HOTEL DESIGN REQUIREMENTS

Building Laws
PD 1096 (National Building Code)
GROUP A Residential Dwellings
Residentials, Hotels, & Apartments
GROUP B
shall be multiple dwelling units, accomodates 10 or more persons

1:3 for highly urbanized areas (car slot)


1:7 for other areas (car slot)
2 tourist bus parking slots for each hotel
1 loading slot for articulated truck or vehicle
PARKING REQUIREMENTS 1 accessible parking slot for 50-150 slots and additional slot for
every 100 thereafter
Car Parking Slot : 2.50m x 5.00m
Note : Accessible Parking Slot : 3.70m x 5.00m
Truck/Bus Slot : 3.60m x 12.00m

Front Side Rear


SETBACK R-3 max 8.00m 2.00m 2.00m
R-5 6.00m 3.00m 3.00m

Occupant Loads (area/person) 18.60 sqm per person

RA 9514 (Fire Code of the Philippines)


Type A Residential occupancies in w/c sleeping accommodations
Classification :
Type B HOTEL

SPACE REQUIREMENTS
Housekeeping Department Engineering and Maintenance
Back of the House Laundry Facilities Offices
Food and Beverage Services Employee Area
Entrance Dining Area
Front of the House Reception Area Function Halls
Lounging Area Rest Rooms

Elevator
Length 45 meters with sprinkler , 60 meters w/o sprinkler
Guest Floor Corridor Width 1.80m to 2.00m to be adequate
Setback doors 300mm to 600mm