Table 3. Technical Data for PVGard 600 Vdc Per-Pole Solar PV Circuit Breakers
JG PVS KD PVS
Number of 600 Vdc circuits 3 3
Maximum voltage rating 600 Vdc 600 Vdc
Ampere range 90–250A 100–400A
Interrupting capacity at 600 Vdc 1.2 kA 3 kA
Time constant 1 ms 1 ms
Trip unit type Thermal-magnetic Thermal-magnetic
Rated impulse withstand voltage
Main conducting paths 8 kV 8 kV
Auxiliary circuits 4 kV 4 kV
Endurance
Mechanical operations 10,000 6000
Electrical operations 400 400
Maximum switching frequency 240 per hour 240 per hour
Third-party certification UL 489B UL 489B
Environment
Design ambient temperature 50°C 50°C
Maximum current at 60°C, as % of rated current 93% 93%
Maximum current at 70°C, as % of rated current 85% 85%
Operating temperature range –20°C to +50°C –20°C to +50°C
Storage temperature range –20°C to +70°C –20°C to +70°C
Suitable for freeze temperatures to –40°C Option Option
Relative humidity 0 to 95% noncondensing 0 to 95% noncondensing
Suitable for reverse-feed applications Yes Yes
Mounting—permissible mounting position
º
º
90
90
90
90
º
º
Connection diagrams
Load
2 eaton www.eaton.com
PVGard 600 and 1000 Vdc solar Technical Data TD01211004E
photovoltaic circuit breakers Effective February 2014
Dimensions
JG PVS 90–250A breaker outlines and drilling plans
4.13
(104.8)
3.57
2.06
(90.6)
(52.4)
1.38 3.34
(34.9) (84.9)
1.38
(34.9)
0.50
(12.7) Line End
0.78
(19.8)
1.91
(48.4) 0.38
(9.5)
6.50
(165.1) 3.95
(100.4)
4.99
6.28 On 23.5°
(126.8) 1.77
(159.5)
2.91 (45.0)
(73.8) 7.00 Tripped
(177.8) 10.5°
Handle
Off 4.0°
Pivot
0.99 1.98 3.97 A
(25.0) (50.4) Reset 6.4° 0.38
(100.7)
(9.5)
1.19 3.34
(30.2) (84.9)
0.59
(15.1) B
Dimensions for 0.50
Terminal Shield (12.7) 0.25
(6.4) Section A-A
Dimensions
Breaker Handle
Status A B Force, Lbs
3.44
(87.3) On 3.96 (100.7) 4.27 (108.4) 19
0.13
(3.2) Tripped 3.38 (85.8) 4.41 (112.0) —
1.94
(49.2) Off 2.71 (68.8) 4.41 (112.0) 14
0.63 Reset 2.60 (66.0) 4.39 (111.5) 21
(15.9)
Dimensions in parentheses in millimeters.
1.00
(25.4)
eaton www.eaton.com 3
Technical Data TD01211004E PVGard 600 and 1000 Vdc solar
Effective February 2014 photovoltaic circuit breakers
4.13
4.13 (104.8)
(104.8)
Line End 1.25
2.06 (31.8)
(52.4) 2.06 0.63
(52.4) (15.9)
0.78 Handle
(19.8)
R 0.19
(4.8) 3.95
(100.4)
3.95
(100.4)
0.91
2.08
(23.0)
2.56 (52.8)
7.00 (65.1)
5.50
(177.8) 3.06
(139.7) Handle Handle
(77.8)
4.13
7.00
(104.8)
(177.8)
Handle
0.69 2.00
(17.5) (50.8)
1.38
Load End (34.9) 4.00
(101.6)
4 eaton www.eaton.com
PVGard 600 and 1000 Vdc solar Technical Data TD01211004E
photovoltaic circuit breakers Effective February 2014
Time/current curves
10000
10
Time in Seconds
7x
1
+20%
–20%
0.1
Interruption rating
determines end of curve
0.01
0.001
1 10 100 1000 10000
eaton www.eaton.com 5
Technical Data TD01211004E PVGard 600 and 1000 Vdc solar
Effective February 2014 photovoltaic circuit breakers
PVGard 1000 Vdc
Technical data
Table 4. Technical Data for PVGard 1000 Vdc Solar PV Circuit Breakers (100% and 80% Rated Frames)
FD PV KD PV LG PV MDL PV
Number of poles 4 4 4 3
Maximum voltage rating 1000 Vdc 1000 Vdc 1000 Vdc 1000 Vdc
Maximum current rating 100A 350A 400A 600A
Interrupting capacity at 1000 Vdc 3 kA 5 kA 5 kA 7.5 kA
Time constant 1 ms 1 ms 1 ms 1 ms
Ampere range 15–100A 125–350A 250–400A 300–600A
Trip unit type Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic
Rated impulse withstand voltage
Main conducting paths 8 kV 8 kV 8 kV 8 kV
Auxiliary circuits 4 kV 4 kV 4 kV 4 kV
Endurance
Mechanical operations 10,000 10,000 8000 8000
Electrical operations 1000 400 400 400
Maximum switching frequency 300 per hour 240 per hour 240 per hour 240 per hour
Third-party certification UL 489B UL 489B UL 489B UL 489B
Environment
Design ambient temperature 50°C 50°C 50°C 50°C
Maximum current at 60°C, as % of rated current 91% 91% 93% 93%
Maximum current at 70°C, as % of rated current 88% 88% 88% 88%
Operating temperature range –20°C to +50°C –20°C to +50°C –20°C to +50°C –20°C to +50°C
Storage temperature range –20°C to +70°C –20°C to +70°C –20°C to +70°C –20°C to +70°C
Suitable for freeze temperatures to –40°C Option Option Option Option
Relative humidity 0 to 95% noncondensing 0 to 95% noncondensing 0 to 95% noncondensing 0 to 95% noncondensing
Suitable for reverse-feed applications Yes Yes Yes Yes
Mounting—permissible mounting position
º
º
90
90
90
90
º
º
Connection diagrams
Load
Load
(A) a b
Terminations
Al/Cu wire #6–300 kcmil (2) 3/0–250 kcmil (2) #2–500 kcmil (3) 3/0–400 kcmil
Cu wire #4–4/0 (2) 3/0–250 kcmil (2) #2–500 kcmil (3) 3/0–300 kcmil
Dimensions in inches (mm)
Height 6.00 (152.4) 10.13 (257.3) 10.13 (257.3) 16.00 (406.4)
Width 5.50 (139.7) 7.22 (183.4) 7.22 (183.4) 8.25 (209.5)
Depth 3.38 (85.9) 4.09 (103.9) 4.09 (103.9) 4.06 (103.1)
Weight in lbs 6 20 20 29
a Suitable for use on ungrounded systems, or grounded systems that have one end of load (A) connected to grounded terminal, opposite poles in series connection.
b Suitable for use on ungrounded systems only.
6 eaton www.eaton.com
PVGard 600 and 1000 Vdc solar Technical Data TD01211004E
photovoltaic circuit breakers Effective February 2014
Dimensions
FD PV four-pole breaker outlines and drilling plans
6X Ø 0.45 (11.43)
5.50
(139.7) Line End 3.50 (88.9)
2.06 (52.4)
1.03 0.75 0.47 3.39 (86.0)
1.38 1.38 1.38
(26.2) (19.1) (11.9) 3.19 (81.0)
(34.9) (34.9) (34.9)
1.41
(35.7) 0.27
4X R
0.16 (4.0) (6.8)
3.63
On (92.1)
Off 5.06
(128.6)
2.72
4.00
(69.1) 6.00
(101.6) 1.77
(152.4) On 14.9° Trip 6.2° (44.8)
4.50
(114.3)
Off 4.3°
Reset 6.5° Handle
0.27 Pivot
(6.7) A
1.00 (25.4)
0.50 (12.7)
0.19 (4.7)
0.37 (9.4)
Dimensions
Breaker Handle
Status A B Force, Lbs
On 2.91 (74.0) 4.02 (102.0) 14
0.08
(2.0)
Tripped 2.57 (65.2) 4.07 (103.4) 4
1.56 Off 2.14 (54.4) 4.07 (103.4) 16
(39.7) Reset 2.06 (52.2) 4.06 (103.1) 21
0.75
(19.1)
Dimensions in parentheses in millimeters.
0.74
(18.8)
0.50 (12.7) Wide Conductor
with Ø 0.25 (5.35) Hole Load End
Ø 0.219 (5.56) Hole Load End
eaton www.eaton.com 7
Technical Data TD01211004E PVGard 600 and 1000 Vdc solar
Effective February 2014 photovoltaic circuit breakers
2.75
(69.9) 1.19
1.38 (30.2)
(34.9) 0.60 R 0.25 (6.4)
Line End 0.69 6X Ø 0.16 (4.2)–32 Tap (15.2)
(17.5)
Handle
Handle
3.63
(92.1)
2.88
(73.0) 2.91
(73.8)
Handle
6.00 Handle
0.59
(152.4) 4.50 (15.1)
(114.3)
2.06
(52.4)
Load End 5.50
(139.7)
8 eaton www.eaton.com
PVGard 600 and 1000 Vdc solar Technical Data TD01211004E
photovoltaic circuit breakers Effective February 2014
KD PV four-pole breaker outlines and drilling plans
7.22
(183.4)
2.75 4.31
(69.9) Line End (109.6)
1.72 3.81
(43.7) (96.9)
0.84 0.62
1.72 1.72
(21.4) (15.9)
(43.7) (43.7)
7.41 8.44
(188.1) (214.3) 1.07
On/I
3.56 4.00 (27.1)
(90.5) (101.6) On 15.1° Tripped 5.6°
8.88
(225.4)
Off/O
R 0.25 Off 3.5° Reset 4.9°
(6.4) 10.12
2.39 (60.7) Handle
(257.2)
0.25 Pivot
1.25
(6.4) A
(31.8)
0.86
1.16 0.94 0.47
(21.8)
(29.4) (23.8) 1.72 Load End (11.9)
1.72 (43.7)
0.6
(43.7) 4.06
(1.6)
6X Ø 0.28 (7.1) Mounting Holes (103.2)
Ø 0.50 (12.7) 2.88 (73.0) from Top, Load End B
Ø 0.50 (12.7) 2.63 (66.7) from Top, Line End
Dimensions for Extended
Ø 0.44 (11.1) 0.75 (19.1) from Bottom Both Ends
Terminals and Barrier
for 0.25–20 x 1.50 (38.1) Mounting Screws
Style Numbers
4212B60G02, 2.44 (61.9)
4212B61G02 and 1.22 (31.0)
1492D24H01 0.44 (11.1)
0.88 (22.2) Dimensions
Breaker Handle
Status A B Force, Lbs
On 5.40 (137.1) 4.79 (121.6) 30
Tripped 4.77 (121.2) 4.91 (124.7) —
Off 4.16 (105.7) 4.93 (125.2) 25
3.81
(96.9) 0.19
Reset 4.07 (103.4) 4.92 (125.0) 35
(4.8)
2.38 Dimensions in parentheses in millimeters.
(60.3)
1.06
0.77 (27.0)
(19.5)
0.75 (19.1) Wide Conductor with
Ø 0.39 (9.9) Hole Line and Load End
eaton www.eaton.com 9
Technical Data TD01211004E PVGard 600 and 1000 Vdc solar
Effective February 2014 photovoltaic circuit breakers
3.44
(87.3) 2.63
1.72 (66.7)
(43.7) 6X Ø 0.25 (6.4) –20 Tap 1.31
Line End 0.86 (33.3)
(21.8)
Handle
R 0.34 (8.7)
Handle
5.77 4.92
(146.5) (125.0)
3.75
(95.3)
Handle
Handle
0.83
1.64 (21.0)
R 0.19
10.12 8.44 (41.7)
(4.8)
(257.2) (214.3)
1.25
(31.8)
2.39
2.75 (60.7)
(69.8) 4.78
Load End 7.22 (121.5)
(183.4)
10 eaton www.eaton.com
PVGard 600 and 1000 Vdc solar Technical Data TD01211004E
photovoltaic circuit breakers Effective February 2014
LG PV four-pole breaker outlines and drilling plans
7.22 4.31
(183.4) (109.4)
2.75 4.06
1.72 (69.9) Line End (103.2)
(43.7)
1.72
(43.7) 1.75 0.84 0.63
1.72 (44.5) (21.4) (15.9)
(43.7)
3.72 0.44
(94.4) (11.1)
R 0.25 5.58
(6.4) 8.88 (141.7)
(225.4)
7.28
2.17
(184.9) 3.04 8.44 On 17.4° Tripped 5.0° (55.2)
(77.1) (214.4)
7.23 10.13
(257.2) Reset 18.0° Off 14.2°
(183.7)
Handle
1.59 Pivot
(40.4) A
1.19
Ø 0.44 0.41
2.13 (30.2) 0.86
(11.1) Load End (10.3)
(54.0) (21.8) 1.72
(43.7)
1.72 0.06
4.06
(43.7) 6X Ø 0.22 (5.5) Mounting Holes (1.6)
(103.2)
Ø 0.44 (11.1) 0.55 (13.9) from Top, Load End
Dimensions for Ø 0.44 (11.1) 0.62 (15.9) from Top, Line End B
Extended Terminals Ø 0.21 (5.3) 0.50 (12.7) from Bottom Both Ends
and Barrier for M5 x 0.8 x 100 mm Mounting Screws
Section A-A
Style Number 2.31 (58.6)
69D4557 1.15 (29.3)
0.59 (15.0)
1.18 (23.0)
Dimensions
Breaker Handle
Status A B Force, Lbs
3.98 On 5.32 (135.1) 5.34 (135.6) 44
(101.2) 0.13 Tripped 4.62 (117.4) 5.43 (137.9) —
(3.2)
2.38 Off 3.55 (90.0) 5.27 (133.9) 56
(60.3)
Reset 3.34 (84.9) 5.20 (132.1) 45
1.34 Dimensions in parentheses in millimeters.
0.85 (34.1)
(21.5)
0.97 (24.6) Wide Conductor with
Ø 0.52 (13.1) Hole Line and Load End
eaton www.eaton.com 11
Technical Data TD01211004E PVGard 600 and 1000 Vdc solar
Effective February 2014 photovoltaic circuit breakers
3.44 2.70
(87.3) (68.6)
6X M5 X 0.8
1.72 1.35
Line End (43.7) 0.86 (34.3)
(21.8)
Handle Handle
R 0.28 (7.0)
5.58
(141.7) 4.73
(120.2)
3.34
(84.8)
Handle
Handle
8.44
(214.3) 1.64 1.33
(41.7) (33.9)
10.13
(257.2)
1.58
(40.2)
2.67
2.75 (67.8)
7.06
(69.9)
Load End 7.22 (179.3)
(183.4)
12 eaton www.eaton.com
PVGard 600 and 1000 Vdc solar Technical Data TD01211004E
photovoltaic circuit breakers Effective February 2014
MDL PV three-pole breaker outlines and drilling plans
8.25
4.13 (209.6) 4.38
(104.8) 0.63 (111.1)
2.75 2.75 Line End 4.06
(15.9)
(69.9) (69.9) (103.2)
1.19
(30.2)
6.44
(163.6)
8.30
R 0.25 (210.9)
(6.4) 14.75
(374.7)
1.38 0.06
4X Ø 0.38 (9.5) Mounting Holes 4.06
(34.9) (1.6)
1.38 Ø 0.74 (18.7) 3.33 (84.6) from Top (103.2)
(34.9) Ø 0.59 (15.1) 0.36 (9.1) from Bottom B
for 0.31 (7.9)–16 x 1.75 (44.5) Mounting Screws
Section A-A
1.87
(47.6) 0.53
(13.5)
1.88 (47.6) Wide Conductor with
Ø 0.42 (10.6) Hole Line and Load End
eaton www.eaton.com 13
Technical Data TD01211004E PVGard 600 and 1000 Vdc solar
Effective February 2014 photovoltaic circuit breakers
2.75
Line End (69.9) 4X Ø 0.31 (7.9) 3.44
1.38 (87.3)
(34.9) 1.72
(43.7)
Handle Handle
7.68
8.30
(195.0)
(210.9)
R 0.25
(6.4)
3.28
Handle (83.3)
14.75 Handle
16.00 (374.7)
(406.4) 1.33
2.29
(33.7)
(58.2)
R 0.19
(4.8)
1.50
(38.1)
4.13
(104.8) 3.64
8.25 (92.5)
(209.6)
7.28
(184.9)
Load End
14 eaton www.eaton.com
PVGard 600 and 1000 Vdc solar Technical Data TD01211004E
photovoltaic circuit breakers Effective February 2014
Time/current curves
10,000
Minimum
10
Time in Seconds
1.000
7x
+20%
–20%
0.100
Interruption rating
determines end of curve
0.010
0.001
100 1,000 10,000 100,000 1,000,000
Current in Percent of Breaker Trip Unit Rating (In)
eaton www.eaton.com 15
Technical Data TD01211004E PVGard 600 and 1000 Vdc solar
Effective February 2014 photovoltaic circuit breakers
10,000
Maximum
Minimum
10
Time in Seconds
7x
+20%
1.000 –20%
Interruption rating
0.100 determines end of curve
0.010
0.001
1 10 100 1000 10,000
16 eaton www.eaton.com
PVGard 600 and 1000 Vdc solar Technical Data TD01211004E
photovoltaic circuit breakers Effective February 2014
10,000
10
Time in Seconds
7x
+20%
–20%
0.1
0.01
0.001
100 1000 10,000 100,000
eaton www.eaton.com 17
Technical Data TD01211004E PVGard 600 and 1000 Vdc solar
Effective February 2014 photovoltaic circuit breakers
18 eaton www.eaton.com
PVGard 600 and 1000 Vdc solar Technical Data TD01211004E
photovoltaic circuit breakers Effective February 2014
eaton www.eaton.com 19
Technical Data TD01211004E PVGard 600 and 1000 Vdc solar
Effective February 2014 photovoltaic circuit breakers
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2014 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. TD01211004E / Z14800 All other trademarks are property
February 2014 of their respective owners.