A) COOKING LOADS
1-10KW RANGE
2-12KW RANGE 17,000 VA = 17000 VA
1-11KW RANGE
2-8KW RANGE
1-5KW RANGE (16+5KW)0.55 = 11550 VA
2-3KW OVEN (2X3KW) 0.75 = 4500 VA
B) AIRCONDITIONING UNITS
C) LIGHTING LOADS
D) OTHER LOADS
IFL = 68890+(.25x12x230)
230
= 302.52 A
ARC WILSON M. RIEGO October 1, 2013
BSEE/ 5TH YEAR ENGR. DEL ROSARIO
A) LIGHTING LOADS
B) OTHER LOADS
= 48,112 VA
IFL = 48112+(.25x12x230)
230
= 121.18A
ARC WILSON M. RIEGO October 1, 2013
BSEE/ 5TH YEAR ENGR. DEL ROSARIO
A) COOKING LOADS
B) AIR-CONDITIONING UNITS
C) LIGHTING LOAD
D) OTHER LOADS
IFL = 59300+(.25x12x230)
230
= 260.82 A
COMPUTATION OF LOADS:
A) LIGHTING LOADS
B) OTHER LOADS
= 23500VA
IFL = 23500+(.25x12x230)
230
= 105.17 A
ARC WILSON M. RIEGO October 1, 2013
BSEE/ 5TH YEAR ENGR. DEL ROSARIO
TRANSFORMER 1
Max. Demand = (23.5 x 12) / 1.45 = 243.10 KVA
Use: 250 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER2
Max. Demand = (23.5 x 12) / 1.45 = 243.10 KVA
Use: 250 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER3
Max. Demand = (23.5 x 12) / 1.45 = 243.10 KVA
Use: 250 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER 4
Max. Demand = (23.5 x 12) / 1.45 = 243.10 KVA
Use: 250 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER 5
Max. Demand = (23.5 x 12) / 1.45 = 243.10 KVA
Use: 250 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER 6
Max. Demand = (23.5 x 10) / 1.45 = 162.07 KVA
Use: 167 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER7
Max. Demand = (23.5 x 12) / 1.45 = 243.10 KVA
Use: 250 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
ARC WILSON M. RIEGO October 1, 2013
BSEE/ 5TH YEAR ENGR. DEL ROSARIO
TRANSFORMER8
Max. Demand = (23.5 x 12) / 1.45 = 243.10 KVA
Use: 250 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER9
Max. Demand = (23.5 x 12) / 1.45 = 243.10 KVA
Use: 250 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER 10
Max. Demand = (23.5 x 12) / 1.45 = 243.10 KVA
Use: 250 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER11
Max. Demand = (23.5 x 12) / 1.45 = 243.10 KVA
Use: 250 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER12
Max. Demand = (23.5 x 10) / 1.45 = 162.07 KVA
Use: 167 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER13
Max. Demand = (48.112 x 10) / 1.45 = 331.81 KVA
Use: 333 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER14
Max. Demand = (48.112 x 10) / 1.45 = 331.81 KVA
Use: 333 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER15
Max. Demand = (48.112 x 10) / 1.45 = 331.81 KVA
Use: 333 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER16
Max. Demand = (48.112 x 10) / 1.45 = 331.81 KVA
ARC WILSON M. RIEGO October 1, 2013
BSEE/ 5TH YEAR ENGR. DEL ROSARIO
TRANSFORMER17
Max. Demand = (48.112 x 10) / 1.45 = 331.81 KVA
Use: 333 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER18
Max. Demand = (48.112 x 10) / 1.45 = 331.81 KVA
Use: 333 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER19
Max. Demand = (48.112 x 10) / 1.45 = 331.81 KVA
Use: 333 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER20
Max. Demand = (48.112 x 10) / 1.45 = 331.81 KVA
Use: 333 KVA, 1Ø Transformer
Supplies: Block 1 (1-6), Block 5 (23-28)
TRANSFORMER21
Max. Demand = (48.112 x 10) / 1.45 = 331.81 KVA
A5
Php Php
washer, square, flat, 2¼'' x 2¼'' x 3/16'', 13/16'' dia. Hole 2
6.85 13.70
Php Php
insulator, suspension, 6'', clevis type 2
90.75 181.50
Php Php
clamp, deadend loop, #6 to #2/0 ACSR 1
33.00 33.00
Php Php
Bolt, Oval Eye, 5/8" X 12" 2
59.45 118.90
7.62/13.2 KV. PRIMARY, 1-
Php Php
PHASE Anchor tape 1
14.31 14.31
DEADEND (SINGLE)
Php Php
Clevis, Secondary Swinging Without Spool 1
61.35 61.35
Php Php
Clamp, Loop Deadend, #6 to #2/0 ACSR 2
36.36 72.72
Php Php
Insulator, Spool, 1-3/4", ANSI Class 53 - 2 1
16.21 16.21
Php Php
Nut, Lock, Mf Type, 5/8" 2
7.08 14.16
Sub Php
Total 525.85
ARC WILSON M. RIEGO October 1, 2013
BSEE/ 5TH YEAR ENGR. DEL ROSARIO
G9
Php Php
Bolt, Machine, 5/8" X 10" 2
28.81 57.62
Php Php
washer, square, flat, 2¼'' x 2¼'' x 3/16'', 13/16'' dia. Hole 2
6.85 13.70
Php Php
Connector, Compression, 4
32.88 131.52
Php Php
Cutout And Arrester Combination 1
4,700.00 4,700.00
Php Php
Cutout Fuse 1
500 500
7.62/13.2 KV SINGLE Php Php
Connector, Split Bolt 1
PHASE TRANSFORMER 100.60 100.60
AT 1- PHASE TANGENT Php Php
Wire, Grounding, Aluminum Alloy, 3 Strand, #4 AWG (Ft.) 6
5.99 35.94
Php Php
Transformer, Pole Type, CSP, 10 KVA 25, 1
152.75 152.75
Php Php
Clamp, Hot Line, #2 - #4/0 ACSR Main to #2 - #4/0 1
259.15 259.15
Lead , Duples Poly. 4 A C S R for 10 KVA, 2 A C SR for 15 Php Php
4
and 25 KVA 500 2000
Php Php
Nut, Lock, Mf Type, 5/8" 2
7.08 14.16
Php Php
Armor Rod, Tapping 1
28.35 28.35
Php
Sub Total
5,493.79
ARC WILSON M. RIEGO October 1, 2013
BSEE/ 5TH YEAR ENGR. DEL ROSARIO
C22X
Php Php
Insulator, Pin Type, Porcelain, ANSI Class 55 - 3 8
87.75 702.00
Php Php
Pin, Pole Top, Channel, 1" Thread, 20" Long 12
109.94 1,319.28
Php Php
Bolt, Machine, 5/8" X 12" 8
33.69 269.52
Php Php
Bolt, Machine, 5/8" X 16" 1
35.75 35.75
washer, square, flat, 2¼'' x 2¼'' x 3/16'', 13/16'' dia. Php Php
8
Hole 6.85 54.80
Php Php
Bolt, Oval Eye, 5/8" X 12" 1
59.76 59.76
Php Php
7.62/13.2 KV 3-PHASE Armor Tape 3.936
14.31 56.32
CROSSARM
Php Php
CONSTRUCTION Clamp, Hot Line, #2 - #4/0 ACSR Main to #2 - #4/0 3
259.15 777.45
SINGLE PHASE JUCTION
Php Php
AT 0 - 5 ANGLE Jumpers , 4 AWG, 3 Strand Aluminum Alloy 1
5.99 5.99
Php Php
Shackle, Anchor, Forged Steel, Galvanized 4
80.19 320.76
Php Php
Insulator, Spool, 3", ANSI Class 53 - 4 2
31.27 62.54
Php Php
Nut, Eye, 5/8" Conventional 4
59.58 238.32
Php Php
clamp, deadend loop, #6 to #2/0 ACSR 4
33.00 132.00
Php Php
Armor Rod, Tapping 3
28.35 85.05
Php Php
Clevis, Secondary Swinging Without Spool 2
200.00 400.00
Php
Sub Total
4,519.54
ARC WILSON M. RIEGO October 1, 2013
BSEE/ 5TH YEAR ENGR. DEL ROSARIO
NO. OF UNIT or
Items Cost/Unit TOTAL (Php)
meter
PHP
Pole, Concrete 35’ 9464.25 10
96,640
PHP
Pole, Concrete 30' 6982.63 46
321,172
PHP
Transformer Bracket 352.77 76
26,810.52
Conductor, Bare,
PHP
ACSR #2 AWG. 6/1 20.25 12000
243,000.00
704.82m,
PHP
Total2
671,347.80
Total1+Total2
OVERALL TOTAL COST
PHP 28,866,140.27
ARC WILSON M. RIEGO October 1, 2013
BSEE/ 5TH YEAR ENGR. DEL ROSARIO