[Project Name]
“This Functional Performance Test document represents FCG's standard test protocol, basic functional test, and FCG's best understanding of the
designed sequence of operation. This document DOES NOT define design intent, supersede contract documents, or direct means and methods.”
FCG_Website_FPT_Air_Leakage_Sample.docx Page 1 of 6
158 Burt Road⏐Lexington, KY 40503⏐Tel. (859) 278-5552⏐Fax (859) 278-6501
2611 Waterfront Parkway, Suite 340⏐Indianapolis, IN 46214⏐Tel. (317) 536-2618
[Project Name]
“This Functional Performance Test document represents FCG's standard test protocol, basic functional test, and FCG's best understanding of the
designed sequence of operation. This document DOES NOT define design intent, supersede contract documents, or direct means and methods.”
FCG_Website_FPT_Air_Leakage_Sample.docx Page 2 of 6
158 Burt Road⏐Lexington, KY 40503⏐Tel. (859) 278-5552⏐Fax (859) 278-6501
2611 Waterfront Parkway, Suite 340⏐Indianapolis, IN 46214⏐Tel. (317) 536-2618
[Project Name]
“This Functional Performance Test document represents FCG's standard test protocol, basic functional test, and FCG's best understanding of the
designed sequence of operation. This document DOES NOT define design intent, supersede contract documents, or direct means and methods.”
FCG_Website_FPT_Air_Leakage_Sample.docx Page 3 of 6
158 Burt Road⏐Lexington, KY 40503⏐Tel. (859) 278-5552⏐Fax (859) 278-6501
2611 Waterfront Parkway, Suite 340⏐Indianapolis, IN 46214⏐Tel. (317) 536-2618
[Project Name]
“This Functional Performance Test document represents FCG's standard test protocol, basic functional test, and FCG's best understanding of the
designed sequence of operation. This document DOES NOT define design intent, supersede contract documents, or direct means and methods.”
FCG_Website_FPT_Air_Leakage_Sample.docx Page 4 of 6
158 Burt Road⏐Lexington, KY 40503⏐Tel. (859) 278-5552⏐Fax (859) 278-6501
2611 Waterfront Parkway, Suite 340⏐Indianapolis, IN 46214⏐Tel. (317) 536-2618
[Project Name]
Q = [CFMref2 x (ΔP/.05)]1/2
8 Bldg. Air Leakage = _______ CFM/sf @ ______Pa (ASTM E779 Reference ΔP)
“This Functional Performance Test document represents FCG's standard test protocol, basic functional test, and FCG's best understanding of the
designed sequence of operation. This document DOES NOT define design intent, supersede contract documents, or direct means and methods.”
FCG_Website_FPT_Air_Leakage_Sample.docx Page 5 of 6
158 Burt Road⏐Lexington, KY 40503⏐Tel. (859) 278-5552⏐Fax (859) 278-6501
2611 Waterfront Parkway, Suite 340⏐Indianapolis, IN 46214⏐Tel. (317) 536-2618
[Project Name]
- END TEST -
“This Functional Performance Test document represents FCG's standard test protocol, basic functional test, and FCG's best understanding of the
designed sequence of operation. This document DOES NOT define design intent, supersede contract documents, or direct means and methods.”
FCG_Website_FPT_Air_Leakage_Sample.docx Page 6 of 6