Académique Documents
Professionnel Documents
Culture Documents
1 Description................................................................................................................................................ 4
2 Operating Instruction ............................................................................................................................... 5
2.1 Describtion Keypad User Interface ..................................................................................................... 5
2.2 Setting / Change Parameter or Set points .......................................................................................... 5
2.3 Code Level .......................................................................................................................................... 6
3 Menu Overview ......................................................................................................................................... 7
3.1 Malfunction management.................................................................................................................... 8
3.1.1 Acknowledge a malfunction ......................................................................................................... 8
3.1.2 Error Memory ............................................................................................................................... 8
3.1.3 System Errors .............................................................................................................................. 9
3.2 Status Alarm...................................................................................................................................... 10
3.3 Status Relay ...................................................................................................................................... 10
3.3.1 Manual operation of the relay .................................................................................................... 10
3.4 Menu Measuring Values ................................................................................................................... 11
3.5 Menu Relay Parameter ..................................................................................................................... 11
3.5.1 Relay Mode ................................................................................................................................ 12
3.5.2 Relay Function Static / Flash ..................................................................................................... 12
3.5.3 Latching Mode ........................................................................................................................... 12
3.5.4 Horn Function ............................................................................................................................ 13
3.5.5 External Relay operation............................................................................................................ 14
3.6 Menu MP Parameter ......................................................................................................................... 14
3.6.1 Activate – Deactivate MP........................................................................................................... 15
3.6.2 Selection Gastype...................................................................................................................... 15
3.6.3 Measuring range ........................................................................................................................ 16
3.6.4 MP Signal................................................................................................................................... 16
3.6.5 Threshold / Hysteresis ............................................................................................................... 16
3.6.6 Delay Alarm ON or OFF............................................................................................................. 16
3.6.7 Control Mode ............................................................................................................................. 17
3.6.8 Assigned MP Fault to Alarm ...................................................................................................... 17
3.6.9 Assigned Alarm to Alarm relay .................................................................................................. 17
3.6.10 Assigned MP Signal to analog Output ....................................................................................... 17
3.7 Menu System Parameter .................................................................................................................. 18
3.7.1 Service Mode ............................................................................................................................. 19
3.7.2 Software Version........................................................................................................................ 19
3.7.3 Maintenance Concept ................................................................................................................ 20
3.7.4 Average Function....................................................................................................................... 20
3.7.5 Systemtime, Systemdate ........................................................................................................... 20
3.7.6 Customer Password (Code 1).................................................................................................... 20
3.7.7 Analog Output ............................................................................................................................ 21
3.7.8 Define the Failure Relay ............................................................................................................ 21
3.7.9 Power On Time .......................................................................................................................... 21
3.7.10 Registration of expansions modules.......................................................................................... 21
1 Description
The PolyGard® MGC-02 Gas Controller is used for the monitoring and warning of toxic- combustible- and
refrigerant- gases as well as temperature and humidity. The Gas Controller series MGC-02 can control up to 24
analog (Gas) Transmitters with 4 to 20 mA signal. For each Measuring Point (MP) are adjustable five freely alarm
thresholds. Every alarm threshold can be asigned to one of the maximum 20 alarmrelays (R) with changeover,
potential free contact. The Gas Controller can interface via 4 to 20 mA outputs to any compatible electronic analog
control, DDC/PLC control or automation system.
The free adjustable parameters and alarm threshold make a very flexible use in the gas measuring possible.
Simple and comfortable start-up is possibily with the factory adjusted parameters.
The configuration parameter settings and operation is easy to do without program knowledge.
The PolyGard® Gas Controller MGC-02 must not be used in areas showing explosive hazards.
2 Operating Instruction
The complete configuration, parameterization and service is made via keypad user interface in combination with
the display screen. Security is provided via two password levels.
Fault Alarm
MSR - Electronic
22.01.05 20:28
Exits programming and saves settings, returns to the previous menu level.
Scrolls down & up in Main menu and Sub menus, increases or decreases a value.
Moves of cursor.
After input valid code the cursor jumps on the first position segment which can be changed.
Finish
All changes of parameters and set point values are protected by four digit numeric Code (= password).
The code level 1 permits the operation of the MGC- 02. This code level is intended for the customer. The code can
be individually changed over the code level 2.
With the code level 2 all parameters and set points are released, this code level are reserved for the service
technician.
A third code level permits additionally an activate or deactivate of measuring points (MP) and expansions modules
(EP).
The release of the code level is deleted if 15 minutes not press a push button.
All menu windows can without release code level be regarded.
3 Menu Overview
The operation of the Gas Controller MGC-02 is made by a easy to learn, simply and logical menu structure.
The operating menu contains the following levels:
• Starting menu with Date and Time.
• Main Menu
• Sub Menu 1 and 2
MSR-Gas-Control
10.02.05 10:38
System Errors
Display and Reset Erros
See from point 3.1
Status Alarm
Display the status of actual alarms
See at point 3.2
Measuring Values
Display the measuring values
See at point 3.4
Relay Parameter
Display and Change the relay parameter
See from point 3.5
Malfunction Reset
MP 02
A1 A2
R 01
OFF
Setting
Symbol Describtion Function
Status
R 01 Relay No. 01 Select Relay No.
OFF = Relay Off (No gas alarm)
ON = Relay On (Gas alarm)
OFF Status Relay OFF
Manual OFF = Relay manual Off
Manual ON = Relay manual On
R 01
OFF Select Relay
Manual ON
Select Function Manual operation
Manual ON = Relay ON
Manual OFF Select Function Manual OFF = Relay OFF
Automatic = Manual operation delete
Reset ? = Acknowledging Latching mode
MP 01 CO ppm
50 *AV 33 CV
Setting
Symbol Describtion Function
Status
Measuring
MP 01 Select MP No
Point No.
CO Gas type CO See 3.6.2
ppm Gas unit See 3.6.2
CV Current value CV Current value of Gas Concentration
AV Average value Avergae value (10 measured values within the time unit)
* Control mode Display, with Control mode is select. (CV or AV)
Not active Status MP Not active MP not announced
Error Malfunction MP Current signal < 3 mA or > 22 mA
Relay Parameter
(Main menu)
R 01
(Selection Relay No.)
Relay Mode
De- energized Relay Mode
See 3.5.1
Static / Flash
Relay Function
0s
See 3.5.2
Latching mode
No Activate Latching Mode
See 3.5.3
Time Quitt. DI
0s 0 0 Definition Horn Function
See 3.5.4
External mode
DI: ON = 0: OFF = 0 Definition external Relay Operation
See 3.5.5
Setting
Symbol Describtion Function
Status
R 01 Relay No. Selection Relay
De- De- De-energized = Alarm ON = Relay ON
Relay Mode
energized energized Energized = Alarm ON = Relay OFF
Setting
Symbol Describtion Function
Status
R 01 Relay No. Selection Relay
0 = Relay Function static
0 Function 0 > 0 = Relay Function flashing ( = Periods time sec.)
Impulse / Break = 1:1
Setting
Symbol Describtion Function
Status
R 01 Relay No. Selection Relay
No = Latching Mode non active
No Latching Mode No
Yes = Latching Mode active
Acknowledging of a latching relay in the menu „Status Relay“ is possible only if the gas concentration is again
smaller than the alarm threshold including hysteresis. In this condition the status Latching is overlay.
On
Alarm 2 Gas Concentration greater smaller as Threshold
Off
On
Relay 2
Off
Setting
Symbol Describtion Function
Status
R 04 Relay No. Selection Relay
0 = Acknowledge the relay at time run off, or over Pushbutton
Quitt Mode 0 1 = Acknowledge the relay over Pushbutton, af time run off and
alarm is still acting, relay is set again. (Response function).
Time for function Automatic acknowledging or Response function
Time 120
0 = non acknowledging function
DI 0 Assignment, which digital input acknowledges the relay.
On
Alarm 4 Gas Concentration greater smaller as Threshold
Of
Time
On
Relay 4
Off
Acknowledging On
signal
Off
On
Alarm 4 Gas Concentration greater smaller as Threshold
Off
Time Time
On
Relay 4
Off
Acknowledging- On
signal
Off
Setting
Symbol Describtion Function
Status
R 01 Relay No. Selection Relay
DI-ON External On 0 If digital input closed, relay switch ON
DI-OFF External Off 0 If digital input closed, relay switch OFF
MP Parameter
(Main Menu)
MP 01
active (Selection MP)
MP Mode
active Activate or deactivate MP
See 3.6.1
Gastype
Define Gastype
CO
See 3.6.2
Measuring range
300 ppm Define Meassuring range
See 3.6.3
MP-Signal
linear Adjustment signal form of transmitter
See 3.6.4
Threshold 1
40 ppm Define Threshold 1
See 3.6.5
Threshold 2
80 ppm Define Threshold 2
See 3.6.5
Threshold 3
100 ppm Define Threshold 3
See 3.6.5
Threshold 4
Define Threshold 4
120 ppm
See 3.6.5
Threshold 5
300 ppm Define Threshold 5
See 3.6.5
Hysteresis
Hysteresis
15 ppm
See 3.6.5
Delay ON time
0s Set Delay ON time
See 3.6.6
C/A Mode
Define Control Mode
CV
See 3.6.7
Alarm - 1 2 3 4 5
Assigned MP Fault to Alarm
Fault - 1 1 0 0 0
See 3.6.8
Setting
Symbol Describtion Function
Status
MP 01 Measuring point Selection MP No.
not active = Measuring point announced
Active MP Status
active not active = Measuring point not announced
Setting Measuring
Symbol Describtion Gastype Unit
Status range1
MP 01 Measuring point .
CO Carbon monoxide ppm 0 – 300
Ex Combusible Gase %LEL 0 – 100
NO Nitric monoxide ppm 0 – 50
NO2 Nitric dioxide ppm 0 – 25
NH3 Ammonia ppm 0 – 300
O2 Oxygen2 %V/V 0 – 25
CO Gastype CO CO2 Carbon dioxide ppm 0 – 2000
R11 Refrigerant gase ppm 0 –xxx
R123 Refrigerant gase ppm 0 – xx
R134 Refrigerant gase ppm 0 – xx
R22 Refrigerant gase ppm 0 – xx
Temp Temperature °C --
RH Humidity % RH 0 – 100
1
Non obligation Recommendation
2
During oxygen measurement falling signal!
3.6.4 MP Signal
Gas transmitter with electro-chemical - or catalytic beat gas sensors spends in rule a linear, for gas concentration
proportional 4 to 20 mA signal.
Semiconductors gas sensors spend a not linear (exponential) signal. This signal leads to a non linear 4 to 20 mA
signal of the gas transmitter.
The Gas Controller MGC-02 is for both type of gas transmitters prepared. The classification of signals is defined in
this menu.
Setting
Symbol Describtion Function
Status
MP 01 Measuring Point Selection MP No.
linear = Transmitter with linear Output signal
Linear MP Signal linear Non linear = Transmitter with non linear Output signal (Only
Series AT from MSR-E)
Default
Symbol Describtion Function
Status
MP 01 Measuring Point Selection MP No.
40 Threshold 1 Gasconcentration > Threshold 1 = Alarm 1
80 Threshold 2 Gasconcentration > Threshold 2 = Alarm 2
100 Threshold 3 Gasconcentration > Threshold 3 = Alarm 3
40 ppm Threshold 120 Threshold 4 Gasconcentration > Threshold 4 = Alarm 4
300 Threshold 5 Gasconcentration > Threshold 5 = Alarm 5
15 Hysteresis Gasconcentration < (Threshold X –Hysteresis)
= Alarm X OFF
Default
Symbol Describtion Function
Status
MP 01 Measuring Point Selection MP No.
Gasconcentration > Threshold: Alarm is only activated at
0s Delay Time ON 0
expiration of the defined time (sec.). 0 sec. = No Delay
Gasconcentration < Threshold: Alarm is only deactivated at
0s Delay Time OFF 0
expiration of the defined time (sec.). 0 sec. = No Delay
Default
Symbol Describtion Function
Status t
MP 01 Measuring Point Selection MP No.
CV = Control the Current Gas value
CV Evaluation CV
AV = Control the Average Gas value
Default
Symbol Describtion Function
Status
MP 01 Measuring Point Selection MP No.
Alarm - 1 2 3 4 5 0 = Alarm not ON at MP Failure
Failure MP 11000
Fault - 1 1 0 0 0 1 = Alarm ON at MP Failure
Default
Symbol Describtion Function
Status
MP 01 Measuring Point Selection MP No.
A1 01 01 = Alarm 1 activate Alarmrelay R 01
A2 02 02 = Alarm 2 activate Alarmrelay R 02
1 A3 03 03 = Alarm 3 activate Alarmrelay R 03
A4 04 04 = Alarm 4 activate Alarmrelay R 04
A5 00 00 = Alarm 5 activate no any Alarmrelay
0 = MP Signal no assigned to any analog output
0 A 0 1 = MP Signal assigned to analog output 1
2 = MP Signal assigned to analog output 2
System Parameter
(Main Menu)
Service Mode
See 3.7.1
OFF
Software Version
GC02- XX See 3.7.2
Service Phone
See 3.7.3
+49/(0)8531/90040
AV Overlay
See 3.7.4
120 s. 120 ppm
AV Time
1800 s See 3.7.4
Time system
See 3.7.5
EU
Time
See 3.7.5
hh:mm:ss
Date
See 3.7.5
TT.MM.JJ
Customers Pass
Change **** See 3.7.6
Analog Output 1
Max. See 3.7.7
Calibration AO 1
4.0=4 mA 20 = Siehe
20.0 See 3.7.7
Analog Output 2
Max. See 3.7.7
Calibration AO 2
See 3.7.7
4.0=4 mA 20 = 20.0
Failure Relay
05 See 3.7.8
Power On Time
30 s See 3.7.9
EP Module 1
Not active See 3.7.10
EP Module 2
Not active See 3.7.10
EP Module 3
See 3.7.10
Not active
EP Module 4
See 3.7.10
Not active
Default
Symbol Describtion Function
Status
Off = Alarms activate the associated alarm relays
Off Service Mode Off
On = Alarms are not passed on to the alarm relays
Default
Symbol Describtion Function
Status
GC02- Software
XX = Software Version
XX Version
Default
Symbol Describtion Function
Status
TT.MM.JJ Maintenance date TT.MM.JJ = Input date for next maintenance.
0853.... Phone No. Input the individual service phone No.
Default
Symbol Describtion Function
Status
120 s 120 s sec. = Delay time average value Overlay. 0 = No overlay Function
AV- Overlay
120 ppm 120 ppm ppm = Threshold average Overlay
1800 s AV-Time 1800 s sec. = Time for calculate average value
Default
Symbol Describtion Function
Status
EU = Display time and date in EU format
EU Time format EU
US = Display time and date in US format
hh.mm.ss = Input the correct time (EU format)
hh.mm.ss Time
hh.mm.ss am = Input the correct time (US format)
TT.MM.JJ = Input the correct date (EU format)
TT.MM.JJ Date
MM.TT.JJ = Input the correct date (US format)
Default
Symbol Describtion Function
Status
Customer-
1234 1234 1234 = Define the Customer Password with 4 characters
password
Default
Symbol Describtion Function
Status
Min. = Spends the minimum value of all assigned MP
Select
Max. Max. Max. = Spends the maximum value of all assigned MP
Output mode
Average = Spends the average value of all assigned MP
4.0 4.0 4.0 = Calibration factor at 4 mA
Calibration
20.0 20.0 20.0 = Calibration factor at 20 mA
Default
Symbol Describtion Function
Status
05 SSM Relay R05 R05 = Define failure relay
Default
Symbol Describtion Function
Status
30 s Power On Time 30 s XX = Define the Power On Time (sec.)
The gas transmitter are connected directly at the module with the carge clamps. To consider the correct polarity.
The Alarms also connected directly at the module with the carge clamps. At the clamps of the alarm relays in each
case 2 contacts are present.
The alarms are available as DPDT, potenialfree contacts. If necessary the power supply volltage is available at the
clamps L1.
The exact position of the clamps for the transmitters and alarm relays is to be inferred the following connection
diagram.
The connection diagram contains those maximally possible number of expansion modules. Depending upon Gas
Controller type are however only individual modules equipped.
1K1
1F1
B10A
N PE
L L1L1 X1 1 2
2
1,5 mm
L N PE Power supply X1 1 2
2
Min. Cable diameter : 1,5 mm
90 to 230V / 50 Hz
Max. Fuse : 16 A Option EPS
Rated current : approx 2 A
G+
G-
X1 1 2 X1110 1112
GND
24 V
0V
SDA
SCL
Module designation: 2N1
> 4-20 mA
> 4-20 mA
> 4-20 mA
< 24 VDC
< 24 VDC
< 24 VDC
< 24 VDC
+ AO 01
+ AO 02
+ DI 01
+ DI 02
+ DI 03
+ DI 04
R 01 R 02 R 03 R 04 R 05
GND
GND
GND
GND
> GND
< 4-20 mA
< 4-20 mA
Maximum contact rating of relay 11
230 V/ 5 A ohmic load! 1K1
1K1 only at 14 12
Option EPS
equipped
X4 4 3 X4 4 3 X4 4 3 X4 4 3
4-20mA
4-20mA
4-20mA
4-20mA
24VDC
24VDC
24VDC
24VDC
MP 01 MP 02 MP 03 MP 04
X1 1 2 X1110 1112
9 01
Modulel-
GND
24 V
0V
SDA
SCL
Module designation: 3N2
78
23
adress 456
> 4-20 mA
> 4-20 mA
> 4-20 mA
< 24 VDC
< 24 VDC
< 24 VDC
< 24 VDC
R 06 R 07 R 08 R 09 R 10
GND
GND
X10 1 2 3 4 5 6 7 8 9 10 X2 1 2 3 4 5 6 7 8 9 10 11 12 131415
L1
X4 4 3 X4 4 3 X4 4 3 X4 4 3
4-20mA
4-20mA
4-20mA
4-20mA
24VDC
24VDC
24VDC
24VDC
MP 05 MP 06 MP 07 MP 08
X1 1 2 X1110 1112
9 01
Module-
GND
24 V
0V
SDA
SCL
Module designation: 4N3
78
23
adress 456
> 4-20 mA
> 4-20 mA
> 4-20 mA
< 24 VDC
< 24 VDC
< 24 VDC
< 24 VDC
R 11 R 12 R 13 R 14 R 15
GND
GND
X10 1 2 3 4 5 6 7 8 9 10 X2 1 2 3 4 5 6 7 8 9 10 11 12 131415
L1
X4 4 3 X4 4 3 X4 4 3 X4 4 3
4-20mA
4-20mA
4-20mA
4-20mA
24VDC
24VDC
24VDC
24VDC
MP 09 MP 10 MP 11 MP 12
X1 1 2 X1110 1112
9 01
Module-
GND
24 V
0V
SDA
SCL
Module designation: 5N4
78
23
adress 456
> 4-20 mA
> 4-20 mA
> 4-20 mA
< 24 VDC
< 24 VDC
< 24 VDC
< 24 VDC
R 16 R 17 R 18 R 19 R 20
GND
GND
X10 1 2 3 4 5 6 7 8 9 10 X2 1 2 3 4 5 6 7 8 9 10 11 12 131415
X4 4 3 X4 4 3 X4 4 3 X4 4 3
4-20mA
4-20mA
4-20mA
4-20mA
24VDC
24VDC
24VDC
24VDC
MP 13 MP 14 MP 15 MP 16
X1 1 2 X1110 1112
9 01
Module-
GND
24 V
0V
SDA
SCL
Module designation: 6N5
78
23
adress 456
> 4-20 mA
> 4-20 mA
> 4-20 mA
< 24 VDC
< 24 VDC
< 24 VDC
< 24 VDC
GND
GND
X10 1 2 3 4 5 6 7 8 9 10
X4 4 3 X4 4 3 X4 4 3 X4 4 3
4-20mA
4-20mA
4-20mA
4-20mA
24VDC
24VDC
24VDC
24VDC
MP 17 MP 18 MP 19 MP 20
X1 1 2 X1110 1112
9 01
Module-
GND
24 V
0V
SDA
SCL
Module designation: 7N6
78
23
adress 456
> 4-20 mA
> 4-20 mA
> 4-20 mA
< 24 VDC
< 24 VDC
< 24 VDC
< 24 VDC
GND
GND
X10 1 2 3 4 5 6 7 8 9 10
X4 4 3 X4 4 3 X4 4 3 X4 4 3
4-20mA
4-20mA
4-20mA
4-20mA
24VDC
24VDC
24VDC
24VDC
MP 21 MP 22 MP 23 MP 24
5 Start-up Operation
5.1 Start-up
Before beginning of start-up the wiring of the Gas Controller including all field devices must be completely
terminated!
If EP-02 modules is present, the module address must according to the following table on each module examined
and if necessary corrected before switching on of supply voltage on.
The address adder for adjusting the module address is accessible after taking off the contact strip X1 (power).
After switching On of the power supply and end of the Power On Time is the Gas Controller ready for use.
The Gas Controller is delivered with standard parameter and Set points. The registration the attached gas
transmitter and the assignment of the alarm relays to the individual alarms must always occurs with start-up.
Additional all other parameters are to be examined and adapted to the local conditions.
The standard parameter are to be taken from the following configuration and parameter card. We recommend to
register the individual parameters and being into the map.
We recommending to check the parameters and set points after the following check list.
System Parameter
Parameter Finish
Announce existing EP-02 modules
Time and Date
Parameter Average Function
Password level 1 (Customer Password)
Function analog output
Define failure relays
Power On Time
Service Phone No.
Maintenance date
Relay Parameter
Parameter Finish
Relay R 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Relay Mode
Function Static / Flash
Latching Mode
Horn function
External Relay operation
MP Parameter
Parameter Finish
MP No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 8 19 20 21 22 23 24
MP Mode
Gastype
Measuring range
MP- Signal
Threshold 1
Threshold 2
Threshold 3
Threshold 4
Threshold 5
Hysteresis
Delay ON time
Delay OFF time
C/A Mode
Assigned Failure <> Alarm
Assigned Alarm <> Alarm relay
Service Software Mainten- Service AV- Overlay Time Costumers Power Failure
Version ance date Phone ppm Time AV- system pass On Relay
Time Time
Default 15 06.06.06 0853190040 120 120 1800 EU 1234 30 s 5
7 Specifications
Electrical
110/230 VAC 50/60Hz;
Power supply
24 VAC/DC -10% + 20%
Power Consumption (incl. max. AT)
MGC-02-04-04-XX 13 W, 500 mA
MGC-02-08-08-XX to MGC-02-12-12-XX 27 W, 1100 mA
MGC-02-16-16-XX to MGC-02-24-16-XX 55 W, 2200 mA
Option Emergency power supply Supply duration 60 minutes
4 to 20 mA, overload and short circuit
Analog Input (max. 24)
protected, input resistor 200 Ω
Power supply for external analog Transmitter 24 VDC max. 50 mA / channel
4 to 20 mA, overload and short circuit
Analog Output
protected, max. 500 Ω load
Alarm relay (max. 20) 250 VAC, 5 A, potentialfree, DPDT
Failure relay 250 VAC, 5 A, potentialfree, DPDT
Option Buzzer - Sound pressure 85 dB (Distance 300 mm)
- Frequency 3,5 kHz
Visualization
Display Two lines, each 16 characters, illumination.
Status LED Yellow = Status Alarm; Red = Failure
Operation 6 Push button
Gases 1
CO, CO2, NO, NO2, NH3, O2, combustible and
Gas Transmitter external
refrigerant Gases
Environmental
Humidity 15 – 95 % r. F. non condensing
Working temperature -5° C bis + 40° C
Storage temperature 0° C bis + 40° C
Physical
Enclosure Plastic housing with view cover
Color RAL 7035 (gray)
Protection IP 65
Weight MGC-02-04-04XX 2,7 kg
MGC-02-08-08 to MGC-02-12-12 4,0 kg
MGC-02-16-16 to MGC-02-20-16 6,0 kg
MGC-02-24-16 7,5 kg
Mounting Wall mounting
Cable entry M 16; M 20; M 25
Wire connection: Power supply Screw type: 2,5 mm2
Relay Carge clamp: min. 0,5 mm2, max. 1,5 mm2
Input Carge clamp: min. 0,5 mm2, max. 1,5 mm2
Dimensions: MGC-02-04-04XX (W x H x D) 298 x 260 x 140 mm
MGC-02-08-08 to MGC-02-12-12 (W x H x D) 298 x 420 x 140 mm
MGC-02-16-16 to MGC-02-20-16 (W x H x D) 298 x 570 x 140 mm
MGC-02-24-16 (W x H x D) 410 x 655 x 140 mm
EMV – Guidelines 89/336/EWG; CE
Guidelines Low voltage guideline 73/23/EWG
VDI 20532
Warranty Two year material and workmanship
MSR - Electronic
22 .01 .05 20: 28
X10 X11
1 2 3 4 5 6 7 8 9 101112 1 2 3 4 5 6 7 8 9 101112
R1 R2 R3 R4 R5 Systembus
Status LED Relay Status LED
Expansionsmodule EP 02
X1 X2
1 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
9 01
78
2 3
456
Adress-
selector
X10 X11
X11
1 2 3 4 5 6 7 8 9 101112 1 2 3 4 5 6 7 8 9 101112
R1 R2 R3 R4 R5 Systembus
Status LED Relay Status LED
9.3 Maintenance
It is recommended that the PolyGard® MGC-02 performance check is done on a routine schedule. Any
performance deviations may be serviced based on needed requirements.