1. Split Air Condition unit.

2. VRV central air condition


3. Chiller Central Air Condition unit.

3
Out Cooled Air

Out warm Freon

In Cool Freon
In Warm Air

4
Fan

Warm In Warm Air


Freon
out

Cool Freon
in

Out Cooled Air


Cool Freon Out

Fan

Low Warm Freon In


In Ambient Air

Out Warm Ambient Air


Out Cooled Air

In Cool Freon

Out warm Freon In Warm Air

FCU (1)
FCU (2)
FCU
7
Shell Fan
Warm In Warm Air
water
out

Cool water
in

Out Cooled Air


10
11
Shell Water
Tubes
Warm
water
out

Cool water
in

Chiller Cycle
13
14
1. Exhaust Fans.
2. Fresh Air Fans.
3. Pressurized Fans.

15
1. Booster Pumps.
2. Submersible pumps.
3. Fire pumps.
4. Jockey pumps.
5. Sewerage Pumps.
......
…….

16
17
18
19
Isolating Switch for maintenance is located
before the equipment directly for maintenance

20
Isolator
Description

Voltage Rated Protection


1ph or 3ph current=CB WP or not
(1) Large Pumps (primary pump, sec,..):
all breaker must be MCCB ( SF=1.25) .
(2) Chillers, AHU:
all breaker must be MCCB ( SF=1.25) .
(3) Small pump (jockey, water supply,,..)
all breaker must be MCB ( SF=2.25) .
(4) FCU (CB=16A, 3x3mm2, No 5/linea):
all breaker must be MCB.
(5) Fans (FAF, press, FAN, EX.fan) :
may be 3 ph or 1ph (usually 3ph)
the breaker may be MCB or MCCB according to
its rating, short circuit level
22
(1) Small pump with MCB:
ICB=2.25xIload due to starting current
Ex: 4 kw water supply pump:
Sload =4/0.8=5KVA
ICB=2.25xIload=2.25x4.5x5=50.5
Standard 50A but wire 3x6mm2

23
(2) Split unit:
ICB=2.25xIload due to starting current
Ex: 3 hp AC split :
Sload =3KVA
ICB=2.25xIload=2.25x4.5x3=30.35
Standard 32A but wire 3x4 mm2

24
(3) Fire pump & jockey pump:
Fire pump : ICB= 3xIn (IEC)
ICB=4xIn (EG)
Ex: 50 hp fire pump: ICB=1.5x3x50=225Amp
Standard cable : 250A MCCB fixed
jockey pump:
ICB=2.25xIload due to starting current (MCB)
ICB=1.25xIload due to starting current (MCCB)
Ex: 6 hp AC split :
Sload =6KVA
ICB=2.25xIload=2.25x1.5x6=20.5
Standard 25A MCB but 5x4mm2

25
(4) Fan coil unit (FCU) 1ph:
FCU load= max 330watt/0.8=400 VA
CB=16A,
wire 3x3mm2,
no of FCU per linea=2000/400=5
One FCU per linea is preferred

26