CT and Connection Details System Details

Line CT Neutral CT Transformer Rating- 300MVA


Ratio 1400/1A 1400/1A Rated Voltage - 132kV
Vk 1300 700
Rct 10Ω 7Ω
Imag 20mA 20mA
Loop Res. 1Ω 1Ω

Settings Requirements

Rated current = VA / (√3 x VL)


Rated current = 300MVA / (√3 x 132kV)
Rated current = 1312 A

Assigned through fault current (rated stability limit) = 16 x rated current = 20.992kA
Required Primary Operate Current (Fault Setting)
10 – 25% of protected winding rated current, or as specified by the user.
POCprov (10 – 25% of Irated) =131.2 - 328A. Say 150A. (0.1A secondary)

Calculation of Required Stability Voltage Limits


The assigned through fault current is 20992A.
With reference to section 2.2.1 of 7SR11 Siemens Manual

Vs ≥ (20992/1400) x (10+1) =164V

Vs ≥ (20992/1400) x (7+1) = 119V

Vs ≤ (700/2) = 350V

164V ≤ Vs ≤ 350V

So Knee point voltage -700V is enough.