DOOR DIMENSION
Feet Meter
Height 7 2.1
Width 3 0.9

From ASHRAE Handbook- HVAC Application

Equation 10:
Vk = 5.68 (qc/W)1/3

Vk = critical air velocity to prevent smoke backflow, fpm


qc = heat release rate into corridor, Btu/h= 8 x 10 6
W = corridor width, ft

Vk = 15,146,667

(qc/W)1/3 #N/A

Page 1
AIR BALANCE FOR TOILET
INPUT AREA
HERE
EXHAUST FLOWRATE SIZING
sq.m sq.ft
Area of Toilet 28.7 308.8
CFM/sq.ft 2
Q (Exhaust Air flowrate ) 618

SUPPLY FLOWRATE SIZING FOR AIRCONDITIONING SYSTEM

Supply Air flowrate 515 CFM


Return Air flowrate CFM
Outdoor Air flowrate 515 CFM

Airconditioning Load Capacity, TR

Q=m (h2-h1)
where:
Q= Cooling Capacity 36364.6 Btu/hr
3.0 TR

m= mass flow
h2= enthalpy of air @ 35 deg.C DB & 27.2 deg.C WB 37 btu/lb
h2= enthalpy of air @ 24 deg.C & 50% RH 20.55 btu/lb

ρ = m/V
ρ = density of air @ 35 deg.C 1.146 kg/cu.m
Volume Flow 14.6 cu.m/min
m= ρV 16.7 kg/min
2210.6 lbs/hr

Page 2
AIR BALANCE FOR TOILET
INPUT AREA TOILET
HERE DESIGNATIO FLOOR VENTILATIO EXHAUST
N LOCATION AREA N RATE FLOWRATE
sq.m CFM/sq.ft
T1 FT GF 28.7 2 617.6
T1 MT GF 28.7 2 617.6
CFM T2 FT GF 19.5 2 419.6
T2
B1 MT
PUBLIC GF 17.1 2 368.0
TOILET B1 (6-7/F-G) 21.3 2 458.4
T1 FT 2F 29.9 2 643.4
T1 MT 2F 41.3 2 888.8
T2 FT 2F 16.8 2 361.5
T2 MT 2F 15.6 2 335.7
TOI 3F 45.6 2 981.3
2 0.0
2 0.0
2 0.0
2 0.0

13.9 0.813 299.1


3.2 0.187 68.9
20.549591084 17.1
419.64
104.91
49.5325779

Page 3
AIR BALANCE FOR TOILET

EXH. FAN SA FOR A/C, RA FOR A/C, OA FOR A/C, MASS


EQPT NO. CFM CFM CFM VOLUME FLOW FLOW
cu.m/min kg.min
291.6 TEF-10 741.1 123.5 617.6 21.0 3,183.3
291.6 TEF-10A 741.1 123.5 617.6 21.0 3,183.3
503.6 83.9 419.6 14.3 2,162.9
371.9 TEF-11
441.6 73.6 368.0 12.5 1,896.7
216.4 EF-02 550.1 91.7 458.4 15.6 2,362.5
303.8 TEF-12A 772.1 128.7 643.4 21.9 3,316.4
419.6 TEF-12 1066.5 177.8 888.8 30.2 4,580.8
329.2 433.8 72.3 361.5 12.3 1,863.4
TEF-13 402.9 67.1 335.7 11.4 1,730.3
463.3 TEF-14 1177.6 196.3 981.3 33.4 5,057.8
0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.0 0.0

141.2 47.0771168 134.3 67.1 361.5


32.5 LPS 63.4 31.7 170.7

42.1

14
45.92
0.050512

Page 4
AIR BALANCE FOR TOILET

0.06
0.05
0.11
0.55

Page 5
AIR BALANCE FOR TOILET

COOLING CAPACITY FCU EQPT NO.


Btu/Hr TR
44,566.0 3.7 13.0 11,217.0 FCU-FTT1-02 349.9 291.6
44,566.0 3.7 13.0 11,217.0 FCU-MTT1-02 349.9 291.6
30,280.0 2.5 8.9 7,621.3 FCU-FTT2-02 237.8 198.1
26,553.2 2.2 7.8 6,683.3 FCU-MTT2-02 208.5 173.7
33,075.1 2.8 9.7 8,324.8 259.7 216.4
46,429.3 3.9 13.6 11,686.0 FCU-FTT1-01 364.6 303.8
64,131.5 5.3 18.8 16,141.5 FCU-MTT1-01 503.6 419.6
26,087.4 2.2 7.6 6,566.0 FCU-FTT2-01 204.8 170.7
24,224.0 2.0 7.1 6,097.0 FCU-MTT2-01 190.2 158.5
70,808.6 5.9 20.7 17,822.1 556.0 463.3
0.0 0.0 0.0 0.0
0.0 0.0 0.0
0.0 0.0 0.0 0.0
0.0 0.0

26.0859380604 22433.90673191

0.8
20.32

697.1
1293.2
610.57602 0.2403717
0.6009294

281.39754 596 0.1107806691 0.3 0.369268897


610.95373 1294 0.2405204461 0.3 0.80173482
187.44098 397 0.0737918216 0.3 0.245972739

Page 6
AIR BALANCE FOR TOILET
1126.0623 2385 0.4433085502 0.3 1.477695167

Page 7
AIR BALANCE FOR TOILET (2)
INPUT AREA
HERE
EXHAUST FLOWRATE SIZING
sq.m sq.ft
Area of Toilet 53 570.3
CFM/sq.ft 2
Q (Exhaust Air flowrate ) 1141

SUPPLY FLOWRATE SIZING FOR AIRCONDITIONING SYSTEM

Supply Air flowrate 1200 CFM


Return Air flowrate CFM
Outdoor Air flowrate 1200 CFM

Airconditioning Load Capacity, TR

Q=m (h2-h1)
where:
Q= Cooling Capacity 79403.7 Btu/hr
6.6 TR

m= mass flow
h2= enthalpy of air @ 35 deg.C DB & 27.2 deg.C WB 37 btu/lb
h2= enthalpy of air @ 25 deg.C & 50% RH 21.6 btu/lb

ρ = m/V
ρ = density of air @ 35 deg.C 1.146 kg/cu.m
Volume Flow 34.0 cu.m/min
m= ρV 39.0 kg/min
5156.1 lbs/hr

Page 8
AIR BALANCE FOR TOILET (2)
INPUT AREA TOILET
HERE DESIGNATIO FLOOR VENTILATIO EXHAUST
N LOCATION AREA N RATE FLOWRATE
sq.m CFM/sq.ft
T1 FT GF 28.7 2 617.6
T1 MT GF 28.7 2 617.6
CFM T2 FT GF 19.5 2 419.6
T2
B1 MT
PUBLIC GF 17.1 2 368.0
TOILET B1 (6-7/F-G) 21.3 2 458.4
T1 FT 2F 29.9 2 643.4
T1 MT 2F 41.3 2 888.8
T2 FT 2F 16.8 2 361.5
T2 MT 2F 15.6 2 335.7
TOI 3F 45.6 2 981.3
2 0.0
2 0.0
2 0.0
2 0.0

13.9 0.813 299.1


3.2 0.187 68.9
21.626849792 17.1
419.64
104.91
49.5325779
77

Page 9
AIR BALANCE FOR TOILET (2)

EXH. FAN SA FOR A/C, RA FOR A/C, OA FOR A/C, MASS


EQPT NO. CFM CFM CFM VOLUME FLOW FLOW
cu.m/min kg.min
291.6 TEF-10 741.1 123.5 617.6 21.0 3,183.3
291.6 TEF-10A 741.1 123.5 617.6 21.0 3,183.3
371.9 TEF-11 503.6 83.9 419.6 14.3 2,162.9
441.6 73.6 368.0 12.5 1,896.7
216.4 EF-02 550.1 91.7 458.4 15.6 2,362.5
303.8 TEF-12A 772.1 128.7 643.4 21.9 3,316.4
419.6 TEF-12 1066.5 177.8 888.8 30.2 4,580.8
329.2 TEF-13 433.8 72.3 361.5 12.3 1,863.4
402.9 67.1 335.7 11.4 1,730.3
463.3 TEF-14 1177.6 196.3 981.3 33.4 5,057.8
0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.0 0.0

141.2 47.0771168 134.3 67.1 361.5


32.5 LPS 63.4 31.7 170.7

42.1

14
45.92
0.050512

Page 10
AIR BALANCE FOR TOILET (2)

0.06
0.05
0.11
0.55

Page 11
AIR BALANCE FOR TOILET (2)

COOLING
CAPACITY FCU EQPT NO.
Btu/Hr TR
44,566.0 3.7 13.0 11,217.0 FCU-FTT1-02 349.9 291.6
44,566.0 3.7 13.0 11,217.0 FCU-MTT1-02 349.9 291.6
30,280.0 2.5 8.9 7,621.3 FCU-FTT2-02 237.8 198.1
26,553.2 2.2 7.8 6,683.3 FCU-MTT2-02 208.5 173.7
33,075.1 2.8 9.7 8,324.8 259.7 216.4
46,429.3 3.9 13.6 11,686.0 FCU-FTT1-01 364.6 303.8
64,131.5 5.3 18.8 16,141.5 FCU-MTT1-01 503.6 419.6
26,087.4 2.2 7.6 6,566.0 FCU-FTT2-01 204.8 170.7
24,224.0 2.0 7.1 6,097.0 FCU-MTT2-01 190.2 158.5
70,808.6 5.9 20.7 17,822.1 556.0 463.3
0.0 0.0 0.0 0.0
0.0 0.0 0.0
0.0 0.0 0.0 0.0
0.0 0.0

26.0859380604 22433.90673191

0.8
20.32

697.1
1293.2
610.57602 0.2403717
0.6009294

281.39754 596 0.1107806691 0.3 0.369268897


610.95373 1294 0.2405204461 0.3 0.80173482
187.44098 397 0.0737918216 0.3 0.245972739

Page 12
AIR BALANCE FOR TOILET (2)
1126.0623 2385 0.4433085502 0.3 1.477695167

Page 13