Académique Documents
Professionnel Documents
Culture Documents
2
(Second edition)
Loads for
Structural Design
1
PREFACE
BRU Technical Guideline NO.2: Loads for Structural Design is one of
the set of guidelines issued by the Ministry of Lands, Housing and
Human Settlements Development through the National Housing
Building and Research Agency (NHBRA). It is intended to be a local
reference to be used by practicing structural engineers in Tanzania by
providing practical advises on how to achieve the given requirements
in the design of buildings. This second edition supersedes the first
edition in the sense that only limited additional information has been
incorporated with regard to local data on wind loading. Similar local
guidelines for design of timber structures, brick-and brickwork
structures, foundations, steel structures and concrete structures will
also be released by the NHBRA.
These guidelines have been compiled by NHBRA jointly and in close
cooperation with the key stakeholders, namely; the Department of
Structural and Construction Engineering of the University of Dar es
Salaam, Commission of Science and Technology, Enginers Registration
Board, National Construction Council, Tanzania Bureau of Standards,
Association of Consulting Engineers Tanzania and local structural
engineering companies.
NHBRA undertakes to develop and release regularly updated
Technical Guidelines as local reference materials as and when new
information is made available; so that they continually serve to
complement foreign standards, mainly the British Standards and Euro
Codes, which are commonly used in Tanzania.
2
Contents
1. INTRODUCTION ...............................................................................7
5
5.2.2 Fire resistance and design methods............................. 47
REFERENCES ......................................................................................... 62
6
1. INTRODUCTION
1.1. Scope
This guideline provides loads and load coefficients for structural design
according to the method of partial safety coefficients. The rules are based
on general design requirements of structural safety and stability stated in
Tanzania Building Regulations.
1.2. Units
In Tanzania Building Regulations the SI units (International System) are
used for measurement; see Table 1.2.1, in accordance with report ISO/DP
4337 Rules for the use of the SI system of units in buildings.
Decimal prefixes are given in Table 1.2.2. Conversion factors from old
units to SI units are given in Table 1.2.3.
Table 1.2.1 SI- Units
Quantity Unit Multiple
Name Symbol Units
Length Metre m 1 mm = 10-3
Area Square metre m2 1 mm2 = 10-6 m2
Volume Cubic metre m3 1 mm3 = 10-9 m3
Force (load) 1 kN (=103 N)
Newton N
1 MN (=106 N)
Time Second s H, d, m
Moment of force Newton metre Nm 1 kNm
Stress Pascal 1 Pa kPa, MPa
=1N/m2
7
Modulus of Pascal Pa MPa
elasticity
Load intensity Pascal Pa kPa, MPa
Mind that the conversions 1 kgf = 10 N and 1 kgf/cm2 = 0.1 N/mm2 are
allowed to be used.
8
1.3. Notations
The notation used in the following complies with ISO Standard 3898,
Bases for calculation of structures notations – general symbols.
A Area, cross section
E Modulus of elasticity
F Force, load, loading capacity
G Permanent loads
K Coefficient (without dimensions)
L Span, length
M Bending moment
N Axial force, variable load, point load
P Variable load, earth pressure, point load
Q Variable load, point load
T Temperature, fundamental period of oscillation. The later is not
according to ISO-Standard 3898.
1.4. Indices
a = acceleration
c = characteristic (e.g. characteristic strength, fc)
d = design (e.g. design strength, fd)
10
f = load, failure, foundation
h = horizontal
m = mean value, materials
p = partial
t = total
v = ventilation, vertical
w = water, wall
x = x-direction
y = y-direction
z = z-direction
1.5. Definitions
11
Design load Characteristic load multiplied with the load
coefficient.
Load Partial safety coefficient for loads. (The coefficient
coefficient takes account of
un-predictable variation of the characteristic load,
inaccuracy in the loading model used and the reduced
probability for loads, all having their characteristic
value simultaneously)
2.1. General
Apriori verification of any structure fulfilling the requirement
corresponding to the limit state considered may be made either by
appropriate method of calculation or by testing.
13
Ultimate limit state design is carried out when sufficient load carrying
capacity is required. Plastic or elastic method of analysis may be applied
depending on the behavior of the materials and the structure when being
exposed to excessive loading.
Serviceability limit state design is carried out when proper service of the
structure is required with respect to deflections and deformations due to
load action, temperature, shrinkage etc. Elastic method of analysis is
normally appropriate.
Fd = f . Fc
14
The accidental load combinations for earthquake, fire and cyclone
winds apply only to structures where the failure consequences are graded
as very serious (safety class 3).
15
methods and models must correspond to the consequences of structural
failure.
The design strength of materials are calculated as
fd = fc/ m n
Fmin c n m f Fc
where:
The coefficient c above takes account of the strength of the test specimen
being related to loading time, temperature, geometric conditions etc.
16
For non-destructive tests of a structure on site the final test load is
made equal Fmin. The calculation of Fmin shall be based on values of the
partial safety coefficient for loads corresponding to serviceability limit
state of the structure. At full load, the structure should be proved
serviceable according to the design requirements given.
For laboratory testing of type structures and structural elements, at
least three specimens should be tested. The structures may be tested in
either of the two following methods.
1. All specimens have to reach Fmin without failure or extensive damage.
2. The ultimate capacity of all samples should be measured, and the
characteristic capacity of the lot is calculated as follows.
Fc =Fm – ks
1
See chapter 1.5 Definitions.
1
2 ( xi ) 2 2
xi n
2
s
n 1
where xi = the result no. i
n= the number of specimens
17
k = a constant depending on the number of specimens in the lot,
Table 2.4.1
n 3 4 5 6 8 10 15 25 ∞
For both methods, the calculation of Fmin shall be based on values of the
partial safety coefficient for loads corresponding to ultimate limit state of
the structure.
3. PERMANENT LOAD
18
Expanded clay concrete 14- 16
Solid concrete blocks 21
Hollow concrete blocks 14
Airated concrete blocks 5- 7
Expanded clay blocks 8- 14
Bricks 14 – 18
Metals Steel 77
Cast iron 71
Aluminium 27
Soils Clay 20
Silt, sand, murram (dry) 18
Sand (loose and dry) 13
Rocks, gravel 15
19
Gypsum board 6- 9
Mineral wool 0.5- 2
Rubber 10-20
3.3.1 General
Earth may consist of any soil or mixture of soil such as stones, gravel,
murram, sand, silt, clay or organic masses.
20
Vibrations, compaction, transport and storing of items in the
neighbourhood etc. may also affect the soil pressure.
The materials coefficient m = 1.3 have been used for calculations of the Kd
in the following chapter.
21
3.3.4 Calculation of design soil Pressure
The design soil pressure on the vertical immovable structure supporting
drained soil and with no loads on the ground may be calculated as
Ps= /2 Kd d h2
1
Where
Kd= the coefficient for design soil pressure as given in Table 3.3.4
where
Pq = Kd . qc . f
where
Pq= the additional soil pressure due to the surface load qc. It is assumed to
act at ⅟₂h below ground level.
PQ = Kd . Qc . f
Where
PQ = additional soil pressure due to the surface load Qc. It is assumed to act
at a distance d below ground level and in a total horizontal length d along
the structure, where d is the horizontal distance between the wall and the
surface load.
23
If the ground is not drained, and the structure is loaded with water
pressure from ground water, the following pressure should be added to Ps
to obtain the total pressure P:
Pw = (1-Kd) . w . hw2 . f
hw = the height of the water table above the bottom of the structure
Qc qc
d h
PQ 2 2h
G.W.
Pq Ps 3
hw Pw
hw
3
Fig. 3.3.4 Calculation of soil pressure
Total pressure P = Pq + PQ + Ps + Pw
If the structure position is fixed, the shear strength of the soil will not be
activated, and the earth pressure will be higher. The pressure can be
24
calculated as shown above by increasing the coefficient for design soil
pressure by 50%.
4. VARIABLE LOADS
4.1.1. General
If the characteristics values are not being determined by statistical
methods according to the definition of characteristic loads, the values in
chapter 4.1.2-4.1.6 may be applied.
Balconies 3.0
25
Shops 3.0
The total calculated reduction must not exceed 50% of the total loads on
any load carrying component. The reduction does not apply to floors
intended for storage.
27
determined, and the structure must be designed to carry the determined
loads.
The loads should be assumed acting on the area which is accessible to the
vehicles. The concentrated loads are to be placed in the most unfavorable
positions within the area and with distances which correspond to the
position of the wheels.
28
Larger impact forces may be regarded as accidental loads.
4.2.1. General
This chapter gives methods for calculating characteristic values for static
wind loads on buildings and structures.
qd =⅟2 . vd2
where vd = design wind speed(m/s) given in 4.2.3
= the density of air (Kg/m3)
For computing the design wind pressure the following approximation may
be used:
qd= 0.613 vd2 (N/m2)
The density of air may be calculated from
p TO
= o
po T
where o 1.3Kg / m3
Po 760mmHg
To 273 o K
P= actual pressure
T= actual temperature
29
4.2.3. Design wind speed
vd = vb x S1 x S2 x S3
vb = basic wind speed as discussed in 4.2.4
S1-3 are obtained from [15] and defined as follows:
S2 = factor for ground roughness, building size and height above the
ground
Sometimes referred to as the effective wind speed
30
4.2.4. Basic wind speed
The basic wind speeds for major stations Tanzania was obtained from a
study of evaluating parent records of maximum monthly wind speeds and
is given in the map of Fig. 4.2.4 and in Table 4.2.4
Lake
Nyasa
Nyasa
31
Table 4.2.4: Basic wind speed
S/N Station Basic wind speed
in m/s
1 Arusha 31
2 Bukoba 48
3 Dar es Salaam 27
4 Dodoma 36
5 Iringa 29
6 Kigoma 48
7 Mbeya 41
8 Morogoro 42
9 Moshi 35
10 Musoma 29
11 Mtwara 38
12 Mwanza 29
13 Shinyanga 46
14 Songea 34
15 Sumbawanga 34
16 Tabora 33
17 Tanga 30
18 Zanzibar 29
qs=µ . qd
32
4.2.6. Shape factors
4.2.6.1. General
Shape factors for wind pressures may be determined either through full
scale tests or model testing.
The shape factors given in this chapter are the most commonly needed
ones. Additional information may be obtained from special literature on
the subject.
Alt. 1 Alt. 2
Structure Wind Shape Wind Shape
Direction factors Direction factors
Heavily
ventilated 0.7 0.5
on one side pressure suction
Heavily
ventilated 0.3 0.3
on two pressure suction
adjacent sides
Heavily
ventilated 0.0 0.5
on two pressure suction
opposite sides
.
Heavily
ventilated 0.3 0.3
on three sides pressure suction
33
Heavily
ventilated 0.3 0.3
all sides suction suction
On the lee side, the shape factor is equal to 0.9 for secondary parts of the
structure.
The total wind loads on any external wall are sum of both internal and
external loads.
h
b Wind
1.1 suc direction
0.6 suc 0.7 press
0.7 1.1 suc 1.1 suc
press Ld
Wind 0.5
direction suc
0.6 0.6
suc suc
0.5 suc
1.1 suc0.6 suc
Ld L d= b/2 or h/2 whichever
is smaller
34
Ld is the smaller of the two values b/₂ and h/₂,
Shape factors for gabled roofs are dependent on the roof slope as well
as the wind direction as described in Fig. 4.2.6.4
Table 4.2.6.4 Shape factors for gabled roofs dependent on Fig. 4.2.6.4
Load Wind towards long façade
area tan ≤ 0 .3 0.3 tan < ≤ 0.6
Alt. 1 Alt. 2
A 2.0 suction 0.7 suction 0.2 pressure
B 1.5 suction 0.7 suction 0.2 pressure
C 1.0 suction 0.7 suction 0.2 pressure
D 0.5 suction 0.5 suction 0.5 suction
Load Wind toward long façade
area
0.6 <tan ≤ 1.0 tan > 1.0
A 0.4 Pressure 0.7 pressure
B 0.4 pressure 0.7 pressure
C 0.4 pressure 0.7 pressure
D 0.5 suction 0.5 suction
Load Wind towards gable
Area tan ≤ 0.2 0.2 ≤ tan ≤ 0.4
E 2.0 Suction 1.0 suction
F 1.0 suction 1.0 suction
G 0.5 suction 1.5 suction
35
0.1b
0.5b A
Wind B
D
direction C h
Ridge
β
A
b
L
0.5b
0.1b Ridge
E F G
Wind
direction E F G
(I) b < L
(II) b/₃ ≤ hw ≥ 3 L
36
Table 4.2.6.5 Shape factors for shed roofs dependent on Fig. 4.2.6.5
Load Wind toward high façade
area
tan ≤ 0.1 0.1< tan ≤ 0.4
A 2.0 suction 2.0 suction
B 1.5 suction 1.2.-1.4 tan β suction
C 1.0 suction 1.2.-1.4 tan β suction
D 0.5 suction 0.5 suction
Load Wind toward low façade
area
tan ≤ 0.1 0.1< tan ≤ 0.4
A 2.0 suction 1.3-2.6 tan β suction
B 1.5 suction 1.3-2.6 tan β suction
C 1.0 suction 1.3-2.6 tan β suction
D 0.5 suction 0.7-1.4 tan β suction
Load Wind towards low gable
area
tan ≤ 1.0 0.1< tan ≤ 0.4
E 2.0 suction 1.0 suction
F 1.0suction 1.0 suction
G 0.5 suction 1.5suction
0.1b
0.5b A
Wind B D
direction C hw β
A L
0.5b b
0.1b
Wind E
G b
direction F
37
4.2.6.6. Horizontal and arched roofs
The shape factors given in Fig.4.2.6.6.a are valid for horizontal roofs when:
(I) b< L
(II) tan β = 0
h h
L
b
a2
a1 b L
The shape factors given in Fig. 4.2.6.6.b are valid for circular arched roof
structures when
b < 3hw
h hw
0.1
b
Where b, h and hw are shown on the figure.
38
h hw
If 0.1 then the shape factors for gable roofs should be used
b
2h hw
assuming tan
b
h
hw
b
0.9 + h - hw suction
b
0.7 pressure 0.5 suction
Wind o
direction α = 40
tan α = 0.8
Wind
direction
39
Where b, and hw are given on the figure
In addition to the evenly distributed loads, the area x width of the roof
should be considered as a rough plain surface with a shape factor = 0.1
for tangential wind loads. These loads act along the foot of the roof.
b
β β
hw
Wind
direction
For wind parallel to the ridge, a suction of = 1.0 acts on an area with a
width of b/2 on the windward side of the roof edge and suction of = 0.5
on the remaining part of the roof.
The shape factors given in Fig. 4.2.6.7.b are valid for saw roofs when
1 = 30 0 (approximately)
2 = 60 0 (approximately)
For tangential wind loads on the wind side of the roof, the some shape
factors as for multiple gabled roofs shall be used.
40
b
2
1
Wind
dir.
μ is the same as for windward side of gable roof
0.5 suction 0.7 suction
µ
Wind
dir.
Shape factor is given as the sum of the shape factors for the two surfaces
of the roof. The wind load is assumed to be perpendicular to the surface of
the roof.
41
Roof type Slope/alt Windward side Lee side
42
Shed roof 0≤ tan ≤ 0.2 Wind type A Wind type B
A
Wind β alt. 1 2.0 tan β
direction
alt. 2 2.0
tan β
B β
2.0 tan β
Wind 2.0 tan β
direction
tan ≤ 2.0
both alternatives
= 2.0 up = 2.0 down
43
Table 4.2.6.9.a Resulting shape factors for rectangular chimneys,
towers and poles
a/b
≤1 2.0 a
Wind
direction b
1–5 2.2 – 0.2 a/b
a
Wind b
direction
>5 1.2
The wind load is lower near the top. Within the length 3b from the top, the
given shape factors may be multiplied by 0.6.
The shape factors are valid for the component of the wind load in the
direction of the wind. The bars projection area, perpendicular to the
direction of the wind is used when calculating the wind loads.
Re =0.67 . 105 . v . d
= (rmax-rmin) /d
44
Where rmax = the maximum radius of the bar
rmin = the minimum radius
d = the diameter
0.8*10-3 0.8
1.5*10-3 0.9
2.5*10-3 1.0
4.0*10-3 1.1
9.0*10-3 1.2
The rmax and rmin shall be measured with respect to the rough, uneven
texture of the surface
45
Dynamic vibration or oscillations of slender structures and components
may occur due to wind action, and should be controlled according to
special literature.
5. ACCIDENTAL LOADS
5.1.1. General
Design in the ultimate limit state for cyclone wind only apply to structures
where failure consequences are graded as very serious and when these
structures are situated within 200km from the coast.
The cyclone may retain wind speeds of 50-60 m/s at 10m height.
However, the area affected by this speed is limited to a width of not less
than 20km along the track of the cyclone centre. The cyclone may reach
inland areas as far as 200km from the coastline, though with a declining
strength as it moves from the coast.
vc=55/3(log10 h+2)
Where vc = the design wind speed in m/s for cyclone wind at the height h
above ground level
46
For densely built areas (e.g. cities) the design wind speed may be reduced
to 80% of the values obtained from the formula above, if the building is
less than 20m high.
5.2.1 General
The load action during fire consists of two basic elements, the permanent
and variable loads as described in chapter 3 and 4 in this guideline and
effect of temperature increase on load carrying structures.
This chapter deals only with the development of temperature during fire
with respect to the load carrying capacity of structure. The design load
combinations are calculated from chapter 2.2 using ultimate limit state,
load combination F.
Ultimate limit state design for fire, only apply to structures where failure
consequences are graded as very serious.
The fire testing methods are based on material studies during and after
the fire testing of the structure or the component in an oven according to
47
internationally accepted test methods . The time–temperature shall vary
according to the following formula
48
Fig. 5.2.3 Time temperature curves for fire cells
49
The ventilation factor K is calculated from the formula
1
K Av .h / At
2
For values of the ventilation factor K which lie outside the range
The fire intensity, f for each fire cell, shall be calculated from the formula
m1,2 = the mass of any combustible materials within the fire cell
which may contribute to the total energy release
At = the total surface area of the fire cell (floor, ceiling and walls,
including openings)
50
All combustible materials, within the cell and within enveloping
structures, shall be included in the calculation above. Table 5.2.3.a and
Table 5.2.3.b give appropriate values for energy densities of materials and
approximate values of energy intensities in some premises respectively.
51
Table 5.2.3.b Some approximate energy intensities, f, in MJ/m 2 for
some types of premises
Type of premises f (MJ/Kg)
Offices 120
Schools and 60
universities
Hospitals 100
Hotels 70
5.3.1 General
Where earthquake design of structures is required, earthquake loads shall
either be determined by the rules given in this chapter or by accurate
dynamic analysis of the structure provided the horizontal ground
acceleration used is not less than given in the map in figure 5.3.3.
Ultimate limit state design for earthquake loads only apply to structures
where failure consequences are graded as very serious
52
- permanent loads, service loads and other loads acting on the structure
simultaneously
- the influence of direct or indirect contact with neighbouring structures
Vd = ka . ks . kn . ki . kf . Wd
53
ki = the building importance factor
ki= 1. 0 for other structures than mentioned below
kf = the foundation factor. The value should be equal to 1.0 when the
foundation rests on rock or very firm soil. For soft fine – grained soil,
the value 1.5 should be used. (A more correct value for kf may be
obtained if the dynamic shear properties of the particular soil in
question are tested)
54
Fig. 5.3.3 Seismic risk map of Tanzania
55
Table 5.3.3. The horizontal force factor kn. The factor reflects the manner in
which structures resist earthquake forces and the ductility of the material
used
Description of structures kn
Steel and reinforced concrete (not pre-stressed) may be regarded as
ductile materials
56
5.3.4 Fundamental period of oscillation, T
The period of oscillation in the direction considered, shall be determined
according to the formula
1
T 0.09hn d 2
T = 0 .10 N
57
60% of hn
hn = height in metres from the
foundation to the top of the main
portion of the structure
ds = the dimension of the lateral load carrying
system in metres in a direction parallel to the lateral load.
Vd = the total equivalent static design load.
The total shear in any horizontal section shall be distributed to the various
elements of the lateral force resisting system in proportion to their
rigidities.
For building with one or two storeys, the lateral force Vr shall be
considered uniformly distributed throughout the height.
58
where Vpd = the design value of the lateral loads
acting on the part considered
ka = the design ground acceleration factor
given in the seismic risk map of
Tanzania, figure 5.3.3
Kp = the partial horizontal force factor for the
part considered according to table 5.3.6
Wpd = the design value of the weight of the part
considered.
59
5.3.7 Overturning moment
The overturning moment at the base or at any other level of the structure
is calculated from the lateral force Vt and the distributed load Vx. The
moment shall be multiplied by a reduction coefficient
Building with set –back storeys (tower) where the plan dimension are not
less than 75% of the plan dimensions of the portion below may be
considered as a uniform building . If the dimensions are less than 75%, the
60
set–back portion shall be designed as a separate structure using the
largest loads obtained either from considering the set-back portion as a
separate structure or considering it as a part of the total structure.
The resulting total shear from the set–back portion shall be applied at the
top of the lower portion. The lower portion may otherwise be designed as
a separate building.
61
REFERENCES
1. General principles on reliability for structural design. Published by
joint committee on structural safety of CEB – CECM – CIB – FIP – IABSE.
1978.
6.
62
6b KOMMENTARER TIL SVENSK BYGGNORM, SBN (comments
on Swedish building code ) no 1976 , 1: Fire engineering design .
Stockholm, Statens planverk. Text in Swedish.
63
14. BUILDING AND ROAD INSTITUTE. Ghana building code, chapter 3.11:
Effects of earthquake. Kumasi 1977.
17. BS 8110: 1997: Structural use of concrete: Part 1: Code of practice for
design and construction, BSI, London
18. BS 6399: 1996: Loading for buildings: Part 1: Code of practice for dead
and imposed loads
64