. IR Values For Electrical Apparatus & Systems
IR Value for Transformer
be ger
|. IR Value for Electric motor
1. IR Values For Electrical Apparatus & Systems
(PEARL Standard / NETA MTS-1997 Table 10.1)
Megger | Min.JR
Size | Value
50 Volts 500 Volts | 25 MO
(00 Volts 4,000 | 100 Mo
Volts
BK 2,500 {1,000 Ma
Volts
BK 2,500 {2,000 MO
Volts
5 KV 2,500 {5,000 M0
Volts
ps5 KV 5,000 | 20,000
Volts ma
B5 KV 15,000 | 100,000
Volts ma
he Kv 15,000 | 100,000
Volts ma
fo KV 15,000 | 100,000
Volts ma
‘One Meg ohm Rule for IR Value for Equipment
Based upon equipment rating:
< 1K V = 1 MQ minimum
>AKV = 1 MQ MIKV
As per IE Rules-1956