De-Energized Tap Changer for

air core buffer reactors

More efficient operation of elec- many melt shops in order to opti-


trical arc furnaces (EAFs) may be mize their melting process. The
achieved by increasing the source taps, which are basically designed
impedance of the EAF's power for manual operation, are made
supply. For this purpose dry-type up by terminals arranged along the
air-core reactors (buffer reactors) winding of each single phase unit.
are connected in series to the pri- To facilitate tap changing, Trench
mary side of the furnace transformer. can provide an off-circuit (i.e. de-
Commonly these reactors are energized) tap changer for remote
equipped with a number of taps, control of the reactor impedance.
typically covering a range from Tap Changer
40% through 100% in steps of Figure 1 shows a circuit diagram
15% of rated impedance. of the tap changer connected to Series Reactor
a tapped reactor.
Since the best impedance value
for a particular melt shop and
type of melt is often not known Equipment description
prior to reactor design, a tapped
reactor offering several values of The Trench dry type buffer
impedance is advantageous for reactors for EAFs are of single
phase design. The winding is
shaped as a vertically oriented
cylinder having a typical length
between 1.5 to 2.5 meters.
Usually the winding is mounted
on support insulators. The support
structure may include extension
brackets to provide additional
clearance under the reactor.

The tap changer is also of single


phase design. The Trench design
consists of a tapping unit, and a
motor drive unit for remote
operation of the tap changer.

Each single phase tap changer is


arranged near to the reactor. It is
mounted on support insulators with
Fig. 1 circuit diagram
the axis in parallel to the coil axis.
The tapping unit consists of an oil The setting of the tap changer For installation in cold climates
filled fiber glass tube which is her- positions is controlled by auxiliary the housing of the motor drive
metically sealed by metallic end control switches ( position switches) unit is equipped with a temperatu-
armatures. The top armature is which are incorporated in the hou- re controlled heater.
equipped with a pressure relief sing of the motor drive unit. These
device (rupture disk) to prevent the switches are actuated by a control As the descriptor “de-energized“
build-up of dangerous pressure in cam mounted on a rotating disc, implies, the tap changer must not
case of an internal fault of the which is driven by the control gear. be operated at any circumstances
unit. The electrical terminals of the Thus, the position of the traveling neither on-load nor on-voltage.
individual tap changer positions contact in the tapping unit is Therefore, prior to changing the
are mounted along the tube. One mechanically coupled with the tap position of the EAF series reac-
or several terminals per tap position position of the control switches tor the associated EAF feeder must
may be provided depending on and the control cam in the motor be shut-off or the reactor must be
the current rating of the tap chan- drive unit indicates the tap bridged by an auxiliary by-pass
ger. Each terminal is connected to changer position. switch.
the associated tap at the reactor The control switches at the end
winding. Inside the tube of the positions automatically limit the To avoid accidental tap changing
tapping unit each terminal carries tapping range, thus they may not while energized, the auxiliary vol-
an electrical contact. The reque- be overrun during normal tap tage for the motor control circuit
sted tap changer position is set by changer operation. Further to shall be interlocked with the EAF
positioning (a) traveling contact(s) these control switches there is an feeder breaker.
to the associated fixed contact(s) auxiliary blocking switch for each
inside the tube wall. The setting of end position which protects the To avoid accidental switching-on of
the traveling contact(s) is accom- tap changer against mechanical the EAF feeder breaker during tap-
plished by the motor-powered damage in case of overrunning the ping operation, the EAF feeder
spindle of the tap changer. end position due to incorrect breaker must be interlocked with
phase sequence of the power sup- the de-energized tap changer.
Depending on the voltage class ply of the motor unit during com-
the tapping unit may be equipped missioning.
with a surge arrester in order to
limit possible transient overvolta- The tap position indicator (control
ges induced by the reactor bet- cam) and the control switches may
ween unloaded terminals. be visually monitored through the
window in the front panel of the
All electrical terminals and all motor drive unit cabinet.
metallic armatures of the tapping
unit are "live" parts and it must The cabinet of the control unit
therefore be insulated to ground. contains all electrical components
Insulation is provided by three sup- necessary to operate the motor
port insulators and one central drive unit, such as the motor
swivel insulator driving the spindle contactors for both running direc-
of the tap changer. tions, the motor protective switch
and associated relays.
The insulators of the tap changer
and the motor drive unit are moun-
ted on a common platform which is
at ground potential.

Main technical data


maximum rated system voltage 36 kV
maximum BIL 200 kV
maximum rated current 2500 A
switch-over time to next tap position 15 s
maximum number of tap positions 7
maximum number of operations
per inspection interval 200,000
Subject to change without notice
04.2000

E 600.30