Académique Documents
Professionnel Documents
Culture Documents
1. Product Description
The standard factory settings for the low and high pressure limits
are: +0.5 psi [ + 3.4 kPa] minimum pressure and + 6.5 psi
[ + 44.8 kPa] maximum pressure. Each Inertaire® system has a
nameplate showing its settings (see Figure 1).
2 ABB
Table 1: Features of standard models.
ABB 3
4
ABB
Figure 2: High pressure hose assemblies.
1.3.C. Active Part 6. Sump: The sump serves as a collection point for any
Figure 3 shows key components of the Inertaire ® system’s moisture or oil condensate that may accumulate within
“active part” which mounts on vibration dampeners within the system. It also serves as a manifold for mounting
the enclosure. The active part’s mounting panel is constructed various components of the Inertaire® system. A drain cock
from 11 gauge (0.120 inch [3 mm]) steel coated with 5 mils at the bottom of the sump permits draining of accumu-
[0.127 mm] of white acrylic enamel paint. lated fluid and manual purging of excess pressure dur-
ing testing or calibration.
Within Figure 3, parts identified by a number inside a circle
are common to all models and are described in the numbered 7. Pressure/Vacuum Gauge: The 4 inch [102 mm] di-
paragraphs below. Parts identified by a letter inside a ameter dial indicates pressure on a -10 to +10 psi scale
square are included in RN_2 models only and are described [-69 to +69 kPa]. With the system in Operating Configu-
in section 1.3.D. ration, the gauge indicates the pressure of the
transformer’s gas space. The gauge is also used dur-
1. Cylinder Pressure Gauge: This 0-3000 psi gauge ing adjustment of the High Pressure Regulator and test-
(0-20,684 kPa) displays the pressure on the input ing of the Pressure Relief Unit.
side of the High Pressure Regulator.
8. Pressure Relief Unit: The setting for this unit is listed on
2. Empty Cylinder Alarm Switch: A “Form C” the nameplate (+6.5 psi [ + 44.8 kPa], standard). When
(change over) contact within this pressure switch the pressure in the transformer gas space exceeds
changes state when the pressure drops below the the setpoint, excess pressure vents through the two
Empty Cylinder Alarm setpoint (200 psi [1,379 kPa], stan- ports in the rear of the unit. When the pressure drops
dard). The terminal points may be wired to a customer’s below the setpoint value, the unit reseals automatically.
alarm system (see Figure 9 for schematic and switch rat-
ings). 9. High Pressure Alarm Switch: The “Form C” contact
within this switch operates when the pressure exceeds
3. High Pressure Regulator: This unit contains two indi- the setpoint limit (+ 8.5 psi [+58.6 kPa], standard). It
vidual stages. The first stage reduces the cylinder pres- automatically resets after the pressure has decreased
sure (approximately 2000 psi [13,789 kPa] when cylin- below the setpoint by a deadband value of approxi-
der is full) to approximately 100 psi [689 kPa] in order to mately 0.75 psi [5.2 kPa]. Excess system pressure can
provide constant pressure and flow to the second stage occur if the pressure relief unit fails, or if system pres-
as the cylinder pressure drops. The second stage fur- sure increases more rapidly than it can be relieved.
ther reduces the gas pressure to required levels.
10. Low Pressure Alarm Switch: The “Form C” contact
The T-handle on the face of the regulator can be used to within this switch operates when the pressure falls be-
adjust the output from the second stage. Turning the T- low the setpoint limit (+ 0.25 psi [+ 1.7 kPa], stan-
handle counter-clockwise (CCW) lowers the pressure, dard). It automatically resets after the pressure has in-
clockwise (CW) raises the pressure. A jam nut on the creased to exceed setpoint by a deadband value of
handle shaft can be tightened against the regulator’s face approximately 0.1 psi [0.7 kPa]. A low pressure con-
to secure the handle at the desired setting. The operat- dition can occur after the nitrogen cylinder is exhausted,
ing setting is shown on the nameplate (+5.0 psi [34 kPa], or if some system component malfunctions.
standard).
11. Terminal Block with clear cover: This 12 point terminal
4. Low Pressure Regulator: This regulator is factory set to block enables customer’s connection to the three alarm
feed nitrogen into the transformer gas space when the switches (Empty Cylinder Alarm, High Pressure Alarm,
gas space pressure falls below (+0.5 psi [3.4 kPa], stan- and Low Pressure Alarm). See wiring diagram in Figure
dard). This unit isolates the gas space from the nitro- 9. Wiring is 14 AWG minimum type SIS VW-1 with
gen supply when the gas space pressure is above its insulated ring-tongue terminals. The block is rated 30
setpoint. The setting on this regulator should not be amps and has #10-32 screws for securing terminals.
changed.
12. Outlet Valve and Bulkhead Adapter: The outboard side
5. Bypass Valve: In the closed position (Operating Con- of this valve is intended for connection to a 1/4 inch
figuration), this valve directs the output of the High Pres- NPT male fitting and tubing leading to the transformer
sure Regulator to the Low Pressure Regulator. When gas space. In the closed position, this valve isolates
the bypass valve is in the open position, it directs the the Inertaire® system from the transformer gas space.
output of the High Pressure Regulator to the sump, by- This position is used when evacuating the transformer,
passing the Low Pressure Regulator. The open position and when testing the Pressure Relief Unit. In the Open
is used to test the operation of the Pressure Relief Unit, position the valve connects the Inertaire® system to the
purge the transformer gas space, and test the system transformer gas space. This position is used in the stan-
for leaks. dard “Operating Configuration”, and for purging and
pressure testing the entire system.
ABB 5
6
ABB
Figure 3: Active part details.
,
®
13. Sampling Valve: This valve is intended for connection terminals; heater wires have TEFLON
Teflon™ insulation and
to the transformer gas space through an independent non-insulated terminals.
fitting and length of tubing. The barbed hose connector
for 1/4" ID tubing allows gas samples to be obtained Mounted Remote from Active Part
from the transformer for testing and analysis. This may F. A bracket at the top of the cabinet includes a base
also be used as an exhaust port when purging the gas for a standard 120 volt bulb wired to a door oper-
space with fresh nitrogen. During normal operation this ated switch (i.e. the light is ON only when the door
valve remains closed. is open). Wiring from the switch and bulb base is
run back to the 6 point block on the active part.
14. Outlet hose: This hose is approximately 6 inches (152
mm) long and connects the sump (6) to the outlet valve
(12).
ABB 7
1.3.E. Tubing Kit Part Number: 1C30327G01
An optional copper tubing kit is available from ABB with the
parts needed to connect the Inertaire® system to the transformer
gas space.
2. Installation
• High pressures
• Lethal voltages
• Heavy components
8 ABB
Important Notice: Failure to observe the requirements flat washers, lock washer and nut (not included) as shown in
of OSHA standard 1910.269 can cause death or severe burns Figures 6 & 7. If there is a gap between the transformer
and disfigurement. That standard specifically prohibits the bracket and the enclosure bracket, one or more washers
wearing of polyester, acetate, nylon, or rayon clothing by em- should be used to shim as necessary to distribute the
ployees working with exposure to electric arcs or flames. enclosure’s weight between the upper and lower brackets.
Safety notations defined in this instruction leaflet, involve two 2.3.B. Connect the low-pressure tubing from the
possible conditions: enclosure to the transformer gas space.
Section 2.3.B. assumes the optional ABB tubing kit has been
1. Personal injury or death. purchased. While the instructions that follow can be used
as general guidelines, please refer to the assembly instruc-
2. Product or property damage (includes damage to this tions provided by supplier of tubing and fittings if the op-
product or other property). tional ABB tubing kit is not purchased.
Safety notations are intended to alert personnel of possible The customer must weld the two 1/4 inch NPT female cou-
personal injury, death, or property damage. They have been plings to the transformer wall to provide access to the trans-
inserted in the instructional text prior to the step in which the former gas space. Some transformer designs locate the
condition is cited. couplings side-by-side, whereas others place the couplings
at diagonally opposite corners near the top of the transformer
The safety notations are headed by one of three hazard inten- for a cross-flow of gas.
sity levels which are defined as follows:
Cut tubing to length, deburr and bend as required. Verify
1. DANGER--immediate hazard which will result in severe that the tubing is free of debris.
personal injury, death, or property damage. ,
®
Using a light coating of thread cement or TEFLON
Teflon™ tape,
2. WARNING--hazard or unsafe practice which could result attach two elbows into the female 1/4 inch NPT female bulk-
in severe personal injury, death, or property damage. head fittings on the right wall of the Inertaire® system’s
enclosure. When tight, these elbows should point upward
3. CAUTION--hazard or unsafe practice which could result in at an angle of about 30° from vertical toward the transformer
minor personal injury, or property damage. wall. See Figure 8.
ABB 9
10
Figure 5: Key dimensions for mounting RNA_ unit within an enclosure.
ABB
ABB
11
Figure 6: Mounting the RNB_ enclosure on a transformer.
12
ABB
Figure 7: Mounting the RNC_ and RND_ enclosure on a transformer.
ABB
13
Figure 8: Connection of tubing to the bulkhead connectors.
14
ABB
Figure 9: Schematic diagram for standard Inertaire® system.
Using a similar process, attach the other two elbows to the 1. Cut one or more holes in the enclosure to accommo-
transformer gas space couplings. The tubing ends should point date the cable or conduit fitting(s) required. Refer to
downward. Figures 6 & 7 for suggested location.
The tube fittings come preassembled finger-tight. Insert the 2. Install fitting(s) (not included) into the hole(s) and install
tube into the fitting. Make sure that the tubing rests firmly on the wiring.
the shoulder of the fitting and that the nut is finger tight. Scribe
the nut at the 6 o-clock position. While supporting the body of 3. Connect leads to the appropriate terminals on the 12-
the fitting with a back-up wrench, tighten the nut 1.25 turns, point terminal block.
watching the scribe mark make one complete revolution and
continue to the 9 o-clock position. Repeat this process for 4. For RN_2 units:
each of the four tube connections. a. Connect the 120 V Line, Neutral, and Ground leads
to the appropriate points on the 6 point terminal
Secure the tubing along its path with supports and hardware block.
as shown in Figure 8. b. The utility switch is wired to terminal block points
10, 11, and 12, and may be connected to suit.
2.3.C. Connect electrical leads and run wiring.
Consult transformer controls wiring diagram for specific con- Two 0.25 inch (6.4 mm) diameter holes along the lower edge
nections in the transformer’s control scheme. A schematic of the "Active Part" can be used to secure wiring with wire
diagram of the standard Inertaire® system alarms and other ties.
electrical equipment is shown in Figure 9.
CAUTION
Do not use a low voltage bell ringer when
checking the alarm circuits; this could exceed
the interrupting ratings of the contacts and may
damage the contacts. An indicating light device
is best for checking the circuits. Figure 9 lists
the interrupting ratings of the alarm contacts.
Cylinder Dimensions:
Capacity 200 ft3 [5.66 m3]
(2200 psi @ 70° F)
[15,168 kPa @ 21° C]
Height: 55 in [1397 mm]
Diameter: 9 in [229 mm]
Weight: approx. 140 lbs [63 kg]
ABB 15
Valve Connection: CGA 580 Female
Purity: max impurities 0.20% by volume CAUTION
Moisture: Dew Point of -55° C [-67° F] Point the opening of the valve away from
or lower personnel in the area to avoid injury from a
Oxygen Content: Maximum 0.20% (2000 ppm) high pressure gas stream or from blowing
by volume particles.
7. Be sure the cylinder valve is free of dirt. A good proce- 2. Close the Outlet Valve (CW to limit).
dure is to briefly open the cylinder valve slightly (CCW)
to allow any contamination lodged in the valve to be 3. Open the Bypass Valve (CCW to limit).
blown out.
4. Release the 1/2 inch jam nut on the high pressure
regulator’s T-handle. While watching the pressure/vacuum
gauge, turn the T-handle clockwise slowly to increase the
pressure. Gas should begin escaping from the Pressure
Relief Unit within +/- 0.5 psi (+/- 3.4 kPa) of the setpoint
value.
16 ABB
If the Pressure Relief Unit does not operate at the correct 5. Open the Sampling Valve (CCW) to exhaust gas from
value, adjust it with a 5/64 inch (0.078 inch) Allen wrench the gas space until gas analysis yields satisfactory re-
through the hole in the center of the unit’s face. Labeling sults. Close the sampling valve securely when the purge
and arrows on the unit show proper direction. is complete.
5. Turn the regulator T-handle counter-clockwise (CCW) to 6. Close the Bypass Valve (CW).
reduce the pressure to its setpoint (+5.0 psi [+34.5 kPa],
standard). Excess pressure may be bled by briefly opening The unit is now back in “Operating Configuration”.
the sump’s drain cock and watching the pressure/vacuum
gauge stabilize. 3.4 Tank Leak test
A 5.0 psi (34.5 kPa) nitrogen pressure test can be made on
6. Close the Bypass Valve (CW). the transformer tank and Inertaire® system. Any small nitrogen
leak should result in a change in pressure on the Inertaire®
7. Open the Outlet Valve (CCW). system’s Pressure/Vacuum gauge. After verifying that the
adjustment of the T-handle is correct (see 3.2), perform the
The unit is now back in “Operating Configuration”. following procedure:
3.3 Purging the Gas Space 1. Open the Bypass Valve (CCW) and allow the system to
Some transformers are shipped with dry air in the gas space stabilize at +5.0 psi (+ 34.5 kPa). See Caution in sec-
rather than nitrogen to allow breathable gas be present for a tion 3.3 regarding expansion of gas from cylinder.
technician to attach internal leads and perform other commis-
sioning activities. When the transformer has been prepared 2. Close the nitrogen cylinder valve (CW) and allow the
for operation, the Inertaire® system may be used to purge the transformer to stand several hours under this pressure.
gas space with nitrogen. Follow the instructions provided by If the pressure falls off with no change in temperature, a
the transformer manufacturer for filling the transformer with oil leak is present and should be located and corrected.
and gas.
3. Check all hose connections, valve packing glands, and
The following procedure may be used generally to purge the fittings for signs of escaping gas. A solution of soapy
gas space. The instructions assume that the system is set in water applied to the joints will bubble where leaks are
the “Operating Configuration” as defined in section 3.1. Also present.
verify there is adequate nitrogen pressure in the cylinder be-
fore beginning the procedure. WARNING
Be certain all current carrying items have been
de-energized before proceeding with this step. Failure
CAUTION to do so could result in electrical shock.
Use extreme care when purging the gas space with 4. Close the Bypass Valve (CW).
nitrogen from a high pressure cylinder. Do not seal
the transformer until the nitrogen in the gas space 5. Open the cylinder valve to limit (CCW).
has reached ambient temperature (i.e. Do not close
the outlet valve which seals the transformer from the The unit is now in “Operating Configuration”.
Inertaire® system’s pressure relief unit). As high pres-
sure (up to 2000 psi (13,789 kPa)) nitrogen is reduced 3.5 Sampling the Gas Space
to atmospheric pressure and piped to the gas space, Before beginning this procedure, verify that there is positive
the gas expansion reduces its temperature. Unless pressure within the transformer gas space by checking the
the gas is free to expand as it warms to ambient tem- pressure/vacuum gauge for a positive reading, and verify that
perature, the pressure within the tank may increase the nitrogen cylinder has adequate pressure remaining.
to such a value as to operate the relief unit.
1. Close the Outlet Valve (CW). 1. Open the sampling valve (CCW) briefly to clear the sam-
pling tube of any oil condensate and static gas.
2. Open the Bypass Valve (CCW).
2. Connect a sampling device with 0.25 inch [6.4 mm]
3. Verify the pressure within the sump is +5.0 psi [+ 34.5 inside diameter hose to the barbed hose connection on
kPa]. Adjust if necessary as described in section 3.2. the sampling valve.
4. Open the Outlet Valve (CCW); the Inertaire® system will 3. Open the sampling valve (CCW) and draw off an adequate
work to pressurize the transformer tank to +5.0 psi [34.5 gas sample. The Inertaire® system will function as re-
kPa]. quired to maintain the pressure above the low pressure
limit.
4. Maintenance
5. Renewal Parts
18 ABB
Inertaire ® System Record
ABB 19
For more information please contact: Note:
1ZUA7633-210, rev. 1
ABB Inc. The information contained in this document is for general information purposes
1133 South Cavalier Drive only. While ABB strives to keep the information up to date and correct, it makes
no representations or warranties of any kind, express or implied, about the
Alamo, Tennessee 38001, USA
completeness, accuracy, reliability, suitability or availability with respect to the
Phone: +1 800 955 8399 information, products, services, or related graphics contained in the document for
+1 731 696 5561 any purpose. Any reliance placed on such information is therefore strictly at your
Fax: +1 731 696 5377 own risk. ABB reserves the right to discontinue any product or service at any
time.
www.abb.com/electricalcomponents
© Copyright 2013 ABB. All rights reserved.