Inverter Single

(50Hz/R410A)

5RMA2-02A(5RMA2-01B)
Inverter Single-50Hz(R410A)

Contents Page

1. Models line up.........................................................................................4

2. Nomenclature..........................................................................................7

3. Features & Benefits................................................................................8

4. Specifications .......................................................................................22

5. Dimensions ...........................................................................................33

6. Wiring diagrams ...................................................................................47

7. Refrigerant cycle diagram....................................................................65

8. Capacity tables .....................................................................................73

9. Capacity coefficient factor...................................................................88

10. Operation range..................................................................................91

11. Air flow and temperature distributions(reference data)..................92

12. Sound level..........................................................................................96

12. Remote controller .............................................................................101

14. Installation.........................................................................................104

2009 Product Data 1


Test condition of international standard

CLASSIFICATION KSC ISO ARI AHAM AS SSA


9306 5151 210/240 1861.1 385
DB°C(°F) 27.0 27.0 26.7(80) 26.7(80) 27.0 29.0
Indoor
Cooling WB°C(°F) 19.5 19.0 19.4(67) 19.4(67) 19.0 19.0
Capacity DB°C(°F) 35.0 35.0 35.0(95) 35.0(95) 35.0 46.0
Outdoor
WB°C(°F) 24.0 24.0 23.9(75) 23.9(75) 24.0 24.0
DB°C(°F) 20.0 20.0 21.1(70) 21.1(70) 20.0 21.0
Indoor
Heating WB°C(°F) 15.0 15.0 15.6(60) 15.6(60) 15.0 15.5
Capacity DB°C(°F) 7.0 7.0 8.3(47) 8.3(47) 7.0 7.0
Outdoor
WB°C(°F)) 6.0 6.0 6.1(43) 6.1(43) 6.0 6.0
DB°C(°F) 32.0 32.0 26.7(80) 32.2(90) 32.0 29.0
Maximum Indoor
WB°C(°F) 23.0 23.0 19.4(67) 22.8(73) 23.0 19.0
Cooling
DB°C(°F) 43.0 43.0 46.1(115) 43.3(110) 43.0 54.0
Operating Outdoor
WB°C(°F) 26.0 26.0 23.9(75) 25.6(78) 26.0 24.0
DB°C(°F) 27.0 27.0 26.7(80) 26.7(80) - -
Maximum Indoor
WB°C(°F) 19.0 19.0 19.4(67) 22.8(73) - -
Heating
DB°C(°F) 21.0 24.0 23.9(75) 23.9(75) - -
Operating Outdoor
WB°C(°F) 15.0 18.0 18.3(65) 18.3(65) - -
Enclosure DB°C(°F) 27.0 27.0 26.7(80) 26.7(80) 27.0 27.0
Indoor
Sweat / WB°C(°F) 24.0 24.0 23.9(75) 23.9(75) 24.0 24.0
Condensate DB°C(°F) 27.0 27.0 26.7(80) 26.7(80) 27.0 27.0
Outdoor
Disposal WB°C(°F) 24.0 24.0 23.9(75) 23.9(75) 24.0 24.0
DB°C(°F) 21.0 21.0 19.4(67) 21.1(70) 21.0 21.0
Freeze-up/ Indoor
WB°C(°F) 15.0 15.0 13.9(57) 15.6(60) 16.0 16.0
Low
DB°C(°F) 21.0 21.0 19.4(67) 21.1(70) 21.0 21.0
Temperature Outdoor
WB°C(°F) 15.0 15.0 13.9(57) 15.6(60) 16.0 16.0

KS : Korea Standard AS : Australia Standard


ISO : International Standard Organization SSA : Saudi Arabian Standard
ARI : Airconditioning and Refrigeration Institute
AHAM : Association of Home Appliance Manufacturers

2 2009 Product Data


General Description

Split type of Air conditioners are known by the category name of Wall Mounted Type of units.These units can be
easily installed in a small space and have exceptional Cooling capacity.Designed for Low-noise operation,it
ensures a pleasant air conditioned environment.
LG Offers various types of units to its customers to suit for the best application and requirement.The following
are the important categories offered by LG :
1) General Wall Mounted Type Units : Units with Simplicity in design.
2) Art Cool Units : A new concept of cooling introduced by LG in the field of Air Conditioning.
3) Inverter Units : These units are capable of minimising the Power consumption with the unique inverter
technology.

Some of the Important Features of these units are listed below :


1) Providing Health to the Customers : By having the Filters such as Plasma Filter which is capable of removing
the Micro Organisms up to 0.1 microns.
2) Long Term Money Saving : By providing Features such as Gold Fin, Auto Clean etc. to maintain the same
performance for the years.
3) Best Comfort : With Features such as Sleep Mode,Timer,Auto Restart etc.

The Units are available with many standard and optional features which gives our Customers the free choice to
select the unit of their own desire.For details refer to the Detailed specification followed after this description.

LG Electronics Inc.
Air Conditioning Company

2009 Product Data 3


1. Models Line up

1.1 Indoor Unit


kW (kBtu/h)
2.63(9) 3.51(12) 5.28(18) 7.03(24) 8.79(30) 10.55(36)
Indoor Type
Super Inverter

AS-W096BMS0 AS-W126BMS0
Maestro
(S09AQ NB0) (S12AQ NB0)

AS-H09GB1U0 AS-H12GB1U0
Libero
(CS09AQ NB0) (CS12AQ NB0)

ART COOL Mirror

*Mirror

AS-W096E*H2 AS-W126E*H2 AS-W1868*H1 AS-W2468*H1


*Silver [C09AW* NE2] [C12AW* NE2] [C18AW* N81] [C24AW* N81]

*Blue

ART COOL

AS-W096F1G2 AS-W126F1G2
[A09AW1 NF2] [A12AW1 NF2]

ART COOL

AS-W096F*G2 AS-W126F*G2
[A09AW* NF2] [A12AW* NF2]
Red Gold Silver

Wall Mounted Type


AS-W096ADR0 AS-W126ADR0
[S09AA NA0] [S12AA NA0]

Wall Mounted Type


AS-W096E1G0 AS-W126E1G0 AS-W1865DH2 AS-W2465DH2
[S09AW NE0] [S12AW NE0] [S18AW N52] [S24AW N52]

Wall Mounted Type

AS-W0964GG1 AS-W1264GG1 AS-W1865GG1 AS-W2465GG1 AS-W306DGM0 AS-W366DGM0


[S09AM N41G] [S12AM N41G] [S18AM N51G] (S24AM N51G) [S30AW ND0] [S36AW ND0]

* denotes the color or the picture used on the front grille of the unit (refer to the Nomenclature section)

4 2009 Product Data


1. Models Line up

1.2 Outdoor Unit


AS-W0964GG1[S09AM N41G] AS-W1264GG1[S12AM N41G]
AS-W096ADR0 [S09AA NA0] AS-W126ADR0 [S12AA NA0]
Heat pump AS-W096E*H2[C09AW* NE2] AS-W126E1G0[S12AW NE0]
AS-W096E1G0[S09AW NE0] AS-W126E*H2 [C12AW*NE2]
AS-W096F1G2[A09AW1 NF2] AS-W126F1G2 [A12AW1 NF2]
AS-W096F*G2 [A09AW* NF2] AS-W126F*G2 [A12AW* NF2]
No. of connectable indoor units Max.1
Total capacity index of connectable kW 2.64 3.52
indoor units kBtu/h 9 12
Power supply 1ø, 220-240V, 50Hz

Chassis

Heat pump AS-W096BMS0[(S09AQ NB0] AS-W126BMS0[S12AQ NB0]


AS-H09GB1U0[CS09AQ NB0] AS-H12GB1U0[CS12AQ NB0]
No. of connectable indoor units Max.1
Total capacity index of connectable kW 2.64 3.52
indoor units kBtu/h 9 12
Power supply 1ø, 220-240V, 50Hz

Chassis

AS-W1865DH2[S18AW N52]
Heat pump AS-W1868*H1 [C18AW* N81] AS-W366DGM0[S36AW ND0]
AS-W1865GG1[S18AM N51G]
No. of connectable indoor units Max.1
Total capacity index of connectable kW 5.28 10.55
indoor units kBtu/h 18 36
Power supply 1ø, 220-240V, 50Hz

Chassis

2009 Product Data 5


1. Models Line up

AS-W2465DH2[S24AW N52]
Heat pump AS-W2468*H1 [C24AW* N81] AS-W306DGM0[S30AW ND0]
AS-W2465GG1[S24AM N51G]
No. of connectable indoor units Max.1
Total capacity index of connectable kW 7.03 8.79
indoor units kBtu/h 24 30
Power supply 1ø, 220-240V, 50Hz

Chassis

6 2009 Product Data


2. Nomenclature

• Europe Model Number

A S W 0 9 6 4 G G 1
1 2 - 3 4 5 6 7 8 9 10

Code Type Code of Model Meaning

1 Production Center, A~Z L: Chang-won R22


Refrigerant A: Chang-won R410A

2 Product Type A~Z S: Split Type Air Conditioner


3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump
X: C/O + E/Heater
Z: H/P + E/Heater
V: AC Inverter C/O
N: AC Inverter H/P
Q: DC Inverter C/O
W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz,
A~Z 2: 220V/60Hz
3: 208-230V/60Hz
5: 200-220V/50Hz
6: 220-240V/50Hz
7: 110V, 50/60Hz

7 Chassis A~Z Name of Chassis

8 Look A~Z ART COOL models


B : Blue C : Cherry K : Mecca 1 : The Kiss(SF chassis)
W: White D : Wood R : Mirror 2 : The Sunset(SF chassis)
M: Metal Q : Quran 3 : London Bridge(SG chassis)

General Wall Mounted models


D – Look ( Panel Type)
G – Look ( Grille Type)
Glory Look :- (a) F – Look (Blue color)
(b) H – Look (Gold)
(c) J – Look (Silver)

9 Function A~Z A Basic


B Basic+4Way
C Plasma Filter
D Plasma Filter+4 Way
E Tele+LCD
F Tele+LCD+Nano plasma+4Way
G NBF F+(A/changeove)+A/clean+Low A
H NBF F+(A/changeove)+A/clean+4way+Low A
I Tele+LED+4way
J Internet
K Plasma F+4Way+Oxygen generator
L NBF F+(A/changeove)+A/clean
M NBF F+(A/changeove)+A/clean+4way
N NBF F+(A/changeove)+A/clean+PTC
P NBF F+(A/changeove)+Autoclean+4way+PTC
Q NBF F+(A/changeove)+A/clean+4way+Low A+PTC
R Negative ion+A/Clean
S (Nano)Plasma+Negative ion+A/Clean
T 4way+(Nano)Plasma F+Negative ion+A/Clean
U Nano Plasma F+4Way+(A/changeove)+A/clean+Oxygen generator
V 4way+(Nano)Plasma F+Negative ion+A/Clean+Oxygen generator
W Dry contact
Y Basic + Low A

10 Serial No. 0~9 LG Model Development Serial No.

2009 Product Data 7


3. Features & Benefits

LG Air Conditioners are environment-friendly and future-oriented.


LG air conditioners are environment-friendly and future-oriented.
To reduce freon gas, a prime ozone destroyer, we adopted an alternative refrigerant R-410A, and neo plasma
air-purifying system for powerful sterilization for health-conscious customers. Also, ARTCOOL series with
outstanding designs have received International Forum Design Award and Reddot Design Award.
These air-conditioners have improved air flow innovatively to realize world’s lowest noise, and provide a more
pleasant and convenient indoor environment.

Environmental concern 2008


As the concern for environment increases day by day, EC Directive made it a regulation to put an indication on all
air conditioning products. With the information regarding energy-saving, customers will easily understand products
considering the environment.
Customers will have to purchase the products considering the energy label to meet their needs. Energy label
shows the energy consumption of the unit classified with 7 different colors.

Energy Efficiency Class of


The Unit In Cooling Mode :

Energy Efficiency Class of


The Unit In Heating Mode :

8 2009 Product Data


3. Features & Benefits

DC Inverter?
You may have heard the excitement about Inverter technology, LG Inverters are the pinnacle of energy efficiency
due to the innovative operation. Rather than using a constant speed compressor, the LG Inverter system uses a
variable speed compressor, which means the Cooling or Heating capacity of the Air Conditioning can be varied to
suit Indoor conditions.
This makes the LG Inverter Units more economical & efficient to operate, produce less noise than standard
counterparts and contain most superior features on the market. All LG Inverter units have the major benefits
including premium features like

Economical
■ Energy Saving ■ Recouping the Initial Investment Cost
Unlike ordinary Conventional air conditioners, inverter Though the initial purchase price is a little higher, in
air conditioners can control the speed of compressors case you use an inverter air conditioner in the long
to adjust cooling and heating. term, you can reduce electricity cost to save on the
When indoor temperatures reach your desired levels, whole investment and management costs.
inverter air conditioners can operate their compressors
at low speeds and maintain desired temperatures, thus Money
saving you electricity cost by about 44% compared to
conventional.

Inverter
Energy
Conventional Saving

Save 44%
1Year

Year

Conventional
Inverter

Energy Saving!

Low Noise!

Powerful
Cooling & Heating!

2009 Product Data 9


3. Features & Benefits

Strong Capable
■ Powerful Cooling & Heating ■ Powerful Heating Capacity
You can change the power by changing the
(Chilly Area Available)
compressor frequency. Provides the greatest heating performance in cold
Operational power with a greater scope areas
- When you return home from outside, in case you start - When outdoor temperatures fall to as low as -10°,
the air conditioner to heat or cool the room, you can you can faster increase the speed of the
speed up the compressor, enhance the power and then compressor, and simultaneously raise the quantity of
operate it. Also, when indoor temperature reach your refrigerant using the electronic expansion valve, thus
desired levels, you can reduce the speed of the further increasing the heating performance
compressor and lower the power. Thus, the product's compared to ordinary conventional model.
operational power has a greater range from low to high You can heat the room even in cold areas using the
levels. air conditioner.

Powerful
Energy Saving Cooling & Heating High Efficiency
Low Noise Low Cost
Light Weight
Outdoor Temp.(˚C)
Max
138%(H)

138%(H) Energy
40°C (Outlet) Saving
100% 100% Min

12% T1
Conventional 12%
T1 : 35% up 15
Inverter 7
Inverter 5
(min) 0
(max) -5
-10 Conventional
-15
-20
Inverter

■ Quick Cooling & Heating


Compared to conventional air conditioners, inverter air
conditioners can operate their compressors faster, thus
giving them powerful performance.
Therefore, on returning home from outside during hot
summer days, you can speed up the compressor to
enhance the performance and cool the room. In case
outdoor temperatures are low in winter, inverters operate
more powerfully than conventional, thus heating the
room faster.

Temp.

Conventional

Target Temp.

Inverter

50%
Time of Convention Time

10 2009 Product Data


3. Features & Benefits

NEO-Plasma Air Purifying System

LG Electronics’ unique neo-plasma air purifying system, equipped with 12-level bio-enzyme filters,
has further enhanced its sterilization power. While air passes each level of filters, the system can more
powerfully eliminate household's fine dust and molds, ordinary odor, food smell, and cigar smoke,
as well as can destroy bacteria's cell walls to completely kill them. It has a strong sterilization power.

Have you ever experienced these symptoms?


Though the industrial development has enhanced people's quality of life and their satisfaction in living, it is
increasingly creating various kinds of pollution, hazardous substances and viruses.
In particular, substances (household tick dust, molds, etc.) that create allergies give rise to respiratory diseases
and atopic diseases. Harmful gases, the prime cause of 'new house syndromes,’ create chronic headache.

Whenever seasons Asthma, and The skin is itchy Frequent headache,


change, You have Continuous coughs. without knowing and chronic fatigue...
runny nose reasons,
You scratch it again

1 First antibiotic Allergy Mold Mite Big dust Blanket dust

Odor of construction Odor of food Chemical


2 Fishy smell Foot stink Smoke
ingredient garbage substance

3 Animal smell Odor of food garbage Chemical substance

4 Influenza Virus Allergy Mite

5 Micro dust Deodorize Mold Pollutant

2009 Product Data 11


3. Features & Benefits

Nano Bio Plasma The PLASMA Air Purifying System


developed uniquely by LG not only
Fusion Filter Filter removes microscopic contaminants
and dust, but also removes house
Nano bio fusion filters allow their nano-size bio enzymes to directly mites, pollen, and pet fur to prevent
penetrate through cell walls of bacteria and allergen to decompose allergic diseases like asthma.

its cell nuclei and kill them.While conventional methods merely inactivate
bacteria or destroy external cell walls, this innovative sterilization method
can completely decompose bacteria's cell nuclei and kill them.
Bacteria,
Virus 5
Bio Active
Site

Nano Nano Nano Nano


Particle Particle Particle Particle

Polluted Air
Regeneration
Active State Bacteria Selective Bacteriolysis
Capture (Active State)

Distinctions from Conventional Filters


Conventional

4
Simply inactivate Destroy bacteria but allow
bacteria part of them to survive

Nano Bio Fusion Filter

The bio enzyme destroys


Nano-size carbon filters catch
cell walls and nuclei of
bacteria and allergens, thus
3 fine odorous particles again,
completely kills bacteria
and doubly and completely
remove odors from the
household, thus offering a
pleasant environment.
What is Nano
Carbon Ball?
Nano(1/1Bil) ball

Nano Carbon structure,consisted of Nano


carbon, is adopted as
2 Filter deodorizing material first in 200~500nm

the world
Kitasato Research Center of Environmental Sciences
Clean Air - Inactivating Germs Test Result 99.9% Performance (No. 16_0113_1,2,3)
Japan Food Research Laboratories
- Inactivating Germs Test Result 99.9% Performance (No. 104093863-001,2,3,4,5)
- Killing Virus (No. 204031236-001,2,3)
Japan Spinners Inspecting Foundation (No. 624217, 019355-13)
- NCB Deodorizing 4 Type Test Result 78%~98% Security
FITI Korea Consumer Science Center (No. 513104-195-A-01)
- Killing bacteria, fungi Test Result 99.9% Security
Pre Filter Triple Filter ITS(International Technical Standard Center) (No. IL26937-A,B)
- Inactivating bacteria Test Result 99.9% Security

The antibacterial pre- The triple filters consist of a various organic-compound filter to eliminate displeasure and pain
filters primarily remove in the eyes and necks with various organic compounds.
large dusts, molds, and It also has a formaldehyde filter to cut off formaldehyde, a prime cause of new-house
quilt dusts. syndromes, and prevents symptoms such as dermatitis, vomiting and pneumonia.
And lastly, it has a filter to remove ordinary odors that are causes of migraine and chronic
fatigues.

12 2009 Product Data


3. Features & Benefits

Healthy Dehumidification
LG Wall Mounted Split models feature a Dehumidification
mode to remove uncomfortable humidity from the room
without over cooling.

Indoor Temperature Distribution Chart

Conventional Healthy
Since the surrounding temperature is Dehumidification
measured after the air from the unit is By increasing the Vane Angle, a
widely distributed, an accurate better assessment of the actual
assessment of the air is not possible. temperature is possible to prevent
over cooling.

Auto Clean
The main cause of air conditioner's odor is molds that
breed in the heatexchanger. If you turn off the air
conditioner as it is, molds and bacteria will breed in the
wet heat exchanger.
The automatic cleaning function will dry the wet heat
exchanger to prevent molds and bacteria from breeding.
It will eliminate air conditioner's odor and save you from
frequent cleaning efforts.

When you press "Auto Clean”, Auto clean starts after

cooling operation.

In 30 minutes, Auto clean" dries the inner


part of Air conditioner.

1STEP : Dries the evaporator with super-weak, low-


noise air blowing, and removes remaining moisture.

2STEP : Fundamentally removes the sources of molds


once again through the neo plasma system.

2009 Product Data 13


3. Features & Benefit

Low Level Noise & Vibration


In the case of the inverter air conditioner’s outdoor
equipment, when indoor temperatures reach your desired
levels, you can lower the speed of the compressor
operating inside the outdoor equipment, thus further
reducing noise compared to ordinary conventional air
conditioners.
Also, the indoor equipment, which adopts a BLDC motor,
can achieve even quieter and industry’s lowest-level
noise, compared to existing conventional air conditioner.
Since even the outdoor equipment is quiet, though the air
conditioner is hung on the wall, it has subdued noise, thus
not disturbing your neighbors. It is perfect for sleeping,
studying, and a quiet indoor ambience.

Indoor Outdoor
20dB 45dB

Low Noise
Compressor
[Indoor equipment] [Outdoor equipment]
1. Uses low-noise BLDC motor and 1. Low-noise inverter compressor
fan and low-noise fan
2. Shuts off noise with an all-side 2. Designed for optimizing
panel design compressor vibration

Anti Corrosion Gold Fin™


LG ’s Outdoor Heat Exchanger is coated with a golden anti-
corrosive epoxy treatment on the aluminum coil to
minimized corrosion. This maintains heat transfer properties
of the coil for an extended time where as non-Gold Fin coils
progressively lose efficiency due to surface corrosion.
Standard on every LG air conditioner, this assists in areas
suffering from pollution or near the ocean where the unit
may subjected to higher levels of salt.
Salt Spray Test for 15 Days

After 15 Days LG Gold Fin™


Anti Corrosion

Gold Coated Aluminum

Conventional
After 15 Days
Starting to
corrode
Uncoated Aluminum

• Gold Fin is long lasting, durable and


makes the Outdoor Unit look prestigious.

14 2009 Product Data


3. Features & Benefits

Optimized Cooling & Heating


Air Flow
LG Electronics' air conditioner, which adopts the twin air
vanes, blows winds horizontally far away in the cooling
mode to prevent direct blowing. And, in the heating
mode, the air conditioner pushes winds downwards to
provide warm air evenly, thus offering pleasant air.

Cooling mode Heating mode

New Chaos Swing


The most comfortable airflow for the human body can
be found in nature. After analysis,LG has applied the
scientific Chaos theory to its air conditioners to
effectively reproduce a natural breeze. The Chaos
technology recreates the flow of natural air by
controlling the angle speed and movement of the air
vane. It also minimizes the temperature difference
between high and low areas in the room,creating a
Cooling mode Heating mode more comfortably conditioned environment.
0.5hr 1hr 2hr 0.5hr 1hr 2hr

LG

Co., A

Co., B

Even & Fast Air flow It swings with random angle speed (0ms~12ms) to
reproduce a natural breeze
LG Electronics' air conditioner improves the difference
between high and low indoor temperatures . It allows
you to reach your desired temperatures even faster.

2009 Product Data 15


3. Features & Benefits

Indoor Temperature Distribution Chart 4 Way Auto Swing


LG Air Conditioning units can now automatically
distribute the air 4-ways.
This effectively eliminates hot and cold patches,
keeping the room at a more stable temperature.
Chaos Swing Auto Swing

Chaos Swing Effect

Jet Cool TM
ARTCOOL_MIRROR TYPE
The Jet cool function allows quick cooling. A little interior accent for the modern you.
The romantic pastel colors, subdued luster,modern texture and the
In this mode, strong, cool air is blown at high speed for super slim design of LG ARTCOOL Mirror are the answers to your
30 minutes, until the room temperature reaches 18˚C. unique mood and personality.

ARTCOOL_PANEL TYPE
LG's unique frame-style of ARTCOOL panel type.
10m Its super-slim and sensory design satisfies your sense.
It can cool the spot ten
meters away in 3 minutes.

16 2009 Product Data


3. Features & Benefits

Auto Changeover Low Ambient


With heat pump model,cooling and heating operation is Cools the room as is necessary, even in winter.
changed automatically on the base of setting temp. - In case you hold a party indoors in winter, you need
to operate equipment in the computer server room
for long hours, or you cannot open windows for the
security's sake, you can cool the room using the
Inverter air conditioner.

Under such circumstances, ordinary conventional air


conditioners may have heat exchangers in indoor
equipment frozen, thus not properly functioning to
cool the room. However, in the case of inverter air
conditioners, you can adjust the speed of
compressors and outdoor equipment's fans to
prevent heat exchangers in indoor equipment from
being frozen, thus cooling the room more easily.

• Initial Setting Temp:18˚C Memorize final setting temp.

Auto Restart Function


In case of a sudden power failure, It automatically sets
the A/C to settings before the power failure when
power returns.
Hot Start Function
During starting of the unit in the heating mode it prevents
cold air blowing from the unit. It starts the indoor fan only
after indoor unit pipe temperature reaches a preset value Sleep Mode Auto Control
(28˚C).
With one touch of the Sleep mode button,
When indoor unit pipe temperature reaches 28˚C, then it automatically programs the Air Conditioning Unit to
for initial 1 minute the indoor fan runs at a low speed turn off, controls the fan speed and adjusts the set
and after that at the setting speed. temperature for a more comfortable sleep.

2009 Product Data 17


3. Features & Benefits

Modern & Luxury Design Gallery In My Room


Its premium designs match well with any part of the Your room will shine chicly with a famous painting or a
household. beautiful photo (showcased in the product).
LG ARTCOOL will convert your room into a gallery.
Do you like Western paintings, Oriental paintings, or
photos?
The product features your desired style of famous
paintings.

Klumt, Gustav(1862-1918) Courbet, Gustav(1817-1877)


The Kiss-Der Kuss Lake Geneva at Sunset
EX)LS-H126F1L0 EX)LS-H126F2L0

Ez-Replaceable Color Panel Digital Air Flow Control


The ARTCOOL chameleon panel enables you to change You feel more comfortable and convenient by
the air conditioner color according to background colors, controlling air flow.
the first of its kind in the world. When you want to
change interior designs (wallpaper colors, furniture, etc.)
or you want to change the air conditioner designs after
you are bored with them. You can only change the
panel.

Normal Jet Cool Sleep Mode


Fast & Even Widely Speedy & Powerful Indirectly & Softly

3 Dimensional Air Flow


Designed like a work of art, and the new concept of 3
Ultra Thin dimensional air flow. It gives even cooling as well as
quick cooling from front and bothsides making the
Technology mixed with sense of
space evenly cool.
art result in the super slim design
which is of 129mm depth.

The slimmest
in the world!!!

129mm
18 2009 Product Data
3. Features & Benefits

Eco Eye(only MAESTRO models)


MAESTRO’s new feature, ‘Eco Eye’ saves power consumption by sensing human motion

• Customized airflow :
Sends out optimized direct or indirect airflow, which is set according to user’s choice, by sensing human
temperature and movement.

Direct Indirect Absence


• Smart-save :
- Operates on power-save mode when there is no presence of human being in the zone
- Saves energy by 35 percent when operated on smart-mode for 1 hour. *LG Test Result

Automatic control
by human movement

Allergy Free Filter


Filter consists of enzyme that breaks down allergen, apatite, and organic/inorganic binder that attaches the
enzyme to the filter. When the air passes the filter, allergen clings to the filter and like tiny pairs of scissors the
enzymes cut allergen's protein to deactivate the allergen.
Filter Step 1 Step 2 Step 3 Step 4

2009 Product Data 19


3. Features & Benefits

Stepping control
With vane that can be controlled by various steps, MAESTRO & LIBERO can send airflow in more precision and
to a wider zone thus allowing the user to choose the location of indoor unit more freely.

Left Only Right Only

Vane Stepping

Vertical 6 Step Horizontal 5 Step

Moisture Cooling (only Maestro models)


Discomfort caused by dried nose and throat is one of the key reasons for not buying an air conditioner.
To overcome this problem, a new operating algorithm was developed for MAESTRO to control not just
temperature but also humidity. While other air conditioners remove moisture during operation, MAESTRO reaches
the desired temperature while maintaining a comfortable relative humidity of 45 percent. The function is especially
desirable for people with respiratory problems and those concerned with dry skin.

*Relative humidity is optimization above


45% conditions.

Conventional Moisture Cooling

20 2009 Product Data


3. Features & Benefits

Quick & Easy Installation


Sufficient piping space
For convenient pipe laying, MAESTRO & LIBERO has wide piping space in
comparison to LG’s previous models and competitor products.

LG Co.A Co.B Co.C "B"


A(mm) 67.7 50.0 60.0 45.0
B(mm) 72.0 80.0 70.0 70.0
% 116% 95% 100% 75% "A"

Installation plate improvement


MAESTRO & LIBERO’s installation plate is wider and modified to save installation time. The instruction tip
engraved in the plate also enables easy installation without having to look through the manual.
Fitting Space

No Instructions on Install Plate Pushing Structure Drain Hose pace


Instructions on Install Plate

Detachable bottom cover


MAESTRO & LIBERO’s indoor unit has a detachable chassis bottom and a supporter, which makes installation
possible without having to disassemble or support the unit. With LG’s patented supporter, installation can be
completed by just one person.

Hanging Separate chassis Lift up using Piping Wiring Finishing


an indoor unit bottom the supporter

Piping Wiring

Elevated service valve


For convenient installation in places without balcony, location of service valve
has been adjusted upward for workers to reach more easily.
145mm

2009 Product Data 21


4. Specifications Inverter single

Super Inverter
Models Unit AS-W096BMS0(S09AQ NB0) AS-H09GB1U0(CS09AQ NB0)
Cooling Capacity kW 0.89~2.50~3.70 0.89~2.50~3.70
Btu/h. 3,070~8,530~12,620 3,070~8,530~12,620
Heating Capacity kW 0.89~3.2~5.00 0.89~3.2~5.00
Btu/h. 3,070~10,920~17,060 3,070~10,920~17,060
Power Input Cooling/Heating W 545/700 545/700
Running Current Cooling/Heating A 2.4 / 3.1 2.4 / 3.1
Starting Current Cooling/Heating A 2.4 / 3.1 2.4 / 3.1
EER W/W 4.6 4.6
Btu/h.W 15.7 15.7
COP W/W 4.6 4.6
Power Supply Ø / V / Hz 1 / 220~240 / 50 1 / 220~240 / 50
Power Factor % 97.4 97.4
Air Flow Rate Indoor,Max m3/min(CFM) 12.0(423) 12.0(423)
Outdoor,Max m3/min(CFM) 33(1,165) 33(1,165)
Moisture Removal l/h. 1.1 1.1
Sound Level Indoor,H/M/L dB(A)±3 38 / 33 / 23 / 19 38 / 33 / 23 / 19
Outdoor,Max dB(A)±3 45 45
Refrigerant & Charge (at 7.5 m) g(oz) R410A, 1,000(35.3) R410A, 1,000(35.3)
Additional Refrigerant charge g/m(oz/ft) 20(0.22) 20(0.22)
Compressor Type Rotary Rotary
Model 5RS102XAA21 5RS102XAA21
Motor Type Brushless DC Motor Brushless DC Motor
Oil Type PVE(FV50S) PVE(FV50S)
Oil Charge cc 320 320
O.L.P. name Internal Internal
Fan(Indoor) Type Cross Flow Fan Cross Flow Fan
Motor Output W 20 20
Fan(Outdoor) Type Propeller Propeller
Motor Type BLDC BLDC
Motor Output W 43 43
Circuit Breaker* A 15 15
Power Supply Cable No.*mm2 3*1.0 3*1.0
Power and Transmission Cable No.*mm2 No.*mm2 4*1.0 (Including Earth) 4*0.75 (Including Earth)
Piping Connections Liquid Side mm(in) 6.35(1/4) 6.35(1/4)
Gas Side mm(in) 9.52(3/8) 9.52(3/8)
Drain Hose(O.D/ I.D.) mm(in) 21.5 /16(0.85 / 0.63) 21.5 /16(0.85 / 0.63)
Dimensions Indoor (W*H*D) mm 895*285*195 885*285*210
inch 35.2*11.2*7.7 34.8*11.2*8.3
Outdoor (W*H*D) mm 770*545*288 770*545*288
inch 30.3*21.5*11.3 30.3*21.5*11.3
Net Weight Indoor kg(lbs) 12(26.5) 11(24.5)
Outdoor kg(lbs) 35(77.2) 35(77.2)
Operation Range Cooling(Outdoor) °C(°F) -10~48(14~118.4) -10~48(14~118.4)
Heating(Outdoor) °C(°F) -10(-15)~24(14.0~75.2) -10(-15)~24(14.0~75.2)
Max. Piping Length m(ft) 2(6.6) / 20(65.6) 2(6.6) / 20(65.6)
Max. Elevation Difference m(ft) 10(32.8) 10(32.8)
Tool Code(Chassis) Indoor + Outdoor SB + UL2 SB + UL2
Functions Temperature Control Thermistor Thermistor
Plasma Filter New New
Prefilter(washable/anti-fungus) O O
Auto Clean O O
CHAOS Wind(Auto Wind) O O
Steps, Fan/Cool/Heat 5/6/6 5/6/5
Airflow Direction Control(up & Down) Auto Auto
Airflow Direction Control(left & right) Auto Auto
Remote Controller Type Wireless LCD Wireless LCD
Setting Temperature Cooling 18°C~30°C 18°C~30°C
Range Heating 16°C~30°C 16°C~30°C
Auto Operation (Micom Control) - -
Auto Changeover (Micom Control) O O
Self Diagnosis O O
Timer 24h, On/Off 24h, On/Off
Sleep Operation O O
Soft Dry Operation O O
Restart Delay(minute) 3 3
Deice Control(Defrost) O O
Hot Start O O
Jet Cool O O
Low Ambient Operation O O
Special Function ECO Eye, Moisure Cooling -

Note : O : Applie, X : Not applied, – : No relation


• Filters are optional in some specific areas.
• For Circuit Breaker Rating, please conform to local standards whenever necessary.

22 2009 Product Data


4. Specifications Inverter single

Super Inverter
Models Unit AS-W126BMS0(S12AQ NB0) AS-H12GB1U0(CS12AQ NB0)
Cooling Capacity kW 0.89~3.50~4.04 0.89~3.50~4.04
Btu/h. 3,070~11,900~13,800 3,070~11,900~13,800
Heating Capacity kW 0.89~4.00~6.00 0.89~4.00~6.00
Btu/h. 3,070~13,600~20,470 3,070~13,600~20,470
Power Input Cooling/Heating W 875/ 955 875/ 955
Running Current Cooling/Heating A 4.0 / 4.3 4.0 / 4.3
Starting Current Cooling/Heating A 4.0 / 4.3 4.0 / 4.3
EER W/W 4.0 4.0
Btu/h.W 13.6 13.6
COP W/W 4.2 4.2
Power Supply Ø / V / Hz 1/220~240/50 1/220~240/50
Power Factor % 95.1 95.1
Air Flow Rate Indoor,Max m3/min(CFM) 12.0(423) 12.0(423)
Outdoor,Max m3/min(CFM) 33(1,165) 33(1,165)
Moisture Removal l/h. 1.3 1.3
Sound Level Indoor,H/M/L dB(A)±3 39 / 33 / 23 / 19 39 / 33 / 23 / 19
Outdoor,Max dB(A)±3 45 45
Refrigerant & Charge (at 7.5 m) g(oz) R410A, 1,000(35.3) R410A, 1,000(35.3)
Additional Refrigerant charge g/m(oz/ft) 20(0.22) 20(0.22)
Compressor Type Rotary Rotary
Model 5RS102XAA21 5RS102XAA21
Motor Type Brushless DC Motor Brushless DC Motor
Oil Type PVE(FV50S) PVE(FV50S)
Oil Charge cc 320 320
O.L.P. name Internal Internal
Fan(Indoor) Type Cross Flow Fan Cross Flow Fan
Motor Output W 20 20
Fan(Outdoor) Type Propeller Propeller
Motor Type BLDC BLDC
Motor Output W 43 43
Circuit Breaker* A 15 15
Power Supply Cable No.*mm2 3*1.0 3*1.0
Power and Transmission Cable No.*mm2 No.*mm2 4*1.0 (Including Earth) 4*0.75 (Including Earth)
Piping Connections Liquid Side mm(in) 6.35(1/4) 6.35(1/4)
Gas Side mm(in) 9.52(3/8) 9.52(3/8)
Drain Hose(O.D/ I.D.) mm(in) 21.5 /16(0.85 / 0.63) 21.5 /16(0.85 / 0.63)
Dimensions Indoor (W*H*D) mm 895*285*195 885*285*210
inch 35.2*11.2*7.7 34.8*11.2*8.3
Outdoor (W*H*D) mm 770*545*288 770*545*288
inch 30.3*21.5*11.3 30.3*21.5*11.3
Net Weight Indoor kg(lbs) 12(26.5) 11(24.5)
Outdoor kg(lbs) 35(77.2) 35(77.2)
Operation Range Cooling(Outdoor) °C(°F) -10~48(14~118.4) -10~48(14~118.4)
Heating(Outdoor) °C(°F) -10(-15)~24(14.0~75.2) -10(-15)~24(14.0~75.2)
Max. Piping Length m(ft) 2(6.6) / 20(65.6) 2(6.6) / 20(65.6)
Max. Elevation Difference m(ft) 10(32.8) 10(32.8)
Tool Code(Chassis) Indoor + Outdoor SB + UL2 SB + UL2
Functions Temperature Control Thermistor Thermistor
Plasma Filter New New
Prefilter(washable/anti-fungus) O O
Auto Clean O O
CHAOS Wind(Auto Wind) O O
Steps, Fan/Cool/Heat 5/6/6 5/6/5
Airflow Direction Control(up & Down) Auto Auto
Airflow Direction Control(left & right) Auto Auto
Remote Controller Type Wireless LCD Wireless LCD
Setting Temperature Cooling 18°C~30°C 18°C~30°C
Range Heating 16°C~30°C 16°C~30°C
Auto Operation (Micom Control) - -
Auto Changeover (Micom Control) O O
Self Diagnosis O O
Timer 24h, On/Off 24h, On/Off
Sleep Operation O O
Soft Dry Operation O O
Restart Delay(minute) 3 3
Deice Control(Defrost) O O
Hot Start O O
Jet Cool O O
Low Ambient Operation O O
Special Function ECO Eye, Moisure Cooling -

Note : O : Applie, X : Not applied, – : No relation


• Filters are optional in some specific areas.
• For Circuit Breaker Rating, please conform to local standards whenever necessary.

2009 Product Data 23


4. Specifications Inverter single

Inverter Single, ART COOL


Models Unit AS-W096E*H2[C09AW* NE2] AS-W096F1G2[A09AW1 NF2]
Cooling Capacity kW 0.89~2.64~3.69 1.30~2.70~3.50
Btu/h. 3,070~9,000~12,620 4,436~9,210~11,942
Heating Capacity kW 0.89~3.60~5.00 1.30~3.50~4.20
Btu/h. 3,070~12,300~17,060 4,436~11,940~14,330
Power Input Cooling/Heating W 650 / 870 830 / 960
Running Current Cooling/Heating A 3.0 / 4.0 3.8 / 4.4
Starting Current Cooling/Heating A 3.0 / 4.0 4.5 / 5.2
EER W/W 4.1 3.3
Btu/h.W 13.9 11.1
COP W/W 4.1 3.7
Power Supply Ø / V / Hz 1 / 220~240 / 50 1 / 220~240 / 50
Power Factor % 94.2 95.0
Air Flow Rate Indoor,Max m3/min(CFM) 10.5(371) 8.0(283)
Outdoor,Max m3/min(CFM) 27.0(954) 26.0(918)
Moisture Removal l/h. 1.2 1.2
Sound Level Indoor,H/M/L dB(A)±3 31 / 27 / 22 35 / 29 / 25 / 22
Outdoor,Max dB(A)±3 45 48
Refrigerant & Charge (at 7.5 m) g(oz) R410A, 1,000(35.3) R410A, 1,000(35.3)
Additional Refrigerant charge g/m(oz/ft) 20(0.22) 20(0.22)
Compressor Type Rotary Rotary
Model 5RS102XAA21 5RS102XAA21
Motor Type Brushless DC Motor Brushless DC Motor
Oil Type FV50S FV50S
Oil Charge cc 320 320
O.L.P. name CS-7L 115 CS-7L 115
Fan(Indoor) Type Cross Flow Fan Tubo Fan
Motor Output W 20 24
Fan(Outdoor) Type Propeller Propeller
Motor Type BLDC BLDC
Motor Output W 43 43
Circuit Breaker* A 15 15
Power Supply Cable No.*mm2 3*1.0 3*1.0
Power and Transmission Cable No.*mm2 No.*mm2 4*1.5 (Including Earth) 4*1.5 (Including Earth)
Piping Connections Liquid Side mm(in) 6.35(1/4) 6.35(1/4)
Gas Side mm(in) 9.52(3/8) 9.52(3/8)
Drain Hose(O.D/ I.D.) mm(in) 21.5 / 16.0(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63)
Dimensions Indoor (W*H*D) mm 915*282*165 770*545*245
inch 36.0*11.1*6.5 30.3*21.5*9.6
Outdoor (W*H*D) mm 770*545*245 770*540*245
inch 30.3*21.5*9.6 30.3*21.3*9.6
Net Weight Indoor kg(lbs) 10(22.1) 15(33.0)
Outdoor kg(lbs) 32(70.6) 34(74.9)
Operation Range Cooling(Outdoor) °C(°F) -5~43(23~109.4) -5~43(23~109.4)
Heating(Outdoor) °C(°F) -10~24(14.0~75.2) -10~24(14.0~75.2)
Max. Piping Length m(ft) 15(49) 15(49)
Max. Elevation Difference m(ft) 7(23) 7(23)
Tool Code(Chassis) Indoor + Outdoor SE + UL SF + UL
Functions Temperature Control Thermistor Thermistor
Plasma Filter Neo Nano
Prefilter(washable/anti-fungus) O O
Auto Clean O O
CHAOS Wind(Auto Wind) O O
Steps, Fan/Cool/Heat 3/4/4 3/4/4
Airflow Direction Control(up & Down) Auto Auto
Airflow Direction Control(left & right) Auto Auto
Remote Controller Type Wireless LCD Wireless LCD
Setting Temperature Cooling 18°C~30°C 18°C~30°C
Range Heating 16°C~30°C 16°C~30°C
Auto Operation (Micom Control) - -
Auto Changeover (Micom Control) O O
Self Diagnosis O O
Timer 24h, On/Off 24h, On/Off
Sleep Operation O O
Soft Dry Operation O O
Restart Delay(minute) 2 2
Deice Control(Defrost) O O
Hot Start O O
Jet Cool O O
Low Ambient Operation O(Logic) O(Logic)
Special Function - -

Note : O : Applie, X : Not applied, – : No relation


• Filters are optional in some specific areas.
• For Circuit Breaker Rating, please conform to local standards whenever necessary.

24 2009 Product Data


4. Specifications Inverter single

Models Unit AS-W096F*G2 [A09AW* NF2] AS-W126E*H2 [C12AW*NE2]


Cooling Capacity kW 1.30~2.70~3.50 0.89~3.51~4.04
Btu/h. 4,436~9,210~11,942 3,070~12,000~13,800
Heating Capacity kW 1.30~3.50~4.20 0.89~4.57~5.48
Btu/h. 4,436~11,940~14,330 3,070~15,600~18,720
Power Input Cooling/Heating W 830 / 960 1,090 / 1,260
Running Current Cooling/Heating A 3.8 / 4.4 4.8 / 5.7
Starting Current Cooling/Heating A 4.5 / 5.2 4.8 / 5.7
EER W/W 3.3 3.2
Btu/h.W 11.1 11.0
COP W/W 3.7 3.6
Power Supply Ø / V / Hz 1 / 220~240 / 50 1/220~240/50
Power Factor % 95.0 98.7
Air Flow Rate Indoor,Max m3/min(CFM) 8.0(283) 10.5(371)
Outdoor,Max m /min(CFM)
3
26.0(918) 27.0(954)
Moisture Removal l/h. 1.2 1.3
Sound Level Indoor,H/M/L dB(A)±3 35 / 29 / 25 / 22 37 / 27 / 22 / 20
Outdoor,Max dB(A)±3 48 45
Refrigerant & Charge (at 7.5 m) g(oz) R410A, 1,000(35.3) R410A, 1,000(35.3)
Additional Refrigerant charge g/m(oz/ft) 20(0.22) 20(0.22)
Compressor Type Rotary Rotary
Model 5RS102XAA21 5RS102XAA21
Motor Type Brushless DC Motor Brushless DC Motor
Oil Type FV50S FV50S
Oil Charge cc 320 320
O.L.P. name CS-7L 115 CS-7L 115
Fan(Indoor) Type Tubo Fan Cross Flow Fan
Motor Output W 24 20
Fan(Outdoor) Type Propeller Propeller
Motor Type BLDC BLDC
Motor Output W 43 43
Circuit Breaker* A 15 15
Power Supply Cable No.*mm2 3*1.0 3*1.0
Power and Transmission Cable No.*mm2 No.*mm2 4*1.5 (Including Earth) 4*1.5 (Including Earth)
Piping Connections Liquid Side mm(in) 6.35(1/4) 6.35(1/4)
Gas Side mm(in) 9.52(3/8) 9.52(3/8)
Drain Hose(O.D/ I.D.) mm(in) 21.5 / 16.0(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63)
Dimensions Indoor (W*H*D) mm 770*545*245 915*282*165
inch 30.3*21.5*9.6 36.0*11.1*6.5
Outdoor (W*H*D) mm 770*540*245 770*545*245
inch 30.3*21.3*9.6 30.3*21.5*9.6
Net Weight Indoor kg(lbs) 15(33.0) 10(22.1)
Outdoor kg(lbs) 34(74.9) 32(70.6)
Operation Range Cooling(Outdoor) °C(°F) -5~43(23~109.4) -5~43(23~109.4)
Heating(Outdoor) °C(°F) -10~24(14.0~75.2) -10~24(14.0~75.2)
Max. Piping Length m(ft) 15(49) 15(49)
Max. Elevation Difference m(ft) 7(23) 7(23)
Tool Code(Chassis) Indoor + Outdoor SF + UL SE + UL
Functions Temperature Control Thermistor Thermistor
Plasma Filter Nano Nano
Prefilter(washable/anti-fungus) O O
Auto Clean O O
CHAOS Wind(Auto Wind) O O
Steps, Fan/Cool/Heat 3/4/4 3/4/4
Airflow Direction Control(up & Down) Auto Auto
Airflow Direction Control(left & right) Auto Auto
Remote Controller Type Wireless LCD Wireless LCD
Setting Temperature Cooling 18°C~30°C 18°C~30°C
Range Heating 16°C~30°C 16°C~30°C
Auto Operation (Micom Control) - -
Auto Changeover (Micom Control) O O
Self Diagnosis O O
Timer 24h, On/Off 24h, On/Off
Sleep Operation O O
Soft Dry Operation O O
Restart Delay(minute) 2 2
Deice Control(Defrost) O O
Hot Start O O
Jet Cool O O
Low Ambient Operation O(Logic) O(Logic)
Special Function - -

Note : O : Applie, X : Not applied, – : No relation


• Filters are optional in some specific areas.
• For Circuit Breaker Rating, please conform to local standards whenever necessary.

2009 Product Data 25


4. Specifications Inverter single

Models Unit AS-W126F1G2 [A12AW1 NF2] AS-W126F*G2 [A12AW* NF2]


Cooling Capacity kW 1.30~3.50~4.00 1.30~3.50~4.00
Btu/h. 4,436~11,940~13,648 4,436~11,940~13,648
Heating Capacity kW 1.30~4.20~5.00 1.30~4.20~5.00
Btu/h. 4,436~14,330~17,060 4,436~14,330~17,060
Power Input Cooling/Heating W 1,090 / 1,160 1,090 / 1,160
Running Current Cooling/Heating A 4.9 / 5.2 4.9 / 5.2
Starting Current Cooling/Heating A 5.7 / 6.9 5.7 / 6.9
EER W/W 3.2 3.2
Btu/h.W 11.0 11.00
COP W/W 3.60 3.60
Power Supply Ø / V / Hz 1 / 220~240 / 50 1 / 220~240 / 50
Power Factor % 96.7 96.7
Air Flow Rate Indoor,Max m3/min(CFM) 9.5(336) 9.5(336)
Outdoor,Max m3/min(CFM) 34(1,200) 34(1,200)
Moisture Removal l/h. 1.5 1.5
Sound Level Indoor,H/M/L dB(A)±3 39 / 32 / 25 / 23 39 / 32 / 25 / 23
Outdoor,Max dB(A)±3 48 48
Refrigerant & Charge (at 7.5 m) g(oz) R410A, 1,000(35.3) R410A, 1,000(35.3)
Additional Refrigerant charge g/m(oz/ft) 20(0.22) 20(0.22)
Compressor Type Rotary Rotary
Model 5RS102XAA21 5RS102XAA21
Motor Type Brushless DC Motor Brushless DC Motor
Oil Type FV50S FV50S
Oil Charge cc 320 320
O.L.P. name CS-7L 115 CS-7L 115
Fan(Indoor) Type Tubo Fan Tubo Fan
Motor Output W 24 24
Fan(Outdoor) Type Propeller Propeller
Motor Type BLDC BLDC
Motor Output W 43 43
Circuit Breaker* A 15 15
Power Supply Cable No.*mm2 3*1.0 3*1.0
Power and Transmission Cable No.*mm2 No.*mm2 4*1.5 (Including Earth) 4*1.5 (Including Earth)
Piping Connections Liquid Side mm(in) 6.35(1/4) 6.35(1/4)
Gas Side mm(in) 9.52(3/8) 9.52(3/8)
Drain Hose(O.D/ I.D.) mm(in) 21.5 / 16.0(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63)
Dimensions Indoor (W*H*D) mm 600*600*145 600*600*145
inch 23.6*23.6*5.7 23.6*23.6*5.7
Outdoor (W*H*D) mm 770*545*245 770*545*245
inch 30.3*21.5*9.6 30.3*21.5*9.6
Net Weight Indoor kg(lbs) 15(33.0) 15(33.1)
Outdoor kg(lbs) 32(70.6) 32(70.5)
Operation Range Cooling(Outdoor) °C(°F) -5~43(23~109.4) -5~43(23~109.4)
Heating(Outdoor) °C(°F) -10~24(14.0~75.2) -10~24(14.0~75.2)
Max. Piping Length m(ft) 15(49) 15(49)
Max. Elevation Difference m(ft) 7(23) 7(23)
Tool Code(Chassis) Indoor + Outdoor SF + UL SF + UL
Functions Temperature Control Thermistor Thermistor
Plasma Filter Nano Nano
Prefilter(washable/anti-fungus) O O
Auto Clean O O
CHAOS Wind(Auto Wind) O O
Steps, Fan/Cool/Heat 3/4/4 3/4/4
Airflow Direction Control(up & Down) Auto Auto
Airflow Direction Control(left & right) Auto Auto
Remote Controller Type Wireless LCD Wireless LCD
Setting Temperature Cooling 18°C~30°C 18°C~30°C
Range Heating 16°C~30°C 16°C~30°C
Auto Operation (Micom Control) - -
Auto Changeover (Micom Control) O O
Self Diagnosis O O
Timer 24h, On/Off 24h, On/Off
Sleep Operation O O
Soft Dry Operation O O
Restart Delay(minute) 2 2
Deice Control(Defrost) O O
Hot Start O O
Jet Cool O O
Low Ambient Operation O(Logic) O(Logic)
Special Function - -

Note : O : Applie, X : Not applied, – : No relation


• Filters are optional in some specific areas.
• For Circuit Breaker Rating, please conform to local standards whenever necessary.

26 2009 Product Data


4. Specifications Inverter single

Models Unit AS-W1868*H1 [C18AW* N81] AS-W2468*H1 [C24AW* N81]


Cooling Capacity kW 1.76~5.28~5.80 3.87~7.03~7.74
Btu/h. 6,000~18,000~19,800 13,200~24,000~26,400
Heating Capacity kW 1.40~6.07~6.65 3.37~8.44~8.88
Btu/h. 4,800~20,700~22,700 11,500~28,800~30,300
Power Input Cooling/Heating W 1,640 / 1,770 2,450 / 2,900
Running Current Cooling/Heating A 7.3 / 8.3 11.0 / 13.0
Starting Current Cooling/Heating A 7.3 / 8.3 11.0 / 13.0
EER W/W 3.2 2.9
Btu/h.W 11.0 9.8
COP W/W 3.43 2.90
Power Supply Ø / V / Hz 1 / 220~240 / 50 1 / 220~240 / 50
Power Factor % 98.3 96.8
Air Flow Rate Indoor,Max m3/min(CFM) 16.0(565) 20.3(717)
Outdoor,Max m3/min(CFM) 42(1,483) 58(2,048)
Moisture Removal l/h. 2.1 2.7
Sound Level Indoor,H/M/L dB(A)±3 42 / 39 / 36 43 / 40 / 36 / 34
Outdoor,Max dB(A)±3 54 55
Refrigerant & Charge (at 7.5 m) g(oz) R410A, 1,200(42.3) R410/1,800(63.0)
Additional Refrigerant charge g/m(oz/ft) 20(0.22) 30(0.32)
Compressor Type E-SCROLL Rotary(Non Tropical)
Model 5CS130XCC03 5KD240XCA21
Motor Type BLDC BLDC
Oil Type RB68A FV50S
Oil Charge cc 480 900
O.L.P. name CS-7L N120 CS-7L N115
Fan(Indoor) Type Cross Flow Fan Cross Flow Fan
Motor Output W 20 24
Fan(Outdoor) Type Propeller Propeller
Motor Type AC Induction AC Induction
Motor Output W 65.0 76.5
Circuit Breaker* A 20 30
Power Supply Cable No.*mm2 3*1.5 3*2.5
Power and Transmission Cable No.*mm2 No.*mm2 4*1.5(Including Earth) 4*2.5 (Including Earth)
Piping Connections Liquid Side mm(in) 6.35(1/4) 9.52(3/8)
Gas Side mm(in) 12.7(1/2) 15.88(5/8)
Drain Hose(O.D/ I.D.) mm(in) 21.5 / 16.0(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63)
Dimensions Indoor (W*H*D) mm 1,107*299*200 1,107*299*200
inch 43.6*11.8*7.9 43.6*11.8*7.9
Outdoor (W*H*D) mm 870*655*320 870*808*320
inch 34.3*25.8*12.6 34.3*31.8*12.6
Net Weight Indoor kg(lbs) 14.1(31.1) 14.1(31.1)
Outdoor kg(lbs) 46(101.4) 60(132.0)
Operation Range Cooling(Outdoor) °C(°F) -5~43(23~109.4) -5~43(23~109.4)
Heating(Outdoor) °C(°F) -10~24(14.0~75.2) -10~24(14.0~75.2)
Max. Piping Length m(ft) 15(49) 30(98)
Max. Elevation Difference m(ft) 7(23) 15(49)
Tool Code(Chassis) Indoor + Outdoor S8 + UE S8 + UE1
Functions Temperature Control Thermistor Thermistor
Plasma Filter O O
Prefilter(washable/anti-fungus) O O
Auto Clean O O
CHAOS Wind(Auto Wind) O O
Steps, Fan/Cool/Heat 3/4/4 3/4/4
Airflow Direction Control(up & Down) Auto Auto
Airflow Direction Control(left & right) Auto Auto
Remote Controller Type Wireless LCD Wireless LCD
Setting Temperature Cooling 18°C~30°C 18°C~30°C
Range Heating 16°C~30°C 16°C~30°C
Auto Operation (Micom Control) - -
Auto Changeover (Micom Control) O O
Self Diagnosis O O
Timer 24h, On/Off 24h, On/Off
Sleep Operation O O
Soft Dry Operation O O
Restart Delay(minute) 2 2
Deice Control(Defrost) O O
Hot Start O O
Jet Cool O O
Low Ambient Operation O O
Special Function - -

Note : O : Applie, X : Not applied, – : No relation


• Filters are optional in some specific areas.
• For Circuit Breaker Rating, please conform to local standards whenever necessary.

2009 Product Data 27


4. Specifications Inverter single

Inverter Single, General Wall Mounted


Models Unit AS-W096ADR0 [S09AA NA0] AS-W096E1G0[S09AW NE0] AS-W0964GG1[S09AM N41G]
Cooling Capacity kW 0.89~2.64~3.69 0.89~2.64~3.69 0.90~2.64~3.46
Btu/h. 3,070~9,000~12,620 3,070~9,000~12,620 3,070~9,000~11,800
Heating Capacity kW 0.89~3.60~5.00 0.89~3.60~5.00 0.90~3.17~3.87
Btu/h. 3,070~12,300~17,060 3,070~12,300~17,060 3,070~10,800~13,200
Power Input Cooling/Heating W 650 / 870 650 / 870 820 / 930
Running Current Cooling/Heating A 3.0 / 4.0 3.0 / 4.0 3.8 / 4.3
Starting Current Cooling/Heating A 3.0 / 4.0 3.0 / 4.0 3.8 / 4.3
EER W/W 4.04 4.1 3.2
Btu/h.W 13.8 13.9 11.0
COP W/W 4.1 4.1 3.4
Power Supply Ø / V / Hz 1/220~240/50 1,220~240,50 1 / 220~240 / 50
Power Factor % 98.7 94.2 93.8
Air Flow Rate Indoor,Max m3/min(CFM) 8.5(300) 8.5(300) 9.5(335)
Outdoor,Max m3/min(CFM) 29(1,024) 29(1,024) 26(918)
Moisture Removal l/h. 1.2 0.6 1.3
Sound Level Indoor,H/M/L dB(A)±3 31 / 27 / 22 31 / 27 / 22 / 20 32 / 28 / 25
Outdoor,Max dB(A)±3 45 45 45
Refrigerant & Charge (at 7.5 m) g(oz) R410A, 1,000(35.3) R410A, 1,000(35.3) R410A, 630(22.2)
Additional Refrigerant charge g/m(oz/ft) 20(0.22) 20(0.22) 20(0.22)
Compressor Type Rotary Rotary Rotary
Model 5RS102XAA21 5RS102XAA21 5RS102XAA21
Motor Type Brushless DC Motor Brushless DC Motor Brushless DC motor
Oil Type FV50S FV50S FV50S
Oil Charge cc 320 320 320
O.L.P. name CS-7L 115 CS-7L 115 CS-7L 115
Fan(Indoor) Type Cross Flow Fan Cross Flow Fan Cross Flow Fan
Motor Output W 20 20 20
Fan(Outdoor) Type Propeller Propeller Propeller
Motor Type BLDC BLDC AC Induction
Motor Output W 43 43 29
Circuit Breaker* A 15 15 15
Power Supply Cable No.*mm2 3*1.0 3*1.0 3*1.0
Power and Transmission Cable No.*mm2 No.*mm2 4*1.5 (Including Earth) 4*1.5(Including Earth) 4*1.0 (Including Earth)
Piping Connections Liquid Side mm(in) 6.35(1/4) 6.35(1/4) 6.35(1/4)
Gas Side mm(in) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Drain Hose(O.D/ I.D.) mm(in) 21.5 / 16.0(0.85 / 0.63) 21.5 /16.0(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63)
Dimensions Indoor (W*H*D) mm 925*295*189 915*282*165 840*270*153
inch 36.4*11.6*7.4 36.0*11.1*6.5 33.1*10.6*6.0
Outdoor (W*H*D) mm 770*545*245 770*545*245 770*545*245
inch 30.3*21.5*9.6 30.3*21.5*9.6 30.3*21.3*9.7
Net Weight Indoor kg(lbs) 11.6(25.6) 8.0(17.6) 7.5(16.5)
Outdoor kg(lbs) 34(74.6) 32(70.6) 32(70.6)
Operation Range Cooling(Outdoor) °C(°F) -5~43(23~109.4) -5~43(23~109.4) -5~43(23~109.4)
Heating(Outdoor) °C(°F) -10~24(14.0~75.2) -10~24(14.0~75.2) -10~24(14.0~75.2)
Max. Piping Length m(ft) 15(49) 15(49) 15(49)
Max. Elevation Difference m(ft) 7(23) 7(23) 7(23)
Tool Code(Chassis) Indoor + Outdoor SA+UL SE + UL S4 + UL
Functions Temperature Control Thermistor Thermistor Thermistor
Plasma Filter - Neo Neo
Prefilter(washable/anti-fungus) O O O
Auto Clean O O O
CHAOS Wind(Auto Wind) O O O
Steps, Fan/Cool/Heat 3/4/4 3/4/4 3/4/4
Airflow Direction Control(up & Down) Auto Auto Auto
Airflow Direction Control(left & right) Auto Auto Manual
Remote Controller Type Wireless LCD Wireless LCD Wireless LCD
Setting Temperature Cooling 18°C~30°C 18°C~30°C 18°C~30°C
Range Heating 16°C~30°C 16°C~30°C 16°C~30°C
Auto Operation (Micom Control) - - -
Auto Changeover (Micom Control) O O O
Self Diagnosis O O O
Timer 24hr, On/Off 24h, On/Off 24h, On/Off
Sleep Operation O O O
Soft Dry Operation O O O
Restart Delay(minute) 2 2 2
Deice Control(Defrost) O O O
Hot Start O O O
Jet Cool O O O
Low Ambient Operation O O(Logic) O
Special Function Smart Clean - -

Note : O : Applie, X : Not applied, – : No relation


• Filters are optional in some specific areas.
• For Circuit Breaker Rating, please conform to local standards whenever necessary.

28 2009 Product Data


4. Specifications Inverter single

Models Unit AS-W126ADR0 [S12AA NA0] AS-W126E1G0[S12AW NE0] AS-W1264GG1[S12AM N41G]


Cooling Capacity kW 0.89~3.51~4.04 0.89~3.52~4.04 0.90~3.52 ~4.04
Btu/h. 3,070~12,000~13,800 3,070~12,000~13,800 3,070~12,000~13,800
Heating Capacity kW 0.89~4,57~5,49 0.89~4.57~5.48 0.90~4.00~4.86
Btu/h. 3,070~15,600~18,720 3,070~15,600~18,720 3,070~13,650~16,600
Power Input Cooling/Heating W 1,090 / 1,260 1,090 / 1,260 1,090 / 1,170
Running Current Cooling/Heating A 4.8 / 5.7 4.8 / 5.7 5.0 / 5.3
Starting Current Cooling/Heating A 4.8 / 5.7 4.8 / 5.7 5.0 / 5.3
EER W/W 3.22 3.20 3.20
Btu/h.W 11.0 11.0 11.0
COP W/W 3.63 3.63 3.40
Power Supply Ø / V / Hz 1 / 220~240 / 50 1 / 220~240 / 50 1 / 220~240 / 50
Power Factor % 98.7 98.7 94.8
Air Flow Rate Indoor,Max m3/min(CFM) 9.5(335) 9.5(335) 10.8(381)
Outdoor,Max m3/min(CFM) 29(1,024) 29(1,024) 26(918)
Moisture Removal l/h. 1.3 1.3 1.5
Sound Level Indoor,H/M/L dB(A)±3 36 / 27 / 22 37 / 27 / 22 / 20 38 / 30 / 25
Outdoor,Max dB(A)±3 45 45 45
Refrigerant & Charge (at 7.5 m) g(oz) R410A, 1,000(35.3) R410A, 1,000(35.3) R410A, 940(33.2)
Additional Refrigerant charge g/m(oz/ft) 20(0.22) 20(0.22) 20(0.22)
Compressor Type Rotary Rotary Rotary
Model 5RS102XAA21 5RS102XAA21 5RS102XAA21
Motor Type Brushless DC Motor Brushless DC Motor Brushless DC motor
Oil Type FV50S FV50S FV50S
Oil Charge cc 320 320 320
O.L.P. name CS-7L 115 CS-7L 115 CS-7L 115
Fan(Indoor) Type BLDC Cross Flow Fan Cross Flow Fan
Motor Output W 20 20 20
Fan(Outdoor) Type BLDC Propeller Propeller
Motor Type BLDC BLDC AC Induction
Motor Output W 43 43 29
Circuit Breaker* A 15 15 15
Power Supply Cable No.*mm2 3*1.0 3*1.0 3*1.0
Power and Transmission Cable No.*mm2 No.*mm2 4*1.5(Including Earth) 4*1.5(Including Earth) 4*1.0 (Including Earth)
Piping Connections Liquid Side mm(in) 6.35(1/4) 6.35(1/4) 6.35(1/4)
Gas Side mm(in) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Drain Hose(O.D/ I.D.) mm(in) 21.5 /16(0.85 / 0.63) 21.5 /16(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63)
Dimensions Indoor (W*H*D) mm 925*295*189 915*282*165 840*270*153
inch 36.4*11.6*7.4 36.0*11.1*6.5 33.1*10.6*6.0
Outdoor (W*H*D) mm 770*545*245 770*545*245 770*545*245
inch 30.3*21.5*9.6 30.3*21.5*9.6 30.3*21.3*9.7
Net Weight Indoor kg(lbs) 11.6(25.6) 8.0(17.64) 7.5(16.5)
Outdoor kg(lbs) 34(74.9) 32(70.6) 32(70.6)
Operation Range Cooling(Outdoor) °C(°F) -5~43(23~109.4) -5~43(23~109.4) -5~43(23~109.4)
Heating(Outdoor) °C(°F) -10~24(14.0~75.2) -10~24(14.0~75.2) -10~24(14.0~75.2)
Max. Piping Length m(ft) 15(49) 15(49) 15(49)
Max. Elevation Difference m(ft) 7(23) 7(23) 7(23)
Tool Code(Chassis) Indoor + Outdoor SA+UL SE + UL S4 + UL
Functions Temperature Control Thermistor Thermistor Thermistor
Plasma Filter - Nano Neo
Prefilter(washable/anti-fungus) O O O
Auto Clean O O O
CHAOS Wind(Auto Wind) O O O
Steps, Fan/Cool/Heat 3/4/4 3/4/4 3/4/4
Airflow Direction Control(up & Down) Auto Auto Auto
Airflow Direction Control(left & right) Auto Auto Manual
Remote Controller Type Wireless LCD Wireless LCD Wireless LCD
Setting Temperature Cooling 18°C~30°C 18°C~30°C 18°C~30°C
Range Heating 16°C~30°C 16°C~30°C 16°C~30°C
Auto Operation (Micom Control) - - -
Auto Changeover (Micom Control) O O O
Self Diagnosis O O O
Timer 24hr, On/Off 24h, On/Off 24h, On/Off
Sleep Operation O O O
Soft Dry Operation O O O
Restart Delay(minute) 2 2 2
Deice Control(Defrost) O O O
Hot Start O O O
Jet Cool O O O
Low Ambient Operation O O(Logic) O
Special Function Smart Clean - -

Note : O : Applie, X : Not applied, – : No relation


• Filters are optional in some specific areas.
• For Circuit Breaker Rating, please conform to local standards whenever necessary.

2009 Product Data 29


4. Specifications Inverter single

Models Unit AS-W1865DH2[S18AW N52] AS-W1865GG1[S18AM N51G]


Cooling Capacity kW 1.76~5.28~5.80 1.78~5.28~5.80
Btu/h. 6,000~18,000~19,800 6,000~18,000~19,800
Heating Capacity kW 1.41~6.07~6.65 1.40 ~5.80~6.65
Btu/h. 4,800~20,700~22,700 4,800~19,790~22,700
Power Input Cooling/Heating W 1,640 / 1,770 1,730 / 1,800
Running Current Cooling/Heating A 7.3 / 8.3 8.0 / 8.3
Starting Current Cooling/Heating A 7.3 / 8.3 8.0 / 8.3
EER W/W 3.2 3.1
Btu/h.W 11.0 10.4
COP W/W 3.4 3.2
Power Supply Ø / V / Hz 1 / 220~240 / 50 1 / 220~240 / 50
Power Factor % 98.8 94.0
Air Flow Rate Indoor,Max m3/min(CFM) 16.0(565) 13.0(459)
Outdoor,Max m3/min(CFM) 42(1,483) 42(1,483)
Moisture Removal l/h. 2.1 2.1
Sound Level Indoor,H/M/L dB(A)±3 42 / 39 / 36 43 / 40 / 37
Outdoor,Max dB(A)±3 55 56
Refrigerant & Charge (at 7.5 m) g(oz) R410A, 1,200(40.8) R410A, 1,200(40.8)
Additional Refrigerant charge g/m(oz/ft) 20(0.22) 20(0.22)
Compressor Type E-SCROLL E-SCROLL
Model 5CS130XCC03 5CS130XCA
Motor Type Brushless DC Motor Brushless DC motor
Oil Type RB68A RB68A
Oil Charge cc 480 480
O.L.P. name CS-7L N120 CS-7L N120
Fan(Indoor) Type Cross Flow Fan Cross Flow Fan
Motor Output W 20 24
Fan(Outdoor) Type Propeller Propeller
Motor Type AC Induction AC Induction
Motor Output W 65.0 85.3
Circuit Breaker* A 15 15
Power Supply Cable No.*mm2 3*1.5 3*1.5
Power and Transmission Cable No.*mm2 No.*mm2 4*1.5 (Including Earth) 4*1.5(Including Earth)
Piping Connections Liquid Side mm(in) 6.35(1/4) 6.35(1/4)
Gas Side mm(in) 12.7(1/2) 12.7(1/2)
Drain Hose(O.D/ I.D.) mm(in) 21.5 / 16.0(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63)
Dimensions Indoor (W*H*D) mm 1,090*300*180 1,090*300*180
inch 42.9*11.8*7.1 42.9*11.8*7.1
Outdoor (W*H*D) mm 870*655*320 870*655*320
inch 34.3*25.8*12.6 34.3*25.8*12.6
Net Weight Indoor kg(lbs) 13(28.7) 13(28.7)
Outdoor kg(lbs) 46(101.4) 46(101.4)
Operation Range Cooling(Outdoor) °C(°F) -5~43(23~109.4) -5~43(23~109.4)
Heating(Outdoor) °C(°F) -10~24(14.0~75.2) -10~24(14.0~75.2)
Max. Piping Length m(ft) 15(49) 15(49)
Max. Elevation Difference m(ft) 7(23) 7(23)
Tool Code(Chassis) Indoor + Outdoor S5 + UE S5 + UE
Functions Temperature Control Thermistor Thermistor
Plasma Filter Nano Neo
Prefilter(washable/anti-fungus) O O
Auto Clean O O
CHAOS Wind(Auto Wind) O O
Steps, Fan/Cool/Heat 3/4/4 3/ 4 / 4
Airflow Direction Control(up & Down) Auto Auto
Airflow Direction Control(left & right) Auto Manual
Remote Controller Type Wireless LCD Wireless LCD
Setting Temperature Cooling 18°C~30°C 18°C~30°C
Range Heating 16°C~30°C 16°C~30°C
Auto Operation (Micom Control) - -
Auto Changeover (Micom Control) O O
Self Diagnosis O O
Timer 24hr, On/Off 24h, On/Off
Sleep Operation O O
Soft Dry Operation O O
Restart Delay(minute) 2 2
Deice Control(Defrost) O O
Hot Start O O
Jet Cool O O
Low Ambient Operation O(Logic) O
Special Function - -

Note : O : Applie, X : Not applied, – : No relation


• Filters are optional in some specific areas.
• For Circuit Breaker Rating, please conform to local standards whenever necessary.

30 2009 Product Data


4. Specifications Inverter single

Models Unit AS-W2465DH2[S24AW N52] AS-W2465GG1(S24AM N51G)


Cooling Capacity kW 3.87~7.03~7.74 3.87~7.03~7.74
Btu/h. 13,200~24,000~26,400 13,200~24,000~26,400
Heating Capacity kW 3.37~8.08~8.88 3.37~8.08~8.88
Btu/h. 11,500~27,570~30,300 11,500~27,570~30,300
Power Input Cooling/Heating W 2,500 / 2,880 2,500 / 2,880
Running Current Cooling/Heating A 11.0 / 13.0 11.0 / 13.0
Starting Current Cooling/Heating A 11.0 / 13.0 11.0 / 13.0
EER W/W 2.80 2.81
Btu/h.W 9.6 9.6
COP W/W 2.80 2.81
Power Supply Ø / V / Hz 1 / 220~240 / 50 1 / 220~240 / 50
Power Factor % 96.8 96.8
Air Flow Rate Indoor,Max m3/min(CFM) 18.0(636) 18.0(636)
Outdoor,Max m3/min(CFM) 58(2,048) 58(2,048)
Moisture Removal l/h. 3.2 3.2
Sound Level Indoor,H/M/L dB(A)±3 44 / 41 / 37 44 / 41 / 37
Outdoor,Max dB(A)±3 56 56
Refrigerant & Charge (at 7.5 m) g(oz) R410A, 1,800(63.5) R410, 1,800(63.5)
Additional Refrigerant charge g/m(oz/ft) 30(0.32) 30(0.32)
Compressor Type Rotary Rotary(Non Tropical)
Model 5KD240XCA21 5KD240XCA21
Motor Type Brushless DC Motor BLDC
Oil Type FV50S FV50S
Oil Charge cc 900 900
O.L.P. name CS-7LN115 CS-7L N115
Fan(Indoor) Type Cross Flow Fan Cross Flow Fan
Motor Output W 20 20
Fan(Outdoor) Type Propeller Propeller
Motor Type AC Induction AC Induction
Motor Output W 76.5 76.5
Circuit Breaker* A 30 30
Power Supply Cable No.*mm2 3*2.5 3*2.5
Power and Transmission Cable No.*mm2 No.*mm2 4*2.5(Including Earth) 4*2.5
Piping Connections Liquid Side mm(in) 9.52(3/8) 9.52(3/8)
Gas Side mm(in) 15.88(5/8) 15.88(5/8)
Drain Hose(O.D/ I.D.) mm(in) 21.5 / 16.0 (0.85 / 0.63) 21.5 / 16.0 (0.85 / 0.63)
Dimensions Indoor (W*H*D) mm 1,090*300*178 1,090*300*178
inch 42.9*11.8*7.1 42.9*11.8*7
Outdoor (W*H*D) mm 870*808*320 870*808*320
inch 34.25*31.5*12.6 34.3*31.5*12.6
Net Weight Indoor kg(lbs) 13(28.7) 13(28.7)
Outdoor kg(lbs) 60(132.3) 60(132.0)
Operation Range Cooling(Outdoor) °C(°F) -5~43(23~109.4) -5~43(Low Ambient)
Heating(Outdoor) °C(°F) -10~24(14.0~75.2) -10~24(14.0~75.2)
Max. Piping Length m(ft) 30(98) 30(98)
Max. Elevation Difference m(ft) 15(49) 15(49)
Tool Code(Chassis) Indoor + Outdoor S5 + UE1 S5 + UE1
Functions Temperature Control Thermistor Thermistor
Plasma Filter O O
Prefilter(washable/anti-fungus) O O
Auto Clean O O
CHAOS Wind(Auto Wind) O O
Steps, Fan/Cool/Heat 3/4/4 3/4/4
Airflow Direction Control(up & Down) Auto Auto
Airflow Direction Control(left & right) Auto Auto
Remote Controller Type Wireless LCD Wireless LCD
Setting Temperature Cooling 18°C~30°C 18°C~30°C
Range Heating 16°C~30°C 16°C~30°C
Auto Operation (Micom Control) - -
Auto Changeover (Micom Control) O O
Self Diagnosis O O
Timer 24hr, On/Off 24h, On/Off
Sleep Operation O O
Soft Dry Operation O O
Restart Delay(minute) 2 2
Deice Control(Defrost) O O
Hot Start O O
Jet Cool O O
Low Ambient Operation O(Logic) O
Special Function - -

Note : O : Applie, X : Not applied, – : No relation


• Filters are optional in some specific areas.
• For Circuit Breaker Rating, please conform to local standards whenever necessary.

2009 Product Data 31


4. Specifications Inverter single

Models Unit AS-W306DGM0[S30AW ND0] AS-W366DGM0[S36AW ND0]


Cooling Capacity kW 3.6~8.0~8.8 4.0~9.0~9.8
Btu/h. 12,283~27,296~30,026 13,648~30,708~33,438
Heating Capacity kW 5.3~9.6~10.2 5.6~10.4~11.0
Btu/h. 18,084~32,775~34,802 19,107~35,485~37,532
Power Input Cooling/Heating W 2,650 / 3,180 2,980 / 3,450
Running Current Cooling/Heating A 12.0 / 14.5 13.6 / 16.5
Starting Current Cooling/Heating A 12.0 / 14.5 13.6 / 16.5
EER W/W 3.0 3.2
Btu/h.W 10.3 10.3
COP W/W 3.0 3.0
Power Supply Ø / V / Hz 1 / 220~240 / 50 1 / 220~240 / 50
Power Factor % 97 97
Air Flow Rate Indoor,Max m3/min(CFM) 21(350) 25(416)
Outdoor,Max m3/min(CFM) 58(2,048) 68(1,133)
Moisture Removal l/h. 3.5 4.2
Sound Level Indoor,H/M/L dB(A)±3 46 / 43 / 39 47 / 44 / 41
Outdoor,Max dB(A)±3 54 58
Refrigerant & Charge (at 7.5 m) g(oz) R410A, 1,800(63.3)(at 10m) R410A, 2,200(77.6)
Additional Refrigerant charge g/m(oz/ft) 30(0.32) 35(0.38)
Compressor Type Rotary Rotary
Model 5KD240XAE21 5JD420XAD22
Motor Type Brushless DC motor Brushless DC motor
Oil Type FV50S FV50S
Oil Charge cc 900 1,300
O.L.P. name CS-7L 115 CS-7L 115
Fan(Indoor) Type Cross Flow Fan Cross Flow Fan
Motor Output W 70 75
Fan(Outdoor) Type Propeller Propeller
Motor Type Brushless DC motor Brushless DC motor
Motor Output W 80 100
Circuit Breaker* A 25 25
Power Supply Cable No.*mm2 3*2.5 3*2.5
Power and Transmission Cable No.*mm2 No.*mm2 4*0.75 (Including Earth) 4*0.75 (Including Earth)
Piping Connections Liquid Side mm(in) 6.35(1/4) 6.35(1/4)
Gas Side mm(in) 15.88(5/8) 15.88(5/8)
Drain Hose(O.D/ I.D.) mm(in) 21.5 / 16.0(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63)
Dimensions Indoor (W*H*D) mm 1,209*346*205 1,209*346*205
inch 47.6*13.6*8.1 47.6*13.6*8.1
Outdoor (W*H*D) mm 870*808*320 870*1,060*320
inch 34.3*31.8*12.6 34.3*41.7*12.6
Net Weight Indoor kg(lbs) 18(39.7) 19(41.9)
Outdoor kg(lbs) 60(132.3) 75(165.3)
Operation Range Cooling(Outdoor) °C(°F) -5~43(23~109.4) -10~43 (14~109.4)
Heating(Outdoor) °C(°F) -10~24(14.0~75.2) -15~24(5~75.2)
Max. Piping Length m(ft) 50(164) 50(164)
Max. Elevation Difference m(ft) 30(98.4) 30(98.4)
Tool Code(Chassis) Indoor + Outdoor SD + UE1 SD + UE2
Functions Temperature Control Thermistor Thermistor
Plasma Filter Neo Neo
Prefilter(washable/anti-fungus) O O
Auto Clean O O
CHAOS Wind(Auto Wind) O O
Steps, Fan/Cool/Heat 3/4/3 3/4/3
Airflow Direction Control(up & Down) Auto Auto
Airflow Direction Control(left & right) Auto Auto
Remote Controller Type Wireless LCD Wireless LCD
Setting Temperature Cooling 18°C~30°C 18°C~30°C
Range Heating 16°C~30°C 16°C~30°C
Auto Operation (Micom Control) - -
Auto Changeover (Micom Control) O O
Self Diagnosis O O
Timer 24h, On/Off 24h, On/Off
Sleep Operation O O
Soft Dry Operation O O
Restart Delay(minute) 3 3
Deice Control(Defrost) O O
Hot Start O O
Jet Cool O O
Low Ambient Operation O O
Special Function - -

Note : O : Applie, X : Not applied, – : No relation


• Filters are optional in some specific areas.
• For Circuit Breaker Rating, please conform to local standards whenever necessary.

32 2009 Product Data


Maestro
5.1 Indoor Units
5. Dimensional drawings

Place a level on raised tab


Unit Outline
442 442

Ø70
Ø70
Installation Plate
Left rear piping Right rear piping

133 95

175 217

SB

2009 Product Data


Indoor units

33
34
Libero

2009 Product Data


5. Dimensional drawings

Place a level on raised tab


Unit Outline
442 442

Ø70
Ø70
Installation Plate
Left rear piping Right rear piping

133 95

175 217

SB
Indoor units
5. Dimensional drawings Indoor units

2009 Product Data 35


5. Dimensional drawings Indoor units

36 2009 Product Data


5. Dimensional drawings Indoor units

296
175 45

221
65
Ø70

926
140
188
Ø70

45

2009 Product Data 37


5. Dimensional drawings Indoor units

38 2009 Product Data


295
59
49
46
925 56
189

66

42
127
136
168
178

Unit Outline
5. Dimensional drawings

M10 Place a level on raised tab M10

175
296
Ø70

45
45

140 Ø70 65
188 221
926

2009 Product Data


Indoor units

39
40
ART COOL Mirror

171
3

2009 Product Data


No. Part Name Remark
1 Front panel
915
2 Display & signal receiver
3 Air suction grille
4

282
282
Knockout hole
5 Installation plate

53
2

51 4

Note
1. Unit should be installed in compliance with the installation manual

37
in the product box.

165
2-R16
2. Unit shall be grounded in accordance with the local regulations or
51
applicable national codes.
50
5. Dimensional drawings

3. The Unit is powered from the outdoor unit. Therefore power cable
should be connected with the outdoor unit.
567
107 354

28
5

50
50*6=300

148
71
77

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: SE


641-713, Korea
www.lge.com/airconditioner
Indoor units
3 ART COOL Mirror

No. Part Name Remark


1 Front panel

299
4 2 Display & signal receiver
3 Air suction grille

10
63
2
53 4 Knockout hole
1107
200

Note

93

48
1. The unit should not be installed in a closed area.
72 2. In an area or space having no proper circulation, an air guide should
58 122 be installed on the outdoor side.
5. Dimensional drawings

175
296
Ø70

45
45
140 Ø70 65
188 221
926

76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: S8


641-713, Korea
www.lge.com/airconditioner

2009 Product Data


Indoor units

41
5. Dimensional drawings Outdoor units

5.2 Outdoor Units

42 2009 Product Data


5. Dimensional drawings Outdoor units

2009 Product Data 43


5. Dimensional drawings Outdoor units

44 2009 Product Data


5. Dimensional drawings Outdoor units

TOOL CODE : UE1


4

2
3
320

360
54 .6

340 79
76.4
1
16 0

31
ÿ5
546
870

301

319 25

808

2009 Product Data 45


5. Dimensional drawings Outdoor units

TOOL CODE : UE2


Remark
Part Name

3
2
4
320

360
1060
340 10
1038

320
1

80
75
55
162
870
546

301

460

10 492 261

46 2009 Product Data


6. Wiring diagrams Indoor Unit

6.1 Indoor units


Models: AS-W096BMS0, AS-W126BMS0

CN-OPTION
CN-L/R1
CN-MOTOR1 CN-U/D1 CN-HVB
(CN-INLET) CN-PIR/MOTOR CN-I/R
CN-DISP
(CN-LIMIT) CN-PIR CN-ROTATE

(CN-12V) (CN-DISP1)

CN-TH1

CN-LIMIT CN-WRITE
CN-INLET1 CN-H/S
(CN-MOVE, CN-HUMIDITY) CN-INLET2
CN-TH3
MAIN PCB

2009 Product Data 47


6. Wiring diagrams Indoor Unit

Models: AS-H09GB1U0, AS-H12GB1U0

CN-MOTOR1 CN-U/D1 CN-INLET


CN-L/R1 CN-OPTION
CN-HVB
CN-LIMIT CN-SUB2 CN-SUB1
CN-H/S CN-TH
CN-LIMIT

CN-12V
CN-DISP1

CN-TH3

CN-SW
CN-DISP

MAIN PCB

48 2009 Product Data


6. Wiring diagrams Indoor Unit

Models: AS-W096E1G0, AS-W0964GG1, AS-W126E1G0, AS-W1264GG1,AS-W1865GG1, AS-W2465DH2

Models: AS-W096F1G2, AS-W096F*G2, AS-W126F*G2

2009 Product Data 49


6. Wiring diagrams Indoor Unit

Models: AS-W096E*H2, AS-W126E*H2, AS-W126F1G2

Models: AS-W096ADR0, AS-W126ADR0

50 2009 Product Data


6. Wiring diagrams Indoor Unit

Models: AS-W1865DH2

CN_L/R(BL) CN_U/D(WH) CN_HVB(BL) CN_DISP2(BL)

CN_DISP1(WH)

CN_MOTOR1

CN_TH1

CN_TH2

2009 Product Data 51


6. Wiring diagrams Indoor Unit

Models: AS-W2463*H3

52 2009 Product Data


6. Wiring diagrams Indoor Unit

Models: AS-W2465GG1

CN_HUB/UV

CN_L/R(BL) CN_L/R(BL) CN_DISP2(BL)

CN_12V
CN_DISP(WH)

CN_MOTOR1
CN_TH1

CN_TH2

2009 Product Data 53


6. Wiring diagrams Indoor Unit

Models: AS-W2468*H1

54 2009 Product Data


6. Wiring diagrams Indoor Unit

Models:AS-W306DGM0,AS-W366DGM0

CN-U/D(WH) CN-DISP2(BL)
CN-MOTOR1 CN-L/R(BL) CN-HVB

CN-12V

CN-DISP1(WH)

CN-TH1

CN-TH2

2009 Product Data 55


6. Wiring diagrams Outdoor units

6.2 Outdoor units


Models: AS-W096BMS0, AS-W126BMS0, AS-H09GB1U0, AS-H12GB1U0

CN-4WAY
CN-COIL1

CN-COIL2 CN-TH2
CN-TH1

CN-EEV1
CN-FAN(DC)

56 2009 Product Data


6. Wiring diagrams Outdoor units

Models: AS-W096E1G0, AS-W126E1G0, AS-W096E*H2, AS-W126E*H2, AS-W096F1G2,


AS-W096F*G2, AS-W126F1G2, AS-W126F*G2

Models: AS-W0964GG1, AS-W1264GG1

2009 Product Data 57


6. Wiring diagrams Outdoor units

Models: AS-W096ADR0, AS-W126ADR0

58 2009 Product Data


6. Wiring diagrams Outdoor units

Models: AS-W1865DH2

CN_FAN(A) CN_4WAY

CN_COIL1
CN_COIL2

CN_TH3
(SUC/DIS_I)

CN_TH2 CN_COM
CN_LEV1 (AIR/PIPE)

2009 Product Data 59


6. Wiring diagrams Outdoor units

Models: AS-W1865GG1

Models: AS-W1868*H1

60 2009 Product Data


6. Wiring diagrams Outdoor units

Models: AS-W2468*H1, AS-W2465DH2

2009 Product Data 61


6. Wiring diagrams Outdoor units

Models: AS-W2465GG1

CN_COIL1 CN_FAN(A)CN_4WAY

CN_COIL2

CN_TH3

CN_TH1

CN_TH2

CN_LEV1

62 2009 Product Data


6. Wiring diagrams Outdoor units

Models: AS-W306DGM0

CN-PFC-OUT CN-PFC-IN CN 4WAY CN_H/P

CN_TH3
CN-TH2

CN-MOTOR1 CN_LEV1
CN_COM

2009 Product Data 63


6. Wiring diagrams Outdoor units

Models: AS-W366DGM0

CN-PFC-OUT CN-PFC-IN CN 4WAY CN_H/P

CN_TH3
CN-TH2

CN-MOTOR1 CN_LEV1
CN-MOTOR2 CN_COM

64 2009 Product Data


7. Refrigerant cycle diagram

Model No : AS-W096BMS0, AS-W126BMS0

Indoor Unit Outdoor Unit

Liquid Side

2-Way Valve EEV


Th2

Th1

Heat Heat
Exchanger Exchanger
Th5
(Evaporator) (Condenser)

Th4

Gas Side

Reversing Valve
3-Way Valve Accumulator

Th3

Compressor Cooling
Heating

LOC. Description PCB Connector


Th1 Thermistor for indoor air temperature CN-TH(INDOOR)
Th2 Thermistor for evaporating temperature CN-TH3(INDOOR)
Th3 Thermistor for discharge pipe temperature CN-TH2(OUTDOOR)
Th4 Thermistor for condensing temperature CN-TH1(OUTDOOR)
Th5 Thermistor for outdoor air temperature CN-TH1(OUTDOOR)

EEV : Electronic Expansion Valve

2009 Product Data 65


7. Refrigerant cycle diagram

Model No : AS-H09GB1U0, AS-H12GB1U0

Indoor Unit Outdoor Unit

Liquid Side

2-Way Valve EEV


Th2

Th1

Th4
Heat Heat
Exchanger Exchanger
Th7
(Evaporator) (Condenser)

Th3 Th6

Gas Side

Reversing Valve
3-Way Valve Accumulator

Th5

Compressor Cooling
Heating

LOC. Description PCB Connector


Th1 Thermistor for sunction air temperature
CN-TH1(Indoor)
Th2 Thermistor for evaporator inlet temperature
Th3 Thermistor for evaporator outlet temperature CN-TH2(Indoor)
Th4 Thermistor for evaporator middle temperature CN-TH3(Indoor)
Th5 Thermistor for discharge pipe temperature CN-TH2(OUTDOOR)
Th6 Thermistor for condensing temperature CN-TH1(OUTDOOR)
Th7 Thermistor for outdoor air temperature CN-TH1(OUTDOOR)

EEV : Electronic Expansion Valve

66 2009 Product Data


7. Refrigerant cycle diagram

Model No : AS-W1865GG1

Indoor Unit Outdoor Unit

Liquid Side CHECK VALVE

3-Way Valve
Th2

Th1
CAPILLARY TUBE

Heat Heat
Exchanger Exchanger
(Evaporator) (Condenser)
Th4

Th3

Gas Side

Reversing Valve
3-Way Valve Accumulator

Compressor Cooling
Heating

N.B. : -
Th1 = Thermistor foor sansing indoor air temperature.
Th2 = Thermistor for sensing evaporating temperature.
Th3 = Thermistor foor sansing outdoor air temperature.
Th4 = Thermistor foor sansing evaporating temperature.

2009 Product Data 67


7. Refrigerant cycle diagram

Model no: AS-W096ADR0,AS-W0964GG1, AS-W096E*H2, AS-W096F1G2,


AS-W096F*G2, AS-W096E1G0, AS-W126E1G0, AS-W126ADR0,
AS-W126E*H2, AS-W126F1G2, AS-W126F*G2, AS-W1264GG1
Indoor Unit Outdoor Unit

Liquid Side

2-Way Valve EEV


Th2

Th1

Heat Heat
Exchanger Exchanger
Th5
(Evaporator) (Condenser)

Th4

Gas Side

3-Way Valve Accumulator

Th3

Compressor Cooling
Heating

LOC. Description PCB Connector


Th1 Thermistor for indoor air temperature CN-TH1(INDOOR)
Th2 Thermistor for evaporating temperature CN-TH1(INDOOR)
Th3 Thermistor for discharge pipe temperature CN-D_PIPE(OUTDOOR)
Th4 Thermistor for condensing temperature CN-TH1(OUTDOOR)
Th5 Thermistor for outdoor air temperature CN-TH1(OUTDOOR)

68 2009 Product Data


7. Refrigerant cycle diagram

Model no: AS-W1865DH2, AS-W1868*H1

Indoor Unit Outdoor Unit

Liquid Side

2-Way Valve EEV


Th2 Th5

Th1

Heat Heat
Exchanger Exchanger
(Evaporator) (Condenser)

Th3 Th4

Gas Side

Reversing Valve
3-Way Valve
Th6
Th7

Compressor Cooling
Heating

LOC. Description PCB Connector


Th1 Thermistor for indoor air temperature
CN_TH1(INDOOR)
Th2 Thermister for indoor pipe(in) temperature
Th3 Thermister for indoor pipe(out) temperature CN_TH2(INDOOR)
Th4 Thermistor for outdoor air temperature
CN_TH2(OUTDOOR)
Th5 Thermister for outdoor pipe temperature
Th6 Thermistor for discharge pipe temperature
CN_TH3(OUTDOOR)
Th7 Thermistor for suction pipe temperature

2009 Product Data 69


7. Refrigerant cycle diagram

Model no: AS-W2468*H1, AS-W2465DH2

Indoor Unit Outdoor Unit

Liquid Side

3-Way Valve EEV


Th2 Th5

Th1

Heat Heat
Exchanger Exchanger
(Evaporator) (Condenser)

Th3 Th4

Gas Side

Reversing Valve
3-Way Valve
Th6
Th7

Compressor Cooling
Heating

LOC. Description PCB Connector


Th1 Thermistor for indoor air temperature
CN_TH1(INDOOR)
Th2 Thermister for indoor pipe(in) temperature
Th3 Thermister for indoor pipe(out) temperature CN_TH2(INDOOR)
Th4 Thermistor for outdoor air temperature
CN_TH2(OUTDOOR)
Th5 Thermister for outdoor pipe temperature
Th6 Thermistor for discharge pipe temperature
CN_TH3(OUTDOOR)
Th7 Thermistor for suction pipe temperature

70 2009 Product Data


7. Refrigerant cycle diagram

Model no: AS-W2465GG1

Indoor Unit Outdoor Unit

Liquid Side

2-Way Valve EEV


Th2

Th1

Heat Heat
Exchanger Exchanger
(Evaporator) (Condenser)

Th3 Th4

Th5

Gas Side

Accumulator Reversing Valve


3-Way Valve
Th6
Th7

Compressor Cooling
Heating

LOC. Description PCB Connector


Th1 Thermistor for indoor air temperature CN_TH1(INDOOR)
Th2 CN_TH2(INDOOR)
Thermistor for evaporating temperature
Th3 CN_TH3(INDOOR)
Th4 Thermistor for outdoor air temperature
CN_TH2(OUTDOOR)
Th5 Thermistor for condensing temperature
Th6 Thermistor for discharge pipe temperature
CN_TH3(OUTDOOR)
Th7 Thermistor for suction pipe temperature

2009 Product Data 71


7. Refrigerant cycle diagram

Model no: AS-W306DGM0, AS-W366DGM0

Indoor Unit Outdoor Unit

Reversing
Liquid Side Valve

Th3 3-Way Valve


Th7 Th5
Th1 High
Pressure
S/W Heat
Heat Accumulator Exchanger
Exchanger Th6
(Condenser)
(Evaporator)

Inverter
Compressor
Th2 Th4

Gas Side EEV

3-Way Valve

Cooling
Heating

LOC. Description PCB Connector


Th1 Thermister for indoor air temperature
CN_TH1(INDOOR)
Th2 Thermister for indoor pipe(in) temperature
Th3 Thermister for indoor pipe(out) temperature CN-TH2(INDOOR)
Th4 Thermister for outdoor pipe temperature
CN_TH2(OUTDOOR)
Th5 Thermister for outdoor air temperature
Th6 Thermister for outdoor discharge pipe temperature(Inverter)
CN_TH3(OUTDOOR)
Th7 Thermister for outdoor suction pipe temperature(Inverter)

72 2009 Product Data


8. Capacity tables Cooling

8.1 Cooling Capacity


AS-W096BMS0

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.45 0.92 0.30 2.34 0.93 0.32 2.20 0.95 0.43
16.0 22.0 2.60 0.88 0.41 2.49 0.89 0.42 2.35 0.91 0.50
18.0 25.0 2.75 0.84 0.45 2.65 0.85 0.45 2.50 0.87 0.53
19.0 27.0 2.83 0.82 0.45 2.72 0.83 0.45 2.58 0.85 0.53
22.0 30.0 3.05 0.78 0.45 2.95 0.79 0.46 2.80 0.81 0.55
24.0 32.0 3.21 0.76 0.45 3.10 0.76 0.47 2.95 0.78 0.56

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.13 0.95 0.48 2.04 0.96 0.52 1.98 0.96 0.51
16.0 22.0 2.28 0.91 0.54 2.19 0.92 0.56 2.13 0.91 0.54
18.0 25.0 2.43 0.87 0.56 2.34 0.88 0.57 2.28 0.87 0.53
19.0 27.0 2.50 0.85 0.55 2.41 0.86 0.57 2.36 0.86 0.53
22.0 30.0 2.73 0.80 0.58 2.64 0.81 0.58 2.58 0.81 0.54
24.0 32.0 2.88 0.78 0.59 2.78 0.79 0.59 2.73 0.78 0.55

AS-H09GB1U0

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.45 0.92 0.30 2.34 0.93 0.32 2.20 0.95 0.43
16.0 22.0 2.60 0.88 0.41 2.49 0.89 0.42 2.35 0.91 0.50
18.0 25.0 2.75 0.84 0.45 2.65 0.85 0.45 2.50 0.87 0.53
19.0 27.0 2.83 0.82 0.45 2.72 0.83 0.45 2.58 0.85 0.53
22.0 30.0 3.05 0.78 0.45 2.95 0.79 0.46 2.80 0.81 0.55
24.0 32.0 3.21 0.76 0.45 3.10 0.76 0.47 2.95 0.78 0.56

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.13 0.95 0.48 2.04 0.96 0.52 1.98 0.96 0.51
16.0 22.0 2.28 0.91 0.54 2.19 0.92 0.56 2.13 0.91 0.54
18.0 25.0 2.43 0.87 0.56 2.34 0.88 0.57 2.28 0.87 0.53
19.0 27.0 2.50 0.85 0.55 2.41 0.86 0.57 2.36 0.86 0.53
22.0 30.0 2.73 0.80 0.58 2.64 0.81 0.58 2.58 0.81 0.54
24.0 32.0 2.88 0.78 0.59 2.78 0.79 0.59 2.73 0.78 0.55

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)

2009 Product Data 73


8. Capacity tables Cooling

AS-W096ADR0

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.59 2.21 0.36 2.48 2.14 0.37 2.32 2.06 0.50
16.0 22.0 2.75 2.24 0.49 2.63 2.18 0.49 2.48 2.09 0.59
18.0 25.0 2.91 2.26 0.53 2.79 2.20 0.53 2.64 2.12 0.62
19.0 27.0 2.99 2.28 0.53 2.87 2.22 0.54 2.72 2.15 0.63
22.0 30.0 3.23 2.33 0.53 3.11 2.27 0.55 2.96 2.21 0.65
24.0 32.0 3.39 2.37 0.53 3.27 2.32 0.55 3.11 2.25 0.66

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.25 1.99 0.56 2.16 1.93 0.62 2.10 1.86 0.60
16.0 22.0 2.41 2.03 0.64 2.31 1.97 0.66 2.25 1.91 0.63
18.0 25.0 2.57 2.06 0.65 2.47 2.01 0.67 2.41 1.94 0.63
19.0 27.0 2.64 2.08 0.65 2.55 2.03 0.68 2.49 1.97 0.63
22.0 30.0 2.88 2.14 0.68 2.78 2.10 0.69 2.72 2.04 0.64
24.0 32.0 3.04 2.19 0.70 2.94 2.15 0.70 2.88 2.09 0.65

AS-W096E*H2

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.14 1.67 0.43 2.09 1.65 0.50 2.00 1.61 0.59
16.0 22.0 2.50 1.89 0.43 2.44 1.88 0.51 2.33 1.82 0.60
18.0 25.0 2.79 2.06 0.44 2.73 2.04 0.52 2.60 1.98 0.61
19.0 27.0 2.91 2.13 0.45 2.85 2.11 0.53 2.72 2.04 0.62
22.0 30.0 3.20 2.26 0.45 3.13 2.23 0.54 2.98 2.16 0.62
24.0 32.0 3.32 2.30 0.46 3.25 2.27 0.54 3.10 2.19 0.63

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 1.94 1.58 0.62 1.86 1.54 0.66 1.82 1.52 0.68
16.0 22.0 2.26 1.78 0.63 2.17 1.74 0.67 2.12 1.71 0.69
18.0 25.0 2.52 1.93 0.64 2.43 1.88 0.68 2.37 1.85 0.70
19.0 27.0 2.64 1.99 0.65 2.54 1.94 0.69 2.48 1.91 0.71
22.0 30.0 2.89 2.10 0.66 2.79 2.05 0.70 2.72 2.01 0.72
24.0 32.0 3.00 2.13 0.67 2.89 2.07 0.71 2.83 2.03 0.73

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)

74 2009 Product Data


8. Capacity tables Cooling

AS-W096F1G2, AS-W096F*G2

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.19 1.71 0.54 2.14 1.69 0.64 2.04 1.65 0.75
16.0 22.0 2.55 1.94 0.55 2.50 1.92 0.65 2.38 1.86 0.76
18.0 25.0 2.85 2.11 0.56 2.79 2.09 0.66 2.66 2.02 0.77
19.0 27.0 2.98 2.18 0.57 2.92 2.16 0.68 2.78 2.09 0.79
22.0 30.0 3.27 2.31 0.58 3.20 2.28 0.68 3.05 2.21 0.80
24.0 32.0 3.40 2.35 0.59 3.33 2.32 0.69 3.17 2.24 0.81

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 1.98 1.61 0.79 1.91 1.58 0.84 1.86 1.55 0.87
16.0 22.0 2.31 1.82 0.80 2.23 1.78 0.86 2.17 1.75 0.88
18.0 25.0 2.58 1.98 0.82 2.48 1.93 0.87 2.43 1.90 0.90
19.0 27.0 2.70 2.04 0.83 2.60 1.99 0.88 2.54 1.95 0.91
22.0 30.0 2.96 2.15 0.84 2.85 2.09 0.89 2.79 2.06 0.92
24.0 32.0 3.07 2.18 0.85 2.96 2.12 0.91 2.89 2.08 0.94

AS-W0964GG1

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.14 1.67 0.54 2.09 1.65 0.64 2.00 1.61 0.74
16.0 22.0 2.50 1.89 0.55 2.44 1.88 0.65 2.33 1.82 0.75
18.0 25.0 2.79 2.06 0.55 2.73 2.04 0.66 2.60 1.98 0.77
19.0 27.0 2.91 2.13 0.56 2.85 2.11 0.67 2.72 2.04 0.78
22.0 30.0 3.20 2.26 0.57 3.13 2.23 0.68 2.98 2.16 0.79
24.0 32.0 3.32 2.30 0.58 3.25 2.27 0.69 3.10 2.19 0.80

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 1.94 1.58 0.78 1.86 1.54 0.83 1.82 1.52 0.86
16.0 22.0 2.26 1.78 0.79 2.17 1.74 0.84 2.12 1.71 0.87
18.0 25.0 2.52 1.93 0.81 2.43 1.88 0.86 2.37 1.85 0.89
19.0 27.0 2.64 1.99 0.82 2.54 1.94 0.87 2.48 1.91 0.90
22.0 30.0 2.89 2.10 0.83 2.79 2.05 0.88 2.72 2.01 0.91
24.0 32.0 3.00 2.13 0.84 2.89 2.07 0.90 2.83 2.03 0.93

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)

2009 Product Data 75


8. Capacity tables Cooling

AS-W126BMS0

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 3.43 0.92 0.49 3.28 0.93 0.51 3.08 0.95 0.68
16.0 22.0 3.64 0.88 0.66 3.49 0.89 0.66 3.29 0.91 0.80
18.0 25.0 3.85 0.84 0.71 3.70 0.85 0.72 3.50 0.87 0.84
19.0 27.0 3.96 0.82 0.72 3.81 0.83 0.73 3.61 0.85 0.85
22.0 30.0 4.28 0.78 0.72 4.12 0.79 0.74 3.92 0.81 0.87
24.0 32.0 4.49 0.76 0.72 4.33 0.76 0.75 4.13 0.78 0.89

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.99 0.95 0.76 2.86 0.96 0.84 2.78 0.96 0.82
16.0 22.0 3.20 0.91 0.86 3.07 0.92 0.90 2.99 0.91 0.86
18.0 25.0 3.40 0.87 0.90 3.27 0.88 0.91 3.19 0.87 0.86
19.0 27.0 3.50 0.85 0.88 3.38 0.86 0.92 3.30 0.86 0.85
22.0 30.0 3.82 0.80 0.92 3.69 0.81 0.93 3.61 0.81 0.86
24.0 32.0 4.03 0.78 0.94 3.90 0.79 0.95 3.82 0.78 0.88

AS-H12GB1U0

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 3.43 0.92 0.49 3.28 0.93 0.51 3.08 0.95 0.68
16.0 22.0 3.64 0.88 0.66 3.49 0.89 0.66 3.29 0.91 0.80
18.0 25.0 3.85 0.84 0.71 3.70 0.85 0.72 3.50 0.87 0.84
19.0 27.0 3.96 0.82 0.72 3.81 0.83 0.73 3.61 0.85 0.85
22.0 30.0 4.28 0.78 0.72 4.12 0.79 0.74 3.92 0.81 0.87
24.0 32.0 4.49 0.76 0.72 4.33 0.76 0.75 4.13 0.78 0.89

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.99 0.95 0.76 2.86 0.96 0.84 2.78 0.96 0.82
16.0 22.0 3.20 0.91 0.86 3.07 0.92 0.90 2.99 0.91 0.86
18.0 25.0 3.40 0.87 0.90 3.27 0.88 0.91 3.19 0.87 0.86
19.0 27.0 3.50 0.85 0.88 3.38 0.86 0.92 3.30 0.86 0.85
22.0 30.0 3.82 0.80 0.92 3.69 0.81 0.93 3.61 0.81 0.86
24.0 32.0 4.03 0.78 0.94 3.90 0.79 0.95 3.82 0.78 0.88

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)

76 2009 Product Data


8. Capacity tables Cooling

AS-W126ADR0

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 3.44 2.88 0.60 3.29 2.79 0.63 3.09 2.67 0.84
16.0 22.0 3.65 2.92 0.82 3.50 2.83 0.82 3.30 2.72 1.00
18.0 25.0 3.87 2.94 0.88 3.71 2.86 0.89 3.51 2.76 1.05
19.0 27.0 3.97 2.97 0.89 3.82 2.89 0.90 3.62 2.79 1.06
22.0 30.0 4.29 3.03 0.89 4.14 2.95 0.92 3.93 2.87 1.08
24.0 32.0 4.50 3.08 0.89 4.35 3.01 0.92 4.14 2.93 1.10

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 3.00 2.58 0.94 2.87 2.50 1.03 2.79 2.42 1.01
16.0 22.0 3.21 2.64 1.07 3.07 2.56 1.11 3.00 2.48 1.06
18.0 25.0 3.41 2.68 1.09 3.28 2.61 1.13 3.20 2.53 1.06
19.0 27.0 3.51 2.70 1.09 3.39 2.64 1.13 3.31 2.56 1.06
22.0 30.0 3.83 2.79 1.14 3.70 2.73 1.15 3.62 2.65 1.07
24.0 32.0 4.04 2.85 1.17 3.91 2.80 1.18 3.83 2.72 1.09

AS-W126E1G0, AS-W126E*H2

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.85 2.22 0.71 2.79 2.21 0.85 2.66 2.14 0.99
16.0 22.0 3.33 2.53 0.73 3.26 2.50 0.86 3.10 2.43 1.00
18.0 25.0 3.71 2.75 0.74 3.63 2.72 0.87 3.46 2.63 1.02
19.0 27.0 3.89 2.84 0.75 3.80 2.81 0.89 3.63 2.72 1.03
22.0 30.0 4.27 3.01 0.76 4.17 2.97 0.90 3.98 2.87 1.05
24.0 32.0 4.43 3.06 0.77 4.33 3.02 0.91 4.13 2.92 1.06

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.58 2.10 1.04 2.49 2.05 1.11 2.43 2.03 1.14
16.0 22.0 3.01 2.38 1.06 2.90 2.32 1.12 2.83 2.28 1.16
18.0 25.0 3.36 2.57 1.07 3.24 2.51 1.14 3.16 2.47 1.18
19.0 27.0 3.52 2.66 1.09 3.39 2.59 1.16 3.31 2.55 1.20
22.0 30.0 3.86 2.81 1.10 3.72 2.73 1.17 3.63 2.68 1.21
24.0 32.0 4.01 2.84 1.12 3.86 2.76 1.19 3.77 2.71 1.23

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)

2009 Product Data 77


8. Capacity tables Cooling

AS-W126F1G2, AS-W126F*G2

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 3.43 2.82 0.60 3.28 2.73 0.63 3.08 2.62 0.84
16.0 22.0 3.64 2.85 0.82 3.49 2.77 0.82 3.29 2.67 1.00
18.0 25.0 3.85 2.88 0.88 3.70 2.80 0.89 3.50 2.70 1.05
19.0 27.0 3.96 2.90 0.89 3.81 2.83 0.90 3.61 2.73 1.06
22.0 30.0 4.28 2.96 0.89 4.12 2.89 0.92 3.92 2.81 1.08
24.0 32.0 4.49 3.02 0.89 4.33 2.95 0.92 4.13 2.87 1.10

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.99 2.53 0.94 2.86 2.45 1.03 2.78 2.36 1.01
16.0 22.0 3.20 2.58 1.07 3.07 2.51 1.11 2.99 2.43 1.06
18.0 25.0 3.40 2.62 1.09 3.27 2.55 1.13 3.19 2.47 1.06
19.0 27.0 3.50 2.64 1.09 3.38 2.59 1.13 3.30 2.51 1.06
22.0 30.0 3.82 2.73 1.14 3.69 2.67 1.15 3.61 2.59 1.07
24.0 32.0 4.03 2.79 1.17 3.90 2.74 1.18 3.82 2.66 1.09

AS-W1264GG1

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.85 2.22 0.71 2.79 2.21 0.85 2.66 2.14 0.99
16.0 22.0 3.33 2.53 0.73 3.26 2.50 0.86 3.10 2.43 1.00
18.0 25.0 3.71 2.75 0.74 3.63 2.72 0.87 3.46 2.63 1.02
19.0 27.0 3.89 2.84 0.75 3.80 2.81 0.89 3.63 2.72 1.03
22.0 30.0 4.27 3.01 0.76 4.17 2.97 0.90 3.98 2.87 1.05
24.0 32.0 4.43 3.06 0.77 4.33 3.02 0.91 4.13 2.92 1.06

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.58 2.10 1.04 2.49 2.05 1.11 2.43 2.03 1.14
16.0 22.0 3.01 2.38 1.06 2.90 2.32 1.12 2.83 2.28 1.16
18.0 25.0 3.36 2.57 1.07 3.24 2.51 1.14 3.16 2.47 1.18
19.0 27.0 3.52 2.66 1.09 3.39 2.59 1.16 3.31 2.55 1.20
22.0 30.0 3.86 2.81 1.10 3.72 2.73 1.17 3.63 2.68 1.21
24.0 32.0 4.01 2.84 1.12 3.86 2.76 1.19 3.77 2.71 1.23

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)

78 2009 Product Data


8. Capacity tables Cooling

AS-W126U*H1

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.85 2.22 0.71 2.79 2.21 0.85 2.66 2.14 0.99
16.0 22.0 3.33 2.53 0.73 3.26 2.50 0.86 3.10 2.43 1.00
18.0 25.0 3.71 2.75 0.74 3.63 2.72 0.87 3.46 2.63 1.02
19.0 27.0 3.89 2.84 0.75 3.80 2.81 0.89 3.63 2.72 1.03
22.0 30.0 4.27 3.01 0.76 4.17 2.97 0.90 3.98 2.87 1.05
24.0 32.0 4.43 3.06 0.77 4.33 3.02 0.91 4.13 2.92 1.06

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.58 2.10 1.04 2.49 2.05 1.11 2.43 2.03 1.14
16.0 22.0 3.01 2.38 1.06 2.90 2.32 1.12 2.83 2.28 1.16
18.0 25.0 3.36 2.57 1.07 3.24 2.51 1.14 3.16 2.47 1.18
19.0 27.0 3.52 2.66 1.09 3.39 2.59 1.16 3.31 2.55 1.20
22.0 30.0 3.86 2.81 1.10 3.72 2.73 1.17 3.63 2.68 1.21
24.0 32.0 4.01 2.84 1.12 3.86 2.76 1.19 3.77 2.71 1.23

AS-W1865DH2

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 5.18 4.27 0.91 4.95 4.13 0.95 4.65 3.96 1.27
16.0 22.0 5.50 4.32 1.23 5.27 4.19 1.24 4.97 4.04 1.50
18.0 25.0 5.81 4.36 1.33 5.59 4.24 1.34 5.28 4.10 1.57
19.0 27.0 5.97 4.40 1.34 5.75 4.28 1.36 5.44 4.14 1.59
22.0 30.0 6.45 4.49 1.34 6.22 4.38 1.38 5.91 4.25 1.63
24.0 32.0 6.77 4.57 1.34 6.54 4.47 1.39 6.23 4.35 1.66

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 4.51 3.83 1.42 4.31 3.71 1.56 4.19 3.58 1.53
16.0 22.0 4.82 3.91 1.61 4.62 3.80 1.68 4.51 3.68 1.60
18.0 25.0 5.14 3.97 1.64 4.94 3.87 1.70 4.82 3.75 1.59
19.0 27.0 5.28 4.01 1.64 5.10 3.92 1.71 4.98 3.80 1.59
22.0 30.0 5.76 4.13 1.72 5.57 4.05 1.73 5.45 3.93 1.61
24.0 32.0 6.08 4.23 1.75 5.88 4.15 1.77 5.76 4.03 1.64

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)

2009 Product Data 79


8. Capacity tables Cooling

AS-W1865GG1

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14 20.0 5.18 4.25 0.96 4.95 4.11 1.00 4.65 3.94 1.34
16 22.0 5.50 4.30 1.30 5.27 4.17 1.31 4.97 4.02 1.58
18 25.0 5.81 4.34 1.40 5.59 4.22 1.41 5.28 4.07 1.66
19 27.0 5.97 4.38 1.42 5.75 4.26 1.43 5.44 4.12 1.68
22 30.0 6.45 4.46 1.42 6.22 4.35 1.45 5.91 4.23 1.72
24 32.0 6.77 4.55 1.41 6.54 4.44 1.47 6.23 4.32 1.75

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14 20.0 4.51 3.81 1.50 4.31 3.69 1.64 4.19 3.56 1.61
16 22.0 4.82 3.89 1.70 4.62 3.78 1.77 4.51 3.66 1.68
18 25.0 5.14 3.95 1.73 4.94 3.85 1.79 4.82 3.73 1.68
19 27.0 5.28 3.99 1.73 5.10 3.90 1.80 4.98 3.78 1.68
22 30.0 5.76 4.11 1.81 5.57 4.02 1.83 5.45 3.91 1.69
24 32.0 6.08 4.21 1.85 5.88 4.13 1.87 5.76 4.01 1.73

AS-W1868*H1

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 4.28 3.36 1.07 4.19 3.33 1.27 3.99 3.24 1.48
16.0 22.0 4.99 3.81 1.09 4.89 3.77 1.29 4.66 3.66 1.51
18.0 25.0 5.57 4.15 1.11 5.45 4.10 1.31 5.20 3.97 1.53
19.0 27.0 5.83 4.29 1.13 5.71 4.24 1.34 5.44 4.10 1.56
22.0 30.0 6.40 4.55 1.14 6.26 4.49 1.35 5.97 4.34 1.58
24.0 32.0 6.64 4.62 1.16 6.50 4.56 1.37 6.19 4.40 1.60

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 3.87 3.17 1.56 3.73 3.10 1.66 3.64 3.06 1.72
16.0 22.0 4.52 3.58 1.59 4.35 3.50 1.69 4.25 3.45 1.75
18.0 25.0 5.04 3.88 1.61 4.85 3.79 1.72 4.74 3.73 1.77
19.0 27.0 5.28 4.01 1.64 5.08 3.91 1.74 4.96 3.84 1.80
22.0 30.0 5.79 4.23 1.66 5.57 4.12 1.77 5.45 4.04 1.83
24.0 32.0 6.01 4.29 1.69 5.78 4.17 1.79 5.65 4.09 1.85

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)

80 2009 Product Data


8. Capacity tables Cooling

AS-W2465GG1

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 6.89 5.65 1.38 6.59 5.47 1.44 6.19 5.25 1.94
16.0 22.0 7.32 5.73 1.87 7.02 5.56 1.89 6.61 5.35 2.28
18.0 25.0 7.74 5.78 2.02 7.44 5.61 2.04 7.03 5.42 2.40
19.0 27.0 7.95 5.83 2.05 7.65 5.67 2.07 7.24 5.49 2.42
22.0 30.0 8.59 5.94 2.05 8.28 5.80 2.10 7.87 5.63 2.48
24.0 32.0 9.02 6.05 2.04 8.70 5.91 2.12 8.29 5.76 2.53

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 6.00 5.07 2.16 5.74 4.92 2.37 5.58 4.75 2.33
16.0 22.0 6.42 5.18 2.45 6.16 5.04 2.56 6.00 4.87 2.43
18.0 25.0 6.84 5.26 2.50 6.58 5.13 2.59 6.42 4.96 2.43
19.0 27.0 7.03 5.31 2.50 6.78 5.19 2.60 6.63 5.03 2.42
22.0 30.0 7.67 5.47 2.62 7.41 5.36 2.64 7.25 5.20 2.45
24.0 32.0 8.09 5.60 2.67 7.83 5.49 2.70 7.67 5.34 2.50

AS-W2465DH2

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 5.70 4.45 1.64 5.58 4.41 1.94 5.32 4.29 2.26
16.0 22.0 6.66 5.05 1.66 6.52 5.00 1.97 6.21 4.86 2.30
18.0 25.0 7.43 5.50 1.69 7.27 5.43 2.00 6.93 5.27 2.33
19.0 27.0 7.77 5.68 1.72 7.61 5.62 2.04 7.25 5.44 2.37
22.0 30.0 8.53 6.03 1.74 8.35 5.95 2.06 7.96 5.75 2.40
24.0 32.0 8.85 6.13 1.76 8.67 6.04 2.09 8.26 5.83 2.44

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 5.16 4.20 2.38 4.97 4.11 2.54 4.86 4.05 2.62
16.0 22.0 6.02 4.75 2.42 5.80 4.64 2.58 5.66 4.57 2.66
18.0 25.0 6.72 5.15 2.46 6.47 5.02 2.61 6.32 4.94 2.70
19.0 27.0 7.03 5.31 2.50 6.77 5.18 2.66 6.62 5.09 2.75
22.0 30.0 7.72 5.61 2.53 7.43 5.46 2.69 7.26 5.36 2.78
24.0 32.0 8.01 5.69 2.57 7.71 5.53 2.73 7.53 5.42 2.82

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)

2009 Product Data 81


8. Capacity tables Cooling

AS-W2468*H1

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 5.70 4.65 1.61 5.58 4.61 1.90 5.32 4.49 2.22
16.0 22.0 6.66 5.28 1.63 6.52 5.23 1.93 6.21 5.08 2.25
18.0 25.0 7.43 5.75 1.65 7.27 5.68 1.96 6.93 5.51 2.29
19.0 27.0 7.77 5.94 1.68 7.61 5.87 1.99 7.25 5.69 2.33
22.0 30.0 8.53 6.30 1.70 8.35 6.22 2.02 7.96 6.01 2.36
24.0 32.0 8.85 6.41 1.73 8.67 6.32 2.05 8.26 6.10 2.39

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 5.16 4.39 2.34 4.97 4.30 2.49 4.86 4.24 2.57
16.0 22.0 6.02 4.97 2.37 5.80 4.85 2.52 5.66 4.78 2.61
18.0 25.0 6.72 5.38 2.41 6.47 5.25 2.56 6.32 5.17 2.65
19.0 27.0 7.03 5.56 2.45 6.77 5.41 2.61 6.62 5.33 2.69
22.0 30.0 7.72 5.87 2.48 7.43 5.71 2.64 7.26 5.61 2.73
24.0 32.0 8.01 5.95 2.52 7.71 5.78 2.68 7.53 5.67 2.77

AS-W306DGM0

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 7.84 6.90 1.46 7.50 6.68 1.53 7.04 6.41 2.05
16.0 22.0 8.33 6.99 1.98 7.98 6.78 2.00 7.52 6.53 2.42
18.0 25.0 8.81 7.05 2.15 8.46 6.85 2.16 8.00 6.62 2.54
19.0 27.0 9.05 7.12 2.17 8.70 6.92 2.19 8.24 6.70 2.57
22.0 30.0 9.78 7.26 2.17 9.43 7.08 2.23 8.96 6.88 2.63
24.0 32.0 10.3 7.39 2.16 9.91 7.22 2.25 9.44 7.03 2.68

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 6.83 6.19 2.29 6.53 6.00 2.52 6.35 5.79 2.46
16.0 22.0 7.31 6.32 2.60 7.01 6.15 2.71 6.83 5.94 2.58
18.0 25.0 7.78 6.42 2.65 7.48 6.26 2.75 7.30 6.06 2.58
19.0 27.0 8.00 6.48 2.65 7.72 6.34 2.76 7.54 6.14 2.57
22.0 30.0 8.73 6.68 2.78 8.43 6.54 2.80 8.25 6.35 2.60
24.0 32.0 9.21 6.84 2.83 8.91 6.71 2.86 8.73 6.52 2.65

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)

82 2009 Product Data


8. Capacity tables Cooling

AS-W366DGM0

Indoor Air Outdoor Air Temperature : °CDB


Temperature
20 25 32
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 8.82 7.29 1.65 8.44 7.05 1.72 7.93 6.77 2.31
16.0 22.0 9.37 7.38 2.23 8.98 7.16 2.25 8.46 6.89 2.72
18.0 25.0 9.91 7.44 2.41 9.52 7.24 2.43 9.00 6.99 2.86
19.0 27.0 10.2 7.51 2.44 9.79 7.31 2.46 9.27 7.07 2.89
22.0 30.0 11.0 7.66 2.44 10.6 7.47 2.50 10.1 7.26 2.96
24.0 32.0 11.5 7.80 2.43 11.1 7.62 2.53 10.6 7.42 3.01

Indoor Air Outdoor Air Temperature : °CDB


Temperature
35 40 43
°CWB °CDB TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 7.68 6.54 2.58 7.35 6.34 2.83 7.14 6.12 2.77
16.0 22.0 8.22 6.67 2.92 7.88 6.49 3.05 7.68 6.27 2.90
18.0 25.0 8.75 6.78 2.98 8.42 6.61 3.09 8.22 6.40 2.90
19.0 27.0 9.00 6.84 2.98 8.69 6.69 3.10 8.48 6.49 2.89
22.0 30.0 9.83 7.05 3.12 9.49 6.90 3.15 9.29 6.70 2.92
24.0 32.0 10.4 7.22 3.19 10.0 7.08 3.22 9.82 6.88 2.98

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)

2009 Product Data 83


8. Capacity tables Heating

8.2 Heating Capacity

AS-W096BMS0, AS-H09GB1U0
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 1.88 2.61 1.98 2.55 2.14 2.66 2.29 2.86 2.54 3.06 2.69 3.19 2.91 3.39
18.0 1.86 2.65 1.97 2.61 2.15 2.74 2.29 2.94 2.52 3.13 2.65 3.25 2.91 3.43
20.0 1.85 2.70 1.97 2.68 2.15 2.82 2.28 3.02 2.50 3.20 2.63 3.30 2.91 3.45
21.0 1.84 2.72 1.97 2.71 2.15 2.86 2.28 3.06 2.48 3.23 2.63 3.32 2.89 3.46
22.0 1.84 2.75 1.97 2.75 2.15 2.90 2.27 3.10 2.47 3.26 2.63 3.34 2.87 3.46
24.0 1.82 2.82 1.96 2.83 2.12 2.98 2.25 3.17 2.45 3.31 2.59 3.37 2.83 3.48

AS-W096ADR0, AS-W096E*H2
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 2.71 0.71 2.85 0.69 3.09 0.72 3.30 0.78 3.66 0.83 3.87 0.87 4.20 0.92
18.0 2.68 0.72 2.84 0.71 3.09 0.75 3.30 0.80 3.64 0.85 3.82 0.88 4.18 0.93
20.0 2.66 0.73 2.84 0.73 3.09 0.77 3.29 0.82 3.60 0.87 3.79 0.90 4.19 0.94
21.0 2.66 0.74 2.84 0.74 3.09 0.78 3.28 0.83 3.58 0.88 3.79 0.90 4.16 0.94
22.0 2.65 0.75 2.84 0.75 3.09 0.79 3.27 0.84 3.55 0.89 3.79 0.91 4.13 0.94
24.0 2.62 0.77 2.82 0.77 3.05 0.81 3.24 0.86 3.52 0.90 3.72 0.92 4.08 0.95

AS-W096F1G2, AS-W096F*G2
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 2.63 0.78 2.77 0.76 3.00 0.80 3.21 0.86 3.56 0.92 3.76 0.96 4.08 1.02
18.0 2.61 0.79 2.76 0.78 3.00 0.82 3.20 0.88 3.53 0.94 3.71 0.97 4.07 1.03
20.0 2.59 0.81 2.76 0.80 3.01 0.85 3.20 0.91 3.50 0.96 3.69 0.99 4.07 1.04
21.0 2.58 0.82 2.76 0.81 3.01 0.86 3.19 0.92 3.48 0.97 3.69 1.00 4.05 1.04
22.0 2.58 0.83 2.76 0.83 3.00 0.87 3.18 0.93 3.45 0.98 3.68 1.00 4.01 1.04
24.0 2.55 0.85 2.74 0.85 2.97 0.89 3.15 0.95 3.43 0.99 3.62 1.01 3.97 1.05

AS-W0964GG1
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 2.38 0.76 2.51 0.74 2.72 0.77 2.90 0.83 3.22 0.89 3.41 0.93 3.70 0.99
18.0 2.36 0.77 2.50 0.76 2.72 0.80 2.90 0.86 3.20 0.91 3.36 0.94 3.68 1.00
20.0 2.34 0.78 2.50 0.78 2.72 0.82 2.89 0.88 3.17 0.93 3.34 0.96 3.69 1.00
21.0 2.34 0.79 2.50 0.79 2.72 0.83 2.89 0.89 3.15 0.94 3.34 0.96 3.67 1.01
22.0 2.33 0.80 2.50 0.80 2.72 0.84 2.88 0.90 3.13 0.95 3.34 0.97 3.64 1.01
24.0 2.31 0.82 2.48 0.82 2.69 0.87 2.86 0.92 3.10 0.96 3.28 0.98 3.59 1.01
Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor) - Outdoor air : 85%RH. However, the condition on nominal capacity
is 7°CDB/6°CWB

84 2009 Product Data


8. Capacity tables Heating

AS-W126BMS0, AS-H12GB1U0
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 2.63 3.26 2.77 3.18 3.00 3.33 3.21 3.58 3.56 3.83 3.76 3.98 4.08 4.24
18.0 2.61 3.31 2.76 3.26 3.00 3.43 3.20 3.68 3.53 3.92 3.71 4.06 4.07 4.29
20.0 2.59 3.37 2.76 3.35 3.01 3.52 3.20 3.78 3.50 4.00 3.69 4.12 4.07 4.32
21.0 2.58 3.40 2.76 3.39 3.01 3.57 3.19 3.82 3.48 4.04 3.69 4.15 4.05 4.32
22.0 2.58 3.44 2.76 3.44 3.00 3.62 3.18 3.87 3.45 4.07 3.68 4.17 4.01 4.32
24.0 2.55 3.52 2.74 3.54 2.97 3.73 3.15 3.97 3.43 4.14 3.62 4.21 3.97 4.36

AS-W126ADR0, AS-W126E1G0, AS-W126E*H2


Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 3.44 1.03 3.62 1.00 3.92 1.05 4.19 1.13 4.65 1.21 4.91 1.25 5.33 1.34
18.0 3.40 1.04 3.61 1.03 3.92 1.08 4.18 1.16 4.62 1.23 4.85 1.28 5.31 1.35
20.0 3.38 1.06 3.61 1.05 3.93 1.11 4.17 1.19 4.57 1.26 4.82 1.30 5.32 1.36
21.0 3.37 1.07 3.61 1.07 3.93 1.13 4.16 1.20 4.54 1.27 4.82 1.31 5.29 1.36
22.0 3.36 1.08 3.61 1.08 3.92 1.14 4.15 1.22 4.51 1.28 4.81 1.31 5.24 1.36
24.0 3.32 1.11 3.57 1.11 3.88 1.17 4.12 1.25 4.47 1.30 4.73 1.33 5.18 1.37

AS-W126F1G2, AS-W126F*G2
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 3.16 0.95 3.32 0.92 3.60 0.97 3.85 1.04 4.27 1.11 4.51 1.16 4.90 1.23
18.0 3.13 0.96 3.32 0.95 3.61 0.99 3.84 1.07 4.24 1.14 4.46 1.18 4.88 1.24
20.0 3.10 0.98 3.32 0.97 3.61 1.02 3.83 1.10 4.20 1.16 4.43 1.20 4.89 1.25
21.0 3.10 0.99 3.32 0.98 3.61 1.04 3.83 1.11 4.17 1.17 4.43 1.20 4.86 1.25
22.0 3.09 1.00 3.32 1.00 3.61 1.05 3.82 1.12 4.14 1.18 4.42 1.21 4.82 1.25
24.0 3.05 1.02 3.29 1.03 3.56 1.08 3.79 1.15 4.11 1.20 4.35 1.22 4.76 1.26

AS-W1264GG1
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 3.01 0.95 3.16 0.93 3.43 0.97 3.66 1.05 4.07 1.12 4.30 1.17 4.66 1.24
18.0 2.98 0.97 3.16 0.95 3.43 1.00 3.66 1.08 4.04 1.15 4.24 1.19 4.65 1.25
20.0 2.96 0.99 3.16 0.98 3.44 1.03 3.65 1.10 4.00 1.17 4.21 1.21 4.66 1.26
21.0 2.95 1.00 3.16 0.99 3.44 1.05 3.64 1.12 3.97 1.18 4.21 1.21 4.63 1.26
22.0 2.94 1.01 3.16 1.01 3.43 1.06 3.63 1.13 3.95 1.19 4.21 1.22 4.59 1.26
24.0 2.91 1.03 3.13 1.03 3.39 1.09 3.61 1.16 3.91 1.21 4.14 1.23 4.53 1.27

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor) - Outdoor air : 85%RH. However, the condition on nominal capacity
is 7°CDB/6°CWB

2009 Product Data 85


8. Capacity tables Heating

AS-W1868*H1
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 4.56 1.44 4.80 1.41 5.20 1.47 5.56 1.58 6.17 1.69 6.52 1.76 7.08 1.88
18.0 4.52 1.46 4.79 1.44 5.21 1.52 5.56 1.63 6.13 1.73 6.44 1.80 7.05 1.90
20.0 4.49 1.49 4.79 1.48 5.21 1.56 5.54 1.67 6.07 1.77 6.40 1.82 7.07 1.91
21.0 4.48 1.51 4.79 1.50 5.21 1.58 5.53 1.69 6.03 1.79 6.40 1.84 7.02 1.91
22.0 4.47 1.52 4.79 1.52 5.21 1.60 5.51 1.71 5.99 1.80 6.39 1.85 6.96 1.91
24.0 4.42 1.56 4.75 1.57 5.15 1.65 5.47 1.75 5.94 1.83 6.28 1.86 6.88 1.93

AS-W1865DH2
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 4.56 1.44 4.80 1.41 5.20 1.47 5.56 1.58 6.17 1.69 6.52 1.76 7.08 1.88
18.0 4.52 1.46 4.79 1.44 5.21 1.52 5.56 1.63 6.13 1.73 6.44 1.80 7.05 1.90
20.0 4.49 1.49 4.79 1.48 5.21 1.56 5.54 1.67 6.07 1.77 6.40 1.82 7.07 1.91
21.0 4.48 1.51 4.79 1.50 5.21 1.58 5.53 1.69 6.03 1.79 6.40 1.84 7.02 1.91
22.0 4.47 1.52 4.79 1.52 5.21 1.60 5.51 1.71 5.99 1.80 6.39 1.85 6.96 1.91
24.0 4.42 1.56 4.75 1.57 5.15 1.65 5.47 1.75 5.94 1.83 6.28 1.86 6.88 1.93

AS-W1865GG1
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 4.36 1.47 4.59 1.43 4.97 1.50 5.31 1.61 5.90 1.72 6.23 1.79 6.76 1.91
18.0 4.32 1.49 4.58 1.47 4.98 1.54 5.31 1.66 5.86 1.76 6.15 1.83 6.74 1.93
20.0 4.29 1.52 4.58 1.51 4.98 1.59 5.30 1.70 5.80 1.80 6.11 1.85 6.75 1.94
21.0 4.28 1.53 4.58 1.53 4.98 1.61 5.28 1.72 5.76 1.82 6.11 1.87 6.71 1.95
22.0 4.27 1.55 4.58 1.55 4.98 1.63 5.27 1.74 5.72 1.83 6.10 1.88 6.65 1.95
24.0 4.22 1.59 4.54 1.59 4.92 1.68 5.23 1.78 5.68 1.86 6.00 1.89 6.58 1.96

AS-W2465GG1
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 5.29 6.59 5.56 6.43 6.03 6.73 6.44 7.23 7.15 7.73 7.55 8.05 8.19 8.57
18.0 5.23 6.69 5.55 6.59 6.04 6.92 6.43 7.43 7.10 7.92 7.46 8.20 8.17 8.67
20.0 5.20 6.81 5.55 6.76 6.04 7.12 6.42 7.63 7.03 8.08 7.41 8.33 8.18 8.72
21.0 5.18 6.87 5.55 6.85 6.04 7.22 6.40 7.73 6.99 8.16 7.41 8.38 8.13 8.73
22.0 5.18 6.95 5.55 6.94 6.04 7.32 6.39 7.82 6.93 8.23 7.40 8.43 8.06 8.73
24.0 5.11 7.12 5.50 7.14 5.96 7.53 6.34 8.01 6.88 8.36 7.27 8.50 7.97 8.80

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor) - Outdoor air : 85%RH. However, the condition on nominal capacity
is 7°CDB/6°CWB

86 2009 Product Data


8. Capacity tables Heating

AS-W2465DH2
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 6.08 2.35 6.39 2.29 6.93 2.40 7.40 2.58 8.21 2.76 8.68 2.87 9.42 3.06
18.0 6.01 2.38 6.38 2.35 6.94 2.47 7.40 2.65 8.16 2.82 8.57 2.92 9.39 3.09
20.0 5.97 2.43 6.38 2.41 6.94 2.54 7.38 2.72 8.08 2.88 8.51 2.97 9.41 3.11
21.0 5.96 2.45 6.38 2.44 6.94 2.57 7.36 2.75 8.03 2.91 8.51 2.99 9.34 3.11
22.0 5.95 2.48 6.38 2.48 6.94 2.61 7.34 2.79 7.97 2.93 8.50 3.00 9.27 3.11
24.0 5.88 2.54 6.32 2.55 6.85 2.68 7.28 2.86 7.91 2.98 8.36 3.03 9.16 3.14

AS-W2468*H1
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 6.35 2.36 6.68 2.31 7.24 2.41 7.73 2.59 8.58 2.78 9.07 2.89 9.84 3.08
18.0 6.28 2.40 6.67 2.36 7.25 2.48 7.73 2.67 8.52 2.84 8.95 2.94 9.81 3.11
20.0 6.24 2.44 6.66 2.43 7.25 2.55 7.71 2.74 8.44 2.90 8.89 2.99 9.83 3.13
21.0 6.22 2.47 6.66 2.46 7.25 2.59 7.69 2.77 8.39 2.93 8.89 3.01 9.76 3.13
22.0 6.21 2.49 6.67 2.49 7.25 2.63 7.67 2.81 8.33 2.95 8.88 3.02 9.68 3.13
24.0 6.14 2.55 6.60 2.56 7.16 2.70 7.61 2.87 8.26 3.00 8.73 3.05 9.57 3.16

AS-W306DGM0
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 7.22 2.65 7.59 2.59 8.23 2.71 8.79 2.91 9.76 3.11 10.3 3.24 11.2 3.45
18.0 7.15 2.69 7.58 2.65 8.24 2.78 8.79 2.99 9.69 3.18 10.2 3.30 11.2 3.49
20.0 7.10 2.74 7.58 2.72 8.25 2.86 8.76 3.07 9.60 3.25 10.1 3.35 11.2 3.51
21.0 7.08 2.77 7.58 2.75 8.25 2.90 8.75 3.11 9.54 3.28 10.1 3.37 11.1 3.51
22.0 7.07 2.80 7.58 2.79 8.24 2.94 8.72 3.15 9.47 3.31 10.1 3.39 11.0 3.51
24.0 6.98 2.86 7.51 2.87 8.14 3.03 8.65 3.22 9.39 3.36 9.93 3.42 10.9 3.54

AS-W366DGM0
Indoor Air Outdoor Air Temperature : °CWB
Temperature (°C) -15 -10 -5 0 6 10 15
°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
16.0 7.82 2.81 8.23 2.74 8.92 2.87 9.52 3.09 10.6 3.30 11.2 3.44 12.1 3.66
18.0 7.74 2.85 8.21 2.81 8.93 2.96 9.52 3.17 10.5 3.38 11.0 3.50 12.1 3.70
20.0 7.69 2.91 8.21 2.89 8.93 3.04 9.50 3.26 10.4 3.45 11.0 3.56 12.1 3.72
21.0 7.67 2.94 8.21 2.92 8.93 3.08 9.47 3.30 10.3 3.48 11.0 3.58 12.0 3.73
22.0 7.66 2.97 8.21 2.96 8.93 3.13 9.45 3.34 10.3 3.51 10.9 3.60 12.0 3.73
24.0 7.56 3.04 8.13 3.05 8.82 3.21 9.37 3.42 10.2 3.57 10.8 3.63 11.8 3.76

Symbol Notes
AFR : Air flow rate [m3/min] 1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry bulb temperature [°C] 2. Indicates nominal maximum capacity.
WB : Wet bulb temperature [°C] 3. Direct interpolation is permissible. Do not extrapolate
TC : Total capacity [kW] 4. Capacities are based on the following conditions:
SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5m
PI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor) - Outdoor air : 85%RH. However, the condition on nominal capacity
is 7°CDB/6°CWB

2009 Product Data 87


9. Capacity coefficient factor

Cooling
100

Capacity(%) 24k 30k/36k


9k/12k/18k

90

80

70
7.5 15 30 50
Total Pipe Length(m)

Heating
100
24k 30k/36k
9k/12k/18k
Capacity(%)

90

80

70
7.5 15 30 50
Total Pipe Length(m)

88 2009 Product Data


9. Capacity coefficient factor

Maestro / Libero

Cooling
110
105
Capacity(%)

100
95 9k/12k
90
85
80

75
70
2 7,5 20
Total Pipe Length(m)

Heating
110
105
Capacity(%)

100
9k/12k
95

90
85
80
75
70 2 7,5 20
Total Pipe Length(m)

2009 Product Data 89


9. Capacity coefficient factor

Max. Pipe Max. Elevation Additional


Model No.
Length(m) (m) Refrigerant[g/m(oz/ft)]
AS-W096BMS0 20 10 20(0.22)
AS-H09GB1U0 20 10 20(0.22)
AS-W096ADR0 15 7 20(0.22)
AS-W0964GG1 15 7 20(0.22)
AS-W096E*H2 15 7 20(0.22)
AS-W096E1G0 15 7 20(0.22)
AS-W096F*G2 15 7 20(0.22)
AS-W096F1G2 15 7 20(0.22)
AS-W126BMS0 20 10 20(0.22)
AS-H12GB1U0 20 10 20(0.22)
AS-W126ADR0 15 7 20(0.22)
AS-W1264GG1 15 7 20(0.22)
AS-W126E*H2 15 7 20(0.22)
AS-W126E1G0 15 7 20(0.22)
AS-W126F*G2 15 7 20(0.22)
AS-W126F1G2 15 7 20(0.22)
AS-W1865DH2 15 7 20(0.22)
AS-W1865GG1 15 7 20(0.22)
AS-W1868*H1 15 7 20(0.22)
AS-W2465DH2 30 15 30(0.32)
AS-W2465GG1 30 15 30(0.32)
AS-W2468*H1 30 15 30(0.32)
AS-W306DGM0 50 30 30(0.32)
AS-W366DGM0 50 30 35(0.37)
Indoor unit
Outdoor unit
Outdoor unit CAUTION:
• Capacity is based on
standard length and
A A
A Oil trap maximum allowance
B Outdoor unit Indoor unit Indoor unit
length is on the basis
B
B of reliability.
• Oil trap should be
installed every 5~7
If piping length is more than 5m meters.
Notes
❈ Equivalent pipe length = actual pipe length + number of band x 0.3
❈ Additional Refrigerant Charge
Example: For Model No. AS-W126ADR0 having 15m pipe length, additional refrigerant to be charged is (15-7) x 20
= 160g
* Refer to the specification for the maximum pipe length of each model.
* 18k S5/S8 Chassis total piping length is 15m.
* Maestro & Libero
Additional refrigerant must be charged after 12.5 m (there is no need to charge till 12.5 m based on reliability)

90 2009 Product Data


10. Operation range

Cooling Heating
46
Operative
43

Outdoor
Unit
[°C DB]
24
Continuous

Warming up
Operation
operation
Outdoor Continuous
Unit operation
[°C DB]

-10
Operative
-10 -15

18 32 16 30
Indoor Unit [°C DB] Indoor Unit [°C DB]

Operative: Intermittent operation due to the operational


conditions (indoor/outdoor temperature, humidity,
load etc.) can cause the heating capacity to
decrease.

2009 Product Data 91


11. Air flow and temperature distributions(reference data)

Super Inverter Maestro / Libero 9kBtu/h


Cooling Heating
Discharge angle:45° Discharge angle:50°
AirVelocity [m/s] AirVelocity [m/s]
2.7m 2.7m

2m 2m
1.2

1.0 1.0
1m 1m
0.75
0.75
0.5 0.5
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

Temperature [°C] Temperature [°C]


2.7m 2.7m

2m 2m

23 1m 1m
29
28 30
25 24
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

Super Inverter Maestro / Libero 12kBtu/h


Cooling Heating
Discharge angle:45° Discharge angle:50°
AirVelocity [m/s] AirVelocity [m/s]
2.7m 2.7m

2m 2m
1.5
1.5
1.25
1m 1.25
1m
1.0 1.0
0.75 0.5
0.5 0.75
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

Temperature [°C] Temperature [°C]


2.7m 2.7m

2m 2m

1m 1m
23
29
25 24 30
28
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

92 2009 Product Data


11. Air flow and temperature distributions(reference data)

General Wall Mouted 9kBtu/h


Cooling Heating
Discharge angle:45° Discharge angle:50°
Air velocity [m/s] Air velocity [m/s]
2.7m 2.7m

2m 2m
1.2
1.0 1.0
1m 1m
0.75
0.75
0.5 0.5
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

Temperature [˚C] Temperature [˚C]


2.7m 2.7m

2m 2m

23 1m 1m
28

29 30
25 24
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

ART COOL Deluxe 9kBtu/h


Cooling Heating
Discharge angle:45° Discharge angle:50°
Air velocity [m/s] Air velocity [m/s]
2.7m 2.7m

2m 2m
1.2
1.0 1.0
1m 1m
0.75
0.75
0.5 0.5
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

Temperature [˚C] Temperature [˚C]


2.7m 2.7m

2m 2m

23 1m 1m
28

29 30
25 24
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

2009 Product Data 93


11. Air flow and temperature distributions(reference data)

ART COOL Deluxe 12kBtu/h


Cooling Heating
Discharge angle:45° Discharge angle:50°
Air velocity [m/s] Air velocity [m/s]
2.7m 2.7m

2m 2m

1.2
1.0 1m 1.0 1m
0.75
0.75 0.5
0.5
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

Temperature [˚C] Temperature [˚C]


2.7m 2.7m

2m 2m

1m 30 1m
23
29
25 24 28
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

ART COOL Standard 12kBtu/h


Cooling Heating
Discharge angle:45° Discharge angle:45°
Air velocity [m/s] Air velocity [m/s]
2.7m 2.7m

2m 2m

1.2
1.0 1m 1.0 1m
0.75
0.75 0.5
0.5
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

Temperature [˚C] Temperature [˚C]


2.7m 2.7m

2m 2m

23 1m 30 1m

29
25 24 28
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

94 2009 Product Data


11. Air flow and temperature distributions(reference data)

General Wall Mouted 12kBtu/h


Cooling Heating
Discharge angle:45° Discharge angle:50°
Air velocity [m/s] Air velocity [m/s]
2.7m 2.7m

2m 2m

1.5 1.5
1.25 1.25
1m 1m

1.0 1.0
0.75 0.5 0.75
0.5
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

Temperature [˚C] Temperature [˚C]


2.7m 2.7m

2m 2m

1m 1m
23 30

29
25 24 28
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

General Wall Mouted 18kBtu/h


Cooling Heating
Discharge angle:45° Discharge angle:50°
Air velocity [m/s] Air velocity [m/s]
2.7m 2.7m

2m 2m

1.5 1.5
1m 1m
1.25 1.25
0.5 0.75 1.0 0.5 0.75 1.0
8m 7m 6m 5m 4m 3m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m

Temperature [˚C] Temperature [˚C]


2.7m 2.7m

2m 2m

23 31
1m 1m

24 29 30
25 28
8m 7m 6m 5m 4m 3m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m

2009 Product Data 95


12. Sound levels

12.1 Indoor Units


Overall
Notes:
- Sound measured at 1m away from the center of the unit.
- Data is valid at free field condition.
- Data is valid at nominal operation condition.
1m - Reference accoustic pressure 0dB=20μPa.
- Sound level will vary depending on a range of factors such as
0.8m the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
Microphone - The operating conditions are assumed to be standard.
Sound Levels [dB(A)] Sound Levels [dB(A)]
Model Model
H M L H M L
AS-W096BMS0 33 23 19 AS-W126F*G2 39 32 25
AS-H09GB1U0 33 23 19 AS-W126F1G2 39 32 25
AS-W096ADR0 31 27 22 AS-W1865DH2 42 39 36
AS-W0964GG1 32 28 25 AS-W1865GG1 43 40 37
AS-W096E*H2 31 27 22 AS-W1868*H1 42 39 36
AS-W096E1G0 31 27 22 AS-W2465DH2 44 41 37
AS-W096F*G2 35 29 25 AS-W2468*H1 43 40 36
AS-W096F1G2 35 29 25 AS-W2465GG1 44 41 37
AS-W126BMS0 33 23 19 AS-W306DGM0 46 43 39
AS-H12GB1U0 33 23 19 AS-W366DGM0 47 44 41
AS-W126ADR0 36 27 22
AS-W1264GG1 38 30 25
AS-W126E*H2 37 27 22
AS-W126E1G0 37 27 22

Sound Pressure Level


AS-W096BMS0 AS-W096ADR0 AS-W0964GG1
AS-H09GB1U0
80 80 80

S/High High High


High Middle Middle
Low Low
70 70 70 Low
Octave Band Sound Pressure Level (dB re 20μPa )

NC-65 NC-65 NC- 65


60 60 60
Sound Pressure Level (dB re 20 Pa )
Sound Pressure Level (dB re 20μPa )

NC-60 NC-60 NC- 60

NC-55 NC-55 NC- 55


50 50 50
NC-50 NC-50 NC- 50

NC-45 NC-45
NC- 45
40 40 40
NC-40 NC-40
NC- 40

NC-35 NC-35
NC- 35
30 30 30
NC-30 NC-30
NC- 30

20 NC-25 20 NC-25
20 NC- 25

Approximate Approximate
NC-20 Hearing NC-20 Appr oximate
Hearing NC- 20
Threshold Hear ing
Threshold
NC-15 NC-15 Threshold
10 10 NC- 15
10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

AS-W096E1G0 AS-W096F1G2 AS-W126BMS0


AS-W096E*H2 AS-W096F*G2 AS-W126B1U0
80 80 80

High High S/High


Middle Middle High
70 Low 70 Low 70 Low
Octave Band Sound Pressure Level (dB re 20μPa )

NC-65 NC-65 NC-65


60 60 60
Sound Pressure Level (dB re 20μPa )
Sound Pressure Level (dB re 20μPa )

NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50

NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40

NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30

NC-30 NC-30 NC-30

20 NC-25 20 NC-25 20 NC-25

Appr oximate Approximate Approximate


NC-20 NC-20 NC-20
Hearing Hearing Hearing
Thr eshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz)

96 2009 Product Data


12. Sound levels

AS-W126E1G0 AS-W126F1G2
AS-W126ADR0 AS-W126E*H2 AS-W126F*G2
80 80 80

High High High


Middle Middle Middle
70 Low 70 Low 70 Low

NC-65 NC-65 NC-65


60 60 60

Sound Pressure Level (dB re 20μPa )

Sound Pressure Level (dB re 20μPa )


Sound Pressure Level (dB re 20μPa )

NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50

NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40

NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30

NC-30 NC-30
NC-30

20 NC-25 20 NC-25
20 NC-25

Approximate Approximate
Approximate NC-20 NC-20
NC-20
Hearing Hearing
Hearing
Threshold Threshold
Threshold NC-15 NC-15
NC-15 10 10
10 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

AS-W1264GG1 AS-W1865DH2 AS-W1865GG1


AS-W1868*H1
80 80 80

High High High


Middle Middle Middle
70 Low 70 Low 70 Low

NC-65
60 NC-65 NC- 65
Sound Pressure Level (dB re 20μPa )

60 60
Sound Pressure Level (dB re 20μPa )

Sound Pressure Level (dB re 20μPa )


NC-60
NC-60 NC- 60

NC-55
50 NC-55 NC- 55
50 50
NC-50
NC-50 NC- 50
NC-45
40 NC-45 NC- 45
40 40
NC-40
NC-40 NC- 40
NC-35
30
NC-35 NC- 35
30 30
NC-30
NC-30 NC- 30

20 NC-25

Approximate 20 NC-25 20 NC- 25


NC-20
Hearing Approximate Appr oximate
Threshold Hearing NC-20 NC- 20
NC-15 Hear ing
10 Threshold
63 125 250 500 1000 2000 4000 8000 NC-15
Threshold NC- 15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

AS-W2465GG1
AS-W2465DH2 AS-W2468*H1 AS-W306DGM0
80 80

High High
Middle Middle
70 Low 70 Low

NC-65 NC-65
60 60
Sound Pressure Level (dB re 20μPa )

Sound Pressure Level (dB re 20μPa )


Sound Pressure Level (dB re 20μPa )

NC-60 NC-60

NC-55 NC-55
50 50

NC-50 NC-50

NC-45 NC-45
40 40

NC-40 NC-40

NC-35 NC-35
30 30

NC-30 NC-30

20 NC-25 20 NC-25

Approximate Approximate
NC-20 Hearing NC-20
Hearing
Threshold Threshold
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz)

2009 Product Data 97


12. Sound levels

AS-W366DGM0
Sound Pressure Level (dB re 20μPa )

Octave Band Center Frequency (Hz)

98 2009 Product Data


12. Sound levels

12.2 Outdoor Units


Overall
Notes:
- Sound measured at 1m away from the center of the unit.
- Data is valid at free field condition.
Center of
Outdoor Unit - Data is valid at nominal operation condition.
- Reference accoustic pressure 0dB=20μPa.
1m - Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
1m
- The operating conditions are assumed to be standard.
Sound Levels [dB(A)] Sound Levels [dB(A)]
Model Model
H H
AS-W096BMS0 45 AS-W126F*G2 48
AS-H09GB1U0 45 AS-W126F1G2 48
AS-W096ADR0 45 AS-W1865DH2 55
AS-W0964GG1 45 AS-W1865GG1 56
AS-W096E*H2 45 AS-W1868*H1 54
AS-W096E1G0 45 AS-W2465GG1 56
AS-W096F*G2 48 AS-W2465DH2 56
AS-W096F1G2 48 AS-W2468*H1 55
AS-W126BMS0 45 AS-W306DGM0 54
AS-H12GB1U0 45 AS-W366DGM0 58
AS-W126ADR0 45
AS-W1264GG1 45
AS-W126E*H2 45
AS-W126E1G0 45

Sound Pressure Level


AS-W096BMS0 AS-W096E1G0 AS-W096F1G2
AS-H09GB1U0 AS-W096E*H2 AS-W096F*G2
AS-W096ADR0
80 80 80

70 70 70

NC-65 NC-65 NC-65


60 60 60
Sound Pressure Level (dB re 20μPa )

Sound Pressure Level (dB re 20μPa )

Sound Pressure Level (dB re 20μPa )

NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50

NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30
NC-30

20 NC-25
20 NC-25 20 NC-25
Approximate
Approximate NC-20 Approximate
NC-20 Hearing NC-20
Hearing Hearing
Threshold
Threshold
NC-15 NC-15 Threshold NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

AS-W0964GG1 AS-W126BMS0 AS-W126E1G0


AS-H12GB1U0 AS-W126E*H2
AS-W126ADR0
80 80 80

70 70 70

NC-65 NC-65 NC-65


60 60 60
Sound Pressure Level (dB re 20μPa )

Sound Pressure Level (dB re 20μPa )

Sound Pressure Level (dB re 20μPa )

NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50

NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40

NC-40 NC-40 NC-40

NC-35 NC-35
NC-35
30 30 30

NC-30 NC-30 NC-30

20 NC-25 20 NC-25
20 NC-25

Approximate Approximate Approximate


NC-20 NC-20 NC-20
Hearing Hearing
Hearing
Threshold Threshold
Threshold NC-15 NC-15
10 NC-15 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

2009 Product Data 99


12. Sound levels

AS-W126F1G2
AS-W126F*G2 AS-W1264GG1 AS-W1868*H1
80 80 80

70 70 70

NC-65 NC-65
NC-65
60 60 60
Sound Pressure Level (dB re 20μPa )

Sound Pressure Level (dB re 20μPa )


NC-60 NC-60

Sound Pressure Level (dB re 20μPa )


NC-60

NC-55 NC-55
50 NC-55
50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

20 NC-25 20 NC-25 NC-25


20
Approximate NC-20 Approximate Approximate
NC-20
Hearing Hearing Hearing
NC-20
Threshold NC-15 Threshold Threshold
10 NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz)

AS-W2465GG1
AS-W1865DH2 AS-W1865GG1 AS-W2465DH2
80 80 80

70 70 70

NC-65 NC-65 NC-65


60 60 60

Sound Pressure Level (dB re 20μPa )


Sound Pressure Level (dB re 20μPa )

Sound Pressure Level (dB re 20μPa )

NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50

NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40

NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30
30 30

NC-30 NC-30
NC-30

NC-25 NC-25 20 NC-25


20 20

Approximate Approximate
Approximate NC-20 Hearing NC-20
NC-20 Hearing
Hearing Threshold
Threshold
Threshold NC-15
NC-15 NC-15 10
10 10
63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

AS-W2468*H1 AS-W306DGM0 AS-W366DGM0


80

70

NC-65
60
Sound Pressure Level (dB re 20μPa )

Sound Pressure Level (dB re 20μPa )

NC-60
Sound Pressure Level (dB re 20μPa )

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

20 NC-25

Approximate
NC-20
Hearing
Threshold NC-15
10
63 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz)

100 2009 Product Data


13. Remote controller

Wireless Remote Controller

The controls will look like the following. ON/OFF BUTTON


Used to turn off/on the unit.
Signal transmitter
OPERATION MODE SELECTION BUTTON
Used to select the operation mode.

ROOM TEMPERATURE SETTING BUTTONS


Used to select the room temperature.

INDOOR FAN SPEED SELECTION BUTTON


Used to select fan speed in six steps low, medium-low,
medium, medium-high, high and natural wind.

HORIZONTAL VANE CONTROL BUTTON


Used to set the desired vertical airflow direction.

(Optional1) VERTICAL LOUVER CONTROL BUTTON(Optional)


Used to set the desired horizontal airflow direction.

AUTO CLEAN BUTTON


(Optional2) Used to set auto clean.
(Optional3)
ENERGY SAVING COOLING BUTTON
Used to save Energy.

ROOM TEMPERATURE CHECKING BUTTON


Used to check the room temperature.

TIMER BUTTON(before adjusting)


Used to set the current time and the time of starting / stopping.
Operation Mode
Cooling Operation TIME ADJUSTING BUTTONS
Used to adjust the time.
Auto Operation or Auto Changeover
TIMER SET/CLEAR BUTTON(after adjusting)
Used to set and to cancel the timer operation.
Healthy Dehumidification Operation

RESET BUTTON
Heating Operation (Only heat pump) Used prior to resetting time.

Air Circulation PLASMA BUTTON(Optional)


Used to start or stop the plasma-purification.

LED LUMINOSITY BUTTON(Optional)


Used to adjust LED luminosity.

2009 Product Data 101


13. Remote controller

The controls will look like the following.

Signal transmitter
Premium type :
- Optional1

ECO EYE BUTTON


Used to set and to cancel the timer operation.

- Optional2
JET COOL / MOISTURE COOLING BUTTON
Used to start or stop the speed cooling and
Moisture Cooling. The Jet Cool operates fan
in super high speed in cooling mode.

- Optional3
(Optional1)
SLEEP MODE AUTO BUTTON
Used to set sleep mode auto operation.

(Optional2)
(Optional3) Rational type :
- Optional1

SLEEP MODE AUTO BUTTON


Used to set sleep mode auto operation.

- Optional2
JET COOL BUTTON
Used to start or stop the speed cooling.
Operation Mode
The Jet Cool operates fan in super high speed
in cooling mode.
Cooling Operation

Auto Operation or Auto Changeover

Healthy Dehumidification Operation

Heating Operation (Only heat pump)

Air Circulation

102 2009 Product Data


13. Remote controller

Wireless Remote Controller


The controls will look like the following. 1. START/STOP BUTTON
Used to turn off/on the unit.
Signal transmitter 2. OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
3. ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
4. INDOOR FAN SPEED SELECTOR BUTTON
Used to select fan speed in four steps
low, medium, high and CHAOS.
5. JET COOL BUTTON
Used to start or stop the speed cooling.
(It operates fan in super high speed in cooling mode)
5 1 6. CHAOS SWING BUTTON
6 Used to stop or start louver movement and set the
desired up/down airflow direction.
3 7. ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping
4 operation.
2 10 8. TIME SETTING BUTTONS
7 9 Used to adjust the time.
12 9. TIMER SET/CANCEL BUTTON
11
17 Used to set and to cancel the timer operation.
8 19
10. SLEEP MODE AUTO BUTTON
13 18
Used to set sleep mode auto operation.
14
15 11. AIR CIRCULATION BUTTON(OPTIONAL)
16
Used to circulate the room air without cooling or heating.
ENERGY-SAVING COOLING MODE BUTTON
(OPTIONAL) For inverter type models
Flip-up door 12. ROOM TEMPERATURE CHECKING BUTTON
(opened) Used to check the room temperature.
13. PLASMA BUTTON(OPTIONAL)
Operation Mode Used to start or stop the plasma-purification function.
14. HORIZONTAL AIRFLOW DIRECTION CONTROL
Cooling Operation BUTTON (OPTIONAL)
Used to set the desired horizontal airflow direction.
15. RESET BUTTON
Auto Operation or Auto Changeover
Used prior to resetting time.
16. 2nd F BUTTON
Healthy Dehumidification Operation Used prior to using modes printed in blue at the
bottom of buttons.
Heating Operation 17. AUTO CLEAN BUTTON(OPTIONAL)
Used to set auto clean mode.
In some models this button has a 2nd function of LED
• Cooling Model( ), Heat Pump Model( )
luminosity control.
18. HEATER BUTTON(OPTIONAL)
(Not available in all models)
19. LCD LUMINOSITY BUTTON(OPTIONAL)
Used to adjust LCD luminosity.
NOTE
To use the functions printed in blue at the bottom of the buttons press 2nd F button first and then the required function
button. Pressing the 2nd F button activates the blue printed function of the respective button. To cancel the function
press the 2nd F button again else it will automatically cancel if remains idle after 10 seconds.

2009 Product Data 103


14. Installation

Installation Map

Installation plate
Sleeve
Bushing-Sleeve
Putty(Gum Type Sealant)
Bend the pipe as closely
on the wall as possible,
but be careful that it
doesn't break.

Vinyl tape (Wide)


• Apply after carrying out a
drainage test.
• To carry out the drainage
test, remove the air filters
Saddle and pour water into the heat
exchanger.

Gas side piping (Optional Parts)


Liquid side piping (Optional Parts)
Additional drain pipe

Vinyl tape (Narrow)


Drain Hose
Connecting cable
(Optional Parts)

- The feature can be changed according a type of model.

NOTICE
You should purchase the installation parts.

104 2009 Product Data


14. Installation

Select the best Location


Indoor unit
1. Do not have any heat or steam near the unit. More than
2. Select a place where there are no obstacles in front 100 More than 200
of the unit.
3. Make sure that condensation drainage can be
conveniently routed away.
More than
4. Do not install near a doorway. 100
5. Ensure that the interval between a wall and the left More than 2300
(or right) of the unit is more than 100mm. The unit
should be installed as high as possible on the wall, (Unit : mm)
allowing a minimum of 200mm from ceiling.
6. Use a metal detector to locate studs to prevent
unnecessary damage to the wall.

Install the indoor unit on the wall where the height from the floor is more than 2.3 meters.

Outdoor unit
1. If an awning is built over the unit to prevent direct
sunlight or rain exposure, make sure that heat
radiation from the condenser is not restricted. More than 600mm
2. Ensure that the space around the back and sides is
more than 300mm. The front of the unit should have
More than 300mm More than 300mm
more than 700mm of space.
3. Do not place animals and plants in the path of the
warm air.
More
4. Take the weight of the air conditioner into account More than 700mm than 600mm
and select a place where noise and vibration are
minimum.
5. Select a place where the warm air and noise from the
air conditioner do not disturb neighbors.

2009 Product Data 105


14. Installation

Fixing Installation Plate


The wall you select should be strong and solid enough
to prevent vibration
1. Mount the installation plate on the wall with Installation Plate

type "A" screws. If mounting the unit on a concrete


wall, use anchor bolts.
• Mount the installation plate horizontally by aligning the Type "A" Screws
centerline using Horizontal meter .

Chassis
Hook

2. Measure the wall and mark the centerline. It is also Place a level on raised tab
Unit Outline
important to use caution concerning the location of 442 442
the installation plate. Routing of the wiring to power
outlets is through the walls typically. Drilling the hole
through the wall for piping connections must be done Ø70
safely. Installation Plate
Ø70

Left rear piping Right rear piping

133 95

175 217

(Unit : mm)

Drill a Hole in the Wall


• Drill the piping hole with a ø70mm hole core drill. WALL
Drill the piping hole at either the right or the left with
Indoor Outdoor
the hole slightly slanted to the outdoor side.

(3/16"~5/16")
5-7mm

Flaring Work
Main cause for gas leakage is due to defect in flaring
work. Carry out correct flaring work in the following
procedure. Copper
pipe Slanted Uneven Rough
Cut the pipes and the cable. 90°

1. Use the piping kit accessory or the pipes purchased


locally.
2. Measure the distance between the indoor and the
outdoor unit.
3. Cut the pipes a little longer than measured distance.
4. Cut the cable 1.5m longer than the pipe length.

106 2009 Product Data


14. Installation

Burrs removal
Pipe
1. Completely remove all burrs from the cut cross Reamer
section of pipe/tube.
2. While removing burrs put the end of the copper
Point down
tube/pipe in a downward direction while removing
burrs location is also changed in order to avoid
dropping burrs into the tubing.

Putting nut on
• Remove flare nuts attached to indoor and outdoor unit, Flare nut
then put them on pipe/tube having completed burr
removal. Copper tube
(not possible to put them on after finishing flare work)

Flaring work
1. Firmly hold copper pipe in a bar in the dimension "A"
Handle
shown in the table below. Bar Bar
2. Carry out flaring work with the flaring tool. Yoke

Cone

Outside diameter A Copper pipe


mm inch mm Clamp handle
Ø6.35 1/4 1.1~1.3 Red arrow mark
Ø9.52 3/8 1.5~1.7
Ø12.7 1/2 1.6~1.8
Ø15.88 5/8 1.6~1.8
Ø19.05 3/4 1.9~2.1

Check Smooth all round


1. Compare the flared work with the figure by. Inside is shiny without scratches
2. If a flared section is defective, cut it off and do flaring
work again. = Improper flaring =

Inclined Surface Cracked Uneven


damaged thickness
Even length
all round

2009 Product Data 107


14. Installation

Connecting the Piping


1. Pull the screw cap at the bottom of the indoor unit
2. Remove the chassis cover from the unit by loosing 2
screws

Chassis cover

3. Pull back the tubing holder.


Indoor unit back side view Tubing holder

4. Remove pipe port cover and positioning the tubing

Right Left
Backwards
Downwards

108 2009 Product Data


14. Installation

Installation Information. For right piping. Follow the instruction below.

Good case
• Press on the tubing cover and unfold the tubing to downward slowly. And then bend to the left side slowly.

Bad case
• Following bending case from right to left directly may cause damage to the tubing.

2009 Product Data 109


14. Installation

Installation of Indoor Unit


1. Hook the indoor unit onto the upper portion of the
installation plate.( engage the three hooks at the top 1
of the indoor unit with the upper edge of the
installation plate) Ensure that the hooks are properly
seated on the installation plate by moving it left and
right 2 Installation plate

2. Unlock the tubing holder from the chassis and mount


between the chassis and installation plate in order to
separate the bottom side of the indoor unit from the
wall

Tubing Holder

Piping

1. Insert the connecting cable through the bottom side of indoor unit and connect the cable (You can see detail
contents in 'Connecting the cables' section)
<Left side piping> <Right side piping>

View View

Terminal block Terminal block


Connecting cable Connecting cable
Cable retainer Cable retainer

2. Secure the cable onto the control board with the cable retainer.

110 2009 Product Data


14. Installation

3. Tape the tubing pipe, drain hose and the connection cable. Be sure that the drain hose is located at the lowest
side of the bundle. Locating at the upper side can cause overflow from the drain pan through the inside of the
unit.

If the drain hose is routed inside the room insulate the hose with an insulation material* so that dripping from
sweating (condensation) will not damage furniture or floors.
* Foamed polyethylene or equivalent is recommended.
<Left side piping> <Right side piping>

Tape
Connecting
Tape
cable
Connecting
Drain hose
cable
Connecting pipe
Drain hose Drain hose
Connecting pipe

Connecting the installation pipe and drain


hose to the indoor unit.
1. Align the center of the pipes and sufficiently tighten
the flare nut by hand Indoor unit tubing Flare nut Pipes

2. Tighten the flare nut with a wrench


Outside diameter Torque Open-end wrench (fixed)

mm inch kgf.m Flare nut


Ø6.35 1/4 1.8~2.5
Wrench Connection pipe
Ø9.52 3/8 3.4~4.2
Ø12.7 1/2 5.5~6.5 Indoor unit tubing

Ø15.88 5/8 6.3~8.2


Ø19.05 3/4 9.9~12.1

3. When needed to extend the drain hose of indoor unit,


assembly the drain pipe as shown on the drawing Drain pipe

Indoor unit drain hose

Vinyl tape(narrow)
Adhesive

2009 Product Data 111


14. Installation

Wrap the insulation material around the connecting Insulation material


portion.
1. Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them
together with vinyl tape so that there may be no gap.

2. Wrap the area which accommodates the rear piping Connection pipe Indoor unit pipe
housing section with vinyl tape. Vinyl tape (wide) Wrap with vinyl tape
Connecting cable

Pipe
Vinyl tape(narrow)

3. Bundle the piping and drain hose together by


wrapping them with vinyl tape sufficient enough to Wrap with vinyl tape

cover where they fit into the rear piping housing Pipe
section.
Vinyl tape(wide)
Drain hose

Finishing the indoor unit installation


1. Mount the tubing holder in the original positon.
2. Ensure that the hooks are properly seated on the
installation plate by moving it left and right.
3. Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots (clicking sound). Type 'C' screw

4. Finish the assembly by screwing the unit to the


installation plate by using two pieces of type "C"
screws. And assemble a chassis cover.

Installation of filters
• Premium type
1. Pull out the [Allergy free filter + Triple Filter] from the
separately packed plastic bag.
2. Detach the two nitto tapes from the filter.
3. Insert the filter into the filter case. Allergy Free Filter + Triple Filter Plasma Filter
4. Detach two nitto tapes from the plasma filter.

• Rational type
1. Pull out the triple filter and allergy free filter from the
separately packed plastic bag.
2. Insert the triple filter into the left case and insert the
allergy free filter into the right case.
3. Detach two nitto tapes from the plasma filter.

Triple Filter Allergy Free Filter Plasma Filter

112 2009 Product Data


14. Installation

Outdoor
Align the center of the pipings and sufficiently tighten
the flare nut by hand.

Finally, tighten the flare nut with torque wrench until the
wrench clicks.
Outdoor unit
• When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on Liquid side piping
the wrench. (Smaller diameter)
Outside diameter Torque
mm inch kgf.m
Ø6.35 1/4 1.8~2.5
Ø9.52 3/8 3.4~4.2
Ø12.7 1/2 5.5~6.5 Torque wrench
Ø15.88 5/8 6.3~8.2 Gas side piping
Ø19.05 3/4 9.9~12.1 (Bigger diameter)

2009 Product Data 113


14. Installation

Connecting the Cables


Indoor
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually
according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No.
are the same as those of the indoor unit.)

• The circuit diagram is subject to change without notice.


• The earth wire should be longer than the common wires.
• When installing, refer to the circuit diagram on the front panel.
• Connect the wires firmly so that they may not be pulled out easily.
• Connect the wires according to color codes, referring to the wiring diagram.

Main power source

If a power plug is not used, provide a circuit


breaker between power source and the unit as
shown by. Air Circuit Breaker
Conditioner Use a circuit breake
or time delay fuse.

The power cord connected to the Indoor unit should be selected according to the following specifications(Type "B"
approved by HAR or SAA).

(mm2) ±5
45
±3
Grade 10
NORMAL CROSS
9k~12k 12k SU / 18k 18k S3 / 24k~36k
-SECTIONAL AREA
1.0 1.5 2.5
Cable Type(B) H05VV-F H05VV-F H05VV-F

The power connecting cable connecting the indoor and outdoor unit should be selected according to the following
specifications (Type "B" approved by HAR or SAA).

(mm2)
±5
45
Grade ±3
10
NORMAL CROSS
9k S4 / 12k S4 9k~18k 18k S3 / 24k 30k~36k
-SECTIONAL AREA
1.0 1.5 2.5 0.75
Cable Type(B) H07RN-F H07RN-F H07RN-F H07RN-F

114 2009 Product Data


14. Installation

Outdoor
1. Remove the control cover from the unit by loosening
Outdoor Unit
the screw.
Connect the wires to the terminals on the control
board individually. 1(L) 2(N) 3

2. Secure the cable onto the control board with the cord
clamp.
3. Refix the control cover to the original position with the
screw.
4. Use a recognized circuit breaker between the power Connecting cable

source and the unit.


A disconnecting device to adequately disconnect all Cover control
Cord clamp
supply lines must be fitted.

Grade
Circuit
9k~12k
Breaker 18k 24k 30k~36k
18k S5
(A)
15 20 30 25

According to the confirmation of the above conditions, prepare the wiring as follows.
1. Never fail to have an individual power circuit specifically for the air conditioner. As for the method of
wiring, be guided by the circuit diagram posted on the inside of control cover.
2. The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3. Specification of power source.
4. Confirm that electrical capacity is sufficient.
5. See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on
the name plate.
6. Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.
7. Always install an earth leakage circuit breaker in a wet or moist area.
8. The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal
function of the overload.
9. The means for disconnection from a power supply shall be incorporated in the fixed wiring and have
an air gap contact separation of at least 3mm in each active(phase) conductors.

2009 Product Data 115


14. Installation

Checking the Drainage


To check the drainage.
1. Pour a glass of water on the evaporator.
2. Ensure the water flows through the drain hose of the Connecting area
indoor unit without any leakage and goes out the drain hose

drain exit.
Leakage
checking

Drain pan

Drain
hose
Leakage
checking

Drain piping
1. The drain hose should point downward for easy drain
flow.
Downward slope

2. Do not make drain piping like the following.

Accumulated
Do not raise
drain water
Tip of drain hose Less than
Air
dipped in water 50mm gap

Water Water Water


Waving
leakage leakage leakage Ditch

116 2009 Product Data


14. Installation

Forming the Piping


Form the piping by wrapping the
connecting portion of the indoor unit with Pipe
insulation material and secure it with two Drain hose
Vinyl tape(narrow)
kinds of vinyl tapes.
• If you want to connect an additional drain hose, the
end of the drain outlet should be routed above the
ground. Secure the drain hose appropriately. Wrap with
vinyl tape(wide)

In cases where the outdoor unit is


installed below the indoor unit perform the
following.
1. Tape the piping, drain hose and connecting cable
from down to up.
2. Secure the tapped piping along the exterior wall
using saddle or equivalent.

In cases where the Outdoor unit is


installed above the Indoor unit perform the
following.
1. Tape the piping and connecting cable from down to
up.
2. Secure the taped piping along the exterior wall. Form
a trap to prevent water entering the room.
3. Fix the piping onto the wall by saddle or equivalent.

2009 Product Data 117


14. Installation

Air Purging
Air purging
The air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
1. Pressure in the system rises.
2. Operating current rises.
3. Cooling(or heating) efficiency drops.
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
5. Water may lead to corrosion of parts in the refrigeration system.
Therefore, after evacuating the system, take a leak test for the piping and tubing between the indoor and outdoor
unit.

Air purging with vacuum pump


1. Preparation
• Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected
and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on
the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
2. Leak test
• Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.

Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi"
knob of the manifold valve must always be kept close.
• Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the
gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.

To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its
bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
1. Do a leak test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves.
Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.

2. After the system is found to be free of leaks,


relieve the nitrogen pressure by loosening the Manifold valve
Indoor unit
charge hose connector at the nitrogen Pressure
cylinder. When the system pressure is gauge Lo Hi

reduced to normal, disconnect the hose from


the cylinder.
Charge hose

Nitrogen gas
cylinder(in vertical
standing position)

Outdoor unit

118 2009 Product Data


14. Installation

Soap water method


1. Remove the caps from the 2-way and 3-way valves. Gas side
2. Remove the service-port cap from the 3-way valve.
3. To open the 2-way valve turn the valve stem
counterclockwise approximately 90°, wait for about 2~3 sec, Liquid side
and close it.
4. Apply a soap water or a liquid neutral detergent on the Hexagonal
indoor unit connection or outdoor unit connections by a soft wrench
brush to check for leakage of the connecting points of the
piping.
5. If bubbles come out, the pipes have leakage
Evacuation 2-way valve
(Open) Cap
1. Connect the charge hose end described in the preceding 3-way valve
(Close)
steps to the vacuum pump to evacuate the tubing and
indoor unit.
Confirm the "Lo" knob of the manifold valve is open.
Then, run the vacuum pump.
The operation time for evacuation varies with tubing Indoor unit
length and capacity of the pump. The following table
shows the time required for evacuation.
Required time for evacuation when 30 gal/h vacuum
pump is used
If tubing length is less If tubing length is longer
than 10m (33 ft) than 10m (33 ft)
10 min. or more 15 min. or more

2. When the desired vacuum is reached, close the "Lo"


knob of the manifold valve and stop the vacuum pump.
Finishing the job
Outdoor unit
1. With a service valve wrench, turn the valve stem of liquid
side valve counter-clockwise to fully open the valve. Manifold valve
2. Turn the valve stem of gas side valve counter-clockwise
to fully open the valve. Pressure Lo Hi
3. Loosen the charge hose connected to the gas side gauge
service port slightly to release the pressure, then remove
the hose.
Open Close
4. Replace the flare nut and its bonnet on the gas side
service port and fasten the flare nut securely with an
adjustable wrench. This process is very important to
prevent leakage from the system.
5. Replace the valve caps at both gas and liquid side
service valves and fasten them tight.
This completes air purging with a vacuum pump.
Vacuum pump
The air conditioner is now ready to test run.

2009 Product Data 119


14. Installation

Test Running
1. Check that all tubing and wiring are properly connected.
2. Check that the gas and liquid side service valves are fully open.
Prepare remote controller
1. Remove the battery cover by pulling it according to
the arrow direction.
2. Insert new batteries making sure that the (+) and (–)
of battery are installed correctly.
3. Reattach the cover by pushing it back into position.

NOTICE
• Use 2 AAA(1.5volt) batteries. Do not use
rechargeable batteries.
• Remove the batteries from the remote controller if
the system is not used for a long time.

Settlement of outdoor unit


Bolt
1. Anchor the outdoor unit with a bolt and nut(ø10mm)
tightly and horizontally on a concrete or rigid mount.
2. When installing on the wall, roof or rooftop, anchor
the mounting base securely with a nail or wire
assuming the influence of wind and earthquake.
3. If the vibration of the unit is transmitted to the hose,
secure the unit with an anti-vibration rubber. Tubing connection

Evaluation of the performance


Operate the unit for 15~20 minutes, then check the Intake temperature
system refrigerant charge:
1. Measure the pressure of the gas side service valve.
Discharge air
2. Measure the temperature of the intake and discharge
of air.
3. Ensure the difference between the intake
temperature and the discharge is more than 8°C
4. For reference; the gas side pressure of optimum Discharge
temperature
condition is as below.(Cooling)
The air conditioner is now ready for use.
Refrigerant Outside ambient The pressure of the gas side
TEMP. service valve.
R410A 35°C (95°F) 8.5~9.5kg/cm2G(120~135 P.S.I.G.)

120 2009 Product Data


14. Installation

NOTICE
If the actual pressure is higher than shown, the system is most likely over-charged, and charge should be
removed. If the actual pressure are lower than shown, the system is most likely undercharged, and charge should
be added.

PUMP DOWN
This is performed when the unit is relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant into the outdoor unit without the loss of refrigerant.

Be sure to perform Pump Down procedure in the cooling mode.

Pump Down Procedure


1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air in the manifold hose using the refrigerant.
3. Close the liquid side service valve(all the way).
4. Turn on the unit's operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side
valve and then quickly turn off the unit. Now Pump Down procedure is completed, and all refrigerant is collected
into the outdoor unit.

2009 Product Data 121


14. Installation

14.1. Installation Guide at the Seaside

CAUTION
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion
on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunc-
tion or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it
needs additional anticorrosion treatment on the heat exchanger.

Selecting the location(Outdoor Unit)


1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.

Sea wind Sea wind

2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.

Windbreak • It should be strong enough like concrete to prevent


the sea wind from the sea.
• The height and width should be more than 150% of
the outdoor unit.
Sea wind • It should be keep more than 70 cm of space
between outdoor unit and the windbreak for easy
air flow.

3) Select a well-drained place.

1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water

122 2009 Product Data


P/No.: 3828A20892L

Air Conditioner
20 Yeouido-dong, Yeongdeungpo-gu,
Yeouido P.O.Box 335 Seoul,
150-721, Korea.
http://www.lgeaircon.com

The air conditioners manufactured by LG


All rights reserved have received ISO9001 certificate for
Printed in Korea March/2009 quality assurance and ISO14001
The specifications, designs, and File No. : A8974 Certificate No. : certificate for environmental
information in this brochure are subject to Volume:1 E00626/1 management system.
change without notice.