Vous êtes sur la page 1sur 44

REINFORCED CONCRETE DESIGN Dr.

AHMED AJEL CH3

Strength Design Method


3.1 Strength Design Method
The Strength Design Method requires that the design strength of a
member at any section should equal or exceed the required strength
calculated by the code-specified factored load combinations. In general,

Design Strength ≥ Required Strength (U)

Where
Design Strength = Strength Reduction Factor (ϕ) x Nominal Strength
ϕ = Strength reduction factor that accounts for
1- the probability of understrength of a member due to variations in
material strengths and dimensions.
2- inaccuracies in the design equations.
3- the degree of ductility and required reliability of the loaded member.
4-the importance of the member in the structure.

Nominal Strength = Strength of a member or cross-section calculated


using assumptions and strength equations of the
Strength Design Method before application of any
strength reduction factors.

Required Strength (U) = Load factors x Service load effects.


The required strength is computed in accordance with the load
combinations.

Load Factor = Overload factor due to probable variation of service


loads.
Service Load = Load specified by general building code (unfactored).

Notations
Required strength:
Mu = factored moment (required flexural strength)
Pu = factored axial force (required axial load strength)
Vu = factored shear force (required shear strength)
Tu = factored torsional moment (required torsional strength)
Nominal strength:
Mn = nominal moment (required flexural strength)
Pn = nominal axial force (required axial load strength)
Vn = nominal shear force (required shear strength)
Tn = nominal torsional moment (required torsional strength)

1
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

Design Strength:
Φ Mn = design moment (required flexural strength)
Φ Pn = design axial force (required axial load strength)
Φ Vn = design shear force (required shear strength)
Φ Tn = design torsional moment (required torsional strength)

3.2 Loads
Loads that act on structures can be divided into three broad categories :
dead loads , live loads , and environmental loads.

3.2.1 Dead Load


Dead loads consist of the weight of all materials of construction
incorporated into the building including, but not limited to, wall, floors,
roofs, ceilings, stairways, built-in partition, finishes , cladding, and other
similarly incorporated architectural and structural items, and fixed service
equipment including the weight of cranes.
Dead loads can be determined with high degree of precision, although not
until after the structure has been designed. For this reason it is necessary
to estimate dead load before a structure analysis is made, in order that the
part of the internal forces due to weight can be taken into account.

2
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

Density of Building Materials


Building Materials kN/m2
Brick 18.63
Gypsum 11.77
Light Weight Concrete 16.67
Plain Concrete 22.65
Reinforced Concrete 23.54
Dry Soil 15.7
Hollow Block 13.73
Sand 15.7
Steel 76.99
Thermoston 8.83

3.2.2 Live Load


Live loads consist chiefly or partially of occupancy loads in buildings and
traffic loads on bridges. They may be either fully or partially in place or
not present at all, and may also change in location. Live load may be
steady or unsteady; they may be fixed, movable, or moving; they may be
applied slowly or suddenly. The live loads which usually be considered
are:
1- The weight of people, furniture, and machinery.
2- The weight of traffic on a bridge.
3- The weight of snow.
4- Dynamic forces resulting from moving loads.

3.2.3 Environmental Loads


Environmental loads consist mainly of snow loads, wind pressure and
suction, earthquake loads, soil pressure on subsurface portions of
structures, loads from possible ponding of rainwater on flat surfaces, and
forces caused by temperature differentials. Like live loads ,
environmental loads at any given time are uncertain in both magnitude
and distributions.

3
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

Minimum Distributed Live Load


Occupancy or Use kN/m2 Occupancy or Use kN/m2
1 Libraries 6 Hospitals
Reading rooms 2.87 Operation room, laboratories 2.87
Stack Rooms 7.18 Patient rooms 1.92
Corridors above first- 3.83 Corridors above first floor 3.83
floor
2 School 7 Hotels and multifamily houses
Class rooms 1.92 Private rooms and corridors 1.92
serving them
First-floor corridors 4.79 Public rooms and corridors 4.79
serving them
Corridors above first- 3.83 8 Office Buildings
floor
3 Stadiums and arenas Lobbies and first-floor 4.79
corridors
Bleachers 4.79 Offices 2.4
Fixed seats 2.87 Corridors above first-floor 3.83
4 Storage warehouses 9 Residential, (one and two family)
Light 6.0 Uninhabitable attics without 0.48
storage
Heavy 11.97 Uninhabitable attics with 0.96
storage
5 Stores Habitable attics and sleeping 1.92
areas
First floor 4.79 10 Manufacturing
Upper floors 3.59 Light 6.00
Wholesale, all floors 6.00 Heavy 11.97
ASCE Standard ,2005, "Minimum Design Loads for Buildings and Other Structure"

3.3 Required Strength (Load Factors)


As previously stated, the required strength U is expressed in terms of
factored loads, or their related internal moments and forces. Factored
loads are the service-level loads specified in the general building code,
multiplied by appropriate load factors in ACI Code section 9.2.
Load factors are numbers, almost larger than 1.0, which are used to
increase the estimated loads applied to structures. They are used for loads
applied to all types of members, not just beams and slabs. The loads are
increased to attempt to account for uncertainties involved in estimating
their magnitude
The ACI Code Section 9.2 prescribes load factors for specific
combinations of loads. A list of these combinations is shown below. The
numerical value of the load factor assigned to each type of load is
influenced by the degree of accuracy with which the load can usually be

4
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

assessed, the variation which may be expected in the load during the
lifetime of a structure and the probability of simultaneous occurrence of
different load types. Hence, dead loads, because they can usually be more
accurately determined and are less variable, are assigned a lower load
factor (1.2) as compared to live loads (1.6). Also, weight and pressure of
liquids with well-defined densities and controllable maximum heights are
assigned a reduced load factor of 1.2 due the lesser probability of
overloading. A higher load factor of 1.6 is required for earth and
groundwater pressures due to considerable uncertainty of their magnitude
and recurrence. Note that while most usual combinations of loads are
included, it should not be assumed that all cases are covered. Section 9.2
contains load combination as follows:

U = 1.4(D + F)…………………………………………………..…. (9-1)


U = 1.2(D + F + T) + 1.6(L + H) + 0.5(Lr or S or R)…………….. (9-2)
U = 1.2D + 1.6(Lr or S or R) + (1.0L or 0.8W)…………………... (9-3)
U = 1.2D + 1.6W + 1.0L + 0.5(Lr or S or R)……………………… (9-4)
U = 1.2D + 1.0E + 1.0L + 0.2S ………….…………………….……(9-5)
U = 0.9D + 1.6W + 1.6H …………………………………….……..(9-6)
U = 0.9D + 1.0E + 1.6H ……………………………………………(9-7)

Where:
D = dead loads, or related internal moments and forces.
E = load effects of seismic forces, or related internal moments and forces.
F = loads due to weight and pressures of fluids with well-defined
densities and controllable maximum heights, or related internal moments
and forces.
H = loads due to weight and pressure of soil, water in soil, or other
materials, or related internal moments and forces.
L = live loads, or related internal moments and forces.
Lr = roof live load, or related internal moments and forces.
R = rain load, or related internal moments and forces.
S = snow load, or related internal moments and forces.
T =cumulative effect of temperature, creep, shrinkage, differential
settlement, and shrinkage compensating concrete.
U = required strength to resist factored loads or related internal moments
and forces.
W = wind load, or related internal moments and forces.

5
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

Example 3.1
The axial loads for a building column have been estimated with the
following results: D = 150 kN, live load from roof Lr = 60 kN, live loads
from floors L = 300 kN, compression wind W = 70 kN, tensile wind W=
60 kN, seismic compression load = 50 kN, and tensile seismic load = 40
kN. Determine critical design load using the ACI load combinations.
Solution
(9-1) U = (1.4)(150 + 0) = 210 kN
(9-2) U = (1.2)(150 +0+0) +(1.6)(300 + 0) + (0.5)(60) = 690 kN
(9-3)(a) U = (1.2)(150) + (1.6)(60) + (1.0)(300) =576 kN
(b) U = (1.2)(150) + (1.6)(60) + (0.8)(70) = 332 kN
(c) U = (1.2)(150) + (1.6)(60) + (0.8)(-60) = 228kN
(9-4)(a) U = (1.2)(150) + (1.6)(70) + (1.0)(300) + (0.5)(60) = 622 kN
(b) U = (1.2)(150) + (1.6)(-60) + (1.0)(300) + (0.5)(60) = 414 kN
(9-5)(a) U = (1.2)(150) + (1.0)(50) + (1.0)(300) + (0.2)(0) = 530 kN
(b) U = (1.2)(150) + (1.0)(-40) + (1.0)(300) + (0.2)(0) = 440 kN
(9-6)(a) U = (0.9)(150) + (1.6)(70) +(1.6)(0) = 247 kN
(b) U = (0.9)(150) + (1.6)(-60) + (1.6) (0) = 39 kN
(9-7)(a) U = (0.9)(150) + (1.0)(50) + (1.6) (0) = 185 kN
(b) U = (0.9)(150) + (1.0)(-40) + (1.6) (0) = 95 kN

Answer : Largest value = 690 kN.

6
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

3.4 ACI Code Provisions (Design Strength)


The design strength provided by a member, its connections to other
members, and its cross-section, in terms of flexure, axial load, shear, and
torsion, is equal to the nominal strength calculated in accordance with
the provisions and assumptions stipulated in the code, multiplied by a
strength reduction factor ϕ, which is less than unity. The rules for
computing the nominal strength are based generally on conservatively
chosen limit states of stress, strain, cracking or crushing, and conform to
research data for each type of structural action.
The ACI Code provided for these variables by using the following
ϕ factors as provided below :
9.3.1 - Design strength provided by a member, its connections to
other members, and its cross sections, in terms of flexure, axial
load, shear, and torsion, shall be taken as the nominal strength
calculated in accordance with requirements and assumptions of
this Code, multiplied by the strength reduction factors ϕ in 9.3.2,
9.3.4, and 9.3.5.
9.3.2 - Strength reduction factor ϕ shall be as given in 9.3.2.1
through 9.3.2.7:
9.3.2.1 - Tension-controlled sections as
defined in 10.3.4 ....................................................0.90
(See also 9.3.2.7)
9.3.2.2 - Compression-controlled sections, as
defined in 10.3.3:
(a) Members with spiral reinforcement
conforming to 10.9.3............................................0.75
(b) Other reinforced members .................................0.65

For sections in which the net tensile strain in the extreme tension
steel at nominal strength, εt, is between the limits for compression-
controlled and tension-controlled sections, ϕ shall be permitted to
be linearly increased from that for compression-controlled sections
to 0.90 as εt increases from the compression-controlled strain limit
to 0.005.

9.3.2.3 - Shear and torsion .................................................0.75


9.3.2.4 - Bearing on concrete (except
for post-tensioned anchorage zones
and strut-and-tie models) ....................................0.65

9.3.2.5- Post-tensioned anchorage zones ………..…….....0.85

7
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

3.4.1 Compression-Controlled Sections


Sections are compression-controlled when the net tensile strain in
the extreme tension steel εt is equal to or less than the
compression-controlled strain limit at the time the concrete in
compression reaches its assumed strain limit of 0.003. The
compression-controlled strain limit is the net tensile strain in the
reinforcement at balanced strain conditions. For Grade 420
reinforcement, and for all prestressed reinforcement, it is
permitted to set the compression-controlled strain limit equal to
0.002.

3.4.2 Tension-Controlled Sections


Sections are tension-controlled when the net tensile strain in the extreme
tension steel is equal to or greater than 0.005 just as the concrete in
compression reaches its assumed strain limit of 0.003. Sections with net
tensile strain in the extreme tension steel between the compression-
controlled strain limit and 0.005 constitute a transition region between
compression-controlled and tension-controlled sections.

8
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

Figure below shows the stress and strain conditions at the limit for
tension-controlled sections. This limit is important because it is the limit
for the use of ϕ = 0.9 (9.3.2.1). Critical parameters at this limit are given
a subscript t.

9
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

3.5 Design Assumptions


1. A plane section before bending remains plane after bending.
2. Stresses and strain are approximately proportional up to moderate
loads (concrete stress 0.5 ́ ) . when the load is increased, the
variation in the concrete stress is no longer linear.
3. Tensile strength of concrete is neglected in the design of reinforced
concrete beams.
4. The maximum usable concrete compressive strain at the extreme
fiber is assumed equal to 0.003 .

5. The steel is assumed to be uniformly strained to the strain that


exists at the level of the centroid of the steel . Also if the strain in
the steel is less than the yield strain of the steel , then the
stress in the steel is . If , then the stress in steel will be
equal to .
6. The bond between the steel and concrete is perfect and no slip
occurs.

Stress in concrete & reinforcement may be calculated from the strains


using curves for concrete & steel. Compressive
relationship for concrete may be assumed to be any shape (rectangular,
trapezoidal, parabolic) that results in an acceptable prediction of strength.

11
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

3.5.1 Equivalent Stress Distribution


The actual distribution of concrete compressive stress is complex and
usually not known explicitly. Research has shown that the important
properties of concrete stress distribution can be approximated closely
using any one of several different assumptions as to the form of stress
distribution. The code permits any particular stress distribution to be
assumed in design if shown to result in predictions of ultimate strength in
reasonable agreement with the results of comprehensive tests. Many
stress distributions have been proposed . The three most common are the
parabola, trapezoid, and rectangle.

The compressive force is modeled as Cc = k1k3f’c b*c at the location


x = k2*c

The compressive coefficients of the stress block at given for the


following shapes. k3 is ratio of maximum stress at fc in the compressive
zone of a beam to the cylinder strength, f c’ (0.85 is a typical value for
common concrete).

11
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

3.5.2 Whitney's Rectangular Stress distributions


For purposes of simplification and practical application, a fictitious but
equivalent rectangular concrete stress distribution was proposed. This
rectangular stress distribution was proposed by Whitney (1942) and
subsequently adopted by the ACI Code.

- According to figure above the average stress distribution is taken


as :
́

- It is assumed to act over the upper area on the beam cross section
defined by width b and depth a as shown in figures above.
- The magnitude of a may determine by :

12
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

where :
c = distance from the outer fiber to the neutral axis
= a factor dependent on concrete strength, and is given by

́
{ ́
( ) ́

3.5.2.1 Requirements for Analysis of Reinforced Concrete Beams

[1] Stress-Strain Compatibility : Stress at a point in member must


correspond to strain at a point.

[2] Equilibrium : Internal forces balances with external forces.

3.5.2.2 Rectangular Reinforced Concrete Beam ( Single Reinforced


Section)

(1) From forces Equilibrium.

∑ ⇒

∑ ⇒ ( )

13
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

(2) Find flexural capacity.

By taking a moment at compression force location

( )

( )
́

( )
́

( )
́

( )
́

( )
́

́
For design use ( √ ́
)

14
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

3.5.3 Flexural Failure Consequence

There are three types of flexural failure of a structural member.

- Steel may reach its yield strength before the concrete reaches its
maximum. (Under-reinforced section).

Tension Failure

́ ́ ⇒ ́

- Concrete may fail before the yield of steel due to the presence of a high
percentage of steel in the section. (Over-reinforced section).

Compression Failure

15
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

- Steel reaches yield at same time as concrete reaches ultimate strength.


(Balanced section).

Hence we simply equate the previous two equations:

́ ́

3.5.4 Reinforcement Ratio Limitations

Which type of failure is the most desirable?

The under-reinforced beam is the most desirable.

16
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

fs = f y

>>

You want ductility → system deflects and still carries load.

Although failure due to yielding of the steel is gradual with adequate


warning of collapse, failure due to crushing of the concrete is sudden and
without warning.
The steel ratio (sometimes called reinforcement ratio) for rectangular
section is given by:

[1] Maximum steel ratio:

The under reinforced beam is preferred and ensured by the specifications


of the ACI.

- To ensure the section is always still as under reinforced section the ACI
Code limited a minimum tensile strain from it we can derive
a relation which give the maximum steel ratio which limited the section
to be always still under reinforced section as :
́

Substitute and
́

- The ACI Code further encourage the use of lower reinforcement ratios
by allowing higher strength reduction factors in such sections. The Code
defines a tension controlled member as having a net tensile strain greater
than or equal to corresponding strength reduction factor is
ϕ = 0.9 , so maximum reinforcement ratio for tension-controlled beam is:
́

Substitute and
17
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

[2] Minimum steel ratio

The ACI Code establishes a lower limit on the amount of tension


reinforcement. The code states that where tension reinforcement is
required , the reinforcement area shall not less that given by :
√́

Where

- For a statically determinate beam with a flange in tension, the value of


bw shall be the lesser of bf and 2bw.

If As (provided) 4/3 As (required) based on analysis, then As (min) is


not required.
4
 Mn  Mu
3

- Temperature and Shrinkage reinforcement in structural slabs and


footings ACI place perpendicular to direction of flexural reinforcement.
For fy=280 or 300 MPa (GR 40 or GR 50 Bars):

As (T&S) = 0.0020 Ag

For fy=420 or 300 MPa (GR 60 or Welded Wire Fabric (WWF)):

As (T&S) = 0.0018 Ag

Ag - Gross area of the concrete.

- The steel ratio provided for sections shall be between max. and min.
limits of ACI Code.

18
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

3.5.5 SECTIONS WITH MULTIPLE LAYERS OF STEEL

The simple and conservative way to design a beam with two


layers of tension steel is to take d t equal to d, the depth to the
centroid of all the tension steel. However, the code does permit
the designer to take advantage of the fact that d t, measured to the
center of the layer farthest from the compression face, is greater
than d. The only time this would be necessary is when designing
at or very close to the strain limit of 0.005 for tension-controlled
sections.

Therefore, the maximum steel ratio for


beam with multiple layers of steel is:

3.5.6 Strength Reduction Factor ϕ


Calculation of the nominal moment capacity frequently involves
determination of the depth of equivalent rectangular stress block a . Since
, it is some times more convenient to compute ratios
than either or the net tensile strain. The assumption that p[lane sections
remain plane ensure a direct correlation between net tensile and the
ratios, as shown in Figure below( for Fy = 420 MPa ) .

19
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

- For the section is tension control.

- For and (Fy = 420 MPa) the section is compression control.

- In general , with any value of Fy the section is

compression control.

- For between the range of tension control and compression control


(transition) the value of ϕ can be evaluated by linear interpolation for any
value as:

1- For other sections

( )
( )

2- For spiral sections

( )
( )

21
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

Example 3.2
Find the ACI design moment capacity of the beam shown in Figure,
use ́ and .

Solutions:

( )

Checking Steel Percentage

√́

The section is Tension Control

( )

( )

21
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

Example 3.3

Determine the ACI design moment capacity of the beam shown in


Figure, if ́ and .

Solutions:
Checking Steel Percentage

√́

⇒ The section is Tension Control

( )

( )

22
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

Example 3.4
For the beam cross section shown in Figure, Calculate the ACI design
moment capacity , if ́
(a) 20.7 MPa
(b) 34.5 MPa
(c) 62.1 MPa
Solutions:
(a) ́
Checking Steel Percentage

√́

⇒ The section is Compression-Control .

Hence the beam is not ductile and does not satisfy the ACI 318 Code.
23
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

(b) ́

Checking Steel Percentage

√́

Hence the beam is ductile, but in the transition zone with less
than 0.90.

( )
( )
( )
( )

24
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

( )

( )

(c) ́
Checking Steel Percentage

√́

Hence the beam is ductile, tension controlled, with = 0.90.

The section is tension control, .

( )

( )

25
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

3.5.7 Adequacy of Sections

A given section is said to be adequate if the internal moment strength of


the section is equal to or greater than the applied forced moment, or
. The procedure can be summarized as follows:

1. Calculate the external applied factored moment,

2. calculate for the basic singly reinforced section:

a. Check that .

b. Calculate ́
and check for .

c. Calculate ( ).

3. if , then the section is adequate .

26
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

Assignment (2)

H.W1 : An 2.44 m span cantilever beam has a rectangular section and


reinforcement as shown in Figure. The beam carries a dead load ,
including its own weight of 2 kN.m and a live load of 1.22 kN.m. Using
́ , check if the beam is safe to carry
the above loads.

H.W.2: A simply supported beam has a span of 6.1 m . If the cross


section of the beam is as shown in figure, ́
, determine the allowable uniformly distributed service live
load on the beam assuming the dead load that due to beam weight.

Given : b = 305 mm , d= 432 mm, total depth h= 508 mm, and reinforced
with three no. 8 bars (As = 1529 mm2).

H.W.3: Check the design adequacy of the section in Figure to resist a


factored moment Mu = 40.68 kN.m , using ́
.

27
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

H.W.4: Determine the design moment strength of a rectangular concrete


section reinforced with four no. 9 bars in one row.

Given : b = 305 mm , d= 419 mm, total depth h= 483 mm, and reinforced
with three no. 9 bars ́ .

H.W.5: Determine the design moment strength of a rectangular concrete


section reinforced with six no. 9 bars in two rows.

Given : b = 305 mm , dt = 622 mm, total depth h= 686 mm, and


reinforced with three no. 9 bars ́ .

28
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

3.5.8 Details of Reinforcement

Good reinforcement details are vital to satisfactory performance of


reinforced concrete structures. Standard practice for reinforcing steel
details has evolved gradually. The Building Code Committee (ACI 318)
continually collects reports of research and practice related to structural
concrete, suggests new research needed, and translates the results into
specific code provisions for details of reinforcement.

Recommended methods and standards for preparing design drawings,


typical details, and drawings for the fabrication and placing of reinforcing
steel in reinforced concrete structures are given in the ACI Detailing
Manual, reported by ACI Committee 315.
 Standard hooks
The requirements for standard hooks for reinforcing bars are illustrated in
Figures below shows the requirements for primary reinforcement and for
stirrups and ties. The standard hook details for stirrups and ties apply to
No. 8 and smaller bar sizes only.
7.1 — Standard hooks
The term “standard hook” as used in this Code shall
mean one of the following:
7.1.1 — 180-degree bend plus 4db extension, but not
less than 65 mm at free end of bar.
7.1.2 — 90-degree bend plus 12db extension at free
end of bar.

7.1.3 — For stirrup and tie hooks


(a) No. 16 bar and smaller, 90-degree bend plus 6db
extension at free end of bar; or
(b) No. 19, No. 22, and No. 25 bar, 90-degree bend
plus 12db extension at free end of bar; or
(c) No. 25 bar and smaller, 135-degree bend plus
6db extension at free end of bar.

29
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

 Minimum bend diameters


Minimum bend diameter for a reinforcing bar is specifi ed as “the
diameter of bend measured on the inside of the bar.” Minimum bend
diameters, expressed as multiples of bar diameters, are dependent on bar
size; for No.3 to No. 8 bars, the minimum bend diameter is 6 bar
diameters; for No. 9 to No. 11 bars, the minimum bend diameter is 8 bar
diameters; and for No. 14 and No. 18 bars, the minimum bend diameter is
10 bar diameters. Exceptions to these provisions are:
7.2 — Minimum bend diameters
7.2.1 — Diameter of bend measured on the inside of
the bar, other than for stirrups and ties in sizes No. 10
through No. 16, shall not be less than the values in
Table 7.2.
7.2.2 — Inside diameter of bend for stirrups and ties
shall not be less than 4db for No. 16 bar and smaller.
For bars larger than No. 16, diameter of bend shall be
in accordance with Table 7.2.
7.2.3 — Inside diameter of bend in welded wire
reinforcement for stirrups and ties shall not be less
than 4db for deformed wire larger than MD40 and 2db
for all other wires. Bends with inside diameter of less
than 8db shall not be less than 4db from nearest
welded intersection.

Bending

 Bending Reinforcement
All reinforcement must be bent cold unless otherwise permitted by the
licensed design professional. For unusual bends, special fabrication
including heating may be required and the licensed design professional
must give approval to the techniques used.
7.3 — Bending
7.3.1 — All reinforcement shall be bent cold, unless
otherwise permitted by the licensed design professional.
7.3.2 — Reinforcement partially embedded in
concrete shall not be field bent, except as shown on
the design drawings or permitted by the licensed

31
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

design professional.
 Spacing Limits for Reinforcement

The arrangement of bars within a beam must allow sufficient concrete on


all sides of each bar to transfer forces into or out of bars , sufficient space
so that the fresh concrete can be placed or consolidated around all the
bars, and sufficient space to allow an internal vibrator to reach through to
the bottom of the beam. Pencil type concrete immersion vibrators used in
consolidation of the fresh concrete are (4-6 cm) in diameter. Enough
space should be provided between the beam bars to allow a vibrator to
reach the bottom of the form in at least one place in the beam width. ACI
Code Sections 3.3.2, 7.6.1, and 7.6.2 specify the spacing and
arrangements shown in figure below.

3.3.2 — Nominal maximum size of coarse aggregate


shall be not larger than:
(a) 1/5 the narrowest dimension between sides of
forms, nor
(b) 1/3 the depth of slabs, nor
(c) 3/4 the minimum clear spacing between individual
reinforcing bars or wires, bundles of bars, individual
tendons, bundled tendons, or ducts.
These limitations shall not apply if, in the judgment of
the licensed design professional, workability and
methods of consolidation are such that concrete can
be placed without honeycombs or voids.

31
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

7.6 — Spacing limits for reinforcement


7.6.1 — The minimum clear spacing between parallel
bars in a layer shall be db, but not less than 25 mm.
See also 3.3.2.
7.6.2 — Where parallel reinforcement is placed in two
or more layers, bars in the upper layers shall be placed
directly above bars in the bottom layer with clear
distance between layers not less than 25 mm.

7.6.3 — In spirally reinforced or tied reinforced


compression members, clear distance between longitudinal
bars shall be not less than 1.5db nor less than
40 mm. See also 3.3.2.
7.6.4 — Clear distance limitation between bars shall
apply also to the clear distance between a contact lap
splice and adjacent splices or bars.
7.6.5 — In walls and slabs other than concrete joist
construction, primary flexural reinforcement shall not
be spaced farther apart than three times the wall or
slab thickness, nor farther apart than 450 mm.

32
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

 Bundled bars
For isolated situations requiring heavy concentration of reinforcement,
bundles of standard bar sizes can save space and reduce congestion for
easier placement and consolidation of concrete. In those situations,
bundling of bars in columns is a means to better locating and orienting
the reinforcement for increased column capacity; also, fewer ties are
required if column bars are bundled.
Bundling of bars (parallel reinforcing bars in contact, assumed to act as a
unit) is permitted, provided specific limitations are met. The limitations
on the use of bundled bars are as follows:

7.6.6 — Bundled bars


7.6.6.1 — Groups of parallel reinforcing bars
bundled in contact to act as a unit shall be limited to
four in any one bundle.
7.6.6.2 — Bundled bars shall be enclosed within
stirrups or ties.
7.6.6.3 — Bars larger than No. 36 shall not be
bundled in beams.

33
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

 Concrete Protection for Reinforcement

It is necessary to have cover (concrete between the surface of the slab or


beam and the reinforcement) for four primary reasons:

1. To bond the reinforcement to the concrete so that the two elements


act together. The efficiency of the bond increases as the cover
increase. A cover of at least one bar diameter is required for this
purpose in beams and columns.
2. To protect the reinforcement against corrosion .
3. To protect the reinforcement from strength loss due to overheating
in case of fire. The cover for fire protection is specified in the local
building code. Generally speaking,20 mm cover to the
reinforcement in structural slab will provide a 1 hour fire rating,
while 40 mm cover to the stirrups or tie of beams corresponding to
a 2-hour fire rating.
4. Additional cover sometimes is provided on the top of slabs,
particularly in garages and factories, so that abrasion and wear due
to traffic will not reduce the cover below that required for
structural and other purposes.

The amount of clear cover (is measured from the concrete surface to the
outermost surface of the steel to which the cover requirement applies)
will be based on ACI Code Section 7.7.1.

7.7 — Concrete protection for reinforcement


7.7.1 — Cast-in-place concrete (nonprestressed)
Unless a greater concrete cover is required by 7.7.6 or
7.7.8, specified cover for reinforcement shall not be
less than the following:
Concrete
cover, mm
(a) Concrete cast against and
permanently exposed to earth ............................................ 75
(b) Concrete exposed to earth or weather:
No. 19 through No. 57 bars ..................................................50
No. 16 bar, MW200 or MD200 wire, and smaller…………...40
(c) Concrete not exposed to weather
or in contact with ground:
Slabs, walls, joists:
No. 43 and No. 57 bars .........................................................40

34
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

No. 36 bar and smaller.........................................................20


Beams, columns:
Primary reinforcement, ties, stirrups,
spirals ..................................................................................40
Shells, folded plate members:
No. 19 bar and larger ..........................................................20
No. 16 bar, MW200 or MD200 wire, and smaller ………....13

Preliminary Beam and Slab Dimensions for Control of Deflections

Estimations Beam Self Weight

If the dimensions of the beam was chosen in analysis it can be used for
calculation of the beam self- weight . The estimate the dimensions for
self-weight can be by rules of thumb and engineering judgment. The
weight of a rectangular beam will be about 15 % of the superimposed
loads (dead, live, etc.). Assume b is about one-half of h . The preferred
economical ratio between the beam depth and width b is between (2)
and (3), if there is no architectural aspects .

The deflections of a beam can be calculated from equations of the form

Rearranging this and making assumptions concerning strain distributions


and neutral-axis depth eventually gives an equation of the form

Thus, for any acceptable ratio of deflection to span length, , it should


be possible to specify span to-to-depth ratios, , which if exceeded may
result in unacceptable deflections. It can be suggested that typical beam
depths range between and , the selected beam depth , , will
need to be checked against the minimum member thicknesses (depth, )
given in the second row of ACI Table 9.5 (a) for member not supporting
partitions or other construction that are likely to be damaged by
deflections.

35
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

 Estimating the effective Depth of a Beam

It is generally satisfactory to estimate the effective depth of a beam


using the following approximations:

For beams with one layer of reinforcement,

For beams with two layers of reinforcement,

For one-way slabs with spans up to 3.5m,

For one –way slabs with spans up to 3.5m,

It is important not to overestimate , because normal construction


practice may lead to smaller value of than are shown on the drawings.
Generally speaking , beam width b should not less than 25 cm , although
with two bars, beams width as low as 18 cm can be used in extreme
cases.

36
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

3.5.9 Design

The design of reinforced concrete members mean that the computations


of proper sections dimensions and the amount of steel reinforcement
required so that the structural member can resist the ultimate factored
applied load safely. The ultimate strength for steel and concrete and the
service loading should be, in some cases the all or some of section
dimensions may be decided by architectural limits. The full design
process accomplished by computing the required steel for stirrups to
resist shear and torsion and checking the deflections and also checking
development lengths and points of cut or bend for steel , all of this should
be draw then on beam section .

 Design of Beams when Section Dimensions are Known

in this case ( )are known , and it only necessary to


compute . This is actually a very common case for continuous
members where the same size will be used in both positive and negative
bending regions and may be used for several of the typical beam spans in
a floor system. These dimensions may be established by architectural
limits on member dimensions or may be established by designing the
section of the beam that is resisting the largest bending moment.

Example 3.5
Evaluate the steel area required for Simply Supported beam shown use
bars with , the concrete strength ̇ . The
beam span 5 m and carry loads (without self-weight),
.

Solutions

37
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

Assume (tension control section)

́
( √ )
́

Assume one layer


( √ )

Check if tension control ( )

⇒ The section is tension control, the assumption is


correct.

Check the steel limits

√́

Use the maximum value

O.K.

38
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

No. of bars ⇒

( )
Check bar spacing

( )

O.K.

Within the ACI Spacing limits

39
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

Example 3.6

Find the necessary reinforcement for a given section, b = 380 mm, h =


510 mm. If it is subjected to a factored moment of 435 kN.m, the
concrete strength ̇ and .

Solutions:
Assume (tension control section)

́
( √ )
́

Assume one layer


( √ )

Check if tension control ( )

The section is in the transition zone.

Use # 32 bars

No. of bars

41
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

Hence the beam is ductile, but in the transition zone with less
than 0.90.

( )
( )
( )
( )

( )

( )

Check bar spacing:


( )

O.K.

41
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

 Design of Beams when Section Dimensions are Not Known

The second type of section design problem involves finding .


Three decisions must be made here, that is, a preliminary estimate of the
self-weight of the beam, selection of a target steel percentage, and final of
the section dimensions ( )

Example 3.7
Design a rectangular beam for 10 m simple span to support a dead load of
20 kN/m (not including beam weight ) and live load of 30 kN/m . use
, the concrete strength ̇ .

Solutions:
Assume that the beam weight is .

Assume ( ) and use


́
( ) ( )

( ) ( )

( )

From the equation below , find

( )
́

( )

42
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

224.32

We chose then find {


Use 500 mm x 800 mm section (d=680 mm)

Beam weight

( )( )( )

Use # 32 bars

No. of bars ⇒

Check the steel limits

√́

Use the maximum value

O.K.

( )
Check bar spacing

43
REINFORCED CONCRETE DESIGN Dr. AHMED AJEL CH3

( )

O.K.

Within the ACI Spacing limits

Use six 32 bars in two rows (4914 mm2).

44

Vous aimerez peut-être aussi