Air System Sizing Summary for 1.

COMEDOR
Project Name: VOLVO 04/02/2019
Prepared by: ANNAT 11:25a. m.

Air System Information


Air System Name 1. COMEDOR Number of zones 1
Equipment Class UNDEF Floor Area 3315.0 ft²
Air System Type SZCAV Location Lima, Peru

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 22.4 Tons Load occurs at Jan 1500
Total coil load 268.6 MBH OA DB / WB 86.0 / 75.0 °F
Sensible coil load 168.2 MBH Entering DB / WB 79.6 / 67.9 °F
Coil CFM at Jan 1500 6184 CFM Leaving DB / WB 54.4 / 53.5 °F
Max block CFM 6184 CFM Coil ADP 51.6 °F
Sum of peak zone CFM 6184 CFM Bypass Factor 0.100
Sensible heat ratio 0.626 Resulting RH 51 %
ft²/Ton 148.1 Design supply temp. 55.0 °F
BTU/(hr·ft²) 81.0 Zone T-stat Check 0 of 1 OK
Water flow @ 10.0 °F rise 53.75 gpm Max zone temperature deviation 0.7 °F

Supply Fan Sizing Data


Actual max CFM 6184 CFM Fan motor BHP 0.51 BHP
Standard CFM 6175 CFM Fan motor kW 0.40 kW
Actual max CFM/ft² 1.87 CFM/ft² Fan static 0.30 in wg

Outdoor Ventilation Air Data


Design airflow CFM 1950 CFM CFM/person 15.00 CFM/person
CFM/ft² 0.59 CFM/ft²

Hourly Analysis Program v5.01 Page 1 of 2


Air System Design Load Summary for 1. COMEDOR
Project Name: VOLVO 04/02/2019
Prepared by: ANNAT 11:25a. m.

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 86.0 °F / 75.0 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 1317 ft² 40117 - 1317 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 3315 ft² 19657 - 3315 ft² 12916 -
Window Transmission 1317 ft² 12929 - 1317 ft² 18801 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 1318 ft² 5092 - 1318 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 4177 W 11917 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1658 W 5068 - 0 0 -
People 130 24912 35100 0 0 0
Infiltration - 1562 3888 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 12125 3899 0% 0 0
>> Total Zone Loads - 133379 42887 - 31717 0
Zone Conditioning - 144481 42887 - -2211 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 6184 CFM 0 - 6184 CFM 0 -
Ventilation Load 1950 CFM 19630 57565 1950 CFM 3101 0
Supply Fan Load 6184 CFM 1375 - 6184 CFM -1375 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 2% 2668 - 2% 634 -
>> Total System Loads - 168154 100452 - 149 0
Central Cooling Coil - 168154 100464 - 0 0
>> Total Conditioning - 168154 100464 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v5.01 Page 2 of 2