POWER SUPPLY UNIT
Navigation
SERVICE MANUAL System
Warning!
This equipment is not fitted with safety interlocks.
High voltages are present when the units are open
and exposed.
Disconnect or switch off and secure power to this
equipment before performing any maintenance or
repair.
CONTENTS Page
3 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--1
3.1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--1
3.2 Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--2
3.3 Principle of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--3
3.4 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--4
3.4.1 Mechanical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--4
3.4.2 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--4
Annex:
1.1 Installation
115 or AC --
230 VAC IN
+ + Ship’s emergency
Protective
earthing DC -- supply 24 VDC IN
D1
K1 Alarm contacts
R2
--
C1 24 VDC OUT
+
1 2 3 4 ALARM L N PE
-- OUT + -- BOARD +
Warning!
Use care during maintenance and repair to avoid contact
with energized electrical conductors. Applicable safety
regulations must be followed, such as VDE, VBG 4,
OSHA 1919, and other consensus safety standards.
Caution!
Maintenance and repair must be performed by trained
and qualified personnel who are knowledgeable in
equipment safety requirements!
Caution!
Device may be damaged!
Exchange of spare parts only with the supply voltage
switched off.
2 Relay K1 does not pick 2.1 Fuse F101 in 2.1.1 Exchange fuse
up, though all ship’s power supply mod- (see Section
mains are available ule defective 2.3.2)
2.2 Power supply mod- 2.2.1 Exchange power
ule defective supply module
(see Section
2.3.3)
2.3 Relay K1 fails 2.3.1 Exchange relay
Warning!
Prior to opening the device, disconnect the input voltage.
The fuse F101 is located close to the plug on the power supply module
-- Loosen fuse cap by means of a screwdriver, size 4
-- Exchange the defective fuse for a new one
R105
L104 R104
R106
R109
R107
Q101 R109 SW101
C120 D107 M
D108
D11o
M
RY101
B C111
D109 P
R106
C115 R107
D107
3 Description
3.1 Application
The Power Supply Unit, Type 119 -- 023, is used where an uninterruptible power supply for
24 VDC loads is required. In case of failure of the AC input voltage -- which is connected
into 24VDC via a power module -- , automatic change--over of the device to the shipborne
24 VDC emergency supply takes place; and, simultaneously, an alarm signal ’Power fail’ is
offered via a floating contact.
3.2 Construction
(see Fig. 3--2)
The power supply module and the components for automatic change--over have been moun-
ted on a mounting plate. Change--over is ensured by:
-- a relay K1
-- a resistor R2
-- a capacitor C1
The mounting plate is mounted in a casing made of steel sheet and intended for bulkhead
mounting.The bottom side of the casing carries cable entries and a ground connection. Late-
rally mounted vent slots ensure heat dissipation.
Power supply
module
Connector
Fuse F101
Capacitor C1 Relay K1
Mounting plate
Resistor R2
Earth screw
Input 1 24V DC
F101
Ship’s mains AC DC
Input
115V or
230V 60Hz Alarm
RY101 M
B
Input 2
Emergency supply
Input
24VDC
+ --
Relay K1
C1
Alarm
Output
24V DC
With failure of the ship’s mains, the relay RY101 in the power supply module drops out. By this
the relay K1 drops out also and changes over the supply for the connected devices to the
24 VDC emergency supply. The capacitor C1 prevents voltage drops during change--over
operations.
Stability with
0 to 100% load: 50 mV
198 to 265 V AC: 10 mV
Ambient temperature: 0 to 50 °C