Académique Documents
Professionnel Documents
Culture Documents
CONTENTS
GENERAL ......................................................................................................................... 4
1.1. Scope ......................................................................................................................... 4
1.2. Project Specifications and Industry Standards .......................................................... 4
1.3. Insulation Types and Applications ............................................................................. 6
1.4. Definitions .................................................................................................................. 9
1.5. Extent of Insulation .................................................................................................... 9
1.6. Requirements ........................................................................................................... 10
INSULATION SYSTEM BASIC DESIGN ........................................................................ 10
2.1. General..................................................................................................................... 10
2.2. Heat Conservation (Type 1) ..................................................................................... 10
2.3. Personnel Protection (Type 2) ................................................................................. 11
2.4. Sound Control (Type 3A, 3B, 3C and Type 4A, 4B, 4C, 4D) .................................. 11
2.5. Steam and Electrical Tracing (Type S, S1, S2 and Type E) ................................... 12
2.6. Steam Jacketing (Type J) ........................................................................................ 12
MATERIAL REQUIREMENTS ........................................................................................ 12
3.1. General..................................................................................................................... 12
3.2. General Requirements for Insulation Materials ....................................................... 14
3.3. General Requirements for Mineral Wool Insulation................................................. 14
3.4. Mineral Wool Preformed Sections ........................................................................... 15
3.5. Mineral Wool Slab .................................................................................................... 15
3.6. Mineral Wool Mattress ............................................................................................. 16
3.7. Mineral Wool Loose Fill............................................................................................ 16
3.8. Glass Fiber Blanket for Expansion Joints ................................................................ 16
3.9. Removable Flexible Insulation ................................................................................. 16
3.10. Finishing Cement ..................................................................................................... 16
3.11. Weatherproofing Mastic ........................................................................................... 17
3.12. Reinforcing Membrane............................................................................................. 17
3.13. Flashing Compound ................................................................................................. 17
3.14. Barium Loaded Vinyl Sheet for Sound Control Applications ................................... 17
3.15. Fabrication Adhesive for Mineral Wool .................................................................... 18
3.16. Cladding ................................................................................................................... 18
3.17. Fasteners ................................................................................................................. 19
3.18. Floating Rings .......................................................................................................... 20
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
GENERAL
1.1. Scope
This specification defines minimum material and field installation requirements for
external thermal insulation and thermal-acoustic insulation of hot temperature service
piping and equipment for the North Field Expansion Project Onshore Facilities FEED.
This specification covers the twelve (14) insulation types, Type 1, 2, 3A, 3B, 3C, 4A, 4B,
4C, 4D, S, S1, S2, E and J.
Industry Standards
AMERICAN SOCIETY OF TESTING AND MATERIALS (ASTM)
[2] ASTM B749 Lead and Lead Alloy Strip, Sheet, and Plate Products
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
[9] ASTM C612 Mineral Fiber Block and Board Thermal Insulation
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Class Thickness
Type Suffix Application Description Table
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Note 1: If normal operating temperature of piping or equipment is less than 61°C, insulation for
heat conservation is not permitted unless the nature of the process is such that sudden
or extreme changes in weather conditions could adversely affect operations. In such
cases insulation may be specified for piping or equipment normally operating at
temperatures of 21°C through 60°C.
Insulation types and nominal thicknesses for piping are indicated on the Piping Isometric
Drawings and Line Index. Any conflicts in insulation thickness between the piping
drawings and the tables herein shall be brought to the attention of COMPANY for
resolution prior to starting insulation fabrication.
Insulation types and nominal thicknesses for equipment are specified in Equipment
List/Data Sheet. Any conflicts between the requirements defined herein or on the
Equipment Drawings and Equipment List shall be brought to the attention of COMPANY
for resolution prior to starting insulation fabrication.
Insulation system design shall be based on the normal operating temperature of the
contained fluid with following considerations:
a. For non-jacketed piping furnished with heat tracing, only the normal operating
temperature of the heated process fluid shall be considered. For jacketed piping,
the temperature of the heating fluid shall govern the selection of insulation thickness.
b. For vertical equipment having design fluid temperature variations over the
equipment length, the normal operating temperature range of the fluid shall be used
and the insulation thickness may be varied over the equipment length.
c. Significant variations in temperature from normal operating conditions
(Regeneration conditions, etc.) requires review of the specific insulation system
design.
d. For sound control applications, the Insulation Type shall be appended with a "Class
Suffix" (A, B, C or D). The class suffix identifies the required noise reductions for
the specific system.
e. Minimum noise reductions in dB for specific class suffixes and octave-band center
frequency combinations shall be as specified in EEMUA Publication 142, Table 2
as follows:
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Where a steel structure is used as a base for the piping, there must be vibration-isolating
pad between the base and pipe support in order to achieve the noise reductions values
of Class Suffix C and D.
The supply and the installation of vibration isolation used for the metal components shall
be done by the mechanical subcontractor.
1.4. Definitions
The term "equipment" includes vessels (towers, drums, spheres, reactors, reboilers, and
exchangers), machinery (pumps, compressors, turbines) and tanks (vertical, cylindrical
storage tanks).
Generic references to the thermal insulation material as "Mineral wool" including
references in ASTM's C547, C592 and C612 to "Mineral fiber" shall be defined as
materials of a rock composition (diabase, silica ore, basalt or similar types), processed
from a molten state into a fibrous form.
"Austenitic stainless steel" includes Types 304, 316, 321 and 347 stainless steel. "High
alloy" includes Monel and Alloy 20 materials.
Unless otherwise specified, "diameter" used in such context as "vessel diameter", "shell
diameter" or "head diameter" refers to the outside diameter of the insulation, not the
outside diameter of the vessel, shell or head.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
1.6. Requirements
If SUBCONTRACTOR proposes materials or method not exactly as specified, but they
are intended to be equal or better in quality or performance, then catalogue, data sheets,
test reports, samples, reasons of change and other supporting information shall be
submitted for approval.
The drawings, specifications and standards are complementary to each other. Where
conflicts occur between documents, they shall be immediately brought to the attention
to COMPANY prior to submission of bids.
After contract award, claims of ignorance regarding the intent and scope of the contract
shall not be allowed.
2.1. General
Twelve (12) basic types of insulation systems are covered by this specification. The
appropriate type shall be applied as specified to piping and equipment as required for
the overall proper performance and safety of the plant.
Insulation systems shall be designated by the "Type" designation listed in Article 1.3, by
COMPANY.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
speed and an insulation system surface emissivity of 0.2 (silver polyester resin coated
aluminized steel cladding):
a. The theoretical temperature of the outer surface of the insulation system shall not
exceed 60°C.
b. The theoretical heat loss to the atmosphere from the outside surface of the
insulation system shall not exceed 190 W/m2.
Hard piped jump-over piping shall be insulated for heat conservation.
3Insulation thickness shall be in accordance with Table III.
2.4. Sound Control (Type 3A, 3B, 3C and Type 4A, 4B, 4C, 4D)
Insulation design for sound control applications shall be in accordance with EEMUA
Publication 142 and the requirements specified herein.
Where sound control is required in conjunction with heat conservation, piping and
equipment shall receive a Type 3 insulation system. The theoretical thermal
performance of the insulation system shall be in accordance with the requirements
specified in Article 2.2 for heat conservation, insulation Type 1.
a. Insulation thickness for insulation Type 3, Class A applications shall be in
accordance with Table V.
b. Insulation thickness for insulation Type 3, Class B or C applications shall be in
accordance with Table VI.
Where sound control is required and heat loss is acceptable, piping and equipment shall
receive a Type 4 insulation system. The theoretical thermal performance of the
insulation system shall be in accordance with the requirements specified in Article 2.3
for personnel protection, insulation Type 2.
a. Insulation thickness for insulation Type 4, Class A applications shall be in
accordance with Table VII.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
MATERIAL REQUIREMENTS
3.1. General
Insulation materials and their application, including all ancillary fastening, coating,
sealing, sheeting and other accessories, shall comply with applicable national and local
government legislation, including safety and health requirements. All applicable federal,
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
state and local codes and all regulations on application, storage, handling and safety
shall be followed.
All insulation and ancillary materials shall be suitable for both application and service in
atmospheric conditions considered as corrosive, dusty and salt laden conditions.
All materials covered by this SPECIFICATION shall be of high quality, good appearance,
and shall not have any deleterious action on the painted surface to be insulated.
All insulation and non-metallic accessory materials shall be formulated without the
addition of asbestos, tremolite, anthrouphylite, actinolite or a combination of these
minerals. Insulation materials shall be chemically inert, rot proof, vermin proof, non-
injurious to health.
Sheeting material shall have no form of flammable material attached to it. All coatings
applied for weatherproofing, joint sealing, etc. shall have a low flame spread ratings.
Insulating materials to be used on austenitic stainless steel shall contain less than 600
ppm leachable chlorides and more than 20 ppm sodium silicate for each ppm of
leachable chlorides.
SUBCONTRACTOR shall submit independent test data showing compliance with the
test method and safe use over stainless steel.
SUBCONTRACTOR shall have complete responsible for the compatibility of all
accessories, compounds and finishes with the insulation materials proposed.
The selection of material shall be submitted to COMPANY for the approval prior to
purchasing.
SUBCONTRACTOR shall be solely responsible for his own material take-off, purchasing,
methods and procedures, tools and equipment, and field-safety programs unless
otherwise specified.
Detailed "Material Specifications" including manufacturer's "Product Data Sheets" of the
selected materials, together with samples of major insulation materials shall be provided
for the approval of COMPANY.
All materials shall only be purchased in strict accordance with these documents
approved.
"Fabrication Procedure" of insulating materials and "Installation Procedure" including
"Detailed Installation Drawing" shall be provided for the approval of COMPANY.
"Detailed Insulation Drawing" shall indicate the exact position and use of the materials
approved. All materials shall only be installed in strict accordance with these
documents approved.
Prior to commencing insulation installation activities, SUBCONTRACTOR shall
ascertain that the latest issue of the material manufacturer's Product Data Sheets,
Application Instructions and Material Safety Data Sheets (MSDS) are available and that
the installation, material handling and waste disposal procedures to be used include all
manufacturer's recommendations, instructions and all pertinent safety precautions.
The waste disposal shall be conformed to local government legislation and safety and
health requirements.
All accessory materials (i.e. coatings, adhesives, sealants, sealers, etc.) shall be
shipped to job-site in marked, unopened containers/boxes as received from the
manufacturers.
Piping insulation used in areas where the mitigation of fire exposure is necessary shall
have a maximum flame spread index 25 when tested in accordance with ASTM E84 or
ANSI/UL 723, and shall maintain those properties that are necessary to maintain
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
physical and thermal integrity during an emergency when exposed to fire, heat, cold, or
water.
In addition to 3.1.13, pipe insulation assemblies used in areas where the mitigation of
fire exposure is necessary shall be one of the following;
(a) Comprised of noncombustible materials per ASTM E136
(b) Covered by an outer protective stainless steel jacket at least 0.02in. (0.51mm) thick
(c) Covered by an outer aluminum jacket at least 0.032in. (0.81mm) thick
(d) Determined to meet the conditions of acceptance in B.3 of NFPA 274
Where insulation materials can cause corrosion of aluminum or stainless steels,
inhibitors or waterproof barriers shall be utilized.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Mineral wool materials shall be suitable for continuous service at temperatures from -
50°C to 650°C.
Mineral wool shall comply with the physical characteristics listed in ASTM C612, ASTM
C547 and ASTM C592, and shall, in addition, meet with the following requirements:
a. When tested in accordance with ASTM C871, chlorine contents shall be less than
10 ppm, fluoride shall be less than 10 ppm and total halide content shall not exceed
15 ppm.
b. Shot content: Less than 6% by weight of shot exceeding 250 microns when tested
in accordance with Section 14 of BS 2972, and less than 25% by of shot and/or
coarse fibers between 63 microns and 250 microns.
c. Total content of Sulphur compounds shall not exceed one half per cent by weight.
d. Alkalinity (pH) shall be between 7 and 8.
e. Binder: Resin impregnation shall be during manufacture prior to compressing and
curing.
f. Thermal conductivity, when tested in accordance with ASTM C177 or C518 at a
mean temperature, shall be no greater than the following:
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
properties and resistant to impact and abrasion damage, with a temperature limit not
less than 175°C for continuous service conditions. When dry, the cement shall be free
from cracking other than fine hairline cracks.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
f. Fabric break strength: 70 kg/cm minimum warp and fill per ASTM D579.
g. Service temperature range: -20°C to 93°C.
3.16. Cladding
The metal cladding weather barrier to provide protection from fire, weather, oil spillage,
mechanical wear or other damage shall be aluminized steel of the specified thickness
comprising cold rolled mild steel sheet to BS 1449 Part 1 Grade CR4, or a COMPANY
approved equivalent, hot dip coated with commercially pure aluminum or
aluminum/silicon alloy to a thickness of 89 microns including both sides, equivalent to a
weight of 240 – 270 g/m2 including both sides.
The exposed side of aluminized steel shall be coated with a 17 micron (5 micron primer
coat and 12 micron top coat) silver polyester resin, and back side of the aluminized steel
shall be protected with a 5 micron polyester resin coating. Color of the back side coating
shall be different from the exposed side for identification. Cut edges shall be coated, and
all damage to exterior coating shall be touch-up repaired, including damage from
banding or banding equipment.
The following are acceptable manufacturers:
a. Coated Metals Limited – “Aludip BQ”
b. Nisshin Steel Company
c. An equivalent approved by the purchaser.
Flat cladding shall be used to finish piping insulation. Nominal cladding thickness shall
be 0.6 mm for insulation O.D.'s up to and including 610 mm, 0.8 mm for insulation O.D.'s
exceeding 610 mm.
Flat cladding for vertical equipment with insulation O.D. of 762 mm or less and for all
insulated horizontal equipment shall be the same thickness as Article 3.16.4, 1,000 mm
wide flat sheet or coil.
Profiled cladding shall be used to finish insulation on vertical equipment shells where
insulation O.D. exceed 762 mm. Nominal cladding thickness shall be 0.8 mm.
Cladding shall be cut to suit support ring spacing. Profiled sheets shall be 762 mm
cover width, with 6 mm deep corrugations at 32 mm pitch. SUBCONTRACTOR shall
standardize on this profile throughout the project.
Profiled cladding specified in Article 3.16.6 for vertical equipment may be amended by
prior agreement with COMPANY to suit alternative commercially available sinusoidal or
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
trapezoidal profiles. Alternative profiles shall have a wind loading strength equal to or
better than the corrugated profile specified, and shall be capable of being lapped 1– 1/2
corrugations.
Cladding for top heads of vertical equipment, bottom heads of leg supported vertical
equipment, end heads of horizontal vessels, conical bottoms, stiffening rings and vessel
transitions, etc. shall be 0.8 mm nominal thickness flat sheet.
Removable metal covers for manholes, equipment flanges, piping flanges, flanged
valves and pumps shall be fabricated from flat sheets having 1.0 mm nominal
thicknesses.
All cladding shall be of prime quality material and shall be furnished factory coated.
Cladding that have not been passed by the manufacturer as "prime quality" and that are
marketed as "seconds", or that have deteriorated in storage are not acceptable.
3.17. Fasteners
Bands and seals for securing insulation and cladding shall be of stainless steel type 304
or 316 to ASTM A167 in the hot rolled annealed and descaled condition.
No burred edges of bands shall be allowed.
Twelve (12) mm wide x 0.4 mm nominal thickness stainless steel bands, shall be used
in the following locations:
a. All single layer pipe and equipment insulation up to 762 mm outside diameter.
b. All outer layers of multiple layer pipe and equipment insulation up to 762 mm outside
diameter.
c. All metal cladding on pipe and equipment up to 762 mm outside diameter.
d. For the fabrication of "S" clips for vertical pipe insulation cladding.
Twenty (20) mm wide x 0.5 mm nominal thickness stainless steel bands, shall be used
in the following locations:
a. All single layer pipe and equipment insulation exceeding 762 mm outside diameter.
b. All outer layers of multiple layer pipe and equipment insulation exceeding 762 mm
outside diameter.
c. All metal cladding on pipe and equipment exceeding 762 mm outside diameter.
Seals for bands shall be heavy duty wing type cut and formed from hard temper 0.8 mm
minimum thickness stainless steel.
Springs shall be compression type fabricated from type 304 or 316 austenitic stainless
steel and shall provide a band loading of approximately 1.43 kg/cm of compression.
Deleted
Wire fastening of piping and equipment insulation shall be soft annealed and shall be
limited to surfaces such as bottom heads within skirts where banding is impracticable,
and to the inner layer(s) of multiple layer insulation. Wire shall be stainless steel type
304 or 316 of the following diameters:
a. 1.2 mm diameter for surfaces up to 762 mm outside diameter.
b. 1.5 mm diameter for surface in excess of 762 mm outside diameter.
Wire mesh for the reinforcement of finishing cement shall be 25 mm hexagonal mesh
with 0.7 mm Monel or stainless steel wire.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
3.20. Screws
Self-tapping screws for the securement of metal cladding shall be type 304 or 316
stainless steel, 4.2 mm diameter x 12 mm long.
Screws shall have a cross recessed head slot "Pozidrive" pattern or equivalent and shall
be complete with tight fitting neoprene washers.
3.21. Pop-Rivets
Pop-rivets for the securement of metal cladding in locations where screws are
impracticable, shall be Monel or type 316 stainless steel. Rivets shall be of the self-
sealing type and shall be 4.0 mm diameter for all applications.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Use of materials other than those defined herein requires the prior written APPROVAL
of COMPANY.
Requests for substitution shall be included as an alternate in the bidder’s proposal.
Requests for substitutions after contract award are not acceptable.
3.26. Deleted
INSTALLATION REQUIREMENTS
4.1. General
Unless otherwise specified, installation requirements specified in Articles 4.1 through
4.9 pertain to all insulation types. Supplementary requirements for acoustic insulation
and storage tank are identified separately in Article 5.
Insulation shall be applied in accordance with BS 5970, good industrial practice and the
additional requirements specified herein. Finished insulation shall have a neat and
workmanlike appearance to the satisfaction of COMPANY.
Insulation work shall not be started until it has been ascertained that:
a. all appropriate testing has been completed, and
b. application of the specified protective coating system is complete and that any
damaged areas have been properly repaired.
SUBCONTRACTOR shall obtain a written APPROVAL from COMPANY authorizing the
start of insulation work. Such APPROVAL shall define the specific piping and/or
equipment items released for insulation.
With the exception of heat traced piping, piping shall generally be insulated
independently and may only be insulated collectively in specific cases where prior
APPROVAL is given by COMPANY.
Unless otherwise specified, insulation at the junction of insulated and uninsulated lines
shall extend to the first block valve of fitting in the uninsulated line.
The following items, but not be limited to, shall be insulated with removable flexible
insulation. Removable flexible insulation shall be used to the maximum extent.
a. Pipe flanges, flanged pipe fittings, flanged valves, manways, nozzles, heat
exchanger bonnets and channel sections, including channel covers, channel cover
flanges, channel flanges and companion shell flanges.
b. Removable metal boxed insulation may be used as an alternative where prior
approval is given by COMPANY.
Insulation on piping shall be stopped short of flanges, whether they are separately
insulated or not, and beveled back to allow for bolt removal. Adequate protection shall
be provided at these points and at any termination of the insulation to prevent the ingress
of water.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Vessel skirts over 1,000 mm outside diameter shall be insulated on the top inside and
outside surfaces. Smaller skirts shall be insulated on the outside only. Insulation shall
terminate at, or adjacent to, the lower insulation support.
SUBCONTRACTOR shall be responsible for inspecting support rings and/or studs
provided on equipment by the equipment fabricator, to ensure that these have been
installed to specified requirements and have not been damaged or dislodged during
transit/erection. SUBCONTRACTOR shall advise COMPANY immediately of any
remedial WORK that may be required prior to starting insulation work.
Only insulation and accessory materials that have been properly stored, kept dry and
are free from contamination shall be used.
Insulation, fabric and cladding shall be protected from mechanical damage during
construction. Damage by SUBCONTRACTOR shall be repaired without cost to
COMPANY. Damage by others shall be reported in writing to COMPANY.
Surfaces to be insulated shall be free from grease, dirt and other foreign matter.
a. The required degree of preparation for surfaces to be insulated shall be a
combination of hand brushing, dusting and hand application of grease cutting
solvent as found necessary and agreed on in advance with COMPANY.
b. Surfaces shall be thoroughly dry before starting insulation work.
c. The grease cutting solvent shall not contain any halogens and/or shall be
compatible with the paint or coating of the piping/equipment.
d. Surfaces which will not be painted are mentioned in the "Line Index". Before
starting the work, this shall be checked, and if unpainted surface which ought to be
painted is found, this shall be reported in writing to COMPANY.
During wet weather conditions, insulation shall be covered at all times with effective,
temporary polyethylene sheeting or temporary cladding until the final cladding has been
installed. Insulation installation during drizzle conditions may continue only at the
discretion of COMPANY.
Insulation shall be covered with cladding as soon as possible after installation. If it is
impractical to apply cladding, exposed insulation shall be temporarily protected with
moisture barrier, such as an appropriate polyethylene film sealed to the piping or
equipment surface. All exposed ends or edges of insulation shall be protected before
the end of each working day.
Cladding shall not be applied over damp insulation. The installation of cladding shall
be delayed until the insulation material has dried thoroughly. Insulation that has
deteriorated as a result of becoming wet or insulation that cannot be dried shall be
completely replaced, as directed by COMPANY.
The use of broken or defective insulation shall not be permitted. Cracks or voids in
installed insulation shall be permitted only where all reasonable precautions have been
taken to avoid them and they have been carefully packed with loose mineral wool.
Removable insulation shall be installed on the area where required for external
inspection or thickness measurements of piping and equipment on the locations
selected at site by COMPANY.
Removable insulation shall be of the same basic insulation and thickness as the rest of
the insulation and of sufficient rigidity to withstand handling.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
SUBCONTRACTOR shall make provision for the support of insulation and cladding on
vertical piping by supplying approved support rings as per Appendix 1, Figure 22 and
bolting these into position. Carbon steel support rings shall be supplied for carbon and
low alloy steel piping. Austenitic stainless steel support rings shall be furnished for
stainless steel and high alloy piping. Vertical spacing of support rings shall be as
specified in Table II, based on a multiple of 925 mm (1,000 mm cladding length less 75
mm overlap) with additional rings positioned at flanges, elbows, branches and tees) in
accordance with Appendix 1, Figures 23, 24 and 25.
a. Rings for carbon steel pipework shall be coated in accordance with Project Painting
Specification.
b. Stainless steel support rings shall not be painted.
TABLE II – SUPPORT RING SPACING
Pipe insulation half sections shall be placed around the pipe with circumferential joints
staggered by half the length of the section. Pipe insulation sections supplied as hinged
preformed sections shall be installed over horizontal pipe with the hinged portion
uppermost. All joints shall be tightly butted. Pipe insulation supplied as beveled lags
shall have joints tightly butted with circumferential joints staggered by half the length of
the lags.
Single layer sections and sections for the outer layer of multiple layer installations shall
be secured with stainless steel bands. Bands shall be located approximately 50 mm
from the end of each section and at intermediate intervals of 250 mm maximum. Bands
shall be machine tensioned and sealed. Inner layers of multiple layer installations shall
have sections secured with stainless steel wire ties. Wire ties shall be located
approximately 50 mm from the end of each section and at the approximate midpoint of
each section.
Longitudinal and circumferential joints in outer layers of multiple layer installations shall
be offset from those in adjacent inner layers by 90 degrees and half the section length,
respectively.
Expansion joints shall be provided below all insulation support rings on vertical piping.
Expansion joints shall consist of 25 mm installed thickness glass fiber blanket,
compressed 50 to 75 percent during installation of the adjacent pipe cover.
Insulation at flanged joints shall be stopped short of the bolts. Sufficient clearance shall
be left on at least one side of flanged connections for bolt removal without damage to
adjacent insulation. The bolts removal clearance left for all flanged connections except
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
those at compressors shall be approximately equal the bolt length plus 25 mm. The
clearance left at compressors shall be bolt length plus 100 mm.
Insulation on heat traced lines shall be oversized preformed mineral wool pipe sections
arranged to enclose both the line and its accompanying tracer. Oversized pipe
sections shall be installed to provide a snug fit over the pipe and tube bundle without
gaps in the longitudinal joints.
External tracer loops around pipe flanges and flanged valves in traced piping shall be
independently insulated for their full length. Flange and valves, if approved for
insulation, shall be independently insulated.
Oversized pipe sections may not be required where electric tracing consists of relatively
thin tape or cable. The inside or bore of pipe insulation section may be abraded or
scored to allow a good fit without open joints. Reductions of the insulation thickness in
excess of 6 mm shall not be permitted. SUBCONTRACTOR shall be responsible for
reviewing tracing information and supplying the correct insulation size.
The installation of preformed mineral wool may be impractical for some small bore, close
coupled piping and tubing. In such cases fiberglass tape insulation may be substituted,
where prior APPROVAL is obtained from COMPANY. The tape shall be spirally wound
to the required thickness and shall have ends securely wired into place.
Weatherproofing shall be obtained by an APPROVED reinforced mastic system.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
All cut outs around projections shall be sealed with a 3 mm minimum dry film thickness
of flashing compound. Cladding collars shall be fitted at locations where flashing
compound by itself is insufficient to prevent water ingress. Collars shall be sealed and
screwed to the main sheet metal and flashed with flashing compound.
"S" clips shall be introduced between individual lengths of metal cladding on vertical pipe
insulation to prevent telescoping. "S" clips shall be fabricated from 12 mm wide x 0.4
mm thick stainless steel band material. In addition, steel angle support clips shall be
pop-riveted to the internal face of the cladding, at locations coinciding with the insulation
support rings. Support clips shall be stopped short of the pipe wall by a minimum
distance of 12 mm.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
equipment shell diameter). Beveled lags shall be used for 1,800 mm diameter and
smaller shell sections where preformed pipe sections are not commercially available.
Rigid slabs shall be used for shell sections having outside diameters exceeding 1,800
mm.
a. Insulation shall be applied in one or more layers to the thicknesses specified. All
joints shall be carefully fitted. Circumferential joints shall be staggered for
horizontal equipment and longitudinal joints shall be staggered for vertical
equipment.
b. All joints in the outer layer of multiple layer installations shall be staggered with
respect to inner layer joints (staggered, broken block construction).
Insulation shall be secured with stainless steel bands, machine tensioned and sealed.
Bands shall be positioned at 250 mm centers on vertical equipment and at 300 mm
centers on horizontal equipment. Expansion band shall be used in case where the
relationship of diameter (meters) x temperature (°C) is equal to, or exceeds, 1,000.
Insulation shall be supported from insulation supports provided by the equipment
fabricator in accordance with Appendix 1, Figure 1 (vertical equipment) or Appendix 1,
Figure 2 (horizontal equipment) as appropriate.
Expansion joints shall be provided beneath insulation support rings on vertical
equipment. Expansion joints shall consist of 25 mm installed thickness glass fiber
blanket, compressed 50 to 75 percent during installation of the adjacent insulation.
Except as noted in Article 4.7.6 below, insulation for vessel and exchanger heads above
1,000 mm outside diameter shall be with rigid slabs. Slabs shall be secured with
stainless steel bands anchored at a stainless steel floating ring supplied by
SUBCONTRACTOR.
Insulation for bottom heads and inside skirt surfaces of vessels over 1,000 mm outside
diameter shall be either curved or standard flat bonded rigid slabs secured by stainless
steel wire or band to insulation rods provided by the equipment fabricator. The
insulation shall be finished with self-setting finishing cement applied over wire mesh.
Thickness of cement shall be adequate to fill in and key into the wire mesh and provide
an approximate 6 mm cover or cap over the outermost surfaces of the wire mesh.
Insulation for 1,000 mm outside diameter and smaller vessel and exchanger heads shall
be in the form of circular discs fabricated from slab insulation. Voids formed local to
the knuckle radius of the head shall be packed with loose mineral wool to an approximate
installed density of 140 - 200 kg/m3. Insulation discs shall retained with stainless steel
bands on the shell insulation which has been extended to enclose the discs in
accordance with Appendix 1, Figure 4.
Insulation at equipment flanges shall be stopped short of the bolts. Sufficient clearance
shall be left on at least one side of flanged connections for bolt removal without damage
to adjacent insulation. The bolt removal clearance left for all flanged equipment
connections except those at compressors shall be approximately equal the bolt length
plus 25 mm. The clearance left at compressors shall be bolt length plus 100 mm.
Insulation shall be fitted as closely as possible around equipment nozzles. All gaps
and crevices shall be packed with loose mineral wool to an approximate installed density
of 140 - 200 kg/m3.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Insulation on the shell sections of vertical equipment above 762 mm diameter shall be
finished with 0.8 mm thick corrugated aluminized steel sheets.
a. Sheets shall be lapped a minimum of 1– 1/2 corrugations vertically and 75 mm
horizontally and shall be installed weather side down.
b. Top sections of sheets shall be secured to support rings with stainless steel self-
tapping screws through valleys at 153 mm pitch.
c. Sheets shall be additionally secured through vertical overlaps with stainless steel
self-tapping screws at 150 mm pitch and with stainless steel bands at 450 mm
centers, including one band over each circumferential overlap. Bands shall be
machine tensioned and sealed.
Corrugated sheets on vertical equipment shall be supplied to suit support ring spacing.
No circumferential seam is allowed between support rings.
a. Sheeting installation shall start from the lowest course. Sheets shall be secured
from the top by screwing directly into the insulation support ring.
b. Subsequent courses shall also be progressively secured from the top by screwing
into the insulation support rings and allowing the bottom of the sheets to overlap
without screw fastening to the underlying sheet.
c. Weather resistant eaves filler strips of foamed plastic shall be incorporated beneath
corrugated cladding level with and at its termination at the bottom insulation support
ring. The filler strip shall be factory contoured to follow the metal cladding profile.
Insulation on the shell sections of horizontal equipment above 610 mm diameter shall
be finished with 0.8 mm thick flat aluminized steel sheeting. Sheets shall lapped a
minimum of 75 mm both circumferentially and longitudinally and shall be installed
weather side down.
a. Sheets shall be secured with stainless steel self-tapping screws at 150 mm pitch
through longitudinal overlaps and with stainless steel bands at 450 mm centers,
including one band over each circumferential overlap.
b. Bands shall be machine tensioned and sealed.
Heads of vertical and horizontal equipment and exchangers above 1,000 mm outside
diameter, other than those within a skirt, shall be finished with 0.8 mm thick flat
aluminized steel sheeting in radial segments from a central disc or ring.
a. Each segment shall be swaged and lapped a minimum of 50 mm and shall be
flashed over/under the shell cladding for a distance of 75 mm to preclude the entry
of rain water.
b. Fastening shall be by stainless steel self-tapping screws through overlaps and to
shell cladding at 100 mm centers.
Head insulation for 1,000 mm outside diameter and smaller equipment and exchanger
heads shall be finished with a flat metal end cap fabricated from 0.8 mm thick flat
aluminized steel sheeting incorporating a lock formed corner.
a. All overlaps shall be a minimum of 50 mm and shall be secured to the shell cladding
by stainless steel self-tapping screws.
Insulation over the remaining portions of 1,000 mm outside diameter and smaller
equipment shall be protected with aluminized steel cladding as described for pipe
insulation under Article 4.3.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Vessel manways, heat exchanger bonnets and channel sections, including channel
covers, channel cover flanges, channel flanges and companion shell flanges shall be
provided with removable flexible insulation. When prior APPROVAL is given by
COMPANY, these parts may be provided with weatherproof removable covers
constructed from specified thick aluminized steel flat sheeting with circumferential lock
formed joints.
a. Cover fabrication shall be one piece for manways and two or more pieces for heat
exchanger bonnets and channel sections. Covers shall be constructed with 25
mm overlaps and shall be secured in place with a sufficient quantity of stainless
steel quick release toggle fasteners to provide stability in service.
b. Removable covers covering flanged joints shall be provided with a drip tube at the
lowest point in accordance with Article 4.6.2.b.
c. Each cover section shall be provided with stainless steel lifting handles to facilitate
handling. Cover size and configuration shall allow easy handling by one or two
men.
d. Removable covers shall be lined on all internal surfaces with preformed mineral
wool rigid sections or slabs and a separate layer of stainless steel wire mesh on the
internal surface or hot face. Insulation thickness shall be equivalent to that applied
on adjacent piping. Metal tabs fabricated from aluminized steel sheet shall be
riveted to the inside of the boxes with Monel or type 316 stainless steel pop-rivets.
Tab length, quantity and placement shall be sufficient to firmly retain the insulation
and wire netting. Fastening insulation by an adhesive or by friction grip washers
attached to steel pins is not acceptable.
All overlaps in the cladding shall be sealed by the application of a gun extruded bead of
flashing compound. The bead shall be located within the ball swage provided at
circumferential and horizontal overlaps. The applied bead shall be a minimum 6 mm
diameter, or of sufficient diameter to provide an effective seal with the overlaps drawn
tight.
Due attention shall be paid to the fitting of cladding to ensure proper overlap of seams
and effective sealing where breaks in the cladding occur (e.g., nozzles, brackets,
supports, etc.) to ensure rapid water run-off and to prevent water ingress. Horizontal
cladding shall be sloped approximately 10 mm per meter to ensure rapid water run-off.
All cut outs around projections shall be sealed with a 3 mm minimum dry film thickness
of flashing compound. Cladding collars shall be fitted at locations where flashing
compound by itself is insufficient to prevent water ingress. Collars shall be sealed and
screwed to the main sheet metal and flashed with flashing compound.
a. Cut out in metal cladding to allow for protrusions such as nozzles, manways,
stairways, saddles and supports shall be made accurately and shall allow for
differential movement between the equipment and the cladding.
b. The cut edges of metal shall be free from any jagged edges or uneven cutting for
which purpose, actual work face snipping shall be kept to a minimum.
Exposed insulation faces at insulation terminations points occurring each side of
exchangers and other equipment flanges, manways, nozzles, etc. shall be provided with
aluminized steel end caps in accordance with Appendix 1, Figures 10, 11 and 13.
Expansion bands for retention of equipment cladding shall be used in cases where the
relationship of diameter (meters) x temperature (°C) is equal to, or exceeds, 1,000.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
SPECIAL REQUIREMENTS
5.1. Acoustic Insulation (Type 3A, 3B, 3C and Type 4A, 4B, 4C, 4D)
Requirements for acoustic insulation of piping shall be in accordance with those
specified for hot insulation under Material Requirements Article 3, Installation
Requirements Article 4, and the additional requirements of this Article.
Cladding for insulation Type 3 or 4, Class A or B applications shall be aluminized steel
sheet. Cladding for insulation Type 3 or 4, Class C applications only, shall consist of
an inner barium loaded vinyl sheet layer covered by aluminized steel sheet.
Anti-vibration seals shall be incorporated at all positions where metal to metal contact
between insulation cladding and the pipe/fitting or its attachments would normally occur.
Anti-vibration seals shall be in general accordance with Appendix 1, Figure 26. The
seals shall have a minimum thickness of 3 mm and a minimum width of 50 mm.
The termination of the cladding or lap onto the anti-vibration seal shall be in the form of
a profiled collar ring fabricated from cladding as per Appendix 1, Figure 26.
All gaps and voids in the insulation shall be filled with mineral wool loose fill and all
seams, overlaps and joints in the cladding shall be properly sealed with a 6 mm minimum
diameter continuous bead of flashing compound.
For Class Suffix B, C, and D locations on vertical pipes where angle support clips are
riveted to the inside of the cladding (i.e., positions coinciding with the insulation support
rings), shall have vibration isolating pads introduced between contact faces in
accordance with Appendix 1, Figure 29.
Insulation at trunnion type pipe supports shall be extended along the trunnion arms as
far as practical. Insulation shall be applied in the same fashion as that required for a
tee or branch connection in accordance with Appendix 1, Figure 16 except that the
termination shall be closed with an aluminized steel cap incorporating an anti-vibration
seal per Appendix 1, Figure 26.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Elbow anchors or trunnion supports for vertical pipes shall have insulation extended
down the trunnion leg as far as practical in accordance with Appendix 1, Figure 28. The
open end at the bottom shall be finished with aluminized steel cap incorporating anti-
vibration seal in accordance with Appendix 1, Figure 26.
Valves provided with removable insulation covers in accordance with Article 4.6 shall
have an anti-vibration seal incorporated in the annular space between the metal cover
and the valve stem.
End caps at valves or flanges shall have anti-vibration seals installed between the end
cap and the pipe.
Pipe support shoes shall be insulated as indicated in Appendix 1, Figure 27A.
When vibration-isolating pad is not provided between pipe shoes and structure, pipe
support shoe shall be insulated as indicated in Appendix 1, Figure 27 with the following
procedures:
a. SUBCONTRACTOR shall supply sufficient mineral wool pipe sections in two halves
and of the required thickness for the full length of pipe involved at each pipe support
position. Fifty percent of this material shall be made freely available for
COMPANY to form insulation cradles in combination with load bearing inserts for
bonding to the lower half bearing plate.
b. SUBCONTRACTOR shall complete the insulation and cladding over the top half,
and shall extend the cladding over the lower half bearing plate by 50 mm and retain
this in position with stainless steel bands.
c. All overlaps and terminations shall be made weatherproof with flashing compound.
d. The 7 mm thick steel cover plates supplied as a free issue by COMPANY, shall be
installed by SUBCONTRACTOR and shall be retained by two stainless steel bands
taken through the existing banding clips welded to the bearing plate.
e. The space between the aluminized steel cladding and the inside of the cover plate,
varying from 7 mm to 19 mm according to size, shall be progressively filled with
glass fiber blanket and the ends sealed with reinforced mastic.
Metal cladding over acoustic insulation on pipes shall be earthed using earthing wire of
minimum size 10 mm2, as follows:
a. Earthing wire shall be installed between the adjacent metal cladding for the intervals
of 25 to 30 meters.
b. The connection of the earthing wire to metal cladding may be carried out using self-
tapping screws.
c. Earthing wire shall be installed between metal cladding to earthing lug at each end.
Lead sheets for insulation Type 4. Class D, must not be burned to cut size and scraps
must be safely disposed.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Insulation on shell section of storage tank shall be secured with stainless steel bands
tightened between the vertical band rods provided by tank fabricator.
Insulation and metal sheeting on tank roof shall be secured using welded insulation pin
studs installed by tank fabricator.
Clips for studs shall be supplied by tank fabricator and installed by SUBCONTRACTOR.
Insulation shall be applied in accordance with Appendix 1, Figure 30.
6.2. Inspection
SUBCONTRACTOR shall advise COMPANY and allow ample notice before starting
specific insulation work.
COMPANY's inspector shall be afforded all reasonable facilities for carrying out his
duties in verifying that the insulation work is executed in accordance with the specified
requirements.
COMPANY's inspector shall have the right to inspect and test the insulation and cladding
at all stages, including any subsequent repairs. COMPANY's inspector may reject any
and all tools, instruments, materials, staging, equipment or work which does not conform
to this specification.
The acceptance or rejection of completed or partially completed insulation work is the
sole right of COMPANY or his representative.
SUBCONTRACTOR shall be responsible for the replacement and repair of any
insulation and/or cladding removed during COMPANY's inspection.
Any defective or rejected insulation and cladding as identified by markings made by
COMPANY's inspector, shall be repaired or replaced by SUBCONTRACTOR in
accordance with Article 6.3.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
TABLE III
* Insulation thickness for items having diameters above 144 inches (3,560 mm) shall be identical to
the thickness required for 144 inch diameter.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
TABLE IV
* Insulation thickness for items having diameters above 144 inches (3,560 mm) shall be identical to
the thickness required for 144 inch diameter.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
TABLE V
* Insulation thickness for items having diameters above 144 inches (3,560 mm) shall be identical to
the thickness required for 144 inch diameter.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
TABLE VI
* Insulation thickness for items having diameters above 144 inches (3,560 mm) shall be identical to
the thickness required for 144 inch diameter.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
TABLE VII
* Insulation thickness for items having diameters above 144 inches (3,560 mm) shall be identical to
the thickness required for 144 inch diameter.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
TABLE VIII
* Insulation thickness for items having diameters above 144 inches (3,560 mm) shall be identical to
the thickness required for 144 inch diameter.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
TABLE IX
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
* Insulation thickness for items having diameters above 144 inches (3,560 mm) shall be
identical to the thickness required for 144 inch diameter.
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement
Date : Aug. 09, 18 SPECIFICATION FOR THERMAL NFEF-60-00-SP-TS-NA-001
Information contained in this document is subject to use and disclosure restrictions under the Agreement