Vous êtes sur la page 1sur 13

2

1 A100 2 2 1 E D C B A
3.50 14.00
3.50 0.50 3.83 2.27 6.40 1.50

0.27
Roof Roof
5.40 5.40
A

2.40

2.40
1.50

W3

B D1
Level 2 Level 2
W2 3.00 3.00
3

3.00

3.00
A100
D2
6.40

Level 1 Level 1
0.10

0.10
0.00 0.00
W1

NORTH ELEVATION EAST ELEVATION


5 4
14.00

1 : 100 1 : 100
REF.
C 1 2 A B C D E
3.50 14.00
1.20 2.30
2.27

W1

D3
1.50 6.40 2.27 3.83
0.27

Roof
D
0.26

Roof
5.40
5.40
2.40

W1

2.40
D4
3.83

D3
Level 2
Level 2
3.00
3.00
D5
0.95

3.00

E
3.00

W1

1.40 2.10
Level 1
0.10

Level 1
0.10

0.00
0.00

FLOOR PLAN LEVEL 01 SOUTH ELEVATION WEST ELEVATION


1 6 2
1 : 100 1 : 100 1 : 100

11/30/2018 5:14:59 PM
OWNER: ENGINEER: PROJECT TITLE: SHEET CONTENTS: NO. DESCRIPTION DATE

JUDA G. COLLAMAR CHRISTIAN G. GODINO SINGLE STOREY


FLOOR PLAN A101
NORTH/SOUTH ELEVATION
RES. CERT.: TIN: PRC REG. NO.: TIN: RESIDENTIAL BUILDING EAST/WEST ELEVATION Drawn by N.Onoy
TCT NO: DATE: PTR. NO.: DATE: LOCATION: SAN ANTONIO, NORTHERN SAMAR Scale 1 : 100
TABLE OF CONTENTS Republic of the Philippines
OFFICE OF THE BUILDING OFFICIAL
ARCHITECTURAL
A100 PERSPECTIVE VIEW, TABLE OF CONTENT,
CROSS SECTION, LONGITUDINAL SECTION
FLOOR PLAN, NORTH/SOUTH
A101 ELEVATION, EAST/WEST ELEVATION
DETAIL OF KITCHEN, DETAIL OF TOILET
A102 & BATHROOM SAN ANTONIO, NORTHERN SAMAR
A103 SCHEDULE OF DOORS AND WINDOWS District /City / Municipality

LAND USE & ZONING

STRUCTURAL LINE & GRADE


S100 GENERAL NOTES

S101 GENERAL NOTES

PLAN OF COLUMN, COLUMN


S102 SCHEDULE
DETAIL OF COLUMN C1,
S103 DETAIL OF COLUMN C7
FOUNDATION PLAN, FOOTING
S104 SCHEDULE, DETAIL OF FC1
PLAN OF BEAM Lv 0.00,BEAM
S105 SCHEDULE, DETAIL OF BEAM
PLAN OF BEAM Lv 3.00, BEAM ARCHITECTURAL
S106 SCHEDULE, DETAIL OF BEAM
PLAN OF SLAB, SLAB SCHEDULE, PLAN
S107 OF TRUSS, DETAIL OF TRUSS

2 1 A B C D E STRUCTURAL

14.00
3.50
1.50 6.40 2.27 3.83
Roof
5.40 ELECTRICAL
0.
2.40

2.40

50

0.50
SEE TRUSS ELECTRICAL
DETAIL SEE TRUSS DETAIL
Level 2
0.06

3.00
3.00
2.94

PLUMBING
PLUMBING PLAN LV 01, ISOMETRIC VIEW,
P100
Level 1 DETAIL OF SEPTIC TANK
0.10

0.10

SANITARY
0.00

CROSS SECTION LONGITUDINAL SECTION


3 2
1 : 100 1 : 100

11/30/2018 5:13:23 PM
OWNER: ENGINEER: PROJECT TITLE: SHEET CONTENTS: NO. DESCRIPTION DATE

JUDA G. COLLAMAR CHRISTIAN G. GODINO SINGLE STOREY


PERSPECTIVE VIEW A100
TABLE OF CONTENT
RES. CERT.: TIN: PRC REG. NO.: TIN: RESIDENTIAL BUILDING CROSS SECTION Drawn by N.Onoy
LONGITUDINAL SECTION
TCT NO: DATE: PTR. NO.: DATE: LOCATION: SAN ANTONIO, NORTHERN SAMAR Scale 1 : 100
5 2 2 C
A102
0.30 0.91 1.12 0.91

Level 2 Level 2
3.00 3.00

0.86

0.86
4

0.76

0.76
A102

0.46

0.46
0.91

0.91
REF.
Level 1 Level 1
C 0.61
0.00 0.00

KITCHEN DETAIL KITCHEN CROSS SECTION KITCHEN LONGITUDINAL SECTION


3 4 5
1 : 50 1 : 50 1 : 50

2 D
2.30 1.90
6 2
A102 1.30 1.00 1.10 0.70

Level 2 Level 2
3.00 3.00
D
3.00

2
A102 1.70

Level 1 Level 1
0.00 0.00

TOILET & BATHROOM DETAIL T&B CROSS SECTION T&B LONGITUDINAL SECTION
1 2 6
1 : 50 1 : 50 1 : 50

11/30/2018 5:13:24 PM
OWNER: ENGINEER: PROJECT TITLE: SHEET CONTENTS: NO. DESCRIPTION DATE

JUDA G. COLLAMAR CHRISTIAN G. GODINO SINGLE STOREY


KITCHEN DETAIL A102
TOILET & BATHROOM
RES. CERT.: TIN: PRC REG. NO.: TIN: RESIDENTIAL BUILDING DETAIL Drawn by N.Onoy
TCT NO: DATE: PTR. NO.: DATE: LOCATION: SAN ANTONIO, NORTHERN SAMAR Scale 1 : 50
MARK D1 DESCRIPTION MARK D2 DESCRIPTION MARK D3 DESCRIPTION MARK D4 DESCRIPTION MARK D5 DESCRIPTION

PRE- FABRICATED PRE- FABRICATED PRE- FABRICATED PVC DOOR PRE- FABRICATED
WOODEN POWDER COATED WOODEN COMPLETE WITH WOODEN
PANEL DOOR OR 10mm THK. TINTED FLUSH DOOR OR JAMB, HINGES AND FLUSH DOOR OR
APPROVED GLASS PANEL APPROVED LOCKSET HOLE OR APPROVED
EQUAL. DOUBLE SLIDING EQUAL. APPROVED EQUAL. EQUAL.
DOOR OR APPROVED
EQUAL.

QUANTITY QUANTITY QUANTITY QUANTITY QUANTITY

- ONE (1) SET - ONE (1) SET - TWO (2) SET - ONE (1) SET - ONE (1) SET
0.86
1.01 0.76
1.73 0.55

LOCATION LOCATION LOCATION LOCATION LOCATION

GROUND FLOOR GROUND FLOOR GROUND FLOOR GROUND FLOOR GROUND FLOOR
- MAIN ENTRANCE - DINING ROOM - BEDROOM 01 - TOILET & BATHROOM - BEDROOM 01
- BEDROOM 02

2.13
2.13

2.13

2.03
2.13
HARDWARE HARDWARE HARDWARE HARDWARE HARDWARE

-SCHLAGE F-SERIES -PRIME-LINE C 1032 -SCHLAGE F- -SCHLAGE F- -SCHLAGE F-


619 CALLINGTON KEYED SLIDING SERIES 605 KNOB SERIES 626 KNOB SERIES 626 KNOB
LEVER STYLE DOOR HANDLE SET GREGORIAN STYLE BELL STYLE BELL STYLE

-6 PCS. 3 1/2"X3 1/2" -3 PCS. 3 1/2"X3 1/2"


STAINLESS STEEL STAINLESS STEEL
HAGER LOOSE PIN HAGER LOOSE PIN
BUTT HINGES OR BUTT HINGES OR
APPROVED EQUAL APPROVED EQUAL

MARK W1 DESCRIPTION MARK W2 DESCRIPTION MARK W3 DESCRIPTION MARK DESCRIPTION MARK DESCRIPTION

POWDER COATED POWDER COATED POWDER COATED


ALUMINUM DOUBLE ALUMINUM SINGLE ALUMINUM TRANSOM
SHUTTER WITH SHUTTER WITH WITH TRIM WINDOW
MULLION WINDOW MULLION WINDOW WITH 6mm THK.
WITH 6mm THK. WITH 6mm THK. TINTED GLASS
TINTED GLASS TINTED GLASS PANELS.
PANELS. PANELS.

QUANTITY QUANTITY QUANTITY QUANTITY QUANTITY

- FOUR (4) SET - ONE (1) SET - ONE (1) SET

0.88
0.55 0.55 0.63

LOCATION LOCATION LOCATION LOCATION LOCATION


0.42

GROUND FLOOR GROUND FLOOR GROUND FLOOR


- LIVING ROOM - LIVING ROOM - LIVING ROOM
1.15

1.38

- BEDROOM 02
1.61
0.82

0.59

11/30/2018 5:13:24 PM
OWNER: ENGINEER: PROJECT TITLE: SHEET CONTENTS: NO. DESCRIPTION DATE

JUDA G. COLLAMAR CHRISTIAN G. GODINO SINGLE STOREY


SCHEDULE OF DOORS AND A103
WINDOWS
RES. CERT.: TIN: PRC REG. NO.: TIN: RESIDENTIAL BUILDING Drawn by Author
TCT NO: DATE: PTR. NO.: DATE: LOCATION: SAN ANTONIO, NORTHERN SAMAR Scale As indicated
1 2

2"ø Vent
C old
tic
mes r
Do Wate
1"ø
ary 1"ø
anit Do
øS m
2" Wa estic
ter Co
ld
3"ø
Sa
nit
ary

1"ø Domestic Cold


C 0.15 1.05 0.15 0.55 0.15
2"ø Sanitary

Water
1.20 0.70

10MM Ø DEF.BARS SPACED @


0.15 M. O.C.
0.15 1.05 0.15 0.55 0.15

0.15
0.30
3"ø Sanitary

0.15
4"Ø PVC PIPE
0.50
INFLOW OUTFLOW
D 1"ø Domestic Cold
Water
1"ø Domestic Cold

0.75
3"ø Sanitary

1.43
INFLOW OUTFLOW
DIGESTIVE LEACHING
Water

CHAMBER CHAMBER

0.40

0.15
E
2% SLOP

0.20

0.20
DETAIL OF SEPTIC TANK
3
1 : 25 0.40
SUPPLY
FROM WATER

TO SEPTIC

10MM Ø DEF.BARS 3-10MMØ HOR. BARS W/


SPACED @ 0.15 M. O.C. 10MM Ø TRANSVERSE
TANK

BARS @ 0.30M. O.C.


PLUMBING NOTES

1. GRADES OF HORIZONTAL PIPINGS 4. PIPE CLEAN-OUTS CLEAN-OUTS ARE REQUIRED UNDER THE F0LLOWING CONDITIONS:
RUN ALL HORIZONTAL PIPINGS IN PERPECT ALIGNMENT AND AT A FORM GRADE NOT LESS THAN TWO PERCENT (2%). a) EVERY CHANGE OF HORIZONTAL DIRECTION EXCEEDING TWENTY TWOAND ONE-HALF DEGREES (22 1/2°).
b) ONE AND ONE-HALF METERS (1.50m.) INSIDE THE PROPERTY LINES BEFORE THE HOUSE DRAINAGE CONNECTION.
2. CHANGE IN DIRECTION c) EVERY FIFTEEN METERS (15.00m) IN HORIZONTAL RUN OF PIPES.
ALL CHANGE IN DIRECTION SHALL BE MADE BY APPROPRIATE USE OF FORTY-FIVE DEGREES (45°) WYES, LONG d) AT THE END OF ANY HORIZONTAL PIPE LINES.
PLUMBING PLAN LEVEL 01 SWEEP QUARTER BEND, SIXTH-EIIGHT OR SIXTEENTH BEND. WHEN THE CHANGE OF FLOW IS FROM HORIZONTAL TO
1 VERTICAL A SINGLE 1/8 BEND COMBINATION MAYBE USED ON VERTICAL STACKS AND SHORT QUARTER BENDS MAYBE 5. THE DIGESTION CHAMBER OF SEPTIC VAULT MUST BE WATERPROOFED.
1 : 50 USED ON WASTE LINE, TEE AND CROSSES MAYBE USED IN BENT PIPES.
6. NOT LESS THAN 0.30 METER OF AIR SPACE MUST BE LEFT BETWEEN THE TOP OF THE SEWAGE AND THE UNDER PART
3. PROHIBITED FITTINGS OF VAULT ROOF SLAB.
NO DOUBLE HUB OR TEE BRANCH SHALL BE USED ON HORIZONTAL SOIL AND WASTE LINES, THE DRILLINGS AND
TAPPING OF HOUSE DRAIN, WASTE OR VENT PIPES AND USED OF SADDLE HUB AND BEND ARE PROHIBITED. 7. NO SEPTIC VAULT SHALL BE CONSTRUCTED UNDER THE BUILDING.

8. ALL PLUMBING WORKS SHALL BE UNDER THE SUPRVISION OF A LICENSED MASTER PLUMBER AND A LICENCED
PLUMBING CONTRACTOR.

11/30/2018 5:13:25 PM
OWNER: ENGINEER: PROJECT TITLE: SHEET CONTENTS: NO. DESCRIPTION DATE

JUDA G. COLLAMAR CHRISTIAN G. GODINO SINGLE STOREY


PLUMBING PLAN LV 01 P100
ISOMETRIC VIEW
RES. CERT.: TIN: PRC REG. NO.: TIN: RESIDENTIAL BUILDING DETAIL OF SEPTIC TANK Drawn by Author
TCT NO: DATE: PTR. NO.: DATE: LOCATION: SAN ANTONIO, NORTHERN SAMAR Scale As indicated
L1 L2 L3
GENERAL NOTES O.25L1 0.25L2 0.25L2 0.25L3
L1/5 L1/4 L2/4 L2/4 L3/4 L3/5
1. IN THE INTERPRETATION OF THESE DRAWINGS, INDICATED DIMENSIONS SHALL GOVERN.
DISTANCES OR SIZES SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. 40D 40D 40D 40D
2. IN CASE OF CONFLICT IN DETAILS OR DIMENSIONS BETWEEN THE ARCHITECTURAL AND SEE TABLE 'B' FOR
ENGINEERING DRAWINGS, REFER TO THE ENGINEER FOR FINAL DECISION. LENGTH OF LAPPED SPLICE
3. IN CASE OF CONFLICT BETWEEN THESE DRAWINGS AND SPECIFICATIONS, THE WORKING
DRAWING SHALL GOVERN.
4. ALL STRUCTURAL DETAILS UNLESS OTHERWISE SHOWN IN THE DRAWINGS SHALL FOLLOW
CONSTRUCTION NOTE DETAILS.
5. ALL CONCRETE WORK SHALL BE DONE IN ACCORDANCE WITH THE ACI-318-95 CODE IN SO
LENGTH OF EMBEDMENT SEE TABLE 'B' FOR LENGTH OF EMBEDMENT
FAR AS THEY DO NOT CONFLICT WITH LOCAL BUILDING CODE REQUIREMENTS.
IN TABLE 'A' LENGTH OF LAPPED SPLICE IN TABLE 'B'
6. CONTRACTOR SHALL COORDINATE WITH THE ARCHITECT, MECHANICAL, ELECTRICAL,
STRUCTURAL ENGINEER PLANS AS TO THE EXACT SIZE AND LOCATION OF OPENINGS THRU
FLOOR SLAB, BEAMS AND WALLS. L1/6 L1/5 L2/5 L2/5 L3/5 L3/6
L1 L2 L3
CONCRETE
TYPICAL DETAIL FOR BEAMS STIRRUPS TYPICAL DETAIL OF STAGGERED
MINIMUM CONCRETE STRENGTH AT 28 DAYS COMPRESSIVE TEST SHALL AS FOLLOWS:
TYPES LAP SPLICES FOR SLAB BOTTOM BAR
1. COLUMNS, REINFORCED CONCRETE WALL - - - - - - - - - - - - - - - - f'c = 28 MPa TYPE A TYPE B TYPE C
2. FOOTINGS, FOOTING TIE BEAMS - - - - - - - - - - - - - - - - - - - - - - - - f'c = 21 MPa NOTES ON BEAMS AND GIRDERS LONG SPAN (L)
3. SUSPENDED SLABS, BEAMS AND GIRDERS - - - - - - - - - - - - - - - - f'c = 28 MPa

W3/4
1. UNLESS OTHERWISE NOTED ON PLANS OR SPECIFICATIONS, CAMBER ALL BEAMS AND GIRDERS AT
4. ELEVATOR CORE & STAIRWELL CORES - - - - - - - - - - - - - - - - - - - f'c = 28 MPa
LEAST 6mm FOR EVERY 4500mm OF SPAN EXCEPT CANTILEVERS FOR WHICH THE CAMBERS SHALL
5. SLAB ON GRAD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - f'c = 17 MPa
BE AS NOTED IN PLANS OR AS ORDERED BY THE DESIGNERS BUT IN NO CASE LESS THAN 20mm
6. OTHERS NOT SPECIFIED - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - f'c = 21 MPa
FOR EVERY 3000mm OF FREE SPAN.
2. WHEN A BEAM CROSSES A GIRDER, REST BEAM BARS ON TOP OF GIRDER BARS, REINFORCING
• CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT
BARS SHALL BE SYMMETRICAL ABOUT THE CENTER LINE WHERE EVER POSSIBLE AND UPPER BARS
SEGREGATION, RE-HANDLING OR FLOWING. PLACING SHALL BE DONE
SHALL BE PLACED DIRECTLY ABOVE THOSE IN THE BOTTOM LAYER.
PREFERABLY WITH BUGGIES, BUCKETS OR WHEELBARROWS. NO CHUTES WILL
3. LONGITUDINAL REINFORCEMENT OF GIRDERS, BOTH TOP AND BOTTOM, TERMINATED IN A COLUMN
BE ALLOWED EXCEPT TO TRANSFER CONCRETE FROM HOPPERS TO BUGGIES, TOP BAR
SHALL BE EXTENDED TO THE FAR FACE OF THE CONFINED CONCRETE CORE OF THE COLUMN AND
WHEELBARROWS OR BUCKETS IN WHICH CASE THEY SHALL NOT EXCEED SIX AT SUPPORT
TERMINATED BY A STANDARD 90 DEGREE HOOK.
(6.00) METERS IN AGGREGATE LENGTH. (THROUGHOUT)
4. PROVIDE HOOP REINFORCEMENT SPACED AT 100mm O.C. OVER THE LENGTH OF LAPPED BARS.

W2/4
SHORT SPAN (W)
5. WELDED SPLICES SHALL NOT BE ALLOWED WITHOUT THE WRITTEN PERMISSION OF THE
• NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF
STRUCTURAL ENGINEER.
VIBRATORS UNLESS AUTHORIZED IN WRITING BY THE DESIGNERS AND ONLY
6. GENERALLY, NO SPLICE SHALL BE PERMITTED ON BEAMS AT POINTS WHERE CRITICAL BENDING

W2
FOR UNUSUAL CONDITIONS WHERE VIBRATIONS IS EXTREMELY DIFFICULT TO
STRESSES OCCUR, LENGTH OF LAPPED SPLICE, WHERE SO PERMITTED, SHALL BE AS SHOWN ON
ACCOMPLISH.
TABLE 'A' AND 'B'. WELDED SPLICES SHALL DEVELOP IN TENSION AT LEAST 125% OF THE SPECIFIED BOTTOM BAR

W2/4
YIELD STRENGTH OF THE BAR NOT MORE THAN 50% OF THE BARS AT ANY ONE SECTION SHALL BE AT MIDSPAN
• WITHOUT PRELIMINARY TEST DATA, THE WATER-CEMENT RATIO FOR A GIVEN
ALLOWED TO BE SPLICED THEREIN. (THROUGHOUT)
CONCRETE PROTECTION
STRENGTH OF FOR REINFORCING
CONCRETE BARS THE VALUES SHOWN IN THE ACI
SHOULD NOT EXCEED
CODE, WHEN STRENGTH IN EXCESS OF 211.0 KG/CM^2 (3 KSI) ARE REQUIRED,
STRENGTH TEST SHOULD BE MADE.
THE FOLLOWING SHALL BE THE CLEAR COVER CONCRETE PROTECTIONS: TABLE 'A' TENSION BARS
LENGTH OF EMBEDMENT LENGTH OF LAP SPLICES
1. FOUNDATION - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 0.08 m.
2. SLAB ON GRADE - - - - - - - - - - - - - - - - - - - - - - - - - - - 0.04 m. BAR SIZE f'c = 13.80MPa f'c = 20.70psi f'c = 27.60psi f'c = 13.80MPa f'c = 20.70psi f'c = 27.60psi
3. SURFACE EXPOSED TO WEATHER - - - - - - - - - - - - - - 0.05 m. db (mm) SCHEDULE OF MINIMUM
TOP OTHER TOP OTHER TOP OTHER TOP OTHER TOP OTHER TOP OTHER
4. COLUMNS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 0.04 m. BARS BARS BARS BARS BARS BARS BARS BARS BARS BARS BARS BARS SLAB REINFORCEMENT
5. BEAMS AND GIRDERS - - - - - - - - - - - - - - - - - - - - - - - 0.04 m.

W1/4
10 310 200 280 180 230 150 400 480 480 460 460 460 THICKNESS MINIMUM
6. SUSPENDED SLABS AND STAIR - - - - - - - - - - - - - - - - 0.02 m BOTTOM BAR (mm) TEMPERATURE BAR
7. WALLS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 0.02 m. 12 430 310 380 280 330 230 690 660 610 560 560 560 (CONTINUOUS) TYPICAL ONE-WAY SLAB 100 10Ø at 275mm O.C.
REINFORCING BARS 16 740 530 590 480 590 430 1200 840 1090 780 940 740
REINFORCEMENT DETAIL 115 10Ø at 250mm O.C.
20 920 690 680 610 760 530 1630 1070 1400 990 1190 860
1. ALL REINFORCING BARS SHALL BE DEFORMED BILLET-STEEL BARS IN ACCORDANCE WITH
ASTM A-615. 22 1200 860 1090 790 970 690 1930 1370 1750 1230 1530 1030 125 10Ø at 200mm O.C.
LONG SPAN (L)
2. 16mm ∅ REBARS & LARGER SHALL BE DEFORMED HARD GRADE - - - - - - - - - - - - - - - - - - fy = 25 1500 1080 1350 970 1160 840 2380 1680 2150 1650 1180 1320 135 10Ø at 200mm O.C.
414 MPa L2
3. 12mm ∅ REBARS & SMALLER SHALL BE DEFORMED INTERMEDIATE GRADE - - - - - - - - - - fy = 150 10Ø at 175mm O.C.
MINIMUM TIME 276
BEFORE
MPa REMOVAL OF FORMS AFTER POURING
4. ALL COLUMN TABLE 'B' COMPRESSION BARS L1/4 L2/4 L2/4 L3/4
1. WALLS - - - - - VERTICAL
- - - - - - - - BARS
- - - - - INCLUDING
- 3 DAYS ELEVATOR AND STAIRWELL CORES - - - - - - - - - fy =
2. 414 MPa - - - - - - - - - - - - - - - - - 3 DAYS
COLUMNS BAR SIZE LENGTH OF EMBEDMENT LENGTH OF LAP SPLICES

W3/4
3. BEAMS - - - - - - - - - - - - - - - - - - - 21 DAYS db (mm)
4. SLABS - - - - - - - - - - - - - - - - - - - - 21 DAYS f'c = 13.80MPa f'c = 20.70psi f'c = 27.60psi f'c = 13.80MPa f'c = 20.70psi f'c = 27.60psi
16 200 180 180 430 330 330
UNDUE SUPERIMPOSED DEAD LOADS SHOULD NOT BE APPLIED DURING ANY SUBSEQUENT CURING PERIOD.
20 230 200 200 510 380 380
REINFORCING BARS SPLICES COLUMN 25 310 260 260 690 510 510 TOP BAR
1. FOR BEAMS: ALL SPLICES SHALL BE LAPPED OR 28 360 330 280 760 580 580 AT SUPPORT
EXTEND A MINIMUM OF 40 DIAMETER UNLESS SHOWN (THROUGHOUT)
32 410 380 330 860 640 640

W2/4
OTHERWISE. HORIZONTAL BARS SPLICE LOCATION

SHORT SPAN (W)


SHALL BE STAGGERED FOR BEAMS AND GIRDERS. 36 430 410 380 990 740 710
40 DIA

SPLICE TOP BARS AT MID-SPAN, BOTTOM BARS AT


SUPPORTS.

W2
H

2. FOR COLUMNS: ALL SPLICES SHALL BE WELDED OR 12mmØ TO 28mmØ


38mm CLEAR

38mm CLEAR MINIMUM


LAPPED LOCATED NEAR THE MID-HEIGHT LEVEL. NO MINIMUM DISTANCE
'2mm BOTTOM BAR
MORE THAN 50% OF THE TOTAL NUMBER OF MAIN

W2/4
WELDING OF REINFORCING TO BE AT MIDSPAN
BARSBARS SHALL BE SPLICED AT ANY SAME LEVEL
45°

FOR BEAM
CUT-OFF IN ACCORDANCE WITH 25mm CLEAR (THROUGHOUT)
LOCATION. MINIMUM
SPECIFICATION AWS D 12-1-61 '3mm
1. UNLESS OTHERWISE SHOWN ON STRUCTURAL FULL PENETRATION SQUARE 25mm SEPARATORS
DRAWINGS, TYPICAL BAR CUT-OFF FOR BEAMS, BUTT WELD CUT END EACH AT 900mm
GIRDERS AND SLABS SHOWN BELOW SHALL BE COLUMN SPLICE ON CENTER
FOLLOWED. HOOKS MAY BE OPTIONAL. DETAIL
TOP BAR
CAMBERING: TYPICAL WELDED SPLICE TYPICAL BEAM AT SUPPORT

W1/4
DETAILS FOR BARS 12mmØ TO SECTION DETAILS (THROUGHOUT)
UNLESS OTHERWISE SPECIFIED BY THE ENGINEER OR ARCHITECT, CAMBER ARE TO BE PROVIDED FOR ALL
SUSPENDED REINFORCED CONCRETE MEMBERS, AS FOLLOWS: 28mmØ
L1/3 L2/4 L2/4 L3/4 L3/2 2/3 L4 TYPICAL TWO-WAY SLAB
1. BEAMS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 12 mm PER 3.05 m.
2. SLABS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 12 mm PER 3.05 m. REINFORCEMENT DETAIL
3. CANTILEVERED BEAMS & SLABS - - - - - - - - - - - 25 mm PER 3.05 m.
NOTES ON CONCRETE SLABS
NOTES ON COLUMN 1. ALL SLAB REINFORCEMENT SHALL HAVE A MINIMUM CLEAR DISTANCE OF 19mm FROM THE BOTTOM
267mm 150mm (MIN) EDGE BAR AND FROM THE OF SLABS.
1. FOR ALL TIED COLUMNS PROVIDE MINIMUM FOUR (4) SETS OF TIES AT 2. IF SLABS ARE REINFORCED BOTH WAYS, BARS ALONG THE SHORTER SPAN SHALL BE PLACED BELOW
150mm O.C. FOR COLUMN REINFORCEMENT JUST ABOVE THE FLOOR, JUST (MIN)
L1/6 L1/3 L2/5 L2/5 L3/5 L3/5 THOSE ALONG THE LONG SPAN AT THE CENTER AND OVER THE LONGER SPAN BARS NEAR THE
BELOW THE GIRDER, AND AT BOTH SIDES OF CONSTRUCTION JOINT. SUPPORTS, TIE SPACING OF THE BARS AT THE COLUMN STRIPS SHALL BE APPROXIMATELY ONE AND
2. COLUMN TIES AND SPIRALS SHALL BE PROTECTED EVERYWHERE BY A ONE-HALF (1 - 1/2) THAT IN THE MIDDLE STRIPS BUT IN NO CASE GREATER THAN TWO AND ONE-HALF
COVERING OF CONCRETE CAST MONOLITHICALLY WITH THE CORE OF L1 L2 L3 L4 (2 - 1.2) SLAB THICKNESS OR 450mm. UNLESS OTHERWISE INDICATED IN THE PLANS.
MINIMUM THICKNESS OF 38mm AND NOT LESS THAN 1 - 1/2 TIMES MAXIMUM EXTERIOR SPAN INTERIOR SPAN INTERION SPAN CANTILEVER SPAN 3. UNLESS OTHERWISE NOTED, ALL BEDDED SLABS SHALL BE REINFORCED WITH 10mm AT 250mm EACH
SIZE OF COARSE AGGREGATE. WAY AT CENTER OF SLAB. CONSTRUCTION JOINTS SHALL NOT BE MORE THAN 3000mm APART.
3. WHERE COLUMNS CHANGE IN SIZE, VERTICAL REINFORCEMENTS SHALL BE 4. UNLESS OTHERWISE NOTED IN THE PLANS ALL OPENINGS IN CONCRETE SLABS SHALL BE
OFFSET AT A SLOPE OF NOT MORE THAN 1 IN 6 AND EXTRA 10mm TIES AT TYPICAL DETAIL FOR SLAB REINFORCEMENT
REINFORCED AROUND WITH 2 - 16mmØ BARS.
100mm O.C. SHALL BE PROVIDED THROUGHOUT THE OFFSET REGION.

11/30/2018 5:13:26 PM
OWNER: ENGINEER: PROJECT TITLE: SHEET CONTENTS: NO. DESCRIPTION DATE

JUDA G. COLLAMAR CHRISTIAN G. GODINO SINGLE STOREY


GENERAL NOTES S100
RES. CERT.: TIN: PRC REG. NO.: TIN: RESIDENTIAL BUILDING Drawn by N.Onoy
TCT NO: DATE: PTR. NO.: DATE: LOCATION: SAN ANTONIO, NORTHERN SAMAR Scale
NOTES ON MASONRY WALL

SEE SCHEDULE FOR TENSILE


LAP SPLICE REQUIREMENTS
COLUMN WIDTH '1000mm
1. ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE
APPLICABLE STANDARDS AND SPECIFICATIONS OF THE NATIONAL CONCRETE 100mm MAX 50mm MAX
MASONRY ASSOCIATION AND UNIFORM BUILDING CODE. DEPRESSION DEPRESSION
2. CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90 GRADE N, LOAD

D
BEARING, UNLESS NOTED OTHERWISE ON PLAN.

t
D
3. MORTAR AND GROUT FOR ALL REINFORCED MASONRY SHALL CONFORM TO ASTM

t
CONSTRUCTION

SPACING S/2
270-TYPE M .

HALF TIES
KEY JOINT

30°
4. ALL MASONRY WALLS SHALL BE REINFORCED ACCORDING TO THE FOLLOWING

30°
SCHEDULE OF CONCRETE HOLLOW BLOCK REINFORCEMENT UNLESS OTHERWISE '50mm D 3t
INDICATED IN THE PLANS.
D/3 D/3
THICKNESS REINFORCEMENT NOTES: D/3 '2000mm
(mm) 1. MINIMUM LAP AT SPLICE = 250mm

EQ. EQ.
HORIZONTAL VERTICAL 2. WHERE CHB WALLS ADJOIN COLUMNS RC
TYPICAL CONSTRUCTION JOINT KEY BEAM DEPRESSION DETAIL SLAB DEPRESSION DETAIL

H
BEAMS AND WALLS DOWELS WITH THE
100 10Ø at 600 O.C. 10Ø at 600 O.C.
SAME SIZE AS VERTICAL OR HORIZONTAL BETWEEN COLUMN AND BEAM.
125 12Ø at 400 O.C. 12Ø at 600 O.C. REINFORCEMENT SHALL BE PROVIDED
3. PROVIDE STIFFENER BEAM & STIFFENER COLUMN AND FOOTING 125mm THK
150 12Ø at 400 O.C. 12Ø at 600 O.C. POST AROUND ALL OPENINGS. 300mm(MIN) 500mm(MIN)
1 - 12mmØ COMPACTED

H/2
4. PROVIDE STIFFENER BEAMS AT LEAST CONTINUOU GRAVEL FILL
EVERY 3000mm HEIGHT OF MASONRY S 40mm(TYP) 40mm(TYP)
WALL AND POST AT LEAST EVERY 3000mm

VARIES
SPACING S/2
'150mm

HALF TIES
WIDTH OF MASONRY WALL.

t
3 TIES AT

t
'300mm 150mm ON CENTER
'75mm
'150mm

TIES SPACING
FOR COLUMN
SEE COLUMN
SCHEDULE
2-12mmØ CONTINUOUS AT S
TYPICAL SLAB TYPICAL SLAB

'300mm
TOP BARS
DEPRESSION ON GRADE DETAIL
4-12mmØ 2-12mmØ CONTINUOUS AT S1
VERTICAL BARS BOTTOM BARS DETAIL
40mm COVER TO MASONRY WALL
MASONRY WALL MASONRY WALL
COLUMN TIES (TYPICAL)

STIFFENER STIFFENER TOP OF TIED COLUMN '300mm WALL DOWELS


COLUMN TYPICAL DETAIL OF BEAM 450mm(MIN)
40mm(TYP)

T/3
MASONRY WALL

50 BAR DIAMETER
USE 8mmØ STIRRUPS USE 8mmØ STIRRUPS 40mm(TYP)

LAP (TYPICAL)
STIFFENER BEAM AND

t
SEE COLUMN
SPACED @ 200mm O.C. SPACED @ 200mm O.C. TYPICAL TIED COLUMN

SCHEDULE

T/3

t
COLUMN SPLICE DETAILS 2 - 16mmØ STARTER BAR
NATURAL NATURAL NATURAL

T/3
GRADE LINE GRADE LINE GRADE LINE 40mm COVER 12mmØ SPACED AT
400mm ON CENTER

'150mm
(TYPICAL)
'300mm
TYPICAL SLAB

'220mm
CONSTRUCTION JOINT DETAIL

'150mm
TYPICAL SLAB ON GRADE 16mmØ CONTINUOUS
EMBEDMENT

EMBEDMENT

EMBEDMENT

'150mm
DEPTH OF

DEPTH OF

DEPTH OF

THICKENED AT MASONRY EACH SIDE OF GRID LINE


WALL DETAIL (TYPICAL)

'450mm
'450mm '450mm

'150mm

750mm (TYPICAL)
'450mm

'450mm
COLUMN

'450mm
'150mm

'450mm
2 - 12mmØ DIAGONAL BARS
76mm COVER EACH CORNERS
6mm SAW CUT
t

'150mm
STANDARD HOOK JOINT (TYPICAL)

TYPICAL TIED COLUMN SPLICE


NOTE: DETAIL AT FOUNDATION
SPLICING OF INDIVIDUAL BAR SHALL BE STAGGERED

'1
50
AT LEAST 760mm AND SHALL BE BUTT-WELDED FULL

m
STRENGTH

m
SEE SCHEDULE FOR TENSILE CAP
LENGTH

LENGTH

SPLICE LENGTH REQUIREMENTS

'1
TYPICAL DETAIL
BAR L

BAR L

LENGTH

50
BAR L

m
OF

m
BUNDLED BARS NOTE:
EXTEND ADDITIONAL REINFORCEMENT TO
BAR S BAR S BAR S 6d ADJACENT BEAMS IN DIRECTION OF SLAB SPAN IF
b7 AT LEAST Ldh NOTES:
5° 5m SUPPORTED FRAMING EXTEND ADDITIONAL
'13 m REINFORCEMENT 750mm BEYOND PAD IN 1. TENSION LAP AT MIDSPAN.
MI 2. 90DEGREE STANDARD HOOK AT WALLS.
WIDTH WIDTH WIDTH N. TEMPERAURE STEEL DIRECTION IF SUPPORTED
90 DEGREE FRAMING AND IN BOTH DIRECTION FOR SLAB ON 3. PLACE REINFORCEMENT AT MID-SAPN OF SLAB.
db GRADE.
12db

TYPICAL SLAB ON GRADE

FACE OF COLUMN
CENTER FOOTING SIDE FOOTING CORNER FOOTING
TYPICAL SLAB ON FILL
I.D. = 4db FOR THICKENED AT MASONRY TIE REINFORCEMENT
OR WALL
10,12,16 mmØ
db WALL DETAIL
TYPICAL DETAIL OF FOOTING BAR SIZE fy = 276 MPa fy = 414 MPa
db (mm) CLASS B
NOTES ON FOUNDATION 5° AT LEAST Ldh CLASS C CLASS B CLASS C NOTES ON TIMBER
'13
10 305 305 455 595
1. FOOTINGS WERE DESIGNED WITH AN ASSUMED ALLOWABLE SOIL BEARING PRESSURE OF 216 KPa. 1. LUMBER SHALL BE PROTECTED FROM ELEMENTS AND IF IN CONTACT WITH
CONTRACTOR SHALL REPORT IN WRITING TO THE STRUCTURAL ENGINEER ACTUAL SOIL CONDITION 180 DEGREE 12 365 475 545 710 CONCRETE OR MASONRY SHALL BE COATED WITH COALTAR OR ASPHALT.
db

UNCOVERED AND CONFIRM ACTUAL BEARING CAPACITY OF SOIL BEFORE DEPOSITING CONCRETE. 2. LUMBER MUST BE SOUND, THOROUGHLY SEASONED, WELL CUT AND FREE
16 485 630 725 950 FROM WARD.
2. NO FOOTING SHALL REST ON UNCOMPACTED FILL. 6db 75mm MIN.
3. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE 75mm CLEAR FOR CONCRETE 20 695 910 1040 1360 3. WELL TREATED APITONG LUMBER SHALL BE USED FOR VERTICAL AND
DEPOSITED AGAINST THE GROUND AND 50mm FOR CONCRETE DEPOSITED AGAINST FORMWORK. 4db OR 65mm MIN. HORIZONTAL STUDDINGS OF SIDINGS, TRUSSES, RAFTERS, FLOOR JOIST,
db 22 845 1105 1260 1650 PURLINS, AND OTHER RELATED ROUGH LUMBER WORKS.
4. PROVIDE TEMPORARY REMOVAL OF WATER FROM ANY SOURCE DURING CONSTRUCTION.
4db FOR 10mm TO 25mm 25 1085 1420 1625 2125 4. WELL SEASONED YAKAL SHALL BE USED FOR ALL PLATES, PLUGS, GIRTS,
DEWATERING SHALL BE CAREFULLY AND PROPERLY PERFORMED TO AVOID DISTURBING THE
5db FOR 28mm TO 32mm 6db FOR 36mm WOOD CORBEL, POST AND OTHER PORTIONS F THE WORK DIRECTLY IN
FOUNDATIONS AND SLAB BEARING SURFACES. 28 1365 1785 2040 2670
5. CONTRACTOR SHALL DESIGN, INSTALL, AND MONITOR ALL EXCAVATION RETENTION SYSTEMS AS CONTACT WITH CONCRETE OR MASONRY.
REQUIRED FOR PROTECTION OF ADJACENT PROPERTIES AND PROVIDE ALL MEASURES AND Ldh = BASIC DEVELOPMENT LENGTH OF 32 1780 2330 2885 3485
PRECAUTIONS NECESSARY TO MINIMIZE SETTLEMENT AND PREVENT DAMAGE TO ADJACENT EXISTING STANDARD HOOKS IN TENSION 36 2250 2840 3375 4410
OR NEW CONSTRUCTION.
6. IN CASES WHERE REQUIRED FOOTING LEVELS SHOW A HONEYCOMBED STRUCTURE CONTAINING
LOOSE MATERIALS, REMOVE LOOSE MATERIALS AND FILL ALL VOIDS WITH 10 MPa LEAN CONCRETE, DETAILS OF STANDARD HOOKS REINFORCING BAR
USE A VIBRATOR TO ASSURE WELL COMPACTED CONCRETE IN ALL VOID PORTIONS.
7. REFER TO ARCHITECTURAL, PLUMBING, AND OTHER TRADES FOR SUB-SOIL DRAINAGE SYSTEM, SPLICE DETAILS
MACHINERY, ANCHORS AND OTHER EMBEDDED ITEMS, DEPRESSIONS, FINISHES, DOWELS FOR
MASONRY WALLS, CURBS, ETC.

11/30/2018 5:13:27 PM
OWNER: ENGINEER: PROJECT TITLE: SHEET CONTENTS: NO. DESCRIPTION DATE

JUDA G. COLLAMAR CHRISTIAN G. GODINO SINGLE STOREY


GENERAL NOTES S101
RES. CERT.: TIN: PRC REG. NO.: TIN: RESIDENTIAL BUILDING Drawn by N.Onoy
TCT NO: DATE: PTR. NO.: DATE: LOCATION: SAN ANTONIO, NORTHERN SAMAR Scale