Académique Documents
Professionnel Documents
Culture Documents
SIPROTEC 5
7UT8x
© Siemens AG 2013 All rights reserved. Answers for infrastructure and cities.
SIPROTEC 5
Transformer differential protection devices
non expandable HW
ƒ 1 differential protection for standard
and auto transformers
expandable
ƒ 1 differential protection for standard
and auto transformers
expandable
ƒ 1 differential protection for standard
and 2 for autotransformers
Protection functions
7UT8x
ƒ Transformer Differential protection
ƒ Restraint characteristic and fast trip stage
ƒ Flexible vector group adaptation
ƒ Inrush and over excitation detection
ƒ CT saturation detection
Protection functions
7UT8x
ƒ Directional O/C protection
ƒ Distance protection
ƒ Tap changer
ƒ Voltage regulator
7UT
8x
87 T
Protection
interface
87 L
7SD
8x
Benefits
Device
(e.g. CT saturation)
ƒ Increased system availability
Idiff
Customer
currents
ƒ Robust at CT saturation (internal faults) trip area
k=0,8 IMP3
ƒ 87T fast stage evaluates instantaneous
values of the differential current i(t)diff = |Ρ iMP(t) |
Siemens
solution
ƒ 87T fast stage in addition to the ƒ Fast tripping time at internal faults
standard restraint characteristic also at saturated currents
ƒ Adaptive algorithm for differential ƒ Stable at heavy external faults with
functions
Benefits
Device
of a transformer)
ƒ Stable at sympathetic inrush currents
(switching ON of a parallel transformer) IMP1 IMP2
differential protection
ƒ New is the one out of two decision of
two different inrush algorithms
ƒ Inrush detection function with two ƒ Avoiding of false trip in the case of
different measuring principles an inrush or sympathetic inrush
ƒ Second harmonic evaluation with ƒ Increased system availability
functions
Benefits
Device
IMP1 IMP2
ƒ New algorithm based on instantaneous
Siemens
solution
Benefits
Device
Benefits
Device
ƒ Flexible applications
Requirement
ƒ Two winding transformer differential protection
ƒ additional functions
ƒ Protection with one device only
ƒ Flexible hardware and communication
Solution
ƒ Transformer differential device 7UT85
ƒ Standard hardware (base module)
ƒ Application template: Two winding basic
ƒ Communication modules
Benefit
ƒ One device for different applications, easy adaptation
ƒ Simplified engineering, reduced wiring, shorter
commissioning
© Siemens AG 2012. All rights reserved.
Page 14 Energy Automation Sector Infrastructure & Cities
Application template:
Two winding transformer basic
Requirement
ƒ Two winding transformer differential protection
ƒ additional functions
ƒ High sensitivity at 1-phase ground faults
ƒ Protection with one device only
Solution
ƒ Transformer differential device 7UT85
ƒ Functions 87T and 87T N
ƒ Standard hardware (base module)
ƒ Application template: Two winding with REF
Benefit
ƒ One device for different applications, easy adaptation
ƒ Simplified engineering, reduced wiring, shorter
commissioning
Requirement
ƒ Two winding transformer differential
protection in 1.5 CB application
ƒ High sensitivity at 1-phase ground faults
ƒ Protection with one device only
Solution
ƒ Transformer differential device 7UT85
ƒ Functions 87T and 87T N
ƒ Standard hardware (base + expansion
module)
ƒ Application template: Two winding for 1,5
CB application
Benefit
ƒ One device for different applications, easy adaptation
ƒ Simplified engineering, reduced wiring, shorter
commissioning
© Siemens AG 2012. All rights reserved.
Page 18 Energy Automation Sector Infrastructure & Cities
Application template:
Two winding transformer 1,5 CB
52 52
B-QA A-QA FG Transformer side 1 FG Circuit breaker A-QA
MP
I-3ph I-3ph 50BF
I-3ph 1
49 87N Ctrl
MP
I-3ph 2 Measured values
BI
CB
BO
Requirement
ƒ Three winding differential protection for different
vector groups
ƒ Protection with one device only
ƒ Flexible hardware and communication
Solution
ƒ Transformer differential device 7UT86
ƒ Standard hardware (base + expansion module)
ƒ Application template: Three winding basic
Benefit
ƒ One device for different applications, easy adaptation
ƒ Simplified engineering, reduced wiring, shorter
commissioning
Requirement
ƒ Three winding differential protection for 1,5 CB
application
ƒ High sensitivity at 1-phase ground faults
ƒ Protection with one device only
ƒ Flexible hardware and communication
Solution
ƒ Transformer differential device 7UT86
ƒ Standard hardware (base + expansion module)
ƒ Application template: Three winding for 1,5 CB
application
Benefit
ƒ One device for different applications, easy adaptation
ƒ Simplified engineering, reduced wiring, shorter
commissioning
52 52
B-QA A-QA FG Transformer side 1
MP
I-3ph
I-3ph 1 FG Circuit breaker A-QA
49 87NT
MP I-3ph 50BF
I-3ph 2
V-3ph 59 81 Ctrl
MP
Measured values
V-3ph 1 BI
CB
BO
Measured values
BI
CB
BO