Vous êtes sur la page 1sur 10

DESIGN NOTES AFTER PRELIMENARY EXAM

Overcurrent Protection (Article 2.40) During ground fault, dangerous voltages


and abnormally large currents exist.

Overcurrent protection devices- protects


circuits and equipment but they protect circuits
in one way and equipment in another way

An OCPD protects a circuit by:

1. By opening when current reaches a


value that would cause an excessive
temperature rise in the conductors
2. The interrupting rating must be
sufficient for the maximum possible
fault current available on the line side
terminals of the equipment
C60 Breakers
3. Short circuits and faults aren’t normal
Article 2.40- provides the requirements for operating conditions. Thus, the OCPD’s
selecting and installing overcurrent protection for equipment have different
devices (OCPD’s) characteristics than OCPD’s for
conductors.
An overcurrent exists when current exceeds the
rating of conductors or equipment. It can result
from overload, short-circuit, or ground fault.

Overload- a condition in which


equipment or conductors carry current
exceeding their rated ampacity. An
example is plugging 4-1500 W hair
dryers into a 20 A branch circuit. Each
dryer is 6.52 amps

Short-circuit- the unintentional


electrical connection between any two
normally current carrying conductors of
a circuit (line to line or line to neutral)
CIRCUIT PROTECTION
Ground fault- an unintentional, OCPD’s come in standard sizes which are
electrically conducting connection listed in
between an ungrounded conductor of a
circuit and the equipment grounding PEC 2.40.1.6 (Standard Ampere Rating)
conductor, metallic enclosures, metallic a. Fuses and Fixed- Trip Circuit
raceways, metallic equipment, or each. Breakers (Inverse time circuit
breakers)
DESIGN NOTES AFTER PRELIMENARY EXAM

15, 20, 25, 30, 35, 40, 45, 50, 60, 70, protected) if all of the conditions are
80, 90, 100, 110, 125, 150, 175, 200, met:
225, 250, 300, 350, 400, 450, 500,
600, 700, 800, 1000, 1200, 1600, - The conductors do not supply multi-
2000, 2500, 3000, 4000, 5000, and outlet receptacle branch circuits
6000 amperes - The ampacity of a conductor after
ampacity adjustment and for
(Red means not available in the
correction doesn’t correspond to
market)
the standard rating of a fuse or a
Additional for fuses: 1,3,6,10 and circuit breaker
601 - The protection device does not
exceed 800 A
b. Adjustable trip Circuit Breakers- the c.
rating of adjustable-trip circuit d. Service conductors are covered
breakers having external means for e. Busway taps are covered
adjusting the current rating setting f. For motors
(long-time pick-up setting), not g. For generators
meeting 2.40.1.6

PEC 2.40.1.8 FUSES OR CIRCUIT


BREAKER IN PARALLEL PEC 2.40.2.5 LOCATION OF OCPD’S ON
PREMISE
- Fuses and circuit breakers shall be
permitted to be connected in a. Accessibility
parallel where they are factory - This rule does not prohibit the
assembled in parallel and listed as a locking of panel doors or the placing
unit. Individual fuses, circuit of a padlock on a circuit breaker to
breakers, or combinations thereof restrict access
shall not otherwise be connected in - Install OCPD enclosures such that
parallel. the center of the grip operating
handle , when in its highest position,
PEC 2.40.1.4 PROTECTION OF isn’t more than 2 meter above the
CONDUCTORS floor or working platform. Four
OCPD application will vary under the exemptions exist for this rule:
following circumstances: o Busways as provided in
3.68.2.3
a. Power Loss Hazard- conductor o Supplementary OCPD’s as
overload protection is not required described in 2.40.1.10
where circuit interruption would o OCPD’s as described in
create a hazard (e.g. fire pump or 2.25.2.11
material-handling magnet). Short o OCPD’s located next to
circuit protection is still required. equipment that they supply
b. Devices rated 800 amperes or less- access shall be by portable
You can use the higher standard means
rating overcurrent device (above the b.
ampacity of the ungrounded being
DESIGN NOTES AFTER PRELIMENARY EXAM

c. Not exposed to Physical damage-


Electrical equipment must be
suitable for the environment. Give
consideration to the presence of
conditions, which may deteriorate
conductors or equipment
d. Not in vicinity of easily ignitable
material- example in clothes closet
e. Not located in bathrooms- not in
dwelling units or guest room (or
guest suites) or hotels or motels.
This rule also applies to service
disconnecting means even in
commercial or industrial facilities

PEC 2.40.3 ENCLOSURES

a. Protection from physical damage


b. Operating handle- shall be
accessible without opening a door or
cover
c. Damp or wet locations- enclosure PEC 2.40.7 CIRCUIT BREAKERS
shall comply with 3.12.1.2(a) a. Method of operation
d. Vertical position- enclosures o Circuit breakers must be
combining OCPD’s must be mounted capable of being opened
in a vertical position unless this is and closed by hand
impractical. Circuit breakers o Non-manual means if
enclosures can be horizontal if the operating a circuit breaker,
circuit breaker is installed per such as electrical shunt trip
2.40.7.2 or pneumatic operation are
- The requirements specify that permitted only if the circuit
where circuit breaker handles are breaker can also be
operated vertically, the “up” manually operated
position of the handle must be in the b. Indicating- circuit breakers shall
“on” position. Therefore, an clearly indicate whether they are
enclosure that contains one circuit open “off” or closed “on” position
breaker can be mounted c. Non-tamperable- the design of the
horizontally, but an enclosure that circuit breaker shall be free from any
contains a panelboard or load center alteration of its trip
with multiple breakerson the point(calibration) or the time
opposite sides of each other would required for its operation requires
have to be mounted vertically. dismantling of the device or
breaking of a seal for other intended
adjustments
DESIGN NOTES AFTER PRELIMENARY EXAM

PEC 2.40.7.4 MARKING - Manufacturer


- Rated kVA
a. Durable and visible- ampere rating
- Primary and secondary
b. Location- for 100 amps or less and
voltage
600 v or less the rating is etched,
- Impedance (if 25kVA or
molded, stamped on their handles
larger)
c. Interrupting rating- shall be shown
- Required clearance (if it has
on the breaker
ventilating openings)
d. Used as switches “SWD or HID”
3. Stay cool
marking
- Although overheating is a
e. Voltage marking- indicative of their
core issue with the
capability to interrupt fault currents
transformer, PEC does not
Transformer completely address it
because it isn’t a design
- A device which steps up or steps manual.
down alternating voltages - Selecting the right
- The current is varied in the opposite transformer for the
direction by the same proportion application is the first step in
when the voltage in the circuit is addressing the heat issue
stepped up or stepped down - The next step in the process
- A transformer does not change one is protecting the
form of power into another like a transformer against
generator or motor overheating by providing
TYPES: overcurrent protection.
- The requirements for
1. Liquid type- construction consists of overcurrent protection of
windings immersed in a liquid and transformer secondaries in
encapsulated/ sealed in tank. The PEC Art. 4.50 apply only to
liquid serves the purpose of an the protection of
insulation medium and a cooling transformers, not to
agent protection of conductors
2. Dry type- consists of insulated - PEC Art. 2.40 apply only to
winding wrapped around a core. the protection of
This type uses air for cooling and conductors not to the
transfer heat protection of transformers
1. Definition –(per PEC 4.50.1.2) - But it is possible that
Transformer- An individual transformer, overcurrent protection of
single or polyphase, identified by a single PEC Art. 4.50 also satisfies
nameplate, unless otherwise indicated the requirements of PEC Art.
in this article. 2.40 for protection of
2. Markings (PEC 4.50.1.11) conductors and vice versa.
Read the label. Every transformer comes 4. Transformer ventilation (PEC 4.50.1.9)
with a nameplate that identifies: Transformer ventilation requirements
can be summed up as follows:
DESIGN NOTES AFTER PRELIMENARY EXAM

- Provide enough ventilation - Be provided with locks that


so that the transformer are accessible only to
doesn’t overhead qualified persons
- Make sure the openings
NOTE: Vaults are for
aren’t blocked by wall or
transformers installed indoors
other obstructions
which are oil insulated
- Install per manufacturer’s
instructions 8. Vault Ventilation (PEC 4.50.3)
5. Accessibility - When designing and
Transformers must be readily accessible locating a transformer vault
to qualified personnel for inspection and do … to ventilate it to the
maintenance however, you don’t make outside. Locate ventilation
dry-type transformer readily accessible, openings as far as possible
if you locate them. from doors, windows and
- In the open on walls, combustible materials air.
columns, or structures PEC 4.50.3.5(A)
- Above suspended ceilings or - A vault ventilated by natural
in hollow spaces of circulation must have no
buildings. Transformers more than 50% of the total
installed in that space, opening area near the floor
however, must be rated no with the remainder of
more than 50kVA and can’t opening area in the roof or
be permanently closed in by sidewalls near the roof. PEC
the structure. 4.50.3.5(B).
6. Construction (PEC Art. 4.50.3.2) - For vault ventilated by
- The floors, walls, ceilings natural circulation, the total
and roof of vaults must have opening must be at least
adequate structural 1900 mm2 per kVA of
strength with a minimum transformer capacity in
fire resistance of 3 hours, service and the net area
such as 100mm thick shall not be less than 0.1
reinforced concrete mm2 for 50 kVA or less. PEC
- The minimum fire resistance 4.50.3.5(C).
(for the vault and door) - Cover openings to avoid
drops to 1 hour, where an unsafe conditions. You can
automatic sprinkler system use grating screens, or
protects the vault louvers to provide
7. Vault doors must be protection. PEC 4.50.3.5(D).
- Swing out - If you have indoor openings,
- Be equipped with panic bars you must provide them with
or pressure plates so the automatic closing fire
door can open from inside dampers rated not less than
under simple pressure 1-1/2 hours. These must
DESIGN NOTES AFTER PRELIMENARY EXAM

close in response to a vault breaker protection for both the primary


fire. and the secondary. For the transformer
in this exhibit, both the primary and
*Table 4.50.1.5(B) MAXIMUM RATING OR
secondary voltage are over 600 volts
SETTING OF OVERCURRENT PROTECTION FOR
TRANSFOREMRS 1000 VOLTS AND LESS (AS A
PERCENTAGE OF TRANSFORMER-RATED Computations for motor circuits are different
CURRENT) from those other circuits must handle
overcurrent.
Page 385-386
When motor start across the line, they typically
Sample Problems:
draw five times the running current. This
1. What is the primary overcurrent device temporary “in rush” is an overload condition.
rating and primary conductor size do you
To handle inrush while still providing adequate
need for a 45kVA, 3 phase, 480V-24-V
overcurrent protection, we divide overcurrent in
transformer that will operate at its full load
two parts:
rating continuously? Terminals are rated 75°
C. 1. Short circuit and ground fault
2. What is the secondary conductor size for the protection- Typically this is via a fuse or
above? circuit breaker sized large enough to let
the motor start. But if it is large enough
to let the motor start, it’s too large to
Table 4.50.1.3(A) MAXIMUM RATING OR provide overload protection.
SETTING OF OVERCURRENT PROTECTION FOR 2. Overload protection- This protect the
TRANSFORMERS OVER 1000 VOLTS (AS A motor and wiring at a value close to the
PERCENTAGE OF TRANSFORMER-RATED actual running current of the motor, but
CURRENT) with sufficient time delay to allow the
motor to start.
Page 385

• A transformer rated over 600 volts with


a primary rated over 600 volts, with MOTOR PROTECTION
secondary protection consisting of six An electrical problem:
circuit conductors. The sum of the • Overvoltage, under-voltage, phase
ratings of the circuit breakers is not unbalance or single-phasing (phase loss)
permitted to exceed 300 percent of the • Short-circuits which can surpass the
rated secondary current. breaking capacity of the contactor
• A transformer rated over 600 volts with A mechanical problem:
a primary rated over 600 volts, with • Stalled rotor, momentary or prolonged
secondary protection consisting of fuses overload
and circuit breakers. The sum of the
FLC (CODE) VERSUS MOTOR NAMEPLATE
ratings of all the overcurrent devices is
AMPERES (ACTUAL)
not permitted to exceed the rating
permitted for fuses. • Full-Load Current (FLC)
• A transformer with 6 percent impedance o Table 4.30.14.1,2,3,4
and rated over 600 volts using circuit- o Table FLC is used to size:
DESIGN NOTES AFTER PRELIMENARY EXAM

▪ Conductors Use FLA for:


▪ Short-circuit and 1. Motors built to operate less than
ground-fault protection 1200 rpm
devices 2. High torque with higher FLC’s
• Motor Nameplate (FLA) 3. Multispeed motors (full load current
o The motor nameplate is used to varies with speed)
size overload protection
Example problems:
STARTING VS RUNNING CURRENT
Which of the following three is the highest rated
• Overload protection is sized between motor?
115% and 125% of the nameplate
1. 10 HP, 208V, 3 phase
running current rating
2. 3 HP, 208V, single phase
• Short-circuit and ground-fault
3. 3 HP, 120V, single phase
protection is sized between 175% and
300% of the motor FLC Solution:

Which current? As per Table 4.30.14.2 and 4.30.14.4

The FLC is in PEC Table 4.30.1 up to Table 3.40.4 1. 10 HP, 208V, 3 phase- FLC is 30.8 A
2. 3 HP, 208V, single phase-FLC is 18.7 A
3. 3 HP, 120V, single phase-FLC is 34 A
Use the FLC to determine:

1. Conductor ampacity
Highest rated,
2. Circuit short circuit and ground fault
overcurrent device When selecting the feeder conductors or the
feeder short circuit ground fault protection
If you have listed motor-operated appliance, you
device, the highest rated motor is the one
must use the motor FLC marked on the appliance
with highest FLC (not the highest
nameplate) to determine the ampacity or rating
horsepower)
of the:

- Disconnecting means
- The branch circuit short DESIGN: SINGLE FAMILY DWELLING (2018)
circuit conductors
Notes on wiring design examples
- Ground fault protection
1. Branch circuit required
FLA is the motor nameplate rating. This is the
a. Not more than 50 sqm. With
current the motor draws while producing its
load not exceeding 3680 volt-
rated horsepower at its rated voltage (based on
amperes—the code permits the
its rated efficiency and power factor)
use of only one 20A circuit
Use FLA to determine the: (Section 2.10.1.11(C)(5))
2. Feeder or service load calculations
1. Conductor ampacity for other than the
a. Follows the method provided in
continuous duty
Part 2.20.2
2. Brach circuit short circuit and ground
3. Selection of conductors
fault overcurrent device size
DESIGN NOTES AFTER PRELIMENARY EXAM

a. Refer to Table 3.10.2.6(B)(16) 1.1 TOTAL LOAD;


thru 17 a. General lighting and Convenience
b. Minimum size of service receptacle load (See Table 2.20.2.3)
entrance conductor, see Section 50 sqm. X 24 volt-amperes per sqm. =
2.30.4.3 page 75 1200VA
c. Conductor ampacities given in b. Typical Appliance Load:
the examples (PEC) for copper One electric flat iron= 1200VA
wires are based on ambient One television set= 80VA
temperature of 30°, except One electric fan=75VA
specified, and at least 125% of One radio= 20VA
the continuous current. Voltage TOTAL LOAD= 2575VA
drop has not been considered.
4. Selection of overcurrent protection
TOTAL COMPUTED CURRENT:
a. Refer to Section 2.40.1.6 page
85 for standard ratings of fuses 2575 VA/230V=11 A
and inverse time circuit breakers
5. Selection of conduit 1.2 CIRCUIT REQUIREMENT: Use 20-ampere, 2
a. Refer to Table C.1 page 967, wire circuit
conduit and tubing fill tables 1.3 SERVICE ENTRANCE CONDUCTORS- Use two-
6. Voltage 3.5mm2 TW copper size minimum breaker
a. Nominal voltage of 230 V is used (See exception Section 2.30.3.2) page 74
in computing the ampere load 1.4 SERVICE EQUIPMENT- Use one-30 ampere,
7. Grounding 2Pst, 250 volt safety switch or use one- 20
a. Refer to Table 2.40.3.17 page amperes trip 2P 240 volt enclosed molded
117 and 2.50.5.13(C)(10) page circuit breaker
117 for sizes of grounding NOTE: NOT THE CURRENT PRACTICE!!! (LOL)
conductors and electrodes
8. Allowance for future expansion SINGLE FAMILY DWELLING UNIT UP TO 150 SQM.
a. Advisable to use a larger service FLOOR (NOT MORE THAN 6 CIRCUITS)
conductor to accommodate The dwelling has a floor area of 145 sqm.
future loads depending on the It has typical household appliances and laundry
anticipated expansion including one-1.5 HP room air conditioning unit
SINGLE FAMILY DWELLING UNIT, UP TO 50 1. TOTAL LOAD
SQUARE METERS FLOOR AREA WITH LOAD NOT a. General lighting and convenience
ECVEEDING 3680 VOLT-AMPERES receptacle BC (Table 2.20.2.3)
The dwelling has a floor area of 50 145 sqm. X 24VA per sqm. = 3480 VA
square meters with typical small appliance loads
for residential units -Calculate the minimum number of
general lighting branch circuits

The computed load is


3480VA/230V = 15.13 A
DESIGN NOTES AFTER PRELIMENARY EXAM

To allow for future needs provide 2-20 Example 1


amperes branch circuits (One circuit is
Using the spare branch circuit how many
theoretically enough/ 1 circuit will be
receptacles can be placed on a 230 volt, 20 amp
spare)
circuit
-Determination of maximum permissible
Solution:
number of lighting fixtures on a general
lighting branch circuit Step 1: Determine the maximum circuit power
=230 V * 20 A (0.8)= 3600 VA
Solution:
Step 2: Then divide the power by the load per
This is a continuous load, so the current used by
receptacle for 20 amp circuit: Maximum
the lights can only be 80% of the branch circuit
allowable number of receptacles =3680VA/180
current rating:
VA =20.4 (not practiced)
Allowable current 20A*0.80= 16A
b. Small appliance load : (Section
By dividing the allowable load by the load of each 2.10.1.11(C)(1))
lamp, the total number of fixtures us
One 20 ampere @ 1500 volt-amperes=
determined:
1500 VA
The total number of fixtures= 16 A/0.7 =22.8
Note: The section says one or more –
fixtures
20A small app BC)
So, the maximum number of fixtures on the
The computed load is 1500/230=6.52 A
circuit is 22. (not practiced)
Provide 1 x 20 amperes small appliance
For good design, usually assume that the general
circuit
lighting branch circuit will have some utilization
equipment fastened in place and must be c. Laundry circuit (Section
derated to 50% of its rating. 2.10.2.11(C))
-To calculate the maximum allowable number of One 20 ampere @ 1500 volt-amperes=
receptacles on a branch circuit 1500 VA
Step 1: Determine the maximum circuit power Provide one- 20 ampere laundry circuit
by multiplying the branch circuit voltage and
amperage SUB TOTAL: 6480 VA

Step 2: Then divide by 180 VA d. Application of demand factor ( Table


2.20.3.3 Lighting Load) page 56
The result from Step 2= the max allowable single,
duplex or triplex receptacles or a combination of First 3000 VA @100 DF= 3000 VA
them on a branch circuit Remainder @ 35% DF (3480*0.35)=
1218 VA

e. Other loads: Table 2.20.3.16 page 58


and Table 4.30.14.2 page 370
DESIGN NOTES AFTER PRELIMENARY EXAM

One- 1.5HP room ACU 10A*230V @


100% DF= 2300 VA

Provide one -20 amperes room ACU


circuits

TOTAL NET COMPUTED LOAD: 6518 VA

2. CIRUIT REQUIREMENTS:

Use 5-20 A 2 wire branch circuit

3. SERVICE ENTRANCE CONDUCTORS:

Total full load current =6518 VA+ 25% (2300


VA)/230V= 31 A

Use two- 8mm2 THW wires (50 amps) min


size

(See Table 2.40.1.6(A) and Table 3.10.2.6(B)


for the conductor and overcurrent
protection ampere rating

See Sec 2.30.4.1 for the minimum service


entrance conductor)

4. SERVICE EQUIPMENT: Ungrounded


conductor
a. Maximum current rating of
protective device with inverse time
circuit breaker=
(3000+1218+250%(2300/230))=43 A

Use 50 ampere trip 2p molded case


circuit breaker

Vous aimerez peut-être aussi