Vous êtes sur la page 1sur 40

Katherm HK


Trench systems

Katherm HK
Heating and cooling with energy efficient
EC cross-flow fan
Technical catalogue
2 Rubrik | Dies ist das Thema Kampmann technical catalogue – Katherm HK

Kampmann.co.uk/katherm_hk
Kampmann technical catalogue – Katherm HK 3

Contents
01    Product information 6

Overview 7
Product data 8
Selection aids: Summary of versions 9
Katherm HK at a glance 10
Grilles 12
Katherm HK with supply air function 14

02    Performance data 16

Information on test conditions 17


Katherm HK 320, 2-pipe, trench height 130 mm 18
Katherm HK 340, 2-pipe, trench height 190 mm 20
Katherm HK 320, 4-pipe, trench height 130 mm 22
Katherm HK 340, 4-pipe, trench height 190 mm 24

03    Design information 26

Information on design and sizing 27


Water connection – pipe inlets/outlets 28

04    Control equipment  29

KaControl 29
Routing cables 31

05    Ordering information 34

Katherm HK 34
Accessories 35
4 Kampmann technical catalogue – Katherm HK

Katherm HK:
Demand-dependent
heating and cooling
from low level, with
individual control
Kampmann technical catalogue – Katherm HK 5

In the new ADAC centre in Munich,


a bespoke version of the Katherm HK
trench system with energy efficient EC
cross-flow fans ensures quiet operation
and energy savings. This trench version
channels filtered, heated or cooled
ambient air from the floor in line with
the current demand. In this project,
Katherm HK and Katherm HK ducts are
matched individually to the polygonal
external façade.
6 Product information Kampmann technical catalogue – Katherm HK

01 Product information
Kampmann technical catalogue – Katherm HK Product information | Overview 7

01  Product information


Katherm HK – decentralised room climate from

02  Performance data


low level
In modern buildings with a high EC technology
Even at low air flow rates, EC fans with intelligent,
proportion of glass façades, areas integrated output electronics can be operated
providing heating and cooling in variably at low speeds in line with demand, which

03  Design information


offers great energy efficiency. Low speeds have a
front of windows are frequently positive effect in areas when it comes to noise, the
unacceptable for aesthetic reasons. level of which is far below that perceivable by
humans and the common measuring range.
At the same time the demand for air
conditioning increases. Katherm HK is available ex works with integrated
KaControl equipment, as an option the KaController
The demand-dependent supply of heated or cooled enables up to six units to be operated in a standalone
ambient air with Katherm HK through the floor solves group. Optional interfaces enable the units to be

04  Control equipment


both problems simultaneously and is practically linked with higher ranking automation systems such
invisible. A higher level of efficiency is achieved by as KNX, Modbus or LON. The units are also available
the EC cross-flow fan. Compared to conventional with a BMS interface: power supply 230 V / 50%.
fans, energy savings of up to 60 % are not Fan speed control 20-100% via 0-10 VDC BMS
uncommon. New flow-optimised barrel fans in a contact.
cascade arrangement guarantee that the convector
receives an optimum air flow across its entire length.

05  Ordering information


Cooling installation example, 4-pipe Heating installation example, 2-pipe Cooling installation example with
(installed in screed, (installed in a raised floor, supply air function
trench height 130 mm) trench height 130 mm) (installed in a raised floor,
trench height 190  mm)

Exterior window Exterior window Exterior window

Air discharge Air intake Air discharge Air intake Air discharge Air intake

6 5 5
3 4 2 2
4 5 3 3
4

1
2 1
1

1 Thermal and impact sound insulation 1 Concrete slab 1 Concrete slab


2 Concrete slab 2 Raised floor 2 Raised floor
3 Screed 3 Floor duct 3 Floor duct
4 Floor duct 4 High performance convector 4 High performance convector
5 High performance convector 5 Filter (option) 5 Filter (option)
6 Filter (option)
8 Product information | Product data Kampmann technical catalogue – Katherm HK

Product data

Product benefits
Heating and cooling, may be selected as
2- and 4-pipe system
Complies with hygiene requirements to
VDI 6022
Quiet high efficiency EC cross-flow fan

Characteristics

Standard range Convection EC cross-flow fan Grille versions


2 trench widths, 2 trench heights, Heating LPHW Roll-up grilles
6 or 3 trench lengths. In addition to Cooling CHW Linear grilles
the standard range (NP), products can Ventilation supply air connection
also be manufactured to order in line on request
with the bespoke range (MP). KaControl optional
System 2-pipe
4-pipe

Performance data

Heating output1) [W] Sound pressure level3) [dB(A)]


923 – 9223 23 – 34

Cooling capacity2) [W] Sound power level [dB(A)]


230 – 1507 31 – 42

Applications

All areas of buildings where higher


cooling loads occur due to internal
loads and insolation. Experience has
shown that the Katherm HK can Hotels/ Retail chains Offices and Residential Pubs/
achieve affordable, effective cooling at motels commercial buildings restaurants
buildings
a noise level which is so low that it will
not be perceived as a nuisance.

1) for the LPHW 75 / 65, tL1 = 20 °C; speed set to 60 %


2) for the CHW 16 / 18, tL1 = 27 °C, 48 % relative humidity; speed set to 60 %
3) The sound pressure level was calculated with an assumed interior attenuation of 8 dB(A). This equates to a distance of 2 m,
an interior volume of 100 m³ and a reverberation period of 0.5 seconds (to VDI 2081); speed set to 60 %.
Kampmann technical catalogue – Katherm HK Product information | Selection aids: summary of versions 9

01  Product information


Selection aids: summary of versions

Trench Trench Trench Heating Cooling Sound pressure Sound power Additional
Version width height 2-/4-pipe length output1) capacity2) level3) level information

[mm] [mm] [mm] [W] [W] [dB(A)] [dB(A)]

 915 690 – 2075 87 – 360 <204) – 39 <284) – 47

02  Performance data


1200 1176 – 3602 150 – 634 <204) – 41 <284) – 49
1700 2135 – 6040 272 – 1064 <204) – 41 <284) – 49
2-pipe Page 18
2000 2404 – 7512 310 – 1342 <204) – 44 <284) – 52
2500 3363 – 10026 429 – 1765 <204) – 44 <284) – 52
3000 4324 – 12479 552 – 2188 <204) – 44 <284) – 52
HK 320 320 130
 915 530 – 1206 87 – 355 <204) – 39 <284) – 47
1200 936 – 2180 149 – 624 <204) – 41 <284) – 49
1700 1720 – 3787 272 – 1047 <204) – 41 <284) – 49
4-pipe Page 22
2000 1985 – 4755 305 – 1321 <204) – 44 <284) – 52

03  Design information


2500 2773 – 6361 428 – 1738 <204) – 44 <284) – 52
3000 3561 – 7967 550 – 2155 <204) – 44 <284) – 52

1250 1655 – 4761 250 – 870 <204) – 35 <284) – 43


2-pipe 2000 2886 – 8302 435 – 1516 <204) – 38 <284) – 46 Page 20
2750 4117–  11842 621 – 2163 <204) – 39 <284) – 47
HK 340 340 190
1250 1334 – 2897 291 – 913 <204) – 35 <284) – 43
4-pipe 2000 2326 – 5051 507 – 1591 <204) – 38 <284) – 46 Page 24
2750 3318 – 7205 723 – 2270 <204) – 39 <284) – 47

04  Control equipment


Katherm HK, Stand 2015/03

05  Ordering information


Sectional views
Katherm HK, Stand 2015/06

Katherm HK 320, trench height 130 mm, Katherm HK 340, trench height 190  mm, 2-pipe Katherm HK 340, trench height 190  mm, 4-pipe
example 2-pipe

1) for the LPHW 75 / 65, tL1 = 20 °C


2) for the CHW 16 / 18, tL1 = 27 °C, 48 % relative humidity
3) The sound pressure level was calculated with an assumed interior attenuation of 8 dB(A). This equates to a distance of 2 m,
an interior volume of 100 m³ and a reverberation period of 0.5 seconds (to VDI 2081).
4) Sound pressure level < 20 dB (A) and sound power level < 28 dB (A) outside the usual measuring and audible range.
10 Product information | Katherm HK at a glance Kampmann technical catalogue – Katherm HK

Katherm HK at a glance
1 Floor duct 3 Connection and 5 High performance 7 Filter
controller box coil

2 Frame profile 4 Condensate tray 6 Separating panel 8 High efficiency EC cross-flow


fan

10 Positive fixing

Characteristics

3 6 8

9 11 12
Kampmann technical catalogue – Katherm HK Product information | Katherm HK at a glance 11

01  Product information


A Roll-up grille:
aluminium, natural, anodised
(example)

02  Performance data


11 Condensate pump mounting set
(accessory)

03  Design information


13 Height adjustment

04  Control equipment


05  Ordering information
1 Floor duct: 5 High performance coil: 8 High efficiency EC cross-flow 11 Condensate pump mounting
made from sendzimir galvanized made from round copper pipes fan: set:
steel with aluminium fins energy saving, with flow- as an accessory, for draining
coated on both sides in graphite coated in graphite grey optimised impellers in a cascade condensate, where required
grey suitable for a maximum arrangement as a continuous fan supplied separately or fitted at
operating pressure of 10 bar at arrangement the factory
2 Grille frame profile: 120 °C even flow through the convector
a colour to match the grille with anti-twist protection robust motor design for quiet 12 Cross-flow fan fixing:
with protective strip on three Eurocone connection running easy maintenance of the
sides for 2- and 4-pipe system variable speed control by means cross-flow fan without tools
of external 0 – 10 V signal new combined coupling/ball pin
3 Connection and controller box: 6 Separating panel: motor monitoring with internal system
for quick and secure electrical acts simultaneously as finger fault processing simultaneous sound insulation
connection; saves installation protection for the cross-flow fan,
time filter frame, air deflector, grille 9 Cover plate: 13 Height adjustment:
KaControl or BMS interface support and cross-brace to acts as visual guard and for height adjustment and
strengthen the trench protection against dirt support of the trench
4 Condensate tray:
for reliable draining of 7 Filter: 10 Height adjustable mounting A Roll-up grille: aluminium,
condensate and simultaneous air optional accessory bracket: natural, anodised (example):
guiding for safely supporting the trench grille dimensions 18 x 5 mm
specifically designed for easy with sound insulation made from corrosion protected
cleaning in line with the hygiene steel spiral springs with colour
guideline VDI 6022 matched spacers
free area approx. 70 %
12 Product information | Grilles Kampmann technical catalogue – Katherm HK

Suitable grilles
Roll-up grilles
Aluminium Aluminium Aluminium
Natural anodised Brass anodised Bronze anodised

Aluminium Aluminium Aluminium


Black anodised Bronze finish Painted DB 703 (gray)

Stainless steel Stainless steel Brass


Natural Polished Natural CuZn 44
Kampmann technical catalogue – Katherm HK Product information | Grilles 13

01  Product information


02  Performance data
Linear grilles
Aluminium Aluminium Aluminium Aluminium
Natural anodised Brass anodised Bronze anodised Bronze finish

03  Design information


04  Control equipment
for further grille versions see
Profile dimensions Kampmann.co.uk/products/grilles/

The grilles shown here have been


I-beam sections represented in four colour prints and are
12 therefore not exact replications of the
original colour.
18

05  Ordering information


5
14 Product information | Katherm HK with supply air function Kampmann technical catalogue – Katherm HK

Katherm HK with supply air function optional

The Katherm HK with supply air Supply air function


The pre-conditioned supply air is generally at a lower
function1) is highly suitable for temperature level than the room air. In the Katherm
inducing pre-conditioned supply HK it is routed through a separate air duct. It escapes
by means of a discharge slot arranged over the
air into the interior. This creates an length of the floor trench. Prior to discharge into the
optimum combination of heating, room it is mixed with the ambient air heated or
cooled by the coil. This creates an optimum air
cooling and air supply. curtain effect in front of window areas with low
turbulence and low air velocity in occupied spaces.
The air ducts for primary air and the flexible pipes on
the floor trench can be optimally routed inside a
raised floor. Versions for pressurized floor voids are
available upon request.

The Katherm HK versions with supply air can be


designed to each individual project. Further details on
request.

1) for Katherm HK 340, trench height 190 mm


Kampmann technical catalogue – Katherm HK Product information | Katherm HK with supply air function 15

01  Product information


02  Performance data
Supply air Maximum air
Trench length ­connector DN 801 ­volume per trench

[mm] [pce.] [m³ / h]


1250 2 120
2000 3 180

03  Design information


2750 4 240

Sectional view (example with roll-up grille) This only applies for 190 mm high trenches. Alternatives on request.

Trench length K Window side

Finned convector length K-430

04  Control equipment


Room side
Plan view (Katherm HK 340 with supply air function, trench height 190 mm)

05  Ordering information


1 Supply air duct
5 2 Flexible pipe
3 Spigot on
Katherm HK
4 Raised floor
6 5 Façade
6 Katherm HK
7 Recirc. air
8 Air discharge
4
1 8
7

1 Max. air volume per supply air connector DN 80 = 60 m³/h.

Alternative supply air connectors and air volumes on request.


16 Performance data Kampmann technical catalogue – Katherm HK

02 Performance data
Kampmann technical catalogue – Katherm HK Performance data | Information on test conditions 17

01  Product information


Information on test conditions

02  Performance data


Heating output and cooling capacities The Katherm HK has been developed and constructed
Heating output and cooling capacities have been for optimum “short cut” performance and therefore
tested in accordance with EN 16430 “Fan assisted minimises this “short cut” as far as is technically
radiators, convectors and trench convectors”. possible.

Part 1 “Technical specifications and requirements” Acoustic performance


Part 2 “Test procedure and assessment of the heating The Katherm HK is frequently used in acoustically
output” sensitive areas. Accordingly, the Katherm HK has been
Part 3 “Test procedure and assessment of the cooling sound optimised. The sound power level is tested in

03  Design information


capacity” line with EN ISO 3744 (Determination of sound power
levels and sound energy levels of noise sources using
This standard specifically regulates how the output of sound pressure – Engineering methods for an
trench convectors is tested under practical conditions essentially free field over a reflecting plane) in a semi-
based on EN  442 “Radiators and connectors”. low-reflection sound test chamber.

Part 1 “Technical specifications and requirements”


Part 2 “Test procedure and assessment of the
performance”

04  Control equipment


EN 16430 Part 3 considers the specific requirements
for cooling operation. The reference air temperature is
measured in the centre of the test cabin (2 m away
from the wall) at a height of 0.75 m. This reference air
temperature should not be confused with the air
intake temperature.
This may be substantially different on account of the
unavoidable “short circuit” between the air discharge

05  Ordering information


and the air intake.

The heating loads are provided by 10 dummies with


regulated output (see photograph) inside the test cabin
in such a way that they will not influence output and
functions at all or not to a reproducible magnitude. Heating output and cooling capacity test cabin

Vergleich
Vergleich
Luftströmungsprofile
Comparison ofLuftströmungsprofile
air flow profiles

In the case of air discharges, not optimised to In the case of air discharges, optimised to
prevent “short circuits” prevent “short circuits”

Façade surface temperature Façade surface temperature


28 °C 28 °C
1800 mm (1500 - 2100 mm)

1800 mm (1500 - 2100 mm)

Reference air temperature Reference air temperature


28 °C 28 °C
150 – 300 mm

approx. 500 – 800 mm


750 mm

750 mm
700 mm

700 mm

750 mm

750 mm
approx.

17 °C 17 °C
14 °C 14 °C
26 °C 26 °C
23 °C 23 °C

18 °C 18 °C 25 °C 25 °C
CHW 6/12
2 °C
m 2m CHW 6/12 °C 2m 2m

Bei nicht kurzschlussoptimiertem


Bei nicht kurzschlussoptimiertem
Luftaustritt Luftaustritt Bei kurzschlussoptimiertem
Bei kurzschlussoptimiertem
Luftaustritt Luftaustritt
18 Performance data | Katherm HK 320, 2-pipe, trench height 130 mm Kampmann technical catalogue – Katherm HK

Katherm HK 320
2-pipe, trench height 130 mm

Technical drawings (all dimensions in mm)

Window side
Front view
Sectional view
(example with roll-up grille)

Window side
Trench length K
302 Finned convector length K-540 238

Room side
Plan view (without cover)

Performance data Water pressure drop


100

Connections: 6 12
50 5 11
Eurocone, same end, 40 4 10
connection on the left 30 3 9
2 8
20
1 7
Condensate connection:
Spigot, 15 mm 10
Water pressure drop heating / cooling RH, RC [kPa]

5 Heating curve:
Fan motors
convector

4
­impellers

1 Trench length 915 mm


3
Finned
Trench
length

length

2 Trench length 1200 mm


Fan

2 3 Trench length 1700 mm


4 Trench length 2000 mm
[mm] [mm] [pce.] [pce.] 5 Trench length 2500 mm
 915  375 1 1 1 6 Trench length 3000 mm
1200  660 2 1
0.5 Cooling curve:
1700 1160 3 1 0.4 7 Trench length 915 mm
2000 1460 4 2 0.3 8 Trench length 1200 mm
9 Trench length 1700 mm
2500 1960 5 2 0.2 10 Trench length 2000 mm
3000 2460 6 2 11 Trench length 2500 mm
0.1 12 Trench length 3000 mm
100 200 300 400 500 600 800 1000
Use our web-based calculation program
Heating medium/CHW flow rate mH, mC [l/h]
in order to calculate the heating output
or cooling capacity as well as heating
medium and chilled water rates with just
a few clicks.
kampmann.co.uk/kathermhk/
calculation
Kampmann technical catalogue – Katherm HK Performance data | Katherm HK 320, 2-pipe, trench height 130 mm 19

01  Product information


Performance data

Sound power level


Sound pressure
­consumption  3)

Air flow rate 6)


consumption

02  Performance data


Heat output1) Cooling capacity 2)
Fan speed
Fan level

current
Power

level 4)
at LPHW at LPHW at CHW at CHW
75 / 65 °C 82 / 71 °C  16 / 18 °C 7 / 12 °C 

QH tL2 QH tL2 QK QS tL2 QK QS tL2 P I


[%] [W] [°C] [W] [°C] [W] [W] [°C] [W] [W] [°C] [W] [mA] [m3/ h] [dB(A)] [dB(A)]
Trench length 915 mm
Power level 100 2075 56.0 2361 61 360 360 20.1 623 536 15.8 7.9 82 175 39 47
Design levels 80 1779 57.9 2023 63,1 300 300 19.6 519 436 15.2 6.5 67 140 33 41

03  Design information


60 1442 59.6 1639 65,1 232 232 19.3 405 331 14.5 5.6 58 110 27 35
40 1079 61.6 1225 67,3 158 158 18.8 284 226 13.7 5.0 52 80 <205) <285)
Minimum level 20 690 64.3 783 70,3 87 87 18.2 167 128 12.8 4.7 49 50 <205) <285)
Trench length 1200 mm
Power level 100 3602 57.5 4089 62,6 634 634 19.6 1211 957 14.8 11.4 118 285 41 49
Design levels 80 3079 59.4 3495 64,7 524 524 19.2 995 773 14.2 8.4 86 235 36 44
60 2483 61.0 2817 66,5 402 402 18.8 765 584 13.5 6.5 67 180 29 37
40 1850 62.9 2098 68,6 272 272 18.4 528 396 12.8 5.5 57 130 20 28
Minimum level 20 1176 65.3 1333 71,3 150 150 17.9 306 225 11.9 4.9 51 80 < 205) < 285)

04  Control equipment


Trench length 1700 mm
Power level 100 6040 58.8 6848 64 1064 1064 19.2 2124 1602 13.9 16.4 169 465 41 49
Design levels 80 5611 59.8 6360 65,2 963 963 19.0 1919 1437 13.7 13.3 137 420 38 46
60 4523 61.5 5126 67 738 738 18.6 1464 1082 13.0 9.0 93 325 31 39
40 3365 63.3 3813 69,1 498 498 18.2 1004 732 12.2 6.5 67 235 23 31
Minimum level 20 2135 65.7 2417 71,7 272 272 17.8 579 416 11.5 5.3 55 140 < 205) < 285)
Trench length 2000 mm
Power level 100 7512 59.1 8513 64,3 1342 1342 19.1 2736 2040 13.8 22.9 237 575 44 52
Design levels 80 6394 60.9 7245 66,3 1094 1094 18.8 2221 1638 13.2 16.7 173 470 39 47

05  Ordering information


60 5132 62.3 5814 68 834 834 18.5 1684 1228 12.6 13.0 135 365 32 40
40 3807 64.1 4312 70 568 568 18.1 1148 827 11.9 11.0 114 260 23 31
Minimum level 20 2404 66.3 2721 72,4 310 310 17.7 658 470 11.2 9.8 102 155 < 205) < 285)
Trench length 2500 mm
Power level 100 10026 59.8 11356 65,1 1765 1765 19.0 3637 2680 13.5 27.8 288 750 44 52
Design levels 80 8937 60.8 10123 66,2 1535 1535 18.8 3151 2306 13.1 21.6 224 650 40 48
60 7177 62.3 8128 67,9 1170 1170 18.4 2388 1728 12.5 15.5 160 505 33 41
40 5325 64.1 6030 69,9 786 786 18.1 1626 1165 11.6 12.0 124 360 25 33
Minimum level 20 3363 66.3 3806 72,4 429 429 17.6 932 661 11.1 10.2 106 220 < 205) < 285)
Trench length 3000 mm
Power level 100 12479 60.0 14132 65,4 2188 2188 18.9 4538 3319 13.3 32.7 339 925 44 52
Design levels 80 11480 60.8 13002 66,2 1976 1976 18.8 4085 2974 13.0 26.5 275 840 41 49
60 9223 62.3 10445 67,9 1507 1507 18.4 3094 2230 12.4 17.9 185 650 34 42
40 6845 64.1 7749 69,9 1012 1012 18.0 2106 1504 11.7 12.9 134 465 26 34
Minimum level 20 4324 66.3 4893 72,4 552 552 17.6 1206 853 11.0 10.6 110 280 < 205) < 285)

QH [W] = heat output; QC [W] = cooling capacity, total; QS [W] = cooling capacity, sensible; tL2 [°C] = leaving air temperature

1) atan room air temperature of tL = 20 °C;  


2) atan room air temperature of tL = 27 °C; relative humidity 48 %
3) For each valve actuator, type 146906, add an additional power consumption of 3 W.
4) The sound pressure level was calculated with an assumed interior attenuation of 8 dB(A). This equates to a distance of 2 m,

an interior volume of 100 m³ and a reverberation period of 0.5 seconds (to VDI 2081).
5) Sound pressure level < 20 dB (A) and sound power level < 28 dB (A) outside the usual measuring and audible range.
6) Values rounded within measuring tolerances.
20 Performance data | Katherm HK 340, 2-pipe, trench height 190 mm Kampmann technical catalogue – Katherm HK

Katherm HK 340
2-pipe, trench height 190 mm

Technical drawings (all dimensions in mm)

Window side
Front view Sectional view
(example with roll-up grille)

Trench length K Window side

Finned convector length K-449

Room side
Plan view (without cover)

Performance data Water pressure drop

30 4 1
Connections: 6 3
1/2”, same end, to the left viewed 5 2
20
from the room interior
Water pressure drop heating / cooling RH, RC [kPa]

10
Condensate connection:
Spigot, 15 mm 5
4
3
2
Fan motors
convector

­impellers

Heating curve:
Finned
Trench
length

length

1
1 Trench length 1250 mm
Fan

2 Trench length 2000 mm


0.5 3 Trench length 2750 mm
[mm] [mm] [pce.] [pce.] 0.4
1250 820 1 1 0.3
Cooling curve:
2000 1570 2 2 0.2 4 Trench length 1250 mm
2750 2320 3 3 5 Trench length 2000 mm
0.1 6 Trench length 2750 mm
50 60 80 100 200 300 400 500 600 800 900
Heating medium/CHW flow rate mH, mC [l/h]
Use our web-based calculation program
in order to calculate the heating output
or cooling capacity as well as heating
medium and chilled water rates with just
a few clicks.
kampmann.co.uk/kathermhk/
calculation
Kampmann technical catalogue – Katherm HK Performance data | Katherm HK 340, 2-pipe, trench height 190 mm 21

01  Product information


Performance data

Sound power level


Sound pressure
­consumption  3)

Air flow rate 6)


consumption

02  Performance data


Heat output1) Cooling capacity 2)
Fan speed
Fan level

current
Power

level 4)
at LPHW at LPHW at CHW at CHW
75 / 65 °C 82 / 71 °C  16 / 18 °C 7 / 12 °C 

QH tL2 QH tL2 QK QS tL2 QK QS tL2 P I


[%] [W] [°C] [W] [°C] [W] [W] [°C] [W] [W] [°C] [W] [mA] [m3/ h] [dB(A)] [dB(A)]
Trench length 1250 mm
Power level 100 4761 57.2 6251 60,3 870 870 20.4 1819 1197 17.9 16.6 144 390 35 43
Design levels 80 4115 58.8 5177 62,8 724 724 20.4 1523 986 18.0 10.9 101 325 30 38

03  Design information


60 3335 60.9 3871 66,1 562 562 20.3 1190 756 18.0 7.7 76 250 23 31
40 2553 63.0 2310 70,4 410 410 20.3 877 543 18.3 5.4 60 185 < 205) < 285)
Minimum level 20 1655 65.7 981 74,4 250 250 20.3 544 327 18.2 4.4 52 110 < 205) < 285)
Trench length 2000 mm
Power level 100 8302 57.2 10877 60,3 1516 1516 20.4 3165 2083 17.9 29.7 244 680 38 46
Design levels 80 7169 58.8 9008 62,8 1263 1263 20.4 2650 1716 18.0 19.5 163 565 32 40
60 5815 60.9 6736 66,1 980 980 20.3 2071 1315 18.0 12.7 115 435 25 33
40 4451 63.0 4019 70,4 714 714 20.3 1526 945 18.2 8.7 86 320 < 205) < 285)
Minimum level 20 2886 65.7 1707 74,4 435 435 20.3 947 569 18.1 6.8 73 190 < 205) < 285)

04  Control equipment


Trench length 2750 mm
Power level 100 11842 57.2 15565 60,3 2163 2163 20.4 4529 2981 17.9 39.6 369 970 39 47
Design levels 80 10226 58.8 12891 62,8 1801 1801 20.4 3792 2455 18.0 25.6 239 805 34 42
60 8296 60.9 9639 66,1 1398 1398 20.3 2963 1882 18.1 16.2 151 625 27 35
40 6349 63.0 5752 70,4 1019 1019 20.3 2184 1352 18.1 10.8 101 450 20 28
Minimum level 20 4117 65.7 2443 74,4 621 621 20.3 1355 814 18.2 8.1 76 275 < 205) < 285)

QH [W] = heat output; QC [W] = cooling capacity, total; QS [W] = cooling capacity, sensible; tL2 [°C] = leaving air temperature

05  Ordering information

1) atan room air temperature of tL = 20 °C;  


2) atan room air temperature of tL = 27 °C; relative humidity 48 %
3) For each valve actuator, type 146906, add an additional power consumption of 3 W.
4) The sound pressure level was calculated with an assumed interior attenuation of 8 dB(A). This equates to a distance of 2 m,

an interior volume of 100 m³ and a reverberation period of 0.5 seconds (to VDI 2081).
5) Sound pressure level < 20 dB (A) and sound power level < 28 dB (A) outside the usual measuring and audible range.
6) Values rounded within measuring tolerances.
22 Performance data | Katherm HK 320, 4-pipe, trench height 130 mm Kampmann technical catalogue – Katherm HK

Katherm HK 320
4-pipe, trench height 130 mm

Technical drawings (all dimensions in mm)

Window side
Front view
Sectional view
(example with roll-up grille)

Window side
Trench length K
302 Finned convector length K-540 238

Room side
Plan view (without cover)

Performance data Water pressure drop 6 5 4 3


100 10
2 9
1 8
50 12
Connections: 40 7 11
Eurocone, alternate sides 30
20

Condensate connection:
Water pressure drop heating / cooling RH, RC [kPa]

10
Spigot, 15 mm
Heating curve:
5 1 Trench length 915 mm
4 2 Trench length 1200 mm
3 3 Trench length 1700 mm
Fan motors
convector

4 Trench length 2000 mm


­impellers

2
Finned

5 Trench length 2500 mm


Trench
length

length

6 Trench length 3000 mm


Fan

1
[mm] [mm] [pce.] [pce.] Cooling curve:
0.5 7 Trench length 915 mm
 915  375 1 1 0.4 8 Trench length 1200 mm
1200  660 2 1 0.3
9 Trench length 1700 mm
1700 1160 3 1 0.2 10 Trench length 2000 mm
11 Trench length 2500 mm
2000 1460 4 2
0.1 12 Trench length 3000 mm
2500 1960 5 2
10 20 30 50 100 200 300 500 1000
3000 2460 6 2 Heating medium/CHW flow rate mH, mC [l/h]

Use our web-based calculation program


in order to calculate the heating output
or cooling capacity as well as heating
medium and chilled water rates with just
a few clicks.
kampmann.co.uk/kathermhk/
calculation
Kampmann technical catalogue – Katherm HK Performance data | Katherm HK 320, 4-pipe, trench height 130 mm 23

01  Product information


Performance data

Sound power level


Sound pressure
­consumption  3)

Air flow rate 6)


consumption

02  Performance data


Heat output1) Cooling capacity 2)
Fan speed
Fan level

current
Power

level 4)
at LPHW at LPHW at CHW at CHW
75 / 65 °C 82 / 71°C  16 / 18 °C 7 / 12 °C 

QH tL2 QH tL2 QK QS tL2 QK QS tL2 P I


[%] [W] [°C] [W] [°C] [W] [W] [°C] [W] [W] [°C] [W] [mA] [m3/ h] [dB(A)] [dB(A)]
Trench length 915 mm
Power level 100 1206 40.9 1379 43,9 355 355 20.2 609 531 15.9 7.9 82 175 39 47
Design levels 80 1072 42.8 1226 46,1 297 297 19.7 511 433 15.3 6.5 67 140 33 41

03  Design information


60 923 45.4 1054 49 230 230 19.3 402 330 14.6 5.6 58 110 27 35
40 748 48.9 855 53 158 158 18.8 284 226 13.7 5.0 52 80 <205) <285)
Minimum level 20 530 54.0 605 58,8 87 87 18.2 168 129 12.7 4.7 49 50 < 205) < 285)
Trench length 1200 mm
Power level 100 2180 42.7 2482 45,8 624 624 19.7 1174 943 15.0 11.4 118 285 41 49
Design levels 80 1933 44.7 2200 45,1 518 518 19.3 973 766 14.4 8.4 86 235 36 44
60 1657 47.3 1886 51,1 399 399 18.9 754 580 13.6 6.5 67 180 29 37
40 1336 51.0 1520 55,2 271 271 18.5 525 395 12.8 5.5 57 130 20 28
Minimum level 20 936 56.1 1064 61 149 149 17.9 306 225 11.9 4.9 51 80 < 205) < 285)

04  Control equipment


Trench length 1700 mm
Power level 100 3787 44.3 4301 47,6 1047 1047 19.3 2057 1577 14.2 16.4 169 465 41 49
Design levels 80 3566 45.3 4050 48,8 951 951 19.1 1866 1419 13.9 13.3 137 420 38 46
60 3054 48.0 3468 51,8 732 732 18.8 1438 1073 13.1 9.0 93 325 31 39
40 2459 51.7 2792 55,9 495 495 18.3 994 728 12.3 6.5 67 235 23 31
Minimum level 20 1720 56.8 1952 61,8 272 272 17.8 577 415 11.5 5.3 55 140 < 205) < 285)
Trench length 2000 mm
Power level 100 4755 44.8 5397 48,1 1321 1321 19.2 2646 2006 14.0 22.9 237 575 44 52
Design levels 80 4205 46.9 4771 50,5 1082 1082 18.9 2167 1618 13.4 16.7 173 470 39 47

05  Ordering information


60 3589 49.6 4073 53,6 828 828 18.5 1657 1218 12.7 13.0 135 365 32 40
40 2871 53.3 3257 57,7 558 558 18.1 1138 824 12.0 11.0 114 260 23 31
Minimum level 20 1985 58.2 2251 63,3 305 305 17.7 656 469 11.2 9.8 102 155 < 205) < 285)
Trench length 2500 mm
Power level 100 6361 45.3 7214 48,6 1738 1738 19.1 3519 2635 13.8 27.8 288 750 44 52
Design levels 80 5849 46.7 6633 50,3 1516 1516 18.9 3067 2273 13.4 21.6 224 650 40 48
60 4996 49.4 5665 53,4 1161 1161 18.5 2344 1713 12.6 15.5 160 505 33 41
40 4001 53.1 4537 57,5 783 783 18.1 1609 1159 11.9 12.0 124 360 25 33
Minimum level 20 2773 58.1 3142 63,2 428 428 17.7 927 659 11.1 10.2 106 220 < 205) < 285)
Trench length 3000 mm
Power level 100 7967 45.6 9032 49 2155 2155 19.1 4392 3265 13.6 32.7 339 925 44 52
Design levels 80 7496 46.6 8498 50,2 1951 1951 18.9 3971 2933 13.3 26.5 275 840 41 49
60 6405 49.4 7259 53,3 1494 1494 18.5 3034 2207 12.6 17.9 185 650 34 42
40 5133 53.0 5818 57,4 1007 1007 18.1 2082 1494 11.8 12.9 134 465 26 34
Minimum level 20 3561 58.1 4035 63,2 550 550 17.6 1199 850 11.1 10.6 110 280 < 205) < 285)

QH [W] = heat output; QC [W] = cooling capacity, total; QS [W] = cooling capacity, sensible; tL2 [°C] = leaving air temperature

1) atan room air temperature of tL = 20 °C;  


2) atan room air temperature of tL = 27 °C; relative humidity 48 %
3) For each valve actuator, type 146906, add an additional power consumption of 3 W.
4) The sound pressure level was calculated with an assumed interior attenuation of 8 dB(A). This equates to a distance of 2 m,

an interior volume of 100 m³ and a reverberation period of 0.5 seconds (to VDI 2081).
5) Sound pressure level < 20 dB (A) and sound power level < 28 dB (A) outside the usual measuring and audible range.
6) Values rounded within measuring tolerances.
24 Performance data | Katherm HK 340, 4-pipe, trench height 190 mm Kampmann technical catalogue – Katherm HK

Katherm HK 340
4-pipe, trench height 190 mm

Technical drawings (all dimensions in mm)

Window side
Front view Sectional view
(example with roll-up grille)

Window side
Trench length K

Finned convector length K-449

Room side
Plan view (without cover)

Performance data Water pressure drop


3 2 1 4
6
30
5
Connections:
1/2”, same end, to the left viewed
20
from the room interior
Water pressure drop heating / cooling RH, RC [kPa]

10
Condensate connection:
Spigot, 15 mm 5
4
3
2
Fan motors
convector

­impellers

Heating curve:
Finned
Trench
length

length

1
1 Trench length 1250 mm
Fan

2 Trench length 2000 mm


0.5 3 Trench length 2750 mm
[mm] [mm] [pce.] [pce.] 0.4
1250 820 1 1 0.3
Cooling curve:
2000 1570 2 2 0.2 4 Trench length 1250 mm
2750 2320 3 3 5 Trench length 2000 mm
0.1 6 Trench length 2750 mm
50 60 80 100 200 300 400 500 600 800 900
Heating medium/CHW flow rate mH, mC [l/h]
Use our web-based calculation program
in order to calculate the heating output
or cooling capacity as well as heating
medium and chilled water rates with just
a few clicks.
kampmann.co.uk/kathermhk/
calculation
Kampmann technical catalogue – Katherm HK Performance data | Katherm HK 340, 4-pipe, trench height 190 mm 25

01  Product information


Performance data

Sound power level


Sound pressure
­consumption  3)

Air flow rate 6)


consumption

02  Performance data


Heat output1) Cooling capacity 2)
Fan speed
Fan level

current
Power

level 4)
at LPHW at LPHW at CHW at CHW
75 / 65 °C 82 / 71 °C  16 / 18 °C 7 / 12 °C 

QH tL2 QH tL2 QK QS tL2 QK QS tL2 P I


[%] [W] [°C] [W] [°C] [W] [W] [°C] [W] [W] [°C] [W] [mA] [m3/ h] [dB(A)] [dB(A)]
Trench length 1250 mm
Power level 100 2897 42.5 3638 43,4 913 913 20.0 1813 1366 16.6 16.6 144 390 35 43
Design levels 80 2624 44.6 3211 43,4 774 774 19.9 1562 1153 16.5 10.9 101 325 30 38

03  Design information


60 2266 47.7 2626 51,1 615 615 19.7 1266 910 16.2 7.7 76 250 23 31
40 1864 51.5 1795 59 461 461 19.4 971 678 16.1 5.4 60 185 < 205) < 285)
Minimum level 20 1334 56.9 882 68,8 291 291 19.2 638 430 15.4 4.4 52 110 < 205) < 285)
Trench length 2000 mm
Power level 100 5051 42.5 6330 43,4 1591 1591 20.0 3155 2377 16.6 29.7 244 680 38 46
Design levels 80 4574 44.6 5587 46,4 1350 1350 19.9 2718 2006 16.5 19.5 163 565 32 40
60 3952 47.7 4569 51,1 1072 1072 19.7 2203 1583 16.2 12.7 115 435 25 33
40 3251 51.5 3123 59 803 803 19.4 1690 1180 16.1 8.7 86 320 < 205) < 285)
Minimum level 20 2326 56.9 1535 68,8 507 507 19.2 1110 748 15.3 6.8 73 190 < 205) < 285)

04  Control equipment


Trench length 2750 mm
Power level 100 7205 42.5 9059 43,4 2270 2270 20.0 4514 3401 16.6 39.6 369 970 39 47
Design levels 80 6525 44.6 7995 46,4 1925 1925 19.9 3889 2871 16.4 25.6 239 805 34 42
60 5637 47.7 6539 51,1 1530 1530 19.7 3152 2266 16.2 16.2 151 625 27 35
40 4637 51.5 4470 59 1146 1146 19.4 2418 1688 15.9 10.8 101 450 20 28
Minimum level 20 3318 56.9 2196 68,8 723 723 19.2 1589 1071 15.4 8.1 76 275 < 205) < 285)

QH [W] = heat output; QC [W] = cooling capacity, total; QS [W] = cooling capacity, sensible; tL2 [°C] = leaving air temperature

05  Ordering information

1) atan room air temperature of tL = 20 °C;  


2) atan room air temperature of tL = 27 °C; relative humidity 48 %
3) For each valve actuator, type 146906, add an additional power consumption of 3 W.
4) The sound pressure level was calculated with an assumed interior attenuation of 8 dB(A). This equates to a distance of 2 m,

an interior volume of 100 m³ and a reverberation period of 0.5 seconds (to VDI 2081).
5) Sound pressure level < 20 dB (A) and sound power level < 28 dB (A) outside the usual measuring and audible range.
6) Values rounded within measuring tolerances.
26 Design information Kampmann technical catalogue – Katherm HK

03 Design information
Kampmann technical catalogue – Katherm HK Design information | Information on design and sizing 27

01  Product information


02  Performance data
Information on design and sizing
The Katherm HK is suitable for all The sound pressure level is not only influenced by the
Katherm HK but also from the number of units as
areas of buildings where cooling well as to a great extent by the acoustic properties of
loads occur. the room. Values may, therefore, in practice deviate

03  Design information


from those stated.
Generally these are arranged immediately on the
perimeter. The Katherm HK can achieve affordable It is therefore recommended, when sizing the
effective cooling, particularly in the case of larger Katherm HK, to take into consideration the
glass façades. respectively permissible sound pressure level in the
interior.
Air discharge
Katherm HK 320 with a trench height of 130 mm or Heat output and cooling capacity
the HK 340 with a trench height of 190 mm are The heat output and cooling capacities have been

04  Control equipment


arranged towards the façade together with the determined in line with EN 16430. For conversion to
convector. The high air flow rate would result in a other operating conditions we recommend our
loss of comfort inside the zone of activity if they were web-based calculation programs at kampmann.co.uk/
arranged inside the room. kathermhk/calculation.

Acoustic performance Comfort levels


When sizing please note that high speeds can result Comfort levels were determined with reference to
in noise levels which could be perceived as a EN ISO 7730 (May 2006) “Ergonomics of the thermal
nuisance. The respective sound power levels of a environment -- Analytical determination and

05  Ordering information


Katherm HK are listed in tables (see Performance interpretation of thermal comfort using calculation of
data). The sound pressure level was calculated with the PMV and PPD indices and local thermal comfort
an assumed interior attenuation of 8 dB(A). This criteria” (ISO 7730:2004).
equates to a distance of 2 m, an interior volume of
100 m³ and a reverberation period of 0.5 seconds (to
VDI 2081).

Use our web-based calculation program


in order to calculate the heating output
or cooling capacity as well as heating
medium and chilled water rates with just
a few clicks.
kampmann.co.uk/kathermhk/
calculation
28 Design information | Water connection – pipe inlets/outlets Kampmann technical catalogue – Katherm HK

372

372

372
Water connection – Flow/Return connections
372

Katherm HK 340, 2-pipe, trench height 190 mm Katherm HK 340, 4-pipe, trench height 190 mm
372 372
Window side Window side

3 2
1 2 1
2 3
3 1
4 4 2

372
302
Plan view Plan view

1 Valve body 1/2”, straight version, 1 Valve body 1/2”, straight version,
type 146909 or type 346909 type 146909 or type 346909
372(on site)
2 extension, 65 mm 2 extension, 65 mm (on site)
302
3 RSV, 1/2”, straight version, type 145952 3 RSV, 1/2”, straight version, type 145952
4 Thermoelectric actuator, type 146906 4 Thermoelectric actuator, type 146906

Katherm HK 320, 2-pipe, trench height 130 mm Katherm HK 320, 4-pipe, trench height 130 mm

302 302 238


Window side Window side

1 1 1
3 4 4

302 2238
302 2 3

Plan view Plan view

1 Valve body 1/2”, axial version, 1 Valve body 1/2”, axial version,
type 246909 or type 346911 type 246909 or type 346911
302 238
2 RSV, 1/2”, angle version, type 145953 2 RSV, 1/2”, straight version, type 145952
3 Thermoelectric actuator, type 146906 3 RSV, 1/2”, angle version, type 145953
4 Thermoelectric actuator, type 146906

302 238
Kampmann technical catalogue – Katherm HK Control equipment | KaControl 29

04

01  Product information


Control equipment

02  Performance data


KaControl – the in one solution for Katherm HK
Katherm HK with KaControl Temperature control with modulating fan
support
equipment is fully wired and supplied Depending on the actual heat demand of the interior,
ready to connect. the Katherm HK is initially operated in heating mode

03  Design information


without fan-assist. On demand, the energy efficient
Each Katherm HK includes internal fuse protection. EC cross-flow fan is regulated with variable speed to
A powerful microprocessor with programmable back up the heating function. In cooling mode, the
parameters covers all required functions. controller works in reverse, but always fan-assisted.
Consequently, each Katherm HK has its own
“intelligence” and can be operated in groups via
Kampmann networks.

Building automation hook-up BMS interface

04  Control equipment


Katherm HK with KaControl can also be equipped The units come on standart with BMS interface
with plug-in communication interfaces for single Power supply 230 V / 50 ....
room control via CAN bus or for a hook-up to higher Fan speed control 20-100% via 0-10 VDC
ranking control systems: KNX, Modbus and LON. BMS-signal.

KaControl functions for Katherm HK


The programmable KaControl offers many different
functions:
Options: 5 fan stages, manually adjustable

05  Ordering information


Valve control for 2-pipe/4-pipe applications Electrical data
(heating/cooling) for thermoelectric valve drives
24 V DC Open/Close
consumption

consumption

Motor monitoring with fault message processing


voltage

Current
Supply
Trench
length

Power

[mm] U [V] P [W] I [mA]


Katherm HK 320, Height 130 mm
915 230 7,9 82

1200 230 11,4 118

1700 230 16,4 169

2000 230 22,9 237

2500 230 27,8 288

3000 230 32,7 339


Katherm HK 340, Height 190 mm
1250 230 16,6 144

2000 230 29,7 244

2750 230 39,6 369

The power and current consumption of the actuators (3W) and the
KaControl controller (1W) has not been considered.
30 Control equipment | KaControl Kampmann technical catalogue – Katherm HK

KaController

The interface of the KaControl building automation


system: the KaController.

The KaController offers maximum user convenience


with its generously sized display screen and operation
via a single selector. Following the principle “As little
as possible, as much as necessary”, even users that
have not been trained can quickly and intuitively
master the available control options.

The principal functions for a pleasant climate are


adjusted via the user friendly KaController.

Product features
Programming units for wall mounting in a high
quality design
Available with or without lateral function keys
Plastic casing in a colour similar to RAL 9010
Communication interface to the Kampmann T LAN
bus system
Generously sized display screen with automatic
backlighting
Integral room temperature sensor
Push and turn navigator with endless turn/lock
function
Integral 7-day switching program
Password-protected programming level
Kampmann technical catalogue – Katherm HK Control equipment | Cable routing 31

01  Product information


Cable routing
Single circuit control – system configuration

02  Performance data


Multi function inputs
Options:
KaController Optional: Room temperature sensor
Example type 3210001 Type 3250110 Digital input 1 Digital input 2
Alternative type 3210002 e.g. remote on/off e.g. window contact

03  Design information


Maximum
2 ** cable length
3 **
30 m

2 **
-C1
2 **

#1

04  Control equipment


3 

2 ** Mains 230 V/50 Hz


For more than 6 and up to 30 Katherm HK
with CAN bus module (accessory)
3 **
-C1 -C1 Maximum cable
length 30 m
Bus cable, up to
300 m with CAN bus
module

05  Ordering information


2  #1 #2 to #30
3 ** CAN bus module
3 
Type 3260301
Mains 230 V/50 Hz

3 
2 **
Mains 230 V/50 Hz
-C1

#1

3 

Mains 230 V/50 Hz

Provide a separate power supply when using a condensate pump.

** Cabling must be compliant with CAT5 (AWG 23 or similar).


Please note: Wire all bus cables linearly – star patterns are not permissible.
32 Control equipment | Cable routing Kampmann technical catalogue – Katherm HK

System configuration BMS interface

External
automation module

Heating
0...10 V switching
0 – 3 V unit OFF
3 – 4 V heating valve OPEN, fan OFF
4 – 9 V heating valve OPEN, fan 0 – 100 %

Cooling
0...10 V switching
0 – 3 V unit OFF
3 – 4 V cooling valve OPEN, fan OFF
4 – 9 V cooling valve OPEN, fan 0 – 100 %
Note: In cooling mode the fan must always run.
The control sequence of the BMS kicks in at a
control voltage of 4 V DVC.
2** 2**

-C1

Internal resistance of the analogue input on


the KaControl PCB: 20 kilohms

3 
2** 2**
Mains 230 V/50 Hz

To further Katherm.
Maximum number of Katherm dependent on the breaking
capacity of the analogue output of the automation
module.

Provide a separate power supply when using a condensate pump.

** Cabling must be compliant with CAT5 (AWG 23 or similar).


Kampmann technical catalogue – Katherm HK Control equipment | Cable routing 33

01  Product information


System configuration BMS interface

02  Performance data


External automation module

Heating valve
Switching 0...10 V or open/close
(dependent on external control system)

03  Design information


Cooling valve
Switching 0...10 V or open/close
(dependent on external control system)

04  Control equipment


2** 2** 2**

-00

Internal resistance of the analogue input of

05  Ordering information


the EC fans
Trench height 130 mm: 100 kilohms
Trench height 190  mm:   67 kilohms
3 
2** 2** 2**
Mains 230 V/50 Hz

To further Katherm.
Maximum number of Katherm dependent on the breaking
capacity of the analogue output of the automation
module.

Provide a separate power supply when using a condensate pump.

** Cabling must be compliant with CAT5 (AWG 23 or similar)..


34 Ordering information | Katherm HK Kampmann technical catalogue – Katherm HK

05 Ordering information

Katherm HK
KaControl version
As standard, the trench systems are supplied with an natural
anodised aluminium grille. However, this can be replaced for an
Trench height

Grille version

additional charge by one of the following grilles. To select an


Trench width

alternative grille, on your order please change the two red digits
2-/4-pipe

to the left of the red line in the product no.


Type

Article no.

[mm] [mm]
Trench lengths 915 mm, 1200 mm, 1700 mm, 2000 mm, 2500 mm, 3000 mm
Roll-up grille 1433223111 13C1 11 12 13 14 15
2-pipe
Linear grille 1433223311 13C1
HK 320 320 130
Roll-up grille 1433243111 13C1
4-pipe
Linear grille 1433243311 13C1
16 31 32 33
Trench lengths 1250 mm, 2000 mm, 2750 mm
Roll-up grille 1430629111 20C1 Product key, grille replacement (sample product no.)
2-pipe
Linear grille 1430629311 20C1
HK 340 340 190
Roll-up grille 1430649111 20C1
4-pipe 1433223111 13C1 Aluminium, natural anodised (standard)
Linear grille 1430649311 20C1 12 Aluminium, brass anodised
13 Aluminium, bronze anodised
14 Aluminium, black anodised
15 Aluminium, bronze finish
Electromechanical version 16 Aluminium, painted DB 703
31 Stainless steel, natural
32 Stainless steel, polished
33 Brass, natural CuZn 44
Trench height

Grille version
Trench width

2-/4-pipe
Type

Article no.
HK 320 is delivered in lengths of 915 mm to 3000 mm. The
[mm] [mm] available trench lengths for HK 340 are staggered in 750 mm
segments (1250 mm to 2750 mm). To select the required trench
Trench lengths 915 mm, 1200 mm, 1700 mm, 2000 mm, 2500 mm, 3000 mm
length, on your order please change the two red digits to the
Roll-up grille 1433223111 1300 right of the red line in the product no.
2-pipe
Linear grille 1433223311 1300
HK 320 320 130
Roll-up grille 1433243111 1300
4-pipe
Linear grille 1433243311 1300 Product key, trench length (sample product no.)
Trench lengths 1250 mm, 2000 mm, 2750 mm HK 320:
Roll-up grille 1430629111 2000
2-pipe 1433223111 13C1 Trench length   915 mm
Linear grille 1430629311 2000
HK 340 340 190 19 Trench length 1200 mm
Roll-up grille 1430649111 2000 29 Trench length 1700 mm
4-pipe
Linear grille 1430649311 2000 35 Trench length 2000 mm
45 Trench length 2500 mm
55 Trench length 3000 mm

HK 340:

1430629111 20C1 Trench length 1250mm


35 Trench length 2000 mm
50 Trench length 2750 mm
Kampmann technical catalogue – Katherm HK Ordering information | Accessories 35

01  Product information


Accessories
Image Product Features Suitable for Article no.
KaControl accessories
Programming unit for wall mounting in a high grade
design, plastic casing, in a colour similar to RAL 9010,
large LCD multi function display, integral room
temperature sensor, communication interface to the

02  Performance data


KaController Kampmann T LAN bus system, automatically controlled
All model sizes 196003210001
with single selector LED backlighting, push and turn navigator with endless
turn/lock function, individually programmable standard
display, integral day, night and 7-day switching
program, password-protected programming level, for
controller level C1

For rapid access to the fan setting,


KaController operating modes, eco mode,
All model sizes 196003210002
with lateral function keys Time and time switching program, otherwise similar to
product no. 196003210001

03  Design information


For wall mounting, IP 30 surface mounted, RAL 9010
Room temperature
white, as an alternative to the temperature sensor in All model sizes 196003250110
sensor
the KaController

For capturing the media temperature, including


Pipe contact sensor retaining strap, lead lengths 3 m, to provide frost All model sizes 196003250115
protection for the unit

04  Control equipment


For extending the number of units controlled in a
Serial CAN bus module All model sizes 196003260301
single circuit

Serial Modbus module For linking to Modbus networks All model sizes 196003260101

05  Ordering information


Serial Konnex module For linking to KNX/EIB networks All model sizes 196003260701

Serial LON FTT10A


For linking to LON FTT10A network All model sizes 196003260501
module

     Cont.  »
36 Ordering information | Accessories Kampmann technical catalogue – Katherm HK

Image Product Features Suitable for Article no.


Valves

Valve body
HK 320 194000246909
axial, ½” connection As a low noise, flow optimised design with stainless
steel shaft and double O-ring seal suitable for Katherm
HK with actuator, product no. 194000146906,
max. operating temperature 120 °C,
Valve body
max. operating pressure 10 bar
axial, ½” connection, HK 320 194000346911
pre-settable

Valve body
straight-through, HK 340 194000146909
As a low noise, flow optimised design with stainless
½” connection
steel shaft and double O-ring seal suitable for Katherm
HK with actuator, product no. 194000146906,
Valve body max. operating temperature 120 °C,
straight-through, max. operating pressure 10 bar
HK 340 194000346909
½” connection,
pre-settable

Return fittings

Brass, nickel plated body, with O-ring seal,


RSV HK 320 (4-pipe),
max. operating temperature 120 °C, 194000145952
straight, ½” connection HK 340
max. operating pressure 10 bar

RSV Brass, nickel plated body, with O-ring seal


angle version, max. operating temperature 120 °C, HK 320 194000145953
½” connection max. operating pressure 10 bar

Setting key For pre-settable valve bodies Settable valve bodies 194000346915

Valve actuators

Power consumption approx. 3 W,


Thermoelectric supply cable length approx. 1900 mm,
All valve bodies 194000146906
actuator, 24 V total height 69 mm, diameter 42 mm,
connection fitting 30 x 1.5  mm

Additional accessories

Supplied separately
194000143813
HK 320, height 130 mm
For the use of the Katherm HK with a
condensate pump
Max. head 8 m,
Supplied separately
max. pump rate 3 l/h, 194000143804
HK 340, height 190 mm
supply voltage 230 V / 50 Hz
Mounting set for
(requires separate power supply),
condensate pump
power consumption 20 W,
Factory fitted
condensate pressure line DN 6 mm (hose connection), 194000143814
HK 320, height 130 mm
condensate overflow alarm contact,
floating changeover contact;
switching capacity 230 V/8 (4) A
Factory fitted
194000143809
HK 340, height 190 mm

Trench width 320 mm 194000100320


Wooden, as protection during the construction phase,
Installation cover inserted at the factory;
grilles are supplied packed separately
Trench width 340 mm 194000100986

     Cont.  »
Kampmann technical catalogue – Katherm HK Ordering information | Accessories 37

01  Product information


Image Product Features Suitable for Article no.
Additional accessories

HK 320, height 130 mm,


143014313013
length 915 mm

02  Performance data


HK 320, height 130 mm,
143014313019
length 1200 mm

HK 320, height 130 mm,


143014313029
length 1700  mm

HK 320, height 130 mm,


143014313035
length 2000  mm

HK 320, height 130 mm,


Air intake filter 143014313045
length 2500 mm

03  Design information


HK 320, height 130 mm,
143014313055
length 3000 mm

HK 340, height 190 mm,


143001431920
NP 1250

HK 340, height 190 mm,


143001431935
NP 2000

HK 340, height 190 mm,

04  Control equipment


143001431950
NP 2750

05  Ordering information


Kampmann.co.uk/katherm_hk

Kampmann GmbH Kampmann UK Ltd.


Friedrich-Ebert-Str. 128 - 130 Dial House, Govett Avenue
49811 Lingen (Ems) Shepperton, Middlesex, TW17 8AG
Germany Great Britain
327/05/15/ 2 GB

T +49 591 7108-0 T +44 (0)1932 228592


F +49 591 7108-300 F +44 (0)1932 228949
E info@kampmann.de E info@kampmann.co.uk
W Kampmann.de W Kampmann.co.uk