No - - Yes Unsolicited response enabled
Yes
URSendOnline No - - No Unsolicited response sends when on-line
Yes
UREvClassMask Off - - Off Unsolicited response, event class mask
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
UROfflineRetry 0 - 10 - 1 5 Unsolicited response retries before off-
line retry mode
tURRetryDelay 0.00 - 60.00 s 0.01 5.00 Unsolicited response retry delay in s
tUROfflRtryDel 0.00 - 60.00 s 0.01 30.00 Unsolicited response off-line retry delay
in s
UREvCntThold1 1 - 100 - 1 5 Unsolicited response class 1 event count
report treshold
tUREvBufTout1 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 1 event
buffer timeout
UREvCntThold2 1 - 100 - 1 5 Unsolicited response class 2 event count
report treshold
tUREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 event
buffer timeout
UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event count
report treshold
tUREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 event
buffer timeout
DelOldBufFull No - - No Delete oldest event when buffer is full
Yes
tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status is
generated
TSyncReqAfTout No - - No Time synchronization request after
Yes timeout
DNPToSetTime No - - No Allow DNP to set time in IED
Yes
Averag3TimeReq No - - No Use average of 3 time requests
Yes
PairedPoint No - - Yes Enable paired point
Yes
tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout
tBrokenConTout 0 - 3600 s 1 0 Broken connection timeout
tKeepAliveT 0 - 3600 s 1 10 Keep-Alive timer

632
Technical reference manual
1MRK505183-UEN C Section 12
Control

Table 387: MST4TCP Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
SlaveAddress 0 - 65519 - 1 1 Slave address
MasterAddres 0 - 65519 - 1 1 Master address
ValMasterAddr No - - Yes Validate source (master) address
Yes
MasterIP-Addr 0 - 18 - 1 0.0.0.0 Master IP-address
MasterIPNetMsk 0 - 18 - 1 255.255.255.255 Master IP net mask
Obj1DefVar 1:BISingleBit - - 1:BISingleBit Object 1, default variation
2:BIWithStatus
Obj2DefVar 1:BIChWithoutTim - - 3:BIChWithRelTim Object 2, default variation
e e
2:BIChWithTime
3:BIChWithRelTim
e
Obj4DefVar 1:DIChWithoutTim - - 3:DIChWithRelTim Object 4, default variation
e e
2:DIChWithTime
3:DIChWithRelTim
e
Obj10DefVar 1:BO - - 2:BOStatus Object 10, default variation
2:BOStatus
Obj20DefVar 1:BinCnt32 - - 5:BinCnt32WoutF Object 20, default variation
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
Obj22DefVar 1:BinCnt32EvWout - - 1:BinCnt32EvWou Object 22, default variation
T tT
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
Obj30DefVar 1:AI32Int - - 3:AI32IntWithoutF Object 30, default variation
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
Obj32DefVar 1:AI32IntEvWoutF - - 1:AI32IntEvWoutF Object 32, default variation
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

633
Technical reference manual
Section 12 1MRK505183-UEN C
Control

Table 388: MST4TCP Non group settings (advanced)


Name Values (Range) Unit Step Default Description
AddrQueryEnbl No - - Yes Address query enable
Yes
tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout
ApplMultFrgRes No - - Yes Enable application for multiple fragment
Yes response
ConfMultFrag No - - Yes Confirm each multiple fragment
Yes
UREnable No - - Yes Unsolicited response enabled
Yes
URSendOnline No - - No Unsolicited response sends when on-line
Yes
UREvClassMask Off - - Off Unsolicited response, event class mask
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
UROfflineRetry 0 - 10 - 1 5 Unsolicited response retries before off-
line retry mode
tURRetryDelay 0.00 - 60.00 s 0.01 5.00 Unsolicited response retry delay in s
tUROfflRtryDel 0.00 - 60.00 s 0.01 30.00 Unsolicited response off-line retry delay
in s
UREvCntThold1 1 - 100 - 1 5 Unsolicited response class 1 event count
report treshold
tUREvBufTout1 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 1 event
buffer timeout
UREvCntThold2 1 - 100 - 1 5 Unsolicited response class 2 event count
report treshold
tUREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 event
buffer timeout
UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event count
report treshold
tUREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 event
buffer timeout
DelOldBufFull No - - No Delete oldest event when buffer is full
Yes
tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status is
generated
TSyncReqAfTout No - - No Time synchronization request after
Yes timeout
DNPToSetTime No - - No Allow DNP to set time in IED
Yes
Averag3TimeReq No - - No Use average of 3 time requests
Yes
PairedPoint No - - Yes Enable paired point
Yes
Table continues on next page

634
Technical reference manual
1MRK505183-UEN C Section 12
Control

Name Values (Range) Unit Step Default Description


tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout
tBrokenConTout 0 - 3600 s 1 0 Broken connection timeout
tKeepAliveT 0 - 3600 s 1 10 Keep-Alive timer

12.10 Single command, 16 signals SINGLECMD

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Single command, 16 signals SINGLECMD - -

12.10.1 Introduction
The IEDs can receive commands either from a substation automation system or
from the local HMI. The command function block has outputs that can be used, for
example, to control high voltage apparatuses or for other user defined functionality.

12.10.2 Principle of operation


Single command, 16 signals (SINGLECMD) function has 16 binary output signals.
The outputs can be individually controlled from a substation automation system or
from the local HMI. Each output signal can be given a name with a maximum of
13 characters in PCM600.

The output signals can be of the types Off, Steady, or Pulse. This configuration
setting is done via the local HMI or PCM600 and is common for the whole
function block. The length of the output pulses are 100 ms. In steady mode,
SINGLECMD function has a memory to remember the output values at power
interruption of the IED. Also a BLOCK input is available used to block the
updating of the outputs.

The output signals, OUT1 to OUT16, are available for configuration to built-in
functions or via the configuration logic circuits to the binary outputs of the IED.

635
Technical reference manual
Section 12 1MRK505183-UEN C
Control

12.10.3 Function block


SINGLECMD
BLOCK ^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16

IEC05000698-2-en.vsd
IEC05000698 V3 EN

Figure 339: SINGLECMD function block

12.10.4 Input and output signals


Table 389: SINGLECMD Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block single command function

Table 390: SINGLECMD Output signals


Name Type Description
OUT1 BOOLEAN Single command output 1
OUT2 BOOLEAN Single command output 2
OUT3 BOOLEAN Single command output 3
OUT4 BOOLEAN Single command output 4
OUT5 BOOLEAN Single command output 5
OUT6 BOOLEAN Single command output 6
OUT7 BOOLEAN Single command output 7
OUT8 BOOLEAN Single command output 8
OUT9 BOOLEAN Single command output 9
OUT10 BOOLEAN Single command output 10
OUT11 BOOLEAN Single command output 11
OUT12 BOOLEAN Single command output 12
OUT13 BOOLEAN Single command output 13
OUT14 BOOLEAN Single command output 14
OUT15 BOOLEAN Single command output 15
OUT16 BOOLEAN Single command output 16

636
Technical reference manual
1MRK505183-UEN C Section 12
Control

12.10.5 Setting parameters


Table 391: SINGLECMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
Mode Off - - Off Operation mode
Steady
Pulsed

637
Technical reference manual
638
1MRK505183-UEN C Section 13
Scheme communication

Section 13 Scheme communication

About this chapter


This chapter describes the scheme communication logic that is used in distance and
earth fault protection function to obtain almost instantaneous fault clearance for
faults on the protected line. The chapter considers scheme communication logic
(ZCPSCH), current reversal and weak-end in-feed logic (ZCRWPSCH) for the
distance protection function and scheme communication logic for residual
overcurrent protection (ECPSCH) and current reversal and weak-end in-feed logic
(ECRWPSCH) for the residual overcurrent function.

Also Local acceleration logic (ZCLCPLAL) is discussed which is a function that


can generate instantaneous tripping as a result of remote end faults without any
telecommunication.

The chapter contains a short description of the design, simplified logical block
diagrams, figure of the function block, input and output signals and setting
parameters.

13.1 Scheme communication logic for distance or


overcurrent protection ZCPSCH

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Scheme communication logic for ZCPSCH - 85
distance or overcurrent protection

13.1.1 Introduction
To achieve instantaneous fault clearance for all line faults, a scheme
communication logic is provided. All types of communication schemes for
example, permissive underreaching, permissive overreaching, blocking,
unblocking, intertrip are available.

The built-in communication module (LDCM) can be used for scheme


communication signaling when included.

Phase segregated communication is also available for correct operation at


simultaneous faults when three distance protection communication channels are
available between the line ends.

639
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

13.1.2 Principle of operation


Depending on whether a reverse or forward directed impedance zone is used to
issue the send signal, the communication schemes are divided into Blocking and
Permissive schemes, respectively.

A permissive scheme is inherently faster and has better security against false
tripping than a blocking scheme. On the other hand, a permissive scheme depends
on a received signal for a fast trip, so its dependability is lower than that of a
blocking scheme.

13.1.2.1 Blocking scheme

The principle of operation for a blocking scheme is that an overreaching zone is


allowed to trip instantaneously after the settable co-ordination time tCoord has
elapsed, when no signal is received from the remote IED.

The received signal, which shall be connected to CR, is used to not release the zone
to be accelerated to clear the fault instantaneously (after time tCoord). The
overreaching zone to be accelerated is connected to the input CACC, see figure 340.

In case of external faults, the blocking signal (CR) must be received before the
settable timer tCoord elapses, to prevent a false trip, see figure 340.

The function can be totally blocked by activating the input BLOCK, block of trip
by activating the input BLKTR, Block of signal send by activating the input BLKCS.

tCoord
CACC
t TRIP
CR AND

en05000512.vsd
IEC05000512 V1 EN

Figure 340: Basic logic for trip signal in blocking scheme

Channels for communication in each direction must be available.

13.1.2.2 Permissive underreaching scheme

In a permissive underreaching scheme, a forward directed underreach measuring


element (normally zone1) sends a permissive signal CS to the remote end if a fault
is detected in forward direction. The received signal CR is used to allow an
overreaching zone to trip after the tCoord timer has elapsed. The tCoord in
permissive underreaching schemes is normally set to zero.

The logic for trip signal in permissive scheme is shown in figure 341.

640
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

tCoord
CACC
t TRIP
CR AND

en05000513.vsd
IEC05000513 V1 EN

Figure 341: Logic for trip signal in permissive scheme

The permissive underreaching scheme has the same blocking possibilities as


mentioned for blocking scheme.

13.1.2.3 Permissive overreaching scheme

In a permissive overreaching scheme, a forward directed overreach measuring


element (normally zone2) sends a permissive signal CS to the remote end if a fault
is detected in forward direction. The received signal CR is used to allow an
overreaching zone to trip after the settable tCoord timer has elapsed. The tCoord in
permissive overreaching schemes is normally set to zero.

The logic for trip signal is the same as for permissive underreaching, as in
figure 341.

The permissive overreaching scheme has the same blocking possibilities as


mentioned for blocking scheme.

13.1.2.4 Unblocking scheme

In unblocking scheme, the lower dependability in permissive scheme is overcome


by using the loss of guard signal from the communication equipment to locally
create a receive signal. It is common or suitable to use the function when older, less
reliable, power-line carrier (PLC) communication is used.

The unblocking function uses a guard signal CRG, which must always be present,
even when no CR signal is received. The absence of the CRG signal for a time
longer than the setting tSecurity time is used as a CR signal, see figure 342. This
also enables a permissive scheme to operate when the line fault blocks the signal
transmission.

The received signal created by the unblocking function is reset 150 ms after the
security timer has elapsed. When that occurs an output signal LCG is activated for
signalling purpose. The unblocking function is reset 200 ms after that the guard
signal is present again.

641
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

CR
tSecurity CRL
t >1
1
CRG
200 ms 150 ms
t OR t AND
AND
LCG

en05000746.vsd
IEC05000746 V1 EN

Figure 342: Guard signal logic with unblocking scheme

The unblocking function can be set in three operation modes (setting Unblock):

Off The unblocking function is out of operation


No restart Communication failure shorter than tSecurity will be ignored
If CRG disappears a CRL signal will be transferred to the trip logic
There will not be any information in case of communication failure (LCG)
Restart Communication failure shorter than tSecurity will be ignored
It sends a defined (150 ms) CRL after the disappearance of the CRG signal
The function will activate LCG output in case of communication failure
If the communication failure comes and goes (<200 ms) there will not be recurrent
signalling

13.1.2.5 Intertrip scheme

In the direct intertrip scheme, the send signal CS is sent from an underreaching
zone that is tripping the line.

The received signal CR is directly transferred to a TRIP for tripping without local
criteria. The signal is further processed in the tripping logic.

In case of single-pole tripping in multi-phase systems, a phase selection is performed.

13.1.2.6 Simplified logic diagram

The simplified logic diagram for the complete logic is shown in figure 343.

642
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

Unblock =Off

CR

Unblock =
OR CRL
NoRestart AND
CRL
Unblock =
tSecurit
Restart
y
CRG 1 t AND

200 ms 150 ms LCG


AND
t OR AND t

SchemeType =
Intertrip

CSUR
tSendMi
n AND
OR

BLOCK AND
CSBLK OR
CRL

Schemetype =
Permissive UR AND CS
OR

tCoord
AND 25 ms
OR
t TRIP
CACC t

Schemetype =
Permissive OR

CSOR OR AND

AND
tSendMin
OR
AND
SchemeType =
Blocking

BLKCS

AND

IEC05000515-2-en.vsd
IEC05000515 V2 EN

Figure 343: Scheme communication logic for distance or overcurrent


protection, simplified logic diagram

643
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

13.1.3 Function block


ZCPSCH
BLOCK TRIP
BLKTR CS
BLKCS CRL
CSBLK LCG
CACC
CSOR
CSUR
CR
CRG

IEC06000286-2-en.vsd
IEC06000286 V2 EN

Figure 344: ZCPSCH function block

13.1.4 Input and output signals


Table 392: ZCPSCH Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Signal for block of trip output from communication
logic
BLKCS BOOLEAN 0 Block of carrier send in permissive OR and
blocking schemes
CSBLK BOOLEAN 0 Reverse directed distance protection zone signal
CACC BOOLEAN 0 Permissive distance protection zone signal
CSOR BOOLEAN 0 Overreaching distance protection zone signal
CSUR BOOLEAN 0 Underreaching distance protection zone signal
CR BOOLEAN 0 Carrier Signal Received
CRG BOOLEAN 0 Carrier guard signal received

Table 393: ZCPSCH Output signals


Name Type Description
TRIP BOOLEAN Trip output
CS BOOLEAN Carrier Send signal
CRL BOOLEAN Carrier signal received or missing carrier guard
signal
LCG BOOLEAN Loss of carrier guard signal

644
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

13.1.5 Setting parameters


Table 394: ZCPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
SchemeType Off - - Permissive UR Scheme type
Intertrip
Permissive UR
Permissive OR
Blocking
tCoord 0.000 - 60.000 s 0.001 0.035 Co-ordination time for blocking
communication scheme
tSendMin 0.000 - 60.000 s 0.001 0.100 Minimum duration of a carrier send signal

Table 395: ZCPSCH Group settings (advanced)


Name Values (Range) Unit Step Default Description
Unblock Off - - Off Operation mode of unblocking logic
NoRestart
Restart
tSecurity 0.000 - 60.000 s 0.001 0.035 Security timer for loss of carrier guard
detection

13.1.6 Technical data


Table 396: ZCPSCH technical data
Function Range or value Accuracy
Scheme type Intertrip -
Permissive Underreach
Permissive Overreach
Blocking
Co-ordination time for blocking (0.000-60.000) s ± 0.5% ± 10 ms
communication scheme
Minimum duration of a send signal (0.000-60.000) s ± 0.5% ± 10 ms
Security timer for loss of guard (0.000-60.000) s ± 0.5% ± 10 ms
signal detection
Operation mode of unblocking logic Off -
NoRestart
Restart

645
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

13.2 Phase segregated scheme communication logic for


distance protection ZC1PPSCH

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Phase segregated Scheme ZC1PPSCH - 85
communication logic for distance
protection

13.2.1 Introduction
Communication between line ends is used to achieve fault clearance for all faults
on a power line. All possible types of communication schemes for example,
permissive underreach, permissive overreach and blocking schemes are available.
To manage problems with simultaneous faults on parallel power lines phase
segregated communication is needed. This will then replace the standard Scheme
communication logic for distance or Overcurrent protection (ZCPSCH) on
important lines where three communication channels (in each subsystem) are
available for the distance protection communication.

The main purpose of the Phase segregated scheme communication logic for
distance protection (ZC1PPSCH) function is to supplement the distance protection
function such that:

• fast clearance of faults is also achieved at the line end for which the faults are
on the part of the line not covered by its underreaching zone.
• correct phase selection can be maintained to support single-pole tripping for
faults occurring anywhere on the entire length of a double circuit line.

To accomplish this, three separate communication channels, that is, one per phase,
each capable of transmitting a signal in each direction is required.

ZC1PPSCH can be completed with the current reversal and WEI logic for phase
segregated communication, when found necessary in Blocking and Permissive
overreaching schemes.

13.2.2 Principle of operation


Depending on whether a reverse or forward directed impedance zone is used to
issue the send signal, the communication schemes are divided into Blocking and
Permissive schemes, respectively.

A permissive scheme is inherently faster and has better security against false
tripping than a blocking scheme. On the other hand, a permissive scheme depends
on a received signal for a fast trip, so its dependability is lower than that of a
blocking scheme.

646
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

The Phase segregated scheme communication logic for distance protection


(ZC1PPSCH) function is a logical function built-up from logical elements. It is a
supplementary function to the distance protection, requiring for its operation inputs
from the distance protection and the communication equipment.

The type of communication-aided scheme to be used can be selected by way of the


settings.

The ability to select which distance protection zone is assigned to which input of
ZC1PPSCH makes this logic able to support practically any scheme
communication requirements regardless of their basic operating principle. The
outputs to initiate tripping and sending of the teleprotection signal are given in
accordance with the type of communication-aided scheme selected and the zone(s)
and phase(s) of the distance protection which have operated.

When power line carrier communication channels are used for permissive schemes
communication, unblocking logic which uses the loss of guard signal as a receive
criteria is provided. This logic compensates for the lack of dependability due to the
transmission of the command signal over the faulted line.

13.2.2.1 Blocking scheme

The principle of operation for a blocking scheme is that an overreaching zone is


allowed to trip instantaneously after the settable co-ordination time tCoord has
elapsed, when no signal is received from the remote IED. The received signal (sent
by a reverse looking element in the remote IED), which shall be connected to
CRLx, is used to not release the zone to be accelerated to clear the fault
instantaneously (after time tCoord). The overreaching zone to be accelerated is
connected to the input CACCLx, see figure 345. In case of external faults, the
blocking signal (CRLx) must be received before the settable timer tCoord elapses,
to prevent an unneccesary trip, see figure 345.

ZC1PPSCH can be totally blocked by activating the input BLOCK, block of trip is
achieved by activating the input BLKTRLx, Block of carrier send is done by
activating the input BLKCSLx.

tCoord 25 ms
CACCLx
t t TRLx
CRLx AND

IEC06000310_2_en.vsd
IEC06000310 V2 EN

Figure 345: Basic logic for trip carrier in one phase of a blocking scheme

13.2.2.2 Permissive underreach scheme

In a permissive underreach scheme, a forward directed underreach measuring


element (normally zone1) sends a permissive signal CSLx to the remote end if a
fault is detected in forward direction. The received signal CRLx is used to allow an

647
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

overreaching zone (connected to CACCLx) to trip after the tCoord timer has
elapsed. The tCoord is in permissive underreach schemes normally set to zero. The
logic for trip carrier in permissive scheme is shown in figure 346. Three channels
for communication in each direction must be available.

tCoord 25 ms
CACCLx t t TRLx
CRLx AND

IEC07000088_2_en.vsd
IEC07000088 V2 EN

Figure 346: Basic logic for trip carrier in one phase of a permissive underreach
scheme

13.2.2.3 Permissive overreach scheme

In a permissive overreach scheme, a forward directed overreach measuring element


(normally zone2) sends a permissive signal CSLx to the remote end if a fault is
detected in forward direction. The received signal CRLx is used to allow an
overreaching zone to trip after the settable tCoord timer has elapsed. The tCoord is
in permissive overreach schemes normally set to zero. The logic for trip carrier is
the same as for permissive underreach, see figure 345.

The permissive overreach scheme has the same blocking possibilities as mentioned
for blocking scheme above. The blocking inputs are activated from the current
reversal logic when this function is included.

Three channels for communication in each direction must be available.

13.2.2.4 Unblocking scheme

In an unblocking scheme, the lower dependability in permissive scheme is


overcome by using the loss of guard signal from the communication equipment to
locally create a carrier receive signal. It is common or suitable to use the function
when older, less reliable, power-line carrier (PLC) communication is used. As
phase segregated communication schemes uses phases individually and the PLC is
typically connected single-phase or phase-to-phase it is not possible to evaluate
which of the phases to release and the unblocking scheme has thus not been supported.

13.2.2.5 Intertrip scheme

In the direct intertrip scheme, the carrier send signal CS is sent from an
underreaching zone that is tripping the line.

The received signal per phase is directly transferred to the trip function block for
tripping without local criteria. The signal is not further processed in the phase
segregated communication logic. In case of single-pole tripping the phase selection
and logic for tripping the three phases is performed in the trip function block.

648
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

13.2.2.6 Simplified logic diagram

The simplified logic diagram for one phase is shown in figure 347.

SchemeType =
Intertrip

CSURLx

tSendMin AND
OR

BLOCK
AND
CSBLKLx OR
CRLx

Scheme Type =
Permissive UR AND CSLx
OR

tCoord
25 ms
AND t TRLx
OR t
CACCLx

Scheme Type =
Permissive OR

CSORLx OR AND

AND

tSendMin
OR

AND
Scheme Type =
Blocking
BLKCSx

AND

CSL1
CSL2 AND

CSL2
OR CSMPH
CSL3 AND

CSL3
CSL1 AND

CSL1
CSL2 GENERAL
OR
CSL3

IEC06000311_2_en.vsd
IEC06000311 V2 EN

Figure 347: Simplified logic diagram for one phase

649
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

13.2.3 Function block


ZC1PPSCH
BLOCK TRIP
BLKTR TRL1
BLKTRL1 TRL2
BLKTRL2 TRL3
BLKTRL3 CSL1
CACCL1 CSL2
CACCL2 CSL3
CACCL3 CSMPH
CSURL1 CRLL1
CSURL2 CRLL2
CSURL3 CRLL3
CSORL1
CSORL2
CSORL3
CSBLKL1
CSBLKL2
CSBLKL3
BLKCSL1
BLKCSL2
BLKCSL3
CRL1
CRL2
CRL3
CRMPH

IEC06000427-2-en.vsd
IEC06000427 V2 EN

Figure 348: ZC1PPSCH function block

13.2.4 Input and output signals


Table 397: ZC1PPSCH Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Common signal for block of trip output from
communication logic in all phases
BLKTRL1 BOOLEAN 0 Signal for block of trip output from communication
logic in Phase L1
BLKTRL2 BOOLEAN 0 Signal for block of trip output from communication
logic in Phase L2
BLKTRL3 BOOLEAN 0 Signal for block of trip output from communication
logic in Phase L3
CACCL1 BOOLEAN 0 Accelerated Distance protection zone start in
Phase L1
CACCL2 BOOLEAN 0 Accelerated Distance protection zone signal in
Phase L2
CACCL3 BOOLEAN 0 Accelerated Distance protection zone signal in
Phase L3
CSURL1 BOOLEAN 0 Underreaching distance protection zone signal in
Phase L1
CSURL2 BOOLEAN 0 Underreaching distance protection zone signal in
Phase L2
CSURL3 BOOLEAN 0 Underreaching distance protection zone signal in
Phase L3
Table continues on next page

650
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

Name Type Default Description


CSORL1 BOOLEAN 0 Overreaching distance protection zone signal in
Phase L1
CSORL2 BOOLEAN 0 Overreaching distance protection zone signal in
Phase L2
CSORL3 BOOLEAN 0 Overreaching distance protection zone signal in
Phase L3
CSBLKL1 BOOLEAN 0 Reverse directed distance protection zone signal
in Phase L1
CSBLKL2 BOOLEAN 0 Reverse directed distance protection zone signal
in Phase L2
CSBLKL3 BOOLEAN 0 Reverse directed distance protection zone signal
in Phase L3
BLKCSL1 BOOLEAN 0 Block of carrier send in POR and Blocking
schemes in Phase L1
BLKCSL2 BOOLEAN 0 Block of carrier send in POR and Blocking
schemes in Phase L2
BLKCSL3 BOOLEAN 0 Block of carrier send in POR and Blocking
schemes in Phase L3
CRL1 BOOLEAN 0 Carrier signal received in Phase L1
CRL2 BOOLEAN 0 Carrier signal received in Phase L2
CRL3 BOOLEAN 0 Carrier signal received in Phase L3
CRMPH BOOLEAN 0 Carrier Signal received for multiphase fault

Table 398: ZC1PPSCH Output signals


Name Type Description
TRIP BOOLEAN Common trip output in any of the phase
TRL1 BOOLEAN Trip output in Phase L1
TRL2 BOOLEAN Trip output in Phase L2
TRL3 BOOLEAN Trip output in Phase L3
CSL1 BOOLEAN Carrier Send in phase L1
CSL2 BOOLEAN Carrier Send in phase L2
CSL3 BOOLEAN Carrier Send in phase L3
CSMPH BOOLEAN carrier Send for multi phase fault
CRLL1 BOOLEAN Carrier signal received in Phase L1
CRLL2 BOOLEAN Carrier signal received in Phase L2
CRLL3 BOOLEAN Carrier signal received in Phase L3

651
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

13.2.5 Setting parameters


Table 399: ZC1PPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation On / Off
On
Scheme Type Off - - Permissive UR Scheme type
Intertrip
Permissive UR
Permissive OR
Blocking
tCoord 0.000 - 60.000 s 0.001 0.000 Trip coordinate time
tSendMin 0.000 - 60.000 s 0.001 0.100 Minimum duration of Carrier Send signal

13.2.6 Technical data


Table 400: ZC1PPSCH technical data
Function Range or value Accuracy
Scheme type Intertrip -
Permissive UR
Permissive OR
Blocking
Co-ordination time for blocking (0.000-60.000) s ± 0.5% ± 10 ms
communication scheme
Minimum duration of a carrier send (0.000-60.000) s ± 0.5% ± 10 ms
signal
Security timer for loss of carrier (0.000-60.000) s ± 0.5% ± 10 ms
guard detection
Operation mode of unblocking logic Off -
NoRestart
Restart

13.3 Current reversal and weak-end infeed logic for


distance protection ZCRWPSCH

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Current reversal and weak-end infeed ZCRWPSCH - 85
logic for distance protection

13.3.1 Introduction
The current reversal function is used to prevent unwanted operations due to current
reversal when using permissive overreach protection schemes in application with
parallel lines when the overreach from the two ends overlap on the parallel line.

652
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

The weak-end infeed logic is used in cases where the apparent power behind the
protection can be too low to activate the distance protection function. When
activated, received carrier signal together with local under voltage criteria and no
reverse zone operation gives an instantaneous trip. The received signal is also
echoed back to accelerate the sending end.

Three phase or phase segregated scheme logic is available.

13.3.2 Principle of operation

13.3.2.1 Current reversal logic

The current reversal logic uses a reverse zone connected to the input IRV to
recognize the fault on the parallel line in any of the phases. When the reverse zone
has been activated for a certain settable time tPickUpRev it prevents sending of a
communication signal and activation of trip signal for a predefined time tDelayRev.
This makes it possible for the receive signal to reset before the trip signal is
activated due to the current reversal by the forward directed zone, see figure 349.

tPickUpRev 10 ms tPickUpRev
IRV t t t
tDelayRev
IRVL
IRVBLK AND t

en05000122_2_en.vsd
IEC05000122 V2 EN

Figure 349: Current reversal logic

The preventing of sending the send signal CS and activating of the TRIP in the
scheme communication block ZCPSCH is carried out by connecting the IRVL
signal to input BLOCK in the ZCPSCH function.

The function has an internal 10 ms drop-off timer which secure that the current
reversal logic will be activated for short input signals even if the pick-up timer is
set to zero.

13.3.2.2 Weak-end infeed logic

The weak-end infeed logic (WEI) function sends back (echoes) the received signal
under the condition that no fault has been detected on the weak-end by different
fault detection elements (distance protection in forward and reverse direction).

The WEI function returns the received signal, see figure 350, when:

653
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

• No active signal present on the input BLOCK.


• The functional input CRL is active. This input is usually connected to the CRL
output on the scheme communication logic ZCPSCH .
• The WEI function is not blocked by the active signal connected to the
WEIBLK1 functional input or to the VTSZ functional input. The later is
usually configured to the BLOCK functional output of the fuse-failure function.
• No active signal has been present for at least 200 ms on the WEIBLK2
functional input. An OR combination of all fault detection functions (not
undervoltage) as present within the IED is usually used for this purpose.

IEC05000123 V1 EN

Figure 350: Echo of a received signal by the WEI function

When an echo function is used in both IEDs (should generally be avoided), a


spurious signal can be looped round by the echo logics. To avoid a continuous lock-
up of the system, the duration of the echoed signal is limited to 200 ms.

An undervoltage criteria is used as an additional tripping criteria, when the tripping


of the local breaker is selected, setting WEI = Echo&Trip, together with the WEI
function and ECHO signal has been issued by the echo logic, see figure 351.

IEC00000551-TIFF V1 EN

Figure 351: Tripping part of the WEI logic, simplified diagram

654
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

13.3.3 Function block


ZCRWPSCH
U3P* IRVL
BLOCK TRWEI
IRVBLK TRWEIL1
IRV TRWEIL2
WEIBLK1 TRWEIL3
WEIBLK2 ECHO
VTSZ
CBOPEN
CRL

IEC06000287-2-en.vsd
IEC06000287 V2 EN

Figure 352: ZCRWPSCH function block

13.3.4 Input and output signals


Table 401: ZCRWPSCH Input signals
Name Type Default Description
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
IRVBLK BOOLEAN 0 Block of current reversal function
IRV BOOLEAN 0 Activation of current reversal logic
WEIBLK1 BOOLEAN 0 Block of WEI logic
WEIBLK2 BOOLEAN 0 Block of WEI logic due to operation of other
protections
VTSZ BOOLEAN 0 Block of trip from WEI logic through fuse-failure
function
CBOPEN BOOLEAN 0 Block of trip from WEI logic by an open breaker
CRL BOOLEAN 0 POR Carrier receive for WEI logic

Table 402: ZCRWPSCH Output signals


Name Type Description
IRVL BOOLEAN Operation of current reversal logic
TRWEI BOOLEAN Trip of WEI logic
TRWEIL1 BOOLEAN Trip of WEI logic in phase L1
TRWEIL2 BOOLEAN Trip of WEI logic in phase L2
TRWEIL3 BOOLEAN Trip of WEI logic in phase L3
ECHO BOOLEAN Carrier send by WEI logic

655
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

13.3.5 Setting parameters


Table 403: ZCRWPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
CurrRev Off - - Off Operating mode of Current Reversal
On Logic
tPickUpRev 0.000 - 60.000 s 0.001 0.020 Pickup time for current reversal logic
tDelayRev 0.000 - 60.000 s 0.001 0.060 Time Delay to prevent Carrier send and
local trip
WEI Off - - Off Operating mode of WEI logic
Echo
Echo & Trip
tPickUpWEI 0.000 - 60.000 s 0.001 0.010 Coordination time for the WEI logic
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level
UPP< 10 - 90 %UB 1 70 Phase to Phase voltage for detection of
fault condition
UPN< 10 - 90 %UB 1 70 Phase to Neutral voltage for detection of
fault condition

13.3.6 Technical data


Table 404: ZCRWPSCH technical data
Function Range or value Accuracy
Detection level phase-to-neutral (10-90)% of UBase ± 1.0% of Ur
voltage
Detection level phase-to-phase (10-90)% of UBase ± 1.0% of Ur
voltage
Reset ratio <105% -
Operate time for current reversal (0.000-60.000) s ± 0.5% ± 10 ms
logic
Delay time for current reversal (0.000-60.000) s ± 0.5% ± 10 ms
Coordination time for weak-end (0.000-60.000) s ± 0.5% ± 10 ms
infeed logic

13.4 Local acceleration logic ZCLCPLAL

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Local acceleration logic ZCLCPLAL - -

656
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

13.4.1 Introduction
To achieve fast clearing of faults on the whole line, when no communication
channel is available, local acceleration logic (ZCLCPLAL) can be used. This logic
enables fast fault clearing during certain conditions, but naturally, it can not fully
replace a communication channel.

The logic can be controlled either by the autorecloser (zone extension) or by the loss-
of-load current (loss-of-load acceleration).

13.4.2 Principle of operation

13.4.2.1 Zone extension

The overreaching zone is connected to the input EXACC. For this reason,
configure the ARREADY functional input to a READY functional output of a used
autoreclosing function or via the selected binary input to an external autoreclosing
device, see figure 353.

This will allow the overreaching zone to trip instantaneously.

IEC05000157 V1 EN

Figure 353: Simplified logic diagram for local acceleration logic

After the autorecloser initiates the close command and remains in the reclaim state,
there will be no ARREADY signal, and the protection will trip normally with step
distance time functions.

In case of a fault on the adjacent line within the overreaching zone range, an
unwanted autoreclosing cycle will occur. The step distance function at the
reclosing attempt will prevent an unwanted retrip when the breaker is reclosed.

On the other hand, at a persistent line fault on line section not covered by
instantaneous zone (normally zone 1) only the first trip will be "instantaneous".

The function will be blocked if the input BLOCK is activated (common with loss-of-
load acceleration).

657
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

13.4.2.2 Loss-of-Load acceleration

When the "acceleration" is controlled by a loss-of-load, the overreaching zone used


for "acceleration" connected to input LLACC is not allowed to trip
"instantaneously" during normal non-fault system conditions. When all three-phase
currents have been above the set value MinCurr for more than setting tLowCurr, an
overreaching zone will be allowed to trip "instantaneously" during a fault condition
when one or two of the phase currents will become low due to a three-phase trip at
the opposite IED, see figure 354. The current measurement is performed internally
and the internal STILL signal becomes logical one under the described conditions.
The load current in a healthy phase is in this way used to indicate the tripping at the
opposite IED. Note that this function will not operate in case of three-phase faults,
because none of the phase currents will be low when the opposite IED is tripped.

IEC05000158 V1 EN

Figure 354: Loss-of-load acceleration - simplified logic diagram

Breaker closing signals can if decided be connected to block the function during
normal closing.

13.4.3 Function block


ZCLCPLAL
I3P* TRZE
BLOCK TRLL
ARREADY
NDST
EXACC
BC
LLACC

IEC05000333-2-en.vsd
IEC05000333 V2 EN

Figure 355: ZCLCPLAL function block

658
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

13.4.4 Input and output signals


Table 405: ZCLCPLAL Input signals
Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
ARREADY BOOLEAN 0 Autoreclosure ready, releases function used for
fast trip
NDST BOOLEAN 0 Non directional criteria used to prevent
instantaneous trip
EXACC BOOLEAN 0 Connected to function used for tripping at zone
xtension
BC BOOLEAN 0 Breaker Close
LLACC BOOLEAN 0 Connected to function used for tripping at loss of
load

Table 406: ZCLCPLAL Output signals


Name Type Description
TRZE BOOLEAN Trip by zone extension
TRLL BOOLEAN Trip by loss of load

13.4.5 Setting parameters


Table 407: ZCLCPLAL Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base setting for current values
LoadCurr 1 - 100 %IB 1 10 Load current before disturbance in % of
IBase
LossOfLoad Off - - Off Enable/Disable operation of Loss of load.
On
ZoneExtension Off - - Off Enable/Disable operation of Zone
On extension
MinCurr 1 - 100 %IB 1 5 Lev taken as curr loss due to remote CB
trip in % of IBase
tLowCurr 0.000 - 60.000 s 0.001 0.200 Time delay on pick-up for MINCURR
value
tLoadOn 0.000 - 60.000 s 0.001 0.000 Time delay on pick-up for load current
release
tLoadOff 0.000 - 60.000 s 0.001 0.300 Time delay on drop off for load current
release

659
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

13.5 Scheme communication logic for residual


overcurrent protection ECPSCH

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Scheme communication logic for ECPSCH - 85
residual overcurrent protection

13.5.1 Introduction

13.5.1.1 Introduction

To achieve fast fault clearance of earth faults on the part of the line not covered by
the instantaneous step of the residual overcurrent protection, the directional
residual overcurrent protection can be supported with a logic that uses
communication channels.

In the directional scheme, information of the fault current direction must be


transmitted to the other line end. With directional comparison, a short operates time
of the protection including a channel transmission time, can be achieved. This short
operate time enables rapid autoreclosing function after the fault clearance.

The communication logic module for directional residual current protection


enables blocking as well as permissive under/overreaching schemes. The logic can
also be supported by additional logic for weak-end infeed and current reversal,
included in Current reversal and weak-end infeed logic for residual overcurrent
protection Current reversal and weak-end infeed logic for residual overcurrent
protection (ECRWPSCH) function.

13.5.2 Principle of operation


The four step directional residual overcurrent protection EF4PTOC is configured to
give input information, that is directional fault detection signals, to the ECPSCH
logic:

660
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

• Input signal CACC is used for tripping of the communication scheme,


normally the start signal of a forward overreaching step of STFW.
• Input signal CSBLK is used for sending block signal in the blocking
communication scheme, normally the start signal of a reverse overreaching
step of STRV.
• Input signal CSUR is used for sending permissive signal in the underreaching
permissive communication scheme, normally the start signal of a forward
underreaching step of STINn, where n corresponds to the underreaching step.
• Input signal CSOR is used for sending permissive signal in the overreaching
permissive communication scheme, normally the start signal of a forward
overreaching step of STINn, where n corresponds to the overreaching step.

In addition to this a signal from the autoreclosing function should be configured to


the BLKCS input for blocking of the function at a single phase reclosing cycle.

13.5.2.1 Blocking scheme

In the blocking scheme a signal is sent to the other line end if the directional
element detects an earth fault in the reverse direction. When the forward directional
element operates, it trips after a short time delay if no blocking signal is received
from the opposite line end. The time delay, normally 30 – 40 ms, depends on the
communication transmission time and a chosen safety margin.

One advantage of the blocking scheme is that only one channel (carrier frequency)
is needed if the ratio of source impedances at both end is approximately equal for
zero and positive sequence source impedances, the channel can be shared with the
impedance measuring system, if that system also works in the blocking mode. The
communication signal is transmitted on a healthy line and no signal attenuation will
occur due to the fault.

Blocking schemes are particular favorable for three-terminal applications if there is


no zero-sequence outfeed from the tapping. The blocking scheme is immune to
current reversals because the received signal is maintained long enough to avoid
unwanted operation due to current reversal. There is never any need for weak-end
infeed logic, because the strong end trips for an internal fault when no blocking
signal is received from the weak end. The fault clearing time is however generally
longer for a blocking scheme than for a permissive scheme.

If the fault is on the line, the forward direction measuring element operates. If no
blocking signal comes from the other line end via the CR binary input (received
signal) the TRIP output is activated after the tCoord set time delay.

661
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

IEC05000448 V1 EN

Figure 356: Simplified logic diagram for blocking scheme

13.5.2.2 Permissive under/overreaching scheme

In the permissive scheme the forward directed earth-fault measuring element sends
a permissive signal to the other end, if an earth fault is detected in the forward
direction. The directional element at the other line end must wait for a permissive
signal before activating a trip signal. Independent channels must be available for
the communication in each direction.

An impedance measuring IED, which works in the same type of permissive mode,
with one channel in each direction, can share the channels with the communication
scheme for residual overcurrent protection. If the impedance measuring IED works
in the permissive overreaching mode, common channels can be used in single line
applications. In case of double lines connected to a common bus at both ends, use
common channels only if the ratio Z1S/Z0S (positive through zero-sequence source
impedance) is about equal at both ends. If the ratio is different, the impedance
measuring and the directional earth-fault current system of the healthy line may
detect a fault in different directions, which could result in unwanted tripping.

Common channels cannot be used when the weak-end infeed function is used in
the distance or earth-fault protection.

In case of an internal earth-fault, the forward directed measuring element operates


and sends a permissive signal to the remote end via the CS output (sent signal).
Local tripping is permitted when the forward direction measuring element operates
and a permissive signal is received via the CR binary input (received signal).

The permissive scheme can be of either underreaching or overreaching type. In the


underreaching alternative, an underreaching directional residual overcurrent
measurement element will be used as sending criterion of the permissive input
signal CSUR.

662
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

In the overreaching alternative, an overreaching directional residual overcurrent


measurement element will be used as sending criterion of the permissive input
signal CSOR. Also the underreaching input signal CSUR can initiate sending.

BLOCK
CRL
CR AND
25 ms

t TRIP
0 - 60 s

CACC AND AND t


50 ms
tCoord
t

AND

BLKCS OR CS
AND
Overreach
CSOR AND

CSUR OR

en05000280_2_en.vsd
IEC05000280 V2 EN

13.5.2.3 Unblocking scheme

In unblocking scheme, the lower dependability in permissive scheme is overcome


by using the loss of guard signal from the communication equipment to locally
create a receive signal. It is common or suitable to use the function when older, less
reliable, power line carrier (PLC) communication is used.

The unblocking function uses a guard signal CRG, which must always be present,
even when no CR signal is received. The absence of the CRG signal for a time
longer than the setting tSecurity time is used as a CR signal, see figure 357. This
also enables a permissive scheme to operate when the line fault blocks the signal
transmission.

The received signal created by the unblocking function is reset 150 ms after the
security timer has elapsed. When that occurs an output signal LCG is activated for
signaling purpose. The unblocking function is reset 200 ms after that the guard
signal is present again.

663
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

CR
tSecurity CRL
t >1
1
CRG
200 ms 150 ms
t OR t AND
AND
LCG

en05000746.vsd
IEC05000746 V1 EN

Figure 357: Guard signal logic with unblocking scheme

The unblocking function can be set in three operation modes (setting Unblock):

Off: The unblocking function is out of operation


No restart: Communication failure shorter than tSecurity will be ignored
If CRG disappears, a CRL signal will be transferred to the trip logic
There will not be any information in case of communication failure (LCG)
Restart Communication failure shorter than tSecurity will be ignored
It sends a defined (150 ms) CRL after the disappearance of the CRG signal
The function will activate LCG output in case of communication failure
If the communication failure comes and goes (<200 ms) there will not be recurrent
signaling

13.5.3 Function block


ECPSCH
BLOCK TRIP
BLKTR CS
BLKCS CRL
CSBLK LCG
CACC
CSOR
CSUR
CR
CRG

IEC06000288-2-en.vsd
IEC06000288 V2 EN

Figure 358: ECPSCH function block

664
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

13.5.4 Input and output signals


Table 408: ECPSCH Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Signal for blocking trip due to communication logic
BLKCS BOOLEAN 0 Signal for blocking CS in Overreach and Blocking
schemes
CSBLK BOOLEAN 0 Reverse residual overcurrent signal for Carrier
Send
CACC BOOLEAN 0 Signal to be used for tripping by Communication
Scheme
CSOR BOOLEAN 0 Overreaching residual overcurrent signal for
Carrier Send
CSUR BOOLEAN 0 Underreaching residual overcurrent signal for
Carrier Send
CR BOOLEAN 0 Carrier Receive for Communication Scheme Logic
CRG BOOLEAN 0 Carrier guard signal received

Table 409: ECPSCH Output signals


Name Type Description
TRIP BOOLEAN Trip by Communication Scheme Logic
CS BOOLEAN Carrier Send by Communication Scheme Logic
CRL BOOLEAN Carrier Receive from Communication Scheme
Logic
LCG BOOLEAN loss of carrier guard signal

13.5.5 Setting parameters


Table 410: ECPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
SchemeType Off - - Permissive UR Scheme type, Mode of Operation
Intertrip
Permissive UR
Permissive OR
Blocking
tCoord 0.000 - 60.000 s 0.001 0.035 Communication scheme coordination
time
tSendMin 0.000 - 60.000 s 0.001 0.100 Minimum duration of a carrier send signal

665
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

Table 411: ECPSCH Group settings (advanced)


Name Values (Range) Unit Step Default Description
Unblock Off - - Off Operation mode of unblocking logic
NoRestart
Restart
tSecurity 0.000 - 60.000 s 0.001 0.035 Security timer for loss of carrier guard
detection

13.5.6 Technical data


Table 412: ECPSCH technical data
Function Range or value Accuracy
Scheme type Permissive Underreaching -
Permissive Overreaching
Blocking
Communication scheme (0.000-60.000) s ± 0.5% ± 10 ms
coordination time

13.6 Current reversal and weak-end infeed logic for


residual overcurrent protection ECRWPSCH

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Current reversal and weak-end infeed ECRWPSCH - 85
logic for residual overcurrent protection

13.6.1 Introduction
The Current reversal and weak-end infeed logic for residual overcurrent protection
ECRWPSCH is a supplement to Scheme communication logic for residual
overcurrent protection ECPSCH.

To achieve fast fault clearing for all earth faults on the line, the directional earth-
fault protection function can be supported with logic that uses communication
channels.

The 670 series IEDs have for this reason available additions to scheme
communication logic.

If parallel lines are connected to common busbars at both terminals, overreaching


permissive communication schemes can trip unselectively due to fault current
reversal. This unwanted tripping affects the healthy line when a fault is cleared on
the other line. This lack of security can result in a total loss of interconnection
between the two buses. To avoid this type of disturbance, a fault current reversal
logic (transient blocking logic) can be used.

666
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

Permissive communication schemes for residual overcurrent protection can


basically operate only when the protection in the remote IED can detect the fault.
The detection requires a sufficient minimum residual fault current, out from this
IED. The fault current can be too low due to an opened breaker or high-positive and/
or zero-sequence source impedance behind this IED. To overcome these
conditions, weak-end infeed (WEI) echo logic is used.

13.6.2 Principle of operation

13.6.2.1 Directional comparison logic function

The directional comparison function contains logic for blocking overreaching and
permissive overreaching schemes.

The circuits for the permissive overreaching scheme contain logic for current
reversal and weak-end infeed functions. These functions are not required for the
blocking overreaching scheme.

Use the independent or inverse time functions in the directional earth-fault


protection module to get back-up tripping in case the communication equipment
malfunctions and prevents operation of the directional comparison logic.

Figure 359 and figure 360 show the logic circuits.

Connect the necessary signal from the autorecloser for blocking of the directional
comparison scheme, during a single-phase autoreclosing cycle, to the BLOCK
input of the directional comparison module.

13.6.2.2 Fault current reversal logic

The fault current reversal logic uses a reverse directed element, connected to input
signal IRV, which recognizes that the fault is in reverse direction. When the
reverse direction element is activated during the tPickUpRev time, the output signal
IRVL is activated, see figure 359. The logic is now ready to handle a current
reversal without tripping. Output signal IRVL will be connected to the block input
on the permissive overreaching scheme.

When the fault current is reversed on the non faulty line, IRV is deactivated and
IRVBLK is activated. The reset of IRVL is delayed by the tDelayRev time, see
figure 359. This ensures the reset of the received CR signal.

667
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

BLOCK
0-60 s 10 ms 0-60 s 0-60 s
IRV AND IRVL
t t t t

IRVBLK tPickUpRev tPickUpRev tDelayRev

IEC09000031-1-en.vsd
IEC09000031 V1 EN

Figure 359: Simplified logic diagram, current reversal

13.6.2.3 Weak-end infeed logic

The weak-end infeed function can be set to send only an echo signal (WEI=Echo)
or an echo signal and a trip signal (WEI=Echo & Trip). See figure 360 and figure
361.

The weak-end infeed logic uses normally a reverse and a forward direction
element, connected to WEIBLK1 via an OR-gate. See figure 360. If neither the
forward nor the reverse directional measuring element is activated during the last
200 ms, the weak-end infeed logic echoes back the received permissive signal. See
figure 360.

If the forward or the reverse directional measuring element is activated during the
last 200 ms, the fault current is sufficient for the IED to detect the fault with the
earth-fault function that is in operation.

BLOCK
200 ms
WEIBLK1 t
50 ms 200 ms
AND
ECHO
& t t
CRL

WEI = Echo

IEC09000032-1-en.vsd
IEC09000032 V1 EN

Figure 360: Simplified logic diagram, weak-end infeed - Echo

With the Echo & Trip setting, the logic sends an echo according to above. Further,
it activates the TRWEI signal to trip the breaker if the echo conditions are fulfilled
and the neutral point voltage is above the set operate value for 3U0>.

The voltage signal that is used to calculate the zero sequence voltage is set in the
earth-fault function that is in operation.

668
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

BLOCK
200 ms
WEIBLK1 50 ms 200 ms
AND
ECHO
t
AND t t
CRL

TRWEI
WEI = Echo&Trip AND

ST3U0
AND

CBOPEN

IEC09000020-1-en.vsd
IEC09000020 V1 EN

Figure 361: Simplified logic diagram, weak-end infeed - Echo & Trip

The weak-end infeed echo sent to the strong line end has a maximum duration of
200 ms. When this time period has elapsed, the conditions that enable the echo
signal to be sent are set to zero for a time period of 50 ms. This avoids ringing
action if the weak-end echo is selected for both line ends.

13.6.3 Function block


ECRWPSCH
U3P* IRVL
BLOCK TRWEI
IRVBLK ECHO
IRV CR
WEIBLK1
WEIBLK2
VTSZ
CBOPEN
CRL

IEC06000289-2-en.vsd
IEC06000289 V2 EN

Figure 362: ECRWPSCH function block

13.6.4 Input and output signals


Table 413: ECRWPSCH Input signals
Name Type Default Description
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
IRVBLK BOOLEAN 0 Block of current reversal function
IRV BOOLEAN 0 Activation of current reversal logic
WEIBLK1 BOOLEAN 0 Block of WEI Logic
WEIBLK2 BOOLEAN 0 Block of WEI logic due to operation of other
protections
VTSZ BOOLEAN 0 Block of trip from WEI logic through fuse-failure
function
CBOPEN BOOLEAN 0 Block of trip from WEI logic by an open breaker
CRL BOOLEAN 0 POR Carrier receive for WEI logic

669
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

Table 414: ECRWPSCH Output signals


Name Type Description
IRVL BOOLEAN Operation of current reversal logic
TRWEI BOOLEAN Trip of WEI logic
ECHO BOOLEAN Carrier send by WEI logic
CR BOOLEAN POR Carrier signal received from remote end

13.6.5 Setting parameters


Table 415: ECRWPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
CurrRev Off - - Off Operating mode of Current Reversal
On Logic
tPickUpRev 0.000 - 60.000 s 0.001 0.020 Pickup time for current reversal logic
tDelayRev 0.000 - 60.000 s 0.001 0.060 Time Delay to prevent Carrier send and
local trip
WEI Off - - Off Operating mode of WEI logic
Echo
Echo & Trip
tPickUpWEI 0.000 - 60.000 s 0.001 0.000 Coordination time for the WEI logic
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level
3U0> 5 - 70 %UB 1 25 Neutral voltage setting for fault
conditions measurement

13.6.6 Technical data


Table 416: ECRWPSCH technical data
Function Range or value Accuracy
Operating mode of WEI logic Off -
Echo
Echo & Trip
Operate voltage 3Uo for WEI trip (5-70)% of UBase ± 1.0% of Ur

Reset ratio >95% -


Operate time for current reversal (0.000-60.000) s ± 0.5% ± 10 ms
logic
Delay time for current reversal (0.000-60.000) s ± 0.5% ± 10 ms
Coordination time for weak-end (0.000–60.000) s ± 0.5% ± 10 ms
infeed logic

670
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

13.7 Current reversal and weak-end infeed logic for


phase segregated communication ZC1WPSCH

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Current reversal and weak-end infeed ZC1WPSCH - 85
logic for phase segregated
communication

13.7.1 Introduction
Current reversal and weak-end infeed logic for phase segregated communication
(ZC1WPSCH) function is used to prevent unwanted operations due to current
reversal when using permissive overreach protection schemes in application with
parallel lines when the overreach from the two ends overlaps on the parallel line.

The weak-end infeed logic is used in cases where the apparent power behind the
protection can be too low to activate the distance protection function. When
activated, received carrier signal together with local under voltage criteria and no
reverse zone operation gives an instantaneous trip. The received signal is also
echoed back to accelerate the sending end.

13.7.2 Principle of operation

13.7.2.1 Current reversal logic

The current reversal logic uses a reverse zone connected to the input IRVLx to
recognize the fault on the parallel line in phase Lx. When the reverse zone has been
activated for a certain settable time tPickUpRev it prevents sending of a
communication signal and activation of trip signal for a predefined time tDelayRev.
This makes it possible for the carrier receive signal to reset before the carrier aided
trip signal is activated due to the current reversal by the forward directed zone, see
figure 363.

tPickUpRev 10 ms tPickUpRev
IRVLn t t t
tDelayRev
IRVOPLn
IRVBLKLn & t

IEC06000474_2_en.vsd
IEC06000474 V2 EN

Figure 363: Current reversal logic

The preventing of sending carrier send signal CSLn and activating of the TRIPLn
in the Scheme communication logic for distance or Overcurrent protection

671
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

(ZCPSCH) is carried out by connecting the IRVOPLn signal to input BLOCKLn in


ZCPSCH function.

The Current reversal and weak-end infeed logic for phase segregated
communication (ZC1WPSCH) function has an internal 10 ms drop-off timer which
secure that the current reversal logic will be activated for short input signals even if
the pick-up timer is set to zero.

Weak-end infeed logic

The WEI function sends back (echoes) the received carrier signal under the
condition that no fault has been detected at the weak end by different fault
detection elements (distance protection in forward and reverse direction).

VTSZ
BLOCK >1

tWEI 50 ms 200 ms ECHOLn - cont.


CRLn
t & t t ECHOLn
&
200 ms
WEIBLKL1
t

200 ms
WEIBLKL2
t

IEC07000085_2_en.vsd
IEC07000085 V2 EN

Figure 364: Weak-end infeed logic

The WEI function returns the received carrier signal, see figure 364, when:

• The input CRLx is active. This input is usually connected to the CRLx output
on the scheme communication logic for distance or Overcurrent protection
(ZCPSCH).
• The WEI function is not blocked by the active signal connected to the
WEIBLKLx input or to the VTSZ input. The later is usually configured to the
STGEN output of the fuse-failure function.
• No active signal has been present for at least 200 ms on the WEIBLK2 input.
An OR combination of all fault detection functions (not undervoltage) as
present within the IED is usually used for this purpose.

When an echo function is used in both IEDs (should generally be avoided), a


spurious signal can be looped round by the echo logics. To avoid a continuous lock-
up of the system, the duration of the echoed signal is limited to 200 ms. An
undervoltage criteria is used as an additional tripping criteria, when the tripping of
the local breaker is selected, setting WEI = Echo &Trip, together with the WEI
function and ECHO signal has been issued by the echo logic, see figure 365.

672
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

WEI = Echo&Trip
ECHOLn - cont.
CBOPEN

STUL1N
100 ms TRWEI
OR OR
STUL2N AND t

STUL3N 15 ms
TRWEIL1
AND t

15 ms
TRWEIL2
AND t

15 ms
TRWEIL3
AND t

en00000551.vsd
IEC00000551-WMF V1 EN

Figure 365: Tripping part of the WEI logic, simplified diagram

13.7.3 Function block


ZC1WPSCH
U3P* TRPWEI
BLOCK TRPWEIL1
BLKZ TRPWEIL2
CBOPEN TRPWEIL3
CRL1 IRVOP
CRL2 IRVOPL1
CRL3 IRVOPL2
IRVL1 IRVOPL3
IRVL2 ECHO
IRVL3 ECHOL1
IRVBLKL1 ECHOL2
IRVBLKL2 ECHOL3
IRVBLKL3
WEIBLK
WEIBLKL1
WEIBLKL2
WEIBLKL3
WEIBLKOP
WEIBLKO1
WEIBLKO2
WEIBLKO3

IEC06000477-2-en.vsd
IEC06000477 V2 EN

Figure 366: ZC1WPSCH function block

673
Technical reference manual
Section 13 1MRK505183-UEN C
Scheme communication

13.7.4 Input and output signals


Table 417: ZC1WPSCH Input signals
Name Type Default Description
U3P GROUP - Voltage
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Block of trip from WEI logic by the fuse-failure
function
CBOPEN BOOLEAN 0 Block of trip from WEI logic by an open breaker
CRL1 BOOLEAN 0 Carrier receive for WEI logic in Phase L1
CRL2 BOOLEAN 0 Carrier receive for WEI logic in Phase L2
CRL3 BOOLEAN 0 Carrier receive for WEI logic in Phase L3
IRVL1 BOOLEAN 0 Activation of current reversal logic in Phase L1
IRVL2 BOOLEAN 0 Activation of current reversal logic in Phase L2
IRVL3 BOOLEAN 0 Activation of current reversal logic in phase L3
IRVBLKL1 BOOLEAN 0 Block of current reversal function in Phase L1
IRVBLKL2 BOOLEAN 0 Block of current reversal function in Phase L2
IRVBLKL3 BOOLEAN 0 Block of current reversal function in Phase L3
WEIBLK BOOLEAN 0 Block of WEI logic
WEIBLKL1 BOOLEAN 0 Block of WEI logic in Phase L1
WEIBLKL2 BOOLEAN 0 Block of WEI logic in Phase L2
WEIBLKL3 BOOLEAN 0 Block of WEI logic in Phase L3
WEIBLKOP BOOLEAN 0 Block of WEI logic due to operation of other
protection
WEIBLKO1 BOOLEAN 0 Block of WEI logic in Phase L1 due to operation
of other protection
WEIBLKO2 BOOLEAN 0 Block of WEI logic in Phase L2 due to operation
of other protections
WEIBLKO3 BOOLEAN 0 Block of WEI logic in Phase L3 due to operation
of other protections

Table 418: ZC1WPSCH Output signals


Name Type Description
TRPWEI BOOLEAN Trip of WEI logic
TRPWEIL1 BOOLEAN Trip of WEI logic in Phase L1
TRPWEIL2 BOOLEAN Trip of WEI logic in Phase L2
TRPWEIL3 BOOLEAN Trip of WEI logic in Phase L3
IRVOP BOOLEAN Operation of current reversal logic
IRVOPL1 BOOLEAN Operation of current reversal logic in Phase L1
IRVOPL2 BOOLEAN Operation of current reversal logic in Phase L2
IRVOPL3 BOOLEAN Operation of current reversal logic in Phase L3
Table continues on next page

674
Technical reference manual
1MRK505183-UEN C Section 13
Scheme communication

Name Type Description


ECHO BOOLEAN Carrier Send by WEI logic
ECHOL1 BOOLEAN Carrier Send by WEI logic in Phase L1
ECHOL2 BOOLEAN Carrier Send by WEI logic in Phase L2
ECHOL3 BOOLEAN Carrier Send by WEI logic in Phase L3

13.7.5 Setting parameters


Table 419: ZC1WPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for Voltage level
OperCurrRev Off - - Off Operating mode of Current Reversal
On Logic
tPickUpRev 0.000 - 60.000 s 0.001 0.020 Pickup time for current reversal logic
tDelayRev 0.000 - 60.000 s 0.001 0.060 Time Delay to prevent Carrier send and
local trip
OperationWEI Off - - Off Operating mode of WEI logic
Echo
Echo & Trip
UPE< 10 - 90 %UB 1 70 Phase to Earth voltage for detection of
fault condition
UPP< 10 - 90 %UB 1 70 Phase to Phase voltage for detection of
fault condition
tPickUpWEI 0.000 - 60.000 s 0.001 0.010 Coordination time for the WEI logic

13.7.6 Technical data


Table 420: ZC1WPSCH technical data
Function Range or value Accuracy
Detection level phase to neutral (10-90)% of UBase ± 1.0% of Ur
voltage
Detection level phase to phase (10-90)% of UBase ± 1.0% of Ur
voltage
Reset ratio <105% -
Operate time for current reversal (0.000-60.000) s ± 0.5% ± 10 ms
Delay time for current reversal (0.000-60.000) s ± 0.5% ± 10 ms
Coordination time for weak-end (0.000-60.000) s ± 0.5% ± 10 ms
infeed logic

675
Technical reference manual
676
1MRK505183-UEN C Section 14
Logic

Section 14 Logic

About this chapter


This chapter describes primarily tripping and trip logic functions. The way the
functions work, their setting parameters, function blocks, input and output signals
and technical data are included for each function.

14.1 Tripping logic SMPPTRC

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Tripping logic SMPPTRC 94

I->O

SYMBOL-K V1 EN

14.1.1 Introduction
A function block for protection tripping is provided for each circuit breaker
involved in the tripping of the fault. It provides the pulse prolongation to ensure a
trip pulse of sufficient length, as well as all functionality necessary for correct co-
operation with autoreclosing functions.

The trip function block includes functionality for evolving faults and breaker lock-
out.

14.1.2 Principle of operation


The duration of a trip output signal from tripping logic SMPPTRC is settable
(tTripMin). The pulse length should be long enough to secure the breaker opening.

For three-phase tripping, SMPPTRC has a single input (TRIN) through which all
trip output signals from the protection functions within the IED, or from external
protection functions via one or more of the IEDs binary inputs, are routed. It has a
single trip output (TRIP) for connection to one or more of the IEDs binary outputs,
as well as to other functions within the IED requiring this signal.

677
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

BLOCK
tTripMin TRIP
TRIN OR
AND t

Operation Mode = On

Program = 3Ph

en05000789.vsd
IEC05000789 V1 EN

Figure 367: Simplified logic diagram for three phase trip

SMPPTRC function for single-phase and two-phase tripping has additional phase
segregated inputs for this, as well as inputs for faulted phase selection. The latter
inputs enable single- phase and two-phase tripping for those functions which do not
have their own phase selection capability, and therefore which have just a single
trip output and not phase segregated trip outputs for routing through the phase
segregated trip inputs of the expanded SMPPTRC function. Examples of such
protection functions are the residual overcurrent protections. The expanded
SMPPTRC function has two inputs for these functions, one for impedance tripping
(for example, carrier-aided tripping commands from the scheme communication
logic), and one for earth fault tripping (for example, tripping output from a residual
overcurrent protection).

The expanded SMPPTRC function has three trip outputs TRL1, TRL2, TRL3
(besides the trip output TRIP), one per phase, for connection to one or more of the
IEDs binary outputs, as well as to other functions within the IED requiring these
signals. There are also separate output signals indicating single-phase, two-phase or
three-phase trip. These signals are important for cooperation with the autorecloser
SMBRREC function.

The expanded SMPPTRC function is equipped with logic which secures correct
operation for evolving faults as well as for reclosing on to persistent faults. A
special input is also provided which disables single- phase and two-phase tripping,
forcing all tripping to be three-phase.

In multi-breaker arrangements, one SMPPTRC function block is used for each


breaker. This can be the case if single pole tripping and autoreclosing is used.

The breaker close lockout function can be activated from an external trip signal
from another protection function via input (SETLKOUT) or internally at a three-
phase trip, if desired.

It is possible to lockout seal in the tripping output signals or use blocking of


closing only the choice is by setting TripLockout.

The TRPx function for single- and two-pole tripping has additional phase
segregated inputs for this, as well as inputs for faulted phase selection. The latter
inputs enable single- and two-pole tripping for those functions which do not have

678
Technical reference manual
1MRK505183-UEN C Section 14
Logic

their own phase selection capability, and therefore which have just a single trip
output and not phase segregated trip outputs for routing through the phase
segregated trip inputs of the expanded TRPx function. Examples of such protection
functions are the residual overcurrent protections. The expanded TRPx function
has two inputs for these functions, one for impedance tripping (e.g. carrier-aided
tripping commands from the scheme communication logic), and one for earth fault
tripping (e.g. tripping output from a residual overcurrent protection). Additional
logic secures a three-pole final trip command for these protection functions in the
absence of the required phase selection signals.

The expanded TRPx function has three trip outputs TRL1, TRL2, TRL3 (besides
the trip output TRIP), one per phase, for connection to one or more of the IEDs
binary outputs, as well as to other functions within the IED requiring these signals.
There are also separate output signals indicating single pole, two pole or three pole
trip. These signals are important for cooperation with the auto-reclosing function.

The expanded TRPx function is equipped with logic which secures correct
operation for evolving faults as well as for reclosing on to persistent faults. A
special input is also provided which disables single- and two-pole tripping, forcing
all tripping to be three-pole.

In multi-breaker arrangements, one TRPx function block is used for each breaker.
This can be the case if single pole tripping and auto-reclosing is used.

The breaker close lockout function can be activated from an external trip signal
from another protection function via input (SETLKOUT) or internally at a three
pole trip, if desired.

It is possible to lockout seal in the tripping output signals or use blocking of


closing only the choice is by setting TripLockout.

14.1.2.1 Logic diagram

TRINL1

TRINL2
OR
TRINL3

1PTRZ OR
1PTREF
OR
TRIN RSTTRIP - cont.
AND
Program = 3ph

en05000517.vsd
IEC05000517 V1 EN

Figure 368: Three-phase front logic — simplified logic diagram

679
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

TRIN

TRINL1

PSL1 L1TRIP
OR
AND

TRINL2

PSL2 L2TRIP
OR
AND

TRINL3

PSL3 L3TRIP
OR
AND

OR

OR OR

-loop
-loop
OR
AND AND
AND
1PTREF AND 50 ms
1PTRZ OR t

en05000518.vsd
IEC05000518-WMF V1 EN

Figure 369: Phase segregated front logic

680
Technical reference manual
1MRK505183-UEN C Section 14
Logic

150 ms
L1TRIP OR
t RTRIP
OR
2000 ms
t
OR
AND

150 ms
L2TRIP OR
t STRIP
OR
2000 ms
t
OR
AND

150 ms
L3TRIP OR
t TTRIP
OR
2000 ms
t
OR
AND
OR

OR AND
P3PTR
OR

-loop

en05000519.vsd
IEC05000519-WMF V1 EN

Figure 370: Additional logic for the 1ph/3ph operating mode

681
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

150 ms
L1TRIP - cont.
t OR RTRIP
OR
2000 ms
t

AND

150 ms
L2TRIP
t OR STRIP
OR
2000 ms
t AND

AND

150 ms
L3TRIP
t OR TTRIP
OR
2000 ms
t

AND
OR

AND
TRIP OR
OR

-loop

en05000520.vsd
IEC05000520-WMF V1 EN

Figure 371: Additional logic for the 1ph/2ph/3ph operating mode

682
Technical reference manual
1MRK505183-UEN C Section 14
Logic

BLOCK

RTRIP TRL1
AND
OR

STRIP TRL2
AND
OR

TTRIP TRL3
AND
OR
RSTTRIP
TRIP
OR

TR3P
AND AND
OR

-loop

AND 10 ms
TR1P
AND t

AND 5 ms
TR2P
AND t
OR
AND

-loop

en05000521.vsd
IEC05000521-WMF V1 EN

Figure 372: Final tripping circuits

14.1.3 Function block


SMPPTRC
BLOCK TRIP
BLKLKOUT TRL1
TRIN TRL2
TRINL1 TRL3
TRINL2 TR1P
TRINL3 TR2P
PSL1 TR3P
PSL2 CLLKOUT
PSL3
1PTRZ
1PTREF
P3PTR
SETLKOUT
RSTLKOUT

IEC05000707-2-en.vsd
IEC05000707 V2 EN

Figure 373: SMPPTRC function block

14.1.4 Input and output signals


Table 421: SMPPTRC Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKLKOUT BOOLEAN 0 Blocks circuit breaker lockout output (CLLKOUT)
TRIN BOOLEAN 0 Trip all phases
Table continues on next page

683
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

Name Type Default Description


TRINL1 BOOLEAN 0 Trip phase 1
TRINL2 BOOLEAN 0 Trip phase 2
TRINL3 BOOLEAN 0 Trip phase 3
PSL1 BOOLEAN 0 Functional input for phase selection in phase L1
PSL2 BOOLEAN 0 Functional input for phase selection in phase L2
PSL3 BOOLEAN 0 Functional input for phase selection in phase L3
1PTRZ BOOLEAN 0 Zone Trip with a separate phase selection
1PTREF BOOLEAN 0 Single phase DEF Trip for separate phase
selection
P3PTR BOOLEAN 0 Prepare all tripping to be three-phase
SETLKOUT BOOLEAN 0 Input for setting the circuit breaker lockout function
RSTLKOUT BOOLEAN 0 Input for resetting the circuit breaker lockout
function

Table 422: SMPPTRC Output signals


Name Type Description
TRIP BOOLEAN General trip output signal
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
TR1P BOOLEAN Tripping single-pole
TR2P BOOLEAN Tripping two-pole
TR3P BOOLEAN Tripping three-pole
CLLKOUT BOOLEAN Circuit breaker lockout output (set until reset)

14.1.5 Setting parameters


Table 423: SMPPTRC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
Program 3 phase - - 1ph/3ph Three ph; single or three ph; single, two
1ph/3ph or three ph trip
1ph/2ph/3ph
tTripMin 0.000 - 60.000 s 0.001 0.150 Minimum duration of trip output signal

Table 424: SMPPTRC Group settings (advanced)


Name Values (Range) Unit Step Default Description
TripLockout Off - - Off On: activate output (CLLKOUT) and trip
On latch, Off: only outp
AutoLock Off - - Off On: lockout from input (SETLKOUT) and
On trip, Off: only inp

684
Technical reference manual
1MRK505183-UEN C Section 14
Logic

14.1.6 Technical data


Table 425: SMPPTRC technical data
Function Range or value Accuracy
Trip action 3-ph, 1/3-ph, 1/2/3-ph -
Minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms
Timers (0.000-60.000) s ± 0.5% ± 10 ms

14.2 Trip matrix logic TMAGGIO

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Trip matrix logic TMAGGIO - -

14.2.1 Introduction
Trip matrix logic (TMAGGIO) function is used to route trip signals and/or other
logical output signals to different output contacts on the IED.

TMAGGIO output signals and the physical outputs are available in PCM600 and
this allows the user to adapt the signals to the physical tripping outputs according
to the specific application needs.

14.2.2 Principle of operation


Trip matrix logic (TMAGGIO) block is provided with 32 input signals and 3
output signals. The function block incorporates internal logic OR gates in order to
provide the necessary grouping of connected input signals (for example, for
tripping and alarming purposes) to the three output signals from the function block.

Internal built-in OR logic is made in accordance with the following three rules:

1. when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical
value 1 (TRUE) the first output signal (OUTPUT1) will get logical value 1
(TRUE).
2. when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical
value 1 (TRUE) the second output signal (OUTPUT2) will get logical value 1
(TRUE).
3. when any one of all 32 input signals (INPUT1 to INPUT32) has logical value
1 (TRUE) the third output signal (OUTPUT3) will get logical value 1 (TRUE).

By use of the settings ModeOutput1, ModeOutput2, ModeOutput3, PulseTime,


OnDelay and OffDelay the behavior of each output can be customized. The
OnDelay is always active and will delay the input to output transition by the set

685
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

time. The ModeOutput for respective output decides wether the output shall be
steady with an drop-off delay as set by OffDelay or if it shall give a pulse with
duration set by PulseTime. Note that for pulsed operation since the inputs are
connected in an OR-function a new pulse will only be given on the output if all
related inputs are reset and then one is activated again. And for steady operation
the of delay will start when all related inputs have reset. Detailed logical diagram is
shown in figure 374

PulseTime

t
&
ModeOutput1
Input 1
Output 1
Ondelay Offdelay
&
³1
³1 t t
Input 16

PulseTime

t
&
ModeOutput2
Input 17
Output 2
Ondelay Offdelay
&
³1
³1 t t
Input 32

PulseTime
t
&

ModeOutput3

Output 3
Ondelay Offdelay
&
³1
³1 t t

IEC09000612_1_en.vsd
IEC09000612 V1 EN

Figure 374: Trip matrix internal logic

Output signals from TMAGGIO are typically connected to other logic blocks or
directly to output contacts in the IED. When used for direct tripping of the circuit
breaker(s) the pulse time delay shall be set to approximately 0.150 seconds in order
to obtain satisfactory minimum duration of the trip pulse to the circuit breaker trip
coils.

686
Technical reference manual
1MRK505183-UEN C Section 14
Logic

14.2.3 Function block


TMAGGIO
INPUT1 OUTPUT1
INPUT2 OUTPUT2
INPUT3 OUTPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
INPUT17
INPUT18
INPUT19
INPUT20
INPUT21
INPUT22
INPUT23
INPUT24
INPUT25
INPUT26
INPUT27
INPUT28
INPUT29
INPUT30
INPUT31
INPUT32

IEC09000830-1-en.vsd

IEC09000830 V1 EN

Figure 375: TMAGGIO function block

14.2.4 Input and output signals


Table 426: TMAGGIO Input signals
Name Type Default Description
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16
INPUT17 BOOLEAN 0 Binary input 17
INPUT18 BOOLEAN 0 Binary input 18
INPUT19 BOOLEAN 0 Binary input 19
INPUT20 BOOLEAN 0 Binary input 20
Table continues on next page

687
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

Name Type Default Description


INPUT21 BOOLEAN 0 Binary input 21
INPUT22 BOOLEAN 0 Binary input 22
INPUT23 BOOLEAN 0 Binary input 23
INPUT24 BOOLEAN 0 Binary input 24
INPUT25 BOOLEAN 0 Binary input 25
INPUT26 BOOLEAN 0 Binary input 26
INPUT27 BOOLEAN 0 Binary input 27
INPUT28 BOOLEAN 0 Binary input 28
INPUT29 BOOLEAN 0 Binary input 29
INPUT30 BOOLEAN 0 Binary input 30
INPUT31 BOOLEAN 0 Binary input 31
INPUT32 BOOLEAN 0 Binary input 32

Table 427: TMAGGIO Output signals


Name Type Description
OUTPUT1 BOOLEAN OR function betweeen inputs 1 to 16
OUTPUT2 BOOLEAN OR function between inputs 17 to 32
OUTPUT3 BOOLEAN OR function between inputs 1 to 32

14.2.5 Setting parameters


Table 428: TMAGGIO Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off / On
On
PulseTime 0.050 - 60.000 s 0.001 0.150 Output pulse time
OnDelay 0.000 - 60.000 s 0.001 0.000 Output on delay time
OffDelay 0.000 - 60.000 s 0.001 0.000 Output off delay time
ModeOutput1 Steady - - Steady Mode for output ,1 steady or pulsed
Pulsed
ModeOutput2 Steady - - Steady Mode for output 2, steady or pulsed
Pulsed
ModeOutput3 Steady - - Steady Mode for output 3, steady or pulsed
Pulsed

688
Technical reference manual
1MRK505183-UEN C Section 14
Logic

14.3 Configurable logic blocks

14.3.1 Introduction
A number of logic blocks and timers are available for user to adapt the
configuration to the specific application needs.

• OR function block.

• INVERTER function blocks that inverts the input signal.

• PULSETIMER function block can be used, for example, for pulse extensions
or limiting of operation of outputs.

• GATE function block is used for controlling if a signal should be able to pass
from the input to the output or not depending on a setting.

• XOR function block.

• LOOPDELAY function block used to delay the output signal one execution
cycle.

• TIMERSET function has pick-up and drop-out delayed outputs related to the
input signal. The timer has a settable time delay.

• AND function block.

• SRMEMORY function block is a flip-flop that can set or reset an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block after a power interruption should return to
the state before the interruption, or be reset. Set input has priority.

• RSMEMORY function block is a flip-flop that can reset or set an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block after a power interruption should return to
the state before the interruption, or be reset. Reset input has priority.

14.3.2 Inverter function block INV


INV
INPUT OUT

IEC04000404_2_en.vsd
IEC04000404 V2 EN

Figure 376: INV function block

689
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

Table 429: INV Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input

Table 430: INV Output signals


Name Type Description
OUT BOOLEAN Output

14.3.3 OR function block OR


The OR function is used to form general combinatory expressions with boolean
variables. The OR function block has six inputs and two outputs. One of the
outputs is inverted.
OR
INPUT1 OUT
INPUT2 NOUT
INPUT3
INPUT4
INPUT5
INPUT6

IEC04000405_2_en.vsd
IEC04000405 V2 EN

Figure 377: OR function block

Table 431: OR Input signals


Name Type Default Description
INPUT1 BOOLEAN 0 Input 1 to OR gate
INPUT2 BOOLEAN 0 Input 2 to OR gate
INPUT3 BOOLEAN 0 Input 3 to OR gate
INPUT4 BOOLEAN 0 Input 4 to OR gate
INPUT5 BOOLEAN 0 Input 5 to OR gate
INPUT6 BOOLEAN 0 Input 6 to OR gate

Table 432: OR Output signals


Name Type Description
OUT BOOLEAN Output from OR gate
NOUT BOOLEAN Inverted output from OR gate

690
Technical reference manual
1MRK505183-UEN C Section 14
Logic

14.3.4 AND function block AND


The AND function is used to form general combinatory expressions with boolean
variables. The AND function block has four inputs and two outputs. One of the
outputs are inverted.
AND
INPUT1 OUT
INPUT2 NOUT
INPUT3
INPUT4N

IEC04000406_2_en.vsd
IEC04000406 V2 EN

Figure 378: AND function block

Table 433: AND Input signals


Name Type Default Description
INPUT1 BOOLEAN 0 Input 1
INPUT2 BOOLEAN 0 Input 2
INPUT3 BOOLEAN 0 Input 3
INPUT4N BOOLEAN 1 Input 4 inverted

Table 434: AND Output signals


Name Type Description
OUT BOOLEAN Output
NOUT BOOLEAN Output inverted

14.3.5 Timer function block TIMER


The function block TIMER has drop-out and pick-up delayed outputs related to the
input signal. The timer has a settable time delay (T).
TIMER
INPUT ON
T OFF

IEC04000378_2_en.vsd
IEC04000378 V2 EN

Figure 379: TIMER function block

Table 435: TIMER Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input to timer

691
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

Table 436: TIMER Output signals


Name Type Description
ON BOOLEAN Output from timer , pick-up delayed
OFF BOOLEAN Output from timer, drop-out delayed

Table 437: TIMER Non group settings (basic)


Name Values (Range) Unit Step Default Description
T 0.000 - 90000.000 s 0.001 0.000 Time delay of function

14.3.6 Pulse timer function block PULSETIMER


The pulse (PULSETIMER) function can be used, for example, for pulse extensions
or limiting of operation of outputs. The pulse timer TP has a settable length.
PULSETIMER
INPUT OUT
T

IEC04000407-2-en.vsd
IEC04000407 V2 EN

Figure 380: PULSETIMER function block

Table 438: PULSETIMER Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input to pulse timer

Table 439: PULSETIMER Output signals


Name Type Description
OUT BOOLEAN Output from pulse timer

Table 440: PULSETIMER Non group settings (basic)


Name Values (Range) Unit Step Default Description
T 0.000 - 90000.000 s 0.001 0.010 Time delay of function

14.3.7 Exclusive OR function block XOR


The exclusive OR function (XOR) is used to generate combinatory expressions
with boolean variables. XOR has two inputs and two outputs. One of the outputs is
inverted. The output signal is 1 if the input signals are different and 0 if they are equal.

692
Technical reference manual
1MRK505183-UEN C Section 14
Logic

XOR
INPUT1 OUT
INPUT2 NOUT

IEC04000409-2-en.vsd
IEC04000409 V2 EN

Figure 381: XOR function block

Table 441: XOR Input signals


Name Type Default Description
INPUT1 BOOLEAN 0 Input 1 to XOR gate
INPUT2 BOOLEAN 0 Input 2 to XOR gate

Table 442: XOR Output signals


Name Type Description
OUT BOOLEAN Output from XOR gate
NOUT BOOLEAN Inverted output from XOR gate

14.3.8 Loop delay function block LOOPDELAY


The Logic loop delay function block (LOOPDELAY) function is used to delay the
output signal one execution cycle.

LOOPDELAY
INPUT OUT

IEC09000296-1-en.vsd
IEC09000296 V1 EN

Figure 382: LOOPDELAY function block

Table 443: LOOPDELAY Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input signal

Table 444: LOOPDELAY Output signals


Name Type Description
OUT BOOLEAN Output signal, signal is delayed one execution
cycle

14.3.9 Set-reset with memory function block SRMEMORY


The Set-reset with memory function block (SRMEMORY) is a flip-flop with
memory that can set or reset an output from two inputs respectively. Each
SRMEMORY function block has two outputs, where one is inverted. The memory

693
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

setting controls if the flip-flop after a power interruption will return the state it had
before or if it will be reset.

Table 445: Truth table for SRMEMORY function block


SET RESET OUT NOUT
0 0 Last Inverted
value last value
0 1 0 1
1 0 1 0
1 1 1 0

SRMEMORY
SET OUT
RESET NOUT

IEC04000408_2_en.vsd
IEC04000408 V2 EN

Figure 383: SRMEMORY function block

Table 446: SRM Input signals


Name Type Default Description
SET BOOLEAN 0 Set input
RESET BOOLEAN 0 Reset input

Table 447: SRM Output signals


Name Type Description
OUT BOOLEAN Output
NOUT BOOLEAN Output inverted

Table 448: SRM Group settings (basic)


Name Values (Range) Unit Step Default Description
Memory Off - - On Operating mode of the memory function
On

14.3.10 Controllable gate function block GATE


The Controllable gate function block (GATE) is used for controlling if a signal
should be able to pass from the input to the output or not depending on a setting.
GATE
INPUT OUT

IEC04000410-2-en.vsd
IEC04000410 V2 EN

Figure 384: GATE function block

694
Technical reference manual
1MRK505183-UEN C Section 14
Logic

Table 449: GATE Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input to gate

Table 450: GATE Output signals


Name Type Description
OUT BOOLEAN Output from gate

Table 451: GATE Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

14.3.11 Settable timer function block TIMERSET


The Settable timer function block (TIMERSET) timer has outputs for delayed input
signal at drop-out and at pick-up. The timer has a settable time delay. It also has an
Operation setting On/, Off/ that controls the operation of the timer.
TIMERSET
INPUT ON
OFF

IEC04000411-2-en.vsd
IEC04000411 V2 EN

Figure 385: TIMERSET function block

Table 452: TIMERSET Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input to timer

Table 453: TIMERSET Output signals


Name Type Description
ON BOOLEAN Output from timer, pick-up delayed
OFF BOOLEAN Output from timer, drop-out delayed

Table 454: TIMERSET Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
t 0.000 - 90000.000 s 0.001 0.000 Delay for settable timer n

695
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

14.3.12 Technical data


Table 455: Configurable logic blocks
Logic block Quantity with cycle time Range or Accuracy
fast medium normal value
LogicAND 60 60 160 - -
LogicOR 60 60 160 - -
LogicXOR 10 10 20 - -
LogicInverter 30 30 80 - -
LogicSRMemory 10 10 20 - -
LogicGate 10 10 20 - -
LogicTimer 10 10 20 (0.000– ± 0.5% ± 10 ms
90000.000) s
LogicPulseTimer 10 10 20 (0.000– ± 0.5% ± 10 ms
90000.000) s
LogicTimerSet 10 10 20 (0.000– ± 0.5% ± 10 ms
90000.000) s
LogicLoopDelay 10 10 20 (0.000– ± 0.5% ± 10 ms
90000.000) s

14.4 Fixed signal function block FXDSIGN

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Fixed signals FXDSIGN - -

The Fixed signals function (FXDSIGN) generates a number of pre-set (fixed)


signals that can be used in the configuration of an IED, either for forcing the
unused inputs in other function blocks to a certain level/value, or for creating
certain logic.

14.4.1 Principle of operation


There are eight outputs from FXDSIGN function block:
• OFF is a boolean signal, fixed to OFF (boolean 0) value
• ON is a boolean signal, fixed to ON (boolean 1) value
• INTZERO is an integer number, fixed to integer value 0
• INTONE is an integer number, fixed to integer value 1
• REALZERO is a floating point real number, fixed to 0.0 value
• STRNULL is a string, fixed to an empty string (null) value
• ZEROSMPL is a channel index, fixed to 0 value
• GRP_OFF is a group signal, fixed to 0 value

696
Technical reference manual
1MRK505183-UEN C Section 14
Logic

14.4.2 Function block


FXDSIGN
OFF
ON
INTZERO
INTONE
REALZERO
STRNULL
ZEROSMPL
GRP_OFF

IEC05000445-2-en.vsd
IEC05000445 V2 EN

Figure 386: FXDSIGN function block

14.4.3 Input and output signals


Table 456: FXDSIGN Output signals
Name Type Description
OFF BOOLEAN Boolean signal fixed off
ON BOOLEAN Boolean signal fixed on
INTZERO INTEGER Integer signal fixed zero
INTONE INTEGER Integer signal fixed one
REALZERO REAL Real signal fixed zero
STRNULL STRING String signal with no characters
ZEROSMPL GROUP SIGNAL Channel id for zero sample
GRP_OFF GROUP SIGNAL Group signal fixed off

14.4.4 Setting parameters


The function does not have any parameters available in the local HMI or PCM600.

14.5 Boolean 16 to Integer conversion B16I

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Boolean 16 to integer conversion B16I - -

14.5.1 Introduction
Boolean 16 to integer conversion function (B16I) is used to transform a set of 16
binary (logical) signals into an integer.

697
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

14.5.2 Principle of operation


Boolean 16 to integer conversion function (B16I) is used to transform a set of 16
binary (logical) signals into an integer. The BLOCK input will freeze the output at
the last value.

14.5.3 Function block


B16I
BLOCK OUT
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16

IEC07000128-2-en.vsd
IEC07000128 V2 EN

Figure 387: B16I function block

14.5.4 Input and output signals


Table 457: B16I Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1
IN2 BOOLEAN 0 Input 2
IN3 BOOLEAN 0 Input 3
IN4 BOOLEAN 0 Input 4
IN5 BOOLEAN 0 Input 5
IN6 BOOLEAN 0 Input 6
IN7 BOOLEAN 0 Input 7
IN8 BOOLEAN 0 Input 8
IN9 BOOLEAN 0 Input 9
IN10 BOOLEAN 0 Input 10
IN11 BOOLEAN 0 Input 11
IN12 BOOLEAN 0 Input 12
IN13 BOOLEAN 0 Input 13
IN14 BOOLEAN 0 Input 14
IN15 BOOLEAN 0 Input 15
IN16 BOOLEAN 0 Input 16

698
Technical reference manual
1MRK505183-UEN C Section 14
Logic

Table 458: B16I Output signals


Name Type Description
OUT INTEGER Output value

14.5.5 Setting parameters


The function does not have any parameters available in the local HMI or PCM600.

14.6 Boolean 16 to Integer conversion with logic node


representation B16IGGIO

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Boolean 16 to integer conversion with B16IGGIO - -
logic node representation

14.6.1 Introduction
Boolean 16 to integer conversion with logic node representation function
(B16IGGIO) is used to transform a set of 16 binary (logical) signals into an integer.

B16IGGIO can receive remote values via IEC 61850 depending on the operator
position input (PSTO).

14.6.2 Principle of operation


Boolean 16 to integer conversion with logic node representation function
(B16IGGIO) is used to transform a set of 16 binary (logical) signals into an integer.
The BLOCK input will freeze the output at the last value.

699
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

14.6.3 Function block


B16IGGIO
BLOCK OUT
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16

IEC07000129-2-en.vsd
IEC07000129 V2 EN

Figure 388: B16IGGIO function block

14.6.4 Input and output signals


Table 459: B16IGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1
IN2 BOOLEAN 0 Input 2
IN3 BOOLEAN 0 Input 3
IN4 BOOLEAN 0 Input 4
IN5 BOOLEAN 0 Input 5
IN6 BOOLEAN 0 Input 6
IN7 BOOLEAN 0 Input 7
IN8 BOOLEAN 0 Input 8
IN9 BOOLEAN 0 Input 9
IN10 BOOLEAN 0 Input 10
IN11 BOOLEAN 0 Input 11
IN12 BOOLEAN 0 Input 12
IN13 BOOLEAN 0 Input 13
IN14 BOOLEAN 0 Input 14
IN15 BOOLEAN 0 Input 15
IN16 BOOLEAN 0 Input 16

Table 460: B16IGGIO Output signals


Name Type Description
OUT INTEGER Output value

700
Technical reference manual
1MRK505183-UEN C Section 14
Logic

14.6.5 Setting parameters


The function does not have any parameters available in the local HMI or PCM600.

14.7 Integer to Boolean 16 conversion IB16

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Integer to boolean 16 conversion IB16 - -

14.7.1 Introduction
Integer to boolean 16 conversion function (IB16) is used to transform an integer
into a set of 16 binary (logical) signals.

14.7.2 Principle of operation


Integer to boolean 16 conversion function (IB16) is used to transform an integer
into a set of 16 binary (logical) signals. IB16 function is designed for receiving the
integer input locally. The BLOCK input will freeze the logical outputs at the last
value.

14.7.3 Function block


IB16
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16

IEC06000501-2-en.vsd
IEC06000501 V2 EN

Figure 389: IB16 function block

701
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

14.7.4 Input and output signals


Table 461: IB16 Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INP INTEGER 0 Integer Input

Table 462: IB16 Output signals


Name Type Description
OUT1 BOOLEAN Output 1
OUT2 BOOLEAN Output 2
OUT3 BOOLEAN Output 3
OUT4 BOOLEAN Output 4
OUT5 BOOLEAN Output 5
OUT6 BOOLEAN Output 6
OUT7 BOOLEAN Output 7
OUT8 BOOLEAN Output 8
OUT9 BOOLEAN Output 9
OUT10 BOOLEAN Output 10
OUT11 BOOLEAN Output 11
OUT12 BOOLEAN Output 12
OUT13 BOOLEAN Output 13
OUT14 BOOLEAN Output 14
OUT15 BOOLEAN Output 15
OUT16 BOOLEAN Output 16

14.7.5 Setting parameters


The function does not have any parameters available in the local HMI or PCM600.

14.8 Integer to Boolean 16 conversion with logic node


representation IB16GGIO

Function description IEC 61850 ANSI/IEEE C37.2


identification device number
Integer to boolean 16 conversion with IB16GGIO - -
logic node representation

702
Technical reference manual
1MRK505183-UEN C Section 14
Logic

14.8.1 Introduction
Integer to boolean conversion with logic node representation function (IB16GGIO)
is used to transform an integer to 16 binary (logic) signals.

IB16GGIO function can receive remote values over IEC61850 depending on the
operator position input (PSTO).

14.8.2 Principle of operation


Integer to boolean conversion with logic node representation function (IB16GGIO)
is used to transform an integer into a set of 16 binary (logical) signals. IB16GGIO
function can receive an integer from a station computer – for example, over IEC
61850. The BLOCK input will freeze the logical outputs at the last value.

The operator position input (PSTO) determines the operator place. The integer
number can be written to the block while in “Remote”. If PSTO is in ”Off”
or ”Local”, then no change is applied to the outputs.

14.8.3 Function block


IB16GGIO
BLOCK OUT1
PSTO OUT2
IN OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16

IEC06000502-2-en.vsd
IEC06000502 V2 EN

Figure 390: IB16GGIO function block

14.8.4 Input and output signals


Table 463: IB16GGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 1 Operator place selection
IN INTEGER 0 input

703
Technical reference manual
Section 14 1MRK505183-UEN C
Logic

Table 464: IB16GGIO Output signals


Name Type Description
OUT1 BOOLEAN Output 1
OUT2 BOOLEAN Output 2
OUT3 BOOLEAN Output 3
OUT4 BOOLEAN Output 4
OUT5 BOOLEAN Output 5
OUT6 BOOLEAN Output 6
OUT7 BOOLEAN Output 7
OUT8 BOOLEAN Output 8
OUT9 BOOLEAN Output 9
OUT10 BOOLEAN Output 10
OUT11 BOOLEAN Output 11
OUT12 BOOLEAN Output 12
OUT13 BOOLEAN Output 13
OUT14 BOOLEAN Output 14
OUT15 BOOLEAN Output 15
OUT16 BOOLEAN Output 16

14.8.5 Setting parameters


This function does not have any setting parameters.

704
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Section 15 Monitoring

About this chapter


This chapter describes the functions that handle measurements, events and
disturbances. The way the functions work, their setting parameters, function
blocks, input and output signals, and technical data are included for each function.

15.1 Measurements

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Measurements CVMMXU -
P, Q, S, I, U, f

SYMBOL-RR V1 EN

Phase current measurement CMMXU -


I

SYMBOL-SS V1 EN

Phase-phase voltage measurement VMMXU -


U

SYMBOL-UU V1 EN

Current sequence component CMSQI -


measurement
I1, I2, I0

SYMBOL-VV V1 EN

Voltage sequence measurement VMSQI -


U1, U2, U0

SYMBOL-TT V1 EN

Phase-neutral voltage measurement VNMMXU -


U

SYMBOL-UU V1 EN

705
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

15.1.1 Introduction
Measurement functions is used for power system measurement, supervision and
reporting to the local HMI, monitoring tool within PCM600 or to station level for
example, via IEC 61850. The possibility to continuously monitor measured values
of active power, reactive power, currents, voltages, frequency, power factor etc. is
vital for efficient production, transmission and distribution of electrical energy. It
provides to the system operator fast and easy overview of the present status of the
power system. Additionally, it can be used during testing and commissioning of
protection and control IEDs in order to verify proper operation and connection of
instrument transformers (CTs and VTs). During normal service by periodic
comparison of the measured value from the IED with other independent meters the
proper operation of the IED analog measurement chain can be verified. Finally, it
can be used to verify proper direction orientation for distance or directional
overcurrent protection function.

The available measured values of an IED are depending on the


actual hardware (TRM) and the logic configuration made in PCM600.

All measured values can be supervised with four settable limits that is, low-low
limit, low limit, high limit and high-high limit. A zero clamping reduction is also
supported, that is, the measured value below a settable limit is forced to zero which
reduces the impact of noise in the inputs.

Dead-band supervision can be used to report measured signal value to station level
when change in measured value is above set threshold limit or time integral of all
changes since the last time value updating exceeds the threshold limit. Measure
value can also be based on periodic reporting.

The measurement function, CVMMXU, provides the following power system


quantities:

• P, Q and S: three phase active, reactive and apparent power


• PF: power factor
• U: phase-to-phase voltage amplitude
• I: phase current amplitude
• F: power system frequency

The measuring functions CMMXU, VNMMXU and VMMXU provide physical


quantities:

• I: phase currents (amplitude and angle) (CMMXU)


• U: voltages (phase-to-earth and phase-to-phase voltage, amplitude and angle)
(VMMXU, VNMMXU)

It is possible to calibrate the measuring function above to get better then class 0.5
presentation. This is accomplished by angle and amplitude compensation at 5, 30
and 100% of rated current and at 100% of rated voltage.

706
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

The power system quantities provided, depends on the actual


hardware, (TRM) and the logic configuration made in PCM600.

The measuring functions CMSQI and VMSQI provide sequential quantities:

• I: sequence currents (positive, zero, negative sequence, amplitude and angle)


• U: sequence voltages (positive, zero and negative sequence, amplitude and
angle).

The CVMMXU function calculates three-phase power quantities by using


fundamental frequency phasors (DFT values) of the measured current respectively
voltage signals. The measured power quantities are available either, as
instantaneously calculated quantities or, averaged values over a period of time (low
pass filtered) depending on the selected settings.

15.1.2 Principle of operation

15.1.2.1 Measurement supervision

The protection, control, and monitoring IEDs have functionality to measure and
further process information for currents and voltages obtained from the pre-
processing blocks. The number of processed alternate measuring quantities
depends on the type of IED and built-in options.

The information on measured quantities is available for the user at different locations:

• Locally by means of the local HMI


• Remotely using the monitoring tool within PCM600 or over the station bus
• Internally by connecting the analogue output signals to the Disturbance Report
function

Phase angle reference


All phase angles are presented in relation to a defined reference channel. The
General setting parameter PhaseAngleRef defines the reference, see section
"Analog inputs".

Zero point clamping


Measured value below zero point clamping limit is forced to zero. This allows the
noise in the input signal to be ignored. The zero point clamping limit is a general
setting (XZeroDb where X equals S, P, Q, PF, U, I, F, IL1-3, UL1-3, UL12-31, I1,
I2, 3I0, U1, U2 or 3U0). Observe that this measurement supervision zero point
clamping might be overridden by the zero point clamping used for the
measurement values within CVMMXU.

707
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Continuous monitoring of the measured quantity


Users can continuously monitor the measured quantity available in each function
block by means of four defined operating thresholds, see figure 391. The
monitoring has two different modes of operating:

• Overfunction, when the measured current exceeds the High limit (XHiLim) or
High-high limit (XHiHiLim) pre-set values
• Underfunction, when the measured current decreases under the Low limit
(XLowLim) or Low-low limit (XLowLowLim) pre-set values.

X_RANGE is illustrated in figure 391.

X_RANGE = 3
High-high limit

X_RANGE= 1 Hysteresis
High limit

X_RANGE=0

X_RANGE=0 t

Low limit

X_RANGE=2

Low-low limit
X_RANGE=4

en05000657.vsd
IEC05000657 V1 EN

Figure 391: Presentation of operating limits

Each analogue output has one corresponding supervision level output


(X_RANGE). The output signal is an integer in the interval 0-4 (0: Normal, 1:
High limit exceeded, 3: High-high limit exceeded, 2: below Low limit and 4: below
Low-low limit). The output may be connected to a measurement expander block
(XP (RANGE_XP)) to get measurement supervision as binary signals.

The logical value of the functional output signals changes according to figure 391.

The user can set the hysteresis (XLimHyst), which determines the difference
between the operating and reset value at each operating point, in wide range for
each measuring channel separately. The hysteresis is common for all operating
values within one channel.

Actual value of the measured quantity


The actual value of the measured quantity is available locally and remotely. The
measurement is continuous for each measured quantity separately, but the reporting
of the value to the higher levels depends on the selected reporting mode. The
following basic reporting modes are available:

708
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

• Cyclic reporting (Cyclic)


• Amplitude dead-band supervision (Dead band)
• Integral dead-band supervision (Int deadband)

Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting
(XRepTyp). The measuring channel reports the value independent of amplitude or
integral dead-band reporting.

In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.

Y
Value Reported Value Reported
Value Reported Value Reported
(1st)

Y3 Value Reported
Y2 Y4

Y1 Y5

t (*) t (*) t (*) t (*)

t
Value 1

Value 2

Value 3

Value 4

Value 5

en05000500.vsd
(*)Set value for t: XDbRepInt

IEC05000500 V1 EN

Figure 392: Periodic reporting

Amplitude dead-band supervision


If a measuring value is changed, compared to the last reported value, and the
change is larger than the ±ΔY pre-defined limits that are set by user (XZeroDb),
then the measuring channel reports the new value to a higher level, if this is
detected by a new measured value. This limits the information flow to a minimum
necessary. Figure 393 shows an example with the amplitude dead-band
supervision. The picture is simplified: the process is not continuous but the values
are evaluated with a time interval of one execution cycle from each other.

709
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Value Reported
Y

Value Reported Value Reported


Value Reported
(1st)
Y3 DY
DY
Y2 DY
DY
DY
DY
Y1

99000529.vsd

IEC99000529 V1 EN

Figure 393: Amplitude dead-band supervision reporting

After the new value is reported, the ±ΔY limits for dead-band are automatically set
around it. The new value is reported only if the measured quantity changes more
than defined by the ±ΔY set limits. Even if amplitude dead-band reporting is
selected, there will be a 30 s "back-ground" cyclic reporting as well.

Integral dead-band reporting


The measured value is reported if the time integral of all changes exceeds the pre-
set limit (XZeroDb), figure 394, where an example of reporting with integral dead-
band supervision is shown. The picture is simplified: the process is not continuous
but the values are evaluated with a time interval of one execution cycle from each
other.

The last value reported, Y1 in figure 394 serves as a basic value for further
measurement. A difference is calculated between the last reported and the newly
measured value and is multiplied by the time increment (discrete integral). The
absolute values of these integral values are added until the pre-set value is
exceeded. This occurs with the value Y2 that is reported and set as a new base for
the following measurements (as well as for the values Y3, Y4 and Y5).

The integral dead-band supervision is particularly suitable for monitoring signals


with small variations that can last for relatively long periods. Even if integral dead-
band reporting is selected, there will be a 30 s "back-ground" cyclic reporting as well.

710
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Y A1 >=
A >= pre-set value
A2 >=
pre-set value pre-set value
Y3 A3 + A4 + A5 + A6 + A7 >=
pre-set value
Y2 A1 A2
A4 A6
Value Reported Y4 A3 A5 A7
(1st) Value
Value Reported Y5
A Reported Value
Reported Value
Y1 Reported

t
99000530.vsd

IEC99000530 V1 EN

Figure 394: Reporting with integral dead-band supervision

15.1.2.2 Measurements CVMMXU

Mode of operation
The measurement function must be connected to three-phase current and three-
phase voltage input in the configuration tool (group signals), but it is capable to
measure and calculate above mentioned quantities in nine different ways depending
on the available VT inputs connected to the IED. The end user can freely select by
a parameter setting, which one of the nine available measuring modes shall be used
within the function. Available options are summarized in the following table:
Set value for Formula used for complex, three- Formula used for voltage and Comment
parameter phase power calculation current magnitude calculation
“Mode”
1 L1, L2, L3 Used when
* * *
S = U L1 × I L1 + U L 2 × I L 2 + U L 3 × I L 3 U = ( U L1 + U L 2 + U L 3 ) / 3
three phase-
EQUATION1385 V1 EN
to-earth
I = ( I L1 + I L 2 + I L 3 ) / 3
voltages are
EQUATION1386 V1 EN available
2 Arone Used when
S = U L1 L 2 × I L1 - U L 2 L 3 × I L 3
* *
U = ( U L1 L 2 + U L 2 L 3 ) / 2 three two
phase-to-
(Equation 126)
I = ( I L1 + I L 3 ) / 2 phase
EQUATION1387 V1 EN

voltages are
EQUATION1388 V1 EN (Equation 127) available
3 PosSeq Used when
S = 3 × U PosSeq × I PosSeq
*
U = 3 × U PosSeq only
symmetrical
(Equation 128) three phase
EQUATION1389 V1 EN
I = I PosSeq
power shall
EQUATION1390 V1 EN (Equation 129) be measured

Table continues on next page

711
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Set value for Formula used for complex, three- Formula used for voltage and Comment
parameter phase power calculation current magnitude calculation
“Mode”
4 L1L2 Used when
S = U L1 L 2 × ( I L1 - I L 2 )
* *
U = U L1 L 2 only UL1L2
phase-to-
(Equation 130)
I = ( I L1 + I L 2 ) / 2
EQUATION1391 V1 EN
phase
voltage is
EQUATION1392 V1 EN (Equation 131) available
5 L2L3 Used when
S = U L 2 L3 × ( I L 2 - I L3 )
* *
U = U L2 L3 only UL2L3
phase-to-
(Equation 132)
I = ( I L2 + I L3 ) / 2
EQUATION1393 V1 EN
phase
voltage is
EQUATION1394 V1 EN (Equation 133) available
6 L3L1 Used when
S = U L 3 L1 × ( I L 3 - I L1 )
* *
U = U L 3 L1 only UL3L1
phase-to-
(Equation 134)
I = ( I L 3 + I L1 ) / 2
EQUATION1395 V1 EN
phase
voltage is
EQUATION1396 V1 EN (Equation 135) available
7 L1 Used when
S = 3 × U L1 × I L1
*
U = 3 × U L1 only UL1
phase-to-
(Equation 136) earth voltage
I = I L1
EQUATION1397 V1 EN

is available
EQUATION1398 V1 EN (Equation 137)
8 L2 Used when
S = 3 ×U L2 × I L2
*
U = 3 × U L2 only UL2
phase-to-
(Equation 138) earth voltage
I = IL2
EQUATION1399 V1 EN

is available
EQUATION1400 V1 EN (Equation 139)
9 L3 Used when
S = 3 ×U L3 × I L3
*
U = 3 × U L3 only UL3
phase-to-
(Equation 140)
I = I L3 earth voltage
EQUATION1401 V1 EN

is available
EQUATION1402 V1 EN (Equation 141)
* means complex conjugated value

It shall be noted that only in the first two operating modes that is, 1 & 2 the
measurement function calculates exact three-phase power. In other operating
modes that is, from 3 to 9 it calculates the three-phase power under assumption that
the power system is fully symmetrical. Once the complex apparent power is
calculated then the P, Q, S, & PF are calculated in accordance with the following
formulas:

P = Re( S )
EQUATION1403 V1 EN (Equation 142)

712
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Q = Im( S )
EQUATION1404 V1 EN (Equation 143)

S = S = P +Q
2 2

EQUATION1405 V1 EN (Equation 144)

PF = cosj = P
S
EQUATION1406 V1 EN (Equation 145)

Additionally to the power factor value the two binary output signals from the
function are provided which indicates the angular relationship between current and
voltage phasors. Binary output signal ILAG is set to one when current phasor is
lagging behind voltage phasor. Binary output signal ILEAD is set to one when
current phasor is leading the voltage phasor.

Each analogue output has a corresponding supervision level output (X_RANGE).


The output signal is an integer in the interval 0-4, see section "Measurement
supervision".

Calibration of analog inputs


Measured currents and voltages used in the CVMMXU function can be calibrated
to get class 0.5 measuring accuracy. This is achieved by amplitude and angle
compensation at 5, 30 and 100% of rated current and voltage. The compensation
below 5% and above 100% is constant and linear in between, see example in
figure 395.

713
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

IEC05000652 V2 EN

Figure 395: Calibration curves

The first current and voltage phase in the group signals will be used as reference
and the amplitude and angle compensation will be used for related input signals.

Low pass filtering


In order to minimize the influence of the noise signal on the measurement it is
possible to introduce the recursive, low pass filtering of the measured values for P,
Q, S, U, I and power factor. This will make slower measurement response to the
step changes in the measured quantity. Filtering is performed in accordance with
the following recursive formula:

X = k × X Old + (1 - k ) × X Calculated
EQUATION1407 V1 EN (Equation 146)

where:
X is a new measured value (that is P, Q, S, U, I or PF) to be given out from the function
XOld is the measured value given from the measurement function in previous execution cycle

XCalculated is the new calculated value in the present execution cycle

k is settable parameter by the end user which influence the filter properties

714
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. Appropriate value of k
shall be determined separately for every application. Some typical value for k =0.14.

Zero point clamping


In order to avoid erroneous measurements when either current or voltage signal is
not present, it is possible for the end user to set the amplitudeIGenZeroDb level for
current and voltage measurement UGenZeroDb is forced to zero. When either
current or voltage measurement is forced to zero automatically the measured values
for power (P, Q and S) and power factor are forced to zero as well. Since the
measurement supervision functionality, included in CVMMXU, is using these
values the zero clamping will influence the subsequent supervision (observe the
possibility to do zero point clamping within measurement supervision, see section
"Measurement supervision").

Compensation facility
In order to compensate for small amplitude and angular errors in the complete
measurement chain (CT error, VT error, IED input transformer errors and so on.) it
is possible to perform on site calibration of the power measurement. This is
achieved by setting the complex constant which is then internally used within the
function to multiply the calculated complex apparent power S. This constant is set
as amplitude (setting parameter PowAmpFact, default value 1.000) and angle
(setting parameter PowAngComp, default value 0.0 degrees). Default values for
these two parameters are done in such way that they do not influence internally
calculated value (complex constant has default value 1). In this way calibration, for
specific operating range (for example, around rated power) can be done at site.
However, to perform this calibration it is necessary to have an external power
meter with high accuracy class available.

Directionality
If CT earthing parameter is set as described in section "Analog inputs", active and
reactive power will be measured always towards the protected object. This is
shown in the following figure 396.

715
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Busbar

IED

P Q

Protected
Object
IEC09000038-1-en.vsd
IEC09000038-1-EN V1 EN

Figure 396: Internal IED directionality convention for P & Q measurements

Practically, it means that active and reactive power will have positive values when
they flow from the busbar towards the protected object and they will have negative
values when they flow from the protected object towards the busbar.

In some application, for example, when power is measured on the secondary side
of the power transformer it might be desirable, from the end client point of view, to
have actually opposite directional convention for active and reactive power
measurements. This can be easily achieved by setting parameter PowAngComp to
value of 180.0 degrees. With such setting the active and reactive power will have
positive values when they flow from the protected object towards the busbar.

Frequency
Frequency is actually not calculated within measurement block. It is simply
obtained from the pre-processing block and then just given out from the
measurement block as an output.

15.1.2.3 Phase current measurement CMMXU

The Phase current measurement (CMMXU) function must be connected to three-


phase current input in the configuration tool to be operable. Currents handled in the
function can be calibrated to get better then class 0.5 measuring accuracy for
internal use, on the outputs and IEC 61850. This is achieved by amplitude and

716
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

angle compensation at 5, 30 and 100% of rated current. The compensation below


5% and above 100% is constant and linear in between, see figure 395.

Phase currents (amplitude and angle) are available on the outputs and each
amplitude output has a corresponding supervision level output (ILx_RANG). The
supervision output signal is an integer in the interval 0-4, see section
"Measurement supervision".

15.1.2.4 Phase-phase and phase-neutral voltage measurements VMMXU,


VNMMXU

The voltage function must be connected to three-phase voltage input in the


configuration tool to be operable. Voltages are handled in the same way as currents
when it comes to class 0.5 calibrations, see above.

The voltages (phase or phase-phase voltage, amplitude and angle) are available on
the outputs and each amplitude output has a corresponding supervision level output
(ULxy_RANG). The supervision output signal is an integer in the interval 0-4, see
section "Measurement supervision".

15.1.2.5 Voltage and current sequence measurements VMSQI, CMSQI

The measurement functions must be connected to three-phase current (CMSQI) or


voltage (VMSQI) input in the configuration tool to be operable. No outputs, but
XRANG, are calculated within the measuring block and it is not possible to
calibrate the signals. Input signals are obtained from the pre-processing block and
transferred to corresponding output.

Positive, negative and three times zero sequence quantities are available on the
outputs (voltage and current, amplitude and angle). Each amplitude output has a
corresponding supervision level output (X_RANGE). The output signal is an
integer in the interval 0-4, see section "Measurement supervision".

15.1.3 Function block


The available function blocks of an IED are depending on the actual hardware
(TRM) and the logic configuration made in PCM600.

717
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

CVMMXU
I3P* S
U3P* S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
U
U_RANGE
I
I_RANGE
F
F_RANGE

IEC05000772-2-en.vsd
IEC05000772 V2 EN

Figure 397: CVMMXU function block

CMMXU
I3P* IL1
IL1RANG
IL1ANGL
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL

IEC05000699-2-en.vsd
IEC05000699 V2 EN

Figure 398: CMMXU function block

VNMMXU
U3P* UL1
UL1RANG
UL1ANGL
UL2
UL2RANG
UL2ANGL
UL3
UL3RANG
UL3ANGL

IEC09000850-1-en.vsd
IEC09000850 V1 EN

Figure 399: VNMMXU function block

VMMXU
U3P* UL12
UL12RANG
UL12ANGL
UL23
UL23RANG
UL23ANGL
UL31
UL31RANG
UL31ANGL

IEC05000701-2-en.vsd
IEC05000701 V2 EN

Figure 400: VMMXU function block

718
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

CMSQI
I3P* 3I0
3I0RANG
3I0ANGL
I1
I1RANG
I1ANGL
I2
I2RANG
I2ANGL

IEC05000703-2-en.vsd
IEC05000703 V2 EN

Figure 401: CMSQI function block

VMSQI
U3P* 3U0
3U0RANG
3U0ANGL
U1
U1RANG
U1ANGL
U2
U2RANG
U2ANGL

IEC05000704-2-en.vsd
IEC05000704 V2 EN

Figure 402: VMSQI function block

15.1.4 Input and output signals


Table 465: CVMMXU Input signals
Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL

Table 466: CVMMXU Output signals


Name Type Description
S REAL Apparent Power magnitude of deadband value
S_RANGE INTEGER Apparent Power range
P_INST REAL Active Power
P REAL Active Power magnitude of deadband value
P_RANGE INTEGER Active Power range
Q_INST REAL Reactive Power
Q REAL Active Power magnitude of deadband value
Q_RANGE INTEGER Reactive Power range
PF REAL Power Factor magnitude of deadband value
PF_RANGE INTEGER Power Factor range
ILAG BOOLEAN Current is lagging voltage
Table continues on next page

719
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Name Type Description


ILEAD BOOLEAN Current is leading voltage
U REAL Calculate voltage magnitude of deadband value
U_RANGE INTEGER Calcuate voltage range
I REAL Calculated current magnitude of deadband value
I_RANGE INTEGER Calculated current range
F REAL System frequency magnitude of deadband value
F_RANGE INTEGER System frequency range

Table 467: CMMXU Input signals


Name Type Default Description
I3P GROUP - Group connection abstract block 1
SIGNAL

Table 468: CMMXU Output signals


Name Type Description
IL1 REAL IL1 Amplitude, magnitude of reported value
IL1RANG INTEGER IL1 Amplitude range
IL1ANGL REAL IL1 Angle, magnitude of reported value
IL2 REAL IL2 Amplitude, magnitude of reported value
IL2RANG INTEGER IL2 Amplitude range
IL2ANGL REAL IL2 Angle, magnitude of reported value
IL3 REAL IL3 Amplitude, magnitude of reported value
IL3RANG INTEGER IL3 Amplitude range
IL3ANGL REAL IL3 Angle, magnitude of reported value

Table 469: VNMMXU Input signals


Name Type Default Description
U3P GROUP - Group connection abstract block 5
SIGNAL

Table 470: VNMMXU Output signals


Name Type Description
UL1 REAL UL1 Amplitude, magnitude of reported value
UL1RANG INTEGER UL1 Amplitude range
UL1ANGL REAL UL1 Angle, magnitude of reported value
UL2 REAL UL2 Amplitude, magnitude of reported value
UL2RANG INTEGER UL2 Amplitude range
UL2ANGL REAL UL2 Angle, magnitude of reported value
Table continues on next page

720
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Name Type Description


UL3 REAL UL3 Amplitude, magnitude of reported value
UL3RANG INTEGER UL3 Amplitude range
UL3ANGL REAL UL3 Angle, magnitude of reported value

Table 471: VMMXU Input signals


Name Type Default Description
U3P GROUP - Group connection abstract block 2
SIGNAL

Table 472: VMMXU Output signals


Name Type Description
UL12 REAL UL12 Amplitude, magnitude of reported value
UL12RANG INTEGER UL12 Amplitude range
UL12ANGL REAL UL12 Angle, magnitude of reported value
UL23 REAL UL23 Amplitude, magnitude of reported value
UL23RANG INTEGER UL23 Amplitude range
UL23ANGL REAL UL23 Angle, magnitude of reported value
UL31 REAL UL31 Amplitude, magnitude of reported value
UL31RANG INTEGER UL31 Amplitude range
UL31ANGL REAL UL31 Angle, magnitude of reported value

Table 473: CMSQI Input signals


Name Type Default Description
I3P GROUP - Group connection abstract block 3
SIGNAL

Table 474: CMSQI Output signals


Name Type Description
3I0 REAL 3I0 Amplitude, magnitude of reported value
3I0RANG INTEGER 3I0 Amplitude range
3I0ANGL REAL 3I0 Angle, magnitude of reported value
I1 REAL I1 Amplitude, magnitude of reported value
I1RANG INTEGER I1 Amplitude range
I1ANGL REAL I1 Angle, magnitude of reported value
I2 REAL I2 Amplitude, magnitude of reported value
I2RANG INTEGER I2 Amplitude range
I2ANGL REAL I2 Angle, magnitude of reported value

721
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Table 475: VMSQI Input signals


Name Type Default Description
U3P GROUP - Group connection abstract block 4
SIGNAL

Table 476: VMSQI Output signals


Name Type Description
3U0 REAL 3U0 Amplitude, magnitude of reported value
3U0RANG INTEGER 3U0 Amplitude range
3U0ANGL REAL 3U0 Angle, magnitude of reported value
U1 REAL U1 Amplitude, magnitude of reported value
U1RANG INTEGER U1 Amplitude range
U1ANGL REAL U1 Angle, magnitude of reported value
U2 REAL U2 Amplitude, magnitude of reported value
U2RANG INTEGER U2 Amplitude range
U2ANGL REAL U2 Angle, magnitude of reported value

15.1.5 Setting parameters


The available setting parameters of the measurement function (MMXU, MSQI) are
depending on the actual hardware (TRM) and the logic configuration made in
PCM600.

Table 477: CVMMXU Non group settings (basic)


Name Values (Range) Unit Step Default Description
SLowLim 0.000 - VA 0.001 0.000 Low limit (physical value)
10000000000.000
SLowLowLim 0.000 - VA 0.001 0.000 Low Low limit (physical value)
10000000000.000
SMin 0.000 - VA 0.001 0.000 Minimum value
10000000000.000
SMax 0.000 - VA 0.001 1000000000.000 Maximum value
10000000000.000
SRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
PMin -10000000000.000 W 0.001 -1000000000.000 Minimum value
- 10000000000.000
PMax -10000000000.000 W 0.001 1000000000.000 Maximum value
- 10000000000.000
PRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
QMin -10000000000.000 VAr 0.001 -1000000000.000 Minimum value
- 10000000000.000
Table continues on next page

722
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
IBase 1 - 99999 A 1 3000 Base setting for current level in A
QMax -10000000000.000 VAr 0.001 1000000000.000 Maximum value
- 10000000000.000
QRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level in kV
Mode L1, L2, L3 - - L1, L2, L3 Selection of measured current and
Arone voltage
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
PowAmpFact 0.000 - 6.000 - 0.001 1.000 Amplitude factor to scale power
calculations
PowAngComp -180.0 - 180.0 Deg 0.1 0.0 Angle compensation for phase shift
between measured I & U
k 0.00 - 1.00 - 0.01 0.00 Low pass filter coefficient for power
measurement, U and I
PFMin -1.000 - 0.000 - 0.001 -1.000 Minimum value
PFMax 0.000 - 1.000 - 0.001 1.000 Maximum value
PFRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
UMin -10000000000.000 V 0.001 0.000 Minimum value
- 10000000000.000
UMax -10000000000.000 V 0.001 400000.000 Maximum value
- 10000000000.000
URepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
IMin -10000000000.000 A 0.001 0.000 Minimum value
- 10000000000.000
IMax -10000000000.000 A 0.001 1000.000 Maximum value
- 10000000000.000
IRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
FrMin -10000000000.000 Hz 0.001 0.000 Minimum value
- 10000000000.000
FrMax -10000000000.000 Hz 0.001 70.000 Maximum value
- 10000000000.000
FrRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband

723
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Table 478: CVMMXU Non group settings (advanced)


Name Values (Range) Unit Step Default Description
SDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
SZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
SHiHiLim 0.000 - VA 0.001 900000000.000 High High limit (physical value)
10000000000.000
SHiLim 0.000 - VA 0.001 800000000.000 High limit (physical value)
10000000000.000
SLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
PDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
PZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
PHiHiLim -10000000000.000 W 0.001 900000000.000 High High limit (physical value)
- 10000000000.000
PHiLim -10000000000.000 W 0.001 800000000.000 High limit (physical value)
- 10000000000.000
PLowLim -10000000000.000 W 0.001 -800000000.000 Low limit (physical value)
- 10000000000.000
PLowLowLim -10000000000.000 W 0.001 -900000000.000 Low Low limit (physical value)
- 10000000000.000
PLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
QDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
QZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
QHiHiLim -10000000000.000 VAr 0.001 900000000.000 High High limit (physical value)
- 10000000000.000
QHiLim -10000000000.000 VAr 0.001 800000000.000 High limit (physical value)
- 10000000000.000
QLowLim -10000000000.000 VAr 0.001 -800000000.000 Low limit (physical value)
- 10000000000.000
QLowLowLim -10000000000.000 VAr 0.001 -900000000.000 Low Low limit (physical value)
- 10000000000.000
QLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
PFDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
PFZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UGenZeroDb 1 - 100 % 1 5 Zero point clamping in % of Ubase
PFHiHiLim -3.000 - 3.000 - 0.001 3.000 High High limit (physical value)
IGenZeroDb 1 - 100 % 1 5 Zero point clamping in % of Ibase
PFHiLim -3.000 - 3.000 - 0.001 2.000 High limit (physical value)
PFLowLim -3.000 - 3.000 - 0.001 -2.000 Low limit (physical value)
PFLowLowLim -3.000 - 3.000 - 0.001 -3.000 Low Low limit (physical value)
Table continues on next page

724
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Name Values (Range) Unit Step Default Description


PFLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
UDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UHiHiLim -10000000000.000 V 0.001 460000.000 High High limit (physical value)
- 10000000000.000
UHiLim -10000000000.000 V 0.001 450000.000 High limit (physical value)
- 10000000000.000
ULowLim -10000000000.000 V 0.001 380000.000 Low limit (physical value)
- 10000000000.000
ULowLowLim -10000000000.000 V 0.001 350000.000 Low Low limit (physical value)
- 10000000000.000
ULimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
IDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
IZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
IHiHiLim -10000000000.000 A 0.001 900.000 High High limit (physical value)
- 10000000000.000
IHiLim -10000000000.000 A 0.001 800.000 High limit (physical value)
- 10000000000.000
ILowLim -10000000000.000 A 0.001 -800.000 Low limit (physical value)
- 10000000000.000
ILowLowLim -10000000000.000 A 0.001 -900.000 Low Low limit (physical value)
- 10000000000.000
ILimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
FrDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
FrZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
FrHiHiLim -10000000000.000 Hz 0.001 65.000 High High limit (physical value)
- 10000000000.000
FrHiLim -10000000000.000 Hz 0.001 63.000 High limit (physical value)
- 10000000000.000
FrLowLim -10000000000.000 Hz 0.001 47.000 Low limit (physical value)
- 10000000000.000
FrLowLowLim -10000000000.000 Hz 0.001 45.000 Low Low limit (physical value)
- 10000000000.000
FrLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
Table continues on next page

725
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
30% of Ir
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
100% of Ir
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir

Table 479: CMMXU Non group settings (basic)


Name Values (Range) Unit Step Default Description
IL1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation Off - - Off Operation Mode On / Off
On
IBase 1 - 99999 A 1 3000 Base setting for current level in A
IL1Max 0.000 - A 0.001 1000.000 Maximum value
10000000000.000
IL1RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
IL1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
IL2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
IL2Max 0.000 - A 0.001 1000.000 Maximum value
10000000000.000
IL2RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
IL2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
IL3DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
IL3Max 0.000 - A 0.001 1000.000 Maximum value
10000000000.000
IL3RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
IL3AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s

726
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Table 480: CMMXU Non group settings (advanced)


Name Values (Range) Unit Step Default Description
IL1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
IL1HiHiLim 0.000 - A 0.001 900.000 High High limit (physical value)
10000000000.000
IL1HiLim 0.000 - A 0.001 800.000 High limit (physical value)
10000000000.000
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
30% of Ir
IL1LowLim 0.000 - A 0.001 0.000 Low limit (physical value)
10000000000.000
IL1LowLowLim 0.000 - A 0.001 0.000 Low Low limit (physical value)
10000000000.000
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
100% of Ir
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir
IL1Min 0.000 - A 0.001 0.000 Minimum value
10000000000.000
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir
IL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
IL2ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
IL2HiHiLim 0.000 - A 0.001 900.000 High High limit (physical value)
10000000000.000
IL2HiLim 0.000 - A 0.001 800.000 High limit (physical value)
10000000000.000
IL2LowLim 0.000 - A 0.001 0.000 Low limit (physical value)
10000000000.000
IL2LowLowLim 0.000 - A 0.001 0.000 Low Low limit (physical value)
10000000000.000
IL2Min 0.000 - A 0.001 0.000 Minimum value
10000000000.000
IL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
IL3ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
IL3HiHiLim 0.000 - A 0.001 900.000 High High limit (physical value)
10000000000.000
IL3HiLim 0.000 - A 0.001 800.000 High limit (physical value)
10000000000.000
IL3LowLim 0.000 - A 0.001 0.000 Low limit (physical value)
10000000000.000
Table continues on next page

727
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


IL3LowLowLim 0.000 - A 0.001 0.000 Low Low limit (physical value)
10000000000.000
IL3Min 0.000 - A 0.001 0.000 Minimum value
10000000000.000
IL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits

Table 481: VNMMXU Non group settings (basic)


Name Values (Range) Unit Step Default Description
UL1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation Off - - Off Operation Mode On / Off
On
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level in kV
UL1Max 0.000 - V 0.001 300000.000 Maximum value
10000000000.000
UL1RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
UL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
UL1AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL2Max 0.000 - V 0.001 300000.000 Maximum value
10000000000.000
UL2RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
UL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
UL2AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL3DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL3Max 0.000 - V 0.001 300000.000 Maximum value
10000000000.000
UL3RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
UL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
UL3AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s

728
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Table 482: VNMMXU Non group settings (advanced)


Name Values (Range) Unit Step Default Description
UL1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UL1HiHiLim 0.000 - V 0.001 260000.000 High High limit (physical value)
10000000000.000
UL1HiLim 0.000 - V 0.001 240000.000 High limit (physical value)
10000000000.000
UL1LowLim 0.000 - V 0.001 220000.000 Low limit (physical value)
10000000000.000
UL1LowLowLim 0.000 - V 0.001 200000.000 Low Low limit (physical value)
10000000000.000
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
UL1Min 0.000 - V 0.001 0.000 Minimum value
10000000000.000
UL2ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UL2HiHiLim 0.000 - V 0.001 260000.000 High High limit (physical value)
10000000000.000
UL2HiLim 0.000 - V 0.001 240000.000 High limit (physical value)
10000000000.000
UL2LowLim 0.000 - V 0.001 220000.000 Low limit (physical value)
10000000000.000
UL2LowLowLim 0.000 - V 0.001 200000.000 Low Low limit (physical value)
10000000000.000
UL2Min 0.000 - V 0.001 0.000 Minimum value
10000000000.000
UL3ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UL3HiHiLim 0.000 - V 0.001 260000.000 High High limit (physical value)
10000000000.000
UL3HiLim 0.000 - V 0.001 240000.000 High limit (physical value)
10000000000.000
UL3LowLim 0.000 - V 0.001 220000.000 Low limit (physical value)
10000000000.000
UL3LowLowLim 0.000 - V 0.001 200000.000 Low Low limit (physical value)
10000000000.000
UL3Min 0.000 - V 0.001 0.000 Minimum value
10000000000.000

Table 483: VMMXU Non group settings (basic)


Name Values (Range) Unit Step Default Description
UL12DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation Off - - Off Operation Mode On / Off
On
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level in kV
UL12Max 0.000 - V 0.001 500000.000 Maximum value
10000000000.000
Table continues on next page

729
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


UL12RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
UL12AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL23DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL23Max 0.000 - V 0.001 500000.000 Maximum value
10000000000.000
UL23RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
UL23AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL31DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL31Max 0.000 - V 0.001 500000.000 Maximum value
10000000000.000
UL31RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
UL31AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s

Table 484: VMMXU Non group settings (advanced)


Name Values (Range) Unit Step Default Description
UL12ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UL12HiHiLim 0.000 - V 0.001 450000.000 High High limit (physical value)
10000000000.000
UL12HiLim 0.000 - V 0.001 420000.000 High limit (physical value)
10000000000.000
UL12LowLim 0.000 - V 0.001 380000.000 Low limit (physical value)
10000000000.000
UL12LowLowLim 0.000 - V 0.001 350000.000 Low Low limit (physical value)
10000000000.000
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
UL12Min 0.000 - V 0.001 0.000 Minimum value
10000000000.000
UL12LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
UL23ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UL23HiHiLim 0.000 - V 0.001 450000.000 High High limit (physical value)
10000000000.000
UL23HiLim 0.000 - V 0.001 420000.000 High limit (physical value)
10000000000.000
UL23LowLim 0.000 - V 0.001 380000.000 Low limit (physical value)
10000000000.000
Table continues on next page

730
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Name Values (Range) Unit Step Default Description


UL23LowLowLim 0.000 - V 0.001 350000.000 Low Low limit (physical value)
10000000000.000
UL23Min 0.000 - V 0.001 0.000 Minimum value
10000000000.000
UL23LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
UL31ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UL31HiHiLim 0.000 - V 0.001 450000.000 High High limit (physical value)
10000000000.000
UL31HiLim 0.000 - V 0.001 420000.000 High limit (physical value)
10000000000.000
UL31LowLim 0.000 - V 0.001 380000.000 Low limit (physical value)
10000000000.000
UL31LowLowLim 0.000 - V 0.001 350000.000 Low Low limit (physical value)
10000000000.000
UL31Min 0.000 - V 0.001 0.000 Minimum value
10000000000.000
UL31LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits

Table 485: CMSQI Non group settings (basic)


Name Values (Range) Unit Step Default Description
3I0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
3I0Min 0.000 - A 0.001 0.000 Minimum value
10000000000.000
3I0Max 0.000 - A 0.001 1000.000 Maximum value
10000000000.000
3I0RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
3I0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
3I0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation Off - - Off Operation Mode On / Off
On
3I0AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
3I0AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
3I0AngRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
I1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I1Min 0.000 - A 0.001 0.000 Minimum value
10000000000.000
Table continues on next page

731
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


I1Max 0.000 - A 0.001 1000.000 Maximum value
10000000000.000
I1RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
I1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I1AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
I1AngRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
I2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I2Min 0.000 - A 0.001 0.000 Minimum value
10000000000.000
I2Max 0.000 - A 0.001 1000.000 Maximum value
10000000000.000
I2RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
I2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
I2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I2AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
I2AngRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband

Table 486: CMSQI Non group settings (advanced)


Name Values (Range) Unit Step Default Description
3I0ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
3I0HiHiLim 0.000 - A 0.001 900.000 High High limit (physical value)
10000000000.000
3I0HiLim 0.000 - A 0.001 800.000 High limit (physical value)
10000000000.000
3I0LowLim 0.000 - A 0.001 0.000 Low limit (physical value)
10000000000.000
3I0LowLowLim 0.000 - A 0.001 0.000 Low Low limit (physical value)
10000000000.000
3I0AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
I1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
I1HiHiLim 0.000 - A 0.001 900.000 High High limit (physical value)
10000000000.000
I1HiLim 0.000 - A 0.001 800.000 High limit (physical value)
10000000000.000
Table continues on next page

732
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Name Values (Range) Unit Step Default Description


I1LowLim 0.000 - A 0.001 0.000 Low limit (physical value)
10000000000.000
I1LowLowLim 0.000 - A 0.001 0.000 Low Low limit (physical value)
10000000000.000
I1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
I1AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
I1AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
I2ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
I2HiHiLim 0.000 - A 0.001 900.000 High High limit (physical value)
10000000000.000
I2HiLim 0.000 - A 0.001 800.000 High limit (physical value)
10000000000.000
I2LowLim 0.000 - A 0.001 0.000 Low limit (physical value)
10000000000.000
I2LowLowLim 0.000 - A 0.001 0.000 Low Low limit (physical value)
10000000000.000
I2AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
I2AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value

Table 487: VMSQI Non group settings (basic)


Name Values (Range) Unit Step Default Description
3U0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
3U0Min 0.000 - V 0.001 0.000 Minimum value
10000000000.000
3U0Max 0.000 - V 0.001 300000.000 Maximum value
10000000000.000
3U0RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
3U0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
3U0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation Off - - Off Operation Mode On / Off
On
3U0AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
3U0AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
3U0AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
3U0AngRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
U1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Table continues on next page

733
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


U1Min 0.000 - V 0.001 0.000 Minimum value
10000000000.000
U1Max 0.000 - V 0.001 300000.000 Maximum value
10000000000.000
U1RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
U1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
U1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
U2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
U2Min 0.000 - V 0.001 0.000 Minimum value
10000000000.000
U2Max 0.000 - V 0.001 300000.000 Maximum value
10000000000.000
U2RepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
U2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
U2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
U2AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
U2AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
U2AngRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
UAmpPreComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage
at 5% of Ir
UAmpPreComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage
at 30% of Ir
UAmpPreComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage
at 100% of Ir

Table 488: VMSQI Non group settings (advanced)


Name Values (Range) Unit Step Default Description
3U0ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
3U0HiHiLim 0.000 - V 0.001 260000.000 High High limit (physical value)
10000000000.000
3U0HiLim 0.000 - V 0.001 240000.000 High limit (physical value)
10000000000.000
3U0LowLim 0.000 - V 0.001 220000.000 Low limit (physical value)
10000000000.000
3U0LowLowLim 0.000 - V 0.001 200000.000 Low Low limit (physical value)
10000000000.000
Table continues on next page

734
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Name Values (Range) Unit Step Default Description


U1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
U1HiHiLim 0.000 - V 0.001 260000.000 High High limit (physical value)
10000000000.000
U1HiLim 0.000 - V 0.001 240000.000 High limit (physical value)
10000000000.000
U1LowLim 0.000 - V 0.001 220000.000 Low limit (physical value)
10000000000.000
U1LowLowLim 0.000 - V 0.001 200000.000 Low Low limit (physical value)
10000000000.000
U1AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
U1AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
U1AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
U1AngRepTyp Cyclic - - Cyclic Reporting type
Dead band
Int deadband
U2ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
U2HiHiLim 0.000 - V 0.001 260000.000 High High limit (physical value)
10000000000.000
U2HiLim 0.000 - V 0.001 240000.000 High limit (physical value)
10000000000.000
U2LowLim 0.000 - V 0.001 220000.000 Low limit (physical value)
10000000000.000
U2LowLowLim 0.000 - V 0.001 200000.000 Low Low limit (physical value)
10000000000.000
U2AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

15.1.6 Technical data


Table 489: CVMMXU technical data
Function Range or value Accuracy
Frequency (0.95-1.05) × fr ± 2.0 mHz

Voltage (0.1-1.5) ×Ur ± 0.5% of Ur at U£Ur


± 0.5% of U at U > Ur

Connected current (0.2-4.0) × Ir ± 0.5% of Ir at I £ Ir


± 0.5% of I at I > Ir

Active power, P 0.1 x Ur< U < 1.5 x Ur ± 1.0% of Sr at S ≤ Sr


0.2 x Ir < I < 4.0 x Ir ± 1.0% of S at S > Sr
Conditions:
Reactive power, Q 0.1 x Ur< U < 1.5 x Ur 0.8 x Ur < U < 1.2 Ur
0.2 x Ir < I < 4.0 x Ir 0.2 x Ir < I < 1.2 Ir
Apparent power, S 0.1 x Ur < U < 1.5 x Ur
0.2 x Ir< I < 4.0 x Ir

Power factor, cos (φ) 0.1 x Ur < U < 1.5 x Ur ± 0.02


0.2 x Ir< I < 4.0 x Ir

735
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

15.2 Event counter CNTGGIO

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Event counter CNTGGIO -
S00946 V1 EN

15.2.1 Introduction
Event counter (CNTGGIO) has six counters which are used for storing the number
of times each counter input has been activated.

15.2.2 Principle of operation


Event counter (CNTGGIO) has six counter inputs. CNTGGIO stores how many
times each of the inputs has been activated. The counter memory for each of the six
inputs is updated, giving the total number of times the input has been activated, as
soon as an input is activated. The maximum count up speed is 10 pulses per
second. The maximum counter value is 10 000. For counts above 10 000 the
counter will stop at 10 000 and no restart will take place.

To not risk that the flash memory is worn out due to too many writings, a
mechanism for limiting the number of writings per time period is included in the
product. This however gives as a result that it can take long time, up to several
minutes, before a new value is stored in the flash memory. And if a new
CNTGGIO value is not stored before auxiliary power interruption, it will be lost.
CNTGGIO stored values in flash memory will however not be lost at an auxiliary
power interruption.

The function block also has an input BLOCK. At activation of this input all six
counters are blocked. The input can for example, be used for blocking the counters
at testing.The function block has an input RESET. At activation of this input all six
counters are set to 0.

All inputs are configured via PCM600.

15.2.2.1 Reporting

The content of the counters can be read in the local HMI.

Reset of counters can be performed in the local HMI and a binary input.

Reading of content can also be performed remotely, for example from a IEC 61850
client. The value can also be presented as a measuring value on the local HMI
graphical display.

736
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

15.2.2.2 Design

The function block has six inputs for increasing the counter values for each of the
six counters respectively. The content of the counters are stepped one step for each
positive edge of the input respectively.

The function block also has an input BLOCK. At activation of this input all six
counters are blocked and are not updated. Valid number is held.

The function block has an input RESET. At activation of this input all six counters
are set to 0.

15.2.3 Function block


CNTGGIO
BLOCK VALUE1
COUNTER1 VALUE2
COUNTER2 VALUE3
COUNTER3 VALUE4
COUNTER4 VALUE5
COUNTER5 VALUE6
COUNTER6
RESET

IEC05000345-2-en.vsd
IEC05000345 V2 EN

Figure 403: CNTGGIO function block

15.2.4 Input signals


Table 490: CNTGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
COUNTER1 BOOLEAN 0 Input for counter1
COUNTER2 BOOLEAN 0 Input for counter2
COUNTER3 BOOLEAN 0 Input for counter3
COUNTER4 BOOLEAN 0 Input for counter4
COUNTER5 BOOLEAN 0 Input for counter5
COUNTER6 BOOLEAN 0 Input for counter6
RESET BOOLEAN 0 Reset of function

Table 491: CNTGGIO Output signals


Name Type Description
VALUE1 INTEGER Output of counter1
VALUE2 INTEGER Output of counter2
VALUE3 INTEGER Output of counter3
Table continues on next page

737
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Name Type Description


VALUE4 INTEGER Output of counter4
VALUE5 INTEGER Output of counter5
VALUE6 INTEGER Output of counter6

15.2.5 Setting parameters


Table 492: CNTGGIO Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On

15.2.6 Technical data


Table 493: CNTGGIO technical data
Function Range or value Accuracy
Counter value 0-10000 -
Max. count up speed 10 pulses/s -

15.3 Event function EVENT

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Event function EVENT -
S00946 V1 EN

15.3.1 Introduction
When using a Substation Automation system with LON or SPA communication,
time-tagged events can be sent at change or cyclically from the IED to the station
level. These events are created from any available signal in the IED that is
connected to the Event function (EVENT). The event function block is used for
LON and SPA communication.

Analog and double indication values are also transferred through EVENT function.

15.3.2 Principle of operation


The main purpose of the event function (EVENT) is to generate events when the
state or value of any of the connected input signals is in a state, or is undergoing a
state transition, for which event generation is enabled.

738
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Each EVENT function has 16 inputs INPUT1 - INPUT16. Each input can be given
a name from the Application Configuration tool. The inputs are normally used to
create single events, but are also intended for double indication events.

EVENT function also has an input BLOCK to block the generation of events.

The events that are sent from the IED can originate from both internal logical
signals and binary input channels. The internal signals are time-tagged in the main
processing module, while the binary input channels are time-tagged directly on the
input module. The time-tagging of the events that are originated from internal
logical signals have a resolution corresponding to the execution cyclicity of
EVENT function. The time-tagging of the events that are originated from binary
input signals have a resolution of 1 ms.

The outputs from EVENT function are formed by the reading of status, events and
alarms by the station level on every single input. The user-defined name for each
input is intended to be used by the station level.

All events according to the event mask are stored in a buffer, which contains up to
1000 events. If new events appear before the oldest event in the buffer is read, the
oldest event is overwritten and an overflow alarm appears.

The events are produced according to the set-event masks. The event masks are
treated commonly for both the LON and SPA communication. The EventMask can
be set individually for each input channel. These settings are available:

• NoEvents
• OnSet
• OnReset
• OnChange
• AutoDetect

It is possible to define which part of EVENT function generates the events. This
can be performed individually for the SPAChannelMask and LONChannelMask
respectively. For each communication type these settings are available:

• Off
• Channel 1-8
• Channel 9-16
• Channel 1-16

For LON communication the events normally are sent to station level at change. It
is possibly also to set a time for cyclic sending of the events individually for each
input channel.

To protect the SA system from signals with a high change rate that can easily
saturate the event system or the communication subsystems behind it, a quota
limiter is implemented. If an input creates events at a rate that completely consume
the granted quota then further events from the channel will be blocked. This block
will be removed when the input calms down and the accumulated quota reach 66%

739
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

of the maximum burst quota. The maximum burst quota per input channel is 45
events per second.

15.3.3 Function block


EVENT
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

IEC05000697-2-en.vsd
IEC05000697 V2 EN

Figure 404: EVENT function block

15.3.4 Input and output signals


Table 494: EVENT Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 GROUP 0 Input 1
SIGNAL
INPUT2 GROUP 0 Input 2
SIGNAL
INPUT3 GROUP 0 Input 3
SIGNAL
INPUT4 GROUP 0 Input 4
SIGNAL
INPUT5 GROUP 0 Input 5
SIGNAL
INPUT6 GROUP 0 Input 6
SIGNAL
INPUT7 GROUP 0 Input 7
SIGNAL
INPUT8 GROUP 0 Input 8
SIGNAL
INPUT9 GROUP 0 Input 9
SIGNAL
INPUT10 GROUP 0 Input 10
SIGNAL
INPUT11 GROUP 0 Input 11
SIGNAL
Table continues on next page

740
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Name Type Default Description


INPUT12 GROUP 0 Input 12
SIGNAL
INPUT13 GROUP 0 Input 13
SIGNAL
INPUT14 GROUP 0 Input 14
SIGNAL
INPUT15 GROUP 0 Input 15
SIGNAL
INPUT16 GROUP 0 Input 16
SIGNAL

15.3.5 Setting parameters


Table 495: EVENT Non group settings (basic)
Name Values (Range) Unit Step Default Description
SPAChannelMask Off - - Off SPA channel mask
Channel 1-8
Channel 9-16
Channel 1-16
LONChannelMask Off - - Off LON channel mask
Channel 1-8
Channel 9-16
Channel 1-16
EventMask1 NoEvents - - AutoDetect Reporting criteria for input 1
OnSet
OnReset
OnChange
AutoDetect
EventMask2 NoEvents - - AutoDetect Reporting criteria for input 2
OnSet
OnReset
OnChange
AutoDetect
EventMask3 NoEvents - - AutoDetect Reporting criteria for input 3
OnSet
OnReset
OnChange
AutoDetect
EventMask4 NoEvents - - AutoDetect Reporting criteria for input 4
OnSet
OnReset
OnChange
AutoDetect
EventMask5 NoEvents - - AutoDetect Reporting criteria for input 5
OnSet
OnReset
OnChange
AutoDetect
EventMask6 NoEvents - - AutoDetect Reporting criteria for input 6
OnSet
OnReset
OnChange
AutoDetect
Table continues on next page

741
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


EventMask7 NoEvents - - AutoDetect Reporting criteria for input 7
OnSet
OnReset
OnChange
AutoDetect
EventMask8 NoEvents - - AutoDetect Reporting criteria for input 8
OnSet
OnReset
OnChange
AutoDetect
EventMask9 NoEvents - - AutoDetect Reporting criteria for input 9
OnSet
OnReset
OnChange
AutoDetect
EventMask10 NoEvents - - AutoDetect Reporting criteria for input 10
OnSet
OnReset
OnChange
AutoDetect
EventMask11 NoEvents - - AutoDetect Reporting criteria for input 11
OnSet
OnReset
OnChange
AutoDetect
EventMask12 NoEvents - - AutoDetect Reporting criteria for input 12
OnSet
OnReset
OnChange
AutoDetect
EventMask13 NoEvents - - AutoDetect Reporting criteria for input 13
OnSet
OnReset
OnChange
AutoDetect
EventMask14 NoEvents - - AutoDetect Reporting criteria for input 14
OnSet
OnReset
OnChange
AutoDetect
EventMask15 NoEvents - - AutoDetect Reporting criteria for input 15
OnSet
OnReset
OnChange
AutoDetect
EventMask16 NoEvents - - AutoDetect Reporting criteria for input 16
OnSet
OnReset
OnChange
AutoDetect
MinRepIntVal1 0 - 3600 s 1 2 Minimum reporting interval input 1
MinRepIntVal2 0 - 3600 s 1 2 Minimum reporting interval input 2
MinRepIntVal3 0 - 3600 s 1 2 Minimum reporting interval input 3
MinRepIntVal4 0 - 3600 s 1 2 Minimum reporting interval input 4
MinRepIntVal5 0 - 3600 s 1 2 Minimum reporting interval input 5
Table continues on next page

742
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Name Values (Range) Unit Step Default Description


MinRepIntVal6 0 - 3600 s 1 2 Minimum reporting interval input 6
MinRepIntVal7 0 - 3600 s 1 2 Minimum reporting interval input 7
MinRepIntVal8 0 - 3600 s 1 2 Minimum reporting interval input 8
MinRepIntVal9 0 - 3600 s 1 2 Minimum reporting interval input 9
MinRepIntVal10 0 - 3600 s 1 2 Minimum reporting interval input 10
MinRepIntVal11 0 - 3600 s 1 2 Minimum reporting interval input 11
MinRepIntVal12 0 - 3600 s 1 2 Minimum reporting interval input 12
MinRepIntVal13 0 - 3600 s 1 2 Minimum reporting interval input 13
MinRepIntVal14 0 - 3600 s 1 2 Minimum reporting interval input 14
MinRepIntVal15 0 - 3600 s 1 2 Minimum reporting interval input 15
MinRepIntVal16 0 - 3600 s 1 2 Minimum reporting interval input 16

15.4 Logical signal status report BINSTATREP

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logical signal status report BINSTATREP - -

15.4.1 Introduction
The Logical signal status report (BINSTATREP) function makes it possible for a
SPA master to poll signals from various other functions.

15.4.2 Principle of operation


The Logical signal status report (BINSTATREP) function has 16 inputs and 16
outputs. The output status follows the inputs and can be read from the local HMI or
via SPA communication.

When an input is set, the respective output is set for a user defined time. If the
input signal remains set for a longer period, the output will remain set until the
input signal resets.

743
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

INPUTn

OUTPUTn
t t

IEC09000732-1-en.vsd
IEC09000732 V1 EN

Figure 405: BINSTATREP logical diagram

15.4.3 Function block


BINSTATREP
BLOCK OUTPUT1
^INPUT1 OUTPUT2
^INPUT2 OUTPUT3
^INPUT3 OUTPUT4
^INPUT4 OUTPUT5
^INPUT5 OUTPUT6
^INPUT6 OUTPUT7
^INPUT7 OUTPUT8
^INPUT8 OUTPUT9
^INPUT9 OUTPUT10
^INPUT10 OUTPUT11
^INPUT11 OUTPUT12
^INPUT12 OUTPUT13
^INPUT13 OUTPUT14
^INPUT14 OUTPUT15
^INPUT15 OUTPUT16
^INPUT16

IEC09000730-1-en.vsd
IEC09000730 V1 EN

Figure 406: BINSTATREP function block

15.4.4 Input and output signals


Table 496: BINSTATREP Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Single status report input 1
INPUT2 BOOLEAN 0 Single status report input 2
INPUT3 BOOLEAN 0 Single status report input 3
INPUT4 BOOLEAN 0 Single status report input 4
INPUT5 BOOLEAN 0 Single status report input 5
INPUT6 BOOLEAN 0 Single status report input 6
INPUT7 BOOLEAN 0 Single status report input 7
INPUT8 BOOLEAN 0 Single status report input 8
INPUT9 BOOLEAN 0 Single status report input 9
Table continues on next page

744
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Name Type Default Description


INPUT10 BOOLEAN 0 Single status report input 10
INPUT11 BOOLEAN 0 Single status report input 11
INPUT12 BOOLEAN 0 Single status report input 12
INPUT13 BOOLEAN 0 Single status report input 13
INPUT14 BOOLEAN 0 Single status report input 14
INPUT15 BOOLEAN 0 Single status report input 15
INPUT16 BOOLEAN 0 Single status report input 16

Table 497: BINSTATREP Output signals


Name Type Description
OUTPUT1 BOOLEAN Logical status report output 1
OUTPUT2 BOOLEAN Logical status report output 2
OUTPUT3 BOOLEAN Logical status report output 3
OUTPUT4 BOOLEAN Logical status report output 4
OUTPUT5 BOOLEAN Logical status report output 5
OUTPUT6 BOOLEAN Logical status report output 6
OUTPUT7 BOOLEAN Logical status report output 7
OUTPUT8 BOOLEAN Logical status report output 8
OUTPUT9 BOOLEAN Logical status report output 9
OUTPUT10 BOOLEAN Logical status report output 10
OUTPUT11 BOOLEAN Logical status report output 11
OUTPUT12 BOOLEAN Logical status report output 12
OUTPUT13 BOOLEAN Logical status report output 13
OUTPUT14 BOOLEAN Logical status report output 14
OUTPUT15 BOOLEAN Logical status report output 15
OUTPUT16 BOOLEAN Logical status report output 16

15.4.5 Setting parameters


Table 498: BINSTATREP Non group settings (basic)
Name Values (Range) Unit Step Default Description
t 0.000 - 60000.000 s 0.001 10.000 Time delay of function

15.5 Fault locator LMBRFLO

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Fault locator LMBRFLO - -

745
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

15.5.1 Introduction
The accurate fault locator is an essential component to minimize the outages after a
persistent fault and/or to pin-point a weak spot on the line.

The fault locator is an impedance measuring function giving the distance to the
fault in percent, km or miles. The main advantage is the high accuracy achieved by
compensating for load current and for the mutual zero-sequence effect on double
circuit lines.

The compensation includes setting of the remote and local sources and calculation
of the distribution of fault currents from each side. This distribution of fault
current, together with recorded load (pre-fault) currents, is used to exactly calculate
the fault position. The fault can be recalculated with new source data at the actual
fault to further increase the accuracy.

Especially on heavily loaded long lines (where the fault locator is most important)
where the source voltage angles can be up to 35-40 degrees apart the accuracy can
be still maintained with the advanced compensation included in fault locator.

15.5.2 Principle of operation


The Fault locator (LMBRFLO) in the IED is an essential complement to other
monitoring functions, since it measures and indicates the distance to the fault with
great accuracy.

When calculating distance to fault, pre-fault and fault phasors of currents and
voltages are selected from the Trip value recorder data, thus the analog signals used
by the fault locator must be among those connected to the disturbance report
function. The analog configuration (channel selection) is performed using the
parameter setting tool within PCM600.

The calculation algorithm considers the effect of load currents, double-end infeed
and additional fault resistance.

R0L+jX0L
R1L+jX1L

R1A+jX1A R1B+jX1B
Z0m=Z0m+jX0m

R0L+jX0L
R1L+jX1L
DRPRDRE
LMBRFLO

IEC05000045_2_en.vsd
IEC05000045 V2 EN

Figure 407: Simplified network configuration with network data, required for
settings of the fault location-measuring function

746
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

If source impedance in the near and far end of the protected line have changed in a
significant manner relative to the set values at fault location calculation time (due
to exceptional switching state in the immediate network, power generation out of
order, and so on), new values can be entered via the local HMI and a recalculation
of the distance to the fault can be ordered using the algorithm described below. It’s
also possible to change fault loop. In this way, a more accurate location of the fault
can be achieved.

The function indicates the distance to the fault as a percentage of the line length, in
kilometers or miles as selected on the local HMI. The fault location is stored as a
part of the disturbance report information (ER, DR, IND, TVR and FL) and
managed via the local HMI or PCM600.

15.5.2.1 Measuring Principle

For transmission lines with voltage sources at both line ends, the effect of double-
end infeed and additional fault resistance must be considered when calculating the
distance to the fault from the currents and voltages at one line end. If this is not
done, the accuracy of the calculated figure will vary with the load flow and the
amount of additional fault resistance.

The calculation algorithm used in the fault locator in compensates for the effect of
double-end infeed, additional fault resistance and load current.

15.5.2.2 Accurate algorithm for measurement of distance to fault

Figure 408 shows a single-line diagram of a single transmission line, that is fed
from both ends with source impedances ZA and ZB. Assume that the fault occurs at
a distance F from IED A on a line with the length L and impedance ZL. The fault
resistance is defined as RF. A single-line model is used for better clarification of
the algorithm.

747
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

A B
ZA IA pZL IB (1-p).ZL ZB

IF

UA RF

xx01000171.vsd
IEC01000171 V1 EN

Figure 408: Fault on transmission line fed from both ends

From figure 408 it is evident that:

U A = I A × p × Z L + IF × R F
EQUATION95 V1 EN (Equation 147)

Where:
IA is the line current after the fault, that is, pre-fault current plus current change due to the fault,

IF is the fault current and

p is a relative distance to the fault

The fault current is expressed in measurable quantities by:

IF A
IF = --------
DA
EQUATION96 V1 EN (Equation 148)

Where:
IFA is the change in current at the point of measurement, IED A and

DA is a fault current-distribution factor, that is, the ratio between the fault current at line end A
and the total fault current.

For a single line, the value is equal to:

( 1 – p ) × Z L + ZB
DA = -----------------------------------------
Z A + Z L + ZB
EQUATION97 V1 EN (Equation 149)

748
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Thus, the general fault location equation for a single line is:

I FA
U A = I A × p × Z L + -------
- × RF
DA
EQUATION98 V1 EN (Equation 150)

Table 499: Expressions for UA, IA and IFA for different types of faults

Fault type: UA IA IFA


L1-N UL1A IL1A + KN x INA 3
--- ´ D ( I L1A – I 0A )
2
EQUATION110 V1 EN

L2-N UL2A IL2A + KN x INA


3
--- ´ D ( I L2A – I 0A )
2
EQUATION111 V1 EN

L3-N UL3A IL3A + KN x INA 3


--- ´ D ( I L3A – I0A )
2
EQUATION112 V1 EN

L1-L2-L3, L1-L2,L1-L2- UL1A-UL2A IL1A - IL2A DIL 1 L 2 A


N
EQUATION113 V1 EN

L2-L3, L2-L3-N UL2A-UL3A IL2A - IL3A DIL2L3A


EQUATION114 V1 EN

L3-L1, L3-L1-N UL3A-UL1A IL3A - IL1A


DIL3L1A
EQUATION115 V1 EN

The KN complex quantity for zero-sequence compensation for the single line is
equal to:

Z0L – Z 1L
K N = ------------------------
3 × Z1L
EQUATION99 V1 EN (Equation 151)

DI is the change in current, that is the current after the fault minus the current
before the fault.

In the following, the positive sequence impedance for ZA, ZB and ZL is inserted
into the equations, because this is the value used in the algorithm.

For double lines, the fault equation is:

749
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

I FA
U A = I A × p × Z 1L + -------- × RF + I 0P × Z 0M
DA
EQUATION100 V1 EN (Equation 152)

Where:
I0P is a zero sequence current of the parallel line,

Z0M is a mutual zero sequence impedance and

DA is the distribution factor of the parallel line, which is:

( 1 – p ) × ( ZA + ZA L + ZB ) + Z B
DA = ----------------------------------------------------------------------------
-
2 × ZA + Z L + 2 × Z B
EQUATION101 V1 EN

The KN compensation factor for the double line becomes:

Z0L – Z 1L Z 0M I 0P
K N = ----------------------- - × -------
- + ----------------
3 × Z1L 3 × Z1L I 0A
EQUATION102 V1 EN (Equation 153)

From these equations it can be seen, that, if Z0m = 0, then the general fault location
equation for a single line is obtained. Only the distribution factor differs in these
two cases.

Because the DA distribution factor according to equation 150 or 152 is a function


of p, the general equation 152 can be written in the form:
2
p – p × K1 + K2 – K3 × RF = 0
EQUATION103 V1 EN (Equation 154)

Where:

UA ZB
K 1 = ---------------
- + --------------------------
-+1
I A × ZL Z L + ZA DD

EQUATION104 V1 EN (Equation 155)

UA ZB
K2 = --------------- × æè --------------------------- + 1öø
IA × Z L Z L + Z A DD

EQUATION105 V1 EN (Equation 156)

IF A æ ZA + ZB
- × --------------------------- + 1ö
K 3 = ---------------
I A × Z L è Z 1 + ZA DD ø
EQUATION106 V1 EN (Equation 157)

and:

750
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

• ZADD = ZA + ZB for parallel lines.


• IA, IFA and UA are given in the above table.
• KN is calculated automatically according to equation 153.
• ZA, ZB, ZL, Z0L and Z0M are setting parameters.

For a single line, Z0M = 0 and ZADD = 0. Thus, equation 154 applies to both single
and parallel lines.

Equation 154 can be divided into real and imaginary parts:


2
p – p × Re ( K 1 ) + Re ( K 2 ) – R F × Re ( K 3 ) = 0
EQUATION107 V1 EN (Equation 158)

– p × Im × ( K1 ) + Im × ( K 2 ) – R F × Im × ( K3 ) = 0
EQUATION108 V1 EN (Equation 159)

If the imaginary part of K3 is not zero, RF can be solved according to equation 159,
and then inserted to equation 158. According to equation 158, the relative distance
to the fault is solved as the root of a quadratic equation.

Equation 158 gives two different values for the relative distance to the fault as a
solution. A simplified load compensated algorithm, which gives an unequivocal
figure for the relative distance to the fault, is used to establish the value that should
be selected.

If the load compensated algorithms according to the above do not give a reliable
solution, a less accurate, non-compensated impedance model is used to calculate
the relative distance to the fault.

15.5.2.3 The non-compensated impedance model

In the non-compensated impedance model, IA line current is used instead of IFA


fault current:

U A = p × Z 1 L × IA + R F × IA
EQUATION109 V1 EN (Equation 160)

Where:
IA is according to table 499.

The accuracy of the distance-to-fault calculation, using the non-compensated


impedance model, is influenced by the pre-fault load current. So, this method is
only used if the load compensated models do not function.

751
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

15.5.2.4 IEC 60870-5-103

The communication protocol IEC 60870-5-103 may be used to poll fault location
information from the IED to a master (that is station HSI). There are two outputs
that must be connected to appropriate inputs on the function block I103StatFltDis,
FLTDISTX gives distance to fault (reactance, according the standard) and
CALCMADE gives a pulse (100 ms) when a result is obtainable on FLTDISTX
output.

15.5.3 Function block


LMBRFLO
PHSELL1* FLTDISTX
PHSELL2* CALCMADE
PHSELL3* BCD_80
CALCDIST* BCD_40
BCD_20
BCD_10
BCD_8
BCD_4
BCD_2
BCD_1

IEC05000679-2-en.vsd
IEC05000679 V3 EN

Figure 409: FLO function block

15.5.4 Input and output signals


Table 500: LMBRFLO Input signals
Name Type Default Description
PHSELL1 BOOLEAN 0 Phase selecton L1
PHSELL2 BOOLEAN 0 Phase selecton L2
PHSELL3 BOOLEAN 0 Phase selecton L3
CALCDIST BOOLEAN 0 Do calculate fault distance (release)

Table 501: LMBRFLO Output signals


Name Type Description
FLTDISTX REAL Reactive distance to fault
CALCMADE BOOLEAN Fault calculation made
BCD_80 BOOLEAN Distance in binary coded data, bit represents 80%
BCD_40 BOOLEAN Distance in binary coded data, bit represents 40%
BCD_20 BOOLEAN Distance in binary coded data, bit represents 20%
BCD_10 BOOLEAN Distance in binary coded data, bit represents 10%
BCD_8 BOOLEAN Distance in binary coded data, bit represents 8%
BCD_4 BOOLEAN Distance in binary coded data, bit represents 4%
BCD_2 BOOLEAN Distance in binary coded data, bit represents 2%
BCD_1 BOOLEAN Distance in binary coded data, bit represents 1%

752
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

15.5.5 Setting parameters


Table 502: LMBRFLO Group settings (basic)
Name Values (Range) Unit Step Default Description
R1A 0.001 - 1500.000 ohm/p 0.001 2.000 Source resistance A (near end)
X1A 0.001 - 1500.000 ohm/p 0.001 12.000 Source reactance A (near end)
R1B 0.001 - 1500.000 ohm/p 0.001 2.000 Source resistance B (far end)
X1B 0.001 - 1500.000 ohm/p 0.001 12.000 Source reactance B (far end)
R1L 0.001 - 1500.000 ohm/p 0.001 2.000 Positive sequence line resistance
X1L 0.001 - 1500.000 ohm/p 0.001 12.500 Positive sequence line reactance
R0L 0.001 - 1500.000 ohm/p 0.001 8.750 Zero sequence line resistance
X0L 0.001 - 1500.000 ohm/p 0.001 50.000 Zero sequence line reactance
R0M 0.000 - 1500.000 ohm/p 0.001 0.000 Zero sequence mutual resistance
X0M 0.000 - 1500.000 ohm/p 0.001 0.000 Zero sequence mutual reactance
LineLength 0.0 - 10000.0 - 0.1 40.0 Length of line

Table 503: LMBRFLO Non group settings (basic)


Name Values (Range) Unit Step Default Description
DrepChNoIL1 1 - 30 Ch 1 1 Recorder input number recording phase
current, IL1
DrepChNoIL2 1 - 30 Ch 1 2 Recorder input number recording phase
current, IL2
DrepChNoIL3 1 - 30 Ch 1 3 Recorder input number recording phase
current, IL3
DrepChNoIN 0 - 30 Ch 1 4 Recorder input number recording
residual current, IN
DrepChNoIP 0 - 30 Ch 1 0 Recorder input number recording 3I0 on
parallel line
DrepChNoUL1 1 - 30 Ch 1 5 Recorder input number recording phase
voltage, UL1
DrepChNoUL2 1 - 30 Ch 1 6 Recorder input number recording phase
voltage, UL2
DrepChNoUL3 1 - 30 Ch 1 7 Recorder input number recording phase
voltage, UL3

753
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

15.5.6 Technical data


Table 504: LMBRFLO technical data
Function Value or range Accuracy
Reactive and resistive reach (0.001-1500.000) Ω/phase ± 2.0% static accuracy
± 2.0% degrees static
angular accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir

Phase selection According to input signals -


Maximum number of fault 100 -
locations

15.6 Measured value expander block RANGE_XP

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Measured value expander block RANGE_XP - -

15.6.1 Introduction
The current and voltage measurements functions (CVMMXU, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI
and VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits that is low-low limit, low limit, high limit and
high-high limit. The measure value expander block (RANGE_XP) has been
introduced to be able to translate the integer output signal from the measuring
functions to 5 binary signals that is below low-low limit, below low limit, normal,
above high-high limit or above high limit. The output signals can be used as
conditions in the configurable logic.

15.6.2 Principle of operation


The input signal must be connected to a range output of a measuring function block
(CVMMXU, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGGIO).
The function block converts the input integer value to five binary output signals
according to table 505.

754
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Table 505: Input integer value converted to binary output signals


Measured supervised below low-low between low‐ between low between high- above high-
value is: limit low and low and high limit high and high high limit
Output: limit limit
LOWLOW High
LOW High
NORMAL High
HIGH High
HIGHHIGH High

15.6.3 Function block


RANGE_XP
RANGE* HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW

IEC05000346-2-en.vsd
IEC05000346 V2 EN

Figure 410: RANGE_XP function block

15.6.4 Input and output signals


Table 506: RANGE_XP Input signals
Name Type Default Description
RANGE INTEGER 0 Measured value range

Table 507: RANGE_XP Output signals


Name Type Description
HIGHHIGH BOOLEAN Measured value is above high-high limit
HIGH BOOLEAN Measured value is between high and high-high limit
NORMAL BOOLEAN Measured value is between high and low limit
LOW BOOLEAN Measured value is between low and low-low limit
LOWLOW BOOLEAN Measured value is below low-low limit

15.7 Disturbance report DRPRDRE

755
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Analog input signals A41RADR - -
Disturbance report DRPRDRE - -
Disturbance report A1RADR - -
Disturbance report A4RADR - -
Disturbance report B1RBDR - -

15.7.1 Introduction
Complete and reliable information about disturbances in the primary and/or in the
secondary system together with continuous event-logging is accomplished by the
disturbance report functionality.

Disturbance report DRPRDRE, always included in the IED, acquires sampled data
of all selected analog input and binary signals connected to the function block that
is, maximum 40 analog and 96 binary signals.

Disturbance report functionality is a common name for several functions:

• Event list
• Indications
• Event recorder
• Trip value recorder
• Disturbance recorder
• Fault locator

Disturbance report function is characterized by great flexibility regarding


configuration, starting conditions, recording times and large storage capacity.

A disturbance is defined as an activation of an input in the AxRADR or BxRBDR


function blocks, which is set to trigger the disturbance recorder. All signals from
start of pre-fault time to the end of post-fault time will be included in the recording.

Every disturbance report recording is saved in the IED in the standard Comtrade
format. The same applies to all events, which are continuously saved in a ring-
buffer. The local HMI is used to get information about the recordings, but the
disturbance report files may be uploaded to PCM600 and further analysis using the
disturbance handling tool.

15.7.2 Principle of operation


Disturbance report DRPRDRE is a common name for several functions to supply
the operator, analysis engineer, and so on, with sufficient information about events
in the system.

The functions included in the disturbance report are:

756
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

• Event list (EL)


• Indications (IND)
• Event recorder (ER)
• Trip value recorder(TVR)
• Disturbance recorder (DR)

Figure 411 shows the relations between Disturbance Report, included functions
and function blocks. Event list (EL), Event recorder (ER) and Indications (IND)
uses information from the binary input function blocks (BxRBDR). Trip value
recorder (TVR) uses analog information from the analog input function blocks
(AxRADR). Disturbance recorder DRPRDRE acquires information from both
AxRADR and BxRBDR.

A1-4RADR Disturbance Report

A4RADR DRPRDRE FL
Analog signals
Trip value rec Fault locator

B1-6RBDR Disturbance
recorder

Binary signals B6RBDR


Event list

Event recorder

Indications

IEC09000336-2-en.vsd
IEC09000336 V2 EN

Figure 411: Disturbance report functions and related function blocks

The whole disturbance report can contain information for a number of recordings,
each with the data coming from all the parts mentioned above. The event list
function is working continuously, independent of disturbance triggering, recording
time, and so on. All information in the disturbance report is stored in non-volatile
flash memories. This implies that no information is lost in case of loss of auxiliary
power. Each report will get an identification number in the interval from 0-999.

757
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Disturbance report

Record no. N Record no. N+1 Record no. N+100

General dist. Trip Event Disturbance


Indications Fault locator Event list
information values recordings recording

en05000125.vsd
IEC05000125 V1 EN

Figure 412: Disturbance report structure

Up to 100 disturbance reports can be stored. If a new disturbance is to be recorded


when the memory is full, the oldest disturbance report is overwritten by the new
one. The total recording capacity for the disturbance recorder is depending of
sampling frequency, number of analog and binary channels and recording time.
Figure 413 shows the number of recordings versus the total recording time tested
for a typical configuration, that is, in a 50 Hz system it is possible to record 100
where the average recording time is 3.4 seconds. The memory limit does not affect
the rest of the disturbance report (Event list (EL), Event recorder (ER), Indications
(IND) and Trip value recorder (TVR)).

Number of recordings
100
3,4 s

80 3,4 s 20 analog
96 binary
40 analog
96 binary
60 6,3 s
6,3 s

6,3 s 50 Hz
40
60 Hz
Total recording time

250 300 350 400 s

en05000488.vsd
IEC05000488 V1 EN

Figure 413: Number of recordings

Disturbance information
Date and time of the disturbance, the indications, events, fault location and the trip
values are available on the local HMI. To acquire a complete disturbance report the

758
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

user must use a PC and - either the PCM600 Disturbance handling tool - or a FTP
or MMS (over 61850) client. The PC can be connected to the IED front, rear or
remotely via the station bus (Ethernet ports).

Indications (IND)
Indications is a list of signals that were activated during the total recording time of
the disturbance (not time-tagged), see section "Indications" for more detailed
information.

Event recorder (ER)


The event recorder may contain a list of up to 150 time-tagged events, which have
occurred during the disturbance. The information is available via the local HMI or
PCM600, see section "Event recorder" for more detailed information.

Event list (EL)


The event list may contain a list of totally 1000 time-tagged events. The list
information is continuously updated when selected binary signals change state. The
oldest data is overwritten. The logged signals may be presented via local HMI or
PCM600, see section "Event list" for more detailed information.

Trip value recorder (TVR)


The recorded trip values include phasors of selected analog signals before the fault
and during the fault, see section "Trip value recorder" for more detailed information.

Disturbance recorder (DR)


Disturbance recorder records analog and binary signal data before, during and after
the fault, see section "Disturbance recorder" for more detailed information.

Fault locator (FL)


The fault location function calculates the distance to fault, see section "Fault
locator LMBRFLO" for more detailed information.

Time tagging
The IED has a built-in real-time calendar and clock. This function is used for all
time tagging within the disturbance report

Recording times
Disturbance report DRPRDRE records information about a disturbance during a
settable time frame. The recording times are valid for the whole disturbance report.
Disturbance recorder (DR), event recorder (ER) and indication function register
disturbance data and events during tRecording, the total recording time.

The total recording time, tRecording, of a recorded disturbance is:

tRecording = PreFaultrecT + tFault + PostFaultrecT or PreFaultrecT + TimeLimit, depending on


which criterion stops the current disturbance recording

759
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Trig point
TimeLimit

PreFaultRecT PostFaultRecT

1 2 3

en05000487.vsd
IEC05000487 V1 EN

Figure 414: The recording times definition

PreFaultRecT, 1 Pre-fault or pre-trigger recording time. The time before the fault including the
operate time of the trigger. Use the setting PreFaultRecT to set this time.
tFault, 2 Fault time of the recording. The fault time cannot be set. It continues as long as
any valid trigger condition, binary or analog, persists (unless limited by TimeLimit
the limit time).
PostFaultRecT, 3 Post fault recording time. The time the disturbance recording continues after all
activated triggers are reset. Use the setting PostFaultRecT to set this time.
TimeLimit Limit time. The maximum allowed recording time after the disturbance recording
was triggered. The limit time is used to eliminate the consequences of a trigger
that does not reset within a reasonable time interval. It limits the maximum
recording time of a recording and prevents subsequent overwriting of already
stored disturbances. Use the setting TimeLimit to set this time.

Analog signals
Up to 40 analog signals can be selected for recording by the Disturbance recorder
and triggering of the Disturbance report function. Out of these 40, 30 are reserved
for external analog signals from analog input modules (TRM) and line data
communication module (LDCM) via preprocessing function blocks (SMAI) and
summation block (3PHSUM). The last 10 channels may be connected to internally
calculated analog signals available as function block output signals (mA input
signals, phase differential currents, bias currents and so on).

760
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

SMAI A1RADR
Block AI3P A2RADR
^GRP2L1 AI1 INPUT1 A3RADR
External
analogue ^GRP2L2 AI2 INPUT2
signals ^GRP2L3 AI3 INPUT3
^GRP2N AI4 INPUT4
Type AIN INPUT5
INPUT6
...

A4RADR

INPUT31
INPUT32
INPUT33
Internal analogue signals INPUT34
INPUT35
INPUT36

...

INPUT40

IEC10000029-1-en.vsd
IEC10000029 V1 EN

Figure 415: Analog input function blocks

The external input signals will be acquired, filtered and skewed and (after
configuration) available as an input signal on the AxRADR function block via the
SMAI function block. The information is saved at the Disturbance report base
sampling rate (1000 or 1200 Hz). Internally calculated signals are updated
according to the cycle time of the specific function. If a function is running at
lower speed than the base sampling rate, Disturbance recorder will use the latest
updated sample until a new updated sample is available.

If the IED is preconfigured the only tool needed for analog configuration of the
Disturbance report is the Signal Matrix Tool (SMT, external signal configuration).
In case of modification of a preconfigured IED or general internal configuration the
Application Configuration tool within PCM600 is used.

The preprocessor function block (SMAI) calculates the residual quantities in cases
where only the three phases are connected (AI4-input not used).SMAI makes the
information available as a group signal output, phase outputs and calculated
residual output (AIN-output). In situations where AI4-input is used as an input
signal the corresponding information is available on the non-calculated output
(AI4) on the SMAI function block. Connect the signals to the AxRADR accordingly.

For each of the analog signals, Operation = On means that it is recorded by the
disturbance recorder. The trigger is independent of the setting of Operation, and
triggers even if operation is set to Off. Both undervoltage and overvoltage can be
used as trigger conditions. The same applies for the current signals.

761
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

If Operation = Off, no waveform (samples) will be recorded and reported in graph.


However, Trip value, pre-fault and fault value will be recorded and reported. The
input channel can still be used to trig the disturbance recorder.

If Operation = On, waveform (samples) will also be recorded and reported in graph.

The analog signals are presented only in the disturbance recording, but they affect
the entire disturbance report when being used as triggers.

Binary signals
Up to 96 binary signals can be selected to be handled by disturbance report. The
signals can be selected from internal logical and binary input signals. A binary
signal is selected to be recorded when:

• the corresponding function block is included in the configuration


• the signal is connected to the input of the function block

Each of the 96 signals can be selected as a trigger of the disturbance report


(Operation = Off). A binary signal can be selected to activate the red LED on the
local HMI (SetLED = On/Off).

The selected signals are presented in the event recorder, event list and the
disturbance recording. But they affect the whole disturbance report when they are
used as triggers. The indications are also selected from these 96 signals with local
HMI IndicationMask=Show/Hide.

Trigger signals
The trigger conditions affect the entire disturbance report, except the event list,
which runs continuously. As soon as at least one trigger condition is fulfilled, a
complete disturbance report is recorded. On the other hand, if no trigger condition
is fulfilled, there is no disturbance report, no indications, and so on. This implies
the importance of choosing the right signals as trigger conditions.

A trigger can be of type:

• Manual trigger
• Binary-signal trigger
• Analog-signal trigger (over/under function)

Manual trigger
A disturbance report can be manually triggered from the local HMI, PCM600 or
via station bus (IEC 61850). When the trigger is activated, the manual trigger
signal is generated. This feature is especially useful for testing. Refer to the
operator's manual for procedure.

Binary-signal trigger
Any binary signal state (logic one or a logic zero) can be selected to generate a
trigger (Triglevel = Trig on 0/Trig on 1). When a binary signal is selected to

762
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

generate a trigger from a logic zero, the selected signal will not be listed in the
indications list of the disturbance report.

Analog-signal trigger
All analog signals are available for trigger purposes, no matter if they are recorded
in the disturbance recorder or not. The settings are OverTrigOp, UnderTrigOp,
OverTrigLe and UnderTrigLe.

The check of the trigger condition is based on peak-to-peak values. When this is
found, the absolute average value of these two peak values is calculated. If the
average value is above the threshold level for an overvoltage or overcurrent trigger,
this trigger is indicated with a greater than (>) sign with the user-defined name.

If the average value is below the set threshold level for an undervoltage or
undercurrent trigger, this trigger is indicated with a less than (<) sign with its name.
The procedure is separately performed for each channel.

This method of checking the analog start conditions gives a function which is
insensitive to DC offset in the signal. The operate time for this start is typically in
the range of one cycle, 20 ms for a 50 Hz network.

All under/over trig signal information is available on the local HMI and PCM600.

Post Retrigger
Disturbance report function does not respond to any new trig condition, during a
recording. Under certain circumstances the fault condition may reoccur during the
post-fault recording, for instance by automatic reclosing to a still faulty power line.

In order to capture the new disturbance it is possible to allow retriggering


(PostRetrig = On) during the post-fault time. In this case a new, complete
recording will start and, during a period, run in parallel with the initial recording.

When the retrig parameter is disabled (PostRetrig = Off), a new recording will not
start until the post-fault (PostFaultrecT or TimeLimit) period is terminated. If a
new trig occurs during the post-fault period and lasts longer than the proceeding
recording a new complete recording will be fetched.

Disturbance report function can handle maximum 3 simultaneous disturbance


recordings.

15.7.3 Function block


DRPRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED

IEC05000406-3-en.vsd
IEC05000406 V3 EN

Figure 416: DRPRDRE function block

763
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

A1RADR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10

IEC05000430-3-en.vsd
IEC05000430 V3 EN

Figure 417: A1RADR function block

A4RADR
^INPUT31
^INPUT32
^INPUT33
^INPUT34
^INPUT35
^INPUT36
^INPUT37
^INPUT38
^INPUT39
^INPUT40

IEC05000431-3-en.vsd
IEC05000431 V3 EN

Figure 418: A4RADR function block, derived analog inputs

B1RBDR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

IEC05000432-3-en.vsd
IEC05000432 V3 EN

Figure 419: B1RBDR function block, binary inputs, example for B1RBDR -
B6RBDR

764
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

15.7.4 Input and output signals


Table 508: RDRE Output signals
Name Type Description
DRPOFF BOOLEAN Disturbance report function turned off
RECSTART BOOLEAN Disturbance recording started
RECMADE BOOLEAN Disturbance recording made
CLEARED BOOLEAN All disturbances in the disturbance report cleared
MEMUSED BOOLEAN More than 80% of memory used

Table 509: A1RADR Input signals


Name Type Default Description
INPUT1 GROUP - Group signal for input 1
SIGNAL
INPUT2 GROUP - Group signal for input 2
SIGNAL
INPUT3 GROUP - Group signal for input 3
SIGNAL
INPUT4 GROUP - Group signal for input 4
SIGNAL
INPUT5 GROUP - Group signal for input 5
SIGNAL
INPUT6 GROUP - Group signal for input 6
SIGNAL
INPUT7 GROUP - Group signal for input 7
SIGNAL
INPUT8 GROUP - Group signal for input 8
SIGNAL
INPUT9 GROUP - Group signal for input 9
SIGNAL
INPUT10 GROUP - Group signal for input 10
SIGNAL

Table 510: A4RADR Input signals


Name Type Default Description
INPUT31 REAL 0 Analogue channel 31
INPUT32 REAL 0 Analogue channel 32
INPUT33 REAL 0 Analogue channel 33
INPUT34 REAL 0 Analogue channel 34
INPUT35 REAL 0 Analogue channel 35
INPUT36 REAL 0 Analogue channel 36
INPUT37 REAL 0 Analogue channel 37
Table continues on next page

765
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Name Type Default Description


INPUT38 REAL 0 Analogue channel 38
INPUT39 REAL 0 Analogue channel 39
INPUT40 REAL 0 Analogue channel 40

Table 511: B1RBDR Input signals


Name Type Default Description
INPUT1 BOOLEAN 0 Binary channel 1
INPUT2 BOOLEAN 0 Binary channel 2
INPUT3 BOOLEAN 0 Binary channel 3
INPUT4 BOOLEAN 0 Binary channel 4
INPUT5 BOOLEAN 0 Binary channel 5
INPUT6 BOOLEAN 0 Binary channel 6
INPUT7 BOOLEAN 0 Binary channel 7
INPUT8 BOOLEAN 0 Binary channel 8
INPUT9 BOOLEAN 0 Binary channel 9
INPUT10 BOOLEAN 0 Binary channel 10
INPUT11 BOOLEAN 0 Binary channel 11
INPUT12 BOOLEAN 0 Binary channel 12
INPUT13 BOOLEAN 0 Binary channel 13
INPUT14 BOOLEAN 0 Binary channel 14
INPUT15 BOOLEAN 0 Binary channel 15
INPUT16 BOOLEAN 0 Binary channel 16

15.7.5 Setting parameters


Table 512: RDRE Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
PreFaultRecT 0.05 - 1.00 s 0.01 0.10 Pre-fault recording time
PostFaultRecT 0.1 - 10.0 s 0.1 0.5 Post-fault recording time
TimeLimit 0.5 - 10.0 s 0.1 1.0 Fault recording time limit
PostRetrig Off - - Off Post-fault retrig enabled (On) or not (Off)
On
ZeroAngleRef 1 - 30 Ch 1 1 Trip value recorder, phasor reference
channel
OpModeTest Off - - Off Operation mode during test mode
On

766
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Table 513: A1RADR Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation01 Off - - Off Operation On/Off
On
NomValue01 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 1
UnderTrigOp01 Off - - Off Use under level trig for analogue cha 1
On (on) or not (off)
UnderTrigLe01 0 - 200 % 1 50 Under trigger level for analogue cha 1 in
% of signal
OverTrigOp01 Off - - Off Use over level trig for analogue cha 1
On (on) or not (off)
OverTrigLe01 0 - 5000 % 1 200 Over trigger level for analogue cha 1 in
% of signal
Operation02 Off - - Off Operation On/Off
On
NomValue02 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 2
UnderTrigOp02 Off - - Off Use under level trig for analogue cha 2
On (on) or not (off)
UnderTrigLe02 0 - 200 % 1 50 Under trigger level for analogue cha 2 in
% of signal
OverTrigOp02 Off - - Off Use over level trig for analogue cha 2
On (on) or not (off)
OverTrigLe02 0 - 5000 % 1 200 Over trigger level for analogue cha 2 in
% of signal
Operation03 Off - - Off Operation On/Off
On
NomValue03 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 3
UnderTrigOp03 Off - - Off Use under level trig for analogue cha 3
On (on) or not (off)
UnderTrigLe03 0 - 200 % 1 50 Under trigger level for analogue cha 3 in
% of signal
OverTrigOp03 Off - - Off Use over level trig for analogue cha 3
On (on) or not (off)
OverTrigLe03 0 - 5000 % 1 200 Overtrigger level for analogue cha 3 in %
of signal
Operation04 Off - - Off Operation On/Off
On
NomValue04 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 4
UnderTrigOp04 Off - - Off Use under level trig for analogue cha 4
On (on) or not (off)
UnderTrigLe04 0 - 200 % 1 50 Under trigger level for analogue cha 4 in
% of signal
OverTrigOp04 Off - - Off Use over level trig for analogue cha 4
On (on) or not (off)
OverTrigLe04 0 - 5000 % 1 200 Over trigger level for analogue cha 4 in
% of signal
Operation05 Off - - Off Operation On/Off
On
Table continues on next page

767
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


NomValue05 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 5
UnderTrigOp05 Off - - Off Use under level trig for analogue cha 5
On (on) or not (off)
UnderTrigLe05 0 - 200 % 1 50 Under trigger level for analogue cha 5 in
% of signal
OverTrigOp05 Off - - Off Use over level trig for analogue cha 5
On (on) or not (off)
OverTrigLe05 0 - 5000 % 1 200 Over trigger level for analogue cha 5 in
% of signal
Operation06 Off - - Off Operation On/Off
On
NomValue06 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 6
UnderTrigOp06 Off - - Off Use under level trig for analogue cha 6
On (on) or not (off)
UnderTrigLe06 0 - 200 % 1 50 Under trigger level for analogue cha 6 in
% of signal
OverTrigOp06 Off - - Off Use over level trig for analogue cha 6
On (on) or not (off)
OverTrigLe06 0 - 5000 % 1 200 Over trigger level for analogue cha 6 in
% of signal
Operation07 Off - - Off Operation On/Off
On
NomValue07 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 7
UnderTrigOp07 Off - - Off Use under level trig for analogue cha 7
On (on) or not (off)
UnderTrigLe07 0 - 200 % 1 50 Under trigger level for analogue cha 7 in
% of signal
OverTrigOp07 Off - - Off Use over level trig for analogue cha 7
On (on) or not (off)
OverTrigLe07 0 - 5000 % 1 200 Over trigger level for analogue cha 7 in
% of signal
Operation08 Off - - Off Operation On/Off
On
NomValue08 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 8
UnderTrigOp08 Off - - Off Use under level trig for analogue cha 8
On (on) or not (off)
UnderTrigLe08 0 - 200 % 1 50 Under trigger level for analogue cha 8 in
% of signal
OverTrigOp08 Off - - Off Use over level trig for analogue cha 8
On (on) or not (off)
OverTrigLe08 0 - 5000 % 1 200 Over trigger level for analogue cha 8 in
% of signal
Operation09 Off - - Off Operation On/Off
On
NomValue09 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 9
UnderTrigOp09 Off - - Off Use under level trig for analogue cha 9
On (on) or not (off)
Table continues on next page

768
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Name Values (Range) Unit Step Default Description


UnderTrigLe09 0 - 200 % 1 50 Under trigger level for analogue cha 9 in
% of signal
OverTrigOp09 Off - - Off Use over level trig for analogue cha 9
On (on) or not (off)
OverTrigLe09 0 - 5000 % 1 200 Over trigger level for analogue cha 9 in
% of signal
Operation10 Off - - Off Operation On/Off
On
NomValue10 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 10
UnderTrigOp10 Off - - Off Use under level trig for analogue cha 10
On (on) or not (off)
UnderTrigLe10 0 - 200 % 1 50 Under trigger level for analogue cha 10
in % of signal
OverTrigOp10 Off - - Off Use over level trig for analogue cha 10
On (on) or not (off)
OverTrigLe10 0 - 5000 % 1 200 Over trigger level for analogue cha 10 in
% of signal

Table 514: A4RADR Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation31 Off - - Off Operation On/off
On
NomValue31 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 31
UnderTrigOp31 Off - - Off Use under level trig for analogue cha 31
On (on) or not (off)
UnderTrigLe31 0 - 200 % 1 50 Under trigger level for analogue cha 31
in % of signal
OverTrigOp31 Off - - Off Use over level trig for analogue cha 31
On (on) or not (off)
OverTrigLe31 0 - 5000 % 1 200 Over trigger level for analogue cha 31 in
% of signal
Operation32 Off - - Off Operation On/off
On
NomValue32 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 32
UnderTrigOp32 Off - - Off Use under level trig for analogue cha 32
On (on) or not (off)
UnderTrigLe32 0 - 200 % 1 50 Under trigger level for analogue cha 32
in % of signal
OverTrigOp32 Off - - Off Use over level trig for analogue cha 32
On (on) or not (off)
OverTrigLe32 0 - 5000 % 1 200 Over trigger level for analogue cha 32 in
% of signal
Operation33 Off - - Off Operation On/off
On
NomValue33 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 33
UnderTrigOp33 Off - - Off Use under level trig for analogue cha 33
On (on) or not (off)
Table continues on next page

769
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


UnderTrigLe33 0 - 200 % 1 50 Under trigger level for analogue cha 33
in % of signal
OverTrigOp33 Off - - Off Use over level trig for analogue cha 33
On (on) or not (off)
OverTrigLe33 0 - 5000 % 1 200 Overtrigger level for analogue cha 33 in
% of signal
Operation34 Off - - Off Operation On/off
On
NomValue34 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 34
UnderTrigOp34 Off - - Off Use under level trig for analogue cha 34
On (on) or not (off)
UnderTrigLe34 0 - 200 % 1 50 Under trigger level for analogue cha 34
in % of signal
OverTrigOp34 Off - - Off Use over level trig for analogue cha 34
On (on) or not (off)
OverTrigLe34 0 - 5000 % 1 200 Over trigger level for analogue cha 34 in
% of signal
Operation35 Off - - Off Operation On/off
On
NomValue35 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 35
UnderTrigOp35 Off - - Off Use under level trig for analogue cha 35
On (on) or not (off)
UnderTrigLe35 0 - 200 % 1 50 Under trigger level for analogue cha 35
in % of signal
OverTrigOp35 Off - - Off Use over level trig for analogue cha 35
On (on) or not (off)
OverTrigLe35 0 - 5000 % 1 200 Over trigger level for analogue cha 35 in
% of signal
Operation36 Off - - Off Operation On/off
On
NomValue36 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 36
UnderTrigOp36 Off - - Off Use under level trig for analogue cha 36
On (on) or not (off)
UnderTrigLe36 0 - 200 % 1 50 Under trigger level for analogue cha 36
in % of signal
OverTrigOp36 Off - - Off Use over level trig for analogue cha 36
On (on) or not (off)
OverTrigLe36 0 - 5000 % 1 200 Over trigger level for analogue cha 36 in
% of signal
Operation37 Off - - Off Operation On/off
On
NomValue37 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 37
UnderTrigOp37 Off - - Off Use under level trig for analogue cha 37
On (on) or not (off)
UnderTrigLe37 0 - 200 % 1 50 Under trigger level for analogue cha 37
in % of signal
OverTrigOp37 Off - - Off Use over level trig for analogue cha 37
On (on) or not (off)
Table continues on next page

770
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Name Values (Range) Unit Step Default Description


OverTrigLe37 0 - 5000 % 1 200 Over trigger level for analogue cha 37 in
% of signal
Operation38 Off - - Off Operation On/off
On
NomValue38 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 38
UnderTrigOp38 Off - - Off Use under level trig for analogue cha 38
On (on) or not (off)
UnderTrigLe38 0 - 200 % 1 50 Under trigger level for analogue cha 38
in % of signal
OverTrigOp38 Off - - Off Use over level trig for analogue cha 38
On (on) or not (off)
OverTrigLe38 0 - 5000 % 1 200 Over trigger level for analogue cha 38 in
% of signal
Operation39 Off - - Off Operation On/off
On
NomValue39 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 39
UnderTrigOp39 Off - - Off Use under level trig for analogue cha 39
On (on) or not (off)
UnderTrigLe39 0 - 200 % 1 50 Under trigger level for analogue cha 39
in % of signal
OverTrigOp39 Off - - Off Use over level trig for analogue cha 39
On (on) or not (off)
OverTrigLe39 0 - 5000 % 1 200 Over trigger level for analogue cha 39 in
% of signal
Operation40 Off - - Off Operation On/off
On
NomValue40 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 40
UnderTrigOp40 Off - - Off Use under level trig for analogue cha 40
On (on) or not (off)
UnderTrigLe40 0 - 200 % 1 50 Under trigger level for analogue cha 40
in % of signal
OverTrigOp40 Off - - Off Use over level trig for analogue cha 40
On (on) or not (off)
OverTrigLe40 0 - 5000 % 1 200 Over trigger level for analogue cha 40 in
% of signal

Table 515: B1RBDR Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation01 Off - - Off Trigger operation On/Off
On
TrigLevel01 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 1
IndicationMa01 Hide - - Hide Indication mask for binary channel 1
Show
SetLED01 Off - - Off Set red-LED on HMI for binary channel 1
On
Table continues on next page

771
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


Operation02 Off - - Off Trigger operation On/Off
On
TrigLevel02 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 2
IndicationMa02 Hide - - Hide Indication mask for binary channel 2
Show
SetLED02 Off - - Off Set red-LED on HMI for binary channel 2
On
Operation03 Off - - Off Trigger operation On/Off
On
TrigLevel03 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 3
IndicationMa03 Hide - - Hide Indication mask for binary channel 3
Show
SetLED03 Off - - Off Set red-LED on HMI for binary channel 3
On
Operation04 Off - - Off Trigger operation On/Off
On
TrigLevel04 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 4
IndicationMa04 Hide - - Hide Indication mask for binary channel 4
Show
SetLED04 Off - - Off Set red-LED on HMI for binary channel 4
On
Operation05 Off - - Off Trigger operation On/Off
On
TrigLevel05 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 5
IndicationMa05 Hide - - Hide Indication mask for binary channel 5
Show
SetLED05 Off - - Off Set red-LED on HMI for binary channel 5
On
Operation06 Off - - Off Trigger operation On/Off
On
TrigLevel06 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 6
IndicationMa06 Hide - - Hide Indication mask for binary channel 6
Show
SetLED06 Off - - Off Set red-LED on HMI for binary channel 6
On
Operation07 Off - - Off Trigger operation On/Off
On
TrigLevel07 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 7
IndicationMa07 Hide - - Hide Indication mask for binary channel 7
Show
SetLED07 Off - - Off Set red-LED on HMI for binary channel 7
On
Table continues on next page

772
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Name Values (Range) Unit Step Default Description


Operation08 Off - - Off Trigger operation On/Off
On
TrigLevel08 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 8
IndicationMa08 Hide - - Hide Indication mask for binary channel 8
Show
SetLED08 Off - - Off Set red-LED on HMI for binary channel 8
On
Operation09 Off - - Off Trigger operation On/Off
On
TrigLevel09 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 9
IndicationMa09 Hide - - Hide Indication mask for binary channel 9
Show
SetLED09 Off - - Off Set red-LED on HMI for binary channel 9
On
Operation10 Off - - Off Trigger operation On/Off
On
TrigLevel10 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 10
IndicationMa10 Hide - - Hide Indication mask for binary channel 10
Show
SetLED10 Off - - Off Set red-LED on HMI for binary channel 10
On
Operation11 Off - - Off Trigger operation On/Off
On
TrigLevel11 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 11
IndicationMa11 Hide - - Hide Indication mask for binary channel 11
Show
SetLED11 Off - - Off Set red-LED on HMI for binary channel 11
On
Operation12 Off - - Off Trigger operation On/Off
On
TrigLevel12 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 12
IndicationMa12 Hide - - Hide Indication mask for binary channel 12
Show
SetLED12 Off - - Off Set red-LED on HMI for binary input 12
On
Operation13 Off - - Off Trigger operation On/Off
On
TrigLevel13 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 13
IndicationMa13 Hide - - Hide Indication mask for binary channel 13
Show
SetLED13 Off - - Off Set red-LED on HMI for binary channel 13
On
Table continues on next page

773
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


Operation14 Off - - Off Trigger operation On/Off
On
TrigLevel14 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 14
IndicationMa14 Hide - - Hide Indication mask for binary channel 14
Show
SetLED14 Off - - Off Set red-LED on HMI for binary channel 14
On
Operation15 Off - - Off Trigger operation On/Off
On
TrigLevel15 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 15
IndicationMa15 Hide - - Hide Indication mask for binary channel 15
Show
SetLED15 Off - - Off Set red-LED on HMI for binary channel 15
On
Operation16 Off - - Off Trigger operation On/Off
On
TrigLevel16 Trig on 0 - - Trig on 1 Trig on positiv (1) or negative (0) slope
Trig on 1 for binary inp 16
IndicationMa16 Hide - - Hide Indication mask for binary channel 16
Show
SetLED16 Off - - Off Set red-LED on HMI for binary channel 16
On
FUNT1 0 - 255 FunT 1 0 Function type for binary channel 1 (IEC
-60870-5-103)
FUNT2 0 - 255 FunT 1 0 Function type for binary channel 2 (IEC
-60870-5-103)
FUNT3 0 - 255 FunT 1 0 Function type for binary channel 3 (IEC
-60870-5-103)
FUNT4 0 - 255 FunT 1 0 Function type for binary channel 4 (IEC
-60870-5-103)
FUNT5 0 - 255 FunT 1 0 Function type for binary channel 5 (IEC
-60870-5-103)
FUNT6 0 - 255 FunT 1 0 Function type for binary channel 6 (IEC
-60870-5-103)
FUNT7 0 - 255 FunT 1 0 Function type for binary channel 7 (IEC
-60870-5-103)
FUNT8 0 - 255 FunT 1 0 Function type for binary channel 8 (IEC
-60870-5-103)
FUNT9 0 - 255 FunT 1 0 Function type for binary channel 9 (IEC
-60870-5-103)
FUNT10 0 - 255 FunT 1 0 Function type for binary channel 10 (IEC
-60870-5-103)
FUNT11 0 - 255 FunT 1 0 Function type for binary channel 11 (IEC
-60870-5-103)
FUNT12 0 - 255 FunT 1 0 Function type for binary channel 12 (IEC
-60870-5-103)
Table continues on next page

774
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Name Values (Range) Unit Step Default Description


FUNT13 0 - 255 FunT 1 0 Function type for binary channel 13 (IEC
-60870-5-103)
FUNT14 0 - 255 FunT 1 0 Function type for binary channel 14 (IEC
-60870-5-103)
FUNT15 0 - 255 FunT 1 0 Function type for binary channel 15 (IEC
-60870-5-103)
FUNT16 0 - 255 FunT 1 0 Function type for binary channel 16 (IEC
-60870-5-103)
INFNO1 0 - 255 InfNo 1 0 Information number for binary channel 1
(IEC -60870-5-103)
INFNO2 0 - 255 InfNo 1 0 Information number for binary channel 2
(IEC -60870-5-103)
INFNO3 0 - 255 InfNo 1 0 Information number for binary channel 3
(IEC -60870-5-103)
INFNO4 0 - 255 InfNo 1 0 Information number for binary channel 4
(IEC -60870-5-103)
INFNO5 0 - 255 InfNo 1 0 Information number for binary channel 5
(IEC -60870-5-103)
INFNO6 0 - 255 InfNo 1 0 Information number for binary channel 6
(IEC -60870-5-103)
INFNO7 0 - 255 InfNo 1 0 Information number for binary channel 7
(IEC -60870-5-103)
INFNO8 0 - 255 InfNo 1 0 Information number for binary channel 8
(IEC -60870-5-103)
INFNO9 0 - 255 InfNo 1 0 Information number for binary channel 9
(IEC -60870-5-103)
INFNO10 0 - 255 InfNo 1 0 Information number for binary channel
10 (IEC -60870-5-103)
INFNO11 0 - 255 InfNo 1 0 Information number for binary channel
11 (IEC -60870-5-103)
INFNO12 0 - 255 InfNo 1 0 Information number for binary channel
12 (IEC -60870-5-103)
INFNO13 0 - 255 InfNo 1 0 Information number for binary channel
13 (IEC -60870-5-103)
INFNO14 0 - 255 InfNo 1 0 Information number for binary channel
14 (IEC -60870-5-103)
INFNO15 0 - 255 InfNo 1 0 Information number for binary channel
15 (IEC -60870-5-103)
INFNO16 0 - 255 InfNo 1 0 Information number for binary channel
16 (IEC -60870-5-103)

775
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

15.7.6 Technical data


Table 516: DRPRDRE technical data
Function Range or value Accuracy
Pre-fault time (0.05–1.00) s -
Post-fault time (0.1–10.0) s -
Limit time (0.5–10.0) s -
Maximum number of recordings 100 -
Time tagging resolution 1 ms See table 28
Maximum number of analog inputs 30 + 10 (external + internally -
derived)
Maximum number of binary inputs 96 -
Maximum number of phasors in the 30 -
Trip Value recorder per recording
Maximum number of indications in a 96 -
disturbance report
Maximum number of events in the 150 -
Event recording per recording
Maximum number of events in the 1000, first in - first out -
Event list
Maximum total recording time (3.4 s 340 seconds (100 recordings) at -
recording time and maximum 50 Hz, 280 seconds (80
number of channels, typical value) recordings) at 60 Hz
Sampling rate 1 kHz at 50 Hz -
1.2 kHz at 60 Hz
Recording bandwidth (5-300) Hz -

15.8 Event list

15.8.1 Introduction
Continuous event-logging is useful for monitoring of the system from an overview
perspective and is a complement to specific disturbance recorder functions.

The event list logs all binary input signals connected to the Disturbance report
function. The list may contain of up to 1000 time-tagged events stored in a ring-buffer.

15.8.2 Principle of operation


When a binary signal, connected to the disturbance report function, changes status,
the event list function stores input name, status and time in the event list in
chronological order. The list can contain up to 1000 events from both internal logic
signals and binary input channels. If the list is full, the oldest event is overwritten
when a new event arrives.

776
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

The list can be configured to show oldest or newest events first with a setting on
the local HMI.

The event list function runs continuously, in contrast to the event recorder function,
which is only active during a disturbance.

The name of the binary input signal that appears in the event recording is the user-
defined name assigned when the IED is configured. The same name is used in the
disturbance recorder function (DR), indications (IND)and the event recorder
function (ER).

The event list is stored and managed separate from the disturbance report
information (ER, DR, IND, TVR and FL).

15.8.3 Function block


The Event list has no function block of it’s own. It is included in the DRPRDRE
block and uses information from the BxRBDR block.

15.8.4 Input signals


The Event list logs the same binary input signals as configured for the Disturbance
report function.

15.8.5 Technical data


Table 517: technical data
Function Value
Buffer capacity Maximum number of events in the list 1000
Resolution 1 ms
Accuracy Depending on time
synchronizing

15.9 Indications

15.9.1 Introduction
To get fast, condensed and reliable information about disturbances in the primary
and/or in the secondary system it is important to know, for example binary signals
that have changed status during a disturbance. This information is used in the short
perspective to get information via the local HMI in a straightforward way.

There are three LEDs on the local HMI (green, yellow and red), which will display
status information about the IED and the Disturbance report function (trigged).

777
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

The Indication list function shows all selected binary input signals connected to the
Disturbance report function that have changed status during a disturbance.

15.9.2 Principle of operation


The LED indications display this information:

Green LED:

Steady light In Service


Flashing light Internal fail
Dark No power supply

Yellow LED:

Steady light A disturbance report is triggered


Flashing light The IED is in test mode or in configuration mode

Red LED:

Steady light Trigged on binary signal N with SetLEDN=On

Indication list:

The possible indicated signals are the same as the ones chosen for the disturbance
report function and disturbance recorder.

The indication function tracks 0 to 1 changes of binary signals during the recording
period of the collection window. This means that constant logic zero, constant logic
one or state changes from logic one to logic zero will not be visible in the list of
indications. Signals are not time tagged. In order to be recorded in the list of
indications the:

• the signal must be connected to binary input(DRB1-6)


• the DRPparameter Operation must be set On
• the DRP must be trigged (binary or analog)

Indications are selected with the indication mask (IndicationMask) when


configuring the binary inputs.

The name of the binary input signal that appears in the Indication function is the user-
defined name assigned at configuration of the IED. The same name is used in
disturbance recorder function (DR), indications (IND) and event recorder function
(ER).

778
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

15.9.3 Function block


The Indications function has no function block of it’s own. It is included in the
DRPRDRE block and uses information from the BxRBDR block.

15.9.4 Input signals


The Indications function may log the same binary input signals as the Disturbance
report function.

15.9.5 Technical data


Table 518: technical data
Function Value
Buffer capacity Maximum number of indications 96
presented for single disturbance
Maximum number of recorded 100
disturbances

15.10 Event recorder

15.10.1 Introduction
Quick, complete and reliable information about disturbances in the primary and/or
in the secondary system is vital, for example, time tagged events logged during
disturbances. This information is used for different purposes in the short term (for
example corrective actions) and in the long term (for example Functional Analysis).

The event recorder logs all selected binary input signals connected to the
Disturbance report function. Each recording can contain up to 150 time-tagged events.

The event recorder information is available for the disturbances locally in the IED.

The event recording information is an integrated part of the disturbance record


(Comtrade file).

15.10.2 Principle of operation


When one of the trig conditions for the disturbance report is activated, the event
recorder logs every status change in the 96 selected binary signals. The events can
be generated by both internal logical signals and binary input channels. The
internal signals are time-tagged in the main processor module, while the binary
input channels are time-tagged directly in each I/O module. The events are
collected during the total recording time (pre-, post-fault and limit time), and are
stored in the disturbance report flash memory at the end of each recording.

779
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

In case of overlapping recordings, due to PostRetrig = On and a new trig signal


appears during post-fault time, events will be saved in both recording files.

The name of the binary input signal that appears in the event recording is the user-
defined name assigned when configuring the IED. The same name is used in the
disturbance recorder function (DR), indications (IND) and event recorder function
(ER).

The event record is stored as a part of the disturbance report information (ER, DR,
IND, TVR and FL) and managed via the local HMI or PCM600.

15.10.3 Function block


The Event recorder has no function block of it’s own. It is included in the
DRPRDRE block and uses information from the BxRBDR block.

15.10.4 Input signals


The Event recorder function logs the same binary input signals as the Disturbance
report function.

15.10.5 Technical data


Table 519: technical data
Function Value
Buffer capacity Maximum number of events in disturbance 150
report
Maximum number of disturbance reports 100
Resolution 1 ms
Accuracy Depending on time
synchronizing

15.11 Trip value recorder

15.11.1 Introduction
Information about the pre-fault and fault values for currents and voltages are vital
for the disturbance evaluation.

The Trip value recorder calculates the values of all selected analog input signals
connected to the Disturbance report function. The result is magnitude and phase
angle before and during the fault for each analog input signal.

The trip value recorder information is available for the disturbances locally in the
IED.

780
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

The trip value recorder information is an integrated part of the disturbance record
(Comtrade file).

15.11.2 Principle of operation


Trip value recorder (TVR)calculates and presents both fault and pre-fault
amplitudes as well as the phase angles of all the selected analog input signals. The
parameter ZeroAngleRef points out which input signal is used as the angle
reference. The calculated data is input information to the fault locator (FL).

When the disturbance report function is triggered the sample for the fault
interception is searched for, by checking the non-periodic changes in the analog
input signals. The channel search order is consecutive, starting with the analog
input with the lowest number.

When a starting point is found, the Fourier estimation of the pre-fault values of the
complex values of the analog signals starts 1.5 cycle before the fault sample. The
estimation uses samples during one period. The post-fault values are calculated
using the Recursive Least Squares (RLS) method. The calculation starts a few
samples after the fault sample and uses samples during 1/2 - 2 cycles depending on
the shape of the signals.

If no starting point is found in the recording, the disturbance report trig sample is
used as the start sample for the Fourier estimation. The estimation uses samples
during one cycle before the trig sample. In this case the calculated values are used
both as pre-fault and fault values.

The name of the analog input signal that appears in the Trip value recorder function
is the user-defined name assigned when the IED is configured. The same name is
used in the Disturbance recorder function (DR).

The trip value record is stored as a part of the disturbance report information (ER,
DR, IND, TVR and fault locator) and managed in via the local HMI or PCM600.

15.11.3 Function block


The Trip value recorder has no function block of it’s own. It is included in the
DRPRDRE block and uses information from the BxRBDR block.

15.11.4 Input signals


The trip value recorder function uses analog input signals connected to A1RADR
to A3RADR (not A4RADR).

781
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

15.11.5 Technical data


Table 520: technical data
Function Value
Buffer capacity Maximum number of analog inputs 30
Maximum number of disturbance reports 100

15.12 Disturbance recorder

15.12.1 Introduction
The Disturbance recorder function supplies fast, complete and reliable information
about disturbances in the power system. It facilitates understanding system
behavior and related primary and secondary equipment during and after a
disturbance. Recorded information is used for different purposes in the short
perspective (for example corrective actions) and long perspective (for example
Functional Analysis).

The Disturbance recorder acquires sampled data from all selected analog input and
binary signals connected to the Disturbance report function (maximum 40 analog
and 96 binary signals). The binary signals are the same signals as available under
the event recorder function.

The function is characterized by great flexibility and is not dependent on the


operation of protection functions. It can record disturbances not detected by
protection functions.

The disturbance recorder information for the last 100 disturbances are saved in the
IED and the local HMI is used to view the list of recordings.

15.12.2 Principle of operation


Disturbance recording (DR) is based on the acquisition of binary and analog
signals. The binary signals can be either true binary input signals or internal logical
signals generated by the functions in the IED. The analog signals to be recorded are
input channels from the Transformer Input Module (TRM), Line Differential
communication Module (LDCM) through the Signal Matrix Analog Input (SMAI)
and possible summation (Sum3Ph) function blocks and some internally derived
analog signals. For details, refer to section "Disturbance report DRPRDRE".

Disturbance recorder collects analog values and binary signals continuously, in a


cyclic buffer. The pre-fault buffer operates according to the FIFO principle; old
data will continuously be overwritten as new data arrives when the buffer is full.
The size of this buffer is determined by the set pre-fault recording time.

782
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

Upon detection of a fault condition (triggering), the disturbance is time tagged and
the data storage continues in a post-fault buffer. The storage process continues as
long as the fault condition prevails - plus a certain additional time. This is called
the post-fault time and it can be set in the disturbance report.

The above mentioned two parts form a disturbance recording. The whole memory,
intended for disturbance recordings, acts as a cyclic buffer and when it is full, the
oldest recording is overwritten. The last 100 recordings are stored in the IED.

The time tagging refers to the activation of the trigger that starts the disturbance
recording. A recording can be trigged by, manual start, binary input and/or from
analog inputs (over-/underlevel trig).

A user-defined name for each of the signals can be set. These names are common
for all functions within the disturbance report functionality.

15.12.2.1 Memory and storage

When a recording is completed, a post recording processing occurs.

This post-recording processing comprises:

• Saving the data for analog channels with corresponding data for binary signals
• Add relevant data to be used by the Disturbance handling tool (part of PCM 600)
• Compression of the data, which is performed without losing any data accuracy
• Storing the compressed data in a non-volatile memory (flash memory)

The recorded disturbance is now ready for retrieval and evaluation.

The recording files comply with the Comtrade standard IEC 60255-24 and are
divided into three files; a header file (HDR), a configuration file (CFG) and a data
file (DAT).

The header file (optional in the standard) contains basic information about the
disturbance, that is, information from the Disturbance report sub-functions (ER,
TVR and FL). The Disturbance handling tool use this information and present the
recording in a user-friendly way.

General:

• Station name, object name and unit name


• Date and time for the trig of the disturbance
• Record number
• Sampling rate
• Time synchronization source
• Recording times
• Activated trig signal
• Active setting group

Analog:

783
Technical reference manual
Section 15 1MRK505183-UEN C
Monitoring

• Signal names for selected analog channels


• Information e.g. trig on analog inputs
• Primary and secondary instrument transformer rating
• Over- or Undertrig: level and operation
• Over- or Undertrig status at time of trig
• CT direction

Binary:

• Signal names
• Status of binary input signals

The configuration file is a mandatory file containing information needed to


interpret the data file. For example sampling rate, number of channels, system
frequency, channel info etc.

The data file, which also is mandatory, containing values for each input channel for
each sample in the record (scaled value). The data file also contains a sequence
number and time stamp for each set of samples.

15.12.2.2 IEC 60870-5-103

The communication protocol IEC 60870-5-103 may be used to poll disturbance


recordings from the IED to a master (station HSI). The standard describes how to
handle 8 disturbance recordings, 8 analog channels (4 currents and 4 voltages)
using the public range and binary signals.

The last 8 recordings, out of maximum 100, are available for transfer to the master.
When the last one is transferred and acknowledged new recordings in the IED will
appear, in the master points of view (even if they already where stored in the IED).

To be able to report 40 analog channels from the IED using IEC 60870-5-103 the
first 8 channels are placed in the public range and the next 32 are placed in the
private range. To comply the standard the first 8 must be configured according to
table 521.

Table 521: Configuration of analog channels


Signal Disturbance recorder
IL1 A1RADR INPUT1
IL2 A1RADR INPUT2
IL3 A1RADR INPUT3
IN A1RADR INPUT4
UL1 A1RADR INPUT5
UL2 A1RADR INPUT6
UL3 A1RADR INPUT7
UN A1RADR INPUT8

784
Technical reference manual
1MRK505183-UEN C Section 15
Monitoring

The binary signals connected to BxRBDR are reported by polling. The function
blocks include function type and information number.

15.12.3 Function block


The Disturbance recorder has no function block of it’s own. It is included in the
DRPRDRE, AxRADR and BxRBDR block.

15.12.4 Input and output signals


For signals see section, in Disturbance report, "Input and output signals".

15.12.5 Setting parameters


For Setting parameters see section "Disturbance report DRPRDRE".

15.12.6 Technical data


Table 522: technical data
Function Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 96
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and maximum number 340 seconds (100
of channels, typical value) recordings) at 50 Hz
280 seconds (80
recordings) at 60 Hz

785
Technical reference manual
786
1MRK505183-UEN C Section 16
Metering

Section 16 Metering

About this chapter


This chapter describes among others, Pulse counter logic which is a function used
to meter externally generated binary pulses. The way the functions work, their
setting parameters, function blocks, input and output signals, and technical data are
included for each function.

16.1 Pulse-counter logic PCGGIO

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Pulse-counter logic PCGGIO -

S00947 V1 EN

16.1.1 Introduction
Pulse counter (PCGGIO) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module and then
read by the pulse counter function. A scaled service value is available over the
station bus. The special Binary input module with enhanced pulse counting
capabilities must be ordered to achieve this functionality.

16.1.2 Principle of operation


The registration of pulses is done for positive transitions (0->1) on one of the 16
binary input channels located on the Binary Input Module (BIM). Pulse counter
values are sent to the station HMI with predefined cyclicity without reset.

The reporting time period can be set in the range from 1 second to 60 minutes and
is synchronized with absolute system time. Interrogation of additional pulse
counter values can be done with a command (intermediate reading) for a single
counter. All active counters can also be read by the LON General Interrogation
command (GI) or IEC 61850.

787
Technical reference manual
Section 16 1MRK505183-UEN C
Metering

Pulse counter (PCGGIO) function in the IED supports unidirectional incremental


counters. That means only positive values are possible. The counter uses a 32 bit
format, that is, the reported value is a 32-bit, signed integer with a range
0...+2147483647. The counter is reset at initialization of the IED.

The reported value to station HMI over the station bus contains Identity, Scaled
Value (pulse count x scale), Time, and Pulse Counter Quality. The Pulse Counter
Quality consists of:

• Invalid (board hardware error or configuration error)


• Wrapped around
• Blocked
• Adjusted

The transmission of the counter value by SPA can be done as a service value, that
is, the value frozen in the last integration cycle is read by the station HMI from the
database. PCGGIO updates the value in the database when an integration cycle is
finished and activates the NEW_VAL signal in the function block. This signal can
be connected to an Event function block, be time tagged, and transmitted to the
station HMI. This time corresponds to the time when the value was frozen by the
function.

The pulse counter function requires a binary input card, BIMp, that
is specially adapted to the pulse counter function.

Figure 420 shows the pulse counter function block with connections of the inputs
and outputs.

SingleCmdFunc PulseCounter EVENT


OUTx BLOCK
INVALID INPUT1
SingleCmdFunc Pulse RESTART INPUT2
OUTx INPUT OUT READ_VAL
Pulse length >1s BLOCKED INPUT3
I/O-module NEW_VAL INPUT4
BI_PULSE
”Reset counter” RS_CNT
NAME
SCAL_VAL IEC EVENT

SMS settings Database


1.Operation = Off/On Pulse counter value:
2.tReporting = 0s...60min 0...2147483647
3.Event Mask = No Events/Report Events
4.Scale = 1-90000
en05000744.vsd
IEC05000744 V1 EN

Figure 420: Overview of the pulse counter function

788
Technical reference manual
1MRK505183-UEN C Section 16
Metering

The BLOCK and READ_VAL inputs can be connected to Single Command


blocks, which are intended to be controlled either from the station HMI or/and the
local HMI. As long as the BLOCK signal is set, the pulse counter is blocked. The
signal connected to READ_VAL performs one additional reading per positive
flank. The signal must be a pulse with a length >1 second.

The BI_PULSE input is connected to the used input of the function block for the
Binary Input Module (BIM).

The NAME input is used for a user-defined name with up to 13 characters.

The RS_CNT input is used for resetting the counter.

Each pulse counter function block has four binary output signals that can be
connected to an Event function block for event recording: INVALID, RESTART,
BLOCKED and NEW_VAL. The SCAL_VAL signal can be connected to the IEC
Event function block.

The INVALID signal is a steady signal and is set if the Binary Input Module,
where the pulse counter input is located, fails or has wrong configuration.

The RESTART signal is a steady signal and is set when the reported value does not
comprise a complete integration cycle. That is, in the first message after IED start-
up, in the first message after deblocking, and after the counter has wrapped around
during last integration cycle.

The BLOCKED signal is a steady signal and is set when the counter is blocked.
There are two reasons why the counter is blocked:

• The BLOCK input is set, or


• The Binary Input Module, where the counter input is situated, is inoperative.

The NEW_VAL signal is a pulse signal. The signal is set if the counter value was
updated since last report.

The SCAL_VAL signal consists of scaled value (according to parameter Scale),


time and status information.

16.1.3 Function block


PCGGIO
BLOCK INVALID
READ_VAL RESTART
BI_PULSE* BLOCKED
RS_CNT NEW_VAL
SCAL_VAL

IEC05000709-2-en.vsd
IEC05000709 V3 EN

Figure 421: PCGGIO function block

789
Technical reference manual
Section 16 1MRK505183-UEN C
Metering

16.1.4 Input and output signals


Table 523: PCGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
READ_VAL BOOLEAN 0 Initiates an additional pulse counter reading
BI_PULSE BOOLEAN 0 Connect binary input channel for metering
RS_CNT BOOLEAN 0 Resets pulse counter value

Table 524: PCGGIO Output signals


Name Type Description
INVALID BOOLEAN The pulse counter value is invalid
RESTART BOOLEAN The reported value does not comprise a complete
integration cycle
BLOCKED BOOLEAN The pulse counter function is blocked
NEW_VAL BOOLEAN A new pulse counter value is generated
SCAL_VAL REAL Scaled value with time and status information

16.1.5 Setting parameters


Table 525: PCGGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
EventMask NoEvents - - NoEvents Report mask for analog events from
ReportEvents pulse counter
CountCriteria Off - - RisingEdge Pulse counter criteria
RisingEdge
Falling edge
OnChange
Scale 1.000 - 90000.000 - 0.001 1.000 Scaling value for SCAL_VAL output to
unit per counted value
Quantity Count - - Count Measured quantity for SCAL_VAL output
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
tReporting 0 - 3600 s 1 60 Cycle time for reporting of counter value

790
Technical reference manual
1MRK505183-UEN C Section 16
Metering

16.1.6 Technical data


Table 526: PCGGIO technical data
Function Setting range Accuracy
Input frequency See Binary Input Module (BIM) -
Cycle time for report of (1–3600) s -
counter value

16.2 Function for energy calculation and demand


handling ETPMMTR

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Energy calculation and demand ETPMMTR - -
handling

16.2.1 Introduction
Outputs from Measurements (CVMMXU) function can be used to calculate
energy. Active as well as reactive values are calculated in import and export
direction. Values can be read or generated as pulses. Maximum demand power
values are also calculated by the function.

16.2.2 Principle of operation


The instantaneous output values of active and reactive power from the
Measurements (CVMMXU) function block are used and integrated over a selected
time tEnergy to measure the integrated energy. The energy values (in MWh and
MVarh) are available as output signals and also as pulsed output which can be
connected to a pulse counter. Outputs are available for forward as well as reverse
direction. The accumulated energy values can be reset from the local HMI reset
menu or with input signal RSTACC.

The maximum demand values for active and reactive power are calculated for the
set time tEnergy and the maximum value is stored in a register available over
communication and from outputs MAXPAFD, MAXPARD, MAXPRFD,
MAXPRRD for the active and reactive power forward and reverse direction until
reset with input signal RSTDMD or from the local HMI reset menu.

791
Technical reference manual
Section 16 1MRK505183-UEN C
Metering

CVMMXU ETPMMTR
PINST P
QINST Q

STACC
TRUE
RSTACC
FALSE
RSTDMD
FALSE

IEC07000121-2-en.vsd
IEC07000121 V2 EN

Figure 422: Connection of Energy calculation and demand handling function


(ETPMMTR) to the Measurements function (CVMMXU)

16.2.3 Function block


ETPMMTR
P ACCST
Q EAFPULSE
STACC EARPULSE
RSTACC ERFPULSE
RSTDMD ERRPULSE
EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD

IEC07000120-2-en.vsd
IEC07000120 V2 EN

Figure 423: ETPMMTR function block

16.2.4 Input and output signals


Table 527: ETPMMTR Input signals
Name Type Default Description
P REAL 0 Measured active power
Q REAL 0 Measured reactive power
STACC BOOLEAN 0 Start to accumulate energy values
RSTACC BOOLEAN 0 Reset of accumulated enery reading
RSTDMD BOOLEAN 0 Reset of maximum demand reading

Table 528: ETPMMTR Output signals


Name Type Description
ACCST BOOLEAN Start of accumulating energy values.
EAFPULSE BOOLEAN Accumulated forward active energy pulse
EARPULSE BOOLEAN Accumulated reverse active energy pulse
Table continues on next page

792
Technical reference manual
1MRK505183-UEN C Section 16
Metering

Name Type Description


ERFPULSE BOOLEAN Accumulated forward reactive energy pulse
ERRPULSE BOOLEAN Accumulated reverse reactive energy pulse
EAFALM BOOLEAN Alarm for active forward energy exceed limit in
set interval
EARALM BOOLEAN Alarm for active reverse energy exceed limit in
set interval
ERFALM BOOLEAN Alarm for reactive forward energy exceed limit in
set interval
ERRALM BOOLEAN Alarm for reactive reverse energy exceed limit in
set interval
EAFACC REAL Accumulated forward active energy value in Ws
EARACC REAL Accumulated reverse active energy value in Ws
ERFACC REAL Accumulated forward reactive energy value in
VArS
ERRACC REAL Accumulated reverse reactive energy value in
VArS
MAXPAFD REAL Maximum forward active power demand value for
set interval
MAXPARD REAL Maximum reverse active power demand value for
set interval
MAXPRFD REAL Maximum forward reactive power demand value
for set interval
MAXPRRD REAL Maximum reactive power demand value in
reverse direction

16.2.5 Setting parameters


Table 529: ETPMMTR Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
StartAcc Off - - Off Activate the accumulation of energy
On values
tEnergy 1 Minute - - 1 Minute Time interval for energy calculation
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes
tEnergyOnPls 0.000 - 60.000 s 0.001 1.000 Energy accumulated pulse ON time in
secs
tEnergyOffPls 0.000 - 60.000 s 0.001 0.500 Energy accumulated pulse OFF time in
secs
EAFAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active forward
accumulated energy value
Table continues on next page

793
Technical reference manual
Section 16 1MRK505183-UEN C
Metering

Name Values (Range) Unit Step Default Description


EARAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active reverse
accumulated energy value
ERFAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive forward
accumulated energy value
ERVAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive reverse
accumulated energy value

Table 530: ETPMMTR Non group settings (advanced)


Name Values (Range) Unit Step Default Description
EALim 0.001 - MWh 0.001 1000000.000 Active energy limit
10000000000.000
ERLim 0.001 - MVArh 0.001 1000.000 Reactive energy limit
10000000000.000
DirEnergyAct Forward - - Forward Direction of active energy flow Forward/
Reverse Reverse
DirEnergyReac Forward - - Forward Direction of reactive energy flow Forward/
Reverse Reverse
EnZeroClamp Off - - On Enable of zero point clamping detection
On function
LevZeroClampP 0.001 - 10000.000 MW 0.001 10.000 Zero point clamping level at active Power
LevZeroClampQ 0.001 - 10000.000 MVAr 0.001 10.000 Zero point clamping level at reactive
Power
EAFPrestVal 0.000 - 10000.000 MWh 0.001 0.000 Preset Initial value for forward active
energy
EARPrestVal 0.000 - 10000.000 MWh 0.001 0.000 Preset Initial value for reverse active
energy
ERFPresetVal 0.000 - 10000.000 MVArh 0.001 0.000 Preset Initial value for forward reactive
energy
ERVPresetVal 0.000 - 10000.000 MVArh 0.001 0.000 Preset Initial value for reverse reactive
energy

794
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Section 17 Station communication

About this chapter


This chapter describes the functions and protocols used on the interfaces to the
substation automation and substation monitoring buses. The way these work, their
setting parameters, function blocks, input and output signals and technical data are
included for each function.

17.1 Overview

Each IED is provided with a communication interface, enabling it to connect to one


or many substation level systems or equipment, either on the Substation
Automation (SA) bus or Substation Monitoring (SM) bus.

Following communication protocols are available:

• IEC 61850-8-1 communication protocol


• IEC 61850-9-2LE communication protocol
• LON communication protocol
• SPA or IEC 60870-5-103 communication protocol
• DNP3.0 communication protocol

Theoretically, several protocols can be combined in the same IED.

17.2 IEC 61850-8-1 communication protocol

17.2.1 Introduction
The IED is equipped with single or double optical Ethernet rear ports (order
dependent) for IEC 61850-8-1 station bus communication. IEC 61850-8-1
communication is also possible from the optical Ethernet front port. IEC 61850-8-1
protocol allows intelligent electrical devices (IEDs) from different vendors to
exchange information and simplifies system engineering. Peer-to-peer
communication according to GOOSE is part of the standard. Disturbance files
uploading is provided.

17.2.2 IEC 61850 generic communication I/O functions SPGGIO,


SP16GGIO

795
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

17.2.2.1 Introduction

IEC61850 generic communication I/O functions (SPGGIO) is used to send one


single logical signal to other systems or equipment in the substation.

17.2.2.2 Principle of operation

Upon receiving a signal at its input, IEC61850 generic communication I/O


functions (SPGGIO) function sends the signal over IEC 61850-8-1 to the
equipment or system that requests this signal. To get the signal, PCM600 must be
used to define which function block in which equipment or system should receive
this information.

17.2.2.3 Function block


SPGGIO
BLOCK
^IN

IEC07000124-2-en.vsd
IEC07000124 V2 EN

Figure 424: SPGGIO function block

SP16GGIO
BLOCK
^IN1
^IN2
^IN3
^IN4
^IN5
^IN6
^IN7
^IN8
^IN9
^IN10
^IN11
^IN12
^IN13
^IN14
^IN15
^IN16

IEC07000125-2-en.vsd
IEC07000125 V2 EN

Figure 425: SP16GGIO function block

17.2.2.4 Input and output signals


Table 531: SPGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN BOOLEAN 0 Input status

796
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Table 532: SP16GGIO Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1 status
IN2 BOOLEAN 0 Input 2 status
IN3 BOOLEAN 0 Input 3 status
IN4 BOOLEAN 0 Input 4 status
IN5 BOOLEAN 0 Input 5 status
IN6 BOOLEAN 0 Input 6 status
IN7 BOOLEAN 0 Input 7 status
IN8 BOOLEAN 0 Input 8 status
IN9 BOOLEAN 0 Input 9 status
IN10 BOOLEAN 0 Input 10 status
IN11 BOOLEAN 0 Input 11 status
IN12 BOOLEAN 0 Input 12 status
IN13 BOOLEAN 0 Input 13 status
IN14 BOOLEAN 0 Input 14 status
IN15 BOOLEAN 0 Input 15 status
IN16 BOOLEAN 0 Input 16 status

17.2.2.5 Setting parameters

The function does not have any parameters available in the local HMI or PCM600.

17.2.3 IEC 61850 generic communication I/O functions MVGGIO

IEC61850 generic communication I/O functions (MVGGIO) function is used to


send the instantaneous value of an analog output to other systems or equipment in
the substation. It can also be used inside the same IED, to attach a RANGE aspect
to an analog value and to permit measurement supervision on that value.

17.2.3.1 Principle of operation

Upon receiving an analog signal at its input, IEC61850 generic communication I/O
functions (MVGGIO) will give the instantaneous value of the signal and the range,
as output values. In the same time, it will send over IEC 61850-8-1 the value, to
other IEC 61850 clients in the substation.

797
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

17.2.3.2 Function block


MVGGIO
BLOCK ^VALUE
^IN RANGE

IEC05000408-2-en.vsd
IEC05000408 V2 EN

Figure 426: MVGGIO function block

17.2.3.3 Input and output signals


Table 533: MVGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN REAL 0 Analogue input value

Table 534: MVGGIO Output signals


Name Type Description
VALUE REAL Magnitude of deadband value
RANGE INTEGER Range

17.2.3.4 Setting parameters


Table 535: MVGGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
MV db 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
MV zeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of range
MV hhLim -10000000000.000 - 0.001 90.000 High High limit
- 10000000000.000
MV hLim -10000000000.000 - 0.001 80.000 High limit
- 10000000000.000
MV lLim -10000000000.000 - 0.001 -80.000 Low limit
- 10000000000.000
MV llLim -10000000000.000 - 0.001 -90.000 Low Low limit
- 10000000000.000
MV min -10000000000.000 - 0.001 -100.000 Minimum value
- 10000000000.000
MV max -10000000000.000 - 0.001 100.000 Maximum value
- 10000000000.000
MV dbType Cyclic - - Dead band Reporting type
Dead band
Int deadband
MV limHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)

798
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

17.2.4 Setting parameters


Table 536: IEC61850-8-1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
GOOSE Front - - OEM311_AB Port for GOOSE communication
OEM311_AB
OEM311_CD

17.2.5 Technical data


Table 537: IEC 61850-8-1 communication protocol
Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX

17.3 IEC 61850-9-2LE communication protocol

17.3.1 Introduction
The IEC 61850-9-2LE process bus communication protocol enables an IED to
communicate with devices providing measured values in digital format, commonly
known as Merging Units (MU). The physical interface in the IED that is used for
the communication is the OEM modules (the two port module version) "CD" port.

17.3.2 Principle of operation


The ABB merging units (MUs) are situated close to primary equipment, like circuit
breakers, isolators, etc. The MUs have the capability to gather measured values
from measuring transformers, non-conventional transducers or both. The gathered
data are then transmitted to subscribers over the process bus, utilizing the IEC
61850-9-2LE protocol.

ABB "physical MU" contains up to 3 logical MUs, each capable of sampling 4


currents and 4 voltages.

The IED communicates with the MUs over the process bus via the OEM module
port "CD". For the user, the MU appears in the IED as a normal analogue input
module and is engineered in the very same way.

799
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

IED

Application

Station Wide
Preprocessing blocks Preprocessing blocks GPS Clock
SMAI SMAI

MU1 MU2
Splitter
Electrical-to-
Optical Converter

1PPS
TRM module OEM Module
CD
110 V 1A 1A

IEC61850-9-2LE

Ethernet Switch

IEC61850-9-2LE

IEC61850-9-2LE

ABB ABB
1PPS 1PPS
Merging Merging
Unit Unit

Combi Combi
CT CT
Sensor Sensor

Conventional VT
en08000072-2.vsd

IEC08000072 V2 EN

Figure 427: Example of signal path for sampled analogue values from MU and
conventional CT/VT

The function has the following alarm signals:

800
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

• MUDATA: Indicates when sample sequence needs to be realigned. that is the


application soon needs to be restarted. The signal is raised to 2 s before the
application is restarted.
• SYNCH: Indicates that the time quality of the hardware is out of the set value
from parameter synchAccLevel (1 μs, 4 μs or unspecified) and the parameter
AppSynch is set to Synch. In case of AppSynch is set to NoSynch the SYNCH
output will never go high.
• SMPLLOST: Indicates that more than one sample has been lost/been marked
invalid/ overflow/ been marked failed, and the sample has thereafter been
substituted. When SMPLLOST is high, protection is blocked.
• MUSYNCH: Indicates that the MU connected is not synchronized. Received
from quality flag in datastream. No IED setting affects this signal.
• TESTMODE: Indicates that the MU connected is in TestMode. Received from
quality flag in datastream. No IED setting affects this signal.

Timeout

TSYNCERR Indicates that there is some timeout on any configured time source or
the time quality is worse than specified in SynchAccLevel. The timeout is
individually specified per time source (PPS, IRIG-B, SNTP etc.) See section
"Time synchronization"

Blocking condition

Blocking of protection functions is indicated by (SAMPLOST is high) or


(MUSYNCH is high and AppSynch is set to Synch) or (SYNCH is high)

Application synch is not required for differential protection based on ECHO mode.
A missing PPS however will lead to a drift between MU and IED. Therefore
protection functions in this case will be blocked.

17.3.3 Function block

The function blocks are not represented in the configuration tool.


The signals appear only in the SMT tool when merging units (MU)
are included in the configuration with the function selector tool. In
the SMT tool they can be mapped to the desired virtual input
(SMAI) of the IED and used internally in the configuration.

801
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

17.3.4 Output signals


Table 538: MU_4I_4U Output signals
Name Type Description
I1 STRING Analogue input I1
I2 STRING Analogue input I2
I3 STRING Analogue input I3
I4 STRING Analogue input I4
U1 STRING Analogue input U1
U2 STRING Analogue input U2
U3 STRING Analogue input U3
U4 STRING Analogue input U4
MUDATA BOOLEAN Fatal error, serious data loss
SYNCH BOOLEAN Protection functions block due to loss of internal
time synchronisation in IED
SMPLLOST BOOLEAN Sample lost
MUSYNCH BOOLEAN Synchronization lost in MU
TESTMODE BOOLEAN MU in test mode

17.3.5 Setting parameters


Table 539: MU_4I_4U Non group settings (basic)
Name Values (Range) Unit Step Default Description
SVId 0 - 40 - 1 ABB_MU0101 MU identifier
SmplGrp 0 - 65535 - 1 0 Sampling group
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite

Table 540: MU_4I_4U Non group settings (advanced)


Name Values (Range) Unit Step Default Description
SynchMode NoSynch - - Init Synchronization mode
Init
Operation

802
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

17.3.6 Technical data


Table 541: IEC 61850-9-2LE communication protocol
Functions Value
Protocol IEC 61850-9-2LE
Communication speed for the IEDs 100BASE-FX

17.4 LON communication protocol

17.4.1 Introduction
An optical network can be used within the substation automation system. This
enables communication with the IED through the LON bus from the operator’s
workplace, from the control center and also from other terminals.

LON communication protocol is specified in LonTalkProtocol Specification


Version 3 from Echelon Corporation and is designed for communication in control
networks. These networks are characterized by high speed for data transfer, short
messages (few bytes), peer-to-peer communication, multiple communication
media, low maintenance, multivendor equipment, and low support costs. LonTalk
supports the needs of applications that cover a range of requirements. The protocol
follows the reference model for open system interconnection (OSI) designed by the
International Standardization Organization (ISO).

In this document the most common addresses for commands and events are
available. For other addresses, refer to section "Related documents".

It is assumed that the reader is familiar with LON communication protocol in general.

17.4.2 Principle of operation


The speed of the network depends on the medium and transceiver design. With
protection and control devices, fibre optic media is used, which enables the use of
the maximum speed of 1.25 Mbits/s. The protocol is a peer-to-peer protocol where
all the devices connected to the network can communicate with each other. The
own subnet and node number are identifying the nodes (max. 255 subnets, 127
nodes per one subnet).

The LON bus links the different parts of the protection and control system. The
measured values, status information, and event information are spontaneously sent
to the higher-level devices. The higher-level devices can read and write memorized
values, setting values, and other parameter data when required. The LON bus also
enables the bay level devices to communicate with each other to deliver, for
example, interlocking information among the terminals without the need of a bus
master.

803
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

The LonTalk protocol supports two types of application layer objects: network
variables and explicit messages. Network variables are used to deliver short
messages, such as measuring values, status information, and interlocking/blocking
signals. Explicit messages are used to transfer longer pieces of information, such as
events and explicit read and write messages to access device data.

The benefits achieved from using the LON bus in protection and control systems
include direct communication among all terminals in the system and support for
multi-master implementations. The LON bus also has an open concept, so that the
terminals can communicate with external devices using the same standard of
network variables.

Introduction of LON protocol


For more information, refer to LON bus, LonWorks Network in Protection and
Control, User’s manual and Technical description.

LON protocol

Configuration of LON
Lon Network Tool (LNT 505) is a multi-purpose tool for LonWorks network
configuration. All the functions required for setting up and configuring a
LonWorks network, is easily accessible on a single tool program. For more
information, refer to the operator's manual.

Activate LON Communication


Activate LON communication in the Parameter Setting tool under Main menu/
Communication/ SLM configuration/ Rear optical LON port/ Horizontal
communication, where Operation must be set to ON.

Add LON Device Types LNT


A new device is added to LON Network Tool from the Device menu or by
installing the device from the ABB LON Device Types package for LNT 505, with
the SLDT 670 series package version 1p2 r03.

LON net address


To establish a LON connection with the 670 series IEDs, the IED has to be given a
unique net address. The net address consists of a subnet and node number. This is
accomplished with the LON Network Tool by creating one device for each IED.

Vertical communication
Vertical communication describes communication between the monitoring devices
and protection and control IEDs. This communication includes sending of changed
process data to monitoring devices as events and transfer of commands, parameter
data and disturbance recorder files. This communication is implemented using
explicit messages.

Events and indications


Events sent to the monitoring devices are using explicit messages (message code
44H) with unacknowledged transport service of the LonTalk protocol. When a

804
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

signal is changed in the IED, one message with the value, quality and time is
transmitted from terminal.

Binary events
Binary events are generated in event function blocks EVENT:1 to EVENT:20 in
the 670 series IEDs. The event function blocks have predefined LON addresses.
table 542 shows the LON addresses to the first input on the event function blocks.
The addresses to the other inputs on the event function block are consecutive after
the first input. For example, input 15 on event block EVENT:17 has the address
1280 + 14 (15-1) = 1294.

For double indications only the first eight inputs 1–8 must be used. Inputs 9–16 can
be used for other type of events at the same event block.

As basic, three event function blocks EVENT:1 to EVENT:3 running with a fast
loop time (3 ms) is available in the 670 series IEDs. The remaining event function
blocks EVENT:4 to EVENT:9 runs with a loop time on 8 ms and EVENT:10 to
EVENT:20 runs with a loop time on 100 ms. The event blocks are used to send
binary signals, integers, real time values like analogue data from measuring
functions and mA input modules as well as pulse counter signals.

16 pulse counter value function blocks PCGGIO:1 to PCGGIO:16 and 24 mA input


service values function blocks SMMI1_In1 to 6 – SMMI4_In1 to 6 are available in
the 670 series IEDs.

The first LON address in every event function block is found in table 542

Table 542: LON adresses for Event functions


Function block First LON address in
function block
EVENT:1 1024
EVENT:2 1040
EVENT:3 1056
EVENT:4 1072
EVENT:5 1088
EVENT:6 1104
EVENT:7 1120
EVENT:8 1136
EVENT:9 1152
EVENT:10 1168
EVENT:11 1184
EVENT:12 1200
EVENT:13 1216
EVENT:14 1232
EVENT:15 1248
EVENT:16 1264
Table continues on next page

805
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Function block First LON address in


function block
EVENT:17 1280
EVENT:18 1296
EVENT:19 1312
EVENT:20 1328

Event masks
The event mask for each input can be set individually from Parameter Setting Tool
(PST) under: Settings/ General Settings/ Monitoring / EventFunction as follows:

• No events
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect, event system itself make the reporting decision, (reporting criteria
for integers has no semantic, prefer to be set by the user)

The following type of signals from application functions can be connected to the
event function block.

Single indication
Directly connected binary IO signal via binary input function block (SMBI) is
always reported on change, no changed detection is done in the event function
block. Other Boolean signals, for example a start or a trip signal from a protection
function is event masked in the event function block.

Double indications
Double indications can only be reported via switch-control (SCSWI) functions, the
event reporting is based on information from switch-control, no change detection is
done in the event function block.

Directly connected binary IO signal via binary input function block (SMBI) is not
possible to handle as double indication. Double indications can only be reported for
the first 8 inputs on an event function block.

• 00 generates an intermediate event with the read status 0


• 01 generates an open event with the read status 1
• 10 generates a close event with the read status 2
• 11 generates an undefined event with the read status 3

Analog value
All analog values are reported cyclic, the reporting interval is taken from the
connected function if there is a limit supervised signal, otherwise it is taken from
the event function block.

Command handling

806
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Commands are transferred using transparent SPA-bus messages. The transparent


SPA-bus message is an explicit LON message, which contains an ASCII character
message following the coding rules of the SPA-bus protocol. The message is sent
using explicit messages with message code 41H and using acknowledged transport
service.

Both the SPA-bus command messages (R or W) and the reply messages (D, A or
N) are sent using the same message code. It is mandatory that one device sends out
only one SPA-bus message at a time to one node and waits for the reply before
sending the next message.

For commands from the operator workplace to the IED for apparatus control, That
is, the function blocks type SCSWI 1 to 32, SXCBR 1 to 18 and SXSWI 1 to 28;
the SPA addresses are according to table 543.

Horizontal communication
Network variables are used for communication between 500 series and 670 series
IEDs. The supported network variable type is SNVT_state (NV type 83).
SNVT_state is used to communicate the state of a set of 1 to 16 Boolean values.

Multiple command send function block (MULTICMDSND) is used to pack the


information to one value. This value is transmitted to the receiving node and
presented for the application by a multiple command function block
(MULTICMDRCV). At horizontal communication the input BOUND on the event
function block (MULTICMDSND) must be set to 1. There are 10
MULTICMDSND and 60 MULTICMDRCV function blocks available. The
MULTICMDSND and MULTICMDRCV function blocks are connected using Lon
Network Tool (LNT 505). This tool also defines the service and addressing on LON.

This is an overview for configuring the network variables for 670 series IEDs.

Configuration of LON network variables


Configure the Network variables according to the specific application using the
LON network Tool. For more information, refer to LNT 505 in Operation manual.
The following is an example of how to configure network variables concerning, for
example, interlocking between two IEDs.

807
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

LON

BAY E1 BAY E3 BAY E4


MULTICMDSND: 7 MULTICMDSND: 9 MULTICMDSND: 9

en05000718.vsd
IEC05000718 V2 EN

Figure 428: Examples connections between MULTICMDSND and


MULTICMDRCV function blocks in three IEDs

The network variable connections are done from the NV Connection window.
From LNT window select Connections/ NVConnections/ New.

en05000719.vsd
IEC05000719 V1 EN

Figure 429: The network variables window in LNT

There are two ways of downloading NV connections. Either the users can use the
drag-and-drop method where they can select all nodes in the device window, drag
them to the Download area in the bottom of the program window and drop them

808
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

there; or, they can perform it by selecting the traditional menu, Configuration/
Download.

en05000720.vsd
IEC05000720 V1 EN

Figure 430: The download configuration window in LNT

Communication ports
The serial communication module (SLM) is used for SPA or IEC60870-5-103 and
LON communication. This module is a mezzanine module, and can be placed on
the Main Processing Module (NUM). The serial communication module can have
connectors for two plastic fibre cables (snap-in) or two glass fibre cables (ST,
bayonet) or a combination of plastic and glass fibre. Three different types are
available depending on type of fibre. The incoming optical fibre is connected to the
RX receiver input, and the outgoing optical fibre to the TX transmitter output.
When the fibre optic cables are laid out, pay special attention to the instructions
concerning the handling and connection of the optical fibres. The module is
identified with a number on the label on the module.

Table 543: SPA addresses for commands from the operator workplace to the IED for apparatus
control
Name Function SPA Description
block address
BL_CMD SCSWI01 1 I 5115 SPA parameters for block
command
BL_CMD SCSWI02 1 I 5139 SPA parameters for block
command
BL_CMD SCSWI02 1 I 5161 SPA parameters for block
command
BL_CMD SCSWI04 1 I 5186 SPA parameters for block
command
Table continues on next page

809
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Name Function SPA Description


block address
BL_CMD SCSWI05 1 I 5210 SPA parameters for block
command
BL_CMD SCSWI06 1 I 5234 SPA parameters for block
command
BL_CMD SCSWI07 1 I 5258 SPA parameters for block
command
BL_CMD SCSWI08 1 I 5283 SPA parameters for block
command
BL_CMD SCSWI09 1 I 5307 SPA parameters for block
command
BL_CMD SCSWI10 1 I 5331 SPA parameters for block
command
BL_CMD SCSWI11 1 I 5355 SPA parameters for block
command
BL_CMD SCSWI12 1 I 5379 SPA parameters for block
command
BL_CMD SCSWI13 1 I 5403 SPA parameters for block
command
BL_CMD SCSWI14 1 I 5427 SPA parameters for block
command
BL_CMD SCSWI15 1 I 5451 SPA parameters for block
command
BL_CMD SCSWI16 1 I 5475 SPA parameters for block
command
BL_CMD SCSWI17 1 I 5499 SPA parameters for block
command
BL_CMD SCSWI18 1 I 5523 SPA parameters for block
command
BL_CMD SCSWI19 1 I 5545 SPA parameters for block
command
BL_CMD SCSWI20 1 I 5571 SPA parameters for block
command
BL_CMD SCSWI21 1 I 5594 SPA parameters for block
command
BL_CMD SCSWI22 1 I 5619 SPA parameters for block
command
BL_CMD SCSWI23 1 I 5643 SPA parameters for block
command
BL_CMD SCSWI24 1 I 5667 SPA parameters for block
command
BL_CMD SCSWI25 1 I 5691 SPA parameters for block
command
BL_CMD SCSWI26 1 I 5715 SPA parameters for block
command
BL_CMD SCSWI27 1 I 5739 SPA parameters for block
command
BL_CMD SCSWI28 1 I 5763 SPA parameters for block
command
Table continues on next page

810
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Name Function SPA Description


block address
BL_CMD SCSWI29 1 I 5787 SPA parameters for block
command
BL_CMD SCSWI30 1 I 5811 SPA parameters for block
command
BL_CMD SCSWI31 1 I 5835 SPA parameters for block
command
BL_CMD SCSWI32 1 I 5859 SPA parameters for block
command
CANCEL SCSWI01 1 I 5107 SPA parameters for cancel
command
CANCEL SCSWI02 1 I 5131 SPA parameters for cancel
command
CANCEL SCSWI03 1 I 5153 SPA parameters for cancel
command
CANCEL SCSWI04 1 I 5178 SPA parameters for cancel
command
CANCEL SCSWI05 1 I 5202 SPA parameters for cancel
command
CANCEL SCSWI06 1 I 5226 SPA parameters for cancel
command
CANCEL SCSWI07 1 I 5250 SPA parameters for cancel
command
CANCEL SCSWI08 1 I 5275 SPA parameters for cancel
command
CANCEL SCSWI09 1 I 5299 SPA parameters for cancel
command
CANCEL SCSWI10 1 I 5323 SPA parameters for cancel
command
CANCEL SCSWI11 1 I 5347 SPA parameters for cancel
command
CANCEL SCSWI12 1 I 5371 SPA parameters for cancel
command
CANCEL SCSWI13 1 I 5395 SPA parameters for cancel
command
CANCEL SCSWI14 1 I 5419 SPA parameters for cancel
command
CANCEL SCSWI15 1 I 5443 SPA parameters for cancel
command
CANCEL SCSWI16 1 I 5467 SPA parameters for cancel
command
CANCEL SCSWI17 1 I 5491 SPA parameters for cancel
command
CANCEL SCSWI18 1 I 5515 SPA parameters for cancel
command
CANCEL SCSWI19 1 I 5537 SPA parameters for cancel
command
CANCEL SCSWI20 1 I 5563 SPA parameters for cancel
command
Table continues on next page

811
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Name Function SPA Description


block address
CANCEL SCSWI21 1 I 5586 SPA parameters for cancel
command
CANCEL SCSWI22 1 I 5611 SPA parameters for cancel
command
CANCEL SCSWI23 1 I 5635 SPA parameters for cancel
command
CANCEL SCSWI24 1 I 5659 SPA parameters for cancel
command
CANCEL SCSWI25 1 I 5683 SPA parameters for cancel
command
CANCEL SCSWI26 1 I 5707 SPA parameters for cancel
command
CANCEL SCSWI27 1 I 5731 SPA parameters for cancel
command
CANCEL SCSWI28 1 I 5755 SPA parameters for cancel
command
CANCEL SCSWI29 1 I 5779 SPA parameters for cancel
command
CANCEL SCSWI30 1 I 5803 SPA parameters for cancel
command
CANCEL SCSWI31 1 I 5827 SPA parameters for cancel
command
CANCEL SCSWI32 1 I 5851 SPA parameters for cancel
command
SELECTOpen=00, SCSWI01 1 I 5105 SPA parameters for select (Open/
SELECTClose=01, Close) command
SELOpen+ILO=10, Note: Send select command
SELClose+ILO=11, before operate command
SELOpen+SCO=20,
SELClose+SCO=21,
SELOpen+ILO+SCO=30,
SELClose+ILO+SCO=31
SELECTOpen=00, SCSWI02 1 I 5129 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI03 1 I 5151 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI04 1 I 5176 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI05 1 I 5200 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI06 1 I 5224 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI07 1 I 5248 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI08 1 I 5273 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI09 1 I 5297 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI10 1 I 5321 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
Table continues on next page

812
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Name Function SPA Description


block address
SELECTOpen=00, SCSWI11 1 I 5345 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI12 1 I 5369 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI13 1 I 5393 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI14 1 I 5417 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI15 1 I 5441 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI16 1 I 5465 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI17 1 I 5489 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI18 1 I 5513 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI19 1 I 5535 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI20 1 I 5561 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI21 1 I 5584 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI22 1 I 5609 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI23 1 I 5633 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI24 1 I 5657 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI25 1 I 5681 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI26 1 I 5705 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI27 1 I 5729 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI28 1 I 5753 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI29 1 I 5777 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI30 1 I 5801 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI31 1 I 5825 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI32 1 I 5849 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
Table continues on next page

813
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Name Function SPA Description


block address
ExcOpen=00, SCSWI01 1 I 5106 SPA parameters for operate (Open/
ExcClose=01, Close) command
ExcOpen+ILO=10, Note: Send select command
ExcClose+ILO=11, before operate command
ExcOpen+SCO=20,
ExcClose+SCO=21,
ExcOpen+ILO+SCO=30,
ExcClose+ILO+SCO=31
ExcOpen=00, SCSWI02 1 I 5130 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI02 1 I 5152 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI04 1 I 5177 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI05 1 I 5201 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI06 1 I 5225 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI07 1 I 5249 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI08 1 I 5274 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI09 1 I 5298 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI10 1 I 5322 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI11 1 I 5346 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI12 1 I 5370 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI13 1 I 5394 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI14 1 I 5418 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI15 1 I 5442 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI16 1 I 5466 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI17 1 I 5490 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI18 1 I 5514 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI19 1 I 5536 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI20 1 I 5562 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI21 1 I 5585 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI22 1 I 5610 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
Table continues on next page

814
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Name Function SPA Description


block address
ExcOpen=00, SCSWI23 1 I 5634 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI24 1 I 5658 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI25 1 I 5682 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI26 1 I 5706 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI27 1 I 5730 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI28 1 I 5754 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI29 1 I 5778 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI30 1 I 5802 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI31 1 I 5826 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI32 1 I 5850 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
Sub Value SXCBR01 2 I 7854 SPA parameter for position to be
substituted
Note: Send the value before Enable
Sub Value SXCBR02 2 I 7866 SPA parameter for position to be
substituted
Sub Value SXCBR03 2 I 7884 SPA parameter for position to be
substituted
Sub Value SXCBR04 2 I 7904 SPA parameter for position to be
substituted
Sub Value SXCBR05 2 I 7923 SPA parameter for position to be
substituted
Sub Value SXCBR06 2 I 7942 SPA parameter for position to be
substituted
Sub Value SXCBR07 2 I 7961 SPA parameter for position to be
substituted
Sub Value SXCBR08 2 I 7980 SPA parameter for position to be
substituted
Sub Value SXCBR09 3I7 SPA parameter for position to be
substituted
Sub Value SXCBR10 3 I 26 SPA parameter for position to be
substituted
Sub Value SXCBR11 3 I 45 SPA parameter for position to be
substituted
Sub Value SXCBR12 3 I 56 SPA parameter for position to be
substituted
Sub Value SXCBR13 3 I 74 SPA parameter for position to be
substituted
Sub Value SXCBR14 3 I 94 SPA parameter for position to be
substituted
Table continues on next page

815
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Name Function SPA Description


block address
Sub Value SXCBR15 3 I 120 SPA parameter for position to be
substituted
Sub Value SXCBR16 3 I 133 SPA parameter for position to be
substituted
Sub Value SXCBR17 3 I 158 SPA parameter for position to be
substituted
Sub Value SXCBR18 3 I 179 SPA parameter for position to be
substituted
Sub Value SXSWI01 3 I 196 SPA parameter for position to be
substituted
Sub Value SXSWI02 3 I 216 SPA parameter for position to be
substituted
Sub Value SXSWI03 3 I 235 SPA parameter for position to be
substituted
Sub Value SXSWI04 3 I 254 SPA parameter for position to be
substituted
Sub Value SXSWI05 3 I 272 SPA parameter for position to be
substituted
Sub Value SXSWI06 3 I 292 SPA parameter for position to be
substituted
Sub Value SXSWI07 3 I 310 SPA parameter for position to be
substituted
Sub Value SXSWI08 3 I 330 SPA parameter for position to be
substituted
Sub Value SXSWI09 3 I 348 SPA parameter for position to be
substituted
Sub Value SXSWI10 3 I 359 SPA parameter for position to be
substituted
Sub Value SXSWI11 3 I 378 SPA parameter for position to be
substituted
Sub Value SXSWI12 3 I 397 SPA parameter for position to be
substituted
Sub Value SXSWI13 3 I 416 SPA parameter for position to be
substituted
Sub Value SXSWI14 3 I 435 SPA parameter for position to be
substituted
Sub Value SXSWI15 3 I 454 SPA parameter for position to be
substituted
Sub Value SXSWI16 3 I 473 SPA parameter for position to be
substituted
Sub Value SXSWI17 3 I 492 SPA parameter for position to be
substituted
Sub Value SXSWI18 3 I 511 SPA parameter for position to be
substituted
Sub Value SXSWI19 3 I 530 SPA parameter for position to be
substituted
Sub Value SXSWI20 3 I 549 SPA parameter for position to be
substituted
Table continues on next page

816
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Name Function SPA Description


block address
Sub Value SXSWI21 3 I 568 SPA parameter for position to be
substituted
Sub Value SXSWI22 3 I 587 SPA parameter for position to be
substituted
Sub Value SXSWI23 3 I 606 SPA parameter for position to be
substituted
Sub Value SXSWI24 3 I 625 SPA parameter for position to be
substituted
Sub Value SXSWI25 3 I 644 SPA parameter for position to be
substituted
Sub Value SXSWI26 3 I 663 SPA parameter for position to be
substituted
Sub Value SXSWI27 3 I 682 SPA parameter for position to be
substituted
Sub Value SXSWI28 3 I 701 SPA parameter for position to be
substituted
Sub Enable SXCBR01 2 I 7855 SPA parameter for substitute
enable command
Note: Send the Value before
Enable
Sub Enable SXCBR02 2 I 7865 SPA parameter for substitute
enable command
Sub Enable SXCBR03 2 I 7885 SPA parameter for substitute
enable command
Sub Enable SXCBR04 2 I 7903 SPA parameter for substitute
enable command
Sub Enable SXCBR05 2 I 7924 SPA parameter for substitute
enable command
Sub Enable SXCBR06 2 I 7941 SPA parameter for substitute
enable command
Sub Enable SXCBR07 2 I 7962 SPA parameter for substitute
enable command
Sub Enable SXCBR08 2 I 7979 SPA parameter for substitute
enable command
Sub Enable SXCBR09 3I8 SPA parameter for substitute
enable command
Sub Enable SXCBR10 3 I 25 SPA parameter for substitute
enable command
Sub Enable SXCBR11 3 I 46 SPA parameter for substitute
enable command
Sub Enable SXCBR12 3 I 55 SPA parameter for substitute
enable command
Sub Enable SXCBR13 3 I 75 SPA parameter for substitute
enable command
Sub Enable SXCBR14 3 I 93 SPA parameter for substitute
enable command
Sub Enable SXCBR15 3 I 121 SPA parameter for substitute
enable command
Table continues on next page

817
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Name Function SPA Description


block address
Sub Enable SXCBR16 3 I 132 SPA parameter for substitute
enable command
Sub Enable SXCBR17 3 I 159 SPA parameter for substitute
enable command
Sub Enable SXCBR18 3 I 178 SPA parameter for substitute
enable command
Sub Enable SXSWI01 3 I 197 SPA parameter for substitute
enable command
Sub Enable SXSWI02 3 I 215 SPA parameter for substitute
enable command
Sub Enable SXSWI03 3 I 234 SPA parameter for substitute
enable command
Sub Enable SXSWI04 3 I 252 SPA parameter for substitute
enable command
Sub Enable SXSWI05 3 I 271 SPA parameter for substitute
enable command
Sub Enable SXSWI06 3 I 290 SPA parameter for substitute
enable command
Sub Enable SXSWI07 3 I 309 SPA parameter for substitute
enable command
Sub Enable SXSWI08 3 I 328 SPA parameter for substitute
enable command
Sub Enable SXSWI09 3 I 347 SPA parameter for substitute
enable command
Sub Enable SXSWI10 3 I 360 SPA parameter for substitute
enable command
Sub Enable SXSWI11 3I 379 SPA parameter for substitute
enable command
Sub Enable SXSWI12 3 I 398 SPA parameter for substitute
enable command
Sub Enable SXSWI13 3 I 417 SPA parameter for substitute
enable command
Sub Enable SXSWI14 3 I 436 SPA parameter for substitute
enable command
Sub Enable SXSWI15 3 I 455 SPA parameter for substitute
enable command
Sub Enable SXSWI16 3 I 474 SPA parameter for substitute
enable command
Sub Enable SXSWI17 3 I 493 SPA parameter for substitute
enable command
Sub Enable SXSWI18 3 I 512 SPA parameter for substitute
enable command
Sub Enable SXSWI19 3 I 531 SPA parameter for substitute
enable command
Sub Enable SXSWI20 3 I 550 SPA parameter for substitute
enable command
Sub Enable SXSWI21 3 I 569 SPA parameter for substitute
enable command
Table continues on next page

818
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Name Function SPA Description


block address
Sub Enable SXSWI22 3 I 588 SPA parameter for substitute
enable command
Sub Enable SXSWI23 3 I 607 SPA parameter for substitute
enable command
Sub Enable SXSWI24 3 I 626 SPA parameter for substitute
enable command
Sub Enable SXSWI25 3 I 645 SPA parameter for substitute
enable command
Sub Enable SXSWI26 3 I 664 SPA parameter for substitute
enable command
Sub Enable SXSWI27 3 I 683 SPA parameter for substitute
enable command
Sub Enable SXSWI28 3 I 702 SPA parameter for substitute
enable command
Update Block SXCBR01 2 I 7853 SPA parameter for update block
command
Update Block SXCBR02 2 I 7864 SPA parameter for update block
command
Update Block SXCBR03 2 I 7883 SPA parameter for update block
command
Update Block SXCBR04 2 I 7905 SPA parameter for update block
command
Update Block SXCBR05 2 I 7922 SPA parameter for update block
command
Update Block SXCBR06 2 I 7943 SPA parameter for update block
command
Update Block SXCBR07 2 I 7960 SPA parameter for update block
command
Update Block SXCBR08 2 I 7981 SPA parameter for update block
command
Update Block SXCBR09 3I6 SPA parameter for update block
command
Update Block SXCBR10 3 I 27 SPA parameter for update block
command
Update Block SXCBR11 3 I 44 SPA parameter for update block
command
Update Block SXCBR12 3 I 57 SPA parameter for update block
command
Update Block SXCBR13 3 I 73 SPA parameter for update block
command
Update Block SXCBR14 3 I 92 SPA parameter for update block
command
Update Block SXCBR15 3 I 122 SPA parameter for update block
command
Update Block SXCBR16 3 I 131 SPA parameter for update block
command
Update Block SXCBR17 3 I 160 SPA parameter for update block
command
Table continues on next page

819
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Name Function SPA Description


block address
Update Block SXCBR18 3 I 177 SPA parameter for update block
command
Update Block SXSWI01 3 I 198 SPA parameter for update block
command
Update Block SXSWI02 3 I 214 SPA parameter for update block
command
Update Block SXSWI03 3 I 236 SPA parameter for update block
command
Update Block SXSWI04 3 I 253 SPA parameter for update block
command
Update Block SXSWI05 3 I 273 SPA parameter for update block
command
Update Block SXSWI06 3 I 291 SPA parameter for update block
command
Update Block SXSWI07 3 I 311 SPA parameter for update block
command
Update Block SXSWI08 3 I 329 SPA parameter for update block
command
Update Block SXSWI09 3 I 349 SPA parameter for update block
command
Update Block SXSWI10 3 I 358 SPA parameter for update block
command
Update Block SXSWI11 3 I 377 SPA parameter for update block
command
Update Block SXSWI12 3 I 396 SPA parameter for update block
command
Update Block SXSWI13 3 I 415 SPA parameter for update block
command
Update Block SXSWI14 3 I 434 SPA parameter for update block
command
Update Block SXSWI15 3 I 453 SPA parameter for update block
command
Update Block SXSWI16 3 I 472 SPA parameter for update block
command
Update Block SXSWI17 3 I 491 SPA parameter for update block
command
Update Block SXSWI18 3 I 510 SPA parameter for update block
command
Update Block SXSWI19 3 I 529 SPA parameter for update block
command
Update Block SXSWI20 3 I 548 SPA parameter for update block
command
Update Block SXSWI21 3 I 567 SPA parameter for update block
command
Update Block SXSWI22 3 I 586 SPA parameter for update block
command
Update Block SXSWI23 3 I 605 SPA parameter for update block
command
Table continues on next page

820
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Name Function SPA Description


block address
Update Block SXSWI24 3 I 624 SPA parameter for update block
command
Update Block SXSWI25 3 I 643 SPA parameter for update block
command
Update Block SXSWI26 3 I 662 SPA parameter for update block
command
Update Block SXSWI27 3 I 681 SPA parameter for update block
command
Update Block SXSWI28 3 I 700 SPA parameter for update block
command

17.4.3 Setting parameters


Table 544: HORZCOMM Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation
On

Table 545: ADE Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation
On
TimerClass Slow - - Slow Timer class
Normal
Fast

17.4.4 Technical data


Table 546: LON communication protocol
Function Value
Protocol LON
Communication speed 1.25 Mbit/s

17.5 SPA communication protocol

17.5.1 Introduction
In this section the most common addresses for commands and events are available.
For other addresses, refer to section "Related documents".

821
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

It is assumed that the reader is familiar with the SPA communication protocol in
general.

17.5.2 Principle of operation


The SPA bus uses an asynchronous serial communications protocol (1 start bit, 7
data bits + even parity, 1 stop bit) with data transfer rate up to 38400 bit/s. For
more information on recommended baud rate for each type of IED, refer to
Technical reference manual. Messages on the bus consist of ASCII characters.

Introduction of SPA protocol


The basic construction of the protocol assumes that the slave has no self-initiated
need to talk to the master but the master is aware of the data contained in the slaves
and, consequently, can request required data. In addition, the master can send data
to the slave. Requesting by the master can be performed either by sequenced
polling (for example, for event information) or only on demand.

The master requests slave information using request messages and sends
information to the slave in write messages. Furthermore, the master can send all
slaves in common a broadcast message containing time or other data. The inactive
state of bus transmit and receive lines is a logical "1".

SPA protocol
The tables below specify the SPA addresses for reading data from and writing data
to an IED with the SPA communication protocol implemented.

The SPA addresses for the mA input service values (MIM3 to MIM16) are found
in table 547.

Table 547: SPA addresses for the MIM function


Function block SPA address
MIM3-CH1 4-O-6508
MIM3-CH2 4-O-6511
MIM3-CH3 4-O-6512
MIM3-CH4 4-O-6515
MIM3-CH5 4-O-6516
MIM3-CH6 4-O-6519
MIM4-CH1 4-O-6527
MIM4-CH2 4-O-6530
MIM4-CH3 4-O-6531
MIM4-CH4 4-O-6534
MIM4-CH5 4-O-6535
MIM4-CH6 4-O-6538
MIM5-CH1 4-O-6546
MIM5-CH2 4-O-6549
Table continues on next page

822
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Function block SPA address


MIM5-CH3 4-O-6550
MIM5-CH4 4-O-6553
MIM5-CH5 4-O-6554
MIM5-CH6 4-O-6557
MIM6-CH1 4-O-6565
MIM6-CH2 4-O-6568
MIM6-CH3 4-O-6569
MIM6-CH4 4-O-6572
MIM6-CH5 4-O-6573
MIM6-CH6 4-O-6576
MIM7-CH1 4-O-6584
MIM7-CH2 4-O-6587
MIM7-CH3 4-O-6588
MIM7-CH4 4-O-6591
MIM7-CH5 4-O-6592
MIM7-CH6 4-O-6595
MIM8-CH1 4-O-6603
MIM8-CH2 4-O-6606
MIM8-CH3 4-O-6607
MIM8-CH4 4-O-6610
MIM8-CH5 4-O-6611
MIM8-CH6 4-O-6614
MIM9-CH1 4-O-6622
MIM9-CH2 4-O-6625
MIM9-CH3 4-O-6626
MIM9-CH4 4-O-6629
MIM9-CH5 4-O-6630
MIM9-CH6 4-O-6633
MIM10-CH1 4-O-6641
MIM10-CH2 4-O-6644
MIM10-CH3 4-O-6645
MIM10-CH4 4-O-6648
MIM10-CH5 4-O-6649
MIM10-CH6 4-O-6652
MIM11-CH1 4-O-6660
MIM11-CH2 4-O-6663
MIM11-CH3 4-O-6664
MIM11-CH4 4-O-6667
MIM11-CH5 4-O-6668
Table continues on next page

823
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Function block SPA address


MIM11-CH6 4-O-6671
MIM12-CH1 4-O-6679
MIM12-CH2 4-O-6682
MIM12-CH3 4-O-6683
MIM12-CH4 4-O-6686
MIM12-CH5 4-O-6687
MIM12-CH6 4-O-6690
MIM13-CH1 4-O-6698
MIM13-CH2 4-O-6701
MIM13-CH3 4-O-6702
MIM13-CH4 4-O-6705
MIM13-CH5 4-O-6706
MIM13-CH6 4-O-6709
MIM14-CH1 4-O-6717
MIM14-CH2 4-O-6720
MIM14-CH3 4-O-6721
MIM14-CH4 4-O-6724
MIM14-CH5 4-O-6725
MIM14-CH6 4-O-6728
MIM15-CH1 4-O-6736
MIM15-CH2 4-O-6739
MIM15-CH3 4-O-6740
MIM15-CH4 4-O-6743
MIM15-CH5 4-O-6744
MIM15-CH6 4-O-6747
MIM16-CH1 4-O-6755
MIM16-CH2 4-O-6758
MIM16-CH3 4-O-6759
MIM16-CH4 4-O-6762
MIM16-CH5 4-O-6763
MIM16-CH6 4-O-6766

The SPA addresses for the pulse counter values PCGGIO:1 to PCGGIO:16 are
found in table 548.

Table 548: SPA addresses for the PCGGIO function


Function block SPA address CNT_VAL SPA address NEW_VAL
PCGGIO:1 3-O-5834 3-O-5833
PCGGIO:2 3-O-5840 3-O-5839
PCGGIO:3 3-O-5846 3-O-5845
Table continues on next page

824
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Function block SPA address CNT_VAL SPA address NEW_VAL


PCGGIO:4 3-O-5852 3-O-5851
PCGGIO:5 3-O-5858 3-O-5857
PCGGIO:6 3-O-5864 3-O-5863
PCGGIO:7 3-O-5870 3-O-5869
PCGGIO:8 3-O-5876 3-O-5875
PCGGIO:9 3-O-5882 3-O-5881
PCGGIO:10 3-O-5888 3-O-5887
PCGGIO:11 3-O-5894 3-O-5893
PCGGIO:12 3-O-5900 3-O-5899
PCGGIO:13 3-O-5906 3-O-5905
PCGGIO:14 3-O-5912 3-O-5911
PCGGIO:15 3-O-5918 3-O-5917
PCGGIO:16 3-O-5924 3-O-5923

I/O modules
To read binary inputs, the SPA-addresses for the outputs of the I/O-module
function block are used, that is, the addresses for BI1 – BI16. For SPA addresses,
refer to section "Related documents".

Single command, 16 signals


The IEDs can be provided with a function to receive signals either from a
substation automation system or from the local HMI. That receiving function block
has 16 outputs that can be used, for example, to control high voltage apparatuses in
switchyards. For local control functions, the local HMI can also be used.

Single command, 16 signals function consists of three function blocks;


SINGLECMD:1 to SINGLECMD:3 for 16 binary output signals each.

The signals can be individually controlled from the operator station, remote-control
gateway, or from the local HMI on the IED. For Single command, 16 signals
function block, SINGLECMD:1 to SINGLECMD:3, the address is for the first
output. The other outputs follow consecutively after the first one. For example,
output 7 on the SINGLECMD:2 function block has the 5O533 address.

The SPA addresses for Single command, 16 signals functions SINGLECMD:1 to


SINGLECMD:3 are found in table 549.

Table 549: SPA addresses for SINGLECMD function


Function block SPA address CMD Input SPA address CMD output
SINGLECMD1-Cmd1 4-S-4639 5-O-511
SINGLECMD1-Cmd2 4-S-4640 5-O-512
SINGLECMD1-Cmd3 4-S-4641 5-O-513
SINGLECMD1-Cmd4 4-S-4642 5-O-514
Table continues on next page

825
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Function block SPA address CMD Input SPA address CMD output
SINGLECMD1-Cmd5 4-S-4643 5-O-515
SINGLECMD1-Cmd6 4-S-4644 5-O-516
SINGLECMD1-Cmd7 4-S-4645 5-O-517
SINGLECMD1-Cmd8 4-S-4646 5-O-518
SINGLECMD1-Cmd9 4-S-4647 5-O-519
SINGLECMD1-Cmd10 4-S-4648 5-O-520
SINGLECMD1-Cmd11 4-S-4649 5-O-521
SINGLECMD1-Cmd12 4-S-4650 5-O-522
SINGLECMD1-Cmdt13 4-S-4651 5-O-523
SINGLECMD1-Cmd14 4-S-4652 5-O-524
SINGLECMD1-Cmd15 4-S-4653 5-O-525
SINGLECMD1-Cmd16 4-S-4654 5-O-526
SINGLECMD2-Cmd1 4-S-4672 5-O-527
SINGLECMD2-Cmd2 4-S-4673 5-O-528
SINGLECMD2-Cmdt3 4-S-4674 5-O-529
SINGLECMD2-Cmd4 4-S-4675 5-O-530
SINGLECMD2-Cmd5 4-S-4676 5-O-531
SINGLECMD2-Cmd6 4-S-4677 5-O-532
SINGLECMD2-Cmd7 4-S-4678 5-O-533
SINGLECMD2-Cmd8 4-S-4679 5-O-534
SINGLECMD2-Cmd9 4-S-4680 5-O-535
SINGLECMD2-Cmd10 4-S-4681 5-O-536
SINGLECMD2-Cmd11 4-S-4682 5-O-537
SINGLECMD2-Cmd12 4-S-4683 5-O-538
SINGLECMD2-Cmd13 4-S-4684 5-O-539
SINGLECMD2-Cmd14 4-S-4685 5-O-540
SINGLECMD2-Cmd15 4-S-4686 5-O-541
SINGLECMD2-Cmd16 4-S-4687 5-O-542
SINGLECMD3-Cmd1 4-S-4705 5-O-543
SINGLECMD3-Cmd2 4-S-4706 5-O-544
SINGLECMD3-Cmd3 4-S-4707 5-O-545
SINGLECMD3-Cmd4 4-S-4708 5-O-546
SINGLECMD3-Cmd5 4-S-4709 5-O-547
SINGLECMD3-Cmd6 4-S-4710 5-O-548
SINGLECMD3-Cmd7 4-S-4711 5-O-549
SINGLECMD3-Cmd8 4-S-4712 5-O-550
SINGLECMD3-Cmd9 4-S-4713 5-O-551
SINGLECMD3-Cmd10 4-S-4714 5-O-552
SINGLECMD3-Cmd11 4-S-4715 5-O-553
Table continues on next page

826
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Function block SPA address CMD Input SPA address CMD output
SINGLECMD3-Cmd12 4-S-4716 5-O-554
SINGLECMD3-Cmd13 4-S-4717 5-O-555
SINGLECMD3-Cmd14 4-S-4718 5-O-556
SINGLECMD3-Cmd15 4-S-4719 5-O-557
SINGLECMD3-Cmd16 4-S-4720 5-O-558

Figure 431 shows an application example of how the user can, in a simplified way,
connect the command function via the configuration logic circuit in a protection
IED for control of a circuit breaker.

A pulse via the binary outputs of the IED normally performs this type of command
control. The SPA addresses to control the outputs OUT1 – OUT16 in SINGLECMD:
1 are shown in table 549.
SINGLECMD PULSETIMER
BLOCK ^OUT1 INPUT OUT To output board, CLOSE
^OUT2 #1.000 T
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7 AND PULSETIMER
^OUT8 INPUT1 OUT INPUT OUT To output board, OPEN
INPUT2 NOUT T
^OUT9 #1.000
INPUT3
^OUT10
INPUT4N
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16

SYNCH OK

IEC05000717-2-en.vsd
IEC05000717 V2 EN

Figure 431: Application example showing a simplified logic diagram for control
of a circuit breaker

The MODE input defines if the output signals from SINGLECMD:1 is off, steady
or pulsed signals. This is set in Parameter Setting Tool (PST) under: Setting /
General Settings / Control / Commands / Single Command.

Event function
Event function is intended to send time-tagged events to the station level (for
example, operator workplace) over the station bus. The events are there presented
in an event list. The events can be created from both internal logical signals and
binary input channels. All the internal signals are time tagged in the main
processing module, while the binary input channels are time tagged directly on
each I/O module. The events are produced according to the set event masks. The
event masks are treated commonly for both the LON and SPA channels. All events
according to the event mask are stored in a buffer, which contains up to 1000
events. If new events appear before the oldest event in the buffer is read, the oldest
event is overwritten and an overflow alarm appears.

827
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Two special signals for event registration purposes are available in the IED,
Terminal Restarted (0E50) and Event buffer overflow (0E51).

The input parameters can be set individually from the Parameter Setting Tool
(PST) under: Setting / General Setting / Monitoring / Event Function as follows:

• No events
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect, event system itself make the reporting decision, (reporting criteria
for integers has no semantic, prefer to be set by the user)

The Status and event codes for the Event functions are found in table 550.

Table 550: Status and event codes

Single indication1) Double indication


Event block Status Set event Reset Intermedi Closed 10 Open 01 Undefined
event ate 00 11
EVENT:1
Input 1 22O1 22E33 22E32 22E0 22E1 22E2 22E3
Input 2 22O2 22E35 22E34 22E4 22E5 22E6 22E7
Input 3 22O3 22E37 22E36 22E8 22E9 22E10 22E11
Input 4 22O4 22E39 22E38 22E12 22E13 22E14 22E15
Input 5 22O5 22E41 22E40 22E16 22E17 22E18 22E19
Input 6 22O6 22E43 22E42 22E20 22E21 22E22 22E23
Input 7 22O7 22E45 22E44 22E24 22E25 22E26 22E27
Input 8 22O8 22E47 22E46 22E28 22E29 22E30 22E31
Input 9 22O9 22E49 22E48 - - - -
Input 10 22O10 22E51 22E50 - - - -
Input 11 22O11 22E53 22E52 - - - -
Input 12 22O12 22E55 22E54 - - - -
Input 13 22O13 22E57 22E56 - - - -
Input 14 22O14 22E59 22E58 - - - -
Input 15 22O15 22E61 22E60 - - - -
Input 16 22O16 22E63 22E62 - - - -

EVENT:2 230.. 23E.. 23E.. 23E.. 23E.. 23E.. 23E..


EVENT:3 240.. 24E.. 24E.. 24E.. 23E.. 24E.. 24E..
- - - - - - - -
- - - - - - - -
- - - - - - - -
EVENT:20 410.. 41E.. 41E.. 41E.. 41E.. 41E.. 41E..

These values are only applicable if the Event mask is masked ≠ OFF.

Connection of signals as events


Signals coming from different protection and control functions and must be sent as
events to the station level over the SPA-bus (or LON-bus) are connected to the
Event function block according to figure 432.

828
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

EVENT
Block BLOCK
ILRANG ^INPUT1
PSTO ^INPUT2
UL12RANG ^INPUT3
UL23RANG ^INPUT4
UL31RANG ^INPUT5
3I0RANG ^INPUT6
3U0RANG ^INPUT7
FALSE ^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

IEC07000065-2-en.vsd
IEC07000065 V2 EN

Figure 432: Connection of protection signals for event handling

17.5.2.1 Communication ports

The serial communication module (SLM) is used for SPA or IEC 60870-5-103 and
LON communication. This module is a mezzanine module, and can be placed on
the Analog/Digital conversion module (ADM). The serial communication module
can have connectors for two plastic fibre cables (snap-in) or two glass fibre cables
(ST, bayonet) or a combination of plastic and glass fibre. Three different types are
available depending on type of fibre.

The incoming optical fibre is connected to the RX receiver input, and the outgoing
optical fibre to the TX transmitter output. When the fibre optic cables are laid out,
pay special attention to the instructions concerning the handling and connection of
the optical fibres. The module is identified with a number on the label on the module.

The procedure to set the transfer rate and slave number can be found in the
Installation and commissioning manual for respective IEDs.

17.5.3 Design
When communicating locally with a computer (PC) in the station, using the rear
SPA port, the only hardware needed for a station monitoring system is:

• Optical fibres
• Opto/electrical converter for the PC
• PC

When communicating remotely with a PC using the rear SPA port, the same
hardware and telephone modems are needed.

The software needed in the PC, either local or remote, is PCM600.

When communicating between the local HMI and a PC, the only hardware required
is a front-connection cable.

829
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

17.5.4 Setting parameters


Table 551: SPA Non group settings (basic)
Name Values (Range) Unit Step Default Description
SlaveAddress 1 - 899 - 1 30 Slave address
BaudRate 300 Bd - - 9600 Bd Baudrate on serial line
1200 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd

Table 552: LONSPA Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation
On
SlaveAddress 1 - 899 - 1 30 Slave address

17.5.5 Technical data


Table 553: SPA communication protocol
Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400
Bd
Slave number 1 to 899

17.6 IEC 60870-5-103 communication protocol

17.6.1 Introduction
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must
have software that can interpret the IEC 60870-5-103 communication messages.

17.6.2 Principle of operation

17.6.2.1 General

IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial


communication exchanging information with a control system, and with a data
transfer rate up to 38400 bit/s. In IEC terminology, a primary station is a master
and a secondary station is a slave. The communication is based on a point-to-point

830
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

principle. The master must have software that can interpret IEC 60870-5-103
communication messages.

Introduction to IEC 60870–5–103 protocol


IEC 60870-5-103 protocol functionality consists of the following functions:

• Event handling
• Report of analog service values (measurements)
• Fault location
• Command handling
• Autorecloser ON/OFF
• Teleprotection ON/OFF
• Protection ON/OFF
• LED reset
• Characteristics 1 - 4 (Setting groups)
• File transfer (disturbance files)
• Time synchronization

For detailed information about IEC 60870-5-103, refer to the IEC 60870 standard
part 5: Transmission protocols, and to the section 103: Companion standard for the
informative interface of protection equipment.

IEC 60870-5-103
The tables in the following sections specify the information types supported by the
IEDs with the communication protocol IEC 60870-5-103 implemented.

To support the information, corresponding functions must be included in the


protection and control IED.

Commands in control direction


Commands in control direction, I103IEDCMD
Command block in control direction with defined output signals.

Number of instances: 1

Command block use PARAMETER as FUNCTION TYPE.

INFORMATION NUMBER is defined for each output signals.


Info. no Message Supported
19 LED Reset Yes
23 Activate setting group 1 Yes
24 Activate setting group 2 Yes
25 Activate setting group 3 Yes
26 Activate setting group 4 Yes

Function commands in control direction, pre-defined I103CMD

831
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Function command block in control direction with defined output signals.

Number of instances: 1

FUNCTION TYPE parameter for each block.

INFORMATION NUMBER is defined for each output signals.


Info. no. Message Supported
16 Auto-recloser on/off Yes
17 Teleprotection on/off Yes
18 Protection on/off Yes

Function commands in control direction, user-defined, I103UserCMD


Function command blocks in control direction with user-defined output signals.

Number of instances: 4

FUNCTION TYPE parameter for each block in private range. Default values are
defined in private range 1 - 4. One for each instance.

INFORMATION NUMBER is required for each output signal. Default values are 1
- 8.
Info. no. Message Supported
1 Output signal 01 Yes
2 Output signal 02 Yes
3 Output signal 03 Yes
4 Output signal 04 Yes
5 Output signal 05 Yes
6 Output signal 06 Yes
7 Output signal 07 Yes
8 Output signal 08 Yes

Status
Terminal status indications in monitor direction, I103IED
Indication block for status in monitor direction with defined IED functions.

Number of instances: 1

Indication block use PARAMETER as FUNCTION TYPE.

INFORMATION NUMBER is defined for each input signals.

832
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Info. no. Message Supported


19 LED reset Yes
23 Setting group 1 active Yes
24 Setting group 2 active Yes
25 Setting group 3 active Yes
26 Setting group 4 active Yes
21 Test mode active Yes

Function status indications in monitor direction, user-defined, I103UserDef


Function indication blocks in monitor direction with user-defined input signals.

Number of instances: 20

FUNCTION TYPE parameter for each block in private range. Default values are
defined in private range 5 - 24. One for each instance.

INFORMATION NUMBER is required for each input signal. Default values are
defined in range 1 - 8.
Info. no. Message Supported
1 Input signal 01 Yes
2 Input signal 02 Yes
3 Input signal 03 Yes
4 Input signal 04 Yes
5 Input signal 05 Yes
6 Input signal 06 Yes
7 Input signal 07 Yes
8 Input signal 08 Yes

Supervision indications in monitor direction, I103Superv


Indication block for supervision in monitor direction with defined functions.

Number of instances: 1

FUNCTION TYPE parameter for each block.

INFORMATION NUMBER is defined for output signals.


Info. no. Message Supported
32 Measurand supervision I Yes
33 Measurand supervision U Yes
37 I>>back-up operation Yes
38 VT fuse failure Yes
46 Group warning Yes
47 Group alarm Yes

833
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Earth fault indications in monitor direction, I103EF


Indication block for earth fault in monitor direction with defined functions.

Number of instances: 1

FUNCTION TYPE parameter for each block.

INFORMATION NUMBER is defined for each output signal.


Info. no. Message Supported
51 Earth fault forward Yes
52 Earth fault reverse Yes

Fault indications in monitor direction, type 1, I103FltDis


Fault indication block for faults in monitor direction with defined functions.

The instance type is suitable for distance protection function.

FUNCTION TYPE parameter for each block.

INFORMATION NUMBER is defined for each input signal.

Number of instances: 1
Info. no. Message Supported
64 Start L1 Yes
65 Start L2 Yes
66 Start L3 Yes
67 Start IN Yes
84 General start Yes
69 Trip L1 Yes
70 Trip L2 Yes
71 Trip L3 Yes
68 General trip Yes
74 Fault forward/line Yes
75 Fault reverse/busbar Yes
78 Zone 1 Yes
79 Zone 2 Yes
80 Zone 3 Yes
81 Zone 4 Yes
82 Zone 5 Yes
76 Signal transmitted Yes
77 Signal received Yes
73 SCL, Fault location in ohm Yes

834
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Fault indications in monitor direction, type 2, I103FltStd


Fault indication block for faults in monitor direction with defined functions.

The instance type is suitable for line differential, transformer differential,


overcurrent and earth fault protection functions.

FUNCTION TYPE setting for each block.

INFORMATION NUMBER is defined for each input signal.

Number of instances: 1
Info. no. Message Supported
64 Start L1 Yes
65 Start L2 Yes
66 Start L3 Yes
67 Start IN Yes
84 General start Yes
69 Trip L1 Yes
70 Trip L2 Yes
71 Trip L3 Yes
68 General trip Yes
74 Fault forward/line Yes
75 Fault reverse/busbar Yes
85 Breaker failure Yes
86 Trip measuring system L1 Yes
87 Trip measuring system L2 Yes
88 Trip measuring system L3 Yes
89 Trip measuring system N Yes
90 Over current trip I> Yes
91 Over current trip I>> Yes
92 Earth fault trip IN> Yes
93 Earth fault trip IN>> Yes

Autorecloser indications in monitor direction, I103AR


Indication block for autorecloser in monitor direction with defined functions.

Number of instances: 1

FUNCTION TYPE parameter for each block.

INFORMATION NUMBER is defined for each output signal.

835
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Info. no. Message Supported


16 Autorecloser active Yes
128 CB on by Autorecloser Yes
130 Autorecloser blocked Yes

Measurands
Function blocks in monitor direction for input measurands. Typically connected to
monitoring function, for example to power measurement .

Measurands in public range, I103Meas


Number of instances: 1

The IED reports all valid measuring types depending on connected signals.

Upper limit for measured currents, active/reactive-power is 2.4 times rated value.

Upper limit for measured voltages and frequency is 1.2 times rated value.
Info. no. Message Supported
148 IL1 Yes
144, 145, IL2 Yes
148
148 IL3 Yes
147 IN, Neutral current Yes
148 UL1 Yes
148 UL2 Yes
148 UL3 Yes
145, 146 UL1-UL2 Yes
147 UN, Neutral voltage Yes
146, 148 P, active power Yes
146, 148 Q, reactive power Yes
148 f, frequency Yes

Measurands in private range, I103MeasUsr


Number of instances: 3

FUNCTION TYPE parameter for each block in private range. Default values are
defined in private range 25 – 27. One for each instance.

INFORMATION NUMBER parameter for each block. Default value 1.


Info. no. Message Supported
- Meas1 Yes
- Meas2 Yes
- Meas3 Yes
Table continues on next page

836
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Info. no. Message Supported


- Meas4 Yes
- Meas5 Yes
- Meas6 Yes
- Meas7 Yes
- Meas8 Yes
- Meas9 Yes

Disturbance recordings
The following elements are used in the ASDUs (Application Service Data Units)
defined in the standard.

Analog signals, 40-channels: the channel number for each channel has to be
specified. Channels used in the public range are 1 to 8 and with:

• IL1 connected to channel 1 on disturbance function block A1RADR


• IL2 connected to channel 2 on disturbance function block A1RADR
• IL3 connected to channel 3 on disturbance function block A1RADR
• IN connected to channel 4 on disturbance function block A1RADR
• VL1E connected to channel 5 on disturbance function block A1RADR
• VL2E connected to channel 6 on disturbance function block A1RADR
• VL3E connected to channel 7 on disturbance function block A1RADR
• VEN connected to channel 8 on disturbance function block A1RADR

Channel number used for the remaining 32 analog signals are numbers in the
private range 64 to 95.

Binary signals, 96-channels: for each channel the user can specify a FUNCTION
TYPE and an INFORMATION NUMBER.

Disturbance upload

All analog and binary signals that are recorded with disturbance recorder can be
reported to the master. The last eight disturbances that are recorded are available
for transfer to the master. A successfully transferred disturbance (acknowledged by
the master) will not be reported to the master again.

When a new disturbance is recorded by the IED a list of available recorded


disturbances will be sent to the master, an updated list of available disturbances can
be sent whenever something has happened to disturbances in this list. For example,
when a disturbance is deteceted (by other client, for example, SPA) or when a new
disturbance has been recorded or when the master has uploaded a disturbance.

Deviations from the standard

837
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Information sent in the disturbance upload is specified by the standard; however,


some of the information are adapted to information available in disturbance
recorder in 670 series.

This section describes all data that is not exactly as specified in the standard.

ASDU23

In ‘list of recorded disturbances’ (ASDU23) an information element named SOF


(status of fault) exists. This information element consists of 4 bits and indicates
whether:

• Bit TP: the protection equipment has tripped during the fault
• Bit TM: the disturbance data are currently being transmitted
• Bit TEST: the disturbance data have been recorded during normal operation or
test mode.
• Bit OTEV: the disturbance data recording has been initiated by another event
than start

The only information that is easily available is test-mode status. The other
information is always set (hard coded) to:

TP Recorded fault with trip. [1]


TM Disturbance data waiting for transmission [0]
OTEV Disturbance data initiated by other events [1]

Another information element in ASDU23 is the FAN (fault number). According to


the standard this is a number that is incremented when a protection function takes
action. In 670 series FAN is equal to disturbance number, which is incremented for
each disturbance.

ASDU26

When a disturbance has been selected by the master; (by sending ASDU24), the
protection equipment answers by sending ASDU26, which contains an information
element named NOF (number of grid faults). This number must indicate fault
number in the power system,that is, a fault in the power system with several trip
and auto-reclosing has the same NOF (while the FAN must be incremented). NOF
is in 670 series, just as FAN, equal to disturbance number.

To get INF and FUN for the recorded binary signals there are parameters on the
disturbance recorder for each input. The user must set these parameters to whatever
he connects to the corresponding input.

838
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Interoperability, physical layer


Supported
Electrical Interface
EIA RS-485 No
number of loads No
Optical interface
glass fibre Yes
plastic fibre Yes
Transmission speed
96000 bit/s Yes
19200 bit/s Yes
Link Layer
DFC-bit used Yes
Connectors
connector F-SMA No
connector BFOC/2.5 Yes

Interoperability, application layer


Supported
Selection of standard ASDUs in monitoring direction
ASDU Yes
1 Time-tagged message Yes
2 Time-tagged message with rel. time Yes
3 Measurands I Yes
4 Time-tagged message with rel. time Yes
5 Identification Yes
6 Time synchronization Yes
8 End of general interrogation Yes
9 Measurands II Yes
10 Generic data No
11 Generic identification No
23 List of recorded disturbances Yes
26 Ready for transm. of disturbance data Yes
27 Ready for transm. of a channel Yes
28 Ready for transm of tags Yes
29 Transmission of tags Yes
30 Transmission fo disturbance data Yes
31 End of transmission Yes
Selection of standard ASDUs in control direction
Table continues on next page

839
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Supported
ASDU Yes
6 Time synchronization Yes
7 General interrogation Yes
10 Generic data No
20 General command Yes
21 Generic command No
24 Order for disturbance data transmission Yes
25 Acknowledgement for distance data transmission Yes
Selection of basic application functions
Test mode No
Blocking of monitoring direction Yes
Disturbance data Yes
Private data Yes
Generic services No

17.6.2.2 Communication ports

The serial communication module (SLM) is used for SPA or IEC 60870-5-103 and
LON communication. This module is a mezzanine module, and can be placed on
the Analog/Digital conversion module (ADM). The serial communication module
can have connectors for two plastic fibre cables (snap-in) or two glass fibre cables
(ST, bayonet) or a combination of plastic and glass fibre. Three different types are
available depending on type of fibre.

The incoming optical fibre is connected to the RX receiver input, and the outgoing
optical fibre to the TX transmitter output. When the fibre optic cables are laid out,
pay special attention to the instructions concerning the handling and connection of
the optical fibres. The module is identified with a number on the label on the module.

17.6.3 Function block


I103IEDCMD
BLOCK 19-LEDRS
FUNTYPE 23-GRP1
24-GRP2
25-GRP3
26-GRP4

IEC05000689-2-en.vsd
IEC05000689 V2 EN

I103CMD
BLOCK 16-AR
FUNTYPE 17-DIFF
18-PROT

IEC05000684-2-en.vsd
IEC05000684 V2 EN

840
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

I103USRCMD
BLOCK OUTPUT1
PULSEMOD OUTPUT2
T OUTPUT3
FUNTYPE OUTPUT4
INFNO_1 OUTPUT5
INFNO_2 OUTPUT6
INFNO_3 OUTPUT7
INFNO_4 OUTPUT8
INFNO_5
INFNO_6
INFNO_7
INFNO_8

IEC05000693-2-en.vsd
IEC05000693 V2 EN

I103IED
BLOCK
19_LEDRS
23_GRP1
24_GRP2
25_GRP3
26_GRP4
21_TESTM
FUNTYPE

IEC05000688-2-en.vsd
IEC05000688 V2 EN

I103USRDEF
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
FUNTYPE
INFNO_1
INFNO_2
INFNO_3
INFNO_4
INFNO_5
INFNO_6
INFNO_7
INFNO_8

IEC05000694-2-en.vsd
IEC05000694 V2 EN

I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
FUNTYPE

IEC05000692-2-en.vsd
IEC05000692 V2 EN

I103EF
BLOCK
51_EFFW
52_EFREV
FUNTYPE

IEC05000685-2-en.vsd
IEC05000685 V2 EN

841
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

I103FLTDIS
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
84_STGEN
69_TRL1
70_TRL2
71_TRL3
68_TRGEN
74_FW
75_REV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
76_TRANS
77_RECEV
73_SCL
FLTLOC
ARINPROG
FUNTYPE

IEC05000686-2-en.vsd
IEC05000686 V2 EN

I103FLTSTD
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
84_STGEN
69_TRL1
70_TRL2
71_TRL3
68_TRGEN
74_FW
75_REV
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FUNTYPE

IEC05000687-2-en.vsd
IEC05000687 V2 EN

I103AR
BLOCK
16_ARACT
128_CBON
130_UNSU
FUNTYPE

IEC05000683-2-en.vsd
IEC05000683 V2 EN

842
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

I103MEAS
BLOCK
IL1
IL2
IL3
IN
UL1
UL2
UL3
UL1L2
UN
P
Q
F
FUNTYPE

IEC05000690-2-en.vsd
IEC05000690 V2 EN

I103MEASUSR
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
FUNTYPE
INFNO

IEC05000691-2-en.vsd
IEC05000691 V2 EN

17.6.4 Input and output signals


Table 554: I103IEDCMD Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of commands

Table 555: I103IEDCMD Output signals


Name Type Description
19-LEDRS BOOLEAN Information number 19, reset LEDs
23-GRP1 BOOLEAN Information number 23, activate setting group 1
24-GRP2 BOOLEAN Information number 24, activate setting group 2
25-GRP3 BOOLEAN Information number 25, activate setting group 3
26-GRP4 BOOLEAN Information number 26, activate setting group 4

Table 556: I103CMD Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of commands

843
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Table 557: I103CMD Output signals


Name Type Description
16-AR BOOLEAN Information number 16, block of autorecloser
17-DIFF BOOLEAN Information number 17, block of differential
protection
18-PROT BOOLEAN Information number 18, block of protection

Table 558: I103USRCMD Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of commands

Table 559: I103USRCMD Output signals


Name Type Description
OUTPUT1 BOOLEAN Command output 1
OUTPUT2 BOOLEAN Command output 2
OUTPUT3 BOOLEAN Command output 3
OUTPUT4 BOOLEAN Command output 4
OUTPUT5 BOOLEAN Command output 5
OUTPUT6 BOOLEAN Command output 6
OUTPUT7 BOOLEAN Command output 7
OUTPUT8 BOOLEAN Command output 8

Table 560: I103IED Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
19_LEDRS BOOLEAN 0 Information number 19, reset LEDs
23_GRP1 BOOLEAN 0 Information number 23, setting group 1 is active
24_GRP2 BOOLEAN 0 Information number 24, setting group 2 is active
25_GRP3 BOOLEAN 0 Information number 25, setting group 3 is active
26_GRP4 BOOLEAN 0 Information number 26, setting group 4 is active
21_TESTM BOOLEAN 0 Information number 21, test mode is active

Table 561: I103USRDEF Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
INPUT1 BOOLEAN 0 Binary signal Input 1
INPUT2 BOOLEAN 0 Binary signal input 2
INPUT3 BOOLEAN 0 Binary signal input 3
Table continues on next page

844
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Name Type Default Description


INPUT4 BOOLEAN 0 Binary signal input 4
INPUT5 BOOLEAN 0 Binary signal input 5
INPUT6 BOOLEAN 0 Binary signal input 6
INPUT7 BOOLEAN 0 Binary signal input 7
INPUT8 BOOLEAN 0 Binary signal input 8

Table 562: I103SUPERV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
32_MEASI BOOLEAN 0 Information number 32, measurand supervision of
I
33_MEASU BOOLEAN 0 Information number 33, measurand supervision of
U
37_IBKUP BOOLEAN 0 Information number 37, I high-high back-up
protection
38_VTFF BOOLEAN 0 Information number 38, fuse failure VT
46_GRWA BOOLEAN 0 Information number 46, group warning
47_GRAL BOOLEAN 0 Information number 47, group alarm

Table 563: I103EF Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
51_EFFW BOOLEAN 0 Information number 51, earth-fault forward
52_EFREV BOOLEAN 0 Information number 52, earth-fault reverse

Table 564: I103FLTDIS Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
64_STL1 BOOLEAN 0 Information number 64, start phase L1
65_STL2 BOOLEAN 0 Information number 65, start phase L2
66_STL3 BOOLEAN 0 Information number 66, start phase L3
67_STIN BOOLEAN 0 Information number 67, start residual current IN
84_STGEN BOOLEAN 0 Information number 84, start general
69_TRL1 BOOLEAN 0 Information number 69, trip phase L1
70_TRL2 BOOLEAN 0 Information number 70, trip phase L2
71_TRL3 BOOLEAN 0 Information number 71, trip phase L3
68_TRGEN BOOLEAN 0 Information number 68, trip general
74_FW BOOLEAN 0 Information number 74, forward/line
75_REV BOOLEAN 0 Information number 75, reverse/bus
Table continues on next page

845
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Name Type Default Description


78_ZONE1 BOOLEAN 0 Information number 78, zone 1
79_ZONE2 BOOLEAN 0 Information number 79, zone 2
80_ZONE3 BOOLEAN 0 Information number 79, zone 3
81_ZONE4 BOOLEAN 0 Information number 79, zone 4
82_ZONE5 BOOLEAN 0 Information number 79, zone 5
76_TRANS BOOLEAN 0 Information number 76, signal transmitted
77_RECEV BOOLEAN 0 Information number 77, signal recevied
73_SCL REAL 0 Information number 73, fault location in ohm
FLTLOC BOOLEAN 0 Faultlocator faultlocation valid (LMBRFLO-
CALCMADE)
ARINPROG BOOLEAN 0 Autorecloser in progress (SMBRREC- INPROGR)

Table 565: I103FLTSTD Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
64_STL1 BOOLEAN 0 Information number 64, start phase L1
65_STL2 BOOLEAN 0 Information number 65, start phase L2
66_STL3 BOOLEAN 0 Information number 66, start phase L3
67_STIN BOOLEAN 0 Information number 67, start residual curent IN
84_STGEN BOOLEAN 0 Information number 84, start general
69_TRL1 BOOLEAN 0 Information number 69, trip phase L1
70_TRL2 BOOLEAN 0 Information number 70, trip phase L2
71_TRL3 BOOLEAN 0 Information number 71, trip phase L3
68_TRGEN BOOLEAN 0 Information number 68, trip general
74_FW BOOLEAN 0 Information number 74, forward/line
75_REV BOOLEAN 0 Information number 75, reverse/bus
85_BFP BOOLEAN 0 Information number 85, breaker failure
86_MTRL1 BOOLEAN 0 Information number 86, trip measuring system
phase L1
87_MTRL2 BOOLEAN 0 Information number 87, trip measuring system
phase L2
88_MTRL3 BOOLEAN 0 Information number 88, trip measuring system
phase L3
89_MTRN BOOLEAN 0 Information number 89, trip measuring system
neutral N
90_IOC BOOLEAN 0 Information number 90, over current trip, stage low
91_IOC BOOLEAN 0 Information number 91, over current trip, stage high
92_IEF BOOLEAN 0 Information number 92, earth-fault trip, stage low
93_IEF BOOLEAN 0 Information number 93, earth-fault trip, stage high
ARINPROG BOOLEAN 0 Autorecloser in progress (SMBRREC- INPROGR)

846
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Table 566: I103AR Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
16_ARACT BOOLEAN 0 Information number 16, auto-recloser active
128_CBON BOOLEAN 0 Information number 128, circuit breaker on by auto-
recloser
130_UNSU BOOLEAN 0 Information number 130, unsuccessful reclosing

Table 567: I103MEAS Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of service value reporting
IL1 REAL 0.0 Service value for current phase L1
IL2 REAL 0.0 Service value for current phase L2
IL3 REAL 0.0 Service value for current phase L3
IN REAL 0.0 Service value for residual current IN
UL1 REAL 0.0 Service value for voltage phase L1
UL2 REAL 0.0 Service value for voltage phase L2
UL3 REAL 0.0 Service value for voltage phase L3
UL1L2 REAL 0.0 Service value for voltage phase-phase L1-L2
UN REAL 0.0 Service value for residual voltage UN
P REAL 0.0 Service value for active power
Q REAL 0.0 Service value for reactive power
F REAL 0.0 Service value for system frequency

Table 568: I103MEASUSR Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of service value reporting
INPUT1 REAL 0.0 Service value for measurement on input 1
INPUT2 REAL 0.0 Service value for measurement on input 2
INPUT3 REAL 0.0 Service value for measurement on input 3
INPUT4 REAL 0.0 Service value for measurement on input 4
INPUT5 REAL 0.0 Service value for measurement on input 5
INPUT6 REAL 0.0 Service value for measurement on input 6
INPUT7 REAL 0.0 Service value for measurement on input 7
INPUT8 REAL 0.0 Service value for measurement on input 8
INPUT9 REAL 0.0 Service value for measurement on input 9

847
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

17.6.5 Setting parameters


Table 569: I103IEDCMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 255 Function type (1-255)

Table 570: I103CMD Non group settings (basic)


Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)

Table 571: I103USRCMD Non group settings (basic)


Name Values (Range) Unit Step Default Description
PULSEMOD 0-1 Mode 1 1 Pulse mode 0=Steady, 1=Pulsed
T 0.200 - 60.000 s 0.001 0.400 Pulse length
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)
INFNO_1 1 - 255 InfNo 1 1 Information number for output 1 (1-255)
INFNO_2 1 - 255 InfNo 1 2 Information number for output 2 (1-255)
INFNO_3 1 - 255 InfNo 1 3 Information number for output 3 (1-255)
INFNO_4 1 - 255 InfNo 1 4 Information number for output 4 (1-255)
INFNO_5 1 - 255 InfNo 1 5 Information number for output 5 (1-255)
INFNO_6 1 - 255 InfNo 1 6 Information number for output 6 (1-255)
INFNO_7 1 - 255 InfNo 1 7 Information number for output 7 (1-255)
INFNO_8 1 - 255 InfNo 1 8 Information number for output 8 (1-255)

Table 572: I103IED Non group settings (basic)


Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)

Table 573: I103USRDEF Non group settings (basic)


Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 5 Function type (1-255)
INFNO_1 1 - 255 InfNo 1 1 Information number for binary input 1
(1-255)
INFNO_2 1 - 255 InfNo 1 2 Information number for binary input 2
(1-255)
INFNO_3 1 - 255 InfNo 1 3 Information number for binary input 3
(1-255)
INFNO_4 1 - 255 InfNo 1 4 Information number for binary input 4
(1-255)
Table continues on next page

848
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Name Values (Range) Unit Step Default Description


INFNO_5 1 - 255 InfNo 1 5 Information number for binary input 5
(1-255)
INFNO_6 1 - 255 InfNo 1 6 Information number for binary input 6
(1-255)
INFNO_7 1 - 255 InfNo 1 7 Information number for binary input 7
(1-255)
INFNO_8 1 - 255 InfNo 1 8 Information number for binary input 8
(1-255)

Table 574: I103SUPERV Non group settings (basic)


Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)

Table 575: I103EF Non group settings (basic)


Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 160 Function type (1-255)

Table 576: I103FLTDIS Non group settings (basic)


Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 128 Function type (1-255)

Table 577: I103FLTSTD Non group settings (basic)


Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)

Table 578: I103AR Non group settings (basic)


Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)

Table 579: I103MEAS Non group settings (basic)


Name Values (Range) Unit Step Default Description
RatedIL1 1 - 99999 A 1 3000 Rated current phase L1
RatedIL2 1 - 99999 A 1 3000 Rated current phase L2
RatedIL3 1 - 99999 A 1 3000 Rated current phase L3
RatedIN 1 - 99999 A 1 3000 Rated residual current IN
RatedUL1 0.05 - 2000.00 kV 0.05 230.00 Rated voltage for phase L1
RatedUL2 0.05 - 2000.00 kV 0.05 230.00 Rated voltage for phase L2
RatedUL3 0.05 - 2000.00 kV 0.05 230.00 Rated voltage for phase L3
Table continues on next page

849
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Name Values (Range) Unit Step Default Description


RatedUL1-UL2 0.05 - 2000.00 kV 0.05 400.00 Rated voltage for phase-phase L1-L2
RatedUN 0.05 - 2000.00 kV 0.05 230.00 Rated residual voltage UN
RatedP 0.00 - 2000.00 MW 0.05 1200.00 Rated value for active power
RatedQ 0.00 - 2000.00 MVA 0.05 1200.00 Rated value for reactive power
RatedF 50.0 - 60.0 Hz 10.0 50.0 Rated system frequency
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)

Table 580: I103MEASUSR Non group settings (basic)


Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 25 Function type (1-255)
INFNO 1 - 255 InfNo 1 1 Information number for measurands
(1-255)
RatedMeasur1 0.05 - - 0.05 1000.00 Rated value for measurement on input 1
10000000000.00
RatedMeasur2 0.05 - - 0.05 1000.00 Rated value for measurement on input 2
10000000000.00
RatedMeasur3 0.05 - - 0.05 1000.00 Rated value for measurement on input 3
10000000000.00
RatedMeasur4 0.05 - - 0.05 1000.00 Rated value for measurement on input 4
10000000000.00
RatedMeasur5 0.05 - - 0.05 1000.00 Rated value for measurement on input 5
10000000000.00
RatedMeasur6 0.05 - - 0.05 1000.00 Rated value for measurement on input 6
10000000000.00
RatedMeasur7 0.05 - - 0.05 1000.00 Rated value for measurement on input 7
10000000000.00
RatedMeasur8 0.05 - - 0.05 1000.00 Rated value for measurement on input 8
10000000000.00
RatedMeasur9 0.05 - - 0.05 1000.00 Rated value for measurement on input 9
10000000000.00

17.6.6 Technical data


Table 581: IEC60870-5-103 communication protocol
Function Value
Protocol IEC 60870-5-103
Communication speed 9600, 19200 Bd

850
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

17.7 Horizontal communication via GOOSE for


interlocking GOOSEINTLKRCV

17.7.1 Function block


GOOSEINTLKRCV
BLOCK ^RESREQ
^RESGRANT
^APP1_OP
^APP1_CL
APP1VAL
^APP2_OP
^APP2_CL
APP2VAL
^APP3_OP
^APP3_CL
APP3VAL
^APP4_OP
^APP4_CL
APP4VAL
^APP5_OP
^APP5_CL
APP5VAL
^APP6_OP
^APP6_CL
APP6VAL
^APP7_OP
^APP7_CL
APP7VAL
^APP8_OP
^APP8_CL
APP8VAL
^APP9_OP
^APP9_CL
APP9VAL
^APP10_OP
^APP10_CL
APP10VAL
^APP11_OP
^APP11_CL
APP11VAL
^APP12_OP
^APP12_CL
APP12VAL
^APP13_OP
^APP13_CL
APP13VAL
^APP14_OP
^APP14_CL
APP14VAL
^APP15_OP
^APP15_CL
APP15VAL
COM_VAL

IEC07000048-2-en.vsd
IEC07000048 V2 EN

Figure 433: GOOSEINTLKRCV function block

17.7.2 Input and output signals


Table 582: GOOSEINTLKRCV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of output signals

851
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Table 583: GOOSEINTLKRCV Output signals


Name Type Description
RESREQ BOOLEAN Reservation request
RESGRANT BOOLEAN Reservation granted
APP1_OP BOOLEAN Apparatus 1 position is open
APP1_CL BOOLEAN Apparatus 1 position is closed
APP1VAL BOOLEAN Apparatus 1 position is valid
APP2_OP BOOLEAN Apparatus 2 position is open
APP2_CL BOOLEAN Apparatus 2 position is closed
APP2VAL BOOLEAN Apparatus 2 position is valid
APP3_OP BOOLEAN Apparatus 3 position is open
APP3_CL BOOLEAN Apparatus 3 position is closed
APP3VAL BOOLEAN Apparatus 3 position is valid
APP4_OP BOOLEAN Apparatus 4 position is open
APP4_CL BOOLEAN Apparatus 4 position is closed
APP4VAL BOOLEAN Apparatus 4 position is valid
APP5_OP BOOLEAN Apparatus 5 position is open
APP5_CL BOOLEAN Apparatus 5 position is closed
APP5VAL BOOLEAN Apparatus 5 position is valid
APP6_OP BOOLEAN Apparatus 6 position is open
APP6_CL BOOLEAN Apparatus 6 position is closed
APP6VAL BOOLEAN Apparatus 6 position is valid
APP7_OP BOOLEAN Apparatus 7 position is open
APP7_CL BOOLEAN Apparatus 7 position is closed
APP7VAL BOOLEAN Apparatus 7 position is valid
APP8_OP BOOLEAN Apparatus 8 position is open
APP8_CL BOOLEAN Apparatus 8 position is closed
APP8VAL BOOLEAN Apparatus 8 position is valid
APP9_OP BOOLEAN Apparatus 9 position is open
APP9_CL BOOLEAN Apparatus 9 position is closed
APP9VAL BOOLEAN Apparatus 9 position is valid
APP10_OP BOOLEAN Apparatus 10 position is open
APP10_CL BOOLEAN Apparatus 10 position is closed
APP10VAL BOOLEAN Apparatus 10 position is valid
APP11_OP BOOLEAN Apparatus 11 position is open
APP11_CL BOOLEAN Apparatus 11 position is closed
APP11VAL BOOLEAN Apparatus 11 position is valid
APP12_OP BOOLEAN Apparatus 12 position is open
APP12_CL BOOLEAN Apparatus 12 position is closed
APP12VAL BOOLEAN Apparatus 12 position is valid
Table continues on next page

852
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Name Type Description


APP13_OP BOOLEAN Apparatus 13 position is open
APP13_CL BOOLEAN Apparatus 13 position is closed
APP13VAL BOOLEAN Apparatus 13 position is valid
APP14_OP BOOLEAN Apparatus 14 position is open
APP14_CL BOOLEAN Apparatus 14 position is closed
APP14VAL BOOLEAN Apparatus 14 position is valid
APP15_OP BOOLEAN Apparatus 15 position is open
APP15_CL BOOLEAN Apparatus 15 position is closed
APP15VAL BOOLEAN Apparatus 15 position is valid
COM_VAL BOOLEAN Receive communication status is valid

17.7.3 Setting parameters


Table 584: GOOSEINTLKRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

853
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

17.8 Goose binary receive GOOSEBINRCV

17.8.1 Function block


GOOSEBINRCV
BLOCK ^OUT1
OUT1VAL
^OUT2
OUT2VAL
^OUT3
OUT3VAL
^OUT4
OUT4VAL
^OUT5
OUT5VAL
^OUT6
OUT6VAL
^OUT7
OUT7VAL
^OUT8
OUT8VAL
^OUT9
OUT9VAL
^OUT10
OUT10VAL
^OUT11
OUT11VAL
^OUT12
OUT12VAL
^OUT13
OUT13VAL
^OUT14
OUT14VAL
^OUT15
OUT15VAL
^OUT16
OUT16VAL

IEC07000047-2-en.vsd
IEC07000047 V2 EN

Figure 434: GOOSEBINRCV function block

17.8.2 Input and output signals


Table 585: GOOSEBINRCV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of output signals

Table 586: GOOSEBINRCV Output signals


Name Type Description
OUT1 BOOLEAN Binary output 1
OUT1VAL BOOLEAN Valid data on binary output 1
OUT2 BOOLEAN Binary output 2
OUT2VAL BOOLEAN Valid data on binary output 2
OUT3 BOOLEAN Binary output 3
OUT3VAL BOOLEAN Valid data on binary output 3
Table continues on next page

854
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Name Type Description


OUT4 BOOLEAN Binary output 4
OUT4VAL BOOLEAN Valid data on binary output 4
OUT5 BOOLEAN Binary output 5
OUT5VAL BOOLEAN Valid data on binary output 5
OUT6 BOOLEAN Binary output 6
OUT6VAL BOOLEAN Valid data on binary output 6
OUT7 BOOLEAN Binary output 7
OUT7VAL BOOLEAN Valid data on binary output 7
OUT8 BOOLEAN Binary output 8
OUT8VAL BOOLEAN Valid data on binary output 8
OUT9 BOOLEAN Binary output 9
OUT9VAL BOOLEAN Valid data on binary output 9
OUT10 BOOLEAN Binary output 10
OUT10VAL BOOLEAN Valid data on binary output 10
OUT11 BOOLEAN Binary output 11
OUT11VAL BOOLEAN Valid data on binary output 11
OUT12 BOOLEAN Binary output 12
OUT12VAL BOOLEAN Valid data on binary output 12
OUT13 BOOLEAN Binary output 13
OUT13VAL BOOLEAN Valid data on binary output 13
OUT14 BOOLEAN Binary output 14
OUT14VAL BOOLEAN Valid data on binary output 14
OUT15 BOOLEAN Binary output 15
OUT15VAL BOOLEAN Valid data on binary output 15
OUT16 BOOLEAN Binary output 16
OUT16VAL BOOLEAN Valid data on binary output 16

17.8.3 Setting parameters


Table 587: GOOSEBINRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

17.9 Multiple command and transmit MULTICMDRCV,


MULTICMDSND

855
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Multiple command and transmit MULTICMDRCV - -
Multiple command and transmit MULTICMDSND - -

17.9.1 Introduction
The IED can be provided with a function to send and receive signals to and from
other IEDs via the interbay bus. The send and receive function blocks has 16 outputs/
inputs that can be used, together with the configuration logic circuits, for control
purposes within the IED or via binary outputs. When it is used to communicate
with other IEDs, these IEDs have a corresponding Multiple transmit function block
with 16 outputs to send the information received by the command block.

17.9.2 Principle of operation


Two multiple transmit function blocks MULTICMDSND:1 and MULTICMDSND:
2 and 8 slow multiple transmit function blocks MULTICMDSND:3 to
MULTICMDSND:10 are available in the IED.

Sixteen signals can be connected and they will then be sent to the multiple
command block in the other IED. The connections are set with the LON Network
Tool (LNT).

Twelve multiple command function blocks MULTICMDRCV:1 to


MULTICMDRCV:12 with fast execution time and 48 multiple command function
blocks MULTICMDRCV:13 to MULTICMDRCV:60 with slower execution time
are available in the IED.

Multiple command function block MULTICMDRCV has 16 outputs combined in


one block, which can be controlled from other IEDs.

The output signals, here OUTPUT1 to OUTPUT16, are then available for
configuration to built-in functions or via the configuration logic circuits to the
binary outputs of the IED.

MULTICMDRCV also has a supervision function, which sets the output VALID to
0 if the block does not receive data within set maximum time.

17.9.3 Design

17.9.3.1 General

The output signals can be of the types Off, Steady, or Pulse. The setting is done on
the MODE settings, common for the whole block, from PCM600.

856
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

• 0 = Off sets all outputs to 0, independent of the values sent from the station
level, that is, the operator station or remote-control gateway.
• 1 = Steady sets the outputs to a steady signal 0 or 1, depending on the values
sent from the station level.
• 2 = Pulse gives a pulse with one execution cycle duration, if a value sent from
the station level is changed from 0 to 1. That means that the configured logic
connected to the command function blocks may not have a cycle time longer
than the execution cycle time for the command function block.

17.9.4 Function block


MULTICMDRCV
BLOCK ERROR
NEWDATA
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16
VALID

IEC06000007-2-en.vsd
IEC06000007 V2 EN

Figure 435: MULTICMDRCV function block

MULTICMDSND
BLOCK ERROR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16

IEC06000008-2-en.vsd
IEC06000008 V2 EN

Figure 436: MULTICMDSND function block

857
Technical reference manual
Section 17 1MRK505183-UEN C
Station communication

17.9.5 Input and output signals


Table 588: MULTICMDRCV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function

Table 589: MULTICMDSND Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Input 1
INPUT2 BOOLEAN 0 Input 2
INPUT3 BOOLEAN 0 Input 3
INPUT4 BOOLEAN 0 Input 4
INPUT5 BOOLEAN 0 Input 5
INPUT6 BOOLEAN 0 Input 6
INPUT7 BOOLEAN 0 Input 7
INPUT8 BOOLEAN 0 Input 8
INPUT9 BOOLEAN 0 Input 9
INPUT10 BOOLEAN 0 Input 10
INPUT11 BOOLEAN 0 Input 11
INPUT12 BOOLEAN 0 Input 12
INPUT13 BOOLEAN 0 Input 13
INPUT14 BOOLEAN 0 Input 14
INPUT15 BOOLEAN 0 Input 15
INPUT16 BOOLEAN 0 Input 16

Table 590: MULTICMDRCV Output signals


Name Type Description
ERROR BOOLEAN MultiReceive error
NEWDATA BOOLEAN New data is received
OUTPUT1 BOOLEAN Output 1
OUTPUT2 BOOLEAN Output 2
OUTPUT3 BOOLEAN Output 3
OUTPUT4 BOOLEAN Output 4
OUTPUT5 BOOLEAN Output 5
OUTPUT6 BOOLEAN Output 6
OUTPUT7 BOOLEAN Output 7
OUTPUT8 BOOLEAN Output 8
OUTPUT9 BOOLEAN Output 9
Table continues on next page

858
Technical reference manual
1MRK505183-UEN C Section 17
Station communication

Name Type Description


OUTPUT10 BOOLEAN Output 10
OUTPUT11 BOOLEAN Output 11
OUTPUT12 BOOLEAN Output 12
OUTPUT13 BOOLEAN Output 13
OUTPUT14 BOOLEAN Output 14
OUTPUT15 BOOLEAN Output 15
OUTPUT16 BOOLEAN Output 16
VALID BOOLEAN Output data is valid

Table 591: MULTICMDSND Output signals


Name Type Description
ERROR BOOLEAN MultiSend error

17.9.6 Setting parameters


Table 592: MULTICMDRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
tMaxCycleTime 0.050 - 200.000 s 0.001 11.000 Maximum cycle time between receptions
of input data
tMinCycleTime 0.000 - 200.000 s 0.001 0.000 Minimum cycle time between receptions
of input data
Mode Steady - - Steady Mode for output signals
Pulsed
tPulseTime 0.000 - 60.000 s 0.001 0.200 Pulse length for multi command outputs

Table 593: MULTICMDSND Non group settings (basic)


Name Values (Range) Unit Step Default Description
tMaxCycleTime 0.000 - 200.000 s 0.001 5.000 Maximum time interval between
transmission of output data
tMinCycleTime 0.000 - 200.000 s 0.001 0.000 Minimum time interval between
transmission of output data

859
Technical reference manual
860
1MRK505183-UEN C Section 18
Remote communication

Section 18 Remote communication

About this chapter


This chapter describes the Binary signal transfer function and associated hardware
functionality. The way the functions work, their setting parameters, function
blocks, input and output signals, and technical data are included for each function.

18.1 Binary signal transfer

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Binary signal transfer BinSignReceive - -
Binary signal transfer BinSignTransm - -

18.1.1 Introduction
The remote end data communication is used either for the transmission of current
values together with maximum 8 binary signals in the line differential protection,
or for transmission of only binary signals, up to 192 signals, in the other 670 series
IEDs. The binary signals are freely configurable and can, thus, be used for any
purpose, for example, communication scheme related signals, transfer trip and/or
other binary signals between IEDs.

Communication between two IEDs requires that each IED is equipped with an
LDCM (Line Data Communication Module). The LDCMs are then interfaces to a
64 kbit/s communication channel for duplex communication between the IEDs.

The IED can be equipped with up to four short range, medium range or long range
LDCM.

18.1.2 Principle of operation


The communication is made on standard ITU (CCITT) PCM digital 64 kbit/s
channels. It is a two-way communication where telegrams are sent every 5 ms
(same in 50 Hz and 60 Hz), exchanging information between two IEDs. The format
used is C37.94 and one telegram consists of start and stop flags, address, data to be
transmitted, Cyclic Redundancy Check (CRC) and Yellow bit (which is associated
with C37.94).

861
Technical reference manual
Section 18 1MRK505183-UEN C
Remote communication

Start Stop
Information CRC
flag flag

8 bits n x 16 bits 16 bits 8 bits


en01000134.vsd

IEC01000134 V1 EN

Figure 437: Data message structure

The start and stop flags are the 0111 1110 sequence (7E hexadecimal), defined in
the HDLC standard. The CRC is designed according to the standard CRC16
definition. The optional address field in the HDLC frame is not used instead a
separate addressing is included in the data field.

The address field is used for checking that the received message originates from
the correct equipment. There is always a risk that multiplexers occasionally mix the
messages up. Each terminal in the system is given a number. The terminal is then
programmed to accept messages from a specific terminal number. If the CRC
function detects a faulty message, the message is thrown away and not used in the
evaluation.

When the communication is used for line differential purpose, the transmitted data
consists of three currents, clock information, trip-, block- and alarm-signals and
eight binary signals which can be used for any purpose. The three currents are
represented as sampled values.

When the communication is used exclusively for binary signals, the full data
capacity of the communication channel is used for the binary signal purpose which
gives the capacity of 192 signals.

862
Technical reference manual
1MRK505183-UEN C Section 18
Remote communication

18.1.3 Function block


LDCMRecBinStat1
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
REMCOMF
LOWLEVEL

IEC07000043-2-en.vsd

IEC07000043 V2 EN

LDCMRecBinStat2
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
REMGPSER
SUBSTITU
LOWLEVEL

IEC07000044-2-en.vsd
IEC07000044 V2 EN

Figure 438: LDCMRecBinStat function blocks

LDCMRecBinStat3
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
REMGPSER
SUBSTITU
LOWLEVEL

IEC05000451-2-en.vsd
IEC05000451 V2 EN

Figure 439: LDCMRecBinStat function block

18.1.4 Input and output signals


Table 594: LDCMRecBinStat1 Output signals
Name Type Description
COMFAIL BOOLEAN Detected error in the differential communication
YBIT BOOLEAN Detected error in remote end with incoming
message
NOCARR BOOLEAN No carrier is detected in the incoming message
Table continues on next page

863
Technical reference manual
Section 18 1MRK505183-UEN C
Remote communication

Name Type Description


NOMESS BOOLEAN No start and stop flags identified for the incoming
message
ADDRERR BOOLEAN Incoming message from a wrong terminal
LNGTHERR BOOLEAN Wrong length of the incoming message
CRCERROR BOOLEAN Identified error by CRC check in incoming message
REMCOMF BOOLEAN Remote terminal indicates problem with received
message
LOWLEVEL BOOLEAN Low signal level on the receive link

Table 595: LDCMRecBinStat2 Output signals


Name Type Description
COMFAIL BOOLEAN Detected error in the differential communication
YBIT BOOLEAN Detected error in remote end with incoming
message
NOCARR BOOLEAN No carrier is detected in the incoming message
NOMESS BOOLEAN No start and stop flags identified for the incoming
message
ADDRERR BOOLEAN Incoming message from a wrong terminal
LNGTHERR BOOLEAN Wrong length of the incoming message
CRCERROR BOOLEAN Identified error by CRC check in incoming message
TRDELERR BOOLEAN Transmission time is longer than permitted
SYNCERR BOOLEAN Indicates when echo synchronication is used
REMCOMF BOOLEAN Remote terminal indicates problem with received
message
REMGPSER BOOLEAN Remote terminal indicates problem with GPS
synchronization
SUBSTITU BOOLEAN Link error, values are substituted
LOWLEVEL BOOLEAN Low signal level on the receive link

Table 596: LDCMRecBinStat3 Output signals


Name Type Description
COMFAIL BOOLEAN Detected error in the differential communication
YBIT BOOLEAN Detected error in remote end with incoming
message
NOCARR BOOLEAN No carrier is detected in the incoming message
NOMESS BOOLEAN No start and stop flags identified for the incoming
message
ADDRERR BOOLEAN Incoming message from a wrong terminal
LNGTHERR BOOLEAN Wrong length of the incoming message
CRCERROR BOOLEAN Identified error by CRC check in incoming message
TRDELERR BOOLEAN Transmission time is longer than permitted
Table continues on next page

864
Technical reference manual
1MRK505183-UEN C Section 18
Remote communication

Name Type Description


SYNCERR BOOLEAN Indicates when echo synchronication is used
REMCOMF BOOLEAN Remote terminal indicates problem with received
message
REMGPSER BOOLEAN Remote terminal indicates problem with GPS
synchronization
SUBSTITU BOOLEAN Link error, values are substituted
LOWLEVEL BOOLEAN Low signal level on the receive link

18.1.5 Setting parameters


Table 597: LDCMRecBinStat1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
ChannelMode Off - - On Channel mode of LDCM, 0=OFF, 1=ON,
On 2=OutOfService
OutOfService
TerminalNo 0 - 255 - 1 0 Terminal number used for line differential
communication
RemoteTermNo 0 - 255 - 1 0 Terminal number on remote terminal
CommSync Slave - - Slave Com Synchronization mode of LDCM,
Master 0=Slave, 1=Master
OptoPower LowPower - - LowPower Transmission power for LDCM, 0=Low,
HighPower 1=High
ComFailAlrmDel 5 - 500 ms 5 100 Time delay before communication error
signal is activated
ComFailResDel 5 - 500 ms 5 100 Reset delay before communication error
signal is reset
InvertPolX21 Off - - Off Invert polarization for X21 communication
On

Table 598: LDCMRecBinStat2 Non group settings (basic)


Name Values (Range) Unit Step Default Description
ChannelMode Off - - On Channel mode of LDCM, 0=OFF, 1=ON,
On 2=OutOfService
OutOfService
TerminalNo 0 - 255 - 1 0 Terminal number used for line differential
communication
RemoteTermNo 0 - 255 - 1 0 Terminal number on remote terminal
DiffSync Echo - - Echo Diff Synchronization mode of LDCM,
GPS 0=ECHO, 1=GPS
GPSSyncErr Block - - Block Operation mode when GPS
Echo synchroniation signal is lost
CommSync Slave - - Slave Com Synchronization mode of LDCM,
Master 0=Slave, 1=Master
OptoPower LowPower - - LowPower Transmission power for LDCM, 0=Low,
HighPower 1=High
Table continues on next page

865
Technical reference manual
Section 18 1MRK505183-UEN C
Remote communication

Name Values (Range) Unit Step Default Description


TransmCurr CT-GRP1 - - CT-GRP1 Summation mode for transmitted current
CT-GRP2 values
CT-SUM
CT-DIFF1
CT-DIFF2
ComFailAlrmDel 5 - 500 ms 5 100 Time delay before communication error
signal is activated
ComFailResDel 5 - 500 ms 5 100 Reset delay before communication error
signal is reset
RedChSwTime 5 - 500 ms 5 5 Time delay before switching in
redundant channel
RedChRturnTime 5 - 500 ms 5 100 Time delay before switching back from
redundant channel
AsymDelay -20.00 - 20.00 ms 0.01 0.00 Asymmetric delay when communication
use echo synch.
MaxTransmDelay 0 - 40 ms 1 20 Max allowed transmission delay
CompRange 0-10kA - - 0-25kA Compression range
0-25kA
0-50kA
0-150kA
MaxtDiffLevel 200 - 2000 us 1 600 Maximum time diff for ECHO back-up
DeadbandtDiff 200 - 1000 us 1 300 Deadband for t Diff
InvertPolX21 Off - - Off Invert polarization for X21 communication
On

Table 599: LDCMRecBinStat3 Non group settings (basic)


Name Values (Range) Unit Step Default Description
ChannelMode Off - - On Channel mode of LDCM, 0=OFF, 1=ON,
On 2=OutOfService
OutOfService
TerminalNo 0 - 255 - 1 0 Terminal number used for line differential
communication
RemoteTermNo 0 - 255 - 1 0 Terminal number on remote terminal
DiffSync Echo - - Echo Diff Synchronization mode of LDCM,
GPS 0=ECHO, 1=GPS
GPSSyncErr Block - - Block Operation mode when GPS
Echo synchroniation signal is lost
CommSync Slave - - Slave Com Synchronization mode of LDCM,
Master 0=Slave, 1=Master
OptoPower LowPower - - LowPower Transmission power for LDCM, 0=Low,
HighPower 1=High
TransmCurr CT-GRP1 - - CT-GRP1 Summation mode for transmitted current
CT-GRP2 values
CT-SUM
CT-DIFF1
CT-DIFF2
RedundantChannel
ComFailAlrmDel 5 - 500 ms 5 100 Time delay before communication error
signal is activated
Table continues on next page

866
Technical reference manual
1MRK505183-UEN C Section 18
Remote communication

Name Values (Range) Unit Step Default Description


ComFailResDel 5 - 500 ms 5 100 Reset delay before communication error
signal is reset
RedChSwTime 5 - 500 ms 5 5 Time delay before switching in
redundant channel
RedChRturnTime 5 - 500 ms 5 100 Time delay before switching back from
redundant channel
AsymDelay -20.00 - 20.00 ms 0.01 0.00 Asymmetric delay when communication
use echo synch.
MaxTransmDelay 0 - 40 ms 1 20 Max allowed transmission delay
CompRange 0-10kA - - 0-25kA Compression range
0-25kA
0-50kA
0-150kA
MaxtDiffLevel 200 - 2000 us 1 600 Maximum time diff for ECHO back-up
DeadbandtDiff 200 - 1000 us 1 300 Deadband for t Diff
InvertPolX21 Off - - Off Invert polarization for X21 communication
On

18.2 Transmission of analog data from LDCM


LDCMTransmit

18.2.1 Function block


LDCMTRN
^CT1L1
^CT1L2
^CT1L3
^CT1N
^CT2L1
^CT2L2
^CT2L3
^CT2N

IEC10000017-1-en.vsd
IEC10000017 V1 EN

Figure 440: LDCMTransmit function block

The function blocks are not represented in the Application


Configuration tool except for the LDCMTRN function block that is
visible in ACT. The signals appear only in the Signal Matrix tool
when a LDCM is included in the configuration with the function
selector tool.

867
Technical reference manual
Section 18 1MRK505183-UEN C
Remote communication

18.2.2 Input and output signals


Table 600: LDCMTRN Input signals
Name Type Default Description
CT1L1 STRING 0 Input to be used for transmit CT-group1 line L1 to
remote end
CT1L2 STRING 0 Input to be used for transmit CT-group1 line L2 to
remote end
CT1L3 STRING 0 Input to be used for transmit CT-group1 line L3 to
remote end
CT1N STRING 0 Input to be used for transmit CT-group1 neutral N
to remote end
CT2L1 STRING 0 Input to be used for transmit CT-group2 line L1 to
remote end
CT2L2 STRING 0 Input to be used for transmit CT-group2 line L2 to
remote end
CT2L3 STRING 0 Input to be used for transmit CT-group2 line L3 to
remote end
CT2N STRING 0 Input to be used for transmit CT-group2 neutral N
to remote end

868
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

Section 19 Hardware

About this chapter


This chapter includes descriptions of the different hardware modules. It includes
diagrams from different elevations indicating the location of connection terminals
and modules.

19.1 Overview

19.1.1 Variants of case and local HMI display size

xx04000458.eps
IEC04000458 V1 EN

Figure 441: 1/2 19” case with medium local HMI display.

869
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

xx04000459.eps
IEC04000459 V1 EN

Figure 442: 1/2 19” case with small local HMI display.

IEC05000762 V1 EN

Figure 443: 3/4 19” case with medium local HMI display.

xx05000763.eps
IEC05000763 V1 EN

Figure 444: 3/4 19” case with small local HMI display.

870
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

xx04000460.eps
IEC04000460 V1 EN

Figure 445: 1/1 19” case with medium local HMI display.

xx04000461.eps
IEC04000461 V1 EN

Figure 446: 1/1 19” case with small local HMI display.

871
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

19.1.2 Case from the rear side


Table 601: Designations for 1/2 x 19” casing with 1 TRM slot

Module Rear Positions


PSM X11
BIM, BOM, SOM or IOM X31 and X32 etc. to X51
and X52
BIM, BOM, SOM, IOM or X51, X52
GSM
SLM X301:A, B, C, D
IRIG-B 1) X302
IEC08000471 BG V1 EN
OEM X311:A, B, C, D
RS485 or LDCM 2) 3) X312
LDCM 2) X313
TRM X401

1) IRIG-B installation, when included in seat P30:2


2) LDCM installation sequence: P31:2 or P31:3
3) RS485 installation, when included in seat P31:2
Note!
1 One LDCM can be included depending of availability of
IRIG-B respective RS485 modules.

872
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

Table 602: Designations for 3/4 x 19” casing with 1 TRM slot

Module Rear Positions


PSM X11
BIM, BOM, SOM, IOM or X31 and X32 etc. to
MIM X101 and X102
BIM, BOM, SOM, IOM, X101, X102
MIM or GSM
SLM X301:A, B, C, D
IRIG-B or LDCM 1) 2) X302
IEC08000472 BG V1 EN
LDCM 2) X303
OEM 4) X311:A, B, C, D
RS485 or LDCM 2) 3) X312
LDCM 2) X313
TRM X401

1) IRIG-B installation, when included in seat P30:2


2) LDCM installation sequence: P31:2, P31:3,
P30:2 and P30:3
3) RS485 installation, when included in seat P31:2
or P31:3
4) OEM X311:A, B (IEC 61850-8-1). X311:C, D
(IEC 61850-8-1 or IEC 61850-9-2 LE)
Note!
2-4 LDCM can be included depending of availability
of IRIG-B respective RS485 modules.

873
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

Table 603: Designations for 3/4 x 19” casing with 2 TRM slot

Module Rear Positions


PSM X11
BIM, BOM, SOM, IOM or X31 and X32 etc. to X71 and
MIM X72
BIM, BOM, SOM, IOM, X71, X72
MIM or GSM
SLM X301:A, B, C, D
IRIG-B or LDCM 1,2) X302
IEC08000473 BG V1 EN
LDCM 2) X303
OEM 4) X311:A, B, C, D
RS485 or LDCM 2) 3) X312
LDCM 2) X313
LDCM 2) X322
LDCM 2) X323
TRM 1 X401
TRM 2 X411

1) IRIG-B installation, when included in seat P30:2


2) LDCM installation sequence: P31:2, P31:3, P32:2,
P32:3, P30:2 and P30:3
3) RS485 installation, when included in seat P31:2, P31:3,
P32:2 or P32:3
4) OEM X311:A, B (IEC 61850-8-1). (X311:C, D IEC
61850-8-1 or IEC 61850-9-2 LE)
Note!
2-4 LDCM can be included depending of availability of IRIG-
B respective RS485 modules.
When IRIG-B, RS485 and 4 pc of LDCM are in use, needs
a second ADM.

874
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

Table 604: Designations for 1/1 x 19” casing with 1 TRM slot

Module Rear Positions


PSM X11
BIM, BOM, X31 and X32 etc. to X161
SOM, IOM or and X162
MIM
BIM, BOM, X161 and X162
SOM, IOM, MIM
or GSM

IEC08000474 BG V1 EN
SLM X301:A, B, C, D
IRIG-B X302

LDCM 1) X312, X313, X302 and X303

OEM 2) X311:A, B, C, D

RS485 X312, X313


TRM X401

Note!
1) 2-4 LDCM can be included. First LDCM
always in position X313, second LDCM always in
position X303. LDCM can also be in position
X302 and X312 if IRIG-B respective RS485
modules are not included.
2) OEM X311:A, B (IEC 61850-8-1). OEM
X311:C, D (IEC 61850-8-1)(IEC 61850-9-2LE)

875
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

Table 605: Designations for 1/1 x 19” casing with 2 TRM slots

Module Rear Positions


PSM X11
BIM, BOM, X31 and X32 etc. to X131
SOM, IOM or and X132
MIM
BIM, BOM, X131, X132
SOM, IOM, MIM
or GSM

IEC08000475 BG V1 EN
SLM X301:A, B, C, D
IRIG-B or LDCM X302
1,2)
LDCM 2) X303
OEM 4) X311:A, B, C, D
RS485 or LDCM X312
2) 3)
LDCM 2) X313
LDCM 2) X322
LDCM 2) X323
TRM 1 X401
TRM 2 X411

1) IRIG-B installation, when included in seat P30:2


2) LDCM installation sequence: P31:2, P31:3,
P32:2, P32:3, P30:2 and P30:3
3) RS485 installation, when included in seat
P31:2, P31:3, P32:2 or P32:4
4) OEM X311:A, B (IEC 61850-8-1). OEM
X311:C, D (IEC 61850-9-2 or IEC 61850-9-2 LE)
Note!
2-4 LDCM can be included depending of
availability of IRIG-B respective RS485 modules.
When IRIG-B, RS485 and 4 pc of LDCM are in
use, needs a second ADM.

876
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.2 Hardware modules

19.2.1 Overview
Table 606: Basic modules
Module Description
Combined backplane module (CBM) A backplane PCB that carries all internal signals
between modules in an IED. Only the TRM (when
included) is not connected directly to this board.
Universal backplane module (UBM) A backplane PCB that forms part of the IED
backplane with connectors for TRM (when
included), ADM etc.
Power supply module (PSM) Including a regulated DC/DC converter that
supplies auxiliary voltage to all static circuits.

• An internal fail alarm output is available.

Numerical module (NUM) Module for overall application control. All


information is processed or passed through this
module, such as configuration, settings and
communication.
Local Human machine interface (LHMI) The module consists of LED:s, an LCD, a push
button keyboard and an ethernet connector used
to connect a PC to the IED.
Transformer input module (TRM) Transformer module that galvanically separates
the internal circuits from the VT and CT circuits. It
has 12 analog inputs.
Analog digital conversion module (ADM) Slot mounted PCB with A/D conversion.

Table 607: Application specific modules


Module Description
Binary input module (BIM) Module with 16 optically isolated binary inputs
Binary output module (BOM) Module with 24 single outputs or 12 double-pole
command outputs including supervision function
Binary I/O module (IOM) Module with 8 optically isolated binary inputs, 10
outputs and 2 fast signalling outputs.
Line data communication modules (LDCM), Modules used for digital communication to remote
short range, medium range, long range, X21 terminal.
Serial SPA/LON/IEC 60870-5-103 Used for SPA/LON/IEC 60870–5–103
communication modules (SLM) communication
Optical ethernet module (OEM) PMC board for IEC 61850 based communication.
mA input module (MIM) Analog input module with 6 independent,
galvanically separated channels.
Table continues on next page

877
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

Module Description
GPS time synchronization module (GSM) Used to provide the IED with GPS time
synchronization.
Static output module (SOM) Module with 6 fast static outputs and 6 change
over output relays.
IRIG-B Time synchronization module (IRIG-B) Module with 2 inputs. One is used for handling
both pulse-width modulated signals and
amplitude modulated signals and one is used for
optical input type ST for PPS time synchronization.

19.2.2 Combined backplane module (CBM)

19.2.2.1 Introduction

The combined backplane module (CBM) carries signals between modules in an IED.

19.2.2.2 Functionality

The Compact PCI makes 3.3V or 5V signaling in the backplane possible. The
CBM backplane and connected modules are 5V PCI-compatible.

Some pins on the Compact PCI connector are connected to the CAN bus, to be able
to communicate with CAN based modules.

If a modules self test discovers an error it informs other modules using the Internal
Fail signal IRF.

19.2.2.3 Design

There are two basic versions of the CBM:

• with 3 Compact PCI connectors and a number of euro connectors depending


on the IED case size. One Compact PCI connector is used by NUM and two
are used by other PCI modules, for example two ADMs in IEDs with two
TRMs. See figure 448
• with 2 Compact PCI connectors and a number of euro connectors depending
on the IED case size. One Compact PCI connector is used by NUM and one is
used by for example an ADM in IEDs with one TRM. See figure 447

Each PCI connector consists of 2 compact PCI receptacles. The euro connectors
are connected to the CAN bus and used for I/O modules and power supply.

878
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

1 2
en05000516.vsd
IEC05000516 V1 EN

Figure 447: CBM for 1 TRM.

Pos Description
1 CAN slots
2 CPCI slots

1 2

en05000755.vsd
IEC05000755 V1 EN

Figure 448: CBM for 2 TRM.

Pos Description
1 CAN slots
2 CPCI slots

879
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

en05000756.vsd
IEC05000756 V1 EN

Figure 449: CBM position, rear view.

Pos Description
1 CBM

19.2.3 Universal backplane module (UBM)

19.2.3.1 Introduction

The Universal Backplane Module (UBM) is part of the IED backplane and is
mounted above the CBM. It connects the Transformer input module (TRM) to the
Analog digital conversion module (ADM) and the Numerical module (NUM).

19.2.3.2 Functionality

The Universal Backplane Module connects the CT and VT analog signals from the
transformer input module to the analog digital converter module. The Numerical
processing module (NUM) is also connected to the UBM. The ethernet contact on
the front panel as well as the internal ethernet contacts are connected to the UBM
which provides the signal path to the NUM board.

19.2.3.3 Design

It connects the Transformer input module (TRM) to the Analog digital conversion
module (ADM) and the Numerical module (NUM).

The UBM exists in 2 versions.

880
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

• for IEDs with two TRM and two ADM. It has four 48 pin euro connectors and
one 96 pin euro connector, see figure 451
• for IEDs with one TRM and one ADM. It has two 48 pin euro connectors and
one 96 pin euro connector, see figure 452.

The 96 pin euro connector is used to connect the NUM board to the backplane. The
48 pin connectors are used to connect the TRM and ADM.

TRM ADM
NUM
AD Data

X1 X2
X3 X4

RS485

X10 X10
Front Ethernet

LHMI connection
port
Ethernet X5

en05000489.vsd
IEC05000489 V1 EN

Figure 450: UBM block diagram.

en05000757.vsd
IEC05000757 V1 EN

Figure 451: UBM for 1 TRM.

881
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

en05000758.vsd
IEC05000758 V1 EN

Figure 452: UBM for 2 TRM.

en05000759.vsd
IEC05000759 V1 EN

Figure 453: UBM position, rear view.

Pos Description
1 UBM

19.2.4 Numeric processing module (NUM)

19.2.4.1 Introduction

The Numeric processing module (NUM), is a CPU-module that handles all


protection functions and logic.

882
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

For communication with high speed modules, e.g. analog input modules and high
speed serial interfaces, the NUM is equipped with a Compact PCI bus. The NUM
is the compact PCI system card i.e. it controls bus mastering, clock distribution and
receives interrupts.

19.2.4.2 Functionality

The NUM, Numeric processing module is a high performance, standard off-the-


shelf compact-PCI CPU module. It is 6U high and occupies one slot. Contact with
the backplane is via two compact PCI connectors and an euro connector.

The NUM has one PMC slot (32-bit IEEE P1386.1 compliant) and two PC-MIP
slots onto which mezzanine cards such as SLM or LDCM can be mounted.

To reduce bus loading of the compact PCI bus in the backplane the NUM has one
internal PCI bus for internal resources and the PMC/PC-MIP slots and external PCI
accesses through the backplane are buffered in a PCI/PCI bridge.

The application code and configuration data are stored in flash memory using a
flash file system.

The NUM is equipped with a real time clock. It uses a capacitor for power backup
of the real time clock.

No forced cooling is used on this standard module because of the low power
dissipation.

883
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

19.2.4.3 Block diagram

Compact
Flash Logic

PMC
connector
PC-MIP

connector
UBM
Memory Ethernet

North
bridge

Backplane
PCI-PCI-

connector
bridge

CPU

en04000473.vsd
IEC04000473 V1 EN

Figure 454: Numeric processing module block diagram

19.2.5 Power supply module (PSM)

19.2.5.1 Introduction

The power supply module is used to provide the correct internal voltages and full
isolation between the terminal and the battery system. An internal fail alarm output
is available.

19.2.5.2 Design

There are two types of the power supply module. They are designed for different
DC input voltage ranges see table 608. The power supply module contains a built-

884
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

in, self-regulated DC/DC converter that provides full isolation between the
terminal and the external battery system.

Block diagram

Input connector
Power
Filter supply

Backplane connector
Supervision

99000516.vsd
IEC99000516 V1 EN

Figure 455: PSM Block diagram.

19.2.5.3 Technical data


Table 608: PSM - Power supply module
Quantity Rated value Nominal range
Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL ± 20%
EL = (90 - 250) V EL ± 20%
Power consumption 50 W typically -
Auxiliary DC power in-rush < 5 A during 0.1 s -

19.2.6 Local human-machine interface (Local HMI)


Refer to section "Local HMI" for information.

19.2.7 Transformer input module (TRM)

885
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

19.2.7.1 Introduction

The transformer input module is used to galvanically separate and transform the
secondary currents and voltages generated by the measuring transformers. The
module has twelve inputs in different combinations of currents and voltage inputs.

Alternative connectors of Ring lug or Compression type can be ordered.

19.2.7.2 Design

The transformer module has 12 input transformers. There are several versions of
the module, each with a different combination of voltage and current input
transformers.

Basic versions:

• 6 current channels and 6 voltage channels


• 7 current channels and 5 voltage channels
• 9 current channels and 3 voltage channels
• 12 current channels
• 6 current channels

The rated values of the current inputs are selected at order.

The TRM is connected to the ADM and NUM via the UBM.

For configuration of the input and output signals, refer to section "Signal matrix
for analog inputs SMAI".

19.2.7.3 Technical data


Table 609: TRM - Energizing quantities, rated values and limits for protection transformer
modules
Quantity Rated value Nominal range
Current Ir = 1 or 5 A (0.2-40) × Ir

Operative range (0-100) x Ir

Permissive overload 4 × Ir cont.


100 × Ir for 1 s *)

Burden < 150 mVA at Ir = 5 A


< 20 mVA at Ir = 1 A

Ac voltage Ur = 110 V 0.5–288 V

Operative range (0–340) V


Permissive overload 420 V cont.
450 V 10 s
Burden < 20 mVA at 110 V
Frequency fr = 50/60 Hz ± 5%
*) max. 350 A for 1 s when COMBITEST test switch is included.

886
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.2.8 Analog digital conversion module, with time


synchronization (ADM)

19.2.8.1 Introduction

The Analog/Digital module has twelve analog inputs, 2 PC-MIP slots and 1 PMC
slot. The PC-MIP slot is used for PC-MIP cards and the PMC slot for PMC cards
according to table 610. The OEM card should always be mounted on the ADM
board. The UBM connects the ADM to the transformer input module (TRM).

Table 610: PC-MIP cards and PMC cards


PC-MIP cards PMC cards
LDCM SLM
LR-LDCM OEM 1 ch
MR-LDCM OEM 2 ch
X21-LDCM
IRIG-B
RS485

19.2.8.2 Design

The Analog digital conversion module input signals are voltage and current from
the transformer module. Shunts are used to adapt the current signals to the
electronic voltage level. To gain dynamic range for the current inputs, two shunts
with separate A\D channels are used for each input current. In this way a 20 bit
dynamic range is obtained with a 16 bit A\D converter.

Input signals are sampled with a sampling freqency of 5 kHz at 50 Hz system


frequency and 6 kHz at 60 Hz system frequency.

The A\D converted signals goes through a filter with a cut off frequency of 500 Hz
and are reported to the numerical module (NUM) with 1 kHz at 50 Hz system
frequency and 1,2 kHz at 60 Hz system frequency.

887
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

Channel 1
AD1 Channel 2
Channel 3
Channel 4
AD2
Channel 5
1.2v Channel 6
AD3 Channel 7
Channel 8
Channel 9
AD4 Channel 10
Channel 11
Channel 12

PMC

level shift

PC-MIP
2.5v

PCI to PCI

PC-MIP

en05000474.vsd
IEC05000474 V1 EN

Figure 456: The ADM layout

888
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.2.9 Binary input module (BIM)

19.2.9.1 Introduction

The binary input module has 16 optically isolated inputs and is available in two
versions, one standard and one with enhanced pulse counting capabilities on the
inputs to be used with the pulse counter function. The binary inputs are freely
programmable and can be used for the input of logical signals to any of the
functions. They can also be included in the disturbance recording and event-
recording functions. This enables extensive monitoring and evaluation of operation
of the IED and for all associated electrical circuits.

19.2.9.2 Design

The Binary input module contains 16 optical isolated binary inputs. The voltage
level of the binary input is selected at order.

For configuration of the input signals, refer to section "Signal matrix for binary
inputs SMBI".

A signal discriminator detects and blocks oscillating signals. When blocked, a


hysteresis function may be set to release the input at a chosen frequency, making it
possible to use the input for pulse counting. The blocking frequency may also be set.

Figure 457 shows the operating characteristics of the binary inputs of the four
voltage levels.

The standard version of binary inputs gives an improved capability to withstand


disturbances and should generally be used when pulse counting is not required.

889
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

[V]

300

176
144
88
72
38
32
19
18

24/30V 48/60V 110/125V 220/250V

xx06000391.vsd
IEC06000391 V1 EN

Figure 457: Voltage dependence for the binary inputs

Guaranteed operation

Operation uncertain

No operation

IEC99000517-ABC V1 EN

This binary input module communicates with the Numerical module (NUM) via
the CAN-bus on the backplane.

The design of all binary inputs enables the burn off of the oxide of the relay contact
connected to the input, despite the low, steady-state power consumption, which is
shown in figure 458 and 459.

890
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

[mA]
30 / 50

1
35 70 [ms]

en07000104-2.vsd
IEC07000104 V2 EN

Figure 458: Approximate binary input inrush current for the two standard
versions of BIM.

[mA]
30

1
3.5 7.0 [ms]

en07000105.vsd
IEC07000105 V1 EN

Figure 459: Approximate binary input inrush current for the BIM version with
enhanced pulse counting capabilities.

891
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

Opto isolated input

Opto isolated input

Process connector Opto isolated input

Opto isolated input

Opto isolated input

Opto isolated input

Opto isolated input


Micro-
Opto isolated input controller

Opto isolated input

Opto isolated input


Memory
Opto isolated input

Backplane connector
Process connector

Opto isolated input

Opto isolated input CAN

Opto isolated input

Opto isolated input

Opto isolated input

99000503.vsd
IEC99000503 V1 EN

Figure 460: Block diagram of the Binary input module.

892
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.2.9.3 Technical data


Table 611: BIM - Binary input module
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL 24/30 V RL ± 20%
48/60 V RL ± 20%
110/125 V RL ± 20%
220/250 V RL ± 20%
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz

Table 612: BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL 24/30 V RL ± 20%
48/60 V RL ± 20%
110/125 V RL ± 20%
220/250 V RL ± 20%
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz

19.2.10 Binary output modules (BOM)

19.2.10.1 Introduction

The binary output module has 24 independent output relays and is used for trip
output or any signaling purpose.

19.2.10.2 Design

The binary output module (BOM) has 24 software supervised output relays. Each
pair of relays have a common power source input to the contacts, see figure 461.

893
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

This should be considered when connecting the wiring to the connection terminal
on the back of the IED.

The high closing and carrying current capability allows connection directly to
breaker trip and closing coils. If breaking capability is required to manage fail of
the breaker auxiliary contacts normally breaking the trip coil current, a parallel
reinforcement is required.

For configuration of the output signals, refer to section "Signal matrix for binary
outputs SMBO".

Output module

xx00000299.vsd

IEC00000299 V1 EN

Figure 461: Relay pair example

1 Output connection from relay 1


2 Output signal power source connection
3 Output connection from relay 2

894
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

Relay
Relay
Relay
Relay
Relay

Process connector
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay

Backplane connector
Process connector

Relay Micro-
controller
Relay
Relay

CAN
Relay
Relay Memory

Relay
Relay

99000505.vsd

IEC99000505 V1 EN

Figure 462: Block diagram of the Binary Output Module

19.2.10.3 Technical data


Table 613: BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays
Binary outputs 24
Max system voltage 250 V AC, DC
Test voltage across open contact, 1 min 1000 V rms
Current carrying capacity
Continuous 8A
1s 10 A
Table continues on next page

895
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

Function or quantity Trip and Signal relays


Making capacity at inductive load with L/R>10 ms
0.2 s 30 A
1.0 s 10 A
Breaking capacity for AC, cos j>0.4 250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms 48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A

19.2.11 Static binary output module (SOM)

19.2.11.1 Introduction

The static binary output module has six fast static outputs and six change over
output relays for use in applications with high speed requirements.

19.2.11.2 Design

The Static output module (SOM) have 6 normally open (NO) static outputs and 6
electromechanical relay outputs with change over contacts.

The SOM consists mainly of:

• An MCU
• A CAN-driver
• 6 static relays outputs
• 6 electromechanical relay outputs
• A DC/DC converter
• Connectors interfacing
• CAN-bus to backplane CBM
• IO-connectors to binary outputs (2 pcs.)

The following parts are supervised:

• Interruption in relay coil


• Short circuit of relay coil
• Driver failure

896
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

Drive &
Read back

Drive &
Read back

Process connector
Drive &
Read back

Drive &
Read back

Drive & Code-


Read back flash

Drive &
Read back

MCU
CAN-
driver

Drive &
Read back

Drive &
Read back
Process connector

Backplane connector
DC/DC
Drive &
Read back

Internal_fail_n
Drive & AC_fail_n
Read back RCAN_ID
Sync
Drive &
Read back
Reset
Drive &
Read back

en07000115.vsd
IEC07000115 V1 EN

Figure 463: Block diagram of the static output module

897
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

IEC09000974-1-en.vsd

IEC09000974 V1 EN

Figure 464: SOM Static output principle

IEC09000975 V1 EN

Figure 465: Connection diagram of the static output module

19.2.11.3 Technical data


Table 614: SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Function of quantity Static binary output trip
Rated voltage 48 - 60 VDC 110 - 250 VDC
Number of outputs 6 6
Impedance open state ~300 kΩ ~810 kΩ
Test voltage across open contact, No galvanic separation No galvanic separation
1 min
Current carrying capacity:
Table continues on next page

898
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

Function of quantity Static binary output trip


Continuous 5A 5A
1.0s 10A 10A
Making capacity at capacitive load
with the maximum capacitance of
0.2 μF :
0.2s 30A 30A
1.0s 10A 10A
Breaking capacity for DC with L/R 48V / 1A 110V / 0.4A
≤ 40ms
60V / 0,75A 125V / 0.35A
220V / 0.2A
250V / 0.15A
Operating time <1ms <1ms

Table 615: SOM - Static Output module data (reference standard: IEC 61810-2):
Electromechanical relay outputs
Function of quantity Trip and signal relays
Max system voltage 250V AC/DC
Number of outputs 6
Test voltage across open contact, 1 min 1000V rms
Current carrying capacity:
Continuous 8A
1.0s 10A
Making capacity at capacitive load with the
maximum capacitance of 0.2 μF:
0.2s 30A
1.0s 10A
Breaking capacity for DC with L/R ≤ 40ms 48V / 1A
110V / 0.4A
125V / 0,35A
220V / 0,2A
250V / 0.15A

19.2.12 Binary input/output module (IOM)

19.2.12.1 Introduction

The binary input/output module is used when only a few input and output channels
are needed. The ten standard output channels are used for trip output or any
signaling purpose. The two high speed signal output channels are used for
applications where short operating time is essential. Eight optically isolated binary
inputs cater for required binary input information.

899
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

19.2.12.2 Design

The binary input/output module is available in two basic versions, one with
unprotected contacts and one with MOV (Metal Oxide Varistor) protected contacts.

Inputs are designed to allow oxide burn-off from connected contacts, and increase
the disturbance immunity during normal protection operate times. This is achieved
with a high peak inrush current while having a low steady-state current, see figure
458. Inputs are debounced by software.

Well defined input high and input low voltages ensures normal operation at battery
supply earth faults, see figure 457.

The voltage level of the inputs is selected when ordering.

I/O events are time stamped locally on each module for minimum time deviance
and stored by the event recorder if present.

The binary I/O module, IOM, has eight optically isolated inputs and ten output
relays. One of the outputs has a change-over contact. The nine remaining output
contacts are connected in two groups. One group has five contacts with a common
and the other group has four contacts with a common, to be used as single-output
channels, see figure 466.

The binary I/O module also has two high speed output channels where a reed relay
is connected in parallel to the standard output relay.

For configuration of the input and output signals, refer to sections "Signal matrix
for binary inputs SMBI" and "Signal matrix for binary outputs SMBO".

The making capacity of the reed relays are limited.

900
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

IEC1MRK002801-AA11-UTAN-RAM V1 EN

Figure 466: Binary in/out module (IOM), input contacts named XA corresponds
to rear position X31, X41, and so on, and output contacts named
XB to rear position X32, X42, and so on

The binary input/output module version with MOV protected contacts can for
example be used in applications where breaking high inductive load would cause
excessive wear of the contacts.

The test voltage across open contact is lower for this version of the
binary input/output module.

901
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

xx04000069.vsd

IEC04000069 V1 EN

Figure 467: IOM with MOV protection, relay example

19.2.12.3 Technical data


Table 616: IOM - Binary input/output module
Quantity Rated value Nominal range
Binary inputs 8 -
DC voltage, RL 24/30 V RL ± 20%
48/60 V RL ± 20%
110/125 V RL ± 20%
220/250 V RL ± 20%
Power consumption -
24/30 V max. 0.05 W/input
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input

Table 617: IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel reed
relay)
Binary outputs 10 2
Max system voltage 250 V AC, DC 250 V AC, DC
Test voltage across open contact, 1000 V rms 800 V DC
1 min
Current carrying capacity
Continuous 8A 8A
1s 10 A 10 A
Making capacity at inductive load
with L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Breaking capacity for AC, cos φ > 250 V/8.0 A 250 V/8.0 A
0.4
Breaking capacity for DC with L/R 48 V/1 A 48 V/1 A
< 40 ms 110 V/0.4 A 110 V/0.4 A
125 V/0.35 A 125 V/0.35 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF

902
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

Table 618: IOM with MOV - contact data (reference standard: IEC 60255-23)

Function or quantity Trip and Signal relays Fast signal relays (parallel
reed relay)
Binary outputs IOM: 10 IOM: 2
Max system voltage 250 V AC, DC 250 V AC, DC
Test voltage across open 250 V rms 250 V DC
contact, 1 min
Current carrying capacity
Continuous 8A 8A
1s 10 A 10 A
Making capacity at inductive
loadwith L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Breaking capacity for AC, cos 250 V/8.0 A 250 V/8.0 A
j>0.4
Breaking capacity for DC with L/ 48 V/1 A 48 V/1 A
R < 40 ms 110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF

19.2.13 mA input module (MIM)

19.2.13.1 Introduction

The milli-ampere input module is used to interface transducer signals in the –20 to
+20 mA range from for example OLTC position, temperature or pressure
transducers. The module has six independent, galvanically separated channels.

19.2.13.2 Design

The Milliampere Input Module has six independent analog channels with separated
protection, filtering, reference, A/D-conversion and optical isolation for each input
making them galvanically isolated from each other and from the rest of the module.

For configuration of the input signals, refer to section "Signal matrix for mA
inputs SMMI".

The analog inputs measure DC current in the range of +/- 20 mA. The A/D
converter has a digital filter with selectable filter frequency. All inputs are
calibrated separately The filter parameters and the calibration factors are stored in a
non-volatile memory on the module.

The calibration circuitry monitors the module temperature and starts an automatical
calibration procedure if the temperature drift is outside the allowed range. The
module communicates, like the other I/O-modules on the serial CAN-bus.

903
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

A/D Converter Opto-


Protection isolation
& filter
Volt-ref DC/DC

Process connector
A/D Converter Opto-
Protection isolation
& filter
Volt-ref DC/DC

A/D Converter Opto-


Protection isolation
& filter
Volt-ref DC/DC

A/D Converter Opto-


Protection isolation
& filter
Volt-ref DC/DC

A/D Converter Opto-


Protection isolation
& filter
Volt-ref DC/DC

Backplane connector
A/D Converter Opto-
Protection isolation
& filter
Volt-ref DC/DC

CAN

Memory Micro-
controller

99000504.vsd
IEC99000504 V1 EN

Figure 468: MIM block diagram

19.2.13.3 Technical data


Table 619: MIM - mA input module
Quantity: Rated value: Nominal range:
Input resistance Rin = 194 Ohm -

Input range ± 5, ± 10, ± 20mA -


0-5, 0-10, 0-20, 4-20mA
Power consumption -
each mA-board £2W
each mA input £ 0.1 W

904
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.2.14 Serial and LON communication module (SLM)

19.2.14.1 Introduction

The serial and LON communication module (SLM) is used for SPA, IEC
60870-5-103 and LON communication. The module has two optical
communication ports for plastic/plastic, plastic/glass or glass/glass. One port is
used for serial communication (SPA and IEC 60870-5-103) and one port is
dedicated for LON communication.

19.2.14.2 Design

The SLM is a PMC card and it is factory mounted as a mezzanine card on the
NUM module. Three variants of the SLM is available with different combinations
of optical fiber connectors, see figure 469. The plastic fiber connectors are of snap-
in type and the glass fiber connectors are of ST type.

IEC05000760 V1 EN

Figure 469: The SLM variants

A Snap in connector for plastic fiber


B ST connector for glass fiber
1 LON port
2 SPA/IEC 60870-5-103 port

905
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

IEC05000761 V1 EN

Figure 470: The SLM layout overview

1 Receiver, LON
2 Transmitter, LON
3 Receiver, SPA/IEC 60870-5-103
4 Transmitter, SPA/IEC 60870-5-103

Observe that when the SLM is mounted on the NUM module, then
contact 4 above will be in the uppermost and contact 1 in the lowest
position.

19.2.14.3 Technical data


Table 620: SLM – LON port
Quantity Range or value
Optical connector Glass fibre: type ST
Plastic fibre: type HFBR snap-in
Fibre, optical budget Glass fibre: 11 dB (1000 m typically *)
Plastic fibre: 7 dB (10 m typically *)
Fibre diameter Glass fibre: 62.5/125 mm
Plastic fibre: 1 mm
*) depending on optical budget calculation

906
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

Table 621: SLM – SPA/IEC 60870-5-103 port


Quantity Range or value
Optical connector Glass fibre: type ST
Plastic fibre: type HFBR snap-in
Fibre, optical budget Glass fibre: 11 dB (3000ft/1000 m typically *)
Plastic fibre: 7 dB (80ft/25 m typically *)
Fibre diameter Glass fibre: 62.5/125 mm
Plastic fibre: 1 mm
*) depending on optical budget calculation

19.2.15 Galvanic RS485 communication module

19.2.15.1 Introduction

The Galvanic RS485 communication module (RS485) is used for DNP3.0


communication. The module has one RS485 communication port. The RS485 is a
balanced serial communication that can be used either in 2-wire or 4-wire
connections. A 2-wire connection uses the same signal for RX and TX and is a
multidrop communication with no dedicated Master or slave. This variant requires
however a control of the output. The 4-wire connection has separated signals for
RX and TX multidrop communication with a dedicated Master and the rest are
slaves. No special control signal is needed in this case.

19.2.15.2 Design

The RS485 is a PMC card and it is factory mounted as a mezzanine card on the
NUM module. The internal structure of the RS485 can be seen in figure 471:

FPGA
32 MHz
Wishbone interconnect switch

Tx
PCI-con

Isolation
6-pole-connector
Internal UART RS485
bus tranceiver
PCI-bus Rx
Local bus Isolation
PCI-
to
Controller
wishbone
PCI-con

Isolation
Status
Register Termination
connector

Info
2-pole

Register
Control
ID-chip
Register Isolated Soft
DC/DC ground

IEC06000516 V1 EN

Figure 471: The internal structure of the RS485 card

RS485 connector pinouts


The arrangement for the pins in the RS485 connector (figure 472) are presented in
table 622:

907
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

Table 622: The arrangement for the pins

Pin Name 2-wire Name 4-wire Description


1 RS485+ TX+ Receive/transmit high or transmit high
2 RS485– TX– Receive/transmit
3 Term T-Term Termination resistor for transmitter (and receiver
in 2–wir case) (connect to TX+)
4 N.A. R-Term Termination resistor for receiver (connect to RX
+)
5 N.A. RX– Receive low
6 N.A. RX+ Receive high

Angle
bracket

Screw
1
terminal
X3 2
1
2 RS485
3 PWB
Screw
4
terminal
5
X1
6

Backplane

IEC06000517 V1 EN

Figure 472: RS485 connector

• 2-wire: Connect pin 1 to pin 6 and pin 2 to pin 5

• Termination (2-wire): Connect pin 1 to pin 3

• Termination (4-wire): Connect pin 1 to pin 3 and pin 4 to pin 6

Soft ground connector pinouts


A second 2-pole screw connector is used for the connection of IO-ground. It can be
used in two combinations like:

• Unconnected: No ground of the IO-part · .

• Soft grounded: The IO is connected to the GND with an RC net parallel with a
MOV

908
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.2.15.3 Technical data


Table 623: Galvanic RS485 communication module
Quantity Range or value
Communication speed 2400–19200 bauds
External connectors RS-485 6-pole connector
Soft ground 2-pole connector

19.2.16 Optical ethernet module (OEM)

19.2.16.1 Introduction

The optical fast-ethernet module is used to connect an IED to the communication


buses (like the station bus) that use the IEC 61850-8-1 protocol (OEM rear port A,
B). The process bus use the IEC 61850-9-2LE protocol (OEM rear port C, D). The
module has one or two optical ports with ST connectors.

19.2.16.2 Functionality

The Optical Ethernet module (OEM) is used when communication systems


according to IEC61850–8–1 have been implemented.

19.2.16.3 Design

The Optical Ethernet module (OEM) is a PMC card and mounted as a mezzanine
card on the ADM. The OEM is a 100base Fx module and available as a single
channel or double channel unit.
PCI - bus Connector
100Base-FX
EEPROM
Transmitter ST fiber optic
Ethernet Controller connectors
100Base-FX
Receiver

PCI - PCI Bridge

100Base-FX
Transmitter
ID chip ST fiber optic
Ethernet Controller
connectors
100Base-FX
EEPROM
IO - bus Connector Receiver

en04000472.vsd
IEC04000472 V1 EN

Figure 473: OEM block diagram.

909
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

ID chip

Receiver

IO bus
LED
Ethernet cont.
25MHz oscillator
Transmitter

Receiver
LED

PCI bus
Ethernet cont. PCI to PCI
bridge
25MHz oscillator
Transmitter

en05000472.vsd
IEC05000472 V1 EN

Figure 474: OEM layout, standard PMC format 2 channels

19.2.16.4 Technical data


Table 624: OEM - Optical ethernet module
Quantity Rated value
Number of channels 1 or 2 (port A, B for IEC61850-8-1 and port C, D
for IEC 61850-9-2LE)
Standard IEEE 802.3u 100BASE-FX
Type of fiber 62.5/125 mm multimode fibre
Wave length 1300 nm
Optical connector Type ST
Communication speed Fast Ethernet 100 MB

19.2.17 Line data communication module (LDCM)

19.2.17.1 Introduction

The line data communication module (LDCM) is used for communication between
the IEDs situated at distances <110 km or from the IED to optical to electrical
converter with G.703 interface located on a distances <3 km away. The LDCM
module sends and rereceives data, to and from another LDCM module. The IEEE/
ANSI standard format is used.

The line data communication module is used for binary signal transfer. The module
has one optical port with ST connectors see figure 475.

Line data communication module LDCM


Each module has one optical port, one for each remote end to which the IED
communicates.

910
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

Alternative cards for Long range (1550 nm single mode), Medium range (1310 nm
single mode) and Short range (850 nm multi mode) are available.

Class 1 laser product. Take adequate measures to protect the eyes.


Never look into the laser beam.

19.2.17.2 Design

The LDCM is a PCMIP type II single width format module. The LDCM can be
mounted on:

• the ADM
• the NUM

ID

ST
16.000
IO-connector

MHz
32,768
MHz

ST

en07000087.vsd
IEC07000087 V1 EN

Figure 475: The SR-LDCM layout. PCMIP type II single width format with two
PCI connectors and one I/O ST type connector

911
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

X1

C
ADN 2.5V
ID
2841

PCI9054
FPGA TQ176
DS DS
256 FBGA
3904 3904

3645
MAX
3
2

en06000393.vsd
IEC06000393 V1 EN

Figure 476: The MR-LDCM and LR-LDCM layout. PCMIP type II single width
format with two PCI connectors and one I/O FC/PC type connector

19.2.17.3 Technical data

Table 625: Line data communication module


Characteristic Range or value
Type of LDCM Short range (SR) Medium range (MR) Long range (LR)
Type of fibre Graded-index Singlemode 9/125 Singlemode 9/125 µm
multimode µm
62.5/125 µm or
50/125 µm
Wave length 850 nm 1310 nm 1550 nm
Optical budget 13 dB (typical 22 dB (typical 26 dB (typical distance 110 km *)
Graded-index distance about 3 distance 80 km *)
multimode 62.5/125 km *)
mm, 9 dB (typical
distance about 2
km *)
Graded-index
multimode 50/125
mm

Optical connector Type ST Type FC/PC Type FC/PC


Protocol C37.94 C37.94 C37.94 implementation **)
implementation **)
Data transmission Synchronous Synchronous Synchronous
Transmission rate / 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s
Data rate
Clock source Internal or Internal or derived Internal or derived from received
derived from from received signal signal
received signal
*) depending on optical budget calculation
**) C37.94 originally defined just for multimode; using same header, configuration and data format as
C37.94

912
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.2.18 Galvanic X.21 line data communication (X.21-LDCM)

19.2.18.1 Introduction

The galvanic X.21 line data communication module is used for connection to
telecommunication equipment, for example leased telephone lines. The module
supports 64 kbit/s data communication between IEDs.

Examples of applications:

• Line differential protection


• Binary signal transfer

19.2.18.2 Design

The galvanic X.21 line data communication module uses a ABB specific PC*MIP
Type II format.

C
en07000196.vsd
IEC07000196 V1 EN

Figure 477: Overview of the X.21 LDCM module

913
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

1 4

1 8

9 15

3 2
en07000239.wmf
IEC07000239 V1 EN

Figure 478: The X.21 LDCM module external connectors

1. Ground selection connector for IO, screw terminals, 2-pole


2. Ground pin
3. Soft ground pin, see figure 479
4. X.21 Micro D-sub 15 pole male connector according to the V11 (X:27)
balanced version

I/O

100kW 100nF

Soft ground

en07000242.vsd
IEC07000242 V1 EN

Figure 479: Schematic view of soft ground

Grounding

At special problems with ground loops, the soft ground connection for the IO-
ground can be tested.

Three different kinds of grounding principles can be set (used for fault tracing):
1. Direct ground - The normal grounding is direct ground, connect terminal 2
direct to the chassi.
2. No ground - Leave the connector without any connection.
3. Soft ground - Connect soft ground pin (3), see figure 478

914
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

X.21 connector

Table 626: Pinout for the X.21 communication connector

Pin number Signal


1 Shield (ground)
2 TXD A
3 Control A
4 RXD A
6 Signal timing A
8 Ground
9 TXD B
10 Control B
11 RXD B
13 Signal timing B
5,7,12,14,15 Not used

19.2.18.3 Functionality

The data format is HDLC. The speed for the transmission of the messages used is
64 kbit/s.

A maximum of 100 meter of cable is allowed to ensure the quality of the data
(deviation from X.21 standard cable length).

Synchronization

The X.21 LDCM works like a DTE (Data Terminal Equipment) and is normally
expecting synchronization from the DCE (Data Circuit Equipment). The
transmission is normally synchronized to the Signal Element Timing signal when a
device is a DTE. When the signal is high it will read the data at the receiver and
when the signal is low it will write data to the transmitter. This behaviour can be
inverted in the control register.

Normally an external multiplexer is used and it should act like the master.

When two X.21 LDCM is directly communicating with each other one must be set
as a master generating the synchronization for the other (the slave). The DTE
Signal Element Timing is created from the internal 64 kHz clock.

The Byte Timing signal is not used in ABB devices.

915
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

19.2.18.4 Technical data


Table 627: Galvanic X.21 line data communication module (X.21-LDCM)
Quantity Range or value
Connector, X.21 Micro D-sub, 15-pole male, 1.27 mm (0.050") pitch
Connector, ground selection 2 pole screw terminal
Standard CCITT X21
Communication speed 64 kbit/s
Insulation 1 kV
Maximum cable length 100 m

19.2.19 GPS time synchronization module (GSM)

19.2.19.1 Introduction

This module includes the GPS receiver used for time synchronization. The GPS
has one SMA contact for connection to an antenna.

19.2.19.2 Design

The GPS time synchronization module is 6U high and occupies one slot. The slot
closest to the NUM shall always be used.

The GSM consists of

• CAN carrier module (CCM)


• GPS clock module (GCM)
• GPS receiver unit

The CCM is a carrier board for the GCM mezzanine PMC card and GPS unit, see
figure 481. There is a cable between the external antenna input on the back of the
GCM and the GPS-receiver. This is a galvanic connection vulnerable to electro-
magnetic interference. The connector is shielded and directly attached to a
grounded plate to reduce the risk. The second cable is a flat cable that connects the
GPS and the GCM. It is used for communication between the GCM and the GPS-
receiver. All communication between the GCM and the NUM is via the CAN-bus.

The CMPPS signal is sent from the GCM to the rest of the time system to provide
1µs accuracy at sampling level.

916
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

PMC
GPS GPS clock
GPS antenna
receiver module

CMPPS

Backplane CAN
CAN

connector
controller CAN

en05000675.vsd
IEC05000675 V1 EN

Figure 480: GSM block diagram

917
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

en07000086.vsd
IEC07000086 V1 EN

Figure 481: A CCM with the GCM and GPS mounted with cables

1 GPS receiver
2 GPS Clock module (GCM)
3 CAN carrier module (CCM)
4 Antenna connector

19.2.19.3 Technical data


Table 628: GPS time synchronization module (GSM)
Function Range or value Accuracy
Receiver – ±1µs relative UTC
Time to reliable time reference with antenna in new <30 minutes –
position or after power loss longer than 1 month
Time to reliable time reference after a power loss <15 minutes –
longer than 48 hours
Time to reliable time reference after a power loss <5 minutes –
shorter than 48 hours

918
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.2.20 GPS antenna

19.2.20.1 Introduction

In order to receive GPS signals from the satellites orbiting the earth a GPS antenna
with applicable cable must be used.

19.2.20.2 Design

The antenna with a console for mounting on a horizontal or vertical flat surface or
on an antenna mast. See figure 482

1 6

4 7

xx04000155.vsd

IEC04000155 V1 EN

Figure 482: Antenna with console

where:
1 GPS antenna
2 TNC connector
3 Console, 78x150 mm
4 Mounting holes 5.5 mm
5 Tab for securing of antenna cable
6 Vertical mounting position
7 Horizontal mounting position

Always position the antenna and its console so that a continuous clear line-of-sight
visibility to all directions is obtained, preferably more than 75%. A minimum of
50% clear line-of-sight visibility is required for un-interrupted operation.

919
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

99001046.vsd
IEC99001046 V1 EN

Figure 483: Antenna line-of-sight

Antenna cable
Use a 50 ohm coaxial cable with a male TNC connector in the antenna end and a
male SMA connector in the receiver end to connect the antenna to GSM. Choose
cable type and length so that the total attenuation is max. 26 dB at 1.6 GHz.

Make sure that the antenna cable is not charged when connected to
the antenna or to the receiver. Short-circuit the end of the antenna
cable with some metal device, when first connected to the antenna.
When the antenna is connected to the cable, connect the cable to the
receiver. REx670 must be switched off when the antenna cable is
connected.

19.2.20.3 Technical data


Table 629: GPS – Antenna and cable
Function Value
Max antenna cable attenuation 26 db @ 1.6 GHz
Antenna cable impedance 50 ohm
Lightning protection Must be provided externally
Antenna cable connector SMA in receiver end
TNC in antenna end

920
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.2.21 IRIG-B time synchronization module IRIG-B

19.2.21.1 Introduction

The IRIG-B time synchronizing module is used for accurate time synchronizing of
the IED from a station clock.

The Pulse Per Second (PPS) input shall be used for synchronizing when IEC
61850-9-2LE is used.

Electrical (BNC) and optical connection (ST) for 0XX and 12X IRIG-B support.

19.2.21.2 Design

The IRIG-B module have two inputs. One input is for the IRIG-B that can handle
both a pulse-width modulated signal (also called unmodulated) and an amplitude
modulated signal (also called sine wave modulated). The other is an optical input
type ST for PPS to synchronize the time between several protections.

32 MHz FPGA

connector
PCI-con

OPTO_INPUT

ST-
PCI-bus
Registers
PCI-Controller
PCI-con

4 mm barrier

IRIG- IRIG_INPUT

connector
Amplitude
ID-chip Decoder

BNC-
modulator
Capture1 Isolated
ZXING
receiver
Zero-cross
Capture2 detector

MPPS
IO-con

PPS
TSU Isolated
DC/DC
CMPPS 5 to +- 12V

en06000303.vsd
IEC06000303 V1 EN

Figure 484: IRIG-B block diagram

921
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

A1
DC//DC
ST

C
Y2

C
C
A1

C
O
T
3
2

O
en06000304.vsd
IEC06000304 V1 EN

Figure 485: IRIG-B PC-MIP board with top left ST connector for PPS 820 nm
multimode fibre optic signal input and lower left BNC connector for
IRIG-B signal input

19.2.21.3 Technical data


Table 630: IRIG-B
Quantity Rated value
Number of channels IRIG-B 1
Number of channels PPS 1
Electrical connector IRIG-B BNC
Optical connector PPS and IRIG-B Type ST
Type of fibre 62.5/125 μm multimode fibre

922
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.3 Dimensions

19.3.1 Case without rear cover

A
D

B C

xx08000164.vsd
IEC08000164 V1 EN

Figure 486: Case without rear cover

923
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

K
F

G
H J

xx08000166.vsd

IEC08000166 V1 EN

Figure 487: Case without rear cover with 19” rack mounting kit

Case size (mm) A B C D E F G H J K


6U, 1/2 x 19” 265.9 223.7 201.1 252.9 205.7 190.5 203.7 - 187.6 -
6U, 3/4 x 19” 265.9 336.0 201.1 252.9 318.0 190.5 316.0 - 187.6 -
6U, 1/1 x 19” 265.9 448.3 201.1 252.9 430.3 190.5 428.3 465.1 187.6 482.6
The H and K dimensions are defined by the 19” rack mounting kit

924
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.3.2 Case with rear cover

A
D

B
C

xx08000163.vsd
IEC08000163 V1 EN

Figure 488: Case with rear cover

925
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

K
F

G
J
H
xx08000165.vsd

IEC08000165 V1 EN

Figure 489: Case with rear cover and 19” rack mounting kit

xx05000503.vsd
IEC05000503 V1 EN

Figure 490: Rear cover case with details

Case size (mm) A B C D E F G H J K


6U, 1/2 x 19” 265.9 223.7 242.1 255.8 205.7 190.5 203.7 - 228.6 -
6U, 3/4 x 19” 265.9 336.0 242.1 255.8 318.0 190.5 316.0 - 228.6 -
6U, 1/1 x 19” 265.9 448.3 242.1 255.8 430.3 190.5 428.3 465.1 228.6 482.6
The H and K dimensions are defined by the 19” rack mounting kit.

926
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.3.3 Flush mounting dimensions

A C
B

E
D

xx08000162.vsd
IEC08000162 V1 EN

Figure 491: Flush mounting

Cut-out dimensions (mm)


Case size
Tolerance A B C D
+/-1 +/-1
6U, 1/2 x 19" 210.1 254.3 4.0-10.0 12.5
6U, 3/4 x 19" 322.4 254.3 4.0-10.0 12.5
6U, 1/1 x 19" 434.7 254.3 4.0-10.0 12.5
E = 188.6 mm without rear protection cover, 229.6 mm with rear protection cover

927
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

19.3.4 Side-by-side flush mounting dimensions

xx06000182.vsd
IEC06000182 V1 EN

Figure 492: A 1/2 x 19” size 670 series IED side-by-side with RHGS6.

G
D
B
E

F
C
xx05000505.vsd

IEC05000505 V1 EN

Figure 493: Panel-cut out dimensions for side-by-side flush mounting

928
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.3.5 Wall mounting dimensions

B
E

C
D

en04000471.vsd
IEC04000471 V1 EN

Figure 494: Wall mounting

Case size (mm) A B C D E


6U, 1/2 x 19” 292.0 267.1 272.8 390.0 243.0
6U, 3/4 x 19” 404.3 379.4 272.8 390.0 243.0
6U, 1/1 x 19” 516.0 491.1 272.8 390.0 243.0

19.3.6 External resistor unit for high impedance differential


protection

WARNING! - USE EXTREME CAUTION!Dangerously high


voltages might be present on this equipment, especially on the plate
with resistors. Do any maintenance ONLY if the primary object
protected with this equipment is de-energized. If required by
national low/standard enclose the plate with resistors with a
protective cover or in a separate box!

929
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

[1.48]
[6.97]

[4.02]

[0.33] [18.31] [0.79] [7.68]


[18.98]

Dimension
mm [inches] xx06000232.eps

IEC06000232 V1 EN

Figure 495: Dimension drawing of a one phase impedance resistor unit


[1.50]
[10.47]

[7.50]

[0.33] [18.31] [0.79] [7.68]


[18.98]

en06000234.eps
[inches]

IEC06000234 V1 EN

Figure 496: Dimension drawing of a three phase high impedance resistor unit

19.4 Mounting alternatives

19.4.1 Flush mounting

19.4.1.1 Overview

The flush mounting kit are utilized for case sizes:

• 1/2 x 19”
• 3/4 x 19”
• 1/1 x 19”
• 1/4 x 19” (RHGS6 6U)

930
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

Only a single case can be mounted in each cut-out on the cubicle panel, for class
IP54 protection.

Flush mounting cannot be used for side-by-side mounted IEDs


when IP54 class must be fulfilled. Only IP20 class can be obtained
when mounting two cases side-by-side in one (1) cut-out.

To obtain IP54 class protection, an additional factory mounted


sealing must be ordered when ordering the IED.

931
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

19.4.1.2 Mounting procedure for flush mounting

xx08000161.vsd
IEC08000161 V1 EN

Figure 497: Flush mounting details.

PosNo Description Quantity Type


1 Sealing strip, used to obtain IP54 class. The sealing strip is factory - -
mounted between the case and front plate.
2 Fastener 4 -
3 Groove - -
4 Screw, self tapping 4 2.9x9.5 mm
5 Joining point of sealing strip - -
6 Panel - -

932
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

19.4.2 19” panel rack mounting

19.4.2.1 Overview

All IED sizes can be mounted in a standard 19” cubicle rack by using the for each
size suited mounting kit which consists of two mounting angles and fastening
screws for the angles.

The mounting angles are reversible which enables mounting of IED size 1/2 x 19”
or 3/4 x 19” either to the left or right side of the cubicle.

Please note that the separately ordered rack mounting kit for side-by-
side mounted IEDs, or IEDs together with RHGS cases, is to be
selected so that the total size equals 19”.

When mounting the mounting angles, be sure to use screws that


follows the recommended dimensions. Using screws with other
dimensions than the original may damage the PCBs inside the IED.

933
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

19.4.2.2 Mounting procedure for 19” panel rack mounting

1a

1b

xx08000160.vsd
IEC08000160 V1 EN

Figure 498: 19” panel rack mounting details

Pos Description Quantity Type


1a, 1b Mounting angels, which can be mounted, either to 2 -
the left or right side of the case.
2 Screw 8 M4x6

19.4.3 Wall mounting

19.4.3.1 Overview

All case sizes, 1/2 x 19”, 3/4 x 19” and 1/1 x 19”, can be wall mounted. It is also
possible to mount the IED on a panel or in a cubicle.

934
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

When mounting the side plates, be sure to use screws that follows
the recommended dimensions. Using screws with other dimensions
than the original may damage the PCBs inside the IED.

If fiber cables are bent too much, the signal can be weakened. Wall
mounting is therefore not recommended for communication
modules with fiber connection; Serial SPA/IEC 60870-5-103 and
LON communication module (SLM), Optical Ethernet module
(OEM) and Line data communication module (LDCM).

19.4.3.2 Mounting procedure for wall mounting

3
4
2

6
xx04000453.vs d
DOCUMENT127716-IMG2265 V1 EN

Figure 499: Wall mounting details.

PosNo Description Quantity Type


1 Bushing 4 -
2 Screw 8 M4x10
3 Screw 4 M6x12 or
corresponding
Table continues on next page

935
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

4 Mounting bar 2 -

5 Screw 6 M5x8
6 Side plate 2 -

19.4.3.3 How to reach the rear side of the IED

The IED can be equipped with a rear protection cover, which is recommended to
use with this type of mounting. See figure 500.

To reach the rear side of the IED, a free space of 80 mmis required on the unhinged
side.

View from above

3
1

80 mm 2

en06000135.vsd
IEC06000135 V1 EN

Figure 500: How to reach the connectors on the rear side of the IED.

PosNo Description Type


1 Screw M4x10
2 Screw M5x8
3 Rear protection cover -

19.4.4 Side-by-side 19” rack mounting

19.4.4.1 Overview

IED case sizes, 1/2 x 19” or 3/4 x 19” and RHGS cases, can be mounted side-by-
side up to a maximum size of 19”. For side-by-side rack mounting, the side-by-side
mounting kit together with the 19” rack panel mounting kit must be used. The
mounting kit has to be ordered separately.

936
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

When mounting the plates and the angles on the IED, be sure to use
screws that follows the recommended dimensions. Using screws
with other dimensions than the original may damage the PCBs
inside the IED.

19.4.4.2 Mounting procedure for side-by-side rack mounting

2
1

xx04000456.vsd
IEC04000456 V1 EN

Figure 501: Side-by-side rack mounting details.

PosNo Description Quantity Type


1 Mounting plate 2 -
2, 3 Screw 16 M4x6
4 Mounting angle 2 -

19.4.4.3 IED in the 670 series mounted with a RHGS6 case

An 1/2 x 19” or 3/4 x 19” size IED can be mounted with a RHGS (6 or 12
depending on IED size) case. The RHGS case can be used for mounting a test
switch of type RTXP 24. It also has enough space for a terminal base of RX 2 type
for mounting of, for example, a DC-switch or two trip IEDs.

937
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

1 2

1 2 1 2

1 1 1 1

2 2 2 2

3 3 3 3

4 4 4 4

5 5 5 5

6 6 6 6

7 7 7 7

8 8 8 8

xx06000180.vsd
IEC06000180 V1 EN

Figure 502: IED in the 670 series (1/2 x 19”) mounted with a RHGS6 case
containing a test switch module equipped with only a test switch
and a RX2 terminal base

19.4.5 Side-by-side flush mounting

19.4.5.1 Overview

It is not recommended to flush mount side by side mounted cases if IP54 is


required. If your application demands side-by-side flush mounting, the side-by-side
mounting details kit and the 19” panel rack mounting kit must be used. The
mounting kit has to be ordered separately. The maximum size of the panel cut out
is 19”.

With side-by-side flush mounting installation, only IP class 20 is


obtained. To reach IP class 54, it is recommended to mount the
IEDs separately. For cut out dimensions of separately mounted
IEDs, see section "Flush mounting".

When mounting the plates and the angles on the IED, be sure to use
screws that follows the recommended dimensions. Using screws
with other dimensions than the original may damage the PCBs
inside the IED.

938
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

Please contact factory for special add on plates for mounting FT


switches on the side (for 1/2 19" case) or bottom of the relay.

19.4.5.2 Mounting procedure for side-by-side flush mounting

1 2

xx06000181.vsd
IEC06000181 V1 EN

Figure 503: Side-by-side flush mounting details (RHGS6 side-by-side with 1/2 x
19” IED).

PosNo Description Quantity Type


1 Mounting plate 2 -
2, 3 Screw 16 M4x6
4 Mounting angle 2 -

19.5 Technical data

19.5.1 Enclosure
Table 631: Case
Material Steel sheet
Front plate Steel sheet profile with cut-out for HMI
Surface treatment Aluzink preplated steel
Finish Light grey (RAL 7035)

939
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

Table 632: Water and dust protection level according to IEC 60529

Front IP40 (IP54 with sealing strip)


Rear, sides, top and IP20
bottom

Table 633: Weight


Case size Weight
6U, 1/2 x 19” £ 10 kg
6U, 3/4 x 19” £ 15 kg
6U, 1/1 x 19” £ 18 kg

19.5.2 Connection system


Table 634: CT and VT circuit connectors
Connector type Rated voltage and current Maximum conductor area
Screw compression type 250 V AC, 20 A 4 mm2 (AWG12)
2 x 2.5 mm2 (2 x AWG14)
Terminal blocks suitable for 250 V AC, 20 A 4 mm2 (AWG12)
ring lug terminals

Table 635: Binary I/O connection system


Connector type Rated voltage Maximum conductor area
Screw compression type 250 V AC 2.5 mm2
2 × 1 mm2
Terminal blocks suitable for 300 V AC 3 mm2
ring lug terminals

Because of limitations of space, when ring lug terminal is ordered


for Binary I/O connections, one blank slot is necessary between two
adjacent IO cards. Please refer to the ordering particulars for details.

19.5.3 Influencing factors


Table 636: Temperature and humidity influence
Parameter Reference value Nominal range Influence
Ambient temperature, +20 °C -10 °C to +55 °C 0.02% /°C
operate value
Relative humidity 10%-90% 10%-90% -
Operative range 0%-95%
Storage temperature -40 °C to +70 °C - -

940
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

Table 637: Auxiliary DC supply voltage influence on functionality during operation


Dependence on Reference value Within nominal range Influence
Ripple, in DC auxiliary voltage max. 2% 12% of EL 0.01% /%
Operative range Full wave rectified
Auxiliary voltage dependence, operate ± 20% of EL 0.01% /%
value
Interrupted auxiliary DC voltage 24-60 V DC ± 20%
90-250 V DC ± 20%
Interruption
interval
0–50 ms No restart
0–∞ s Correct
behaviour at
power down
Restart time <180 s

Table 638: Frequency influence (reference standard: IEC 60255–6)


Dependence on Within nominal range Influence
Frequency dependence, fr ± 2.5 Hz for 50 Hz ± 1.0% / Hz
operate value fr ± 3.0 Hz for 60 Hz

Harmonic frequency 2nd, 3rd and 5th harmonic of fr ± 1.0%


dependence (20%
content)
Harmonic frequency 2nd, 3rd and 5th harmonic of fr ± 6.0%
dependence for distance
protection (10% content)
Harmonic frequency 2nd, 3rd and 5th harmonic of fr ±5.0%
dependence for high
impedance differential
protection (10% content)

19.5.4 Type tests according to standard


Table 639: Electromagnetic compatibility
Test Type test values Reference standards
1 MHz burst disturbance 2.5 kV IEC 60255-22-1, Class III
Ring wave immunity test 2-4 kV IEC 61000-4-12, Class III
Surge withstand capability 2.5 kV, oscillatory IEEE/ANSI C37.90.1
test 4.0 kV, fast transient
Electrostatic discharge 15 kV air discharge IEC 60255-22-2, Class IV
Direct application 8 kV contact discharge
Indirect application 8 kV contact discharge IEC 61000-4-2, Class IV
Electrostatic discharge 15 kV air discharge IEEE/ANSI C37.90.1
Direct application 8 kV contact discharge
Indirect application 8 kV contact discharge
Fast transient disturbance 4 kV IEC 60255-22-4, Class A
Table continues on next page

941
Technical reference manual
Section 19 1MRK505183-UEN C
Hardware

Test Type test values Reference standards


Surge immunity test 1-2 kV, 1.2/50 ms IEC 60255-22-5
high energy
Power frequency immunity 150-300 V, IEC 60255-22-7, Class A
test 50 Hz
Conducted common mode 15 Hz-150 kHz IEC 61000-4-16, Class IV
immunity test
Power frequency magnetic 1000 A/m, 3 s IEC 61000-4-8, Class V
field test
Damped oscillatory magnetic 100 A/m IEC 61000-4-10, Class V
field test
Radiated electromagnetic 20 V/m, 80-1000 MHz IEC 60255-22-3
field disturbance
Radiated electromagnetic 20 V/m, 80-2500 MHz EN 61000-4-3
field disturbance
Radiated electromagnetic 35 V/m IEEE/ANSI C37.90.2
field disturbance 26-1000 MHz
Conducted electromagnetic 10 V, 0.15-80 MHz IEC 60255-22-6
field disturbance
Radiated emission 30-1000 MHz IEC 60255-25
Conducted emission 0.15-30 MHz IEC 60255-25

Table 640: Insulation


Test Type test values Reference standard
Dielectric test 2.0 kV AC, 1 min. IEC 60255-5
Impulse voltage test 5 kV, 1.2/50 ms, 0.5 J
Insulation resistance >100 MW at 500 VDC

Table 641: Environmental tests


Test Type test value Reference standard
Cold test Test Ad for 16 h at -25°C IEC 60068-2-1
Storage test Test Ad for 16 h at -40°C IEC 60068-2-1
Dry heat test Test Bd for 16 h at +70°C IEC 60068-2-2
Damp heat test, steady state Test Ca for 4 days at +40 °C IEC 60068-2-78
and humidity 93%
Damp heat test, cyclic Test Db for 6 cycles at +25 IEC 60068-2-30
to +55 °C and humidity 93 to
95% (1 cycle = 24 hours)

Table 642: CE compliance


Test According to
Immunity EN 50263
Emissivity EN 50263
Low voltage directive EN 50178

942
Technical reference manual
1MRK505183-UEN C Section 19
Hardware

Table 643: Mechanical tests


Test Type test values Reference standards
Vibration response test Class II IEC 60255-21-1
Vibration endurance test Class I IEC 60255-21-1
Shock response test Class II IEC 60255-21-2
Shock withstand test Class I IEC 60255-21-2
Bump test Class I IEC 60255-21-2
Seismic test Class II IEC 60255-21-3

943
Technical reference manual
944
1MRK505183-UEN C Section 20
Labels

Section 20 Labels

About this chapter


This chapter includes descriptions of the different labels and where to find them on
the IED.

20.1 Different labels

2
3

6
6 5
7
xx06000574.eps
IEC06000574 V1 EN

945
Technical reference manual
Section 20 1MRK505183-UEN C
Labels

1 Product type, description and serial number


2 Order number, dc supply voltage and rated
frequency
3 Optional, customer specific information
4 Manufacturer
5 Transformer input module, rated currents
and voltages
6 Transformer designations

IEC06000577-CUSTOMER-SPECIFIC V1 EN

7 Ordering and serial number

IEC06000576-POS-NO V1 EN

946
Technical reference manual
1MRK505183-UEN C Section 20
Labels

4
en06000573.eps
IEC06000573 V1 EN

1 Warning label
2 Caution label
3 Class 1 laser product label

IEC06000575 V1 EN

4 Warning label

947
Technical reference manual
948
1MRK505183-UEN C Section 21
Connection diagrams

Section 21 Connection diagrams

This chapter includes diagrams of the IED with all slot, terminal block and optical
connector designations. It is a necessary guide when making electrical and optical
connections to the IED.

949
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams

IEC08000470 V1 EN

950
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams

IEC08000471 V1 EN

951
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams

IEC08000472 V1 EN

952
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams

IEC08000473 V1 EN

953
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams

IEC08000474 V1 EN

954
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams

IEC08000475 V1 EN

955
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams

IEC08000476 V1 EN

956
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams

IEC08000477 V1 EN

957
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams

IEC08000478 V1 EN

958
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams

IEC08000479 V1 EN

959
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams

IEC08000480 V1 EN

960
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams

IEC08000481 V1 EN

961
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams

IEC08000482 V1 EN

962
Technical reference manual
1MRK505183-UEN C Section 21
Connection diagrams

IEC08000483 V1 EN

963
Technical reference manual
Section 21 1MRK505183-UEN C
Connection diagrams

IEC08000484 V1 EN

964
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

Section 22 Inverse time characteristics

About this chapter


This chapter describes current and voltage dependant time functionality. Both
ANSI and IEC Inverse time curves and tables are included.

22.1 Application

In order to assure time selectivity between different overcurrent protections at


different points in the network different time delays for the different protections are
normally used. The simplest way to do this is to use definite time-lag. In more
sophisticated applications current dependent time characteristics are used. Both
alternatives are shown in a simple application with three overcurrent protections
operating in series.

I> I> I>


xx05000129.vsd
IEC05000129 V1 EN

Figure 504: Three overcurrent protections operating in series

Stage 3

Time
Stage 2 Stage 2

Stage 1 Stage 1 Stage 1

Fault point
position

en05000130.vsd

IEC05000130 V1 EN

Figure 505: Definite time overcurrent characteristics

965
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

Time

Fault point
position

en05000131.vsd

IEC05000131 V1 EN

Figure 506: Inverse time overcurrent characteristics with inst. function

The inverse time characteristic makes it possible to minimize the fault clearance
time and still assure the selectivity between protections.

To assure selectivity between protections there must be a time margin between the
operation time of the protections. This required time margin is dependent of
following factors, in a simple case with two protections in series:

• Difference between pickup time of the protections to be co-ordinated


• Opening time of the breaker closest to the studied fault
• Reset times of the protections
• Margin dependent of the time delay inaccuracy of the protections

Assume we have the following network case.

966
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

A1 B1
Feeder

I> I>

Time axis

t=0 t=t1 t=t2 t=t3

en05000132.vsd

IEC05000132 V1 EN

Figure 507: Selectivity steps for a fault on feeder B1

where:
t=0 is The fault occurs
t=t1 is Protection B1 trips

t=t2 is Breaker at B1 opens

t=t3 is Protection A1 resets

In the case protection B1 shall operate without any intentional delay


(instantaneous). When the fault occurs the protections start to detect the fault
current. After the time t1 the protection B1 send a trip signal to the circuit breaker.
The protection A1 starts its delay timer at the same time, with some deviation in
time due to differences between the two protections. There is a possibility that A1
will start before the trip is sent to the B1 circuit breaker. At the time t2 the circuit
breaker B1 has opened its primary contacts and thus the fault current is interrupted.
The breaker time (t2 - t1) can differ between different faults. The maximum
opening time can be given from manuals and test protocols. Still at t2 the timer of
protection A1 is active. At time t3 the protection A1 is reset, that is the timer is stopped.

In most applications it is required that the times shall reset as fast as possible when
the current fed to the protection drops below the set current level, the reset time
shall be minimized. In some applications it is however beneficial to have some type
of delayed reset time of the overcurrent function. This can be the case in the
following applications:

967
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

• If there is a risk of intermittent faults. If the current IED, close to the faults,
starts and resets there is a risk of unselective trip from other protections in the
system.
• Delayed resetting could give accelerated fault clearance in case of automatic
reclosing to a permanent fault.
• Overcurrent protection functions are sometimes used as release criterion for
other protection functions. It can often be valuable to have a reset delay to
assure the release function.

22.2 Principle of operation

22.2.1 Mode of operation


The function can operate in a definite time-lag mode or in a current definite inverse
time mode. For the inverse time characteristic both ANSI and IEC based standard
curves are available. Also programmable curve types are supported via the
component inputs: p, A, B, C pr, tr, and cr.

Different characteristics for reset delay can also be chosen.

If current in any phase exceeds the set start current value (here internal signal
startValue), a timer, according to the selected operating mode, is started. The
component always uses the maximum of the three phase current values as the
current level used in timing calculations.

In case of definite time-lag mode the timer will run constantly until the time is
reached or until the current drops below the reset value (start value minus the
hysteresis) and the reset time has elapsed.

For definite time delay curve ANSI/IEEE Definite time or IEC Definite time are
chosen.

The general expression for inverse time curves is according to equation 161.

æ ö
ç A
÷
t[ s ] = ç + B ÷×k
ç æ i öp ÷
çç ÷ -C ÷
è è in > ø ø
EQUATION1189 V1 EN (Equation 161)

where:
p, A, B, C are constants defined for each curve type,
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current.

968
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

For inverse time characteristics a time will be initiated when the current reaches the
set start level. From the general expression of the characteristic the following can
be seen:

ææ i öp ö
(top - B × k ) × ç ç ÷ - C ÷ = A×k
è è in > ø ø
EQUATION1190 V1 EN (Equation 162)

where:
top is the operating time of the protection

The time elapsed to the moment of trip is reached when the integral fulfils
according to equation 163, in addition to the constant time delay:

t
ææ i öp ö
ò ç çè in > ÷ø - C ÷ × dt ³ A × k
0 è ø
EQUATION1191 V1 EN (Equation 163)

For the numerical protection the sum below must fulfil the equation for trip.

n æ æ i( j ) ö p ö
Dt × å ç ç ÷ - C ÷ ³ A× k
j =1 è è in > ø ø
EQUATION1192 V1 EN (Equation 164)

where:
j=1 is the first protection execution cycle when a fault has been
detected, that is, when

i
>1
in >
EQUATION1193 V1 EN

Dt is the time interval between two consecutive executions of the


protection algorithm,
n is the number of the execution of the algorithm when the trip
time equation is fulfilled, that is, when a trip is given and
i (j) is the fault current at time j

For inverse time operation, the inverse time characteristic is selectable. Both the
IEC and ANSI/IEEE standardized inverse time characteristics are supported.

For the IEC curves there is also a setting of the minimum time-lag of operation, see
figure 508.

969
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

Operate
time

tMin

Current
IMin
IEC05000133-3-en.vsd
IEC05000133 V2 EN

Figure 508: Minimum time-lag operation for the IEC curves

In order to fully comply with IEC curves definition setting parameter tMin shall be
set to the value which is equal to the operating time of the selected IEC inverse
time curve for measured current of twenty times the set current pickup value. Note
that the operating time value is dependent on the selected setting value for time
multiplier k.

In addition to the ANSI and IEC standardized characteristics, there are also two
additional inverse curves available; the RI curve and the RD curve.

The RI inverse time curve emulates the characteristic of the electromechanical


ASEA relay RI. The curve is described by equation 166:

æ ö
ç k ÷
t[ s ] = ç
in > ÷
ç 0.339 - 0.235 × ÷
è i ø
EQUATION1194 V1 EN (Equation 166)

where:
in> is the set start current for step n
k is set time multiplier for step n
i is the measured current

970
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

The RD inverse curve gives a logarithmic delay, as used in the Combiflex


protection RXIDG. The curve enables a high degree of selectivity required for
sensitive residual earth-fault current protection, with ability to detect high-resistive
earth faults. The curve is described by equation 167:

æ i ö
t[ s ] = 5.8 - 1.35 × ln ç ÷
è k × in > ø
EQUATION1195 V1 EN (Equation 167)

where:
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current

If the curve type programmable is chosen, the user can make a tailor made inverse
time curve according to the general equation 168.

æ ö
ç A
÷
t[ s ] = ç + B÷×k
ç æ i öp ÷
çç ÷ -C ÷
è è in > ø ø
EQUATION1196 V1 EN (Equation 168)

Also the reset time of the delayed function can be controlled. There is the
possibility to choose between three different reset time-lags.
• Instantaneous Reset
• IEC Reset
• ANSI Reset.

If instantaneous reset is chosen the timer will be reset directly when the current
drops below the set start current level minus the hysteresis.

If IEC reset is chosen the timer will be reset after a set constant time when the
current drops below the set start current level minus the hysteresis.

If ANSI reset time is chosen the reset time will be dependent of the current after
fault clearance (when the current drops below the start current level minus the
hysteresis). The timer will reset according to equation 169.

971
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

æ ö
ç tr ÷
t [s] = ç ÷×k
çæ i ö ÷
2

çç ÷ -1 ÷
è è in > ø ø
EQUATION1197 V2 EN (Equation 169)

where:
The set value tr is the reset time in case of zero current after fault clearance.

The possibility of choice of reset characteristics is to some extent dependent of the


choice of time delay characteristic.

For the definite time delay characteristics the possible reset time settings are
instantaneous and IEC constant time reset.

For ANSI inverse time delay characteristics all three types of reset time
characteristics are available; instantaneous, IEC constant time reset and ANSI
current dependent reset time.

For IEC inverse time delay characteristics the possible delay time settings are
instantaneous and IEC set constant time reset).

For the programmable inverse time delay characteristics all three types of reset
time characteristics are available; instantaneous, IEC constant time reset and ANSI
current dependent reset time. If the current dependent type is used settings pr, tr
and cr must be given, see equation 170:

æ ö
ç tr ÷
t [s] = ç ÷×k
çæ i ö ÷
pr

çç ÷ - cr ÷
è è in > ø ø
EQUATION1198 V2 EN (Equation 170)

For RI and RD inverse time delay characteristics the possible delay time settings
are instantaneous and IEC constant time reset.

972
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

22.3 Inverse characteristics

Table 644: ANSI Inverse time characteristics


Function Range or value Accuracy
Operating characteristic: k = (0.05-999) in steps of -
0.01 unless otherwise stated
æ A ö
t = ç P + B÷ × k
ç ( I - 1) ÷
è ø
EQUATION1249-SMALL V1 EN

Reset characteristic:

tr
t = ×k
(I 2
)
-1
EQUATION1250-SMALL V1 EN

I = Imeasured/Iset

ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 , ANSI/IEEE C37.112,


tr=29.1 class 5 + 30 ms
ANSI Very inverse A=19.61, B=0.491, P=2.0 ,
tr=21.6
ANSI Normal Inverse A=0.0086, B=0.0185,
P=0.02, tr=0.46
ANSI Moderately Inverse A=0.0515, B=0.1140,
P=0.02, tr=4.85
ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0,
tr=30
ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0,
tr=13.46
ANSI Long Time Inverse k=(0.05-999) in steps of 0.01
A=0.086, B=0.185, P=0.02,
tr=4.6

973
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

Table 645: IEC Inverse time characteristics


Function Range or value Accuracy
Operating characteristic: k = (0.05-999) in steps of 0.01 -

æ A ö
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN

I = Imeasured/Iset

Time delay to reset, IEC inverse time (0.000-60.000) s ± 0.5% of set time ± 10
ms
IEC Normal Inverse A=0.14, P=0.02 IEC 60255-3, class 5 +
40 ms
IEC Very inverse A=13.5, P=1.0
IEC Inverse A=0.14, P=0.02
IEC Extremely inverse A=80.0, P=2.0
IEC Short time inverse A=0.05, P=0.04
IEC Long time inverse A=120, P=1.0
Programmable characteristic k = (0.05-999) in steps of 0.01 IEC 60255, class 5 + 40
Operate characteristic: A=(0.005-200.000) in steps ms
of 0.001
æ A ö B=(0.00-20.00) in steps of
t = ç P + B÷ × k 0.01
ç (I - C ) ÷ C=(0.1-10.0) in steps of 0.1
è ø
P=(0.005-3.000) in steps of
EQUATION1370-SMALL V1 EN
0.001
Reset characteristic: TR=(0.005-100.000) in steps
of 0.001
TR CR=(0.1-10.0) in steps of 0.1
t = ×k PR=(0.005-3.000) in steps of
(I PR
- CR ) 0.001
EQUATION1253-SMALL V1 EN

I = Imeasured/Iset

Table 646: RI and RD type inverse time characteristics


Function Range or value Accuracy
RI type inverse characteristic k = (0.05-999) in steps of 0.01 IEC 60255-3, class 5 +
40 ms
1
t = ×k
0.236
0.339 -
I
EQUATION1137-SMALL V1 EN

I = Imeasured/Iset

RD type logarithmic inverse characteristic k = (0.05-999) in steps of 0.01 IEC 60255-3, class 5 +
40 ms
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN

I = Imeasured/Iset

974
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

Table 647: Inverse time characteristics for overvoltage protection


Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in Class 5 +40 ms
steps of 0.01 unless
k otherwise stated
t =
æU -U >ö
ç ÷
è U> ø
EQUATION1436-SMALL V1 EN

U> = Uset
U = Umeasured

Type B curve: k = (0.05-1.10) in


steps of 0.01 unless
k × 480 otherwise stated
t =
2.0
æ 32 × U - U > - 0.5 ö
ç ÷ - 0.035
è U > ø
EQUATION1437-SMALL V1 EN

Type C curve: k = (0.05-1.10) in


steps of 0.01 unless
k × 480 otherwise stated
t =
3.0
æ 32 × U - U > - 0.5 ö
ç ÷ - 0.035
è U > ø
EQUATION1438-SMALL V1 EN

Programmable curve: k = (0.05-1.10) in


steps of 0.01 unless
k×A otherwise stated
t = +D A = (0.005-200.000)
P
æB × U - U > ö in steps of 0.001
ç -C÷
B = (0.50-100.00) in
è U > ø
EQUATION1439-SMALL V1 EN
steps of 0.01
C = (0.0-1.0) in
steps of 0.1
D = (0.000-60.000)
in steps of 0.001
P = (0.000-3.000) in
steps of 0.001

975
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

Table 648: Inverse time characteristics for undervoltage protection


Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in Class 5 +40 ms
steps of 0.01 unless
k otherwise stated
t =
æ U < -U
ö
ç ÷
è U< ø
EQUATION1431-SMALL V1 EN

U< = Uset
U = UVmeasured

Type B curve: k = (0.05-1.10) in


steps of 0.01 unless
k × 480 otherwise stated
t = + 0.055
2.0
æ 32 × U < -U - 0.5 ö
ç ÷
è U < ø
EQUATION1432-SMALL V1 EN

U< = Uset
U = Umeasured

Programmable curve: k = (0.05-1.10) in


steps of 0.01 unless
é ù otherwise stated
ê ú A = (0.005-200.000)
k×A in steps of 0.001
t =ê ú+D
ê æ U < -U P
ú B = (0.50-100.00) in
ö
êçB × -C÷ ú steps of 0.01
ëè U < ø û C = (0.0-1.0) in
EQUATION1433-SMALL V1 EN
steps of 0.1
U< = Uset D = (0.000-60.000)
in steps of 0.001
U = Umeasured
P = (0.000-3.000) in
steps of 0.001

976
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

Table 649: Inverse time characteristics for residual overvoltage protection


Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of Class 5 +40 ms
0.01
k
t =
æU -U >ö
ç ÷
è U> ø
EQUATION1436-SMALL V1 EN

U> = Uset
U = Umeasured

Type B curve: k = (0.05-1.10) in steps of


0.01
k × 480
t =
2.0
æ 32 × U - U > - 0.5 ö
ç ÷ - 0.035
è U > ø
EQUATION1437-SMALL V1 EN

Type C curve: k = (0.05-1.10) in steps of


0.01
k × 480
t =
3.0
æ 32 × U - U > - 0.5 ö
ç ÷ - 0.035
è U > ø
EQUATION1438-SMALL V1 EN

Programmable curve: k = (0.05-1.10) in steps of


0.01
k×A A = (0.005-200.000) in
t = +D steps of 0.001
P
æB × U - U > ö B = (0.50-100.00) in
ç -C÷
steps of 0.01
è U > ø
EQUATION1439-SMALL V1 EN
C = (0.0-1.0) in steps of
0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in
steps of 0.001

977
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

A070750 V2 EN

Figure 509: ANSI Extremely inverse time characteristics

978
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

A070751 V2 EN

Figure 510: ANSI Very inverse time characteristics

979
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

A070752 V2 EN

Figure 511: ANSI Normal inverse time characteristics

980
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

A070753 V2 EN

Figure 512: ANSI Moderately inverse time characteristics

981
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

A070817 V2 EN

Figure 513: ANSI Long time extremely inverse time characteristics

982
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

A070818 V2 EN

Figure 514: ANSI Long time very inverse time characteristics

983
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

A070819 V2 EN

Figure 515: ANSI Long time inverse time characteristics

984
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

A070820 V2 EN

Figure 516: IEC Normal inverse time characteristics

985
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

A070821 V2 EN

Figure 517: IEC Very inverse time characteristics

986
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

A070822 V2 EN

Figure 518: IEC Inverse time characteristics

987
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

A070823 V2 EN

Figure 519: IEC Extremely inverse time characteristics

988
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

A070824 V2 EN

Figure 520: IEC Short time inverse time characteristics

989
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

A070825 V2 EN

Figure 521: IEC Long time inverse time characteristics

990
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

A070826 V2 EN

Figure 522: RI-type inverse time characteristics

991
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

A070827 V2 EN

Figure 523: RD-type inverse time characteristics

992
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

GUID-ACF4044C-052E-4CBD-8247-C6ABE3796FA6 V1 EN

Figure 524: Inverse curve A characteristic of overvoltage protection

993
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

GUID-F5E0E1C2-48C8-4DC7-A84B-174544C09142 V1 EN

Figure 525: Inverse curve B characteristic of overvoltage protection

994
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

GUID-A9898DB7-90A3-47F2-AEF9-45FF148CB679 V1 EN

Figure 526: Inverse curve C characteristic of overvoltage protection

995
Technical reference manual
Section 22 1MRK505183-UEN C
Inverse time characteristics

GUID-35F40C3B-B483-40E6-9767-69C1536E3CBC V1 EN

Figure 527: Inverse curve A characteristic of undervoltage protection

996
Technical reference manual
1MRK505183-UEN C Section 22
Inverse time characteristics

GUID-B55D0F5F-9265-4D9A-A7C0-E274AA3A6BB1 V1 EN

Figure 528: Inverse curve B characteristic of undervoltage protection

997
Technical reference manual
998
1MRK505183-UEN C Section 23
Glossary

Section 23 Glossary

About this chapter


This chapter contains a glossary with terms, acronyms and abbreviations used in
ABB technical documentation.

AC Alternating current
ACT Application configuration tool within PCM600
A/D converter Analog to digital converter
ADBS Amplitude dead-band supervision
ADM Analog digital conversion module, with time synchronization
ANSI American National Standards Institute
AR Autoreclosing
ArgNegRes Setting parameter/ZD/
ArgDir Setting parameter/ZD/
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
AWG American Wire Gauge standard
BBP Busbar protection
BFP Breaker failure protection
BIM Binary input module
BOM Binary output module
BR External bi-stable relay
BS British standard
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signals
between IEDs
CAN Controller Area Network. ISO standard (ISO 11898) for
serial communication
CB Circuit breaker
CBM Combined backplane module

999
Technical reference manual
Section 23 1MRK505183-UEN C
Glossary

CCITT Consultative Committee for International Telegraph and


Telephony. A United Nations sponsored standards body
within the International Telecommunications Union.
CCM CAN carrier module
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI
CMPPS Combined mega pulses per second
CO cycle Close-open cycle
Co-directional Way of transmitting G.703 over a balanced line. Involves
two twisted pairs making it possible to transmit information
in both directions
COMTRADE Standard format according to IEC 60255-24
Contra-directional Way of transmitting G.703 over a balanced line. Involves
four twisted pairs of with two are used for transmitting data
in both directions, and two pairs for transmitting clock signals
CPU Central processor unit
CR Carrier receive
CRC Cyclic redundancy check
CS Carrier send
CT Current transformer
CVT Capacitive voltage transformer
DAR Delayed auto-reclosing
DARPA Defense Advanced Research Projects Agency (The US
developer of the TCP/IP protocol etc.)
DBDL Dead bus dead line
DBLL Dead bus live line
DC Direct current
DFT Discrete Fourier transform
DIP-switch Small switch mounted on a printed circuit board
DLLB Dead line live bus
DNP Distributed Network Protocol as per IEEE/ANSI Std.
1379-2000
DR Disturbance recorder
DRAM Dynamic random access memory
DRH Disturbance report handler
DSP Digital signal processor
DTT Direct transfer trip scheme

1000
Technical reference manual
1MRK505183-UEN C Section 23
Glossary

EHV network Extra high voltage network


EIA Electronic Industries Association
EMC Electro magnetic compatibility
EMF Electro motive force
EMI Electro magnetic interference
EnFP End fault protection
ESD Electrostatic discharge
FOX 20 Modular 20 channel telecommunication system for speech,
data and protection signals
FOX 512/515 Access multiplexer
FOX 6Plus Compact, time-division multiplexer for the transmission of
up to seven duplex channels of digital data over optical fibers
G.703 Electrical and functional description for digital lines used by
local telephone companies. Can be transported over balanced
and unbalanced lines
GCM Communication interface module with carrier of GPS
receiver module
GDE Graphical display editor within PCM600
GI General interrogation command
GIS Gas insulated switchgear
GOOSE Generic object oriented substation event
GPS Global positioning system
GSM GPS time synchronization module
HDLC protocol High level data link control, protocol based on the HDLC
standard
HFBR connector Plastic fiber connector
type
HMI Human machine interface
HSAR High speed auto reclosing
HV High voltage
HVDC High voltage direct current
IDBS Integrating dead band supervision
IEC International Electrical Committee
IEC 60044-6 IEC Standard, Instrument transformers – Part 6:
Requirements for protective current transformers for
transient performance

1001
Technical reference manual
Section 23 1MRK505183-UEN C
Glossary

IEC 60870-5-103 Communication standard for protective equipment. A serial


master/slave protocol for point-to-point communication
IEC 61850 Substation Automation communication standard
IEEE Institute of Electrical and Electronics Engineers
IEEE 802.12 A network technology standard that provides 100 Mbits/s on
twisted-pair or optical fiber cable
IEEE P1386.1 PCI Mezzanine card (PMC) standard for local bus modules.
References the CMC (IEEE P1386, also known as Common
mezzanine card) standard for the mechanics and the PCI
specifications from the PCI SIG (Special Interest Group) for
the electrical EMF Electro Motive Force.
IED Intelligent electronic device
I-GIS Intelligent gas insulated switchgear
IOM Binary input/output module
Instance When several occurrences of the same function are available
in the IED they are referred to as instances of that function.
One instance of a function is identical to another of the same
kind but will have a different number in the IED user
interfaces. The word instance is sometimes defined as an
item of information that is representative of a type. In the
same way an instance of a function in the IED is
representative of a type of function.
IP 1. Internet protocol. The network layer for the TCP/IP
protocol suite widely used on Ethernet networks. IP is a
connectionless, best-effort packet switching protocol. It
provides packet routing, fragmentation and re-assembly
through the data link layer.
2. Ingression protection according to IEC standard
IP 20 Ingression protection, according to IEC standard, level 20
IP 40 Ingression protection, according to IEC standard, level 40
IP 54 Ingression protection, according to IEC standard, level 54
IRF Internal fail signal
IRIG-B: InterRange Instrumentation Group Time code format B,
standard 200
ITU International Telecommunications Union
LAN Local area network
LIB 520 High voltage software module
LCD Liquid crystal display
LDCM Line differential communication module
LDD Local detection device

1002
Technical reference manual
1MRK505183-UEN C Section 23
Glossary

LED Light emitting diode


LNT LON network tool
LON Local operating network
MCB Miniature circuit breaker
MCM Mezzanine carrier module
MIM Milli-ampere module
MPM Main processing module
MVB Multifunction vehicle bus. Standardized serial bus originally
developed for use in trains.
NCC National Control Centre
NUM Numerical module
OCO cycle Open-close-open cycle
OCP Overcurrent protection
OEM Optical ethernet module
OLTC On load tap changer
OV Over voltage
Overreach A term used to describe how the relay behaves during a fault
condition. For example a distance relay is over-reaching
when the impedance presented to it is smaller than the
apparent impedance to the fault applied to the balance point,
i.e. the set reach. The relay “sees” the fault but perhaps it
should not have seen it.
PCI Peripheral component interconnect, a local data bus
PCM Pulse code modulation
PCM600 Protection and control IED manager
PC-MIP Mezzanine card standard
PISA Process interface for sensors & actuators
PMC PCI Mezzanine card
POTT Permissive overreach transfer trip
Process bus Bus or LAN used at the process level, that is, in near
proximity to the measured and/or controlled components
PSM Power supply module
PST Parameter setting tool within PCM600
PT ratio Potential transformer or voltage transformer ratio
PUTT Permissive underreach transfer trip
RASC Synchrocheck relay, COMBIFLEX

1003
Technical reference manual
Section 23 1MRK505183-UEN C
Glossary

RCA Relay characteristic angle


REVAL Evaluation software
RFPP Resistance for phase-to-phase faults
RFPE Resistance for phase-to-earth faults
RISC Reduced instruction set computer
RMS value Root mean square value
RS422 A balanced serial interface for the transmission of digital
data in point-to-point connections
RS485 Serial link according to EIA standard RS485
RTC Real time clock
RTU Remote terminal unit
SA Substation Automation
SC Switch or push-button to close
SCS Station control system
SCT System configuration tool according to standard IEC 61850
SLM Serial communication module. Used for SPA/LON/IEC
communication.
SMA connector Subminiature version A, A threaded connector with constant
impedance.
SMT Signal matrix tool within PCM600
SMS Station monitoring system
SNTP Simple network time protocol – is used to synchronize
computer clocks on local area networks. This reduces the
requirement to have accurate hardware clocks in every
embedded system in a network. Each embedded node can
instead synchronize with a remote clock, providing the
required accuracy.
SPA Strömberg protection acquisition, a serial master/slave
protocol for point-to-point communication
SRY Switch for CB ready condition
ST Switch or push-button to trip
Starpoint Neutral point of transformer or generator
SVC Static VAr compensation
TC Trip coil
TCS Trip circuit supervision
TCP Transmission control protocol. The most common transport
layer protocol used on Ethernet and the Internet.

1004
Technical reference manual
1MRK505183-UEN C Section 23
Glossary

TCP/IP Transmission control protocol over Internet Protocol. The de


facto standard Ethernet protocols incorporated into 4.2BSD
Unix. TCP/IP was developed by DARPA for internet
working and encompasses both network layer and transport
layer protocols. While TCP and IP specify two protocols at
specific protocol layers, TCP/IP is often used to refer to the
entire US Department of Defense protocol suite based upon
these, including Telnet, FTP, UDP and RDP.
TEF Time delayed earth-fault protection function
TNC connector Threaded Neill Concelman, A threaded constant impedance
version of a BNC connector
TPZ, TPY, TPX, Current transformer class according to IEC
TPS
Underreach A term used to describe how the relay behaves during a fault
condition. For example a distance relay is under-reaching
when the impedance presented to it is greater than the
apparent impedance to the fault applied to the balance point,
i.e. the set reach. The relay does not “see” the fault but
perhaps it should have seen it. See also Overreach.
U/I-PISA Process interface components that deliver measured voltage
and current values
UTC Coordinated universal time. A coordinated time scale,
maintained by the Bureau International des Poids et Mesures
(BIPM), which forms the basis of a coordinated
dissemination of standard frequencies and time signals. UTC
is derived from International Atomic Time (TAI) by the
addition of a whole number of "leap seconds" to synchronize
it with Universal Time 1 (UT1), thus allowing for the
eccentricity of the Earth"s orbit, the rotational axis tilt (23.5
degrees), but still showing the Earth"s irregular rotation, on
which UT1 is based. The Coordinated Universal Time is
expressed using a 24-hour clock and uses the Gregorian
calendar. It is used for aeroplane and ship navigation, where
it also sometimes known by the military name, "Zulu time".
"Zulu" in the phonetic alphabet stands for "Z" which stands
for longitude zero.
UV Undervoltage
WEI Weak end infeed logic
VT Voltage transformer
X.21 A digital signalling interface primarily used for telecom
equipment
3IO Three times zero-sequence current. Often referred to as the
residual or the earth-fault current

1005
Technical reference manual
Section 23 1MRK505183-UEN C
Glossary

3UO Three times the zero sequence voltage. Often referred to as


the residual voltage or the neutral point voltage

1006
Technical reference manual
1007
Contact us

1MRK505183-UEN C © Copyright 2010 ABB. All rights reserved.


ABB AB
Substation Automation Products
SE-721 59 Västerås, Sweden
Phone +46 (0) 21 32 50 00
Fax +46 (0) 21 14 69 18

www.abb.com/substationautomation

Vous aimerez peut-être aussi