Vous êtes sur la page 1sur 2

Jiangxi Sunyuang Electric Power

KYN28 6KV No. SY-QPR-81-050


Co., LTD.
Switchgear Factory Versio
QPR Record File Inspection Reports B/1
n
Type 型 号 规 格: 出厂编号 Factory No:
Item Technical Requirement Data Resu
lt
1、Electrical equipment and components, components should be correct, the connection
should be solid and reliable. All should be in line with the drawings requirements. Main,
auxiliary circuit wiring is correct and in accordance with the drawings requirements.
一、General 所装电器设备及部件、元件应正确,连接应牢固可靠,符合图纸要求。主、辅电路接线
inspection; 正确并符合图纸要求。
一般检查 2、Cabinet shape installation dimensions in line with the drawings, technical documents.
Nameplate, symbols and signs accurate, clear, complete, the installation location is correct.
柜体外形安装尺寸符合图纸、技术文件要求。铭牌、符号及标志准确、清晰、齐全、安
装位置正确。
3、The connection of the ground wire and the terminal should be firm and reliable, and the
cross section meets the relevant requirements.
接地线与接线端子的连接应牢固、可靠,截面符合相关要求。
4、The inner and outer surfaces of the cabinet should be smooth, non-corrosive, coating
peeled off and bump damage. The paint used meets the requirements of technical
documents, the coating should be firm, uniform, no significant color and reflective.
柜体的内外表面应平整、光洁、无锈蚀、涂层脱落和磕碰损伤。所用涂料符合技术文件
的要求,涂层应牢固、均匀、无明显色差和反光。
1、Mechanical properties of switches, earthing switches, mechanical operating elements,
latches, and other components under specified operating conditions shall be in accordance
二、Functional with their respective technical conditions.
test 开关、接地开关、机械操作元件、锁扣、等部件在规定的操作条件下的机械特性,应符
功能试验 合各自技术条件。
2、 Switch no-load operation, interlocking operation, manual sub-5 times, indicating correct,
sub-normal without card stagnation, loose phenomenon.
开关空载分合操作、联锁操作,手动分合 5 次,指示正确,分合正常无卡滞、松动现象。
3、 Push and pull the vacuum circuit breaker, 25 times each, It should be flexible and reliable,
the valve division normal, no delay.
手车推进、推出各 25 次,应灵活可靠,活门分合正常、无卡滞。
1、35Kv side of the main circuit to the ground and the phase to phase 85Kv / 1min, no
二 、 Main, breakdown, discharge phenomenon
auxiliary 35Kv 侧主回路对地及相间 85Kv/1min,无击穿、放电现象。
circuit, power 2、10Kv side of the main circuit to the ground and the phase to phase 85Kv / 1min, no
frequency breakdown, discharge phenomenon
withstand 10Kv 侧主回路对地及相间 42Kv/1min,无击穿、放电现象。
voltage test 3、6Kv side of the main circuit to the ground and the phase to phase 85Kv / 1min, no
主、辅回路, breakdown, discharge phenomenon
工频耐压试 6Kv 侧主回路对地及相间 32Kv/1min,无击穿、放电现象。
验 4、Cabinet 10Kv transformer Oil transformer is 35Kv / 1min, no breakdown, discharge
high-voltage side to ground phenomenon.
柜内 10Kv 变压 油变为 35Kv/1min,无击穿、放电现象。

1
Jiangxi Sunyuang Electric Power
KYN28 6KV No. SY-QPR-81-050
Co., LTD.
Switchgear Factory Versio
QPR Record File Inspection Reports B/1
n
器高压侧对地 Dry transformer is 28Kv / 1min, no breakdown, discharge
phenomenon.
干变为 28Kv/1min 无击穿、放电现象。
5、Auxiliary circuit directly connected with the main circuit, withstand voltage test 2500V / 1s,
no breakdown, discharge phenomenon
对与主电路直接连接的辅助电路耐压试验 2500V/1s,无击穿、放电现象。
6、Auxiliary circuit not connected directly with the main circuit withstand voltage test 1500V /
1s, no breakdown, discharge phenomenon.
对不与主电路直接连接的辅助电路耐压试验 1500V/1s,无击穿、放电现象。
7、Cabinet 35Kv cable voltage withstand test 52.5Kv / 1min, no breakdown, discharge
phenomenon
柜内 35Kv 电缆耐压试验 52.5Kv/1min,无击穿、放电现象。
8、Cabinet 10Kv cable voltage test 18Kv / 1m, no breakdown, discharge phenomenon.
柜内 10Kv 电缆耐压试验 18Kv/1m,无击穿、放电现象。
四 、 Main 1、A 相电阻值 A phase resistance≤150μ Ω 。
circuit 2、B 相电阻值 B phase resistance≤150μ Ω 。
resistance 3、C 相电阻值 C phase resistance≤150μ Ω 。
measurement
主回路电
阻测量
1、 Circuit breaker open and close 5 times, indicating correct, without stagnation, loose
phenomenon.
断路器电动分合 5 次正常、指示正确,分合无卡滞、松动现象。
2、All kinds of indicating instruments, measuring instruments work properly, the auxiliary
五 、 Power switch moves correctly
and 各种指示仪表、计量仪表工作正常,辅助开关动作正确。
protection 3,Overcurrent protection is Overcurrent protection action is normal 过流保护动作正常
action test normal 过电流保护正常 Quick break protection action is normal 速断保护动作正常
通电及保护 Heavy gas protection action is normal 重瓦斯保护动作正常
动作试验 4,Non-power protection is 轻瓦斯发信正常 Light gas signal sent normally
normal Temperature protection action is normal 温度保护动作正常
非电量保护正常 Temperature signal action is normal 温度发信正常
5、Differential protection is normal 差动保护正常
6、Zero sequence protection is 零序电流保护正常
normal 零序保护正常 零序电压保护正常
7、Other protection is normal 其他保护正常:
结 论 经检验:该产品符合 GB3906-2006 标准的要求,准予出厂。
Conclusion THE PRODUCT IS IN CONFORMITY WITH THE TECHINICAL STANDARD, AND IT IS PERMITTED TO LEAVE
THE FACTORY.

检验员/日期 Inspector/ Date:

Vous aimerez peut-être aussi