I-1 Causes and Auto Actions:

Causes: Effects:
1. PV-6/7 will close to allow any fuel into
1. I – 19 burner fuel header because it may lead to
In case of no C.W or no instrument air it is overheating of tubes or accumulation of
better to shut down the plant than to run it fuel in fire box that may lead to explosion
under these dangerous conditions 2. FV-185/185A will close to prevent any fuel
2. Low Process Gas Flow (4655NMC/hr) into the furnace and FV-187 will open to
If feed gas flow to F-101 decreases to a very low vent any fuel present
value and fuel is not reduced catalyst tubes may 3. FV-3/7 will close so no feed gas is allowed
burst due to over heating into catalyst tubes
3. Low Steam Flow To F-101 (18750kg/hr) 4. Shutdown of K-1003 because no gas is
Steam flow is very important and critical for required after I-1 actuation as it will cause
reforming furnace. Low steam flow will cause coking of reformer tubes.
coking. 5. FV-4/8 will close to stop steam flow. Higher
4. Low Fuel Pressure (0.6psi) flows will result in unnecessary overloading
Low fuel pressure may cause the burner flame of the boilers and rapid cooling of the
to light off and unburnt fuel will accumulate in system. So, main steam flow valve is closed
the furnace that may cause explosion on trip of reformer while steam flow
5. Low Steam / Gas Ratio (1.45kg/NMC) continues through the bypass valve.
Back up security for low steam flow 6. HV-11 will open to provide steam for
6. Low Level In C-105 (33%on 1-LIT-709) process gas coil protection against thermal
Loss of water in the boiler drum will lead to shocks.
overheating of the waste heat exchangers 7. HV-116 will open for process air coil
tubes. Refilling of the boiler will result into protection.
severe thermal quench and damage of tubes. 8. HV-119 will close to stop Condensate to L-
7. High Draft In F-101 (-25mmH2O) 106 so that in no excess condensate flow to
High draft in furnace may cause refractory lining the shift converters.
to collapse due to very high negative pressure 9. 2-FV-1 will close to stop any steam from
in the furnace which will result in metal entering HTSC to avoid condensation in
overheating. Flame failure may also occur shift convertors
8. Low Draught In F-101 (+5mmH2O) 10. I-2/I-6/I-11/I-12/I-13/I-14 will be actuated
If draught in the furnace is decreased then air because no process gas would be present in
for combustion will decrease accordingly. So, case of I-1 actuation
unburned fuel will accumulate in F-101 firebox, 11. I-8/I-9 will actuate because there is no air
which may result in drastic explosion. requirement after I-1 actuation.
9. ID Fan low Speed (300 rpm) 12. CO2 compressor will trip because there will
It is an additional security to safeguard low be no CO2 generation after reforming
draught. reaction has stopped
10. Shutdown K-1003
This is back up security for low feed gas flow
security.
11. Manual trip CCR or field
I-2 Causes and Auto Actions:
Effects:
Causes:
1. CV-14/14A will open to vent the air present.
1. I – 19 2. BV-704/705, CV-5 will close to stop the air
In case of no C.W or no instrument air or no entry into C-102.
power it is better to shut down the plant than 3. CV-61 will open to cool down the burner
to run it under these dangerous conditions. tip.
2. Low air flow (6500NMC/hr) 4. HV-116 will open to avoid over heating of
At this air flow we assume that the burner in C- process air coils in F-101.
102 may light off which will let the oxygen in 5. I-11/I-12 will actuate because the molar wt.
the air to pass on and it will oxidize the catalyst. of the gas will change due to N2 absence
3. Low gas/air ratio (0.6) and this will in turn damage the syn
Additional security against low air flue or low compressors.
gas flow. 6. I-13/I-14 will actuate because there will be
4. Manual trip CCR or field
no ammonia vapor generation due to
tripping of Syn compressors.
I-3 Causes and Auto Actions:
Causes: Effects:
1. I – 19 1. FV-6A/B and FV-7A/B will close to avoid loss
In case of no C.W or no instrument air or no of level in C-208 because loss of level will
power it is better to shut down the plant than result in absorber dry out and will damage
to run it under these dangerous conditions. the vanadation layer
2. Low level in C-208 (11% level) 2. I-6 will be actuated because in case of I-3
Low level tripping prevents the complete loss of actuation CO2 slippage may occur which will
level to avoid absorber dry run because in case increase methanator catalyst temperature
of level loss process gas may break through 3. I-11/I-12 will be actuated because after I-6
which will damage the vanadation layer and actuation there will be no gas after
move towards stripper operating at low methanator. CO2 presence will change gas
pressure molar wt. and CO2 gas is a poison for
3. Low level in C-203A/B bottom (30% level) convertor catalyst.
In case of strippers bottom low level, lean 4. I-13/I-14 will actuate because there will be
solution pump will trip and no lean solution will no ammonia vapor generation after syn
be present and CO2 slippage will occur which compressor tripping.
will increase methanator temperature and is
also a poison for convertor catalyst
4. Low level in flash vessel (6% level)
Low level in flash vessel will trip the semi lean
pumps and no semi lean solution will be
present for CO2 capture and CO2 slippage may
occur resulting in methanator temperature
increase or convertor catalyst damage
5. Low level in C-203A/B middle (23% level)
If semi lean solution pumps are selected with C-
203A/B middle, then low level in middle will
cause the pumps to trip.
6. Manual trip field or CCR
I-4/I-5 Causes and Auto
Actions:
Causes: Effects:
Low level in C-203A/B bottom (30% level) 1. In case of I-4 actuation i.e I-4A/B/C, I-3 will
be actuated because level loss will cause
1. I-4A actuates when G-206A trips on low the gas to pass onto strippers and no lean
level of C-203A bottom or any other cause. solution will be available which will increase
2. I-4B actuates when G-206B trips on low CO2 slippage.
level of C-203A bottom or any other cause.
3. I-4C actuates when G-206C trips on low 2. In case of I-5 actuation i.e I-5A/B/C, I-3 will
level of C-203A/B bottom i.e which one is be actuated because level loss will cause
selected or any other cause. the gas to pass onto strippers no semi-lean
solution will be available which will increase
Low level in C-2001 (6% level) CO2 slippage.

1. I-5A actuates when G-201A trips on low


level of C-2001 or C-203A middle level
(which one is selected) or any other cause.
2. I-5B actuates when G-201B trips on low
level of C-2001 or C-203B middle level
(which one is selected) or any other cause.
3. I-5C actuates when G-201C trips on low
level of C-2001 or C-203A/B middle level
(which one is selected) or any other cause.
I-6 Causes and Auto Actions:
Causes: Effects:
1. TV-32 will close to save methanator catalyst
1. High methanator temperature (398ᵒC)
from any upsets.
High temperature will affect the life of 2. I-11/I-12 will be actuated because after I-6
methanator catalyst. Also high temperature
actuation there will be no gas after
means CO2 or CO presence which is poison for
methanator. CO2 presence will change gas
convertor catalyst
molar wt. and CO2 gas is a poison for
2. Low I/A pressure to TV-32 (65psi) convertor catalyst.
Low instrument air pressure will not operate 3. I-13/I-14 will actuate because there will be
methanator inlet I/V and it is better to trip the no ammonia vapor generation after syn
methanator then to operate it under dangerous compressor tripping
conditions

3. I-1/I-3 actuation
In case of I-1 actuation there will be no process
gas available. I-3 actuation means there is no
CO2 removal so to save methanator from high
temperature I-6 actuates

4. Manual trip CCR or field