1
Goal of this document

 To help the Vijeo Citect 7.0 new user to design his first project,
starting from scratch

 To help the Vijeo Citect 7.0 new user to take benefits of the
packaged features that are Unity SpeedLink and OFS

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 2


Vijeo Citect 7.0: features

 Vijeo Citect 7.0 proposes a new native tool to directly populate the Vijeo
Citect 7.0 tags database from the variables of a Unity application

 This tool is the Unity SpeedLink Static

 The preferred communication link between Vijeo Citect 7.0 and the Unity
PLC is OFS 3.31 that comes with Vijeo Citect 7.0

 Of course, advanced users can still define other communication


architectures according to their needs

 Vijeo Citect 7.0 now manages clusters, and a cluster must be defined
even for a stand alone system

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 3


Steps described in this document

 Vijeo Citect 7.0 installation

 Creation of
 a new project, and PC configuration in order to run it;
 an I/O device, and its tags definition from the PLC variables

 Definition of
 Alarms and Trends
 Pages
 Users

 Introduction to
 Genies
 Device

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 4


Tools used

 Vijeo Citect 7.0

 OFS 3.31, that comes with Vijeo Citect 7.0

 Unity 3.0

 The Unity Pro 3.0 Demo application for the M340 PLC

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 5


Vijeo Citect 7.0: before the installation

 If you already have OFS installed and registered on


the PC, first uninstall it

 In Windows, Start  Settings  Control Panel

 Select Add/Remove Programs

 Uninstall OPC Factory Server

 Uninstall OFS Configuration Tool

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 6


Vijeo Citect 7.0: before the installation

 Uninstall Vijeo Citect 6.1

 Uninstall all the companion tools you installed with


Vijeo Citect 6.1

 Web Server

 Knowledge base

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 7


Vijeo Citect 7.0: installation

 Run the SETUP

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 8


Vijeo Citect 7.0: installation

 Take time to read the documentation, then <Next>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 9


Vijeo Citect 7.0: installation

 Accept the license agreement, then <Next>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 10


Vijeo Citect 7.0: installation

 Select <Server> environment, then <Next>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 11


Vijeo Citect 7.0: installation

 Unselect <Web Server> feature if Internet Information


Services is not installed on the PC, then <Next>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 12


Vijeo Citect 7.0: installation

 Select the installation folders, then <Next>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 13


Vijeo Citect 7.0: installation

 Select the options folder, then <Next>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 14


Vijeo Citect 7.0: installation

 Click <Install> to start the installation

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 15


Vijeo Citect 7.0: installation

 If Dot Net 2.0 is missing, the installer will install it

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 16


Vijeo Citect 7.0: installation

 After the completion of the installation, click <Finish>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 17


Vijeo Citect 7.0: Project Explorer

 Start the Vijeo Citect Explorer

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 18


Vijeo Citect 7.0: Project Explorer

 Right click on <My Projects>  <New Project>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 19


Vijeo Citect 7.0: Project Explorer

 Give your <XP_Style> project name and description

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 20


Vijeo Citect 7.0: Project Explorer

 Switch to the Project Editor tool

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 21


Vijeo Citect 7.0: Cluster definition

 A cluster is a discrete group of alarms servers, trends


servers, reports servers, and I/O servers

 It would usually also possess local Vijeo Citect display


clients

 For a plant comprising several individual sections or


systems, multiple clusters can be used, one cluster for
each section

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 22


Vijeo Citect 7.0: Cluster definition

 From the <Servers> menu, select <Clusters>, even for


a Stand Alone architecture

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 23


Vijeo Citect 7.0: Cluster definition

 Give the cluster a name and a comment, then <Add>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 24


Vijeo Citect 7.0: Network Addresses definition

 From the <Servers> menu, select <Network


Addresses>, enter the IP address of the PC, then
<Add>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 25


Vijeo Citect 7.0: IOServer definition

 From the <Servers> menu, select <I/O Servers>,


select the cluster, enter a name, select the network
address, then <Add>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 26


Vijeo Citect 7.0: Alarm Server definition

 From the <Servers> menu, select <Alarm Servers>,


select the cluster, enter a name, select the network
address, then <Add>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 27


Vijeo Citect 7.0: Trend Server definition

 From the <Servers> menu, select <Trend Servers>,


select the cluster, enter a name, select the network
address, then <Add>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 28


Vijeo Citect 7.0: from Unity variables to tags

 For each PLC application variable, Unity proposes a


<Custom> field you can use to store any comment

 Vijeo Citect 7.0 SpeedLink uses this Unity <Custom>


to filter the PLC variables intended to be tags in the
SCADA project

 Let <Custom> blank for “no tag from this variable”, or


set it to “VJC” to create a tag, to “VJA” to create an
Alarm, to “VJT” to create a Trend

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 29


Vijeo Citect 7.0: from Unity variables to tags

 This is what can be defined

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 30


Unity 3.0: exporting data from the PLC project

 Right click on <Variables & FB instances>export

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 31


Unity 3.0: exporting using XSY format

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 32


Unity 3.0: set autosaving Unity files options

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 33


OFS 3.31 configuration tool: define M340 alias

Select
the XVM
file as
symbols
file

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 34


OFS 3.31 configuration tool: define network and
address for the Unity Simulator

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 35


OFS 3.31 testing client: check the alias before
using it in the SCADA

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 36


Vijeo Citect 7.0: creating an I/O Device

 Use the Express I/O Device Setup wizard

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 37


Vijeo Citect 7.0: creating an I/O Device

 This wizard will configure the I/O device

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 38


Vijeo Citect 7.0: creating an I/O Device

 Use the already defined I/O Server

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 39


Vijeo Citect 7.0: creating an I/O Device

 Create a new I/O Device

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 40


Vijeo Citect 7.0: creating an I/O Device

 Select a new External I/O Device

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 41


Vijeo Citect 7.0: creating an I/O Device

 Select OPC as the driver communication model

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 42


Vijeo Citect 7.0: creating an I/O Device

 Click <Next> to accept OFS as OPC server

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 43


Vijeo Citect 7.0: creating an I/O Device

 Do not link the I/O Device

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 44


Vijeo Citect 7.0: creating an I/O Device

 Click on <Finish> to commit the configuration

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 45


Vijeo Citect 7.0: communication model

1 3

2 Set this
parameter to 4
1000 for a
1000 ms
OFS group
rate

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 46


Vijeo Citect 7.0: importing tags

 From Projects Explorer, select ToolsImport Tags

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 47


Vijeo Citect 7.0: importing tags

 Define the parameters as below, click <Import>

Reminder:
Unity Pro XSY
export format is Add
available from any ExCustom=?*;
Unity Pro 3.0 grade
but STU link is only
available
From
Unity Pro 3.0 XL!

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 48


Vijeo Citect 7.0: configuring the computer

 From <Tools>, run the <Computer Setup Editor>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 49


Vijeo Citect 7.0: adding OPC parameters
Add OPC,
UseOPC2,
value 1
Add
OPCAccessPaths,
<IOServer>
<IODevice>
=
<OFS Alias>
FileSave to
save your
changes

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 50


Vijeo Citect 7.0: creating the first page

 Switch to Graphics Builder

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 51


Vijeo Citect 7.0: creating the first page

 Switch to Graphics Builder, add a new page

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 52


Vijeo Citect 7.0: creating the first page

 Select a <normal> template using the <XP_Style>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 53


Vijeo Citect 7.0: adding the first graphic object

 Add a rectangle, select <Filled> appearance option

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 54


Vijeo Citect 7.0: adding the first animation

 In the <Fill> tab, select <On/Off> type, and browse the tags

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 55


Vijeo Citect 7.0: saving the page

 Close and save the page

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 56


Vijeo Citect 7.0: compiling the project

 Compile the project before choosing it as the project to run

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 57


Vijeo Citect 7.0: defining a role for the computer

 Run the <Computer Setup Wizard>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 58


Vijeo Citect 7.0: choosing <Setup> and project

 Run the <Computer Setup Wizard>, select <Express Setup>,


select the project to run

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 59


Vijeo Citect 7.0: network setup

 Select <Server and Display Client>, then <No networking>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 60


Vijeo Citect 7.0: committing setup

 Select <Finish>, the PC is ready to run the project!

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 61


Vijeo Citect 7.0: running the project

 Right click on <Project>, select <Run>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 62


Vijeo Citect 7.0: DEMO mode

 With no license key, the system will prompt

 Click <OK> to run the project in DEMO mode during 15 minutes

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 63


Vijeo Citect 7.0: OFS debug window

OPC group for


Vijeo Citect
OPC client

Group rate as
defined in the
Board

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 64


Vijeo Citect 7.0: what is automatically created

 From the Unity variables, the <Import> feature creates tags

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 65


Vijeo Citect 7.0: what is automatically created

 From the variables stamped “VJA” or “VJT”, the <Import> feature


creates Digital Alarms and Trends

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 66


Vijeo Citect 7.0: completing trend definition

 From the project Editor, click on Main MenuTagsTrend Tags


 Press <F2> to display the lower half of the form, then complete
the trend as shown

1 second sampling

periodic sampling

2 external files filled in 24


hours (circular buffers)

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 67


Vijeo Citect 7.0: check DATA folder

 Run the project, then list the files located in DATA folder

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 68


Vijeo Citect 7.0: display trend page

 Open the <Single Trend> page and right click on the first pen to
select it

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 69


Vijeo Citect 7.0: select a pen

 Select the trend for this pen

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 70


Vijeo Citect 7.0: changing the scale

 Select the trend for this pen


Click
there to
set 100%
scale
value

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 71


Vijeo Citect 7.0: creating a user

 From the project editor, select Main MenuSystemUsers

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 72


Vijeo Citect 7.0: creating a user

 From the project editor, select Main MenuSystemUsers


 Define a <kernel> with a password and all the 8 distinct privileges
 The < kernel > user can browse the project with no restriction

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 73


Vijeo Citect 7.0: Administrator logon

 Run the project


 Log on the SCADA system using <kernel> account
 Once the user is logged, his name is displayed

1 2 3

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 74


Vijeo Citect 7.0: Administrator logon

 Once the user with privileges is logged, a right click on an alarm


line displays the Alarm menu, from which you can Acknowledge
them

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 75


Vijeo Citect 7.0: creating a genie

 A Genie is a combination of several objects grouped and saved


as a single object to be reused from a library

 You can define a Genie when you plan to use a lot of times the
same group of object

 A variable can be directly assigned to an animation in a Genie

 A Genie also accepts string substitution to be substituted when


an instance of the Genie is created

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 76


Vijeo Citect 7.0: creating a genie

 From the Graphics Builder, select <NEW> then <Genie>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 77


Vijeo Citect 7.0: creating a genie

 Paste a symbol, select a tank from a <Tanks> library, then draw


a rectangle inside the tank

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 78


Vijeo Citect 7.0: creating a genie

 Set <Filled> appearance option for the rectangle

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 79


Vijeo Citect 7.0: creating a genie

 Select a tag to fill the level

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 80


Vijeo Citect 7.0: creating a genie

 Replace M340_Material_A by %PLC%_%PROCESS%

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 81


Vijeo Citect 7.0: creating a library

 Close and save the Genie


 You are prompted to create a new library

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 82


Vijeo Citect 7.0: saving the Genie

 Create the new library then save the Genie

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 83


Vijeo Citect 7.0: creating instances of the Genie

 Open the page previously created and select the genie from the
library

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 84


Vijeo Citect 7.0: creating instances of the Genie

 You are prompted to substitute %PLC% and %PROCESS% in


order to assign a valid tag name used for the animation!

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 85


Vijeo Citect 7.0: creating instances of the Genie

 Copy and paste a second instance of the genie, then assign


%PLC% and %PROCESS% in order to bind a second valid tag

When you assign


strings for
substitution, the
resulting tag is
immediately
checked!

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 86


Vijeo Citect 7.0: devices

 Mouse or keyboard input can trigger a message to be sent to a


log device via the MsgLog field

 The log device must also be defined with MsgLog as one of the
format fields

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 87


Vijeo Citect 7.0: devices

 From the Project Editor, open the Devices Editor

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 88


Vijeo Citect 7.0: devices

 Device an ASCII device as shown below

Format: {Date,10,R} {Time,8,R},{MsgLog,32},{Arg1,6,R},{UserName,16},{Page,16}

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 89


Vijeo Citect 7.0: command from graphics

 Open the previous page and add a <Number>

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 90


Vijeo Citect 7.0: command from graphics

 Define an <Input> key sequence for the <Enter> command and a


Log message

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 91


Vijeo Citect 7.0: tool tip text and Log Device

 In the <Access> tab, enter a tool tip text and select the Log
Device

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 92


Vijeo Citect 7.0: command from graphics

 Run the project, log on using <kernel> account, then set the
value

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 93


Vijeo Citect 7.0: Log file

 From DATA folder, open the CommandLog.TXT file

Automation Business Unit – SCADA Department – Patrick Bourges - October 2007 94