ELECTRICAL RESEARCH AND DEVELOPMENT ASSOCIATION

(Accredited by the National Accreditation Board forTesting and Calibration laboratories, Govt. of India)
ERDA Road, Makarpura Industrial Estate, Vadodara-390 010, India.
EPABX : +91 (0265) 2642942, 2642964, 26423n, 3043128/29/30/31 133
Fax: +91 (0265) 2638382
Certificate No. : T-0071
E-mail: erda@erda.org
Web : http://www.erda.org

TEST REPORT
SHEET 1 OF 5
NAME &. ADDRESS OF CUSTOMER REPORT NO.: LSCS/018
DATE: 16.04.2013
ABB LTD. CUSTOMER REF. NO.: DATED:
PP HV DISCONNEqORS, NIL 11.04.2013
DATE OF SAMPLE DATE OF
Maneja Works, Maneja, RECEIPT: TESTING:
Vadodara, Gujarat- 390013, India. 25.03.2013 11.04.2013
SAMPLE DESCRIPTION SAMPLE IDENTIFICATION
72.SkV, 1600A HORIZONTAL CENTER BREAK ERDA ID NO.: LSCS-13-017/01
DISCONNECTOR
Rated Voltage (Ur) : 72.5 kV
Rated Operational Current: 1600 A SR. NO.: 3600024535-10-002
Rated Frequency (fr) : 50/60 Hz.
Rated Insulation Voltage: 72.5kVrms/140kVrms/325kVp
No. of Poles: Two (Test done on only one pole) TYPE DESIGNATION: SDF72.5
Method of operation: Motor operated
Type of Material for Contacts:
a) Contacts : Silver Faced Copper Alloy DRAWING NO.:
~
b) Terminals: Aluminium As per Drawing No.
Rated Short Time Withstand Current & its Duration: lHYD990402-005 Revision A
40 kArms for 3 sees. with an initial peak of 104 kA.
Sh. NO.1 of 1
Quantity (tested): 1 No. (Total 5 Sheets)
TEST DETAILS TEST SPECIFICATIONS
Short time withstand current and peak As per customer's requirement,
withstand current tests. (CI. No. 6.6) test procedure followed as per
IEC 62271-102 : 2012 &
IEC 62271-1 : 2011
ENCLOSURES:
NUMBER OF OSCILLOGRAMS : One
NUMBER OF PHOTOGRAPHS : One
NUMBER OF TEST CIRCUIT DIAGRAMS : One
NUMBER OF DRAWINGS : Five

TEST WITNESSED BY: Mr. Arabinda Bhattacharjee (Design Engineer, ABB Ltd.)
Mr. Darshan Trivedi (Design Engineer, ABB Ltd.)
Mr. Gunjan Patel (R&D Engineer, ABB Ltd.)

REMARKS: The sample conforms to the requirement of short time withstand current and
peak withstand current tests as specified by customer.

o MtfoJ.eY
to PRE~DBY CHECKED BY
00 NOTE: 1. This report relates only to the particular sample received for testing In good condition at ERDA.
en 2. This report cannot be reproduced in part under any circumstances.
o:;:::t 3. Publication of this report requires prior permission in writing from Director, ERDA.
4. Only test asked for by customer have been carried out.
rl 5. In case of any dispute, Vadodara will be the exclusive jurisdiction & shall be construed as where the
rl cause has arised.
Caution: ERDA is not responsible for the authenticity of photocopied or reproduced test reports.
W ERDA provides support to customers for verification of the authenticity of test reports issued by ERDA.
t-
-: