Fire Hydrant System

February 2018, Kalidasan S

Restricted © Siemens AG 20XX siemens.tld/keyword

Restricted © Siemens AG 20XX


Page 1 January 2018 I BT SSP-OP
Overview of Fire Protection

Today most of the equipment's used in offices, Industries and at home are highly sophisticated and
high-end equipment's. Every workplace has mission critical areas that need to be protected from fire
hazard not only to save life and property but also to ensure that the enterprise does not come to a
stand still.

The most common fuels in fire and explosion incidents are petroleum products, cellulose materials
(wood, paper, cloth) and polymers.

Restricted © Siemens AG 20XX


Page 2 January 2018 I BT SSP-OP
The Combustion Process

The combustion process will continue as long as the conditions or a chemical reaction exist

Extinguishment can be achieved by removal of any 1 or more elements:


Heat, Fuel or Oxygen

Restricted © Siemens AG 20XX


Page 3 January 2018 I BT SSP-OP
Type of Fire Protection Systems

Fire
Protection System

Water Gas
Based System Based Systems

Restricted © Siemens AG 20XX


Page 4 January 2018 I BT SSP-OP
Water based Systems

Water Based Systems

Yard
Wet Riser Sprinkler Spray Foam
Hydrant
System System System System
System

Restricted © Siemens AG 20XX


Page 5 January 2018 I BT SSP-OP
STANDARDS/CODES FOLLOWED FOR FIRE FIGHTING SYSTEM

Restricted © Siemens AG 20XX


Page 6 January 2018 I BT SSP-OP
HAND HELD EXTINGUISHERS

Restricted © Siemens AG 20XX


Page 7 January 2018 I BT SSP-OP
Types of Fires & Media

Suitable Media

Water

Foam

Gas

DCP

Wet Chemical
Restricted © Siemens AG 20XX
Page 8 January 2018 I BT SSP-OP
TYPE OF EXTINGUISHERS TO BE USED

Restricted © Siemens AG 20XX


Page 9 January 2018 I BT SSP-OP
TYPE OF EXTINGUISHERS TO BE USED

Restricted © Siemens AG 20XX


Page 10 January 2018 I BT SSP-OP
EXTINGUISHER OPERATION

Restricted © Siemens AG 20XX


Page 11 January 2018 I BT SSP-OP
EXTINGUIHSER OPERATION

Restricted © Siemens AG 20XX


Page 12 January 2018 I BT SSP-OP
EXTINGUIHSER OPERATION

Restricted © Siemens AG 20XX


Page 13 January 2018 I BT SSP-OP
SIGNAGE FOR FIRE EXTINGUISHER

Restricted © Siemens AG 20XX


Page 14 January 2018 I BT SSP-OP
EXTINGUISHER IMAGES

Restricted © Siemens AG 20XX


Page 15 January 2018 I BT SSP-OP
EXTINGUISHER IMAGES

Restricted © Siemens AG 20XX


Page 16 January 2018 I BT SSP-OP
FIRE HYDRANT SYSTEM

Restricted © Siemens AG 20XX


Page 17 January 2018 I BT SSP-OP
HYDRANT SYSTEM

Network of piping installed underground or overhead around various facilities with


hydrant stand posts fitted with landing valves at regular intervals or at distances from
the protected risks according to the occupancies.

Restricted © Siemens AG 20XX


Page 18 January 2018 I BT SSP-OP
HYDRANT SYSTEM

COMPONENTS

PUMPS

Jockey pump
Electrical pump
Diesel Pump

Heavy or Medium Grade


MS or GI PIPES

Restricted © Siemens AG 20XX


Page 19 January 2018 I BT SSP-OP
HYDRANT SYSTEM

COMPONENTS

HYDRANT VALVES

HOSE BOXES

HOSES

NOZZLES & BRANCH PIPES

Restricted © Siemens AG 20XX


Page 20 January 2018 I BT SSP-OP
HYDRANT SYSTEM

COMPONENTS

FIRE BRIGADE INLET

ISOLATION VALVES

AIR RELEASE VALVE

Restricted © Siemens AG 20XX


Page 21 January 2018 I BT SSP-OP
HYDRANT SYSTEM

COMPONENTS

WATER MONITOR FOAM MONITOR

Restricted © Siemens AG 20XX


Page 22 January 2018 I BT SSP-OP
HYDRANT SYSTEM
COMPONENTS

WRAPPING & COATING


(Under Ground PIPES

PEDESTAL
(Above Ground PIPES)

UNDER GROUND
VALVE CHAMBER

Restricted © Siemens AG 20XX


Page 23 January 2018 I BT SSP-OP
FIRE PUMP ROOM

Restricted © Siemens AG 20XX


Page 24 January 2018 I BT SSP-OP
COMPONENTS OF PUMP ROOM

PUDDLE FLANGES

SUCTION SIDE VALVES

Y-STRAINER

JOCKEY PUMP TO
MAINATAIN LINE PRESSEURE

ELECTRICAL PUMPS
FOR HYDRANT & SPRINKLERS

Restricted © Siemens AG 20XX


Page 25 January 2018 I BT SSP-OP
COMPONENTS OF PUMP ROOM

DIESEL ENGINE PUMP FOR


SPRINKLER & HYDRANTS

Restricted © Siemens AG 20XX


Page 26 January 2018 I BT SSP-OP
COMPONENTS OF PUMP ROOM

NON RETURN VALVE


DELIVERY SIDE
ISOLATION VALVES
TEST ARRAY LINE
PRESSURE GUAGE
PRESSURE SWITCH

FLOW METER

Restricted © Siemens AG 20XX


Page 27 January 2018 I BT SSP-OP
PUMP MCC PANELS

Restricted © Siemens AG 20XX


28
Page 28 January 2018 I BT SSP-OP
OPERATING PRESSURE

PUMPS PRESSURE (KG/ SQ.CM)

JOCKEY 8 KG/ SQ.CM

ELECRICAL 5 KG/ SQ.CM

DIESEL 4 KG/ SQ.CM

Restricted © Siemens AG 20XX


Page 29 January 2018 I BT SSP-OP
PUMPS OPERATION

PUMPS ON OFF

JOCKEY AUTO AUTO

ELECRICAL AUTO MANUAL

DIESEL AUTO MANUAL

Restricted © Siemens AG 20XX


Page 30 January 2018 I BT SSP-OP
PUMP ROOM LAYOUT

Restricted © Siemens AG 20XX


31
Page 31 January 2018 I BT SSP-OP
PUMP ROOM LAYOUT - POSITIVE SUCTION

Restricted © Siemens AG 20XX


32
Page 32 January 2018 I BT SSP-OP
POSITIVE SUCTION

Restricted © Siemens AG 20XX


Page 33 January 2018 I BT SSP-OP
PUMP ROOM LAYOUT - NEGATIVE SUCTION

Restricted © Siemens AG 20XX


34
Page 34 January 2018 I BT SSP-OP
DESIGN CRITERIA

TYPES OF HAZARD

MODERATE (OR) HIGH HAZARD –


LIGHT HAZARD STORAGE HAZARD
ORDINARY HAZARD A&B

EG:HOSPITALS,HOTELS EG:TEXTILE ,PAPER MILLS EG:PAINT


,INSTITIUTIONS,LIBRA , CHEMICAL UNITS
,ENGINEERING WORK
FACTORIES,OIL EG:WARE
RIES,LAUNDRIES,MUSE MILLS,PETROCHEMICA
UMS AND NURSING SHOP,LABORITIES,WAX,
LS AND REFINERIES
HOUSES
HOMES,OFFICE VERMICELLY AND
BUILDING,PRIOSNS , PRINTING PRESS,ETC.
SCHOOL AND
COLLEGS,ETC

Restricted © Siemens AG 20XX


Page 35 January 2018 I BT SSP-OP
HYDRANT DESIGN CRITERIA

Type of Hazard being protected (light or ordinary or high hazard)


Number of hydrants required for all the facilities
Adequate sizing of pipes in the hydrant network to achieve appropriate
discharge
Assumption of two simultaneous major fires in vulnerable areas
Combined protection of tankages and pressured storage vessels by water
spray systems

Restricted © Siemens AG 20XX


Page 36 January 2018 I BT SSP-OP
HYDRANT DESIGN CRITERIA

Combined protection of tankages by foam systems


Protection of transformers, cable cellars etc., by water spray systems
Adequate selection of fire water pumps
Provision of water for the installed pumping capacity
Trained manpower to handle disastrous situations
Other relevant considerations if any for the type of risk
Compliance to relevant codes for design

Restricted © Siemens AG 20XX


Page 37 January 2018 I BT SSP-OP
Hydrant Placement

Yard hydrants At every 45, 30M periphery of the buildings for light,
ordinary and high hazard risks situated between 1.5 M to 15M from
external walls

Internal Hose reels to be provided that no part of the building inside is at


more than 30M from the nearest internal Hose reel
Upper floors : All upper floors shall be protected with hydrant wetrisers,
landing valves located at each landing of external/protected internal
staircases as below:

Restricted © Siemens AG 20XX


Page 38 January 2018 I BT SSP-OP
Hydrant System

Restricted © Siemens AG 20XX


Page 39 January 2018 I BT SSP-OP
Wet Riser System

Restricted © Siemens AG 20XX


Page 40 January 2018 I BT SSP-OP
Spray System for LPG Bullets

Restricted © Siemens AG 20XX


Page 41 January 2018 I BT SSP-OP
Spray System for the LPG Sphere

Restricted © Siemens AG 20XX


Page 42 January 2018 I BT SSP-OP
PUMP CAPACITY

A) Light Hazard
Number of Hydrants Pump Capacity (M3 per hour at Kg/cm2)
Up to 20 96 M3 per hour at 5.6 Kg/cm2
More than 20 and up to 55 137 M3 per hour at 7 Kg/cm2
More than 20 and up to 55 171 M3 per hour at 7 Kg/cm2
More than 100 171 M3 per hour plus additional 171 M3 per hour for every
125 hydrants or part thereof at 7/8.8 Kg/cm2
Water requirement shall be at least 1 hour of pump run subject to a minimum of 135M3
B) Ordinary Hazard
Number of Hydrants Pump Capacity (M3 per hour at Kg/cm2)
Up to 20 137 M3 per hour at 7 Kg/cm2
More than 20 and up to 55 171 M3 per hour at 7 Kg/cm2
More than 20 and up to 55 273 M3 per hour at 7 Kg/cm2
More than 100 273 M3 per hour plus additional 273 M3 per hour for every
125 hydrants or part thereof at 7/8.8 Kg/cm2
Water requirement shall be at least 2 hours pump Run
Restricted © Siemens AG 20XX
Page 43 January 2018 I BT SSP-OP
PUMP CAPACITY

C) High Hazard - A
Number of Hydrants Pump Capacity (M3 per hour at Kg/cm2)
Up to 20 171 M3 per hour at 7 Kg/cm2
More than 20 and up to 55 273 M3 per hour at 7/8.8 Kg/cm2
More than 20 and up to 55 410 M3 per hour at 7/8.8 Kg/cm2
More than 100 410 M3 per hour plus additional 171 M3 per hour for every
125 hydrants or part thereof at 7/8.8/10.5 Kg/cm2
Water requirement shall be at least 3 hours pump Run
D) High Hazard - B
Number of Hydrants Pump Capacity (M3 per hour at Kg/cm2)
Upto 20 Two of 171 M3 per hour at 7 Kg/cm2
More than 20 and up to 55 Two of 273 M3 per hour at 7/8.8 Kg/cm2
More than 20 and up to 55 Two of 410 M3 per hour at 7/8.8 Kg/cm2
More than 100 Two of 410 M3 per hour plus additional 410 M3 per hour
for every 200 hydrants or part thereof at 8.8/10.5 Kg/cm2
Water requirement shall be at least 4 hours pump Run
Restricted © Siemens AG 20XX
Page 44 January 2018 I BT SSP-OP
PIPE SIZING
(WHEN THE NUMBER OF HYDRANTS IS LESS THAN 100)

Number of hydrants in Size of Mains Percentage of all mains


the whole system in mm including terminals and
risers

1 to 5 100 100%
6 to 20 100 60%
125 40%
21 to 55 100 45%
125 35%
150 20%
56 to 100 100 35%
125 40%
150 25%

Restricted © Siemens AG 20XX


Page 45 January 2018 I BT SSP-OP
YARD HYDRANT

Restricted © Siemens AG 20XX


Page 46 January 2018 I BT SSP-OP
YARD HYDRANT

Restricted © Siemens AG 20XX


Page 47 January 2018 I BT SSP-OP
YARD HYDRANT

Restricted © Siemens AG 20XX


Page 48 January 2018 I BT SSP-OP
DOWN COMER SYSTEM

Restricted © Siemens AG 20XX


50
Page 50 January 2018 I BT SSP-OP
WET RISER SYSTEM

Restricted © Siemens AG 20XX


51
Page 51 January 2018 I BT SSP-OP
HYDRANT SYSTEM LAYOUT

Restricted © Siemens AG 20XX


52
Page 52 January 2018 I BT SSP-OP
Foam System

Foam is a blanking agent and the principle of extinguishment is oxygen


exclusion coupled with the prevention of hydrocarbon fuel vapors
being released from fire and the cooling effects of the water content.

Restricted © Siemens AG 20XX


Page 53 January 2018 I BT SSP-OP
Foam System

Therefore it is mainly used for fighting fires on flammable liquids. In


modern foam systems, foam concentrate is mixed with water, usually in the
ratio from 3% to 6% and passed through an aerating device so creating a
foam which can have expansion ratios varying from
7.5% to 20 Low expansion
20 to 250 Medium expansion
250 to 1000 High expansion

Restricted © Siemens AG 20XX


Page 54 January 2018 I BT SSP-OP
Foam System

The quantity of foam required is different for variety of risks and different
types of tanks. The application time is also specified in relevant codes

The stock of foam compound to be maintained shall be equivalent to at


least two times the requirement of the tank needing maximum quantity of
foam.

Restricted © Siemens AG 20XX


Page 55 January 2018 I BT SSP-OP
Foam System for Oil Tank

Restricted © Siemens AG 20XX


Page 56 January 2018 I BT SSP-OP
IMAGES OF FOAM MONITOR

Restricted © Siemens AG 20XX


58
Page 58 January 2018 I BT SSP-OP
59

Thank You

Restricted © Siemens AG 20XX