Panel-type Filter, Type FP oprema

Panel-type Filter, Type FP, is intended for air filtration in ventilation and air-conditioning systems; it is most frequently applied as a
pre-filter in function of a dust filter. It can be installed in a wall (vertically) or in a ceiling (horizontally). The FP panel filter consists of
filter cells 610 x 610 mm in size, arranged in rows and columns (along length and height dimension), and an installation frame
with masonry anchors. Construction is made of galvanised steel sheet and profiles. Various filter media are applicable; the most
frequently used are G3 and G4 class filter media acc. to EN 779 (s. 5/S0 brochure). Inlet air velocities, depending on filter
medium selected and permitted pressure drop, range from 0.9 to 2.5 m/s (s. guidelines in 5/S0 brochure). Filter insert change is
performed from the air entry side of the filter ("dirty side").

FILTER INSERT
stiffener

TIGHTENING FRAME
tightening element

VOID SPACE FOR


FILTER CHANGE

5/S2-02
INDEX

oprema Panel-type Filter, Type FP

Schedule of Air Flow Rates at Various Air Velocities

Filter Size (mm) Number of Cells Air Flow Rate (m3/h) at Velocity of Approx.
B x H a x b c d 0.9 m/s 1 m/s 1.5 m/s 2 m/s 2.5 m/s Weight (kg)
610 610 1 1 1125 1300 1950 2600 3300 7.5
610 1220 1 2 1 15
2250 2600 3900 5200 6600
1220 610 2 1 1 15
610 1830 1 3 2 22.5
3375 3900 5850 7800 9900
1830 610 3 1 2 22.5
610 2440 1 4 3 30
1220 1220 2 2 1 1 4500 5200 7800 10400 13200 30
2440 610 4 1 3 30
610 3050 1 5 4 37.5
5625 6500 9750 13000 16500
3050 610 5 1 4 37.5
1220 1830 2 3 1 2 45
1830 1220 3 2 2 1 6750 7800 11700 15600 19800 45
3660 610 6 1 5 45
4270 610 7 1 6 7875 9100 13650 18200 23100 52.5
1220 2440 2 4 1 3 60
2440 1220 4 2 3 1 9000 10400 15600 20800 26400 60
4880 610 8 1 7 60
1830 1830 3 3 2 2 67.5
10125 11700 17550 23400 29700
5490 610 9 1 8 67.5
1220 3050 2 5 1 4 75
3050 1220 5 2 4 1 11250 13000 19500 26000 33000 75
6100 610 10 1 9 75
1830 2440 3 4 2 3 90
2440 1830 4 3 3 2 13500 15600 23400 31200 39600 90
3660 1220 6 2 5 1 90
4270 1220 7 2 6 1 15750 18200 27300 36400 46200 105
1830 3050 3 5 2 4 112.5
16875 19500 29250 39000 49500
3050 1830 5 3 4 2 112.5
2440 2440 4 4 3 3 120
18000 20800 31200 41600 52800
4880 1220 8 2 7 1 120
3660 1830 6 3 5 2 135
20250 23400 35100 46800 59400
5490 1220 9 2 8 1 135
2440 3050 4 5 3 4 150
3050 2440 5 4 4 3 22500 26000 39000 52000 66000 150
6100 1220 10 2 9 1 150
4270 1830 7 3 6 2 23625 27300 40950 54600 69300 157.5
3660 2440 6 4 5 3 180
27000 31200 46800 62400 79200
4880 1830 8 3 7 2 180
3050 3050 5 5 4 4 28125 32500 48750 65000 82500 187.5
5490 1830 9 3 8 2 30375 35100 52650 70200 89100 202.5
4270 2440 7 4 6 3 31500 36400 54600 72800 92400 210
3660 3050 6 5 5 4 225
33750 39000 58500 78000 99000
6100 1830 10 3 9 2 225
4880 2440 8 4 7 3 36000 41600 61500 83200 105600 240
4270 3050 7 5 6 4 39375 45500 68250 91000 115500 262.5
5490 2440 9 4 8 3 40500 46800 70200 93600 118800 270
4880 3050 8 5 7 4 300
45000 52000 78000 104000 132000
6100 2440 10 4 9 3 300
5490 3050 9 5 8 4 50625 58500 87750 117000 148500 337.5
6100 3050 10 5 9 4 56250 65000 97500 130000 165000 375

Ordering Example: FP 1220 × 1830 G4

Filter medium

Dimensions: B x H

5/S2-03
INDEX

Panel-type Bag Filter, Type FV oprema

Panel-type filter, Type FV, with bag filters, is intended for air filtration in ventilation and air-conditioning systems; it is most
frequently installed in a wall (vertically). When installed horizontally (in a ceiling) the filter bags must be hanging. The FV
panel/bag filter consists of bag-type filter cells arranged in rows and columns (along length and height dimension), and an
installation frame with masonry anchors. Basic size of the filter cell is 595 x 595 mm, i.e., 610 x 610 mm when in installation frame.
Half a cell (1/2 cell, 290 x 595 mm) and a quarter of a cell (1/4 cell, 290 x 290 mm) can also be delivered. Length of the filter bag
depends on airflow rate and the type of filter medium. Installation frame is made of galvanised steel sheet and profiles. Various
filter media are applicable; the most frequently used are G4 and F5 class filter media acc. to EN 779 (s. 5/S0 brochure). Energy
efficient operation of an FV filter is achieved at inlet air velocity of around 2.5 m/s and air flow rate of 3250 m3/h per filter cell. Filter
bags are changed from the air entry side of the filter ("dirty side").

VOID SPACE FOR


FILTER CHANGE

5/S2- 4
INDEX

oprema

Possible combinations of B and H dimensions, and relevant air flow rates (m3/h) at inlet velocity of v = 2.5 m/s

H [mm] 616 924 1232 1540 1848 2156 2464 2772 3080 3388 3696
B[mm] No. of Cells
1 1+1/2 2 2+1/2 3 3+1/2 4 4+1/2 5 5+1/2 6
616 1 3250 4875 6500 8125 9750 11375 13000 14625 16250 17875 19500
924 1+1/4 4875 7312 9750 8937 14625 17062 19500 21937 24375 26812 29250
1232 2 6500 9750 13000 16250 19500 21125 26000 29250 32500 35750 39000
1540 2+1/4 8125 8937 16250 20312 24375 28437 30875 36562 40625 44687 48750
1848 3 9750 14625 19500 24375 29250 34125 39000 43875 48750 53625 58500
2156 3+1/4 11375 17062 21125 28437 34125 39812 45500 51187 56875 62562 68250
2464 4 13000 19500 26000 30875 39000 45500 52000 58500 65000 71500 78000
2772 4+1/4 14625 21937 29250 36562 43875 51187 58500 65812 73125 80437 87750
3080 5 16250 24375 32500 40625 48750 56875 65000 73125 81250 89375 97500
3388 5+1/4 17875 26812 35750 44687 53625 62562 71500 80437 89375 128562 140250
3696 6 19500 29250 39000 48750 58500 68250 78000 87750 97500 107250 117000

Typical cell frames: Ordering Example:


FV 1848 x 1540 G4
Dimensions (mm)
Cell Size Cell Filter insert Filter medium

1 616 x 616 595 x 595 Dimensions: B x H


1/2 308 x 616 290 x 595
1/4 308 x 308 290 x 290

5/S2-05
INDEX

Panel-type Wedge Filter, Type FK oprema

Panel-type filter, Type FK, with wedge filters, is intended for air filtration in ventilation and air-conditioning systems, in which it is
most frequently used as a pre-filter. It is generally installed in a wall (vertically). When installed horizontally, wedge filters must be
pointing down to the ground. The FK panel/wedge filter consists of flat filter cells put together in a wedge-form arrangement in
rows and columns along length and height of the installation frame. Dimensions of the front area of the wedge cell are 457.5 x 610
mm. The bearing structure is made of galvanised steel sheet and profiles. Various filter media are applicable; the most frequently
used is G4 class filter medium acc. to EN 779 (s. 5/S0 brochure). Inlet air velocities, depending on filter medium selected and
permitted pressure drop, range from 2 to 5 m/s. Inlet air velocity of 3 m/s should be selected for energy efficient operation of an FK
filter. Filter frames/cells are changed from the air entry side of the filter ("dirty side").

FILTER MEDIUM

TIGHTENING FRAME

VOID SPACE
FOR FILTER
CHANGE

5/S2-06
INDEX

oprema Panel-type Wedge Filter, Type FK

Schedule of Air Flow Rates at Various Inlet Front Air Velocities

Filter Size (mm) Numb.of Cells Air Flow Rate (m3/h) at Velocity of Approx.
B x H a x b c d 2 m/s 3 m/s 4 m/s 5 m/s Weight (kg)
458 610 1 1 2000 3000 4000 5000 20.5
458 1220 1 2 1 34.5
4000 6 000 8000 10000
915 610 2 1 1 43
458 1830 1 3 2 49
6000 9000 12000 15000
1373 610 3 1 2 66
458 2440 1 4 3 63.5
915 1220 2 2 1 1 8000 12000 16000 20000 71
1830 610 4 1 3 89
458 3050 1 5 4 78
10000 15000 20000 25000
2288 610 5 1 4 111.5
915 1830 2 3 1 2 100
1373 1220 3 2 2 1 12000 18000 24000 30000 107
2745 610 6 1 5 134.5
3203 610 7 1 6 14000 21000 28000 35000 158
915 2440 2 4 1 3 129
1830 1220 4 2 3 1 16000 24000 32000 40000 143
3660 610 8 1 7 180
1373 1830 3 3 2 2 150
18000 27000 36000 45000
4118 610 9 1 8 203
915 3050 2 5 1 4 158
2288 1220 5 2 4 1 20000 30000 40000 50000 179
4575 610 10 1 9 225.5
1373 2440 3 4 2 3 194
1830 1830 4 3 3 2 24000 36000 48000 60000 201
2745 1220 6 2 5 1 215.5
3203 1220 7 2 6 1 28000 42000 56000 70000 252
1374 3050 3 5 2 4 238
30000 45000 60000 75000
2288 1830 5 3 4 2 252
1830 2440 4 4 3 3 259
32000 48000 64000 80000
3660 1220 8 2 7 1 288
2745 1830 6 3 5 2 303
36000 54000 72000 90000
4118 1220 9 2 8 1 324
1830 3050 4 5 3 4 317
2288 2440 5 4 4 3 40000 60000 80000 100000 324.5
4575 1220 10 2 9 1 250
3203 1830 7 3 6 2 42000 63000 84000 105000 353
2745 2440 6 4 5 3 390
48000 72000 96000 120000
3660 1830 8 3 7 2 404
2288 3050 5 5 4 4 50000 75000 100000 125000 397
4118 1830 9 3 8 2 54000 81000 101080 135000 455
3203 2440 7 4 6 3 56000 84000 112000 140000 455
2745 3050 6 5 5 4 477
60000 90000 120000 150000
4575 1830 10 3 9 2 505
3660 2440 8 4 7 3 64000 96000 128000 160000 520
3203 3050 7 5 6 4 70000 105000 140000 175000 557
4118 2440 9 4 8 3 72000 108000 144000 180000 585
3660 3050 8 5 7 4 636
80000 120000 160000 200000
4575 2440 10 4 9 3 651
4118 3050 9 5 8 4 90000 135000 180000 225000 716
4575 3050 10 5 9 4 100000 15 0000 200000 250000 796

Ordering Example: FK 1373 x 1830 G4

Filter medium

Dimensions: B x H

5/S2-07
INDEX

Duct-type Bag Filter, Type FKV oprema

Duct-type filter, Type FKV, with bag filters, is intended for air filtration in ventilation and air-conditioning system, in which it is
installed in tin ducts. The FKV filter consists of cells with filter bags of standardised size, arranged in rows within an installation
frame. Complete set of installation frame with filter cells is laterally slid into the filter casing built in the air duct. The filter casing is
laterally closed by a cover. Free cross-sectional area, i.e., dimensions of the casing are given in the table below. Filter bags are
always oriented vertically (see figure below). The casing is fitted with differential pressure gauge connections for pressure drop
measurements and filter saturation control. Basic size of the filter cell is 595 x 595 mm; half a cell (1/2 cell, 290 x 595 mm) and a
quarter of a cell (1/4 cell, 290 x 290 mm) can also be delivered. Construction is made of galvanised steel sheet and profiles.
Various filter media can be applied; the most frequently used are G5 or F5 class filter media acc. to EN 779 (s. 5/S0 brochure).

(Other lengths on special request)

Possible combinations of B x H dimensions, and relevant


AIR DUCT air flow rates (m3/h) at inlet frontal velocity of v = 2.5 m/s
H [mm ] 308 616 924 1232
B [mm ] No. of Cells 1/2 1 1+1/2 2
308 1/2 854 1707 2561 3415
616 1 1707 3415 5121 6830
924 1+1/2 2561 5121 7684 10245
1232 2 3415 6830 10245 13660

Ordering Example:

FKV 616 x 1232 G4

Filter medium
Void space for
filter change
Dimensions: B x H

5/S2-08
INDEX

oprema Duct-type Filter, Type FKN-1

v Void space for Void space for


H filter change from filter change from
left side "L" right side "D"

305

700 800 B 800

Duct-type filter, Type FKN-1, is intended for air filtration Example:


in ventilation and air-conditioning systems, in which it is
installed in ducts. The FKN-1 filter consists of filter cells Given:
that are laterally slid into the filter casing and set into the
inclined position, achieving thereby excellent sealing Duct filter FKN-1; B x H = 610 x 915 mm
characteristics. The casing is made of galvanised steel Volume flow rate V = 6030 m3/h, at v = 3 m/s
sheet and profiles. Filter inserts of various - G1 to F5 Filter insert class: G4
class - filter media can be applied (s. 5/S0 brochure).
Inlet air velocity depends on filter medium selected and Solution:
permitted pressure drop. For the flow resistance the air
velocity at the frontal (inlet) cross-section of the casing Diag. p.10:
is relevant. Filter change/insertion can be performed Initial pressure drop of filter insert: 50 Pa
laterally, either from left or from right side; the side Pressure drop of filter casing: 165 Pa
required should be specified in the order. Total: 215 Pa

Final pressure drop of filter insert


(selected from table in 5/S0 brochure): 160 Pa
Pressure drop of filter casing: 165 Pa
Total: 325 Pa

The result:
Pressure drop calculation of the installation should ensure
pressure of 325 Pa for this filter.

Table of air flow rates (m3/h)

Inlet air velocity v (m/s)


B x H
1m 1,5 m 2m 3m 4m 5m
610 x 305 670 1005 1340 2010 2680 3350
610 x 610 1340 2010 2680 4020 5360 6700
610 x 915 2010 3015 4020 6030 8040 10050
610 x 1220 2680 4020 5360 8040 10720 13400
610 x 1525 3350 5025 6700 10050 13400 16750
610 x 1830 4020 6030 8040 12060 16080 20100

Pressure drop diagram Ordering Example:


is given on page 10.
FKN-1 610 x 915 - L - G4

Filter medium

Filter cells changed/inserted:


L - from left side
D - from right side
Dimensions of inlet cross-section: B x H

5/S2-09
INDEX

Duct-type Filter, Type FKN- 2 oprema

v
Void space for Void space for
H filter change from filter change from
left side "L" right side "D"

305

700 800 B 800

Example:
Duct-type filter, Type FKN-2, is intended for air filtration in ventilation
and air-conditioning systems, in which it is installed in ducts. The Given:
FKN-2 filter consists of two rows of filter cells that are laterally slid
into the filter casing and set into the inclined position, achieving Duct filter FKN-2; B x H = 1220 x 915 mm
thereby excellent sealing characteristics. The casing is made of Volume flow rate V = 12060 m3/h, at v = 3 m/s
galvanised steel sheet and profiles. Filter inserts of various - G1 to F5 Filter insert class: G4
class - filter media can be applied (s. 5/S0 brochure).
Inlet air velocity depends on filter medium selected and permitted
pressure drop. For the flow resistance relevant is air velocity at the Solution:
frontal (inlet) cross-section of the casing. Filter change/insertion can
be performed laterally, either from left or from right side; the side Diag. p.10:
required should be specified in the order.( Filter cells are arrenged in Initial pressure drop of filter insert: 5 0 Pa
two rows, and are thus slid into or taken out of the casting one after Pressure drop of filter casing: 165 Pa
another.) Total: 215 Pa

Final pressure drop of filter insert


(selected from table in 5/S0 brochure): 160 Pa
Pressure drop of filter casing: 165 Pa
Table of air flow rates (m3/h) Total: 325 Pa
Inlet air velocity v (m/s)
BxH The result:
1m 1.5 m 2m 3m 4m 5m
1220 x 305 1340 2010 2680 4020 5360 6700
1220 x 610 2680 4020 5360 8040 10720 13400 Pressure drop calculation for this case gives the
1220 x 915 4020 6030 8040 12060 16080 20100 same results as in example for FKN-1, given on
1220 x 1220 5360 8040 10720 16080 21440 26800 page 9, because the case is an example of parallely
1220 x 1525 6700 10050 13400 20100 26800 33500 increased air volume flow rate.
1220 x 1830 8040 12060 16080 24120 32160 40200 This means, the installation should ensure pressure
of 325 Pa for this filter.
Pressure Drop Diagram
240

Ordering Example:
200
Initial pressure drop (Pa)

FKN – 2 1220 x 915 – L – G 4

160
Filter medium
ing

Filter cells changed/inserted:


as

120
rc

L - from left side


te

D - from right side


F5

G4
Fil

80
Dimensions of
inlet cross-section: B x H
G3
40 G1

0
1 1.5 2 3 4 5
Inlet air velocity v (m/s)

5/S2-10
INDEX

oprema Combined Duct-type Filter, Type FKK

Combined duct-type filter, Type FKK, is intended for air filtration in ventilation and air-conditioning systems, in which it is installed
in ducts. The FKK filter consists of two sections: flat-type section (R) and wedge-type section (K). Wedge-type section consists of
plane filter cells of size 610 x 610 mm arranged (inclined) in the casing in the form of a wedge. Individual sections R and K can be
ordered and supplied separately. Filter inserts of both sections are laterally slid (inserted) into the two-part casing. Sections are
laterally closed by covers. The casing is fitted with differential pressure gauge connections for pressure drop measurements and
filter saturation control. Differential pressure gauge is supplied only on special request. The two-part casing is made of
galvanised steel sheet and profiles. Filter media - in range from G1 to F5 class - can be applied (s. 5/S0 brochure). As a rule, plane
section R serves as a pre-filter, and wedge section K as a main filter.
Air volume flow rate at inlet cross-section of the FKK filter should be selected so that air velocity gets the value within the range
from 0.8 to 2 m/s.
Void space for filter insertion/change can be on either left or right side of the filter casing; the side required should be specified in
the order.

Void space for filter


Void space for filter change from right
change from left side "D"
side "L"

Table of air flow rates (m3/h)

Inlet air velocity v (m/s)


H(mm)
1 1.5 2 2.5 3
440 960 1440 1920 2400 2880
660 1450 2175 2900 3625 4350
880 1920 2880 3040 4800 5760
1100 2400 3600 4800 6000 7200
1320 2900 4350 5800 7250 8700
1540 3370 5055 6740 3850 10110
1760 3850 5775 7700 4400 11550
1980 4350 6525 13050 4950 13050
2200 4800 7200 14400 5600 14400

5/S2-11
INDEX

Combined Duct-type Filter, Type FKK oprema


Example 1:

Given:

Combined duct filter FKK; H = 1320 mm


From table on p.11: volume flow rate V = 8700 m3/h, at v = 3 m/s
Chosen: filter insert for R-section: G1 class
filter insert for K-section: G4 class

Solution:
Diag. p.12:
Initial pressure drop of R-section filter insert: 60 Pa
Initial pressure drop of K-section filter insert: 50 Pa
Pressure drop of filter casing: 160 Pa
Total: 270 Pa

Final pressure drop of filter insert


(selected from table in 5/S0, p.6): for G1 of R-section: 150 Pa
for G4 of K-section: 160 Pa
Pressure drop of filter casing (diag. p.12): 160 Pa
Total: 470 Pa

Example 2:

Given:

Combined duct filter FKK; H = 1320 mm


From table on p.11: volume flow rate V = 4350 m3/h, at v = 1.5 m/s
Chosen: filter insert for R-section: G3 class
filter insert for K-section: F5 class

Solution:
Diag. p.12:
Initial pressure drop of R-section filter insert: 30 Pa
Initial pressure drop of K-section filter insert: 105 Pa
Pressure drop of filter casing: 45 Pa
Total: 180 Pa

Final pressure drop of filter insert


(selected from table in 5/S0, p.6): for G3 of R-section: 160 Pa
for F5 of K-section: 200 Pa
Pressure drop of filter casing: 45 Pa
Total: 405 Pa

Initial Pressure Drop Diagram for Filter Inserts


200

Order Example:
160 FKK 1320 – L – G3 / F5
Initial pressure drop (Pa)

F5

F5

Filter medium of K-section (from diag.)


120
ing

Filter medium of R-section (from diag.)


as
rc
lte

4
G

80 Filter cells changed/inserted: L - from left side


Fi

G3 D - from right side


G1 Filter height: H
G1 G1
40
G1

0
0.8 1 1.5 2 3
Inlet air velocity v (m/s)
Example for ordering only one of sections:
Orange curves - for R-section filter inserts
- for R-section:R - 1320 - L - G3
Black curves - for K-section filter inserts - for K-section:K - 1320 - L - F5

5/S2-12

Vous aimerez peut-être aussi