Vous êtes sur la page 1sur 4

Inspection Report

Company MePTCL Customer 132 KV Maithan Feeder


name name

132/33 KV EPIP-I
Address Address Rajabagan
Sub-Station

Tel/Fax Tel/Fax

E-mail E-mail

Contact 9436707477 Contact

Instrument name Thermal vision Instrument type TI 395

Lens 21.5 mm
Instrument serial No. 900039012041

Measurement point

Name

Address details

Measurement description

Afternoon

1/4
Afternoon

NO. File: Date: Measuring Time:


1 P163256.JPG 2018-06-14 16:32:57

Emissivity 0.96

Remark

Marke Emissivity Min temp. Avg temp. Max temp. Remark


P1 0.96 51.6℃ 51.6℃ 51.6℃
132Kv Maithan Feeder Line
L1 - 12.4℃ 34.2℃ 64.9℃ Isolator B-Phase
Histogram Temperature line

Note
132 KV Maithan Smelter Feeder Line side Isolator B-phase.

2/4
NO. File: Date: Measuring Time:
2 P163331.JPG 2018-06-14 16:33:32

Emissivity 0.96

Remark

Marke Emissivity Min temp. Avg temp. Max temp. Remark


P1 0.96 >250℃ >250℃ >250℃
132Kv Maithan Feeder Bus
L1 - 42.2℃ 99.9℃ >250℃ isolator R-Phase
Histogram Temperature line

Note

3/4
NO. File: Date: Measuring Time:
3 P163400.JPG 2018-06-14 16:34: 1

Emissivity 0.96

Remark

Marke Emissivity Min temp. Avg temp. Max temp. Remark


P1 0.96 63.2℃ 63.2℃ 63.2℃
132 KV Maithan Feeder Line
L1 - 30.2℃ 46.8℃ 60.6℃ Isolator B-Phase(CB Side)
Histogram Temperature line

Note

Report date 14.06.2018

Author B.Ch Das.

4/4

Vous aimerez peut-être aussi